Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 1 Addendum No. 001 – 03/04/2020 ADDENDUM NO. 001 To Drawings and Project Manual Documents for: Lyndale Community School – SAFE/SECURE ENTRY ENTRANCE & MONUMENT SIGN OFFICIAL PUBLICATION NUMBER: OP#20-2918 OWNER'S PROJECT NO.: 19LYND001 ARCHITECT'S PROJECT NO.: 53560-19131A OWNER: Minneapolis Public Schools 1250 West Broadway Avenue Minneapolis, MN 55411 ARCHITECT: POPE ARCHITECTS, INC. 1295 Bandana Blvd N, Suite 200 St. Paul, Minnesota 55108 (651) 789-1638 DATE: 03/04/2020 This Addendum forms a part of the Permit Set Documents dated 02/13/20, and modifies the original Docu- ments as noted below. This Addendum applies to any or all contracts and subcontracts. All work required by this addendum shall be in complete accord with the Contract Documents and subsequent Addenda here- to. The Items listed in this addendum are not in any order in regard to the drawings or the specifications. All contractors are cautioned to examine each and every item of this addendum. The following changes or clarifications to the plans and specifications shall be included as part of the Con- tract Document. This Addendum consists of (4) written pages and (5) full sized drawings.

Upload: others

Post on 13-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001

Permit Set – 02/13/20 Page 1

Addendum No. 001 – 03/04/2020

ADDENDUM NO. 001

To Drawings and Project Manual Documents for:

Lyndale Community School – SAFE/SECURE ENTRY ENTRANCE & MONUMENT SIGN

OFFICIAL PUBLICATION NUMBER: OP#20-2918

OWNER'S PROJECT NO.: 19LYND001

ARCHITECT'S PROJECT NO.: 53560-19131A

OWNER: Minneapolis Public Schools

1250 West Broadway Avenue

Minneapolis, MN 55411

ARCHITECT: POPE ARCHITECTS, INC.

1295 Bandana Blvd N, Suite 200

St. Paul, Minnesota 55108

(651) 789-1638

DATE: 03/04/2020

This Addendum forms a part of the Permit Set Documents dated 02/13/20, and modifies the original Docu-

ments as noted below. This Addendum applies to any or all contracts and subcontracts. All work required

by this addendum shall be in complete accord with the Contract Documents and subsequent Addenda here-

to. The Items listed in this addendum are not in any order in regard to the drawings or the specifications. All

contractors are cautioned to examine each and every item of this addendum.

The following changes or clarifications to the plans and specifications shall be included as part of the Con-

tract Document.

This Addendum consists of (4) written pages and (5) full sized drawings.

Page 2: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001

Permit Set – 02/13/20 Page 2

Addendum No. 001 – 03/04/2020

A. PROJECT MANUAL

1. PROJECT MANUAL COVER

a. REVISE the Official Publication Number to be: OP#20-2918.

2. 00 01 01 - PROJECT TITLE PAGE

a. REVISE the MPS Official Publication Number to be: OP#20-2918.

3. 00 11 13 – CALL FOR BIDS

a. REVISE the MPS Official Publication Number to be: OP#20-2918.

B. DRAWINGS

1. SHEET AD-110 – OVERALL DEMOLITION FIRST FLOOR PLAN (Drawing is ReIssued)

a. ADD DEMOLITION KEYNOTE D43, “DEMO EXISTING CORRIDOR DIVIDER DOOR COMPLETE

INCLUDING WALL / OVERHEAD TRACKS AND SUPPORT FRAMING. PATCH EXISTING WALL FINISH

AS REQUIRED.”

b. DEMO complete the two existing corridor gates as indicated, KEYNOTE 43.

2. SHEET I-00 – INTERIOR MATERIAL IDENTIFICATION AND ABBREVIATIONS (Drawing is not reissued)

a. REVISE the CTW-2 color to be: “0135 ALMOND”.

Page 3: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001

Permit Set – 02/13/20 Page 3

Addendum No. 001 – 03/04/2020

b. REVISE the CTW-3 color to be: “1194 ELECTRIC BLUE”.

c. REVISE the PT-7 color to be: “SW6802 JACARANDA”.

d. ADD: VCT-5; MANUFACTURER: ARMSTRONG; STYLE: PREMIUM EXCELON – CROWN; COLOR:

5C868 SMOKEY BROWN; SIZE: 12”X12”; INSTALL: MONOLITHIC.

2. SHEET I-110 – OVERALL FIRST FLOOR – FLOOR FINISH PLAN (Drawing is ReIssued)

a. REFER to the reissued plan for the changes.

2. SHEET I-111 – OVERALL FIRST FLOOR – WALL FINISH PLAN (Drawing is not reissued)

a. CONFERENCE ROOM 111: REVISE the wall accent color from “PT7” to be “PT6”.

3. SHEET MD111 – LEVEL 1 MECHANICAL DEMOLITION PLAN (Drawing is not reissued)

a. Add the following to Keyed Note MD1: TURN OVER CONTROL VALVES AND UNIT HEATER TO

OWNER.

b. Revise Keyed Note MD5 as follows (underlined items are added; strikethrough items are omit-

ted): REMOVE EXISTING VAV REHEAT COIL IN ITS ENTIRETY, INCLUDING PIPING, DUCTWORK,

INSULATION, HANGERS & SUPPORTS. REMOVE EXISTING PNEUMATIC TUBING AS FAR BACK AS

POSSIBLE AND MECHANICALLY CAP IN WALL.

4. SHEET MP-111 – LEVEL 1 HYDRONIC PLAN (Drawing is ReIssued)

a. Revise Keyed Note MP23 as follows (underlined items are added; strikethrough items are omit-

ted): PROVIDE ¾” GHWS/R WITH VALVE AND CAP FOR FUTURE VAV.

b. Add the following to Keyed Note MP24: PROVIDE SHUT-OFF VALVE.

c. Add the following to Keyed Note MP25: PROVIDE ISOLATION VALVE AT CONNECTION.

d. Refer to Secure Vestibule 118I: Provide space temperature sensor on east wall. Include Keyed

Note MP17. Coordinate Location with items within space.

5. SHEET MH111 – LEVEL 1 MECHANICAL HVAC PLAN (Drawing is not reissued)

a. Refer to Corridor 118J: Identified CAP note to locations of ductwork removed back to main.

b. Refer to Staff Breakroom 115: Added room tag.

Page 4: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001

Permit Set – 02/13/20 Page 4

Addendum No. 001 – 03/04/2020

c. Refer to Staff Breakroom 115: Identified CAP note to duct removed back to wall.

6. SHEET MH111 – LEVEL 1 MECHANICAL DEMOLITION PLAN (Drawing is not reissued)

a. Refer to Detail 3/M-510: Add Note to supply duct main take-off as follows: BELL-MOUTH OR

CONICAL TAKE-OFF.

b. Refer to Detail 13/M-510: Revise Numbered Note 1 to read: REFER TO MECHANICAL

SPECIFICATION FOR EXACT TYPE OF CONTROL VALVE, BALANCE VALVE, VENT, FITTINGS,

STRAINER, PIPING, EXT. USED FOR APPLICATION.

c. Refer to Detail 13/M-510: Add Note to equal distance piping: PROVIDE ISOLATION VALVES.

d. Refer to Detail 10/M-510: Add Note D: PROVIDE WITH SAFETY CHAIN.

7. SHEET ED111 – LEVEL 1 ELECTRICAL DEMOLITION PLAN (Drawing is Reissued)

a. Add additional demolition to existing Conference Room 111E. Refer to sheet for details.

b. Add Keyed Note E64. Refer to sheet for details.

8. SHEET ET111 – LEVEL 1 TECHNOLOGY PLAN (Drawing is Reissued)

a. Review clock location in Staff Breakroom 115. Refer to sheet for details.

b. Unshaded Storage Room 108C. Refer to sheet for details.

c. Add Keyed Notes E65 and E66. Refer to sheet for details.

E. ATTACHMENTS

1. AD-110 – OVERALL DEMOLITION FIRST FLOOR PLAN

2. I-110 – OVERALL FIRST FLOOR – FLOOR FINISH PLAN

3. MP-111 – LEVEL 1 HYDRONIC PLAN

4. ET111 – LEVEL 1 TECHNOLOGY PLAN

5. ED111 – LEVEL 1 ELECTRICAL DEMOLITION PLAN

* END OF ADDENDUM NO. 001 *

Page 5: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

UP

UP

FS

FS

F S

F S

DNUP

A) THE OWNER RESERVES THE RIGHT TO SALVAGE ANY EXISTING MATERIAL, EQUIPMENT, ETC. PRIOR TO THE START OF DEMOLITION. THE CONTRACTOR SHALL VERIFY THOSE ITEMS TO BE SALVAGED WITH OWNER.

B) ALL EXISTING CONSTRUCTION INDICATED TO REMAIN THAT IS DAMAGED OR AFFECTED BY THE DEMOLITION SHALL BE REPAIRED AND RESTORED TO ITS ORIGINAL CONDITION.

C) CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH THE OCCUPANT TO AVOID DISRUPTION OF THE FACILITY OPERATIONS. MAINTAIN REQUIRED EGRESS DURING CONSTRUCTION. PROVIDE TEMPORARY BARRICADES, ENCLOSURES AND PROTECTION AS NECESSARY DURING CONSTRUCTION.

D) WHERE WALLS OR PARTITIONS ARE SHOWN TO BE REMOVED, ALSO REMOVE ALL ITEMS ATTACHED, CONNECTED OR INTERNAL TO THE WALLS INCLUDING TRIM, SHELVING, ACCESSORIES, CABINETS, BLOCKING, EQUIPMENT, MARKERBOARDS, ETC. REMOVE IN THEIR ENTIRETY, FASTENERS AND WALL ATTACHMENT DEVICES. PATCH AND REPAIR AS NEEDED TO COMPLETE WORK.

E) CONTRACTOR TO VERIFY EXACT LOCATION AND IDENTIFY, LABEL AND PROTECT EXISTING MECHANICAL AND ELECTRICAL SERVICES WHICH MAY BE AFFECTED BY DEMOLITION.

F) ALL DEMOLITION WORK NOTED ON THESE DRAWINGS SHALL BE COORDINATED WITH CORRESPONDING NEW WORK FLOOR PLANS AND DETAILS. REMOVE EXISTING CONSTRUCTIONAS INDICATED OR REQUIRED BY THE NEW WORK.

G) DETAILS OF EXISTING CONDITIONS: ACTUAL FIELD CONDITIONS WHICH ARE CONCEALED BYEXISTING CONSTRUCTION MAY VARY FROM THOSE INDICATED IN THE DRAWINGS. ALL WORKTHAT RELATES TO, OR IS IN ANY WAY AFFECTED BY EXISTING CONDITIONS WHICH VARY FROM THOSE INDICATED SHALL BE MODIFIED AS REQUIRED TO COMPLY WITH THE NEW WORKREQUIREMENTS.

H) THE DEMOLITION DRAWINGS INDICATE MAJOR ITEMS TO BE DEMOLISHED AND REMOVED. MISCELLANEOUS ABANDONED ITEMS INCLUDING CONDUIT, WALL PENETRATIONS (SCREWS, NAILS,ANCHORS, ETC), WOOD BLOCKING, AND OTHER VARIOUS ITEMS FASTENED TO EXISTING WALLS MAY NOT BE INDICATED ON THE DRAWINGS. REMOVE SUCH ITEMS THAT ARE NOT USED IN, ORCONCEALED BY NEW WORK. PATCH AND REPAIR DAMAGE TO THE WALLS WHERE SUCH ITEMSARE REMOVED.

I) SAWCUT AND REMOVE THE EXISTING CONCRETE SLAB AS REQUIRED TO ACCOMODATE NEWSTRUCTURAL, PLUMBING, ELECTRICAL WORK, ETC. REFERENCE STRUCTURAL, PLUMBING,ELECTRICAL DRAWINGS. MINOR LOCATIONS MAY NOT BE INDICATED.

J) REFER TO THE GENERAL NOTES FOR OTHER APPLICABLE INFORMATION.

K) REMOVE ALL CEILING MOUNTED ITEMS INCLUDING LIGHT FIXTURES, GRILLS, REGISTERS, SPEAKERS, FIRE ALARM DEVICES, ETC. COORDINATE WITH MECHANICAL AND ELECTRICAL DRAWINGS.

L) SALVAGE ALL CEILING MOUNTED PROJECTORS AND TURN OVER TO OWNER.

M) REFER TO CIVIL, STRUCTURAL, PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.

N) PORTIONS OR ELEMENTS (I.E. DOOR FRAMES) OF WALL SCHEDULED TO BE REMOVED OR SAWCUT AND REMOVED SHALL BE DONE SO TO PREVENT DAMAGE TO ADJACENT CONSTRUCTION TO REMAIN.

O) LIMITS INDICATED FOR DEMOLITION OF EXISTING BRICK AND CMU MASONRY ARE APPROXIMATE. REMOVE MASONRY UNITS TO NEAREST MORTAR JOINTS TO PREMIT "TOOTHING IN" OF NEW MASONRY TO EXISTING COURSING, UNLESS NOTED OTHERWISE. REFER TO MECHANICAL DRAWINGS FOR REMOVAL OF THRU-WALL MECHANICAL GRILLES, REGISTERS, AND DUCTWORK. AT MASONRY WALLS REMOVE BRICK AND CMU TO NEAREST MORTAR JOINTS TO PERMIT "TOOTHING IN" OF INFILL MASONRY TO MATCH EXISTING COURSING.

P) ITEMS IDENTIFIED TO BE SALVAGED ("REMOVE AND DELIVER TO OWNER") SHALL BE CAREFULLY REMOVED AND DELIVERED TO A STORAGE AREA DESIGNATED BY THE OWNER FOR THIS PURPOSE. ITEMS OWNER CHOOSES TO RETAIN SHALL BE RELOCATED FROM THE STORAGE AREA BY OWNER (NIC). ALL OTHER ITEMS SHALL BE SUBSEQUENTLY REMOVED AND DISPOSED OF BY CONTRACTOR WHEN AUTHORIZED BY OWNER.

Q) EXISTING LOOSE FURNITURE, EQUIPMENT, SUPPLIES, AND PERSONAL BELONGINGS LOCATED IN SPACES TO BE RENOVATED SHALL BE REMOVED AND RELOCATED BY OWNER (NIC).

R) COORDINATE DEMOLITION WORK WITH NEW WORK NOTES TO ENSURE PROPER REMOVAL OF ITEMS.

S) REMOVE ALL CEILINGS UNLESS OTHERWISE NOTED.

T) REMOVE ALL CEILING MOUNTED PROJECTORS, SPEAKERS AND A/V ITEMS IN ALL ROOMS AND TURN OVER TO OWNER. A/V WIRING SHALL REMAIN ABOVE CEILING AND BRACKET SUPPORTED FROM THE STRUCTURE ABOVE.

U) DEMO ALL CONCRETE MECH AND ELECTRICAL UNIT HOUSEKEEPING PADS. SEE MECH/ELEC.

V) NOTE: THE CONTRACTOR SHALL ASSUME THAT THERE IS EXISTING FLOORING UNDER ALL EXISTING CASEWORK AND THAT THE FLOORING CONTAINS ASBESTOS. ONCE THE CONTRACTOR HAS REMOVED THE EXISTING CASEWORK THE CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE OWNER AND THE OWNER'S ASBESTOS ABATEMENT CONTRACTOR PRIOR TO RESUMING WITH THE REQUIRED WORK IN THE ROOM OR AREA WHERE THE CASEWORK IS REMOVED.

W) REMOVE ALL EXISTING FLOORING FINISHES AND WALL BASE WHERE NEW FLOORING AND WALL BASE ARE INDICATED AND / OR SCHEDULED.

X) THE CONTRACTOR SHALL COORDINATE WITH THE OWNER'S ASBESTOS ABATEMENT CONTRACTOR THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT. A COPY OF THE OWNER'S ABATEMENT CONTRACTOR SCOPE OF WORK IS INCLUDED IN THE PROJECT MANUAL FOR REFERENCE, ATTACHMENT F.

DEMOLITION GENERAL NOTESDEMOLITION PLAN SYMBOLSEXISTING DOOR AND FRAME TO REMAIN

EXISTING DOOR AND FRAME TO BE REMOVED

EXISTING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

EXISTING WINDOW TO REMAIN

EXISTING WINDOW TO BE DEMOLISHED

INDICATES EXISTING BUILDING AREAS WITH NO ARCHITECTURAL SCOPE OF WORK, U.N.O.

AREA OF FLOOR STRUCTURE DEMOLITION AND REPLACEMENT. COORDINATE WITH STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS.

UP

UPUP

UP

OPEN TO BELOW

D06D06

CL.

120

CL.

118 STAFF

112

MEN'S

TOILET

114

WOMEN'S

TOILET

116

D06 D07

D06

D06

D06

D06

D01

D05

F.V.+/- 9'-2"

PRINCIPALS

OFFICE

111A

CONFERENCE

ROOM

115

OFFICE

111C

OFFICE

111D

WORKROOM

111E

HEALTH

OFFICE

111F

STORAGE

111G

MISA

111H

MAIN OFFICE

111

D11

D11

CL.

126

CL.

100

CL.

136

CL.

134

CL.

132

CL.

130

CL.

128

CL.

102

CL.

104

OFFICE

109D

OFFICE

109E

STORAGE

108C

MEN'S

TOILET

108B

WOMEN'S

TOILET

108A

STORAGE

103B

FREEZER

108G

STORAGE

108A

STORAGE

108DTLT

108F

MULTI-PURPOSE

ROOM

108

GYM

109

WOMEN'S

LOCKERS

109A

MEN'S

LOCKERS

109B

Room

109F

TOILET

12TOILET

10

TOILET

11

JANITOR

103A

STORAGE

105D

GYM 110

239

WORK

ROOM

127

CL.

101

CL.

103

STORAGE

106

CL.

105

COMPUTER

ROOM

123/125

MEDIA

OFFICE

107

GIRLS'

TOILET

131 BOYS'

TOILET

129

LIBRARY

111K

STORAGE

106A

D02

D01

D01 D01

D02

D03

D10

D05

D05

EXISTING CHASE

AD-111

1

D08

D08

EXISTING ACCESS HATCH

DN

ELEVATOR

D04

D28

D18

D30

D31

D31

D32

D32

EXISTING CHASE ETR.

DASHED LINE OF OPEN CEILING ABOVE.

RECEIVING

108E

DISH

108C

KITCHEN

108B

D35

D39

108E D42

1

1

D43

D43

Issues and Revisions:

Commission No:

Drawn by:

Checked by:

SHEET

1295 BANDANA BLVD N, SUITE 200

ST. PAUL, MN 55108-2735

(651) 642-9200 | FAX (651) 642-1101

www.popearch.com

POPE ARCHITECTS, INC.

0" 1/2" 1"

TRUE SHEET SCALE

INFORMATION ON THESE PLANS REGARDING EXISTING STRUCTURE WAS TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS

PROVIDED BY MINNEAPOLIS PUBLIC SCHOOLS. ACTUAL FIELD CONDITIONS MAY VARY FROM

WHAT IS SHOWN. ALL DIMENSIONS, ELEVATIONS AND CONDITIONS OF EXISTING CONDITIONS TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

CONSTRUCTION.

3/4/2020 2:08:15 PMC:\Revit Projects\P1-53560-19131 MPS Lyndale ES - R19 -workshared_rlister.rvt

AD-110

OVERALL DEMOLITIONFIRST FLOOR PLAN

RDL

SAM

53560-19131

MPS LYNDALECOMMUNITY SCHOOL -

SAFE/SECUREENTRANCE AND

MONUMENT SIGN

312 W 34TH STMINNEAPOLIS, MN

55408

3/32" = 1'-0"AD-110

1 OVERALL DEMOLITION FIRST FLOOR PLAN

NORTH

DEMOLITION KEYNOTESKey Value Keynote Text

D01 THE OWNERS ASBESTOS ABATEMENT CONTRACTOR WILL DEMO THE EXISTING METAL STUDAND GYPSUM WALLBOARD WALL IN ITS ENTIRETY. SEE OWNER'S ABATEMENT CONTRACTORREPORT FOR FULL SCOPE OF WORK.

D02 DEMO EXISTING CONCRETE MASONRY WALL IN ITS ENTIRETY.D03 DEMO EXISTING DOOR, FRAME (INCLUDING ANY SIDELITE) AND HARDWARE.D04 DEMO EXISTING CONCRETE SLAB COMPLETE IN AREA OF RENOVATED TOILET ROOMS.D05 DEMO EXISTING PORTION OF WALL AS REQUIRED FOR NEW OPENINGS.D06 DEMO EXISTING CASEWORK SHOWN DASHED. SEE MECHANICAL DRAWINGS FOR FIN TUBE

SYSTEM DEMOLITION. SEE DEMOLITION GENERAL NOTES FOR ASBESTOS COORDINATIONREQUIREMENTS. SEE OWNER'S ABATEMENT CONTRACTOR REPORT FOR FULL SCOPE OFWORK.

D07 DEMO EXISTING HOLLOW METAL FRAME ENTRANCE SYSTEM.D08 DEMO EXISTING PLUMBING FIXTURE. SEE MECH FOR FULL PLUMBING SCOPE OF WORK.D10 REMOVE CMU BLOCK AND BRICK BEARING WALL, SEE STRUCT FOR NEW WALL. SALVAGE

BRICK FOR REINSTALLATION AROUND CUH REPLACEMENT AND EXISTING WINDOW INFILLLOCATIONS.

D11 DEMO CUH, SEE MECH.D18 DEMO EXISTING FLOOR SLAB AS REQUIRED TO INSTALL NEW FLOOR POWER/DATA BOXES.D27 SAWCUT CONCRETE FLOOR FOR NEW MECH. SEE MECH.D28 SAWCUT EXISTING FLOOR AS REQUIRED FOR NEW CASEWORK SINK.D30 DEMO EXISTING 3'-4" X 9'-0" TALL WINDOW.D31 PROTECT EXISTING WALL MOUNTED MURALS.D32 REMOVE EXISTING DOOR AND HARDWARE, EXISTING FRAME TO REMAIN.D35 REMOVE EXISTING FOUNTAIN AND SALVAGE.D36 THE OWNER'S ASBESTOS ABATEMENT CONTRACTOR WILL DEMO THE EXISTING

MARKERBOARDS. SEE OWNER'S ABATEMENT CONTRACTOR REPORT FOR FULL SCOPE OFWORK.

D37D38 THE OWNER'S ASBESTOS ABATEMENT CONTRACTOR WILL DEMO ALL OF THE EXISTING

CERAMIC TILE FLOORING AND WALL BASE WHERE NEW FLOORING AND WALL BASE ISINDICATED AND/OR SCHEDULED. SEE OWNER'S ABATEMENT CONTRACTOR REPORT FOR FULLSCOPE OF WORK.

D39 DEMO ALL EXISTING FLOORING AND WALL BASE WHERE NEW FLOORING AND WALL BASE ISINDICATED AND/OR SCHEDULED.

D40 DEMO EXISTING CEILING TILE AND GRID.D41 REMOVE EXISTING CEILING GRID AND TILES AS REQUIRED TO GET ACCESS TO DUCTWORK

ABOVE. SALVAGE GRID AND TILES FOR REINSTALLATION ONCE MECHANICAL WORK ISCOMPLETE.

D42 REMOVE EXISTING DOOR HARDWARE. EXISTING DOOR AND FRAME TO REMAIN. REFER TOSECURITY DRAWINGS FOR ADDITIONAL WORK SCOPE.

D43 DEMO EXISTING CORRIDOR DIVIDER DOOR COMPLETE INCLUDING WALL / OVERHEAD TRACKSAND SUPPORT FRAMING. PATCH EXISTING WALL FINISH AS REQUIRED.

ISSUE FOR BIDDING 02/13/20

ADDENDUM #1 03/04/20

NOTE: KEYNOTES THAT ARE NOT LISTED ARE NOT USEDAND THEREFORE HAVE BEEN INTENTIONALLY OMITTED.

1

Page 6: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

ACCACC

ACC

REF.

AC

C

CHECKIN

112B

WAITING

112A

SECURE

VESTIBULE

118I

CORRIDOR

118J

TOILET

116

TOILET

114

TOILET

112L

TOILET

112KCORRIDOR

112C

OFFICE

112E

OFFICE

112D

HEALTH

OFFICE

112J

CLASSROOM

113

CLASSROOM

120

CONFERENCE

ROOM

111

MEDIA

OFFICE

107

LIBRARY

1

STAFF

BREAKROOM

115

CPT2 RB1

OFFICE

112H

WORKROOM

112I

OFFICE

112F

CL.

122

CPT2 RB1

CPT2 RB1

CPT3 RB1

SC RB1

LVT1 RB2

CPT2 RB1

CPT2 RB1

VCT1 RB2

PTF1 PTB1

PTF1

PTB1

PTF1

PTB1

PTF1

PTB1

PTF1

PTB1

LVT1 RB2

CPT2 RB1

VCT1 RB2

VCT1 RB2

CPT3 RB1

VCT2

VCT3

VCT4

4'-0"

4'-0"4'-0"

EXIST EXIST

EXIST EXIST

4'-0"

4'-0"

VCT3

VCT2

VCT4

CL.

124

CL.

128

CL.

130

GIRLS'

TOILET

119

BOYS'

TOILET

117

WOMEN'S

LOCKERS

109A

STORAGE

109C

Room

109F

OFFICE

109D

OPEN TO BELOW

EXIST RB2

4'-0"

PROVIDE NEW VCT

1

ALIGNALIGN

VCT5 RB2

ALIGN

VCT5 RB2

ALIGN

1

1

XX#

XX# FLOOR FINISH, BASE FINISH

FINISH PLAN SYMBOLS LEGEND

XX#

XX#

BASE FINISH (WHERE VARIES WITHIN ROOM)

WALL FINISH

WALL FINISH (WHERE VARIES WITHIN ROOM)

FLOORING GRAIN DIRECTION

WALL PROTECTION (WP-1 U.N.O.)

XX# WALL FINISH (ABOVE) REFER TO INTERIOR ELEVATIONS

A) SUBMIT DRAW-DOWNS AND SAMPLES FOR ALL FINISH MATERIALS FOR APPROVAL BY ARCHITECT/DESIGNER PRIOR TO MATERIAL APPLICATION.

B) SUBMIT FINISH FLOORING SEAMING DIAGRAMS FOR APPROVAL BY ARCHITECT/DESIGNER PRIOR TO INSTALLATION.

C) FLOOR SURFACE PREPARATION: SURFACES TO BE PREPARED IN ACCORDANCE WITH PRODUCT MANUFACTURER'S RECOMMENDATIONS. FILL AND SMOOTH OUT ALL CRACKS, UNEVEN AND/OR ROUGH SURFACES IN SUBSTRATE WHERE NEW FLOOR COVERING IS TO BE INSTALLED. PRIOR TO INSTALLING FLOOR COVERING, REMOVE ANY AND ALL SUBSTANCES FROM SUBSTRATE, WHICH MAY TELEGRAPH THROUGH FINISH FLOORING.

D) JOINTS IN RESILIENT BASE SHALL NOT OCCUR CLOSER THAN 6" FROM CORNER AND SHALL BE BUTTED TIGHTLY TOGETHER.

E) PROVIDE REDUCER/TRANSITION STRIP BETWEEN DISSIMILAR FINISH FLOOR MATERIALS AT ALL AREAS. PROVIDE SAMPLE FOR ARCHITECT/DESIGNER APPROVAL.

F) MILLWORK SURFACE PREPARATION SHALL INCLUDE PUTTYING OF NAIL HOLES, CRACKS, AND BLEMISHES. PUTTY TO MATCH THE FINISH SURFACE.

G) WALL AND CEILING SURFACE PREPARATION: SURFACES TO BE PREPARED IN ACCORDANCE WITH THE FINISH MATERIAL MANUFACTURERS RECOMMENDATION. CONTRACTOR SHALL CONFIRM AND COORDINATE THE REQUIREMENTS. NO TELEGRAPHING OF WALL OR CEILING IRREGULARITIES WILL BE ACCEPTED.

H) CONTRACTOR SHALL REMOVE ALL ELECTRICAL SWITCHES AND OUTLET PLATES, SURFACE HARDWARE, GRILLE COVERS ETC., BEFORE PAINTING. PROTECT AND REPLACE SAME, IF IN GOOD CONDITION, WHEN PAINTING IS COMPLETE.

J) MISCELLANEOUS ITEMS (GRILLES, REGISTERS, METAL PANELS, ETC.) ON CEILINGS AND WALLS TO BE PAINTED TO MATCH SURFACE COLORS ON WHICH THEY OCCUR, UNLESS OTHERWISE NOTED.

K) CONTRACTOR SHALL FINISH AFFECTED SURFACES TO MATCH THE ADJACENT CONDITIONS. FINISH SURFACES TO THE NEXT LOGICAL JOINT OR WALL/CEILING CORNER UNLESS NOTED OTHERWISE.

FINISH PLAN GENERAL NOTESL) REFER TO THE GENERAL NOTES FOR OTHER APPLICABLE INFORMATION.

M) THRESHOLDS AT RESTROOMS DOORS TO BE TS-2. TRANSITIONS FROM CPT TO RESILIENT TO BE TS-1.

O) ALL CLOSET SHELVING TO BE PLAM-1.

P) SEE FLOOR FINISH PLANS AND/OR WALL FINISH PLANS AT I-110 TO I-121, FOR SPECIFIC FINISH INFORMATION.

Q) ALL WALLS TO BE PT-2 U.N.O.

R) INSTALL ONE (1) COAT HOOK CENTERED ON DOORS AT SINGLE STALL TOILET ROOMS .

S) ALL HOLLOW METAL DOOR & WINDOW FRAMES TO BE PAINTED TO MATCH EXISTING, SEMI-GLOSS FINISH ONLY, U.N.O.

T) EXTEND FLOOR AND WALL FINISHES UNDER AND BEHIND ALL APPLIANCES AND INTO ACCCESSIBLE SINK SPACES. EXTEND FLOOR AND WALL FINISHES UNDER ALL CASEWORK AND EQUIPMENT.

U) SHADED AREAS INDICATE EXISTING FINISHES TO REMAIN, U.N.O.

V) WHERE WALL FINISH VARIES, REFER TO ELEVATIONS FOR ADDITIONAL FINISH INFORMATION.

W) ALL SIGN TEXT (ROOM NAME & NUMBER) TO BE APPROVED BY OWNER PRIOR TO FABRICATION.

X) BASIS OF DESIGN FOR SIGNAGE IS ASI INTOUCH SERIES - REFER TO ELEVATION FOR DESIGN INTENT.

Issues and Revisions:

Commission No:

Drawn by:

Checked by:

SHEET

1295 BANDANA BLVD N, SUITE 200

ST. PAUL, MN 55108-2735

(651) 642-9200 | FAX (651) 642-1101

www.popearch.com

POPE ARCHITECTS, INC.

0" 1/2" 1"

TRUE SHEET SCALE

INFORMATION ON THESE PLANS REGARDING EXISTING STRUCTURE WAS TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS

PROVIDED BY MINNEAPOLIS PUBLIC SCHOOLS. ACTUAL FIELD CONDITIONS MAY VARY FROM

WHAT IS SHOWN. ALL DIMENSIONS, ELEVATIONS AND CONDITIONS OF EXISTING CONDITIONS TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

CONSTRUCTION.

3/4/2020 2:08:23 PMC:\Revit Projects\P1-53560-19131 MPS Lyndale ES - R19 -workshared_rlister.rvt

I-110

OVERALL FIRSTFLOOR - FLOOR FINISH

PLAN

RDL

MX

53560-19131

MPS LYNDALECOMMUNITY SCHOOL -

SAFE/SECUREENTRANCE AND

MONUMENT SIGN

312 W 34TH STMINNEAPOLIS, MN

55408

1/8" = 1'-0"I-110

1 OVERALL FIRST FLOOR - FLOOR FINISH PLAN

NORTH

FINISH PLAN KEYED NOTESI01 ENTIRE WALL TO RECEIVE NEW PAINT, PT-2.I02 PAINT TO MATCH ADJACENT WALL FINISH IN COLOR & SHEEN.I04 ROOM SIGNAGE TO BE TYPE A.I05 ROOM SIGNAGE TO BE TYPE B.I06 WAYFINDING SIGNAGE TO BE TYPE C.1.I07 WAYFINDING SIGNAGE TO BE TYPE C.2.I08 PROVIDE OPAQUE VINYL DECAL ON INTERIOR SIDE OF ROOM LOCATIONS WHERE SIGNS ARE

MOUNTED ON GLASS. DECALS TO BE THE SAME SIZE AND COLOR AS ROOM SIGN.

ISSUE FOR BIDDING 02/13/20

ADDENDUM #1 03/04/20

Page 7: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

F

S

AP

F

F

F

FS

V

V

F

F

F

F

AP

AP

F

F

F

F

K

C

AP

S

F

F

F

F

S

SS

IR

VP

AP

F

F

VP

IR

S S

S S

AP

SS

F

F

S

S

S

S

IR

AP

VP

S

S

S

IR

VP

AP

S

S

C

C

M

MTV

TV

FS

TV

S

S

F

F

SMSSSMSSSMSS

C

FS

SG

B

J

C

FS

FS

C

C

C

C

C

C

M

C

AP

FS MD

FSP

F

C

C

SM

D

SC

RS

VI

SD

C

F

F

S

F

F

S

C

C

F

F

FS

FS

FS

FS F

S

P

P

C

F

C

C

C

C

F S

F S

DH

DH

L2-7

L1-8

L1-4

SRSR

E3

E3

SR

SR

SR

SR

SR

SR SR

SR SRSR

SR

SRSR

E1

E1

CUH

CUH

FIBER & CL

DEMARC

TIME

CONTROL

CENTER

IDF

TERM BLOCKS

MDF

CUH

E50

CUH

E44

E1

L1-6

E14

STORAGE

108C

E64

1

OFFICE

109D

OFFICE

109E

MEDIA OFFICE

107

CORRIDOR

118J

TOILET

112L

TOILET

114

1

8' 16'4'01/8" = 1'-0"ED111

1 LEVEL 1 ELECTRICAL DEMOLITION PLAN

Issues and Revisions:

Commission No:

Drawn by:

Checked by:

SHEET

Date:

I hereby certify that this plan,specification,or report was

prepared by me or under my direct supervision and that I

am a duly Licensed Professional Engineer under the laws of

the State of MINNESOTA

Lic. No:

1295 BANDANA BLVD N, SUITE 200

ST. PAUL, MN 55108-2735

(651) 642-9200 | FAX (651) 642-1101

www.popearch.com

POPE ARCHITECTS, INC.

0" 1/2" 1"

TRUE SHEET SCALE

JAMES STEVEN SOMMER

54049

3/3/2020 1:38:41 PMC:\Autodesk\RevitTemp\MEP19 - MPS [email protected]

ED111

LEVEL 1 ELECTRICALDEMOLITION PLAN

JSS

DRP

19-141

02/13/2020

LYNDALE COMMUNITYSCHOOL -

SAFE/SECUREENTRANCE &

MONUMENT SIGN

312 W 34TH STMINNEAPOLIS, MN

55408

KEYED NOTES

E1 DEMOLISH THE EXISTING PANELBOARD, FEEDER CONDUIT AND CONDUCTORS, NEW PANELBOARD TO BE

PLACED IN SAME LOCATION WHERE POSSIBLE. EXISTING BRANCH CIRCUITS NOT REMOVED THROUGH

OTHER DEMOLITION WORK WILL REMAIN AND BE RECONNECTED TO NEW PANELBOARD.

E3 DEMOLISH POWER AND DATA CONNECTIONS AT FLOOR BOXES. CUT OUT AND REMOVE THE EXISTING

FLOOR BOXES. COORDINATE FLOOR PATCHING WITH GENERAL CONTRACTOR.

E14 EXISTING PAGING SYSTEM TO BE DEMOLISH AND RELOCATED IN NEW OFFICE. MAINTAIN AND EXTEND

ALL EXISTING PAGING SYSTEM CABLE TO NEW LOCATION.

E44 DEMOLISH EXISTING DEVICE MAINTAIN EXISTING CIRCUIT TO BE RE-USED.

E50 DEMOLISH POLE LIGHT. SAVE CIRCUITRY TO BE REUSED. SEE EP SERIES DRAWINGS.

E64 DEMOLISH EXISTING DATA RACK, TERMINAL BLOCK, GROUNDING BAR, AND RELATED EQUIPMENT.

RELOCATE EXISTING FIBER DEMARCATION POINT TO STORAGE ROOM 108C. COORDINATE RELOCATION

OF DEMARCATION POINT WITH UTILITY PROVIDER.

GENERAL SHEET NOTES

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET E-000 AND ELECTRICAL DEMOLITION SPECIFICATION

FOR ADDITIONAL REQUIREMENTS.

B. SEE ARCHITECTURAL DEMOLITION PLANS FOR EXTENT OF WALLS, CEILING AND ROOM FINISHES TO BE

REMOVED.

C. REFER TO SPECIFICATIONS FOR SCOPE OF DEMOLITION FOR EACH SYSTEM.

D. DEMOLISH ALL ELECTRICAL DEVICES IN WALLS TO BE DEMOLISHED OR REFINISHED. WALLS TO BE

DEMOLISHED ARE SHOWN DASHED. DISCONNECT AND REMOVE ASSOCIATED BOXES, CONDUIT AND WIRE

BACK TO SOURCE UNLESS NOTED OTHERWISE. NOT ALL DEVICES TO BE REMOVED MAY BE SHOWN.

E. THE EXISTING INTRUSION DETECTION SYSTEM SHALL BE EXISTING TO REMAIN. PROTECT IN PLACE AND

EXTEND ANY EXISTING CABLING AS REQUIRED TO ACCOMPLISH THE REQUIRED DEMOLITION. PROVIDE

NEW CABLING WHERE REQUIRED. COORDINATE EXTENT OF DEMOLITION WITH ELECTRICAL, MECHANICAL

AND ARCHITECTURAL DEMOLITION DRAWINGS. IF SYSTEM IS DISABLED / CUT DURING CONSTRUCTION, IT

SHALL BE REPAIRED IMMEDIATELY BY THE CONTRACTOR RESPONSIBLE.

F. TEMPORARILY DISCONNECT AND REMOVE WIRELESS ACCESS POINTS TO FACILITATE WORK IN ALL

AREAS WHERE CEILINGS ARE TO BE REMOVED. LABEL EQUIPMENT LOCATION AND RE-INSTALL IN NEW

CEILING AT PREVIOUS LOCATION.

G. TEMPORARILY DISCONNECT AND REMOVE SOUND REINFORCEMENT SPEAKERS AND INFRARED SENSORS

TO FACILITATE WORK IN ALL AREAS WHERE CEILINGS ARE TO BE REMOVED. LABEL EQUIPMENT

LOCATION AND RE-INSTALL IN NEW CEILING AT PREVIOUS LOCATION.

H. VIDEO PROJECTORS ARE TO BE REMOVED, EXCEPT AS NOTED. DISCONNECT AND REMOVE VIDEO

PROJECTORS AND RETURN TO OWNER. DISCONNECT AND REMOVE CONDUCTORS, CABLING, CONTROLS

AND MISCELLANEOUS HARDWARE ASSOCIATED WITH THIS SYSTEM. PROVIDE BLANK COVERPLATES

WHERE REQUIRED.

I. MAINTAIN EXISTING FIRE ALARM SYSTEM AND EXTEND TO NEW LOCATION. REFER TO ET SERIES SHEETS

FIRE ALARM RISER AND SPECFIICATION FOR ADDITIONAL INFORMATION.

NORTH

1

ISSUE FOR BIDDING 02/13/20

1 ADDENDUM 1 03/04/20

Page 8: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

REF.

ACCACC

ACC

AC

C

S

S

S

S

S

S

S

S

S

S

F

S

AP

F

F

F

F S

V

V

F

F

FF

S

S

S

S

IR

AP

VP

S

S

S

S

C

C

M

MTV

TV

F S

TV

S

S

F

F

C

C

F S

F

AP

AP

IR

IR

AP

S

S

S

S

SS

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

F

F

F S

F S

F S

F S F S

F

F

F

F

F

F

F

F

F

F

FF

FF

F

F

F

F

F

F

S

F

FF

F

S

S

S

S

F

S

S

C

F

C

C

C

C

F

S

S

S

F

F

F

F

C

C

CC

C

C

C

F

F

S

S

S

S

F SF S

T

FAA

FAA

E5

E5

E5

FB1

FB1

FB1

SRSR

SR

SR

SR

SR

SR

SR

SR

SR

SR

SR

SEE SECURITY PLANS -TY SERIES - FOR SECUREDENTRY DEVICE INSTALLATION

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

PA

E58

E55

DH

DH

TIMECONTROLCENTER

FB1

E5

STAFFBREAKROOM

115

CLASSROOM

113

CL.

122

WORKROOM

112I

OFFICE

112H

OFFICE

112F

CORRIDOR

112C

HEALTH OFFICE

112J

OFFICE

112EOFFICE

112D

CHECKIN

112B

TOILET

112K

TOILET

112LTOILET

116

TOILET

114

WAITING

112A

SECUREVESTIBULE

118IWOMEN'SLOCKERS

109A

MEN'S LOCKERS

109B

GYM 110

110

Room

109F

CORRIDOR

118J

CLASSROOM

120

LIBRARY

1

CONFERENCEROOM

111

MEDIA OFFICE

107

OFFICE

109D

OFFICE

109E

GYM 109

109

STORAGE

109C

PA

PA

PA

PA

PA

PA

PA

PA

E61

E61

E61

E61

E61

E61

E61

E61

E61

E61

E61E61

E61

E61

E61

E61

E61

E61

E61

E61

E61

E61

E61 E61

E61

E61

E61

E61

E61

E62

E55

E63

AC

STORAGE

108C E65

E66

1

8' 16'4'01/8" = 1'-0"ET111

1 LEVEL 1 TECHNOLOGY PLAN - AREA B

Issues and Revisions:

Commission No:

Drawn by:

Checked by:

SHEET

Date:

I hereby certify that this plan,specification,or report was

prepared by me or under my direct supervision and that I

am a duly Licensed Professional Engineer under the laws of

the State of MINNESOTA

Lic. No:

1295 BANDANA BLVD N, SUITE 200

ST. PAUL, MN 55108-2735

(651) 642-9200 | FAX (651) 642-1101

www.popearch.com

POPE ARCHITECTS, INC.

0" 1/2" 1"

TRUE SHEET SCALE

JAMES STEVEN SOMMER

54049

3/3/2020 1:37:50 PMC:\Autodesk\RevitTemp\MEP19 - MPS [email protected]

ET111

LEVEL 1TECHNOLOGY PLAN

JSS

DRP

19-141

02/13/2020

LYNDALE COMMUNITYSCHOOL -

SAFE/SECUREENTRANCE &

MONUMENT SIGN

312 W 34TH STMINNEAPOLIS, MN

55408

KEYED NOTES

E5 PROVIDE 1 ¼” SPARE CONDUIT TO UNUSED COMPARTMENT IN 4 COMPARTMENT FLOOR BOX. STUB UPABOVE ACCESSIBLE CEILING, PROVIDE BUSHING, CAP END AND LABEL CONDUIT FOR FUTURE A/V TOFLOOR BOX. PROVIDE 1” CONDUIT FOR DATA OUTLET.

E55 PROVIDE MUTING RELAY(S) ATLAS SOUND AA-PPRC OR SIMILAR FOR SOUND SYSTEM IN SPACE. MUTESOUND SYSTEM UPON FIRE ALARM OUTPUT.

E58 TAP LOWER DUE TO PROXIMITY TO VCA.

E61 PROVIDE A FIRE ALARM DEVICE THAT IS COMPATIBLE WITH THE EXISTING SYSTEM. EXTEND EXISTINGCIRCUITS TO NEW LOCATION AND REZONE. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E62 RELOCATE EXISTING PAGING SYSTEM. EXTEND ALL CABLES TO NEW LOCATION. CONTRACTOR TOPROVIDE ALL ADDITIONAL PART NEEDED TO PROVIDE A COMPLETE OPERATIONAL SYSTEM AS IN THEORIGINAL LOCATION.

E63 PROVIDE SURFACE MOUNTED RACEWAY FROM ABOVE THE CEILING TO FIRE ALARM ANNUNCIATOR ASNEEDED.

E65 EXTEND CABLING FOR EXISTING TO REMAIN CAMERAS THAT WHERE FED FROM DEMOLISHED RACK INOLD OFFICE. REFER TO SHEET ED111.

E66 LOCATION OF RELOCATED FIBER DEMARCATION POINT. COORDINATE EXACT LOCATION ON FIELD.

GENERAL SHEET NOTES

A. REFER TO GENERAL TECHNOLOGY NOTES ON SHEET E-000 AND ELECTRICAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

B. SEE ARCHITECTURAL PLANS FOR EXTENT OF WALLS, CEILINGS AND ROOM FINISHES TO BE INSTALLED.

C. REFER TO SPECIFICATIONS FOR SCOPE OF WORK REQUIRED FOR EACH SYSTEM.

D. EXTEND OR PROVIDE NEW INTRUSION DETECTION SYSTEM CABLING TO RE-INSTALL IN RENOVATED SPACE. SYSTEM TO REMAIN FUNCTIONAL DURING CONSTRUCTION. COORDINATE ANY PARTIAL AREA SHUTDOWNS REQUIRED FOR EXPANSION OR RECONNECTION WORK WITH OWNER.

E. REINSTALL EXISTING WIRELESS ACCESS POINTS TO IN ALL AREAS WHERE CEILINGS WERE RENOVATED. REFER TO LABELED EQUIPMENT LOCATION AND RE-INSTALL IN NEW CEILING AT PREVIOUS LOCATION OR AS DIRECTED BY OWNER.

F. REINSTALL SOUND REINFORCEMENT SPEAKERS AND INFRARED SENSORS IN ALL AREAS WHERE CEILINGS WERE RENOVATED. REFER TO LABELED EQUIPMENT LOCATION AND RE-INSTALL IN NEW CEILING AT PREVIOUS LOCATION OR AS DIRECTED BY OWNER.

NORTH

ISSUE FOR BIDDING 02/13/20

1 ADDENDUM 1 03/04/20

Page 9: ADDENDUM NO. 001 · 2020-03-05 · Lyndale Community School – Safe / Secure Entrance and Monument Sign Addendum No. 001 Permit Set – 02/13/20 Page 4 Addendum No. 001 – 03/04/2020

REF.

T

T

T

T

T

T

T

T

T

T

T

T

T

VAV-1.10

Htg: 2.5

VAV-1.11

Htg: 3

VAV-1.12

Htg: 4.2

VAV-3.1

Htg: 3.5

VAV-3.9

Htg: 1.9 VAV-3.10

Htg: 1.6

VAV-3.8

Htg: 1.6

VAV-3.7

Htg: 1.6

VAV-3.6

Htg: 1.6

VAV-3.5

Htg: 1.9

RCT-6

Htg: 1.8

CUH-8

Htg: 6.2

2" GHWS

2 1/2" GHWRR

3/4"3/4"

2" GHWS

3/4"3/4"

3/4"3/4"

2" GHWS3" GHWRR

3/4"3/4"

3" GHWRR

2" GHWS

3/4"

3/4"

3/4"3/4"

1"1"

2" GHWS

2" GHWRR

2" GHWRR2" GHWS

3/4"3/4"

2" GHWRR

2" GHWS

3/4"

2" GHWRR2" GHWS

RCT-10

Htg: 1.8

VAV-3.4

Htg: 4.2

RCT-5

Htg: 1.8RCT-5

Htg: 1.8

2 1/2" GHWRR

RCT-5

Htg: 1.8

CUH-7

Htg: 6.2

RCT-5

Htg: 1.8

RCT-5

Htg: 1.8

RCT-5

Htg: 1.8

<

<

<

<

<

<

<>

>

>>

>

>

>

>

>

3/4"3/4"

3/4"

3/4"

>

MP17

1"1"

LIBRARY

1

CLASSROOM

113

CLASSROOM

120

CONFERENCEROOM

111

MEDIA OFFICE

107

OFFICE

109D

OFFICE

109E

Room

109F

STORAGE

109C

GYM 109

109

GYM 110

110

WOMEN'SLOCKERS

109A

MEN'S LOCKERS

109B

SECUREVESTIBULE

118I

CORRIDOR

118J

TOILET

114TOILET

116

TOILET

112L

TOILET

112K

HEALTH OFFICE

112J WAITING

112A

CHECKIN

112B

CORRIDOR

112C

OFFICE

112D

OFFICE

112E

OFFICE

112F

OFFICE

112H

WORKROOM

112I

CL.

122

BOYS' TOILET

117

GIRLS' TOILET

119

STAFFBREAKROOM

115

(E) 2" GHWRR

(E) 1 1/2" GHWS

3" GHWRR

2" GHWS

2" GHWRR

2" GHWS

2 1/2" GHWRR2" GHWS

MP17

MP17

MP17

MP17

MP17

MP17

MP17

MP17

MP17

MP17

MP15 MP15

MP15

MP15

MP23

3/4"

MP24

MP24

MP17

2" GHWS

MP22

MP22

2" GHWRR

MP15

MP15

MP15

MP15

MP15

MP15 MP15

MP24

MP24

MP14

MP22

MP25

MP25

MP25

MP25

MP25MP25

MP25

MP18MP18

MP18

MP18

MP26

MP18

3/4"3/4"

1 1/4"1 1/4"

1"

1"

1

1

1

1

1

M17

3/4"

3/4"

1

Issues and Revisions:

Commission No:

Drawn by:

Checked by:

SHEET

Date:

I hereby certify that this plan,specification,or report was

prepared by me or under my direct supervision and that I

am a duly Licensed Professional Engineer under the laws of

the State of MINNESOTA

Lic. No:

1295 BANDANA BLVD N, SUITE 200

ST. PAUL, MN 55108-2735

(651) 642-9200 | FAX (651) 642-1101

www.popearch.com

POPE ARCHITECTS, INC.

0" 1/2" 1"

TRUE SHEET SCALE

LARRY G. JUSTIN

22460

3/3/2020 12:45:58 PMC:\Users\ajentenza\Documents\MEP19 - MPS Lyndale_ajentenza.rvt

MP111

LEVEL 1 HYDRONICPLAN

LGJ

AJE

19-141

02/13/2020

LYNDALE COMMUNITYSCHOOL -

SAFE/SECUREENTRANCE &

MONUMENT SIGN

312 W 34TH STMINNEAPOLIS, MN

55408

KEYED NOTES

M17 REPLACE EXISTING EXHAUST FAN ON ROOF WITH NEW EXHAUST FAN. PROVIDECURB ADAPTOR & EXTEND/RECONNECT DUCTWORK AS REQUIRED. PROVIDE NEWMOTORIZED DAMPER. REFER TO DETAIL 11/M503.

MP14 INSTALL CABINET UNIT HEATER AT LOCATION OF REMOVED. COORDINATE WITHGENERAL CONTRACTOR ON WALL WORK AND REPAIR AS NEEDED. REFER TODETAIL (3-WAY CONTROL VALVE).

MP15 CONNECT GHWS/R TO VAV. REFER TO DETAIL (2-WAY CONTROL VALVE)

MP17 INSTALL TEMPERATURE SENSOR AT LOCATION OF REMOVED IF POSSIBLE

MP18 RADIANT CEILING PANEL. REFER TO DETAIL AND COORDINATE WITHMANUFACTURER ABOUT SITE SPECIFIC INSTALLATION REQUIREMENTS

MP22 CONNECT TO TO EXISTING GHWS/R ; CONFIRM SIZE.

MP23 PROVIDE 3/4" GHWS/R WITH VALVE AND CAP FOR FUTURE VAV.

MP24 CAP FOR FUTURE CONNECTION. PROVIDE SHUT-OFF VALVE.

MP25 CONNECT TO EXISTING GHWS/R ABOVE. PROVIDED ISOLATION VALVE ATCONNECTION. CONFIRM SIZE.

MP26 INSTALL CEILING MOUNTED CABINET UNIT HEATER. REFER TO DETAIL 10/M-510

NORTH

8' 16'4'01/8" = 1'-0"MP111

1 LEVEL 1 HYDRONIC PIPING PLAN

ISSUE FOR BIDDING 02/13/20

1 ADDENDUM 1 03/04/20

1