sprinklers reliable

7
 Model F1 Model F1 Recessed Standard Respon se Sprinklers The Designer  ® Model F1 Sprinkler Standard Upright Standard Pendent Extended Coverage Pendent Conventional Vertical Sidewall Horizontal Sidewall – HSW1 Deflector The Designer  ® II Model F1 Recessed Sprinkler Recessed Pendent Recessed Extended Coverage Pendent Approval Organizations 1. Underwriters Laboratories Inc. 2. Underwriters’ Laboratories of Canada 3. Factory Mutual Research Corp. 4. Loss Prevention Council 5. NYC BS&A No. 587-75-SA 6. Pleniere Assemblee 7. Verband der Schadenversicherer 8. NYC MEA 258-93-E UL Listing Category Sprinklers, Automatic & Open (VNIV) Patents: U.S. Patent No. 6,374,92 Applies to Model F1 Vertical Sidewall Sprinklers. Product Description The F1 Glass Bulb Sprinkler combines the durability of a standa rd sprinkler with the attractiv e low profil e of a decorative sprinkler. Whether installed on exposed piping or in an office ceiling, it is functi onal and attracti ve. The Horizontal and Vertical Si dewall Sprink lers provide an equall y attra ctive appearance when ceiling piping cannot be used. Beautifully versatile is the description for the Reliable Model F1 Recessed Des igner glass bulb sprinkler. Reces sing The Design er ® enhances its already low profile decorative appearance, and facilitates a rapid and perfect installation. Model F1 Recessed Designer’s escutcheon is highly adj ust abl e. The two piece constr uct ion makes field inst al lation a very easy and rapid task. This also allows cei ling pane ls to lat er be removed wit hout shutti ng down the fi re protecti on syst em, thus facil it at ing maintenance of above ceiling services. The Des igne r ® Aut omatic Spr ink ler uti liz es a fra ngi ble glass bulb. The glass bulb consists of an accurately contr olled amount of specia l fluid hermetically sealed inside of a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fas t thermal response. The Reliable Automatic Sprinkler Co.,  Inc.,  103 Fairview Park Drive,  Elmsford, New York, 10523 At normal temperatures, the glass bulb contains the fluid in both the liquid phase and in the vapor phase. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands forcing the bubble smaller and smaller as the liquid pressure increases. Continued heating for ces the liquid to pu sh out against the bulb, causing the glass to sha tter, opening the waterway and allowing the deflector to distribute the discharging water. The F1 Sprinkler temperature rating is identified by the color of the glass bulb capsule as well as frame color where applicable. Upright  Pendent Horizontal Sidewall Conventional Reces sed Pend ent Exte nded Cove rage Pendent Rece ssed Exte nded Cove rage Pend ent Bulletin 117  Rev.T Vert ical Sid ewal l B  u l     l      e  t    i     n 1  1  7  R  e v . T  

Upload: dragos-nitescu

Post on 06-Oct-2015

238 views

Category:

Documents


0 download

DESCRIPTION

tipe and dimensions

TRANSCRIPT

  • Model F1Model F1 RecessedStandard ResponseSprinklers

    The Designer Model F1 SprinklerStandard UprightStandard PendentExtended Coverage PendentConventionalVertical SidewallHorizontal Sidewall HSW1 Deflector

    The DesignerII Model F1 Recessed SprinklerRecessed PendentRecessed Extended Coverage Pendent

    Approval Organizations1. Underwriters Laboratories Inc.2. Underwriters Laboratories of Canada3. Factory Mutual Research Corp.4. Loss Prevention Council5. NYC BS&A No. 587-75-SA6. Pleniere Assemblee7. Verband der Schadenversicherer8. NYC MEA 258-93-E

    UL Listing CategorySprinklers, Automatic & Open (VNIV)

    Patents: U.S. Patent No. 6,374,92Applies to Model F1 Vertical Sidewall Sprinklers.

    Product DescriptionThe F1 Glass Bulb Sprinkler combines the durability

    of a standard sprinkler with the attractive low profile ofa decorative sprinkler. Whether installed on exposedpiping or in an office ceiling, it is functional andattractive. The Horizontal and Vertical SidewallSprinklers provide an equally attractive appearancewhen ceiling piping cannot be used.

    Beautifully versatile is the description for the ReliableModel F1 Recessed Designer glass bulb sprinkler.Recessing The Designer enhances its already lowprofile decorative appearance, and facilitates a rapidand perfect installation.

    Model F1 Recessed Designers escutcheon is highlyadjustable. The two piece construction makes fieldinstallation a very easy and rapid task. This also allowsceiling panels to later be removed without shuttingdown the fire protection system, thus facilitatingmaintenance of above ceiling services.

    The Designer Automatic Sprinkler utilizes a frangibleglass bulb. The glass bulb consists of an accuratelycontrolled amount of special fluid hermetically sealedinside of a precisely manufactured glass capsule. Thisglass bulb is specially constructed to provide fastthermal response.

    The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York, 10523

    At normal temperatures, the glass bulb contains thefluid in both the liquid phase and in the vapor phase.The vapor phase can be seen as a small bubble. Asheat is applied, the liquid expands forcing the bubblesmaller and smaller as the liquid pressure increases.Continued heating forces the liquid to push out againstthe bulb, causing the glass to shatter, opening thewaterway and allowing the deflector to distribute thedischarging water.

    The F1 Sprinkler temperature rating is identified bythe color of the glass bulb capsule as well as framecolor where applicable.

    Upright Pendent

    Horizontal Sidewall

    Conventional

    Recessed Pendent

    Extended CoveragePendent

    Recessed ExtendedCoverage Pendent

    Bulletin 117 Rev.T

    Vertical Sidewall

    Bulle

    tin117

    Re

    v.T

  • Model F1 Upright, Pendent & Conventional SprinklersInstallation Wrench: Model D Sprinkler Wrench

    Upright Pendent Conventional

    2.

    NominalOrifice Thread Size

    Nominal K Factor SprinklerHeight

    ApprovalOrganization

    Sprinkler Identification Numbers(SIN)

    US Metric Upright PendentStandard-Upright (SSU) and pendent Deflectors Marked to Indicate Position

    "(15mm)

    " NPT(R1/2)

    5.6 802.2"

    (56mm)1,2,3,4,5,6,7 R1725(4) R1715

    17/32"(20mm)

    " NPT(R3/4)(1)

    8.0 1152.3"

    (58mm)1,2,3,4,7,8 R1722(4) R1712

    "(15mm)(3)

    " NPT(R1/2)

    5.6 802.2"

    (56mm)7

    17/32"(20mm)(3)

    " NPT(R3/4)

    8.0 1152.3"

    (58mm)7

    7/16"(11mm)

    " NPT(R1/2)

    4.2 602.2"

    (56mm)1,2,8 R1723(4) R1713

    3/8"(10mm)

    " NPT(R1/2)(2)

    2.8 402.54"

    (65mm)1,2,8 R1721(4) R1711

    10mm XLH R3/8 4.2 60 56.1mm 4,6,7 R1724 R1714

    Conventional-Install in Upright or Pendent Position

    10mm XLH R3/8 4.2 60 56.1mm ---------- R1774

    15mm" NPT(R1/2)

    5.6 80 56.1mm 4,6,7 R1775

    20mm" NPT(R3/4)

    8.0 115 58.1mm 4,7 R1772

    Installation Data:

    (1) LPC Approval up to 286F (141C)(2) FM Approval for SSU up to and including 200F (93C) only.(3) (F1S5) VdS Approval for Intermediate Response 155F (68C) only.(4) Polycoated upright UL and ULC listed corrosion resistant.

  • Model F1 Recessed Pendent SprinklerInstallation Wrench: Model GFR1 Sprinkler Wrench

    Recessed Pendent

    (1) When installed directly into a tee, the escutcheon dimension's

    adjustment will be reduced.

    NominalOrifice Thread Size

    Nominal K FactorSprinkler Height ApprovalOrganization

    Sprinkler IdentificationNumbers (SIN)US Metric

    "(15mm)

    " NPT(R1/2)

    5.6 802.2"

    (56mm)1,2,3,4,5,7 R1715

    17/32"(20mm)

    " NPT(R3/4)

    8.0 1152.3"

    (58mm)1,2,3,4,8 R1712

    "(15mm)(4)

    " NPT(R1/2)

    5.6 802.2"

    (56mm)7

    17/32"(20mm)(4)

    " NPT(R3/4)

    8.0 1152.3"

    (58mm)7

    7/16"(11mm)

    " NPT(R1/2)

    4.2 602.2"

    (56mm)1,2,8 R1713

    3/8"(10mm)

    " NPT(R1/2)

    2.8 402.2"

    (56mm)1,2,8 R1711

    10mm R3/8 4.2 60 56.1mm 4,7 R1714

    Installation Data:

    (2) FM Approval

    Light Hazard - No Limitations

    Ordinary Hazard - Groups 1 & 2, Wet Systems only.

    (3) LPC Approval is for 57C through 93C ratings.(4) VdS Approval for Intermediate Response 155F (68C) only.

    3.

  • 4.

    Model F1 Vertical Sidewall SprinklerInstallation Wrench: Model D Sprinkler WrenchInstallation Position: Upright or PendentApproval Type: Light Hazard Occupancy

    Model F1 Horizontal Sidewall SprinklerDeflector: HSW 1Installation Wrench: Model D Sprinkler Wrench

    Horizontal Sidewall

    Nominal Orifice Thread SizeNominal K Factor Sprinkler

    HeightApproval

    OrganizationsSprinkler

    IdentificationNumbers (SIN)US Metric

    " (15mm) " NPT (R1/2) 5.6 8.0 2.2" (56.1mm) 1,2,3,4,6,8 R1785

    Installation Data:

    Sprinkler Type Deflector to Ceiling Distance(Min. - Max.)Upright 4" (102mm) - 12" (305mm)

    Pendent 4" (102mm) - 12" (305mm)

    U.S. Patent No. 6,374,920

    (1) LPC Approval is pendent only, 57C through 141C ratings.

    Vertical Sidewall

    NominalOrifice Thread Size

    Nominal K FactorSprinkler

    HeightApproval Organizations Sprinkler

    IdentificationNumbers (SIN)US Metric Light Hazard OrdinaryHazard

    " (15mm)" NPT(R1/2)

    5.6 80 2.63" (67mm) 1,2,3,5 1,2,5 R1735

    Installation Data:

    Note: UL and ULC Listing permits use with F1 escutcheons, light hazard only.

  • 5.

    (1) When installed directly into a tee, the escutcheondimension's adjustment will be reduced.

    Extended Coverage Pendent

    Extended CoverageRecessed

    Model F1 Extended Coverage Pendent SprinklerDeflector: EC PendentInstallation Wrench: Model D Sprinkler WrenchApproval Type: Extended Coverage - Light Hazard Occupancy

    Model F1 Recessed Extended Coverage Pendent SprinklerDeflector: EC PendentInstallation Wrench: Model GFR1 Sprinkler WrenchApproval Type: Extended Coverage - Light Hazard Occupancy

    NominalOrifice

    ThreadSize

    Nominal K Factor SprinklerHeight

    ApprovalOrganizations

    Temperature Rating SprinklerIdentification

    Numbers (SIN)US Metric F C17/32"

    (20mm)" NPT(R3/4)

    8.0 115 2.2" (56mm) 1,2,8 135, 155 57, 68 R1742

    " (15mm)" NPT(R1/2)

    5.6 80 2.2" (56mm) 1,2,8 135, 155 57, 68 R1745

    Installation Data:

    Coverage Area

    Flow RatePressure

    Max. AreaWidth x LengthNominal

    K=8.0 (115) K=5.6 (80)gpm L/min psi bar psi bar ft. x ft. m x m

    263340

    98.4125.0151.4

    10.617.025,0

    0,71,21,7

    21.634.751.0

    1,52,43,5

    16 x 1618 x 1820 x 20

    4.9 x 4.95.5 x 5.56.0 x 6.0

    NominalOrifice

    ThreadSize

    Nominal K Factor SprinklerHeight

    ApprovalOrganizations

    Temperature Rating SprinklerIdentification

    Numbers (SIN)US Metric F C17/32"

    (20mm)" NPT(R3/4)

    8.0 115 2.2" (56mm) 1,2,8 135, 155 57, 68 R1742

    " (15mm)" NPT(R1/2)

    5.6 80 2.2" (56mm) 1,2,8 135, 155 57, 68 R1745

    Installation Data:

    Coverage Area

    Flow RatePressure

    Max. AreaWidth x LengthNominal

    K=8.0 (115) K=5.6 (80)gpm L/min psi bar psi bar ft. x ft. m x m

    263340

    98.4125.0151.4

    10.617.025,0

    0,71,21,7

    21.634.751.0

    1,52,43,5

    16 x 1618 x 1820 x 20

    4.9 x 4.95.5 x 5.56.0 x 6.0

  • Model F1 & F1 Recessed SprinklersApplication

    Model F1 and F1 Recessed sprinklers are used infixed fire protection systems: Wet, Dry, Deluge orPreaction. Care must exercised that the orifice size,temperature rating, deflector style and sprinkler typeare in accordance with the latest published standardsof the National Fire Protection Association or theapproving Authority Having Jurisdiction.

    InstallationModel F1 sprinklers are standard response sprinklers

    intended for installation as specified in NFPA 13. Theymust also be installed with the Model D SprinklerWrench specifically designed by Reliable for use withthese sprinklers.

    The Model F1 Recessed Sprinklers are to be installedwith a maximum recess of inch (19mm). The Model

    F1 Escutcheon illustrated is the only recessedescutcheon to be used with the Model F1 Pendent andEC Sprinklers. The use of any other recessedescutcheon will void all approvals and negate allwarranties. When installing Model F1 RecessedPendent and EC Pendent Sprinklers, use the ModelGFR1 Sprinkler Wrench. Any other type of wrench maydamage these sprinklers.

    Glass bulb sprinklers have orange covers to protectthe bulb during the installation process. REMOVE THISPROTECTION ONLY AFTER THE SYSTEM HAS BEENHYDROSTATICALLY TESTED AND, WHEN APPLICABLE,THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCOwrenches are designed to install sprinklers whencovers are in place.

    MaintenanceThe Models F1 and F1 Recessed Sprinklers should

    be inspected quarterly and the sprinkler systemmaintained in accordance with NFPA 25. Do not cleansprinklers with soap and water, ammonia or any othercleaning fluid. Remove any sprinkler which has beenpainted (other than factory applied) or damaged in anyway. A stock of spare sprinklers should be maintainedto allow quick replacement of damaged or operatedsprinklers. Prior to installation, sprinklers should bemaintained in the original cartons and packaging untilused to minimize the potential for damage to sprinklersthat would cause improper operation or non-operation.

    Ordering InformationSpecify:1. Sprinkler Model2. Sprinkler Type3. Orifice Size4. Deflector Type5. Temperature Rating6. Sprinkler Finish7. Escutcheon Finish (where applicable)

    ClassificationSprinkler

    TemperatureMaximumAmbient

    Temperature BulbColorF C F C

    OrdinaryOrdinaryIntermediateIntermediateHigh(1)

    Extra High(1)

    135155175200286360

    57687993141182

    100100150150225300

    38386666107149

    OrangeRed

    YellowGreenBlue

    Mauve

    Temperature Ratings

    (1) Not Available for F1 Recessed

    Patents: U.S. Patent No. 6,374,920Applies to Model F1 Vertical Sidewall Sprinklers.

    Standard FinishesSprinkler Escutcheon

    BronzeChromeWhite Polyester Coated(3)(6)

    BrassChromeWhite Painted

    Special Application FinishesSprinkler Escutcheon

    Bright Brass(2)

    Black PlatedBlack Paint(3)(4)

    Off White(3)

    Satin ChromeLead Plated(3)(4)

    Wax Coated(3)(4)(5)

    Wax Over Lead(3)(4)

    Bright BrassBlack PlatedBlack PaintOff WhiteSatin Chrome

    Finishes

    (1) Other colors and finishes are available on special order. Consultfactory for details.(2) 200F (93C) maximum.(3) UL and ULC listed, and NYC approved only.(4) 155F to 200F (68C to 93C) ratings only.(5) 286F (141C) sprinklers may be coated for ambient conditions notexceeding 150F (66C).(6) UL and ULC listed corrosion resistant SIN numbers: R1721, R1722,R1723 and R1725.

    Note: For " orifice pendent FM approved whitepolyester coated and UL approved white polyestercorrosion resistant sprinklers refer to Bulletin 013.

    The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances wheneverapplicable.Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the mosthighly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

    (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 829-2042 Corporate Officeswww.reliablesprinkler.com Internet Address

    Manufactured by

    E.G. Printed in U.S.A. 11/08 P/N 9999970011

    Revision lines indicate updated or new data