addendum no. 02
TRANSCRIPT
Page No. 1 of 1
ADDENDUM NO. 02
Date: June 28, 2021
NHJ – Indian Creek Intermediate School Roof Replacement
and Pool Hallway Building Roof Maintenance Work
Trafalgar, INDIANA
Owner: Nineveh-Hensley-Jackson United
School Corp. (Indian Creek Schools)
802 South Indian Creek Drive
Trafalgar, IN 46181
TO: All interested bidders of record
This Addendum No. 02 forms part of the contract documents and modifies the original
bidding documents dated June 07, 2021. Acknowledge receipt of this addendum in the
space provided on the Bid Form. Failure to acknowledge this addendum may subject the
Bidder to disqualification.
This addendum consists of following information:
I. GENERAL INFORMATION
a. Attached is the new Trane Poolpak unit submittal for your information.
II. CHANGES TO THE PROJECT CONTRACT MANUAL
1. Replace Project Manual cover page.
2. Replace section 00 41 16 Bid Form in its entirety. We have added a unit cost for
the replacement of the bad insulation.
3. The roofing contractor shall follow the installation of the new Pool Pak unit that is
planned to be installed during Fall break 10/11/2021-10/15/2021. This also
included the mechanical piping, HVAC ductwork, and electrical work is
completed. The roofing contractor shall need to flash the new roof curb for the
unit.
END
PROJECT CONTRACT MANUALVolume 1 of 1
Divisions 00 – 07
Prepared For:
NINEVEH-HENSLEY-JACKSON UNITED SCHOOL CORP.
(INDIAN CREEK SCHOOL)
Intermediate School Roof Replacement and Pool Hallway Building Roof Maintenance Work
Trafalgar, IN
Date: June 07, 2021
SECTION 00 41 16
BID FORM
Addendum #02
00 41 16-1 BID FORM
Addendum #02
COMPANY NAME OF BIDDER: ____________________________________________
PROJECT: Indian Creek Intermediate School Roof Replacement
and Pool Hallway Building Roof Maintenance Work
BID DATE: July 01st, 2021
BID TIME: 1:00 pm
BIDDERS ARE TO COMPLETE AND SUBMIT THE FOLLOWING FORMS WITH THEIR BID:
1. Bid Form (1) hard copy
2. Bid Security (1) hard copy, either in the form of a Bid Bond in the amount of 10% of the
Base Bid or a certified check in the amount of 10% of the Base Bid
3. Indiana State Board of Accounts Form 96 (revised 2013) including a signed Non-Collusion
Affidavit
4. Documents listed above in a sealed envelope.
SUBMIT SEALED BIDS TO:
Nineveh-Hensley-Jackson United School Corp.
802 South Indian Creek Drive
Trafalgar, IN 46181
Attn: Dr. Timothy Edsell
The undersigned Bidder, having visited the site of the work and having familiarized himself/herself
with local conditions affecting the cost of this Work, hereby proposes to perform the following
listed Work, in accordance with the Project Contract/Contract Manual/Specifications and Drawings,
dated 06/07/2021 and all Addenda and Revisions/Clarifications Letters issued prior to the due date
of bids, for a Lump Sum Amount.
Guarantee of Prices: By signing and submitting a proposal, Bidder agrees to guarantee the bids
(prices) for sixty (60) consecutive days from date of submittal and to enter into an agreement with
the Hagerman Inc to perform work for the stated bid sums at any time during this period.
Addenda Received & Included: No. Dated__________
Addenda Received & Included: No. Dated__________
Addenda Received & Included: No. Dated__________
Revisions/Clarifications Letter Received/Included: Dated
SECTION 00 41 16
BID FORM
Addendum #02
00 41 16-2 BID FORM
Addendum #02
Revisions/Clarifications Letter Received/Included: Dated
SCOPE OF BIDS ACKNOWLEDGEMENT: I certify that I have reviewed the Scope of Bids included in
Specification Section 00 24 00, covered by this Bid Form, and acknowledge that the price stated
below includes all costs associated with the work stated in the Scope of Bids without any
modifications. ________ (initial)
PERFORMANCE BOND AND PAYMENT BOND: A Performance Bond and Payment Bond in the
amount of one hundred percent (100%) of the Contract Amount may be required of the successful
bidder. Provide amount on bid form with associated Bid Item.
BASE BID:
Bid Item #01: Roofing Work
Intermediate School Roofing Work
(words)
$
Performance & Payment Bond Include in base bid
Include Roof Allowance of $15,000 in the Intermediate School Roof Work in your base bid
Man-days required for this work: ____ Days
Pool Hallway Connector Roofing Work
(words)
$
Performance & Payment Bond Include in base bid
Include Roof Allowance of $15,000 in the Pool Hallway Connector Roofing Work
in your base bid
Man-days required for this work: ____ Days
SECTION 00 41 16
BID FORM
Addendum #02
00 41 16-3 BID FORM
Addendum #02
UNIT PRICING:
1. Roofing Contractor shall include a unit price for bad insulation discovered when removing the existing roofing. This shall include the removal, and replacement of the insulation. This money is to be taken out of the Allowance. $ ____________ / (SQFT) ALLOWANCES: $15,000 Intermediate Roof
$15,000 Pool Hallway Connector Roof
SECTION 00 41 16
BID FORM
Addendum #02
00 41 16-4 BID FORM
Addendum #02
GENERAL INFORMATION:
LEGAL NAME OF BIDDER:
d/b/a NAME (if different):
ADDRESS:
FEDERAL ID NUMBER:
PHONE (Office):
PHONE (Mobile):
FAX:
E-MAIL ADDRESS:
BY:
PRINTED NAME:
TITLE:
DATE:
Please provide the contact information for the project estimator responsible for preparing this bid.
NAME:
PHONE (Mobile):
END OF SECTION
Project Name: Indian Creek
Prepared For: Chase MorrisTrane Co. (Indianapolis, IN)
PoolPak Model #: PPK-190-VL-X-A3EH1173W2E2AD0H
OAFC Model #: NG-V-22-EUHMO-V
https://www.poolpak.com
3491 Industrial DriveYork, Pennsylvania 174021-717-757-2648
June 14, 2021
Submittal 60086.11 Jun 14, 2021Page 2 of 35
Table of Contents Unit Summary 3
Design and Unit Performance 4
Unit Dimension Drawing 8
Dry Cooler Dimension Drawing 9
Features Summary 10
Installation 13
OA Duct Design 17
Field Wiring Diagram 18
Pool Water Piping 19
Placing Equipment 20
General Specification 21
Warranty 30
Hot Water Valve 33
Submittal 60086.11 Jun 14, 2021Page 3 of 35
Indian CreekPPK-190-VL-X-A3EH1173W2E2AD0H
Model 40 Ton 2-compressor dehumidifier
Unit Subseries Pool Water Heater, Vented
Unit Location Outdoor
Cabinet Horizontal 2-in Double Walled - ReturnPlenum - Left Side
Supply Voltage 460V-480V/3PH
Unit Control CommandPak
Refrigerant R410A
Disconnect Non Fused Disconnect Unit Mounted
Outdoor Air OA Inlet Motorized Damper & Filter
Exhaust Fan Unit mounted Exhaust Fan
Space Heating Unit mounted hot water coil
Heat Control Modulating - factory supplied and wired valve
Air Conditioning Air Cooled A/C - For Use With RemoteOutdoor Air Cooled Equipment
OAFC Voltage 460V-480V/3PH
Warranty Standard - 2 years on driveline, 2 years oncompressor, 2 years on coils
Extras Complete Extra Filter Set MERV-13 2"
OA on RH Side
Supply Air CFM 17000
Outdoor Air CFM 6000
Exhaust Air CFM 6600
Supply Air Orientation Horizontal (Supply End)
Outdoor Air Orientation Left
Pool Water Connection Bottom
Condensate Drain Side
Heating Capacity 557 MBH
Entering Water Temperature 150 F
Unit Summary
Submittal 60086.11 Jun 14, 2021Page 4 of 35
Indian CreekPPK-190-VL-X-A3EH1173W2E2AD0H
Unit Data
Refrigerant Charge (including remote OACCand line set, compared to all DX systems)
88lbs vs 452lbs
Design Data
Outdoor Air (CFM) 6000
ESP 0.0 inches
Room Conditions (°FDB/%RH) 83/60
Unit Total Airflow (CFM) 17000
Electrical Data
Unit Voltage (V/Ph/Hz) 460V-480V/3PH/60
Unit Full Load Amps - FLA (A) 66.1
Unit MCA (A) (min circuit ampacity) 75
Unit MOP (A) (max overcurrent protect) 100
Supply Air Blower
Airflow (CFM) 17000
Type Plenum
Unit ESP (in WC) 1.0
Number of Motors 1
Motor HP 20.0
Motor FLA (A) 25.9
Motor Drive VFD
Design and Unit Performance
Submittal 60086.11 Jun 14, 2021Page 5 of 35
Exhaust Fans
Exhaust Air (CFM) 6600
Type Axial
ESP 0.0 inches
ESP Supply Air 0.75 inches
ESP Return Air 0.25 inches
Number of Motors 1
Motor HP 5.3
Motor FLA (A) 4.7
Compressor
Type Scroll
Number of compressors 1
Refrigerant R410A
Motor RLA/LRA (A) 32.1/191.0
Evaporator Coil
Sensible Capacity (MBH) 313.0
Total Capacity (MBH) 576.3
Latent Capacity (Lbs/h) 232.8
Circuits 2
Condensate Drain Connection 1.25
Reheat Coil
Total Heat Rejection (MBH) 720.4
Control Type Full Modulation
Glycol Pump
Number of Motors 1
Motor HP 1.75
Motor FLA (A) 3.4
Design and Unit Performance
Submittal 60086.11 Jun 14, 2021Page 6 of 35
Pool Heating
Type Cupro-nickel Co-axial Vented
Capacity (MBH) 390
Water Flow Rate (GPM) 70
Water Pressure Drop (PSI) 5.0
Connection Size (in) 2
Connection Type Stub
Connection Stub Material PVC
Maximum Circuit Pressure Rating (PSI) 60.0
Auxiliary Heat
Location Unit Mounted
Type Hot Water Coil
Capacity (MBH) 557
Entering/Leaving Fluid Temp (°F) 150/120
Entering/Leaving Air Temp (°F) 83/129.6
Unit Fluid Flow Rate (GPM) 37.1
Fluid Pressure Drop (ft) 6.3
Valve Pressure Drop (ft) 2
Total Pressure Drop (ft) 8.3
Connection Size (in ID) 1 1/2
Connection Type Stub
Maximum Circuit Pressure (psi) 250
Control Modulated
Design and Unit Performance
Submittal 60086.11 Jun 14, 2021Page 7 of 35
Fluid Cooled A/C
Fluid Flow Rate (GPM) 100.0
Fluid Pressure Drop (PSI) 2.4
Connection Size, in/out 2
Connection Type Butterfly valve
Brazed Plate HX Volume Litres 0.00
Fluid System Fill (US Gal) 22.0
Recom'd Field Line Size (in, ID), Option A 2-1/2
Max Total Equivalent Length (ft), Option A 300
Recom'd Field Line Size (in, ID), Option B 3
Max Total Equivalent Length (ft), Option B 900
May differ from connection size
Remote Outdoor Air Dry Cooler
Model NG-V-22
Design Air On Temp (°F) 95 F
Capcity (MBH) 720.4
Connection Size, in/out 2-1/2
Connection Type Flange
Voltage (V/Ph/Hz) 460V-480V/3PH/60
Number of Motors 4
Motor HP 3.9
Motor FLA (A) 4.3
MCA (A) 19
MOP (A) 20
Fluid Fill (by others) 38.0
Design and Unit Performance
amikhaiel
005/06/21DRAWN BY
REV
SHEET
CAD FILE
DESCRIPTION
LEGEND SELECT OPTIONS
Access Panel
Condensate Drain
Exhaust Air
Heat Recovery
Outside Air
AP
CD
EA
HR
OA
Purge Exhaust Air
Pipe Chase
Purge Outside Air
Return Air
Supply Air
PEA
PC
POA
RA
SA
Disconnect
Roof Curb (Installed by others)
Side Condensate Drain
PPK-70_120 OUTDOOR (EA)
1 OF 1
AAX-S-LH-SIE1P0 RHOADATE
UNIT OPERATING WEIGHT: 7 400 LBS
36" accessrequired all around
ELEVATION
PLAN
(A=22%, B=24%, C=30% & D=24%)
A
D
B
C
66 PC C/L6
8 Typ.
59 87
18
6240
dslater 1 OF 1DRAWN BY
DATE
SHEET
CAD FILE
DESCRIPTION
NG-V-22 rev05
01/04/19
100
Inlet 2 1/2" FlangeUNIT OPERATING WEIGHT: 2400 LBS
Outlet 2 1/2" Flange
50 u1
Main Electrical Panel
96
79
Important note:Minimum 36" of clearance all theway around for proper air flow.
96" of clearance required.
93 1/2
Non-Fused Disconnect (Optional)
76 u1
34 u1
NG-V VERTICAL AIR FLOW
Noise level at 30' (may vary due to installation):Low speed, 67 dBAHigh speed, 75 dBA
Submittal 60086.11 Jun 14, 2021Page 10 of 35
VIRTUAL-TECH® TECHNOLOGY – REMOTE INTERNET CONTROL, DIAGNOSTICS AND REPORTING
There’s only one way we could provide superb, factory-engineered performance after a dehumidifier leaves our plant. It’s called Virtual-Tech Technology.
Virtual-Tech Technology provides a powerful array of capabilities designed to ensure peak operating performance, a minimum of down time and the absolute lowest cost of ownership in the industry. Like an umbilical cord back to the factory, with Virtual-Tech, literally every aspect of the dehumidifier’s performance can be monitored, recorded, analyzed and tweaked for its entire lifetime. Our recording servers are equipped with sophisticated monitoring algorithms designed to detect and protect each and every dehumidifier with literally minute by minute monitoring, 24 hours a day 7 days a week.
From regular service issues to potentially serious matters, if any kind trouble indicator is identified, instant alerts are sent to predetermined contacts including designated service technicians via email alerts. Upon notification, authorized service technicians can instantly login to the system live, to observe, adjust and control important parameters via Virtual-Tech’s web or smart phone interface.
Virtual-Tech brilliantly solves the most challenging issues of dehumidifier industry to guarantee your client has the very best dehumidifier performance, with fewer service calls and minimum down time while enjoying the best lifetime service and value of any dehumidifier in the industry.
Virtual-Tech® Advantages• Premium extended 1st year warranty – parts and labor• Fully monitored remote factory start-up capability• Comprehensive installing contractor support • Virtual-Tech smart phone interface
Features Summary
Submittal 60086.11 Jun 14, 2021Page 11 of 35
Virtual-Tech® Capabilities• Remote monitoring for lifetime of dehumidifier• Real time monitoring and alarm service• Secure online access to real time data• Secure remote access for set point adjustments• Remote access with smart phone application Web
COMMANDPAK® CONTROLLER – FOR PEAK PERFORMANCE PoolPak’s CommandPak Controller, provides unmatched space control, operating efficiency and equipment protection.
CommandPak® Capabilities• Automated, programmable, remote controllable system control• Utilizes built-in pressure transducers• Measures, monitors and controls hundreds of operating parameters• Real time clock with battery back-up and on-board memory for
data logging• Easy to use programming interface with alternate web and smart
phone control capability• Optional remote operator panel unit can be located up to 1,000 ft.
away from unit• Allows live 24-7 monitoring, performance logging, computer analysis, and secure remote control via
the Internet or smart phone with PoolPak’s Virtual-Tech Technology
CommandPak® Specifications• Both staged and modulated control for space heating, cooling and dehumidification. • 20 unit mounted sensors including space/pool conditions and refrigerant pressures. • 16 digital inputs (dry contacts) used for monitoring fault conditions and external control of the unit• 24 digital outputs and 4 analog outputs used for controlling internal and external components. • 2 RS-485 serial ports and 1 RS-232 serial port• 1 Ethernet port (RJ45) • LON, Modbus, BACnet building automation option available.
Sensor Information• Refrigerant high pressure• Refrigerant suction pressure• Outside air temperature• Outside air humidity• Air temperature leaving the evaporator• Supply air temperature• Compressor superheat temperature• Compressor compartment temperature
Features Summary
Submittal 60086.11 Jun 14, 2021Page 12 of 35
Service Technician Mode• History log of sensor data with date/time• History log of alarms and status• History log of operation• Force modes of operation• Adjust damper• Calibrate damper• Test Internal and External Contacts
Alarms• Communication fault, Sensor fault, Dirty filter, High refrigerant pressure fault, Low refrigerant pressure
fault, No airflow, Blower overload, Firestat, High supply air temperature
INDUSTRY LEADING FEATURESPoolPak dehumidifiers match or exceed the specifications of every other competitor in the marketplace.
Built-in Refrigerant Pressure Transducers• Allow 24-7 Monitoring of critical suction and discharge pressures to ensure optimal system
performance Superior Compressor Protection• Advanced monitoring and control technologies to protect compressors including sight glasses on
receiversFully Dipped Coils• Provide 100% protection against corrosion (not just the fins)Direct Driven, Backward Inclined Airfoil Plenum Fans• Provide powerful, quiet, efficient, reliable performance with no belts to adjust, wear out or replace• These fans also allow factory installed auxiliary air heating while providing maximum flexibility for
supply air duct optionsService Vestibule Outside Air Stream• Protects critical components from chlorinated air stream, maximizes AC efficiency, and allows unit
servicing while in operationUltra Compact Designs• Allow twice the capacity in half the footprint (StakPak Series) with up to 14 tons of dehumidification
fitting through a 30 inch door.
Features Summary
Submittal 60086.11 Jun 14, 2021Page 13 of 35
Heavy objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for an even unit lift. Other lifting arrangements may cause damage to equipment, serious injury or death of personnel. Always place, assemble, and suspend single sections. Do not lift units in windy conditions. Do not raise units overhead with personnel below unit.
Improper lifting procedure! Test lift the unit 24 inches to verify proper operation of lifting equipment and positioning of lift points such that the unit is level. Failure to properly lift the unit could result in equipment damage, serious injury or death. PoolPak® is not responsible for the improper use of lifting equipment.
When lifting unit, appropriate personal protection equipment (PPE) such as steel-toed boots and hard hats must be worn to avoid potentially serious injury.
! WARNING
! WARNING
! WARNING
MECHANICAL INSTALLATION
Lifting and Rigging Procedures• Determine the approximate center of gravity before lifting the unit. Consult unit design drawings
provided in the submittal documents to center total weight and weight distribution.
• Never assemble split sections before lifting them to the installation location. Always lift sections as received from the factory.
• Lift sections using the provided lifting lugs
• To avoid damage, do not attach intake or exhaust hoods prior to lifting the unit into place.
Unit Assembly (Split Units Only)Under special conditions, the unit may be split into two or more sections to ease the installation process. Base angles are attached using 3/8” bolts, and inside angles are bolted using 5/16” bolts. Ensure that all provided holes are used. Caulk seams on the outside of the unit to make the join air-tight. Install the standing seam roof rib.
Duct ConnectionsAll duct connections should be installed in accordance with local and national standards. To ensure the highest fan efficiency, duct turns and transitions should be made to minimize air friction losses and turbulence. See supplied unit drawing from the submittal for location and size of unit duct connections. Use only flexible duct connectors to connect to the unit.
Installation
Submittal 60086.11 Jun 14, 2021Page 14 of 35
Piping and Unit ConnectionsSee the unit label for unit connection line sizes. The installer must endeavor to ensure that all industry standards for refrigeration component installation are met. This includes but is not limited to; proper line sizing, materials, nitrogen purging, brazing with Silfos 5 or better (NO SOFT SOLDER), evacuation, cleanliness, traps, long radius elbows and system charging.
Drain Pans - Condensate DrainThe dehumidifier is a draw through configuration as a result the entire cabinet is under negative pressure. Without a P-trap, condensate will not drain and the unit will overflow into your mechanical room.
• Per Figure 1 pitch the condensate drain line a minimum of 1/8” per linear foot, and support the pipe with code approved hangers at least every 5 feet.
• If the drain line passes through an unconditioned space, heat tracing is required to prevent the condensate in the drain from freezing.
When gravity disposal is not possible, a condensate pump can be used. Follow the pump manufacturer’s installation instructions.
Figure 1Drain Pans - Condensate Drain
Field Installed Outdoor Air Cooled Condensers and Fluid CoolersThis condenser is used in air conditioning mode where it rejects unneeded heat from the space to outdoors. Proper installation is essential to ensure it can function as intended. Proper airflow and refrigerant piping are paramount. Ensure an appropriate maximum ambient air temperature has been specified. Ensure the unit has proper airflow per Figure 2. A perimeter of free area equal to its width must be provided. Use line sizes as specified by PoolPak. To avoid potential seasonal system charge problems, ensure the installed line lengths are never longer than indicated on the plans and specifications. If the condenser is installed above the dehumidifier, ensure the hot gas line has proper oil traps. Contact PoolPak if the condenser is installed more than eight (8) feet below the dehumidifier. The installer must endeavor to ensure that all industry standards for refrigeration component installation are met. This includes but is not limited to; proper line sizing, materials, nitrogen purging, brazing with Silfos 5 or better (NO SOFT SOLDER), evacuation, cleanliness, traps, long radius elbows and system charging. Install the remote condenser on a level, hard surface. Bolt the condenser in place.
Installation
Submittal 60086.11 Jun 14, 2021Page 15 of 35
Refrigerant Piping of Remote CondensersPCP series dehumidifiers are equipped with isolation valves and access valves located in the blower compartment. Do not open the isolation valves until all exterior piping is leak checked and evacuated. The last outdoor condenser vacuum can be broken with liquid refrigerant (R-410A). Monitor the exact amount of refrigerant added, as the total system charge must be per the unit nameplate. The PCP series dehumidifiers have refrigerant pipe stubs for the line set connection inside the cabinet. Use standard commercial refrigeration piping practices when installing the refrigeration piping between the dehumidifier and the remote air-cooled condenser.
• Hot Gas and Liquid line sizes should be per unit nameplate. The stubs inside the unit will be the correct sizes for line lengths up to 50’
• Do not exceed 50’ total line length or install the condenser more than 8’ below the unit. Consult PoolPak before installing the outdoor air-cooled condenser more then 8 feet below or more than 50 feet away from the dehumidifier.
• Per Figure 3, install an oil trap at the start of and at every 15 feet of vertical lift in the hot gas discharge line as shown. Pitch horizontal lines a minimum of 1/2” every 5 feet in the direction of flow. All piping must be clean and de-burred. Keep copper chips and foreign materials out of the tubing. A nitrogen purge while brazing is paramount to reduce the chances of oxidation in the pipes.
• Keep the Hot Gas and Liquid lines a minimum of 2” apart to prevent heat transfer. Insulate the hot gas line in all areas where a person may come in contact with the line and be in danger of a burn.
• When all piping work is complete, check for leaks by pressurizing the remote condenser and line set with dry nitrogen. If no leaks are detected, the circuit is ready to be evacuated. Evacuate the condenser and piping to a minimum 250 microns. Isolate the piping for ONE HOUR to verify that the system is free from leaks, moisture, and non-condensables. For further details on proper vacuum and evacuation procedures, see section H – Routine Maintenance.
Figure 2. Typical Outdoor Condenser Installation
Installation
Submittal 60086.11 Jun 14, 2021Page 16 of 35
Charging of Remote CondensersOnce a proper evacuation has been accomplished the system is ready for charging. The outdoor air-cooled condenser requires a field charge by the installing contractor. The field charge required depends on the size of the condenser and the length of the piping. The unit nameplate will show the exact field charge required. The last vacuum can be broken with liquid refrigerant. Monitor the exact amount of refrigerant added, as the total system charge must be per the unit nameplate. Connect the control wiring to the terminals provided inside the electrical compartment of the dehumidifier and outdoor condenser. Refer to the low voltage wiring schematic for details. The condenser fan(s) will not operate until this is complete. Once you have charged and checked the condenser and line set for leaks, open the service valves located in the compressor compartment of the dehumidifier. There is an access valve in the liquid line after the pump down valve. The pump down valve can be manually closed during start-up mode via the controller. Add only as much refrigerant as is needed to get to the total charge indicated on the nameplate. Never charge liquid into the suction line access valve! The receiver has 2 sight glasses with float balls to help ensure the maximum and minimum refrigerant levels are easily met.
Fluid Cooler InstallationFluid cooled units come with a separate pump for the fluid loop. PVC piping is highly recommended for fluid cooler installation.
Figure 3. Typical Outdoor Condenser Installation
Installation
Submittal 60086.11 Jun 14, 2021Page 17 of 35
Duct Design for Accurate Airflow Schematic
DUCT DESIGN FOR ACCURATE AIRFLOW MEASUREMENT
The outside air measurement uses cross airflow sensing elements. The accuracy of these flow measuring stations is dependent on the flow conditions in the duct. The minimum installation requirements for possible duct configuration for airflow rates less than 2,500 fpm is shown below.
ELBOWS TRANSITIONS
OPPOSED BLADE DAMPERS
DUCT TAKE-OFFS
AXIAL FANS
CENTRIFUGAL FANS
OA Duct Design
F.Y.W.
CAD FILE
DAS-PHS-000-001
B.P.
12/28/17DATE
DRAWN BY APPROVED BY
TITLE
Pool Heating Schematic For Dehumidifiers
BALL VALVE
BALL VALVE
POOL
BALL VALVE(BY PASS)
BALL VALVE
AUXILIARY PUMP
BALL VALVE
BALL VALVE
BALL VALVE
BALL VALVE
BALL VALVE
FLOW
DEHUMIDIFIER
DEHUMIDIFIER
CERTAINMODELS
METER
*
*
*
*
*
*
*FLOWMETER
NOTES:---*-Components are optional---This drawing is to be used as referrence only
AUT.CHEMICAL
FEEDER
AUX. POOLHEATER
CHECKVALVE
POOLFILTER
Submittal 60086.11 Jun 14, 2021Page 20 of 35
PLACING THE EQUIPMENT
Although the design of the unit roof mounting supports is usually done by an architect or structural engineer, it is coordinated with dimensional data supplied by the manufacturer. Recommended mounting details and dimensions which the mechanical contractor may use for verification of correct steel roof curb dimensions and electrical and gas service locations on the job site before the arrival of the equipment are furnished by the manufacturer. If this is done, time and money may be saved when the equipment arrives. If any details are found to be questionable, consult with the local Sales Representative or the factory directly.
When the equipment arrives, the dehumidifiers are chained to a flat bed trailer. Coordinated arrival of the equipment and the crane should have previously been arranged with the factory. This is necessary if extra unloading costs are to be avoided. The truck driver will unchain the units. NOTE: It is the responsibility of the contractor to provide the necessary personnel to unload and rig the equipment to the roof and the manufacturer will assume NO additional costs incurred by the failure of the contractor to meet this responsibility.
Units which are mounted on a roof curb must utilize a curb gasket material. The curb gasket acts as a moisture and weather seal between the unit and the roof curb. An ample supply of curb gasket is shipped inside the unit. A label on the unit will identify exactly where in the unit the gasket may be found. It is the responsibility of the contractor to install the curb gasket. The curb gasket should be installed around the perimeter of the curb and any duct opening cross members.
Each unit is provided with lifting brackets attached to the unit base frame for the purpose of attaching lifting hooks (see drawing). It is the responsibility of the crane operator to provide and utilize adjustable cable spreader bars. The spreader bars must be placed as close to the top of the unit as possible. The spreader bars must also be wider than the unit so that the cable will angle away from the unit. This will prevent damage to the cabinet. The manufacturer will not be responsible for damage to the equipment due to improper rigging procedures.
Drawing depicts recommended spreader bar configuration. Actual number of lifting lugs may vary. Consult factory.
Placing Equipment
Submittal 60086.11 Jun 14, 2021Page 21 of 35
1.
A.
B.
C.
D.
E.
F.
2.
A.
B.
C.
D.
E.
F.
G.
H.
1.
I.
Part 1 - General Scope
Furnish and install, where indicated, a factory-assembled, fully-enclosed, split environmental control system with energy
recovery feature(s) designed for natatorium environment control
Features shall include:
Space heating by means of a packaged hot water coil
Cooling mode with heat rejection to a remote outdoor air cooled fluid cooler (dry-cooler). No field refrigeration work shall be
required. Substituting an outdoor condenser and increasing the refrigerant charge grows the owner’s long-term liability and
will not be allowed.
Pool water heating from reclaimed compressor waste heat by means of a vented heat exchanger
Packaged minimum exhaust fan
Integral minimum outdoor air connection
Convenience outlet and light included factory mounted in control cabinet, powered and wired separately.
Quality and Safety Assurance
The system shall be ETL listed
The system shall be completely assembled, wired, piped, and test-run at the factory prior to shipping. All controls shall be
factory adjusted to satisfy the design conditions.
Manufacturer shall have a minimum of ten-plus years prior experience making similar equipment as described in this
specification.
Wherever possible, the system shall have a mechanical vestibule where the electrical panel, compressor(s), pool water
heat exchanger(s), receiver(s) and most of the refrigeration controls are out of the process air stream
The system shall have a microprocessor controller with unit-mounted refrigerant pressure transducers on each refrigeration
circuit, multiple temperature sensors and an Ethernet connection for factory logging and parameter adjustment via the
Internet. The refrigerant pressure transducers shall be actively used for system control. The customer (or their authorized
representative) shall be provided access to the online logging and parameter adjustment interface, upon request.
Demonstration of these capabilities must be carried out at the engineer's office prior to bid day
The system shall have remote factory start-up assistance capability, when connected to a network with Internet access
The system shall have 24-7 remote computer logging capability with automated alarm notifications and system performance
alerts transmitted via e-mail to authorized users, when connected to a network with Internet access
Warranty: The entire system shall have a 24-month limited parts warranty from the factory ship date
A 1-year labor warranty shall be provided by the manufacturer when the system is connected to the factory via an
Internet monitoring system from the date of initial commissioning
When connected to a network with Internet access, the system shall have remote service capability with the ability for field
service technicians to receive service and trouble alerts by e-mail and make parameter adjustments via a browser interface
on any Internet-capable device
General Specification
Submittal 60086.11 Jun 14, 2021Page 22 of 35
3.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
4.
A.
1.
2.
3.
B.
1.
2.
3.
C.
1.
2.
3.
4.
5.
6.
D.
1.
2.
3.
4.
Part 2 - Product General
The natatorium control system shall include:
Mechanical process dehumidification
Outdoor cabinet configuration
A packaged hot water heating coil, sized as specified by the design engineer to meet the skin losses and outdoor air
heating loads
Potable water rated coaxial condensing heat exchanger(s) with double wall vented construction for pool water heating using
reclaimed compressor waste heat
Air filtration via MERV-13 pleated panel filters for return
Minimum outdoor air connection
Minimum exhaust fan(s)
Programmable microprocessor controller with remote Internet logging and parameter adjustment
A service vestibule where the compressor, refrigeration specialties, control valves and all electronics are outside of process
air stream
Convenience outlet and light included factory mounted in control cabinet, powered and wired separately.
Sequence of Operation
The system shall be designed and sized to maintain the specified space conditions
System Startup
Power is turned on or the system is restarted
After a short initial delay to allow the sensors to stabilize, the blower starts and operates continuously
Based on sensor feedback, the system shall begin or resume operation based on the sequence below
Airside Configuration
The system continuously delivers the specified supply air volume to the natatorium
The minimum exhaust air volume is set to meet the engineer's schedule.
The minimum outdoor air volume is set to meet the engineer's schedule.
Dehumidification Mode
The return air relative humidity is above the humidity setpoint
Return air dewpoint is above dewpoint setpoint.
The compressor enters the Compressor Start sequence
If the system cannot maintain the relative humidity below setpoint, the second compressor circuit will start
Compressor waste heat is rejected into a glycol fluid loop which feeds the reheat coils and the air conditioning air-
cooled heat exchanger in parallel.
The reheat coils are fully modulating (0-100%). The reheat output will modulate to maintain the space temperature at
set point year-round. Reheat coils that are on off or only give heat from one circuit are not acceptable since they do not
closely match the requirement of the space and cause swings in space conditions.
Air Conditioning Mode
The return air temperature is above the room temperature setpoint
The compressor starts, if not already operating in Dehumidification Mode
Excess compressor hot gas is diverted to a fluid-cooled heat exchanger. Up to 100% of compressor heat is rejected
into the glycol fluid loop which is pumped outdoors to an outdoor air-cooled heat exchanger for 100% heat rejection at
summer design ambient conditions
100% of compressor heat is rejected at the outdoor air-cooled heat exchanger on a summer design day. On off-peak
General Specification
Submittal 60086.11 Jun 14, 2021Page 23 of 35
5.
E.
1.
2.
F.
1.
2.
3.
4.
G.
1.
2.
3.
5.
A.
1.
2.
3.
4.
5.
6.
7.
8.
days, the air reheat output will modulate to maintain the space temperature at the set point
If the system cannot maintain the return air temperature setpoint, the second compressor will start
Space Heating Mode
The return air temperature is below the room temperature setpoint
The microprocessor space heating output signal (0-10 volts) is sent to the heating coil controller. The signal output will
regulate based on the return air temperature
Pool Water Heating Mode
The return pool water temperature is below the pool water setpoint and the pool water flow switch or minimum
temperature differential is satisfied.
If the compressor is already operating due to a Dehumidification or Air Conditioning demand, the control valves will
divert the compressor hot gas through the coaxial heat exchanger to heat the pool water, with the remainder rejected at
the air reheat coil or the AC heat exchanger. Auxliiary pool water heater will be engaged as a second stage as needed.
If there is no pre-existing demand for the compressor to operate, the microprocessor sends a signal to the auxiliary pool
water heater (remote by others) to operate. The compressor will not operate solely for a pool water heating demand
unless specifically configured to do so at the controller
Factory-installed relay(s) and factory furnished, field-installed pool water temperature sensor(s) are provided to enable
the smart pool feature. This feature provides the ability to activate booster pool water pump(s) feeding the unit when
pool water heating is in demand.
Freeze Protection
The supply air temperature falls below the freezestat setpoint
Exhaust fan(s) are stopped and outdoor air damper(s) are fully closed
When the freezestat alarm is tripped, it must be manually cleared by the operator
Cabinet
Cabinet Construction: All cabinet 16, 20 and 24 gauge sheet metal shall be galvanized G90 steel or GalvalumeTM alloy
with mill-applied zinc phosphate primer followed by an exterior grade white silicone modified polyester top coat. The sheet
metal is engineered to form a cabinet with maximum strength and rigidity. All seams shall be caulked with silicone to
prevent air and water leakage or infiltration
Base Rails: The cabinet shall have a base frame comprised of 2 layers of 10 gauge mill galvanized G90 steel. Lifting
lugs shall be provided on the base frame for rigging the system.
The cabinet walls shall be of double-wall construction using 20 gauge pre-painted steel with a fully painted inner metal
liner and 2 inches of fiberglass insulation
The cabinet floor shall be comprised of a 16-gauge galvanized steel panel with a 20-gauge pre-painted steel inner liner,
2-inch double wall engineered with structural bending for maximum rigidity and be mechanically fastened to the base
frame of the unit
The cabinet roof shall be 20-gauge pre-painted steel, 2-inch double wall engineered with structural bending for
maximum rigidity and be mechanically fastened to the base walls of the unit
The cabinets shall be mechanically assembled with stainless steel 5/32" sealed blind rivets. Where bolts are required
bright zinc plated bolts shall be used
Access doors shall be supported on multiple hinges, held shut by compression latches for quick access. Doors shall be
provided for entrance to all sections housing components requiring routine maintenance. Full height access doors shall
have "hold back" latches to prevent door closure during the performance of service procedures
The unit shall have non-corroding protective mesh screens on all air intake openings
The system shall have non-corroding protective mesh screens covering internal fan blades, protective grates covering
all floor access ports
General Specification
Submittal 60086.11 Jun 14, 2021Page 24 of 35
B.
1.
C.
1.
2.
3.
4.
D.
1.
2.
3.
4.
6.
A.
B.
C.
7.
A.
1.
2.
3.
B.
1.
2.
3.
8.
9.
A.
1.
2.
3.
Outdoor Air Intake:
Minimum Outdoor Air connection: motorized damper, filter and time clock
Insulation: The unit shall be insulated per the following standards:
All exterior cabinet sections shall be insulated with two (2) inch thick fiberglass inside the double walled cabinet
Fire resistant rating to conform to NFPA Standard 90A and 90B
Sound attenuation coefficient shall not be less than 1.02 at a frequency of 1,000 Hz as per ASTM Standard C423
Thermal conductivity shall not exceed 0.26 Btu/hr-sqft-ft at 75 °F
Cabinet configuration shall include:
A filter rack with separate access doors shall be provided for the return air and minimum outdoor air streams
Unit shall be equipped with duct collars to admit the minimum outdoor air as scheduled. The outdoor air intake
assembly shall have a built in air filter rack with separate access door, manual air balancing device and motorized 2
position extruded aluminum, Insulated, silicone side-sealed damper operated by 24-hour time clock
Mechanical vestibule: The unit shall have the compressor, receiver, solenoid valves and the electrical panel in a
separate compartment out of the processed air stream. All components shall be serviceable while the unit is in
operation without disturbing the airflow
Electrical panel: The unit shall have a built-in electrical control panel in a separate compartment in order not to disturb
the airflow within the dehumidifier during electrical servicing. All electrical components shall be mounted on a 16 gauge
galvanized sub-panel
Filters
Wherever possible, air filters shall be standard sized, replaceable, off-the-shelf filters including:
Return Air: 2-Inch MERV 13, 90% pleated filters with rust-free non-metallic structure on a slide-in or face-loading rack
Outside Air: 2-Inch MERV 8, 30% pleated filters with rust-free non-metallic structure
Dirty air filter switches included on the return air filter for indicating an alarm when pressure drop exceeds a set point.
Coils
Evaporator/dehumidifier coils shall be designed for maximum moisture removal capacity
Coils shall be fully dipped and coated with a polyester/enamel coating for maximum corrosion protection. Coating shall
comply with ASTM B117/D1654 and ASTM D2126 for corrosion resistance against common acids, salt and gases
Coil shall have galvanized casing and end plates
Aluminum fin and copper tubes mechanically bonded to assure high heat transfer.
Air reheat coils shall be sized for variable heat transfer into the air with a capacity of 100% of the compressors total required
heat of rejection. Air reheat coils that are on off will cause unstable space conditions and are not acceptable.
Coils shall be fully dipped and coated with a polyester/enamel coating for maximum corrosion protection. Coating shall
comply with ASTM B117/D1654 and ASTM D2126 for corrosion resistance against common acids, salt and gases
Coil shall have galvanized casing and end plates
Aluminum fin and copper tube joints mechanically bonded to assure high heat transfer
Drain Pans
Each evaporator coil shall be provided with a positive draining, compound-sloped, baked powder paint coated aluminum drain
pan with fully-welded corners to ensure zero water retention. In no way will stainless steel or galvanized drain pans be
acceptable.
Blowers and Blower Motors
Supply blowers:
The complete blower assembly shall be statically and dynamically balanced on precision electronic balancers
The blower assembly shall be mounted on a 1" deflection spring isolated rack
The fan inlets shall be equipped with accidental contact protection screen
General Specification
Submittal 60086.11 Jun 14, 2021Page 25 of 35
4.
B.
1.
2.
3.
4.
5.
6.
7.
8.
10.
A.
B.
11.
A.
B.
C.
D.
12.
A.
B.
C.
D.
E.
13.
Motor(s) shall be Premium efficiency painted cast iron construction TEFC, NEMA MG1-PART 31 Inverter Duty 15:1
Constant Torque Severe Duty with a service factor 1.25. Motors shall be 6 Pole 1200 RPM synchronous speed with
HOA switch with motor safeties against overloading at 60 Hz operation directly on mains. Motors shall have double lip
seals on both ends with re-greasable bearings 254T frame and larger with Polyurea grease
Exhaust blowers:
The packaged exhaust blower (EF1) shall be sized to maintain the negative pressure requirement in the space during
normal operation and its operation tied to the system's occupancy scheduler
The fan shall be direct driven axial fan made of high-strength composite material in which the motor and controller are
integrated. It includes FE2owlet blades combined with guide vanes and EC commutated direct-current external rotor
motors provides maximum efficiency the quietest performance. The EC motor shall have maintenance-free electronic
circuitry, a rotor with permanent magnets, and an integral controller to provide the windings with electrical current so
that, the motor rotates continuously and quietly. The fan is aerodynamically-optimized, sickle-blade profile, patterned
with serrated trailing edge and winglets on the blade outer edge for energy and noise-optimized operation
The fan assembly shall be balanced in Class G 6.3 acc DIN ISO 1940, dynamic on two levels
The fan assembly shall be suitable for ambient temperatures of -40°C to max. +70°C
Thermal contacts installed in the windings compliant with THCL 155
Drive motor in external rotor principle, sealed in protection class IP54 with moisture protection impregnation of the
windings, topical protection
High corrosion resistance design with high quality and reliability
The exhaust fan shall be controlled from an end switch on the power open of the exhaust air damper. The exhaust
dampers shall be protected by louvers to divert rain from the face of the dampers
Dampers
Internal dampers shall be made from extruded anodized aluminum with a parallel blade configuration and neoprene double-seal
tips to minimize leakage. Damper blades shall be mounted on steel rods which rotate on nylon bushings. All damper hardware
shall be corrosion resistant
The system shall be provided with normally closed outside air and exhaust air dampers equipped with spring-return
actuators The dampers adjust between 0% to 100% open position.
The outdoor air and exhaust air dampers shall be of opposed blade configuration. Dampers shall have 0.750-inch insulated
blades made from extruded anodized aluminum with neoprene double-seal tips to minimize leakage. Damper leakage shall
be less than 1% of maximum flow at 4-inch water column differential. Damper blades shall be mounted on steel rods which
rotate on nylon bushings. All damper hardware shall be corrosion resistant
Pool Water Heater
Potable water rated coaxial heat exchanger shall be double-wall vented construction with corrosion-resistant cupro-nickel water
circuit tubing
Self-purging and self-draining counter flow design
Water circuit piping shall consist of transparent braided PVC hose
Terminating connections are PVC schedule 40 NPT fittings located at the cabinet wall for easy connection
The maximum loop operating pressure is 60 psig
Compressors
Hermetic, scroll action compressor, suction gas cooled, suitable for refrigerant R-410A
The compressor(s) shall be mounted on rubber-in-shear isolators to limit the transmission of noise and vibration
The compressor(s) shall be equipped with removable crankcase heater(s) for liquid migration protection
The compressor(s) shall be located outside the conditioned air stream in the system's service vestibule
The compressor manufacturer must have a wholesale outlet for replacement parts in the nearest major city
Refrigeration Circuit
General Specification
Submittal 60086.11 Jun 14, 2021Page 26 of 35
A.
B.
C.
D.
E.
F.
G.
H.
14.
A.
B.
C.
D.
E.
F.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
G.
H.
I.
J.
K.
L.
M.
15.
A.
The system shall consist of two factory sealed refrigeration circuits for dehumidification and sensible cooling. No site
refrigeration work shall be required
Each refrigeration circuit shall have pressure transducers monitoring the refrigerant discharge (high) and suction (low)
pressures. The refrigeration circuit shall be accessible for diagnostics, adjustment and servicing without the need for service
manifold gauges
All refrigeration circuits shall have solenoid control valves, check valves, a liquid line filter-drier, liquid and moisture
indicator, thermostatic expansion valve and a pump down solenoid valve
The system shall have an externally adjustable balanced port design mechanical thermostatic expansion valve. The valve
shall have a removable power head
Tamper proof, hermetically sealed non-adjustable high and low pressure switches and refrigeration service valves shall be
installed using Schrader type valves. Refrigeration service valves shall be located outside of the airstream
The receiver shall have two refrigerant level (maximum and minimum) indicating sight glasses
The suction line shall be fully insulated with 0.500-inch closed cell insulation
The maximum operating pressure for the glycol loop is 100 psi. The glycol loop temperature should not exceed 134 ºF.
Control Panel
The electrical contractor shall be responsible for external power wiring and disconnect switch fusing. Power block terminals
shall be provided
The system shall include a factory-installed non-fused disconnect
Main control panel shall be mounted inside the service vestibule outside of the process air stream
Blower motors shall be protected with thermal trip overloads
The system shall have a voltage monitor with phase protection
Available dry contacts shall include:
Alarm
Blower interlock
Stage 1 & 2 heating
Outdoor air damper control
Remote exhaust fan #1
Remote exhaust fan #2
Outdoor-air cooled equipment
System on
Auxiliary pool heater 1
Heat recovery
Terminals shall be provided to send 24-volt power to the outdoor air cooled condenser or fluid cooler fan contactor
All wiring shall be installed in accordance with UL or CSA safety electrical code regulations and shall be in accordance with
the NFPA All components used in the system shall be UL or CSA listed
Wiring diagrams shall be located near the electrical panel(s) on the system. These diagrams shall provide colour-coding
and wire numbering for easy troubleshooting. All wires shall be contained in a wire duct.
The compressor(s) shall have a time delay on start to prevent short cycling
Pressure transducers for measuring refrigerant discharge (high) pressure and suction (low) pressure shall be provided.
An airflow switch and a dry contact for alarm(s) shall be provided and factory-mounted.
Convenience outlet and light included factory mounted in control cabinet, powered and wired separately.
Microprocessor Control
A microprocessor controller with the following characteristics will be provided:
General Specification
Submittal 60086.11 Jun 14, 2021Page 27 of 35
1.
2.
3.
4.
5.
6.
7.
8.
B.
C.
1.
2.
3.
4.
5.
6.
7.
D.
1.
2.
3.
E.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
F.
1.
2.
3.
4.
All set points and parameter adjustments are pre-programmed at the factory during quality control testing
The microprocessor program shall be stored on updatable FLASH memory
A minimum of 11 analogue inputs, 4 analogue outputs, 24 digital inputs and 16 digital outputs
Four serial interface ports including both RS232 and RS485 types
An Ethernet port with RJ-45 connector and LED activity indicator
A real time clock to time-stamp the system operation log and to enable a programmable 7-day occupation schedule
Two manual demand forced modes to allow the user to manually bypass the microprocessor in the event of controller
failure
The local and remote operator panel(s) shall have a backlit graphic liquid crystal display with touch controls
The system shall have pressure transducers monitoring the refrigerant discharge (high) and suction (low) pressures. The
refrigeration circuit shall be accessible for diagnostics, adjustment and servicing without the need of service manifold
gauges.
The following status LEDs shall be on the controller:
Alarm - indicates there has been a failure requiring service.
Dehumidification - indicates that the system is dehumidifying the space.
Cooling - indicates that the air-conditioning mode.
Pool Heating - indicates that the system is heating the pool water with recycled energy.
Space Heat - indicates that the space heating is operating.
Maintenance - indicates whether or not maintenance is required.
Manual - indicates that the system has been set to manual operation.
The following set points shall be accessible and adjustable from the operator panel:
Space temperature
Space relative humidity
Pool water temperature
The following sensors shall be unit-mounted and monitored at the operator panel. All information from these items shall be
actively used in the system control and operation strategies:
Refrigerant high pressure
Refrigerant low pressure
Return air temperature
Supply air temperature
Return air relative humidity
Entering pool water temperature
Leaving pool water temperature
Evaporator leaving air temperature
Suction temperature
Discharge temperature
System Fault: Shall indicate via text message to the display what systems require attention or servicing. Built-in monitoring
and diagnostics shall allow the user to view the following:
Power failure
Dirty air filter
Refrigerant high and low pressure
System off
General Specification
Submittal 60086.11 Jun 14, 2021Page 28 of 35
5.
16.
A.
B.
C.
D.
E.
F.
G.
17.
A.
B.
C.
D.
E.
1.
2.
3.
4.
5.
18.
A.
Anti-short cycle delay
Auxiliary Air Heating
The packaged hot water coil shall be sized to meet the scheduled heating capacity and have the following characteristics:
Modulating (0-10V) auxiliary air heat control by means of a factory mounted and wired three-way control valve
Auxiliary air heating coil tubes, fins, headers, casing and end-plates shall be fully protected by a polyester/enamel coating
for maximum corrosion protection. The protective coating shall comply with ASTM B117/D1654 and ASTM D2126 for
corrosion resistance against common acids, salts and gases
Coil casing and end-plates shall be made of galvanized steel
Fin and tube joints shall be mechanically bonded to ensure high heat transfer
Fins shall be made of aluminum
Tubes shall be made of copper
The maximum loop operating pressure shall not be less than 250 psig
Air Conditioning
Air-cooled air conditioning via a fluid cooler
The system shall be equipped with an air conditioning mode where excess compressor heat is rejected to a remote outdoor
air-cooled heat exchanger (aka Dry Cooler) via a single glycol fluid loop. No site refrigeration work shall be required. The
system shall include a circulating pump and expansion tank. The packaged fluid cooled condenser and remote outdoor air-
cooled heat exchanger shall both be capable of rejecting 100% of the compressor heat rejection with an air on temperature
at summer design conditions
The system shall be provided with a dry contact rated for 24VAC/5A to operate the remote outdoor fluid cooler control
Each refrigeration circuit shall include refrigerant valves, a receiver with pressure relief valve set at 650 psig, a pressure
control valve and a pressure differential valve, and two manual shutoff valves to isolate the outdoor fluid cooler
Coils shall be tested at 425 PSIG and mounted vertically for complete surface utilization. Coils shall be counter flow and
have adequate capacity to dissipate the total heat rejection of the system at design conditions
The fan(s) shall be direct driven axial fan(s) made of aluminum in which the motor and controller are integrated. The fan(s)
include an EC commutated direct-current external rotor motor providing maximum efficiency and the quietest performance.
The EC motor shall have maintenance-free electronic circuitry, a rotor with permanent magnets and an integral controller to
provide the windings with electrical current so that the motor rotates continuously and quietly. The fan has an
aerodynamically-optimized, sickle-blade profile, patterned with serrated trailing edge and winglets on the blade outer edge
for energy and noise-optimized operation
The fan assembly shall be balanced in Class G 6.3 acc DIN ISO 1940, dynamic on two levels
The fan assembly shall be suitable for ambient temperatures of -40°C to max. +70°C
Thermal contacts installed in the windings compliant with THCL 155
Drive motor in external rotor principle, sealed in protection class IP54 with moisture protection impregnation of the
windings, topical protection
High corrosion resistance design with high quality and reliability
Factory Performance Testing
The system shall be thoroughly tested under factory test conditions.
General Specification
Submittal 60086.11 Jun 14, 2021Page 29 of 35
19.
A.
B.
C.
D.
E.
F.
20.
A.
B.
C.
21.
22.
A.
B.
C.
Part 3 - Execution Product Delivery, Acceptance, Storage and Handling
Perform a thorough physical inspection of the system upon delivery from the shipment carrier
Identify and immediately report any physical damage to manufacturer
If the system is to be stored prior to installation, store in a clean, dry place protected from weather, dirt, fumes, water,
construction and physical damage
Handle the system carefully during installation to prevent damage
Damaged systems or components shall not be installed. Contact the manufacturer for RMA instructions
Comply with the manufacturer's rigging and installation instructions for unloading the system and moving it into position
Connections
Where installing piping adjacent to the system, allow space for service and maintenance
Duct connections: drawings indicate the general arrangements of the ducts. Connect the system to ducts with flexible duct
connectors. Comply with code requirements for flexible duct connectors
Electrical connections: comply with code requirements for power wiring, switches and motor controls in electrical sections
Installation
The agency responsible for start-up should work in accordance with the specifications and in accordance with the
manufacturer's instructions and only by workers experienced in this type of work
Start Up
Detailed instructions for start up as provided by the manufacturer must be followed
Installing contractor must contact the manufacturer prior to start up to confirm start up procedures
Remote Internet access and control must be initiated and confirmed by the factory prior to start up for extended labor
warranty to be in effect
General Specification
Submittal 60086.11 Jun 14, 2021Page 30 of 35
Pools - Equipment Warranty
General Policy
Warranty Void Unless Registered
Initial 90-day Comprehensive Warranty
Internet Connected, Conditional One Year Repair Warranty
Two-Year Parts Warranty
Replacement Part Warranty
All PoolPak service and warranty work is managed exclusively by Dehumidified Air Services (DASV). All warranties apply to theoriginal equipment owner and are not transferable. All warranty inquiries should be made to Dehumidified Air Services.
Dehumidified Air Services:Phone: 1-833-327-7665 Email: [email protected]
PoolPak warrants as set forth and for the time periods shown below that it will provide through either a DASV Service Technician oran authorized service organization specified and approved by DASV, a new or rebuilt part to replace a factory installed part whichhas failed because of defect in workmanship or material.
NOTE: EVERY REQUEST RELATED TO WARRANTY OF ANY NATURE AS DESCRIBED BELOW MUST BEOFFICIALLY AUTHORIZED AND DOCUMENTED IN ADVANCE BY DASV TO QUALIFY FOR WARRANTYCOVERAGE.
All Warranties are void unless start-up of the equipment is approved by a DASV service technician. Upon completion of the start-up,a “Warranty Registration Certificate” will be issued, along with the Start-Up Report, which activates the Warranty Period of theequipment. The Warranty Period will commence either upon completion of start-up registration of the equipment or 6 months fromfactory ship date, whichever comes first.
During the first 90 days from initial start-up, all parts and repairs related to factory defects or replacement parts are covered byPoolPak manufacturer warranty. All parts and labor requirements will either be handled by DASV technicians directly or managedand approved in advance by DASV through DASV authorized technicians.
If and only if the equipment is connected to the internet from the date of warranty activation, a Repair Warranty will be provided foran additional 9 months subsequent to the initial 90-Day Comprehensive Warranty for a total of 12 months of parts and laborwarranty coverage. The unit must be connected and communicating to PoolPak Virtual-Tech for the entire term from start-up inorder to qualify.
If qualified, PoolPak will provide or pay for the required part and direct labor only, related to the part replacement. Only the laborrequired to replace the defective part is under warranty for this 9-month extension. Travel time, diagnostic time, per diems, truckcharges, shipping charges etc. are not covered under this Conditional Repair Warranty.
If any factory installed part supplied by PoolPak fails because of a defect in workmanship or material prior to the completion of the24th month from date of completion of the warranty activation, PoolPak will provide a new or rebuilt part F.O.B. factory. No laborreimbursement will be made for expenses incurred in replacing the part except as set in the Initial 90-day Comprehensive orInternet Connected, Conditional One-Year Repair Warranty.PoolPak reserves the right to have the defective part returned to the factory in order to determine the warranty applicability. Partsshipping and handling costs (to and from the factory) are not covered outside of the Initial 90-day Warranty.
If a replacement part provided by PoolPak under this warranty fails due to a material defect prior to the end of the Two-Year PartsWarranty (or the end of the extended warranty period if applicable), whichever comes first, PoolPak will provide a new or rebuilt partF.O.B. factory.
Warranty
Submittal 60086.11 Jun 14, 2021Page 31 of 35
1.
•
•
•
•
•
•
•2.
1.
2.
Applicability
Products that have become defective or damaged as a result of non-DASV or unauthorized service work, poormaintenance, faulty electrical supply, act of God, or any other circumstances outside of the specified care, maintenance oroperation of the equipment including:
Components that have been relocated from their original placement during manufacturing.
Any portion of the system not supplied by PoolPak.
Components on which the model and/or serial number plates have been removed or defaced.
Components which have become defective or damaged as a result of unauthorized opening of the refrigeration circuit,
improper wiring, electrical supply characteristics, poor maintenance, accidents, transportation, misuse, abuse, fire,
flood, alteration and/or misapplication of the product.
Products not installed, operated and maintained as per the PoolPak Operating and Maintenance Manual.
Products operating in mechanical rooms that house chemicals (i.e. chlorine, bromine, water treatment chemicals).
Products on which payment is in default. Parts that wear out due to normal usage, such as air filters, fuses and sensors are not covered by this warranty.
Limitations DASV is a Manufacturer Service organization, not a first-response or urgent response local service company. As such, wehighly recommend that equipment owners have a relationship with their own qualified first response service organization orone recommended by DASV.
DASV hours of operation are from 8:00 AM to 6:00 PM Eastern, Monday through Friday unless otherwise agreed to under a
separate agreement.
Parts replacement can be subject to availability. We highly recommend for mission-critical applications that owners
purchase and maintain a local stock of critical components in case immediate replacement be required. If for any reason
one of those components is replaced under applicable warranty conditions, PoolPak will reimburse the original cost of any
component used under terms of Warranty.
NOTE: PoolPak expressly disclaims any liability for parts replacement delays due to parts unavailability or shipping delays. This warranty is given in lieu of all other warranties. Anything in the warranty notwithstanding, any implied warranties offitness for particular purpose and merchantability shall be limited to the duration of the warranties described above. PoolPakexpressly disclaims and excludes any liability for consequential or incidental damage for breach of any express or impliedwarranty.
Where a jurisdiction does not allow limitations or exclusions in a warranty, the foregoing limitations and exclusions shall not
apply to the extent of the legislation, however, in such case the balance of the above warranty shall remain in full force and
effect.
This warranty gives specific legal rights. Other rights may vary according to local legislation.
This warranty is applicable only to products that are purchased and installed in the United States and Canada. This warranty is NOTapplicable to:
NOTE: Refrigerant lost during the Initial 90-day Comprehensive or Internet Monitored, Conditional One-Year RepairWarranty will be reimbursed in accordance to the current market price of refrigerant at the time of repair and upon discretion ofDASV's Customer Support team. PoolPak will not be responsible for refrigerant lost from the system due to improperly installedcontractor piping to the remote outdoor air-cooled condenser.
Warranty
Submittal 60086.11 Jun 14, 2021Page 32 of 35
••••••
Force Majeure
Optional Extended Warranties
1. Optional Five-Year Compressor Warranty
2. Optional Five-Year Dehumidifier Coil Warranty
3. Optional Ten Year Dehumidifier Coil Warranty
4. Optional Five-Year Driveline Warranty
Supply fan motorExhaust fan motor (including Min Exhaust and Purge Exhaust motors)Heat recovery loop pumpCompressor glycol/water pumpDry cooler/outdoor condenser fan(s)Dry cooler pump(s)
PoolPak will not be liable for delay or failure to provide warranty service due to government restrictions or restraints, war, strikes,material shortages, acts of God or other causes beyond PoolPak control.
If purchased prior to shipment and documented with a registered extended warranty statement certificate, PoolPak will providereplacement components within the specified period of the extended warranties. Extended warranties commence either uponcompletion of start-up registration of the equipment or 6 months from factory ship date, whichever comes first, and cover partsreplacement only for parts that fail as a result of manufacturing defect. The failed parts must be returned to the factory withtransportation prepaid by the customer as a condition of these warranties. Optional extended warranties are for parts only andsubject to all the terms of the Two-Year Parts Warranty.
Subject to the terms above, PoolPak will provide a replacement compressor for up to 60 months from the date of the warrantyactivation.
Subject to the terms above, PoolPak will provide a replacement coil for up to 60 months from the date of the warranty activation.Extended coil warranties are for parts of the dehumidifier only and does not cover parts of dry cooler or OACC coils.
Subject to the terms above, PoolPak will provide a replacement coil for up to 120 months from the date of the warranty activation.Extended coil warranties are for parts of the dehumidifier only and does not cover parts of dry cooler or OACC coils.
Subject to the terms above, PoolPak will provide driveline replacement parts for up to 60 months from the date of the warrantyactivation.
Driveline Components Include:
Warranty
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls, Inc. www.johnsoncontrols.com
1
VG1000 Series Three-Way, Plated Brass Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators Catalog Page
• Graphite-Reinforced Polytetrafluoroethylene (PTFE) Seats — include 15% graphite-reinforced ball seals, providing better wear resistance.
• 500:1 Rangeability — provides accurate control under all load conditions.
• Chrome-Plated Brass Ball and Stem Assembly Standard — handles both chilled and hot water applications with a fluid temperature range of 23 to 203°F (-5 to 95°C).
Repair InformationIf the VG1000 Series Ball Valve fails to operate within its specifications, replace the valve body, actuator, or entire assembly. For replacement parts, contact the nearest Johnson Controls representative.
DescriptionVG1000 Series Ball Valves are designed to regulate the flow of hot or chilled water and, for some models, low-pressure steam in response to the demand of a controller in HVAC systems. Available in sizes 1/2 through 2 in. (DN15 through DN50), this family of two- and three-way forged brass valves is factory or field mounted to Johnson Controls® VA9104 and VA9300 Series Non-Spring Return and VA9203 and VA9208 Series Spring-Return Electric Actuators for on/off, floating, or proportional control.
Refer to the VG1000 Series Forged Brass Ball Valves Product Bulletin (LIT-977132) for important product application information.
Features• Forged Brass Body — provides 580 psig
static pressure rating.• 200 psi Closeoff Pressure Rating —
provides tight shutoff.
Selection Charts Three-Way Plated Brass Trim Ball Valves, Non-Spring Return, VA9104 Series Electric Actuators without SwitchesFluid Temperatures: 23 to 203°F (-5 to 95°C)Not Rated for Steam Service
AC 24 V
Valve Size, in. Cv Closeoffpsig
On/Off (Floating)
without Timeout1
1. To avoid excessive wear or drive time on the motor for the AGA models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
On/Off (Floating)with Timeout
DC 0 to 10 V Proportional
Actuators with M3 Screw Terminals VA9104-AGA-3S VA9104-IGA-3S VA9104-GGA-3S
VG1841AD 1/2 1.2 / 0.72
2. Valve has a characterizing disk.
200 VG1841AD+9T4AGA VG1841AD+9T4IGA VG1841AD+9T4GGA
VG1841AE 1.9 / 1.22 VG1841AE+9T4AGA VG1841AE+9T4IGA VG1841AE+9T4GGA
VG1841AF 2.9 / 1.92 VG1841AF+9T4AGA VG1841AF+9T4IGA VG1841AF+9T4GGA
VG1841AG 4.7 / 2.92 VG1841AG+9T4AGA VG1841AG+9T4IGA VG1841AG+9T4GGA
VG1841AL 7.4 / 4.72 VG1841AL+9T4AGA VG1841AL+9T4IGA VG1841AL+9T4GGA
VG1841AN 11.7 / 5.8 VG1841AN+9T4AGA VG1841AN+9T4IGA VG1841AN+9T4GGA
VG1841BG 3/4 4.7 / 2.92 200 VG1841BG+9T4AGA VG1841BG+9T4IGA VG1841BG+9T4GGA
VG1841BL 7.4 / 4.72 VG1841BL+9T4AGA VG1841BL+9T4IGA VG1841BL+9T4GGA
VG1841BN 11.7 / 5.8 VG1841BN+9T4AGA VG1841BN+9T4IGA VG1841BN+9T4GGA
VG1841CL 1 7.4 / 4.72 200 VG1841CL+9T4AGA VG1841CL+9T4IGA VG1841CL+9T4GGA
VG1841CN 11.7 / 7.42 VG1841CN+9T4AGA VG1841CN+9T4IGA VG1841CN+9T4GGA
VG1841CP 18.7 / 9.4 VG1841CP+9T4AGA VG1841CP+9T4IGA VG1841CP+9T4GGA
Actuators with 120 in. (3.05 m) 18 AWG Plenum Cable VA9104-AGA-2S VA9104-IGA-2S VA9104-GGA-2S
VG1841AD 1/2 1.2 / 0.72 200 VG1841AD+9A4AGA VG1841AD+9A4IGA VG1841AD+9A4GGA
VG1841AE 1.9 / 1.22 VG1841AE+9A4AGA VG1841AE+9A4IGA VG1841AE+9A4GGA
VG1841AF 2.9 / 1.92 VG1841AF+9A4AGA VG1841AF+9A4IGA VG1841AF+9A4GGA
VG1841AG 4.7 / 2.92 VG1841AG+9A4AGA VG1841AG+9A4IGA VG1841AG+9A4GGA
VG1841AL 7.4 / 4.72 VG1841AL+9A4AGA VG1841AL+9A4IGA VG1841AL+9A4GGA
VG1841AN 11.7 / 5.8 VG1841AN+9A4AGA VG1841AN+9A4IGA VG1841AN+9A4GGA
VG1841BG 3/4 4.7 / 2.92 200 VG1841BG+9A4AGA VG1841BG+9A4IGA VG1841BG+9A4GGA
VG1841BL 7.4 / 4.72 VG1841BL+9A4AGA VG1841BL+9A4IGA VG1841BL+9A4GGA
VG1841BN 11.7 / 5.8 VG1841BN+9A4AGA VG1841BN+9A4IGA VG1841BN+9A4GGA
VG1841CL 1 7.4 / 4.72 200 VG1841CL+9A4AGA VG1841CL+9A4IGA VG1841CL+9A4GGA
VG1841CN 11.7 / 7.42 VG1841CN+9A4AGA VG1841CN+9A4IGA VG1841CN+9A4GGA
VG1841CP 18.7 / 9.4 VG1841CP+9A4AGA VG1841CP+9A4IGA VG1841CP+9A4GGA
VG1000 Series Three-Way, Non-Spring Return, Plated Brass
Ball and Stem Ball Valve Assemblies without End Switches
Code No. LIT-1900229
Issued March 2017
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls, Inc. www.johnsoncontrols.com
2
VG1000 Series Three-Way, Plated Brass Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators Catalog Page (Continued)
Three-Way Plated Brass Trim Ball Valves, Non-Spring Return, VA9300 Series Electric Actuators without SwitchesFluid Temperature:23 to 203°F (-5 to 95°C)Not Rated for Steam Service
AC/DC 24 V
On/Off Floating DC 0(2) to 10 V Proportional
Valve Size, in. Cv Closeoffpsi
VA9310-HGA-2
VG1841DN 1-1/4 11.71 200 VG1841DN+910HGA
VG1841DP 18.71 VG1841DP+910HGA
VG1841DR 29.2 VG1841DR+910HGA
VG1841EP 1-1/2 18.71 200 VG1841EP+910HGA
VG1841ER 29.21 VG1841ER+910HGA
VG1841ES 46.8 VG1841ES+910HGA
VG1841FR 2 29.21 200 VG1841FR+910HGA
VG1841FS 46.81 VG1841FS+910HGA
VG1841FT 73.7 VG1841FT+910HGA
1. Valve has a characterizing disk.
Three-Way Plated Brass Trim Ball Valves, Non-Spring Return, VA9300 Series Electric Actuators with SwitchesFluid Temperature:23 to 203°F (-5 to 95°C)Not Rated for Steam Service
AC/DC 24 V
On/Off Floating DC 0(2) to 10 V Proportional
Valve Size, in. Cv Closeoffpsi
VA9310 actuator with M9000-2 Switch Kit1
VG1841AD 1/2 1.22 200 VG1841AD+910HGC
VG1841AE 1.92 VG1841AE+910HGC
VG1841AF 2.92 VG1841AF+910HGC
VG1841AG 4.72 VG1841AG+910HGC
VG1841AL 7.42 VG1841AL+910HGC
VG1841AN 11.7 VG1841AN+910HGC
VG1841BG 3/4 4.72 200 VG1841BG+910HGC
VG1841BL 7.42 VG1841BL+910HGC
VG1841BN 11.7 VG1841BN+910HGC
VG1841CL 1 7.42 200 VG1841CL+910HGC
VG1841CN 11.72 VG1841CN+910HGC
VG1841CP 18.7 VG1841CP+910HGC
VG1841DN 1-1/4 11.72 200 VG1841DN+910HGC
VG1841DP 18.72 VG1841DP+910HGC
VG1841DR 29.2 VG1841DR+910HGC
VG1841EP 1-1/2 18.72 200 VG1841EP+910HGC
VG1841ER 29.22 VG1841ER+910HGC
VG1841ES 46.8 VG1841ES+910HGC
VG1841FR 2 29.22 200 VG1841FR+910HGC
VG1841FS 46.82 VG1841FS+910HGC
VG1841FT 73.7 VG1841FT+910HGC
1. For field mounting order VA9310-HGA-2 and the M9300-2 Switch Kit separately2. Valve has a characterizing disk.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls, Inc. www.johnsoncontrols.com
3
VG1000 Series Three-Way, Plated Brass Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators Catalog Page (Continued)
Technical Specifications VG1000 Series Three-Way, Plated Brass Trim, NPT End Connections Ball Valves with Non-Spring Return Electric Actuators
Service1
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
Hot Water, Chilled Water, and 50/50 Glycol Solutions for HVAC Systems
Valve Fluid Temperature Limits Water 23 to 203F (-5 to 95C)
Steam Not Rated for Steam Service
Maximum Fluid Temperature Limit 203°F (95°C) VA9104 Series Actuators
VA9300 Series Actuator
Valve Body Pressure Rating Water 580 psig (4,000 kPa) at 203°F (95°C) (PN40)
Steam Not Rated for Steam Service
Maximum Closeoff Pressure 200 psig (1,378 kPa)
Maximum Recommended Operating Pressure Drop 50 psig (340 kPa)
Flow Characteristics Three-Way Equal Percentage Flow Characteristics of In-Line Port A (Coil) and Linear Flow Characteristics of Angle Port B (Bypass)
Rangeability2
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
Greater than 500:1
Minimum Ambient Operating Temperature
-4°F (-20°C) VA9104 Series Non-Spring Return Actuators
-22°F (-30°C) VA9300 Series Non-Spring Return Actuators
Maximum Ambient Operating Temperature
140°F (60°C) VA9104 Series Non-Spring Return Actuators
VA9300 Series Non-Spring Return Actuators
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections National Pipe Thread (NPT)
Materials Body Forged Brass
Ball Chrome Plated Brass
Blowout-Proof Stem Nickel Plated Brass
Seats Graphite-Reinforced PTFE with Ethylene Propylene Diene Monomer (EPDM) O-Ring Backing
Stem Seals EPDM Double O-Rings
Characterizing Disk Amodel® AS-1145HS Polyphthalamide Resin
87O.D.
236 1/2 O.D.
14 Min.Height
2x2 Wood Nailer
Prime Galv. Steel
1 1/2" FiberglassInsulation
SECTION A-A
DateRev. Int. Description
Qty.:
The information contained in thisdrawing is the sole property of
Thybar Corporation. Anyreproduction in part or wholewithout the written consent of
Thybar Corporation is prohibited
REVISION HISTORYDrawn:
Date:
Job# :Tag:
(DO NOT SCALE DRAWING)Unless otherwise specifieddimensions are in inches
tolerances are`1/16 `0.0625 `1°
REVISION HISTORY File: Rev:
Trane IN/ Indian Creek
Insulated Roof Curb Equipment BasesPoolPak PPK-70-120
Q-21043851
6/16/21 S10980-1JC
----
Thybar Corporation has a policy of continuous product improvementand reserves the right to change the product design without notice
2
1 1/2
ELEVATION VIEW
PLAN VIEW
SUBMITTALCURB WALL THICKNESS AND
RESTRAINT REQUIREMENTS TO BEDETERMINED BY SEISMIC/WINDLOAD
CALCULATIONS.
VERIFY ROOF PITCH AND DIRECTION
APPROVED
BY:
DATE: / /
APPROVEDPENDINGCHANGES
A
A
PITCH
120.25
Ref. 18 15/16Max Height