nromoef.gov.innromoef.gov.in/smpr/01062015/11.docx · web viewhspcb guideline. 7. construction...

29
Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana SIX- MONTHLY ENVIRONMENTAL COMPLIANCE REPORT FOR STIPULATED & GENERAL CONDITIONS OF ENVIRONMENTAL CLEARANCE (OCTOBER 2014 TO MARCH 2015) FOR GROUP HOUSING PROJEC ATHARVA SEC-109, AT VILLAGE PANWALA, KHUSRUPUR, GURGOA HARYANA. SUBMITTED TO: Ministry of Environment & Forests (MoEF) Northern Regional office Bays No 24-25 Sector 31- A Dakshin Marg Chandigarh SUBMITTED BY: RAHEJA DEVELOPERS LTD MAY 2015 1

Upload: duongnhan

Post on 10-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

SIX- MONTHLY ENVIRONMENTAL COMPLIANCE REPORT FOR STIPULATED & GENERAL CONDITIONS OF ENVIRONMENTAL CLEARANCE

(OCTOBER 2014 TO MARCH 2015)

FOR

GROUP HOUSING PROJEC ATHARVA SEC-109, AT VILLAGE PANWALA, KHUSRUPUR, GURGOA HARYANA.

SUBMITTED TO:

Ministry of Environment & Forests (MoEF)Northern Regional office Bays No 24-25 Sector 31- A Dakshin Marg Chandigarh

SUBMITTED BY:

RAHEJA DEVELOPERS LTD

MAY 2015

1

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

Table of Contents

DESCRIPTION Page No.Chapter 1 Introduction and Project Description

1.1 Introduction 41.2 Project Description 41.3 Present Status 51.4 Purpose of the report 5

Chapter 2 Compliance of Stipulated Conditions of Environmental ClearancePart A Specific Conditions for buildings in operational phase

I. Construction Phase 6II. Operation Phase 9

Part B General Conditions 11Chapter 3 Details of Environmental Monitoring

3.1 Ambient Air Quality Monitoring 133.1.1 Ambient Air Quality Monitoring Stations 133.1.2 Ambient Air Quality Monitoring Methodology 133.1.3 Discussion on Ambient Air Quality in the Study Area 143.2 Ambient Noise Monitoring 14

3.2.1 Ambient Noise Monitoring Locations 143.2.2 Methodology of Noise Monitoring 153.2.3 Ambient Noise Monitoring Results 153.2.4 Discussion on Ambient Noise Levels in the Study Area 153.3 Groundwater Quality Monitoring 16

3.3.1 Groundwater Quality Locations 163.3.2 Methodology of Groundwater Quality Monitoring 163.3.3 Groundwater Quality Monitoring Results 163.3.4 Discussion on Groundwater Quality in the Study Area 173.4 Soil Monitoring 17

3.4.1 Soil Monitoring Locations 173.4.2 Methodology of Soil Monitoring 183.4.3 Soil Monitoring Results 183.4.4 Discussion on Soil Characteristics in the Study Area 19

TABLES3.1 Details of Ambient Air Quality Monitoring Stations 133.2 Techniques used for Ambient Air Quality Monitoring 143.3 Ambient Air Quality Monitoring Results 143.4 Details of Ambient Noise Monitoring Stations 153.5 Ambient Noise Monitoring Results 153.6 Details of Water Quality Monitoring Station 163.7 Groundwater Quality Monitoring Results 173.8 Details of Soil Quality Monitoring Location 183.9 Physico-Chemical Characteristics of soil in the Study Area 18

2

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

LIST OF ANNEXURES

S.NO. DESCRIPTION ANNEXURE1 Environmental Clearance letter Annexure-I2 Latest Monitoring report Annexure-II3 License Renewal Copy Annexure-III4 CTE Renewal Copy Annexure-IV5 Airport Authority Renewal Copy Annexure-V

3

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

CHAPTER 1

INTRODUCTION AND PROJECT DESCRIPTION

1.1 INTRODUCTION

“Atharva” a group housing project measuring area 14.812 acres is being developed at village Panwala, Khusrupur, Sector 109, Gurgoan, Haryana, by M/s Raheja Developers Ltd. to facilitate Residential services in the nearby area. The project includes all facilities which will give enhance the green area and other facilities in the nearby area.

The project has been awarded Environmental Clearance with ‘Gold’ grading by State Environmental Impact Assessment Authority, under category 8(a) Haryana, vide reference number DEH/09/SEIAA/66 dated 01/04/2009.

The project has been sanctioned License vide letter number 257 of 2007 dated 07.11.2007 by the Department of Town and Country Planning (DTCP), Govt. of Haryana .

Project has been accorded Airport Authority permission vide no AAI/20012/650/2008-ARI.

1.2 PROJECT DESCRIPTION

SALIENT FEATURES:

This project involves construction of group housing on a plot area of 14.812 Acres or 59941.94 m2. Total Built–up area is 1, 57,918.34 m2. The group housing project contains 2 Basements and containing G+16 Floors. The total numbers of dwelling units are 528 and there are 18 Villas.

The group housing project contains 1 nursery school, 1 community center, 116 EWS and commercial area for the residential of the society. The maximum permissible height of the building is 60 m for which the permission is already being taken from the airport authority of India vide letter AAI/20012/650/2008-ARI. Dated 02.01.2014

The total water requirement is 600 KLD out of which 324 KLD will be fresh water requirement. The waste water generation will be about 447 KLD which will be treated in STP of 470 KLD capacity. The 276 KLD of treated water will be reused in horticulture, cooling of DG, flushing and washing and the excess water will be discharged into the public sewer with permission.

Total waste generation will be 1475 Kg/day, which will be disposed off as per SWM & Handling Rules.

4

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

PARKING:

Adequate parking will be provided in the group housing project. Total of 1152 ECS has been provided for the parking. Due care will be taken for the movement of the vehicles to tackle the traffic movement. The project will have complete parking facility and no outside open parking area will be used.

WATER SUPPLY:

The primary source of water for the construction phase will be treated STP water supplied through private tankers and during the operational phase water will be sourced through HUDA.

ELECTRICITY:

The maximum demand load for the group housing project will be approximately 4858 KW and the power will be sourced through Dakshin Haryana Bijli Vitran Nigam Limited.

1.3 PRESENT STATUS

Project is in construction phase.

1.4 PURPOSE OF THE REPORT

This six- monthly report is being submitted as per the condition stipulated in the Environmental Clearance letter.

Further, the study will envisage the environmental impacts that have generated in the local environment due to the project.

The environment assessment is being carried out to verify:

That the project does not have any adverse environmental impacts in the project area and it’s surrounding.

Compliance with the conditions stipulated in the Environmental Clearance letter. That the Project Management is implementing the environmental mitigation measures as

suggested in the approved Form-1, Form-1A, Environmental Management Plan (EMP) and building plans.

The project proponent is implementing the environmental safeguards in the true spirit. Any non-conformity in the project with respect to the environmental implication of the

project.

5

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

CHAPTER 2

Compliance of Stipulated condition of Environmental Clearance for Buildings in Construction & Operational Phase.

PART A – SPECIFIC CONDITIONS

I. CONSTRUCTION PHASE

S. No.

Conditions of Environmental Clearance Status of Compliance

1. The Project Proponent will first obtain permission of CGWA for abstraction of ground water and only after that they will start construction.

Agreed. The treated water through private tankers is being used for the construction purpose and no abstraction of ground water is in practice.

2. All required sanitary and hygienic measures should be in place before starting construction activities and to be maintained throughout the construction phase.

Agreed. All required sanitary and hygienic measures are being taken care with proper water and mobile toilets facilities to the construction worker due care is being taken for the safety and will be practiced further throughout the construction phase of the project.

3. A first aid room will be provided in the project both during construction and operation phase of the project.

Agreed. First aid facility is readily available at the project site for the safety of the workers during the construction phase and is in the custody of the project in charge. The facility will be maintained even during the operation phase of the project.

4. Adequate drinking water and sanitary facilities should be provided for construction workers at site. Provision should be made for mobile toilets. The safe disposal of waste water and solid wastes generated during the construction phase should be ensured.

Agreed. Adequate drinking water and sanitary facility is being provided for the construction workers during the construction phase. There is provision of mobile toilets in the construction site and these are proper facility of waste water and solid waste disposal.

5. All the top soil excavated during construction activities should be stored for use in horticulture/landscape development within the project site.

Agreed. All the top soil from the excavation of the project is being stored at the safest secured location and will be used for the horticulture and landscaping purpose once the construction of the project is complete.

6. Disposal of muck during construction phase should not create any adverse effect on the neighboring communities and be disposed taking the necessary precautions for general safety and health aspects of people, only in approved sites with the

Very small amount of muck was generated during the starting of the construction of the project. Due care was being taken for the safety and health aspects of the peoples. No hazardous waste is being generated, however if it would be so then, disposal would be as per

6

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

approval of competent authority. HSPCB guideline.7. Construction spoils, including bituminous

material and other hazardous materials, must not be allowed to contaminate watercourses and the dump sites for such material must be secured so that they should not leach into the ground water.

Agreed. Construction spoils, including bituminous material and other hazardous materials was disposed off in scientific manner. Due care was being taken to have zero impact on the watercourse.

8. Any hazardous waste generated during construction phase, should be disposed off as per applicable rules and norms with necessary approval of the Haryana State pollution Control Board.

Agreed. Since the project is a construction of group housing project thus there is nil generation of hazardous waste. However if applicable, necessary approval will be taken from the competent authority.

9. The diesel generator sets used during construction phase should be of low sulphur diesel type and should conform to Environment (Protection) Rules prescribed for air and noise emission standards.

Agreed. Low sulphur diesel is being used to run the DG sets during power failure and it conforms to Environment (Protection) Rules prescribed for air and noise emission standards.

10. The diesel required for operating DG sets shall be stored in underground tanks and if required, clearance from Chief Controller of Explosives shall be taken.

Agreed. Very low quantity of diesel is being required during the power failure and DG sets are being run only during the power failure. The diesel required for operating DG sets is stored /secured in such a way that no accidents, spillage and leakage is possible. Due care is being taken during the storage and transportation of the diesel.

11. Vehicles hired for bringing construction material to the site should be in good condition and should have a pollution check certificate and should conform to applicable air and noise emission standards and should be operated only during non peak hours.

Agreed. Vehicles hired for bringing construction material to the site are new and are in good condition. Vehicles with proper pollution certificates are allowed inside the premises of the construction site.

12. Ambient noise levels should conform to residential standards both during day and night. Incremental pollution loads on the ambient air and noise quality should be closely monitored during construction phase, so as to conform to the stipulated standards.

Agreed. Ambient noise level monitoring was carried out dated 31.03.2015 near the site office and it was found within the prescribed limit of residential standards during day and night. Incremental pollution loads on the ambient air and noise quality are closely monitored during construction phase. Water sprinklers and other specific measures are being used for reducing the pollution level in and around the construction site. Adequate measures have been taken to reduce ambient air and noise level during construction phase.

13. Fly ash should be used as building material Fly Ash is being used in Ready Mix Concrete as

7

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

in the construction as per the provisions of Fly Ash Notification of September, 1999 and amended as on 27th August 2003.

building material in the construction as per the provisions of Fly Ash Notification of September, 1999 and amended as on 27th August 2003.

14. Ready mix concrete must be used in building construction

Ready Mix Concrete is being used for the building construction.

15. Storm water control and its re-use as per CGWB and BIS standards for various application

Storm water is being controlled by laying proper internal drainage network within the project site as per the CGWB and BIS standards.

16. Water demand during construction should be reduced by use of pre-mixed concrete, curing agents and other best practices referred.

Agreed. To conserve water, pre-mixed concrete, curing agents and other best practices are being followed in the project.

17. Permission from competent authority for supply of water shall be obtained prior to construction/operation of the project.

Assurance for Water supply has been obtained from HUDA for the operation phase.

18. Separation of grey and black water should be done by use of dual plumbing line for separation of grey and black water.

Practice of dual plumbing line is in practice for separation of grey and black water as per provision.

19. Fixtures for showers, toilet flushing and drinking should be of low flow either by use of aerator or pressure reducing devices or sensor based control.

Agreed. Due care is being taken for reducing the daily water demand load and same will be followed during the operation phase of the project by using low water consuming equipments in flushing and other purposes.

20. Use of glass may be reduced by up to 40% to reduce the electricity consumption and load on air conditioning. If necessary use high quality glass with special reflective coating in windows.

Same will be complied during the use of glass during the completion/operation phase of the project.

21. Roof should meet prescribed requirement as per Energy Conservation Building Code by using appropriate thermal insulation materials to fulfill requirement.

Energy conservation measures are being adopted for roof treatment.

22. Opaque wall should meet prescriptive requirement as per Energy Conservation Building Code which is proposed to be mandatory for all air conditioned spaces while it is aspirational for non- air conditioned spaces by use of appropriate thermal insulation material to fulfill requirement.

Energy conservation measures are being adopted for walls.

23. The approval of the competent authority shall be obtained for structural safety of the building due to earthquake, adequacy of fire fighting equipments etc as per National Building Code including protection

Agreed. All approvals from the competent authority have been obtained for structural safety of the building for earthquake, adequacy of fire fighting equipments etc.

8

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

measures from lighting etc. If any forest land is involved in the proposed site, clearance under forest Conservation Act shall be taken from the competent Authority.

The project does not involve any forest land. The project falls under the residential zone as per the master plan however NOC from forest department has been obtained.

24. Regular supervision of the above and other measures for monitoring should be in place all through the construction phase, so as to avoid disturbance to the surroundings.

During the construction phase of the project due care is being taken for minimizing the construction effect in the surrounding area near the project site. Regular site inspection by the Environmental Monitoring team of the RDL is in practice.

25. Under the provision of the Environmental (Protection) Act 1986, legal action shall be initiated against the project proponent if it is found that the construction of the project has been started without obtaining environmental clearance.

The Construction of the project was started after obtaining Environmental Clearance from the SEIAA Haryana.

II. OPERATION PHASE

1. The STP shall be installed for the treatment of the sewage generated to the prescribed standards including odour and treated effluent will be recycled to the maximum and excess treated sewer discharged in public sewer after UV treatment

For the purpose of treating waste water generated from the project there is a provision of STP for treating entire sewage generated from the building. The treated water from the STP will be recycled and will be used for the horticulture and flushing and DG set cooling purpose.

2. Separation of grey and black water should be done by use of dual plumbing line. Treatment of 100% gray water by decentralized treatment should be done.

Provision of dual plumbing line has been made for separation of grey and black water. Treated waste water will be used for flushing, landscaping and DG cooling.

3. For disinfection of the treated waste water ultraviolet radiation or ozonization should be used.

Use of UV Treatment has been proposed for disinfection of treated waste water in the STP.

4. The solid waste generated should be properly collected and segregated. Wet garbage should be composted and dry / inert solid waste should be disposed off to the approved sites for land filling after recovering recyclable material.

Solid waste is being disposed through MCG authorized waste collector and is being disposed to the government approved disposal site. Practice of daily collection and segregation is being followed and will be practiced further.

5. Diesel power generation sets proposed as a source of backup power for lifts, common area illumination and for domestic use should be of enclosed type and conform to

DG sets installed would be of enclosed enclosure type conforming to the rules made under EP Act 1986.Proper stack height above the rooftop is being

9

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

rules made under the Environment (Protection) Act, 1986. The location of the DG sets should be in the basement as promised by the project proponent with appropriate stack height as per the CPCB norms. The diesel used for the DG sets should be of low sulphur contents (maximum 0.25%)

provided for the easy dispersion of the emissions as per the rules.

Low sulphur diesel (with maximum sulphur content of 0.25%) is in practice while running the DG sets during the power failure.

6. Ambient Noise level should be controlled to ensure that it does not exceed the prescribed standards both within and at the boundary of the proposed Hotel complex.

Ambient Noise level at the project site during operation phase is in practice on a regular basis. Due care is being taken for maintaining minimum noise level both within and around the construction site for the welfare of the residential.

7. The project proponent should maintain at least 30% as green cover area out of which 15% area should be used for tree plantation especially all around the periphery of the project and on the road sides preferably with local species so as to provide protection against particulate and noise. The open spaces inside the plot should be preferably landscaped and covered with vegetation / grass.

There is provision of 30 % of Landscape area in the project site and complete landscaping will be developed once the completion of the project gets over. 15 % Periphery avenue plantation is in practice for reducing the dust and noise level around the project site. The open space inside the project will be used for the grass and vegetation plantation once the construction gets over.

8. Weep holes in the compound walls shall be provided to ensure natural drainage of rain water in the catchment area during the monsoon period.

There is provision of weep holes in the compound walls for natural drainage of rain water in the catchment area during the monsoon period.

9. Rain water harvesting for roof run off as per plan submitted should be implemented. Before recharging the surface run, pre run off treatment must be done to remove suspended matter, oil and grease. The bore well for rain water recharging should be kept at least 5 m above the highest ground water table.

Adequate number of RWH pits will be constructed in the operational part of the building. RWH pits have been designed as per CGWB norms.

10. The ground water level and its quality would be monitored regularly in consultation with Central Ground Water Authority.

The ground water level and its quality is being monitored on a regular basis and due care is being taken for maintaining and conserving the ground water.

11. Traffic congestion near the entry and exit points for the road adjoining the proposed project site. Parking should be fully internalized and no public space should be utilized.

Project has proper adequate car parking space available for residential and visitors during the operation phase of the project and no traffic congestion will take place during the operation phase of the project. No public space will be

10

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

utilized for parking during operation phase.12. A report on the energy conservation

measures conforming to energy conservation norms finalized by Bureau of Energy Efficiency should be prepared incorporating details about building materials and technology, R&U Factors etc. and submit to the IA division of Environment Department, Haryana in three months time.

The report on the energy conservation measures conforming to energy conservation norms finalized by Bureau of Energy Efficiency will be prepared and the same will be submitted to the IA Division of Environment Department, Haryana.

13. Energy conservation measures like installation of CFLs/ TFLs for lighting the areas outside the building should be integral part of the project design and should be in place before project commissioning. Used CFLs and TFLs should be properly collected and disposed off / sent for recycling as per the prevailing guidelines/rules of the regulatory authority to avoid mercury contamination. Use of solar panel should be done to maximum possible extent.

Energy efficient luminaries like CFL and LED etc is integral part of the project and are in practice and will be encouraged further during the operational phase of the project.

14. Adequate measures should be taken to prevent odour problem from solid waste processing plant and STP

Adequate measures will be taken to prevent odour problem from solid waste processing plant and STP during operation phase.

15. The building should have adequate distance between them to allow movement of fresh air and passage of natural light, air and ventilation.

The architecture of the building has been planned to allow fresh air and natural light for the residential of the project.

16. The solid waste generated should be properly collected and segregated as per the requirement of the MSW Rules 2000. The wet garbage should be sent for composting and dry / inert solid waste should be disposed off to the approved site for land filling after recovering recyclable materials.

Solid waste will be collected by MCG authorized collector and disposed off securely at Municipal Waste Management Facility approved by the government authority.

PART B- GENERAL CONDITIONS

S.No

Conditions of Environmental Clearance Status of Compliance

I The environmental safeguards contained in the documents should be implemented in

Environmental safeguards as prescribed by the Ministry of Environment and Forests in the

11

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

letter and spirit. clearance document are being implemented in true spirit and will be proceed further.

II Provision should be made for the supply of kerosene or cooking gas and pressure cooker to the labours during construction phase.

Most of the labors for the construction of the project are being hired from the nearby villages through contractors. As per the provision, supply of kerosene or cooking gas and pressure cooker to the labors during construction phase will be done.

III Six-monthly monitoring reports should be submitted to the HSPCB and Regional Office, MOEF, GOI, Northern Region.

Six monthly environmental compliance reports are being submitted regularly to the HSPCB and SEIAA Haryana, MOEF GOI and Northern Region office, Chandigarh.

IV In case of any change in the scope of the project, the project would require a fresh appraisal by the SEIAA/SEAC, Haryana.

There is no change in the scope of the project.

V The SEIAA, Haryana reserves the right to add additional safeguard measures subsequently, if found necessary. Environmental Clearance granted will be revoked if it is found that false information has been given for getting the approval of this project.

Agreed. The project will accept any suggestion by the SEIAA for environmental safeguard for the welfare of the residential and society.

VI All other statutory clearances such as the approvals for storage of diesel from Chief Controller of Explosives, Fire Department, Civil Aviation Department, Forest Conservation Act, 1980 and Wildlife (Protection) Act, 1972, shall be obtained, as applicable by project proponent from the respective authorities.

Agreed. All other statutory clearances required for the project will be obtained from the concerned authorities. However, approval from AAI has been obtained.

VII These stipulations would be enforced among others under the provisions of Water (Prevention and Control) Act, 1981, The Environment Protection Act 1986, The Public Liability (Insurance) Act, 1991 and EIA Notification, 2006.

Same will be complied.

VIII The project proponent will not violate any judicial orders/ pronouncement issued by the Hon’ble Supreme Court / High Courts.

Agreed. The project proponent will abide by any judicial orders / pronouncements issued by the Hon’ble Supreme / High Courts.

IX Any appeal against this Environmental Clearance shall lie with the National Environmental Appelate Authority, if preferred, within a period of 30 days as prescribed under section 11 of the National Environmental Appellate Act 1997.

Agreed. Any appeal against this Environmental Clearance shall lie with the National Environmental Appellate Authority as per National Environmental Appellate Act 1997.

12

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

CHAPTER 3

DETAILS OF ENVIRONMENTAL MONITORING

3.1 AMBIENT AIR QUALITY MONITORING

3.1.1 AMBIENT AIR QUALITY MONITORING STATIONS

Ambient air quality monitoring has been carried out at one location near the site office to access the ambient air quality. This will enable us to have analytical understanding about air quality and the changes in the air environment in the study area with respect to the condition prevailing. The locations of the ambient air quality monitoring stations are given in Table 3.1

Table 3.1 Details of Ambient Air Quality Monitoring Station

S. No. Location Code Location Name / Description Environmental Setting1. AAQ-1 Near Site office Residential

3.1.2 AMBIENT AIR QUALITY MONITORING METHODOLOGY

Monitoring was conducted in respect of the following parameters

Particulate Matter 2.5 (PM 2.5) Particulate Matter 10 (PM 10 ) Sulphur Dioxide ( SO2) Nitrogen Dioxide (NO2) Ozone as O3

The said monitoring for all parameters were done with the method IS 5182 and UL/STM for 24 hours except O3 which was conducted for 1 hour. Grab sample of ambient air was taken to analyze while O3 was monitored on 1-hourly basis. This is to allow a comparison with the National Ambient Air Quality Standards. Colorimetric Measurement techniques have been used for sampling and analysis protocol for the estimation of Ozone as O3. The air samples were analyzed as per standard methods specified by Central Pollution Control Board (CPCB) and IS: 5182 (Pt-2, Pt-6 and Pt-23), UL/STM/A/11 and also UL/STM/A/09. The test protocols are given in Table 3.2.

13

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

Table 3.2 Techniques used for Ambient Air Quality Monitoring

S. No. Parameter Technique Technical ProtocolGuidelines for planning the sampling IS- 5182 (Part-14)

1 Particulate Matter PM 2.5 Fine particulate sampler APM 460, Gravimetric Method

UL/STM/A/11

2 Particulate Matter PM 10 Respirable Dust Sampler AAS 190, Gravimetric Method

IS- 5182 (Part-23)

3 Sulphur Dioxide Improved West and Geake method IS-5182 (Part-II)4 Nitrogen Dioxide Jacob & Hochheister IS-5182 (Part- VI)5 Ozone as O3 Colorimetric Measurement Method UL/STM/A/092

3.1.3 DISCUSSION ON AMBIENT AIR QUALITY IN THE STUDY AREA

PM 10 levels and PM 2.5 levels were within the permissible limit i.e. 100 µg/m3 while 60 µg/m3

(for residential, rural and other areas as stipulated in the National Ambient Air Quality Standards) and also the Limits for SO2, NO2 and O3 limits were within the permissible limit. Monitoring data for the ambient air quality is being described in table 3.3.

Table 3.3 Detailed monitoring data for Ambient Air Quality Monitoring

S. No. Parameter Units Results NAAQS TWA Technical Protocol1 Particulate Matter PM 2.5 µg/m3 28 60 24 hrs IS- 5182 (Part-23)2 Particulate Matter PM 10 µg/m3 66 100 24 hrs UL/STM/A/113 Sulphur Dioxide µg/m3 7.4 80 24 hrs IS-5182 (Part-II)4 Nitrogen Dioxide µg/m3 13.8 80 24 hrs IS-5182 (Part- VI)5 Ozone as O3 µg/m3 52 180 1 hrs UL/STM/A/09

3.2 AMBIENT NOISE MONITORING

3.2.1 AMBIENT NOISE MONITORING LOCATIONS The main objective of noise monitoring in the study area is to assess the present ambient noise levels in the nearby area of project site and project boundary due to various construction allied activities and increased vehicular movement. A preliminary reconnaissance survey has been undertaken to identify the major noise generating sources in the area. Ambient noise monitoring was conducted at one location about 1 meter distance from the boundary inside the project as given in Table 3.4.

14

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

Table 3.4 Details of Ambient Noise Monitoring Stations

S. No Location Code Location Name/Description Present Land use1. N1 Near site office; 1 m distance from the

boundary inside the project.Residential

3.2.2 METHODOLOGY OF NOISE MONITORING

Ambient noise level and source was monitored by using a calibrated Sound Level Meter. The instrument has a range to record noise level between 30 – 130 dB. Noise level was monitored inside the project premises at selected location for day and night, continuously for 24 hours.

During each hour Leq were directly computed by the instrument based on the sound pressure levels. Lday (Ld), Lnight (Ln) and Ldn values were computed using corresponding hourly Leq. Monitoring methodology used were IS 9876 & IS 9989.

3.2.3 AMBIENT NOISE MONITORING RESULTS

The time wise ambient noise monitoring results is summarized in Table 3.5.

Table 3.5 Ambient Noise Monitoring Results

Sr.No.

Test Locations

Day Time – dB (A) Night Time – dB(A)

Results

Limits as per CPCB

Guidelines Results

Limits as per CPCB Guidelines

1.Near site office at 1 m distance from the boundary inside the project.

47.6 55 <30 45

3.2.4 DISCUSSION ON AMBIENT NOISE LEVELS IN THE STUDY AREA

Day Time Noise Levels (Lday):The day time noise levels were found to be lower than the limit prescribed near the site office location.

Night Time Noise Levels ( Lnight):The night time noise levels were found much within the limit prescribed for Residential area i.e. 45 dB (A)

15

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

3.3 GROUNDWATER QUALITY MONITORING

3.3.1 GROUNDWATER QUALITY MONITORING LOCATIONS

Keeping in view the importance of groundwater as an important source of drinking water to the local population, sample of ground water was collected near the project site for the impact assessment of the project on the groundwater quality.

Water sample was collected from one location near the project site. The sample was analyzed for various parameters to compare with the standards for drinking water as per IS: 3025 (Part –I) for ground water sources. The details of water sampling are given in Table 3.6.

Table 3.6 Details of Water Quality Monitoring Station

S. No Location Code Location Name / Description1. GW 1 Near Project Site

3.3.2 METHODOLOGY OF GROUNDWATER QUALITY MONITORING

Sampling of ground water was carried out on 31st March, 2015. Samples were collected as grab sample and sampling forms were filled in as per the sampling plan. Grab sample were drawn, kept in a clean and dry container and preserved in ice box in the manner, as prescribed in IS 3025 (Part 1). The samples were transported to the laboratory for further analysis. Soon after the completion of sampling, chain of custody sheets for the samples were filled in and then were transported by road to Ultratec Labs Pvt. Ltd, Gurgoan for further analysis. Proper care was taken during packing and transportation of samples. All the samples reached the central laboratory within the holding times for different parameters. After ensuring the same the samples were forwarded immediately for analysis.

The samples were analyzed as per the standard procedures specified in ‘Standard Methods for the Examination of Water and Wastewater’ published by American Public Health Association (APHA) and CPCB. The analytical techniques and the test methods adopted for testing of ground water are given in Table 3.7.

3.3.3 GROUNDWATER QUALITY MONITORING RESULTS

The detailed groundwater quality monitoring results are presented in Table 3.7

16

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

Table 3.7 Groundwater Quality Monitoring Results

S. No Parameter Unit Results Test Protocol

1. Colour Hazen <5 IS:3025(PART-4)2. Odour … Agreeable IS 3025(PART5)3. pH value at 25˚C … 7.44 IS 3025(PART 11)4. Turbidity NTU 1.1 IS:3025(PART-10)5. Total dissolved Solids mg/l 1312 IS:3025 Part 166. Total Hardness as CaCo3 mg/l 439 IS 3025( Part 21)7. Calcium as Ca mg/l 62 IS:3025(PART-40)8. Magnesium as Mg mg/l 69 IS:3025 (Part 46)9. Total Alkanity as Calcium Carbonate mg/l 322 IS:3025(Part 23)10. Chloride as Cl mg/l 637 IS:3025(PART-32)11. Sulphate as SO4 mg/l 47 IS:3025(Part 24)12. Iron as Fe mg/l 0.85 IS:3025 Part 5313. Fluoride as F mg/l 1.33 IS:3025 Part 6014. Nitrite Nitrigen as NO2-N mg/l <0.5 IS:3025 Part 3415. Total Phosphorous as P mg/l 4.1 IS:3025 Part 3116. Chemical Oxygen demand mg/l 15 IS:3025 Part 5817. Sodium as Na mg/l 82 IS:3025 (Part 45)18. Total Coliform* MPN/100ML ND IS:1622-198119. Boron* mg/l <0.1 IS:3025 Part 5720. Nitrite as NO3 * mg/l 0.8 IS:3025 (PART 34)

*Not covered under NABL scope. 3.3.4 DISCUSSION ON GROUNDWATER QUALITY IN THE STUDY AREA

The ground water quality in the project area is observed to having total alkalinity up to 322mg/l which is slightly higher than desirable limit of 200 mg/L. Total dissolved solids in the ground water is 1312 mg/L which is higher than the prescribed limit of 500 mg/L.

3.4 SOIL MONITORING

3.4.1 SOIL MONITORING LOCATIONS

The objective of soil monitoring is to identify the impact of ongoing project activities on soil quality and also predict impacts, which have arisen due to execution of various constructions and allied activities and in consonance of the above, take corrective measures. Accordingly, a study of assessment of the soil quality has been carried out.

To assess impacts of ongoing project activities on the soil in the area, the physic-chemical characteristics of soils were examined by obtaining soil samples and analysis of the same. One sample of soil was collected from back side of the site office from a depth of approximately 6’’

17

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

to 9” below the earth surface for studying soil characteristics, the location of which is listed in Table 3.8.

Table 3.8 Details of Soil Quality Monitoring Location

S. No Location Code Location Name / Description1 S1 Back side of site office

3.4.2 METHODOLOGY OF SOIL MONITORING

Samples of top soil, from a depth of nearly 6″-9″ below the surface, were collected from the project premises. The samples were preserved in clean and lock-in polyethylene and transported to the laboratory for testing. Testing was performed with reference to the standard methods prescribed in UL/SOP/EX/02.

The samples were analyzed as per the established scientific methods for physic-chemical parameters. The heavy metals have been analyzed by using Atomic Absorption Spectrophotometer and Inductive Coupled Plasma Analyzer.

3.4.3 SOIL MONITORING RESULTS

The physic-chemical characteristics of the soil, as obtained from the analysis of the soil sample, are presented in Table 3.9.

Table 3.9 Physico-Chemical Characteristics of Soil in the Study Area

S. No

Parameter Unit Observed Value Test Protocol

1. pH value at 25˚C .. 8.16 IS: 2720 Pt 262. Conductivity at 25˚C µmhos/cm 664 IS: 2720 Pt 213. Moisture Content % 11.2 IS : 2720 Pt 24. Texture based soil

classification- Sandy Clay Loam UL/SOP/EX/23

5. Water Holding Capacity % 31 UL/SOP/EX/136. Phosphorous as P2 O5 Kg/Hectare 13.7 UL.STM.S.047. Potassium as K2 O Kg/Hectare 4.4 UL.STM.S.058. Nitrogen as N Kg/Hectare 37 UL.STM.S.039. Calcium Carbonate % 13.1 IS: 2720 Pt 2310. Organic Content % 0.4 IS:2720 Pt 2211. Soluble Sulphate % 0.28 IS: 2720 Pt 2712. Total Soluble Solids - Normal IS: 2720 Pt XXI

18

Project: “Atharva” Sec 109, Village-Panwala, Khusrupur, Gurgoan Haryana

3.4.4 DISCUSSION ON SOIL CHARACTERISTICS IN THE STUDY AREA

The soil in study area is characterized by slightly alkaline in nature. The soil quality in the project area has not been affected by the project activities. Desirable range of the pH value is 6.0–7.5 for horticultural purpose. pH 6.6 – 6.9 is slightly acidic, 7.1 – 8.5 is moderately alkaline, >8.5 is strongly alkaline.

19