5 sprinklers in healthcare - ij
TRANSCRIPT
-
8/14/2019 5 Sprinklers in Healthcare - IJ
1/45
1
Sprinklers in Healthcare23rd September 2009
Ian James G I Fire EHafod y Hendre
Builth Wells
-
8/14/2019 5 Sprinklers in Healthcare - IJ
2/45
2
Objectives
-
8/14/2019 5 Sprinklers in Healthcare - IJ
3/45
3
Objectives
Background
The Truths and the Myths
Legislative Position
Facts of Sprinkler Systems
Firecode Trade-Offs
Considerations & Benefits of Sprinklers in Healthcare
Cost Exercise
Conclusion
-
8/14/2019 5 Sprinklers in Healthcare - IJ
4/45
4
Background
-
8/14/2019 5 Sprinklers in Healthcare - IJ
5/45
5
BackgroundSprinklers have a proven track record for minimising fire lossesin buildings ( in 2007, 2 million sprinklers were installed in the
UK) however, they are seldom specified in hospitals
The reasons:
Expense
No requirement
Lack of understanding
Sprinkler Systems in Healthcare Premises Guidance Note(WHEN(09)04) published to enable informed decisions and
dispel the myths.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
6/45
6
The Truths and
the Myths
-
8/14/2019 5 Sprinklers in Healthcare - IJ
7/45
7
The Truths and the Myths
It is a myth that all sprinkler heads will operate
simultaneously throughout the building
BRE Automatic Fire Sprinkler Systems A good practice guide Corinne Williams
-
8/14/2019 5 Sprinklers in Healthcare - IJ
8/45
8
The Truths and the Myths
Losses from fires in buildings protected by sprinklers are
estimated to be 1/10th
of those in unprotected buildingsSource: European statistics over 10 year period
In buildings fully protected by sprinklers:
99% of fires were controlled by sprinklers alone
60% of fires were controlled by the spray from nomore than 4 sprinklers
Source: European statistics over 10 year period
There have been no recorded cases of Legionella beingcontracted from any fire protection system in the world.Source: BASA BIF No6 Nov 2005
-
8/14/2019 5 Sprinklers in Healthcare - IJ
9/45
9
The Truths and the Myths
Discharge due to manufacturers defects is 1 in 14,000,000(per year of service)Source: FM (USA) and Loss Prevention Council (UK) statistics
Accidental discharge of water from all causes is 1 in 500,000(per year of service).Source: FM (USA) and Loss Prevention Council (UK) statistics
-
8/14/2019 5 Sprinklers in Healthcare - IJ
10/45
10
Legislation
-
8/14/2019 5 Sprinklers in Healthcare - IJ
11/45
11
Legislative Position
There are no statutory requirements for sprinklers to beprovided in hospitals
Firecode does not require sprinklers, with the exception ofhigh rise buildings (in excess of 30m) and in certain commercial
enterprises contained within hospitals
Although the design team is expected to consider theadvantages that might be gained by installing life-safety
sprinklers throughout the buildingHTM05/02 Para 6.94
The RR(FS)O does not require the inclusion of sprinklers inhealthcare premises.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
12/45
12
Future Legislative Position?
National Assembly recognises the potential benefits thatsprinklers can have on life safety and property protection: -
Legislative Competence Order No 7 (LCO) aims to introduce arequirement that sprinkler systems be installed in new
residential / domestic premises
Wales Arson Reduction Strategy(2007)
reduce the cost to society of fires in public buildings, notingthat actions to increase the use of sprinklers in public buildings(which includes those of the NHS) should be explored withincentives introduced to encourage their use.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
13/45
13
Sprinkler Standards
Sprinklers in healthcare premises should be installed inaccordance with BS EN 12845 Fixed fire fighting systems -
Automatic sprinkler systems - Design, installation and maintenance
Alternatively, subject to the type of building being considered,
a BS 9251:2005 Sprinkler systems for residential and domesticoccupancies system may be specified i.e. for staff residences orresidential homes.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
14/45
14
Overview of
Sprinkler Systems
-
8/14/2019 5 Sprinklers in Healthcare - IJ
15/45
15
How do Sprinklers Extinguish/Control Fire?
Suppress and control the fire
Wet surrounding combustible materials
Wet surfaces to cool the building structure
Cool smoky gases
Reduce the likelihood of flashover
-
8/14/2019 5 Sprinklers in Healthcare - IJ
16/45
16
Facts of Sprinkler Operation
Sprinkler heads are heat activated valves
Generally operate at 30oc above the highest anticipated ambient
temperature, normally being 68oc
Operating temperatures are indicated by colour coding
Only the head(s) that reach their operating temperature will discharge water
Sprinklers do not false alarm - they only operate when heated (by fire)
Sprinklers respond quicker than the FRS therefore a smaller fire toextinguish and less water discharge
Glass bulb coding
-
8/14/2019 5 Sprinklers in Healthcare - IJ
17/45
17
Types of Sprinkler Systems
Wet
Permanently charged with water
Dry
System charged with compressed air, used where freezing water
may be encountered all the year round. When a sprinkler operates,the compressed air is released opening the control valve, allowingwater to flow into the pipework and through the open sprinkler
AlternateSystem charged with water in the summer and air in the winterwhen there is a danger of pipework freezing
-
8/14/2019 5 Sprinklers in Healthcare - IJ
18/45
18
Types of Sprinkler Systems
Pre-action
Based on dry system. Comprises of a standard sprinkler system
linked to an independent system of detectors installed in the sameareas as the sprinklers. When a detector activates the system opensthe control valves, allowing water to flow into the sprinklerpipework in readiness for the first sprinkler to operate upon heat
Deluge
Designed to bring a large number of open sprayers into actionsimultaneously in the event of a fire (high hazards areas such as plant
or aircraft hangars)Recycling
Similar to pre-action, with ability to stop/start flow in response to
fire conditions thereby minimising potential water damage.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
19/45
19
Hazard Classification
Sprinkler systems are designed for specific hazard classes.BS 12845 classes Hospitals as Ordinary Hazard Group 1
Hazard classification determines:
water volume and duration
pressure and flow requirements
maximum area of operation etc
Generally water capacity and discharge increases with the higherthe classification.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
20/45
20
Life Safety Systems
Firecode - where sprinklers are installed to satisfy the requirements ofFirecode or the Building Regulations, they should be regarded as a life-safety
systemHTM05/02 Para 6.98
Life-safety systems are defined in BS 12845 as sprinkler systems forming anintegral part of measures required for the protection of life
Life safety systems require additional features, including duplicate valve setsand pumps, increased zoning, fast response sprinkler heads (in certaincircumstances), and increased monitoring of valves in accordance with BS
12845 Annex FSprinkler systems are complex and should only be entrusted to 3rd partyaccredited organisations
-
8/14/2019 5 Sprinklers in Healthcare - IJ
21/45
21
Firecode
Requirements
-
8/14/2019 5 Sprinklers in Healthcare - IJ
22/45
22
Firecode Trade-Offs
HTM05/02 Para 6.109 states, Where sprinklers are installed, theguidance may be modified subject to a suitable and sufficient risk
assessment being undertaken and the information being recordedin the fire safety manual
Sprinklers can also be used to compensate for greater designfreedom and more open spatial planning, (generally addressed aspart of a more detailed fire engineered package of fireprecautions)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
23/45
23
Firecode Trade-Offs
Glazing in Sub-Compartment Walls No restriction on the size of un-insulated glazing in sub-
compartment walls where sprinklers are provided, i.e. no limiton the use of 30-minute (integrity only) glazing
Insulating glass is significantly more expensive, removing thelimitation also allows greater design flexibility
(HTM 05:02 5.295.31)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
24/45
24
Firecode Trade-Offs
Elements of Structure Where sprinklers are provided throughout the whole building
the periods of fire resistance to elements of structure can bereduced by 30-minutes
Limited cost benefit for concrete frame - more significant forsteel frame buildings
Restrictions on the use of materials of limited combustibility canalso be dispensed with if sprinklers are provided.
(HTM 05:02 6.26.4 and 6.11)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
25/45
25
Firecode Trade-Offs
Compartmentation In sprinkler protected buildings up to 12m above ground level
compartment walls can be reduced from 60-minutes to 30-
minutes FR Minor cost savings, e.g. a 60-minute fire door could be
reduced to 30-minute rating, compartment walls still requirefire smoke dampers (linked to the fire alarm system)
(HTM 05:02 6.56.11 & PHE 5.45.11)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
26/45
26
Firecode Trade-Offs
Fire Hazard Rooms and Areas Where sprinklers are installed, subject to risk assessment,
there is no need to enclose individual fire hazard rooms in 30-
minute fire-resistance construction Significant cost benefit, especially in facilities providing care for
mental health or elderly occupancies, as these bedroomswould traditionally require 30-minute protection.
(HTM 05:02 6.286.34)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
27/45
-
8/14/2019 5 Sprinklers in Healthcare - IJ
28/45
-
8/14/2019 5 Sprinklers in Healthcare - IJ
29/45
29
Firecode Trade-Offs
External Fire Spread
Space separation distances between buildings or facing
compartments can be halved if sprinklers are provided External envelope protection requirements for re-entrant
angle protection can be relaxed if sprinklers are provided
(HTM 05:02 6.636.76)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
30/45
30
Firecode Trade-Offs
Number and Location of Fire-Fighting Shafts
Potential reduction in the number / location of fire fightingshafts if sprinklers are provided.
(HTM 05:02 7.197.20)
-
8/14/2019 5 Sprinklers in Healthcare - IJ
31/45
31
Considerations
-
8/14/2019 5 Sprinklers in Healthcare - IJ
32/45
32
Responsibility & Maintenance
Systems are reliable - It is generally accepted that correctlyspecified and installed systems may not require any major
modification for 30 years
RR(FS)O Article 17 requires that the responsible personmaintains the general fire precautions for the protection of the
relevant personsBS12845 details maintenance/testing requirements(manufacturers recommendations should also be followed)
The RP must ensure that regular PPM is undertaken and robustprocedures are in place for reactive maintenance
Consideration should also be given to fire safety during system
shut down/isolation periods.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
33/45
33
Faults / Accidental & Malicious Damage
Statistically, the likelihood of a sprinkler head activating throughmanufacturing fault is 1 in 14,000,000 and spuriously from any
cause is 1 in 500,000
WHE research confirmed that there has been only one suchinstance, whereby a sprinkler head in close proximity to a faulty
heater outlet activatedThe risk of accidental damage can be further mitigated with theprovision of sprinkler head guards or concealed type sprinkler
heads, in areas where heads may be exposed to potential damageAll sprinkler systems have an alarm valve - any activation willcause the water flow alarm to operate, thus alerting the
occupants.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
34/45
34
Points of Ligature
It is possible that the body (yoke) of atraditional sprinkler head could be misused as a
point of ligature
Institutional sprinkler heads could be specified
Specifically designed for use inprisons and mental health facilities to
remove the risk ligature, whilst alsoreducing (not eliminating) thepotential for tampering
-
8/14/2019 5 Sprinklers in Healthcare - IJ
35/45
35
Future Flexibility
Hospitals are often considered to be dynamic environments
The change of use of individual rooms or ward occupancies is
unlikely to result in any significant complications with thesprinkler system
Alterations to internal partitions (i.e. removing or erecting new
partitions), will require liaison with the sprinklerinstallation/maintenance contractor to ensure that thealterations do not negate the effectiveness of the installation
Where modification of a sprinkler installation becomesnecessary, robust procedures will also be required to ensureadequate fire safety during periods of isolation.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
36/45
36
Cost Exercise
-
8/14/2019 5 Sprinklers in Healthcare - IJ
37/45
37
Cost Exercise
Ysbyty Aneurin Bevan(YAB) 107 single-bed, two storey hospital being built in Ebbw Vale
Ward A comprising 32 single-bedrooms (with en-suites) used for
the study
Four options were assessed in the cost evaluation: -
Option 1 Ward A without sprinklers (assuming Elderly Occupancy)Option 2 Ward A without sprinklers (assuming Medical/Surgical Occupancy)
Option 3 Ward A with sprinklers (including ceiling void suppression)
Option 4 Ward A with sprinklers (without ceiling void suppression)
All options were based on a fully code-compliant HTM05/02design, except Option 4 which addressed a derogation omittingceiling void suppression.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
38/45
38
Extent of Ward A
Cost Exercise
Ward A Ysbyty Aneurin BevanWard A (typical first floor plan)
32 single bed/en-suite rooms
-
8/14/2019 5 Sprinklers in Healthcare - IJ
39/45
C E i
-
8/14/2019 5 Sprinklers in Healthcare - IJ
40/45
40
Cost Exercise
Comparison of CostsOption Cost of fire
precautions *
Cost difference
compared with Option 4
1 without sprinklers (assumingElderly Occupancy) 80,429
28,227
more expensive than Option 4
2 without sprinklers (assumingMedical/Surgical Occupancy)
1,617 50,585
less expensive than Option 4
3 with sprinklers (including
ceiling void suppression)
64,681 12,479
more expensive than Option 4
4 with sprinklers (withoutceiling void suppression)
52,202 0
* The cost of fire precautions relates solely to the features that can be varied throughthe recognised trade-offs for hazard room enclosures if sprinklers are provided
Excludes costs for the fire precautions that are common to all four options, eg theescape lighting, AFD, signage or extinguishers, these features are required regardless ofthe provision of sprinklers or not.
C t E i
-
8/14/2019 5 Sprinklers in Healthcare - IJ
41/45
41
Cost Exercise
Option 1 - Without sprinklers (assuming Elderly Occupancy)32 x 30minute fire walls/doors
32 x Glazing 2.5m2 @ 650/m2
71 x Dampers to Mech Vent.
Area ofglazing
Approx2.5m2
Extract Supply
Damper
C t E i
-
8/14/2019 5 Sprinklers in Healthcare - IJ
42/45
42
Cost Exercise
Summary
Sprinklers are not necessarily more expensive to install
Exercise only focussed on hazard rooms, proves YAB wouldhave cost over 100,000 more WITHOUT sprinklers
Sprinklers at YAB equate to approx 30/m2
Further research required to address: -
Full costing appraisal addressing all recognised trade-offs
Life cycle costing Cost impact following a fire.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
43/45
43
Conclusion
-
8/14/2019 5 Sprinklers in Healthcare - IJ
44/45
44
Conclusion
It is extremely important that decisions concerning firesafety in healthcare premises should be well informed so an
objective overview of the key issues should be consideredwhen evaluating the merits of sprinkler systems for particularprojects
WHEN(09)04 calls out for Trusts and their appointed designteams to fully consider all of the implications and potential
benefits offered by sprinkler systems in the design ofhealthcare premises through a thorough option appraisalprocess.
-
8/14/2019 5 Sprinklers in Healthcare - IJ
45/45
45
Summary
Background
The Truths and the Myths
Legislative Position
Facts of Sprinkler Systems
Firecode Trade-Offs
Considerations & Benefits of Sprinklers in Healthcare
Cost Exercise
Conclusion