COVERSHEET
CVR
ISSUED FOR BID
ARCHITECTHEITKAMP SWIFT ARCHITECTS
HMH SJ2 SUITE 212
DR DIGGS CLINIC
MEP ENGINEERCFI COMPANIES
ISSUED FOR BID
00
00
chad fin
ley
Dec 1
4, 2017 -
10:0
9am
S:\pro
jects
\17415 -
HM
H -
SJ2 S
uite 2
12 D
iggs\C
AD
\Sheets
\CV
R.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
2500 Wilcrest Drive, Suite 150 Houston, Texas 77042Tel: (281) 809-7532 Fax: (281) 809-7536
www.cficompanies.com
CompaniesCFI
I TE
ARCH
T
S
C
ETX
A3
EDR
SIG
T
T
E
RE
S
OET
48A
T
1
F
3
FIWSNELLA
12/13/2017
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
212.00B EX EX EX EX EX EX EX EX EX - - - PROVIDE "HES-8500 SERIES" OR EQUAL ELECTRIC STRIKE TO RELEASE BUTTON IN ADMIN 212.13. FINAL LOCATION TO BE CONFIRMED.
212.00A EX EX V1 EX EX EX AL MA B FF - - PROVIDE GLASS INSERT INTO EXISTING DOOR WITH FROSTED FILM, AND NEW SIDE LITE WITH FROSTED FILM.
212.06 EX EX EX EX EX EX EX EX EX - - - RELOCATED DOOR, FRAME, AND HARDWARE. PROVIDE FLOOR STOP.
212.09 EX EX EX EX EX EX EX EX EX - - - PROVIDE KEYPAD. PRICE "KABA SIMPLEX L1021 LEVER MECHANICAL PUSHBUTTON LOCK KEY BYPASS". TO BE CONFIRMED BY OWNER.
DOOR & FRAME TYPES NTS 3
2A
/A0
.00
2E/A0.00
A
ALUMINUM DOOR
FRAME AND SIDE LITE.
MATCH EXISTINGFRAME FINISH.
V1
RE
: D
OO
R S
CH
ED
UL
E
RE: DOOR
SCHEDULE
RE: DOOR
SCHEDULE
1 1/2" 1 1/2"
1 1
/2"
RE
: D
OO
R S
CH
ED
UL
E
FLUSH DOORRE: 2G/D0.00 FOR
GLASS INSERT
DOOR/OPENING SCHEDULE
DOORS FRAMES HDW REMARKS
MARK W H THICKNESS FINISH MAT. FINISH SETTYPE
FIRE RATINGGLAZ.
MAT.TYPE
1NTSDOOR AND HARDWARE SCHEDULE
DOOR HARDWARE GENERAL NOTES:1. REUSE EXISTING STOPS.
2. VERIFY RELOCATED HARDWARE IS IN WORKING CONDITION. PROVIDE NEW AS REQUIRED TO MATCH EXISTING FUNCTION.
3. LOCKSETS TO MATCH BUILDING STANDARD "SARGENT 8200 SERIES US26" WITH LNB TRIM.
4. OWNER TO PROVIDE "BEST" CYLINDERS.
2D
/A0
.00
1. DOOR CONSTRUCTION TYPICAL - SC - SOLID CORE
EX - EXISTING
2. FINISH TYPICAL - PLAM - PLASTIC LAMINATE
EX - EXISTING
MA - MATCH EXISTING FINISH
3. FRAME TYPICAL - AL - ALUMINUM
EX - EXISTING
4. GLAZING TYPICAL - FF - FROSTED FILM
EX - EXISTING
GLASS
SCHEDULED
PARTITION
1-1
/2"
GLASS
SCHEDULEDDOOR
F - WINDOW
SILLE - WINDOW
JAMB AT DOOR
GLASS
SCHEDULED
PARTITION
C - WINDOW
HEAD OR JAMB
SCHEDULEDCEILING
A - DOORHEAD
SCHEDULEDDOOR
ALUMINUMSTUD
SCHEDULEDDOOR
EXTRUDED
SCHEDULED
PARTITION
B - DOORJAMB
LINE OF
CEILING OR
INTERSECTINGWALL
D - DOOR
SILL
3/8
"
SCHEDULED
FLOOR
SCHEDULED
DOOR
SCHEDULED
PARTITION
G - GLASS
INSERT DETAIL
1/2
"
STOP TO
MATCH DOORMATERIAL
18"X
18"
QUIRK
FINISHFLOOR
2C
/A0
.00
2F
/A0
.00
2C/A0.00
8" 8"
8"
10
"
FF
FF
2NTSFRAME DETAILS
2B/A0.00
HEITKAMP SWIFT ARCHITECTS
CONTACT: Allen Swift
1165 Brittmoore Road
(713) 626-4301 FAX
Houston, Texas 77043
(713) 626-4300
ARCHITECT
OWNER
LIST OF DRAWINGSPROJECT DATAGENERAL NOTES
PROJECT DESCRIPTON
CONTACT INFORMATION
I. INTERIORSSHEET NO.
DRAWING SERIES
15/A2.01
15 MAY. 10
P. PLUMBING
MOST RECENTISSUE DATE
REVISION NUMBERDWG IN THIS ISSUE
DETAIL NUMBERON SHEET
S. STRUCTURALK. KITCHEN
L. LANDSCAPE
E. ELECTRICALM. MECHANICAL
C. CIVILA. ARCHITECTURAL
DISCIPLINE
#1
DRAWING NUMBER KEY
PROJECT SCOPE INCLUDES 1,556 SF ON THE 2ND FLOOR THAT WILL
RENOVATE AN EXISTING CLINIC SPACE. SCOPE OF WORK WILL INCLUDE:NEW FINISHES THROUGH-OUT THE SPACE, PROVIDE NEW WORK AREA, 1
NEW SINK IN AN EXISTING TOILET, AND 1 NEW EXAM.
EXISTING WAITING, OFFICE, ADMINISTRATIVE AREA, 3 EXAMS, 1 TOILET,
STORAGE CLOSET, AND LAB AREA WILL RECEIVE FINISH UPGRADE.
HANDICAPPED SPACES
DESIGN NO.
DESIGN NO.
DESIGN NO.
BUSINESS - GROUP IIB
FIRE ALARM
EMERGENCY POWER
ELEVATOR
STAIR
VERTICAL SHAFTS
SUITE
INTERIOR WALL OPENING PROTECTION
PARTITIONS
EXTERIOR WALLS
ROOF ( MORE THAN 20' )
FLOOR
TYPE OF CONSTRUCTION
NUMBER OF STORIES
OCCUPANCY LOAD
GROSS FLOOR AREA - RENOVATION
HEIGHT ABOVE GROUND
EXISTINGPARKING SPACES
OCCUPANCY TYPE
(TOTAL)
PROJECT ADDRESS
PROJECT NAME
CODE
EXISTING
FLOOR 2
STRUCTURAL FRAME
MECHANICAL
1,556 SF
DESIGN NO.
DESIGN NO.
DESIGN NO.
4301 Garth Road, Suite 212
EXISTING
EXISTING
RE: Electrical
N/A
N/A
N/A
N/A
DESIGN NO. EXISTING
DESIGN NO. EXISTING
HMH SJ2 SUITE 212 DIGGS
Baytown, TX 77521
1. THE CONTRACTOR SHALL CONSULT THE ARCHITECT CONCERNING ANY ITEM OF
WORK TO BE PERFORMED NOT SHOWN ON THE DRAWINGS.
2. ALL MATERIALS, FIXTURES, CASEWORK AND OTHER ITEMS REMOVED FROM THE
PROJECT SITE, UNLESS SPECIFICALLY NOTED OTHERWISE IN THE CONTRACT
DOCUMENTS, ARE TO BE DISPOSED OF BY THE CONTRACTOR. THE
CONTRACTOR SHALL CONSULT THE OWNER CONCERNING THE DISPOSITION OFANY ITEMS IN QUESTION.
3. UNLESS SHOWN ON THE DRAWINGS BY EXACT DIMENSION, THE CONTRACTOR
SHALL VERIFY WITH THE OWNER THE EXACT LOCATIONS OF ALL ELECTRICALOUTLETS, TELEPHONE OUTLETS, SPECIAL DEVICES AND APPURTENANCES
INDICATED ON THE DRAWINGS.
4. THE CONTRACTOR SHALL ERECT SUCH BARRIER DUST PARTITIONS AND OTHERTEMPORARY CONSTRUCTION AS MAY BE REQUIRED TO ENSURE THE
CONTINUED SAFE OPERATION OF ALL AREAS ADJACENT TO THE PROJECT.
COORDINATE ALL TEMPORARY CONSTRUCTION WITH OWNER.
5. THE CONTRACTOR SHALL REPAIR OR REPLACE, TO THE SATISFACTION OF AND
WITHOUT ADDITIONAL COST TO OWNER ANY FURNITURE, FIXTURE, FINISH OR
SYSTEM DAMAGED BY THE CONTRACTOR DURING THE EXECUTION OF THEWORK OF THE CONTRACT.
6. THE CONTRACTOR SHALL CLEAN UP THE CONSTRUCTION SITE AT THE END OF
EACH WORKING DAY AND REMOVE ALL TRASH AND DEBRIS FROM THE SITE. THECONTRACTOR SHALL NOT ALLOW ADJACENT AREAS TO BECOME DUSTY, DIRTY
OR CLUTTERED AS A RESULT OF CONSTRUCTION OPERATIONS. THE
CONTRACTOR SHALL PERFORM FINAL CLEAN UP PRIOR TO ACCEPTANCE OF THE
COMPLETED WORK.
7. THE CONTRACTOR SHALL PATCH AND FINISH, TO MATCH EXISTING, ANY
ADJACENT ROOMS OR CORRIDORS WHICH ARE AFFECTED IN ANY MANNER BY
THIS CONSTRUCTION, INCLUDING THOSE SPACES ABOVE OR BELOW THE SITEWHICH MAY PROVIDE REQUIRED ACCESS TO THE WORK. THE CONTRACTOR
SHALL COORDINATE SUCH ADJACENT ACCESS REQUIREMENTS WITH OWNER,
ALLOWING AS MUCH ADVANCED NOTICE AS IS PRACTICAL.
8. THE CONTRACTOR SHALL FILL AND PATCH ALL OPENING AND HOLES, SEAL
AROUND ALL PIPES, DUCTS, CONDUIT, ETC., AND ENSURE THE INTEGRITY OF ALL
REQUIRED FIRE AND/OR SMOKE SEPARATIONS IN ACCORDANCE WITH
APPLICABLE CODES AND ORDINANCES.
9. WORK WITH NOISE PRODUCING EQUIPMENT IS SUBJECT, AT ALL TIME, TO THE
OWNER'S APPROVAL OF THE ENTIRE PROCEDURE.
10. THE CONTRACTOR SHALL CONTACT THE OWNER IN WRITING TO SCHEDULE ALL
UTILITY SHUTDOWNS REQUIRED FOR THE WORK. A MINIMUM OF 72 HOURS
NOTICE SHALL BE REQUIRED FOR ANY SHUTDOWN; SHUTDOWNS ARE TO BE
SCHEDULED BETWEEN THE HOURS OF 6:00 PM AND 6:00 AM MONDAY THRUFRIDAY AND FRIDAY THRU MONDAY AND WEEKENDS.
11. THE CONTRACTOR SHALL SUBMIT TO THE OWNER A MATERIAL SAFETY DATA
SHEET FOR ANY VOLATILE, FLAMMABLE, EXPLOSIVE, CORROSIVE, ORPOISONOUS MATERIALS BEFORE DELIVERY TO THE PREMISES.
12. CONTRACTOR IS REQUIRED TO VISIT THE SUITE BEFORE ANY BIDS ARE
SUBMITTED TO VERIFY AND CHECK EXISTING CONDITIONS.
13. IF DRAWINGS ARE IN CONFLICT, THE GREATER AMOUNT OF WORK SHALL BE
PRICED. BRING THE CONFLICT TO THE ATTENTION OF THE ARCHITECT AND
REQUEST DIRECTION BEFORE PROCEEDING WITH ORDERS AND WORK.
Baytown, Texas
AREA MAP
PROJECT LOCATION
VICINITY MAP
D0.00
PROJECT DATADOOR ANDPARTITION
SCHEDULES
IPC, International Plumbing Code 2009
IFC, Internatinal Fire Code 2009
IMC, International Mechanical Code 2009
NEC, National Electrical Code 2014
TDLR, Texas Department of Licensing and Regulation March 15, 2012
IBC, International Building Code 2009
IEC, International Energy Conservation Code 2014
Baytown, Texas
PROJECT LOCATION
PROJECT DATA DOOR AND PARTITION SCHEDULESD0.00
ARCHITECTURAL
COVER SHEETCVR
ISS
UE
FO
R:
DA
TE
ISS
UE
D F
OR
BID
12
/14
/20
17
REFLECTED CEILING AND FINISH PLAN AND SCHEDULEA2.01
OVERALL LIFE SAFETY PLANA1.00
DEMOLITION AND FLOOR PLANSA1.01
MECHANICAL
POWER FLOOR PLANE2.03
ELECTRICAL DEMOLITION PLANE1.03
MECHANICAL DEMOLITION PLANM1.03
PLUMBING DEMOLITION PLANP1.01
MECHANICAL FLOOR PLANM2.03
LIGHTING FLOOR PLANE3.03
ELECTRICAL
PLUMBING
MEP ENGINEER
Suite 150
CFI COMPANIES
CONTACT: Steve Fredericks
2500 Wilcrest Drive
(281) 809-7536 FAX
Houston, Texas 77042
(281) 306-0635
EXISTINGCORE AND SHELL
16 (100 SF PER OCCUPANT)
4 STORIES
SPRINKLER SYSTEM
100% BUILDING IS EQUIPPED WITH A
FULLY AUTOMATIC ALARM SYSTEM
100% BUILDING IS EQUIPPED WITH A
FULLY AUTOMATIC SPRINKLER SYSTEM
ISSUED FOR BID
00
00
chad fin
ley
Dec 1
4, 2017 -
10:1
3am
S:\pro
jects
\17415 -
HM
H -
SJ2 S
uite 2
12 D
iggs\C
AD
\Sheets
\D0_00.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
2500 Wilcrest Drive, Suite 150 Houston, Texas 77042Tel: (281) 809-7532 Fax: (281) 809-7536
www.cficompanies.com
CompaniesCFI
I TE
ARCH
T
S
C
ETX
A3
EDR
SIG
T
T
E
RE
S
OET
48A
T
1
F
3
FIWSNELLA
12/13/2017
CONTACT: Kelly Tolleson
6550 FanninSM. 201Houston, Texas 77030
(713) 441-5201
HOUSTON METHODIST, MOB
INTERIOR ELEVATIONS AND MILLWORK SECTIONSA7.01
MECHANICAL DETAILS AND SCHEDULESM3.01
ELECTRICAL ONE LINE AND SCHEDULESE4.01
ELECTRICAL DETAILSE5.01
PLUMBING FLOOR PLANP2.01
PLUMBING SCHEDULES AND DETAILSP3.01
4301 Garth Road, Suite 112Baytown, TX 77521
4301 Garth Road, Suite 112Baytown, TX 77521
True North
Plan North
MEP INFORMATION SHEETMEP0.0
MEP INFORMATION SHEET
MEP MECHANICAL SPECIFICATIONS
MEP0.1
MEP1.0
MEP ELECTRICAL SPECIFICATIONSMEP1.1
True North
Plan North
City of Baytown
PARTITION DESIGNATION 'Z1'
NTS
3'-0" NTS
ACOUSTICAL INSULATION
PARTITION DESIGNATION 'B21'
NTS
EXISTING
PARTITION BELOW
SCHEDULED
CEILING
CONTINUOUSRUNNER
SOUND ATTENUATION
BATTS
SCHEDULED
CEILING
5/8" GYP.BD.
BOTH SIDES
SCHEDULED
BASE
ACOUSTIC SEALANT
BOTH SIDES
SCHEDULEDFLOORING
CONTINUOUSRUNNER
STUD SIZE TO MATCH
EXISTING SUITE PARTITIONS,AND INSTALLED AT 16" O.C.
3'-0" NTS
ACOUSTICAL INSULATION
STRUCTURE
CONTINUOUSRUNNER
SOUND ATTENUATION BLANKETCOMPRESSED BETWEEN
RUNNER AND CEILING.
5/8" GYPSUM ON STUD TOMATCH PARTITION BELOW.
SOUND ATTENUATION BLANKET
COMPRESSED BETWEEN
DECKING RIBS.
STRUCTURE
CONTINUOUSRUNNER
SOUND ATTENUATION BLANKET
COMPRESSED BETWEEN
RUNNER AND CEILING.
5/8" GYPSUM ON STUD
TO MATCH EXISTINGPARTITION BELOW.
SOUND ATTENUATION BLANKET
COMPRESSED BETWEENDECKING RIBS.
ALUMINUM DUMMY TRIM.
FINISH TO MATCH EXISTING.
MEP PLUMBING SPECIFICATIONSMEP1.2
STAIR # 2MECH.
200
CORRIDOR
PUBLIC (2)
(2)
WP
1
1
5
4
1
1
1
3
6
2
8
9
10
11
12
13
13
13
14
15
15
13
14
15
1614
15
15
14
13
14
15
7 17
18
11
1
1
19
19
1919
STAIR # 2MECH.
200
CORRIDOR
PUBLIC
212.00
WAITING212.01
DR OFFICE
CHECK-IN
212.13
ADMIN
212.02
EXAM 1
212.03
EXAM 2
212.12
STORAGE
212.11
TOILET
212.09
LAB
212.04
STATION
WORK
212.06
EXAM 3
212.07
TOILET
212.08
EXAM 4
T
EX (2)
EX38"(2)
EX38"(3)
EX38"
EX38"
38"(3)EX
38"EX
38"EX
38"EX
(2)EX
EX (2)
EX44"
EX44"
EX44"
(2)
EX44"
(2)EX
EX (2)
44" EX
44" EX
44"EX 24"
EX44"
44"EX
44"EX
EX EX
EX
EX
EX EX
84" COAXEX
84"EX
EX
EX
EX48" EX
EX
36" EX
EX
EXEX EX
EXEXEXEXEXEXEXEX
EX
EX
EX
EX
EX
EX
EX EX EX
EX
EXEX
EX
212.00A
22
42"
36"
G1
D1
212.00B
1/A7.01
EXIST
EXIST
EXIST
EXIST
EXIST
212.09
212.06
212.05
CORRIDOR
13
/A7
.01
17/A7.01
5/A
7.0
1
9/A7.01
2/A
7.0
1
22
22
22
22
22
22
22
22
5'-1
0"
3'-5
1/2
"
3'-8
"
1'-6
"
MIN
.
E1
E1B1
E1
E1
E1
E1
E1
B1B1
B1
B1
B1
(4)
(4)
(4)
24
J1
25
26
26
26
26
26
26
COPY/FAX
6/A7.01
M1
Z1
EXIST
EXIST
1'-7
1/2
"
Z1
Z1
Z1
Z1
Z1
Z1
Z1
Z1 Z1
Z1
Z1
21
36"
36"
36"(2)EX
EXEX
(2)
EXEXEX
B1
Z1
1'-5"
23
R1/2"
R1/2
"
R1/
2" R1/2
"
R1/
2"
R1/
2"
R1/2"
27
EX
10
/A7
.01
14/A7.01
ISSUED FOR BID
00
00
chad fin
ley
Dec 1
4, 2017 -
11:0
1am
S:\pro
jects
\17415 -
HM
H -
SJ2 S
uite 2
12 D
iggs\C
AD
\Sheets
\A1_01.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
2500 Wilcrest Drive, Suite 150 Houston, Texas 77042Tel: (281) 809-7532 Fax: (281) 809-7536
www.cficompanies.com
CompaniesCFI
I TE
ARCH
T
S
C
ETX
A3
EDR
SIG
T
T
E
RE
S
OET
48A
T
1
F
3
FIWSNELLA
12/13/2017
11/4" = 1'-0"1/4" = 1'-0" 2 DEMOLITION PLANFLOOR PLANA1.01
DEMOLITIONAND FLOOR
PLANS
GENERAL NOTES
LEGEND TO SHEET
NOTES TO SHEET
#
A. PROVIDE TEMPORARY FIRE EXTINGUISHERS IN ACCORDANCE WITH NFPA 10 AT
DEMO AREA.
B. REMOVE ALL WALL HUNG ITEMS, CLEAN, PATCH/REPAIR ALL EXISTING WALLS, AND
PREP FOR SCHEDULED FINISH. COORDINATE WITH OWNER IF WALL HUNG ITEMS ARE
TO BE REINSTALLED.
C. REMOVE ALL ELECTRICAL, DATA, ETC. AT SCHEDULED DEMO WALLS AND SHOWN IN
DEMOLITION PLAN. REMOVE ASSOCIATED WIRING BACK TO SOURCE PANEL. PATCH
WALLS AS REQUIRED.
D. CONTRACTOR TO COORDINATE AFTER HOURS WORK, MOVE SCHEDULE, ITEMS TO BE
RETURNED WITH OWNER.
E. REMOVE FLOORING, BASE, AND PREP WALLS FOR SCHEDULED FINISH WITHIN SUITEUNLESS NOTED OTHERWISE.
F. DIMENSIONS SHOWN ON THE FLOOR PLANS FOR NEW CONSTRUCTION ARE FROM
CENTERLINE OF COLUMNS TO FACE OF FINISH OF EXTERIOR WALLS UNLESSOTHERWISE INDICATED OR DETAILED.
G. PROVIDE 1'-0" CLEAR FLOOR SPACE AT THE PUSH SIDE OF EVERY DOOR WITH A
CLOSER. PROVIDE 1'-6" CLEAR AT THE PULL SIDE OF EVERY DOOR.
H. ALL LAVATORIES AND SINKS SHALL BE MOUNTED A MINIMUM OF 1'-3" FROM THE
CENTERLINE OF THE FIXTURE TO THE FINISHED FACE OF THE ADJACENT PARTITION.
THERE SHALL BE 4" MINIMUM BETWEEN THE SIDE OF THE FIXTURE AND FACE OFADJACENT WALL, CASEWORK, ETC.
I. ELECTRICAL DEVICE COVER PLATES ARE TO BE BUILDING STANDARD.
J. REPLACE DAMAGED PARTITION TRIM THROUGH-OUT SPACE.K. PROVIDE ALTERNATE PRICING TO REPLACE EXISTING BLINDS IN SUITE WITHALUMINUM BLADE BLINDS. 12 WINDOWS.
EXISTING PARTITION TO BE REMOVED
REMOVE MILLWORK.
RETURN DOORS, FRAMES, AND HARDWARE TO OWNER IF
NOT SCHEDULED TO BE RELOCATED.
1
2
3
4
REMOVE DOOR AND REUSE HARDWARE.5
REMOVE EXISTING CRASHRAIL AND PATCH WALLS.
EXISTING FLOORING TO REMAIN. STRIP, CLEAN, AND WAX.
XXXPARTITION TYPE DESIGNATION (RE: D0.00)
TYPICAL PARTITION CONSTRUCTION TO BE "B31" U.N.O.
###.##
X#TOILET ACCESSORY DESIGNATION
(RE: TOILET ACCESSORY DESIGNATION)
X/A7.XX
EXISTING NOT IN SCOPE OF CONSTRUCTION
UNLESS NOTED OTHERWISE
NEW ELECTRICAL AND DATA. PROVIDE BOX WITH PULLSTING AT DATA. NUMBER IN PARENTHESIS REPRESENTS
NUMBER OF DATA LINES TO PROVIDE IN BOX.
NUMBER REPRESENTS INSTALL HEIGHT ABOVE FINISH FLOOR.
NO NUMBER REPRESENT STANDARD 18" ABOVE FINISHFLOOR. IF ABOVE COUNTER, MOUNT 8" ABOVE HORIZONTALLY.
(#)
#" #"
EX
NEW PARTITION
DOOR KEY DESIGNATION (RE D0.00)
EXISTING ITEM TO REMAIN.
ELEVATION DESIGNATION
EXISTING PARTITION
EXISTING DOOR TO REMAIN
NOTE TO SHEET DESIGNATION
EXISTING 2X4 FIXTURE TO BE REUSED AS REQUIRED.
DIFFUSER. REUSE AND RELOCATE AS REQUIRED.
REMOVE PLUMBING FIXTURE AND ASSOCIATED PLUMBING LINES. NO DEAD LEGS.
REMOVE GLASS AND BLINDS.6
PROVIDE DOOR RELEASE BUTTON TO ELECTRIC STRIKE.21
REMOVE LOWER CABINETS WHILE MAINTAINING COUNTERTOP.7
REPAIR/RELAMINATE DAMAGED MILLWORK.22
REMOVE TILE FROM FLOORS AND WALLS. REMOVE ALL GROUT AS REQUIRED, AND
PREP FOR LEVELING.8
REMOVE FLOOR DRAIN AND ASSOCIATED PLUMBING LINES. NO DEAD LEGS.9
PROVIDE $200 TOWARDS LEVELING MATERIALS. KEEP TRACK OF AMOUNT USED.23
PREP HARDWARE FOR KEYPAD.10
REMOVE WATER CONNECTION BACK TO SOURCE.11
MODIFY MILLWORK BELOW SINK FOR LOCKABLE CABINET DOORS. FIELD VERIFY SIZE.24
MODIFY WINDOW SILL TO LIKE NEW CONDITION.25
PROVIDE MILLWORK LOCK ON LOWER CABINET. EACH TO BE KEYED INDIVIDUALLY.26
REMOVE PORTION OF LOWER AND UPPER MILLWORK TO ALIGN. RE: 6/A7.0112
CLEAN AND HOLD HAND SANITIZER FOR CONTRACTOR REINSTALLATION.13
CLEAN AND RETURN PAPER TOWEL DISPENSER TO OWNER.14
CLEAN AND HOLD SOAP DISPENSER FOR CONTRACTOR REINSTALLATION.15
CLEAN AND HOLD TOILET SEAT COVER FOR CONTRACTOR REINSTALLATION.16
DRAWER/DRAWER/FILE BOX TO REMAIN. PROVIDE FINISH ENDS.17
TOILET ACCESSORY LEGENDTAG DESCRIPTION CFCI OFCI
B1 PAPER TOWEL DISPENSER X
MODEL: BOBRICK B-263
D1 TOILET PAPER DISPENSER XMODEL: BOBRICK B-2840
E1 SOAP DISPENSER X
REINSTALL EXISTING
E2 PURELL DISPENSER - REINSTALL EXISTING. XCOORDINATE NEW LOCATIONS WITH OWNER.G1 GRAB BAR X
REINSTALL EXISTING
J1 SPECIMEN PASSTHRU X
MODEL: BOBRICK B-50516
COAT HOOKL1 EXISTING TO BE REINSTALLED. COORDINATE XLOCATION WITH OWNER PRIOR TO INSTALL.M1 MIRROR X
REINSTALL EXISTING
18 CLEAN AND HOLD MIRROR FOR CONTRACTOR REINSTALLATION.
19 CLEAN AND RETURN EXIT SIGNAGE TO OWNER.
PROVIDE ALTERNATE PRICE FOR LAMINATED PRIVACY PANEL UNDER SINK.27
1
1
R
R
R
2
2
3 3
33
4
5
5
R
STAIR # 2MECH.
200
CORRIDOR
PUBLIC
212.00
WAITING212.01
DR OFFICE
CHECK-IN
212.13
ADMIN
212.02
EXAM 1
212.03
EXAM 2
212.12
STORAGE
212.11
TOILET
212.09
LAB
212.04
STATION
WORK
212.06
EXAM 3
212.07
TOILET
212.08
EXAM 4
212.05
CORRIDOR
LVT-1
FB-1
PP21
1P
1P
LVT-1
FB-1
PP12
1P
1P
VCT-1
RB-1
PP11
1P
1P
CPT-1
RB-1
PP11
1P
1PVCT-1
RB-1
PP11
1P
1P
VCT-1
RB-1
PP11
1P
1P
CPT-1
RB-1
PP11
1P
1P
CPT-1
RB-1
PP11
1P
1P
VCT-1
RB-1
PP11
1P
1P
VCT-1
RB-1
PP11
1P
1P
VCT-1
RB-1
PP11
1P
1P
PT-1
PTB-1
WPWP11
1WP
1WP
CPT-1VCT-1
21
21
21
21
21
22
21
21
2121
21
21
WAX
RB-1
PP11
1P
2P
ISSUED FOR BID
00
00
chad fin
ley
Dec 1
4, 2017 -
11:2
4am
S:\pro
jects
\17415 -
HM
H -
SJ2 S
uite 2
12 D
iggs\C
AD
\Sheets
\A2_01.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
2500 Wilcrest Drive, Suite 150 Houston, Texas 77042Tel: (281) 809-7532 Fax: (281) 809-7536
www.cficompanies.com
CompaniesCFI
I TE
ARCH
T
S
C
ETX
A3
EDR
SIG
T
T
E
RE
S
OET
48A
T
1
F
3
FIWSNELLA
12/13/2017
11/4" = 1'-0"1/4" = 1'-0" 2 REFLECTED CEILING PLANFINISH PLANA2.01
REFLECTEDCEILING ANDFINISH PLAN
AND SCHEDULE
GENERAL NOTES
LEGEND TO SHEET
NOTES TO SHEET
FLR
BASE
WALLWALLFINISHFINISH
FINISHWALL
FINISHWALL
FINISH DESIGNATION.
DIRECTION OF FLOOR PATTERN
WALL TREATMENTSPAINTP-1 (PRIMARY AND FURRDOWNS)
MFR.: SHERWIN WILLIAMSCOLOR: SW6107 NOMADIC DESERTP-2 (ACCENT)
MFR.: SHERWIN WILLIAMSCOLOR: SW2806 ROCKWOOD BROWNWALL PATTERNSWP-1 (HALF HEIGHT WALL PATTERN, REFER TO 14/A7.01)
PTB-1, PT-1 WITH SCHULTER TRIM ON EDGE, AND P-1 ON WALL.
MILLWORKPLASTIC LAMINATEPL-1MFR.: WILSONART
COLOR: 7040K-78 FIGURED MAHOGANY
FLOOR BASEFB-14" WOOD BASE WITH 1/4" CHAMFERED EDGE, AND SHOEMOLD.
STAINED TO MATCH VINYL WOOD FLOORING.RUBBER BASERB-1MFR.: ROPPE
COLOR: 100 BLACK
SIZE: 4" COVE
PORCELAIN TILE BASEPTB-1MFR. DALTILE
COLLECTION: COLORBODY PORCELAINSTYLE: PORTFOLIO (P36C9-T AND PC36C9-T)
COLOR: CHOCOLATE PF08
SIZE: 6" X 12"
NOTE: REFER TO ELEVATION FOR INSTALL PATTERN.
FLOOR TREATMENTSCARPETCPT-1MFR.: PATCRAFT
COLLECTION: CONUNDRUM MODULAR (I0218)COLOR: RIDDLE (18169)LUXURY VINYL TILELVT-1MFR.: MANNINGTONCOLLECTION: NATURE'S PATHS SELECT
COLOR: HERITAGE HICKORY (12140 SABLE)
SIZE: 5" X 48" PLANKVINYL COMPOSITION TILEVCT-1MFR.: ARMSTRONGCOLLECTION: STANDARD EXCELON IMPERIAL TEXTURE
COLOR: TAUPE 51901
SIZE: 12" X 12"
BASE
MFR. ARMSTRONG
STYLE CORTEGA 770PROFILE SQUARE EDGE
SIZE 24" x 24"
GRID PRELUDE 15/16"NOTE SPEC PROVIDED FOR PRICING PURPOSES ONLY.FIELD VERIFY AND MATCH BUILDING STANDARD
EXISTING NOT IN SCOPE OF CONSTRUCTION
UNLESS NOTED OTHERWISE
2'-0" X 4'-0" LIGHT FIXTURE
(RE: ELECTRICAL)
# NOTE TO SHEET DESIGNATION
EXIT SIGNAGE. (RE: ELECTRICAL)
A. FIELD VERIFY EXISTING LIGHT FIXTURE CONDITION AND QUANTITY, AND REUSE AS
REQUIRED. NOTIFY ARCHITECT IF ANY ARE BEYOND REPAIR, KELVIN OF BULBS ARETO BE THE SAME THROUGHOUT.
B. DAMAGED CEILING TILES THROUGH-OUT SPACE ARE TO BE REPLACE. MINIMUM 5
BOXES WORTH.
C. CEILING MOUNTED ITEMS ARE TO BE COORDINATED WITH OWNER FOR
REINSTALLATION.
D. ALL EXISTING LIGHT FIXTURES LENS IN SCOPE TO BE CLEANED. NEW AND REUSED
LENS'S ARE TO NEVER BE IN THE SAME ROOM. COORDINATE WITH ARCHITECT FOR
COORDINATION.
E. EXISTING CEILING DIFFUSERS ARE TO BE CLEANED AND REUSED AS REQUIRED.
F. DIFFUSER AND LIGHT FIXTURE LOCATION TO NOT BE IN CONTACT OF PARTITIONS,MILLWORK, ETC. COORDINATE WITH ARCHITECT OF ANY CONFLICTS.
G. ALL NEW AND EXISTING-TO-REMAIN GYPSUM BOARD SURFACES TO BE PREPARED
FOR PAINT AS SCHEDULED.
H. PREPARE EXISTING SLAB TO RECEIVE NEW SCHEDULED FINISH PER
MANUFACTURER'S RECOMMENDED INSTALLATION.
I. CEILING ACCESS PANELS TO BE SPRAY-PAINTED TO MATCH ADJACENT COLOR.
J. FLOORING TRANSITIONS AT DOOR OPENINGS ARE TO ALIGN WITH THE CENTERLINE
OF THE CLOSED DOOR, UNLESS OTHERWISE NOTED.
K. ALL EXPOSED EDGES OF PORCELAIN TILE IS TO RECEIVE SCHLUTER TRIM BOTH
HORIZONTALLY AND VERTICALLY. VERTICAL OUTSIDE CORNERS ARE TO BE
INCLUDED AS WELL.
MAIN RUNNER
WALL WASHER
(RE: ELECTRICAL)
1 REPLACE DAMAGED CEILING TILE AND GRID.
DIFFUSER (RE: MECHANICAL)
SLOT DIFFUSER (RE: MECHANICAL)
FLOORING TRANSITION STRIP. SUBMIT MANUFACTURE PROFILES AND COLORSELECTIONS
21
FINISH SCHEDULE
2 RELOCATE SPRINKLER HEADS. 2 MINIMUM.
TILEPORCELAIN TILEPT-1MFR. DALTILE
COLLECTION: COLORBODY PORCELAIN
STYLE: PORTFOLIO
COLOR: CHOCOLATE PF08SIZE: 12" X 24"
NOTE: REFER TO ELEVATION FOR INSTALL PATTERN.
3 PROVIDE ALTERNATE PRICING FOR DIRECT/INDIRECT FIXTURES. RE: ELECTRICAL.
4 REPLACE DAMAGED PARTITION TRIM.
5 FIELD VERIFY CEILING LEAK AND NOTIFY OWNER OF ISSUE, AND PROVIDE COST TO
REPAIR. NO WORK TO BE DONE UNTIL OWNER APPROVES PROPOSED SOLUTION.
PROVIDE SCHLUTER FLOORING TRANSITION STRIP.22
CLINICAL AIR
TEMPERATURE AND PRESSURE RELIEF VALVE
OD
PLUG VALVE
STRAINER
UNION
BALL VALVE
XXXX
ELBOW UP
THERMOMETER
FLOOR DRAIN
ELBOW DOWN
CD CONDENSATE DRAIN LINE
PRESSURE REDUCING VALVE
BRANCH CONNECTION, TOP
BRANCH CONNECTION, BOTTOM
VENT THRU ROOF
WALL CLEANOUT
FLOOR CLEANOUT
PRESSURE GAUGE
ITEMS TO BE REMOVED
HOSE BIBB
F.F.
FLR.
F.D.
F.C.O.
F.S.
FIRE RISER IDENTIFICATION
PLUMBING RISER IDENTIFICATION
(N)NEW CONNECTION TO (E)EXISTING
DOWN SPOUT RISER IDENTIFICATION
ACID WASTE RISER IDENTIFICATION
LB.
P.S.I.
POUNDS
G.P.M.
G.P.H.
G.C.O.
G.V.
H.W.R.
H.W.
INV.
POUNDS PER SQUARE INCH
OILY WASTE
EXISTING SANITARY VENT PIPING
STORM OVERFLOW DRAIN PIPING
FIRE PROTECTION MAIN
SANITARY VENT PIPING
STORM DRAIN PIPING
SANITARY WASTE PIPING
MEDICAL VACUUM
SOFTENED COLD WATER
NATURAL GAS
MEDICAL OXYGEN
MEDICAL AIR
NITROGEN
ACID VENT
NITROUS OXIDE
CONDENSATE DRAIN
F
OW
G
CD
FLOOR
FINISHED FLOOR
FLOOR DRAIN
FLOOR SINK
FLOOR CLEAN OUT
NITROGEN
ACID WASTE
CHECK VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
EXISTING DOMESTIC COLD WATER
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER
DOMESTIC HOT WATER
B.F.P.
A.D.
HEAT TRACE AND INSULATE
GREASE VENT
GALLONS PER MINUTE
GRADE CLEAN OUT
GALLONS PER HOUR
HOT WATER RETURN
C.O.
C.W.
B.T.
BLW.
C.V.
B.S.
B.V.
B.D.
D.
D.F.U.
°F
D.D.
CONT.
COND.
AREA DRAIN
BATHTUB/SHOWER
BELOW
CHECK VALVE
CLEANOUT
COLD WATER
BAR SINK
BALANCING VALVE
BALCONY DRAIN
DRAIN
CONTINUED
DECK DRAIN
CONDENSATE
DEGREES FAHRENHEIT
DRAINAGE FIXTURE UNITS
BACKFLOW PREVENTER
W.H.
V.T.R.
W.C.O.
W.C.
W.B.
WALL HYDRANT
WATER CLOSET
WASHER BOX
VENT THRU ROOF
WALL CLEAN OUT
(E)
F.
F.H.C.
F.D.C.
FIRE
FIRE HOSE CABINET
FIRE DEPARTMENT CONNECTION
DIESEL FUEL RETURN
DIESEL FUEL SUPPLYDFS
SCW
CLINICAL AIR
TEMPERATURE AND PRESSURE RELIEF VALVE
OD
PLUG VALVE
STRAINER
UNION
BALL VALVE
XXXX
ELBOW UP
THERMOMETER
FLOOR DRAIN
ELBOW DOWN
CD CONDENSATE DRAIN LINE
PRESSURE REDUCING VALVE
BRANCH CONNECTION, TOP
BRANCH CONNECTION, BOTTOM
VENT THRU ROOF
WALL CLEANOUT
FLOOR CLEANOUT
PRESSURE GAUGE
ITEMS TO BE REMOVED
HOSE BIBB
F.F.
FLR.
F.D.
F.C.O.
F.S.
FIRE RISER IDENTIFICATION
PLUMBING RISER IDENTIFICATION
(N)NEW CONNECTION TO (E)EXISTING
DOWN SPOUT RISER IDENTIFICATION
ACID WASTE RISER IDENTIFICATION
LB.
P.S.I.
POUNDS
G.P.M.
G.P.H.
G.V.
H.W.R.
H.W.
INV.
POUNDS PER SQUARE INCH
OILY WASTE
EXISTING SANITARY VENT PIPING
STORM OVERFLOW DRAIN PIPING
GREASE WASTE PIPING
AUTOMATIC SPRINLER
FIRE PROTECTION MAIN
SANITARY VENT PIPING
STORM DRAIN PIPING
SANITARY WASTE PIPING
MEDICAL VACUUM
SOFTENED COLD WATER
NATURAL GAS
MEDICAL OXYGEN
MEDICAL AIR
NITROGEN
ACID VENT
NITROUS OXIDE
CONDENSATE DRAIN
F
OW
A/S
G
CD
FLOOR
FINISHED FLOOR
FLOOR DRAIN
FLOOR SINK
FLOOR CLEAN OUT
NITROGEN
ACID WASTE
CHECK VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
EXISTING DOMESTIC COLD WATER
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER
DOMESTIC HOT WATER
B.F.P.
A.D.
HEAT TRACE AND INSULATE
GALLONS PER MINUTE
GRADE CLEAN OUT
GALLONS PER HOUR
HOT WATER
INVERT
C.O.
C.W.
B.T.
BLW.
C.V.
B.S.
B.V.
B.D.
D.
D.F.U.
°F
D.D.
CONT.
COND.
AREA DRAIN
BATHTUB/SHOWER
BELOW
CHECK VALVE
CLEANOUT
COLD WATER
BAR SINK
BALANCING VALVE
BALCONY DRAIN
DRAIN
CONTINUED
DECK DRAIN
CONDENSATE
DEGREES FAHRENHEIT
DRAINAGE FIXTURE UNITS
BACKFLOW PREVENTER
W.H.
V.T.R.
W.C.O.
W.C.
W.B.
WALL HYDRANT
WATER CLOSET
WASHER BOX
VENT THRU ROOF
WALL CLEAN OUT
(E)
F.
F.H.C.
F.D.C.
FIRE
EXISTING
FIRE HOSE CABINET
FIRE DEPARTMENT CONNECTION
SUB-SOILED DRAIN PIPING
DIESEL FUEL RETURN
DIESEL FUEL SUPPLYDFS
SCW
W
GREASE VENT PIPINGGVGW
CA
N2
MA
N20
MV
SD
SSD
DFR
CA
N2
MA
N20
MV
SD
SSD
DFR
FIRE ALARM SPEAKER STROBE
FIRE ALARM STROBE
SMOKE DETECTOR
HEAT DETECTOR
MANUAL PULL STATION
FIRE ALARM MAGNETIC DOOR HOLD-OPEN
DUCT SMOKE DETECTOR
QUADRUPLEX RECEPTACLE
OCCUPANCY SENSOR CEILING MOUNT
VARIABLE FREQUENCY DRIVE FURNISHED
BY DIV 23, CONNECTED BY DIV 26VFD
PLUGMOLD WITH DUPLEX OUTLETS, 18" OC U.O.N.
"12" INDICATES OUTLETS 12" OC"24" INDICATES OUTLETS 24" OC.
"C" INDICATES WITH COMM COMPARTMENT
FLUSH FLOOR QUADRUPLEX RECEPTACLE
FLUSH FLOOR DUPLEX RECEPTACLE
FLOOR DATA OUTLET
WALL TELEPHONE OUTLET WITH PLATE (W-WALL MOUNTED)
NURSE CALL CENTRAL EQUIPMENT CABINET
TELEVISION SIGNAL OUTLET
FLUSH WALL MOUNTED JUNCTION BOX FOR
MOUNTING HEIGHT REFER TO ARCHITECTURAL
AND MEDICAL EQUIPMENT PLAN DRAWINGS.
SINGLE POWER RECEPTACLE, 20A, 125V 3W GNDG UON.
CIRCUIT BREAKER - 100 AMPFRAME, 3 POLE, UON
FUSED SWITCH 100 AMP SWITCH/100
AMP TYPE "FA" FUSE 3 POLE UON
CONDUIT HOME RUN TO PANEL
BOARD "1LB" WITH CIRCUITS 1,3,5
DISCONNECT SWITCH - 30A, NON-FUSED,
3-POLE UON. NEMA 1 ENCLOSURE EXCEPT
"3R" INDICATES NEMA 3R.
AUTOMATIC TRANSFER SWITCH AMPS/ POLES AS INDICATED ON PLANS
COMBINATION MOTOR CONTROLLERAND NON-FUSED DISCONNECT
SWITCH
20ADUPLEX CONVENIENCE RECEPTACLE
NUMERAL INDICATES CKT NUMBER
IG = ISOLATED GROUND (ORANGE DEVICE)
G = GROUND FAULT INTERRUPER 20A = 20 AMP RATED RECEPTACLE *
* ALL RECEPTACLES ON DEDICATED 20 AMP
CIRCUITS SHALL BE RATED 20A.
INDICATES WALL OUTLET AT NON-STANDARD HEIGHTWHEN SHOWN ADJACENT TO ANY OUTLET OR
RECEPTACLE. AT COUNTERS, MOUNT 6" ABOVE SPLASH
UON.
WALL MOUNTED DATA/TELEPHONE
GROUND CONNECTION
IGTC
G2PC
400A / 3PT
TIME CLOCKPHOTOCELL CONTROL SWITCH
100CB 60
1LB-1,3,5
MAGNETIC MOTOR STARTER, H-O-A-P U.O.N.
MOTOR
LIGHTING RELAY PANEL
PANELBOARD
TRANSFORMER
CEILING MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
CAPPED CONDUIT
CONDUIT TURNING UP/DOWN
JJJ
UNFUSED SWITCH - 100 AMP 3 POLE, UON
100/100100100
ER RELAY
FIREMAN'S PHONE
FIREMAN'S PHONE HANDSET
FIRE ALARM SPEAKER
FIRE ALARM REMOTE ANNUNCIATOR
FIRE ALARM CONTROL PANELFACP
NURSE CALL CODE BLUE
NURSE CALL STAFF/DUTY STATION
NURSE CALL PATIENT STATION
NURSE CALL MASTER STATION
CEILING MOUNTED ZONE LIGHT
CEILING MOUNTED DOME LIGHT
GENERATOR ANNUNCIATOR PANELGAP
INFRARED SENSORS. SENSORS SHALL BE
CONNECTED TO CORRIDOR LIGHTINGIR
KEY PAD. CONTRACTOR RESPONSIBLE TO PROVIDE ALLREQUIRED HARDWARE AND ELECTRICAL CONNECTIONS.
KPDOOR CONTACT. CONTRACTOR RESPONSIBLE TO
PROVIDE ALL REQUIRED HARDWARE AND ELECTRICAL
CONNECTIONS.
DC
FIRE ALARM WATER FLOW
FIRE ALARM TAMPER SWITCH
FAAP
ELECTRICAL SYMBOLS LEGEND
+XX"
NCM
NCC
PUSHBUTTON
K = KEY OPERATED SWITCH (UP/OFF/DOWNPOSITION)
E = EMERGENCY POWER OFF BUTTON
CEILING EXIT LIGHT - DIRECTIONAL ARROWSWHERE INDICATED, SHADED QUADRANTS
INDICATE ILLUMINATED FACES
WALL EXIT LIGHT - DIRECTIONAL ARROWS
WHERE INDICATED SHADED QUADRANTSINDICATE ILLUMINATED FACES
FLUSH MOUNTED CIRCUIT BREAKER 100A
FRAME/60A TRIP 3 POLE UON
LRP
EMERGENCY BATTERY PACKFIXTURE
C/B
FC
GA
GFI
GALV
GND
FLA
HP
N
NO
HORIZ
HTG
HOA
GRC
HGT
NF
NL
OL
NEMA
NFPA
NETA
O/C
NEC
P
PB
PH
PF
PLB
EL ELEVATION
FLUOR FLUORESCENT
FEETFT
ELECTRIC
ELEVATOR
EQUIVALENT
EQUIPMENT
FIRE ALARM
FEEDER
FIXTURE
ON EMERGENCY CIRCUIT
ELECTRICAL METALLIC TUBING
FLOOR
FLUSH
FLR
FIXT
FL
FA
FDR
EQMT
EQ
EMT
ELEV
EM
ELEC
VOLT AMPERES
VERTICAL
VENTILATING
VAPORPROOF
WIRE GUARD
WEATHERPROOF
LOCATED
TRANSFORMER
YARD
1 CONDUCTOR, 2 CONDUCTORS, ETC.1/C, 2/C,
LOC.
XFMR
YD
WP
VERT
WG
VP
VENT
VA
CATALOG
CIRCUIT
CEILING
CLOCK
CONTINUOUS
DIRECT CURRENT
CONVENIENCE
DIAMETER
CURRENT TRANSFORMER
COLUMN
CONCRETE
CONT
DC
DIA
C/T
CONV
COL
CONC
CLG
CKT
CL
CAT
ROOT MEAN SQUARE
HEATING
POWER FACTOR
PHASE
PLUMBING
NATIONAL ELECTRICAL TESTING ASSOC.
NATIONAL ELEC MANUFACTURERS ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
OVERCURRENT
ON NIGHT LIGHTING CIRCUIT
OVERLOAD
POLES
PULL BOX
NORMALLY OPEN
NATIONAL ELECTRICAL CODE
NON-FUSE
NEUTRAL
UNDERFLOOR DUCT
UNDERWRITERS LABORATORIES, INC.
TELEPHONE COMPANY
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
GROUND FAULT CIRCUIT INTERRUPTER
HORIZONTAL
HAND OFF AUTOMATIC
HORSEPOWER
GALVANIZED RIGID CONDUIT
HEIGHT
GROUND
GALVANIZED
FULL LOAD AMPERES
FOOT CANDLE
GUAGE
RMS
RM
REQ
REV
RECEPT
REL
RC
REVERSE
REQUIRED
ROOM
REMOTE CONTROL
RECEPTACLE
RELOCATE
PWR
P/T
R
PVC
PP
PNL
POWER
REMOVE
POWER PANEL
PANEL
TELEVISIONTV
UFD
V
UL
UC
TYP
VOLTS
TYPICAL
UNDERCOUNTER
TELCO
SYM
TEL
SWGR
SUSP
SWBD
SYMMETRICAL
TELEPHONE
SUSPENDED
SWITCHBOARD
SWITCHGEAR
ABOVE FINISHED FLOOR
ARCHITECTURAL
ASYMMETRICAL
AUDIO/VISUAL
AUXILLARY
ABOVE FINISHED GRADE
BUILDING
CIRCUIT BREAKER
CONDUIT
AMERCIAN WIRE GAUGE
AUTOMATIC TRANSFER SWITCH
AMERICAN SOCIETY FOR TESTING MATERIALS
AMERICAN NATIONAL STANDARDS INSTITUTE
AWG
C
BLDG
A/V
AUX
ATS
ASTM
ARCH
ASYM
ANSI
AFG
AFF
AMPS
ADJACENT
ALTERNATING CURRENT/ABOVE COUNTERAC
ADJ
A
MOTOR CONTROL PANEL
NORMALLY CLOSED
MAIN LUGS ONLY
SPECS
SPKLR
SQ
SW
SURF
STD
SPKR
SQUARE
STANDARD
SURFACE
SWITCH
SPRINKLER
SPEAKER
SPECIFICATIONS
NC
SP
MTR
MLO
MTD
MOTOR
SPARE
MOUNTED
MIC
MCP
MICROPHONE
KW
KWH
LBS
KVA
LP
LTG
MA
MC
MACH
MCM
MCC
MCB
METAL-CLAD CABLE
MAIN CIRCUIT BREAKER
THOUSAND CIRCULAR MILS
MOTOR CONTROL CENTER
MILLIAMPS
MACHINE
KILOVOLT AMPERES
KILOWATT HOURS
LIGHTING PANEL
POUNDS
LIGHTING
KILOWATT
DP
EC
DWG
IG
HVAC
INCAND
IEEE
IMC
INSUL
J-BOX
INT
E
HEATING, VENTILATING & AIR CONDITIONING
ISOLATED GROUND
INCANDESCENT
JUNCTION BOX
INSULATION
INTERCOM
EMPTY CONDUIT
INTERMEDIATE METAL CONDUIT
DISTRIBUTION PANEL
EXISTING TO REMAIN
DRAWING
EPO
QUAD QUADRUPLEX
PHASEØ
ABBREVIATIONSSYMBOL DESCRIPTION SYMBOL DESCRIPTION
INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
EMERGENCY POWER OFF
GFP GROUND FAULT PROTECTION
TOGGLE SWITCH, 15A / 277VAC UON2 = DOUBLE POLE3 = THREE-WAY
4 = FOUR-WAY
a = CONTROLS OUTLET OR FIXTURE NOTED "a"
K = KEY OPERATEDP = WITH PILOT LIGHT
T = INTERVAL TIMER, 30 MIN. UON
M = MOTOR RATED SWITCH, RATED FOR MOTOR
SERVEDMO = SPDT MOMENTARY CONTACT
D = DIMMER SWITCH
OC = OCCUPANCY SENSOR
X
SPD SURGE PROTECTION DEVICE
AIR DEVICE MARK
AIR FLOW WITH LETTER DESIGNATION
∅
CONNECTION POINT OF NEW TO EXISTING C CENTER LINE
DIAMETER
HUMIDIFIERH PIPE ALIGNMENT GUIDE
PIPE ANCHOR
HEAT TRACING ON PIPE
FLANGED END
INDICATES DISCONNECTION POINT
SOUND TRAPSTRELATIVE ROOM PRESSURE---+
INDICATES SECTION NUMBERINDICATES DRAWING NUMBER
INDICATES DETAIL NUMBER
INDICATES DRAWING NUMBER
SD
FS
MARK-#
AP ACCESS PANEL
FLEXIBLE CONNECTION, FLEXIBLE DUCT
DUCT ELBOW WITH TURNING VANES
DUCT ELBOW WITHOUT VANES
BDD
FLEXIBLE DUCT CONN. TO RECTANGULAR
BACK DRAFT DAMPER
SPLITTER DAMPER - DIMENSION AS
DUCT WITH SPIN-IN CONNECTOR
SDDIM. NOTED ON DRAWING
EQUIPMENT MARK AND NUMBER
REFER TO DETAIL #1 ON DRAWING M-7
UNDERCUT DOOR 1"UCD 1"
RE: I/M-7 CD
PRESSURE MONITOR
FIRESTATF
P
SD SMOKE DETECTOR
CONDENSATE DRAIN
EXPANSION JOINT
THERMOMETER
TEST PLUG
MANUAL AIR VENT
PRESSURE GAUGE W/GAUGE COCK
AUTOMATIC AIR VENT
THERMOMETER WELL
SOLENOID VALVE
FLOW SWITCH
RELIEF VALVE
STEAM TRAP
STEAM MOISTURE SEPARATOR
TEMPERATURE AND PRESSURE
STEAM CONTROL VALVE
EJ
45° ELBOW DOWN (OGEE)
TEE
UNION (SCREWED)
CROSS
TOP CONNECTION
TEE DOWN
TEE UP
UNION (FLANGED)
PIPE BREAK
CONCENTRIC REDUCER
DUCT MOUNTED TEMPERATURE SENSOR
DUCT MOUNTED PRESSURE SENSOR
DUCT MOUNTED SMOKE DETECTOR
CHWS
CWR
CHWR
HWS
HWR
CWS
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
RED. PRESS PRINCIPAL
BACKFLOW PREVENTER
ISOLATION VALVE
BALL VALVE
BUTTERFLY VALVE
END SUCTION PUMP
ECCENTRIC REDUCER
BALANCING VALVE
TWO-WAY VALVE (PNEUMATIC)
PRESSURE REDUCING VALVE
CHECK VALVE, SWING GATE
THREE-WAY VALVE (PNEUMATIC)
ANGLE PRESSURE RELIEF VALVE
GATE VALVE WITH QUICK DISCONNECT
PRESSURE REGULATOR
FLEXIBLE CONNECTION
THREE-WAY VALVE (ELECTRIC)
TWO-WAY VALVE (ELECTRIC)
STRAINER W/BLOW DOWN VALVE
QUICK OPENING/CLOSING VALVE
LOCK SHIELD
SUPPLY AIR DUCT UP (PLAN)
AD
DUCT SPLIT WITH SPLITTER DAMPER
TRANSITION IN DUCT
ACCESS DOOR
SUPPLY AIR DUCT DOWN (PLAN)
RETURN OR OUTSIDE
RETURN OR OUTSIDE
RETURN AIR/TRANSFER AIR BOOT
CEILING SUPPLY AIR DEVICE
CEILING RETURN AIR /
EXHAUST AIR DUCT UP (PLAN)
EXHAUST AIR DUCT DOWN (PLAN)
BRANCH DUCT TAP
AIR DUCT UP (PLAN)
AIR DUCT DOWN (PLAN)
EXHAUST REGISTER
FD
M
VD
AFS
R
D
APD
SIDEWALL SUPPLY/EXHAUST REGISTER
RETURN AIR GRILLE WITH BOOT
MOTORIZED VOLUME DAMPER
COMBINATION FIRE/SMOKE DAMPER
AIR PRESSURE DIFFERENTIAL SWITCH
DROP IN DUCT ELEVATION
RISE IN DUCT ELEVATION
AIR FLOW SWITCH
SMOKE DAMPER
FIRE DAMPER
VOLUME DAMPER
HUMIDISTAT
PIPE UP
90° ELBOW
CAP
PIPE DOWN
H
45° ELBOW
THERMOSTAT - MOUNT 48" AFF UNOT
PRV
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HOT WATER SUPPLY
HOT WATER RETURN
NEW CONSTRUCTION
EXISTING TO REMAIN
(E = EXHAUST) (R = RETURN)
D/P DIFFERENTIAL PRESSURE SENSOR
PLUMBING SYMBOLS LEGEND
MECHANICAL SYMBOLS LEGEND
CONTRACTOR SHALL ALLOW TIME TO ASSIST THE COMMISSIONING AGENT AND
COMMISSIONING PROCESS FOR ATTENDING A COMMISSIONING KICKOFF MEETING AND
FILLING OUT PRE-FUNTIONAL CHECKLISTS. THE MECHANICAL AND CONTROLSCONTRACTOR SHALL ASSIST WITH FUNCTIONAL TESTING OF THE HVAC SYSTEM
INCLUDING A 20% SAMPLING OF VAV BOXES. THE ELECTRICAL CONTRACOTR SHALL
ASSIST WITH TESTING OF THE LIGHTING RELAY SYSTEM.
MEP COMMISSIONING
MEP0.00 MEP INFORMATION SHEET
MEP0.01 MEP SPECIFICATIONS MECHANICAL
MEP0.02 MEP ELECTRICAL SPECIFICATIONS
MEP0.03 MEP PLUMBING SPECIFICATIONSM1.01 MECHANICAL DEMOLITION PLAN
M2.01 MECHANICAL FLOOR PLAN
M2.02 MECHANICAL ROOF PLAN
M3.01 MECHANICAL DETAILS AND SCHEDULESE1.01 ELECTRICAL DEMOLITION PLAN
E2.01 ELECTRICAL LIGHTING PLAN
E3.01 ELECTRICAL POWER FLOOR PLAN
E4.01 ELECTRICAL ONE LINE AND SCHEDULESE5.01 ELECTRICAL DETAILS
P1.01 PLUMBING DEMOLITION PLAN
P2.01 PLUMBING PLANS
P3.01 PLUMBING DETAILS AND SCHEDULES
INDEX TO MEP DRAWINGS
MEP0.0
MEP INFO
SHEET
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
EP
0.0
_M
EP
IN
FO
SH
EE
T.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
F.F.
FLR.
F.D.
F.C.O.
F.S.
LB.
P.S.I.
POUNDS
G.P.M.
G.P.H.
G.C.O.
G.V.
H.W.R.
H.W.
INV.
POUNDS PER SQUARE INCH
FLOOR
FINISHED FLOOR
FLOOR DRAIN
FLOOR SINK
FLOOR CLEAN OUT
B.F.P.
A.D.
GREASE VENT
GALLONS PER MINUTE
GRADE CLEAN OUT
GALLONS PER HOUR
HOT WATER RETURN
C.O.
C.W.
B.T.
BLW.
C.V.
B.S.
B.V.
B.D.
D.
D.F.U.
°F
D.D.
CONT.
COND.
AREA DRAIN
BATHTUB/SHOWER
BELOW
CHECK VALVE
CLEANOUT
COLD WATER
BAR SINK
BALANCING VALVE
BALCONY DRAIN
DRAIN
CONTINUED
DECK DRAIN
CONDENSATE
DEGREES FAHRENHEIT
DRAINAGE FIXTURE UNITS
BACKFLOW PREVENTER
W.H.
V.T.R.
W.C.O.
W.C.
W.B.
WALL HYDRANT
WATER CLOSET
WASHER BOX
VENT THRU ROOF
WALL CLEAN OUT
(E)
F.
F.H.C.
F.D.C.
FIRE
FIRE HOSE CABINET
FIRE DEPARTMENT CONNECTION
F.F.
FLR.
F.D.
F.C.O.
F.S.
LB.
P.S.I.
POUNDS
G.P.M.
G.P.H.
G.V.
H.W.R.
H.W.
INV.
POUNDS PER SQUARE INCH
FLOOR
FINISHED FLOOR
FLOOR DRAIN
FLOOR SINK
FLOOR CLEAN OUT
B.F.P.
A.D.
GALLONS PER MINUTE
GRADE CLEAN OUT
GALLONS PER HOUR
HOT WATER
INVERT
C.O.
C.W.
B.T.
BLW.
C.V.
B.S.
B.V.
B.D.
D.
D.F.U.
°F
D.D.
CONT.
COND.
AREA DRAIN
BATHTUB/SHOWER
BELOW
CHECK VALVE
CLEANOUT
COLD WATER
BAR SINK
BALANCING VALVE
BALCONY DRAIN
DRAIN
CONTINUED
DECK DRAIN
CONDENSATE
DEGREES FAHRENHEIT
DRAINAGE FIXTURE UNITS
BACKFLOW PREVENTER
W.H.
V.T.R.
W.C.O.
W.C.
W.B.
WALL HYDRANT
WATER CLOSET
WASHER BOX
VENT THRU ROOF
WALL CLEAN OUT
(E)
F.
F.H.C.
F.D.C.
FIRE
EXISTING
FIRE HOSE CABINET
FIRE DEPARTMENT CONNECTION
FIRE ALARM SPEAKER STROBE
FIRE ALARM STROBE
SMOKE DETECTOR
HEAT DETECTOR
MANUAL PULL STATION
FIRE ALARM MAGNETIC DOOR HOLD-OPEN
DUCT SMOKE DETECTOR
QUADRUPLEX RECEPTACLE
OCCUPANCY SENSOR CEILING MOUNT
VARIABLE FREQUENCY DRIVE FURNISHED
BY DIV 23, CONNECTED BY DIV 26VFD
PLUGMOLD WITH DUPLEX OUTLETS, 18" OC U.O.N."12" INDICATES OUTLETS 12" OC
"24" INDICATES OUTLETS 24" OC.
"C" INDICATES WITH COMM COMPARTMENT
FLUSH FLOOR QUADRUPLEX RECEPTACLE
FLUSH FLOOR DUPLEX RECEPTACLE
FLOOR DATA OUTLET
WALL TELEPHONE OUTLET WITH PLATE (W-WALL MOUNTED)
NURSE CALL CENTRAL EQUIPMENT CABINET
TELEVISION SIGNAL OUTLET
FLUSH WALL MOUNTED JUNCTION BOX FOR
MOUNTING HEIGHT REFER TO ARCHITECTURALAND MEDICAL EQUIPMENT PLAN DRAWINGS.
SINGLE POWER RECEPTACLE, 20A, 125V 3W GNDG UON.
CIRCUIT BREAKER - 100 AMP
FRAME, 3 POLE, UON
FUSED SWITCH 100 AMP SWITCH/100
AMP TYPE "FA" FUSE 3 POLE UON
CONDUIT HOME RUN TO PANELBOARD "1LB" WITH CIRCUITS 1,3,5
DISCONNECT SWITCH - 30A, NON-FUSED,3-POLE UON. NEMA 1 ENCLOSURE EXCEPT
"3R" INDICATES NEMA 3R.
AUTOMATIC TRANSFER SWITCH AMPS/ POLES AS INDICATED ON PLANS
COMBINATION MOTOR CONTROLLERAND NON-FUSED DISCONNECT
SWITCH
20ADUPLEX CONVENIENCE RECEPTACLE
NUMERAL INDICATES CKT NUMBER
IG = ISOLATED GROUND (ORANGE DEVICE) G = GROUND FAULT INTERRUPER
20A = 20 AMP RATED RECEPTACLE *
* ALL RECEPTACLES ON DEDICATED 20 AMP
CIRCUITS SHALL BE RATED 20A.
INDICATES WALL OUTLET AT NON-STANDARD HEIGHT
WHEN SHOWN ADJACENT TO ANY OUTLET OR
RECEPTACLE. AT COUNTERS, MOUNT 6" ABOVE SPLASH
UON.
WALL MOUNTED DATA/TELEPHONE
GROUND CONNECTION
IGTC
G2PC
400A / 3PT
TIME CLOCKPHOTOCELL CONTROL SWITCH
100CB 60
1LB-1,3,5
MAGNETIC MOTOR STARTER, H-O-A-P U.O.N.
MOTOR
LIGHTING RELAY PANEL
PANELBOARD
TRANSFORMER
CEILING MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
CAPPED CONDUIT
CONDUIT TURNING UP/DOWN
JJJ
UNFUSED SWITCH - 100 AMP 3 POLE, UON
100/100100100
ER RELAY
FIREMAN'S PHONE
FIREMAN'S PHONE HANDSET
FIRE ALARM SPEAKER
FIRE ALARM REMOTE ANNUNCIATOR
FIRE ALARM CONTROL PANELFACP
NURSE CALL CODE BLUE
NURSE CALL STAFF/DUTY STATION
NURSE CALL PATIENT STATION
NURSE CALL MASTER STATION
CEILING MOUNTED ZONE LIGHT
CEILING MOUNTED DOME LIGHT
GENERATOR ANNUNCIATOR PANELGAP
INFRARED SENSORS. SENSORS SHALL BECONNECTED TO CORRIDOR LIGHTING
IRKEY PAD. CONTRACTOR RESPONSIBLE TO PROVIDE ALLREQUIRED HARDWARE AND ELECTRICAL CONNECTIONS.
KPDOOR CONTACT. CONTRACTOR RESPONSIBLE TO
PROVIDE ALL REQUIRED HARDWARE AND ELECTRICAL
CONNECTIONS.
DC
FIRE ALARM WATER FLOW
FIRE ALARM TAMPER SWITCH
FAAP
ELECTRICAL SYMBOLS LEGEND
+XX"
NCM
NCC
PUSHBUTTONK = KEY OPERATED SWITCH (UP/OFF/DOWN
POSITION)
E = EMERGENCY POWER OFF BUTTON
CEILING EXIT LIGHT - DIRECTIONAL ARROWS
WHERE INDICATED, SHADED QUADRANTSINDICATE ILLUMINATED FACES
WALL EXIT LIGHT - DIRECTIONAL ARROWS
WHERE INDICATED SHADED QUADRANTSINDICATE ILLUMINATED FACES
FLUSH MOUNTED CIRCUIT BREAKER 100AFRAME/60A TRIP 3 POLE UON
LRP
EMERGENCY BATTERY PACKFIXTURE
C/B
FC
GA
GFI
GALV
GND
FLA
HP
N
NO
HORIZ
HTG
HOA
GRC
HGT
NF
NL
OL
NEMA
NFPA
NETA
O/C
NEC
P
PB
PH
PF
PLB
EL ELEVATION
FLUOR FLUORESCENT
FEETFT
ELECTRIC
ELEVATOR
EQUIVALENT
EQUIPMENT
FIRE ALARM
FEEDER
FIXTURE
ON EMERGENCY CIRCUIT
ELECTRICAL METALLIC TUBING
FLOOR
FLUSH
FLR
FIXT
FL
FA
FDR
EQMT
EQ
EMT
ELEV
EM
ELEC
VOLT AMPERES
VERTICAL
VENTILATING
VAPORPROOF
WIRE GUARD
WEATHERPROOF
LOCATED
TRANSFORMER
YARD
1 CONDUCTOR, 2 CONDUCTORS, ETC.1/C, 2/C,
LOC.
XFMR
YD
WP
VERT
WG
VP
VENT
VA
CATALOG
CIRCUIT
CEILING
CLOCK
CONTINUOUS
DIRECT CURRENT
CONVENIENCE
DIAMETER
CURRENT TRANSFORMER
COLUMN
CONCRETE
CONT
DC
DIA
C/T
CONV
COL
CONC
CLG
CKT
CL
CAT
ROOT MEAN SQUARE
HEATING
POWER FACTOR
PHASE
PLUMBING
NATIONAL ELECTRICAL TESTING ASSOC.
NATIONAL ELEC MANUFACTURERS ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
OVERCURRENT
ON NIGHT LIGHTING CIRCUIT
OVERLOAD
POLES
PULL BOX
NORMALLY OPEN
NATIONAL ELECTRICAL CODE
NON-FUSE
NEUTRAL
UNDERFLOOR DUCT
UNDERWRITERS LABORATORIES, INC.
TELEPHONE COMPANY
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
GROUND FAULT CIRCUIT INTERRUPTER
HORIZONTAL
HAND OFF AUTOMATIC
HORSEPOWER
GALVANIZED RIGID CONDUIT
HEIGHT
GROUND
GALVANIZED
FULL LOAD AMPERES
FOOT CANDLE
GUAGE
RMS
RM
REQ
REV
RECEPT
REL
RC
REVERSE
REQUIRED
ROOM
REMOTE CONTROL
RECEPTACLE
RELOCATE
PWR
P/T
R
PVC
PP
PNL
POWER
REMOVE
POWER PANEL
PANEL
TELEVISIONTV
UFD
V
UL
UC
TYP
VOLTS
TYPICAL
UNDERCOUNTER
TELCO
SYM
TEL
SWGR
SUSP
SWBD
SYMMETRICAL
TELEPHONE
SUSPENDED
SWITCHBOARD
SWITCHGEAR
ABOVE FINISHED FLOOR
ARCHITECTURAL
ASYMMETRICAL
AUDIO/VISUAL
AUXILLARY
ABOVE FINISHED GRADE
BUILDING
CIRCUIT BREAKER
CONDUIT
AMERCIAN WIRE GAUGE
AUTOMATIC TRANSFER SWITCH
AMERICAN SOCIETY FOR TESTING MATERIALS
AMERICAN NATIONAL STANDARDS INSTITUTE
AWG
C
BLDG
A/V
AUX
ATS
ASTM
ARCH
ASYM
ANSI
AFG
AFF
AMPS
ADJACENT
ALTERNATING CURRENT/ABOVE COUNTERAC
ADJ
A
MOTOR CONTROL PANEL
NORMALLY CLOSED
MAIN LUGS ONLY
SPECS
SPKLR
SQ
SW
SURF
STD
SPKR
SQUARE
STANDARD
SURFACE
SWITCH
SPRINKLER
SPEAKER
SPECIFICATIONS
NC
SP
MTR
MLO
MTD
MOTOR
SPARE
MOUNTED
MIC
MCP
MICROPHONE
KW
KWH
LBS
KVA
LP
LTG
MA
MC
MACH
MCM
MCC
MCB
METAL-CLAD CABLE
MAIN CIRCUIT BREAKER
THOUSAND CIRCULAR MILS
MOTOR CONTROL CENTER
MILLIAMPS
MACHINE
KILOVOLT AMPERES
KILOWATT HOURS
LIGHTING PANEL
POUNDS
LIGHTING
KILOWATT
DP
EC
DWG
IG
HVAC
INCAND
IEEE
IMC
INSUL
J-BOX
INT
E
HEATING, VENTILATING & AIR CONDITIONING
ISOLATED GROUND
INCANDESCENT
JUNCTION BOX
INSULATION
INTERCOM
EMPTY CONDUIT
INTERMEDIATE METAL CONDUIT
DISTRIBUTION PANEL
EXISTING TO REMAIN
DRAWING
EPO
QUAD QUADRUPLEX
PHASEØ
ABBREVIATIONSSYMBOL DESCRIPTION SYMBOL DESCRIPTION
INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
EMERGENCY POWER OFF
GFP GROUND FAULT PROTECTION
TOGGLE SWITCH, 15A / 277VAC UON
2 = DOUBLE POLE3 = THREE-WAY
4 = FOUR-WAY
a = CONTROLS OUTLET OR FIXTURE NOTED "a"K = KEY OPERATED
P = WITH PILOT LIGHT
T = INTERVAL TIMER, 30 MIN. UON
M = MOTOR RATED SWITCH, RATED FOR MOTORSERVED
MO = SPDT MOMENTARY CONTACT
D = DIMMER SWITCH
OC = OCCUPANCY SENSOR
X
SPD SURGE PROTECTION DEVICE
AIR DEVICE MARK
AIR FLOW WITH LETTER DESIGNATION
∅
CONNECTION POINT OF NEW TO EXISTING C CENTER LINE
DIAMETER
HUMIDIFIERH PIPE ALIGNMENT GUIDE
PIPE ANCHOR
HEAT TRACING ON PIPE
FLANGED END
INDICATES DISCONNECTION POINT
SOUND TRAPSTRELATIVE ROOM PRESSURE---+
INDICATES SECTION NUMBERINDICATES DRAWING NUMBER
INDICATES DETAIL NUMBER
INDICATES DRAWING NUMBER
SD
FS
MARK-#
AP ACCESS PANEL
FLEXIBLE CONNECTION, FLEXIBLE DUCT
DUCT ELBOW WITH TURNING VANES
DUCT ELBOW WITHOUT VANES
BDD
FLEXIBLE DUCT CONN. TO RECTANGULAR
BACK DRAFT DAMPER
SPLITTER DAMPER - DIMENSION AS
DUCT WITH SPIN-IN CONNECTOR
SDDIM. NOTED ON DRAWING
EQUIPMENT MARK AND NUMBER
REFER TO DETAIL #1 ON DRAWING M-7
UNDERCUT DOOR 1"UCD 1"
RE: I/M-7 CD
PRESSURE MONITOR
FIRESTATF
P
SD SMOKE DETECTOR
CONDENSATE DRAIN
EXPANSION JOINT
THERMOMETER
TEST PLUG
MANUAL AIR VENT
PRESSURE GAUGE W/GAUGE COCK
AUTOMATIC AIR VENT
THERMOMETER WELL
SOLENOID VALVE
FLOW SWITCH
RELIEF VALVE
STEAM TRAP
STEAM MOISTURE SEPARATOR
TEMPERATURE AND PRESSURE
STEAM CONTROL VALVE
EJ
45° ELBOW DOWN (OGEE)
TEE
UNION (SCREWED)
CROSS
TOP CONNECTION
TEE DOWN
TEE UP
UNION (FLANGED)
PIPE BREAK
CONCENTRIC REDUCER
DUCT MOUNTED TEMPERATURE SENSOR
DUCT MOUNTED PRESSURE SENSOR
DUCT MOUNTED SMOKE DETECTOR
CHWS
CWR
CHWR
HWS
HWR
CWS
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
RED. PRESS PRINCIPAL BACKFLOW PREVENTER
ISOLATION VALVE
BALL VALVE
BUTTERFLY VALVE
END SUCTION PUMP
ECCENTRIC REDUCER
BALANCING VALVE
TWO-WAY VALVE (PNEUMATIC)
PRESSURE REDUCING VALVE
CHECK VALVE, SWING GATE
THREE-WAY VALVE (PNEUMATIC)
ANGLE PRESSURE RELIEF VALVE
GATE VALVE WITH QUICK DISCONNECT
PRESSURE REGULATOR
FLEXIBLE CONNECTION
THREE-WAY VALVE (ELECTRIC)
TWO-WAY VALVE (ELECTRIC)
STRAINER W/BLOW DOWN VALVE
QUICK OPENING/CLOSING VALVE
LOCK SHIELD
SUPPLY AIR DUCT UP (PLAN)
AD
DUCT SPLIT WITH SPLITTER DAMPER
TRANSITION IN DUCT
ACCESS DOOR
SUPPLY AIR DUCT DOWN (PLAN)
RETURN OR OUTSIDE
RETURN OR OUTSIDE
RETURN AIR/TRANSFER AIR BOOT
CEILING SUPPLY AIR DEVICE
CEILING RETURN AIR /
EXHAUST AIR DUCT UP (PLAN)
EXHAUST AIR DUCT DOWN (PLAN)
BRANCH DUCT TAP
AIR DUCT UP (PLAN)
AIR DUCT DOWN (PLAN)
EXHAUST REGISTER
FD
M
VD
AFS
R
D
APD
SIDEWALL SUPPLY/EXHAUST REGISTER
RETURN AIR GRILLE WITH BOOT
MOTORIZED VOLUME DAMPER
COMBINATION FIRE/SMOKE DAMPER
AIR PRESSURE DIFFERENTIAL SWITCH
DROP IN DUCT ELEVATION
RISE IN DUCT ELEVATION
AIR FLOW SWITCH
SMOKE DAMPER
FIRE DAMPER
VOLUME DAMPER
HUMIDISTAT
PIPE UP
90° ELBOW
CAP
PIPE DOWN
H
45° ELBOW
THERMOSTAT - MOUNT 48" AFF UNOT
PRV
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HOT WATER SUPPLY
HOT WATER RETURN
NEW CONSTRUCTION
EXISTING TO REMAIN
(E = EXHAUST) (R = RETURN)
D/P DIFFERENTIAL PRESSURE SENSOR
MECHANICAL SYMBOLS LEGEND
MEP0.1 MEP INFORMATION SHEET
MEP1.0 MEP MECHANICAL SPECIFICATIONS
MEP1.1 MEP ELECTRICAL SPECIFICATIONS
MEP1.2 MEP PLUMBING SPECIFICATIONSM1.03 LEVEL 3 MECHANICAL DEMO PLAN
M1.04 LEVEL 4 MECHANICAL DEMO PLAN
M2.03 LEVEL 3 MECHANICAL FLOOR PLAN
M2.04 LEVEL 4 MECHANICAL FLOOR PLANM3.01 MECHANICAL DETAILS AND SCHEDULES
E2.03 LEVEL 3 POWER FLOOR PLAN
E2.04 LEVEL 4 POWER FLOOR PLAN
E3.03 LEVEL 3 LIGHTING FLOOR PLANE3.04 LEVEL 4 LIGHTING FLOOR PLAN
E4.02 ELECTRICAL PANEL SCHEDULES
E5.01 ELECTRICAL DETAILS
P1.03 LEVEL 3 PLUMBING DEMOLITION PLANP1.04 LEVEL 4 PLUMBING DEMOLITION PLAN
P2.03 LEVEL 3 PLUMBING FLOOR PLAN
P2.04 LEVEL 4 PLUMBING FLOOR PLAN
P4.01 PLUMBING SCHEDULESP5.01 PLUMBING DETAILS
INDEX TO MEP DRAWINGS
CLINICAL AIR
TEMPERATURE AND PRESSURE RELIEF VALVE
OD
PLUG VALVE
STRAINER
UNION
BALL VALVE
XXXX
ELBOW UP
THERMOMETER
FLOOR DRAIN
ELBOW DOWN
CD CONDENSATE DRAIN LINE
PRESSURE REDUCING VALVE
BRANCH CONNECTION, TOP
BRANCH CONNECTION, BOTTOM
VENT THRU ROOF
WALL CLEANOUT
FLOOR CLEANOUT
PRESSURE GAUGE
ITEMS TO BE REMOVED
HOSE BIBB
FIRE RISER IDENTIFICATION
PLUMBING RISER IDENTIFICATION
(N)NEW CONNECTION TO (E)EXISTING
DOWN SPOUT RISER IDENTIFICATION
ACID WASTE RISER IDENTIFICATION
OILY WASTE
EXISTING SANITARY VENT PIPING
STORM OVERFLOW DRAIN PIPING
FIRE PROTECTION MAIN
SANITARY VENT PIPING
STORM DRAIN PIPING
SANITARY WASTE PIPING
MEDICAL VACUUM
SOFTENED COLD WATER
NATURAL GAS
MEDICAL OXYGEN
MEDICAL AIR
NITROGEN
ACID VENT
NITROUS OXIDE
CONDENSATE DRAIN
F
OW
G
CD
NITROGEN
ACID WASTE
CHECK VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
EXISTING DOMESTIC COLD WATER
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER
DOMESTIC HOT WATER
HEAT TRACE AND INSULATE
X
P
X
DS
X
F
X
AW
DIESEL FUEL RETURN
DIESEL FUEL SUPPLYDFS
SCW
CLINICAL AIR
TEMPERATURE AND PRESSURE RELIEF VALVE
OD
PLUG VALVE
STRAINER
UNION
BALL VALVE
XXXX
ELBOW UP
THERMOMETER
FLOOR DRAIN
ELBOW DOWN
CD CONDENSATE DRAIN LINE
PRESSURE REDUCING VALVE
BRANCH CONNECTION, TOP
BRANCH CONNECTION, BOTTOM
VENT THRU ROOF
WALL CLEANOUT
FLOOR CLEANOUT
PRESSURE GAUGE
ITEMS TO BE REMOVED
HOSE BIBB
FIRE RISER IDENTIFICATION
PLUMBING RISER IDENTIFICATION
(N)NEW CONNECTION TO (E)EXISTING
DOWN SPOUT RISER IDENTIFICATION
ACID WASTE RISER IDENTIFICATION
OILY WASTE
EXISTING SANITARY VENT PIPING
STORM OVERFLOW DRAIN PIPING
GREASE WASTE PIPING
AUTOMATIC SPRINLER
FIRE PROTECTION MAIN
SANITARY VENT PIPING
STORM DRAIN PIPING
SANITARY WASTE PIPING
MEDICAL VACUUM
SOFTENED COLD WATER
NATURAL GAS
MEDICAL OXYGEN
MEDICAL AIR
NITROGEN
ACID VENT
NITROUS OXIDE
CONDENSATE DRAIN
F
OW
A/S
G
CD
NITROGEN
ACID WASTE
CHECK VALVE
BUTTERFLY VALVE
GATE VALVE
GLOBE VALVE
EXISTING DOMESTIC COLD WATER
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER
DOMESTIC HOT WATER
HEAT TRACE AND INSULATE
X
P
X
DS
X
F
X
AW
SUB-SOILED DRAIN PIPING
DIESEL FUEL RETURN
DIESEL FUEL SUPPLYDFS
SCW
W
GREASE VENT PIPINGGVGW
CA
N2
MA
N20
MV
SD
SSD
DFR
CA
N2
MA
N20
MV
SD
SSD
DFR
PLUMBING SYMBOLS LEGEND
MEP0.1
MEP INFO
SHEET
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
EP
0.1
_M
EP
IN
FO
SH
EE
T.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
BASIC REQUIREMENTSA. CODES AND STANDARDS:1. ALL WORK SHALL COMPLY WITH THE MOST RECENTLY REVISED VERSIONS OF ALL APPLICABLE LAWS, RULES,REGULATIONS AND ORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES AND APPLICABLE UTILITIES.NONE OF THE TERMS OR PROVISIONS OF THIS SPECIFICATION SHALL BE CONSTRUED AS WAIVING ANY PART OFTHE RULES, REGULATIONS OR REQUIREMENTS OF THESE AUTHORITIES.B. DRAWINGS AND SPECIFICATIONS2. DRAWINGS: THE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE APPROXIMATE LOCATIONS OF THE HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS, FIRE PROTECTION SYSTEMS, PLUMBING EQUIPMENT,FIXTURES AND PIPING SYSTEMS, EXCEPT WHERE SPECIFIC LOCATIONS ARE NOTED AND DIMENSIONED ON THEDRAWINGS. ALL ITEMS ARE SHOWN APPROXIMATELY TO SCALE. THE INTENT IS TO SHOW HOW THESE ITEMS SHALLBE INTEGRATED INTO THE CONSTRUCTION. LOCATE ALL ITEMS BY ON THE JOB MEASUREMENTS AND INACCORDANCE WITH THE CONTRACT DOCUMENTS. COORDINATE WITH OTHER TRADES.C. COMPLETENESS OF WORK1. THE CONTRACT DOCUMENTS DEPICT MECHANICAL AND PLUMBING SYSTEMS WHICH ARE INTENDED TO BECOMPLETE AND FUNCTIONING SYSTEMS. ALL PRODUCTS, MATERIALS, AND LABOR NECESSARY TO RENDER AFULLY FUNCTIONAL SYSTEM TO FULFILL THE DESIGN INTENT SHOWN ON THE DOCUMENTS SHALL BE PROVIDED BYTHE CONTRACTOR.2. CATALOG NUMBERS REFERENCED THROUGHOUT THE DIVISION 15 DRAWINGS AND SPECIFICATIONS ARE INTENDEDTO CONVEY A GENERAL UNDERSTANDING OF THE TYPE AND QUALITY OF THE PRODUCT REQUIRED. WHEREWRITTEN DESCRIPTIONS DIFFER FROM INFORMATION CONVEYED BY A CATALOG NUMBER, THE WRITTENDESCRIPTION SHALL GOVERN. NO EXTRA SHALL BE ALLOWED BECAUSE A CATALOG NUMBER IS FOUND TO BEINCOMPLETE OR OBSOLETE.D. COORDINATION1. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL ITEMS THAT WILL AFFECT THEINSTALLATION OF THE WORK OF THIS DIVISION. THE COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO,VOLTAGE, AMPACITY, CAPACITY, ELECTRICAL/PIPING CONNECTIONS, STRUCTURAL SUPPORTS, SPACEREQUIREMENTS, LOCATING DEVICES IN ARCHITECTURAL FINISH ELEMENTS, STAGING THE CONSTRUCTION ANDBUILDING REQUIREMENTS, AND SPECIAL CONDITIONS.2. BY SUBMITTING SHOP DRAWINGS ON THE PROJECT, THIS CONTRACTOR IS INDICATING THAT ALL NECESSARYCOORDINATION HAS BEEN COMPLETED AND THAT THE SYSTEMS, PRODUCTS AND EQUIPMENT SUBMITTED CAN BEINSTALLED IN THE BUILDING AND WILL OPERATE AS SPECIFIED AND INTENDED, IN FULL COORDINATION WITH ALLOTHER DISCIPLINES.E. WARRANTIES AND GUARANTEES1. GENERAL: CONTRACTOR SHALL GUARANTEE ALL MATERIAL AND EQUIPMENT INSTALLED BY HIM AGAINST DEFECTSIN WORKMANSHIP AND MATERIAL FOR A PERIOD OF TWELVE (12) MONTHS AFTER FINAL ACCEPTANCE OF THEWORK BY THE OWNER, AND HE SHALL REPAIR OR REPLACE ANY MATERIALS OR EQUIPMENT DEVELOPING SUCHDEFECTS WITHIN THAT TIME, PROMPTLY ON DUE NOTICE GIVEN HIM BY THE OWNER AND AT CONTRACTOR'S SOLECOST AND EXPENSE.2. EQUIPMENT: ALL EQUIPMENT BEARING A MANUFACTURER'S GUARANTEE SHALL BE CONSTRUED TO HAVE ANEXTENDED GUARANTEE TO THE OWNER BY THE MANUFACTURER. ANY SUCH EQUIPMENT THAT PROVES DEFECTIVEIN MATERIALS OR WORKMANSHIP WITHIN THE GUARANTEE PERIOD IS TO BE REPLACED BY THE CONTRACTOR INACCORDANCE WITH THE MANUFACTURER'S GUARANTEE.G. BASE BUILDING STANDARDS1. THE INTENT OF THIS SPECIFICATION IS TO PROVIDE A LEVEL OF QUALITY THAT MEETS OR EXCEEDS APPLICABLECODES AND OWNERS EXPECTATIONS. IF ANY PORTION OF THESE SPECIFICATIONS ARE DIFFERENT THAT THEBUILDING STANDARDS, THIS SHOULD BE BROUGHT TO THE ENGINEER'S ATTENTION IMMEDIATELY TO DETERMINEWHICH IS THE CORRECT SPECIFICATION. ANY CHANGE WILL NOT BE CONSIDERED A CHANGE ORDER AS THECONTRACTOR SHOULD BID ON THE MOST STRINGENT OF THE TWO.H. SYSTEM CLEANING
1. DUCTWORK: THE DUCT SYSTEM SHALL BE KEPT CLEAN AND FREE FROM DUST AND DIRT
DURING THE FABRICATION AND ERECTION PROCESS. WIPE EACH SECTION OF DUCT DOWNPRIOR TO HANGING IN PLACE. OPEN ENDS OF DUCT SYSTEMS SHALL BE SEALED WITH SHEET
PLASTIC UNTIL FINAL CONNECTION TO AIR DEVICES HAS BEEN MADE. CLEAN ALL INTERIOR
SURFACES OF DUCTWORK PRIOR TO STARTING THE SYSTEM FAN. REPAIR ALL TEARS IN
INTERNAL DUCT LINER WITH MASTIC RATED FOR THE INSULATION SYSTEM.
2. EQUIPMENT: KEEP EQUIPMENT CLEAN AND DRY DURING THE CONSTRUCTION PROCESS.
PRIOR TO START UP, INSPECT AND CLEAN ALL INTERIOR EQUIPMENT SURFACES, CLEAN AND
REPAIR TORN INSULATION, REMOVE ALL DIRT AND DEBRIS. PROVIDE TEMPORARY FILTER
MEDIA AS REQUIRED FOR UNIT OPERATION PRIOR TO FINAL COMMISSIONING.GENERAL MECHANICAL NOTESA. BEFORE SUBMITTING A BID, IT WILL BE NECESSARY FOR EACH CONTRACTOR WHOSE WORK IS INVOLVED TO VISIT THESITE AND ASCERTAIN FOR HIMSELF THE CONDITIONS TO BE MET IN INSTALLING THE WORK AND MAKE PROVISIONSFOR THE CONDITIONS IN HIS FINAL PRICE. FAILURE ON THE PART OF THE CONTRACTOR TO COMPLY WITH THISREQUIREMENT SHALL NOT BE CONSIDERED JUSTIFICATION FOR THE OMISSION OR FAULTY INSTALLATION OF ANYWORK COVERED BY THE CONTRACT DOCUMENTS.B. THE CONTRACTOR SHALL SECURE ALL PERMITS, LICENSES AND INSPECTIONS REQUIRED FOR HIS WORK, AND SHALLPAY ALL FEES IN CONNECTION WITH SUCH PERMITS, LICENSES AND INSPECTIONS.C. WORK SHALL COMPLY WITH THE MOST RECENT VERSION OF ALL APPLICABLE LAWS, RULES, REGULATIONS ANDORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES. IN THE EVENT OF CONFLICT BETWEEN THECONTRACT DOCUMENTS AND THE LOCAL ENFORCING AUTHORITY, THE LATTER SHALL RULE. ANY MODIFICATIONRESULTING THEREFROM SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER OR ARCHITECT/ENGINEER. THECONTRACTOR SHALL REPORT ANY SUCH MODIFICATIONS TO THE ARCHITECT/ENGINEER AND SECURE HIS APPROVALBEFORE PROCEEDING. SHOULD THE REQUIREMENTS OF THE CONTRACT DOCUMENTS EXCEED THE REQUIREMENTSOF THE CODES, THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE PROVIDED THEY ARE NOT IN CONFLICT WITHTHOSE CODES.D. ALL ITEMS OF EQUIPMENT AND ALL MATERIALS FOR WHICH APPROVAL STANDARDS HAVE BEEN ESTABLISHED BYUNDERWRITERS' LABORATORIES, INC. (UL), FACTORY MUTUAL (FM), CERTIFIED BALLAST MANUFACTURER (CBM),ELECTRICAL TESTING ASSOCIATION (NEMA) SHALL BE SO APPROVED AND SHALL BEAR APPROVAL LABELS.E. PENETRATIONS THROUGH FLOORS OR FIRE-RATED CONSTRUCTION SHALL BE FIRESAFED TO COMPLY WITH ASTME-814 (UL 1479), AND LOCAL CODE REQUIREMENTS.SUBMITTALS AND SHOP DRAWINGSA. CONTRACTOR SHALL PROVIDE THE ENGINEER WITH PRODUCT DATA AND SHOP DRAWINGS FOR ALL MATERIALS &EQUIPMENT SPECIFIED BELOW. SUBMITTALS SHALL BE PROVIDED IN AN ELECTRONIC FORMAT. SUBMITTAL DATASHALL INCLUDE:1. COVER SHEET WITH NAMES AND ADDRESSES OF PROJECT, ARCHITECT MEP ENGINEER, GENERAL CONTRACTOR &SUB CONTRACTOR.2. DRAWING REFERENCE NUMBER, PRODUCT NAME AND/OR DESCRIPTION.3. INDEX OF ALL DATA IN SUBMITTAL.4. DIMENSIONAL DATA AND SKETCHES SHOWING THAT SUBMITTED EQUIPMENT WILL FIT INTO SPACE AVAILABLE ANDWILL HAVE REQUIRED CODE AND MAINTENANCE CLEARANCES.5. IDENTIFICATION OF EACH ITEM MATCHING THAT INDICATED ON THE DRAWINGS.6. SUFFICIENT PERFORMANCE DATA, CAPACITY, SOUND DATA, DIAGRAMMATIC DATA AND DESCRIPTIVE INFORMATIONTO SHOW ITS COMPLIANCE'S WITH THE CONTRACT DOCUMENTS. OPTIONS OR SPECIAL REQUIREMENTS SHALL BECLEARLY INDICATED. APPLICABLE INFORMATION SHALL BE CLEARLY INDICATED AND NON APPLICABLE DATA SHALLBE CROSSED OFF.7. MATERIALS AND EQUIPMENT PURCHASED OR INSTALLED WITHOUT A "NO EXCEPTIONS TAKEN" SHOP DRAWINGREVIEW SHALL BE AT THE RISK OF THE CONTRACTOR. THE COST OF REMOVAL AND AT THE RISK OF THECONTRACTOR. THE COST OF REMOVAL AND REPLACEMENT OF SUCH MATERIALS WHICH IS JUDGEDUN-SATISFACTORY BY THE ENGINEER FOR ANY REASON SHALL BE AT THE EXPENSE OF THE CONTRACTOR.8. ANY ITEMS KNOWINGLY SUBMITTED THAT DO NOT COMPLY WITH SPECIFICATIONS SHALL BE LISTED WITHEXPLANATION AS TO WHY THEY ARE BEING SUBMITTED.B. REQUIRED SUBMITTALS/SHOP DRAWINGS.1. DAMPERS2. GRILLES, REGISTERS AND DIFFUSERSGENERAL MATERIALS AND METHODSA. HANGERS AND SUPPORTS1. GENERAL: PROVIDE PIPE HANGERS AND SUPPORT MATERIALS AS SPECIFIED HEREIN. ALL HORIZONTAL ANDVERTICAL PIPING SHALL BE THOROUGHLY AND SUBSTANTIALLY SUPPORTED IN ACCORDANCE WITH ANSI B31.1STANDARD CODE FOR PRESSURE PIPING AND MANUFACTURERS' STANDARDIZATION SOCIETY MSS
SP-69 PIPE HANGERS AND SUPPORTS - SELECTION AND APPLICATION. THE DESIGN, TYPE, SPACING
AND APPLICATION OF ALL HANGERS, SUPPORTS, ANCHORS AND GUIDES SHALL COMPLY WITH THE ABOVESTANDARDS. HANGER RODS SHALL BE GALVANIZED OR CADMIUM PLATED. HANGER ROD CLAMPS AND INSERTSSHALL BE AS RECOMMENDED BY THE CLAMP OR INSERT MANUFACTURER FOR THE INTENDED USE AND SHALL BEAPPROVED IN WRITING BY THE STRUCTURAL ENGINEER. ALL METHODS OF ATTACHMENT TO THE STRUCTURE ANDTHE USE OF AFTER-SET INSERTS SHALL BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. THE LOADAND SPACING ON EACH HANGER AND/OR INSERT SHALL NOT EXCEED THE SAFE ALLOWABLE LOAD FOR ANYCOMPONENT OF THE SUPPORT SYSTEM, INCLUDING THE CONCRETE WHICH HOLDS THE INSERTS.REINFORCEMENT AT INSERTS SHALL BE PROVIDED AS REQUIRED TO DEVELOP THE STRENGTH REQUIRED.B. PAINTING1. ALL MACHINERY AND EQUIPMENT NOT FINISHED AT THE FACTORY SHALL BE GIVEN A PRIME COAT AND THEN FINISHPAINTED WITH TWO COATS OF ENAMEL IN COLORS AS DIRECTED BY THE ARCHITECT/ENGINEER OR OWNER'SREPRESENTATIVE. NO NAMEPLATES ON EQUIPMENT SHALL BE PAINTED, AND SUITABLE PROTECTION SHALL BEAFFORDED SUCH PLATES TO PREVENT THEIR BEING RENDERED ILLEGIBLE DURING THE PAINTING OPERATIONS.2. ALL UNINSULATED BLACK STEEL PIPE, HANGERS AND SUPPORTS SHALL BE GIVEN TWO COATS OF PRIMER. WHEREEXPOSED TO OUTDOOR WEATHER OR PUBLIC VIEW, THESE ITEMS SHALL BE PRIMED AND FINISHED WITH TWOCOATS OF ENAMEL IN COLORS .3. ALL INSULATED PIPING EXPOSED TO VIEW SHALL HAVE THE FINISHED INSULATION PAINTED WITH TWO COATS OFACRYLIC IN COLORS AS INDICATED IN THE PIPING SYSTEM IDENTIFICATION TABLE. PIPING CONCEALED INFURRINGS, CHASES, OR ABOVE SUSPENDED CEILINGS, NEED NOT BE PAINTED.C. IDENTIFICATION AND LABELING1. ROOFTOP EQUIPMENT, AIR HANDLING UNITS, PUMPS, WATER HEATERS, SUPPLY FANS, DUCT HEATERS, EXHAUSTFANS, WATER CHILLING UNITS, BOILERS, COOLING TOWERS, AND ANY OTHER EQUIPMENT DESIGNATED BY THEARCHITECT/ENGINEER SHALL BE LABELED WITH PERMANENTLY ATTACHED ENGRAVED NAMEPLATESCONSTRUCTED FROM LAMINATED PHENOLIC PLASTIC, AT LEAST 1/16 INCH THICK, 3-PLY, BLACK SURFACES ANDWHITE CORE. ENGRAVING SHALL BE CONDENSED GOTHIC AT LEAST 3/8 INCH HIGH. ENGRAVING SHALL INCLUDEEQUIPMENT NAME AND NUMBER AND ELECTRICAL PANEL AND CIRCUIT WHICH SERVICES THE EQUIPMENT.CONSULT ARCHITECT/ENGINEER FOR LABEL NOMENCLATURE.2. ALL VALVES AT MAJOR EQUIPMENT AND IN ALL EQUIPMENT ROOMS SHALL BE MARKED WITH 1-1/2" DIAMETERALUMINUM OR ENGRAVED PLASTIC TAGS SECURELY ATTACHED TO VALVE STEMS WITH "S" HOOKS.3. PIPING AT MAJOR EQUIPMENT AND IN ALL EQUIPMENT ROOMS SHALL BE IDENTIFIED BY COLOR CODED MARKERSAS TO TYPE OF USE, SERVICE AND DIRECTION OF FLOW AS INDICATED WITHIN THE PIPING SYSTEM IDENTIFICATIONTABLE. MARKERS SHALL BE LOCATED AT EACH VALVE, ON 20 FOOT CENTERS ON STRAIGHT RUNS OF PIPE AND ATLEAST ONCE IN OR ABOVE EACH ROOM AND EACH STORY TRAVERSED BY THE PIPING. PIPING CONCEALED INACCESSIBLE LOCATIONS SHALL BE MARKED ON 50 FOOT CENTERS ON STRAIGHT RUNS OF PIPE AND AT ALLCHANGES IN DIRECTION. LABELS SHALL BE AS MANUFACTURED BY BRADY, BRIMAR, SETON, MARKING SERVICES,INC., OR WESTLINE.4. ACCESS DOORS PROVIDED FOR ACCESS AND SERVICING OF FIRE AND SMOKE DAMPERS SHALL BE LABELED AS TOTYPE OF DAMPER (FIRE, SMOKE, COMBINATION FIRE AND SMOKE) SERVED.AIR BALANCEA. UPON COMPLETION OF THE INSTALLATION OF THE HVAC SYSTEMS, THE AIR VOLUME FOR EACH GRILLE HALL BE SETTO DELIVER THE LISTED AIR VOLUME AND THE EXHAUST SYSTEM SHALL BE ADJUSTED TO ITS RATED EXHAUSTVOLUME. AN INDEPENDENT, NEBB OR AABC CERTIFIED AIR BALANCE CONTRACTOR SHALL PERFORM THE AIR BALANCEAND SHALL SUBMIT A REPORT TO THE ENGINEER INDICATING AIR QUANTITIES AT ALL AIR HANDLING EQUIPMENT ANDAIR DISTRIBUTION DEVICES. THE REPORT SHALL SHOW DESIGN QUANTITIES AND MEASURED QUANTITIES. ALL SUPPLYAND EXHAUST VOLUMES MUSTBE EQUAL TO OR WITHIN +5% OF THE LISTED AIRFLOW RATE.AIR DISTRIBUTION DEVICES AND DAMPERSA. SCOPE1. GENERAL: FURNISH AND INSTALL AIR DISTRIBUTION DEVICES AS SHOWN, SCHEDULED, SPECIFIED, AND REQUIRED.DEVICES SHALL BE COMPLETE WITH ALL REQUIRED MOUNTING ACCESSORIES FOR INSTALLATION IN THE ACTUALCONSTRUCTION AT THE INSTALLATION LOCATION.QUALITY ASSURANCEB. QUALITY ASSURANCE1. MANUFACTURERS: IF THEY COMPLY WITH THESE SPECIFICATIONS AND REQUIREMENTS, PRODUCTS OF THEFOLLOWING MANUFACTURERS WILL BE ACCEPTABLE:1.1 NAILOR1.2 KRUEGER1.3 METALAIRE1.4 TITUS1.5 PRICE1.6 RUSKINC. PRODUCTS1. GENERAL: PROVIDE AIR DISTRIBUTION DEVICES OF THE SIZE, SHAPE, AND TYPE CONSTRUCTED OF MATERIALSAND COMPONENTS AND WITH FINISHES AS SPECIFIED, SCHEDULED, AND SHOWN. GRILLES, REGISTERS, ANDCEILING DIFFUSERS SHALL BE PROVIDED WITH NEOPRENE OR SOFT FELT GASKETS. IF AMANUFACTURER OTHER THAN THE ONE SCHEDULED IS USED, THE SIZES SHOWN ON THE DRAWINGS SHALL BECHECKED FOR PERFORMANCE, NOISE LEVEL, FACE VELOCITY, THROW, PRESSURE DROP, ETC., BEFORE THESUBMITTAL IS MADE. SELECTIONS SHALL MEET THE MANUFACTURER'S OWN PUBLISHED DATA FOR THE ABOVEPERFORMANCE CRITERIA. THE THROW SHALL BE SUCH THAT THE VELOCITY AT THE END OF THE THROW IN THEFIVE FOOT OCCUPANCY ZONE WILL BE NOT MORE THAN 50 FPM NOR LESS THAN 25 FPM. NOISE LEVELS SHALL NOTEXCEED THOSE PUBLISHED IN THE ASHRAE APPLICATIONS HANDBOOK FOR THE TYPE OF SPACE BEING SERVED(NC LEVEL) EXCEPT NONE SHALL EXCEED NC 35.2. SURFACE COMPATIBILITY: AIR DISTRIBUTION DEVICES SHALL HAVE FRAMES FULLY COMPATIBLE WITH THE CEILING,WALL, AND FLOOR SURFACES IN WHICH THEY ARE INSTALLED AND SHALL BE PROVIDED WITH ALL REQUIREDMOUNTING ACCESSORIES FOR INSTALLATION IN THE ACTUAL CONSTRUCTION AT THE INSTALLATION LOCATION.PROVIDE CONCEALED FASTENING ON ALL SURFACES.3. FINISHES: ALL CEILING AND WALL MOUNTED AIR DEVICES SHALL HAVE CORROSION RESISTANT TREATEDSURFACES AND BE PAINTED WHITE OR OFF-WHITE WITH BAKED ENAMEL UNLESS SPECIFIED OTHERWISE AND ALLAIR DEVICES SHALL BE THE SAME COLOR. WHERE THE FACTORY FINISH ON ALL DEVICES IS NOT THE SAME ASDETERMINED BY THE ARCHITECT/ENGINEER, THE DIVISION 15 CONTRACTOR SHALL BE RESPONSIBLE FORCOORDINATING FIELD PAINTING OF ALL AIR DEVICES BY THE DIVISION 9 CONTRACTOR. THE MECHNAICALCONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH DIVISION 9 FIELD PAINTING OF WHITEOR OFF-WHITE AIR DEVICES. SPECIAL COLOR PAINTING OF AIR DEVICES SHALL BE THE RESPONSIBILITY OF THEDIVISION 9 CONTRACTOR. THE ARCHITECT/ENGINEER'S DECISION ON WHITE COLOR COMPATIBILITY IS FINAL. THEINTERIOR OF ALL PERFORATED PLATE DIFFUSERS SHALL BE PAINTED FLAT BLACK. ALL STEEL COMPONENTS SHALL BE FULLY PHOSPHATIZED PRIOR TO PAINTING AND THERE SHALL BE NO UNPAINTED STEEL PARTS.4. CEILING DIFFUSERS: PROVIDE OPPOSED BLADE VOLUME CONTROL DAMPERS WITH SUPPLY AIR DIFFUSERSWHERE DIFFUSERS ARE INSTALLED ABOVE INACCESSIBLE CEILINGS AND WHERE SCHEDULED. WHEREAPPLICABLE, PROVIDE ADAPTERS WITH DIFFUSERS TO PERMIT CONNECTION TO ROUND SUPPLY DUCT.PERFORATED PLATE SUPPLY AIR DIFFUSERS SHALL HAVE PATTERN CONTROL BLADES INSTALLED IN THEDIFFUSER NECK UNLESS NOTED OTHERWISE. PATTERN CONTROLLERS ATTACHED TO THE PERFORATED PLATEARE NOT ACCEPTABLE. PROVIDE CONCEALED FASTENING ON ALL CEILING DIFFUSERS. DEVICE NECK SIZE SHALLBE AS SHOWN ON THE DRAWINGS.5. REGISTERS AND GRILLES: PROVIDE REGISTERS WHICH CONTAIN A KEY-OPERATED OPPOSED BLADE DAMPEROPERABLE FROM THE FACE SIDE WHERE REGISTERS ARE DUCTED AND INSTALLED IN INACCESSIBLE SURFACES.SUPPLY AIR REGISTERS SHALL BE OF THE DOUBLE DEFLECTION TYPE. RETURN AIR GRILLES AND REGISTERSSHALL HAVE FIXED FACE BLADES AND MATCH THE FACE OF THE SUPPLY AIR CEILING DIFFUSERS, UNLESSOTHERWISE INDICATED. PROVIDE CONCEALED FASTENING FOR ALL REGISTERS AND GRILLES.DAMPERSA. FIRE DAMPERS1. FURNISH AND INSTALL DYNAMIC FIRE DAMPERS AT ALL LOCATIONS SHOWN ON THE DRAWINGS AND AS REQUIRED.ALL FIRE DAMPERS SHALL BE UL LABELED AS DYNAMIC FIRE DAMPERS AND SHALL MEET ALL THE REQUIREMENTSOF THE CURRENT EDITION OF NFPA 90A AND UL STANDARD 555.2. DAMPERS SHALL BE ACTIVATED BY A UL APPROVED FUSIBLE LINK WHICH SHALL AUTOMATICALLY CLOSE THEDAMPER UPON OPERATION. FUSIBLE LINKS SHALL OPERATE AT APPROXIMATELY 50OF ABOVE THE MAXIMUMTEMPERATURE IN THE DUCT SYSTEM IN NORMAL OPERATION, BUT NOT LESS THAN 165OF. ALL DAMPERSASSOCIATED WITH LIFE SAFETY SYSTEMS SHALL HAVE MINIMUM 212OF FUSIBLE LINKS. HINGED DAMPERS SHALLHAVE STAINLESS OR CADMIUM PLATED SPRING STEEL CATCHES. ALL DAMPERS SHALL HAVE SPRING CLOSURE TOINSURE POSITIVE SHUT-OFF AT VELOCITIES UP TO 5000 FPM AND PRESSURES UP TO 10" WG.3. DAMPERS INSTALLED IN ONE-HOUR AND TWO-HOUR RATED ASSEMBLIES SHALL BE UL RATED AT ONE ANDONE-HALF (1-1/2) HOURS PER UL STANDARD 555 AND SHALL BE RUSKIN TYPE DIBD2 STYLE B AND C, AIR BALANCETYPE B OR C, NATIONAL CONTROLLED AIR, OR LISTED MANUFACTURER APPROVED EQUAL.4. DAMPERS SHALL BE SIZED SO THAT THE FREE AREA SPACE IS NOT LESS THAN 90% OF THE CONNECTED DUCTFREE AREA SPACE FOR LOW VELOCITY, LOW PRESSURE DUCT WORK AND 100% OF THE CONNECTED DUCT FREEAREA SPACE FOR HIGH VELOCITY, HIGH PRESSURE DUCT WORK. DAMPERS SHALL BE INSTALLED SO AS TOPROVIDE A POSITIVE BARRIER TO THE PASSAGE OF AIR WHEN IN THE CLOSED POSITION. DAMPERS SHALL BEINSTALLED WITH ANGLE IRON FRAMES AND SLIP JOINT CONNECTIONS PER MANUFACTURER'S INSTALLATIONREQUIREMENTS AND SMACNA STANDARDS SUCH THAT THEY ARE SELF-SUPPORTING IN THE CASE OF DUCTDESTRUCTION DUE TO HEAT. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING
LOCATIONS WHICH REQUIRE SPECIAL SLEEVES.5. PROVIDE ACCESS DOORS AS SPECIFIED UNDER DUCT WORK FOR ALL INTERNALLY ACTUATED DAMPERS. WHEREDUCT ACCESS DOORS ARE INSTALLED IN NON-ACCESSIBLE LOCATIONS, PROVIDE CEILING OR WALL ACCESSDOORS. LABEL DUCT ACCESS DOORS "FIRE DAMPER ACCESS" WITH 1/2" HIGH BLACK STENCIL LETTERS.B. AUTOMATIC DAMPERS1. SEE SECTION "BUILDING CONTROL AND AUTOMATION SYSTEM" FOR REQUIREMENTS, INCLUDING BLANK-OFF ANDTRANSITION PROVISIONS. PROVIDE ACCESS DOORS FOR DAMPERS AS REQUIRED.C. FIRE/SMOKE DAMPERS1. FURNISH AND INSTALL DYNAMIC FIRE/SMOKE DAMPERS AT ALL DUCT PENETRATIONS OF SMOKE PARTITIONS, ANDAS SHOWN ON THE DRAWINGS OR REQUIRED. DAMPERS SHALL BE MULTI-BLADE OPPOSED BLADE TYPECOMBINATION FIRE/SMOKE DAMPERS AND SHALL POSSESS A 1-1/2 HOUR UL LABEL IN ACCORDANCE WITH ULSTANDARD 555S AND SHALL MEET ALL REQUIREMENTS OF THE LATEST EDITION OF NFPA 90A AND 101. DYNAMICDAMPERS SHALL BE TESTED AND CERTIFIED IN ACCORDANCE WITH AMCA STANDARD 500-89 AND SHALL BELEAKAGE CLASS I, 250OF PER UL STANDARD 555S.2. FIRE/SMOKE DAMPERS AND OPERATORS SHALL BE UL LISTED AND LABELED IN THE SIZES USED ON THE PROJECTAND ALL DAMPERS ON THE PROJECT SHALL BE BY THE SAME MANUFACTURER. UL LABELING OF DAMPER SIZESUSED ON THE PROJECT SHALL BE CLEARLY INDICATED ON SHOP DRAWING SUBMITTAL.3. DAMPERS SHALL BE SUITABLE FOR OPENING AND CLOSING AT ELEVATED TEMPERATURE, STATIC PRESSURE UP TO4.0" WG AND AT AIR VELOCITIES UP TO 2000 FPM. DAMPERS SHALL BE ULTRA LOW LEAKAGE TYPE, CLASS 1 RATED.4. ALL COMBINATION FIRE/SMOKE DAMPERS SHALL INCLUDE AN OPERATING SHAFT WHICH, WHEN ROTATED, CAUSESTHE DAMPER TO OPERATE BETWEEN OPEN AND CLOSED. OPERATING SHAFT AND DAMPER COMBINATION BY ANYSTANDARD ELECTRIC DAMPER OPERATOR HAVING SUFFICIENT TORQUE CHARACTERISTICS. COMBINATIONFIRE/SMOKE DAMPERS SHALL BE RUSKIN TYPE FSD-60, FSD-60LP OR AN APPROVED EQUAL BY AIR BALANCE,GREENHECK, NATIONAL CONTROLLED AIR, OR SAFE-AIR WITH 212°F THERMAL LINKS AND RECTANGULAR, ROUNDOR OVAL DUCT CONNECTIONS AS REQUIRED.5. EACH COMBINATION FIRE/SMOKE DAMPER SHALL BE FURNISHED COMPLETE WITH FACTORY SLEEVE, DAMPEROPERATOR AND THERMAL LINK FACTORY INSTALLED. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FORCOORDINATING LOCATIONS WHICH REQUIRE A SPECIAL SLEEVE AND N.O./ N.C. FEATURES. ALL DAMPERS SHALLSPRING CLOSED UPON ACTIVATION OF FIRESTATS AND MELTING OF FUSIBLE LINKS. FUSIBLE LINKS SHALL BERATED FOR 212°F. ACTUATORS SHALL BE 120 VOLT ELECTRIC TWO POSITION TYPE. DAMPER OPERATORS SHALLBE UL LISTED AS FIRE DAMPER OPERATORS, SHALL BEAR THE APPROPRIATE UL FIRE DAMPER OPERATOR LABELAND SHALL BE RATED FOR CONTINUOUS OPERATION AT 350°F. DAMPER OPERATORS SHALL HAVE THE FOLLOWINGCONFIGURATIONS:a. SMOKE EXHAUST SYSTEM APPLICATIONS: PROVIDE NORMALLY CLOSED (N.C.) TYPE OPERATORS OF THEPOWER OPEN/SPRING - RETURN FAIL CLOSED TYPE THAT WILL CLOSE THE DAMPER UPON LOSS OF CONTROLPOWER.b. HVAC SYSTEM APPLICATIONS: PROVIDE NORMALLY OPEN (N.O.) TYPE OPERATORS OF THE POWERCLOSED/SPRING - RETURN FAIL OPEN TYPE THAT WILL OPEN THE DAMPER UPON LOSS OF CONTROL POWER.6. ALL POWER AND CONTROL WIRING, SWITCHES, AND RELAYS TO INTERFACE THE CONTROLS WITH THE FIREDETECTION AND ALARM SYSTEMS SHALL BE FURNISHED AND INSTALLED UNDER DIVISION 16. DAMPERS SHALL BEINSTALLED WITH ANGLE IRON FRAMES AND SLIP JOINT CONNECTIONS PER MANUFACTURER'S RECOMMENDATIONSAND SMACNA STANDARDS SUCH THAT THEY ARE SELF-SUPPORTING IN THE CASE OF DUCT DESTRUCTION DUE TOHEAT. PROVIDE ACCESS DOORS AS SPECIFIED UNDER DUCT WORK AND SHEET METAL FOR ALL INTERNALLYACTUATED DAMPERS AND FOR MAINTENANCE INSPECTION OF ALL EXTERNALLY ACTUATED DAMPERS. WHEREDUCT ACCESS DOORS ARE INSTALLED IN NON-ACCESSIBLE LOCATIONS, PROVIDE CEILING OR WALL ACCESSDOORS. LABEL DUCT ACCESS DOORS "FIRE-SMOKE DAMPER ACCESS" WITH 1/2" HIGH BLACK STENCIL LETTERS.7. AT THE CONTRACTOR'S OPTION, FIRE/SMOKE DAMPERS WITH MANUAL AIR BALANCING CAPABILITY MAY BE USEDIN LIEU OF FIRE/SMOKE DAMPERS AND ADJACENT VOLUME DAMPERS.D. RADIATION DAMPERS1. CEILING RADIATION TYPE FIRE DAMPERS SHALL BE INSTALLED IN ALL U.L. DESIGN ASSEMBLY FIRED RATEDCEILINGS IN STRICT ACCORDANCE WITH MANUFACTURERS U.L. LISTED INSTALLATION INSTRUCTIONS. CEILINGDAMPERS SHALL CONFORM TO U.L. STANDARD 555C.2. PROVIDE RUSKIN MODEL #CFD(R)2, CFD(R)3 OR LISTED MANUFACTURER APPROVED EQUAL RECTANGULAR ORROUND NECK, EXTENDED COLLAR, FUSIBLE LINK FOR UP TO 20 INCH DIAMETER ROUND NECK OR UP TO 18 X 18INCH SQUARE NECK, T-BAR 24 X 24 FACE LAY-IN DIFFUSER. AIR DEVICE PAN SHALL BE MINIMUM OF 24 GAUGESTEEL AS REQUIRED BY U.L.3. DIFFUSER PAN INSULATION SHALL BE 1/2" THICK CERAMIC INSULATION BLANKET OR 3/4" THICK MINERAL WOOLINSULATION BLANKET. THERMAL INSULATION BLANKETS SHALL BE TOTALLY ENCLOSED IN AN APPROVED JACKETMATERIAL TO KEEP FIBERS OUT OF THE PLENUM RETURN AIR STREAM.4. DAMPER BLADES REQUIRING RADIATION PROTECTION SHALL UTILIZE SHEET ROCK (GYPSUM BOARD) ATTACHED TOTHE BLADES.5. FUSIBLE LINKS SHALL BE ACCESSIBLE FROM THE FACE OF THE UNIT IN THE OPEN OR CLOSED POSITION FOR TESTAND RESET PURPOSES. REMOVAL OF DUCT SHALL NOT BE REQUIRED TO REPLACE FUSIBLE LINKS.E. VOLUME BALANCING DAMPERS1. BALANCING DAMPERS SHALL BE PROVIDED IN ALL ZONES OF MULTI-ZONE AIR HANDLING UNITS, BRANCH TAP TOALL AIR DEVICES, AND WHERE SHOWN ON THE DRAWINGS AND SHALL CONSIST OF SINGLE BLADE DAMPERS ONRECTANGULAR DUCT UP TO 11" HIGH AND OPPOSED BLADE DAMPERS IN DUCTS 12" AND LARGER. SINGLE BLADEDAMPERS SHALL BE IN ACCORDANCE WITH FIG. 2-11 OF THE SMACNA MANUAL AND OPPOSED BLADE DAMPERSSHALL BE IN ACCORDANCE WITH FIG. 2-12 OF THE SMACNA MANUAL. DAMPERS SHALL BE OF THE FOLLOWINGTYPES:a. SINGLE BLADE DAMPERS FOR RECTANGULAR DUCT SHALL BE RUSKIN MD35 SINGLE BLADE SERIES OR ANAPPROVED EQUAL.b. OPPOSED BLADE DAMPERS FOR RECTANGULAR DUCT SHALL BE RUSKIN MD 35/OB OR LISTEDMANUFACTURER APPROVED EQUAL.c. RIGID ROUND DUCT DAMPERS SHALL BE DURODYNE "JDS" SERIES JIFFY DAMPER OR AND APPROVED EQUAL.d. SPIN-IN FITTING WITH DAMPER, 2" BUILD-OUT, 3/8" SQUARE SHAFT, U-BOLT, NYLON BUSHINGS, EVERLOCKLOCKING QUADRANT WITH HANDLE FOR ALL ROUND BRANCH DUCTS TO AIRDEVICES.2. DAMPER REGULATORS FOR CONCEALED ACCESSIBLE APPLICATIONS SHALL BE YOUNG VALCALOX 400 SERIES ORAN APPROVED EQUAL. WHERE REGULATORS ARE INSTALLED ON EXTERNALLY INSULATED DUCT WORK, PROVIDESTAND-OFF PLATFORMS AT LEAST 1/4" HIGHER THAN THE INSULATION THICKNESS. WHERE REGULATORS AREREQUIRED IN NON-ACCESSIBLE LOCATIONS, PROVIDE ACCESS DOORS OR YOUNG OR EQUAL EXTENSION RODS,COUPLINGS, 90O GEAR DRIVES, ETC. AS REQUIRED AND YOUNG 301 OR APPROVED EQUAL FLUSH MOUNTEDREMOTE REGULATOR AS DIRECT BY THE ARCHITECT.F. BACK DRAFT DAMPERS - COUNTERBALANCED1. FURNISH AND INSTALL COUNTERBALANCED BACK DRAFT DAMPERS WHERE INDICATED ON THE DRAWINGS. EACHDAMPER SHALL BE SIZED AS INDICATED ON THE DRAWINGS, AND SHALL BE SUITABLE FOR INSTALLATION IN THEMOUNTING ARRANGEMENT SHOWN.2. BACK DRAFT DAMPER SHALL BE THE HEAVY DUTY PRESSURE RELIEF COUNTERBALANCED SHUTTER TYPE SIMILARTO RUSKIN TYPE CBS4, OR LISTED MANUFACTURER APPROVED EQUAL AS FOLLOWS:a. DAMPER FRAME SHALL BE AT LEAST 16 GAUGE GALVANIZED STEEL OR 16 GAUGE ALUMINUM. DAMPER FRAMESHALL BE OF CHANNEL CONSTRUCTION FOR DUCT WORK MOUNTING OR HAVE A FRONT FLANGE WHENINSTALLED IN A WALL.b. DAMPER BLADES SHALL BE AT LEAST 16 GAUGE GALVANIZED STEEL OR ALUMINUM. PROVIDE INDIVIDUALCOUNTERWEIGHTS ON EACH BLADE. THE DAMPER SHALL BE CAPABLE OF MAINTAINING STATIC PRESSURESOF 0.05 TO 0.20 INCHES WG. FURNISH TIE BARS CONSTRUCTED OF AT LEAST 16 GAUGE GALVANIZED STEELOR ALUMINUM ON DAMPER SECTIONS OVER 24" WIDE. AFTER DAMPER HAS BEEN INSTALLED,COUNTERWEIGHTS SHALL BE ADJUSTED TO BALANCE THE SYSTEM STATIC PRESSURE AS DIRECTED BY THEENGINEER.c. DAMPER BLADES SHALL HAVE POLYURETHANE FOAM, NEOPRENE, OR VINYL GASKETS GLUED, RIVETED ORROLLED INTO BLADE EDGES.d. DAMPER BEARINGS SHALL BE BRONZE OILITE, NYLON, OR CYCOLOY.e. FURNISH COUNTERBALANCED BACK DRAFT DAMPERS WITH NO. 1-1/2 MESH ALUMINUM BIRD SCREEN FORREAR MOUNTING WHERE COUNTERBALANCED BACK DRAFT DAMPERS ARE MOUNTED IN OUTSIDE WALLS.H. BACK DRAFT DAMPERS1. FURNISH AND INSTALL BACK DRAFT DAMPERS WHERE INDICATED ON THE DRAWINGS. EACH DAMPER SHALL BESIZED AS INDICATED ON THE DRAWINGS AND SHALL BE SUITABLE FOR INSTALLATION IN THE MOUNTINGARRANGEMENT SHOWN. BACK DRAFT DAMPERS MOUNTED IN ROOF CURBS SHALL BE SECURED TO GALVANIZEDSTEEL SUPPORT ANGLES FASTENED TO THE CURB.2. BACK DRAFT DAMPERS SHALL BE HEAVY RELIEF TYPE SUITABLE FOR WALL AND DUCT MOUNTING OR INSTALLATION
AT A FAN DISCHARGE. BACK DRAFT DAMPERS SHALL BE SIMILAR TO RUSKIN TYPE BD2-A1 FOR FACE VELOCITIESTO 1500 FPM AND RUSKIN TYPE BD2-A2 FOR FACE VELOCITIES TO 2500 FPM, OR LISTED MANUFACTURERAPPROVED EQUAL AS FOLLOWS:a. DAMPER FRAME SHALL BE CONSTRUCTED OF AT LEAST 0.090" THICK ALUMINUM OR AT LEAST 18 GAUGEGALVANIZED STEEL. DAMPER FRAME SHALL BE ON CHANNEL CONSTRUCTION WHEN INSTALLED IN DUCTWORK OR HAVE A FRONT FLANGE WHEN INSTALLED IN A WALL.b. DAMPER BLADES SHALL BE CONSTRUCTED OF AT LEAST 22 GAUGE EXTRUDED ALUMINUM SUITABLE FORFACE VELOCITIES UP TO 1500 FPM AND AT LEAST 16 GAUGE EXTRUDED ALUMINUM FOR FACE VELOCITIES TO2500 RPM. DAMPER BLADES SHALL HAVE NEOPRENE OR VINYL GASKETS RIVETED OR ROLLED INTO THEBLADE EDGE. EACH BACK DRAFT DAMPER SECTION SHALL BE FURNISHED WITH TIE BARS CONSTRUCTED OFAT LEAST 16 GAUGE ALUMINUM. FURNISH TWO TIE BARS ON DAMPER SECTIONS OVER 40 INCHES WIDE.c. DAMPER BEARING SHALL BE BRONZE OILITE, NYLON, OR CYCOLOY.d. FURNISH BACK DRAFT DAMPERS WITH 2 X 2 MESH ALUMINUM BIRD SCREEN FOR REAR MOUNTING WHEREBACK DRAFT DAMPERS ARE MOUNTED IN OUTSIDE WALLS.e. DAMPER LEAKAGE SHALL NOT EXCEED 12 CFM PER SQUARE FOOT IF DAMPER FACE AREA AT 0.5 INCHES W.G.DIFFERENTIAL.I. INSTALLATION1. GENERAL: INSTALL ALL MATERIALS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTALLATIONINSTRUCTIONS, APPLICABLE STANDARDS AND RECOGNIZED INDUSTRY PRACTICES.A. LOCATION COORDINATION: WHERE AIR DISTRIBUTION DEVICES ARE INSTALLED IN ACOUSTICAL TILE AND OTHERCEILINGS THEY SHALL BE EITHER CENTERED ON TILE OR CEILING JOINTS AS DIRECTED BY ARCHITECT AT JOBSITE.COORDINATE LOCATION OF ALL CEILING AIR DEVICES WITH ARCHITECTURAL REFLECTED CEILING PLANS.B. DAMPERS: ALL FIRE, MOTORIZED AND RADIATION DAMPERS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH ULLISTED INSTALLATION PROCEDURES PROVIDED BY MANUFACTURER.C. BALANCING DAMPERS: INSTALL BALANCING DAMPERS A MINIMUM OF THREE FEET (3') UPSTREAM OF SUPPLYDIFFUSERS SERVED AND THREE FEET (3') DOWNSTREAM OF RETURN/EXHAUST DIFFUSERS SERVED.1. TESTING: FIRE, FIRE/SMOKE, AND RADIATION DAMPER OPERATION SHALL BE TESTED AFTER INSTALLATION ISCOMPLETE. PROVIDE WRITTEN CERTIFICATION OF EACH DAMPER LOCATION, TYPE, SIZE AND DATE TESTED ASSPECIFIED IN SECTION 15010.2. ACCESS DOORS: PROVIDE ACCESS DOORS IN DUCT WORK AND BUILDING CONSTRUCTION FOR DAMPERS ASREQUIRED.
MEP1.0
MEP
MECHANICAL
SPECIFICATIONS
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
EP
1.0
_M
EP
ME
CH
AN
ICA
L S
PE
CIF
ICA
TIO
NS
.dw
g
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
GENERAL ELECTRICAL NOTES:A. BEFORE SUBMITTING A BID, IT WILL BE NECESSARY FOR EACH CONTRACTOR WHOSE WORK IS
INVOLVED TO VISIT THE SITE AND ASCERTAIN FOR HIMSELF THE CONDITIONS TO BE MET IN
INSTALLING THE WORK AND MAKE PROVISIONS FOR THE CONDITIONS IN HIS FINAL PRICE. FAILUREON THE PART OF THE CONTRACTOR TO COMPLY WITH THIS REQUIREMENT SHALL NOT BE
CONSIDERED JUSTIFICATION FOR THE OMISSION OR FAULTY INSTALLATION OF ANY WORK
COVERED BY THE CONTRACT DOCUMENTS.
B. THE CONTRACTOR SHALL SECURE ALL PERMITS, LICENSES AND INSPECTIONS REQUIRED FOR HIS
WORK, AND SHALL PAY ALL FEES IN CONNECTION WITH SUCH PERMITS, LICENSES AND
INSPECTIONS.
C. WORK SHALL COMPLY WITH THE MOST RECENT VERSION OF ALL APPLICABLE LAWS, RULES,
REGULATIONS AND ORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES. IN THE EVENT
OF CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE LOCAL ENFORCING AUTHORITY, THE
LATTER SHALL RULE. ANY MODIFICATION RESULTING THEREFROM SHALL BE MADE WITHOUTADDITIONAL COST TO THE OWNER OR ARCHITECT/ENGINEER. THE CONTRACTOR SHALL REPORT
ANY SUCH MODIFICATIONS TO THE ARCHITECT/ENGINEER AND SECURE HIS APPROVAL BEFORE
PROCEEDING. SHOULD THE REQUIREMENTS OF THE CONTRACT DOCUMENTS EXCEED THE
REQUIREMENTS OF THE CODES, THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE PROVIDEDTHEY ARE NOT IN CONFLICT WITH THOSE CODES.
D. ALL ITEMS OF EQUIPMENT AND ALL MATERIALS FOR WHICH APPROVAL STANDARDS HAVE BEEN
ESTABLISHED BY UNDERWRITERS' LABORATORIES, INC. (UL), FACTORY MUTUAL (FM), CERTIFIEDBALLAST MANUFACTURER (CBM), ELECTRICAL TESTING ASSOCIATION (NEMA) SHALL BE SO
APPROVED AND SHALL BEAR APPROVAL LABELS.SUBMITTALS AND SHOP DRAWINGSA. CONTRACTOR SHALL PROVIDE THE ENGINEER WITH PRODUCT DATA AND SHOP DRAWINGS FOR ALL MATERIALS &EQUIPMENT SPECIFIED BELOW. SUBMITTALS SHALL BE PROVIDED IN AN ELECTRONIC FORMAT. SUBMITTAL DATA SHALLINCLUDE:1. COVER SHEET WITH NAMES AND ADDRESSES OF PROJECT, ARCHITECT MEP ENGINEER, GENERAL CONTRACTOR & SUBCONTRACTOR.2. DRAWING REFERENCE NUMBER, PRODUCT NAME AND/OR DESCRIPTION.3. INDEX OF ALL DATA IN SUBMITTAL.4. DIMENSIONAL DATA AND SKETCHES SHOWING THAT SUBMITTED EQUIPMENT WILL FIT INTO SPACE AVAILABLE ANDWILL HAVE REQUIRED CODE AND MAINTENANCE CLEARANCES.5. IDENTIFICATION OF EACH ITEM MATCHING THAT INDICATED ON THE DRAWINGS.6. SUFFICIENT PERFORMANCE DATA, CAPACITY, SOUND DATA, DIAGRAMMATIC DATA AND DESCRIPTIVE INFORMATION TOSHOW ITS COMPLIANCE'S WITH THE CONTRACT DOCUMENTS. OPTIONS OR SPECIAL REQUIREMENTS SHALL BECLEARLY INDICATED. APPLICABLE INFORMATION SHALL BE CLEARLY INDICATED AND NON APPLICABLE DATA SHALL BECROSSED OFF.7. MATERIALS AND EQUIPMENT PURCHASED OR INSTALLED WITHOUT A "NO EXCEPTIONS TAKEN" SHOP DRAWINGREVIEW SHALL BE AT THE RISK OF THE CONTRACTOR. THE COST OF REMOVAL AND AT THE RISK OF THECONTRACTOR. THE COST OF REMOVAL AND REPLACEMENT OF SUCH MATERIALS WHICH IS JUDGEDUN-SATISFACTORY BY THE ENGINEER FOR ANY REASON SHALL BE AT THE EXPENSE OF THE CONTRACTOR.8. ANY ITEMS KNOWINGLY SUBMITTED THAT DO NOT COMPLY WITH SPECIFICATIONS SHALL BE LISTED WITHEXPLANATION AS TO WHY THEY ARE BEING SUBMITTED.B. REQUIRED SUBMITTALS / SHOP DRAWINGS:1. WIRING DEVICES2. CONDUIT3. LIGHTING FIXTURES
CONDUITA. ALL CONDUITS SHALL BE CONCEALED IN PIPE CHASES, WALLS, FURRED SPACED, OR ABOVE THE
CEILING OF THE BUILDING UNLESS OTHERWISE INDICATED. CONDUIT SHALL NOT BE EMBEDDED IN
ANY STRUCTURAL SLAB OR STRUCTURAL MEMBER UNLESS APPROVED IN WRITING BY THESTRUCTURAL ENGINEER.
B. CONDUIT MAY BE RUN EXPOSED IN MECHANICAL ROOMS, DUCT AND PIPING CHASES, BUT ONLY
WHERE NECESSARY. ALL EXPOSED CONDUIT SHALL BE RUN IN THE NEATEST, MOSTINCONSPICUOUS MANNER, AND PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
C. ALL CONDUIT AND SURFACE RACEWAYS SHALL BE ADEQUATELY AND PROPERLY SUPPORTED FROM
THE BUILDING STRUCTURE BY MEANS RECOMMENDED BY THE MANUFACTURER, OR BY THE USE OFHANGER RODS OR CLAMPS.
D. ALL CONDUITS THROUGHOUT THE BUILDING SHALL BE SUPPORTED 8 FEET ON CENTERS
HORIZONTALLY AND SUPPORTED 6 FEET ON CENTERS VERTICALLY.
E. VERTICAL CONDUITS SHALL BE SUPPORTED FROM FLOOR LINES WITH RISER CLAMPS SIZED TO FIT
THE CONDUIT AND TO ADEQUATELY ALLOW FOR CONTRACTION. AT THE BASES OF CONDUIT.
WHERE REQUIRED FOR PROPER SUPPORT, PROVIDE ANCHOR BASE FITTINGS OR OTHER APPROVEDSUPPORTS.
F. CONDUIT SHALL NOT BE SUPPORTED FROM DUCTWORK, PIPING, OR EQUIPMENT.
G. THE LOAD AND SPACING ON EACH HANGER AND/OR INSERT SHALL NOT EXCEED THE SAFE
ALLOWABLE LOAD FOR ANY COMPONENT OF THE SUPPORT SYSTEM, INCLUDING THE CONCRETE
WHICH HOLDS THE INSERTS. REINFORCEMENT AT INSERTS SHALL BE PROVIDED AS REQUIRED TO
DEVELOP THE STRENGTH REQUIRED.
H. ALL CONDUITS NOT EMBEDDED IN CONCRETE OR MASONRY SHALL BE SECURELY AND
INDEPENDENTLY SUPPORTED SO THAT NO STRAIN WILL BE TRANSMITTED TO OUTLET BOX AND
PULL BOX SUPPORTS, ETC. SUPPORTS SHALL BE RIGID ENOUGH TO PREVENT DISTORTION OFCONDUITS DURING WIRE PULLING.
I. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN CONDUIT, OR SURFACE METAL RACEWAYS.
J. RIGID STEEL CONDUIT SHALL BE USED WHERE CONDUIT IS UNDERGROUND, IN A CONCRETE SLAB
WITH A VAPOR BARRIER, EXPOSED TO THE WEATHER, IN DAMP OR OTHER WET LOCATIONS, WHERE
EXPOSED TO VIEW, WHERE SUBJECT TO PHYSICAL DAMAGE, OR IN SIZES GREATER THAN 4" INDIAMETER.
K. CONDUIT SHALL BE JOINED WITH THREADED COUPLINGS AND SHALL BE SECURED IN CABINETS,
OUTLETS, ETC., WITH DOUBLE LOCKNUTS AND SHALL BE PROVIDED WITH INSULATED BUSHINGS AS
MANUFACTURED BY MIDWEST, STEEL CITY, OR EFCOR. COUPLINGS, ETC., SHALL BE THREADED.
L. RIGID STEEL CONDUIT SHALL BE HOT DIPPED GALVANIZED INSIDE AND OUT. FULL LENGTHS OF PIPE
SHALL HAVE GALVANIZED OR ZINC- COATED THREADS ON BOTH ENDS.
M. RIGID STEEL CONDUIT SHALL BE PITTSBURGH STANDARD, REPUBLIC, ALLIED, TRIANGLE, ROME,
SPANG, WESTERN, WHEATLAND, WESTERN TUBE AND CONDUIT, OR YOUNGSTOWN HOT DIPPED
GALVANIZED INSIDE AND OUT, NATIONAL "SHERADUCT", WALKER "DUALCOTE", OR GENERAL
ELECTRIC (J&L) "WHITE" ZINC METALLIZED INSIDE AND OUT, OR APPROVED EQUAL.
N. EMT MAY BE USED INDOORS WHERE CONCEALED OR EXPOSED ABOVE GRADE, EXCEPT WHERE
RIGID STEEL CONDUIT IS REQUIRED. ELECTRICAL METALLIC TUBING SHALL BE MADE OF THIN-WALL
STEEL TUBING SHALL BE MADE OF THIN-WALL STEEL TUBING UP TO 4" CONDUIT SIZE, AND SHALL BEGALVANIZED INSIDE AND OUTSIDE.
O. EMT SHALL BE JOINED WITH STEEL SET SCREW TYPE COUPLINGS AND CONDUITS SHALL BE
SECURED WITH STEEL SET SCREW TYPE CONNECTORS AT PANELS, JUNCTION BOXES, OUTLETS,ETC. EMT WHICH IS CAST IN CONCRETE SHALL BE JOINED USING CONCRETE TIGHT COMPRESSION
FITTINGS. DIE CAST TYPE CONNECTORS ARE NOT ACCEPTABLE.
P. IF IT COMPLIES WITH THESE SPECIFICATIONS, CONDUIT AND CONNECTORS MANUFACTURED BY ONEOF THE FOLLOWING WILL BE ACCEPTABLE: AFC CABLE SYSTEMS, ALLIED, ANAMET, CALCONDUIT,
ELECTRI-FLEX, FSR, O-Z/GEDNEY, PLASTI-BOND.
Q. METAL CONDUIT SHALL BE OF AMPLE SIZE TO PERMIT THE EASY INSERTION OR WITHDRAWAL OFCONDUCTORS WITHOUT ABRASION. ALL JOINTS SHALL BE CUT SQUARE, REAMED SMOOTH AND
DRAWN UP TIGHT. NO NON-FLEXIBLE METAL CONDUIT SHALL BE SMALLER THAN 1/2"C.
R. SO FAR AS PRACTICABLE, ALL EXPOSED METAL CONDUIT SHALL RUN WITHOUT TRAPS. WHERETRAPS OR DIPS ARE UNAVOIDABLE, A JUNCTION OR PULL BOX SHALL BE PLACED AT EACH LOW
POINT.
S. EACH ENTIRE METAL CONDUIT SYSTEM SHALL BE INSTALLED COMPLETE BEFORE ANYCONDUCTORS ARE DRAWN IN. TO GUARD AGAINST OBSTRUCTIONS AND OMISSIONS, EACH RUN OF
CONDUIT SHALL BE FINISHED BEFORE PLASTERING IS INSTALLED. ALL METAL CONDUIT SHALL BE
SWABBED AFTER PLASTER IS FINISHED AND DRY.
T. AS SOON AS CONDUIT HAS BEEN PERMANENTLY INSTALLED IN PLACE, CONDUIT SHALL BE CAPPED
OR PLUGGED WITH STANDARD ACCESSORIES.
U. CONDUITS USED FOR DATA, PHONE AND PULLSTRINGS SHALL TERMINATE WITH PLASTIC GROMMETINSERTS SO THAT THE CABLE IS NOT DAMAGED BY THE OPEN END OF THE CONDUIT.
V. ALL CONDUITS IN WALLS SHALL BE RUN VERTICALLY. HORIZONTAL RUNS IN WALLS ARE NOT
ACCEPTABLE EXCEPT FOR RECEPTACLES UNDER WINDOWS.FLEXIBLE METAL CONDUITA. FLEXIBLE METAL CONDUIT SHALL BE HOT DIPPED GALVANIZED STEEL STRIP, SPIRAL WOUND AND
INTERLOCKED, AND SHALL BE PROVIDED WITH INSULATED ANTI SHORT BUSHINGS AT ALLTERMINATIONS.
B. FLEXIBLE METAL CONDUIT SHALL BE SECURED WITH GALVANIZED CONNECTORS SUITABLE FOR
CONNECTION TO THE ASSOCIATED BOXES AND CONDUITS. DIE CAST CONNECTORS ARE NOTACCEPTABLE
C. FLEXIBLE METAL CONDUIT AND LIQUID TIGHT FLEXIBLE METAL CONDUIT SHALL BE SECURED NO
LESS THAN EVERY 54" AND WITHIN 12" OF A JUNCTION BOX. IT IS NOT ACCEPTABLE TO LAY CABLESON CEILING, DUCTWORK, ETC.
D. CONTINUITY OF THE EQUIPMENT GROUND ACROSS FLEXIBLE METAL CONDUIT CONNECTIONS SHALL
BE MAINTAINED FOR ALL SYSTEMS THAT ARE OVER 150 VOLTS TO GROUND. THE CONTINUITY SHALLBE MAINTAINED BY INSTALLING A BARE COPPER BONDING CONDUCTOR SIZED IN ACCORDANCE
WITH TABLE 250-122 OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. THE BARE
COPPER BONDING CONDUCTOR SHALL BE INSTALLED OUTSIDE THE FLEXIBLE CONDUIT AND SHALL
BE CONNECTED ON ONE END OF THE FLEXIBLE CONDUIT BY A SUITABLE BINDING POST ANSIMILARLY CONNECTED ON THE OPPOSITE END WITH ANOTHER SUITABLE BINDING POST.
E. IF IT COMPLIES WITH THESE SPECIFICATIONS, CONDUIT AND CONNECTORS MANUFACTURED BY ONE
OF THE FOLLOWING WILL BE ACCEPTABLE: AFC CABLE SYSTEMS, ALLIED, ANAMET, CALCONDUIT,ELECTRI-FLEX, FSR, O-Z/GEDNEY, PLASTI-BOND.
TYPE "MC" METAL-CLAD CABLEA. METAL-CLAD CABLE "MC" USED FOR CONNECTION OF FIXTURE-TAILS, SWITCH LEGS, AND RECEPTACLES ON "NORMAL"POWER CIRCUITS (NON-EMERGENCY) SHALL BE HOSPITAL GRADE 3-WIRE TYPE WITH 2-#12 "THWN" SOLID COPPERINSULATED PHASE CONDUCTORS, ONE #12 SOLID COPPER INSULATED GROUND CONDUCTOR, AND A BARE BONDINGCONNECTOR. IF ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, TYPE "MC" CABLE MAY BE USED IN WALLPARTITIONS IN FINISHED AREAS ONLY. THE USE OF TYPE "MC" CABLE ON TYPE 1 ESSENTIAL ELECTRICAL SYSTEMS,EXCEPT AS ALLOWED BY THE NATIONAL ELECTRICAL CODE, SECTION 517-30 (C) IS STRICTLY PROHIBITED.B. WHERE PERMITTED BY THE LOCAL AUTHORITY - METAL-CLAD CABLE MAY BE USED INDOORS WHERE CONCEALED ABOVEGRADE, FOR FIXTURE-TAILS OF INDIVIDUAL LIGHTING FIXTURES IN SUSPENDED ACCESSIBLE TYPE CEILINGS. THESEFIXTURE-TAILS SHALL IN LENGTHS NOT TO EXCEED 6 FEET FOR CONNECTION TO THEIR ASSOCIATED LIGHTING JUNCTIONBOXES. THE POINT OF CONNECTION OF THE METAL-CLAD CABLE TO THE INDIVIDUAL LIGHTING FIXTURES SHALL NOT BEMORE THAN 3" FROM THE FIXTURE BALLASTS.C. WHERE PERMITTED BY THE AUTHORITY HAVING JURISDICTION - METAL-CLAD CABLE MAY BE USED INDOORS FORINDIVIDUAL DROPS TO OUTLETS AND SWITCHES, WHERE CONCEALED IN EXISTING WALLS AND PARTITIONS - PROVIDEDTHE FOLLOWING CONDITIONS ARE MET:1. THE CIRCUIT PROVIDING THE POWER FOR THE SWITCH OR OUTLET IS NOT FED FROM THE ESSENTIAL POWER SYSTEM(EXCEPT AS ALLOWED BY THE NATIONAL ELECTRICAL CODE, SECTION 517-30(C)).2. THE BRANCH CIRCUIT HOMERUN WIRING IS INSTALLED IN THE ACCESSIBLE CEILING PLENUM USING METAL CONDUIT.3. JUNCTION BOXES ARE LOCATED IN THE ACCESSIBLE CEILING PLENUM ADJACENT TO THE ASSOCIATED WALLS ORPARTITIONS IN WHICH OUTLETS OR SWITCH LEGS ARE INSTALLED.4. LENGTH OF ARMORED CABLE DROP IS NOT GREATER THAN 12' -0".5. METAL-CLAD CABLE SHALL NOT BE USED FOR HOMERUN WIRING. HOMERUNS SHALL BE HARD PIPED WITH THE USE OFMETAL CONDUIT.D. METAL-CLAD CABLE SHALL BE PROVIDED WITH INSULATED ANTI-SHORT BUSHINGS AT ALL TERMINATIONS. METAL-CLADCABLE CONNECTORS SHALL BE STEEL GALVANIZED OR, SUITABLE FOR CONNECTION TO ASSOCIATED BOXES. DIE CASTCONNECTORS ARE NOT ACCEPTABLE.E. METAL-CLAD CABLE SHALL BE SECURED NO LESS THAN EVERY 54" AND WITHIN 12" OF A JUNCTION BOX. IT IS NOTACCEPTABLE TO LAY CABLES ON CEILING, DUCTWORK, ETC.F. IF IT COMPLIES WITH THE SPECIFICATIONS, METAL-CLAD CABLE MANUFACTURED BY ONE OF THE FOLLOWING WILL BEACCEPTABLE: AMERICAN FLEXIBLE CONDUIT, BRAND-REX, OR CABLEC.G. IF IT COMPLIES WITH THE SPECIFICATIONS, CONNECTORS MANUFACTURED BY ON OF THE FOLLOWING WILL BEACCEPTABLE: STEEL CITY, THOMAS & BETTS, OR MIDWEST.OUTLET BOXESA. REFER TO THE ARCHITECT AND VENDOR'S DRAWINGS FOR EXACT MOUNTING HEIGHT AND
LOCATION OF ALL ELECTRICAL/TELEPHONE/DATA DEVICES.
B. ALL METAL OUTLETS AND JUNCTION BOXES, EXCEPT WHERE OTHERWISE SPECIFIED, SHALL BE OF
ONE PIECE CONSTRUCTION, AND SHALL BE PROTECTED AGAINST CORROSION BY AN APPROPRIATE
GALVANIZING PROCESS.
C. ALL JUNCTION BOXES SHALL BE PROVIDED WITH COVERS OF THE SAME MANUFACTURER AS THE
BOXES. THE TYPE OF COVER SELECTED SHALL MEET THE CONDITIONS IMPOSED IN EVERY CASE.
ALL SUCH BOXES SHALL BE LEFT IN A NEAT, CLEAN AND WORKMANLIKE MANNER.
D. THE OUTLET BOXES SHALL BE SECURELY ATTACHED TO THE PARTITION STUDS. IT IS NOT
ACCEPTABLE TO SECURE OUTLET BOXES ONLY TO DRYWALL PARTITION. SECURE ONE SIDE OF THE
BOX TO WALL STUD. THE OTHER SIDE OF EACH BOX SHALL BE SUPPORTED WITH A BRACKET EQUAL
TO THE INSIDE DIMENSION OF THE WALL STUD SO WHEN BOTH SIDES OF THE GYP BOARD HAVEBEEN INSTALLED, THE BOX DOES NOT MOVE. PROVIDE APPROPRIATE SUPPORTING DEVICES FOR
OUTLET BOXES BY CADDY FASTENERS OR EQUAL AS FOLLOWS:
1. "RB" BOX MOUNTING BRACKETS.2. SCREW GUN MOUNTING BRACKETS.
3. "H" BOX MOUNTING BRACKETS.
E. OUTLET, SWITCH AND JUNCTION BOXES FOR VARIOUS USES SHALL BE AS MANUFACTURED BYCROUSE-HINDS, FSR, HOFFMAN, HUBBELL, MONOSYSTEMS, O-Z/GEDNEY, PLASTI-BOND, OR AN
APPROVED EQUAL.CONDUCTORSA. ALL CONDUCTORS FURNISHED AND INSTALLED SHALL COMPLY WITH THE REQUIREMENTS AND
LATEST REVISIONS OF THE NATIONAL ELECTRICAL CODE (NEC), NATIONAL ELECTRICAL SAFETY
CODE (NESC), STANDARDS OF THE UNDERWRITER'S LABORATORIES (UL), NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION (NEMA), INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS(IEEE).
B. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SOFT DRAWN, ANNEALED COPPER,HAVING A CONDUCTIVITY OF NOT LESS THAN 98% OF THAT OF PURE COPPER, AND MEETING
BEFORE STRANDING, THE REQUIREMENTS OF ASTM B-3, "STANDARD SPECIFICATIONS FOR SOFT OR
ANNEALED COPPER WIRE FOR ELECTRICAL PURPOSES", LATEST EDITION.
C. UNLESS OTHERWISE SPECIFIED OR NOTED, ALL CONDUCTORS NO. 10 AND SMALLER SHALL BE
SOLID COPPER THWN WITH AN INSULATING OUTER JACKET SUITABLE FOR CONDUCTOR
TEMPERATURES OF 75°C, EXCEPT FOR NEC CLASS 1, 2, 3, CONDUCTORS WHICH MAYBE STRANDED
IF TERMINATED AS REQUIRED HEREIN.
D. UNLESS OTHERWISE SPECIFIED OR NOTED, ALL CONDUCTORS NO. 8 AND LARGER SHALL BE
THWN/THHN, 600 VOLT, STRANDED WITH A THERMOPLASTIC INSULATING COMPOUND AND AN OUTER
JACKET (THWN/THHN ONLY) SUITABLE FOR CONDUCTOR TEMPERATURES OF 75°C. OR 90°C.,INCLUSIVE. STRANDED WIRE SHALL BE TERMINATED AS SPECIFIED HEREIN.
E. IN THE CEILING AREAS OF EQUIPMENT ROOMS WHERE THE TEMPERATURE MAY EXCEED 102°F.UNDER OPERATING CONDITIONS, HIGHER TEMPERATURE INSULATION SHALL BE USED ONCONDUCTORS. ACCEPTABLE TYPES ARE RHH, THHN, AND XHHW.
F. IF IT COMPLIES WITH THESE SPECIFICATIONS, THE FOLLOWING CONDUCTOR MANUFACTURERS WILL
BE ACCEPTABLE: ALPHA WIRE COMPANY, AMERICAN BARE CONDUCTOR, BELDEN INC., ENCOREWIRE CORPORATION, GENERAL CABLE TECHNOLOGIES CORPORATION, SERVICE WIRE CO.,
SOUTHWIRE COMPANY, WESCO.
G. IF IT COMPLIES WITH THESE SPECIFICATIONS, CABLE LUGS AND TERMINATION FITTINGSMANUFACTURED BY ONE OF THE FOLLOWING WILL BE ACCEPTABLE: BLACKBURN, BURNDY, IDEAL,
ILSCO, KEARNEY, MAC, THOMAS & BETTS, SQUARE D, AMP.
H. NO SPLICES OR TAPS SHALL BE MADE IN ANY CONDUCTOR EXCEPT IN OUTLET BOXES, JUNCTIONBOXES, SPLICE BOXES, OR OTHER DEVICES AND EQUIPMENT IN EXPOSED AND ACCESSIBLE
LOCATIONS APPROVED FOR THE PURPOSE BY THE LATEST EDITION OF THE NEC.
I. ALL NO. 10 AWG AND SMALLER SOLID CONDUCTORS SHALL BE SPLICED WITH PRE-INSULATEDSPRING CONNECTORS. ALL NO. 10 AWG AND SMALLER STRANDED CONDUCTORS FOR NEC CLASS 1,
2, 3 WIRING SHALL BE TERMINATED WITH AMP 'PIDG' UL LISTED PREMIUM GRADE INSULATED FORK
CONNECTORS, OR APPROVED EQUAL, AND SHALL BE SPLICES IN A JUNCTION BOX WITH AMP
"PLASTIC-GRIP" UL LISTED STANDARD GRADE INSULATED BUTT SPLICES, OR APPROVED EQUAL.
J. ALL NO. 8 AWG AND LARGER COPPER CONDUCTORS SHALL BE CONNECTED WITH HIGH
CONDUCTIVITY, WROUGHT COPPER, COLOR KEYED COMPRESSION CONNECTORS. COMPRESSION
CONNECTORS FOR ALL FEEDERS SHALL BE THOMAS & BETTS SERIES 54200, OR EQUAL, TWO- HOLECONNECTORS.
K. ALL NO. 8 AWG AND LARGER COPPER CONDUCTORS WHICH ARE TO BE SPLICED OR TAPPED IN
WIREWAYS, GUTTERS, OR JUNCTION BOXES SHALL BE SLICED OR TAPPED USING HYDRAULICALLYAPPLIED, HIGH CONDUCTIVITY COMPRESSION CONNECTOR, T & B 54700, AND 3-M ELECTRICAL TAPE
OR MANUFACTURED CONNECTOR COVERS APPROVED FOR THE PURPOSE.
GROUNDINGA. THE ELECTRICAL DISTRIBUTION SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250
OF THE NATIONAL ELECTRICAL CODE (NEC), AS SHOWN AND SPECIFIED, AND RECOGNIZED
INDUSTRY PRACTICES TO ENSURE THAT PRODUCTS SERVE THE INTENDED FUNCTIONS.WIRING DEVICESA. DUPLEX RECEPTACLES SHALL BE LEVITON #16252-I, 20AMP, 125V., 3W. DECORATOR STYLE, ''SPECIFICATION GRADE", SIDEWIRED WITH MATCHING COVER PLATE UNLESS OTHERWISE INDICATED. LIGHTING WALL SWITCHES SHALL BE LEVITON#5621 OR #5623 WITH MATCHING COVER PLATES. MOTION SWITCHES SHALL BE LEVITON #6768 WITH MATCHING COVERPLATES. THE COLOR OF PLATES AND WIRING DEVICES SHALL BE AS SELECTED BY ARCHITECT. GFI RECEPTACLES SHALLBE LEVITON #6898-HG. 20A., 125V., 3W. PROVIDE WEATHERPROOF ENCLOSURE FOR RECEPTACLES MOUNTED OUTSIDE.LIGHTINGA. LUMINAIRE TYPES AND LAMPING SHALL BE AS LISTED ON THE DRAWINGS. REFER TO LIGHT FIXTURE SCHEDULE FORADDITIONAL NOTES AND REQUIREMENTS.B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIEDTESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.C. NRTL COMPLIANCE: LUMINAIRES FOR HAZARDOUS LOCATIONS SHALL BE LISTED AND LABELED FOR INDICATED CLASS ANDDIVISION OF HAZARD BY AN NRTL.D. FM GLOBAL COMPLIANCE: LUMINAIRES FOR HAZARDOUS LOCATIONS SHALL BE LISTED AND LABELED FOR INDICATEDCLASS AND DIVISION OF HAZARD BY FM GLOBAL.E. UL COMPLIANCE: COMPLY WITH UL 1598. EMERGENCY EGRESS LIGHTING COMPONENTS SHALL COMPLY WITH UL 924.F. LAMP BASE COMPLYING WITH ANSI C81.61 OR IEC 60061-1.G. NOMINAL OPERATING VOLTAGE: 12 V DC, 24 V DC, 120 V AC, 240 V AC, 277 V AC, OR 480 V AC; PER DRAWINGS.H. RECESSED LUMINAIRES: COMPLY WITH NEMA LE 4.FIRE ALARM FUNCTIONA. THE ALARM OPERATING SEQUENCE FOR THIS SYSTEM IS AS FOLLOWS:
1. ACTIVATION OF ANY AUTOMATIC DETECTOR (HEAT, CEILING OR DUCT SMOKE), MANUAL STATIONOR SPRINKLER WATER FLOW SWITCH WILL:
a. ACTIVATE THE SYSTEM FIRE ALARM AUDIBLE SIGNAL AND ILLUMINATE THE ALARM LED ATTHE CONTROL PANEL. THE FIRE ALARM ACKNOWLEDGE KEY WILL SILENCE THE LOCAL
AUDIBLE SIGNAL.
b. CAUSE THE ZONE OF ALARM TO BE IDENTIFIED WITH A CUSTOM ENGLISH LANGUAGE LABEL
AT THE FIRE ALARM CONTROL PANEL.c. ACTIVATE THE AUDIBLE AND VISUAL ALARM SIGNALS SELECTIVELY IN THE ENTIRE FACILITY.
d. SHUTDOWN THE AIR HANDLING UNIT(S) SERVING THE ZONE OF ALARM.
e. ANY SUBSEQUENT ALARM FROM ANOTHER DEVICE LISTED ABOVE WILL REACTIVATE ANY
SILENCED ALARM INDICATING APPLIANCES AND ACTIVATE THE RESPECTIVE CONTROLSEQUENCES DESCRIBED ABOVE.
f. UPON RESET OF THE FIRE ALARM CONTROL PANEL, AIR HANDLING UNIT(S) WILL
SEQUENTIALLY START UP AT TIME INTERVALS.
B. VALVE SUPERVISION
1. THE OPERATING SEQUENCE FOR STANDPIPE ZONE VALVE ANNUNCIATION FOR THIS SYSTEM IS
AS FOLLOWS:
a. ACTIVATE THE SYSTEM SUPERVISORY SERVICE AUDIBLE SIGNAL AND ILLUMINATE THE LED
AT THE CONTROL PANEL.
b. THE SUPERVISORY SERVICE ACKNOWLEDGE KEY WILL SILENCE THE LOCAL AUDIBLESIGNAL.
c. CAUSE THE ZONE OF ALARM TO BE IDENTIFIED WITH A CUSTOM ENGLISH LANGUAGE LABEL
AT THE FIRE ALARM CONTROL PANEL.
d. DIFFERENTIATION BETWEEN VALVE TAMPER AND OPENS AND OR GROUNDS ON THEINITIATING CIRCUIT WIRING IS PROVIDED BY THE LATTER BEING REPORTED AS TROUBLES.
e. ACTIVATION OF A ZONE VALVE SUPERVISORY SWITCH WILL NOT PREVENT THE ALARM
EVENTS LISTED ABOVE FROM OCCURRING.
f. RESTORING THE VALVE TO THE NORMAL POSITION WILL CAUSE THE SUPERVISORYSERVICE AUDIBLE SIGNAL TO PULSE INDICATING THE RESTORATION TO NORMAL POSITION.
THE SUPERVISORY SERVICE ACKNOWLEDGE KEY WILL SILENCE THE AUDIBLE SIGNAL.
C. DEVICE LOCATIONS
1. REFER TO ELECTRICAL LIGHTING PLAN AND MECHANICAL FLOOR PLAN FOR PROPOSED DEVICE
LOCATIONS. FINAL DEVICE LOCATIONS SHALL BE BY LICENSED FIRE ALARM ENGINEER.
MEP1.1
MEP
ELECTRICAL
SPECIFICATIONS
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
EP
1.1
_M
EP
ELE
CT
RIC
AL S
PE
CIF
ICA
TIO
NS
.dw
g
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
BASIC REQUIREMENTSCODES AND STANDARDS:A. ALL WORK SHALL COMPLY WITH THE MOST RECENTLY REVISED VERSIONS OF ALL APPLICABLE LAWS, RULES, REGULATIONS AND ORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES AND APPLICABLE UTILITIES. NONE OF THE TERMS OR PROVISIONS OF THIS SPECIFICATION SHALL BECONSTRUED AS WAIVING ANY PART OF THE RULES, REGULATIONS OR REQUIREMENTS OF THESEAUTHORITIES.DRAWINGS AND SPECIFICATIONSA. DRAWINGS: THE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE APPROXIMATE LOCATIONS OF THE HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS, FIRE PROTECTION SYSTEMS, PLUMBINGEQUIPMENT, FIXTURES AND PIPING SYSTEMS, EXCEPT WHERE SPECIFIC LOCATIONS ARE NOTED ANDDIMENSIONED ON THE DRAWINGS. ALL ITEMS ARE SHOWN APPROXIMATELY TO SCALE. THE INTENT IS TOSHOW HOW THESE ITEMS SHALL BE INTEGRATED INTO THE CONSTRUCTION. LOCATE ALL ITEMS BY ON THEJOB MEASUREMENTS AND IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. COORDINATE WITH OTHERTRADES.COMPLETENESS OF WORKA. THE CONTRACT DOCUMENTS DEPICT MECHANICAL AND PLUMBING SYSTEMS WHICH ARE INTENDED TO BECOMPLETE AND FUNCTIONING SYSTEMS. ALL PRODUCTS, MATERIALS, AND LABOR NECESSARY TO RENDERA FULLY FUNCTIONAL SYSTEM TO FULFILL THE DESIGN INTENT SHOWN ON THE DOCUMENTS SHALL BEPROVIDED BY THE CONTRACTOR.B. CATALOG NUMBERS REFERENCED THROUGHOUT THE DIVISION 15 DRAWINGS AND SPECIFICATIONS AREINTENDED TO CONVEY A GENERAL UNDERSTANDING OF THE TYPE AND QUALITY OF THE PRODUCTREQUIRED. WHERE WRITTEN DESCRIPTIONS DIFFER FROM INFORMATION CONVEYED BY A CATALOGNUMBER, THE WRITTEN DESCRIPTION SHALL GOVERN. NO EXTRA SHALL BE ALLOWED BECAUSE ACATALOG NUMBER IS FOUND TO BE INCOMPLETE OR OBSOLETE.COORDINATIONA. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL ITEMS THAT WILL AFFECT THEINSTALLATION OF THE WORK OF THIS DIVISION. THE COORDINATION SHALL INCLUDE, BUT NOT BE LIMITEDTO, VOLTAGE, AMPACITY, CAPACITY, ELECTRICAL/PIPING CONNECTIONS, STRUCTURAL SUPPORTS, SPACEREQUIREMENTS, LOCATING DEVICES IN ARCHITECTURAL FINISH ELEMENTS, STAGING THE CONSTRUCTIONAND BUILDING REQUIREMENTS, AND SPECIAL CONDITIONS.B. BY SUBMITTING SHOP DRAWINGS ON THE PROJECT, THIS CONTRACTOR IS INDICATING THAT ALLNECESSARY COORDINATION HAS BEEN COMPLETED AND THAT THE SYSTEMS, PRODUCTS AND EQUIPMENT SUBMITTED CAN BE INSTALLED IN THE BUILDING AND WILL OPERATE AS SPECIFIED ANDINTENDED, IN FULL COORDINATION WITH ALL OTHER DISCIPLINES.EQUIPMENT NOISE AND VIBRATIONA. IT IS THE INTENT TO SPECIFY AND FOR THE CONTRACTOR TO INSTALL SYSTEMS THAT ARE QUIET AND FREEOF VIBRATION. EQUIPMENT SHALL BE BALANCED AND VIBRATION ISOLATED TO MEET THE REQUIREMENTSSPECIFIED HEREIN FOR BOTH THE EQUIPMENT ITSELF AND CONDITIONS WITHIN OCCUPIED SPACES. THISCONTRACTOR IS RESPONSIBLE FOR OBTAINING AND INSTALLING EQUIPMENT THAT IS QUIET IN OPERATIONAS COMPARED TO OTHER AVAILABLE EQUIPMENT OF ITS SIZE, CAPACITY, AND TYPE.B. EQUIPMENT NOT MEETING THESE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR TO ANACCEPTABLE LEVEL BUT WITHIN THE REQUIREMENTS OF THE SPECIFICATIONS AT NO COST TO THE OWNER,ARCHITECT OR ENGINEER.C. AIR DISTRIBUTION EQUIPMENT SHALL BE SOUND TESTED AT THE DESIGN OPERATING CONDITIONS ANDSHALL NOT EXCEED AN NC OF 35 AT RATED CFM.D. NOISE LEVEL: UNLESS NOTED OTHERWISE HEREIN OR ON THE DRAWINGS, THE NOISE LEVEL IN ALLOCCUPIED SPACES SHALL NOT EXCEED THE "LOWEST VALUE IN THE RANGE" OF THE NOISE CRITERIACURVES PUBLISHED IN THE CURRENT FUNDAMENTALS EDITION OF THE ASHRAE GUIDE AND DATA BOOK.THE NOISE CRITERIA CURVES SHALL BE BASED ON ANSI STANDARD S1.6-1967 OCTAVE BANDS AND A SOUNDPRESSURE LEVEL IN DECIBELS REFERENCED TO 0.002 MICROBARS. SOUND LEVELS IN OCCUPIED SPACESMUST MEET THE DESIGN CRITERIA WITH ALL CONSTRUCTION IN PLACE.E. VERIFICATION: SHOULD A QUESTION ARISE REGARDING THE ACCEPTABLE LEVEL OF NOISE OR VIBRATION IN A PARTICULAR SPACE OR PIECE OF EQUIPMENT, THE CONTRACTOR SHALL BE RESPONSIBLE FORPROVIDING THE SERVICES OF AN APPROVED ACOUSTICAL CONSULTANT TO DETERMINE ACTUALNOISE/VIBRATION CONDITIONS.WARRANTIES AND GUARANTEESA. GENERAL: CONTRACTOR SHALL GUARANTEE ALL MATERIAL AND EQUIPMENT INSTALLED BY HIM AGAINSTDEFECTS IN WORKMANSHIP AND MATERIAL FOR A PERIOD OF TWELVE (12) MONTHS AFTER FINALACCEPTANCE OF THE WORK BY THE OWNER, AND HE SHALL REPAIR OR REPLACE ANY MATERIALS OR EQUIPMENT DEVELOPING SUCH DEFECTS WITHIN THAT TIME, PROMPTLY ON DUE NOTICE GIVEN HIM BY THEOWNER AND AT CONTRACTOR'S SOLE COST AND EXPENSE.B. EQUIPMENT: ALL EQUIPMENT BEARING A MANUFACTURER'S GUARANTEE SHALL BE CONSTRUED TO HAVEAN EXTENDED GUARANTEE TO THE OWNER BY THE MANUFACTURER. ANY SUCH EQUIPMENT THAT PROVESDEFECTIVE IN MATERIALS OR WORKMANSHIP WITHIN THE GUARANTEE PERIOD IS TO BE REPLACED BY THECONTRACTOR IN ACCORDANCE WITH THE MANUFACTURER'S GUARANTEE.BASE BUILDING STANDARDSA. THE INTENT OF THIS SPECIFICATION IS TO PROVIDE A LEVEL OF QUALITY THAT MEETS OR EXCEEDSAPPLICABLE CODES AND OWNERS EXPECTATIONS. IF ANY PORTION OF THESE SPECIFICATIONS AREDIFFERENT THAT THE BUILDING STANDARDS, THIS SHOULD BE BROUGHT TO THE ENGINEER'S ATTENTION IMMEDIATELY TO DETERMINE WHICH IS THE CORRECT SPECIFICATION. ANY CHANGE WILL NOT BECONSIDERED A CHANGE ORDER AS THE CONTRACTOR SHOULD BID ON THE MOST STRINGENT OF THE TWOGENERAL PLUMBING NOTES:A. BEFORE SUBMITTING A BID, IT WILL BE NECESSARY FOR EACH CONTRACTOR WHOSE WORK IS INVOLVED TOVISIT THE SITE AND ASCERTAIN FOR HIMSELF THE CONDITIONS TO BE MET IN INSTALLING THE WORK ANDMAKE PROVISIONS FOR THE CONDITIONS IN HIS FINAL PRICE. FAILURE ON THE PART OF THE CONTRACTORTO COMPLY WITH THIS REQUIREMENT SHALL NOT BE CONSIDERED JUSTIFICATION FOR THE OMISSION ORFAULTY INSTALLATION OF ANY WORK COVERED BY THE CONTRACT DOCUMENTS.B. THIS CONTRACTOR SHALL SECURE ALL PERMITS, LICENSES AND INSPECTIONS REQUIRED FOR HIS WORK,AND SHALL PAY ALL FEES IN CONNECTION WITH SUCH PERMITS, LICENSES AND INSPECTIONS.C. WORK SHALL COMPLY WITH THE MOST RECENT VERSION OF ALL APPLICABLE LAWS, RULES, REGULATIONSAND ORDINANCES OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES. IN THE EVENT OF CONFLICTBETWEEN THE CONTRACT DOCUMENTS AND THE LOCAL ENFORCING AUTHORITY, THE LATTER SHALL RULE.ANY MODIFICATION RESULTING THEREFROM SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNEROR ARCHITECT/ENGINEER. THE CONTRACTOR SHALL REPORT ANY SUCH MODIFICATIONS TO THEARCHITECT/ENGINEER AND SECURE HIS APPROVAL BEFORE PROCEEDING. SHOULD THE REQUIREMENTSOF THE CONTRACT DOCUMENTS EXCEED THE REQUIREMENTS OF THE CODES, THE CONTRACTDOCUMENTS SHALL TAKE PRECEDENCE PROVIDED THEY ARE NOT IN CONFLICT WITH THOSE CODES.D. ALL ITEMS OF EQUIPMENT AND ALL MATERIALS FOR WHICH, APPROVAL STANDARDS HAVE BEENESTABLISHED BY UNDERWRITERS' LABORATORIES, INC. , FACTORY MUTUAL (FM), AMERICAN STANDARDCODES, ASME, AGA, AMCA, ASA, ANSI, ASHRAE, AND ARI SHALL BE SO APPROVED.E. PENETRATIONS THROUGH FLOORS OR FIRE-RATED CONSTRUCTION SHALL BE FIRESAFED TO COMPLY WITHASTM E-814 (UL 1479), AND LOCAL CODE REQUIREMENTS.
SUBMITTALS AND SHOP DRAWINGSA. CONTRACTOR SHALL PROVIDE THE ENGINEER WITH PRODUCT DATA AND SHOP DRAWINGS FOR ALLMATERIALS & EQUIPMENT SPECIFIED BELOW. SUBMITTALS SHALL BE PROVIDED IN AN ELECTRONICFORMAT. SUBMITTAL DATA SHALL INCLUDE:1. COVER SHEET WITH NAMES AND ADDRESSES OF PROJECT, ARCHITECT MEP ENGINEER, GENERALCONTRACTOR & SUB CONTRACTOR.2. DRAWING REFERENCE NUMBER, PRODUCT NAME AND/OR DESCRIPTION.3. INDEX OF ALL DATA IN SUBMITTAL.4. DIMENSIONAL DATA AND SKETCHES SHOWING THAT SUBMITTED EQUIPMENT WILL FIT INTO SPACEAVAILABLE AND WILL HAVE REQUIRED CODE AND MAINTENANCE CLEARANCES.5. IDENTIFICATION OF EACH ITEM MATCHING THAT INDICATED ON THE DRAWINGS.6. SUFFICIENT PERFORMANCE DATA, CAPACITY, SOUND DATA, DIAGRAMMATIC DATA AND DESCRIPTIVEINFORMATION TO SHOW ITS COMPLIANCE'S WITH THE CONTRACT DOCUMENTS. OPTIONS OR SPECIALREQUIREMENTS SHALL BE CLEARLY INDICATED. APPLICABLE INFORMATION SHALL BE CLEARLYINDICATED AND NON APPLICABLE DATA SHALL BE CROSSED OFF.7. MATERIALS AND EQUIPMENT PURCHASED OR INSTALLED WITHOUT A "NO EXCEPTIONS TAKEN" SHOPDRAWING REVIEW SHALL BE AT THE RISK OF THE CONTRACTOR. THE COST OF REMOVAL AND AT THERISK OF THE CONTRACTOR. THE COST OF REMOVAL AND REPLACEMENT OF SUCH MATERIALS WHICH ISJUDGED UN-SATISFACTORY BY THE ENGINEER FOR ANY REASON SHALL BE AT THE EXPENSE OF THECONTRACTOR.8. ANY ITEMS KNOWINGLY SUBMITTED THAT DO NOT COMPLY WITH SPECIFICATIONS SHALL BE LISTEDWITH EXPLANATION AS TO WHY THEY ARE BEING SUBMITTED.B. REQUIRED SUBMITTALS / SHOP DRAWINGS:1. FIXTURES
2. EQUIPMENT
3. HANGERS
4. PIPINGDOMESTIC WATER PIPINGA. ALL BRANCH WATER PIPING INSIDE THE BUILDING SHALL BE TYPE "L" COPPER TUBING (ASTM B-88) WITHWROUGHT COPPER FITTINGS (ANSI B16.22). CLEAN AND DEBURR THE INSIDE OF ALL FITTINGS CAREFULLYBEFORE JOINING WITH LEAD-FREE TIN/COPPER/SILVER/NICKLE SOLDER CONFORMING TO ASTM B32.WOLVERINE SILVABRITE 100 LEAD-FREE SOLDER OR HARRIS NICK LEAD-FREE SOLDER ARE ACCEPTABLELEAD-FREE SOLDERS. USE WATER SOLUBLE FLUX RECOMMENDED BY SOLDER MANUFACTURER ANDCONFORMING TO ASTM B813 AND NSF 61. WOLVERINE SILVABRITE 100 WATER SOLUBLE FLUX OR BRIDGITWATER SOLUBLE PASTE FLUX ARE ACCEPTABLE FLUX . NO ACIDS SHALL BE USED TO CLEAN EITHER PIPEOR FITTINGS OR AS A FLUX IN SWEATING JOINTS. THE USE OF DRILLED-T CONNECTIONS IS NOT PERMITTED.B. ALL COPPER WATER PIPING SHALL BE COMPLETELY ISOLATED FROM METAL HANGERS, METAL STUDS ORANY OTHER ELECTRICALLY CONDUCTIVE BUILDING COMPONENTS. PROVIDE DIELECTRIC UNION AT ALLCONNECTIONS BETWEEN COPPER AND GALVANIZED PIPE.C. PROPRESS MAY BE USED FOR TUBING SIZES 1/2" THRU 4" AND SHALL CONFORM TO THE MATERIALS ANDSIZING REQUIREMENTS OF ASME B16.18 OR ASME B 16.22 AND HAVE "NSF-61" STAMPED ONTO THE FITTINGS.NO MIXING OF FITTING MANUFACTURERS SHALL BE ALLOWED. SEALING ELEMENTS FOR COPPER PRESSFITTINGS SHALL BE EPDM. SEALING ELEMENTS SHALL BE FACTORY INSTALLED OR AN ALTERNATIVESUPPLIED BY FITTING MANUFACTURER. PRESS ENDS SHALL HAVE A FEATURE DESIGN LEAKAGE PATH.COPPER PRESS FITTINGS SHALL HAVE A SPECIFIC DESIGN FEATURE TO ENSURE THAT UNPRESSEDFITTINGS WILL BE IDENTIFIED AT ANY PRESSURE GREATER THAN 15 PSIG. COPPER PRESS FITTINGS SHALLBE RATED FOR 200 PSIG WORKING PRESSURES AND TEMPERATURES 250 DEGREES F.D. DOMESTIC WATER PIPING SHALL BE HYDROSTATICALLY TESTED AT 1.5 TIMES SYSTEM DESIGN PRESSURE.SANITARY SOIL WASTE AND VENT PIPING - CAST IRONA. ABOVE GRADE WASTE AND VENT SHALL BE NO-HUB STANDARD WEIGHT CAST IRON PIPE WITH NO-HUBDRAINAGE FITTINGS USING STAINLESS STEEL COUPLINGS THAT MEET ASTM C 1540.B. CAST IRON PIPE SHALL BE AS MANUFACTURED BY CHARLOTTE, AB&I OR TYLER.C. SLOPE ALL WASTE AND VENT PIPING IN ACCORDANCE WITH LOCAL CODES.D. PROVIDE AND INSTALL ALL CLEANOUTS INDICATED AND AS REQUIRED BY LOCAL CODES.E. THE WASTE AND VENT SYSTEM SHALL BE TESTED AS REQUIRED BY THE PLUMBING CODES HAVINGJURISDICTION.DRAINS AND CLEANOUTSA. FURNISH AND INSTALL CLEANOUTS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY LOCALORDINANCE. CLEANOUTS SHALL BE MANUFACTURED BY JAY R. SMITH, JOSAM, JONESPEC, WADE, OR ZURNUNLESS NOTED OTHERWISE.B. CLEANOUTS SHALL BE THE SAME NOMINAL SIZE AS THE PIPE THEY SERVE UP TO FOUR INCHES.C. CLEANOUTS SHALL HAVE A CAST IRON BODY WITH TAPERED CAST BRASS OR BRONZE PLUG PROVIDINGGAS AND WATERTIGHT SEAL.D. INTERIOR FLOOR CLEANOUTS SHALL HAVE STAINLESS STEEL OR NICKEL BRONZE SCORIATED TOP.PROVIDE CARPET MARKER WHEN INSTALLED IN AREAS TO BE COVERED BY CARPET.E. EXTERIOR CLEANOUTS AT GRADE SHALL HAVE SCORIATED CAST IRON TOP.F. WALL CLEANOUTS SHALL BE PROVIDED WITH STAINLESS STEEL ACCESS COVERS OF ADEQUATE SIZE TOALLOW RODDING OF DRAINAGE SYSTEM. WALL CLEANOUTS INCORPORATING COVER SCREWS THATEXTEND COMPLETELY THROUGH THE ACCESS PLUG ARE NOT ACCEPTABLE.G. SET TOP OF FLOOR DRAINS AND FLOOR SINKS TO MEET THE LOW POINT ELEVATION OF FINISHED FLOOR.H. FINAL MOUNTING OF INTERIOR CLEANOUT TOP OR ACCESS COVER SHALL BE SET FLUSH WITH THEFINISHED FLOOR OR WALL SURFACE. LUBRICATE THREADED CLEANOUT PLUGS WITH MIXTURE OFGRAPHITE AND LINSEED OIL.I. ENCASE EXTERIOR CLEANOUTS WITHIN 14"X14"X6" THICK REINFORCED CONCRETE PAD. SET TOP FLUSHWITH FINISHED GRADE SURFACE.J. LOCATE CLEANOUTS WITH REQUIRED CLEARANCE FOR RODDING OF DRAINAGE SYSTEM.K. ROUND WALL CLEANOUT COVERS SHALL NOT BE LARGER THAN REQUIRED FOR 4 INCH DIA. PIPE. ACCESSPANELS SHALL BE PROVIDED AS APPROVED BY ARCHITECT/ENGINEER FOR LARGER PIPE SIZES.
PIPING INSULATIONA. DOMESTIC WATER (COLD, HOT AND HOT WATER RETURN) PIPING, FITTINGS AND VALVES SHALL BEINSULATED WITH NOMINAL 1'' WALL THICKNESS FIBERGLASS PIPE INSULATION, WITH A K FACTOR NOT TOEXCEED 0.23 BTU*IN/HR*SF*DEGREE F @ 75 DEGREES F, HAVING FLAME SPREAD RATING OF 25 OR LESSAND A SMOKE DENSITY OF 50 OR LESS WHEN TESTED BY ASTM E-84 METHOD. THE INSULATION SHALLINCLUDE AN ALL PURPOSE JACKET, CONSISTING OF HIGH DENSITY, WHITE KRAFT BONDED TO ALUMINUMFOIL AND REINFORCED WITH FIBERGLASS YARN. THE JACKET SHALL INCLUDE A LONGITUDINAL LAP WITH APRESSURE SENSITIVE TAPE SEAL.B. INSULATED PIPING SHALL NOT BE EXPOSED AT HANGER AND COME INTO DIRECT CONTACT WITH HANGERWITHOUT INSULATION AND SHIELD AS DESCRIBED BELOW.C. PROVIDE PROTECTION SHIELDS AT ALL PIPE HANGERS. WHERE PROTECTION SHIELDS ARE USED, PROVIDEAN INSERT BETWEEN THE PIPING AND THE SHIELD 2'' LONGER AND WIDER THAN THE SHIELD, HAVING THESAME THICKNESS AND CONTOUR AS THE ADJOINING INSULATION. INSERTS SHALL BE MINIMUM 8.0#DENSITY, MINIMUM 100 PSI COMPRESSIVE STRENGTH.D. ACCEPTABLE INSERT MATERIALS ARE:1. PITTSBURGH-CORNING "FOAMGLAS" CELLULAR GLASS2. SCHULLER THERMO-12 CALCIUM SILICATE3. OWENS-CORNING KAYLO AF CALCIUM SILICATEE. CLOTH TAPE IS NOT ACCEPTABLE FOR USE IN THIS APPLICATION.DOMESTIC WATER VALVES (COLD AND HOT)A. LINE-SHUT OFF VALVES UP TO AND INCLUDING 2" SHALL BE TWO PIECE BRONZE BODY OF ASTM B584 ALLOY844, ASTM B61 OR ASTM B62, FULL PORT BALL TYPE RATED AT 600 WOG WITH THREADED CONNECTIONS,BLOW-OUT PROOF STEM, PLASTIC COATED LOCKABLE LEVER HANDLE, TEFLON PACKING, 316 STAINLESSSTEEL BALL AND STEM. ACCEPTABLE VALVES ARE NIBCO MODEL T-585-70-66-LL-LF OR APPROVED EQUALMODEL BY CRANE, MILWAUKEE OR APOLLO.B. LINE SHUT-OFF VALVES 2-1/2” AND LARGER INSTALLED WITHIN SYSTEMS HAVING DESIGN OPERATINGPRESSURES BETWEEN 160 AND 250 P.S.I.G. SHALL BE THREADED LUG TYPE DUCTILE IRON BODYBUTTERFLY VALVE WITH EXTENDED NECK, LOCKABLE LEVER HANDLE, 316 STAINLESS STEEL STEM ANDDISC, EPDM LINER AND SEAL, SUITABLE FOR BI-DIRECTIONAL FLOW AND DEAD END SERVICE WITHDOWNSTREAM FLANGE REMOVED. ACCEPTABLE VALVES ARE NIBCO MODEL LD-3022, OR APPROVEDEQUIVALENT MODEL BY KEYSTONE, JAMESBURY, DEZURIK, MILWAUKEE, CRANE OR APOLLO.C. PROVIDE STEM EXTENSIONS OF A NON-THERMAL CONDUCTING MATERIAL FOR VALVES IN INSULATED LINESTO ALLOW UNOBSTRUCTED OPERATION.D. DOMESTIC HOT WATER RETURN CIRCUIT BALANCING VALVES 1/2" THROUGH 3" SHALL BE MACHINED BALLTYPE CALIBRATED BALANCING VALVE WITH LEAD FREE ASTM B283-C69300 BRASS BODY/304 STAINLESSSTEEL BALL CONSTRUCTION, GLASS AND CARBON FILLED TFE SEAT RINGS, EPDM STEM "O" RING,THREADED NPT INLET/OUTLET CONNECTIONS, 400 PSIG MAXIMUM WORKING PRESSURE AT 250ºF. VALVESHALL HAVE DIFFERENTIAL PRESSURE READ-OUT PORTS ACROSS VALVE SEAT AREA FITTED WITHINTERNAL EPT INSERTS/CHECK VALVES. VALVE BODY SHALL HAVE 1/4" NPT TAPPED DRAIN/PURGE PORT.VALVE SHALL HAVE CALIBRATED NAMEPLATE AND MEMORY STOP FEATURE TO ALLOW VALVE TO BECLOSED FOR SERVICE AND THEN REOPENED TO SET POINT WITHOUT DISTURBING BALANCE POSITION.VALVE SHALL CONTAIN LESS THAN 0.25% LEAD CONTENT BY WEIGHT ON WETTED SURFACES AND BEDESIGNED FOR POSITIVE SHUT-OFF.. VALVES SHALL BE SAME SIZE AS THE PIPE INSTALLED. PROVIDEVALVES AS SCHEDULED ON CONTRACT DRAWINGS MANUFACTURED BY BELL & GOSSETT CIRCUIT SETTERPLUS CB SERIES, OR OWNER APPROVED EQUAL.E. SPRING LOADED CHECK VALVES, 2" AND SMALLER - SILENT CLOSING, BRONZE, CLASS 125, WITH THREADEDCONNECTIONS, BUNA DISC, BRONZE OR STAINLESS STEEL SPRING. MANUFACTURED BY NIBCO MODEL T-480OR APPROVED EQUIVALENT MODEL BY MILWAUKEE OR CRANE.F. SPRING LOADED CHECK VALVES, 2-1/2" AND LARGER - 200 POUND CWP, IRON BODY, WITH BRONZE ORSTAINLESS STEEL TRIM. MANUFACTURED BY NIBCO MODEL F-910 OR APPROVED EQUIVALENT MODEL BYMILWAUKEE OR CRANE.PIPE HANGERS AND SUPPORTSA. ALL PIPE SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE IN A NEAT ANDWORKMANLIKE MANNER AND WHEREVER POSSIBLE, PARALLEL RUNS OF HORIZONTAL PIPING SHALL BEGROUPED TOGETHER ON TRAPEZE TYPE HANGERS. VERTICAL RISERS SHALL BE SUPPORTED AT EACHFLOOR LINE WITH STEEL PIPE CLAMPS. SPACING OF PIPE SUPPORTS SHALL BE IN ACCORDANCE WITH NFPA13.B. ALL PIPING SHALL BE PITCHED TO DRAIN IN ACCORDANCE WITH NFPA 13. PROVIDE VALVES WITH HOSECONNECTIONS AT ALL SYSTEM DRAIN POINTS.C. IF IT COMPLIES WITH THESE SPECIFICATIONS, HANGERS AND SUPPORTS MANUFACTURED BY ONE OF THEFOLLOWING MANUFACTURERS WILL BE ACCEPTABLE: FEE AND MASON, GRINNELL, ELCEN OR APPROVEDEQUAL.PLUMBING PIPING HANGER SPACINGA. MAXIMUM SPACING BETWEEN PIPING HANGERS SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE:SIZE OF PIPING DISTANCE BETWEEN SUPPORTS: COPPER1/2" 5' 3/4" 6' 1" 7' 1-1/4" 8' 1-1/2" 9' 2" 10' B. PROVIDE ADDITIONAL SUPPORTS TO PREVENT SAGGING OF PIPEC. SUPPORTS SHALL BE ARRANGED SO AS TO BE NEAR THE WEAKEST POINT OF THE SPAN SUCH AS JOINTS,TURNS AND AT THE BASE OF ALL VERTICAL TO HORIZONTAL OFFSETS AND AT ALL WASTE TRAPS.D. ALL PIPING SHALL BE RIGIDLY INSTALLED IN ALL CHASES OR WALLS. TEST FOR RIGIDITY SHALL BE THATTHE PIPING IS VIRTUALLY IMMOVABLE BY HAND, SHORT OF DEFORMING THE PIPING.E. IN NO CASE SHALL ANY PIPING DEPEND ON BLOCKS, BRICKS, STONE, WOOD SLEEPERS OR TIE WIRES FORITS FINAL SUPPORT.F. SUPPORT SYSTEM SHALL BE AS MANUFACTURED BY "HOLDRITE" OR AN APPROVED EQUAL.
MEP1.2
MEP
PLUMBING
SPECIFICATIONS
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
EP
1.2
_M
EP
PLU
MB
ING
SP
EC
IFIC
AT
ION
S.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
200
CORRIDOR
PUBLIC
11
1
1
1
1
1
1
1 1
2
2
1
1
T 3 T 3 T 3
T 3
EXISTING TO REMAINEXISTING TO BE REMOVEDDEMO TO THIS POINT
EXISTING AIR DEVICE TO REMAIN. TYPICAL.RELOCATE EXISTING AIR DEVICE. REFER TO M2.03 FOR NEW LOCATION. SEAL TAP AIR TIGHT IF NOTUSED.EXISTING TEMPERATURE SENSOR SHALL REMAIN.
1. WHERE DUCTWORK IS REMOVED FROM MAIN BRANCHES, CAP AND SEAL DUCTWORK AIR TIGHT ANDREPAIR INSULATION TO MATCH EXISTING PRIOR TO ORDERING SHEET METAL, FIELD VERIFY ANDCOORDINATE EXACT DUCT ROUTING WITH NEW AND EXISTING STRUCTURAL CONDITIONS ANDPROVIDE SHOP DRAWINGS FOR REVIEW. COORDINATE WITH OTHER DISCIPLINES.2. IF SPECIFICATIONS DIFFER FROM BUILDING STANDARDS AND/OR SPECIFICATIONS LET ENGINEERKNOW IMMEDIATELY. INTENT IS TO MATCH BUILDING STANDARDS; HOWEVER, ENGINEER RESERVESTHE RIGHT TO MAKE THE FINAL DECISION.3. PRIOR TO DEMOLITION, CONTRACTOR SHALL TAKE READINGS OF ALL AIR DEVICES IN THE SPACE.
123
M1.03
LEVEL 3
MECHANICAL
DEMO PLAN
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
2pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
1.0
3_M
EC
HA
NIC
AL D
EM
OLIT
ION
PLA
N.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
1/4" = 1'-0"
PLAN
NORTH
TRUE
NORTH
200
CORRIDOR
PUBLIC
212.00
WAITING212.01
DR OFFICE
CHECK-IN
212.13
ADMIN
212.02
EXAM 1
212.03
EXAM 2
212.12
STORAGE
212.11
TOILET
212.09
LAB
212.04
STATION
WORK
212.06
EXAM 3
212.07
TOILET
212.08
EXAM 4
212.05
CORRIDORCOPY/FAX
T T T
T
11
1
1
1
1
11 2
3 A95
-65
1
1
14
444
HVAC IN THIS ROOM SHALL REMAIN. REBALANCE AIR DEVICES TO PRE-CONSTRUCTION CFMREADINGS.RELOCATE EXISTING AIR DEVICE AND REBALANCE AS INDICATED. REUSE TAP AND EXTEND FLEX ASNECESSARY.NEW CEILING SUPPLY DIFFUSER. PROVIDE NEW SPIN-IN AND FLEX DUCTWORK. BALANCE TO CFMINDICATED. SEE SCHEDULE. TYPICAL.EXISTING THERMOSTAT SHALL REMAIN IN PLACE.
EXISTING TO REMAINNEW CONSTRUCTIONCONNECT AT THIS POINT
1. REFER TO MECHANICAL INFORMATION SHEET FOR ABBREVIATIONS AND NOTES.2. COORDINATE CEILING AIR DEVICES WITH LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES.3. PRIOR TO ORDERING SHEET METAL, FIELD VERIFY AND COORDINATE EXACT DUCT ROUTING WITHNEW AND EXISTING STRUCTURAL CONDITIONS AND PROVIDE SHOP DRAWINGS FOR REVIEW.4. ALL DUAL DUCT BOXES ARE EXISTING TO REMAIN. REFURBISH TO LIKE-NEW CONDITIONS. RE-SEALAND INSULATE ALL CONNECTIONS AS REQUIRED.5. ALL PRIMARY AND SECONDARY DUCTWORK IS EXISTING TO REMAIN. RE-SEAL AND INSULATE ALLDUCTWORK AS REQUIRED. SEAL ALL UNUSED TAPS AIR TIGHT.
1234
M2.03
MECHANICAL
FLOOR PLAN
1/4" = 1'-0"
PLAN
NORTH
TRUE
NORTH
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
6pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
2.0
3_M
EC
HA
NIC
AL F
LO
OR
PLA
N.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning
SIDE CONNECTION
TOP CONNECTION
IF THERE IS INSUFFICIENT HEADROOM FOR TOP CONNECTION AS DETAILED, USE SIDE CONNECTION.
CEILING
DUCT FULLY EXTENDED
ROUND DUCT ADAPTOR
DIFFUSER
FOR RECTANGULAR
MAX. 6 FT LENGTH FLEXIBLE
1.
NOTES:
CEILING
DIFFUSER
D MIN.
DUCT FULLY EXTENDED
ROUND DUCT CONNECTOR
DIFFUSER NECK SIZE
MAXIMUM 6 FT. LENGTH FLEXIBLE
THERMAL DUCT INSULATION
DIFFUSER
2-3/4 IN. MINIMUM
6" MINIMUM
R=D
EXTERNALLY INSULATED
PLENUM BOX
STAINLESS STEEL CLAMPS
SPIN-IN FITTING W/ SQUARE DAMPER ROD & DAMPER OPERATOR
ON RAISED PLATFORM. INSULATE EXTERNALLY.
EXTERNALLY INSULATED SUPPLY
OR RETURN DUCT
2. USE RIGID ROUND INSULATED DUCT FOR LENGTHS IN EXCESS OF 6'-0".
3. USE ONLY ON SUPPLY AND RETURN BRANCHES TO CEILING DEVICES.
USE RIGID DUCT ON ALL BRANCHES TO EXHAUST DEVICES AND ON EXPOSED APPLICATIONS.
BRANCH DUCT SHALL BE SAME SIZE AS DIFFUSER CONNECTION.4.
FLEXIBLE DUCT CONNECTION DETAIL 1
RETURN AIR GRILLE DETAIL
PERFORATEDRA GRILLEFACELAY-IN TYPESCHEDULED AIRDEVICE
3
SUPPLY AIR FLOW
RETURN/EXHAUIST AIR FLOW
VOLUME DAMPER WITHLOCKING TYPE INDICATORQUADRANT AND SADDLE TOCLEAR INSULATION
CLINCH COLLAR
1/4W", 4" MINIMUM
3/8" SQUARE ROD
END BEARING
BRANCH DUCT
MAIN DUCT
W
45°
4RECTANGULAR DUCT ANGULAR TAP
WITH VOLUME DAMPER
M3.01
MECHANICAL
DETAILS AND
SCHEDULES
2500 Wilcrest Drive, Suite 150Tel: (281) 809-7532Texas Reg. No.: F-12902 Houston, Texas 77042Fax: (281) 809-7536CFI Project No.: 117165.00www.cficompanies.com
12/13/17
ISSUED FOR BID
00
00
msald
ana
Dec 1
3, 2017 -
2:5
5pm
P:\2017\1
17165.0
0 H
SA
HM
H S
J2 S
uite 2
12 D
iggs\D
raw
ings\C
AD
\117165_M
3.0
1_M
EC
HA
NIC
AL D
ET
AIL
S A
ND
SC
HE
DU
LE
S.d
wg
(F) 713.626.4301
(T) 713.626.4300
HOUSTON, TEXAS 77043
1165 BRITTMOORE ROAD
Copyright C 2017 Heitkamp Swift Architects
in association with:
HMH SJ2
SUITE 212
DIGGS
4301 GARTH ROAD
SUITE 212
BAYTOWN, TX 77521
12/13/2017
17415
SHEET INFORMATION
SHEET
TITLE
JOB NUMBER
DATE
NO. ISSUE DATE
REVISIONS
XXXXX MO/DA/YR
HEITKAMP SWIFTARCHITECTSArchitecture Interiors Planning