4900 series air separators — standard & high velocity series air separators — standard &...

28
4900 Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components with the Taco 4900 Series air and dirt removal separators. The 4900 Series scrubber system is designed and constructed to ASME code, with technology proven in the field, around the world. Built with the quality and dependability that’s made Taco famous for its performance and reliability. 4900 Series’ internal PALL Ring basket assemblies have been developed with safety and ease of maintenance in mind. Air Elimination & Control Available with and without removable cover Patent# 5, 123, 938 ©Taco Catalog #400-1.4 Supersedes: 08/25/15 Effective Date: 01/20/17 Printed in USA

Upload: ngohanh

Post on 05-May-2018

228 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

4900 Series Air Separators— Standard & High Velocity

Save money and lengthen the life of system pumps, piping, and components with the Taco 4900 Series air and dirt removal separators. The 4900 Series scrubber system is designed and constructed to ASME code, with technology proven in the field, around the world. Built with the quality and dependability that’s made Taco famous for its performance and reliability. 4900 Series’ internal PALL Ring basket assemblies have been developed with safety and ease of maintenance in mind.

Air Elimination & Control

Available with and without removable coverPatent# 5, 123, 938

©Taco Catalog #400-1.4 Supersedes: 08/25/15

Effective Date: 01/20/17Printed in USA

Page 2: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Eliminate bubbles and dirt in thesystem before they cause trouble.Air and dirt trapped in the system can produce majorproblems such as reduced heat transfer, loss of effi-ciency, pipe corrosion, pump damage, increased energy consumption, and irritating noise. The highly efficient Taco 4900 Series separator, now with optional remov-able covers, clears the system of microbubbles, sand, dirt, and rust to save money, energy, and component wear. 4900 Series’ stainless steel PALL Ring baskets can be removed by one person. Unlike many competitive models each 4900 unit is designed and constructed to the requirements of Section VIII of the ASME code as standard.

European PALL Ring technology. Taco ingenuity.The 4900 Series’ integral PALL ring technology has been proven in countless European installations. PALL rings are used in the processing industry to mix gases with, or sepa-rate gases from liquids. The use of PALL rings in hydronic air separation is so unique, it’s patented. By applying PALL ring technology to air and dirt separation, the 4900 Series will:

• Remove microbubbles as small as 18 X 10-6m (18 microns) from the system

• Remove air which has dissolved in the system’s water

• Remove air from places where an air vent cannot be installed

• Remove and separate solid particles from the flow

• 2 PSI or less pressure drop at optimal flow rate*

High efficiency cleaning of air and dirt.PALL ring technology has been used for many years in the processing industry. Taco’s application of PALL rings to hydronic air and dirt separation is new to the HVAC industry. While air bubbles are separated by the PALL rings through a process known as coalescence, dirt particles are actually caught and sifted to the bot-tom of the tank, where they can be removed through a blowdown valve. The 4900 Series provides higher ef-ficiency, with reduced pressure drops, so a somewhat smaller pump may be used for maximum efficiency.

Superior air bubble removal

When water is brought into contact with a PALL RING, the stream is deflected in many directions. Microbubbles attach to the ring surface, by coalescence growing large enough to be separated. Large numbers of PALL rings in the 4900 Series yields virtually air-free system water.

Removable Cover andStainless Steel PallRing Basket Assembly

Features & Benefits -2-

Series 4900-A models clean the system of free air and microbubbles; Series 4900-AD models remove both air AND dirt from the hydronic system. 304 stainless steel screens are provided on the inlet/outlet of each separator to isolate the separator’s internals from the hydronic system. A flushing cock allows for the cleaning of the PALL rings. A full port ball valve is provided at the bottom of the unit to permit blowdown of accumulated particles. While construction of both models differs somewhat, the PALL ring operating principle is the same.

* See pages 13 & 14 for optimal flow rates.

Page 3: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Prepared for:

E4187.05 Summary

Summary: Efficiency of particle separation

I. Pothof

Report

January 2004

Taco Inc., Cranston RI

Taco air and dirt separator 4903AD-4

delft hydraulics

Prepared for:

E4187.06 Summary

Summary: Efficiency of air separation

I. Pothof

Report

January 2006

Taco Inc., Cranston RI

Taco air and dirt separator 4903AD-4

delft hydraulics

Delft Hydraulics has tested and certified the 4900 Series’ superior performance for dirt and micro bubble removal. Choose from the 4900-A Series for air removal only, or the 4900-AD Series for air and dirt removal from any hydronic heating or chilled water system. Delft Hydraulics’ 2004 and 2006 test reports for particle separation efficiency (shown below) provide information on the test procedures followed, show test results for particle separation, and offer conclusions and practical implications.

Delft HydraulicsEfficiency Reports

Features & Benefits-3-

The choice is yours.

Page 4: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Air Control and EliminationWater contains a certain amount of entrained air. If this air comes out of solution, it can increase corrosion rates of metals within the system. In addition, air can form pockets at the top of pipes and heating units. These airpockets can actually restrict or block flow in a hydronic piping system. This is referred to as “air locking”.

The table below shows a solubility curve for air in water. Note that at a fixed pressure, increasing the temperature reduces the amount of air that can be dissolved. For example, at 60 PSIA and 40°F, the water can contain just over 10% air by volume. At 60 PSIA and 200°F, the percentage decreases to just over 4%.

Conversely, at fixed temperature reducing the pressure reduces the amount of air that can be dissolved. For example at 100°F and 80 PSIA the water can contain 8% air by volume. At 100°F and 20 PSIA the percentage decreases to 2%.

The highest temperature in a system is typically on the discharge of boilers and inlet of chillers. Therefore, the general rule of thumb in hydronic systems is that “Air separators should be located downstream of boilers (Figure 2) and upstream of chillers (Figure 3).”

The lowest pressure in a system is typically at the expansion tank, since this is the point of no pressure change and the location of the fill valve. Therefore, the general rule of thumb in hydronic systems is that “Air separators should be located at the expansion tank connection to the system.”

908070605040302010

18%

16%

14%

12%

10%

8%

6%

4%

2%

32 50 75 100

TEMPERATURE (DEGREE F)

SOLUBILITY OF AIRIN WATER AT STANDARD

TEMPERATURE AND PRESSURE

125 150 175 200 212

PSIA

Solubility Curve

Figure 1

The conclusion is that air is least soluble in water at the highest temperature and lowest pressure. Air separators should therefore be located at these points.

FAN COIL

TACO

CIRCULATOR

TACO

TWIN TEE®

TACO 4900 SERIES

AIR SEPARATOR

BOILER

TACO

EXPANSION

TANK

TACO

MULTI-PURPOSE

VALVE

TACO PUMP

TACO

SUCTION

DIFFUSER

Boiler & Air Separator Location

Figure 2

NAME: FIGURE 8

LOCATION:

FAN COIL

TACO

CIRCULATOR

TACO

TWIN TEE®

TACO

AIR SEPARATOR

CHILLER

TACO

EXPANSION

TANK

TACO

MULTI-PURPOSE

VALVE

TACO PUMP

TACO

SUCTION

DIFFUSER

Chiller and Air Separator Location

Figure 3

Applications -4-

Page 5: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

In addition, as water is heated from the fill tempera-ture to the operating temperature, a great deal of air is released. Therefore, the simple act of bringing the water to operating temperature could lead to corrosion and air pockets, both of which should be avoided.

A method of removing this released air from the pip-ing system is therefore required. Enter the air separa-tor. An air separator is a device that removes the air from the circulating fluid.

There are several types of air separators in use today. Depending upon the type of expansion tank used in the system, the air separator is part of an Air Control System or an Air Elimination System.

Air Control SystemsIf a conventional (non-bladder) style expansion tank is used, it is desirable to redirect the separated air to the space above the water level in the expansion tank (Figure 4). The dotted line from the air separa-tor (scoop) to the plain steel tank shows the proper connection, with the air piped from the scoop to the expansion tank through a special tank fitting.

This fitting directs the air to the top portion of the tank, and discourages air from migrating back into the system (Figure 5), when the system cools on the “off ” cycle. Note that since the air is “recycled” to pro-vide a cushion in the expansion tank, this system is called an “Air Control” system.

Note that the circulator is on the supply side of the boiler. This is the proper location, as it results in the highest pressure at the top of the system ( if the circulator was on the return side of the boiler, the boiler pressure drop reduces the pressure at the top.) Having a higher pressure at the top keeps air in solution, and helps prevent problems and air binding.

TACO PLAIN STEEL

EXPANSION TANK

TACO

CIRCULATOR

TACO

AIR SCOOP

BOILER

TACO

TANK FITTING

FILL VALVE

RELIEF

VALVE

BACK FLOW PREVENTER

*COLD WATER FILL

FLO-CHEK

18”

Air Control System

Figure 4

TANK

TANK FITTING

AIR

WATER

BAFFLE TRAPS

AIR AND DIRECTS

IT TO THE TOP OF

TANK THRU

OUTER TUBE

Tank Fitting

Figure 5

Applications-5-

Page 6: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Air Elimination SystemsIf a Captive Air or Bladder Style expansion tank is used, there is no reason to “save” the separated air (Figure 6). Therefore, if an air separator (scoop) is used in an air elimination system rather than an air control system, the separator is fitted with an automatic air vent (Taco’s Hy-Vent® series), which discharges the separated air to the atmosphere. Note that since the air is eliminated through an air vent this systemis called an “Air Elimination” system.

Optimum performance is achieved at line velocities up to 4 ft/sec. However, air scoops have been suc-cessfully installed on applications with velocities up to 8 ft/sec. Air scoops are specifically designed for the line size which they are to be installed. These sizes range from 1 inch to 4 inch.

Most manufacturers rate their air scoop product lines for 125 psi with a maximum operating tem-perature of 300˚F. Air scoops are installed in con-junction with an expansion tank and air vent as shown in figure 7. (See Taco Catalog# 100-7.2 for additional information.)

NAME: FIGURE #1

LOCATION:

TACO

FLO-CHEK

TACO HY-VENT®

TACO AIR SCOOP®

BOILER

TACO

CIRCULATOR

TACO PRESSURE

REDUCING VALVE

TACO

DIAPHRAM TYPE

EXPANSION TANK

COLD WATER

SUPPLY

Figure 7

DIAPHRAM TYPEEXPANSION TANK

TACOCIRCULATOR

TACO AIR SCOOP

VENT

BOILER

TACO

RELIEFVALVE

FLO-CHEK18”

Figure 6

Types of Air SeparatorsAir Scoop®

Taco Air scoops are applied in residential and light commercial applications for the removal of free air in water or water/glycol systems. The body of each air scoop provides an increased cross sectional area which lowers velocity within the piping network thereby allowing free air to rise due to buoyant force. To assist with the removal of smaller air bub-bles integral baffles are incorporated within most air scoops.

Applications• Smaller systems• Lower cost• Compact installation

Applications -6-

Page 7: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

NAME: FIGURE #1

LOCATION:

TACO

FLO-CHEK

TACO HY-VENT®

TACO VORTECH®

BOILER

TACO

CIRCULATOR

TACO PRESSURE

REDUCING VALVE

TACO

DIAPHRAM TYPE

EXPANSION TANK

COLD WATER

SUPPLY

Figure 8

Applications• Smaller systems• Higher efficiencies• Compact installation

In-Line ASME Air SeparatorsTaco In-Line Air Separators are applied in commercial, institutional and industrial applications for the removal of free air in water or water/glycol systems. The In-Line designed air separator utilizes the advantages resulting from large body diameter in rela-tion to the entering nozzle diameter.

The design of in-line air separators depends upon the lowering of the system fluid velocity within the separator, the change in direction of fluid flow within the unit, and buoyant force to direct air to the automatic air vent normally positioned at the top of the separator.

These air separators are designed, built and stamped to the requirements of ASME. The rated working pressure of these units is dependent upon the design pressure of the hydronic system into which they are being installed.Manufacturers offer these units in working pressures of 125, 150, 175, 250, 300 psi and higher if required.

VorTech®Taco VorTech® Air Separators are applied in residential and light commercial applica-tions for the removal of free air in water or water/glycol systems. The body of a VorTech features a primary separa-tion chamber where the process of air elimination is controlled and optimized.

The body of each VorTech is specially designed to direct the flow of the system fluid tangentially exiting at the bottom of the chamber. To assist with the removal of larger air pockets each VorTech incorporates a 300 series stainless bubble breaker cartridge to breakup larger air volumes.

Due to the tangential effect the system fluid with its higher density is pushed to the outside wall of the chamber as the less dense air is directed toward the vor-tex of the flow and vented from the system.

Optimum performance is achieved at line velocities up to 4 ft/sec. However, VorTech style units have been suc-cessfully installed on applications with velocities up to 8 ft/sec. VorTech separators are specifically designed for the line size which they are to be installed. These sizes range from 3/4 inch to 2 inch.

VorTech style separators are rated for 150 psi with a maximum operating temperature of 240°F. VorTech are commonly installed in conjunction with an expansion tank and air vent as shown in Figure 8.(See Taco Catalog #100-2.9 for additional information.)

Applications-7-

Page 8: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

NAME: FIGURE #3

LOCATION:

STRAINER REMOVAL

COLD WATER

SUPPLY

TACO CAPTIVE AIR

EXPANSION TANK

TACO PRESSURE

REDUCING VALVE

TACO

AIR SEPERATORPRESSURE

GAUGETACO PUMP

TACO

SUCTION

DIFFUSER

TACO

MULTI-PURPOSE

VALVE

TACO HY-VENT®

Figure 10

Applications• Larger systems• Lower pressure drop• Removal of larger particles

Optional stainless steel strainers are specified to capture and allow the removal of larger debris. These screens are normally specified with 3/16 inch perforations and free area of not less than 5 times the open area of the nozzle to minimize pressure drop. Most manufacturersprovide a blowdown connection at the bottomof the unit.

When In-Line Air Separators are installed in conven-tional Air Control systems with plain steel expansion tanks (Figure 9) care must be taken to insure that piping between the air separator and the plain steel expan-sion tank is pitched at least 3 degrees to facilitate the migration of captured air back into the expansion vessel. Systems with plain steel expansion tanks must not have automatic vents installed as this will lead to the loss of the expansion tank compression cushion.

NAME: FIGURE #3

LOCATION:

STRAINER REMOVAL

COLD WATER

SUPPLY

TACO PLAIN STEEL

EXPANSION TANK

TACO PRESSURE

REDUCING VALVE

TACO

AIR SEPERATOR

SLOPE PIPE

UP TO TANK

PRESSURE

GAUGE

TACO PUMP

TACO

SUCTION

DIFFUSER

TACO

MULTI-PURPOSE

VALVE

Figure 9

Tangential ASME Air SeparatorsTaco Tangential Air Separators are applied in commercial, insti-tutional and industrial applica-tions for the removal of free air in water or water/glycol systems. The Tangential design air separators utilize the difference in density to separate free air from system fluid.

System fluid within a tangential air separator is forced to the wall of the separator due to centrifugal force. The less dense air then migrates to the center of the separator for venting at the top of the unit. Tangential air separators produce higher pressure drops than in-line or micro-bubble sepa-rators due to the vortex development within the unit.These units are designed, built and stamped to the requirements of ASME. Manufacturers offer tangential separators in working pressures of 125, 150, 175, 250, 300 psi and higher if required.

Optional stainless steel strainers are specified to capture and allow the removal of large debris. These screens are normally specified with 3/16 inch perforations and free area of not less than 5 times the open area of the nozzle

Air Separator withPlain Steel Expansion Tank

Air Separator with Captive Air Tank

When In-Line Air Separators are installed in Air Elimination systems (Figure 10) with Captive Air bladder or diaphragm style expansion tanks, automatic air vents should be installed at the top of each separator. As Air Elimination systems have a permanent separation provided by the bladder or diaphragm between the initial tank pre-charge and the system fluid, no loss of pre-charge air will occur. (See Taco Catalog# 400-1.1 for additional information.)

Applications -8-

Page 9: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

4900 Series High Efficiency Micro-BubbleAir and Dirt ASME SeparatorTaco 4900 Series High Efficiency Micro-Bubble Air and Dirt Separators are applied in commercial, institutional and industrial applications for the removal of free and entrained air. The 4900 Series uti-lize the coalescence of micro air bubbles around PALL rings to separate free air from a system fluid.

The 4900 Series incorporates the highest available coalescence surface area availableon the market today. This enhanced surface area allows the removal of micro-bubbles as small as 18 microns in diameter. The 4900 Series separators remove up to 100% of the free air, 100% of the entrained air, and up to 99.6% of the dissolved air in the system fluid. This feature is especially beneficial in correcting problems in air entrained systems. An additional feature of the 4900 Series is the capability to remove dirt from hydronic systems. 4900 Series dirt separators are capable of removing dirt particles as

to minimize pressure drop. Most manufacturers provide a blowdown connection at the bottom of the unit.

When Tangential Air Separators are installed in conven-tional Air Control systems with plain steel expansion tanks (Figure 9) care must be taken to insure that piping between the air vent and the plain steel tank is pitched at least 3 degrees to facilitate the migration of captured air back into the expansion vessel. Systems with plain steel expansion tanks must not have automatic air vents installed as this will lead to the loss of the expansion tank compression cushion.

When Tangential Air Separators are installed in Air Elimination systems (Figure 10) with Captive Air bladderor diaphragm style expansion tanks, automatic air vents should be installed at the top of each air separator. AsAir Elimination systems have a permanent separation provided by the bladder or diaphragm between the initial tank pre-charge and the system fluid, no loss of pre-charge will occur. (See Taco Catalog# 400-2.8 for additional information.)

Applications• Larger systems• Removal of larger particles

small as 5 microns in diameter. This feature is especial-ly beneficial in cleaning up dirty systems with clogged strainers, balance and control valves.

The 4900 Series has been designed in two veloc-ity ranges, a standard product series suitable for line velocity to 4.9 ft/sec. and a high velocity series suitable for line velocities up 11 ft/sec. The performance of the 4900 product line has been independently tested and published. (These test results are available through your local Taco representative.)

These units are designed, built and stamped to the requirements ASME Section VIII, Division 1. Manufacturers offer micro bubble air and dirt separators in working pressures of 125, 150, 175, 250, 300 psi.

When High Efficiency Micro Bubble Air and Dirt Separators are installed in conventional Air Control systems with plain steel expansion tanks (Figure 9) care must be taken to insure that piping between the air vent and the plain steel tank is pitched at least 3 degrees to facilitate the migration of captured air back to the expansion vessel. Systems with plain steel expansion tanks must not have automatic vents installed as this will lead to the loss of the expansion tank compression cushion.

When High Efficiency Micro Bubble Air and Dirt Separators are installed in Air Elimination systems (Figure 10) with Captive Air bladder or diaphragm style expansion tanks, automatic air vents are built into the top of each air separator. As Air Elimination systems have permanent separation provided by the bladder or diaphragm between the initial tank pre-charge and the system fluid, no loss of pre-charge air will occur.

Applications• Larger systems• Higher efficiencies• Higher velocities• Removal of smaller air bubbles e.g. removal of air in air entrained systems (removes micro air bubbles)• Removal of smaller particles e.g. cleaning of dirty systems (removes particles and dirt)

Applications-9-

Page 10: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Selection Examples

Example 1

Problem:

Select an air separator for a new installation. For maximum performance of the hydronic system the project requires removal of micro air bubbles from the system. The system will have better than average maintenance.

Conditions:

Flow rate = 700 gpmPipe size = 6”Velocity = 8 fpsMaximum pressure drop - 3 ft.

1. Determine the type of air separator required. For removal of micro air bubbles this would require a Taco 4900 Series Air Separator with a model number 4906AH (See #2 below)

For systems requiring dirt removal select the standard non-removable top head cover design with a blown down valve located at the bottom of the unit. Add letter designation “D” to indicate dirt removal. (e.g. 4906ADH).

2. Determine the velocity range of the 4900 Series that is suitable for these conditions. The velocity range for the standard unit is 4.9 fps. The velocity range for the high velocity unit is 11 fps. Therefore, select the high velocity model number ending with an “H”.

3. Determine the size of the 4900 for the specified maximum pressure drop. For a maximum pressure drop of 3 ft. the unit size required is a 6” (2.7 ft.). This is Model 4906ADH.

Non-Removable Head Cover

New Selection Proceedure -10-

FAN COIL

TACO

CIRCULATOR

TACO

TWIN TEE®

TACO 4900 SERIES

AIR SEPARATOR

BOILER

TACO

EXPANSION

TANK

TACO

MULTI-PURPOSE

VALVE

TACO PUMP

TACO

SUCTION

DIFFUSER

Boiler & Air Separator Location

Page 11: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Selection Examples

Example 2

Problem:

Select an air separator for an existing installation with air entrainment and dirt problems. The system has less than average maintenance or open systems.

Conditions:

Flow rate = 150 gpmPipe size = 4”Velocity = 4 fpsMaximum pressure drop - 3 ft.

1. Determine the type of air separator required. For removal of micro air bubbles and dirt this would require a Taco 4900 Series Air and Dirt Separator with a model number ending with an “AD”.

For a system with less than average maintenance or open systems select the removable top head cover for easier cleaning. This is a model number ending with an “R”.

2. Determine the velocity range of the 4900 Series that is suitable for these conditions. The velocity range for the standard unit is up to 4.9 fps. The velocity range for the high velocity unit is 11 fps. If the velocity is under 4.9 fps select the standard velocity unit. If the application velocity is above 4.9 fps and below 11 fps a high velocity unit would be required. This would require the addition of the letter “H” at the end of the model number.

No additional letter designation is required for low velocity selections.

3. Determine the size of the 4900 for the specified maximum pressure drop. For a maximum pressure drop of 3 ft. the unit size required is a 4” (1.6 ft.). This is Model 4904ADR

Removable Top Head CoverTaco recommends the use of a removable top head cover option on all open systems.

Existing Selection Proceedure-11-

Page 12: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Furnish and install air and dirt removal device of the size and type shown on the plans. Air and dirt sepa-ration devices shall be Taco 4900 series or approved equal. Listing of a manufacturers name does not allow their construction standards to deviate from the requirements of this specification.

Air and dirt removal device shall be constructed of steel. It shall be designed, fabricated and stamped per ASME Section VIII Division 1 with a maximum working pressure of 125psi, 150, 175, 250, 300 optional at 240˚F. Units up to three 3-inch in size shall be provided with thread-ed connections as standard. Units 4-inch and larger shall be provided with flanged system connections as standard. Pressure drops not to exceed 2 psi.

Each air and dirt removal device shall be equipped with a brass conical shaped air venting chamber designed to minimize system fluid from fouling the venting assembly. A brass flushing cock shall be located on the side of each separator to facilitate system fast-fill and removal of the floating impurities from the air system interface within the separator. A blow down valve shall be provided by the unit manu-facturer on the bottom of each unit to allow blow down and cleaning. On units 2-1/2” and smaller the valve and all of its fittings shall be 1”. On units three 3” and larger the valve and all openings shall be 2”.

The air and dirt removal device shall remove air down to 18 microns and shall remove dirt particles as small as 5 microns in diameter. The unit shall be 100% efficient at removing dirt down to 90 microns in 100 passes or less. The unit manufacturer shall provide the owner and design engineer third party independent test data cer-tifying that their unit performs to the above standards. Suppliers not providing these independent perfor-mance test results will not be acceptable.

TACO 4900 SERIES

AIR SEPARATOR

BOILER

TACO

EXPANSION

TANK

TACO PUMP

Dirt Removal Efficiency of Separator

Part

icle

Siz

e 10

-6m

(m

icro

ns)

1.64 2.46 3.28 4.10 4.920.50 0.75 1.00 1.25 1.50

Typical installation

The air and dirt separator shall employ the use of high surface area pall rings to achieve optimal separation of air and dirt with minimal pressure drop. The pall rings shall be made of stainless steel. Stainless steel will be the only acceptable material used for suppressing tur-bulence and increasing surface area for high efficiency air and dirt removal. Inferior materials of construction such as copper for the straining medium will not be acceptable. The minimum allowable surface area of the straining medium shall be ____ sq ft for the ______model and _______sq ft for the _______model.

(OPTIONAL) The unit shall be manufactured with a removable upper head to facilitate removal, inspection, and cleaning of the pall ring basket.

Typical Specifications -12-

Page 13: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

401-

074

US

-STD

EFF

EC

TIV

E: M

AY

12,

201

4

21⁄2" (

49025)

2" (4902)

3" (4903)

4" (4904)

5" (4905)

6" (4906) 8" (4908)

10" (4910)

12" (4912) 14" (4914)

16" (4916)

2

3

4

8

6

10

15

20

30

40

5060

80100

150

200

300

400

500600

800

1000

1500

2000

3000

4000

.01

.015.0

2

.03

.04

.05

.07.1.15.2.3.4.7 .51.0

1.5

2.0

(PSI

)(ft

)

(GPM)

.25.51234

MO

DEL

GPM

@4.

9Pe

r./Se

c.

4902

4902

5

4903

4904

4905

4906

4916

4914

4912

4910

4908

51 73 113

204

306

469

816

4918

4920

4922

4924

4926

7,64

7

4930

4936

3,67

3

4,56

1

5,30

0

6,34

6

10,2

62

14,9

05

1,29

1

1,83

7

2,10

6

2,79

0

Stan

dard

Vel

ocity

490

0 Se

ries

Pre

ssur

e D

rops

Standard Velocity Pressure Drops-13-

Cons

ult

Fact

ory

for

Mod

els

4918

thr

ough

493

6

Page 14: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-14-High Velocity Pressure Drops

21⁄2" (

49025H)

2" (4902H)

3" (4903H)

4" (4904H) 5" (4905H) 6" (4906H)

8" (4908H) 10" (4910H) 12" (4912H) 14" (4914H) 16" (4916H)

.01

.015.0

2

.03

.04

.05

.07.1.15.2.3.4.7 .51.0

1.5

2.0

(PSI

)(ft

)

.25.51234

2

3

4

8

6

10

15

20

30

405060

80100

150

200

300

400500600

8001000

1500

2000

3000

4000

(GPM)

6000

10000

MO

DEL

4902

H

4902

5H

4903

H

4904

H

4905

H

4906

H

4916

H

4914

H

4912

H

4910

H

4908

H

115

165

253

438

686

1,01

5

1,73

0

2,71

8

4,12

4

4,72

7

6,26

2

4918

H

4920

H

4936

H

4930

H

4926

H

4924

H

4922

H

8,24

6

10,2

38

11,8

74

14,2

45

17,1

67

23,0

37

33,4

57

401-

074

US

-HIG

H

EFF

EC

TIV

E: M

AY

12,

201

4

GPM

@11

Ft./S

ec.

Hig

h Ve

loci

ty 4

900

Seri

es P

ress

ure

Dro

psCo

nsul

t Fa

ctor

y fo

r M

odel

s 49

18 t

hrou

gh 4

936

Page 15: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

PIPESIZE

MODELNUMBER

(1)

ADIA.

(INCH)

BMAX.

(INCH)C

(INCH)D

(INCH)E

(INCH)F

DIA.(INCH)

G(INCH)

SURFACEAREA

(SQ. FT.)(2)

OPTIMUMFLOW(GPM)

APPROX.DRY WGT.

(LBS)

2 4902AT-125 10 161⁄2 12 71⁄2 37⁄8 – – 12.7 51 302 4902A-125 10 161⁄2 20 71⁄2 37⁄8 – – 12.7 51 45

21⁄2 49025AT-125 10 161⁄2 12 71⁄2 37⁄8 – – 12.7 73 4021⁄2 49025A-125 10 161⁄2 20 71⁄2 37⁄8 – – 12.7 73 503 4903AT-125 12 221⁄8 141⁄2 81⁄2 71⁄2 – – 22 113 653 4903A-125 12 221⁄8 22 81⁄2 71⁄2 – – 22 113 754 4904A-125 12 221⁄8 22 81⁄2 71⁄2 – – 22 204 805 4905A-125 14 283⁄8 24 101⁄2 12 12 63⁄4 36.8 306 2006 4906A-125 14 283⁄8 24 101⁄2 12 12 63⁄4 36.8 469 2158 4908A-125 18 365⁄8 28 131⁄4 16 14 7 77.2 816 290

10 4910A-125 24 473⁄4 36 167⁄8 22 20 63⁄4 132.8 1291 56512 4912A-125 24 543⁄4 36 177⁄8 28 20 63⁄4 147.2 1837 64514 4914A-125 30 62 42 22 291⁄2 24 8 293.5 2106 91016 4916A-125 30 673⁄4 42 22 351⁄4 24 8 330.3 2790 965

Submittal Data Information“4900” Series Air Separators

401-137

SUPERSEDES: May 12, 2014 EFFECTIVE: September 15, 2015

JOB ENGINEER CONTRACTOR REP.

FLUSHVALVE

AIR VENT

PALLRINGS

SYSTEMCONNECTION

OPTIONALBASE RING

EB

D

GF

LIFTING LUG(2) - 180° APART

(5" THRU 16") 4”

A

C

ITEM NO. LOCATION MODEL NO. QUANTITY GPM

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII

Div. 1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @

240°F• Construction: Carbon Steel with exterior red oxide primer

finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the

piping system. Factory review is necessary should anypiping loads be present.

CAUTION: LIFTING LUGS FOR RIGGING ANDLIFTING USE ONLY, NOT FOR ANCHORING ORHANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Flush ValveOPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Connection Types

o ‘G’ Grooved Pipe Connections up to 16"• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125R

(1) For 150 psi models, replace - 125 with -150. Dimension for ‘T’ option only. (2) Coalescence (Pall Ring) Surface Area.Comments:

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

***

*

OPTIONALGROOVED

CONNECTONDETAIL VIEW

-15- Non-Removable Cover

4900 Series Air Separators, Non-Removable Cover(Submittal 401-137)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature: 125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction: Carbon Steel with exterior red oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Flush Valve (125 psi @ 240°F, Standard)

OPTIONS• Higher Design Pressures and Temperatures than 150 psi @ 240°F are available

• Optional System Connection Sizes available

• Optional Connection Types - ‘G’ Grooved Pipe Connections up to 21⁄2”

• Optional Base Ring - Add Suffix ‘R’ (4905 thru 4916)

(1) For 150 psi models, replace - 125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA* Dimension for ‘T’ option only

All dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea(2)

(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902AT-125 10 16-1/2 12* 7-1/2 3-7/8 --- --- 12.7 51 30

2 4902A-125 10 16-1/2 20 7-1/2 3-7/8 --- 12.7 51 45

2-1/2 49025AT-125 10 16-1/2 12* 7-1/2 3-7/8 --- --- 12.7 73 40

2-1/2 49025A-125 10 16-1/2 20 7-1/2 3-7/8 --- 12.7 73 50

3 4903AT-125 12 22-1/8 14-1/2* 8-1/2 7-1/2 --- --- 22 113 65

3 4903A-125 12 22-1/8 22 8-1/2 7-1/2 --- 22 113 75

4 4904A-125 12 22-1/8 22 8-1/2 7-1/2 --- --- 22 204 80

5 4905A-125 14 28-3/8 24 10-1/2 12 12 6-3/4 36.8 306 200

6 4906A-125 14 28-3/8 24 10-1/2 12 12 6-3/4 36.8 469 215

8 4908A-125 18 36--5/8 28 13-1/4 16 16 7 77.2 816 290

10 4910A-125 24 47-3/4 36 16-7/8 22 22 6-3/4 132.8 1291 565

12 4912A-125 24 54-3/4 36 17-7/8 28 28 6-3/4 147.2 1837 645

14 4914A-125 30 62 42 22 29-1/2 29-1/2 8 293.5 2106 910

16 4916A-125 30 67-3/4 42 22 35-1/4 35-1/4 8 330.3 2790 965

Page 16: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-16-Non-Removable Cover

4900 Series Air Separators, Non-Removable Cover(Submittal 401-091)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:150 PSI @ 240˚F

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and temperatures -Consult factory• Base Ring Standard on (4918 thru 4936)

PipeSize

ModelNumber

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea*(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

18 4918A-150 36 72-1/2 48 26-7/8 9 30 7-11/16 571.4 3673 1450

20 4920A-150 42 84 54 29-7/8 10-1/2 35 7-5/8 839.4 4561 2130

22 4922A-150 48 91 60 33-3/8 12 40 8-7/16 1215.5 5300 2820

24 4924A-150 48 98 60 33-3/8 12 40 8-7/16 1295.7 6346 3045

26 4926A-150 54 106-1/2 67 37-1/4 13-1/2 44 9-1/2 1687.0 7647 4170

30 4930A-150 60 122-1/2 74 40-7/8 15 50 9-7/8 2336.5 10262 6190

36 4936A-150 72 146 90 50-5/8 15 64 12-3/4 3993.1 14905 10610

*COALESCENCE (PALL RING) SURFACE AREAAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

Submittal Data Information‘4900’ Series Air Separators

401-091

SUPERSEDES: July 23, 2015 EFFECTIVE: September 5, 2015

Job:

COMMENTS:

ITEM LOCATION MODEL QUANTITY GALLONS

PIPESIZE

MODELNUMBER

ADIA.

(INCH)

BMAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

FDIA.

(INCH)

G(INCH)

SURFACEAREA *(FEET 2 )

OPTIMUMFLOW(GPM)

APPROX.WEIGHT

(LBS.)18 4918A-150 36 75 ½ 48 26 ⅞ 9 30 711⁄16 571.4 3673 148020 4920A-150 42 84 54 29 ⅞ 10 1⁄2 35 75⁄8 839.4 4561 218022 4922A-150 48 91 60 33 ⅜ 12 40 87⁄16 1215.5 5300 287524 4924A-150 48 98 60 33 ⅜ 12 40 87⁄16 1295.7 6346 310026 4926A-150 54 106 ½ 67 37 ¼ 13 1⁄2 44 91⁄2 1687.0 7647 427030 4930A-150 60 122 ½ 74 40 ⅞ 15 50 97⁄8 2336.5 10262 636536 4936A-150 72 146 90 50 ⅝ 15 64 123⁄4 3993.1 14905 10930

A

E

BALL VALVE

LIFTING LUG(2) 180° APART

AIR VENT

PALLRINGS

FLANGEDSYSTEMCONNECTIONS

BASE RING

B

D

G

F

C

6”4”

* Coalescence (Pall Ring) Surface Area

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per ASME

Code Section VIII Div. 1• Registered with the National Board

of Pressure Vessel Manufacturers• Standard Design Pressure and

Temperature: 150 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with

exterior red oxide primer finish• 304 Stainless Steel Coalescence

Pall Rings

CAUTION: LIFTING LUGS FORRIGGING AND LIFTING USEONLY, NOT FOR ANCHORINGOR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max.

50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and

temperatures -Consult factory• Base Ring

Standard on (4918 thru 4936)

Page 17: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-17-Non-Removable Cover

4900 Series High Velocity Air Separators, Non-Removable Cover(Submittal 401-136)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

All dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea(2)

(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902AHT-125 12 25 14* 10 9 --- --- 40 115 85

2 4902AH-125 12 25 22 10 9 --- --- 40 115 85

2-1/2 49025AHT-125 12 25 14* 10 9 --- --- 40 165 90

2-1/2 49025AH-125 12 25 22 10 9 --- --- 40 165 90

3 4903AHT-125 14 28-1/2 16-1/2* 10-7/8 12-3/4 --- --- 53 253 100

3 4903AH-125 14 28-1/2 24 10-7/8 12-3/4 --- --- 53 253 100

4 4904AH-125 14 28-1/2 24 10-7/8 12-3/4 --- --- 53 458 110

5 4905AH-125 20 40 30 14-1/4 14 16 6-3/4 110 686 190

6 4906AH-125 20 40 30 14-1/4 14 16 6-3/4 110 1015 205

8 4908AH-125 24 47-1/2 34 16-7/8 21-3/4 20 7 191 1730 430

10 4910AH-125 30 59-1/2 42 20-1/2 28-1/2 24 8 305 2718 600

12 4912AH-125 30 59-1/2 42 20-1/2 28-1/2 24 8 305 4124 650

14 4914AH-125 36 72 48 24 32 30 8 545 4727 940

16 4916AH-125 36 72 48 24 32 30 8 545 6262 965

PIPESIZE

MODELNUMBER

(1)

ADIA.

(INCH)

BMAX.

(INCH)C

(INCH)D

(INCH)E

(INCH)F

DIA.(INCH)

G(INCH)

SURFACEAREA

(SQ. FT.)(2)

OPTIMUMFLOW(GPM)

APPROX.DRY WGT.

(LBS)

2 4902AHT-125 12 25 22 10 9 – – 40 115 852 4902AH-125 12 25 22 10 9 – – 40 115 85

21⁄2 49025AHT-125 12 25 22 10 9 – – 40 165 9021⁄2 49025AH-125 12 25 22 10 9 – – 40 165 903 4903AHT-125 14 281⁄2 24 107⁄8 113⁄4 – – 53 253 1003 4903AH-125 14 281⁄2 24 107⁄8 113⁄4 – – 53 253 1004 4904AH-125 14 281⁄2 24 107⁄8 113⁄4 – – 53 458 1105 4905AH-125 20 40 30 141⁄4 18 16 63⁄4 110 686 1906 4906AH-125 20 40 30 141⁄4 18 16 63⁄4 110 1015 2058 4908AH-125 24 471⁄2 34 167⁄8 213⁄4 20 7 191 1730 43010 4910AH-125 30 591⁄2 42 201⁄2 281⁄2 24 8 305 2718 60012 4912AH-125 30 591⁄2 42 201⁄2 281⁄2 24 8 305 4124 65014 4914AH-125 36 72 48 24 36 30 8 545 4727 94016 4916AH-125 36 72 48 24 36 30 8 545 6262 965

Submittal Data Information“4900” Series Hi-Velocity Air Separators

401-136

SUPERSEDES: May 12, 2014 EFFECTIVE: September 15, 2015

JOB ENGINEER CONTRACTOR REP.

LIFTING LUG(2) - 180° APART

(3" THRU 16")

FLUSHVALVE

AIR VENT

PALL RINGCAGE

SYSTEMCONNECTION

OPTIONALBASE RING

E

B

D

GF

4”

C

A

ITEM NO. LOCATION MODEL NO. QUANTITY GPM

(1) For 150 psi models, replace - 125 with -150. (2) Coalescence (Pall Ring) Surface Area.

Comments:

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping. Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII Div. 1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @ 240°F• Optional Design Pressure and Temperature: 150 psi @ 240°F• Construction: Carbon Steel with exterior red oxide primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the pip-

ing system. Factory review is necessary should any pipingloads be present.

CAUTION: LIFTING LUGS FOR RIGGING ANDLIFTING USE ONLY, NOT FOR ANCHORING ORHANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Flush Valve

OPTIONS• Higher design pressures and temperatures

o 150 psi @ 240°F, available• Optional System Connection Sizes available• Optional Connection types

o ‘G’ Grooved Pipe Connections up to 16"• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125R)

OPTIONALGROOVED

CONNECTONDETAIL VIEW

*Dimensions for “T” option only (1) For 150 psi models, replace - 125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA

Page 18: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-18-Non-Removable Cover

4900 Series High Velosity Air Separators, Non-Removable Cover(Submittal 401-093)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:150 PSI @ 240˚F

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and temperatures -Consult factory• Base Ring Standard on (4918 thru 4936)

PipeSize

ModelNumber

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea*(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

18 4918AH-150 42 84 57 24-13/16 10-1/2 35 7-11/16 796.9 8246 2160

20 4920AH-150 48 91 62 27-9/16 12 40 8-7/16 1062.3 10238 2715

22 4922AH-150 54 98 67 30-3/4 13-1/2 44 9-1/2 1434.1 11874 3890

24 4924AH-150 54 106 67 30-3/4 13-1/2 44 9-1/2 1593.4 14245 4230

26 4926AH-150 60 113 74-1/2 32-1/4 15 50 9-7/8 2124.5 17167 5990

30 4930AH-150 66 128 82 37-1/4 15 58 13-5/8 2761.9 23037 7670

36 4936AH-150 84 150 104 44-7/8 15 72 14 5045.8 33457 15110

*COALESCENCE (PALL RING) SURFACE AREAAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

Submittal Data Information‘4900’ Series Hi-Velocity Air Separators

401-093

SUPERSEDES: July 23, 2015 EFFECTIVE: September 5, 2015

Job:

COMMENTS:

ITEM LOCATION MODEL QUANTITY GALLONS

PIPESIZE

MODELNUMBER

ADIA.

(INCH)

BMAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

FDIA.

(INCH)

G(INCH)

SURFACEAREA *(FEET 2 )

OPTIMUMFLOW(GPM)

APPROX.WEIGHT

(LBS.)18 4918AH-150 42 84 57 2413⁄16 101⁄2 35 711⁄16 796.9 8246 216020 4920AH-150 48 91 62 279⁄16 12 40 87⁄16 1062.3 10238 271522 4922AH-150 54 98 67 303⁄4 131⁄2 44 91⁄2 1434.1 11874 389024 4924AH-150 54 106 67 303⁄4 131⁄2 44 91⁄2 1593.4 14245 423026 4926AH-150 60 113 741⁄2 321⁄4 15 50 97⁄8 2124.5 17167 599030 4930AH-150 66 128 82 371⁄4 15 58 135⁄8 2761.9 23037 767036 4936AH-150 84 150 104 45 15 72 14 5045.8 33457 15110

A

ELIFTING LUG

(2) 180° APART

AIR VENT

PALLRINGS

FLANGEDSYSTEMCONNECTIONS

BASE RING

B

D

G

FC

BALL VALVE 6”4”

* Coalescence (Pall Ring) Surface Area

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per

ASME Code Section VIII Div. 1• Registered with the National Board

of Pressure Vessel Manufacturers• Standard Design Pressure and

Temperature: 150 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with

exterior red oxide primer finish• 304 Stainless Steel Coalescence

Pall Rings• Taco 4900 units are designed to be

self-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FORRIGGING AND LIFTING USEONLY, NOT FOR ANCHORINGOR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max.

50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and tem-

peratures-Consult factory• Base Ring

Standard on (4918 thru 4936)

Page 19: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-19-Non-Removable Cover

4900 Series Air/Dirt Separators, Non-Removable Cover(Submittal 401-138)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature: 125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction: Carbon Steel with exterior red oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve (125 psi @ 240°F, Standard)

OPTIONS• Higher Design Pressures and Temperatures than 150 psi @ 240°F are available

• Optional System Connection Sizes available

• Optional Connection Types - ‘G’ Grooved Pipe Connections up to 2-⁄2”

• Optional Base Ring - Add Suffix ‘R’ (4905 thru 4916)

All dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea(2)

(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902ADT-125 10 16-1/2 12* 7-1/2 3-7/8 --- --- 12.7 51 30

2 4902AD-125 10 16-1/2 20 7-1/2 3-7/8 --- 12.7 51 45

2-1/2 49025ADT-125 10 16-1/2 12* 7-1/2 3-7/8 --- --- 12.7 73 40

2-1/2 49025AD-125 10 16-1/2 20 7-1/2 3-7/8 --- 12.7 73 50

3 4903ADT-125 12 22-1/8 14-1/2* 11-1/2 7-1/2 --- --- 22 113 75

3 4903AD-125 12 22-1/8 22 11-1/2 7-1/2 --- 22 113 85

4 4904AD-125 12 22-1/8 22 11-1/2 7-1/2 --- --- 22 204 90

5 4905AD-125 14 28-3/8 24 15-3/4 12 13-1/2 12-3/8 36.8 306 230

6 4906AD-125 14 28-3/8 24 15-3/4 12 13-1/2 12-3/8 36.8 469 245

8 4908AD-125 18 36--5/8 28 18-1/8 16 17-1/2 12-5/8 77.2 816 325

10 4910AD-125 24 47-3/4 36 25-3/8 22 20 12-7/8 132.8 1291 615

12 4912AD-125 24 54-3/4 36 26-3/8 28 20 12-7/8 147.2 1837 695

14 4914AD-125 30 62 42 33 29-1/2 24 13-3/4 293.5 2106 1000

16 4916AD-125 30 67-3/4 42 34 35-1/4 24 13-3/4 330.3 2790 1055

PIPESIZE

MODELNUMBER

(1)

ADIA.

(INCH)

BMAX.

(INCH)C

(INCH)D

(INCH)E

(INCH)F

DIA.(INCH)

G(INCH)

SURFACEAREA

(SQ. FT.)(2)

OPTIMUMFLOW(GPM)

APPROX.DRY WGT.

(LBS)

2 4902ADT-125 10 161⁄2 12 71⁄2 37⁄8 – – 12.7 51 302 4902AD-125 10 161⁄2 20 71⁄2 37⁄8 – – 12.7 51 45

21⁄2 49025ADT-125 10 161⁄2 12 71⁄2 37⁄8 – – 12.7 73 4021⁄2 49025AD-125 10 161⁄2 20 71⁄2 37⁄8 – – 12.7 73 503 4903ADT-125 12 251⁄8 141⁄2 111⁄2 71⁄2 – – 22 113 753 4903AD-125 12 251⁄8 22 111⁄2 71⁄2 – – 22 113 854 4904AD-125 12 251⁄8 22 111⁄2 71⁄2 – – 22 204 905 4905AD-125 14 335⁄8 24 153⁄4 12 131⁄2 123⁄8 36.8 306 2306 4906AD-125 14 335⁄8 24 153⁄4 12 131⁄2 123⁄8 36.8 469 2458 4908AD-125 18 411⁄2 28 181⁄8 16 171⁄2 125⁄8 77.2 816 325

10 4910AD-125 24 561⁄4 36 253⁄8 22 20 127⁄8 132.8 1291 61512 4912AD-125 24 631⁄4 36 263⁄8 28 20 127⁄8 147.2 1837 69514 4914AD-125 30 73 42 33 291⁄2 24 133⁄4 293.5 2106 100016 4916AD-125 30 793⁄4 42 34 351⁄4 24 133⁄4 330.3 2790 1055

Submittal Data Information“4900” Series Air/Dirt Separators

401-138

SUPERSEDES: May 1, 2015 EFFECTIVE: September 15, 2015

JOB ENGINEER CONTRACTOR REP.

FLUSHVALVE

AIR VENT

PALLRINGS

SYSTEMCONNECTION

OPTIONALBASE RING

EB

D

GF

LIFTING LUG(2) - 180° APART

(5" THRU 16")

FACTORY INSTALLEDBLOWDOWN VALVE(1" ON 4902 & 49025)

(2" ON 4903 & LARGER)

4”

A

C

(1) For 150 psi models, replace - 125 with -150. Dimension for ‘T’ option only. (2) Coalescence (Pall Ring) Surface Area.

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

OPTIONALGROOVED

CONNECTONDETAIL VIEW

***

*

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII

Div. 1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @

240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exterior red oxide primer

finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the

piping system. Factory review is necessary should anypiping loads be present.

CAUTION: LIFTING LUGS FOR RIGGING ANDLIFTING USE ONLY, NOT FOR ANCHORING ORHANGING

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush ValveOPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Connection Types

o ‘G’ Grooved Pipe Connections up to 16"• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125RNot Available (4902 thru 4904)

ITEM NO. LOCATION MODEL NO. QUANTITY GPM(1) For 150 psi models, replace - 125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA* Dimension for ‘T’ option only

Page 20: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-20-Non-Removable Cover

4900 Series Air/Dirt Separators, Non-Removable Cover(Submittal 401-092)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:150 PSI @ 240˚F

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and temperatures -Consult factory• Base Ring Standard on (4918 thru 4936)

PipeSize

ModelNumber

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea*(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

18 4918AD-150 36 91 48 42-1/4 9 30 13-1/2 571.4 3673 1650

20 4920AD-150 42 100 54 45-3/4 10-1/2 38 12-3/4 839.4 4561 2410

22 4922AD-150 48 109 60 51-11/16 12 44 12-5/8 1215.5 5300 3190

24 4924AD-150 48 118 60 53-1/2 12 44 12-5/8 1295.7 6346 3360

26 4926AD-150 54 127 67 57-11/16 13-1/2 50 13-1/8 1687.0 7647 4620

30 4930AD-150 60 145 74 62-1/2 15 54 14 2336.5 10262 7050

36 4936AD-150 72 172 90 76-5/16 15 66 15-3/4 3993.1 14905 12030

*COALESCENCE (PALL RING) SURFACE AREAAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

Submittal Data Information‘4900’ Series Air/Dirt Separators

401-092

SUPERSEDES: July 23, 2015 EFFECTIVE: September 5, 2015

Job:

COMMENTS:

ITEM LOCATION MODEL QUANTITY GALLONS

PIPESIZE

MODELNUMBER

ADIA.

(INCH)

BMAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

FDIA.

(INCH)

G(INCH)

SURFACEAREA *(FEET 2 )

OPTIMUMFLOW(GPM)

APPROX.WEIGHT

(LBS.)18 4918AD-150 36 91 48 421⁄4 9 30 131⁄2 571.4 3673 165020 4920AD-150 42 100 54 453⁄4 101⁄2 38 123⁄4 839.4 4561 241022 4922AD-150 48 109 60 5111⁄16 12 44 125⁄8 1215.5 5300 319024 4924AD-150 48 118 60 531⁄2 12 44 125⁄8 1295.7 6346 336026 4926AD-150 54 127 67 5711⁄16 131⁄2 50 131⁄8 1687.0 7647 462030 4930AD-150 60 145 74 621⁄2 15 54 14 2336.5 10262 705036 4936AD-150 72 172 90 765⁄16 15 66 153⁄4 3993.1 14905 12030

AE

BALL VALVELIFTING LUG

(2) 180° APART

AIR VENT

PALLRINGS

FLANGEDSYSTEMCONNECTIONS

BASE RING

B

D

G

FC

FACTORY INSTALLED2" BLOWDOWN VALVE

6”4”

* Coalescence (Pall Ring) Surface Area

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per

ASME Code Section VIII Div. 1• Registered with the National Board

of Pressure Vessel Manufacturers• Standard Design Pressure and

Temperature: 150 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with

exterior red oxide primer finish• 304 Stainless Steel Coalescence

Pall Rings

CAUTION: LIFTING LUGS FORRIGGING AND LIFTING USEONLY, NOT FOR ANCHORINGOR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max.

50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher Design Pressures and

Temperatures-Consult factory• Base Ring

Standard on (4918 thru 4936))

Page 21: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-21- Non-Removable Cover

4900 Series High Velocity Air/Dirt Separators, Non-Removable Cover(Submittal 401-135)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless SteelCoalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

*Dimensions for “T” option only (1) For 150 psi models, replace - 125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA

All dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea(2)

(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902ADHT-125 12 32 14* 16 10 --- --- 64 115 100

2 4902ADH-125 12 32 22 16 10 --- --- 64 115 100

2-1/2 49025ADHT-125 12 32 14* 16 10 --- --- 64 165 105

2-1/2 49025ADH-125 12 32 22 16 10 --- --- 64 165 105

3 4903ADHT-125 14 40-1/4 16-1/2* 20-1/8 14-1/4 --- --- 82 253 120

3 4903ADH-125 14 40-1/4 24 20-1/8 14-1/4 --- --- 82 253 120

4 4904ADH-125 14 40-1/4 24 20-1/8 14-1/4 --- --- 82 458 130

5 4905ADH-125 20 57-1/2 30 28-3/4 21 18 13 165 686 255

6 4906ADH-125 20 57-1/2 30 28-3/4 21 18 13 165 1015 270

8 4908ADH-125 24 69-1/4 34 34-5/8 25-3/4 20 13-1/8 290 1730 520

10 4910ADH-125 30 86 42 43 32-1/2 24 13-3/4 456 2718 735

12 4912ADH-125 30 86 42 43 32-1/2 24 13-3/4 456 4124 785

14 4914ADH-125 36 103 48 51-1/2 39-1/2 30 13-5/8 800 4727 1100

16 4916ADH-125 36 103 48 51-1/2 39-1/2 30 13-5/8 800 6262 1125

Submittal Data Information“4900” Series Hi-Velocity Air/Dirt Separators

401-135

SUPERSEDES: May 5, 2015 EFFECTIVE: September 15, 2015

JOB ENGINEER CONTRACTOR REP.

LIFTING LUG(2) - 180° APART

(3" THRU 16")

FLUSHVALVE

AIR VENT

PALL RINGCAGE

SYSTEMCONNECTION

OPTIONALBASE RING

E

B

D

GF

FACTORY INSTALLEDBLOWDOWN VALVE(1" ON 4902 & 49025)

(2" ON 4903 & LARGER)

4”

C

A

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping. Contact your local Taco representative should certified dimensional drawings be required.

(1) For 150 psi models, replace - 125 with -150. (2) Coalescence (Pall Ring) Surface Area.

PIPESIZE

MODELNUMBER

(1)

ADIA.

(INCH)

BMAX.

(INCH)C

(INCH)D

(INCH)E

(INCH)F

DIA.(INCH)

G(INCH)

SURFACEAREA

(SQ. FT.)(2)

OPTIMUMFLOW(GPM)

APPROX.DRY WGT.

(LBS)

2 4902ADHT-125 12 32 22 16 10 – – 64 115 1002 4902ADH-125 12 32 22 16 10 – – 64 115 100

21⁄2 49025ADHT-125 12 32 22 16 10 – – 64 165 10521⁄2 49025ADH-125 12 32 22 16 10 – – 64 165 1053 4903ADHT-125 14 401⁄4 24 201⁄8 141⁄4 – – 82 253 1203 4903ADH-125 14 401⁄4 24 201⁄8 141⁄4 – – 82 253 1204 4904ADH-125 14 401⁄4 24 201⁄8 141⁄4 – – 82 458 1305 4905ADH-125 20 571⁄2 30 283⁄4 21 18 13 165 686 2556 4906ADH-125 20 571⁄2 30 283⁄4 21 18 13 165 1015 2708 4908ADH-125 24 691⁄4 34 345⁄8 253⁄4 20 131⁄8 290 1730 52010 4910ADH-125 30 86 42 43 321⁄2 24 133⁄4 456 2718 73512 4912ADH-125 30 86 42 43 321⁄2 24 133⁄4 456 4124 78514 4914ADH-125 36 103 48 511⁄2 391⁄2 30 135⁄8 800 4727 110016 4916ADH-125 36 103 48 511⁄2 391⁄2 30 135⁄8 800 6262 1125

ITEM NO. LOCATION MODEL NO. QUANTITY GPM

Comments:

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII Div. 1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exterior red oxide primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the piping

system. Factory review is necessary should any piping loads bepresent.

CAUTION: LIFTING LUGS FOR RIGGING ANDLIFTING USE ONLY, NOT FOR ANCHORING ORHANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush ValveOPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Connection Types

o ‘G’ Grooved Pipe Connections up to 16"• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125RNot Available (4902 thru 4904)

OPTIONALGROOVED

CONNECTONDETAIL VIEW

Page 22: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-22-Non-Removable Cover

4900 Series High Velocity Air/Dirt Separators, Non-Removable Cover(Submittal 401-094)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:150 PSI @ 240˚F

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and temperatures -Consult factory• Base Ring Standard on (4918 thru 4936)

PipeSize

ModelNumber

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea*(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

18 4918ADH-150 42 121 57 61-3/4 10-1/2 38 12-3/4 1109.5 8246 2930

20 4920ADH-150 48 132 62 67-9/16 12 44 12-5/8 1585.0 10238 3705

22 4922ADH-150 54 143 67 75-3/4 13-1/2 50 13-1/8 2113.4 11874 5350

24 4924ADH-150 54 148 67 72-3/4 13-1/2 50 13-1/8 2430.4 14245 5890

26 4926ADH-150 60 165 74-1/2 84-1/4 15 54 14 3275.7 17167 8430

30 4930ADH-150 66 186 82 95-1/4 15 60 14-13/16 4226.8 23037 10630

36 4936ADH-150 84 219 104 113-7/8 15 78 15-3/8 7925.2 33457 21460

*COALESCENCE (PALL RING) SURFACE AREAAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

Submittal Data Information‘4900’ Series Hi-Velocity Air/Dirt Separators

401-094

SUPERSEDES: July 23, 2015 EFFECTIVE: September 5, 2015

Job:

COMMENTS:

ITEM LOCATION MODEL QUANTITY GALLONS

PIPESIZE

MODELNUMBER

ADIA.

(INCH)

BMAX.(INCH)

C

(INCH)

D

(INCH)

E

(INCH)

FDIA.

(INCH)

G

(INCH)

SURFACEAREA *(FEET 2 )

OPTIMUMFLOW(GPM)

APPROX.WEIGHT

(LBS.)18 4918ADH-150 42 121 57 613⁄4 101⁄2 38 123⁄4 1109.5 8246 293020 4920ADH-150 48 132 62 679⁄16 12 44 125⁄8 1585.0 10238 370522 4922ADH-150 54 143 67 753⁄4 131⁄2 50 131⁄8 2113.4 11874 535024 4924ADH-150 54 148 67 723⁄4 131⁄2 50 131⁄8 2430.4 14245 589026 4926ADH-150 60 165 741⁄2 841⁄4 15 54 14 3275.7 17167 843030 4930ADH-150 66 186 82 951⁄4 15 60 1413⁄16 4226.8 23037 1063036 4936ADH-150 84 219 104 1137⁄8 15 78 153⁄8 7925.2 33457 21460

AELIFTING LUG

(2) 180° APART

AIR VENT

PALLRINGS

FLANGEDSYSTEMCONNECTIONS

BASE RING

B

D

G

FC

FACTORY INSTALLED2" BLOWDOWN VALVE

BALL VALVE 6”4”

* Coalescence (Pall Ring) Surface Area

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per ASME

Code Section VIII Div. 1• Registered with the National Board of

Pressure Vessel Manufacturers• Standard Design Pressure and

Temperature: 150 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exte-

rior red oxide primer finish• 304 Stainless Steel Coalescence Pall

Rings• Taco 4900 units are designed to be

self-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FORRIGGING AND LIFTING USEONLY, NOT FOR ANCHORINGOR HANGING.

FACTORY INSTALLED• Air Vent is suitable for water, max.

50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher Design Pressures and

Temperatures-Consult factory• Base Ring

Standard on (4918 thru 4936)

Page 23: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-23-Non-Removable Cover

4900 Series Dirt Separators, Non-Removable Cover(Submittal 401-109)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressureand Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal downto 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless SteelCoalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

**COALESCENCE (PALL RING) SURFACE AREA*Dimensions for “T” option only All dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

PipeSize

ModelNumber

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

SurfaceArea**(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902DT-125 10 16-1/2 12* 7-1/2 5-1/4 --- --- 12.7 51 30

2 4902D-125 10 16-1/2 20 7-1/2 5-1/4 --- --- 12.7 51 35

2-1/2 49025DT-125 10 16-1/2 12* 7-1/2 5-1/4 --- --- 12.7 73 40

2-1/2 49025D-125 10 16-1/2 20 7-1/2 5-1/4 --- --- 12.7 73 50

3 4903DT-125 12 21-7/8 14-1/2* 11-5/8 6 --- --- 22 113 75

3 4903D-125 12 21-7/8 22 11-5/8 6 --- --- 22 113 85

4 4904D-125 12 21-7/8 22 11-5/8 6 --- --- 22 204 95

5 4905D-125 14 28-5/8 24 15-3/4 6 13-1/2 12-3/8 36.8 306 125

6 4906D-125 14 28-5/8 24 15-3/4 6 13-1/2 12-3/8 36.8 469 135

8 4908D-125 18 33-7/8 28 18-1/4 7-1/4 17-1/2 12-5/8 77.2 816 215

10 4910D-125 24 45-1/4 36 25-3/8 9 20 12-7/8 132.8 1291 360

12 4912D-125 24 47 36 26-3/8 9 20 12-7/8 147.2 1837 400

Submittal Data Information‘4900’ Series Dirt Separators

401-109

SUPERSEDES: May 12, 2014 EFFECTIVE: September 15, 2015JOB ENGINEER CONTRACTOR REP.

ITEM QUANTITY MODEL NUMBER SIZE

A

B

D

G

E

FC

A

B

D

E

C

PALLRINGS

SYSTEMCONNECTION

1⁄2"BALL VALVE

FACTORY INSTALLEDBLOWDOWN VALVE(1" ON 4902 & 49025)

(2" ON 4903 & LARGER)

FACTORY INSTALLEDBLOWDOWN VALVE(1" ON 4902 & 49025)

(2" ON 4903 & LARGER)

OPTIONALBASE RING

(5" THRU 12")ADD SUFFIX ‘R’

PALLRINGS

SYSTEMCONNECTION

1⁄2"BALL VALVE

LIFTING LUG(2) – 180° APART

(5" THRU 12")

THREADED CONNECTIONS4902DT THRU 4903DT

FLANGED CONNECTIONS4902D THRU 4912D

* COALESCENCE (PALL RING) SURFACE AREA

PIPESIZE

MODELNUMBER

A DIA.(INCH)

B MAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

F DIA.(INCH)

G(INCH)

SURFACEAREA*

(SQ. FT.)

OPTIMUMFLOW(GPM)

APPROX.WGT. (LBS)

2 4902DT-125 10 161⁄2 15 71⁄2 51⁄4 — — 12.7 51 302 4902D-125 10 161⁄2 20 71⁄2 51⁄4 — — 12.7 51 35

21⁄2 49025DT-125 10 161⁄2 15 71⁄2 51⁄4 — — 12.7 73 4021⁄2 49025D-125 10 161⁄2 20 71⁄2 51⁄4 — — 12.7 73 503 4903DT-125 12 217⁄8 181⁄2 115⁄8 6 — — 22 113 753 4903D-125 12 217⁄8 22 115⁄8 6 — — 22 113 854 4904D-125 12 217⁄8 22 115⁄8 6 — — 22 204 955 4905D-125 14 285⁄8 24 153⁄4 6 131⁄2 123⁄8 36.8 306 1256 4906D-125 14 285⁄8 24 153⁄4 6 131⁄2 123⁄8 36.8 469 1358 4908D-125 18 337⁄8 28 181⁄4 71⁄4 171⁄2 125⁄8 77.2 816 215

10 4910D-125 24 451⁄4 36 253⁄8 9 20 127⁄8 132.8 1291 36012 4912D-125 24 47 36 263⁄8 9 20 127⁄8 147.2 1837 400

SIZES & DIMENSIONSAll dimensions shown are subject to change and should not be used for prepiping.Contact your local Taco representative should certified dimensional drawings be required.

SPECIFICATIONS• Designed and constructed per ASME Code

Section VIII Div. 1• Registered with the National Board of

Pressure Vessel Manufacturers• Standard Design Pressure and Temperature:

125 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exterior red

oxide primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-sup-

porting in the piping system. Factory review isnecessary should any piping loads be pre-sent.

CAUTION: LIFTING LUGS FOR RIGGING AND LIFTING USE ONLY, NOTFOR ANCHORING OR HANGING.FACTORY INSTALLED• Blowdown Valve• Flush ValveOPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4912) Exp.4912AD-125R

Page 24: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-24-

4900 Series Removable Cover, Air Separators (Submittal 401-175)

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

H(Inch)

K(Inch)

SurfaceArea (2)

(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902ATR-125 10 20 12* 7-1/2 5-1/4 --- --- 8 11 13.3 51 85

2 4902AR-125 10 20 20 7-1/2 5-1/4 --- --- 8 11 13.3 51 85

2-1/2 49025AR-125 10 20 12* 7-1/2 5-1/4 --- --- 8 11 13.3 73 90

2-1/2 49025ATR-125 10 20 20 7-1/2 5-1/4 --- --- 8 11 13.3 73 90

3 4903AR-125 12 23 14-1/2* 8-5/8 6 --- --- 9 12 22.5 113 125

3 4903ATR-125 12 23 22 8-5/8 6 --- --- 9 12 22.5 113 125

4 4904AR-125 12 23 22 8-5/8 6 --- --- 9 12 22.5 204 130

5 4905AR-125 14 29-1/2 24 10-1/2 6 12 6-3/4 10 17 29.6 306 380

6 4906AR-125 14 29-1/2 24 10-1/2 6 12 6-3/4 10 17 29.6 469 385

8 4908AR-125 18 36-5/8 28 13-1/4 7-1/4 14 7 12 21 63.9 816 550

10 49010AR-125 24 47-3/4 36 16-7/8 8-7/8 20 6-3/4 15 28 109.7 1291 1000

12 4912AR-125 24 54-3/4 36 17-7/8 8-7/8 20 6-3/4 15 35 140.4 1837 1030

14 4914AR-125 30 63 42 22 10-1/2 24 8 18 38 221.0 2106 1300

16 4916AR-125 30 68-3/4 42 22 10-1/2 24 8 18 44 258.8 2790 1350

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

Removable Cover

*Dimensions for “T” option only (1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 WITH -150(2) COALESCENCE (PALL RING) SURFACE AREA

Submittal Data Information“4900” Series Removable Cover, Air Separator

401-175

SUPERSEDES: December 8, 2014 EFFECTIVE: September 15 , 2015JOB ENGINEER CONTRACTOR REP.

ITEM QUANTITY MODEL NUMBER SIZE

4”

(1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 WITH -150(2) COALESCENCE (PALL RING) SURFACE AREA

SPECIFICATIONS• Designed and constructed per ASME Code Section

VIII Div. 1• Registered with the National Board of Pressure

Vessel Manufacturers• Standard Design Pressure and Temperature: 125

psi @ 240°F• Construction: Carbon Steel with exterior red oxide

primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting

in the piping system. Factory review is necessaryshould any piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FORANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush ValveOPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp.4912AD-125R

Not Available (4902 thru 4904)

PIPESIZE

MODELNUMBER(1)

A DIA.(INCH)

B MAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

F DIA.(INCH)

G(INCH)

APPROX.WGT. (LBS)

2 4902AR-125 10 20 20 71⁄2 51⁄4 – – 85

21⁄2 49025AR-125 10 20 20 71⁄2 51⁄4 – – 90

3 4903AR-125 12 23 22 85⁄8 6 – – 1254 4904AR-125 12 23 22 85⁄8 6 – – 1305 4905AR-125 14 291⁄2 24 101⁄2 6 12 63⁄4 3806 4906AR-125 14 291⁄2 24 101⁄2 6 12 63⁄4 3858 4908AR-125 18 365⁄8 28 131⁄4 71⁄4 14 7 550

10 4910AR-125 24 473⁄4 36 167⁄8 87⁄8 20 63⁄4 100012 4912AR-125 24 543⁄4 36 177⁄8 87⁄8 20 63⁄4 103014 4914AR-125 30 63 42 22 101⁄2 24 8 130016 4916AR-125 30 683⁄4 42 22 101⁄2 24 8 1350

SURFACEAREA(2)

(SQ. FT.)

13.3

13.3

22.522.529.629.663.9

109.7140.4221.0258.8

OPTIMUMFLOW(GPM)

51

73

113204306469816

1291183721062790

H(INCH)

8

8

99

10101215151818

K(INCH)

11

11

121217172128353844

2 4902ATR-125 10 20 20 71⁄2 51⁄4 – – 8513.3 518 11

21⁄2 49025ATR-125 10 20 20 71⁄2 51⁄4 – – 9013.3 738 11

3 4903ATR-125 12 23 22 85⁄8 6 – – 12522.5 1139 12

Page 25: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-25- Removeable Cover

4900 Series Removable Cover, Air/Dirt Separators (Submittal 401-176)

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

H(Inch)

K(Inch)

SurfaceArea (2)

(Sq.Ft)

GPM @4.9

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902ADTR-125 10 20 12* 7-1/12 5-1/4 --- --- 8 11 13.3 51 85

2 4902ADR-125 10 20 20 7-1/12 5-1/4 --- --- 8 11 13.3 51 85

2-1/2 49025ADTR-125 10 20 12* 7-1/12 5-1/4 --- --- 8 11 13.3 73 90

2-1/2 49025ADR-125 10 20 20 7-1/12 5-1/4 --- --- 8 11 13.3 73 90

3 4903ADTR-125 12 26 14-1/2* 11-5/8 6 --- --- 9 14 27.7 113 135

3 4903ADR-125 12 26 22 11-5/8 6 --- --- 9 14 27.7 113 135

4 4904ADR-125 12 26 22 11-5/8 6 --- --- 9 14 27.7 204 140

5 4905ADR-125 14 34-1/2 24 15-3/4 6 --- --- 10 21 38.0 306 430

6 4906ADR-125 14 34-1/2 24 15-3/4 6 --- --- 10 21 38.0 469 440

8 4908ADR-125 18 41-1/2 28 18-1/8 7-1/4 17-1/2 12-5/8 12 25 78.3 816 630

10 49010ADR-125 24 56-1/4 36 25-3/8 8-7/8 20 12-7/8 15 35 140.4 1291 1155

12 4912ADR-125 24 63-1/4 36 26-3/8 8-7/8 20 12-7/8 15 39 157.5 1837 1180

14 4914ADR-125 30 74 42 33 10-1/2 24 13-3/4 18 44 258.8 2106 1550

16 4916ADR-125 30 80-3/4 42 34 10-1/2 24 13-3/4 18 51 303.8 2790 1580

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

*Dimensions for “T” option only (1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA

Submittal Data Information“4900” Series Removable Cover, Air/Dirt Separator

401-176

SUPERSEDES: December 8, 2014 EFFECTIVE: September 15, 2015JOB ENGINEER CONTRACTOR REP.

ITEM QUANTITY MODEL NUMBER SIZE

4”

(1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 WITH -150(2) COALESCENCE (PALL RING) SURFACE AREA

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII Div. 1• Registered with the National Board of Pressure Vessel Manufacturers• Standard Design Pressure and Temperature: 125 psi @ 240°F• Construction: Carbon Steel with exterior red oxide primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the piping system.

Factory review is necessary should any piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGING AND LIFTING USEONLY, NOT FOR ANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher design pressures and temperatures

o 150 psi @ 240°F, Available• Optional System Connection sizes available• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125RNot Available (4902 thru 4904)

PIPESIZE

MODELNUMBER(1)

A DIA.(INCH)

B MAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

F DIA.(INCH

G(INCH)

H(INCH)

K(INCH)

SURFACEAREA(2)

(SQ. FT.)

OPTIMUMFLOW(GPM)

APPROX.WGT.(LBS)

2 4902ADTR-125 10 20 20 7 1/12 5 1/4 – – 8 11 13.3 51 852 4902ADR-125 10 20 20 7 1/12 5 1/4 – – 8 11 13.3 51 85

21⁄2 49025ADTR-125 10 20 20 7 1/12 5 1/4 – – 8 11 13.3 73 9021⁄2 49025ADR-125 10 20 20 7 1/12 5 1/4 – – 8 11 13.3 73 90

3 4903ADTR-125 12 26 22 11 5/8 6 – – 9 14 27.7 113 1353 4903ADR-125 12 26 22 11 5/8 6 – – 9 14 27.7 113 1354 4904ADR-125 12 26 22 11 5/8 6 – – 9 14 27.7 204 1405 4905ADR-125 14 34 1/2 24 15 3/4 6 – – 10 21 38.0 306 4306 4906ADR-125 14 34 1/2 24 15 3/4 6 – – 10 21 38.0 469 4408 4908ADR-125 18 41 1/2 28 18 1/8 7 1/4 17 1/2 12 5/8 12 25 78.3 816 630

10 4910ADR-125 24 56 1/4 36 25 3/8 8 7/8 20 12 7/8 15 35 140.0 1291 115512 4912ADR-125 24 63 1/4 36 26 3/8 8 7/8 20 12 7/8 15 39 157.5 1837 118014 4914ADR-125 30 74 42 33 101⁄2 24 13 3/4 18 44 258.8 2106 155016 4916ADR-125 30 80 3/4 42 34 101⁄2 24 13 3/4 18 51 303.0 2790 1580

Page 26: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-26-Removeable Cover

4900 Series Removable Cover, High Velocity Air Separators(Submittal 401-177)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

H(Inch)

K(Inch)

SurfaceArea (2)

(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902AHTR-125 12 25 14* 10 6 --- --- 9 14 18.5 115 135

2 4902AHR-125 12 25 22 10 6 --- --- 9 14 18.5 115 135

2-1/2 49025AHTR-125 12 25 14* 10 6 --- --- 9 14 18.5 165 140

2-1/2 49025AHR-125 12 25 22 10 6 --- --- 9 14 18.5 165 140

3 4903AHTR-125 14 28-1/2 16-1/2* 11 6 12 6-3/4 10 16 32.3 253 280

3 4903AHR-125 14 28-1/2 24 11 6 12 6-3/4 10 16 32.3 253 280

4 4904AHR-125 14 28-1/2 24 11 6 12 6-3/4 10 16 32.3 458 290

5 4905AHR-125 20 40 30 14/1/4 7-1/4 16 6-3/4 12 23 71.1 686 520

6 4906AHR-125 20 40 30 14/1/4 8-7/8 16 6-3/4 15 23 71.1 1015 535

8 4908AHR-125 24 47-1/2 34 16-7/8 8-7/8 20 6-3/4 15 27 111.5 1730 870

10 49010AHR-125 30 60-1/2 42 20-1/2 10-1/2 24 8 18 35 140.4 2718 1000

12 4912AHR-125 30 60-1/2 42 20-1/2 10-1/2 24 8 18 35 140.4 4124 1050

14 4914AHR-125 36 72 48 24 12 30 7-7/8 20 44 258.8 4727 1500

16 4916AHR-125 36 72 48 24 12 30 7-7/8 20 44 258.8 6262 1530

*Dimensions for “T” option only (1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA

Submittal Data Information“4900” Series Removable Cover, High Velocity Air Separator

401-177

SUPERSEDES: December 8, 2014 EFFECTIVE: September 15 , 2015JOB ENGINEER CONTRACTOR REP.

ITEM QUANTITY MODEL NUMBER SIZE

4”

(1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 WITH -150(2) COALESCENCE (PALL RING) SURFACE AREA

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII Div. 1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @ 240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exterior red oxide primer finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the piping

system. Factory review is necessary should any piping loadsbe present.

CAUTION: LIFTING LUGS FOR RIGGING AND LIFTING USE ONLY, NOT FORANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% glycol• Flush Valve

OPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125RNot Available (4902 thru 49025)

PIPESIZE

MODELNUMBER(1)

A DIA.(INCH)

B MAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

F DIA.(INCH

G(INCH)

H(INCH)

K(INCH)

SURFACEAREA(2)

(SQ. FT.)

OPTIMUMFLOW(GPM)

APPROX.WGT.(LBS)

2 4902AHTR-125 12 25 22 10 6 – – 9 14 18.5 115 1352 4902AHR-125 12 25 22 10 6 – – 9 14 18.5 115 135

21⁄2 49025AHTR-125 12 25 22 10 6 – – 9 14 18.5 165 14021⁄2 49025AHR-125 12 25 22 10 6 – – 9 14 18.5 165 140

3 4903AHTR-125 14 28 1/2 24 11 6 12 6 3/4 10 16 32.3 253 2803 4903AHR-125 14 28 1/2 24 11 6 12 6 3/4 10 16 32.3 253 2804 4904AHR-125 14 28 1/2 24 11 6 12 6 3/4 10 16 32.3 458 2905 4905AHR-125 20 40 30 14 1/4 7 1/4 16 6 3/4 13 23 71.1 686 5206 4906AHR-125 14 40 24 14 1/4 8 7/8 16 6 3/4 13 23 71.1 1015 5358 4908AHR-125 24 47 1/2 34 16 7/8 8 7/8 20 6 3/4 15 27 111.5 1730 870

10 4910AHR-125 30 60 1/2 42 20 1/2 10 1/2 24 18 18 35 140.0 2718 100012 4912AHR-125 30 60 1/2 42 20 1/2 10 1/2 24 18 18 35 140.4 4124 105014 4914AHR-125 36 72 48 24 12 30 7 7/8 18 44 258.8 4727 150016 4916AHR-125 36 72 48 24 12 30 7 7/8 20 44 258.8 6262 1530

Page 27: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

-27- Removable Cover

4900 Series Removable Cover, High Velocity Air/Dirt Separators (Submittal 401-178)

Designed and constructed perASME Section VIII, Div. 1

Registered with the National Board of Pressure Vessel Manufacturers

Standard Design Pressure and Temperature:125 PSI @ 240˚F

Optional Design Pressure and Temperature:(150 PSI @240˚F Option Available)

Particle removal down to 5 microns

Construction:Carbon Steel with exteriorred oxide primer finish

304 Stainless Steel Coalescence Pall Rings

Taco 4900 units are designed to beself-supporting in the piping system.Factory review is necessary shouldany piping loads be present.

CAUTION: LIFTING LUGS FOR RIGGINGAND LIFTING USE ONLY, NOT FOR ANCHORING OR HANGING.

PipeSize

ModelNumber (1)

A Dia.(Inch)

B Max.(Inch)

C(Inch)

D(Inch)

E(Inch)

F Dia.(Inch)

G(Inch)

H(Inch)

K(Inch)

SurfaceArea (2)

(Sq.Ft)

GPM @11

Ft./Sec.

Approx.Wt.

(LBS.)

2 4902ADHTR-125 12 32 14* 16-1/8 6 --- --- 9 18 25.4 115 150

2 4902ADHR-125 12 32 22 16-1/8 6 --- --- 9 18 25.4 115 150

2-1/2 49025ADHTR-125 12 32 14* 16-1/8 6 --- --- 9 18 25.4 165 155

2-1/2 49025ADHR-125 12 32 22 16-1/8 6 --- --- 9 18 25.4 165 155

3 4903ADHTR-125 14 40-1/4 16-1/2* 20-1/4 6 --- --- 10 25 54.8 253 300

3 4903ADHR-125 14 40-1/4 24 20-1/4 6 --- --- 10 25 54.8 253 300

4 4904ADHR-125 14 40-1/4 24 20-1/4 6 --- --- 10 25 54.8 458 310

5 4905ADHR-125 20 57-1/2 30 28-3/4 7-1/4 18 13 12 36 117.5 686 585

6 4906ADHR-125 20 57-1/2 30 28-3/4 8-7/8 18 13 15 36 117.5 1015 600

8 4908ADHR-125 24 69-1/4 34 34-5/8 8-7/8 20 12-7/8 15 45 195.4 1730 960

10 49010ADHR-125 30 87 42 43 10-1/2 24 13-3/4 18 57 236.6 2718 1130

12 4912ADHR-125 30 87 42 43 10-1/2 24 13-3/4 18 57 236.6 4124 1180

14 4914ADHR-125 36 103 48 51-1/2 12 30 13-3/4 20 69 416.5 4727 1660

16 4916ADHR-125 36 103 48 51-1/2 12 30 13-3/4 20 69 416.5 6262 1690

*Dimensions for “T” option only (1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 with -150(2) COALESCENCE (PALL RING) SURFACE AREA

Submittal Data Information“4900” Series Removable Cover, High Velocity Air/Dirt Separator

401-178

SUPERSEDES: December 8, 2014 EFFECTIVE: September 15, 2015JOB ENGINEER CONTRACTOR REP.

ITEM QUANTITY MODEL NUMBER SIZE

4”

(1) FOR 150 PSI MODEL NUMBERS, REPLACE -125 WITH -150(2) COALESCENCE (PALL RING) SURFACE AREA

SPECIFICATIONS• Designed and constructed per ASME Code Section VIII Div.

1• Registered with the National Board of Pressure Vessel

Manufacturers• Standard Design Pressure and Temperature: 125 psi @

240°F• Particle removal down to 5 microns• Construction: Carbon Steel with exterior red oxide primer

finish• 304 Stainless Steel Coalescence Pall Rings• Taco 4900 units are designed to be self-supporting in the

piping system. Factory review is necessary should any pip-ing loads be present.

CAUTION: LIFTING LUGS FOR RIGGING AND LIFTING USE ONLY, NOT FORANCHORING OR HANGING.FACTORY INSTALLED• Air Vent is suitable for water, max. 50% 0glycol• Blowdown Valve• Flush Valve

OPTIONS• Higher Design Pressures and Temperatures

o 150 psi @ 240°F, Available• Optional System Connection Sizes available• Optional Base Ring

o Add Suffix ‘R’ (4905 thru 4916) Exp. 4912AD-125RNot Available (4902 thru 4904)

PIPESIZE

MODELNUMBER(1)

A DIA.(INCH)

B MAX.(INCH)

C(INCH)

D(INCH)

E(INCH)

F DIA.(INCH

G(INCH)

H(INCH)

K(INCH)

SURFACEAREA(2)

(SQ. FT.)

OPTIMUMFLOW(GPM)

APPROX.WGT.(LBS)

2 4902ADHTR-125 12 32 22 16 1/8 6 – – 9 18 25.4 115 1502 4902ADHR-125 12 32 22 16 1/8 6 – – 9 18 25.4 115 150

21⁄2 49025ADHTR-125 12 32 22 16 1/8 6 – – 9 18 25.4 165 15521⁄2 49025ADHR-125 12 32 22 16 1/8 6 – – 9 18 25.4 165 155

3 4903ADHTR-125 14 28 1/2 24 11 6 12 6 3/4 10 16 32.3 253 2803 4903ADHR-125 14 28 1/2 24 11 6 12 6 3/4 10 16 32.3 253 2804 4904ADHR-125 14 40 1/4 24 20 1/4 6 — — 10 25 54.8 458 3105 4905ADHR-125 20 57 1/2 30 28 3/4 7 1/4 18 13 13 36 117.5 686 5856 4906ADHR-125 20 57 1/2 30 28 3/4 8 7/8 18 13 13 36 117.5 1015 6008 4908ADHR-125 24 69 1/4 34 34 5/8 8 7/8 20 12 7/8 15 45 195.4 1730 96010 4910ADHR-125 30 87 42 43 10 1/2 24 13 3/4 18 57 236.6 2718 113012 4912ADHR-125 30 87 42 43 10 1/2 24 13 3/4 18 57 236.6 4124 118014 4914ADHR-125 36 103 48 48 51 1/2 30 13 3/4 20 69 416.5 4727 166016 4916ADHR-125 36 103 48 48 51 1/2 30 13 3/4 20 69 416.5 6262 1690

Page 28: 4900 Series Air Separators — Standard & High Velocity Series Air Separators — Standard & High Velocity Save money and lengthen the life of system pumps, piping, and components

Hydronic Professionals trust Taco for the highest quality systems, components, technology and support.

Visit www.TacoComfort.com for more information on 4900 Series Air Separators, additional products, systems, software & training.

Taco quality through & through

Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360 Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436

www.TacoComfort.com