1 | weatherization assistance program standardized curriculum – december 2012eere.energy.gov hvac...

71
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY

Upload: talon-hetherington

Post on 31-Mar-2015

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

HVAC Distribution Systems

WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY

Page 2: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

2 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Learning Objectives

By attending this session, participants will be able to:

• Name functions of the components of forced warm air, hot water, and steam distribution systems.

• Demonstrate common diagnostic and assessment methods for ducted distribution systems.

• Describe common problems for each distribution system type.

• Explain solutions to these common problems.

HVAC DISTRIBUTION SYSTEMS

Page 3: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

3 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Good Ducted System Design

A well-designed duct system:• Provides conditioned air to meet all room heating loads.

• Provides thermal comfort evenly in all conditioned rooms.

• Is properly sized so that static pressure is within manufacturer specifications.

• Is sealed to provide proper airflow and prevent air from entering the house or duct system from polluted zones.

• Has balanced supply and return airflows to maintain a neutral pressure in the house.

• Minimizes duct air temperature losses between the air handler and supply registers.

HVAC DISTRIBUTION SYSTEMS

Page 4: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

4 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Forced Air Distribution System

The parts include:• An air handler at the furnace.• A heat exchanger where the heat from combustion is

transferred to the distribution air.• A supply air plenum to which the supply trunks are attached.• Branches attached to the supply trunk.• Supply registers through which conditioned air flows to the

living space.• Return grilles through which air flows back to the furnace.• Return branches and trunks attached to the return plenum.

HVAC DISTRIBUTION SYSTEMS

Page 5: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

5 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Ducted Distribution System

HVAC DISTRIBUTION SYSTEMS

Page 6: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

6 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Ducted Distribution System, Cont’d

HVAC DISTRIBUTION SYSTEMS

Page 7: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

7 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Open Returns

Photo Courtesy of PA Weatherization Training Center

Open return

Draft hood(open at bottom)

HVAC DISTRIBUTION SYSTEMS

Page 8: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

8 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Atmospheric Gas Furnace

Distribution System Components

Find the:

1. Circulating fan

2. Air filter

3. Cold air return

4. Heat exchanger

5. Warm air to house

Source: Heating with Gas, Natural Resources Canada, 1998.

HVAC DISTRIBUTION SYSTEMS

Page 9: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

9 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Function of Heat Exchanger

• The furnace heat exchanger is where the heat from combustion gases—usually between 70% and 95%— is transferred to the distribution air in the ductwork.

• The heat exchanger is an extremely important part of any furnace because it can have a significant impact on efficiency and health and safety.

• Combustion byproducts must not mix with distribution air.

HVAC DISTRIBUTION SYSTEMS

Page 10: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

10 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Heat Exchanger Leakage Testing

Test methods:

1. Visual inspection

2. Inspection with small torch

3. CO reading

4. Wavering flame

5. Tracer gas

Photo courtesy of New River Center for Energy Research and Training (NRCERT)

Damaged area of heat exchanger

HVAC DISTRIBUTION SYSTEMS

Page 11: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

11 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Ductwork Efficiency

• Specify duct sealing where ducts are located in unconditioned spaces.

• Ducts in unconditioned spaces should be insulated to recommended levels.

• Seal all returns in spaces where atmospheric fossil fuel appliances are located.

It is often necessary to remove duct insulation to properly seal ducts. Seal with mastic, then re-insulate.

It is often necessary to remove duct insulation to properly seal ducts. Seal with mastic, then re-insulate.

Photos courtesy of NRCERT

HVAC DISTRIBUTION SYSTEMS

Page 12: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

12 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Ductwork

This sheet metal ductworkis located within the building envelope, so it does not need to be insulated.Photos courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 13: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

13 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Ducted System Controls

The primary controls are:

• Thermostat.

• Fan and limit control.

• Balancing dampers.

• Motorized dampers (these are not common).

HVAC DISTRIBUTION SYSTEMS

Page 14: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

14 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Furnace Thermostat

The thermostat activates the burner on a furnace.

The fan and limit switch turns the air handler blower on and off.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 15: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

15 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Fan and Limit Control

This control turns the air handler blower on andoff at set temperatures. This is the fan control.

It also shuts down the blower if the heat exchanger area gets too hot (usually at about 200). This isthe limit control.

Recent versions areelectronic and cannot beadjusted in the field.

Graphic source: Heating with Gas, Natural Resources Canada, 1998.Photo courtesy of Honeywell.

HVAC DISTRIBUTION SYSTEMS

Page 16: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

16 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Balancing damperBalancing damper

Balancing Dampers

Graphic source: Heating with Gas, Natural Resources Canada, 1998.

Dampers help control airflow to rooms.

Manual balancing dampers are not as commonas they should be. Sometimes they need to be added.

HVAC DISTRIBUTION SYSTEMS

Page 17: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

17 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Motorized Dampers

Motorized dampers are used for zoning a ducted distribution system, rather than for balancing.

When a zone requires heat, the thermostat of that zone opens the zone damper and activates the furnace burner.

Motorized dampers are uncommon.

Motorized dampers are uncommon.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 18: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

18 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Common Ductwork Problems

Common problems include:

• Duct leakage to/from the outdoors.

• Restricted return side.

• System not balanced.

• Temperature too high or too low at heat exchanger.

• Static pressure out of range.

• Airflow of air handler fan not matched to system.

• People live within the distribution system. Closing a bedroom door or covering a register or grille can significantly alter airflow.

HVAC DISTRIBUTION SYSTEMS

Page 19: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

19 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Diagnostics for Ductwork

Diagnostics include:

• Pressure pan (duct leakage).

• Duct blower (duct leakage).

• Static pressure.

• Temperature rise.

• Room-to-room pressure differences (door restrictions).

• Air handler blower CFM flow.

HVAC DISTRIBUTION SYSTEMS

Page 20: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

20 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Pressure Pan

Test the duct system with a pressure pan and blower door to identify:

• Leakage to the outdoors when ducts are located outside the thermal boundary.

• Leakage pathways from duct-containing building cavities to the outdoors (e.g., floor-joist cavities adjacent to porch roofs, cantilevers).

Photo courtesy of NRCERT

Pressure pan testing of the duct

system

Pressure pan testing of the duct

system

HVAC DISTRIBUTION SYSTEMS

Page 21: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

21 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

• Depressurize house to 50 Pa with blower door.

• Test each register and grille. Document readings.

• Registers too large or oddly shaped may be covered with plastic and taped on edges.

• Seal duct leaks and retest.

• Goal = readings lower than 1 Pa

Pressure Pan Procedure Summary

Photo courtesy of NRCERT

The handle allows for easy testing of

hard-to-reach ducts.

The handle allows for easy testing of

hard-to-reach ducts.

HVAC DISTRIBUTION SYSTEMS

Page 22: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

22 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Pressure Pan Use

Sample mobile home duct pattern

Bedroom0.8 Pa

Bedroom1.2 Pa

Bath2.4 Pa

Furnace Closet (living room) 2.6 PaLiving Room

2.6 PaKitchen

1.2 PaKitchen

0.5 Pa

Total: 10.7 Pa

2.4 Pa at the bath register and 2.6 Pa at the living room register indicate a large leak between them, probably at the furnace plenum.

Photo courtesy of NRCERT

HVAC DISTRIBUTION SYSTEMS

Page 23: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

23 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Duct Blower for Duct Leakage

Use duct pressurization testing to quantify:

• Total duct leakage (to indoors and outdoors).

• Duct leakage to outdoors.

Photo courtesy of The Energy Conservatory

ManometerManometer

Duct blasterDuct blaster

HVAC DISTRIBUTION SYSTEMS

Page 24: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

24 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Duct Blower Procedure Summary #1

To test for total duct leakage:

1. Open a window or door to the outdoors.

2. Install duct blower to the air handler compartment.

3. Temporarily seal all supply registers and return grilles.

4. Insert manometer hose into a supply duct.

5. Open up rooms containing ducts.

6. Pressurize the ducts to 25 Pa and record the airflow.

HVAC DISTRIBUTION SYSTEMS

Page 25: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

25 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Duct Blower Procedure Summary #2

To test for duct leakage to outdoors:

1.Close all exterior windows and doors.

2.Set up blower door to pressurize the house.

3.Connect duct blower to air handler compartment and manometer hose to air handler compartment.

4.Temporarily seal all supply registers and return grilles.

5.Pressurize the ducts to 25 Pa.

6.Pressurize the house until the pressure difference of the house and the ductwork is 0 Pa.

7. Record the airflow at the duct blower.

HVAC DISTRIBUTION SYSTEMS

Page 26: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

26 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Room-to-Room Imbalances #1

Closed doors that prevent supply air from getting back to a return cause positive pressures in those rooms with supply vents. . .

…which starves the return for air, causing negative pressure in the zone where the return is located.

Return Supply

Closed door

HVAC DISTRIBUTION SYSTEMS

Page 27: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

27 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Room-to-Room Imbalances #2

MasterBedroom

Bedroom Bath

Utility Room Kitchen

Living Room

Whole-house return in hallway

HVAC DISTRIBUTION SYSTEMS

Page 28: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

28 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Room-to-Room Imbalances #3

Measure room-to-room pressure imbalancesRoom pressure imbalances over 3 Pa should be remedied by adding supply or return air. Then retest.

Photo courtesy of PA Weatherization Training Center

HVAC DISTRIBUTION SYSTEMS

Page 29: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

29 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Room-to-Room Imbalances #4

Graphic source: Air Distribution System Design, DOE, 2003.

Solutions1. Undercut door.

2. Add jumper duct.

3. Add door grille.

4. Add wall grille.

5. Add transfer grille.

6. Install return in affected room.

Find the size of the free vent area of your solution by opening the door while the air handler is running. When the manometer reading falls below 3 Pa, measure

the in2 of door opening. This is the in2 of free opening for your solution.

HVAC DISTRIBUTION SYSTEMS

Page 30: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

30 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Point the tip into the air stream

Measuring Static Pressure #1

Static pressure tip

Photo courtesy of Rob deKieffer

MagnetMagnet

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 31: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

31 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Measuring External Static Pressure• Check nameplate for External Static Pressure (ESP).

• Measure both return and supply sides of the air handler as the unit was shipped.

o Measure at inlet and outlet of blower.

o Have a clean filter in place (suggested).

o Don’t measure beyond the A/C coil unless it shipped with unit.

• Add return and supply pressures together, IGNORING the negative sign.

Measuring Static Pressure #2

HVAC DISTRIBUTION SYSTEMS

Page 32: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

32 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

External Static PressureIWC (Pa)

Air Handler Fan FlowCubic Feet per Minute

0.69 (173) 1,350

0.62 (155) 1,400

0.55 (138) 1,450

0.47 (118) 1,500

0.39 (98) 1,550

0.31 (78) 1,600

If the static pressure is too high, the fan flow will drop.

General External Static Pressure and Fan Relationship

Measuring Static Pressure #3

HVAC DISTRIBUTION SYSTEMS

Page 33: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

33 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Measuring External Static Pressure• If ESP is too high, the airflow might be blocked or the ductwork might

be too small or restricted.

• If ESP is too low, the ductwork might be very leaky or the fan might be dirty or damaged.

• Typical ESP totals are around 0.5 IWC or 125 Pa with an air conditioning coil and filter.

• Typical ESP totals are around 0.25 IWC or 62 Pa without an air conditioning coil and filter.

• It is preferred to have the return and supply sides of similar magnitudes, for example, a return of -34 Pa and supply of +31 Pa.

Measuring Static Pressure #4

HVAC DISTRIBUTION SYSTEMS

Page 34: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

34 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

• Place thermometer in supply side as close to furnace as possible but out of “sight” of the heat exchanger.

o Use manufacturer’s recommended measurement method, or

o Use the four-corner method (measure at each corner or supply plenum and average readings).

• Place thermometer in return side.

• Fire furnace.

• When the supply-side temperature reaches steady state, subtract return-side from supply-side temperature to get temperature rise.

• Check specified temperature rise on furnace name plate. Actual should be in the middle of the nameplate range.

Temperature Rise Test #1

HVAC DISTRIBUTION SYSTEMS

Page 35: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

35 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Measuring Temperature Rise &

Calculating CFM

Temperature Rise Test #2

The temperature rise for this example

is 70:

145 supply side

-75 return side

70 temperature rise

HVAC DISTRIBUTION SYSTEMS

Page 36: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

36 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Excessive temperature rise can result from:

• Low fan output.

o Wrong fan speed, bad motor bearings, low voltage to motor, dirty blower wheel, wrong motor rotation, slipping blower belt.

• Low airflow from restrictions in system.

o Undersized or restricted ducts, dirty filter, dirty cooling coil.

• Overfired burner (gas pressure or oil nozzle).

Temperature Rise Test #3

HVAC DISTRIBUTION SYSTEMS

Page 37: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

37 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Low temperature rise can result from:

• Excessive fan speed.

• Excessive duct leakage.

• Underfired burner.

o Low gas pressure.

o Oil nozzle not matched with airflow rate.

Temperature Rise Test #4

HVAC DISTRIBUTION SYSTEMS

Page 38: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

38 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Temperature rise that is too high can:

• Damage the heat exchanger.

• Cause rocking on the high limit.

Temperature rise that is too low can:

• Lead to condensation.

• Cause excessive soot buildup.

• Lead to occupant discomfort.

Temperature Rise Test #5

HVAC DISTRIBUTION SYSTEMS

Page 39: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

39 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

TrueFlow® Air Handler Flow Meter

Measures airflowin residentialair handlers

#20#14

Measuring Air Flow at Air Handler #1

Photos courtesy of The Energy Conservatory

HVAC DISTRIBUTION SYSTEMS

Page 40: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

40 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Airflow in CFM Furnace BTUH Input

500 Less than 60,000

700 60,000 to 79,999

900 80,000 to 99,999

1,200 More than 100,000

Measuring Air Flow at Air Handler #2

General Minimum Airflow Values

HVAC DISTRIBUTION SYSTEMS

Page 41: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

41 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Analysis of Existing Ductwork - 1Interview occupants about the thermal comfort of the existing system.

Ask about:• Uncomfortable rooms.

• Excessive noise.

• Frequent cycling of furnace.

Assessing Ductwork #1

Plumbing through return duct!Plumbing through return duct!Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 42: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

42 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Analysis of Existing Ductwork - 2Inspect air handler and ductwork for such things as:

• Disconnected ducts.

• Duct leakage.

• Restricted returns.

• Panned floor joists.

• Ducts in unconditioned spaces.

• Balancing dampers.

Assessing Ductwork #2

Disconnected duct!Disconnected duct!

Photo courtesy of R. Karg

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 43: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

43 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Do technical testing and appraisal of the duct system and equipment.

• Duct leakage

o Pressure pan testing

o Duct blower testing

• Room-to-room pressure imbalances

• Static pressure

• Temperature rise

• Blower CFM

Assessing Ductwork #3

Very dirty blower vanes!Very dirty blower vanes!

Photo courtesy of NRCERT

HVAC DISTRIBUTION SYSTEMS

Page 44: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

44 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Analysis of Existing Ductwork - 5Determine strategies for duct repair:

• Write down possible problems.

• Determine required alterations to furnace and ductwork.

• Decide on consumer education strategies.

Assessing Ductwork #4

HVAC DISTRIBUTION SYSTEMS

Page 45: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

45 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Good Hot Water Distribution Design

Good design:

• Provides conditioning to meet all room heating loads.

• Provides thermal comfort evenly in all conditioned rooms.

• Heats the dwelling quietly.

Hot water or steam distribution is often referred to as “hydronic.”

HVAC DISTRIBUTION SYSTEMS

Page 46: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

46 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Hot Water Distribution System

The parts include:

• Thermostat(s) that activate the circulator pump.

• Circulator pump(s). Might include zone valves rather than two or more circulator pumps.

• Aquastat control.

• A heat exchanger where the heat from combustion is transferred to the distribution water.

• Supply and return piping at boiler.

• The expansion tank.

• Hot water baseboard units (convector) where the thermal energy is transferred to the conditioned rooms.

HVAC DISTRIBUTION SYSTEMS

Page 47: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

47 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Series Loop Hot Water System

Based on graphic from the International Association of Certified Home Inspectors, Inc.

A series loop hot water distribution system is probably the most common system layout because it is the least expensive.

HVAC DISTRIBUTION SYSTEMS

Page 48: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

48 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Series Loop Hot Water Baseboard

Typical hot water baseboard distribution

Photos courtesy of Slant/Fin

Damper finDamper fin

HVAC DISTRIBUTION SYSTEMS

Page 49: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

49 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Expansion Tanks

Old-style tanks (above) and newer tanks (right) allow for expansion of heated water and contraction of cool distribution water.

Photos courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 50: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

50 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Hot Water Distribution Controls

Thermostat

Circulator pump(s)

Zone valves

Aquastat

HVAC DISTRIBUTION SYSTEMS

Basic controls include:

Page 51: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

51 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Boiler Thermostat

The thermostat activatesthe boiler circulator orzone valve and circulator.

The aquastat controlsthe burner.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 52: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

52 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Boiler Aquastat

An aquastat:1. Maintains boiler water

temperature.

2. Provides high-limit temperature protection.

3. Will not allow circulator to operate if boiler water temperature is too low.

Also assists with DHWtemperature control if the

water heater is tankless or indirect-fired.

Normally, the aquastat control is covered.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 53: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

53 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Zone Valves

Zone valves are controlled by thermostats in each zone.

This house has 3 zones with one thermostat for each.

The 4th zone valve is for domestic hot water from the boiler.

Zone valves take the place of circulators.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 54: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

54 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Hot Water #1

Poor maintenance:• If a hot water distribution

system is maintained properly, there is little that can go wrong.

o Oil-fired boilers should be cleaned and tuned every year.

o Gas-fired boilers should be cleaned and tuned once every three years.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 55: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

55 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Hot Water #2

Older tanks (above) shouldbe drained and refilled annually.

Newer expansion tanks (right)require very little maintenance.

Poor expansion tank maintenance

Photos courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 56: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

56 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Hot Water #3

If the air bleeder valve malfunctions, air will not be purged from the distribution system.

This air (oxygen) will create sludge and make the system noisy as the air is pumped with the water.

Air bleeder ventAir bleeder vent

Expansion tankExpansion tank

Air in the distribution system

HVAC DISTRIBUTION SYSTEMS

Page 57: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

57 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Good Steam Distribution Design

A good design:

• Provides conditioning to meet all room heating loads.

• Provides thermal comfort evenly in all conditioned rooms.

HVAC DISTRIBUTION SYSTEMS

Page 58: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

58 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Steam Distribution System

The parts include:

• A thermostat(s) that activates the circulator pump.

• Pressure control (Pressuretrol).

• A heat exchanger where the heat from combustion is transferred to the distribution water/vapor.

• Supply and return piping at boiler.

o For one-pipe distribution, the supply and return pipes are the same.

o For two-pipe distribution, there are separate supply and return pipes.

• Steam radiators that transfer thermal energy to the conditioned rooms.

HVAC DISTRIBUTION SYSTEMS

Page 59: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

59 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Steam Distribution Controls and Gauges

Basic controls include:

• Thermostat

• Pressure control (Pressuretrol)

• Sight or gauge glass

• Low-water cutoff

HVAC DISTRIBUTION SYSTEMS

Page 60: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

60 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Steam Boiler Thermostat

The thermostat activates the steam boiler burner.

The Pressuretrol turns the burner off when the set pressure is reached.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 61: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

61 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Steam Boiler

Pressuretrol(pressure control)

Sight glass

Low-water cutoff

Oil burner

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 62: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

62 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Steam Distribution Controls

Sight (gauge) glass

Low-water cutoff

The low-water cutoff will shut off the burner if the water falls to an unsafe level. This is required by code.

The sight or gauge glass provides an easy way to determine the water level in a steam boiler.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 63: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

63 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Pressure Control for Steam

Photo courtesy of Honeywell Controls

This device determines the operating range of the boiler during the heating cycle.

When the thermostat calls for heat, the burner will cycle up to the cut-out pressure setting of the Pressuretrol. The burner will then shut off.

HVAC DISTRIBUTION SYSTEMS

Page 64: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

64 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

One-Pipe Steam Distribution

Graphic based on Basic Steam Heating Systems, Hoffman Specialty, ITT Industries, 1999, p. 2, www.hoffmanspecialty.com.

One-Pipe Steam Distribution

Both steam and condensate use the same pipe.

Steam travels to each radiator, condenses (giving off heat), and flows back to the boiler through the same pipe as condensed water.

HVAC DISTRIBUTION SYSTEMS

Page 65: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

65 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Two-Pipe Steam Distribution

Steam moves to theradiators in one pipe and the condensate flows back to the boiler through the other pipe.

These pipes are usually a smaller diameter thanone-pipe systems.

Graphic based on Basic Steam Heating Systems, Hoffman Specialty, ITT Industries, 1999, p. 2, www.hoffmanspecialty.com.

HVAC DISTRIBUTION SYSTEMS

Page 66: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

66 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Steam #1

Steam distribution pipesare sometimes coveredwith asbestos insulation.

If this material is friable,be careful; it might bebest to avoid blower doortesting.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 67: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

67 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Steam #2

Air valveAir valveSupply valveSupply valve

If one- or two-piperadiators don’t heat up, the supply valve may be closed or the airvalve may be blocked.

Two-pipe radiator

Photo source: The Open Fire Centre Ltd., Yorkshire St., Oldham, Lancashire, UK. www.fireplaces-oldham.co.uk.

HVAC DISTRIBUTION SYSTEMS

Page 68: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

68 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Steam #3

Steam pressure is often set too high. This can cause distribution problems and wastes energy.

For most residential low-pressure, one-pipe systems, 2 psi cut-out pressure or less will work fine and maximize efficiency.

High pressure can cause distribution problems and waste energy.

Photo courtesy of Bill Van der Meer

HVAC DISTRIBUTION SYSTEMS

Page 69: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

69 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Potential Problems with Steam #4

When replacing a steamboiler, the new unit mustbe sized to match the installed radiation, rather than the heat load of the house.

Photo courtesy of R. Karg

HVAC DISTRIBUTION SYSTEMS

Page 70: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

70 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Summary #1

• The function of all distribution systems is to provide even thermal comfort in all rooms of the home.

• Major components of forced air distribution systems include an air handler, heat exchanger, supply air plenum, supply and return registers, grilles, branches, and ducts.

• Forced air system diagnostic procedures include duct leakage testing, measuring static pressure, temperature rise, room-to-room pressure imbalances, and airflow across the heat exchanger.

• Common problems associated with ducted systems include room pressure imbalances, improper temperature rise, and energy wasted through duct leakage to the outdoors.

HVAC DISTRIBUTION SYSTEMS

Page 71: 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov HVAC Distribution Systems WEATHERIZATION ENERGY AUDITOR SINGLE

71 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012 eere.energy.gov

Summary #2

• Major components of hot water distribution systems include the thermostat, circulator pump, aquastat control, heat exchanger, supply and return piping, expansion tank, and hot water baseboard units.

• Major components of steam distribution systems include the thermostat, pressure control (Pressuretrol), heat exchanger, supply and return piping at the boiler, steam radiators, sight glass or gauge glass, and low-water cutoff.

• Some common problems associated with hot water or steam distribution include expansion tank degradation, low water levels (steam), or improper sizing once the home is weatherized.

• Compared with ductwork, hot water and steam distribution are relatively trouble-free, and diagnostic procedures are easy. We merely ask the occupants if there are problems with the thermal comfort of the home and conduct a simple inspection of the distribution components.

HVAC DISTRIBUTION SYSTEMS