Project N° Unit Document Code Serial N° Rev. Page 0775 21 CS 1600 03 B 1/9 TECHNIP KT INDIA LTD. B 19.08.2010 ISSUED FOR REVIEW ATG KDS VJK MB REV. DATE STATUS WRITTEN BY (Name) CHECKED BY (Name) APPROVED BY (Name) PM (Name) DOCUMENT REVISIONS Sections changed in last revision are identified by a line in the right margin The present document or drawing is property of TECHNIP KT INDIA LTD. and shall not, under any circumstances, be totally or partially, directly or indirectly, transferred, reproduced, copied, disclosed or used, without its prior written consent, for any purpose and in any way other than that for which it is specifically furnished or outside the extent of the agreed upon right of use. OWNER : OIL AND NATURAL GAS CORPORATION LIMITED. ENGG. CONSULTANT : TECHNIP KT INDIA LIMITED. PROJECT : G1 & GS-15 FIELDS DEVELOPMENT PROJECT PART-C SECTION-4 ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

Upload: sumantcsingh1694

Post on 12-Dec-2015

16 views

Category:

Documents


1 download

DESCRIPTION

rfg

TRANSCRIPT

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 1/9

TECHNIP KT INDIA LTD.

B 19.08.2010 ISSUED FOR REVIEW ATG KDS VJK MB

REV. DATE STATUS WRITTEN BY (Name)

CHECKED BY (Name)

APPROVED BY (Name)

PM (Name)

DOCUMENT REVISIONS Sections changed in last revision are identified by a line in the right margin

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d or

use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

OWNER : OIL AND NATURAL GAS CORPORATION LIMITED.

ENGG. CONSULTANT : TECHNIP KT INDIA LIMITED.

PROJECT : G1 & GS-15 FIELDS DEVELOPMENT PROJECT

PART-C SECTION-4

ELECTRICAL WORK FOR

STORAGE & TREATMENT OF RAW WATER FOR PLANT

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 2/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

CONTENTS

1.0 SCOPE OF WORK...................................................................................................................3

2.0 DETAILED SCOPE OF WORK................................................................................................3

3.0 NOTES .....................................................................................................................................6

4.0 INSPECTION............................................................................................................................8

5.0 APPROVALS ...........................................................................................................................9

6.0 OTHER REQUIREMENTS .......................................................................................................9

ATTACHMENT

1. SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION (Pages 8) 2. SCHEDULE OF QUANTITIES FOR ELECTRICAL SUPPLY (Pages 4) 3. ELECTRICAL LOAD LIST (FORMAT) (Page 1)

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 3/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

1.0 SCOPE OF WORK

1.1 The Scope of Work covers the survey, basic and detail engineering, procurement engineering, supply, installation, testing and commissioning of Electrical system required for PW / IWTU at Chunchulla Canal pump station & ONGC Gas Processing Terminal at Odalarevu.

2.0 DETAILED SCOPE OF WORK 2.1 ELECTRICAL WORK AT CANAL PUMP STATION FOR CONTRACTOR

ONGC shall provide the power supply from state Electricity grid by providing overhead lines with poles including step down pole mounted transformer at battery limit of canal pump station. Site survey, basic engineering, detail engineering, procurement engineering, supply, Installation, testing and commissioning of Electrical system starting from transformer secondary to the various electrical load of pump station is in the scope of contractor. This includes all electrical panels, motors, cables, wire, cable tray, trench, conduit, wiring, lighting fittings with lamps, switch sockets, mounting arrangement, supports, earthing, lightning protection & associated civil works etc as required to complete the facility in all respect. Completeness of facility till end of commissioning to be identified & shall be fulfilled by contractor without any implication.

Electrical panels shall be housed in the covered space in compliance of all statutory requirement, code and standards and tender document. Contractor shall provide all document & certificates to ONGC required for obtaining connection from state electricity.

Main electrical panel shall be minimum of IP 41 grade, wall/floor mounted and consists of the following as minimum but not limited to the following: • Incomer (Two way 200A manual changeover switch+200A MCCB with over current

(50% to 100% setting range), short circuit and earth fault protection (5% to 50% setting range).

• Each incoming power supply cubicle shall be with individual measuring instruments

(energy meter, ammeter with selector switch, voltmeter with selector switch), Indications (phase indications). Common MCCB trip indication shall be provided.

• Busbar 250A CU, 50kA TPN,

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 4/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

• Suitable star/delta starters for pump motors shall be provided . Starters shall have under current protection. Other features of star/delta starter shall be as per the design basis of onshore terminal plant (00701-21-JSD-1600-001)

• 63A TPN feeder for lighting cum small power distribution board

• One number 63A TPN feeder as spare • 32A TPN feeder as spare

• Motor spare feeder 10% of used or 1 whichever higher to be provided.

Industrial type lighting cum small power panel(s) shall be provided wall mounted with 63A MCB +ELCB and 12Nos, 10A SPN outgoing feeders as minimum. However, contractor shall be responsible to meet the requirement without any implication.

All above rating and quantities are as minimum. However, contractor shall be responsible to identify the complete requirement in all respect & to meet the requirement without any implication. Local control station shall be provided for each pump motor near the motor.

All required power & control cables shall be laid on trays/underground as required from transformer to panel(s) & panel(s) to motors, local control stations and lighting cum small power panel(s) etc. as minimum. However, contractor shall be responsible to meet the requirement without any implication. Lighting system shall be provided with suitable light fittings, with mounting arrangement including all wiring (through surface conduit/concealed conduit or armoured cable by cleat /laying in trench etc), switches, industrial type sockets as required for canal pump station.

Earthing system for pumping station shall be provided. At least two earth pits are to be provided. Earth resistance to be maintained <1 Ohm. Earth bus to be provided near each motor & panel.

Lightning protection shall be provided at canal pump station if required. Providing all cable glands, cable lugs, tray, trenches, supports & hardware etc. is in the contractor scope. All electrical safety hazard charts, rubber mat, first add, hand glows, tool kit, fire extinguishers, fire bucket with sand & stand etc. shall be provided for pump station.

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 5/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

Contractor shall also provide required tools & tackles, consumables and all equipments & machinery required for installation, pre-commissioning and commissioning of the system. Contractor’s responsibility to remove all unused/scrap material from site. Contractor shall provide all commissioning spares, consumables, and mandatory spares etc. Contractor shall provide load details in the prescribed format per required feeder with technical proposal/survey report.

2.2 ELECTRICAL WORK AT GAS PROCESSING TERMINAL AT ODALAREVU FOR PW/IWTU

ONGC shall provide the power supply feeder from existing electrical panels at substation. Lighting and small power supply feeders may be provided locally from nearest existing circuit/local panel which is subject to the load, availability of spare feeder/spare capacity of circuit (s) or ONGC shall provide separate feeder from the substation for lighting DB & small power DB. This is to be decided during detail engineering. Contractor shall provide load details in the prescribed format per required feeder with technical proposal/survey report. Site survey, basic engineering, detail engineering, interface requirement, supply, Installation, testing and commissioning etc of Electrical system required for PW / IWTU at ONGC Gas Processing Terminal at Odalarevu shall be carried out by contractor. This includes all electrical panels, motors, cables & wires, cable tray, trench, wiring, lighting fittings with lamps, switch sockets, mounting arrangement, supports, earthing, lightning protection, hardware & associated civil works etc as required to complete the facility in all respect. Completeness of facility till end of commissioning to be identified & shall be fulfilled by contractor without any implication. Contractor shall provide the local control stations/panel for pump motors. All required power & control cables shall be laid on existing tray/trench wherever available. The availability of existing tray/trench shall be finalized during detail engineering. However, new trays with supports, hardware & buried trenches with sand and bricks as required shall be provided by contractor including all civil works, materials etc.

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 6/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

Providing earthing of motors, skids, local control stations, JBs, poles, DBs & panels etc. from plant earth grid is in the contractor scope. This includes the provision of earth buses, earthing cables, earth strips, lugs, hardware, extension of plant grid thru buried trench etc. Providing lighting system for pumps area etc. This includes providing lighting fixtures, poles, JBs, cables, gland, lugs, hardware & supports etc. Necessary buried trench as required shall be provided by contractor. Power supply for lighting fixtures may be taken from nearest lighting points as available or to be drawn from substation. Necessary cabling, civil work etc as required shall be carried out by contractor. Contractor shall also provide required tools & tackles, consumables and all equipments & machinery required for installation, pre-commissioning and commissioning of the system. Contractor’s responsibility to remove all unused/scrap material from site. Contractor shall provide all commissioning spares, consumables, and mandatory spares etc. Contractor shall provide load details in the prescribed format per required feeder with technical proposal/survey report.

3.0 NOTES

3.1 Contractor shall be responsible for the estimation of electrical materials. It is clearly understood that completion of the system and its hook-up etc. in totality shall be in contractor scope irrespective of the same is covered in this tender or not. The Contractor shall own single point responsibility from survey to commissioning including basic engineering, detail engineering, procurement engineering, interface responsibility, supply, installation procurement, inspection, testing etc.

3.2 All electrical installation shall conform to various job specifications already issued for construction.

3.3 All electrical materials shall confirm to the electrical design basis doc no. 000701-21-JSD-1600-01, Rev 0, general supply rules for LV induction motors doc no. 00701-21-JSS-1691-001, Rev 0, General Supply Rules for Low Voltage Switchgear doc. No. 00701-21-JSS-1654-01, Rev 0, General Supply Rules for Electrical HV & LV Cables & Accessories doc. No. 00701-21-JSS-1621-01, Rev 0, General Supply Rules for Local Control Station doc no. 00701-21-JSS-1627-01, Rev 0, Typical installation Detail – Power doc no. 00701-21-STD-1682-001, Typical installation – Earthing doc no. 00701-21-STD-1681-001, Typical installation – Lighting doc no. 00701-21-STD-1683-001, Area classification drawing doc no. 00701-21-DW-1920-001, Overall Earthing Layout

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 7/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

doc no. 00701-21-DW-1611-001, Earthing & Lightning Protection Layout - Plant Area doc no. 00701-21-DW-1611-006 & data sheets.

3.4 All technical requirements shall be followed strictly. Materials not fully conforming to the above shall be rejected by the owner at any stage of inspection/construction or commissioning. Contractor shall be responsible to replace all such items at his cost within the given time schedule.

3.5 All engineering document shall be submitted to the owner/PMC for their information/review/approval.

3.6 Exceptions or deviations to the job specifications shall be allowed, only where the contractor has obtained written prior approval of the Owner.

3.7 Any difference between the item description / details mentioned in elsewhere, above documents / specification / data Sheets or any other codes/ standards etc, shall be reported to the Owner before taking any procurement action. In such cases the stricter requirement will apply. Owner’s decision shall be final and binding.

3.8 Vendor document shall be reviewed and approved by contractor prior to send to OWNER/PMC for their review/information/approval.

3.9 House keeping shall be an integral part of work of contractor & shall be provided as & when required as per the instruction of engineer incharge.

3.10 Slippage of any kind happening in the process of review of any of the Contractor’s documents by OWNER/ PMC shall in no case absolve the CONTRACTOR of his contractual obligations.

3.11 In case imported equipment, standards of country of origin shall be applicable, if these standards are equivalent or stringent than the applicable Indian standards.

3.12 In case Indian standards are not available for any equipment, standards issued by IEC/BS/VDE/IEEE/NEMA or equivalent agency shall be applicable.

3.13 The offered items shall be brand new with state of art technology and proven field record. No proto type equipment shall be offered.

3.14 Vendor shall ensure the availability of spare parts and maintenance support services for the offered equipment for at least seven years from the date of supply.

3.15 Vendor shall give a notice of at least one year to the end user of equipment before phasing out the product/spares to enable the end user for placement of order for spares and services.

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 8/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

3.16 Offered items shall be suitable to operate under specified site conditions.

3.17 Vendor document shall be forwarded to OWNER/PMC for their review and approval. Vendor documents shall be review & approved by contractor prior to send to the OWNER/PMC.

3.18 This is sole responsibility of contractor for their items to meet the requirement as well as satisfactory operation with plant integration & this is not subject to review & approval of document from OWNER/PMC. OWNER/ PMC may point out any observation at any stage of project; contractor shall be responsible for compliance without time and price implications.

3.19 Weekly program of detailed activities must be proposed by the Contractor, approved and then authorized by Engineer in Charge. The programs should take in consideration the overall schedule and availability of materials.

3.20 The installation activities in the existing plant area are subject to the issue of permits to work.

3.21 Contractor shall issue daily report on forms that will be approved by Construction Management, 1 month before the beginning of works.

3.22 Dedicated people such as supervisors, foremen and technicians with relevant equipment and tools shall be especially assigned to tasks as per the construction programme.

3.23 Temporary storage, labeling, preservation, and identifications of all materials in storage by contractor.

3.24 Power supply required for construction/installation/testing and commissioning shall be provided by contractor at their own cost.

4.0 INSPECTION Purchaser or his authorised representative (third party) will carry out inspection. All assistance shall be provided for the same and timely co-ordination shall be the responsibility of the Contractor.

5.0 APPROVALS Contractor shall prepare and submit all documents /drawings for approval to the concerned state /local authorities and extend full assistance and follow up in getting the required approvals in time.

Project N° Unit Document Code Serial N° Rev. Page

0775 21 CS 1600 03 B 9/9

TECHNIP KT INDIA LTD. ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER FOR PLANT

OWNER : Oil And Natural Gas Corporation Limited.

PROJECT : G1 & GS-15 Fields Development Project

The

pres

ent d

ocum

ent o

r dra

win

g is

pro

perty

of T

EC

HN

IP K

T IN

DIA

LTD

. an

d sh

all n

ot, u

nder

any

circ

umst

ance

s, b

e to

tally

or p

artia

lly, d

irect

ly o

r ind

irect

ly, t

rans

ferre

d, re

prod

uced

, cop

ied,

disc

lose

d o

r use

d, w

ithou

t its

prio

r writ

ten

cons

ent,

for a

ny p

urpo

se a

nd in

any

way

oth

er th

an th

at fo

r whi

ch it

is s

peci

fical

ly fu

rnis

hed

or o

utsi

de th

e ex

tent

of t

he a

gree

d up

on ri

ght o

f use

.

6.0 OTHER REQUIREMENTS Guarantee / Warranty, Quality plan, Inspection, HSE Requirements, documentation requirements and others shall be governed by other project requirements which shall be furnished to the Contractor during job execution.

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 1 of 8

QTY QTY

At Canel pump station At Gas processing unit

1.0 ELECTRICAL WORK FOR STORAGE & TREATMENT OF RAW WATER PLANT FOR PLANTEQUIPMENT INSTALLATIONS

1.1 WEATHERPROOF LIGHTING PANELS/ POWER PANELS

Installation, earthing, testing and commissioning of wheatherproof lighting cum power panels wallmounted, supply & making of concrete foundations, painted steel support, if so required forsupports.Glanding and termination of all incoming and outgoing cables including supply of Cu lugs &all consumables as per drawings, specification and direction of Engineer-in-charge. This shall includetransportation from owner's issue point within plant to actual place of installation by contractor's ownlifting & transporting arrangement.Free issue items shall be issued as & where basis, this includes the identification of mismatches/un-healthiness /shortage of items & shall be rectified/provided by E&I contractor to make inline with therequirement.

1.1.1 Weather proof, industrial type switchboard double front/single front with lifting lugs, base channel, 250A TPN, 50KA for 1 sec cu busbar for main outgoing feeder, Totally metal enclosed, compartmented, floor Mounted, Dust & Vermin Proof, Enclosure Protection not less than IP 41 with TPN busbars with Metering, Protection, Control indication circuits with Earthing lugs, cable lugs & cable galnds complete in all respect in line with specifications & other enclosed documents and relevant IS codes. Detail of incomer & outgoing feeder as given below :-

A) 1 no. Incomer:- • Incomer (Two way 200A manual changeover switch+200A MCCB with over current (50% to 100% setting range), short circuit and earth fault protection (5% to 50% setting range.• Each incoming power supply cubicle shall be with individual measuring instruments (energy meter, ammeter with selector switch, voltmeter with selector switch), Indications (phase indications). Common MCCB trip indication shall be provided.

B) Outgoings:- 1) Suitable star/delta starters for pump motors shall be provided . Starters shall have under current protection. Other features of star/delta starter shall be as per the design basis of onshore terminal plant (00701-21-JSD-1600-001). 2) 63A TPN feeder for lighting cum small power distribution board3) One number 63A TPN feeder as spare4) 2nos. 100A SFU TPN with ON indication.5) 32A TPN feeder as spare 6) Motor spare feeder 10% of used or 1 whichever higher to be provided.

Nos 1 1

1.1.2 Weatherproof, Industrial type Local Lighting Cum Power Panel with canopy with 63 Amps 4 pole MCB & ELCB as incomer and 12Nos.10 Amps Single pole MCB as outgoings. Nos 1 1

2 MOTORS

EARTHING, TESTING, PRE-COMMISSIONING & COMMISSIONING OF LT MOTORS

TOTAL QTYS.NO. UNITDESCRIPTION

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 2 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

Earthing Testing and commissioning of free issued low voltage 3-phase Ex'd'/Ex'e'/Safe area,induction motors installed by others. Motor shall be tested for insulation value, winding resistanceetc.If the insulation value is found to be lowed, it shall be improved by heating by means of externalheater or by low voltage injection locked rotor method. Health check for condition assessment Motoralignment to be checked and verified. Motors shall be de-coupled and run on no load for eight hoursand hourly readings of insulation, current, temperature etc. to be recorded. Motors shall be coupled toload and aligned after successful completion of no load run and then to be run on load under specificinstruction of the Engineer-in-charge. Load run parameters to be recorded.Change of grease inbearings including supply of approved type of grease. All tools, instruments required for the job are tobe provided by the E&I contractor. Including all labour as per specification of this tender anddirections of Engineer-in-charge.

2.1 415V MOTORS

2.1.1 Upto & including 3.7 KW Nos. 8 8

2.1.2 From 5.5 KW upto & including 15 KW Nos. 2 2 4

2.1.3 From 18.5 KW upto & including 37 KW Nos.

2.1.4 From 45 KW upto & including 75 KW Nos.

2.1.5 From 90 KW upto & including 160 KW Nos.

2.2 CANOPY FOR HT / LT MOTORS

(Quantities are tentative)

Supply, fabrication and erection of hot dip galvanised GI sheet steel canopy (2mm thick) for outdoor LT motors of following frame sizes and mounting including supply of all hardwares etc.

415V MOTORS

2.2.1 Upto ND112M ( Upto 3.7 KW ) Nos. 8 82.2.2 Upto ND160M ( Above 3.7 KW & Upto 9.3 KW ) Nos.

2.2.3 Upto ND200L ( Above 11 KW & Upto 30 KW ) Nos. 2 2 42.2.4 Above 30 KW & Upto 37 KW Nos.

2.2.5 Upto ND280S ( Above 37 KW & Upto 75 KW ) Nos.

2.2.6 Upto ND315S ( Above 75 KW & Upto 110 KW ) Nos.

2.3 LOCAL CONTROL STATIONS(Quantities are tentative)

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 3 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

2.3.1 Installation, Earthing ,Testing & Commissioning of weather proof, Industrial type local controlstations (LCS) on steel structures/concrete coloumn/wall as per drawing and specification includingsupply & making of concrete foundations, if so required for supports.This also includes supply of GIconsumables,canopy (If required), cement, sand necessary hardwares,painted steel supports,touchup painting, all materials & labour complete as per approved drawings, specification of this tender anddirections of Engineer- in -charge. E& I contactor furnish the unit price of each type of LCS foraddition/deletion purpose.

2.3.1.1 LCS with Start/Stop PBs Nos.6 6

2.3.1.2 LCS with Start/Stop PBs & ammeter Nos.2 2

2.3.1.3 LCS with Start/Stop PBs & Auto- Manual Selector switch Nos. 2 2

2.3.1.4 LCS withStart/Stop PB, Ammeter & Auto-Manual selector switch Nos. 2 2

3.1 LIGHTING FIXTURES/CONTROL GEAR BOX

Installation,earthing,glanding,termination of Incoming and Outgoing Cables/ wires at luminaire andcontrol gear box, testing and commissioning of different type of lighting luminaires (eg. street light,fance light, flood light wall/celling/recess/pole mounting etc.with flourescent/ MV/ SV/ MLL/ GLS/CFLlamps), Control gear box and other accessories. This shall include transportation from owner's issuepoint to actual place of installation by E&I contractor's own lifting & transporting arrangement,unpacking assembly of luminaries, supply and installation of all fixing accessories, support if sorequired & GI hardwares, minor civil work like grouting/ chipping/ remaking etc. as required, all labourand material complete as per drawings, specification of this tender and directions of Engineer-in-charge. This will also include any modifications required to be carried out on the mounting bracket tosuit mounting of lighting fixtures & any modifications inside control gear box/fixture for propercommissioning of fixture.Free issue shall be issued as & where basis, this includes the identification of mismatches/un-healthiness /shortage of items & shall be rectified/provided by E&I contractor to make inline with therequirement.

3.1.1 Industrial type flourescent tube light/CFL fixture with 2x36/40W flourescent lamps, high frequency electronic ballast as per requried Nos. 6 6

3.1.2 Commerical type street lighting fixture (aluminium bright anodised reflector provide for optical efficiency) with 1x 85W Compact flourescent lamps Nos. 10 10

3.1.3 Industrial type, non intergal type flood light fixture of cast aluminium housing and spun aluminium reflector heat resistant glass cover & adujsting facility with 400W HPSV lamp. Nos. 5 3 8

3.1.4 Industrial type type Control gear box suitable for 400 W HPSV lighitng fixture (flood light) 5 3 8

4.1 SOCKETS OUTLETS

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 4 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

Installation,Earthing,glanding,termination of Incoming and Outgoing Cables/ wires, testing &commissioning of Convenience Socket Outlets including supply of all necessary supports,minor civilwork, including supply of GI consumables etc.,including all labour, materials and accessories likefixing bolt, complete as per drawings, specifications of this tender and directions of Engineer-in-charge.

4.1.1 Industrial type, non-flameproof, 15 A, 240 V Convenience socket with switch Nos. 2 2

5.1 WELDING SOCKETS

Installation, Earthing ,Testing & Commissioning of weather proof /flame proof welding sockets onsteel structures/concrete coloumn/wall as per drawing and specification including supply & making ofconcrete foundations, painted supports,if so required etc.This also includes supply of GIconsumables, cement, sand necessary hardwares,touch up painting, as requried all labour andmaterials complete as per approved drawings specification of this tender and directions of Engineer-in -charge.

5.1.1 Weather proof with IP-55 protection welding socket (63 Amps) including FRP canopy Nos. 1 1

6.1 LIGHTING POLES

Installation, alignment & earthing of single arm/ double arm GI/ painted lighting pole as per approveddrawing including , supply of all necessary G.I consumables and hardwares ( Including U Clampsalso),necessary excavation, providing concrete foundation including supply of cement and associatedmaterials disposal of surplus earth, providing shoring,shrutting, dewatering if required and other civilworks as necessary including painting, supply of paint, fixing of G.I pipes, sealing of cable entry atbase plates G.I flat for earthing purpose all labour and materials complete as per approved drawings,specification of this tender and directions of Engineer-in-charge. This shall include transportationfrom owner's issue point within plant to actual place of installation by contractor's own lifting &transporting arrangement.Free issue item shall be issued as & where where basis, this includes theidentification of mismatches/un-healthiness /shortage of items Minor mismatch/un-healthiness/shortage of item shall be rectified/provided by E&I contractor to makeinline with the requirement.

6.1.1 Street lighting pole of 7.5 M height suitable for 1 fixtureNos. 5 3 8

6.1.2 Street lighting pole of 11.0 M height suitable for 1 fixtureNos. 10 10

6.2 JUNCTION BOX

Installation, earthing, testing and commissioning of junction box,Marshlling box surface/ structure/pole mounted, Glanding and termination of all incoming and outgoing cables including supply of Culugs & all consumables as per drawings, specification and direction of Engineer-in-charge.

6.2.1 Industrial type weather proof 4 way lighting junction box Nos. 2 1 3

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 5 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

7.1 POINT WIRING

Point wiring in concealed/ surface conduit including supply and erection of GI/ PVC conduits withcomplete accessories, copper wires, recessed GI boxes housing for switches/ sockets of 5A, 15A, 5A/ 15A rating, lighting fixture box, fan box, AC DB including chipping and remaking of chasses for walls/ceilings for embedding conduits, cutting and sealing of wall for installing boxes etc. Supply of lightingfixtures/switches/fan/socket considered elsewhere.

7.1.1 LIGHT POINT CONTROLLED BY MCB WITH CABLENos. 3 3

Wiring of flood light/medium bay light with 3c x 2.5 sq.mm PVC insulated single core copperconductor cable in surface/ recessed GI/ PVC conduit including all accessories on surface or inrecess, including supply and fixing of MCB, GI box including circuit wiring, earthing of light fixture with2.5 sqmm PVC insulated single core copper wire etc.as required. The above scope includes cutting,chasing of wall and filling the chases with mortar and making good finish as required. From pole box/marshalling box/control gear to lighting fitting with 3c x 2.5sqmm cable including earthing of lightfixture with 2.5 sqmm PVC insulated single core copper wire, termination of wires at pole box/marshalling box/control gear & at lighting fitting. This also include the supply of wires.Supply andwiring of light point

7.1.2 SUPPLY & WIRING OF 15A SWITCH SOCKET OUTLET Nos. 2 2Supply and wiring of 6 pin 5/15A switch socket outlet with 2.5/4 sq.mm PVC insulated single corecopper conductor in surface/ recessed/wall GI/ PVC conduit including all accessories on surface or inrecess, including supply and fixing of switch socket outlet,GI box, cover plate including earthing of 3rdpin 2.5 sqmm PVC insulated single core copper wire etc.as required. The above scope includescutting, chasing of wall and filling the chases with mortar and making good finish as required.

7.1.3 STREET LIGHTING POLES & OUTSIDE FLOOD LIGHT WIRING CONTROLLED BY SFU FEEDER

Wiring of lighting poles/flood light/medium bay light controlled by SFU feeder in existing feeder pillarwith 4C x 16/4C x 10sqmm copper cable Inculding installation of 4 way JB. For street light from polebox/ marshalling box/control gear to lighting fitting with 3c x 2.5sqmm cable including earthing of lightfixture with 2.5 sqmm PVC insulated single core copper wire, termination of wires at pole box/marshalling box/control gear & at lighting fitting. This also include the supply of wires.

7.1.4 lighting pole of 7.5 M height suitable for 1 fixture Nos. 5 3 87.1.5 Street lighting pole of 11.0 M height suitable for 1 fixture Nos. 10 10

8.1 EARTHING AND LIGHTNING PROTECTION INSTALLATION

8.1.1 EARTH PITS

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 6 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

Installation with required treatment with Salt and charcoal as per procedure inclusive of chamber andother accessories as per Installation Drawing, connection to main earth grid, testing andcommissioning of earth pits in hard soil area complete with 65 mm dia & 3000 mm long GI pipeelectrode with funnel, GI test link, earth bus, concrete chamber with hinged CI cover includingexcavation of earth pit, supply and filling salt/ coke/ charcoal and sand layer, supply of civil material,back filling, numbering of pits, including measurement of Earth resistance, including all labour andmaterials as per standard drawing complete as per specification of this tender and directions ofEngineer-in-charge.

Nos. 2 2

Supply & Installation of chember, testing & required treatment to achieve resistance as per the projectspecifications for already installed electrodes. This includes identification, healthiness of earth pit &ensure/provide the continuity with main earth grid.

8.1 LAYING OF EARTHING CONDUCTORS AND CONNECTIONS

Receivig, lifting, shifting to work location from the place of issue which is within site premises,Laying,clamping and connecting following GI/Al/Cu earth conductors for main earth loop/earthingnetwork along structure, cable trays, racks walls,roofs,underground ,in trench etc. includingexcavation and back filling of earth,chipping and remaking of concrete surface,supply and fixing ofGI/Al clamps, supply & fixing of GI fasteners and Cu/Al. cable lugs of suitable size whereverrequired.Supply & applying bitumin paint & hessian tap on underground joints & cold zinc spray onaboveground joints.Earthing to be carreid out as per IS:3043.

8.1.1 75 x 10 mm GI earth strip Mtr 200 70 270

8.1.2 8 SWG solid wire Mtr 60 130 190

8.1.3 10mm (3/8") dia GI wire rope Mtr 40 40 80

9.1 LIGHTNING PROTECTION Nos.9.1.1 Fixing, connecting, testing & commissioning of lightning rod. This lightning rod shall be connected with

main lightning grid/pit including supply of fixing fastners/ material.

10.1 LV CABLE LAYING, TESTING & COMMISSIONING

(Quantities are tentative.)

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 7 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

Receiving, lifting, shifting to work location from the place of issue which is within site premises,unpacking,discard the packing materials to designated location etc laying ,Testing & Commissioning,precommissioing checks, charging the cables as per procedure etc. of LV Power & Control Cables.Horizontal & vertical laying of free issued cables of different voltage grade and types in readytrench/trays/Racks, underground, supported on structures, through pipe sleeves, clamping to columnwall or structure using GI spacers and saddles (at an interval of 300 mm) securing the cables oncable tray with proper dressing , tieing of cables with cable tray with steel reinforced Cable ties ,tieing of SS cable tags on every 30 mts,each bends and both ends of cables with SSwires.Installation & supply of G.I saddles & GI Clamps,tags,ties & necessary hardwares, sealingcompounds at cable entries etc. Cables laid in trays shall be dressed and clamped using GI Clamps at every 750 mm. Scope shallinclude opening the RCC slabs/Covers from Cable Trenches before laying and replacing them afterlaying.Cable cutting shall be as per actual length measurement & cable schedule/cable drumschedule.Return of unused cable/drums to the owner's store & removal of empty drum to Owner'sScrap Yard, all labour and materials complete as per approved drawings, specifications of this tenderand directions of Engineer-in-charge.The jobs to be completed in all respect but not limited the above.

1.1 kV Grade FRLS PVC insulated, Armoured, Cu conductor Power cable .

10.1.1 3C x 2.5sqmmMtrs 200 200

10.1.2 4C x 4sqmmMtrs 4100 4100

10.1.3 4C x 10sqmmMtrs 300 300

10.1.4 4C x 16sqmmMtrs 200 200

10.1.5 3.5C X 25 sqmmMtrs 1600 1600

10.1.6 3.5C X 35 sqmmMtrs 20 20

10.1.7 3.5C X 70 sqmmMtrs 80 80

10.1.8 7C X 2.5 sqmmMtrs 40 4100 4140

10.1.9 10C X 2.5 sqmmMtrs 800 800

10.2 1.1 kV Grade FRLS PVC insulated, Unarmoured, Cu conductor Power cable .

10.2.1 3C x 2.5sqmmMtrs 70 70

Technip KT India Ltd

ATTACHMENT-1SCHEDULE OF QUANTITIES FOR ELECTRICAL INSTALLATION

Rev B Sheet:- 8 of 8

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYS.NO. UNITDESCRIPTION

11.1 LT TERMINATIONTermination of PVC insulated armoured cables (upto 1100 V grade) and connections of leads cuttingstripping of cable insulation, drilling of gland plate, fixing of cable gland, crimping type lugs on to theconductor, clamping of the cable cones, supply, fixing & marking with wire number ferrules etc. allnecessary consumables and GI hardware, installation & supply of PVC shrouds for outdoorterminations including all labour and materials complete as per approved drawings, specification &directions of Engineer-in-charge.This will also include provision of additional supports, if required, forproper dressing and support of cables form part of the E&I contractor.Cable glands & lugs shall beprovided by respective vendors with their equipment/panels.However,this includes the identification ofmismatches/shortage of glands/lugs & to supply(considered elsewhere) cable glands/lugs ,reducers/adaptors to make the proper termination of cables by E&I contractor.

11.1.1 4C x 4sqmm Nos. 16 16

11.1.2 4C x 10sqmm Nos. 6 6

11.1.3 3.5C X 25 sqmm Nos. 4 4

11.1.4 3.5C X 35 sqmm Nos. 2 2

11.1.5 3.5C X 70 sqmm Nos. 2 2

11.1.6 7C X 2.5 sqmm Nos. 4 16 20

11.1.7 10C X 2.5 sqmm Nos. 4 4 8

12.1 ExcavationM³ 66 210 276

12.2 Back fillingM³ 41 100 141

12.3 Installation of red bricks Nos 1680 4560 624012.4 Spreading of fine river sand M³ 25 110 135

Technip KT India Ltd

ATTACHMENT-2SCHEDULE OF QUANTITIES FOR ELECTRICAL SUPPLY

Rev BSheet:- 1 of 4

QTY QTY

At Canel pump station At Gas processing unit

SUPPLY OF LIGHTING & POWER PANEL

(Sizes, weight & rating of switch boards are tentative)

Weather proof, industrial type switchboard double front/single front with lifting lugs, base channel, 250A TPN, 50KA for 1 sec cu busbar for main outgoing feeder Totally metal enclosed, compartmented, floor Mounted, Dust & Vermin Proof, Enclosure Protection not less than IP 41 with TPN busbars with Metering, Protection, Control indication circuits with Earthing lugs, cable lugs & cable galnds complete in all respect in line with specifications & other enclosed documents and relevant IS codes. Detail of incomer & outgoing feeder as given below :-A) 1 no. Incomer:- • Incomer (Two way 200A manual changeover switch+200A MCCB with over current (50% to 100% setting range), short circuit and earth fault protection(5% to 50% setting range.• Each incoming power supply cubicle shall be with individual measuring instruments (energy meter, ammeter with selector switch, voltmeter with selector switch), Indications (phase indications). Common MCCB trip indication shall be provided.

B) Outgoings:- 1) Suitable star/delta starters for two pump motors shall be provided. Starters shall have under current protection. Other features of star/delta starter shall be as per the design basis of onshore terminal plant (00701-21-JSD-1600-001). 2) 63A TPN feeder for lighting cum small power distribution board3) One number 63A TPN feeder as spare4) 2nos. 100A SFU TPN with ON indication.5) 32A TPN feeder as spare 6) Motor spare feeder 10% of used or 1 whichever higher to be provided.

Nos 1 1

Weatherproof, Industrial type Local Lighting Cum Power Panel with canopywith 63 Amps 4 pole MCB & ELCB as incomer and 12Nos.10 Amps Single pole MCB as outgoings.

Nos 1 1

SUPPLY OF LOCAL CONTROL STATIONS

TOTAL QTYUNITDECRIPTION

Technip KT India Ltd

ATTACHMENT-2SCHEDULE OF QUANTITIES FOR ELECTRICAL SUPPLY

Rev BSheet:- 2 of 4

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYUNITDECRIPTION

LCS with Start/Stop PBsNos 6 6

LCS with Start/Stop PBs & ammeter Nos 2 2

LCS with Start/Stop PBs & Auto- Manual Selector switchNos 2 2

LCS with Start/Stop PBs, ammeter & Auto- Manual Selector switchNos 2 2

SUPPLY OF FOLLOWING LIGHTING FIXURES WITH LAMPS

Industrial type flourescent tube light/CFL fixture with 2x36/40W flourescent lamps, high frequency electronic ballast as per requried Nos 6 6

Industrial type street lighting fixture (aluminium bright anodised reflector provide for optical efficiency) with 1x 85W Compact flourescent lamps Nos 10 10

Industrial type, non intergal type flood light fixture of cast aluminium housing and spun aluminium reflector heat resistant glass cover & adujsting facility with 400W HPSV lamp.

Nos 5 3 8

Industrial type type Control gear box suitable for 400 W HPSV lighitng fixture (flood light) Nos 5 3 8

SUPPLY OF INDUSTRIAL TYPE SOCKET WITH SWITCH

Industrial type, non-flameproof, 15 A, 240 V Convenience socket with switch Nos 2 2

SUPPLY OF INDUSTRIAL TYPE WELDING SOCKET WITH SWITCH

Weather proof with IP-55 protection welding socket (63 Amps) includingFRP canopy

Nos.1 1

SUPPLY LIGHTING POLESStreet lighting pole of 7.5 M height suitable for 1 fixture No 5 3 8

Street lighting pole of 11.0 M height suitable for 4 fixture No 10 10

Technip KT India Ltd

ATTACHMENT-2SCHEDULE OF QUANTITIES FOR ELECTRICAL SUPPLY

Rev BSheet:- 3 of 4

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYUNITDECRIPTION

EARTHING AND LIGHTNING PROTECTION75 x 10 mm GI earth strip

mtr 200 70 270

Earth plate(360 X 75 X 10) Nos. 5 5 10

8 SWG solid wire Nos. 60 130 190

10mm (3/8") dia GI wire rope Nos. 40 40 80

SUPPLY OF LV POWER & CONTROL CABLES

LV Power, Control & Lighting Cables shall be 1.1kV grade, FRLS PVCinsulated, PVC sheathed, armoured type with Stranded copper conductorsand shall be as per IS-15543C x 2.5sqmm

mtr 200 50 250

4C x 4sqmmmtr 4100 4100

4C x 10sqmmmtr 300 300

4C x 16sqmmmtr 200 200

3.5C X 25mtr 1600 1600

3.5C X 35mtr 20 20

Technip KT India Ltd

ATTACHMENT-2SCHEDULE OF QUANTITIES FOR ELECTRICAL SUPPLY

Rev BSheet:- 4 of 4

QTY QTY

At Canel pump station At Gas processing unitTOTAL

QTYUNITDECRIPTION

3.5C X 70mtr 80 80

7C X 2.5mtr 40 4100 4140

10C X 2.5mtr 800 800

1.1 kV Grade FRLS PVC insulated, Unarmoured, Cu conductor Powercable .

3C x 2.5sqmm70 70

SUPPLY OF JB

4-WAY JB SUITABLE FOR 4 C X 10SQMM CABLE Nos. 2 2

4-WAY JB SUITABLE FOR 4 C X 16SQMM CABLE Nos. 1 1

SUPPLY OF CONDUITS

25MM DIA CONDUIT Nos. 40 40

SUPPLY OF RED BRICKS Nos

1680 4560 6240

SUPPLY OF FINE RIVER SANDM³

25 110 135

TECHNIP KT INDIA LTD

ELECTRICAL LOAD LIST

CONN. KVA DF MAX.DEM.

KVA UF KVAR

KW/ (EFF * PF)

BKW/KW

BKW/ (EF*PF) C I S C/I S C/I S C/I

REMARKS

REQ.KVA -MAX KVA/(C+I)*UF

SOURCE (SW. BD)

VOLTAGE LEVEL

OPER. MODE RATING IN KWDESCRIPTION BKW EFF PF

LEGEND: C : CONTINOUS; I :INTERMITTENT; S : STANDBY ; UF : UTILIZATION FACTOR

ankgupta
ATTACHMENT-3
ankgupta