a mestek company - mesteksa.commesteksa.com/fileuploads/literature/sterling commercial...
TRANSCRIPT
LCS-6
A MESTEK COMPANY
COMMERCIAL HYDRONIC PRODUCTS®
Light Commercial Slope-TopEnclosures for Hydronic Heating
LCS-10
INTRODUCING THE LCS-10
FEATURES
GENERAL LAYOUT
Sterling Light Commercial Slope-Top EnclosuresThe Sterling LCS-10 offers an outstanding value in a lightcommercial hydronic heating enclosure. Capable of utilizingtwo tiers of element, the LCS-10 offers high output in alow profile slope-top enclosure. The 3 1/4 inch depth andslope top make this attractive enclosure a real space-saver.LCS-10 elements are available in both copper/aluminumand steel in a wide variety of sizes and outputs.
For ease of installation, the LCS-10 features a self locatingbracket with pre-punched mounting holes. The stampedpencil-proof louvers prevent trash accumulation on theelement while meeting the specifications of demandingengineers and architects. And, because the LCS-10 doesnot require a full backplate, it can be mounted off of thefinished floor.
All Sterling LCS-10 enclosures feature a durable baked pow-der finish and are available in Sterling’s full selection ofcolors. Constructed of 18-gauge cold rolled steel (16-gauge optional), this durable enclosure is ideal for dormi-tories, military housing, nursing homes, offices and recep-tion areas.
• Two tier capacity• Heavy 18-gauge enclosure (16-gauge optional)• Narrow 3 1/4 inch depth• Low 10 1/4 inch height• Stamped pencil-proof louvers• Broad choice of elements• Baked powder finish• Self-locating brackets
All Sterling commercial hydronic products are made fromrecycled materials. Material recycled contents can beobtained from your local Sterling representative or byviewing the www.sterlingheat.com website. Sterling is aparticipating member of USGBC-LEEDS.
I.P.S SIZE 1"1"
11⁄4"
CATALOGDESIGNATION
R11R12R13
FIN SIZEHEIGHT X WIDTH3 3/4 X 2 3/4
5 X 2 3/45 X 2 3/4
FIN/FT.
404040
FINTHICKNESS
0.0240.0240.024
MTG.HEIGHTIN INCHES
14 1⁄414 1⁄414 1⁄4
STEAM215°
FACTOR1.00910910930
0.86785785800
0.78710710725
0.69630630625
0.61555555570
0.53485485495
0.45410410420
HOT WATER (AVG.)200° 190° 180° 170° 160° 150°
FACTOR
STEEL ELEMENT
TUBE SIZE
3/4"1"
CATALOGDESIGNATION
R02R03
FIN SIZE HEIGHT X WIDTH2 1/2 X 2 3/42 1/2 X 2 3/4
FIN/FT.
5555
FINTHICKNESS
0.0110.011
MTG.HEIGHTIN INCHES
14 1⁄414 1⁄4
STEAM215°
FACTOR1.00
15601600
0.8613401375
0.7812151250
0.6910751105
0.61950975
0.53825845
0.45700720
HOT WATER (AVG.)200° 190° 180° 170° 160° 150°
FACTOR
COPPER ALUMINUM ELEMENT
TUBE SIZE
3/4"3/4"1"1"1"1"
11⁄4"11⁄4"11⁄4"
CATALOGDESIGNATION
R02R04R03R05R06R07R08R09R10
FIN SIZEHEIGHT X WIDTH2 1/2 X 2 3/43 3/4 X 2 3/42 1/2 X 2 3/43 3/4 X 2 3/4
5 X 2 3/45 X 2 3/4
3 3/4 X 2 3/45 X 2 3/45 X 2 3/4
FIN/FT.
605055504050504050
FINTHICKNESS
0.0100.0110.0110.0110.0200.0200.0200.0200.020
MTG.HEIGHTIN INCHES
14 1⁄414 1⁄414 1⁄414 1⁄414 1⁄414 1⁄414 1⁄414 1⁄414 1⁄4
STEAM215°
FACTOR1.00
114011701090113012001210115011501230
0.869801010935979
103010409909901060
0.78890915850880935945895895960
0.69785810755780830835795795850
0.61695715665690730740700700750
0.53605620575600630645610610655
0.45515530490510540545515515555
HOT WATER (AVG.)200° 190° 180° 170° 160° 150°
FACTOR
COPPER/ALUMINUM ELEMENT
RATING BTU/H WITH (2) TIER ELEMENT 31⁄2" CENTERED
The ratings of the charts above include factors shown in the chart below for the recommended mounting height. Two tier ratings are based on 31⁄2" between elements.Ratings are in BTU per hour per lineal foot of active length. “Active length” is the catalog ordering length less 4". The water ratings applicable to water flow rates of three ormore feet per second, have been determined by applying factors shown to the Steam Ratings. Elements unpainted. If the unit is to be installed at a height different than therecommended mounting height, the rating must be adjusted as follows:
RATING MULTIPLIED BY: FACTOR FROM TABLE B FOR THE ACTUAL MOUNTING HEIGHT FACTOR FROM TABLE B FOR THE RECOMMENDED MOUNTING HEIGHT
MOUNTING HEIGHT IN IN.FACTOR 3 1/4" OFFSET
18 or less1.100
191.100
201.098
211.091
221.085
231.078
241.071
251.065
261.058
271.051
281.045
291.038
301.031
321.019
341.012
361.006
38 or more1.000
Table B
CAT NO.R02R03R04R05R06R07R08R09R10R11R12R13
A MIN.5 15/16(150.8)6 1/6(154)6 9/16(166.7)6 9/16(166.7)
7 1/8(181)
6 11/16(169.9)
7 3/16(182.6)
6 11/16(169.9)
7 3/16(182.6)
A MAX.8 7/16(214.3)8 5/8
(219.1)8 15/16(227)9 1/8
(231.8)
8 11/16(220.7)
9 1/4(235)
8 11/16(220.7)
9 3/16(233.4)
8 11/16(220.7)
Dimensions are in inches. Dimensions in parentheses are in millimeters
RATINGS LCS-10
u
u
u
u
u
u
u
u
u Bold, italicized units are rated t
A MESTEK COMPANY
260 North Elm Street, Westfield, MA 01085Tel: (413) 564-5535 FAX: (413) 562-8437
www.sterlingheat.com
Furnish and install where shown on all plans/drawings, Sterling LCS-10 Finned Tube Enclosure and Element as describedor approved equal of both quality and BTU capacity. Ratings are to be AHRI approved.
The finned tube enclosure, as called out LCS-10, will be manufactured from 18-gauge (16-gauge optional) bonderized C.R.S.with a baked powder prime finish. The air discharge louvers are to be die formed stamped into the steel enclosure. The louver open-ings are to be “Pencil Proof”. All lateral bends are to be formed on bottoming dies to ensure continuity of all adjoining enclosures andaccessories. The enclosure lengths are to be provided in 6 inch increments from 2 feet through 8 feet long. The enclosure is to fullyengage in a continuous full length mounting strip mounted to the wall. A two (2) inch joiner strip is to be used where two pieces ofenclosure are adjoining each other in a run.
All accessories will be die formed 20-gauge cold rolled steel and finished with the baked prime finish described above. Theaccessories will overlap the installed enclosure and are to provide adjustment for make-up in the installed runs of enclosure.
The brackets are to be of a one piece, die formed construction. The material is to be 14-gauge C.R.S. with a baked primefinish. The bracket is to be self locating for vertical positioning at installation. The bottom horizontal leg is to snap into bottom bend ofthe enclosure and is to support the element when slide shoes are used. The top horizontal leg is to support the adjustable elementhanger. Adjustable rod hangers are to be supplied when specified. These will be used in conjunction with the various elements thatdo not incorporate a nylon slide. They will also be used when the installation requires pitch adjustment for steam applications.
The mounting strip is to be supplied in eight (8) foot lengths. It will be die formed heavy gauge, galvannealed material.All elements are to be of the mechanically expanded type to ensure that proper fin to tube bonding is maximized.
Copper/Aluminum elements are to be provided with one end mechanically swaged (flared) for proper assembly. Steel/Steel elementare to be provided with both ends threaded to accept all domestic NPT fittings or cut square and chamfered for field welding.
In the interest of product improvement, we reserve the right to make changes without notice.
SPECIFICATIONS FOR THE LCS-10
ACCESSORIES
6" (152 mm) End CapWith Access Door
14" (356 mm) Fill-In Section
Outside Corner 2" (51 mm)Splice Plate
3" (76 mm) End Cap
135° Outside Corner
6" (152 mm) End Cap 3" (76mm) or 6" (152 mm)Wall Sleeve
Inside Corner90° & 135°
8" (203 mm) Valve Compartment
COMMERCIAL HYDRONIC PRODUCTS®