© Sprecher Automation 2012 www.sprecher-automation.com SPRECON SPRECON - - E E - - P DQ6 P DQ6 Transformer Differential Protection Protection and Combined Protection and Control Devices

Upload: others

Post on 22-Nov-2021

32 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2012-12 SPRECON-E-P DQ6 EN

© Sprecher Automation 2012

www.sprecher-automation.com

SPRECONSPRECON--EE--P DQ6P DQ6

Transformer Differential ProtectionProtection and Combined Protection and Control Devices

Page 2: 2012-12 SPRECON-E-P DQ6 EN

2

SPRECONSPRECON--EE--P DQ6P DQ6

Page 3: 2012-12 SPRECON-E-P DQ6 EN

3

SPRECONSPRECON--EE--P DQ6P DQ6

Differential protection for:• Two- and three-winding transformer• Short line (considering the maximum current range)• Bay (for maximal three ends, considering the maximum current

range)

Differential- and full motor protection for:• Motor • amplitudes adaptation, vector groups adaptation, rotating field

adaptation and zero current correction are integrated• 4-section characteristic of biased differential protection• improved sensitivity in the case of earth faults with integrated

biased earth current differential protection (with measuring of neutral point current)

• Overexcitation- and und Inrush restraint (with 2. und 5. harmonics) • Stabilisation against current transformer saturation• Many additionally functions

Page 4: 2012-12 SPRECON-E-P DQ6 EN

4

SPRECONSPRECON--EE--P DQ6P DQ6

Designation Code:

DxQx6D … digital

2 … for two winding transformers3 … for three winding transformer

Q … Differential protection U … with Voltage- and Frequency Protection

6 … Family Range

DxQx6-1 Protection devices (Circuit-breaker control and check-back)

DxQx6-2 Protection and Control devices (Circuit-breaker- and disconnector control)

Page 5: 2012-12 SPRECON-E-P DQ6 EN

5

SCADAIEC 60870-5-101/-104 SPRECON-E Designer

SPRECON-E Service Program

SPRECON-V460HMI Workstation

IEC 61850 / IEC 60870-5-104

(LWL)

SPRECON-E-CGateway 2

(redundant)SPRECON-E-C

Gateway 1

SPRECON-E-C

SPRECON-E-P D6-2

OBS

SPRECON-E-P D6-2

OBSSPRECON-E-P D6-2

OBS (One Box Solution)

SPRECON-E-CBay unit

SPRECON-E-CBay unit

SPRECON-E-P D4

Protection device

SPRECONSPRECON--EE--P AS A PART OF P AS A PART OF ENERGY STATION AUTOMATIONENERGY STATION AUTOMATION

SPRECON-E-P ERER 3Earth fault Protector

SPRECON-E-P D6-1Protection device

Page 6: 2012-12 SPRECON-E-P DQ6 EN

6

SPRECONSPRECON--EE--P DQ6P DQ6

D2Qx6• 7I Star / Delta• 7I+1U Star / Delta + voltage input• 8I Star / Star or Star / Delta + frame leakage protection

7I 8I 8I7I+1U

Page 7: 2012-12 SPRECON-E-P DQ6 EN

7

SPRECONSPRECON--EE--P DQ6P DQ6

D3Qx6• 11I Star / Star / Delta with earth fault differential protection

orStar / Delta / Delta with frame leakage protection

• 12I Star / Star / Delta with frame leakage protection

11I11I 11I 12I

Page 8: 2012-12 SPRECON-E-P DQ6 EN

8

SPRECONSPRECON--EE--P DQ6P DQ6

D3QU6• 10I+1U Star / Delta / Delta + voltage input or

Star / Star / Star without Earth current differential protection + voltage input

• 11I+1U Star / Star / Delta with 2 x Earth current differential protection or Star / Delta / frame leakage protection leakage protection + voltage input

10I+1U 11I+1U 11I+1U10I+1U

Page 9: 2012-12 SPRECON-E-P DQ6 EN

9

SPRECONSPRECON--EE--P DQ6P DQ6

IL – measurement of the phase currents per transformer side

IE 1x – measurement of the earth current for earth current differentialprotection (REF)

IE 20x – sensitive measurement of the earth current (frame leakage protection)

U – measurement of voltage (voltage protection, frequency protection) *)

*) Protection functions in preparation (Hardware available!!!)

D2Q6 D2QU6*) D3Q6 D3QU6

*)Variants:Variant / transformer inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U

IE- sensitivity of the earth current transformer 1x

1x/1x or 1x

1x/1x or 1x/1x/

20x 1x1x/1x

or

1x/20x 1x/20x 1x/20x

Page 10: 2012-12 SPRECON-E-P DQ6 EN

10

SPRECONSPRECON--EE--P DQ6P DQ6

*) Enlargement by an optional application of the DIU10C4 module(DIU10C4: 10 DI, 4 DO)

**) optional Outputs for a direct control of engine-done switch devices (not accessibly for the protective part)

Designation of the protection modules:

D2Q6 D2QU6 D3Q6 D3QU6Variants:Variant / Transformer inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U

DI 15-25 15-25 15-25 15-25 15-25 15-25 15-25

DO *) 14-18 14-18 14-18 14-18 14-18 14-18 14-18

PowerRelais (option) **) 2 2 2 2 2 2 2

DQ6 PROT-D2Q6-IE1…………………………….. PR-281

PROT-D2Q6-2xIE1…………………………….. PR-285

PROT-D2Q6-IE1-IE20…………………………….. PR-286

PROT-D2QU6-IE1…………………………….. PR-291

PROT-D3Q6-2xIE1…………………………….. PR-2A5

PROT-D3Q6-IE1-IE20…………………………….. PR-2A6

PROT-D3Q6-2xIE1-IE20…………………………….. PR-2A8

PROT-D3QU6-IE1…………………………….. PR-2B1

PROT-D3QU6-2xIE1…………………………….. PR-2B5

PROT-D3QU6-IE1-IE20…………………………….. PR-2B6

Page 11: 2012-12 SPRECON-E-P DQ6 EN

11

SPRECONSPRECON--EE--P DQ6 FUNCTIONSP DQ6 FUNCTIONS

Reference Type

Implemented protection functionsIEEE C37.2

IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6

Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U

Neutral-Point current sensitivity 1x

1x/1x or 1x

1x/1x or 1x/1x/ 20x 1x

1x/1x or

1x/20x 1x/20x 1x/20x

Differential protection, number of ends 87T PDIF 2 2 2 3 3 3 3

Ground differential protection, number of ends 87N PDIF 1 2 1 2 2 1 2

Switch on protection (SOTF, SOP), assignable to end 50, 50N PIOC x x x x x x x

IL>DT/IDMT, three stages per end, number of ends 50, 51 PTOC 2 2 2 3 3 3 3

IE>DT/IDMT, three stages per end, number of ends

50N,51N, 51Ns PTOC 2 2 2 3 3 3 3

Inrush restraint PHAR x x x x x x x

Overload protection (2 images, assignable to end) 49, 49N PTTR x x x x x x x

Lockout, number of ends 86 PMRI 2 2 2 3 3 3 3

Page 12: 2012-12 SPRECON-E-P DQ6 EN

12

SPRECONSPRECON--EE--P DQ6 FUNCTIONSP DQ6 FUNCTIONS

Reference Type

Implemented protection functionsIEEE C37.2

IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6

Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U

Neutral-Point current sensitivity 1x1x/1x oder 1x

1x/1x oder 1x/1x/

20x 1x1x/1x oder

1x/20x 1x/20x 1x/20x

Circuit breaker failure prot. (CBF), two stages per end, number of ends 50BF RBRF 2 2 2 3 3 3 3

Circuit breaker tripping by up to 6 external signals (PTRC) x x x x x x x

Trip circuit supervision, number of ends 74TC 2 2 2 3 3 3 3

Parameter sets 4 4 4 4 4 4 4

Logic + time stages for optocoupler inputs x x x x x x x

Virtual binary inputs 15 15 15 15 15 15 15

Logic + hold time for output relays x x x x x x x

Measurands, short report x x x x x x x

Event logging, non-volatile RDRE x x x x x x x

Disturbance data recording, non-volatile RADR,RBDR x x x x x x x

Statistics x x x x x x x

Measurand checks, self supervision x x x x x x x

Assistance for test and putting into operation x x x x x x x

Page 13: 2012-12 SPRECON-E-P DQ6 EN

13

SPRECONSPRECON--EE--P DQ6P DQ6FUNCTIONS IN PREPARATIONFUNCTIONS IN PREPARATION

Reference Type

Implemented protection functionsIEEE C37.2

IEC 61850-7-4 D2Q6 D2QU6 D3Q6 D3QU6

Number of current and voltage inputs 7I 8I 7I+1U 11I 12I 10I+1U 11I+1U

Neutral-Point current sensitivity 1x1x/1x oder 1x

1x/1x oder 1x/1x/

20x 1x1x/1x oder

1x/20x 1x/20x 1x/20x

*) Functions in preparation

Overvoltage protection (U>), two stages (*)

59 PTOV x x x

Undervoltage protection (U<), two stages (*)

27 PTUV x x x

Frequency protection (four stages f<, two stages f>) (*)

81 PTUF,PTOF x x x

Negative sequence protection Ineg>, three stages, assignable to end (*)

46 PTOC 2 2 2 3 3 3 3

Starting protection, locked rotor protection (motor protection), assignable to end (*)

49R, 66, 48,

51LRPMRI/PMSS x x x x x x x

Underload protection (motor protection) (*)

37 PTUC x x x x x x x

Circuit breaker failure prot. (CBF), two stages per end, number of ends

50BF RBRF 2 2 2 3 3 3 3

Current annunciation stages, (3x IL>an, 3x IE>an), assignable to end (*) x x x x x x x

Page 14: 2012-12 SPRECON-E-P DQ6 EN

14

Characteristic of the biased transformer differential protection

SPRECONSPRECON--EE--P DQ6 P DQ6

Page 15: 2012-12 SPRECON-E-P DQ6 EN

15

SPRECONSPRECON--EE--P DQ6 P DQ6

Characteristic of the biased transformer earth current differential protection

Page 16: 2012-12 SPRECON-E-P DQ6 EN

16

SPRECONSPRECON--E COMME COMM--3 3 –– ENGINEERING ENGINEERING TOOL FOR PROTECTIONTOOL FOR PROTECTION One Tool for all phases….

• Engineering (Protection Adjusting) • Operating (Documentation / Archiving of all Settings, Measurands,

Events and Disturbance records)• Commissioning and Testing of the Protection (export of the

settings as XML- file for the numerical testing device, Evaluation / Analysis of the network faults, also graphical Analysis by using of COMTRADE- Viewer)

Page 17: 2012-12 SPRECON-E-P DQ6 EN

17

PARAMETRISATION WITH COMMPARAMETRISATION WITH COMM--33

Page 18: 2012-12 SPRECON-E-P DQ6 EN

18

THANK YOU FOR THANK YOU FOR YOUR ATTENTION !YOUR ATTENTION !

Any liability regarding the correctness and completeness of any information and/or specifications in the presentation is excluded. All rights are reserved to alter specifications, make modifications, or terminate models without prior notice. The specifications of a model may vary from country to country.