2010-0201-iom-steampac

76
Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 1 Fulton SteamPac Unfired Steam Generators Installation, Operation and Maintenance Manual Fulton Thermal Corp. 972 Centerville Road Pulaski, NY 13142 Telephone: (315) 298-5121 Facsimile: (315) 298-6390 www.fulton.com Serial # __________________________ Model # __________________________ Fulton Order # __________________________ Sold To __________________________ Job Name __________________________ Date __________________________

Upload: engr-adeniji-adetayo

Post on 14-Sep-2014

61 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 1

Fulton SteamPac Unfired Steam Generators

Installation, Operation and Maintenance Manual

Fulton Thermal Corp. 972 Centerville Road Pulaski, NY 13142 Telephone: (315) 298-5121 Facsimile: (315) 298-6390 www.fulton.com

Serial # __________________________ Model # __________________________ Fulton Order # __________________________ Sold To __________________________ Job Name __________________________ Date __________________________

Page 2: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 2

Page 3: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 3

Table of Contents

Section 1 – Safety Warnings & Precautions

Section 2 – Installation 1. Introduction

2. Placement

3. Transport

4. Location

5. Access

6. Clearance

7. Installation Check Points

8. Ventilation

9. Feedwater

10. Recommended Water Conditions

11. Water Supply

12. Glossary of Water Supply Terms

13. Chemical Dosing

14. The Water Column

15. Water Gauge & Gauge Glass

Installation Instructions

16. General

17. Thermal Fluid Pipework

18. Bolting Sequence

19. System Connections

20. Valves

21. Testing

22. Insulation

23. Thermal Fluids

24. Return Tank and Connecting Pipework

25. Connection to Drains

26. Steam Pipework

27. The Blow-Off Valve

28. The Feed Water Piping

29. The Steam Supply

30. The Steam Safety Valve

31. The Steam Pressure Gauge Assembly

32. Electrical Supply

33. Frost Protection

Section 3 – Operation 1. Unit Description and Application

2. Basic Operation

3. Steam Pressure Controls

4. Feed Pump Control

5. High Steam Pressure Control

6. Steam Safety Valve

7. Steam Pressure Gauge

8. Overload Protection

9. Control Switch

Section 4 – Maintenance 1. Recommended Water Conditions

2. Maintenance Schedule

3. Safety Relief Valves

4. De-scaling

5. Cleaning the Water Probes

6. Feed Pump

7. Electrical Controls

8. Miscellaneous

9. Troubleshooting

Section 5 – Parts & Warranty Section 6 – Product Specs & Data

Page 4: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 4

Page 5: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 5

Section 1

Page 6: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 6

Page 7: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 7

Section 1 – Safety Warnings & Precautions This manual is provided as a guide to the correct operation and maintenance of your Fulton SteamPac

Unfired Steam Generator, and should be permanently available to the staff responsible for the operation

of the SteamPac.

These instructions must not be considered as a complete code of practice, nor should they replace

existing codes or standards which may be applicable.

The requirements and instructions contained in this section generally relate to the standard Fulton

SteamPac Unfired Steam Generator. When installing a packaged unit, this entire section should be read

to ensure that the installation work is carried out correctly.

Prior to shipment, the following tests are made to assure the customer the highest standards of

manufacturing:

a) Material inspections

b) Manufacturing process inspections

c) ASME welding inspection

d) ASME hydrostatic test inspection

e) Electrical components inspection

f) Operating test

g) Final engineering inspection

h) Crating inspection

Note

The installation of Fulton SteamPac Unfired Steam Generators should be carried out by competent personnel in accordance with the standards of the National Fire Protection Association, National or Canadian Electrical Code. All state and jurisdictional codes beyond the scope of the applicable ASME Boiler and Pressure Vessel Codes, for its corresponding classification, should be followed in all cases. Jurisdictional authorities must be consulted prior to installation. All units are crated for fork lift transport. Once uncrated, all units can be transported with a forklift. Under no circumstances should weight be allowed to bear on the jacket, control panel, or fan housing of any Fulton equipment.

Page 8: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 8

Rigging your heater into position should be handled by a competent rigger experienced in handling heavy equipment. The customer should examine the unit for any damage.

Note

All factory piping flanges should have bolts re-torqued before filling of system as bolts may loosen in shipping.

Note

All unions on piping should be tightened prior to operation.

For Your Safety

The following WARNINGS, CAUTIONS and NOTES appear in various chapters of this manual. They are

repeated on these safety summary pages as an example and for emphasis.

• WARNINGS must be observed to prevent serious injury or death to personnel.

• CAUTIONS must be observed to prevent damage or destruction of equipment or loss of

operating effectiveness.

• NOTES must be observed for essential and effective operating procedures, conditions, and as a

statement to be highlighted.

It is the responsibility and duty of all personnel involved in the operating and maintenance of this

equipment to fully understand the WARNINGS, CAUTIONS and NOTES by which hazards are to be

eliminated or reduced. Personnel must become familiar with all aspects of safety and equipment prior to

operation or maintenance of the equipment.

Caution

Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping thoroughly with clean water after leak check has been completed.

Note

Where a condensate return tank is to be fitted, this should: 1. Be vented 2. Have a capacity sufficient to satisfy boiler consumption as well as maintain proper return tank temperature.

Page 9: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 9

3. Vent pipe should not be downsized (This may cause pressure build up in the condensate tank.) 4. Return pipes must not be insulated. This can cause overheating the return system, causing a vapor lock in the pump. 5. See return system instruction manual for detailed instructions.

Note

Care should be taken to ensure that the blow off receptacle used meets the regulations covering such vessels. If in doubt consult a Fulton Representative for advice. Only properly trained personnel should install and maintain water gauge glass and connections. Wear safety glasses during installation. Before installing, make sure all parts are free of chips and debris. Keep gauge glass in original packaging until ready to install. Never operate with lucite gauge glass guard removed or without brass rods for gauge glass protection kit.

Warning

Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.

Warning

Under no circumstances should the water softener water flow limit be exceeded.

Note

After installation is complete and prior to operation the pressure vessel should be cleaned.

Note

a) The non-fused disconnect switch on the control panel that controls the feed water pump should be kept in the “on” position at all times during the boiler operation as well as during the non-operating period of the boiler. b) This switch should be turned “off” only when repairs or adjustments should be made. The pump will continue to operate until the water reaches the correct level in the SteamPac. This level is approximately the center of the water gauge glass.

Page 10: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 10

Warning

Prior to the commencement of any work requiring the removal of cover plates and the opening of the control panel box, the electrical supply to the boiler must be disconnected. When stopping the SteamPac for any extensive repairs, shut off main disconnect switches on both the boiler side as well as the feed water side.

Note

To ensure the continued safety and efficiency of the SteamPac, the schedule of maintenance outlined in this manual should be adhered to.

Note

Fulton recommends that the feedwater treatment should be added between the pump and the SteamPac.

Warning

Make sure main power switch is off before starting work.

Caution

Do not clean the gauge or glass while pressurized or in operation.

Note

All of the above maintenance procedures should be completed by trained personnel. Appropriate training and instructions are available from the Fulton Service Department at (315) 298-7148 or your local Fulton Thermal Representative.

Note

Room temperature not to exceed 100o F.

Page 11: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 11

Section 2

Page 12: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 12

Page 13: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 13

Section 2 – Installation

1. Introduction

a) This manual is provided as a guide to the correct operation and maintenance of your

unfired steam generator, and should be permanently available to the staff responsible for

the operation and maintenance of the unfired steam generator. These instructions must

not be considered as a complete code of practice, nor should they replace existing codes

or standards that may be applicable.

b) In the event that you require after sales service, Fulton Thermal Corporation has a

complete staff of field service technicians, and spare parts are available direct from the

factory. Should you require additional information or assistance on the operation and

maintenance of your unfired steam generator, please contact the Fulton service

department at (315) 298-7148 or contact your local Fulton Representative.

2. Placement a) Proper placement of your unfired steam generator is essential. Attention paid to the

following points will save a great deal of difficulty in the future. Correct placement is the

first step to trouble free installation, operation and maintenance.

3. Transport a) Fulton SteamPacs are skid mounted. Rollers should be placed beneath the frame of the

skid or the fork lift holes in the bottom of the skid may be utilized for positioning in the

installation area.

4. Location 1. Authorities with jurisdiction over any national, local or insurance codes should be

consulted prior to installation to assure compliance.

2. The unfired steam generator should be located as close as possible to the steam users in

order to keep condensation & pressure drop to a minimum.

3. A level, hard surface of non-combustible material is required as a suitable base for

mounting the unit. It is suggested that a 4” containment curb be installed completely

around the unit. In the event of a spill of thermal fluid, the curb will help contain the fluid.

5. Access 1. Access around the unfired steam generator should be provided to facilitate maintenance.

Place the SteamPac with clearances to unprotected combustible materials including

plaster or combustible supports not less than the clearances listed in the table below.

Page 14: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 14

Pipes should not be run within 10” of any control cabinets or combustible material. All

SteamPacs will also require a minimum clearance overhead for personnel access. In

cases where available height is insufficient, a roof or ceiling trap might be considered.

6. Clearance a) Front/Vertical: TBD-Consult the end assembly drawing for the tube bundle

removal length specific to the model purchased.

b) Sides: 18” (0.5m)

c) Rear: 18” (0.5m)

7. Installation Check Points a) Make sure all piping connections are complete and tight.

b) Make sure the pressure controls are adjusted properly.

c) Make sure all electrical connections in the control panel box, the water column, and

elsewhere are secure.

Note

After installation is complete and prior to operation the pressure vessel should be cleaned. In general, ensure that the SteamPac area is in conformance with established boiler room requirements. Review national and local codes.

Note

Where a condensate return tank is to be fitted, this should: 1. Be vented to a safe location 2. Have a capacity sufficient to satisfy boiler consumption as well as maintain proper return tank temperature. 3. Vent pipe should not be downsized (this may cause pressure build up in the condensate tank). 4. Return pipes should not be insulated. This can cause overheating the return system, causing a vapor lock in the pump. 5. See Return System Instruction Manual for detailed instructions.

Care should be taken to ensure that the blow off receptacle used meets the regulations covering such vessels. If in doubt consult a Fulton Representative for advice.

Page 15: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 15

d) Make sure two check valves are installed between the SteamPac and feedwater pump.

e) An end of the line trap should be installed in the SteamPac steam header.

f) There are three valves on the SteamPac: the main blowdown valve, the gauge glass

drain valve, and the water column drain valve. The SteamPac blow off valve supplied

with the SteamPac should be installed on the blow off pipe and connected to a blow off

receptacle of approved design.

g) With a pressure transducer, this control sends out a 4 – 20 ma signal to modulate the

thermal fluid valve. The controller also sends out a 120V signal to energize an air

solenoid on the modulating valve. In the event the steam pressure exceeds the set point

by (X) PSI, the valve will de-energize sending the modulating valve to its fail position.

h) All these procedures should be done in accordance with state and/or local codes. The

water column blow off valve and the gauge glass blow off valve should be connected to

the main blow off line.

Caution

Do not tamper with the safety features of the low water safety cut out.

i) Pressure Relief Valve

1. Limits maximum operating pressure of the SteamPac.

j) Operating Seam Pressure Control

1. Located at the control panel box is a digital process control. The

pressure control regulates the thermal fluid control valve, diverting the

flow of fluid when maximum pressure is reached and opening the valve

when the steam pressure falls below a predetermined level.

k) Sight Glass Isolation Valves

1. The brass sight glass isolation valves are equipped with an internal ball

check. In the event that a sight glass should break, the ball will seat,

preventing the discharge of steam and water. The brass valve stem must

be opened fully to enable this feature. If the valve is in any other position

than full open, the ball will not seat. For added safety all Fulton boilers

are equipped with gauge glass protectors.

l) High Limit Pressure Control

1. Located at the control panel box and connected to the steam pressure

gauge assembly by means of a copper tube. The pressure is usually set

10 to 15 PSI (.703 – 1.054 kg/cm2) above the operating pressure, but

below the maximum pressure of the pressure relief valve. If the pressure

exceeds the high limit pressure control setting, the SteamPac will

automatically shut off.

Page 16: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 16

2. The high limit pressure control must be manually reset by depressing the

plunger located on top of the control.

8. Ventilation a) Ventilation in the room must be sufficient to maintain a building temperature of 100°F or

less.

9. Feedwater a) In its readily available form, water is a corrosive chemical solution having dissolved and

suspended solids and it is therefore, essential that feed water for any steam generating

plant be conditioned prior to use. Specialists in water treatment should always be

consulted.

b) Just with any other type of steam boiler, the generator must be fed with clean soft water

free from calcium and magnesium salts, organic compounds and corrosive reagents. See

the table below for upper limits of water characteristics for the steam generator use.

10. Recommended Water Conditions for Boilers/Unfired Steam Generators a) Following are recommendations for feed water and boiler water. Contact your local water

treatment professional for testing and treatment recommendations. It is very important

that a strict water treatment program be followed.

b) It is critical that the boiler pH follow the attached schedule whenever water is in the boiler.

Solids that enter in with the feed water will concentrate in the boiler. A regular schedule of

boiler blowdown must be maintained to prevent high solid concentrations from corroding

the vessel or forming deposits.

Page 17: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 17

Carbon Steel Stainless Steel Parameter Feedwater Vertical

Boiler/ SteamPac Water

Horizontal Boiler/SteamPac Water

Feedwater Vertical Boiler/SteamPac Water

Horizontal Boiler/SteamPac Water

pH 7.5-9.5 8.5-10.5 8.5-10.5 6.0-9.5 8.5-10.5 8.5-10.5 Feedwater Temperature

140F* --- --- 140F* --- ---

Hardness as CaCO3

< 2ppm < 10 ppm < 15 ppm < 2ppm < 10 ppm < 15 ppm

Chlorides --- --- --- --- 50 ppm 50 ppm Total Alkalinity

--- < 300 ppm < 500 ppm --- < 300 ppm < 500 ppm

Total Dissolved Solids

--- < 2000 ppm

< 3000 ppm --- < 2000 ppm < 3000 ppm

Suspended Solids

No visual turbidity**

No visual turbidity**

No visual turbidity**

No visual turbidity**

No visual turbidity**

No visual turbidity**

Total Organic Carbon

No sheen No foam +

No sheen No foam +

No sheen No foam +

No sheen No foam +

No sheen No foam +

No sheen No foam +

Iron Colorless liquid++

Colorless liquid++

Colorless liquid++

Colorless liquid++

Colorless liquid++

Colorless liquid++

Dissolved Oxygen

<1 ppm* ND ND < 5 ppm ND ND

Visual Oil ND ND ND ND ND ND Conductivity (μS/cm)

--- < 2985 < 4477 --- < 2985 < 4477

NOTES:

*Feedwater temperatures below 200oF will require an oxygen scavenger

** Suspended solids: Take a water sample. After the sample sits for 10 minutes, no solids should be visible.

+ Total Organic Carbon: Take a water sample. Shake vigorously for 30 seconds. No sheen or foam should be visible.

++ Iron: Take a water sample. Hold the sample against a white background. The water should have no visible yellow, red or orange tinge.

ND: None Detected.

11. Water Supply a) The quality of the water used in the boiler will affect the life of the elements and pressure

vessel and it is strongly recommended that a competent water treatment company be

consulted prior to the installation of the boiler. Elements/PV damaged due to adverse

water conditions will not be replaced under warranty.

b) Natural feedwater supplies contain solids and dissolved gases. These may promote

scale, foaming, corrosion, and/or poor steam quality. To prevent this, feedwater must be

studied individually and treated accordingly. The treatment should provide quality

feedwater to the boiler such that corrosion and deposition in the boiler will be minimized.

Thermal cycling, dissolved oxygen, high or low pH can all be major causes of corrosion.

Untreated hardness is the major cause of scale deposits. Poor quality feedwater requires

increased blowdown and increased chemical treatment costs to prevent boiler corrosion

and scaling.

Page 18: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 18

c) One way to lower the amount of dissolved gases in the boiler feed water is to preheat the

feedwater. This option injects live steam into the feedwater to increase the water

temperature to 180 degrees F or higher which removes oxygen and carbon dioxide from

the water.

d) RO/DIWater: Reverse Osmosis / Deionized water is water that all dissolved solids have

been removed. Osmosis is a process that uses a semi-permeable membrane, under

pressure, to reject dissolved salts and allow water to pass through. When a solution of

salt and water is separated by a membrane, the osmotic pressure forces the water

through the membrane, diluting the salt solution. When pressure greater than osmotic

pressure is applied to the salt solution, the membrane allows the water from the salt

solution to pass into the water solution and rejects the dissolved salts. The osmotic

process is reversed, hence, reverse osmosis. RO/DI water has no buffering capacity and

a pH of <6.5. It is corrosive to carbon steel, however, not to stainless steel. Very high

purity steam quality can be obtained with RO/DI water.

e) Electric boiler and unfired steam generators’ pressure vessels made from carbon steel

that use RO/DI water for the supply water will require pH neutralization for vessel

longevity. Electric boilers and unfired steam generators with stainless steel pressure

vessels do not require pH neutralization. ASME Code allows electric boilers to be

manufactured with stainless steel pressure vessels provided RO/DI water is used as the

water supply.

f) The Fulton Warranty does not cover damage or failure that can be attributed to corrosion,

scale or fouling.

12. Glossary of Water Supply Terms a) Dissolved Oxygen: Oxygen that is dissolved in the feedwater will cause the steel in the

boiler and the feedwater system to be attacked by the water in a manner described as

“pitting”. The pits that are produced can vary from tiny depressions to holes large enough

to penetrate the boiler metal and are usually covered with tubercles of iron oxide. Once

pitting starts, it may be extremely hard to arrest. Pitting can proceed at a surprisingly

rapid rate and can occur not only in the boiler proper, but also in pre-boiler equipment

such as ecomomizers, feedwater tanks, and feedwater lines.

b) Sodium Sulfite: Its purpose is to chemically remove the dissolved oxygen left in the

feedwater after the feedwater has been mechanically deareated. Sodium Sulfite reacts

chemically with dissolved oxygen, producing sodium sulfate. Since it is desirable to

remove dissolved oxygen from the feedwater before it reaches a boiler. Sodium sulfite is

best introduced continuously at some suitable point in the feedwater system (the storage

section of the feedwater heater or deareator, six inches below the water line). Chemical

residual control is based on the maintenance of a specific excess of sodium sulfite in the

boiler water. The essential requirement being to maintain in the feedwater at all times

Page 19: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 19

slightly more than enough sodium sulfite to consume all of the dissolved oxygen that slips

through the deareating equipment. Sulfite as a treatment represents the second line of

defense against oxygen corrosion. Primary protection against this type of attack requires

adequate facilities for mechanical deareation of the feed-water plus a vigorous

maintenance program to safe guard against oxygen leakage into the pre-boiler system.

c) Suspended Solids: Suspended solids are the undissolved matter in water, inc-luding

dirt, silt, vegetation, iron oxides, and any other insoluble matter. Normally suspended

solids are expressed in terms of turbidity. Suspended solids may also deposit in low

velocity areas and create fouling. In line filters, or various types of pretreatment can be

used to lower the suspended solids level. Various polymers assist in holding solids in

suspension. Periodic blowdowns will eliminate suspended solids.

d) Alkalinity: Alkalinity is the capacity of a water to neutralize acids. Common water

alkalinities consist of bicarbonate, carbonates, hydroxide, phosphate, and silicate. These

alkalinities, especially bicarbonates and carbonates, break down to form carbon dioxide

in steam, which is a major factor in the corrosion on condensate lines. High alkalinity also

causes foaming and carry over in boilers. Both foaming and carry over cause erratic

boiler operation. When foaming occurs an antifoam should be added or increased. The

reason for the high alkalinity should be determined. It may result from lack of sufficient

blow off. Quite often the source of alkalinity is an overdose of alkaline internal water

treatment chemical.

e) pH: pH is a measure of the degree of acid or base of solution. pH ranges of 8.0-10.5 will

have little influence on the corrosion rate of carbon steel. A low pH can result in corrosion

of metals, while a high pH can result in scale formation or caustic embrittlement. In order

to control boilers and equipment used for the external treatment of make up water, it is

essential that reliable pH measurements be made. RO/DI water will have a pH of 6.0 -

6.5 and will require neutralization if used in a carbon steel vessel.

f) Chlorides: If chloride levels are high enough to cause severe corrosion, they can be

controlled by limiting the cycles of concentration and increasing boiler blowdowns.

Corrosion from chlorides can also be controlled by increasing the amount of corrosion

inhibitor or changing to a more effective inhibitor. Reverse osmosis is another method of

pretreatment to reduce chlorides. Chlorides are a major concern in a stainless steel

vessel.

g) Oil: Oil is not a natural constituent of boiler water; still it can frequently enter a system

through leaks in a condenser or other heat exchanger. Oil can also enter a system

through the lubrication of steam driven reciprocating equipment. Whatever the source,

the presence of oil in boiler water is undesirable. Oil can act as a binder to form scale. In

high heat-transfer areas oil can carbonize and further contribute to the formation of scale

and low pH. Foaming is one indication of oil in boiler water. Its presence can also be

confirmed by first shaking a bottle containing boiler water. If oil is present foam will

Page 20: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 20

result. Often oil in boiler water will originate in the condensate. This contaminated

condensate should be directed to the sewer until the source of the oil is determined and

corrective steps taken.

h) Iron (oxides): Iron in any of its oxide or complex forms is undesirable in boiler water. Iron

in its various forms can originate in the raw water makeup, condensate return water, or

form directly in the boiler as a result of corrosion. It can concentrate in the boiler and it

tends to collect in stagnant areas. If a boiler is using raw water makeup, iron is almost

certain to be a major component of developing scale or create fouling.

i) Water Hardness: Water hardness is the measure of calcium and magnesium content as

calcium carbonate equivalents. Water hardness is a primary source of scale in boiler

equipment. Hardness is removed by softening.

j) Feedwater: Feedwater is the combination of fresh makeup and returning condensate that

is pumped to the boiler.

k) Condensate: Condensate is condensed steam that is normally low in dissolved solids.

Hence, it does not contribute to the dissolved solid content of the feedwater. In addition,

condensate is very expensive to waste. It's been chemically treated, heated, pumped,

converted to steam, and condensed. This costs money and when condensate is returned

to the boiler, money is saved.

Warning

Improper installation or maintenance of gauge glass and connections can cause immediate or delayed breakage resulting in bodily injury and/or property damage.

l) It is critical that the SteamPac pH be alkaline (9-11) whenever water is in the SteamPac.

Solids that enter in with the water concentrate in the vessel. Daily boiler blowdown is

recommended to help prevent the formation of deposits. Consult instruction manual for

proper blowdown procedure.

m) The most common method of water softening is by base or ion exchange, and softeners

of this type are readily available from a number of manufacturers.

n) Periodically, the ion exchange resin bed requires regeneration by flushing through with a

brine solution followed by rising with fresh water.

o) The interval between regeneration is dependent upon the raw water hardness and flow

rate. Softeners can usually be set to initiate the regeneration cycle during periods when

the generator is off line. If this is not possible, it is essential either to install a duplex

softener arrangement or select a return tank of sufficient capacity to provide constant full

water supply during the regeneration period.

p) Peak flow rates should be taken into consideration when selecting a softener. The hourly

raw water throughput will depend on the system condensate return but can be taken at a

Page 21: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 21

maximum of 110% of the generator steam capacity where no condensate return is

expected.

Warning

Under no circumstances should the water softener water flow limit be exceeded.

q) In all cases the water hardness should be tested periodically and prior to starting the

generator to ensure efficient operation of the softener. In no event must unsoftened water

be allowed to enter the steam generator.

13. Chemical Dosing a) In addition to softening the feedwater, it is also important to consider other factors such

as dissolved oxygen and acidity. Depending on the results of an analysis, it may be

necessary to inject appropriate amounts of corrective chemical into the feedwater

system. This is usually achieved by means of a chemical compound solution and variable

output metering pump mounted at the storage vessel. It is important that the chemicals

and quantities are correct and it is advisable to contact a water treatment company to

arrange a feedwater analysis.

14. The Water Column a) Install the piping from the water column and water gauge glass to a safe blow-off point.

15. Water Gauge & Gauge Glass Installation Instructions

Note

Only properly trained personnel should install and maintain water gauge glass and connections. Wear safety glasses during installation. Before installing, make sure all parts are free of chips and debris. Keep gauge glass in original packaging until ready to install.

a) Verify the proper gauge has been supplied.

b) Examine the gauge glass and packings carefully for damage before

installation. Do not use the glass if it contains any scratches, chips, or any other visible

signs of damage.

c) Do not subject the gauge glass to bending or torsional stresses.

d) Apply teflon tape or pipe dope to pipe threads. Install top gauge fitting (fitting without a

drain valve) into the uppermost tapping. Wrench tighten the fitting until it is snug and the

Page 22: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 22

glass outlet is pointing at five o’clock (about 1/8 turn from its final downward vertical

position).

e) Install the bottom gauge fitting (the fitting with a drain valve) until it is snug and the glass

outlet is pointing directly upward. Verify top and bottom fittings are threaded into the

tappings the same number of turns (distance A = distance B).

f) Remove glass packing nut, friction washer and glass packing from the

fittings, and place them, in the same order, on to both ends of the gauge glass. Push both

packings about an inch up the gauge glass.

g) Gently insert one end of the glass into the top gauge fitting. Keeping the glass inside

the top fitting, gently rotate to the top gauge fitting clockwise until vertically aligned with

the bottom gauge fitting, then inset glass into bottom fitting until glass bottoms out on

the shoulder inside the bottom fitting.

h) Carefully raise glass about 1/16” and slide lower glass packing down until the glass

packing contacts the lower gauge fitting. DO NOT allow the glass to remain in contact

with any metal!

i) Carefully slide upper glass packing up as far as possible.

j) Hand tighten both glass packing nuts, then tighten 1/2 turn more by wrench. Tighten only

enough to prevent leakage. DO NOT OVER TIGHTEN! If any leakage should occur,

tighten slightly, a quarter turn at a time, checking for leakage after each turn.

k) Install the protective guard, and utilize automatic ball checks where necessary to help

prevent injury in case of glass breakage.

16. General a) All components exposed to thermal fluid flow, including pipe, valves, and screens, must

not be made out of copper, copper alloys, aluminum, or cast iron. Cast iron is porous to

thermal fluids, and copper and aluminum act as catalysts in the degradation of some

thermal fluids. Carbon or stainless steel, or ductile iron, are recommended.

b) For standard applications, all components must be rated to 650°F unless otherwise

stipulated.

c) All pipework, valves, and user equipment must be suited to the maximum operating

pressure of the heater. Consult the nameplate on the heater for this rating.

d) If an isolating valve is completely closed, the pressure in the system will rise to the

deadhead pressure of the pump. Suitably sized pipe will enable the system to withstand

the total head generated by the circulating pump, should this occur. In applications where

it is desirable to design to pressures lower than the safety relief valve setpoint, an

alternative safeguard is to install additional appropriately sized safety valves.

e) Where secondary circulating pumps are installed, the system must be suitable for the

aggregate head, against a closed valve, of both pumps.

Page 23: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 23

f) During construction of the installation, ensure that no dirt, water, or residue from welding

is left in the system.

17. Thermal Fluid Pipework a) The thermal fluid pipework and main body of the generator should be lagged. Leave the

lower flange of the generator free so that the heat exchanger may be removed

periodically if required.

b) All pipework should be constructed from seamless mild steel pipe, conforming to ASME

SA 106B or SA 53A schedule 40 or equal.

c) Expansion joints or properly designed and sited loops should be provided to

accommodate thermal expansion. Thermal expansion should be calculated using the

maximum possible utilization fluid temperature, regardless of whether the pipe

considered is in the feed or return circuit. Steel pipe will expand approximately 1” per 100’

over a 100°F temperature rise (1 mm per meter over 100°C rise).

d) Supports and anchors must be provided for all pipes where necessary to prevent undue

stresses from being placed on items of equipment, including pumps, valves and the

SteamPac. Supports and anchors which will not interfere with thermal expansion should

be chosen.

e) All pipe joints should be either welded or flanged construction. Screwed joints must be

avoided where possible. In no instance should screwed joints be used in the flow circuit.

f) All flanges should be welded to the pipe and not screwed. Flanges should be 150# of

300# raised face flanges, SA105.

g) Gasketing material suitable for use with thermal fluids at high temperatures should be

used to make all flanged joints. Flexible graphite gaskets are suited for most thermal

fluids. Recommended gasket thickness is 1/10 – 1/8 inch.

h) Ensure that all bolts are tightened evenly and to the torque recommended values

provided by the gasket manufacturer.

i) Gasket Installation Instructions

1. Lubricate nuts, bolts and washers with a graphite/oil mixture.

2. Assure that the flange surfaces are clean and free from damage.

3. Center gasket properly over flange. In retrofit, use pry bar to spread

flange apart enough that then gasket will not be damaged when sliding in

place.

4. Install all flange nuts and bolts.

5. Hand tighten.

6. Utilizing a torque wrench, tighten all bolts to 20% final torque

specification following a “star” pattern. (This means do not tighten bolts in

the order of a clock. This will result in a poor seal

between 12 o’clock and 1 o’clock).

Page 24: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 24

7. Tighten all bolts to 40% final torque specification following a “star”

pattern.

8. Tighten all bolts to 60% final torque specification following a “star”

pattern.

9. Tighten all bolts to 80% final torque specification following a “star”

pattern.

10. Tighten all bolts to 100% final torque specification following a “star”

pattern.

11. Following a sequential pattern, ensure that all bolts are tightened to

100% final torque specification.

12. It is important that all bolts are checked and retorqued after flanges have

been heated and cooled down for the first time.

Page 25: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 25

Standard gaskets supplied by Fulton are JM Clipper Elastograph for operating temperatures up to 650oF.

Recommended Loads for JM Clipper elastograph 150# Gaskets SAE Grade 5 Bolts (typical) or Equal

Nominal Flange Size Inches Number of Bolts

Diameter of Bolts Inches

Preferred Torque Required per Bolt

Ft-Lbs. 1/2 4 1/2 30 3/4 4 1/2 30 1 4 1/2 30

1 ¼ 4 1/2 30 1 ½ 4 1/2 30

2 4 5/8 60 2 ½ 4 5/8 60

3 4 5/8 60 4 8 5/8 60 5 8 3/4 100 6 8 3/4 100 8 8 3/4 100

10 12 7/8 160

Recommended Loads for JM Clipper elastograph 300# Gaskets SAE Grade 5 Bolts (typical) or Equal

Nominal Flange Size Inches Number of Bolts

Diameter of Bolts Inches

Preferred Torque Required per Bolt

Ft-Lbs. 1/2 4 1/2 30 3/4 4 5/8 60 1 4 5/8 60

1 ¼ 4 5/8 60 1 ½ 4 3/4 100

2 8 5/8 60 2 ½ 8 3/4 100

3 8 3/4 100 4 8 3/4 100 5 8 3/4 100 6 12 3/4 160 8 12 7/8 245

10 16 1 160

Page 26: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 26

Standard gaskets supplied by Fulton for operating temperatures above 650oF are Flexitallic Spiral Wound.

Recommended Loads for Flexitallic Spiral Wound Class 150# Gaskets SAE Grade 5 Bolts (typical) or Equal

Nominal Flange Size Inches Number of Bolts

Diameter of Bolts Inches

Preferred Torque Required per Bolt

Ft-Lbs. 1/2 4 1/2 45 3/4 4 1/2 45 1 4 1/2 45

1 ¼ 4 1/2 45 1 ½ 4 1/2 45

2 4 5/8 90 2 ½ 4 5/8 90

3 4 5/8 90 3 ½ 8 5/8 90

4 8 5/8 90 5 8 3/4 150 6 8 3/4 150 8 8 3/4 150

10 12 7/8 240

Recommended Loads for Flexitallic Spiral Wound Class 300# Gaskets

SAE Grade 5 Bolts (typical) or Equal

Nominal Flange Size Inches Number of Bolts

Diameter of Bolts Inches

Preferred Torque Required per Bolt

Ft-Lbs. 1/2 4 1/2 45 3/4 4 5/8 90 1 4 5/8 90

1 ¼ 4 5/8 90 1 ½ 4 3/4 150

2 8 5/8 90 2 ½ 8 3/4 150

3 8 3/4 150 3 ½ 8 3/4 150

4 8 3/4 150 5 8 3/4 150 6 12 3/4 150 8 12 7/8 240

10 16 1 368

Page 27: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 27

18. Bolting Sequence for 4 and 8 Bolt Flanges

a) High point bleeds are to be installed at all high points in the system piping. 1/2” x 12”

nipples welded in the top of the piping with ball valves & plugs attached are to be

used.

b) It will save a considerable amount of time during the cold filtration if the thermal

system piping is cleaned prior to assembly.

c) The mill scale (the results of oxidation) on the inside of the piping as well as

construction debris can foul the oil and cause the need for the filters to be cleaned

more than need be. This can range from simply using a rag to ordering pickled pipe.

(“Pickling” is a process where the piping is first soaked in an acid bath, then soaked in

a neutralizing bath, then given a protective oil coating.)

d) All pipes should be installed with a pitch to facilitate draining and venting.

19. System Connections

a) If screwed connections have to be made, e.g. to items of control equipment, then a

thread sealant suitable for use with fluids at elevated temperature must be used. Teflon

tape, standard pipe dope, or hemp and paste are not acceptable.

b) Screw threads must be carefully and accurately cut. If possible, new tools should be

used. Threaded connections larger than 1” are not to be used. It is recommended that

GR5 or better tensile steel bolts be used for all flanged joints.

20. Valves a) Manual control and isolating valves should be the flanged or weld type, manufactured

from cast or forged steel or ductile iron, with internals and gland seals made from

materials suitable for use with high temperature fluids.

Page 28: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 28

b) When ordering valves, the maximum possible service temperature and type of fluid must

be indicated on the order.

c) A partial list of manufacturers known to market valves of acceptable quality follows:

1. Jenkins Brothers

2. Lunkenheimer Company

3. Nibco Incorporated

4. Stockham Valves and Fittings Company

5. Velan

6. Vogt Machine Company

7. Worcester Valve Company

d) Automatic Fluid Control Valves

1. Because of the widely varied thermal systems, it is not possible to set

down specific rules for the selection of automatic fluid control valves.

Generally, these valves must satisfy the materials and construction

requirements described above.

2. The type of operation and design of porting are governed by the degree

of control required as well as the particular application.

21. Testing a) Upon completion of the installation, a pneumatic test not exceeding 15 psig should be

conducted. Soap tests should be made at all welds and joints to ensure that the system is

free from leaks.

b) Under no circumstances should the system be filled with water. Make sure that the air

supply is as free from moisture as possible.

c) The most satisfactory method of testing is to introduce bottled nitrogen through a

pressure control valve. Check pressure ratings on all the equipment in the system to

make sure that it is capable of withstanding the pressure involved.

d) The time needed to be spent during boilout directly corresponds to the amount of

moisture in the system. Boilout can take anywhere from two to three days to complete.

Pressure testing on the system should be done by means of an inert gas, such as

nitrogen, or by an air compressor producing dry air (air with a dewpoint of 50o F or less).

Never perform a hydrostatic test on the system.

22. Insulation a) After the appropriate system tests have been satisfactorily completed, all hot pipework,

including manifolds on the heater, must be adequately insulated with material suited to

the temperature and application to prevent both heat loss and personnel injury.

b) It is recommended that for inspection and maintenance, pumps, flanges, valves, and

fittings be left un-insulated but suitably shielded for safety.

Page 29: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 29

c) Hot oil pipe insulation should be a minimum of 2” thick, high temperature, laminated,

foamglass cellular glass insulation as manufactured by Pittsburgh Corning Corporation,

or equal.

23. Thermal Fluids Thermal Fluids at Elevated Temperatures

a) Plant engineers must be familiar with the nature of potential hazards when working with

thermal fluids at operating temperatures.

b) Unlike steam or high-pressure water systems, thermal fluid attains extremely high

temperatures without a corresponding increase in pressure. While this lack of high

pressure in the system yields many advantages, a false sense of security should not be

allowed to develop on account of this alone.

c) Certain types of thermal fluid may have operating temperatures reaching 650°F (345°C)

and above, so all exposed pipework is hazardous and should be insulated, as indicated

in the preceding sections.

d) Flanged joints must be checked for tightness during and after the first warming up of the

system. After these checks, exposed hot flanges, pumps, valves and fittings should be

fitted with some sort of shield.

e) It is important to remember that there is pressure generated in the system by the

circulating pump. Great care should be exercised when opening any drain or vent valves

in the system.

d) This is especially important during commissioning, when any air trapped in the system is

vented at high points, and when water, which will flash into steam, is either expelled from

the deaerator vent or drained off at low points.

Caution

During operation, any leaks are usually detected by a small amount of vapor. Leaks should be attended to as soon as possible because under certain circumstances, such as saturated insulation, thermal fluid can ignite when exposed to air and heat.

e) If a fire does occur, extinguish using CO2, foam or dry chemical. DO NOT USE WATER.

f) Selecting a Thermal Fluid

1. The selection of the thermal fluid most suited to your application is very

important. Factors to be considered include efficiency,

thermal stability, adaptability to various systems, and physical properties,

including vapor pressure, freezing point, and flash and fire points.

2. Heat transfer fluids of both mineral and synthetic origin have been

specially developed to give thermal stability over a very wide range of

Page 30: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 30

temperature. A wide variety of thermal fluids have been used

successfully in Fulton Thermal Fluid Heater systems, however, your final

selection should be made in conjunction with Fulton Thermal Corporation

or the fluid manufacturer.

3. The safe maximum bulk temperature of the fluid must be strictly adhered

to. The safe maximum temperature of the fluid varies, but a typical

maximum for many types of mineral oil based fluids is 600°F (320°C).

4. Special care must be taken when consulting fluid manufacturers’

literature, as maximum fluid temperatures quoted are the actual limit to

which any of the fluids may be subjected. It is important to remember

that in any fired heater there exists a “film temperature” which is higher

than the temperature of the “bulk” of the fluid.

5. It is the BULK fluid temperature and NOT the FILM temperature that is

indicated by the instruments.

6. As a general guide, the following list of fluids that have given satisfactory

service over many years is provided.

7. This is by no means a complete list. Any fluid specifically designed for

heat transfer use may be considered; multipurpose oils are not

acceptable. a. AMOCO Transfer Oil 4199

b. CHEVRON Teknifax

c. DOW Dowtherm A or G

d. EXXON Caloria HT 43

e. MOBIL Mobiltherm 603 or 605

f. MONSANTO Therminol

g. MULTITHERM PG1, IG4, IG1

h. PARATHERM Paratherm NF or HE

i. PETROCANADA CalFlo, AF, Purity FG, CalFlo LT

j. SHELL Thermia 23

k. TEXACO Texatherm

8. Any fluid specifically designed for heat transfer use must also exhibit

these characteristics:

a. Be a stable and homogenous liquid to a temperature of

at least 100°F over and above the maximum intended

temperature of utilization, compatible with metals used in

the installation, and tolerating contact with atmospheric

air.

b. The absence of any solid matter in suspension.

c. Non-toxic in the case of leakage.

d. Sufficient lubricity, i.e. not likely to cause seizure.

Page 31: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 31

9. The thermal fluid manufacturer must guarantee the characteristics of the

product, and verify that the fluid bulk temperature limitation exceeds the

expected operating temperature.

10. After a fluid is selected, refer to the manufacturer’s recommendations,

published in compliance with OSHA.

11. If the fluid expansion volume from 50o F to 600°F exceeds 20% of the

initial fluid volume, consult Fulton Thermal Corporation.

Note

Fulton Thermal Corporation cannot be held responsible in the case of accident or damage resulting from the use of inadequate fluid.

g) Routine Analysis of Heat Transfer Fluid

1. Nearly all leading manufacturers of heat transfer fluids provide an after

sales service to monitor the condition of the fluid in operation and make

recommendations when replacement becomes necessary.

2. Each fluid manufacturer has procedures for regular testing and analysis

of the fluid. These usually allow for a sample to be taken and analyzed at

least once a year, although actual frequency will depend on operating

temperature, number of hours operated weekly, and the results of tests

made during the first weeks of system operation.

3. Fulton Thermal Corporation recommends that the thermal fluid in your

system be analyzed within the first two months after start-up.

4. During the first few months of operation, sampling may be carried out at

frequent intervals to confirm that system performance has been

predicted correctly.

5. If the supplier of your thermal fluid does not contact you within four

weeks of commissioning, contact the supplier and make certain that the

“fill” is registered for routine analysis.

h) Thermal Fluid Breakdown

1. The possibilities of thermal fluid breakdown are very slim in a typical

closed loop thermal fluid system. Fulton’s D/A tank creates a “cold seal”

of fluid that is slightly above ambient temperature. This prevents

oxidation that will happen when high temperature fluid contacts air.

2. This will also occur when hot thermal fluid contacts air at a leak in the

system piping. Oxidized thermal fluid becomes acidic and will damage

the thermal fluid system. Thermal fluid breakdown can occur in sections

of piping where there is a low flow

Page 32: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 32

condition. A low flow rate through the heater will result in high film

temperatures leading to breakdown of the thermal fluid.

3. Multiple pressure switches and a differential pressure switch are used to

prevent this condition from occurring. These safeties must not be

bypassed at any time.

4. Exceeding the maximum operating temperature of the thermal fluid will

also result in thermal fluid breakdown. Fulton heaters are equipped with

a temperature limit switch (located on the front of the panel box) to

prevent this from occurring.

5. A high temperature limit switch acts as an over temperature safety

device. If the high temperature limit shuts down the unit, the manual

reset button on the limit switch must be pressed. The reset button on the

flame programmer must also be pressed to reset the unit before it can be

restarted.

24. Return Tank and Connecting Pipework a) Typically Fulton SteamPacs are sold as a completely skidded packaged units which

include: a safety relief valve, steam separator (vertical models only), pressure gauge,

return system complete with feedwater pump plus controls, a blow-off separator,

automatic control valve and accessories similar to those found on a boiler.

b) The return tank is pre-piped on the skid except for the condensate return connection, the

vent connection, the overflow opening and the cold water make up.

c) The feedwater for our standard package should be maintained in a temperature range of

180°F. If higher temperatures are required, contact the factory for proper pump selection.

d) Where there is insufficient condensate return to maintain this temperature, it is

sometimes necessary to provide some alternative method of preheating such as steam

injection. This can be controlled using a thermostat and steam inlet solenoid valve.

e) The vent pipe must rise continuously so there are no low points where condensate could

accumulate and cause an obstruction. It must always terminate open to atmosphere

outside the building and be arranged in a manner which eliminates danger to personnel

or property in the event of a steam discharge.

f) Local water authority requirements must also be met where applicable.

25. Connection to Drains a) Water softener finishing pipes and return tank overflows may be connected to drains in

accordance with water softener manufacturer’s instructions.

b) Blowdown pipe work must run to a suitable catch pit or receiver vessel to be cooled

before connection to the main drains. The blowdown separator may also be equipped

with a cooling kit.

Page 33: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 33

Caution

It is imperative that an adequate vent to atmosphere is provided on all such covered or enclosed vessels which may receive steam.

c) Special care is to be taken to ensure that blowdown lines are properly secured so no

movement (other than expansion) can be caused by the action of steam discharge from

that pipe.

d) Care must always be taken to comply with water board or other authority requirements to

avoid damage to PVC main drains due to the discharge of hot effluent. If cold water is

blended with the effluent to assist cooling, this should usually come from a separate tank

or directly from the main supply.

Note

A deaerator may be supplied in lieu of a return tank. Please consult the manufacturers manual for installation and operation of the deaerator.

26. Steam Pipework a) All pipework and equipment to be fed with steam must either be designed to withstand

the generator safety relief valve setting, or alternatively, an additional safety valve or

valves should be inserted in the service line adjacent to the equipment to be protected.

All steam pipework should comply with all Federal, State and Local Codes.

b) Steam pipework to the plant must be sized to suit the steam flow and pressure. The

correct diameter for interconnecting pipework to the steam generator is at least equal to

the diameter of the main steam outlet valve above the generator.

c) All safety relief valves must be connected to a discharge line of a diameter at least equal

to the discharge port. These lines should be piped directly to outside the building and

terminate in such a way that steam discharge does not create a danger to personnel or

property. Extra care must be exercised when this pipework cannot be of minimal length,

and, if necessary a larger diameter pipe employed to reduce resistance to flow.

d) Discharge pipework is to be installed such that no water can accumulate and a small

drain provided close to the relief valve(s) and piped to a safe place.

Warning

No undue load is to be imposed on the safety relief valve body by this pipework.

Page 34: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 34

e) Allowance must be made for expansion of both the pipework and the generator;

especially if the pipework is rigidly fixed in any place other than adjacent to the safety

valve.

f) All open ended pipes are to be suitable secured to ensure that no movement (other than

expansion) can be caused by the action of steam discharge from that pipe.

g) In cases where multiple generators are to be installed, a header incorporating a steam

trap must be provided. In all instances where generators are connected in parallel with

another steam boiler, it is the responsibility of the customer to comply with Local

Authority, Insurance Company, Factory Act and Health & Safety at Work Act

requirements. These requirements are concerned mainly with maximum pressure, water

contents, safety valves, piping sizes etc.

27. The Blow-Off Valve a) There are two blow off valves on the Steampac: The main valve and the water gauge

glass blow off valve. The SteamPac blow off valve supplied with the boiler should be

screwed to the blow off pipe and connected to a blow off receptacle of approved design.

This should be done in accordance with state and local codes.

28. The Feed Water Piping a) Provisions must be made for adequate water supply and properly sized piping. Piping

must be done in compliance with all local codes.

b) When feeding the SteamPac using a return system, the city water pressure should not

exceed 40 PSI. A pressure reducing valve should be installed a head of the return tank

when above this pressure.

c) It is important that all piping be lined up and not forced into place. It is recommended that

you begin piping at the pump. If the lines are ended at the pump, particularly if the last

piece is cut too short or too long, the pump will be forced to meet the pipe and strain or

distortion will result.

d) Do not use the pump as a piping support. It is critical that the pipe be independently

supported near the pump so no strain will be transmitted to the unit.

e) Connect the feed water stop valve to the feed water pipe and pipe it to the return

system.

29. The Steam Supply a) Pipe the steam supply line from the steam outlet.

Page 35: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 35

30. The Steam Safety Valve a) Before installing, be sure that all pipes and connects have been blown clean. Pipe

compound or dope is used on external threads only. Be sure inlet of valve is free of any

foreign material.

b) Do not use a pipe wrench on flange bolts/nuts! When making installation, use proper

type and size wrench.

c) The valve can be installed in any position (the upright position is preferred) in the

connection provided on the top left side of the boiler with no unnecessary intervening

pipe. Under no circumstances should there be a shut off valve or restriction of any kind

between the safety valve and the connection provided.

d) Do not cap or plug drain hole in the side of valve body.

e) Since the purpose of this safety valve is to protect against an overpressure situation, it

will loudly discharge hot steam in doing so. Therefore, it is recommended that a

discharge pipe be securely installed and run to a safe point of disposal.

f) When a discharge pipe is used, it must be of a pipe size equal to or greater than

that of the valve outlet. Use schedule 40 discharge pipe only. Do not use schedule 80,

extra strong or double extra strong discharge pipe or connections. It must be as short and

straight as possible and so arranged as to avoid undue stress on the valve. It must have

ample provision for draining condensate at or near the valve outlet. It must terminate

freely to atmosphere with no intervening valve of any description and it must be securely

anchored and supported.

31. The Steam Pressure Gauge Assembly a) The gauge should be facing towards the panel box and/or operator of the boiler.

b) Except as noted, each assembly or any of its component parts may be oriented, other

than as shown to provide improved operating clearances and/or view of gauge. Before

installing steam gauge on the siphon, add a small amount of water to the siphon to create

a water seal to buffer the gauge element. This must be done to prevent inaccurate

pressure readings and/or premature failure of the gauge. Install the steam gauge into the

siphon on the water column.

32. Electrical Supply a) A wall mounted, fused disconnect sized for the unit must be provided and fitted by the

customer/contractor if a disconnect is not supplied on the panel.

b) Fuses must be sized according to motor name plates, element ratings, NEC and local

electrical codes.

c) Normal supply will be 460 volts, 3 phase, 60 Hz AC unless otherwise specified. Consult

electrical drawing for specifics relating to your equipment.

Page 36: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 36

d) Make sure the information on the electrical drawings corresponds to your voltage and

frequency. Check the supply voltage and make sure that there is no over or under

voltage exceeding 10% of the nominal value.

e) In all cases, connections to a ground point must be made with correctly sized wire.

32. Frost Protection a) When the unfired steam generator is installed in an unheated area, frost could cause

serious damage to the generator and also to the water softener (when supplied). The

resin bed will be destroyed when the temperature drops below 32°F.

b) It is therefore, advisable to install protective electrical heating with thermostatic control

switching on the protection as soon as temperature becomes too close to 32°F. Should

this have to be done in a very large building it would be preferable to create a small

cubicle around the generator to reduce the volume to be protected.

c) Should, however, frost protection be totally unpractical, the heat exchanger shell and the

water feed pump must be drained as do the water softener, chemical feed, and positioner

on modulating thermal fluid valve.

Page 37: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 37

Section 3

Page 38: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 38

Page 39: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 39

Section 3 – Operation

1. Unit Description and Application a) The basic system consists of a fully automatic oil or gas fired Fulton Thermal Fluid Heater

with circulation pump and expansion tank which delivers high temperature thermal fluid to

the independent unfired steam generator (as well as to other heat exchange equipment).

b) The steam generator, can, therefore be sited where the steam is required thus avoiding

long runs of distribution pipework.

c) The vertical steam generator basically consists of a small diameter cylindrical shell,

inside which is the single or multiple tube heat exchanger, containing the hot thermal

fluid. Water is fed into the bottom of the shell and is turned into steam by means of the

exchange of heat from the thermal fluid. The steam is discharged from the top into a

steam separator immediately above. Dry steam is thus produced. The steam output can

be widely varied with great rapidity. Output is varied by controlling the rate of circulation

of the thermal fluid through the unit by means of a control valve.

d) Since the shell diameter is small, the liquid content is minimal giving very safe operation.

The unit is very compact although relatively tall.

e) It includes various accessories such as safety valve, feed pump, control panel box,

pressure gauge, pressure switches, 3-way fluid control valve feed tank and pipework.

f) The unit thus gives rapid steam raising, with widely varying load and, if required, at

reasonably high pressures due to the small shell diameter. It is fully automatic once put

into operation.

2. Basic Operation a) In the main heat exchanger hot thermal fluid (refer to the original specification/quotation

for minimum required thermal fluid temperature) passes through the tube bundle and is

controlled by the quick acting two or three way control valve. Water is fed into the shell

side of the exchanger from the treated return tank via the boiler and feed pump and feed

check valve(s).

b) Vertical units: The wet steam produced in the heat exchanger passes through into the

steam separator above. Water from the separator returns under gravity to the bottom of

the heat exchanger via feedwater piping. Dry steam flows to the users from the final stop

valve above the separator for vertical units, steam outlet connection for horizontal

models.

c) Horizontal units: Horizontal steampacs consist of custom designed single or multiple to

be heat exchanger, containing the hot thermal fluid, mounted in a large horizontal shell.

Steam is produced in this vessel, passes over the internal baffling and exits through the

steam outlet.

Page 40: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 40

3. Steam Pressure Controls a) The basic controls consist of a thermal fluid control valve which varies the rate of flow of

hot fluid through the heat exchanger. This valve may be modulating type and be either

electric motorized, pneumatic, or solenoid operated. It is this valve’s operations that

controls the steaming rate of the generator. It is operated by means of a steam pressure

switch or control mounted on the control panel which monitors steam pressure.

b) The pressure control, if of the modulating type, will have a set point which it will try to

maintain via an analog output to a three-way control valve (or 2-way modulating valve).

c) When the desired steam pressure has been reached, the pressure switch contacts open

to de-energize the control valve which stops the thermal fluid flow into the generator.

Note

Pneumatic control valves are operated by controlling the air supply to the valve diaphragm by means of a solenoid valve integral to the actuator body. These valves have a spring return and will shut off thermal fluid flow in case of control circuit failure. Minimum 80 PSIG clean, dry instrument air is required. Consult valve O&M manual for SCFH of air required.

4. Feed Pump Control a) Water is fed into the base of the steam generator by the feed pump. This pumps a preset

quantity of water into the generator. The quantity is usually just in excess of the steaming

rate to avoid superheat, afford control, and to carry dissolved solids.

b) The feed pump is controlled by means of a high water level probe or float device located

in the water bottle attached to the side of the steam separator (or steampac).

5. High Steam Pressure Control a) The unit is fitted with an excess steam pressure switch which will shut down both thermal

fluid flow. This is a manual reset switch and must be reset before operation of the unit will

resume.

6. Steam Safety Valve a) The steam safety valve is fitted to the top of the steam generator shell to prevent excess

steam pressure if the controls were to malfunction. It is set at the maximum design

pressure for the generator. When modifying the operating pressure, do not alter the

safety valve setting.

7. Steam Pressure Gauge

Page 41: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 41

a) The steam pressure inside the generator is monitored by a small pressure gauge

mounted at the top.

8. Overload Protection a) The feed pump motor is protected by thermal relays in case of excessive current caused

by voltage variation or malfunction of the feed pump. If the overload operates it must be

manually rest after ascertaining the cause.

9. Control Switch a) The generator is switched on and off by means of a three-way position selector switch on

the control panel Position 1 is “off”. Position 2 is to enable the feed pump only to be

selected in order to fill the unit before start-up. Position 3 is to enable the three-way

control valve to start steam generator.

Page 42: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 42

Page 43: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 43

Section 4

Page 44: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 44

Page 45: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 45

Section 4 – Maintenance Warning

Prior to commencement of any work requiring the removal of cover plates at the opening of the control panel box, the electrical supply to the SteamPac must be disconnected. The unit should be off and cool before performing work on any piping or components.

1. Recommended Water Conditions a) Following are the recommendations for feedwater and boiler water. Contact your local

water treatment professional for testing and treatment recommendations. It is very

important that a strict water management program be maintained.

b) Feedwater 1. Dissolved Oxygen less than 0.005 ppm

2. pH Value 9 to 11 (tested at room temperature)

3. *Hardness less than 50 ppm in the form of

CaCO3

4. Oil None

5. Suspended Solids None

6. Organic Matter None

7. Chloride less than 50 ppm

8. Total Dissolved Solids less than 300 ppm

9. Iron 2 ppm max.

c) Boiler Water 1. Phosphate 30 to 50 ppm in the form of PO4

2. Alkalinity less than 300 ppm in the form of

CaCO3

3. Chloride less than 50 ppm

4. pH Value 9 to 11 (tested at room temperature)

5. Total Dissolved Solids 400 – 2,000 ppm

6. Iron 1 ppm max.

7. Silica 180 ppm max. in the form of

SiO2

8. Hardness less than 50 ppm

9. Dissolved Oxygen None

10. Suspended Solids 15 ppm

11. Oil None

ppm = parts per million; CaCO3 = Calcium Carbonate; PO4 = Phosphate; SiO2 = Silicon Dioxide

*1 Grain Hardness = 17.118 ppm; therefore: 70 ppm = 4.10 grains hardness

Page 46: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 46

d) It is critical that the SteamPac pH be alkaline (9-11) whenever water is in the vessel.

Solids that enter in with the water concentrate in the SteamPac. Daily blowdown is

recommended to help prevent the formation of deposits.

2. Maintenance Schedule Daily a) The following procedures should be carried out daily. They are designed to prevent the

build up of scale, silt or sludge in the SteamPac. In addition to these procedures, the

advice of a water treatment specialist should be sought and followed. An ASME Section

VIII blow off receptacle must be provided for the appropriate pressure.

b) Blow down the SteamPac each morning from the bottom blow down connection

by starting the SteamPac and generating not more that 10 psi of steam.

c) Blowdown the water column each morning for 5 seconds at 10 psi or less

d) Drain gauge glass each morning for 1 second at 5 psi or less.

e) Ensure that chemical treatment/water softener is operating properly.

f) Ensure that the feedwater pump is operating properly.

g) Observe at least 1 cycle of operation to ensure proper operation.

Monthly a) Clean the water column gauge glass.

b) Clean the water pump strainers.

c) Check motor starter contacts for pitting or burns.

d) Check operation of all steam traps on condensate return system.

e) Check tightness of all joints or flanges on the water, steam and thermal fluid piping.

Tighten or replace any leaking valve packing.

f) Check operation of pressure switches/controllers. When the unit is in operation, reduce

the setting of the pressure switches to a value well below that of which they

normally operate. The steam pressure control should shut the fluid control valve.

Semi-Annually a) Clean water level and pump probes with light sandpaper or emory cloth. For float

type water level controllers check float & float housing for unrestricted movement.

b) Drain and flush condensate return tank.

Annually a) Remove hand hole covers and inspect the inside of the pressure vessel. Check

for scale, sludge or pitting. Check tube bundle for fouling. Any of these conditions indicate

improper water management.

Page 47: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 47

3. Safety Relief Valves a) When the valves leave the factory, they have been carefully set and tested to ensure that

the seating surfaces are perfect. However, in service, and when the pressure in the

vessel is neat to the set pressure of the valve, the clamping force between the seating

surfaces is very light and any foreign matter lodged between the two surfaces will cause

the valve to leak.

b) Particles lodged on the seating surfaces are, therefore, the first things to look for in the

case of a leaking valve and it is usually sufficient to flush the seating surfaces. If

however, the seating surfaces have been damaged, it will be necessary to replace the

valve.

4. De-scaling a) The need to de-scale the steam generator is indicated when steam generation becomes

slower and more difficult. Operation of the unit may become erratic.

b) De-scaling is normally carried out chemically by preparing a solution of proprietary

chemical such as “Scale Kleen”, and pouring it into the top of the generator. (Remove the

pressure gauge and use its connection). The pump is run so that the generator is filled. If

possible, some heat is added to warm the solution slightly. Note: It is the responsibility of

the customer to insure that during the descaling of the tube bundle, the tubes are not

chemically attacked and form leaks or cracks.

c) There are two basic ways of ensuring the scale dissolving process continues. Either keep

filling the generator with new solution and drain off the used solution, or use suitable

circulating pump, rubber piping and bucket to continuously circulate the chemical through

the exchanger. Usually the solution changes color, as an indication that the acid is spent.

If necessary, add more solution. Scale cleaning is only completed when no further color

change of new solution takes place. Finally, flush through with an alkali, such as soda

ash (1 oz. Per 250 pounds of nominal steaming rate of the unit) in solution. If desired,

remove the heat exchanger tube bundle and visually inspect the interior.

d) During the cleaning process, the equipment must be vented and no unshielded lights

allowed in the vicinity.

Warning

Follow all safety instructions provided by the manufacturer of the de-scaling chemical. Read the MSDS sheets that are provided. Disposal of spent solution must be done in accordance with local regulations.

Page 48: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 48

Warning

When dissolved, the solution is a severe irritant and must be treated in the same manner as all strong acids. If any of the solution comes into contact with eyes or skin, flush immediately with a large volume of water. If the eyes are affected, seek immediate medical attention.

5. Cleaning the Water Probes a) Clean the probes in the water column. Make sure there is no pressure on the SteamPac

during the removal of the probes. Remove one probe (using 7/8” socket) clean with a

very fine emory cloth and replace it before removing another probe to assure no probe

mix-ups that would change the control functions.

6. Feed Pump a) The better the pump is maintained, the longer its working life will be.

b) In many cases it is not possible to install the pumps in places where they are protected

against frost (especially when used in conjunction with steam generators.)

c) Please follow these special instructions to prevent damage.

d) As soon as the boiler has been shut down, the pumps must be carefully drained.

e) Before the pump is returned to service, the pump should be primed with hot water and

turned several times by hand. Only then should the equipment be started up.

7. Electrical Controls a) Monthly – Check that connection screws have not become loose. Clean electrical

contacts on relays etc. inside the panel with a small brush.

b) Check operation of the controlling pressure switches.

c) When the unit is in operation, reduce the setting of the pressure switches to a value well

below that of which they normally operate.

d) The steam pressure control should shut the fluid control valve.

e) The excess steam pressure switch should shut the fluid control valve.

8. Miscellaneous a) Check tightness of all joints or flanges on the water, steam, and thermal fluid piping.

Tighten or replace any leaking valve packing. Note: Shut off and cool the system prior to

replacing valve packing.

Page 49: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 49

9. Troubleshooting a) The following troubleshooting guide will assist in the diagnosis and correction of minor

field problems. In any case requiring additional assistance, contact your local authorized

Fulton Representative.

b) Feedwater Pump

1. Problem: Pump rotates freely but does not pump.

Check:

1. Excessive feed water temperature (normal maximum

180°F) will result in flashing at

pump inlet. This is usually caused by leaky

check valve between pump and boiler or

failure of steam traps to close tightly. Repair

or replace defective equipment at once

before causing damage to pump.

2. Obstruction in suction line. This can be determined by a

visual check or installing a

compound gauge (reading vacuum and pressure) in the

pump suction line close to the pump. An unrestricted line

will produce a pressure reading on the gauge of

approximately 1 PSIG while the pump is running. A

vacuum reading on the gauge indicates an obstruction,

which must be eliminated. Be sure to remove strainer

basket, scrub clean and reinstall.

3. Motor not up to rated speed. Check speed with

tachometer.

4. Wrong direction of rotation. Check arrow on pump

casing.

5. Broken pump shaft. Check shaft at both ends.

2. Problem: Pump vibrates or is very noisy.

Check:

1. Misalignment of pump and motor. Check coupling and

piping strain.

2. Bent or broken shaft.

3. Pump impeller binding. Check for foreign

matter in pump, bent impeller, or mineral

deposits on impeller, channel ring or spacer. If mineral

Page 50: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 50

deposits occur, have the water analyzed and treated by

a reliable chemical treatment company. Remove any

mineral deposits from pump parts.

4. Worn bearings. Replace.

5. Pump cavitation. High water temperatures

or a suction line restriction, such as a clogged strainer,

will cause cavitation. Any restriction must be corrected

immediately or severe pump damage will result.

3. Problem: Receiver overflows constantly.

Check:

1. Make-up valve seat worn, not sealing tight.

Replace valve.

2. Make-up valve float waterlogged or disconnected.

Replace.

3. Lower the level of make-up water to allow

more tank volume for condensate.

4. Problem: Some Common Causes of Motor Failure.

Check:

1. Tripped starter overload. Reset and check

motor and pump for proper operation.

2. Improper power supply. Check voltage and

motor nameplate data.

3. Incorrect connections. Check wiring diagram.

4. Mechanical failure. Check for free rotation

and examine bearings.

5. Short-circuited windings. Indicated by blown

fuse or failure to start. Motor must be replaced.

6. Overload. Check pump for proper operation and free

rotation.

7. One phase open in three-phase circuit. Check power

supply lines.

5. Problem: Starter overload tripped.

Check:

Page 51: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 51

1. Reset and inspect pump and motor for proper operation.

6. Problem: Motor fails to start.

Check:

1. Make certain boiler level switch is functioning properly.

2. Check control circuit for continuity.

7. Problem: Preheat kit solenoid valve does not open.

Check:

1. Check wiring to the solenoid valve and aquastat.

2. If faulty, replace solenoid and/or aquastat.

Page 52: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 52

Page 53: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 53

Section 5

Page 54: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 54

Page 55: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 55

Section 5 – Parts & Warranty Part Number

Description Approx. lbs.

Weight kgs.

Pressure Switches & Transducers

2-40-000233 Pressuretrol L404C1162-M/R 1.96 .89

2-40-000663 Pressuretrol L404B1320 1.96 .89

2-40-000662 6NNK54FIA SOR Pressuretrol-NEMA 4 1.62 .73

2-40-000661 6R3-D5-SOR Pressuretrol-M/R-NEMA 4 2.1 .95

2-40-000999 Pressure transducer – 0-100psi

2-40-000994 Pressure transducer – 0-200psi

2-40-000998 Pressure transducer – 0-15psi

Temperature Controls/Limits/Thermocouples

2-40-000861 UT 350 Yokogawa 1.2 .55

2-40-000862 UT 350L Yokogawa 1.16 .55

O&M Manuals

5-60-000121 Unfired steam generator manual

SteamPac Components

2-40-000420 Fulton pump relay – 120v .5 .23

2-40-000422 Base for Fulton relay (8pin) .25 .11

2-40-000403 IDIDO Relay 2.0 .91

2-40-000202 Motor starter R4243 – 30amp .52 .24

2-40-000421 120V water level relay

2-40-000423 Base for 120V water level relay (11 pin)

2-40-000229 Pressuretrol L404A1396 2.0 .91

2-40-000960 Model 2705 masonilian press control Obsolete

Miscpart Bourdon tube-ss for masonilian Obsolete

2-30-000139 Fairchild reg mod 10 - 2-way Obsolete

2-12-000004 Handhole gasket .04 .02

2-12-000007 5/8” x 9-1/4” gauge glass .2 .09

2-12-000019 5/8” rubber gasket .004 0.0

2-12-000020 5/8” brass gasket .002 0.0

2-30-000149 ½” water gauge valve w/ball checks 1.5 .68

2-30-000047 ½” tri-cock .42 .19

2-20-000017 Low water cut off probe – 17-1/8” cut to any length .5 .23

2-20-000010 Low water probe .5 .23

2-20-000012 High water probe .5 .23

2-30-000029 ½” float valve .72 .33

2-30-000028 ¾” float valve .76 .35

2-30-000124 4-1/2” float ball only .6 .27

2-12-000534 ½” float valve disc .01 0.0

Page 56: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 56

2-12-000535 ¾” float valve disc .01 0.0

2-30-000332 300# steam gauge .5 .23

Water Column

2-11-000106 Fulton water column bottle casting – 4-100hp 20.0 9.09

5-20-000023 Fulton water column bottle casting – w/tri-cock tappings 20.0 9.09

4-21-000010 Water column electrode basket & cover .5 .23

2-21-000021 Water column probe cover – 4” .05 .02

2-21-000013 Water column probe cover – 4” 1.0 .45

2-45-000128 White wire for probe – per foot

2-45-000128 Black wire for probe – per foot

2-45-000130 Blk/wht striped wire for probe – per foot

2-30-000149 Water gauge glass valves w/ball checks 1.5 .68

4-75-000049 Water gauge glass assy w/valves, rods, and glass 2.5 1.14

2-30-000019 ¼” ball valve .6 .27

2-35-000648 ¼” x close brass nipple

2-30-000398 ¼” MxF ball valve – 200# .6

2-30-000047 Tri-cock .4 .18

2-12-000065 8-5/8” extra heavy gauge glass (9.5hp) .05 .02

2-12-000007 9-1/4” extra heavy gauge glass .1 .05

2-12-000017 9-1/4” water gauge glass – corning .05 .02

2-12-000018 10” water gauge glass .06 .03

2-12-000071 12” water gauge glass .07 .03

2-12-000063 14” water gauge glass .08 .04

2-30-000255 Conbraco 250# GG valve w/ball check (9.5hp) 1.5 .68

2-12-000020 Brass water gauge glass gasket .0018 0.0

2-12-000019 Rubber water gauge glass gasket .004 0.0

2-12-000080 Teflon water gauge gaskets .01 0.0

2-12-000024 8-5/8” gauge glass guard

2-35-000514 Brass packing nut for gauge glass valve .1 .05

2-30-000330 Gauge glass protector rods .04 .02

2-12-000022 Lucite gauge glass guard for 9-1/4” glass .4 .18

2-12-000023 Lucite gauge glass guard for 10” glass .5 .23

2-12-000021 Lucite gauge glass guard for 12” glass (53MM) .06 .03

2-12-000024 Lucite gauge glass guard 9.5hp .045 .02

*NOTE: CUSTOM LENGTHS AVAILABLE

4-30-000052 Set of four (4) water level probes & plugs 6-100hp 1.3 .59

4-30-000042 Set of 3 (3) water column probes .8 .36

2-20-000010 Pump off probe – 7-1/4” .2 .09

2-20-000011 Pump on probe – 9-1/4” .2 .09

2-20-000012 Low water probe in water column – 11-1/4” .3 .14

2-20-000017 Low water probe in boiler – 17-1/2” .5 .23

2-21-000012 Probe cove PV – 2” 1.0 .45

Page 57: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 57

2-20-000057 Auburn plug – WCC-1112KH – 151 to 451 psi .2 .09

2-20-000016 16” brass rod – cut to length .1 .04

2-40-000227 Pressuretrol L404A1354 – 2-15psi 1.7 .77

2-40-000228 Pressuretrol L404A1370 5-50psi 2.0 .91

2-40-000229 Pressuretrol L404A1396 10-150psi 2.0 .91

2-30-000230 Pressuretrol L404A1404 20-300psi 2.7 1.23

2-40-000231 Pressuretrol L404C1147 2-15psi 2.0 .91

2-40-000232 Pressuretrol L404C1154 5-50psi 2.0 .91

2-40-000233 Pressuretrol L404C1162 10-150psi 2.0 .91

2-40-000234 Pressuretrol L404C1139 20-300psi 2.7 1.23

2-40-000101 Pressuretrol L404F1078 5-50psi w/micro switch 2 .91

2-40-000100 Pressuretrol L404F1060 2-15psi w/micro switch 2.0 .91

2-40-000102 Pressuretrol L404F1102 10-150psi w/micro switch 2.0 .91

2-40-000103 Pressuretrol L404F1094 20-300psi w/micro switch 2.0 .91

Miscpart Pressuretrol L404FA1035 – M/R 2-15psi w/micro switch 2.0 .91

2-40-000322 Pressuretrol L404FA1050 – M/R 10-150psi w/micro switch 2.0 .91

2-40-000999 Pressure transducer 0-100psi .5 .23

2-40-000994 Pressure transducer 0-200psi .5 .23

2-40-000998 Pressure transducer 0-15psi .5 .23

2-30-000225 ¼” spring loaded check valve .5 .22

2-30-000297 ½” spring check valve .75 .34

2-35-000395 ¾” spring loaded check valve – 200# 1.75 .8

2-30-000396 1” spring loaded check valve – 200# 2.55 1.16

4-30-000030 1” stainless steel check valve – 200# 3.0 1.36

2-30-000397 1-1/4” spring loaded check valve – 200# 3.8 1.73

2-30-000449 1-1/2” spring loaded check valve – 200# 4.0 1.81

2-30-000601 ¾” swing check valve – 200psi 1.2 .55

2-30-000602 1” swing check valve – 200psi 1.7 .77

2-30-000762 1” swing check valve – 300psi 2.55 1.16

2-30-000603 1-1/4” swing check valve – 200psi 5.75 2.61

2-30-000604 1-1/2” swing check valve – 200psi 5.75 2.61

2-30-000398 ¼ ”MxF ball valve – 200# .6

2-30-000019 ¼” ball valve – 200# .6 .27

2-30-000008 ½” ball valve – 200# .7 .32

2-30-000027 ¾” ball valve – 200# 1.4 .64

2-30-000026 1” ball valve – 200# 1.75 .8

2-30-000001 1” MxF ball valve 2.0 .91

2-30-000017 1-1/4” ball valve – 200# 3.1 1.41

2-30-000018 1-1/2” ball valve – 200# 4.7 2.14

2-30-000025 2” ball valve – 200# 6.35 2.89

2-30-000208 3” ball valve – 200# 18.0 8.18

2-30-000787 ¾” gate valve – 150# 1.2 .55

Page 58: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 58

2-30-000788 1” gate valve – 150# 2.0 .91

2-30-000789 1-1/4” gate valve – 150# 3.2 1.28

2-30-000790 1-1/2” gate valve – 150# 4.9 2.23

2-30-000791 2” gate valve – 150# 6.8 3.09

2-30-000793 3” gate valve – NPT, OS&Y 12.0 4.8

2-30-000391 1” Y type blowdown valve – 225UT- 200# 4.0 1.82

2-30-000392 1-1/4” Y type blowdown valve – 225UT – 200# 5.5 2.5

2-30-000393 1-1/2” Y type blowdown valve – 225UT – 200# 8.4 3.82

2-30-000394 2” Y type blowdown valve – 225UT – 200# 13.5 6.14

2-30-000007 1” Everlasting blowdown valve – 4000A 13.0 5.91

2-30-000014 1-1/4” Everlasting blowdown valve – 4000A 14.0 6.36

2-30-000023 1-1/2” Everlasting blowdown valve – 4000A 23.0 10.45

2-30-000024 2” Everlasting blowdown valve – 4000A 28.0 12.73

2-40-000311 Timer-Mueller/easy 412-AC-RC .5

2-40-000315 Timer-Mueller/easy 618-AC-RC .5 .23

2-30-000130 Timer for automatic blowdown system-omron .8 .36

2-30-000386 1” Motorized valve for automatic blowoff 9.8 4.45

2-30-000387 1-1/4” Motorized valve for automatic blowoff 10.7 4.86

2-30-000403 1-1/2”motorized valve for automatic blowoff 12.6 5.73

2-30-000389 2” hot water solenoid valve – 120v 13.7 6.23

2-30-000144 ½” hot water solenoid valve – 120v 1.8 .82

2-30-000090 ¾” hot water solenoid valve – 120v 1.9 .86

2-30-001080 1” hot water solenoid valve – 120v 4.0 1.82

2-30-001066 ½” steam solenoid valve 2.3 1.05

2-30-000122 ¾” steam solenoid valve – 120v 2.5 1.14

2-30-000146 1” steam solenoid valve – 120v 4.5 2.05

2-30-000147 1-1/4” steam solenoid valve – 120v 4.9 2.23

2-30-000149 1-1/2” steam solenoid valve – 120v 6.3 2.86

2-30-000214 ¾” 15# series 19 V-stamped safety valve 2.0 .9

2-30-000215 1” 15# series 19 V-stamped safety valve 4.3 1.95

2-30-000216 1-1/4” 15# series 19 V-stamped safety valve 6.75 3.1

2-30-000016 1-1/2” 15# series 19 V-stamped safety valve 12.4 5.63

2-30-000217 2” 15# series 19 V-stamped safety valve 14.85 6.75

2-30-000062 ½” - 100# safety valve – 19KDCA100 1.2 .55

2-30-000063 ½” - 125# safety valve – 19KDCA125 1.3 .59

2-30-000143 ½” - 150# safety valve – 19KDCA150 1.3 1.0

2-30-000064 ¾” - 15# safety valve - 13-202-08 1.0 .45

2-30-000065 ¾” - 30# safety valve - 19KEDA30 1.8 .82

2-30-000067 ¾” - 75# safety valve - 19KEDA 75 3.2 1.45

2-30-000068 ¾” - 100# safety valve - 19KEDA100 2.0 .91

2-30-000069 ¾” - 125# safety valve - 19KEDA125 2.0 .91

2-30-000070 ¾” - 150# safety valve - 19KEDA150 1.4 .64

Page 59: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 59

2-30-000071 ¾” - 200# safety valve - 19KEDA200 5.1 2.23

2-30-000073 ¾” - 300# safety valve - 19KEDA300 2.35 1.07

2-30-000074 1” - 15# safety valve - 13-202-08 1.1 .5

2-30-000075 1” - 75# safety valve - 19FEA75 4.0 1.82

2-30-000076 1” - 100# safety valve - 19FEA100 4.1 1.86

2-30-000077 1” - 125# safety valve - 19FEA125 4.1 1.86

2-30-000078 1” - 150# safety valve - 19FEA150 4.1 1.86

2-30-000079 1” - 200# safety valve - 19FEA200 4.0 1.82

2-30-000081 1” - 300# safety valve 5.0 2.27

2-30-000082 1-1/4” - 15# safety valve - 13-213-08 1.85 .84

2-30-000083 1-1/4” - 100# safety valve - 19KGFA100 6.6 3

2-30-000084 1-1/4” - 125# safety valve - 19KGFA125 6.75 2.07

2-30-000085 1-1/4” - 150# safety valve - 19KGFA150 6.8 3.09

2-30-000086 1-1/2” - 15# safety valve - 13-214-08 2.0 .91

2-30-000087 1-1/2” - 100# safety valve - 19KHGA100 12.4 5.64

2-30-000088 1-1/2” - 125# safety valve - 19KHGA125 10.9 4.95

2-30-000089 1-1/2” - 150# safety valve - 19KHGA150 12.3 5.59

2-30-000185 1-1/2” - 200# safety valve - 19KHGA200 12.0 5.59

2-30-000980 Steam trap UB850 ½” 6.0 2.73

2-30-000981 Steam trap UB850 ¾” 6.0 2.73

2-30-000985 Repair kit UB850 4.0 1.82

2-30-000986 880 ½” 125# Armstrong trap 5.5 2.5

2-30-000987 880 ¾” 125# Armstrong trap 5.5 2.5

2-30-001090 890 ½” 125# Armstrong trap 5.0 2.27

2-30-001091 890 ¾” 125# Armstrong trap 5.0 2.27

2-30-000988 Repair kit 7/16” Armstrong trap .1 .05

2-30-001079 Trap gasket .05 .02

2-30-001252 BIHS – 125 ½ 125 Spirex sarco 5.5 2.5

2-30-001251 BIH - 125 ½ 125 Spirex sarco 5.5 2.5

Miscpart 1031 - 125# Watson McDaniel trap 5.5 2.5

Miscpart 1041 - 125# Watson McDaniel trap 5.5 2.5

Miscpart PCA kit .01 0.0

2-35-000518 ¼” steel pigtail siphon for steam gauge assy-short .3 .14

2-35-000519 ¼” steel pigtail siphon for steam gauge assy-long .6 .27

2-30-000202 Pressure & Temp gauge (0-250 degrees F) 1.0 .45

2-30-000174 0-15psi W.C. gas pressure gauge 1.0 .45

2-30-000326 0-30psi Steam pressure gauge .5 .23

2-30-000334 0-60psi Steam pressure gauge .5 .23

2-30-000336 0-100psi Steam pressure gauge .5

2-30-000333 0-200psi Steam pressure gauge .5 .23

2-30-000332 0-300psi Steam pressure gauge .5 .23

2-30-000327 0-600psi Steam pressure gauge .5 .23

Page 60: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 60

2-12-000025 Teflon disc for 1” Y valve .2 .09

2-11-000015 Brass seat for 1” Y valve .1 .05

2-12-000026 Teflon disc for 1-1/4” Y valve .5 .23

2-11-000016 Brass seat for 1-1/4” Y valve .1 .05

2-12-000027 Teflon disc for 1-1/2” Y valve .2 .09

2-11-000017 Brass seat for 1-1/2” Y valve .1 .05

2-11-000018 Brass seat for 2” Y valve .1 .05

2-30-001062 PRV ½” 7-25# 7.0 3.18

2-30-001064 PRV ¾” 7-25# 7.0 3.18

2-30-001061 PRV 1” 50-140# 7.0 3.18

2-30-001065 PRV 1” 7-15# 7.0 3.18

7-75-000000 14 x 24 Horiz. Tank only - HT8 old style 70.0 31.82

7-75-000002 18 x 20 Horiz. Tank only - HT8 new style 80.0 36.36

7-75-000004 18 x 30 Horiz. Tank only - HT10 95.0 43.18

7-75-000006 18 x 36 Horiz. Tank only - HT20 105.0 47.73

7-75-000008 18 x 42 Horiz. Tank only - HT300 115.0 52.27

7-75-000010 24 x 36 Horiz. Tank only - HT50 180.0 81.82

7-75-000012 24 x 48 Horiz. Tank only - HT60 175.0 79.55

7-75-000014 28 x 48 Horiz. Tank only - HT80 215.0 97.73

7-75-000016 30 x 48 Horiz. Tank only - HT100 265.0 120.45

7-75-000017 30 x 72 Horiz. Tank only - HT150-200 300.0 136.36

7-75-000018 36 x 72 Horiz. Tank only - HT250-300 325.0 147.73

7-75-000019 42 x 72 Horiz. Tank only - HT350-400 350.0 159.09

7-75-000040 16 x 20 Vertical Tank only - VT8 old style 65.0 29.55

7-75-000042 18 x 20 Vertical Tank only - VT8 new style 80.0 36.36

7-75-000044 18 x 30 Vertical Tank only - VT10 95.0 43.18

7-75-000046 18 x 36 Vertical Tank only - VT20 105.0 47.73

7-75-000048 18 x 42 Vertical Tank only - VT30 115.0 52.27

7-75-000122 18 x 20 Vertical Tank & Stand - V8T 85.0 38.64

7-75-000124 18 x 30 Vertical Tank & Stand - VT10 120.0 54.55

7-75-000126 18 x 36 Vertical Tank & Stand - VT20 125.0 56.82

7-75-000128 18 x 42 Vertical Tank & Stand - VT30 140.0 63.64

7-75-000130 24 x 36 Vertical Return Tank & Stand 50- VT 225.0 102.27

7-75-000132 24 x 48 Vertical Return Tank & Stand - 60VT 255.0 115.91

7-75-000134 28 x 48 Vertical Return Tank & Stand - VT80 275.0 125.0

7-75-000136 30 x 48 Vertical Return Tank & Stand - VT100 305.0 138.64

7-75-000058 Stand for 18x20, 18x36, 18x42 Vertical tanks 25.0 11.36

7-75-000100 18 x 20 Horiz. Tank & Stand - HT8 125.0 56.82

7-75-000104 18 x 30 Horiz. Tank & Stand - HT10 130.0 59.09

7-75-000106 18 x 36 Horiz. Tank & Stand - HT20 135.0 61.36

7-75-000108 18 x 42 Horiz. Tank & Stand - HT30 140.0 63.64

7-75-000110 24 x 36 Horiz. Tank & Stand - HT50 225.0 102.27

Page 61: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 61

7-75-000112 24 x 48 Horiz. Tank & Stand - HT60 255.0 115.91

7-75-000114 28 x 48 Horiz. Tank & Stand - HT80 275.0 125.0

7-75-000116 30 x 48 Horiz. Tank & Stand - HT100 305.0 138.64

7-75-000118 30 x 72 Horiz. Tank & Stand - HT150-200 380.0 172.73

7-75-000119 36 x 72 Horiz. Tank & Stand - HT250-300 405.0 184.09

7-75-000120 42 x 72 Horiz. Tank & Stand - HT350-400 440.0 200.0

7-75-000035 Horiz. Stand only for 18 x 20 25.0 11.36

7-75-000021 Horiz. Stand only for 18 x 30 25.0 11.36

7-75-000022 Horiz. Stand only for 18 x 36 27.0 12.27

7-75-000023 Horiz. Stand only for 18 x 42 30.0 13.64

7-75-000024 Horiz. Stand only for 24 x 36 35.0 15.91

7-75-000025 Horiz. Stand only for 24 x 48 40.0 18.18

7-75-000026 Horiz. Stand only for 28 x 48 45.0 20.46

7-75-000027 Horiz. Stand only for 30 x 48 55.0 25.0

7-75-000028 Horiz. Stand only for 30 x 72 70.0 31.82

4-75-000018 8-1/2” end plate in herculite 2.0 .91

2-30-000384 8-1/2” end plate gasket for herculite .05 .02

2-35-000567 Float valve bushing – herculite .04 .02

2-20-000079 Magnetic anode 2.0 1.0

4-75-000158 Std. Preheat kit - 8-30HP- does not include sparge tube

150psi

16.0 7.27

4-75-000159 Std. Preheat kit - 40-100HP- does not include sparge tube

150psi

16.0 7.27

4-75-000136 Std. Preheat kit - 8-30HP- does not include sparge tube

150psi

16.0 7.27

4-75-000137 Std. Preheat kit -40-100HP- does not include sparge tube

150psi

16.0 7.27

4-75-000188 Self-actuated preheat kit - 8-30 does not include sparge

tube - 150psi

30.0 13.64

4-75-000189 Self-actuated preheat kit - 40-100 does not include sparge

tube - 150psi

30.0 13.64

4-75-000196 Self-actuated preheat kit -150-200HP does not include

sparge tube - 150psi

***

4-75-000198 Self-actuated preheat kit - 240-400HP -does not include

sparge tube - 150psi

***

4-75-000194 Self-actuated preheat kit - 100-150HP - does not include

sparge tube - 150psi

4-75-000138 Self-actuated preheat kit - 200-400HP - does not

include sparge tube - 150psi

***Special Sparge Tube Required Consult factory

4-50-000074 F-10 Cooling kit – 120v 12.0 5.45

Page 62: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 62

4-50-000078 F-10 Cooling kit – 220v 12.0 5.45

4-50-00075 F20 – 150 Cooling kit – 120v 12.0 5.45

4-50-000079 F20 – 150 Cooling kit – 220v 12.0 5.45

4-50-000076 F10 Cooling kit – self actuated – 120v 20.0 9.09

4-50-000077 F20-150 Cooling kit – self actuated – 120v 20.0 9.09

2-30-000551 Liquid level HG-34 SqD 4.3 1.95

7-21-000035 Venturi steam injector (sparge tube) 7.0 3.18

2-30-001410 Self-actuated preheat valve w/sensor 6.5 2.96

2-30-001411 Self-actuated cooling valve w/sensor – 152F 6.5 2.96

2-30-000362 ½” strainer for preheat kit – Y type 1.0 .45

2-40-000113 Aquastat L6006A1160 1.0 .45

2-40-000112 Aquastat L4006E1067 M/R 110-290 deg. 1.0 .45

2-40-000426 Aquastat T991A1061 1.0 .45

2-30-000205 Well .35 .16

2-30-000123 Hotwater thermometer 1.0 .45

4-75-000010 6-3/4” diameter – end plate with ½” coupling 2.0 .9

4-75-000011 6-3/4” diameter – end plate with ¾” coupling 2.0 .9

4-75-000013 6-3/4” diameter – end plate with 1” coupling 2.0 .9

4-75-000014 6-3/4” diameter – end plate for vertical tank 2.0 .9

2-30-003000 6-3/4” diameter – end plate gasket .05 .02

4-75-000015 7-14” diameter – end plate with ½” coupling 2.0 .91

4-75-000017 7-14” diameter – end plate with ¾” coupling 2.0 .91

2-30-000030 7-14” diameter – end plate gasket .05 .02

4-75-000019 7-14” diameter – end plate for vertical tank 2.0 .91

4-75-000016 8” diameter – end plate with ½” coupling 3.0 1.36

2-30-000031 8” diameter – end plate gasket .05 .02

5-10-000276 9-12” diameter – end plate for vertical tank 3.0 1.36

2-30-002999 9-1/2” end plate gasket .05 .02

5-10-000278 9-1/2” diameter – end plate – HT6-30 3.0 1.36

5-10-000278 9-1/2” diameter – end plate – HT50-300 3.0 1.36

2-30-002005 B&G #6 - ½” water PRV-use when incoming pressure

exceeds 45#

3.0 1.36

2-30-002007 B&G #7 – ¾” water PRV-use when incoming pressure

exceeds 45#

3.0 1.36

4-75-000048 Set gauge glass valve complete with 7” glass & rods 2.0 .91

4-75-000049 Set gauge glass valve complete with 9-1/4” glass & rods 2.5 1.14

2-30-000405 ¼” drain cock .3 .13

2-12-000016 7” water gauge glass .05 .02

4-75-000050 ½” float valve assembly – short rod 2.0 .91

4-75-000052 ¾” float valve assembly 2.0 .91

4-75-000051 ½” float valve assembly - reg. 1.8 .82

4-75-000501 ½” trim kit 10-30HP 4.0 1.82

Page 63: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 63

4-75-000502 ¾” trim kit 50-100HP 4.0 1.82

4-75-000054 1” float valve assembly (HT-200) 2.1 .95

2-30-000029 ½” float valve only .6 .27

2-30-000028 ¾” float valve only .8 .36

2-30-000142 1” float valve only 1.2 .55

2-12-000534 ½” float valve disc .01 0.0

2-12-000535 ¾” float valve disc .01 0.0

2-12-000536 1” float valve disc .01 0.0

2-30-000124 Float ball only .6 .27

2-11-000000 ¼” rod for float valve assembly – short .15 .07

2-11-000001 ¼” rod for float valve assembly – long .2 .09

2-30-000469 Strainer gasket – 1” .001 0.0

2-30-000466 Strainer gasket – 1-1/2” .001 0.0

2-30-000363 1” strainer for return system 4-30HP – 1” inlet/1-1/4” out 3.7 1.68

2-30-000364 1-1/2” strainer for return system 50HP-up-1-1/2” in/1-1/4” out 6.2 2.82

2-30-000365 2-1/2” strainer for return system 8.0 3.64

2-30-000366 Screen for strainer 1” .1 .05

2-30-000367 Screen for strainer 1-1/2” .1 .05

2-30-000368 Screen for strainer 2-1/2” .1 .05

2-30-000971 Strainer cap 1” .5 .23

2-30-000970 Strainer cap 1-1/2” .5 .23

2-30-000607 1-1/4” suction hose – per foot .5 .23

2-30-000608 1-3/4” suction hose – per foot .5 .23

Water Treatment

2-30-001508 EHB10R1-PEH, chemical feeder, tank, agintator-120v 30.0 13.64

2-30-001509 EHB10R2-PEH, chemical feeder, tank, agitator – 120v 30.0 13.64

Miscpart Agitator for chemical feed tank 8.0 3.64

2-30-001502 FB-150-900 , 120V/60 water softener - 4-30 HP 120.0 54.55

2-30-001503 FB- 150-900, 220V/50 water softener - 4-30 HP 120.0 54.55

2-30-001505 FB-450-900 , 120V/60 water softener - 40-60 HP 250.0 114.0

2-30-001504 FB- 450-900, 220V/50 water softener – 40-60 HP 250.0 114.0

2-30-001507 FB- 600-900, 120V/60 water softener - 80-100 HP 310.0 141.0

2-30-001506 FB- 600-900, 220V/50 water softener – 80-100 HP 310.0 141.0

Consult factory for larger sizes

Test Equipment & Tools

2-40-000090 Test leads .6 .27

2-40-000215 Microampmeter – W136 2.0 .91

2-60-000102 Pocket draft meter 1.0 .45

2-60-000103 All purpose draft meter 3.0 1.36

2-60-000104 CO tester – gas 15.0 6.82

2-60-000105 CO tubes .25 .11

2-60-000106 Stack thermometer 4.0 1.82

Page 64: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 64

2-60-000108 Smoke tester – oil 2.0 .91

2-60-000110 Fisher gauge – 50 PZ 1.0 .45

2-30-000123 Hot water thermometer 1.0 .45

2-60-000112 Flue cleanout brush – 1” .8 .36

2-60-000155 Flue cleanout brush – 5/8” Edge .8 .36

2-60-000247 Flue brush – pipetype – 2-1/2” – 80 & 100HP 1.0 .45

2-60-000248 Flue brush – pipetype – 2” – 40/50/60HP VMP (80 oldstyle) 1.0 .45

5-10-000397 Tee handle wrench – 1-1/4” 2.7 1.23

8-00-000043 Fan puller – 5/8” hub 2.0 .91

8-00-000042 Fan puller – 1” hub 2.0 .91

2-30-001580 Burks impeller puller 2.0 .91

2-30-000382 Spanner wrench 1.0 .45

5-10-000394 Oil pump alignment tool 2.0 .9

2-45-000109 Terminal wire gun

Page 65: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 65

Standard Warranty for Fulton Thermal Fluid Heaters

Warranty Valid for Models FT-A, FT-C, FT-S, FT-N, FT-HC

One (1) Year (12 Month) Material and Workmanship Warranty The pressure vessel is covered against defective material or workmanship for a period of one (1) year from the date of shipment from the factory. Fulton will repair or replace F.O.B. factory any part of the equipment, as defined above, provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by Fulton. The commissioning agency must also successfully complete and return the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department. This warranty covers any failure caused defective material or workmanship. Parts Warranty Fulton will repair or replace F.O.B. factory any part of the equipment of our manufacture that is found to be defective in workmanship or material within one (1) year of shipment from the factory provided this equipment has been installed, operated and maintained by the buyer in accordance with approved practices and recommendations made by both Fulton and the component manufacturers and the commissioning agency has successfully completed and returned the equipment Installation and Operation Checklists to Fulton’s Quality Assurance department. General Fulton shall be notified in writing as soon as any defect becomes apparent. This warranty does not include freight, handling or labor charges of any kind. These warranties are contingent upon the proper sizing, installation, operation and maintenance of the boiler and peripheral components and equipment. Warranties valid only if installed, operated, and maintained as outlined in the Fulton Installation and Operation Manual. No Sales Manager or other representative of Fulton other than the Quality Manager or an officer of the company has warranty authority. Fulton will not pay any charges unless they were pre-approved, in writing, by the Fulton Quality Manager. This warranty is exclusive and in lieu of all other warranties, expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Fulton shall in no event be liable for any consequential or incidental damages arising in any way, including but not limited to any loss of profits or business, even if the Fulton Companies has been advised of the possibility of such damages. Fulton’s liability shall never exceed the amount paid for the original equipment found to be defective. To activate the warranty for this product, the appropriate commissioning sheets must be completed and returned to the Fulton Quality Assurance department for review and approval.

9/10/09

Page 66: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 66

Page 67: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 67

Section 6

Page 68: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 68

Page 69: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 69

Section 6 –Product Specs & Data Fulton SteamPac Packaged Heat Exchanger Systems

1. General Description a) Contractor shall furnish and install a_____HP thermal fluid to steam heat exchanger

package. The entire system shall be “Fulton” as manufactured by Fulton Thermal

Corporation, Pulaski, New York. The system shall be a complete package including a

thermal fluid to steam heat exchanger, condensate return tank with pump, blowdown

tank, interconnecting piping with thermal fluid pneumatic control valve provided.

2. Heat Exchanger Size & Operating Temperature a) The heat exchanger shall require thermal fluid at _____ degrees F at a minimum flow

rate of ________GPM. It shall produce a minimum of ___________BHP (from and at 212

degrees F) (___________BTU/Hr.) output as measured at the steam outlet. The heat

exchanger system shall be supplied complete with control panel, thermal fluid control

valve and all required safety devices for a maximum operating steam pressure of 150

PSIG (consult factory for higher operation pressures). The heat exchanger shall

incorporate a steam safety relief valve rated for use with a Section I vessel (“V” stamped)

and the safety valve shall be located on the steam separator; set pressure 150 PSIG

standard and sized according to exchanger maximum steaming capacity.

3. Heat Exchanger Design a) Vertical or Horizontal

b) Factory Piped, Wired and Tested

c) Design Pressure - 150 PSIG

d) Test Pressure: Per ASME Code, Section VlIl, Division I

e) Construction Materials- Carbon Steel ASTM 53B and SA 285C Plate

f) Stamped per ASME Code

4. Steam Separator Vertical Design Units

a) Vertical Centrifugal

b) ASME Code Section l

c) Design Pressure - 150 PSIG MAWP Standard

d) Test Pressure -as per ASME Code Section I

e) Construction Materials -�SA-53B seamless pipe and SA 285C plate

f) Stamped per ASME Code

5. Water Bottle Design

Page 70: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 70

a) Houses probes for electronic water level controller

b) Sight glass incorporated into water bottle for visual inspection of water level

c) Cast construction as per ASME Code Section I

6. Instrumentation & Controls a) The following instrumentation/controls/safety devices shall be supplied as a minimum

requirement:

1. Pressure Gauge – Fulton

2. Operating Pressure Control - Yokogawa UT-350 w/ pressure transducer

3. High Limit Pressure Control – Danfoss

4. Water Level Control - Fulton

5. Pump Motor Starter

6. Thermal Fluid 3-way Control Valve. Contractor to provide: 440/480/3/60

for pump operation and 120 volt/single phase for control circuit. Note:

Smaller Steampacs will have 120 volt/single phase motor.

7. Tests a) Shall include a hydrostatic test of the pressure vessels in the presence of an

inspector having a National Board Commission. He shall certify a Data Report which shall

be delivered with the heater as evidence of ASME Code compliance.

b) Full electrical checks will be performed including testing of all controls and circuitry.

8. Operating Manual a) Instructions for installation, operation, and maintenance of the heat transfer system shall

be contained in a manual provided with each unit.

b) A complete wiring diagram, corresponding to the equipment supplied, shall be part of the

manual and one shall also be affixed to the inside of the heater’s panel box.

Page 71: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 71

Specifications and Dimensions Horizontal SteamPacs

Specifications – Fulton Horizontal SteamPacs from 70 to 350 HP Models FT 070XH 100XH 150XH 180XH 200XH 250XH 300XH 350XH

Steam Output*

LB/HR

KG/HR

2,415

1,096

3,450

1.565

5,175

2,347

6,210

2,817

6,900

3,130

8,625

3,912

10,350

4,695

12,075

5,477

Input

BTU/HR (1000)

KCAL/HR (1000)

2,343

590

3,347

843

5,021

1,265

6,025

1,518

6,694

1,687

8,368

2,108

10,041

2,530

11,715

2,952

Flow Rate

GPM

M3/HR

160

37

228

52

342

78

411

94

456

104

570

130

684

156

798

182

*From and at 212oF (100oC). Steam Output is based in a minimum thermal fluid temperature of 425oF (218oC)

Dimensions – Fulton Horizontal SteamPacs from 70 to 350 HP Models FT 070XH 100XH 150XH 180XH 200XH 250XH 300XH 350XH

A. Width

IN

MM

68

1,727

80

2,032

80

2,032

80

2,032

96

2,438

96

2,438

96

2,438

96

2,438

B. Length

IN

MM

107

2,718

117

2,972

117

2,972

132

3,353

150

3,810

150

3,810

150

3,810

160

3,810

C. Height

IN

MM

75

1,905

110

2,794

110

2,794

110

2,794

112

2,845

112

2,845

112

2,845

112

2,845

All dimensions are based on 550oF thermal fluid temperature and are subject to change based on

specific customer requirements.

Page 72: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 72

Specifications and Dimensions Vertical SteamPacs

Specifications – Fulton Vertical SteamPacs from 10 to 100 HP Models FT 010X 015X 020X 030X 040X 050X 075X 100X

Steam Output*

LB/HR

KG/HR

345

157

517

235

690

313

1,035

470

1,380

626

1,725

783

2,587

1,174

3,450

1,565

Input

BTU/HR (1000)

KCAL/HR (1000)

335

84

502

126

669

169

1,017

256

1,339

337

1,674

422

2,678

675

3,347

843

Flow Rate

GPM

M3/HR

23

5.2

35

8

46

10.5

69

16

92

21

114

26

171

39

228

52

*From and at 212oF (100oC). Steam Output is based in a minimum thermal fluid temperature of 425oF (218oC)

Dimensions – Fulton Horizontal SteamPacs from 10 to 100 HP Models FT 010X 015X 020X 030X 040X 050X 075X 100X

A. Width

IN

MM

84

2,134

72

1,829

92

2,337

92

2,337

92

2,337

92

2,337

92

2,337

92

2,337

B. Length

IN

MM

72

1,829

84

2,134

72

1,829

72

1,829

72

1,829

72

1,829

92

2,337

92

2,337

C. Height

IN

MM

125

3,3175

125

3,3175

125

3,3175

125

3,3175

143

3,632

143

3,632

169

4,93

169

4,293

All dimensions are based on 550oF thermal fluid temperature and are subject to change based on

specific customer requirements. Vertical SteamPac dimensions include feedwater tank and blowdown separator.

All SteamPac accessories including feedwater tanks, feedwater pumps, blowdown separators,

chemical feed and water softeners are available from Fulton.

Page 73: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 73

Page 74: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 74

Page 75: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 75

Page 76: 2010-0201-iom-steampac

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201 Page 76

No part of this Installation, Operation, and Maintenance manual may be reproduced in any form or by any means without permission in writing from the Fulton Companies.

For more of the following patents apply to this unit: U.S. Patent Numbers 4856558, 4884963, 4926789, 4951706 and 5, 145, 345.

Swiss Registration Numbers 119122 and 119243. Swedish Registration Numbers 51873 and 51874. German Patent Number

M9104923.7. Benelux Registration Numbers 21548-01/02, 03/04 and 21548-05/06. French Registration Numbers 0304011,

0304015, and 0304016. Other patents pending.

Fulton Boiler Works, Inc., Fulton Heating Solutions, Inc. & Fulton Thermal Corporation are part of the Fulton Group of Companies, a global manufacturer of steam, hot water and thermal fluid heat transfer systems.