addendum - blane casey

48
Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 1 of 8 ADDENDUM Date October 11, 2019 To Prospective Bidders Re Addendum No. 2 to the Construction Documents for: Yarmouth High School Additions and Renovations Yarmouth, Maine Project No. 19103 This Addendum forms a part of the Contract Documents and modifies the original Construction Documents dated September 24, 2019 and Addendum No. 1 October 3, 2019. Acknowledge receipt of this Addendum in the space provided in the Proposal Form. This Addendum consists of eight pages, Specification Section 087100 – Door Hardware and drawings as listed on Page 8. Harriman Daniel Cecil, AIA Principal

Upload: others

Post on 14-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 1 of 8

ADDENDUM Date October 11, 2019 To Prospective Bidders Re Addendum No. 2 to the Construction Documents for:

Yarmouth High School Additions and Renovations Yarmouth, Maine Project No. 19103 This Addendum forms a part of the Contract Documents and modifies the original Construction Documents dated September 24, 2019 and Addendum No. 1 October 3, 2019. Acknowledge receipt of this Addendum in the space provided in the Proposal Form. This Addendum consists of eight pages, Specification Section 087100 – Door Hardware and drawings as listed on Page 8. Harriman

Daniel Cecil, AIA Principal

Page 2: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 2 of 8

QUESTIONS AND ANSWERS Q. B3/A83.1 calls for linear bar diffuser continuous length of casework. M10.3 seems to show individual grilles. Are grilles continuous for length of casework or individual grilles in casework? A. The length and locations of the linear diffusers shall be coordinated to match the length and locations of the fin tube radiation shown on sheets M20.1 – M20.3.

Q. A10.5 calls for cementitious wall panels and refers to E5/A80.2, which is not shown. Should this refer to C7/A80.2?

A. Yes the note should refer to C7/A80.2.

Q. C7/A80.2 does not show rigid acoustical insulation but does show 1 x 3 (nominal, ¾” actual thickness) strapping. Is rigid acoustical insulation required at CAWP in Mechanical Rooms? If so, is it ¾” thick (same thickness as strapping) or 1” thick as per Spec Section 062000 2.2 B?

A. Detail C7/A80.2 shall be revised to include 1” rigid acoustical insulation installed between the furring. The furring note shall be changed to 5/4 x 3 spaced 23 ¾” OC to match the finish width of the panels and allow for the 1” thick insulation. Q. CAWP cementitious acoustical wall panels are listed on the Room Finish Schedule for Mech Mezz 720 but not called out on D5/A10.5. CAWP is also not called out on wall sections and there are no interior elevations for this room. Should CAWP be included in Mech Mezz 720? A. Yes, CAWP shall be installed on the four walls of Mech Mezz 720 per revised detail C7/A80.2. Q. I’m hoping you can direct me in the right direction. I am trying to understand the scope of work for the ramp rebuild in Alternate #8. Drawing A10.5 is directing us to the structural drawings but I have not been able to come up with a detail showing the scope of the reconstruction. The Demo drawings is asking us to remove the flooring and the sheathing but again no rebuild instructions. Am I missing something? A. 2 x 10 floor framing will be installed at 16” oc between the existing floor joist framing. New ¾” plywood floor sheathing, glued and screwed to structure, will then be installed over the overbuilt corridor and ramp area. Q. Per our phone conversation just now, we need clarification on 108500, page 5, section B where it indicates that we would provide an opaque sheet behind the reflective white vinyl on exterior doors and/or classroom windows. We usually just apply the reflective white vinyl to the glass, but if they do need a black backer or something on the opposite side we can provide that. Please offer a clarification when you can. A. Refer to Addendum 2. Q. “I don’t see any hardware sets specified for this job. Can you please reach out and see if the design team plans on releasing one? A. Apparently the wrong Section 087100 was sent at bid time. Section 087100 without hardware sets was from the 100% Review Set. The correct section with the hardware sets will be sent with the addendum items.

Page 3: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 3 of 8

Q. On the miscellaneous items schedule it has MB6, MB8, TB4, TB6, TB8 all listed as 8ft long. Is this correct?” A. No, the number in the designations is the length of the item (MB6 is 6 feet long). Section 10100 – Visual Display Units clarifies this in Article 2.2.B.6 and Article 2.3.B.1. Q. “The miscellaneous items schedule lists GB-36” and GB-42”, the detail A7, and F4 on A11.1 Also show GB- 18”. Is the intent to have 18” GB in all bathrooms?” A. 18” vertical grab bars are required per the IBC code besides all accessible toilets. See detail A7/A11. Q. I was wondering what the plan was for an emergency exit from the second floor in Stair 1 when the stair is removed to install the new one. A. Stair 1 work will be completed in Phase 3 when that portion of the school will not be occupied. At that point Stair 6 should be completed to provide adequate second means of egress from the second floor. Q, “On drawing A51.1 E1) Roof Type R1 at pitched steel locations. The roof plan does not show any roof area that is getting Roof Type R1. Drawing A50.3 detail B3 and C3 are showing a pitched roof eave detail and a pitched roof peak detail. Is one of the roof areas on the roof plan A15.1 mis labeled on the roof type? Please clarify. “ A. R1 roof type is noted on the sloped roof above the new main entrance. Q. A3/A50.3 calls for reinforced membrane, however spec section 075323 2.4 calls for non-reinforced EPDM. Please clarify. A. Note shall read EPDM ROOFING MEMBRANE OVER PLYWOOD SHEATHING. Q. Spec section 075323 2.4 calls for epichlorohydrin sheets. Are these required? If so please clarify where. A. EPDM roofing is specified and required. Q. Spec section 075323 calls for walkway pads however none are shown on the roof plan. Will a layout be provided or are we to only provide walkway pads per manufacturers requirements? A. They will be required. A revised roof plan will be issued in a subsequent Addendum. Q. Spec section 075323 2.8 B calls for 3” iso at flat steel locations. E5/A51.1 calls for 2.5” iso. Please clarify which is correct. A. Base Poly Iso insulation shall all be 3” thickness. Q. Spec section 077200 2.5 calls for roof tie offs. There is none shown on the plans. Please provide a layout or a count of these for us to flash. A. The provider, Guardian, needs to provide a layout of tie off locations per OHSA requirements as part of the specifications. Q. What is the construction traffic flow? A. Refer to Civil documents.

Page 4: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 4 of 8

Q. When will the w14s be installed at the existing 2-story classroom? A. Preferably in the summer. This would have to be coordinated with the Yarmouth High School if needed to be completed sooner. Q. Maintaining egress at the Courtyard / classroom wing. A. Egress from the Building 4 classroom wing will need to be maintain while that portion of the building is occupied. Additionally, construction fencing must allow egress from existing courtyard. Q. In the OT-Robotics room question about is the swing staying? A. The swing will be relocated by the owner, but contractor to provide structural support as indicated on drawings. Q. Do we anticipate the bid date being moved? A. No, not at this time. Q. Below grade plumbing removal be abandoned, can it be abandoned? A. Refer to Plumbing drawings. Q. Looking at the phasing plan, the new construction and roof replacements for areas C and D are clear. However, we would like clarification for the roof replacement schedules for areas A and B. Will this be 2020-2021 work? Please see attached. A. Roof replacement for areas A and B are shown to be between April 2020 and October 2020. Q. Please advise on when the Door Hardware Schedule will be issued? A. Refer to Addendum 2. Q. On the new parking lot shown next to athletic field access road, sheet C00.1 shows “New Pre-Cast Concrete Curb”. I assume they actually want slipform curbing, not precast curbing, as I haven’t seen that used in many years. Can you confirm? A. Drawing C00.1 Site Plan: At new parking lot and bus parking area near the athletic field, the Precast Concrete Curb(PCC) will be used as shown on detail D7 on drawing C50.2. Slip-form cast-in-place concrete curb will not be an acceptable alternate, since the pavement may be removed from the contract. CHANGES TO SPECIFICATIONS 1. SECTION 075323 – ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING

a. Article 2.3, D., delete paragraph and replace with the following: “D. Fully Adhered EPDM Roof System Assembly R4, Existing Construction: New fully adhered

roof membrane adhered to new cover. Cover board shall be fastened through existing insulation, 4 inches deep, and into poured reinforced gypsum, 1-1/2 - 2 inches deep, on formboard deck supported on bulb tees."

b. Article 2.3, F., delete paragraph and replace with the following:

“F. Gym Roof EPDM Roof System Assembly R6, Existing Construction: Fully adhered roof membrane adhered to new cover board. Cover board shall be fastened through existing insulation, 4 inches deep, and into poured reinforced gypsum, 1-1/2 - 2 inches deep, on formboard deck supported on bulb tees."

Page 5: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 5 of 8

c. Article 2.5, C. delete paragraph in its entirety; no protection sheet is required on project. 2. SECTION 083323 – OVERHEAD COILING DOORS

a. Article 2.1.A, add the following: “3. Overhead Door Corp.: Stormtite AP Model 627.”

3. SECTION 087100 – DOOR HARDWARE

a. Revised and re-issued with this addendum. 4. SECTION 088000 - GLAZING a. Article 2.5, D., delete and replace with the following: “D. Low-E, Clear, Insulated Glass Units with Security Glass, SG-IG.” 5. SECTION 108500 – BUILDING SPECIALTIES

a. Article 2.2.B, delete paragraph and associated subparagraphs and replace with the following: “B. Vinyl Characters, Identification Numbers for Exterior Doors and Windows of Occupied

Rooms: Laser cut, white reflective vinyl characters cut from 3- to 3.5-mil thick, UV- and weather-resistant vinyl film with release liner on the back and carrier film on the front for on-site alignment and application.

1. Size as follows: a. Exterior Doors: 10 inches high. b. Windows in Occupied Rooms: 8 inches high. 2.Font: Arial. 3. Text: To be determined by Architect. 4. Quantitiy: As follows:

a .Exterior Doors: Allow for a two digit identification number at every exterior door, new and existing.

b. Windows in Occupied Rooms: Provide a three digit identification number on one window of occupied rooms: allow for 75 rooms.”

6. SECTION 260721- FIRE ALARM SYSTEMS a. Article 2.1, A., delete and replace with the following: “A. Edwards – No Substitutions.” 7. SECTION 270100 – COMMUNICATIONS SYSTEMS a. Article 2.03, A., delete and replace with the following:

“A. Provide a new facility wide public address and clock system. The public address system shall be and Hybrid IP/Analog system. Basis of design is the Carehawk CH1000 Communications System, sold and serviced by Canfield Systems, Inc. Public Address and Master Clock systems shall be based on the Valcom IP6000 (VE6025) platform, no equals.”

b. Article 2.04, A.,1.,delete and replace with the following:

“1. The Card Access System shall be Avigilon Access Control Manager (ACM), as specified, no equals.The ACM system shall be an IT-friendly Physical Access Control System (PACS) suitable for enterprise-class installations. It should combine video management, wireless locking, and intrusion control and visitor management into a powerful access management solution.”

Page 6: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 6 of 8

c. Article 2.04 B., 1., delete and replace with the following: “1. Video Management System shall be based on the Avigilon Control Center V7

Enterprise, Part # ACC7-ENT as specified, no equals. The VMS shall include unlimited viewing clients, Mobile App, High Definition Stream Management, Analytics, and Appearance Search technology. The VMS must be ONVIF Profile S and T compliant and an open platform to accept multiple camera manufacturers. The VMS shall not require recurring annual support fees and must provide free updates within the version software. Provide all licensing required for all cameras and components plus 20%.”

d. Article 2.04, C., 1., delete and replace with the following:

“ 1. Main Control Panel shall be Bosch alarm panel B series D9412GV4, as specified, no equal. Provide universal enclosure and all mounting hardware. Equal products must be fully compatible with the platform provided. Provide universal enclosure, power supplies, standby battery and all mounting hardware. Install on backboard in the MDF. All alarm points on the system shall be individually addressable.”

8. SECTION 333000 – SANITARY SEWERS

a. Article 1.2, A., delete and replace with the following: “A. This section includes gravity-flow nonpressure sanitary sewerage outside the building with

the following components:” b. Article 2.5, B., delete and replace with the following: “B. Manhole Channels and Benches: Formed fiberglass invert channel and benches.” CHANGES TO DRAWINGS

1. DRAWING C00.1 – SITE PLAN A. At new parking lot and bus parking area near the athletic field, the Precast Concrete Curb(PCC) will

be used as shown on detail D7 on drawing C50.2. Slip-form cast-in-place concrete curb will not be an acceptable alternate, since the pavement may be removed from the contract.

2. DRAWING A01.3 – PHASING PLAN A. The note at the pair of doors at the end of corridor 430 shall be changed to: B. “Provide temporary type 243n wall on the west side of the existing wall with a temporary pair of

doors swinging toward the exterior. The right hand leaf shall be 4’-0 x 7’-0 and open against the existing magnetic hold open. The left hand leaf shall be 2’-0 x 7’-0. See hardware schedule for additional information.

3. DRAWING A05.1 – FIRST FLOOR DEMOLITION PLAN

A. The note at the pair of doors at the end of corridor 430 shall be changed to: “remove and salvage cross corridor door leafs and hardware for reinstallation after phase 3.”

4. DRAWING A10.5 – SECOND FLOOR PLANS

A. A1 second floor plan – room 619a note shall change from: “cementitious wall panels see e5/a80.2” to “cementitious wall panels see c7/a80.2.”

B. D5 second floor plan area b., add the following note referring to the 4 walls in the mech mezz: “cementitious wall panels see c7/a80.2.”

5. DRAWING A50.1 – EXTERIOR SECTION DETAILS

A. D6 - foundation detail (cmu backup) 2” rigid insulation under entire slab shall be changed to: “4’-0 wide 2” rigid insulation”

B. C5 – foundation detail (ss backup) 2” rigid insulation under entire slab shall be changed to: “4’-0 wide 2” rigid insulation”

Page 7: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 7 of 8

C. B4 - foundation detail (ss backup) 2” rigid insulation under entire slab shall be changed to: “4’-0 wide 2” rigid insulation”

6. DRAWING A50.3 – EXTERIOR SECTION DETAILS

A. A3 – lap to roof transition – reinforced roofing membrane over plywood sheathing shall be changed to: “epdm roofin membrane over plywood sheathing.”

7. DRAWING A51.1 – ROOF DETAILS

A. E5 – roof type r5 1 layer 2 ½” roof insulation shall be changed to: “ 1 layer 3” roof insulation.”

8. DRAWING A60.1 – DOOR SCHEDULE A. Door 700 shall be changed from “wood” to “hollow metal.” B. Door 703 shall be changed from “wood” to “hollow metal.” C. Add door 801 to the door schedule. It shall receive insulated laminated glazing. D. Doors st1b, st6b and st6d shall be changed from “wood” to “hollow metal.” E. Door 620a shall be changed from “wood” to “hollow metal.”

9. DRAWING A60.2 – DOOR DETAILS

A. C4 head detail - at door 330 lintel flashing, weep holes and frame insulation are not required as it’s an interior door.

10. DRAWING A80.1 – STANDARD INTERIOR DETAILS

A. Miscellaneous item schedule – 1. Add “gb – 18” ada vertical grabbar” 2. Change mb6 to: “marker board, 6’-0 long x 4’-0 high” 3. Change tb4 to: “tackboard 4’-0 long x 4’-0 high” 4. Change tb6 to: “ tackboard 6’-0 long x 4’-0 high”

11. DRAWING A80.2 – STANDARD INTERIOR DETAILS

A. Detail c7 shall change in the following way. Furring shall change to: “5/4 x 3 spaced at 23 ¾” oc.” 1” thick rigid acoustical insulation shall be placed between the furring.

12. DRAWING A80.2 – STANDARD INTERIOR DETAILS

A. Detail c7 shall change in the following way. Furring shall change to: “5/4 x 3 spaced at 23 ¾” oc.” 1” thick rigid acoustical insulation shall be placed between the furring.

13. DRAWING S10.1 – FOUNDATION PLANS AREA A A. Near e31/r1 note “provide ¼” thick steel box…” add “see c2/a50.1 for additional information” B. Near eM.9/K.2 new concrete slab should read “new 4” thick concrete slab on ground infill with fiber

reinforcing”

14. DRAWING S10.2 – FOUNDATION PLANS AREA B AND D A. At grids 11.6 and 11.8 on D.6 adjust top of footing elevations to [-3’-0”].

Page 8: ADDENDUM - Blane Casey

Addendum No. 2 H:\2019\19103\4-Bidding-Negotiation\Addenda\Addendum2\addendum2_Final.docx Page 8 of 8

15. DRAWING S20.1: SECOND FLOOR AND LOW ROOF FRAMING PLAN AREA A A. For framing plan note 7. the net uplift pressure shall be 15psf.

16. DRAWING S20.2:SECOND FLOOR FRAMING PLANS AREA B AND D

A. For framing plan note 7. the net uplift pressure shall be 15psf. B. Cut section A1/S60.3 on grid D between 1 and 3. C. At the edge of the mezzanine stair opening the change the E.O.S note to read “ 1’-7” e.o.s. provide 3/8”

thick bent plate”. D. Change the “D1” deck over the weight room to “D2”.

17. DRAWING S30.1: ROOF FRAMING PLAN AREA A

A. For framing plan note 7. the net uplift pressure shall be 15psf. B. Cut section A2/S60.3 on grid K.1 between 21 and 22.

18. DRAWING S30.2: ROOF FRAMING PLANS AREA B AND D

A. For framing plan note 7. the net uplift pressure shall be 15psf.

19. DRAWING S40.3: BRACING ELEVATIONS AND DETAILS A. Remove “S3-3” from elevation C3 on grid 3. B. On elevation A6 change the shear lug notation at grid A to “SL-3”.

20. DRAWING S60.2: FRAMING DETAILS

A. In section D5 remove “0” from the weld symbol. B. In section C6 change “(3) ¾” dia. A325 bolts” to “(4) ¾” dia. A325 bolts”.

DRAWINGS REVISED AND REISSUED WITH THIS ADDENDUM, DATED 10-11-19: 1. Drawing S50.2 – FOUNDATION DETAILS 2. Drawing S60.3 – FRAMING DETAILS DRAWINGS ISSUED WITH THIS ADDENDUM, DATED 10-11-19: 1. Drawing SKA1 - Additional Pavement and New Location of Fence and Sidewalk 2. Drawing SKA2 - Revised Pavement Detail 3. Drawing SKA3 - Revised Portion of C00.4 4. Drawing SKA4 - Canopy Framing Plans Area D 5. Drawing SKA5 - Partial Roof Framing Plans Area D 6. Drawing SKA6 - Partial Foundation Plan Area A

Page 9: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 1

SECTION 087100 - DOOR HARDWARE

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following: 1. Commercial door hardware for the following:

a. Swinging doors. 2. Cylinders for doors specified in other Sections. 3. Electrified door hardware. 4. On site inspection of installed hardware, including proper installation of closers for

degree of swing. 5. At electrified hardwired locks, provide the low voltage wiring harness and terminations

within the door from the hinge to the lock, hinge to above the door frame to permit connection by access controls vendor, electric strike to hardware mullion and hardware mullion to above the door frame to permit connection by access controls vendor.

B. Related Sections include the following: 1. Division 08 Section "Steel Doors and Frames" for kerf smoke seals and sound seals and

weatherstripping provided as part of the frame. 2. Division 08 Section "Wood Doors" for astragals provided as part of a fire-rated labeled

assembly. 3. Division 26 and 27 Sections for connections to electrical power system and for low-

voltage wiring work. 4. Division 27 Sections for access control system.

1.3 SUBMITTALS

A. General: Submit in accordance with Division 01 Section "Submittal Procedures." 1. Submittals for Division 08 Sections "Hollow Metal Doors and Frames," "Wood Doors,"

"Aluminum-Framed Entrances and Storefronts: and "Door Hardware" shall be made concurrently.

B. Product Data: Include installation details, material descriptions, dimensions of individual components and profiles, and finishes.

C. Shop Drawings: Details of electrified door hardware, indicating the following: 1. Wiring Diagrams: Detail wiring for power, signal, and control systems and differentiate

between manufacturer-installed and field-installed wiring. Include the following: a. System schematic.

2. Detail interface between electrified door hardware and fire alarm system.

D. Samples: For exposed door hardware of each type indicated below, in specified finish, full size. Tag with full description for coordination with the Door Hardware Schedule. Submit samples before, or concurrent with, submission of the final Door Hardware Schedule.

Page 10: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 2

1. As requested by Architect. 2. Samples will be returned to Contractor. Units that are acceptable and remain undamaged

through submittal, review, and field comparison process may, after final check of operation, be incorporated into the Work, within limitations of keying requirements.

E. Door Hardware Schedule: Prepared by or under the supervision of supplier, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final Door Hardware Schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware. 1. Format: Comply with scheduling sequence and vertical format in DHI's "Sequence and

Format for the Hardware Schedule." 2. Organization: Organize the Door Hardware Schedule into door hardware sets indicating

complete designations of every item required for each door or opening. a. Organize door hardware sets in same order as in the Door Hardware Schedule at

the end of Part 3. 3. Content: Include the following information:

a. Type, style, function, size, label, hand, and finish of each door hardware item. b. Manufacturer of each item. c. Fastenings and other pertinent information. d. Location of each door hardware set, cross-referenced to Drawings, both on floor

plans and in door and frame schedule. e. Explanation of abbreviations, symbols, and codes contained in schedule. f. Mounting locations for door hardware. g. Door and frame sizes and materials. h. Description of each electrified door hardware function, including location . i. Provide hardware for every door in the project, except as indicated, so that each

door functions correctly for its intended use. Where a door is not included in the Door Hardware Schedule at end of Part 3, provide hardware scheduled for similar type opening and review with Architect.

4. Submittal Sequence: Submit the final Door Hardware Schedule at earliest possible date, particularly where approval of the Door Hardware Schedule must precede fabrication of other work that is critical in the Project construction schedule. Include Product Data, Shop Drawings of other work affected by door hardware, and other information essential to the coordinated review of the Door Hardware Schedule.

F. Keying Schedule: Meet directly with the Owner to review hardware function and keying requirements. Prepare keying schedule by or under the supervision of supplier, detailing Owner's final keying instructions for locks. Include schematic keying diagram and index each key set to unique door designations.

G. Qualification Data: For firms and persons specified in "Quality Assurance" Article. 1. Include lists of completed projects with project names and addresses of architects and

owners, and other information specified.

H. Maintenance Data: For each type of door hardware to include in maintenance manuals specified in Division 01.

I. Warranties: Special warranties specified in this Section.

Page 11: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 3

1.4 QUALITY ASSURANCE

A. Installer Qualifications: An experienced installer who has completed door hardware similar in material, design, and extent to that indicated for this Project and whose work has resulted in construction with a record of successful in-service performance.

B. Supplier Qualifications: Door hardware supplier with warehousing facilities in Project's vicinity and who is or employs a qualified Architectural Hardware Consultant, available during the course of the Work to consult with Contractor, Architect, and Owner about door hardware and keying. 1. Electrified Door Hardware Supplier Qualifications: An experienced door hardware

supplier who has completed projects with electrified door hardware similar in material, design, and extent to that indicated for this Project, whose work has resulted in construction with a record of successful in-service performance, and who is acceptable to manufacturer of primary materials.

2. Scheduling Responsibility: Preparation of door hardware and keying schedules.

C. Architectural Hardware Consultant Qualifications: A person who is currently certified by the Door and Hardware Institute as an Architectural Hardware Consultant and who is experienced in providing consulting services for door hardware installations that are comparable in material, design, and extent to that indicated for this Project. 1. Architectural hardware consultant shall be a full time employee of the hardware supplier,

shall be located within 2 hours driving time of the project site, and participate in job site meetings, keying and hardware function reviews, coordination and field examination of installed hardware.

D. Source Limitations: Obtain each type and variety of door hardware from a single manufacturer, unless otherwise indicated.

E. Pre-Ordering Meeting: Before ordering hardware, have a meeting with the Contractor, Owner and Architect to review hardware functions, door swing clearances and closer requirements, requirements and conflicts with hold open devices, electronic locking, door stops and other similar hardware requirements affecting the use and operation of each opening. 1. Prepare a list of questions and potential conflicts and distribute to the Architect 5 days

before the meeting. 2. Shop drawings, including door and frame shop drawings and door hardware schedule

shall be furnished to the Architect at least 10 days before the meeting. 3. Review each door on the project and record meeting notes regarding any coordination,

modifications and changes. Submit meeting minutes within 3 days of meeting date.

F. Conditions and Coordination: Hardware supplier shall determine conditions and materials of doors and frames for proper application of hardware. 1. The Door Hardware Schedule submittal shall list the actual product series numbers.

Hardware supplier shall follow manufacturers' catalog requirement for the actual size of door closers, brackets and holders. Door opening sizes are as noted on the Door and Frame Schedule and hardware shall be in strict accordance with requirements of height, width, and thickness.

G. Regulatory Requirements: Comply with provisions of the following: 1. Comply with all applicable codes. Comply with Americans with Disabilities Act (ADA),

as follows:

Page 12: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 4

a. Handles, Pulls, Latches, Locks, and other Operating Devices: Shape that is easy to grasp with one hand and does not require tight grasping, tight pinching, or twisting of the wrist. 1) Operable parts of such hardware shall be 34 inches minimum and 48 inches

maximum above the finish floor or ground. b. Door Closers: Comply with the following maximum opening-force requirements

indicated: 1) Interior Hinged Doors: 5 lbf applied perpendicular to door. 2) Fire Doors: Minimum opening force allowable by authorities having

jurisdiction. c. Thresholds: Not more than 1/2 inch high. Bevel raised thresholds with a slope of

not more than 1:2. 2. NFPA 101: Comply with the following for means of egress doors:

a. Latches, Locks, and Exit Devices: Not more than 15 lbf to release the latch. Locks shall not require the use of a key, tool, or special knowledge for operation.

b. Door Closers: Not more than 30 lbf to set door in motion and not more than 15 lbf to open door to minimum required width.

c. Thresholds: Not more than 1/2 inch high. 3. Electrified Door Hardware: Listed and labeled as defined in NFPA 70, Article 100, by a

testing agency acceptable to authorities having jurisdiction.

H. Fire-Rated Door Assemblies: Provide door hardware for assemblies complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire ratings indicated, based on testing according to NFPA 252. 1. Test Pressure: After 5 minutes into the test, neutral pressure level in furnace shall be

established at 40 inches or less above the sill (Positive pressure).

I. Keying Conference: Conduct conference directly with the Owner. Incorporate keying conference decisions into final keying schedule after reviewing door hardware keying system including, but not limited to, the following: 1. Function of building, flow of traffic, purpose of each area, degree of security required,

and plans for future expansion. 2. Requirements for key control system. 3. Address for delivery of keys.

J. Preinstallation Conference: Conduct conference at Project site with hardware supplier, hardware installer, electrical subcontractor, and access control vendor to comply with requirements in Division 01 Section "Project Management and Coordination." Review methods and procedures related to door hardware including, but not limited to, the following: 1. Inspect and discuss electrical roughing-in and other preparatory work performed by other

trades. 2. Review sequence of operation for each type of electrified door hardware. 3. Review and finalize construction schedule and verify availability of materials, Installer's

personnel, equipment, and facilities needed to make progress and avoid delays. 4. Review required testing, inspecting, and certifying procedures. 5. Review requirements that screws for door hinges in fire rated wood doors are not to be

removed once they have been installed into the fire rated door edge material. 6. Review proper installation procedures for locksets, exit devices and closers with Installer

and Hardware Supplier. 7. Coordinate job site meeting for locating magnetic hold open devices. 8. Coordinate on site inspection of installed hardware, including proper installation of

closers for degree of swing, allowing doors to open to door stops without binding.

Page 13: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 5

1.5 DELIVERY, STORAGE, AND HANDLING

A. Inventory door hardware on receipt and provide secure lock-up for door hardware delivered to Project site.

B. Tag each item or package separately with identification related to the final Door Hardware Schedule, and include basic installation instructions with each item or package.

C. Deliver keys to Owner by registered mail or overnight package service.

1.6 COORDINATION

A. Templates: Obtain and distribute to the parties involved templates for doors, frames, and other work specified to be factory prepared for installing door hardware. Check Shop Drawings of other work to confirm that adequate provisions are made for locating and installing door hardware to comply with indicated requirements.

B. Electrical System Roughing-in: Coordinate layout and installation of electrified door hardware with connections to power supplies fire alarm system, and access control system.

1.7 WARRANTY

A. General Warranty: Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

B. Special Warranty: Written warranty, executed by manufacturer agreeing to repair or replace components of door hardware that fail in materials or workmanship within specified warranty period. Failures include, but are not limited to, the following: 1. Structural failures including excessive deflection, cracking, or breakage. 2. Faulty operation of operators. 3. Deterioration of metals, metal finishes, and other materials beyond normal weathering.

C. Warranty Period for Manual Closers: 10 years from date of Substantial Completion.

D. Warranty Period for Electric Strikes: 5 years from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 SCHEDULED DOOR HARDWARE

A. General: Provide door hardware for each door to comply with requirements in this Section, and the Door Hardware Schedule at the end of Part 3. 1. Door Hardware Sets: Provide quantity, item, size, finish or color indicated, and named

manufacturer's products specified. 2. Sequence of Operation: Provide electrified door hardware function, sequence of

operation, and interface with other building control systems indicated.

B. Designations: Requirements for function, and other distinctive qualities of each type of door hardware are indicated in the Door Hardware Schedule at the end of Part 3.

Page 14: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 6

2.2 HINGES AND PIVOTS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Hinges:

a. Hager Companies. b. McKinney Products Company; Div. of ESSEX Industries, Inc. c. Stanley Commercial Hardware; Div. of The Stanley Works.

2. Continuous Geared Hinges: a. Select Products Limited SL11HD. No substitution.

B. Standards: Comply with the following: 1. Butts and Hinges: BHMA A156.1. 2. Template Hinge Dimensions: BHMA A156.7. 3. Self-Closing Hinges and Pivots: BHMA A156.17.

C. Quantity: Provide the following, unless otherwise indicated: 1. Two Hinges: For doors with heights up to 60 inches. 2. Three Hinges: For doors with heights 61 to 90 inches. 3. Four Hinges: For doors with heights 91 to 120 inches. 4. For doors with heights more than 120 inches, provide 4 hinges, plus 1 hinge for every 30

inches of door height greater than 120 inches.

D. Size: Provide the following, unless otherwise indicated, with hinge widths sized for door thickness and clearances required: Metal

Thickness (inches)

Maximum Door Size (inches) Hinge Height (inches)

Standard Weight

Heavy Weight

40 and under by 1-3/4 4-1/2 0.134 0.180 Over 40 by 1-3/4 5 0.146 0.190

E. Hinge Weight: Unless otherwise indicated, provide the following: 1. Exterior Doors with Leaf Hinges: Heavy-weight hinges. 2. Interior Doors with Closers: Antifriction-bearing hinges. 3. Interior Doors:

a. General: Standard-weight hinges, oil-impregnated bearings unless specified otherwise.

b. Interior doors at Stairs, Cross Corridors, Vestibules, and entry doors into Gymnasium,: Shall be heavy weight hinges.

F. Hinge Base Metal: Unless otherwise indicated, provide the following: 1. Exterior Hinges: Stainless steel, or non-ferrous with stainless-steel pin. 2. Interior Hinges: Steel, with steel pin or stainless steel, with stainless-steel pin.. 3. Hinges for Fire-Rated Assemblies: Steel, with steel pin.

G. Hinge Options: Comply with the following: 1. Nonremovable Pins: Provide set screw in hinge barrel that, when tightened into a groove

in hinge pin, prevents removal of pin while door is closed; for the following applications: a. Outswinging exterior doors.

Page 15: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 7

b. Outswinging interior doors with locks. 2. Corners: Square.

H. Electrified Functions for Hinges: Comply with the following: 1. Electrical Contact: Exposed electrical contacts for transfer of power. 2. Power Transfer: Concealed PTFE-jacketed wires, secured at each leaf and continuous

through hinge knuckle. a. 8 wire configuration for doors with electrified exit devices. b. Provide wires with PoE modular plug-in connectors.

I. Continuous-Geared Hinges: Provide for exterior and interior doors where scheduled. Heavy duty hinge leaves with minimum overall width of 4 inches; fabricated to full height of door and frame; concealed leaf mounting. Finish components after milling and drilling are complete. Fabricate hinges to template screw locations. 1. Anodize finish components after milling and machining are complete. Clear anodized. 2. Hinge shall have lifetime lubrication. 3. Fire rated hinges shall not require fire pins or studs. 4. Power Transfer: Removable panel, concealed PTFE-jacketed wires, secured at each leaf

and continuous through hinge knuckle. 8 wire configuration.

J. Fasteners: Comply with the following: 1. Machine Screws: For metal doors and frames. Install into drilled and tapped holes. 2. Threaded-to-the-Head Wood Screws: For fire-rated wood doors. 3. Screws: Phillips flat-head screws; machine screws (drilled and tapped holes) for metal

doors. Finish screw heads to match surface of hinges. 4. Stainless steel for stainless steel hinges and for continuous hinges at exterior doors.

2.3 LOCKS AND LATCHES

A. Manufacturers: Subject to compliance with requirements, provide products by the following: 1. Mortise Locks, Mechanical Locks and Latches complying with lock function

requirements. a. Corbin Russwin. b. Sargent. c. Schlage.

B. Mortise Locks: Stamped steel case with steel or brass parts; BHMA Grade 1; Series 1000. 1. Corbin-Russwin: Series ML2200, Lever design NSA. 2. Sargent: Series 8200, Lever design LN. 3. Schlage: Series L9000, Lever design 07A.

C. Auxiliary Locks: BHMA Grade 1.

D. Lock Trim: Comply with the following: 1. Lever: Forged or Cast. 2. Escutcheon (Rose): Wrought.

E. Lock Functions: Function numbers and descriptions indicated in the Door Hardware Schedule. 1. Classroom Security Function: Double cylinder mortise lockset with dead latching latch

bolt. Provide with interior locked visual indicator. Exiting room does not unlock lever. 2. Institutional Privacy Function: Key outside retracts latchbolt. Specialty key override of

thumb turn inside when held in locked position. Lever outside, except when locked by

Page 16: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 8

thumb turn. Lever outside unlocks when the door closes or operating inside lever. Lever inside always retracts latchbolt. Auxiliary deadlatch.

F. Lock Throw: Comply with testing requirements for length of bolts to comply with labeled fire door requirements, and as follows: 1. Minimum 3/4-inch latchbolt throw. 2. Deadbolts: Minimum 1-inch bolt throw. 3. Thumb Turn: ADA compliant throw lever.

G. Backset: 2-3/4 inches, unless otherwise indicated.

H. Specialty Lock Function: 1. Time Out Lock: Pushing and holding outside button disengages inside spindle, allowing

inside lever to free-wheel without retracting latch. Release of outside button allows free egress from inside. a. Schlage ND45.Schlage ND-Lever Series, Lever design Rhodes RHO, 3-1/2-inch

Rose, or equal from Corbin-Russwin or Sargent. Keyway to match mortise locks.

2.4 DOOR BOLTS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Surface Bolts:

a. Glynn-Johnson. b. Ives. c. Rockwood.

2. Flush Bolts: a. Door Controls International. b. Glynn-Johnson. c. Ives. d. Rixson. e. Rockwood.

B. Standards: Comply with the following: 1. Surface Bolts: BHMA A156.16. 2. Automatic and Self-Latching Flush Bolts: BHMA A156.3.

C. Surface Bolts: BHMA Grade 1. 1. Flush Bolt Heads: Minimum of 1/2-inch- diameter rods, or flat bar of brass, bronze, or

stainless steel with minimum 12-inch- long rod for doors up to 84 inches in height. Provide longer rods as necessary for doors exceeding 84 inches.

D. Flush Bolts: BHMA Grade 1, designed for mortising into door edge.

E. Bolt Throw: Comply with testing requirements for length of bolts to comply with labeled fire door requirements, and as follows: 1. Surface Bolts: Minimum 7/8-inch throw. 2. Fire-Rated Surface Bolts: Minimum 1-inch throw; listed and labeled for fire-rated doors. 3. Mortise Flush Bolts: Minimum 3/4-inch throw.

F. Strikes: Provide matching strikes for heads of doors. Provide dust proof strikes at all floor locations.

Page 17: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 9

2.5 EXIT DEVICES

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Sargent; 80 Series.

a. Provide narrow design 8500 Series for aluminum doors. 2. Von Duprin; 98 Series.

a. Provide narrow design 35A Series for aluminum doors.

B. Panic Exit Devices: Listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for panic protection, based on testing according to UL 305. Fire rated exit devices and exit devices in smoke partitions shall not have cylinder dogging. Exit devices that are not in fire rated walls or smoke partitions shall have cylinder dogging. Exit devices at exterior doors shall have cylinder dogging. 1. Electronic and mechanical exit devices shall be from the same manufacturer.

C. Fire Exit Devices: Complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire and panic protection, based on testing according to UL 305 and NFPA 252.

D. Smoke Door Exit Devices: Smoke doors are required to latch. Cylinder dogging of smoke doors is not permitted.

E. Outside Trim: Lever with cylinder; Cylinder at doors scheduled to receive pulls; material and finish to match locksets, unless otherwise indicated. 1. Match design for locksets and latchsets, unless otherwise indicated.

2.6 POWER SUPPLIES

A. Boxed Power Supply: Provided by access controls vendor, specified in Division 27. 1. Low Voltage Wire (Harness): Size, type and configuration for the equipment, distance

and connections required. Provide wiring from the electric transfer hinges to above the door frame to permit connection by access controls vendor and from the hinge to the exit device, and provide wiring from the electrified hardware mullion to above the door frame to permit connection by access controls vendor and from the hardware mullion to the electric strikes to assure proper interface and connections of the hardware.

2.7 CYLINDERS AND KEYING

A. Manufacturers: Subject to compliance with requirements, provide products by the following: 1. Cylinders: Provide for exit devices, locksets, locks and latches.

a. Corbin Russwin to match existing.

B. Standards: Comply with the following: 1. Cylinders: BHMA A156.5. 2. Key Control System: BHMA A156.5.

C. Cylinder Grade: BHMA Grade 1.

D. Construction Keying: Comply with the following:

Page 18: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 10

1. Construction Cores: Provide construction cores that are replaceable by permanent cores. Provide 10 construction master keys. Standard key temporary cores acceptable. Provide temporary cores for all exterior doors and for 6 interior doors. a. Replace construction cores with permanent cores at completion of project.

E. Keying System: Unless otherwise indicated, provide a factory-registered keying system complying with the following requirements: 1. Master Key and/or Grand Master Key System: Cylinders are operated by a change key, a

master key, and a grand master key. 2. Master Keys shall be sent to the Owner by registered mail, return receipt required. 3. Furnish manufacturer’s job number to Architect and Owner.

F. Keys: Provide nickel-silver keys complying with the following: 1. Stamping: Permanently inscribe each key with a visual key control number and include

the following notation: a. Notation: "DO NOT DUPLICATE."

2. Quantity: In addition to one extra blank key for each lock, provide the following: a. Cylinder Change Keys: Three for each cylinder keyed differently; Six for each set

keyed alike; Four for sets where only two cylinders are keyed alike. b. Master Keys, Grand Master Keys: Six for each set.

2.8 STRIKES

A. Manufacturers: Same manufacturer as lock, latch and device bolt engaging into strike.

B. Standards: Comply with the following: 1. Strikes for Mortise Locks and Latches: BHMA A156.13. 2. Strikes for Auxiliary Deadlocks: BHMA A156.5. 3. Dustproof Strikes: BHMA A156.16.

C. Strikes: Provide manufacturer's standard strike with strike box for each latch or lock bolt, with curved lip extended to protect frame, finished to match door hardware set, unless otherwise indicated.

D. Dustproof Strikes: BHMA Grade 1.

E. Electric Strike: Hes, 12V DC, BHMA Grade 1 strike. Provide all strikes with SMART Pac III accessory in-line power control, bridge rectifier, surge protection. 1. Hardware Mullion Strike: 9600 series Genesis III.

2.9 OPERATING TRIM

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Burns. 2. Ives. 3. Rockwood.

B. Standard: Comply with BHMA A156.6, solid bar.

Page 19: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 11

C. Materials: Fabricate from stainless steel, unless otherwise indicated. 1. Door Pulls: 1inch diameter by 12 inches long, 2-1/2 inch clearance, decorative thru bolt.

Ives 8103EZ Rockwood BF112 Burns HCP26C Hager H10L

2. Push/Pull Bars: 1inch diameter, 12-inch Pull, 2-1/2 inch clearance, concealed back-to-back mounting. Ives 9103EZHD (8103EZ + 9100 Push) Rockwood BF11247 (BF112 x 47 push) Burns HCP26C x 422 Hager H154 (H10L x 130S)

3. Door Pull Plates: 1inch diameter by 10 inches long, .125 x 3-1/2”/4” x 15”/16” plate Ives 8303 Rockwood 111x70B Burns 7326C Hager 30S, 4J

2.10 ACCESSORIES FOR PAIRS OF DOORS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Coordinators:

a. Door Controls International. b. Glynn-Johnson. c. Hager Companies. d. Rockwood.

2. Removable Mullions: a. Corbin Russwin. b. Sargent. c. Von Duprin.

B. Standards: Comply with the following: 1. Coordinators: BHMA A156.3, Type #21 unless indicated otherwise.

a. Shall be provided at all pairs of label doors equipped with overlapping astragals or where improper closing sequence would interfere with proper operating of doors.

b. Furnish filler pieces to close opening between coordinator and jamb of frame. Provide mounting brackets as required for proper mounting of additional hardware.

c. Models: Hager 297D, Door Controls 600 Series, Glynn Johnson Series "COR", or Rockwood 1600 Series. 1) Provide projection door coordinator at location indicated: Ives 469 ½.

2. Removable Mullions: BHMA A156.3, steel. Powder coat finish to match aluminum doors.

C. Removable Mullions: Provide removable mullions for use with fire exit devices complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire and panic protection, based on testing according to

Page 20: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 12

UL 305 and NFPA 252. Mullions shall be used only with exit devices for which they have been tested. 1. Provide primer finish for field finish. 2. Electrified mullions shall have quick disconnect twist apart plug connectors.

2.11 CLOSERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Surface-Mounted Closers:

a. LCN Closers. b. Sargent.

B. Standards: Comply with the following: 1. Closers: BHMA A156.4. 2. Closer Holder Release Devices: BHMA A156.15.

C. Surface Closers: BHMA Grade 1, cast-iron body. 1. Door closers shall have fully hydraulic, full rack and pinion action. Cylinder body shall

be 1-1/2" in diameter, and double heat treated pinion shall be 11/16" in diameter. 2. Spring power shall be continuously adjustable over the full range of closer sizes, and

allow for reduced opening force for the physically handicapped. Hydraulic regulation shall be by tamper-proof, non-critical valves. Closers shall have separate adjustment for latch speed, general speed, and hydraulic back-check.

3. All closers shall have heavy (extra) duty (EDA) solid forged steel main arms (and forged forearms for parallel arm closers).

4. Closer arms shall have a powder coating finish. 5. Provide drop, mounting plates for aluminum doors, and where required. 6. Provide parallel arm closers at all locations unless door configuration and function does

not permit. 7. Door closers shall be adjusted by the installer in accordance with the manufacturer's

templates and written instructions. Closers with parallel arms shall have back-check features adjusted prior to installation.

8. Closers shall conform to all applicable code and law requirements relative to setting closing speeds for closers and maximum pressure for operating interior and exterior doors.

9. Models:

LCN Sargent

Exterior 4111S-CUSH 281 - CPS 4111S-H-CUSH 281 - CPSH

Interior 4011 281 - 0 4111 281 - P10

4111S-CUSH 281 - CPS 4111S-H-CUSH 281 – CPSH

D. Swing: Allow door to swing to the maximum degree opening allowable for the swing condition. Where doors with closers do not have a bumper stop or overhead stop, provide closer with CUSH-N-STOP feature. Do not allow leading edge of door to swing into the path of an adjacent door opening.

Page 21: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 13

E. Size of Units: Unless otherwise indicated, comply with manufacturer's written recommendations for size of door closers depending on size of door, exposure to weather, and anticipated frequency of use. Provide factory-sized closers, adjustable to meet field conditions and requirements for opening force.

2.12 POWERED DOOR OPERATORS

A. Electrically - Powered Door Operator 1. Referenced Standard: Provide unit that conforms to AAMA/BHMA A156.19 low energy

operation, and to ADA Architectural Guidelines for opening force and time to close standards.

2. Products: Subject to compliance with requirements, furnish one of the following products: a. Interior Doors: Horton 7000 LE. No substitution. b. Exterior Doors: Horton 4000 LE. No substitution.

3. General: Furnish complete system, including electro-mechanical swinging door operator and solid-state electronic control, aluminum header matching door frame, connecting hardware, and power on/off switch.

4. Operator: Opening by means of a fractional HP DC motor, through reduction gears, splined spindle, door arm and linkage assembly. If door encounters an obstacle, operator shall stop the door in the open position by electrically reducing the motor voltage and stalling. Spring closing, with closing speed controlled by the motor operating as a dynamic brake. Operator shall function as a manual door closer in the direction of swing, with or without electrical power. a. Operator shall be removable from the header as a unit, for servicing and replacement. b. Door Speed and Timing:

1. Door opening time: Adjustable but not less than 4 seconds. 2. Door closing time: Adjustable but not less than 4.5 seconds. 3. Hold Open: Adjustable from 6 to 60 seconds, to allow safe passage between series

of doors at entrance and vestibule. c. Furnish unit without power assist ("Push-N-Go") feature, or with device that allows

Owner to activate or disconnect the feature after the door has been installed. d. Provide interface module and cube relay for card access lock release.

5. Header: 0.125 minimum wall thickness extruded aluminum. 6. 6. Metal Finish: Finish covers, mounting plates, and arm system with manufacturer's

standard powder-coat finish. Match finish of storefront framing system. 7. Presence Sensor: Overhead diffused active infrared presence sensor that can sense moving

and stationary objects, protecting swing path and threshold protection until object has fully cleared swing path of door. BEA Bodyguard.

a. BEA Bodyguard. b. Location: Provide at each operator.

8. Push-Plate Control: Nominal 4 inch square or 4-1/2 inch diameter round push-plate control; stainless steel with No. 4 satin finish; with international accessibility symbol engraved and painted blue.

a. Push plates provided with no exposed fasteners on the faceplate area. Furnish wall-mounted type, as appropriate to mounting conditions indicated on Drawings.

2.13 PROTECTIVE TRIM UNITS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Metal Protective Trim Units:

Page 22: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 14

a. Burns Manufacturing Incorporated. b. Don-Jo Mfg., Inc.. c. Rockwood Manufacturing Company.

B. Standard: Comply with BHMA A156.6.

C. Materials: Fabricate protection plates from the following: 1. Stainless Steel: 0.050 inch thick; beveled top and 2 sides.

D. Fasteners: Provide manufacturer's oval head exposed fasteners for door trim units consisting of either machine or self-tapping screws, for installation in counter sunk holes.

E. Furnish protection plates sized 2 inches less than door width on push side by the following height: 1. Armor Plates: 34 inches. 2. Kick Plates: 8 inches 3. Push Plates: 8 inches wide by 16 inches high.

2.14 STOPS AND HOLDERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Glynn-Johnson. 2. Hager Companies. 3. Ives. 4. Rockwood.

B. Standards: Comply with the following: 1. Stops and Bumpers: BHMA A156.16. 2. Mechanical Door Holders: BHMA A156.16. 3. Electromagnetic Door Holders: BHMA A156.15. 4. Door Silencers: BHMA A156.16.

C. Stops and Bumpers: BHMA Grade 1. 1. Wall Stops: Convex with concealed mounting. 2. Floor Stops: Dome stop, base thickness to accommodate flooring thickness.

D. Electromagnetic Door Holders for Labeled Fire Door Assemblies: Coordinate with fire detectors and interface with fire alarm system and interface with access control system. Coordinate mounting and projection requirements to hold back door to the maximum swing possible. 1. Provide concealed wired units. 2. Provide device type and location that does not require the use of chain extensions.

a. Field verify location and conditions, and coordinate with the hardware schedule.

E. Wall Stops: For doors, unless floor or other type stops are scheduled or indicated. Do not mount floor stops where they will impede traffic. 1. Where floor or wall stops are not appropriate, provide heavy duty overhead holders.

a. Glynn-Johnson GJ90. b. Sargent 590.

Page 23: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 15

F. Silencers for Metal Door Frames: BHMA Grade 1; neoprene or rubber, minimum diameter 1/2 inch; fabricated for drilled-in application to frame.

2.15 DOOR GASKETING

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Door Gasketing and Door Bottoms:

a. National Guard.. b. Pemko. c. Reese Enterprises. d. Zero.

B. General: Provide continuous weather-strip gasketing on exterior doors and provide smoke, light, or sound gasketing on interior doors where indicated or scheduled. Provide noncorrosive fasteners for exterior applications and elsewhere as indicated. 1. Perimeter Gasketing: Apply to head and jamb, forming seal between door and frame. 2. Meeting Stile Gasketing: Fasten to meeting stiles, forming seal when doors are closed. 3. Door Bottoms: Apply to bottom of door, forming seal with threshold when door is

closed.

C. Weather-Strip Gasketing Models: Listed manufacturers with comparable models to the following:

Product Pemko Reese NGP Thresholds as detailed Brush Seal 45062AP 970 A626A Door Sweep 345AV 353 101AV Set Astragals Pemko 29310CPK, concealed fastener Rain Drip 346C R201A 16AD Door Bottom 234PK Note: Provide door bottom in addition to sweep. Coordinate flush bottom on hollow metal doors and door clearance to threshold to permit door bottom installation. Smoke Seals Head and Jambs: Kerf gasketing specified in Division 08 Section “Hollow Metal Doors and

Frames.” Set Astragals Surface applied with concealed fasteners, silicone bulb with aluminum

retainer, equal to Pemko 29310CPK unless indicated otherwise.

D. Fire-Labeled and Smoke Gasketing: Assemblies complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire ratings indicated, based on testing according to UL 10B or NFPA 252. 1. Head and Jambs: Kerf gasketing specified in Division 08 Section “Hollow Metal Doors

and Frames.”

E. Sound Gasketing: 1. Head and Jambs: Kerf gasketing specifiedSection 081113 - Steel Doors and Frames. 2. Head and Jamb Perimeter Surface Applied Seals: Surface applied adjustable perimeter

seals, equal to models indicated.

Page 24: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 16

3. Astragal/Meeting Stile Gasket: Surface applied with concealed fasteners, silicone bulb with aluminum retainer, equal to Pemko 29310CPK.

4. Automatic Door Bottom: Concealed mortised automatic drop seal, equal to models indicated.

2.16 THRESHOLDS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. National Guard. 2. Pemko. 3. Reese. 4. Zero.

B. Standard: Comply with BHMA A156.21.

C. General: Extruded aluminum, depth as required for sill condition. Where thresholds extend out beyond face of frame, provide returned closed ends by miter cutting on a 45 degree angle and return to face of frame.

D. Height: 1/2 inch ADA compliant. Provide 1/4 inch high at locations indicated.

E. Provide half-saddle threshold where butting carpet, entrance matting and ceramic tile, 1/4 inch or 1/2 inch height to match height of adjacent finish.

2.17 FABRICATION

A. Base Metals: Produce door hardware units of base metal, fabricated by forming method indicated, using manufacturer's standard metal alloy, composition, temper, and hardness. Furnish metals of a quality equal to or greater than that of specified door hardware units and BHMA A156.18 for finishes. Do not furnish manufacturer's standard materials or forming methods if different from specified standard.

B. Fasteners: Provide door hardware manufactured to comply with published templates generally prepared for machine, wood, and sheet metal screws. Provide screws according to commercially recognized industry standards for application intended. Provide Phillips flat-head screws with finished heads to match surface of door hardware, unless otherwise indicated. 1. Concealed Fasteners: For door hardware units that are exposed when door is closed,

except for units already specified with concealed fasteners. Do not use through bolts for installation where bolt head or nut on opposite face is exposed unless it is the only means of securely attaching the door hardware. Where through bolts are used on hollow door and frame construction, provide sleeves for each through bolt.

2. Steel Machine or Wood Screws: For the following fire-rated applications: a. Mortise hinges to doors. b. Strike plates to frames. c. Closers to doors and frames.

3. Spacers or Sex Bolts: For through bolting of hollow metal doors. 4. Fasteners for Wood Doors: Comply with requirements of DHI WDHS.2,

"Recommended Fasteners for Wood Doors."

Page 25: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 17

2.18 FINISHES

A. Standard: Comply with BHMA A156.18.

B. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

C. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations in the same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

D. BHMA Designations: Comply with base material and finish requirements indicated by the following: 1. BHMA 613 (US10B): Dark oxidized satin bronze, bronze base material, oil rubbed.

E. With the following exceptions, all hardware items shall be furnished in 10B oil rubbed bronze finish. 1. Exceptions are as follows:

Door Closers: Sprayed dark bronze Thresholds: Aluminum

Aluminum: Dark Bronze Anodized Aluminum

PART 3 - EXECUTION

3.1 EXAMINATION

A. Contractor shall examine doors and frames, with Installer present, for compliance with requirements for installation tolerances, labeled fire door assembly construction, wall and floor construction, and other conditions affecting performance. If errors in dimensions or preparation are encountered, they are to be corrected by the responsible parties prior to the installation of hardware.

B. Examine roughing-in for electrical power systems to verify actual locations of wiring connections before electrified door hardware installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Steel Doors and Frames: Comply with DHI A115 series. 1. Surface-Applied Door Hardware: Drill and tap doors and frames according to SDI 107.

B. Wood Doors: Comply with DHI A115-W series.

3.3 INSTALLATION

A. Mounting Heights: Mount door hardware units at heights indicated in following applicable publications, unless specifically indicated or required to comply with governing regulations: 1. Standard Steel Doors and Frames: DHI's "Recommended Locations for Architectural

Hardware for Standard Steel Doors and Frames."

Page 26: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 18

2. Wood Doors: DHI WDHS.3, "Recommended Locations for Architectural Hardware for Wood Flush Doors."

B. Install each door hardware item to comply with manufacturer's written instructions. Where cutting and fitting are required to install door hardware onto or into surfaces that are later to be painted or finished in another way, coordinate removal, storage, and reinstallation of surface protective trim units with finishing work specified in Division 09 Sections. Do not install surface-mounted items until finishes have been completed on substrates involved. 1. Set units level, plumb, and true to line and location. Adjust and reinforce attachment

substrates as necessary for proper installation and operation. 2. Drill and countersink units that are not factory prepared for anchorage fasteners. Space

fasteners and anchors according to industry standards.

C. Fire Rated Wood Door Hinges: Coordinate installation of hinges in wood doors to prevent the removal and reinstallation of screws into the edges. Install screws into fire rated door edge material providing proper torque on screws without over tightening, stripping. and weakening edge material. After fasteners have been screwed into fire rated door edge material, do not remove screws. If hinge needs to be removed from opening, remove from metal frame side only. Removal and reinstallation of screws weaken holding power of screw threads in fire rated door edge material. If screws are removed after initial installation, door leaf shall be replaced at no additional cost to the Owner.

D. Exit devices shall be carefully installed so as to permit friction free operation of touch bar and lever. Latching mechanism shall also operate freely without friction or binding.

E. At electrified hardwired locks, provide the low voltage plug-in wiring harnesses and terminations within the door from the hinge to the lock, and from the hinge to above the door frame to permit connection by access controls vendor.

F. Magnetic Hold Open Devices: After installation of door frames in rough stud opening, meet with contractor and electrical subcontractor to verify door swing and mounting location for all magnetic hold open devices to assure proper device selection, attachment and function of magnetic hold opens without the use of extension chains or rods.

G. Door closers shall be installed in accordance with the manufacturer's instructions. Each door closer shall be carefully installed, on each door, at the degree of opening dictated by the frame condition relative to adjacent construction and clearances to permit full swing of the door to the door stops. Arm position shall be as shown on the instruction sheets. Coordinate templating and bracket requirements for doors receiving overhead stops.

H. The adjustments for all door closers shall be the installer’s responsibility and these adjustments shall be made at the time of installation of the door closer. The closing speed and the latching speed valves shall be adjusted individually to provide a smooth, continuous closing action without slamming. The delayed action feature or back check valve shall also be adjusted so as to permit the correct delayed action cycle or hydraulic back check cushioning of the door in the opening cycle. All valves shall be properly adjusted at the time of installation. Each door closer has adjustable spring power capable of being adjusted, in the field, from size 1 thru 6. It shall be the installer’s responsibility to adjust the spring power for each door closer in exact accordance with the spring power adjustment chart illustrated in the door closer installation sheet packed with each door closer. Coordinate installation of hinges in wood doors to prevent requiring the removal and reinstallation of screws into the edges. Do not remove screws after

Page 27: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 19

they have been installed on fire rated doors. Provide proper torque on screws without over tightening and stripping.

I. Thresholds: Set thresholds for exterior doors in full bed of sealant complying with requirements specified in Division 07 Section "Joint Sealants." 1. Screw attach thresholds to substrate in a manner that will prevent displacement, free of

movement. Screws shall be countersunk flush with threshold surface.

J. Prior to Substantial Completion, the installer, accompanied by representative of the supplier of latchsets and locksets, closers, door control devices, and other major hardware, shall perform the following work: 1. Examine and re-adjust each item of door hardware as necessary to restore function of

doors and hardware to comply with specified requirements. Review the location of door closers and verify door closers are properly installed for the degree of swing required to permit maximum opening range of the door without binding or stress that could damage doors and frames. Verify arm position is at proper location.

2. Consult with and instruct Owner’s personnel in recommended maintenance procedures. 3. Replace hardware items that have deteriorated or failed due to faulty design, materials, or

installation of hardware units.

3.4 ADJUSTING

A. Initial Adjustment: Adjust and check each operating item of door hardware and each door to ensure proper operation or function of every unit. Replace units that cannot be adjusted to operate as intended. Adjust door control devices to compensate for final operation of heating and ventilating equipment and to comply with referenced accessibility requirements. 1. Door Closers: Adjust sweep period so that, from an open position of 70 degrees, the door

will take at least 3 seconds to move to a point 3 inches from the latch, measured to the leading edge of the door.

B. Six-Month Adjustment: Approximately six months after date of Substantial Completion, Installer shall perform the following: 1. Examine and readjust each item of door hardware as necessary to ensure function of

doors, door hardware, and electrified door hardware. 2. Consult with and instruct Owner's personnel on recommended maintenance procedures. 3. Replace door hardware items that have deteriorated or failed due to faulty design,

materials, or installation of door hardware units.

3.5 CLEANING AND PROTECTION

A. Clean adjacent surfaces soiled by door hardware installation.

B. Clean operating items as necessary to restore proper function and finish.

C. Provide final protection and maintain conditions that ensure door hardware is without damage or deterioration at time of Substantial Completion.

3.6 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain door hardware and door hardware finishes.

Page 28: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 20

3.7 DOOR HARDWARE SCHEDULE

A. Each Hardware Set listed below represents the complete hardware requirements for one opening (single door or pair of doors). Furnish the quantities required for each set for the work. 1. If a door is found in the door schedule that is not included in the hardware sets, provide

door hardware for similar condition and notify Architect. 2. Where “Note: Kerf smoke/seals/weatherstripping seals provided in Section 081113” or

similar verbiage is listed in the hardware sets, all doors listed for the hardware set shall have a kerfed hollow metal frame and gasketing complying with the requirements of Section 081113.

HW 1

Classroom WD x HM Doors: 413 Each Door Shall Have: Hinges, Lockset (Classroom Security Function), Floor Stop, Silencers, Cylinders

HW 2 AD Storage WD x HM Door: 310A Each Door Shall Have: Hinges, Latchset (Passge Function), Wall Stop, Silencers

HW 3 Gym HM x HM x Pair (Fire Rated) Door: 330 Each Opening Shall Have: Continuous Hinges, VR Exit Devices LBR w/ Locking Trim (No Dogging), Door Closers w/EDA Arm, Surface OH Stops 110° (GJ804S), Transition Threshold (1/4-inch high x 8 inches deep, equal to Pemko 2748A), Astragal Smoke Seals, Cylinders Kerf smoke seals provided in Section 081113.

HW 4 District Storage, Jan, Storage WD x HM (Smoke) Doors: 506A, 619B, 619F Each Leaf Shall Have: Hinges, Lockset (Storeroom Function), Door Closer w/EDA Arm, Kick Plate, Wall Stop, Silencers, Cylinder

HW 5 ELL, Teacher Work, Reception WD x HM (Smoke) Doors: 506B, 513. 922, 618E Each Door Shall Have: Hinges, Lockset (Classroom Security Function), Door Closer w/EDA Arm, Wall Stop, Silencers, Cylinders

Page 29: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 21

HW 6 Hall WD x HM (Smoke) Door: 507 Each Door Shall Have: Hinges, Latchset (Passage Function), Door Closer w/EDA Arm, Wall Stop Kerf sound seals provided in Section 081113.

HW 7 Safe Rm WD x HM x Single Door: 507A Each Door Shall Have: Continuous Hinge, Lockset (Schlage ND45 Time Out Function), Concealed Drop Seal (NGP 423N Smooth Aluminum Plate (Threshold) (1/4” x 3”), smooth surface, both top edges beveled, vertical portion of edge 1/8” high to butt flooring; Pemko 14/1A), Wall Stop, Silencers Kerf sound seals provided in Section 081113.

HW 8 Learning Center/FLS WD x HM Doors: 507B Each Door Shall Have: Hinges, Lockset (Classroom Security Function), Floor Stop, Silencers, Cylinders Kerf sound seals provided in Section 081113.

HW 9 Single Toilet - Safe Rm Hall, Weight/Cardio, Reception (Student/Public use) WD x HM Doors: 507C, 706. 707, 924 Each Door Shall Have: Hinges, Lockset (Institutional Privacy Function, Corridor key overrides thumb turn), Wall Stop, Silencers

HW 10 Classroom, Training, Conference WD x HM Doors: 508, 509, 514, 517, 709, 607, 608, 609, 610, 611, 612, 613, Each Door Shall Have: Hinges, Lockset (Classroom Security Function), Wall Stop, Silencers, Cylinders Note: See HW Alt. No. 4 regarding door hardware for doors 508, 509, 608, 609 under Alternate No. 4.

HW 11 Classroom (50 or greater occupancy) WD x HM Doors: 510, 510A, 512, 512A Each Door Shall Have: Hinges, Rim Exit Device w/Trim (Classroom Security Function), Door Closer w/EDA Arm, Kick Plate, Wall Stop, Silencers, Cylinders

Page 30: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 22

HW 12 Science Prep, Ice, Band Storage WD x HM Doors: 511A, 511B, 705, 418, 418A Each Door Shall Have: Hinges, Lockset (Classroom Function), Wall Stop, Silencers, Cylinders

HW 13 Staff Toilet - Corridor WD x HM (Smoke Partition) Doors: 514A Each Door Shall Have: Hinges, Lockset (Hotel Function with Occupied Indicator, Inside lever retracts latch and deadbolt, Emergency key override), Door Closer w/EDA Arm, Kick Plate, Silencers, Cylinder

HW 14 Cross Corridor HM x HM x Pair (Fire Rated) Door: 700 Each Opening Shall Have: Continuous Hinges, Vertical Rod Exit Device LBR w/ Trim (Passage Function – RHRB Leaf), Vertical Rod Exit Device LBR (no trim), Door Closers w/EDA Arm, Kick Plates, Electro Magnetic Holders (Wall Mount), Astragal Smoke Seals, Silencers Kerf smoke seals provided in Section 081113

HW 15 CL Storage WD x HM x Pair (Smoke) Door: 701 Each Opening Shall Have: Hinges, Lockset (Storeroom Function), Automatic Flush Bolt, Coordinator, Door Closers w/EDA Arm, Armor Plates, Silencers, Cylinder

HW 16 Exterior – Corridor Lobby HM x HM x Pair Doors: 702, 703A, Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging. Provide w/ Cylinder Entry on one leaf), Removable Mullion, Door Pulls, Door Closers w/EDA Arms, Concealed OH Stops (GJ102S-US32D), Kick Plates, Threshold, Door Bottoms, Sweeps, Mullion Weatherstripping, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

Page 31: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 23

HW 17 Weight/Cardio HM x HM x Pair (Fire Rated) Door: 703 Each Opening Shall Have: Continuous Hinges, Vertical Rod Exit Device LBR w/ Trim (Classroom Function), Vertical Rod Exit Device LBR (no trim), Door Closers w/EDA Arm, Kick Plates, Electro Magnetic Holders (Wall Mount), Astragal Smoke Seals, Cylinders Kerf smoke seals provided in Section 081113.

HW 18 Exterior - Weight/Cardio HM x HM x Pair Door: 703A Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging. Provide w/ Cylinder Entry on RHRB leaf), Electrified Removable Mullion, Electric Strike (RHRB leaf), Door Closers w/EDA Arms, Surface OH Stops (GJ81S), Door Pull (RHRB leaf), Kick Plates, Threshold, Door Bottoms, Sweeps, Mullion Weatherstripping, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold. Operations Narrative: Electric strike electronically locked at all times. Exiting by depressing exit devices at all times. Door leaf momentarily unlocked by card reader, and shunts door violation event. Note: Card reader, electric strike power supply, mag switches, request to exit and low voltage wiring by access controls vendor.

HW 19 JC WD x HM Door: 704 Each Leaf Shall Have: Hinges, Lockset (Storeroom Function), Silencers, Cylinder

HW 20 Storage WD x HM x Pair (Smoke) Door: 708 Each Opening Shall Have: Hinges, Lockset (Classroom Security Function), Automatic Flush Bolt Less Bottom Bolt w/Fire Pin, Coordinator, Door Closers w/EDA Arm, Kick Plates, Silencers, Cylinder

Page 32: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 24

HW 21 Exterior – Storage HM x HM x Pair Door: 708A Each Opening Shall Have: Continuous Hinges, Lockset (Storeroom Function – RHRB leaf), 12” Surface Bolts (equal to Ives SB360 to receive padlock), Door Closers Cush Stop CUSH w/HO EDA Arm, Latch Protector (equal to Don-Jo CLP-110-630), Kick Plate, Threshold, Door Bottoms, Sweeps, Astragal Weatherstripping, Cylinder Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 22 Exterior – Mech to Roof HM x HM Door: 720 Each Leaf Shall Have: Hinges, Latchset (Passage Function), Double Cylinder Deadbolt, Door Closer Cush Stop w/ EDA Arm, Threshold, Door Bottom, Sweep, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 23 Exterior Main Entry Alum x Alum x Pair Door: 921A Each Opening Shall Have: Rim Exit Devices (Cylinder Dogging w/ Cylinder Entry on one leaf), Electrified Removable Mullion, Electric Strikes, Door Pulls, Door Closers w/EDA Arm (180° swing), Kick Plates, Mullion Weatherstripping (equal to Pemko 5110, Zero 8780N), Cylinders Note: Continuous hinges, threshold, frame weatherstripping and sweeps specified in Section 084113 - Aluminum-Framed Entrances and Storefronts. Operations Narrative: Electric strike electronically unlocked in the morning for student arrival, locked during school hours, with emergency lockdown by office controls. Exiting by depressing exit device at all times. Note: Electric strike power supply, mag switches, request to exit and low voltage wiring by access control vendor.

Page 33: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 25

HW 24 Exterior Main Entry Alum x Alum x Pair Door: 921B Each Opening Shall Have: Rim Exit Devices (Cylinder Dogging w/Cylinder Entry on one leaf), Electrified Removable Mullion, Electric Strikes, Door Pulls, Door Operator with 2 Push Pads and Release Interface (LHRB leaf), Presence Sensor, Door Closer w/EDA Arm, Kick Plates, Mullion Weatherstripping (equal to Pemko 5110, Zero 8780N), Cylinders Note: Continuous hinges, threshold, frame weatherstripping and sweeps specified in Section 084113 -

Aluminum-Framed Entrances and Storefronts. Operations Narrative: Electric strike electronically unlocked in the morning, with emergency lockdown by office controls. Exiting by depressing exit device at all times. When exiting building requires powered door operator, interior automatic door operator push pad momentarily releases strike if locked and opens door to permit exit. Door leaf momentarily unlocked by card reader, and shunts door violation event. Exterior powered door operator push pad functions after card reader unlocks door. Door unlocked remotely permits exterior push pad use for powered door operator. Note: Card reader, electric strike power supply, mag switches, interface with door operator, request to exit and low voltage wiring by access control vendor.

HW 25 Main Entry Vestibule Alum x Alum x Pair Door: 921C Each Opening Shall Have: Continuous Hinges, Rim Exit Devices(Cylinder Dogging w/Cylinder Entry on one leaf), Electrified Removable Mullion, Electric Strikes, Door Pulls, Door Closers w/EDA Arm, Concealed OH Stop (GJ) at LHRB leaf only, Wall Stop Kick Plates, Cylinders Note: Continuous hinges and frame weatherstripping specified in Section 084113 - Aluminum-Framed Entrances and Storefronts. Operations Narrative: Electric strike electronically unlocked in the morning for student arrival. Locked during the day. Emergency lockdown by office controls. Exiting by depressing exit device at all times. Doors unlock with fire alarm. Note: Electric strike power supply, mag switches, request to exit and low voltage wiring by access controls vendor.

Page 34: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 26

HW 26 Main Entry Vestibule Alum x Alum x Pair Door: 921D Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging w/Cylinder Entry on one leaf), Electrified Removable Mullion, Electric Strikes, Door Pulls, Door Operator with 2 Push Pads and Card Interface (LHRB leaf), Presence Sensor, Door Closer w/EDA Arm, Concealed OH Stop (GJ) at RHRB leaf only, Wall Stop), Kick Plates, Cylinders Note: Continuous hinges and frame weatherstripping specified in Section 084113 - Aluminum-Framed Entrances and Storefronts. Operations Narrative: Electric strikes electronically unlocked in the morning for student arrival. Locked during the day. Door leaf momentarily unlocked by card reader, and shunts door violation event. Emergency lockdown by office controls. Exiting by depressing exit device at all times. When exiting building requires power door operator, interior door operator push pad momentarily releases strike if locked and opens door to permit exit. When entering, doors unlocked by card reader or remotely permits Vestibule push pad use for power door operator. Doors unlock with fire alarm. Note: Electric strike power supply, mag switches, request to exit and low voltage wiring by security vendor.

HW 27 Exterior –Stairs HM x HM x Pair (Egress Only) Doors: ST1A, ST6A Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging. Provide w/ Cylinder Entry on one leaf), Removable Mullion, 6” Pull (keyed leaf), Door Closers w/EDA Arms, Concealed OH Stops, Kick Plates, Threshold, Door Bottoms, Sweeps, Mullion Weatherstripping, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 27A Exterior –Stairs HM x HM x Pair Doors: ST2 Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging. Provide w/ Cylinder Entry on one leaf), Electrified Removable Mullion, Electric Strikes, Door Pulls, Door Closers w/EDA Arms, Concealed OH Stops, Kick Plates, Threshold, Door Bottoms, Sweeps, Mullion Weatherstripping, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold. Operations Narrative: Electric strike electronically unlocked by exterior keypad during school hours. Exiting by depressing exit device at all times. Exterior keypad disabled during non-school hours. Note: Key pad, electric strikes power supply, mag switches and low voltage wiring by access control vendor.

Page 35: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 27

HW 28 Stair HM x HM x Pair (Fire Rated) Doors: ST1B, ST6B, ST6C Each Opening Shall Have: Continuous Hinges, Vertical Rod Exit Device LBR w/ Trim (Passage Function), Vertical Rod Exit Device LBR (no trim), Door Closers w/EDA Arm, Kick Plates, Electro Magnetic Holders (Wall Mount), Astragal Smoke Seals Kerf smoke seals provided in Section 081113

HW 29

Exterior – Mech Mezz Stair HM x HM Doors: ST5, ST7 Each Leaf Shall Have: Continuous Hinge, Lockset (Storeroom Function), Door Closer Cush/Stop/HO w/ EDA Arm, Threshold, Door Bottom, Sweep, Cylinder Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 30 Exterior – Corridor HM x HM x Pair Door: 400A Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Cylinder Dogging. Provide w/ Cylinder Entry on one leaf), Removable Mullion, Door Pulls, Door Closers w/EDA Arms, Kick Plates, Threshold, Door Bottoms, Sweeps, Mullion Weatherstripping, Wall Stops, Cylinders Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 31 Band Room HM x HM x Pair Doors: 417 Each Opening Shall Have: Continuous Hinges, Rim Exit Devices (Classroom Security Function), Removable Mullion, Door Closers w/EDA Arm, Kick Plate, Perimeter Sound Seals (NGP 303NA), Concealed Drop Seals (NGP 423N), Astragal Sound Seals (Pemko 375), Mullion Weatherstripping (Applied to face of removable mullion in addition to astragal seals, Cylinders Kerf seals provided in Section 081113 (in addition to sound seals).

Page 36: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 28

HW 32

Exterior – Band HM x HM Doors:417A Each Leaf Shall Have: Continuous Hinge, Rim Exit device (Cylinder Dogging. Provide w/ Cylinder Entry), Door Closer w/ EDA Arm, Concealed OH Stop, Kick Plate, Threshold, Door Bottom, Sweep, Cylinder Kerf weatherstripping provided in Section 081113. Note: Coordinate door undercut for proper clearance and contact of door bottom fins and top of threshold.

HW 33 Stage Delivery HM x HM x Pair (Fire Rated) Door: 901 Each Opening Shall Have: Continuous Hinges, Lockset (Classroom Function), Automatic Flush Bolts, Projection Door Coordinator (Ives 469 1/2), Door Closers w/EDA Arm, Magnetic Hold Opens, Perimeter Sound Seals (NGP 303NDKB), Concealed Drop Seals (NGP 423N), Astragal Sound Seals (NGP 109NDKB, Mount on RH Leaf), Kick Plates, Cylinder Kerf smoke seals provided in Section 081113 (in addition to sound seals).

HW 34 Mech WD x HM (Smoke) Doors: 619A Each Door Shall Have: Hinges, Lockset (Storeroom Function), Door Closer w/EDA Arm, Wall Stop, Concealed Drop Seals (NGP 423N), Cylinder Kerf smoke seals provided in Section 081113.

HW 35

Cross Corridor – Double Egress HM x HM x Pair Fire Rated Door: 620A Each Opening Shall Have: Continuous Hinges, Vertical Rod Exit Devices LBR / No Trim, Door Closers w/EDA Arm, Kick Plates, Electro Magnetic Holders, Astragal Smoke Seals Kerf smoke seals provided in Section 081113.

Page 37: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 29

HW 36 Exterior - Flex EXG HM x EXG HM x Single Door: 415A Each Leaf Shall Have: Mortise Lock Exit Device w/ Cylinder Dogging (ANSI 06 Function. Operates only when key is in cylinder and turned. Lever retracts latchbolt), Cylinders Note: Remove existing mortise lockset. Prep door and frame with new cutouts and reinforcement required to receive new mortise exit device and strike. Fill in existing holes and cutouts left by removed lockset with welded metal plates flush with adjacent surfaces and finish imperfections smooth with bondo filler.

HW 37 Exterior – Maintenance, Receiving EXG HM x EXG HM HM x Single Door: 413B, 801 Each Leaf Shall Have: Electric Locking Mortise Lock (Fail Secure), Armored Door Chord w/Conductor Wires (From frame jamb to door stile). Adjust length so excess is not hanging in the opening with door open that would catch materials transported through door opening), Armor Plates, Cylinders Note: Remove existing mortise lockset. Drill wire path through core from lock pocket to armored door chord. Connect armored door chord to face of door and to wire mold junction box. Operations Narrative: Door lever released by card reader to permit entry. Exterior key override permits emergency entry. Note: Card reader, electric strike power supply, mag switches, request to exit and low voltage wiring by security vendor.

HW 38 Exterior – Locker Room Entry EXG HM x EXG HM HM x Single Door: 802 Each Leaf Shall Have: Surface Electric Strike - Fail Secure (Existing Rim Exit Device) Operations Narrative: Door lever released by card reader to permit entry. Existing exterior key override permits emergency entry. Note: Card reader, electric strike power supply, mag switches, request to exit and low voltage wiring by security vendor.

HW 39 Flex 415 - Existing Opening to Corridor EXG WD x EXG HM x Pair (Non-rated) Door Opening: 415 Each Opening Shall Have: Mortise Exit Device LBR w/ Trim (LHRB Leaf. Classroom Function), Automatic Flush Bolts (Top only), Door Coordinator, Door Closers w/EDA Arm, Kick Plates Note: Remove existing manual flush bolt and prep door for automatic flush bolt.

Page 38: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 30

HW 40 Operable Walls Pocket Doors Openings: Pocket Doors Classrooms 508/509, 608/609 Each Opening Shall Have: Cylinders Note: Deadlocks to receive cylinders specified in Section 102226 - Operable Partitions.

HW 41 Openings to receive new laminated glazing and security glazing as indicated on the Door Schedule Door Openings: 410A, 413B, 413F (See Alt. No. 2 for New Door and Hardware), 413G, 415A, 103B, 113. 230, 231A, 231B, 250A, 250B, 405B, 406B, 416E, 430A, 500B, 501B, 801, 802 Reglazing of doors specified in Section 088000 – Glazing.

HW 42 Temporary Cross Corridor Door HM x HM x Pair Fire Rated Door Opening: 430 (See Drawing A 01.3, Area2A for notes regarding temporary door location) Each Opening Shall Have: Continuous Hinges, Vertical Rod Exit Device LBR w/ Trim (LHRB Leaf. Passage Function), Automatic Flush Bolts (Top only with fire pin.), Projection Door Coordinator (Ives 469 1/2), Door Closers w/EDA Arm, Kick Plates, Electro Magnetic Holder Armature (LHRB Leaf.) Existing wall mounted mag to remain), Silencers Note: Remove existing double egress doors, and hardware from existing frame. Store doors and hardware and reinstall after completion of Phase 5. Turn temporary door hardware over to the Owner upon completion of Phase 5. Note: Provide new fire rated hollow metal frame and door leafs (4’0 leaf and 2’0 leaf) with existing wall anchors specified in Section 081113 - Hollow Metal Doors and Frames into new stud partition located tight to existing frame. Fire rating shall match rating of existing double egress opening.

HW 43 Gate Egress Hardware Door Opening: 999 Egress gate hardware for ornamental metal security fence specified in Section 323000 – Site Improvements.

Alternates

HW Alt. No. 2 Exterior – Steam Workshop HM x HM x Pair Door: 413F Each Opening Shall Have: Continuous Hinges, Lockset (Storeroom Function), Automatic Flush Bolts, Coordinator, Door Closers Cush Stop w/HO EDA Arm, Surface Overhead Stop/Holders, Door Closers Cush Stop w/HO EDA Arm, Surface Overhead Stop/Holder, Latch Protector (equal to Don-Jo CLP-110-630), Armor Plates, Threshold, Door Bottoms, Sweeps, Astragal Weatherstripping, Cylinders Kick Plates, Threshold, Door Bottoms, Sweeps, Astragal Weatherstripping, Cylinders Kerf weatherstripping provided in Section 081113.

Page 39: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 31

HW Alt. No. 4

Classroom WD x HM Doors: 508, 509, 608, 609 (delete hardware listed in HW 10 and provide the following) Each Door Shall Have: Hinges, Rim Exit Device (Classroom Security Function), Door Closer w/EDA Arm, Wall Stop, Silencers, Cylinders

HW Alt. No. 7 Music Practice Metal Sound Control Door Assemblies Doors: 416C.1, 416C.3 Each Door Shall Have: Latchset (Passage Function), Wall Stop, Cylinder Balance of hardware furnished with door assembly specified in Section 083473 - Metal Sound Control Door Assemblies

HW Alt. No. 9 Work Space WD x HM Door: 232A Each Door Shall Have: Hinges, Lockset (Classroom Security Function), Wall Stop, Silencers, Cylinders

HW Alt. No. 12 Laundry (Fire Rated) WD x HM Door: 301 Each Door Shall Have: Hinges, Lockset (Classroom Function), Door Closer w/EDA Arm, Wall Stop, Silencers, Cylinders

END OF SECTION 087100

Page 40: ADDENDUM - Blane Casey

YARMOUTH HIGH SCHOOL - ADDITIONS AND RENOVATIONS PROJECT NO. 19103 YARMOUTH, ME Addendum No. 2

DOOR HARDWARE 087100 - 32

This Page Left Intentionally Blank

Page 41: ADDENDUM - Blane Casey

N

YARMOUTH, MAINE

Graphic Scale

HA Project No.

Scale

Revision DescriptionRev Date

Harriman Associatesc

PA / PE: Drawn By:

Auburn

Boston

Portland

Portsmouth

OCTOBER 11, 2019

1"=30'

19103

2019

FLC PLS

SKA1

ADDITIONAL PAVEMENT

AND NEW LOCATION OF

FENCE AND SIDEWALK

YARMOUTH HIGH

SCHOOL

ADDITIONS AND

RENOVATIONS

AutoCAD SHX Text
24"oak
AutoCAD SHX Text
12"cherry
AutoCAD SHX Text
12"maple cluster
AutoCAD SHX Text
B
AutoCAD SHX Text
S
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
30"pine
AutoCAD SHX Text
5"twin
AutoCAD SHX Text
2"cluster
AutoCAD SHX Text
2"twin
AutoCAD SHX Text
12"maple
AutoCAD SHX Text
10"maple
AutoCAD SHX Text
culvert buried
AutoCAD SHX Text
FFE:146.28'
AutoCAD SHX Text
FFE:146.25'
AutoCAD SHX Text
FFE:143.31'
AutoCAD SHX Text
FFE:143.33'
AutoCAD SHX Text
FFE:143.32'
AutoCAD SHX Text
FFE:143.31'
AutoCAD SHX Text
FFE:143.28'
AutoCAD SHX Text
FFE:145.21'
AutoCAD SHX Text
NUE FOR NEW GATE LOCK
AutoCAD SHX Text
NEW 4' WIDE SECURE PEDESTRIAN GATE WITH PANIC HARDWARE
AutoCAD SHX Text
NEW 12' WIDE DOUBLE LEAF 7' TALL STEEL SECURITY GATE TO MATCH FENCE WITH LOCK
AutoCAD SHX Text
NEW BITUMINOUS PAVED WALK
AutoCAD SHX Text
NEW 7' TALL STEEL SECURITY FENCE AMERISTAR MONTAGE INDUSTRIAL "CLASSIC"
AutoCAD SHX Text
0
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
(1 inch = 30 feet)
AutoCAD SHX Text
15
AutoCAD SHX Text
30
AutoCAD SHX Text
60
Page 42: ADDENDUM - Blane Casey

YARMOUTH, MAINE

Graphic Scale

HA Project No.

Scale

Revision DescriptionRev Date

Harriman Associatesc

PA / PE: Drawn By:

Auburn

Boston

Portland

Portsmouth

OCTOBER 11, 2019

N.T.S.

19103

2019

FLC PLS

SKA2

REVISED PAVEMENT

DETAIL

YARMOUTH HIGH

SCHOOL

ADDITIONS AND

RENOVATIONS

AutoCAD SHX Text
%%UREVISED DETAIL A1 ON C50.1
AutoCAD SHX Text
COMPACTED SUBGRADE
AutoCAD SHX Text
14" GRAVEL SUBBASE
AutoCAD SHX Text
4" GRAVEL BASE
AutoCAD SHX Text
NEW TACK COAT AS SPECIFIED
AutoCAD SHX Text
BITUMINOUS PAVEMENT 1 1/4" SURFACE 2 3/4" BINDER
AutoCAD SHX Text
BITUMINOUS PAVEMENT 2"SURFACE
AutoCAD SHX Text
BITUMINOUS ROADS & PARKING
AutoCAD SHX Text
BITUMINOUS SIDEWALK
AutoCAD SHX Text
12" GRAVEL SUBBASE
AutoCAD SHX Text
4" GRAVEL BASE
AutoCAD SHX Text
ALTERNATE #14 GRAVEL ONLY
AutoCAD SHX Text
ALTERNATE #14 GRAVEL ONLY
Page 43: ADDENDUM - Blane Casey

N

YARMOUTH, MAINE

Graphic Scale

HA Project No.

Scale

Revision DescriptionRev Date

Harriman Associatesc

PA / PE: Drawn By:

Auburn

Boston

Portland

Portsmouth

OCTOBER 11, 2019

1"=30'

19103

2019

FLC PLS

SKA3

REVISED PORTION OF

C00.4

YARMOUTH HIGH

SCHOOL

ADDITIONS AND

RENOVATIONS

AutoCAD SHX Text
temporary benchmark: "X" on west side of concrete lamp base. elevation:143.47'
AutoCAD SHX Text
B
AutoCAD SHX Text
H
AutoCAD SHX Text
Y
AutoCAD SHX Text
D
AutoCAD SHX Text
H
AutoCAD SHX Text
Y
AutoCAD SHX Text
D
AutoCAD SHX Text
dugout
AutoCAD SHX Text
dugout
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
snow & ice
AutoCAD SHX Text
snow & ice
AutoCAD SHX Text
FFE:146.28'
AutoCAD SHX Text
FFE:146.25'
AutoCAD SHX Text
FFE:143.31'
AutoCAD SHX Text
YHS-3
AutoCAD SHX Text
TEMPORARY CHAIN LINK GATE AFTER JUNE 26, 2020
AutoCAD SHX Text
TEMPORARY CHAIN LINK GATE UNTIL JUNE 26, 2020
AutoCAD SHX Text
0
AutoCAD SHX Text
GRAPHIC SCALE
AutoCAD SHX Text
(1 inch = 30 feet)
AutoCAD SHX Text
15
AutoCAD SHX Text
30
AutoCAD SHX Text
60
Page 44: ADDENDUM - Blane Casey

A

B

11

W16X31 [6](+ 13'-3" )

W14

X30

[8]

(+ 1

3'-3

" )

W12

X16

[8]

(+ 1

3'-3

" )W

12X1

6 [8

](+

13'

-3" )

A.8

11.2 11.4

xA

x2

E C6X13 E 12B16.5

E 12

WF2

7

3'-6 1/8" 8'-2"

HSS6X4X1/4(+ 8'-6" )

HSS6X4X1/4(+ 8'-6" )

5" 5"

3"3'

-2"

5"

D1

D3S60.2

E5S60.1

SIM.

W12

X16

[8]

(+ 1

3'-3

" )W

12X1

6 [8

](+

13'

-3" )

W8X24LINTEL

BEAR ON EXISTINGCMU, TYP.

xB

D.8

11.6 11.8

HSS6x4x1/4(+ 8'-6")

HSS6X4X1/4(+ 8'-6")

8'-2"

5"

5"

BEAR ON EXISTINGCMU, TYP.

D1

D3S60.2

3'-5

"

0 4' 8' 12'

HA Project No.

Scale

Date

1/8" = 1'-0"

Harriman Associatesc

Auburn

Boston

Portland

Portsmouth

1/8" = 1'-0"

SKA4

CANOPY FRAMING PLANSAREA D

YARMOUTH, MAINE

19103

10-11-19

2019

YARMOUTH HIGHSCHOOL ADDITIONS AND

RENOVATIONS

SCALE: 1/8" = 1'-0"1 CANOPY FRAMING PLAN AREA DSCALE: 1/8" = 1'-0"2 CANOPY FRAMING PLAN AREA D

Page 45: ADDENDUM - Blane Casey

C

D

E

11

W18

X76

(+ 2

8'-0

" )

W14

X22

(+ 2

8'-0

" )

xB

x2 x3 x4

E 12

B14

E 12

B14

E 12

B14

E 12

B14

E 12

B14

E 12

B14

E 12

B14

E 12B22

D.8

W12

X14

W12

X14

W12

X14

V.I.F

.

23'-7

"+/-

V.I.F

.

6'-5

"+/-

A3S60.3

A4S60.3

1 3

B

CW14X22 (+ 13'-4" )

W21

X44

(+ 1

3'-4

" )

23'-2

3/4

"

L

L

0.5

B.8

B.5

A.8

3'-4

3/4

"8'

-2"

4'-1

1"

D1

5"5"

5" 1'-4"

HSS6X4X1/4(+ 8'-6" )

HSS6X4X1/4(+ 8'-6" )

D3S60.2

E5S60.1

TYP.

1 3

B

C

23'-2

3/4

"

W14X22(+ 27'-9 1/2" )

W21

X44

(+ 2

8'-0

" )

L

L

L

12K1

12K1

12K1

12K1

12K1B.8

B.5

A.8

4'-1

1"3'

-4 3

/4"

8'-2

"

D1D7S60.1

F7S60.1

L

0 4' 8' 12'

HA Project No.

Scale

Date

1/8" = 1'-0"

Harriman Associatesc

Auburn

Boston

Portland

Portsmouth

1/8" = 1'-0"

SKA5

PARTIAL ROOF FRAMINGPLANS AREA D

YARMOUTH, MAINE

19103

10-11-19

2019

YARMOUTH HIGHSCHOOL ADDITIONS AND

RENOVATIONS

SCALE: 1/8" = 1'-0"2 ROOF FRAMING PLAN AREA DSCALE: 1/8" = 1'-0"1 SECOND FLOOR FRAMING PLAN AREA D

SCALE: 1/8" = 1'-0"3 ROOF FRAMING PLAN AREA D

Page 46: ADDENDUM - Blane Casey

22 24

K

L

M

N

4" CONCRETE SLAB ON GROUNDWITH FIBER REINFORCING

T/SLAB ELEVATION 146.2' (+1'-0")

K.1

17'-0" 17'-0" 1'-1"

A3S50.1

F5A [-5'-0"] F5A [-5'-0"]

F7C [-3'-6"]

F5B [-3'-6"]

EXISTING BUILDING FOUNDATION

e12e11

23

F5A [-5'-0"]

F7C [-3'-6"]

F5B [-5'-0"]

e8 e10

eW.1

eU.4

eX

eW.3

( 1'-0" )

( 1'-8" )

( 0" )

( 0" )

P4 (2 5/8") P4 (2 5/8") P2A (4")

P2A (4")

P2A (4")

P4 (0")P4 (0")SS1

[ -5'-0" ]

[ -5'-0" ]1'

-4"

1'-4"

7'-5

3/4

"

8"

10'-0 3/8"

4'-4 1/4"8"4'-4 1/4" 8"

DOWEL NEWSLAB TO EXISTING

DRILL AND EPOXY NEWSLAB TO EXISTING

EXISTING FOOTING4'-6"x4'-6"x1'-0"[-4'-0"] +/-

EXISTING FOOTING4'-6"x4'-6"x1'-0"

[-4'-0"] +/-

EXISTING FOOTING4'-6"x4'-6"x1'-0"

[-4'-0"] +/-

2'-0

3/8

"

31'-5

3/4

"

S.K. S.K.

S.K.

S.K. S.K.

A6S50.2

8 3/8"

P6 (0")DRILL AND EPOXY PIER REINF. TO EXIST. FTG.

SS1

10'-8"

( 10 5/8" )

( 1'-8" )

( 10 5/8" )

( 1'-0" )

8 3/

8" ( 2 5/8" )

( 2 5/8" )

B4S50.2B3

S50.2

0 4' 8' 12'

HA Project No.

Scale

Date

1/8" = 1'-0"

Harriman Associatesc

Auburn

Boston

Portland

Portsmouth

1/8" = 1'-0"

SKA6

PARTIAL FOUNDATIONPLAN AREA A

YARMOUTH, MAINE

19103

10-11-19

2019

YARMOUTH HIGHSCHOOL ADDITIONS AND

RENOVATIONS

Page 47: ADDENDUM - Blane Casey

EXISTINGFOUNDATION

REINFORCED CMUW/ MATCHING DOWELSINTO FOUNDATION

+/-

1'-1" 8 5/8"

1'-5"

#4 AT 12" O.C. (TYP.)

#4 AT 12" O.C. HORIZ.

#4 L BARS AT 12" O.C.

(3) #5 CONT.

30db

30db

x44

EXIST. CMU

1'-6

"

MATCH BOTTOM OFEXISTING FOOTING

K.2 e51

HSS COLUMN(SEE PLAN)

EXISTING HSS COLUMN

EXISTING FTG.TO REMAIN

NEW FTG.(SEE PLAN)

8"

MATCH BOTTOMOF EXISTING FOOTING

IN F

IELD

VER

IFY

THIC

KNES

S

11

EXISTINGFOUNDATION WALL

EXISTING CONRETESLAB ON GROUND

CONCRETESLAB ON GROUND

(SEE PLAN)

DOWEL NEW SLAB TOEXISTING PER F1/S50.1

CUT DOWN EXISTINGFOUNDATION WALL AMINIMUM OF 12"

21

1'-1"1'

-0"

CONCRETESLAB ON GROUND(SEE PLAN)

1'-11 3/4"

1/2"

1 1/

2"

SEE TYPICAL SECTIONSFOR REINFORCING

1'-4"

SEE ARCH'L DETAILFOR ADDITIONAL INFORMATION

241'-1"

STRUCTURALENTRANCE SLAB

FINISH PAVERS

SEE TYPICAL SECTIONSFOR REINFORCING

4"

1'-0

"

1'-4"

CONCRETESLAB ON GROUND(SEE PLAN)

ANGLE SUPPORT.SEE A4/S50.1

R1'-0 1/2"

4"

4 1/2" 3 1/2"1/2" CONCRETE

SLAB ON GROUND(SEE PLAN)

STRUCTURALENTRANCE SLAB

FINISH PAVERS

SEE TYPICAL SECTIONSFOR REINFORCING

8"

1'-0

"

ANGLE SUPPORT.SEE A4/S50.1

R1'-0 1/2"

4" 8" 1/2"CONCRETESLAB ON GROUND(SEE PLAN)

STRUCTURALENTRANCE SLAB

4"8"

FINISH PAVERS

8"

SEE TYPICAL SECTIONSFOR REINFORCING

ANGLE SUPPORT.SEE A4/S50.1

12e68

EXISTINGFOUNDATIONS

AND FOOTINGS

EXISTING COLUMN

HSS COLUMN(SEE SCHEDULE)

CONCRETE SLABON GROUND(SEE PLAN)

CONCRETE PIER (BEYOND)(SEE PLAN)

FOOTING(SEE PLAN)

MATCH BOTTOM OFEXISTING FOOTING

4'-0"

K.1eW.3

REINFORCED CONCRETEPIER (SEE SCHEDULE)

REINFORCED CONCRETEFOOTING (SEE PLAN)

V.I.F.

MATCH EXISTING BOTTOM OF FOOTING(VERIFY ELEVATION IN FIELD)

EXISTINGFOOTING

EXISTINGFOUNDATION

WALL

L eX

EXISTING PIERBEYOND

EXISTING FOOTING

FIELD ADJUST REINFORCINGAT EXISTING FOOTING

STEP WALL FOOTING(SEE TYP. DETAIL)

CONCRETE PIER(SEE SCHEDULE)

MATCH EXISTING BOTTOM OF FOOTING(VERIFY ELEVATION IN FIELD)

Graphic Scale

AUBURN PORTLAND PORTSMOUTHBOSTON

Graphic Scale

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Key Plan

Harriman Project No.

PA / PE:

Drawn By: Harriman Associatesc

Proj North

Plo

t Dat

e:

Revision DescriptionRev Date

SEPTEMBER 24, 2019

10/1

0/20

19 1

:23:

37 P

M

YARMOUTH, MAINE

19103

S50.2

AMJ

MRM

FOUNDATION DETAILS

2019

YARMOUTH HIGH SCHOOLADDITIONS ANDRENOVATIONS

CONSTRUCTION DOCUMENTS

SCALE: 1/2" = 1'-0"A1 SECTIONSCALE: 1/2" = 1'-0"A2 SECTION

SCALE: 1/2" = 1'-0"A3 SECTIONSCALE: 3/4" = 1'-0"A5 SECTION

SCALE: 3/4" = 1'-0"A6 SECTIONSCALE: 3/4" = 1'-0"A7 SECTION

SCALE: 3/4" = 1'-0"B1 SECTIONSCALE: 1/2" = 1'-0"B2 SECTION

SCALE: 1/2" = 1'-0"B3 SECTIONSCALE: 1/2" = 1'-0"B4 SECTION

10-11-19 ADDENDUM #2

Page 48: ADDENDUM - Blane Casey

D

W BEAM(SEE PLAN)

JOIST (BEYOND)(SEE PLAN)

METAL ROOF DECK(SEE PLAN)

CONCRETE SLABON METAL DECK

(SEE PLAN)

2" TCX

E.O.S.

3 1/2" 1 1/2" E.O.D.

1'-0" 3"

(2) L4x3x1/4 SEAT

TYP.

CONT. (2) L4x3 1/2x1/4(LLV) WELDED

1" E.O.D.

K K.12 1/8" 10"

TCX

1'-0"

E.O.D.

10"

JOIST (SEE PLAN)

METAL ROOF DECK(SEE PLAN)

CONT. 3/8"x7"x1'-0"BENT PLATE (LLH)

SEE SECTION C4/S60.1FOR ADDITIONAL

INFORMATION NOTSHOWN HERE

TYP.

x2

EXISTINGW BEAM(SEE PLAN)

W BEAM(SEE PLAN)

EXISTING BULB-T's AT32" O.C. +/- W/ POURED

GYPSUM ROOF DECK

EXISTINGW BEAM

(SEE PLAN)

3/16TYP.

PROVIDE STEELSHIMS AS REQ'D FORTIGHT FIT TO EXISTINGBULB-T's

2" 1'-0"

+/- (V.I.F.)

W BEAM(SEE PLAN)

V.I.F

.

3/8" STIFFENER(EACH SIDE)

WT6x25 x 0'-8" CUT TO FIT.ANCHOR TO EXISTING BONDBEAM W/ (2) 5/8" DIA. x 4" EMBED.HILTI HIT HY200 ADHESIVEANCHORS

1/4

Graphic Scale

AUBURN PORTLAND PORTSMOUTHBOSTON

Graphic Scale

Graphic ScaleGraphic Scale

Graphic ScaleGraphic Scale

Key Plan

Harriman Project No.

PA / PE:

Drawn By: Harriman Associatesc

Proj North

Plo

t Dat

e:

Revision DescriptionRev Date

SEPTEMBER 24, 2019

10/1

0/20

19 1

:23:

51 P

M

YARMOUTH, MAINE

19103

S60.3

AMJ

MRM

FRAMING DETAILS

2019

YARMOUTH HIGH SCHOOLADDITIONS ANDRENOVATIONS

CONSTRUCTION DOCUMENTS

SCALE: 1 1/2" = 1'-0"A1 SECTIONSCALE: 3/4" = 1'-0"A2 SECTION

SCALE: 3/4" = 1'-0"A3 SECTIONSCALE: 1 1/2" = 1'-0"A4 SECTION

10-11-19 ADDENDUM #2