1407 pacific highway, warrawee€¦ · alternative solution report – 1407 pacific highway,...

38
J Squared Engineering Pty. Ltd. ACN 605 793 986 FIRE SAFETY ENGINEERING | ESSENTIAL SERVICES MAINTENANCE MANAGEMENT | BUILDING SERVICES DESIGN NSW Office - PO Box 169, Jindabyne NSW 2627, Phone: 02 6456 1285, Mobile: 0427 571 420 SA Office - PO Box 146, Magill SA 5072, Phone: 08 8390 0462, Mobile: 0412 882 122 [email protected] www.jsquared.com.au 1407 PACIFIC HIGHWAY, WARRAWEE FIRE ENGINEERING REPORT DEVELOPED IN ACCORDANCE WITH THE PERFORMANCE REQUIREMENT OF THE BCA PROTECTION OF OPENINGS EXTENDED TRAVEL DISTANCES REDUCTION IN FIRE RESISTANCE LEVELS FIRE HYDRANT PUMP ROOM DATE: 15 JUNE 2017 REPORT NO: 0379 - REV A FINAL PREPARED FOR: BAINI DESIGN PREPARED BY: J 2 CONSULTING ENGINEERS | FIRE SAFETY ENGINEERING

Upload: others

Post on 29-Jan-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

  • JSquaredEngineeringPty.Ltd.ACN605793986

    FIRESAFETYENGINEERING|ESSENTIALSERVICESMAINTENANCEMANAGEMENT|BUILDINGSERVICESDESIGN

    NSWOffice-POBox169,JindabyneNSW2627,Phone:0264561285,Mobile:0427571420

    SAOffice-POBox146,MagillSA5072,Phone:0883900462,Mobile:0412882122

    [email protected]

    1407PACIFICHIGHWAY,WARRAWEEFIREENGINEERINGREPORTDEVELOPEDINACCORDANCEWITHTHEPERFORMANCEREQUIREMENTOFTHEBCA

    • PROTECTIONOFOPENINGS• EXTENDEDTRAVELDISTANCES• REDUCTIONINFIRERESISTANCELEVELS• FIREHYDRANTPUMPROOM

    DATE:15JUNE2017REPORTNO:0379-REVAFINALPREPAREDFOR:BAINIDESIGNPREPAREDBY:J2CONSULTINGENGINEERS|FIRESAFETYENGINEERING

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    2

    CONTENTS

    EXECUTIVESUMMARY&RECOMMENDATIONS........................................................................................4REQUIREMENTSOFALTERNATIVESOLUTION..........................................................................................4

    1.0INTRODUCTION............................................................................................................................................61.1BasisoftheReport...................................................................................................................................................61.2PurposeoftheReport.............................................................................................................................................61.3LimitationsoftheReport.......................................................................................................................................71.4AssumptionsoftheReport....................................................................................................................................7

    2.0FIREENGINEERINGBRIEF.........................................................................................................................82.1RelevantStakeholders............................................................................................................................................82.2BuildingandOccupantCharacteristics.............................................................................................................82.3Hazards,PreventativeandProtectiveMeasuresAvailable.......................................................................92.4DirectlyrelevantIFEGSub-Systems................................................................................................................11

    3.0ALTERNATIVESOLUTION1–PROTECTIONOFOPENINGS..........................................................123.1Deemed-to-SatisfyProvisions...........................................................................................................................123.2DetailsofBCADTSDeviation.............................................................................................................................123.3RelevantPerformanceRequirement..............................................................................................................133.4AssessmentMethodology...................................................................................................................................133.5AcceptanceCriteria...............................................................................................................................................143.6QualitativeandQuantitativeAssessment.....................................................................................................153.7AssessmentagainstrelevantPerformanceRequirement.......................................................................163.9AssessmentConclusion.......................................................................................................................................17

    4.0ALTERNATIVESOLUTION2–EXTENDEDTRAVELDISTANCES..................................................184.1Deemed-to-SatisfyDeviation.............................................................................................................................184.2DetailsofAlternativeSolution..........................................................................................................................184.3RelevantPerformanceRequirements............................................................................................................184.4AssessmentMethodology...................................................................................................................................194.5AcceptanceCriteria...............................................................................................................................................194.6QualitativeAssessment.......................................................................................................................................194.7AssessmentagainstrelevantPerformanceRequirement.......................................................................214.8AssessmentConclusion.......................................................................................................................................22

    5.0ALTERNATIVESOLUTION3–REDUCTIONINFIRERESISTANCELEVELS................................235.1Deemed-to-SatisfyNon-compliance................................................................................................................235.2DetailsofBCADTSDeviation.............................................................................................................................236.3RelevantPerformanceRequirement..............................................................................................................235.4AssessmentMethodology...................................................................................................................................245.5AcceptanceCriteria...............................................................................................................................................245.6QuantitativeAssessment....................................................................................................................................255.7AssessmentagainstrelevantPerformanceRequirement.......................................................................255.8AssessmentConclusion.......................................................................................................................................26

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    3

    6.0ALTERNATIVESOLUTION4–FIREHYDRANTPUMPROOM........................................................276.1Deemed-to-SatisfyNon-compliance................................................................................................................276.2DetailsofBCADTSDeviation.............................................................................................................................276.3RelevantPerformanceRequirement..............................................................................................................286.4AssessmentMethodology...................................................................................................................................286.5AcceptanceCriteria...............................................................................................................................................286.6QualitativeAssessment.......................................................................................................................................296.7AssessmentagainstrelevantPerformanceRequirement.......................................................................306.8AssessmentConclusion.......................................................................................................................................30

    7.0CONCLUSIONS..............................................................................................................................................317.1Conclusion................................................................................................................................................................317.2SpecificationoftheFinalTrialDesign............................................................................................................317.3MaintenanceRequirements...............................................................................................................................317.4RequirementsoftheAlternativesolution....................................................................................................31

    8.0REFERENCES................................................................................................................................................32AppendixA–DataRelieduponintheFEB/RProcess..........................................................................32CommonAbbreviationsUsedinFireEngineering............................................................................................33ClientDesignandBuildingRegulatoryObjectives............................................................................................33MethodsofAnalysis.....................................................................................................................................................34RelevantIFEGSub-Systems.......................................................................................................................................34AcceptanceCriteriaandFactorsofSafetyfortheAnalysis............................................................................35ApproachesandMethodsofAnalysis....................................................................................................................37ConstructionandCommissioningRequirements..............................................................................................37

    REVISION STATUS REPORT No. & REVISION DATE STATUS WRITTEN CHECKED 0359 REV A 17/01/17 DRAFT

    JS JA

    0359 REV A 15/06/17 FINAL

    JS JA

    COMMERCIAL IN CONFIDENCEThis document contains confidential material that is intended solely for J2 Engineering Pty. Ltd.. The project team and all regulatory authorities shall exercise precautionary measures to ensure that the information contained herein is not to be accessed by any third party. J2 Engineering Pty. Ltd will take no responsibility for the use of any information contained within this report by any third party.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    4

    EXECUTIVESUMMARY&RECOMMENDATIONS

    J2 Fire Engineers have been commissioned to carry out a fire safety engineering analysis and assessment of theproposedapartmentdevelopmentlocatedat1407PacificHighway,Warrawee.ThisreportprovidesaFireEngineeredAlternativeSolutiondevelopedtopermitthefollowingBCAnon-compliancesinthesubjectbuilding.AlternativeSolutions BCA DTS

    ProvisionBCAPerformanceRequirement

    AssessmentMethodology

    Topermitwindowopeningstobelocatedmarginallylessthan3mfromthesideallotmentboundarywithoutrequiringprotectionaspertherequirementsofBCAC3.4.

    C3.2,C3.4 CP2 QualitativeandquantitativeassessmentdemonstratingcompliancewiththeperformancerequirementsunderA0.3(a)(i)viaaperformancebasedapproachpermittedunderA.05(b)(ii).

    Topermitextendedtraveldistancesofupto8.8mtoasingleexitservingtheapartmentsontheupperlevelsofthebuilding.

    D1.4 DP4,EP2.2 QualitativeassessmentdemonstratingcompliancewiththeperformancerequirementsunderA0.3(a)(i)viaaperformancebasedapproachpermittedunderA.05(b)(ii).

    Topermitareducedslabthickness(setdownof30mmtoallowfortilebeds)toachievetherequiredFRLof120/120/120or90/90/90dependingonthelocationofthesetdown.

    B1.4,Spec.C1.1

    CP1,CP2 QualitativeassessmentdemonstratingcompliancewiththeperformancerequirementsunderA0.3(a)(i)viaaperformancebasedapproachpermittedunderA.05(b)(ii).

    Topermitthefirehydrantpumproomtobeaccessedviaastairwaynotcontainedinafireisolatedshaft.

    E1.3 EP1.3 QualitativeassessmentdemonstratingcompliancewiththeperformancerequirementsunderA0.3(a)(i)viaaperformancebasedapproachpermittedunderA.05(b)(ii).

    REQUIREMENTSOFALTERNATIVESOLUTION

    Considering the relevant provisions of the BCA, the Alternative Solution, subject to the provision of the followingrequirements,isconsideredtomeetandcomplywiththePerformanceRequirementCP1,CP2,DP4,EP1.3andEP2.2:

    AlternativeSolution11. Bedroomwindows1and2withinunitsG.1,1.1and2.1shallbeprovidedwithmetallicflyscreens,suitablefor

    use in bushfire prone areas as per the requirements of AS3959, with maximum 2mm aperture size.Alternatively,thesewindowscanbefixedintheshutposition.

    2. Bedroomwindows2and3,andthebathroomwindowwithinunitsG.4and1.4shallbeprovidedwithmetallicflyscreens,suitableforuseinbushfireproneareasaspertherequirementsofAS3959,withmaximum2mmaperturesize.Alternatively,thesewindowscanbefixedintheshutposition.

    3. Bedroom windows 1 and 2, and the bathroom window within unit 2.4 shall be provided with metallic flyscreens, suitable for use in bushfire prone areas as per the requirements of AS3959, withmaximum 2mmaperturesize.Alternatively,thesewindowscanbefixedintheshutposition.

    AlternativeSolution24. Theentrydoorwaystothestairwaysonlevels1and2shallbeconfiguredasself-closingsmokedoorswhich

    shallbeprovidedwithmediumtemperaturesmokeseals.Theconstructionaroundthewallsandceilingshallberesistanttothepassageofsmokethroughsealingofanypenetrationsthroughthewall/ceilingconstructionofthestairwayonthesetwoupperlevels.

    5. ThedoorwaysopeningintothelobbyfromtheSOUsandservicesroomonthegroundfloorshallbeprovidedwithmediumtemperaturesmokeseals.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    5

    AlternativeSolution36. Theminimumslabthicknessatthepointofsetdownmustnotbelessthan150mmatanylocation.7. Theminimumconcretecoveronanysteelreinforcementbarsrunninghorizontallywithintheslabshallnotbe

    lessthan30mm.

    AlternativeSolution48. The fire hydrant pump room shall be provided with fire rated construction achieving a minimum FRL of

    120/120/120withtheentrydoorwayachievingaminimumFRLof-/120/30.9. The wall bounding the carpark and the stairway/corridor leading to the fire isolated stairway shall be

    provided with fire rated construction achieving a minimum FRL of 120/120/120 with the exit doorwayachievingaminimumFRLof-/120/30.

    10. Thefirehydrantpumpshallbeautomaticallyoperatedfromapressureswitch,flowswitchorsimilar.Maintenance11. The recommendations of this reportmust form part of the fire safety certificate and the annual fire safety

    statement for the building to ensure the recommendations of this report are compliedwith throughout thebuildingoperation.

    TheAlternativeSolutionhasbeendevelopedusingcomparisonwiththeDeemed-to-SatisfyProvisionsandaqualitativeandquantitativeassessment, and is considered to complywithBCAPerformanceRequirementCP1,CP2,DP4,EP1.3andEP2.2.TheBCArecognisestheseAssessmentMethodasacceptablemethodsfordeterminingthattheAlternativeSolutionsatisfiesthePerformanceRequirementinaccordancewithBCAClausesA0.3(a)(i)andA0.5(b)(ii).

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    6

    1.0INTRODUCTION

    J2 Fire Engineers have been commissioned to carry out a fire safety engineering analysis and assessment of theproposedapartmentdevelopmentlocatedat1407PacificHighway,Warrawee.ThisreportprovidesaFireEngineeredAlternativeSolutiondevelopedtopermitthefollowingBCAnon-compliancesinthesubjectbuilding.

    • Topermitwindowopeningstobelocatedmarginallylessthan3mfromthesideallotmentboundarywithoutrequiringprotectionaspertherequirementsofBCAC3.4.

    • Topermitextendedtraveldistancesofupto8.4mtoasingleexitservingtheapartmentsontheupperlevelsofthebuilding.

    • Topermitareducedslabthickness(setdownof30mmtoallowfortilebeds)toachievetherequiredFRLof120/120/120or90/90/90dependingonthelocationofthesetdown.

    • Topermitthefirehydrantpumproomtobeaccessedviaastairwaynotcontainedinafireisolatedshaft.Thisreportdemonstratesthatupontheadoptionofsuitablealternativesolutions,asdetailedintheExecutiveSummaryofthereport,therelevantPerformanceRequirementoftheBuildingCodeofAustralia(BCA)willbemet.

    1.1BasisoftheReport

    ThisAlternativeSolutionReportisbasedonadesktopassessmentofthefollowingdocumentation:

    • BuildingCodeofAustralia2016,publishedbytheAustralianBuildingCodesBoard(ABCB)• InternationalFireEngineeringGuidelines2005,publishedbyAustralianBuildingCodesBoard(ABCB)• TheGuidetotheBCA2016,publishedbytheAustralianBuildingCodesBoard(ABCB)• ArchitecturaldetailspreparedbyBainiDesignasfollows:

    DrawingNumber Revision01 B03 B04 B05 B06 B07 B08 B09 B10 B11 B

    PreparationoftheAssessmentReportwillsatisfytherelevantPerformanceRequirementsoftheBCAthroughabsoluteassessmenttechniques.

    Nootheraspectsorpartsofthebuildingapartfromthealternativesolutionsasoutlinedabovewillbeassessedandtheremainderof theproposeddevelopment isassumedtocomplywith therelevantDTSprovisionsor thePerformanceRequirementoftheBCA.

    1.2PurposeoftheReport

    Thisreporthasbeenpreparedtoaddressnon-compliancematterswith theDeemed-to-SatisfyProvisionsof theBCA(as tabled in the Executive Summary), and to provide an Alternative Solution developed in accordance with theprovisionsoftheBCA.Thepurposeof this report is todemonstrate that theproposeddevelopmentwill satisfyPerformanceRequirementsCP1,CP2,DP4,EP1.3andEP2.2asthedesignisatleastequivalenttotherelevantDeemed-to-SatisfyprovisionsoftheBCAand/orsatisfiesthePerformanceRequirementoftheBCA.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    7

    This report is prepared for the purposes of submitting to the Certifying Authority (CA) for acceptance prior to theissuingofaConstructionCertificaterelevanttotheproposal.

    1.3LimitationsoftheReport

    Thisreportexcludesanyworksnotoutlinedabove,howeverspecificallyexcludesthefollowing:• Determining full compliancewith theBCA,other than thematters identified in theexecutive summaryof this

    report;• AddressinganymattersthatareoutsidethescopeorlimitationsoftheBCA;• AmendmentstotheAlternativeSolutionBriefduetodesignchangesorincapacitytocomplywiththeTrial

    Designs;• IssuingofanyPart4AcertificatespursuanttotheEnvironmentalPlanningandAssessmentAct1979.Thisreport

    isnotaPart4AcompliancecertificateundertheEnvironmentalPlanning&AssessmentAct1979orRegulation2000;

    • Considerationofanyfireservicesoperations(includinghydraulic,electricalorothersystems);• Consideration of any structural elements or geotechnical matters relating to the building, including any

    structuralorotherassessmentoftheexistingfireresistancelevelsofthebuilding;• ThisreportdoesnotprovideconcessionsforanyAlternativeSolutionorexemptionsfromtherequirementsof

    theBCA,otherthanthatidentifiedintheExecutiveSummaryofthisreport;• DeterminingcompliancewiththeDisabilityDiscriminationAct1992orPartD3oftheBCA;• Reportingonhazardousmaterials,OH&Smattersorsitecontamination;• Anyenergyefficiencyassessment;howeverifnecessary,proposalscanbeobtainedfromsuitablyqualifiedand

    accreditedassessors.

    1.4AssumptionsoftheReport

    This report provides an Alternative Solution for the Deemed-to-Satisfy non-compliance identified in the ExecutiveSummary.Theremainderof thebuilding isassumedtocomplywiththeDeemed-to-SatisfyProvisionsof theBCAforthepurposeofthisreport.Thereportisprovidedonthebasisthat:• TheAlternativeSolutiononlyappliestopropertydetailedinsection2.2.• TheAlternativeSolutionisapplicabletothedesigndocumentationprovidedforassessmentandaslistedin• Section 1.1. Any future alteration, enlargement or addition will require re-assessment to determine the

    applicationofthissolutiontothosechanges.• TheBuildingwill generally complywith theDeemed-to-Satisfy Provisions of theBCA, exceptwheremodified

    specificallybythisreport.• It is assumed that the building will be subject to ongoing annual maintenance and the fire safety measures

    requiredbythisreportandtheBCAwillbemaintainedtoastandardnotlessthantheirinstallationstandard.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    8

    2.0FIREENGINEERINGBRIEF

    The development of this report follows a consultative process with the Certifying Authority and the Developer’sRepresentative. In lieu of submitting a formal Fire Engineering Brief (FEB) for this project, the proposed fireengineeringassessmentwasdiscussedandagreeduponwiththecertifyingauthoritypriortocompletionofthisreport.FurtherdetailsofthedatarelieduponintheFEB/FERprocessaredetailedinAppendixA.

    2.1RelevantStakeholders

    Stakeholder/Role NameCertifyingAuthority CertifiedBuildingSpecialistsArchitect BainiDesign–RomanTalatoFireEngineer J2ConsultingEngineers–JamesSunjaya,James

    Alexander

    2.2BuildingandOccupantCharacteristics

    GeneralBuildingCharacteristics

    BuildingCharacteristic DescriptionOccupancy/UseBuildingClass/es:Typeofconstruction:StoreysContained;RiseinStoreys:EffectiveHeight:

    ResidentialunitsandassociatedcarparkingonthebasementlevelsClass2,7aTypeA4411.7m

    Location:Generaldescriptionofdevelopment:

    1407PacificHighway,WarraweeThedevelopmentproposestoconstructthreestoreysofapartmentsatopabasementlevelcarparkassociatedwiththeapartmentbuildingabove.

    OccupantCharacteristics

    OccupantCharacteristic DescriptionTypeandnumber Occupants would generally be expected to be capable of caring for themselves

    consistent with residential housing use. It is not anticipated that more than acombined50peoplewouldnormallyinhabitthetwelveresidences.

    Occupantstate Building occupants could be both awake and asleep. Occupants may also beintoxicatedorsober.Occupantsonalllevelswouldbeexpectedtohaveareasonablelevelofmobilitytocomfortablynegotiatethestairsaccessonaday-to-daybasis.

    Physical and mentalattributes

    Themajority of occupants are considered to bemobile and ambulatory. Given thebuilding contains only fourteen units it is possible that a relationship will existbetween occupants, which would not normally be the case in a multi-storeyresidentialunitdevelopment.

    Assistancerequired/available

    Itwillbelikelythatassistancewillnotberequiredastheoccupantswillbefamiliarwiththelocationoftheexitsandthepathstotheexitsgiventhesimplelayout.TheassistanceavailablewillbeintheformoftheBuildingOccupantWarningSystem

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    9

    OccupantCharacteristic Descriptiontohelpoccupantsinanevacuation.Assistancemayalsobeprovidedfromotherablebodiedoccupants.

    TrainingandRoles Occupantsareconsideredtohavelimitedtrainingorexperience.Hazards Kitchencookingareas.

    Occupantssmokinginapartments.Electricalequipmentlocatedincorridorsprovidingelectricitytotheresidentialpartsaswellascommunicationscablingandequipment.Carrelatedfireinthebasementcarpark.

    2.3Hazards,PreventativeandProtectiveMeasuresAvailable

    Thefollowinghazardshavebeenidentifiedinthesoleoccupancyunits.Hazard Details/Precaution

    GeneralLayoutandDesign Nohazardsidentifiedwithdesign.Activities Informationisnotavailabletosuggestthatactivitiesoutsidethose

    normally undertaken in residential house will be carried out andhencethehazardisnotconsideredtobeincreased.

    Cooking - NSWFB statistical dataindicates that these firesmake up 33%ofallreportedresidentialfires.(NSWFB2001/2002)

    A smoke alarm or detection system would notify occupants torespond to cooking fire outbreaks if unattended. If the outbreakdevelops beyond that controllable occupants are required toevacuate.

    Occupants smoking in Sole OccupancyUnits (SOU’s). NSWFB statistical dataindicates that fires in sleeping areasmakeup44%ofallreportedresidentialfires. These predominantly includesmokinginbedandcombustiblesplacedupon or near heaters. (NSWFB2001/2002)

    A smoke alarm or detection system would notify occupants torespond to smoking related fire outbreaks if unattended. If theoutbreakdevelopsbeyondthatcontrollableoccupantsarerequiredtoevacuate.

    Electrical equipment failure located inSOU’s,concealedspacesorcarpark.

    SOUhabitablespaceA smoke alarm or detection system would notify occupants torespond to electrical fires. If the outbreak develops beyond thatcontrollableoccupantsarerequiredtoevacuate.ConcealedspacesTheroofvoidhazardislimitedtodownlightsandelectricalwiringasanignitionsourcewhichmakesupaverysmallpercentageofthenumber firestartsaccordingtheNSWFBstatisticaldata,hencetheroofvoidhazardisconsideredlow.CarparkandcommonareasElectrical failure is limited to Power outlets lighting and garagedoorfunctionsinthecarpark.Consideredaverylowlevelofhazard.

    Multiple arson attack, malicious acts,andactsofterrorism.

    The resulting impact of fires from these hazards has not beenaddressedinthisreportastheyarebeyondthescopeoftheBCA.

    Thehazardsthatarepresentinthebuildinghavebeenremovedorreducedbysixsub-systemsofpreventativeandprotectivemeasures.Sub-System PresentinBuilding/Requirements

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    10

    Sub-System PresentinBuilding/Requirements

    AFireinitiation,development

    andcontrol

    Fire loads or heat release rates are not proposed to be in excess of a normalresidentialunitoccupancyandhence firedevelopmentwillnotbeabnormallyfast.

    BSmokedevelopment,spread

    andcontrol

    DTScompliantboundingconstructionbetweenSOU’swillpreventsmokespreadtoneighbouringunits.Theenclosingofthestairintoashaftassistsinimprovingtenabilityconditionsforbuildingoccupantsseekingegressintheeventofafire.

    CFirespread,impactand

    control

    Fire separation between the SOU’s is compliant and provides an FRL of90/90/90 between units. Minor setdowns in the slab for the wet areas areprovidedwhich are addressedwithin an alternative solution containedwithinthisreport.

    DFiredetection,warningand

    suppression

    An AS1670.1 smoke detection system or AS3786 smoke alarms will notifyoccupants toa fireoutbreak.Occupantsof theunit are likely tobenotifiedbyotheroccupantswithintheunitviaverbalcommunicationintheeventthattheyarelocatedremotefromthefire.

    EOccupantevacuationand

    control

    Exitstoopenspaceareavailablefromeachunitwithoutpassingthroughorbyunprotectedopeningsoftheotherunit.

    FFireservicesintervention

    ThebuildingisservedbyfulltimefirebrigadepersonnelattheHornsbyNSWFBstationwhichislocated5.0kmfromthesite.Onthisbasis,itisconsideredthatfire services intervention is likely exceed or at least equivalent to mostresidentialareasinsuburbanSydneymetropolitanarea. Thedirectionstositefromthestationcanbeseeninthefigurebelow.

    The nearest alternate fire station is the Gordon fire station which is located5.2kmfromthesite.

    *InternationalFireEngineeringGuidelines2005(IFEG)Sub-systemA –FireInitiationandDevelopmentandControlSub-systemB –SmokeDevelopmentandSpreadandControlSub-systemC –FireSpreadandImpactandControlSub-systemD –FireDetection,WarningandSuppressionSub-systemE –OccupantEvacuationandControlSub-systemF –FireServicesIntervention

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    11

    2.4DirectlyrelevantIFEGSub-Systems

    ThedirectlyrelevantIFEGsub-systems(SS)forthisanalysisare:IFEGSub-System Description SymbolSub-systemBSmokeDevelopment,SpreadandControl

    • Smokesealsondoorsenteringstairway

    Sub-systemCFireSpreadandImpactandControl

    • Solidcoredoorsfittedwithself-closersfittedtoegressstairwayEnsuring minimum concrete cover is retained oversteelreinforcement.

    Sub-systemFFireServicesIntervention

    • Fire rating of doorset leading to corridor to protectfirefightersfromtheeffectsoffirewithinthecarparkareaofthebuilding.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    12

    3.0ALTERNATIVESOLUTION1–PROTECTIONOFOPENINGS

    AnalternativesolutionhasbeendevelopedtoaddresstheproposeddeviationfromtheDTSprovisionsofC3.2relatingtoallowingopeningswithinawallrequiredtoachieveafireresistanceleveltoremainunprotectedwithoutprovisionofwindowwettingfiresprinklers(asrequiredtosatisfyclauseC3.4).Thesolutionproposestoconsiderthesizeofthewindowopeningsandthesetbackofthewindowsfromtheboundarywhichappeartobemarginallylessthan3mfromtheadjacentsiteallotmentboundarywhenscaledofffloorplans.

    3.1Deemed-to-SatisfyProvisions

    ThefollowingDTSprovisionshavebeenidentifiedasbeingsubjecttothealternativesolution: C3.2ProtectionofopeningsinexternalwallsOpeningsinanexternalwallthatisrequiredtohaveanFRLmust—(a)ifthedistancebetweentheopeningandthefire-sourcefeaturetowhichitisexposedislessthan—

    (i)3mfromasideorrearboundaryoftheallotment;or(ii)6mfromthefarboundaryofaroad,river,lakeorthelikeadjoiningtheallotment,ifnotlocatedinastoreyatorneargroundlevel;or(iii)6mfromanotherbuildingontheallotmentthatisnotClass10,beprotectedinaccordancewithC3.4andifwall-wettingsprinklersareused,theyarelocatedexternally;and

    (b)ifrequiredtobeprotectedunder(a),notoccupymorethan1/3oftheareaoftheexternalwallofthestoreyinwhichitislocatedunlesstheyareinaClass9bbuildingusedasanopenspectatorstand.C3.4Acceptablemethodsofprotection(a)Whereprotectionisrequired,doorways,windowsandotheropeningsmustbeprotectedasfollows:

    (i)Doorways—(A)internalorexternalwall-wettingsprinklersasappropriateusedwithdoorsthatareself-closingorautomaticclosing;or(B)–/60/30firedoorsthatareself-closingorautomaticclosing.

    (ii)Windows—(A)internalorexternalwall-wettingsprinklersasappropriateusedwithwindowsthatareautomaticclosingorpermanentlyfixedintheclosedposition;or(B)–/60/–firewindowsthatareautomaticclosingorpermanentlyfixedintheclosedposition;or(C)–/60/–automaticclosingfireshutters.

    (iii)Otheropenings—(A)excludingvoids—internalorexternalwall-wettingsprinklers,asappropriate;or(B)constructionhavinganFRLnotlessthan–/60/–.

    (b)Firedoors,firewindowsandfireshuttersmustcomplywithSpecificationC3.4.

    3.2DetailsofBCADTSDeviation

    In accordance with C3.2(a)(i) and C3.4(a)(ii), window openings within an external wall required to achieve a fireresistancelevelmustbeprotectedwithwindowwettingsprinklersandbefixedclosed/automaticclosingorachieveafireratingthroughothermeans.Inthisinstance,itisproposedtopermitwindowslocatedatnonearerthan2.9mfromthesideallotmentboundarytoremainunprotectedwithintheclass2building.Theextentofexposedwindowscanbeseeninthefigurebelow.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    13

    Figure1–ApartmentExposurestoEasternBoundaryShadedBlue(2.9mfromBoundary)

    As is evident, there are a seriesofwindows locatedwithin3mof theboundarywhichwill be addressedwithin thisalternativesolution.

    3.3RelevantPerformanceRequirement

    PursuanttoA0.10(b)ofBCAthefollowingperformancerequirementhasbeenidentifiedasbeingdirectlyrelevanttotheDTSprovisionsidentifiedinSection3.1above:CP2(a)Abuildingmusthaveelementswhichwill,tothedegreenecessary,avoidthespreadoffire-

    (i) toexits;and(ii) tosole-occupancyunitsandpubliccorridors;and(iii)betweenbuildings;and(iv)inabuilding

    (b)Avoidanceofthespreadoffirereferredtoin(a)mustbeappropriateto-(i) thefunctionoruseofthebuilding;and(ii)thefireload;and(iii)thepotentialfireintensity;and(iv)thefirehazard;and(v) thenumberofstoreysinthebuilding;and(vi)itsproximitytootherproperty;and(vii)anyactivefiresafetysystemsinstalledinthebuilding;and(viii)thesizeofanyfirecompartment;and(ix)firebrigadeintervention;and(x) otherelementstheysupport;and(xi)theevacuationtime.

    3.4AssessmentMethodology

    In order to address the provisions of the BCA, a performance based approach will be adopted to demonstratecompliance of the Alternative Solution with the BCA. The proposed Alternative Solution will review the proposedsolutionusingquantitativeandqualitativemeasuresagainsttherequirementsofCP2.ThequantitativeassessmentwillassesscomplianceagainstBCAverificationmethodCV1.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    14

    3.5AcceptanceCriteria

    Itmustbeacceptedthattheopeningsaresuchthatfirespreadtoorfromtheboundaryoradjacentfiresourcefeatureisnotpromoted.IftheproposedalternativesolutioncandemonstratethattheopeningsarenotlikelytoresultinfirespreadviaopeningsintheadjacentbuildingthealternativesolutionwillbeconsideredtosatisfytherequirementsofCP2throughqualitativeandquantitativeabsoluteassessment.Quantitatively,itmustbeacceptedthattheproximityoftheunprotectedwindowsdoesnotpromoteincreasedriskoffire spread between each building and/or the property boundary. If the proposed alternative solution is capable ofdemonstrating that fire spread is unlikely to occur, it will be considered that the solution adequately satisfies theperformancerequirementsoftheBCA.FireSpreadtoBoundaryTheradiantheatfluxcriteriaforfirespreadtoboundariesissetoutintableCV1oftheBCAwhichstatesthat‘abuildingwill not cause heat flux in excess of those set out in column 2 of Table CV1 at locations within the boundaries of anadjoiningpropertysetoutincolumn1ofTableCV1whereanotherbuildingmaybeconstructed’.Column1 Column2Location HeatFlux(kW/m2)OnBoundary 801mfromboundary 403mfromboundary 206mfromboundary 10FireSpreadfromBoundaryFurthertothis,CV1statesthatwhenabuildingis‘locatedatthedistancesfromtheallotmentboundarysetoutincolumn1ofTableCV1,abuildingiscapableofwithstandingtheheatfluxsetoutincolumn2ofTableCV1withoutignition’.Itwillconservativelybeassumedthatallfireshaveachievedflashoverconditions.Inordertodeterminewhetherornotfirespreadhasoccurred,itisproposedtoutilisethefollowingradiantheatfluxcriteriawhichoutlinetherequiredlevelorradiantheatfluxtocausetheignitionofcellulosicmaterials(pilotedandnon-piloted)(Drysdale1998).

    Figure2–RadiantHeatRequiredforPilotedandNon-PilotedIgnition

    Ifitcanbedemonstratedthatignitionisnotcapableofoccurringviaaquantitativeanalysis,therequirementsofCP2willbeconsideredtobeachieved.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    15

    3.6QualitativeandQuantitativeAssessment

    FireSpreadtoBoundaryTableCV1oftheBCAoutlinesthemaximumradiantheatfluxespermittedtobereceivedattheboundary,1montheoppositesideoftheboundary,3montheoppositesideoftheboundaryand6montheoppositesideoftheboundaryfromawindow in the subject building. These radiant heat fluxes are 80kW/m2, 40kW/m2, 20kW/m2 and10kW/m2respectively.Calculationsundertakenindicatethatutilisingsimpleradiantheattransfercalculationsfromaflashoverfireburningat1,000˚C inthesubjectbuilding, thefollowing levelsofradiantheatarereceivedattheboundaryfromeachapartmentwindowlocatedat2.9mfromthesideallotmentboundary.Forthepurposesofcalculation,ithasbeenconservativelyassumedthatallwindowsfromeachapartmentaresimultaneouslyradiatingtowardstheboundary.Unit Window Width(m) Height(m) Setbackto

    Centre(m)HeatFlux(kW/m2)atDistancesasListedAtboundary

    1m fromboundary

    3m fromboundary

    6m fromboundary

    UnitsG.1,1.1or2.1

    Bed1Bed2

    2.42.4

    0.70.7

    2.92.9

    9.7

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    16

    Level Window TypeofOpening Width(m) Height(m) Setback(m) RadiantHeatReceived(kW/m2)

    Unit2.4

    Bed1Bed2Bath

    DistanceUnknown.Assumedthatopeningis1mawayfromboundaryandhasdimensionsof12mlongby1.28minheight.

    12m 1.28m 2.9fromboundaryand3.9fromradiator

    22.3

    Thetransmittedradiantheatfluxfromtheboundaryradiation(kW/m2)receivedatthewindowopeningswithinthreemetresoftheboundaryfromafireattheboundaryaredetailedinthetableabove.As per the above it can be seen that the radiant heat received at all of the assessedwindow openings exceed thatrequired for piloted ignition of the aluminium framedwindows (12.0kW/m2) as outlined in the acceptance criteriaabove.Theradiantheatfluxishowever,insufficienttoresultinnon-pilotedignition(occurringat28.0kW/m2)andonthisbasisitisproposedtoeitherfixthesewindowsintheshutpositionorprovideemberresistantmetallicflyscreensoverthewindowsthatwillpreventpilotedignitionfromoccurring.Onthebasisofthecalculationsundertakenabove,itisconsideredthattherelevantperformancerequirementCP2hasbeensatisfiedforopeningsfacingtheboundariesprovidingtheaffectedwindowsasscheduledaboveareprovidedwithemberresistantmetallic fly screens thatpreventember ingress.Thesescreensshallbeapproved foruse inbushfireproneareasaspertherequirementsofAS3959.

    3.7AssessmentagainstrelevantPerformanceRequirement

    The following table summarises the proposed qualitative assessment against the relevant performance requirementCP2.

    CP2 (a)Abuildingmusthaveelementswhichwill,tothedegreenecessary,avoidthespreadoffire-

    (i)toexits;and Notapplicabletothisalternativesolution.(ii) to sole-occupancy units and publiccorridors;and

    Notapplicabletothisalternativesolution.

    (iii)betweenbuildings;and The analysis demonstrates that a fire in the building will not result inradiantheatfluxesinexcessofthatoutlinedinverificationmethodsCV1and CV2 when fitted with metallic ember resistant screens withmaximum2mmaperturesize.

    (iv)inabuilding Notapplicabletothisalternativesolution.(b)Avoidanceofthespreadoffirereferredtoin(a)mustbeappropriateto-

    (i) the function or use of the building;and

    Asoutlinedabove, thebuilding is considered tobea typical class2 lowriseapartmentbuildingwithoccupantsgenerallybeingfamiliarwiththelocationoftheexit(astheexitisformedbythefrontentrydoorway).

    (ii)thefireload;and Asoutlinedabove,thefireloadisconsideredtobeequivalentto(aclass2building.

    (iii)thepotentialfireintensity;and The fire intensity within the subject building is considered to beequivalenttothatofatypicalclass2building.

    (iv)thefirehazard;and Thefirehazardscontainedwithinthebuildingarenodifferenttothatofatypicalclass2building.

    (v)thenumberofstoreysinthebuilding; Thebuildingonlycontains4 storeyswhich is considered toensure that

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    17

    and rapid evacuation to open space can occur whilst ensuring that firefighting operations can be undertaken from outside that will mitigateagainstfirespreadtoneighbouringbuildings.

    (vi)itsproximitytootherproperty;and The subject window openings are only marginally less than thatpermitted under the BCA (2.9m in lieu of 3.0m) and the provision ofmetallic fly screenswithmaximum 2mm aperture sizewill ensure thatpilotedignitioncannotoccur.

    (vii) any active fire safety systemsinstalledinthebuilding;and

    ThebuildingisprovidedwithsmokealarmsandfiredetectionandalarmsystemsaspertheDTSprovisionsoftheBCA.

    (viii) the size of any fire compartment;and

    The upper levels of the building are considered to be a single firecompartment with additional compartmentation provided around eachSOUtofurtherreducetheimpactoffirespreadwithinthebuilding.

    (ix)firebrigadeintervention;and ThenearestfirebrigadeatHornsbyiswithinreasonableproximityofthebuildingandisafulltimestationthatwouldhaveeasyandquickaccesstosite.

    (x)otherelementstheysupport;and Notapplicabletothisalternativesolution.(xi)theevacuationtime. The evacuation time is not considered to differ from that of a standard

    class2dwelling.

    3.9AssessmentConclusion

    Whilst the DTS provisions of C3.2 and C3.4 require the provision of window wetting fire sprinkler protection toautomaticclosingorpermanentlyclosedwindowswithin3moftheboundaryfiresourcefeatureinabuildingofTypeAconstruction, in this instance, a qualitative and quantitative assessment has been undertakenwhich has establishedthatsprinklerprotectionisnotrequiredtobeprovidedastheseopeningsareunlikelytocausetheunduespreadoffire.On this basis, Performance Requirement CP2 is considered to be satisfied subject to the following additionalrequirements:

    • Bedroomwindows1and2withinunitsG.1,1.1and2.1shallbeprovidedwithmetallicflyscreens,suitableforuse in bushfire prone areas as per the requirements of AS3959, with maximum 2mm aperture size.Alternatively,thesewindowscanbefixedintheshutposition.

    • Bedroomwindows2and3,andthebathroomwindowwithinunitsG.4and1.4shallbeprovidedwithmetallicflyscreens,suitableforuseinbushfireproneareasaspertherequirementsofAS3959,withmaximum2mmaperturesize.Alternatively,thesewindowscanbefixedintheshutposition.

    • Bedroom windows 1 and 2, and the bathroom window within unit 2.4 shall be provided with metallic flyscreens, suitable for use in bushfire prone areas as per the requirements of AS3959, withmaximum 2mmaperturesize.Alternatively,thesewindowscanbefixedintheshutposition.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    18

    4.0ALTERNATIVESOLUTION2–EXTENDEDTRAVELDISTANCES

    An Alternative Solution has been developed to address the proposed deviation from the DTS provisions to permitextendedtraveldistancesontheapartmentlevelsofthebuildingofupto8.8mtothesingleexitservingeachstoreyinlieuofthemaximum6mpermissibleundertheDTSprovisionsoftheBCA.

    4.1Deemed-to-SatisfyDeviation

    Pursuant to A.0.10(a) of BCA the following DTS provisions have been identified as being subject to the alternativesolution: D1.4Exittraveldistances(a) Class2and3buildings—

    (i) Theentrancedoorwayofanysole-occupancyunitmustbenotmorethan—(A) 6mfromanexitorfromapointfromwhichtravelindifferentdirectionsto2exitsisavailable;

    or(B) 20mfromasingleexitservingthestoreyatthelevelofegresstoaroadoropenspace;and

    (ii) nopointonthefloorofaroomwhichisnotinasole-occupancyunitmustbemorethan20mfromanexitorfromapointatwhichtravelindifferentdirectionsto2exitsisavailable.

    4.2DetailsofAlternativeSolution

    InaccordancewithClauseD1.4(a)(i)(A)above,itisarequirementthateachSOUentrancedoorwaybenofurtherthan6m froman exit. In this case, thedistanceof travel to the top stair tread (considered to the exit), is at the furthest,located8.8mfromthefurthestSOUentrancedooronlevel1.Thiscanbeseeninthefigurebelow.

    Figure2–ExtendedTravelDistanceonLevel1(Level2traveldistancesaresimilar)

    4.3RelevantPerformanceRequirements

    PursuanttoA0.10(b)ofBCAperformancerequirementsDP4andEP2.2havebeenidentifiedasbeingdirectlyrelevanttotheDTSprovisionsidentifiedinSection4.1above.DP4Exitsmustbeprovidedfromabuildingtoallowoccupantstoevacuatesafely,withtheirnumber,locationanddimensionsbeingappropriateto—(a) thetraveldistance;and

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    19

    (b) thenumber,mobilityandothercharacteristicsofoccupants;and(c) thefunctionoruseofthebuilding;and(d) theheightofthebuilding;and(e) whethertheexitisfromaboveorbelowgroundlevel.EP2.2(a) Intheeventofa fire inabuildingtheconditions inanyevacuationroutemustbemaintained fortheperiodof

    timeoccupantstaketoevacuatethepartofthebuildingsothat—(i) thetemperaturewillnotendangerhumanlife;and(ii) thelevelofvisibilitywillenabletheevacuationroutetobedetermined;and(iii) theleveloftoxicitywillnotendangerhumanlife.

    (b) Theperiodoftimeoccupantstaketoevacuatereferredtoin(a)mustbeappropriateto—(i) thenumber,mobilityandothercharacteristicsoftheoccupants;and(ii) thefunctionoruseofthebuilding;and(iii) thetraveldistanceandothercharacteristicsofthebuilding;and(iv) thefireload;and(v) thepotentialfireintensity;and(vi) thefirehazard;and(vii) anyactivefiresafetysystemsinstalledinthebuilding;and(viii) firebrigadeintervention.

    4.4AssessmentMethodology

    Inordertoaddress theprovisionsof theBCA,aquantitativeandabsoluteperformancebasedsolution formulated inaccordance with A.0.3(a)(i) and A.0.5(b)(ii) has been adopted to demonstrate the compliance of the AlternativeSolutionwiththerelevantPerformanceRequirements.

    4.5AcceptanceCriteria

    It must be demonstrated that in the proposed trial design incorporating extended travel distances, the proposedarrangement categorically satisfies each element of the relevant performance requirements. If this is demonstrated,compliancewithDP4andEP2.2isconsideredtobeachieved.

    4.6QualitativeAssessment

    BCASectionD1.3outlineswhenfireisolatedstairwaysarerequiredtobeprovided.Inaclass2buildinghavingariseinstoreysof4withthebottommoststoreyonlyusedtohousevehicles,astairwayprovidingegressforthebuildingisnotrequiredtobefireisolated.Whilstitisthereforepermittedthatthisstairwayprovidesdirectconnectionbetweenthethreeapartmentlevelsinthebuilding, in this instance the central exit interconnects the threeupper storeysof thebuildingonlyandprovidesnointerconnectiontothebasement.Furthermore,thisexitisproposedtobeprovidedwithsmokeseparatingconstructionateachlevelwiththeentrancedoorwayconfiguredasaself-closingsolidcoredoorwaywhichwillbelocatedat5.4mfromthefurthestapartmentonlevel1and5.0mfromthefurthestapartmentonlevel2.Thiscanbeseeninthefigurebelow(level2shown).Itcanbeseenthatwhilst the traveldistance technicallyexceeds themaximumpermissible6mto thesingleexit, theproposed smoke resisting construction, coupledwith the fire rated bounding construction afforded through normalapartmentconstruction,willensurethatoccupantsreachaplaceofrelativesafetyearlier.Furthermore,thelikelihoodofsmokeingressintothestairwayfromlevels1or2(wheretheextendedtraveldistancesoccur),isreducedtherebyincreasingtheabilityforoccupantstoevacuatefromthebuilding.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    20

    Figure3–ProposedTrialDesignIncorporatingSmokeResistingConstructiononLevel2(Level1similar)

    Asameasureofconservatism,topreventsmokeloggingoftheentrycorridoronthegroundfloor,itisproposedthatmediumtemperaturesmokesealsbeprovidedontheentrydoorstoapartmentsonthegroundfloorofthebuildingascanbeseeninthefigurebelow.

    Figure4–ProposedTrialDesignIncorporatingSmokeSealsonGroundFloorofBuilding

    On this basis, the arrangement is considered to provide a high degree of life safety and is considered to achievecompliancewith relevant performance requirements DP4 and EP2.2 subject to the assessment against the relevantperformancerequirementscontainedbelow.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    21

    4.7AssessmentagainstrelevantPerformanceRequirement

    ThefollowingisanassessmentoftherelevantPerformanceRequirementDP4andEP2.2.

    DP4 Exits must be provided from a building to allow occupants to evacuate safely, with their number, location anddimensionsbeingsappropriateto-(a)thetraveldistance;and Whilstthetraveldistancetothetopofthestairwayisincreasedbeyond6m,

    smokeresistingconstructionprovidedbetweenthefurthestapartmentandthe stairway,which encloses the entire staircase, provides a safe place foroccupantsbeforethe6mdistancehaselapsed.Onthisbasistheincreaseinlife safety to building occupants from the affected apartments in at leastsufficient to offset the additional 3.5s of egress time (assuming aconservativetravelspeedof0.8m/s).

    (b) the number, mobility and othercharacteristicsofoccupants;and

    Itisexpectedthatthemajorityofoccupantswouldberesidentswhowouldbe familiarwith the location of the exit. The building contains a relativelylownumberofbuildingoccupants and therefore evacuation is expected tooccurrapidly.

    (c)thefunctionoruseofthebuilding;and

    Theuse as a residential unit suggests occupantswill be very familiarwithexit options. Any guests are expected to be either accompanied, or willfollowexitsignageasappropriate.

    (d)theheightofthebuilding;and

    The distance of travel from the top floor to the point of discharge onlyinvolvestravellingdowntwolevelstoreachgroundfloorwheretheuseofanon-fireisolatedstairwayisconsideredtobeadequate.

    (e) whether theexit is fromaboveorbelowgroundlevel.

    Notrelevanttothisalternativesolution.

    EP2.2 (a) Intheeventofafireinabuildingtheconditionsinanyevacuationroutemustbemaintainedfortheperiod

    oftimeoccupantstaketoevacuatethepartofthebuildingsothat:

    (i) the temperaturewillnotendangerhumanlife;and

    Theadditionofsmokeseparationofthestairwayontheupperlevel,andtheprovisionofmedium temperature smoke seals to thedoorwayswithin thegroundfloorlobbywilldecreasetheabilityforfire/smoketoaffectbuildingoccupantsseekingevacuationfromthebuilding.

    (ii)thelevelofvisibilitywillenabletheevacuation route to be determined;and(iii) the level of toxicity will notendangerhumanlife.(b)Theperiodoftimeoccupantstaketoevacuatereferredtoin(a)mustbeappropriateto(i) the number, mobility and othercharacteristicsoftheoccupants;and

    Itisexpectedthatthemajorityofoccupantswouldberesidentswhowouldbe familiarwith the location of the exit. The building contains a relativelylownumberofbuildingoccupants and therefore evacuation is expected tooccurrapidly.

    (ii)thefunctionoruseofthebuilding;and

    Theuse as a residential unit suggests occupantswill be very familiarwithexit options. Any guests are expected to be either accompanied, or willfollowexitsignageasappropriate.

    (iii) the travel distance and othercharacteristicsofthebuilding;and

    Whilstthetraveldistancetothetopofthestairwayisincreasedbeyond6m,smokeresistingconstructionprovidedbetweenthefurthestapartmentandthe stairway,which encloses the entire staircase, provides a safe place for

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    22

    occupantsbeforethe6mdistancehaselapsed.Onthisbasistheincreaseinlife safety to building occupants from the affected apartments in at leastsufficient to offset the additional 3.5s of egress time (assuming aconservativetravelspeedof0.8m/s).

    (iv)thefireload;and Thefireload,intensityandfirehazardisnotconsideredtodifferfromthatofatypicalapartmentbuilding.(v)thepotentialfireintensity;and

    (vi)thefirehazard;and(vii) any active fire safety systemsinstalledinthebuilding;and

    ThebuildingwillbeprovidedwithactivefiresafetysystemsaspertheDTSprovisionsof theBCAwhichwillconsistofsmokealarmsordetectors, firehydrantsandportablefireextinguishers.

    (viii)firebrigadeintervention. The nearest fire brigade at Hornsby iswithin reasonable proximity of thebuildingandisafulltimestationthatwouldhaveeasyandquickaccesstosite.

    4.8AssessmentConclusion

    Theaboveassessmenthasdemonstratedthattheproposedincreasesintraveldistanceareconsideredtobesufficienttobesufficientlyoffsetthroughtheproposedtrialdesignincorporatingadditionalsmokeresistingconstructionaroundthestairwayandwithinthegroundfloorlobbyofthebuilding.On this basis, it is considered that via demonstrating equivalence with the BCA DTS provisions, the relevantperformance requirements DP4 and EP2.2 are considered to be satisfied subject to the following additionalrequirements:

    • Theentrydoorwaystothestairwaysonlevels1and2shallbeconfiguredasself-closingsmokedoorswhichshallbeprovidedwithmediumtemperaturesmokeseals.Theconstructionaroundthewallsandceilingshallberesistanttothepassageofsmokethroughsealingofanypenetrationsthroughthewall/ceilingconstructionofthestairwayonthesetwoupperlevels.

    • ThedoorwaysopeningintothelobbyfromtheSOUsandservicesroomonthegroundfloorshallbeprovidedwithmediumtemperaturesmokeseals.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    23

    5.0ALTERNATIVESOLUTION3–REDUCTIONINFIRERESISTANCELEVELS

    Analternativesolutionhasbeendevelopedtopermitthebathroomstocontaina30mmsetdownintheconcreteslabforthetilebedandtoassesswhetherornotthiscompromisestheabilityoftheconcreteslabtoachievetherequiredfireresistancelevelof90/90/90or120/120/120dependingonthelocationofthesetdown.

    5.1Deemed-to-SatisfyNon-compliance

    ThefollowingDTSprovisionshavebeenidentifiedasbeingsubjecttothealternativesolution:B1.4(b) DeterminationofstructuralresistanceofmaterialsandformsofconstructionThestructuralresistanceofmaterialsandformsofconstructionmustbedeterminedinaccordancewiththefollowing,asappropriate:(b) Concrete: (i) Concreteconstruction(includingreinforcedandprestressedconcrete):AS3600. (ii) Autoclavedaeratedconcrete:AS5146.1. (iii) Post-installedandcast-infastenings:..Further to this, Spec. C1.1 requires an FRL of 120/120/120 be achieved on the ground floor of the buildingwhichseparates the basement level carpark from the residential areas, and that an FRL of 90/90/90 is provided betweenapartmentlevels(level1and2slab).

    5.2DetailsofBCADTSDeviation

    Inordertoprovidetherequiredwaterproofing,whilstensuringtherequiredfallstowardsfloorwastescanbeachievedinwetareas,atypicalconstructiondetailinvolvessettingdowntheslabandscreedingthefloorontoptoenabletiledfloorswithinwetareastobeinstalledatgrade.Thistypicaldetailcanbeseeninthefigurebelow.

    Figure5–ProposedSlabSetDownArrangement

    Asisevident,wheretheslabissetdown,adecreaseinconcretecoveroverthesteelreinforcementexistswhichwillreduce the required fire resistance of the slab. This alternative solutionproposes to calculate the required concretecoveronthesteelelementstodeterminewhetherornot theproposed30mmreduction inthe200mmconcreteslabwillcompromisetheabilityfortheslabtoachieveanFRLof120/120/120intheworstinstance.

    6.3RelevantPerformanceRequirement

    PursuanttoA0.10(b)ofBCAperformancerequirementCP1andCP2havebeenidentifiedasbeingdirectlyrelevanttotheDTSprovisionsidentifiedabove.CP1andCP2statethat:

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    24

    CP1Abuildingmusthaveelementswhichwill,tothedegreenecessary,maintainstructuralstabilityduringafireappropriateto-(a) thefunctionoruseofthebuilding;and(b) thefireload;and(c) thepotentialfireintensity;and(d) thefirehazard;and(e) theheightofthebuilding;and(f) itsproximitytootherproperty;and(g) anyactivefiresafetysystemsinstalledinthebuilding;and(h) thesizeofanyfirecompartment;and(i) firebrigadeintervention;and(j) otherelementstheysupport;and(k) theevacuationtimeCP2(a)Abuildingmusthaveelementswhichwill,tothedegreenecessary,avoidthespreadoffire-

    (i) toexits;and(ii) tosole-occupancyunitsandpubliccorridors;and(iii)betweenbuildings;and(iv)inabuilding

    (b)Avoidanceofthespreadoffirereferredtoin(a)mustbeappropriateto-(i) thefunctionoruseofthebuilding;and(ii)thefireload;and(iii)thepotentialfireintensity;and(iv)thefirehazard;and(v) thenumberofstoreysinthebuilding;and(vi)itsproximitytootherproperty;and(vii)anyactivefiresafetysystemsinstalledinthebuilding;and(viii)thesizeofanyfirecompartment;and(ix)firebrigadeintervention;and(x) otherelementstheysupport;and(xi)theevacuationtime.

    5.4AssessmentMethodology

    In order to address the provisions of the BCA, a performance based approach will be adopted to demonstratecompliance of the Alternative Solution with the BCA. The proposed Alternative Solution will review the proposedsolutionusingquantitativemeasuresagainsttherequirementsofCP1andCP2.Thequantitativeanalysiswillcalculatethe required level of concrete cover over the structural elements to determine whether or not the fire resistingperformance is insufficient to achieve the required FRLs. In the case that the required FRLs are incapable of beingachieved,itisproposedtoundertakefireseveritycalculationstodeterminewhatFRLswouldberequiredinordertoovercomeaflashoverfirewithinthebuilding.

    5.5AcceptanceCriteria

    Itmustbeacceptedthat therequiredconcretecoveroversteelreinforcementwithinthe200mmthickconcreteslab(wherereducedto170mmdueto30mmslabsetdown)isreadilyachievabletoeitherachievetheDTSFRLsasoutlinedintheBCAorreducedFRLswhichwillbesubjecttofireseveritycalculationsifrequired.

    If this can be demonstrated, it will be considered that the solution adequately satisfies the relevant performancerequirementsCP1andCP2.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    25

    5.6QuantitativeAssessment

    Research undertaken by the Portland Cement Association (Bilow et. al 2008) provides a technical review of therequiredconcreteperformancewhenexposedtofire.Thereviewoutlinestheminimumthicknessesoffloorslabs,andtheminimum required concrete cover over steel reinforcement beams in order to achieve certain durations of fireresistingperformance.Thetablebelowdeterminesthatinordertoachieveafireratingof2hours,theminimumslabthicknessisbetween3.6and5inches(91.4to127mm)dependingonthetypeofaggregateused.Inthiscasetheslabthicknessis200mm,whichisproposedtobereducedinareasby30mmtoaminimumslabthicknessof170mm.Thegroundfloorslabtherefore isconsideredtobeofsufficient thickness toachievetherequired120/120/120(2hour)fireresistingperformance,andthelevel1and2slabsaresimilarlyconsideredtoachievetherequired90/90/90(1.5hour)FRL.

    Figure6–MinimumSlabThicknesstoAchieveFireResistingPerformanceinCastinPlaceFloorandRoofSlabs(ininches)

    Thepaperalsooutlines theminimumrequiredconcretecoveroversteel reinforcementbeamswithinconcreteslabswhichcanbeseeninthefigurebelow.Onceagain,dependingonthetypeofaggregateused,inordertoachieveafireresistanceof2hours,therequiredconcretecovermustbebetween0.75-1inches(19.1-25.4mm).Giventhethicknessoftheslabat170mmatthepointofsetdown,itisconsideredthatthiswouldbereadilyachievablebyprocuringandinstallingchairsofthecorrectdimensionatthispointintheslab.

    Figure7–MinimumConcreteCoverforFloorandRoofSlabs(ininches)

    On thisbasis it is considered that compliancewith theDTSprovisionsof theBCA is readilyachievablewhichwouldthereforesatisfyrelevantperformancerequirementsCP1andCP2.

    5.7AssessmentagainstrelevantPerformanceRequirement

    ThefollowingtableprovidesananalysisoftheproposedarrangementagainsttherelevantPerformanceRequirementCP1andCP2todeterminewhetherornotcomplianceiscapableofbeingachieved.CP1A building must have elements which will, to the degree necessary, maintain structural stability during a fireappropriateto-(a)thefunctionoruseofthebuilding;and

    Thebuildingisusedasanapartmentbuilding.

    (b)thefireload;and Thefireload,intensityandfirehazardareconsistentwiththatofatypicalapartmentbuilding.(c)thepotentialfireintensity;and

    (d)thefirehazard;and(e)theheightofthebuilding;and Theriseinstoreysis4whichisrelativelylowandfacilitateseaseofegress

    foroccupantsandeaseofaccessforattendingfirefighters.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    26

    CP1(f)itsproximitytootherproperty;and Notapplicabletothisalternativesolution.(g) any active fire safety systemsinstalledinthebuilding;and

    ThebuildingwillbeprovidedwithactivefiresafetysystemsaspertheDTSprovisionsoftheBCAwhichwillconsistofsmokealarmsordetectors,firehydrantsandportablefireextinguishers.

    (h) the size of any fire compartment;and

    Theupperlevelsareconsideredtoformasingle‘firecompartment’butarefurther divided into smaller fire rated areas through the provision ofcomplyingboundingconstruction.

    (i)firebrigadeintervention;and Thenearest firebrigadeatHornsby iswithinreasonableproximityof thebuildingandisafulltimestationthatwouldhaveeasyandquickaccesstosite.

    (j)otherelementstheysupport;and The slab is load bearing and is considered to be able to provide therequiredperformanceundertheDTSprovisionsoftheBCA.

    (k)theevacuationtime. Thetimetoevacuatethebuildingwhichhasarelativelylowriseinstoreysisnotconsideredtoexceed2hours.

    CP2(a)Abuildingmusthaveelementswhichwill,tothedegreenecessary,avoidthespreadoffire-(i)toexits;and Notapplicabletothisalternativesolution.(ii)tosoleoccupancyunitsandpubliccorridors;and

    Notapplicabletothisalternativesolution.

    (iii)betweenbuildings;and Notapplicabletothisalternativesolution.(iv)inabuilding. Aspertheinformationprovided,theproposedfireresistancelevelsarenot

    proposedtobereducedbeyondthatoftheDTSprovisionsoftheBCAwhichshouldbereadilyachievableattheslabsetdown.

    (b)Avoidanceofthespreadoffirereferredtoin(a)mustbeappropriateto-(i) the function and use of thebuilding;and

    RefertoCP1above.

    (ii)thefireload;and RefertoCP1above.(iii)thepotentialfireintensity;and RefertoCP1above.(iv)thefirehazard;and RefertoCP1above.(v) the number of storeys in thebuilding;and

    Theriseinstoreysis4whichisrelativelylowandfacilitateseaseofegressforoccupantsandeaseofaccessforattendingfirefighters.

    (vi) its proximity to other property;and

    RefertoCP1above.

    (vii) any active fire safety systemsinstalledinthebuilding;and

    RefertoCP1above.

    (viii)thesizeofthefirecompartment;and

    RefertoCP1above.

    (ix)firebrigadeintervention;and RefertoCP1above.(x)otherelementstheysupport;and RefertoCP1above.(xi)theevacuationtime. RefertoCP1above.

    5.8AssessmentConclusion

    Theaboveanalysisdemonstratesthatdespitehavingasetdownof30mminareasoftheslab,therequiredFRLsarestillcapableofbeingachievedproviding:

    • Theminimumslabthicknessatthepointofsetdownmustnotbelessthan150mmatanylocation.• Theminimumconcretecoveronanysteel reinforcementbars runninghorizontallywithin theslabshall

    notbelessthan30mm.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    27

    Providing the above is adhered with, compliance with the relevant performance requirements CP1 and CP2 isconsideredtobeachieved.6.0ALTERNATIVESOLUTION4–FIREHYDRANTPUMPROOM

    AnalternativesolutionhasbeendevelopedtoaddresstheproposeddeviationfromtheDTSprovisions topermitthefirehydrantpumproomtobeaccessedfromastairwaywhichisnotfireisolated.

    6.1Deemed-to-SatisfyNon-compliance

    BCAClauseE1.3hasbeenidentifiedasbeingsubjecttothealternativesolution.E1.3Firehydrants(a) Afirehydrantsystemmustbeprovidedtoserveabuilding—

    (i) havingatotalfloorareagreaterthan500m2;and(ii) whereafirebrigadeisavailabletoattendabuildingfire.

    (b) Thefirehydrantsystem—(i) mustbeinstalledinaccordancewithAS2419.1,exceptaClass8electricitynetworksubstationneednot

    complywithclause4.2ofAS2419.1if—(A) itcannotbeconnectedtotownmainsupply;and(B) onehourwaterstorageisprovidedforfirefighting;and

    (ii) where internal fire hydrants are provided, theymust serve only the storey on which they are locatedexceptthatasole-occupancyunit—(A) inaClass2 or3buildingorClass4part of abuildingmaybe servedbya single firehydrant

    locatedatthelevelofegressfromthatsole-occupancyunit;or(B) ofnotmorethan2storeysinaClass5,6,7,8or9buildingmaybeservedbyasinglefirehydrant

    locatedatthelevelofegressfromthatsoleoccupancyunitprovidedthefirehydrantcanprovidecoveragetothewholeofthesole-occupancyunit.

    Furthertothis,AS2419.1states:6.4.2InternalpumproomsPumproomslocatedwithinabuildingshallhave–

    a) Adooropeningtoaroadoropenspace,oradooropeningtofire-isolatedpassageorstairwhichleadstoaroadoropenspace;and

    b) ExceptwherethebuildingissprinklerprotectedinaccordancewithAS2118.1,enclosingwallswithanFRLnotlessthanthatprescribedbytheBCAforafirewallfortheparticularbuildingclassificationservedbythefirehydrantsystem.

    6.2DetailsofBCADTSDeviation

    Intheproposedarrangement,theaccesstothefirehydrantpumproomisneitherachievedfromadooropeningdirecttoroadoropenspace,norfromafire-isolatedpassage.Ascanbeseeninthefigurebelow,thefirehydrantpumproomis provided with a doorway which in turn opens into an airlock which then involves having to travel belowapproximately3mofundercoverspacebeforeleadingtoopenspace.Asthepumproomdoesnotopendirecttoopenspace,thiscorridorisrequiredtobefireisolated.Theproposalistoallowthiscorridorspacetocontinuetoopendirecttoopenspaceinlieuoffireisolatingtheentirecorridor.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    28

    Figure8–FireHydrantPumpRoomAccess

    6.3RelevantPerformanceRequirement

    PursuanttoA0.10(b)ofBCAperformancerequirementEP1.3hasbeenidentifiedasbeingdirectlyrelevanttotheDTSprovisionsidentifiedabove.EP1.3Afirehydrantsystemmustbeprovidedtothedegreenecessarytofacilitatetheneedsofthefirebrigadeappropriateto—(a)fire-fightingoperations;and(b)thefloorareaofthebuilding;and(c)thefirehazard.

    6.4AssessmentMethodology

    InordertoaddresstheprovisionsoftheBCA,anabsoluteassessmenthasbeenadoptedwhichassessestheproposeddeviation against the provisions of relevant performance requirementEP1.3 to determinewhether categorically therequirementsaresatisfiedthroughqualitativeassessmenttechniques.AnassessmentofeachofthedeviationsabovewillbeundertakenagainsteachaspectofEP1.3.

    6.5AcceptanceCriteria

    TheproposedarrangementwillbeconsideredtoachievecompliancewiththerelevantperformancerequirementEP1.3iftheabsoluteandqualitativeanalysisdemonstratesthateachelementoftherelevantperformancerequirementsarecategoricallysatisfied.Furthermore,thesolutionwillneedtobedemonstratedtosuittheoperationalrequirementsofthefirebrigade.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    29

    6.6QualitativeAssessment

    AS2419.1providesguidanceforexternalpumproomsasfollows:6.4.3ExternalpumproomsPumproomsandenclosures,locatedexternaltoandwithin6mofanynon-sprinklerprotectedbuildingtheyareprotecting,shallhaveenclosingwallswithanFRLnotlessthanthatprescribedbytheBCAforafirewallfortheparticularbuildingclassificationservedbythefirehydrantsystem.Asisevident,thereareoptionstolocatethefirehydrantpumproomeitherinternaltothebuilding,orexternaltothebuilding.Theintentbehindclauses6.4.2and6.4.3appearstobe:

    • Toensurethatfirefighterscaneasilyaccessthepumproomwithoutbeingsubjecttothedangerouseffectsoffire

    • Toensurethatfirefighters,whenlocatedwithinthepumproom,aresafefromthedangerouseffectsoffire.Inthiscase,thefullheightmasonryconstructionsurroundingthefirehydrantpumproomwillenablethepumproomto be easily fire rated through the provision of a fire door to the fire hydrant pump room. Furthermore the wallboundingthestairwayandthebasementactsasaretainingwall(toretainthefillbeneaththestair)andwillalsobeconstructedasamasonrywall.Onthisbasisthemethodofconstructionbetweenthestairway,corridorandthecarparkappearstoberelativelyfirerated.Byprovidingaself-closingfiredoorbetweenthecarparkandthestairwaycorridor,itisconsideredthatfullfireseparationcanbeachievedinthislocation.Whilst this still does not technically complywith AS2419.1 clause 6.4.2 as the entire corridor does not form a fireisolated tunnel, thearrangement is similar to thatpermitted in clause6.4.3 forexternalpumproomswhere the firepumproomandaccesstoitisfireseparatedfromthebuildingitisprotecting.Furthertothis thereasontheproposed internal firepumproomdoesnotopendirect toopenspace(aspermitted inclause6.4.2) is that there is a small sectionof overhanging soffit (approx. 3m in length).By fire ratingbetween thecarparkandthisare,theriskofafireoccurringinthisareaisextremelylowandthearrangementcanbeconsideredtobesimilartoapumproomwhichopensdirecttoopenspace.OnthisbasisitisconsideredthattheintentofAS2419.1isachievedthroughthetrialdesignwhichcanbeseeninthefigurebelow.

    Figure9–ProposedTrialDesignIncorporatingFireRatedConstruction

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    30

    Onthebasisoftheaboveit isconsideredthattherelevantperformancerequirementEP1.3issatisfiedsubjecttothefollowingassessmentagainsttheEP1.3.

    6.7AssessmentagainstrelevantPerformanceRequirement

    The following table summarises the proposed qualitative assessment against the relevant performance requirementEP1.3.

    EP1.3 Afirehydrantsystemmustbeprovidedtothedegreenecessarytofacilitatetheneedsofthefirebrigadeappropriateto—

    (a) fire-fightingoperations;and

    Theproposedfireratingofthewallboundingthecarparkandthestairwaycorridorwillensurethatfirefightersareprovidedwithsafeaccesstothefirehydrantpumproomtoshutofftheautomaticallyoperatedfirehydrantpumpsetsifrequiredtofacilitatefirefightingoperations.

    (b) thefloorareaofthebuilding;and

    Notapplicabletothisalternativesolution.

    (c)thefirehazard Thefirehazardinthestairwaycorridorislargelynon-existent.

    6.8AssessmentConclusion

    An alternative solutionhas beendeveloped to permit the access to the fire hydrant pump room to not be via a fireisolated corridor or direct from open space. This has been demonstrated to comply with relevant performancerequirementEP1.3,subjecttocompliancewiththetrialdesignrequirementslistedbelow:

    • Thefirehydrantpumproomshallbeprovidedwith fireratedconstructionachievingaminimumFRLof120/120/120withtheentrydoorwayachievingaminimumFRLof-/120/30.

    • Thewall bounding the carpark and the stairway/corridor leading to the fire isolated stairway shall beprovidedwith fire rated constructionachievingaminimumFRLof120/120/120with theexitdoorwayachievingaminimumFRLof-/120/30.

    • Thefirehydrantpumpshallbeautomaticallyoperatedfromapressureswitch,flowswitchorsimilar.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    31

    7.0CONCLUSIONS

    7.1Conclusion

    TheAlternative Solutionhasbeendevelopedusingaquantitative assessment andaqualitative comparisonwith theDeemed-to-Satisfy Provisions and quantitative assessment and is considered to comply with BCA PerformanceRequirementsCP1,CP2,DP4,EP1.3andEP2.2.TheBCArecognisestheseAssessmentMethodasacceptablemethodsfordeterminingthat theAlternativeSolutionsatisfies thePerformanceRequirement inaccordancewithBCAClausesA0.3(a)(i)andA0.5(b)(ii).Accordingly,basedontheabove,itisconsideredthatthedirectlyrelatedPerformanceCP1,CP2,DP4,EP1.3andEP2.2havebeenmet,providedtheAlternativeSolutionrequirementslistedaboveareimplemented.

    7.2SpecificationoftheFinalTrialDesign

    Considering the relevant provisions of the BCA and the above assessment, the Alternative Solution, subject to theprovisionoftheTrialDesignrequirements,isconsideredtomeetandcomplywiththePerformanceRequirementCP1,CP2, DP4, EP1.3 and EP2.2. The Trial Design requirements detailed in each solution and in the Executive SummarybecometheAlternativeSolutions.

    7.3MaintenanceRequirements

    Therecommendationsofthisreportmustformpartofthefiresafetycertificateandtheannualfiresafetystatementforthebuildingtoensuretherecommendationsofthisreportarecompliedwiththroughoutthebuildingoperation.

    7.4RequirementsoftheAlternativesolution

    The discussions undertaken have demonstrated compliance with the relevant performance requirements via theproposeddesignandinstallationofoffsetmeasures.TheoffsetmeasuresrequiredaspartofthisAlternativeSolutionarelistedintheExecutiveSummaryandmustbefullyimplementedinorderforcompliancetobeachieved.

    JamesSunjaya JamesAlexanderDirector DirectorMFSE,B.Eng.(Elec.),B.Med.Sci.BPBAccreditedFireEngineerGradeC10TASRegisteredBuildingPractitioner(FireSafety,BuildingServices)VICRegisteredBuildingPractitioner(FireSafety)RegisteredProfessionalEngineerQueenslandNPERandCPEng(FireSafety,BuildingServices)

    B.App.Sci(Bldg),GradDip(DispRes),ME(Firesafety),GradDip(BldgSurv)AIBSNationallyAccreditedLevel1BuildingSurveyorBPBGradeA1AccreditedCertifierandPCAFireSafetyEngineer

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    32

    8.0REFERENCES

    • AustralianBuildingCodesBoard,“FireSafetyEngineeringGuidelines”,Edition2001,November2001,

    Australia.

    • AustralianBuildingCodesBoard,“TheBuildingCodeofAustralia”,Edition2011,May2011,Australia.

    • AustralianBuildingCodesBoard,“TheGuidetotheBuildingCodeofAustralia”,Edition2007,May2007,Australia.

    • IFEG(2005).InternationalFireEngineeringGuidelines2005,ABCB.

    • NSWFB(2001/2002)."NSWFireBrigadeAnnualStatisticalReportTenYearReview."

    • Bilow,D.N.,Kamara,M.E.,(2008)“FireandConcreteStructures”,ASCE

    AppendixA–DataRelieduponintheFEB/RProcess

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    33

    CommonAbbreviationsUsedinFireEngineeringAbbreviation/Term Meaning

    AFAC FireandEmergencyServiceAuthoritiesCouncil

    AS AlternativeSolution

    ASB AlternativeSolutionBrief - identical toFEB.ASBwillnotbeusedother than torelate thistermtotheFireEngineeringBrief.

    ASR AlternativeSolutionReport-identicaltoFEB.ASRwillnotbeusedotherthantorelatethistermtotheFireEngineeringReport.BCA BuildingCodeofAustralia.

    CFD ComputationalFluidDynamics–Usedtodescribethefiremodellingforabuilding

    Comparative

    Amethodologyusedforafireengineeringanalysisthatusesacomparisonwiththedeemedto satisfy provisions of the BCA. Thismethodology shows that the alternative solution isequivalent to the DTS provisions of the BCA and is often referred to as the equivalenceapproach.

    DTS Deemed-To-Satisfy-RepresentingthedeemedtosatisfyprovisionssetoutintheBCA.

    Equivalence The equivalence approach is a fire engineering approach using a comparison to the DTSprovisionsoftheBCA.FEB FireEngineeringBrief-identicaltoASB.FEBisusedthroughoutthereport.

    FER FireEngineeringReport-identicaltoASR.FERisusedthroughoutthereport.

    FDS Fire Dynamics Simulator – The software program used to perform fire modelling onbuildingsFRL FireResistanceLevel

    FRNSW FireandRescueNewSouthWales

    IFEG InternationalFireEngineeringGuidelines

    NFPA NationalFireProtectionAuthority

    SFPA SocietyofFireProtectionEngineers.

    ClientDesignandBuildingRegulatoryObjectivesTheclientdesignobjectivesaretoaddresstheissuesofdeemed-to-satisfynon-compliancewiththeproductionofanalternativesolutionthatmeetstherelatedPerformanceRequirement.OneofthepurposesofthisFireEngineeringReportistoprovidethestakeholderswithadocumentforconsiderationandtoaddfurtherinputwithregardstothespecificobjectives.ThestructureoftheBCAisdepictedinthefollowingfigureandisahierarchaldocumentwithobjectives,functionalstatementsandPerformanceRequirement.

    TheprimaryobjectivesoftheBCAaretoprotectthelifesafetyofoccupantsbyallowingthemtoexitthebuildingwithoutbeingexposedtohazardousoruntenableconditions,theprotectionofadjacentbuildingsfromcollapseorfirespreadandprotectionofthelifesafetyoffirefightersbygivingreasonabletimefortheemergencypersonneltoperformtheirduties.

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    34

    ThePerformanceRequirementaretheonlysectionoftheBCAtowhichadesignmustcomply,withobjectivesandfunctionalstatementsgivenasguidancetoexplaintheintentofthePerformanceRequirement.SatisfyingthePerformanceRequirementcanbeachievedthroughoneofthreeways:

    a) ComplyingwithDeemed-To-Satisfy(DTS)provisionsoftheBCAb) FormulatinganAlternativeSolutionwhichcomplieswiththePerformanceRequirementc) Combinationofa)andb)

    ForthisparticularprojectthemeansofcompliancetotheBCAwillbeshownbycomplyingtoa/b/cabove.BCAclauseA0.9providesthefollowingassessmentmethodstodeterminethatabuildingsolutioncomplieswiththeBCAPerformanceRequirement:

    a) Evidence to support that the use of amaterial, form of construction or designmeets a Performance Requirement or aDeemed-to-SatisfyProvision

    b) VerificationMethodssuchas—i) TheverificationmethodsintheBCA;orii) Such other verification methods as the appropriate authority accepts for determining compliance with the

    PerformanceRequirementc) ComparisonwiththeDeemed-to-SatisfyProvisionsd) ExpertJudgement

    TheassessmentmethodsthatwillbeadoptedforthisprojectareinaccordancewithA0.9aboveandthespecificmethodsaredetailedinthealternativesolutionsections.

    MethodsofAnalysisThemethodsofanalysisusedinthedevelopmentofalternativesolutionsaredetailedinBCAClauseA0.9,andincludeA0.9(b)(i) VerificationMethods,suchastheVerificationmethodsintheBCAA0.9(b)(ii) VerificationMethods,otherthanthoseintheBCAthattheappropriateauthorityacceptsforcompliancewiththe

    PerformanceRequirementA0.9(c) Comparisontothedeemed-to-satisfyprovisionsoftheBCAA0.9(d) ExpertjudgementInordertosatisfyBCAClauseA0.5-MeetingthePerformanceRequirement(b) formulatinganAlternativeSolutionwhich-

    (i) complieswiththePerformanceRequirement;or(ii) isshowntobeatleastequivalenttotheDeemed-to-SatisfyProvisions;

    Thespecificassessmentmethodsusedfortheanalysisaredetailedinalternativesolutionsectionforeachissue.

    RelevantIFEGSub-SystemsTherelevantIFEGsub-systems(SS)forthisanalysisare:

    IFEGSub-System Description Symbol

    Sub-systemA

    FireInitiationandDevelopmentandControl

    Limitationofignitionsources

    Limitationofnatureandquantityoffuel

    Arrangementandconfigurationoffuel

    Separationofignitionsourcesandfuel

    Management of combustibles including housekeepingmeasures

    Electricalsafetyequipment

    Regularplantmaintenance

    Adherencetoproceduresfor'hotwork'(e.g.welding)

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    35

    IFEGSub-System Description Symbol

    Sub-systemB

    SmokeDevelopmentandSpreadandControl

    Smokebarriers

    Naturalsmokeventing

    Mechanicalsmokemanagement

    Sub-systemC

    FireSpreadandImpactandControl

    Separationoffuel

    Separationofbuildings

    Fireresistivebarriers

    Fireresistivestructuralelements

    Fireresistiveair-handlingducts

    Fireresistivedampers

    Exposureprotection

    Sub-systemD

    FireDetection,WarningandSuppression

    Automaticandmanualdetectionequipment

    Automaticandmanualwarningequipment

    Surveillanceequipment

    Automaticsuppressionequipment

    Manualsuppressionequipment

    Sub-systemE

    OccupantEvacuationandControl

    Evacuationplans

    Occupanttraining

    Emergencycommunications

    Egresssignage

    Egressroutes(includingfireisolatedelements)

    Sub-systemF

    FireServicesIntervention

    Type of fire services available (full-time/permanent orvolunteer).

    Characteristicsoffireservicescapabilityandresources

    Fireserviceaccesstothesiteandtothebuilding

    Watersuppliesandinfrastructure

    AcceptanceCriteriaandFactorsofSafetyfortheAnalysisQualitativeAssessmentsTheacceptancecriteriaforqualitativeassessmentsaretheequivalencetoadeemedtosatisfysolution(preferred)orthecollectiveagreementofthestakeholders.TheIFEGallowsbothqualitativeandquantitativeapproachesandstatesthat-"themethodschosenwillbeappropriatetotheapproachused".TheIFEGstates-"Intheminorityofcases,qualitativeanalysismaybeagreedduringtheFEBprocesstobesufficientfortheconsiderationofasinglenon-complianceissue.Thebasis(logic)onwhichthisapproachisusedshouldbedocumentedwithappropriatereferences.A“Delphi”approachmayalsobeappropriateincertaincircumstances,whereagroupofsuitablyqualifiedexpertprofessionalsreachconsensusagreementregardingthesuitabilityofaparticularsolution."TheIFEGfurtherstates-"Bothcomparativeandabsoluteapproachesmaybeadoptedintheanalysisstrategy.Themethodschosenwillbeappropriatetotheapproachused.Comparativeapproach:

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    36

    Typically,thefiresafetyprovidedbyoneelement,orasub-system,orthecompletefiresafetysystem,iscomparedtotheleveloffiresafetythatwouldbeachievedinanidenticalbuildinginwhichthatelement,sub-systemorsystemisdesignedincompliancewiththedeemed-to-satisfyorprescriptiveprovisionsidentifiedinSection1.2.8.Iftheanalysisiscarriedoutonsuchacomparativebasis,itwillinvolvethesameassumptions,models,calculationsandinputdatafortheproposedtrialdesignandthedeemed-to-satisfyorprescriptivedesign.Acomparativeapproachaimstodeterminewhetherthealternativesolutionisequivalentto(orbetterthan)thedeemed-to-satisfyorprescriptivedesign.Thecomparativeapproachisoftenreferredtoasan“equivalence”approach."QuantitativeAssessmentsThefollowingacceptancecriteriaareproposedfortheassessmentofthealternativesolutionscompliancewiththePerformanceRequirementoftheBCA.Theacceptancecriteriawillbetodemonstratethatfiresafetyisnotadverselyaffectedandthattheoccupantsmaysafelyevacuatethebuildingand/orthefirewillnotspreadtoadjacentpropertyand/orwillallowfirefighterstosafelyperformtheirduties.HeatRadiation-Thelimitingconditionforradiationisassumedtobeintherange1.57to6.3kW/m2.Thetolerancetimeforradiationatthislevelis6minutes.

    FireBrigadeIntervention:Inconsideringtheroleofthefirebrigadeinattackingafire,itisimportanttoestimatethetimeatwhichthebrigadewillbeeffectiveinlimitingthespreadofthefireandreducingtheheatoutputofthefireintheenclosureoffireorigin.Howeverthisresponsetimeisvariableandisafunctionofthetimeatwhichthealarmisreceivedatthefirestation,thetraveltimetothebuilding,thesetting-uptimeoncethefirebrigadehasarrivedandthetimetoimpactthefire.Whilethefirebrigadewillbeavailabletoassistevacuationthroughsearchandrescueofoccupants,thisactionisnotrelieduponforoccupantevacuation.Thefiresafetyassessmentisthereforeconservativeinthisregard.Theconditionsthatdefinethetenabilitycriteriaforfirebrigadepersonnelwillbeconsiderediftheoccupantscannotbeshowntohavesufficientavailableegresstimepriortoonsetofuntenableconditions.Incertaininstancesthefirebrigadeinterventiontimeswillberequiredtobedeterminedandtenabilityforthefirefightersassessedi.e.deletionofsprinklersfromacarpark.ThetimeforthefirebrigadetoarriveandcommencefirefightingoperationswillbedeterminedusingtheFireBrigadeInterventionModelorliteraturedataonthefirebrigaderesponsetimetofires.SummaryofTenabilityFailureCriteria:

    Condition CriteriaConvectiveheat Temperature>60oCwhensmokelayerisbelowtenabilityheight.Radiantheatexposure

    2.5kW/m2 at head height or smoke layer temperature exceeds 200oC when abovetenabilityheightof2.1m.

    Visibility 10mwhen smoke layer is below tenability height of 2.1m for large rooms or 5m forsmallrooms.

    Toxicity OD>0.1m–1(10dB/m)whensmoke layer isbelowtenabilityheightof2.1m,butnotaccessedifvisiblyacceptable.

    Thefollowingtableisanoverviewofthetenability’sasacceptedbytheFireandEmergencyServiceAuthoritiesCouncil(AFAC)1.

    RoutineConditionHazardousCondition

    ExtremeCondition

    CriticalCondition

    MaximumTime,min 25 10 1 10

    1 Weng Poh ‘Tenability in building fires: Limits and design criteria’. Fire Australia, 2010, No. 3,. pp 24-26

    T<1.57kW/m2to6.3kW/m2

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    37

    ApproachesandMethodsofAnalysisApproachFireengineeringdesigncaninvolvetheuseofanumberofapproachesincluding:

    • ComparativeorAbsolute• QualitativeorQuantitative• DeterministicorProbabilistic

    TheIFEGgivesdescriptionsofeachtypeofapproach,whereitcanbenotedthatadeterministicorprobabilisticapproachcanonlybeappliedtoaquantitativeanalysis.Thedifferencesbetweenacomparativeandabsoluteapproachandtypicalexamplesofacceptancecriteriaaredepictedinthefollowingtable(reproducedfromUKFireEngineeringGuidelinesPD7974-0).Comparativevs.AbsoluteApproach

    FireSafetyObjectives

    AnalysisMethod Deterministic Probabilistic

    Comparative TimeavailableforescapeisatleastequaltothatinanequivalentcodecompliantbuildingLevelofriskoflifeequivalenttoacodecompliantbuilding

    Absolute ThetimeavailableforescapeexceedsthetimetountenableconditionsExpectednumberofcasualtiesperyear

    Adefinitionofeachtypeofapproachisoutlinedinthefollowingtable,whichhasbeenadoptedfromtheIFEG.Thetypeofapproachadoptedwilldependonthetypeofcomplianceissueinquestionandsubsequentmethodsofanalysiswillbeprepared.AnalysisApproaches

    Approach Definition

    Comparative A comparative approachaims todeterminewhether the alternative solution is equivalent to (orbetterthan)thedeemed-to-satisfyorprescriptivedesign.Thecomparativeapproach isoftenreferredtoasan“equivalence”approach.

    Absolute In an absolute approach, results of the analysis are matched directly against the PerformanceRequirementoftheBCA,usingagreedacceptancecriteria.

    Qualitative AqualitativeanalysismaybeagreedduringtheFEBprocesstobesufficientfortheconsiderationofminorstand-alonecompliance issues.Thebasis (logic)onwhich thisapproach isusedshouldbedocumentedwithappropriatereferences.

    Quantitative Thecomplexityofthecomplianceissueswilloftenrequireaquantitativeapproach.ThisentailstheuseofoneormoreofthemanyanalysismethodsavailableThequantitativemethodswilloftenbesupportedbyadditionalqualitativearguments.

    Deterministic Deterministicanalysesarebasedonphysicalrelationshipsderivedfromscientifictheoriesandempiricalresults.Characteristically,foragivensetofinitialboundaryconditions,adeterministicmethodologywillalwaysproducethesameoutcome.Theydonot,however,indicatetheprobabilityofthatoutcomebeingrealized.

    Probabilistic Probabilistic approaches use a variety of risk based methodologies. These methods generally assignreliabilities to the performance of the various fire protection measures and assign frequencies ofoccurrenceofevents.Theymayanalyseandcombineseveraldifferentscenariosaspartofacompletefireengineeringevaluationofabuildingdesign.Thisuseofmultiplescenariosandtheircombinationthroughprobabilistictechniquesisthekeyfeatureofsomeofthemethods.

    ConstructionandCommissioningRequirementsThefiresafetymeasuresshallbedesigned,installedandcommissionedinaccordancewiththerelevantAustralianStandards.

    • Themanagementof thebuildingmustbeawareof theAlternativeSolutioncontainedwithin thebuilding,aswellas therequiredmeasuresformaintenance.

    • The BuildingManagement System,must incorporatemaintenancemeasures to ensure satisfactorymaintenance, testingandinspectionofallfiresafetymeasures.

    Allfiresafetymeasuresaretobecommissionedandtestedpriortooccupationofthebuilding.Thefireservicescontractormustprovidecertificationoftheinstallationandcommissioningofthefireservicesrequiredbythisreport,includingbutnotlimitedto:

  • J2CONSULTINGENGINEERS|FIRESAFETYENGINEERINGALTERNATIVESOLUTIONREPORT–1407PacificHighway,Warrawee

    38

    • FireHydrantsSystems• Smokedetection• Firedoorsandsmokeseals• Exitsignage&emergencylighting• Appropriatedoorhardwareanddoorswing

    Thefiresafetymeasureswithinthebuildingmustbemaintainedtoensurecorrectoperationatalltimesthatthebuildingisoccupied.Allfirefightingequipmentshouldbetaggedwhentested/inspectedandlogbookskeptup-to-dateforallsmokedetection,warningsystemsandsprinklersystems(whereinstalled).AnannualfiresafetycertificatemustbesubmittedtothelocalconsentauthorityandtheNSWFireBrigadeeachyearindicatingsatisfactoryperformanceofthefiresafetymeasurescontainedwithinthebuilding.Theannualfiresafetystatementshouldbedisplayedinaprominentplacewithinthebuilding(i.e.themainentryfoyer).Thecorrectoperationandmaintenanceofthebuildingsfiresafetymeasuresiscriticalinaffordinganadequateleveloffiresafety.OtherissuesidentifiedintheFEB/Rthatwillneedtobeincorporatedintothemanagementinuseofthefacilityinclude:

    • Nosmokingpolicyistobeimplementedinallpublicareas.• Commissioning and integrated function testing of all fire safety and protection systems including interfaces to ensure

    properfunction.• AllessentialservicesaretobemaintainedandtestedinaccordancewithBCAandAustralianStandardAS1851.• Ensureexitsandpathsoftraveltoexitsremainunobstructed(inparticularstairways).• Avoidstorageofmaterialsinunoccupiedareas.• Limitstorageofflammable/combustiblematerialstodesignatedandapprovedareas.• Preventchockingopenfire/smokedoors.• Preventstorageofmaterialsthatcouldhinderaccesstofirefightingequipment.