Manual de Operación / Operating Manual ZIGOR SOLAR XTR3 Inversor Solar Trifásico / Three Phase Solar Inverter www.zigor.com

Upload: others

Post on 10-Jun-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Manual de Operación / Operating Manual

ZIGOR SOLAR XTR3 Inversor Solar Trifásico / Three Phase Solar Inverter

www.zigor.com

Page 2: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR i

Index

1 PRECAUTIONS ............................................................................................................................ 1

1.1 General precautions ................................................................................................................................... 11.2 Storage and Transport Precautions ......................................................................................................... 21.3 Environmental precautions ....................................................................................................................... 3

2 GENERAL DESCRIPTION ............................................................................................................ 42.1 Introduction ................................................................................................................................................ 42.2 Main features .............................................................................................................................................. 4

2.2.1 Build characteristics ............................................................................................................ 42.2.2 Description of the unit ......................................................................................................... 52.2.3 Design Life .......................................................................................................................... 6

3 INSTALLATION ............................................................................................................................ 73.1 Reception of material ................................................................................................................................. 73.2 Installation conditions ............................................................................................................................... 83.3 Assembling the unit ................................................................................................................................... 9

3.3.1 Installation of the Assembly Plate ....................................................................................... 93.4 Connection ................................................................................................................................................ 10

3.4.1 AC Supply Connection ...................................................................................................... 103.4.2 Connecting the (DC) Generator ........................................................................................ 12

3.5 Optional coupling of ZIGOR SOLAR PCM3 ........................................................................................... 154 CONTROL PANEL FUNCTIONS ................................................................................................ 20

4.1 Handling Menus ........................................................................................................................................ 224.1.1 Measurements menu ........................................................................................................ 234.1.2 Settings menu ................................................................................................................... 244.1.3 Alarms menu ..................................................................................................................... 254.1.4 Control menu .................................................................................................................... 26

5 STARTING UP THE ZIGOR SOLAR XTR3 INVERTER .............................................................. 275.1 Operation and installation instructions ................................................................................................. 275.2 Daily inverter’s turn on and turn off ....................................................................................................... 305.3 Inverter’s manual stop ............................................................................................................................. 30

6 COMMUNICATIONS INTERFACE .............................................................................................. 316.1 Access remote WEB (http) ...................................................................................................................... 31

6.1.1 Configuration by DHCP ..................................................................................................... 316.1.2 Configuration without DHCP ............................................................................................. 316.1.3 Configuration for external connection ................................................................................ 316.1.4 Configuration for inverter-computer direct connection ....................................................... 326.1.5 Login page ........................................................................................................................ 356.1.6 Start menu ........................................................................................................................ 356.1.7 Status menu ...................................................................................................................... 366.1.8 Energy menu .................................................................................................................... 376.1.9 Settings menu ................................................................................................................... 376.1.10 Alarm menu ................................................................................................................... 386.1.11 Control menu ................................................................................................................. 396.1.12 Network menu ............................................................................................................... 40

6.2 Communications protocol ....................................................................................................................... 406.2.1 SNMP Communication Protocol ........................................................................................ 406.2.2 Modbus Communication Protocol ...................................................................................... 41

7 TROUBLESHOOTING ................................................................................................................ 428 TECHNICAL SPECIFICATIONS ................................................................................................. 449 WARRANTY ............................................................................................................................... 46

Page 3: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

ii © ZIGOR

© 2016, ZIGOR All rights reserved. The total or partial reproduction of this Operating Manual, its transmission of any type or by any means, be this mechanical or electronic, by means of photocopies, registration or other information storage or recovery procedure, without the permission of the editor, is totally forbidden.

The contents of this manual are exact at the time it was printed. However, with the intention of complying with our aim of continuous development and improvement, the manufacturer reserves the right to modify product specifications, its operation or the contents of the Operation Manual without prior warning.

Page 4: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 1

1 PRECAUTIONS 1.1 General precautions For your own safety and that of the unit, you must read and understand the instructions contained in this document before starting work. Keep these instructions in a place accessible to all the personnel who work with the unit so that these may be consulted. Only expert and duly authorised personnel may operate our units.

Danger warnings. When handling or gaining access to the interior of the equipment, please remember that some parts may be live. Pay special attention to soldering points, printed circuits, connecting terminals, relay contacts, etc. Before opening the equipment, disconnect

the voltage of all poles (both alternating and direct) and wait at least 10 minutes for the internal condensers to discharge. Arbitrary modifications are forbidden. The unit must not be subjected to any modification regarding its construction or safety without ZIGOR’s express consent. Any modification shall free ZIGOR of any responsibility for any damage caused as a result of the modification. In particular, all repair work, soldering of printed circuit boards and replacing of components, modules and printed circuit boards, without the express authorisation of ZIGOR, is forbidden. Should spare parts be used, only ZIGOR original parts shall be utilised. Only ZIGOR authorised installers may open the connection box. Do not open the connection box when the Inverter is powered up. Only Maintenance personnel are authorised to open the top (Power stage) of the ZIGOR SOLAR XTR3 Inverter; if this is not under low voltage conditions. ZIGOR shall not accept any responsibility for any inadequate, negligent or incorrect installation of the equipment. Use the unit for the purpose for which it was designed. The system supplied must be used only for the purpose for which it was designed. Any other use is strictly forbidden. ZIGOR cannot accept responsibility for any damage that might result from its use for any other purpose. In such cases, the user shall assume exclusive responsibility for any risk. The use for which the unit was designed is defined in the documentation. The system shall be exposed only to admissible environmental conditions. These are defined in the technical details provided for the equipment. Please follow the indications set out below to operate under conditions of complete safety: The System must be checked once the installation has been completed by a qualified technician

and before being put into operation. Should these indications not be adhered to, the warranty shall be considered null and void.

These units do not contain parts usable for other purposes by the user. Do not power up the device before a technician has checked it. The unit does not contain any user repairable or replaceable elements. In the case of any

malfunction or problems operating the unit, please contact ZIGOR. Do not place the ZIGOR SOLAR XTR3 near power magnets as this might cause a malfunction. Do not block or cover the ventilation grills in the housing. Should you have any problems with the contents of this manual, you must ask ZIGOR for

assistance. The ZIGOR SOLAR XTR3 is designed in accordance with current Spanish legislation. Check

these regulations against those corresponding to the country in which the unit is to be installed and against the most restrictive regulations of the electricity supplier.

Once installed, the system does not need to be opened. It operates completely autonomously. Work inside the cabinet should be undertaken only by qualified personnel who are familiar with

the safety measures to be applied and the specific technical characteristics of the unit.

Page 5: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

2 © ZIGOR

Before touching any live parts, you must check that the unit is not powered up. This system has been designed for industrial and/or domestic-commercial use. During assembly work, start-up or maintenance, wear goggles to avoid any damage to your eyes

due to accidental electric arcing. Once the system is exposed to the light, the equipment supplies a DC voltage to ECP.

Connecting PV modules. Before connecting the PV modules, you must check that the voltage parameters specified in the manufacturer’s technical documentation correspond to the real parameters. When you verify the voltage reading, remember that PV modules supply a higher no-load voltage when the temperature is low and sun levels remain unchanged. At -4º F (-20º C) the open circuit voltage of PV modules must never exceed 500 V. The PV module datasheet will indicate the applicable temperature factors in order to determine the theoretical voltage in an open circuit at -4º F (-20º C). If the PV modules have an open circuit voltage of 500 V, it is forbidden to connect the PV module. Failure to respect these storage regulations may lead to a withdrawal of the product warranty. The PV Inverter is fitted with a residual current monitoring unit in accordance with VDE0126-1-1. This device measures the earth fault current of the PV and prevents the PV Inverter from supplying the grid in the case of an earth fault.

1.2 Storage and Transport Precautions The place where the equipment is to be stored must allow the material to be protected from the weather and risk of flooding or contact with water. The material shall be protected from any risk of overheating due to exposure to direct sunlight or through windows. The recommended storage temperature is from 15ºC to 25ºC. The recommended relative humidity is from 30% to 90%. To avoid any risk of mechanical shock, do not stack the packages. These must be placed in accordance with the silkscreen printed details on the boxes used for packaging. Failure to respect these storage regulations may lead to a withdrawal of the product warranty. ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They must not be turned over. Any handling of ZIGOR’s inverter systems is subject to this standard. Inside ZIGOR SOLAR XTR3 systems there are components that are very sensitive to impact and being placed in an incorrect position. Inadequate handling of the equipment may cause damage not included within the warranty.

ANY FAILURE TO RESPECT THESE PRECAUTIONS MAY RENDER THE WARRANTY NULL AND VOID

Page 6: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 3

1.3 Environmental precautions

ZIGOR, in accordance with the exceptions detailed in the First Additional Provision of Law 11/1997 on commercial or industrial containers, declares that the end user, being responsible for container waste and used containers, must deliver these in appropriate condition for reuse to an authorised recovery or recycling entity or valuer.

System subassemblies are recyclable products. In order to protect the environment, manage these in accordance with current environmental regulations and requirements in force in each country or community. If you are in any doubt please consult the manufacturer.

The drawing of a crossed out wheeled container on the product or in the documentation or packaging means that the electrical-electronic components and batteries must be disposed of separately at the end of their service life. This requirement is applied in the European Union and in those locations where individual disposal systems are available. Do not dispose of these components in the form of unsorted municipal waste.

Page 7: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

4 © ZIGOR

2 GENERAL DESCRIPTION 2.1 Introduction The ZIGOR SOLAR XTR3 is a single phrase solar inverter. It is responsible for converting the direct current generated by photovoltaic panels into alternating current for injection into the electrical power distribution grid. The ZIGOR SOLAR XTR3 can be used both to back up consumption and as a system to produce electricity. In the first case, if the electrical power consumption of the location in which the inverter is installed is lower than the power consumed by this unit, excess production is delivered to the grid. If this consumption exceeds production, the energy required to complete the balance is taken from the electricity grid. In the second case, all the power generated by the equipment is injected into the electricity grid. In both cases, the appropriate power measurement systems must be installed for each use. The installation of the ZIGOR SOLAR XTR3 and its connection to the electricity grid shall be done in accordance with local regulations and may require the installation of adequate electricity consumption measuring devices. The PV inverter only operates when it is connected to the electrical power distribution line and cannot operate as a stand-alone unit.

Fig. 2-1 Simplified diagram of the inverter connection

2.2 Main features • System is designed transformerless: remember that the photovoltaic modules must be A class

according to the standard IEC 61730 • Euro efficiency upper to 96%. • High input range of voltage: from 300Vdc to 800Vdc. • MPPT efficiency upper to 99%.

• Firmware can be update easily. • 3 MPPT independent inputs. • Detection modes of Islanding failure: active and passive.

• Internal GFCI (Ground fault circuit interrupter).

2.2.1 Build characteristics The cabinet of the ZIGOR SOLAR XTR3 is built for operating indoors or outdoors. The protection level of this system is IP54. The most important build characteristics of the equipment are as follows: • IP54 enclosure. • Alternating current output: 400Vac 50/60Hz. • Industrial and domestic range components. • Optimised, intelligent refrigeration system. • The unit shall be installed on a wall. • All the connections enter at the bottom of the cabinet.

Page 8: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 5

Fig. 2-2 Front View Fig. 2-3 Lower View

Dimensions ZIGOR SOLAR XTR3

Length (mm) 480

Height (mm) 665

Width (mm) 220

2.2.2 Description of the unit The cabinet of the ZIGOR SOLAR XTR3 can manage a maximum of 6 series of panels of the photovoltaic field. The ZIGOR SOLAR XTR3 cabinet has the following parts, referenced in the enclosed figure:

Fig. 2-4 ZIGOR SOLAR XTR3 Unit Description

Page 9: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

6 © ZIGOR

1. 6 pairs of DC terminals: each pair consists in a terminal for the positive pole and another for the negative pole.

2. Fans: to obtain optimised, intelligent refrigeration. The system has 4 fans to eliminate the hot thanks to a sink. When the temperature reaches 60ºC the fans will activate automatically.

3. Communications cables enclosure: Input of wires of the communication port. 4. AC Output cables enclosure: Security enclosure to ensure the AC wires. 5. Display: This displays information on the operational status of the PV Inverter.

2.2.3 Design Life ZIGOR guarantees that ZIGOR SOLAR XTR3 units are designed for a lifetime not lower than 10 years. During that time, ZIGOR guarantees a complete assistance in the following cases:

• Repairs.

• Provision and replacement of components. • Assistance and updating of the unit’s software.

Page 10: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 7

3 INSTALLATION 3.1 Reception of material Make a visual check that the location is appropriate. This must be clean, without drips and with good ventilation.

On receiving the material, a visual inspection should be made in order to detect any anomalies that may have occurred during transport.

Checking the material

List and check all the items indicated on the delivery note. Should any component be missing, notify the forwarding agent within the established deadline. Extract all parts from the packaging and examine the unit for any damage caused during transport. Report any damage to the forwarding agent and ZlGOR. Check that the material delivered corresponds to the delivery note. Check the manufacturer's label placed at the rear or on one side of the unit. Responsibility for the loss or damage of Products shall transfer to the Customer from the moment ZIGOR, places these at the location indicated by the Customer. Check the contents of the package. The standard contents must include: • 1 Operating Manual • 6 sets of pairs of PV connectors 1 • 1 set of accessories for the assembly frame 3

Fig. 3-1 ZIGOR SOLAR XTR3 Material

NO CLAIMS WILL BE ACCEPTED IF, 24 HOURS FOLLOWING THE DELIVERY OF THE GOODS, NO NOTIFICATION OF RECEPTION OF MATERIAL IN BAD CONDITIONS HAS BEEN RECEIVED AND IF THIS CIRCUMSTANCE IS NOT NOTIFIED TO THE FORWARDING AGENT AT THE TIME OF DELIVERY.

Page 11: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

8 © ZIGOR

3.2 Installation conditions The ZIGOR SOLAR XTR3 is a cabinet with IP54 protection and therefore it can be installed indoors and outdoors. The unit must be mounted on a wall with the packing glands at the bottom. The unit must be installed by ZIGOR personnel. Due to its IP54 protection, the unit can be installed outdoors, but it is not submersible. In order to assure the maximum service life of the unit, the installation must have the following characteristics: • The unit must be wall mounted. • The Inverter is heavy. Bear this in mind when choosing the location and the installation method. • Place the system on a plain, stable surface free of vibrations and of sufficient strength to bear the

weight of the unit. • Ensure the appropriate height to facilitate connections. • The location must be such that excess humidity and high level heat sources can be avoided.

o Avoid direct rainfall. o Prevent direct exposure to the sun. o Avoid flood-prone areas.

• Protection against atmospheric agents. Elements susceptible to electrical discharges. • Optimum atmospheric operating temperature between +20 ˚C and +25˚C. • Proximity to magnetic fields and high-power lamps must be avoided. • Do not expose to gases or corrosive products. The PV Inverter and has been designed to be installed vertically on a wall as indicated in the following drawing. Never install the PV Inverter horizontally or in such a way that it tilts forwards.

Fig. 3-2 Placing the ZIGOR SOLAR XTR3

Install the inverter vertically

Never install the PV Inverter horizontally or tilted forward. When choosing the location, ensure that there is sufficient space to allow heat dissipation. Under normal operating conditions, the following guide must be applied in order to keep a free space around the Inverter.

Minimum tolerance Sides 20 cm Top part 20 cm Bottom part 20 cm Front part 5 cm

Page 12: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 9

3.3 Assembling the unit We recommend you to use the wall bracket supplied in order to mount the ZIGOR SOLAR XTR3 Inverter. For vertical assemblies and installations on solid concrete or concrete block walls, take into consideration the weight of the Inverter when selecting the assembly materials.

Fig. 3-3 Rear of ZIGOR SOLAR XTR3

If you do not wish to use the supplied assembly plate as a template, observe the dimensions indicated in the following illustration. The Inverter assembly procedure, using the assembly plate, is described in the following pages.

3.3.1 Installation of the Assembly Plate Step 1. Place the assembly plate. In order to indicate the position of the holes, you can use the assembly flange as a template.

Page 13: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

10 © ZIGOR

Fig. 3-4 ZIGOR SOLAR XTR3 support plate

Step 2. Drill four holes marked on the wall. Insert the four snap bushings, now insert the screw and tighten them. Step 3. Now put the PV Inverter on to the plate. Tight the below screw to ensure the union between the inverter and mounting bracket

Fig. 3-5 ZIGOR SOLAR XTR3 wall mount

Step 4. Ensure that the PV Inverter is secured firmly to the plate.

Fig. 3-6 ZIGOR SOLAR XTR3 wall mount detail

3.4 Connection

3.4.1 AC Supply Connection In order to connect the AC cable, proceed as follows: Step 1. Measure the grid voltage and frequency. * The voltage and frequency of the grid may vary from one country to another. Step 2. Before wiring the ZIGOR SOLAR XTR3 Inverter, ensure that the primary switch box circuit breaker is in the OFF position. Place the aforementioned circuit breaker in the ON position only when all the wiring has been completed according to instructions. Step 3. Find the recommended AC-output cable size:

Page 14: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 11

Do not use cables where losses will exceed 1%. R (L1), S (L2) , T (L3), N and Gnd : 4/6mm2 cross-sectional area wire.

Step 4. Remove the bottom cover of the inverter where AC terminals are by unscrewing the 3 screws that hold it, 2 near the fans and the other in the opposite side (as it is illustrated in the below figure). Due to the air seal located between the inferior and superior cover, placed to avoid the entrance of liquids in the system, the extraction of the inferior cover can be difficult, for it, also clears the screws of the indicated superior cover n the following image and this one will leave with extreme facility.

Fig. 3-7 Location of the screws

Step 5. Insert AC cables through the gland located on the left bottom corner, through rubber bushing, and AC-output cover. Then, insert Ground through the same enclosure. Step 6. The choice of cable together with the way it is routed, the ambient temperatures the inverter operates at, and other underlying conditions determines the maximum AC fuse protection used for the inverter.

Fig. 3-8 Cables AC

*In order to avoid any danger of electrical shock, ensure that the earth cable is connected correctly to earth before putting the PV Inverter into operation.

Page 15: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

12 © ZIGOR

NOTE: Remember that voltage and frequency of the grid depend on each country. To configure the system to the grid, go to the 5th section of this manual. Step 7. Fix the R (L1), S (L2), T (L3), N and Gnd in the block of terminals. Please note that all 5 wires should be firmly connected. Connect the wires based on the polarity that is indicated on the terminal block.

Fig. 3-9 AC termianals detail

Step 8. Verify the phases and GND wires are fimly tighten. Step 9. If it would be necessary, fix another earth cable on the frame. Step 10. Fix the AC output cover back with a screwdriver and twist on the connector cable gland to lock the bushing and cable

3.4.2 Connecting the (DC) Generator The PV Inverter can connect up to 3 MPPT strings with a uniform structure (modules of the same type, orientation, inclination and identical number). The unit has six DC plugs (two for each string) for connecting PV modules. The connection cables of PV Modules must also be equipped with this kind of plug. The following table shows the specifications for the DC connectors. Though the section of the DC wires can be until a maximum of 10mm2, ZIGOR has designed this system to use a section of DC wires of 4mm2.

Connector type Connection Cable Section Max. Admissible Current

Female panel receiver

Ø 4 - 8 mm connection system 1.5 - 10 mm2

40A

Page 16: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 13

Male panel receiver

Ø 4 - 8 mm connection system 1.5 - 10 mm2

40A

Fig. 3-10 Detail of Quick Connections

* In order to connect the PV generator to the PV Inverter input and in order to determine the number of panels required in the PV string (panels connected in series) refer to the following three points: 1. To prevent any damage to the Inverter, ensure that the output of the PV generator and that the maximum open circuit voltage (OCV) of each PV string are never in excess of 1000 VDC under any circumstance because this situation would damage the PV Inverter. 2. Do not exceed the maximum short-circuit current of the generator indicated in the ZIGOR SOLAR XTR3 Inverter. 3. In order to attain maximum generator performance, ensure that the voltage at maximum power does not fall below 300VDC and that this does not exceed 800 VDC in accordance with most conditions. SB: The positioning of the photovoltaic connectors that are in Figure 3.9, does not represent all the models of ZIGOR SOLAR XTR3, but however if it represents with better detail the physical difference between the male connectors and females.

Step 1: Check that the polarity of the PV generator connectors is correct and that these do not exceed the maximum voltage of the string.

In order to wire the PV generator to the ZIGOR SOLAR XTR3 Inverter, follow these steps:

Step 2: Connect the POSITIVE wire (+) from PV string no. 1 to the positive quick connect wire (+) of the PV Inverter. Step 3: Connect the NEGATIVE wire (+) from PV string no. 1 to the negative quick connect wire (-) of the PV Inverter. Step 4: If necessary, repeat step 2 and step 3 for the other PV strings. Ensure that the wires are placed correctly.

Page 17: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

14 © ZIGOR

DC Photovoltaic system with DC breaker:

Fig. 3-11 DC Connections with DC breaker

DC Photovoltaic system without DC breaker:

Fig. 3-12 DC Connections without DC breaker

Page 18: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 15

Step 1. Before disconnecting the ZIGOR SOLAR XTR3 inverter, make sure that it is off. In order to disconnect the AC cable, proceed as follows:

Step 2. Place the circuit breaker of the primary switch box in the OFF position and ensure that there is no voltage. Step 3. Press the lugs of each connector in order to remove these one by one. Should it be necessary, use a flat screwdriver or similar tool in order to press these lugs.

Fig. 3-13 DC Connectors

Note: Remember that though the systems is off, can be exist voltage in the connectors

WARNING

Remember, that though the system is off, once the photovoltaic system is exposed to the light, can be exist voltage in the DC connectors, supplies a DC voltage to the ECP.

WARNING

If it wishes to disconnect DC cables of the entrance of the inverter for its maintenance or other reasons; please, disconnect in the first place the AC claves. A failure can cause to damage the photovoltaic panels due to an inverse current or a surge.

WARNING

Remember, that the system is a transformerless equipment, then, the photovoltaic modules must be A class according to the IEC 61730 standard

3.5 Optional coupling of ZIGOR SOLAR PCM3 ZIGOR SOLAR XTR3 inverter can be installed beside ZIGOR SOLAR PCM3 equipment. This equipment is a direct hybridization system of photovoltaic power with network and/or genset. Refer to 302862MAOP OPERATION MANUAL ZIGOR SOLAR PCM1/PCM3 for more information about this option. A figure indicating the different parts of the ZIGOR SOLAR PCM3 is shown below:

Page 19: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

16 © ZIGOR

Fig. 3-14 Fig. 3-15

Inside the Zigor Solar PCM3, the main parts are the transmission board, protection fuses and connection terminals. Each one of the aforementioned parts carry out a number of specific functions that are explained below.

Fig. 3-16

In order to be able to carry out the cabling correctly, the Zigor Solar PCM3 three phase is provided with the following inputs. As shown in the Fig. 3-16, the unit is prepared for the connection of the communications cables that will be connected to the transmission board, as well as the wiring of the current and supply transformers. The communications cable will be connected to the transmission board of ZIGOR SOLAR PCM3. To do this, as can be seen in the Fig. 3-17, it is necessary to connect a telephone cable with the RJ12 terminal to the CON5 terminal block if a crossover cable is involved, for direct cable connect to the CON4. The other end of the aforementioned cable must be connected to the receiver board of ZIGOR SOLAR XTR3, placed inside the equipment (see Fig. 3-18). The maximum total distance for the aforementioned cable will be 1000 m. For greater distances please contact Zigor.

Fig. 3-17 Transmission board of ZIGOR SOLAR PCM3 Fig. 3-18 Receiver board of ZIGOR SOLAR XTR3

For connections with a crossover cable, follow the principle schematic layout below:

Page 20: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 17

Fig. 3-19 Fig. 3-20

Should it be preferred to use the direct cable, the connection may be made as below:

Fig. 3-21 Fig. 3-22

For operating in the three-phase case, current transformers shall be connected to each one of the three phases, and the output of the aforementioned transformers shall be connected to the ZIGOR SOLAR PCM3. The maximum distance between the ZIGOR SOLAR PCM3 and current transformers shall be less than 10 m. The required communications cable is a standard telephone cable with a RJ-12 connector. The current transformers used here are supplied by Zigor. The gauge of the aforementioned current transformers, supplied by Zigor, shall be determined In accordance with the maximum line power. The connection shall be made in the following manner:

Page 21: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

18 © ZIGOR

Fig. 3-23

The outputs of the current transformers must be connected to the connection terminals strip inside the ZIGOR SOLAR PCM3. The aforementioned terminals strip and the place where each connection must be made are detailed below.

Fig. 3-24

The connections in the protection terminal strip must be made as shown in Fig. 3-24. It should be pointed out that in order to ensure that the system operates correctly the phases must be connected in the correct order; otherwise the measurements carried out by the ZIGOR SOLAR PCM3 will be incorrect. The auxiliary input is provided for those uses in which there is an electricity grid and a power generator operating alongside. When the generator is in operation, the inverter will adopt an operating mode that will allow it to adapt more quickly to the grid conditions generated by the generator. When working in a grid, it will behave automatically in compliance with the established Grid Code. Having completed the steps set out above, the installation must follow the diagram shown in Fig. 3-25.

Page 22: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 19

Fig. 3-25

Connecting the cables coming from current transformers, each pair of cables must be crossed, as shown in the figure. The same issue is recommended for power cables.

Fig. 3-26 Fig. 3-27

Page 23: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

20 © ZIGOR

4 CONTROL PANEL FUNCTIONS There is an LCD screen on the front of the ZIGOR SOLAR XTR3 Unit. This provides you with details of the status of your Inverter and you can use this as a Command and Control element. The dial features:

• 128x64 point LCD graphics display. • 5-key keyboard.

• Indication with three LED diodes.

Fig. 4-1 Solar Inverter Dial

On the left of the display there are three LEDs that indicate the operating conditions of the inverter. The information to which these refer is described below:

Led no. On Blinks Off

(Green) Start Start- up process Non energised

(Amber) The external conditions are not correct for the start up Adequate external

conditions

(Red) Serious error No serious error

Table 4 Luminous indicators

Page 24: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 21

An example of the presentation of the LCD display, describing the information it shows, is given below.

The keys we will use to browse the system menus are located the right-hand side near the display (indicated with number ):

Key Use

Used to browse upwards through the menus and to increase the values of the specifications.

Used to browse downwards through the menus and to reduce the values of the specifications.

Key used to access submenus.

Key used to go back or return from the submenus.

Acceptance and confirmation key.

Hour

Events indication There are no active events Unrecognized events actives (flashes) Recognized events actives (flashes)

Generated Active Power

Charge state

DC input voltage

Page 25: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

22 © ZIGOR

4.1 Handling Menus The most efficient way of browsing the different system menus is shown below: In addition to the icons described above, the following descriptive icons are used for browsing:

PV1 / PV2 / PV3 INPUT

INVERTER OUTPUT

CONSOLE EVENTS HISTORY

STATUS

CONSOLE

Information

INPUT

PV1

Information

PV2

Information

PV3

Information

INVERTER

Information

OUTPUT

Information

Page 26: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 23

SETTINGS

CONSOLE

Information

INPUT

Information

INVERTER

Information

OUTPUT

Information

ALARMS

ALARMS

Information

HISTORY

Information

CONTROL

Information

4.1.1 Measurements menu CONSOLE STATUS:

Description LCD message

Today's date Date

Production Code Pro Cod

Software version Soft Ver

Hardware version Hard Ver

Inverter status Status

IP IP

Subnet mask Mask

Inverter Gateway G.W

Primary domain server pDNS

INPUT STATUS:

Description LCD message

Page 27: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

24 © ZIGOR

Photovoltaic input voltage Ve

Photovoltaic input current Ie

Isolation Resistance Rais

Low Isolation Resistance Rais low

INVERTER STATUS

Description LCD message

Solar inverter model Model

Software version Version

Equipment status Status

R Output current R Iout

S Output current S Iout

T Output current T Iout

R Output power R Pout

S Output power S Pout

T Output power T Pout

Output power Pout

Nominal output power Pout Nom

Inverter load Charge

Sink temperature Tsink

Fan operation Fan

OUTPUT STATUS:

Description LCD message

R AC grid voltage R Vgrid

S AC grid voltage S Vgrid

T AC grid voltage T Vgrid

AC grid frequency Fgrid

Peak output power Peak power

Today's energy E-Today

Accumulated energy E-Total

Reactive output power R Qout R

Reactive output power S Qout S

Reactive output power T Qout T

4.1.2 Settings menu CONSOLE STATUS:

Page 28: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 25

Description LCD message

Console Access level Level

Display language Language

ModBus Address MB Address

ModBus Mode MB Mode

ModBus Velocity MB Baudios

ModBus Data Bits MB BitData

ModBus Parity Bit MB Parity

ModBus Stop Bits MB BitStop

MPPT mode configuration MPPT mode

Display contrast configuration Contrast

Display illumination configuration Backlight

Buzzer configuration Buzzer

Type of tone Tone

Volume selection Volume

System date Date

Time zone configuration DST Zone

Type of currency Currency

Money Cash

Dynamic host configuration protocol Enable DHCP

IP address IP address

Mask Subway Mask

Router Router

Configure primary DNS Primary DNS

INPUT STATUS:

Description LCD message

Number of active MPPTs N PV

INVERTER STATUS:

Description LCD message

System model Model

OUTPUT STATUS:

Description LCD message

Grid Code Grid Code

4.1.3 Alarms menu EVENT STATUS:

Page 29: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

26 © ZIGOR

Description LCD message

Active events Active

Events not recognised by the system No recog.

Events recognised by the system Recognised

EVENT LOG:

Description LCD message

Number of events

Events

Active events Active

Events not recognised by the system No recog.

Events recognised by the system Recognized

Information events Informative

4.1.4 Control menu ORDER STATUS:

Description LCD message

Equipment start-up Status

Equipment reset Reset

Events deletion Events

Set up IP, default IP or new IP Net

Page 30: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 27

5 STARTING UP THE ZIGOR SOLAR XTR3 INVERTER Before putting the ZIGOR SOLAR XTR3 Inverter into operation: • Ensure that the enclosure cover is securely bolted. • Ensure that the AC circuit breaker is in the OFF position. • Ensure that the DC cables (PV strings) are connected. • Ensure that the AC wire (grid) is connected correctly.

5.1 Operation and installation instructions 1. Establish the voltage of the PV strings by connecting the DC circuit breaker. The PV Inverter

display automatically lights when receives a DC voltage higher than 300 VDC. 2. In the LCD screen, after the ZIGOR brand appears, the screen will show the following boot menu.

Fig. 5-1 Boot menu

3. Pressing the right scroll button of the display , the screen will show the following menu (Fig. 5-2). We can choose different languages. Choose your correct language using the scroll buttons

up and down . When the correct language has been selected, press ok button . To

continue with the inverter configuration; please, press the right scroll button .

List of selectable languages:

1. English 2. French 3. Portuguese

4. English 5. French 6. Portuguese

Fig. 5-2 Language choice

4. On the next screen, four different types of possible MPPTs could be chosen (depends on the

photovoltaic panels configuration). After choosing, press the confirmation button to accept

and the right scroll button to continue with the configuration.

Page 31: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

28 © ZIGOR

Fig. 5-3 Independent 3 MPPT configuration

Fig. 5-4 Only 1 MPPT configuration

Fig. 5-5 Independent 2 MPPT configuration

Fig. 5-6 Independent 2 MPPT configuration

Page 32: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 29

The numbers of the strings of the MPPT indicated in the previous figures correspond with the following figure:

Fig. 5-7 MPPT strings

In order to change the MPPT configuration, it is realized of simple form from the menu of display, goes to the menu “settings”, inside to the submenu “system”. In line 10 is the configuration of the MPPT. Remember, use the same type, the same number of panel and the same direction when it does parallels of series of panels to connect into the same string.

5. In this screen, the grid code has to be chosen. The screen will show different countries that are saved in the database of the unit. Depends on the country selection, the inverter will charge some voltage and frequency specific values. These values are defined by each country standards. If your geographic place is not saved in the inverter’s database, please check with ZIGOR customer service ([email protected]). If you don’t select a grid code, next time that the inverter starts, this boot menu will appear again. As in previous cases, press confirmation key and the right scroll button.

Country Display’s number

Spain 1

UK 2

Portugal 3

France 4

Italy 5

Germany 6

Taiwan 7

Malaysia 8

India 9

China 10

Hong Kong 11

Fig. 5-8 Grid code

Page 33: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

30 © ZIGOR

6. When the initial setup have finished, a screen will appear as a summary with the different options chosen. Press right scroll button and, finally the inverter’s main screen will appear.

Fig. 5-9 Main screen

7. Connect the AC circuit breaker. The grid voltage must be within the margins set up in the unit. 8. After detect the grid voltage and confirm that the photovoltaic panels voltage is bigger than

300Vdc, go to “orders” (press the left scroll button for access to the menu), inside this menu see: “state” and select “start”. The system will make a general check of all specifications. After confirming that everything is okay the system will wait for 180 seconds. The first led will start blinking.

9. After 180 seconds different checks, the system will start up and begin to produce energy.

10. If the start-up operation is completed successfully, the LCD screen will indicate the produced energy by the inverter and at the same time, the first LED will stop blinking and then the unit will be turn on completely. After operating of the unit for a time, the screen will turn off to save power.

Note: To modify the current configuration of the system, enter into the configuration menu because this boot sequence only appears at first start-up.

5.2 Daily inverter’s turn on and turn off After a correct configuration of the inverter ZIGOR SOLAR XTR3, this will start automatically when all start-up conditions are correct, after waiting for 180 seconds with a photovoltaic voltage more than 300Vdc, voltage and frequency grid in the limits and if there isn´t bad event in the LCD screen. The system will return energy to the grid. During a time period when the light existence is low, the inverter will stop automatically. The inverter will not be powered by the grid voltage. The inverter only will start with the adequate conditions.

5.3 Inverter’s manual stop There’s a system to do a manual stop, for example for doing the maintenance. In this situation, ZIGOR SOLAR XTR3 is stand-by status. To get this status, in the main screen, press the left scroll button to access “control” menu. Then, go to “status” line and select “stop”. When the relevant work have been done, so the system starts working normally, repeat the same action but this time, select “start” instead of “stop”.

Page 34: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 31

6 COMMUNICATIONS INTERFACE 6.1 Access remote WEB (http) To communicate with the system, by the website, some settings have to be done previously. First of all, the system has to be connected by an Ethernet cable to the router. In the lower part of the system, there is the communication board: starting for the left side, there are: an Ethernet connector, two R115 connectors, and one USB connector (for ZIGOR exclusive use only).

Fig. 6-1 Communication Board

There is NO user installable software. The system is accessed by an internet explorer and it is used the same user interface for local mode and remote mode. When the wires are connected, the network has to be configured. There are two options; first, the router assign an IP to the inverter (DHCP: Dynamic Host Configuration Protocol) or configure it manually. Second, involves the configuration of the subnet mask, router and primary DNS. Note: It is required Internet Explorer 8 or higher or Mozilla Firefox 3 or higher. Note: There are some parameters that can be modified by the user; and another parameters, for your safety, that the manipulation is exclusive for ZIGOR maintenance workers.

6.1.1 Configuration by DHCP In the default configuration, the inverter is configured without DHCP. To enable, it has to be done from “settings” menu, “system” and in the 15th point is the option of “enable DHCP”, change the status to activate (“yes”). When this process has be done, go to “control” and in the fourth point “net”, select “IP NEW” and accept. The inverter will reset and it will be configured automatically for connecting by web. In this case, the inverter will have an IP direction that it has to be known, so the communication could be possible. It is located in the router (depends on the router) or from the inverter, being more easily this second choice To get the IP by the inverter’s screen, go to the “status” menu, “system” and annotate the IP. To do the communication, put the IP direction in the web navigator.

6.1.2 Configuration without DHCP In the default configuration, the inverter is configured without DHCP and with one IP direction, mask, router and primary DNS at random. Some admissible directions will have to be inserted manually, depends on the place will be connected. So the user manual of the router has to be looked up, and in case of doubts consult to your telephone service provider.

6.1.3 Configuration for external connection The steps haves been described for the connection of the inverter to one telephone network can only be used for doing the communication in the same network. To connect from computer that it isn’t connected to the same router but with Internet connection, one port in the router have to be opened. For more information you will have to consult to your telephone service provider.

Page 35: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

32 © ZIGOR

6.1.4 Configuration for inverter-computer direct connection In the same way as it has been commented in the previous points, the system by defect comes configured without DHCP. Do not modify this configuration and go through display to “status” - “console” and write the values of the following parameters for the configuration of the communication of the computer:

• IP • MASK • G.W. • pDNS

Connect an Ethernet cable between the computer and the card of communications of system ZIGOR SOLAR XTR3, it is advised that the cable is always crossover, because all the computers are not able to turn cables crossover configuration to smooth. Next the configuration that is to be realized in the laptop (or personal computer), for it is described as much include views for Windows XP as for Windows 7.

1. First of all push in the “Start” menu of Windows and go to “Control Panel”:

Fig. 6-2 Win XP Control Panel Fig. 6-3 Win 7 Control Panel

2. Within “Control Panel” go to the “Network and Internet Connections” menu in the case of Win XP or to the “Network and Internet” if the computer works with Win 7:

Fig. 6-4 Network and Internet Connections in Win XP Fig. 6-5 Network and Internet in Win 7

3. Once inside this folders, select the “Network Connections” submenu in Win XP and “Network and

Sharing Center” in Win 7

Page 36: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 33

Fig. 6-6 Network Connections in Win XP Fig. 6-7 Network and Sharing Center in Win 7

4. If you are working with Win Xp system, click 2 times with the left button on your Local Area

Connection; in the case that you are working with Win 7, click on the “Local Area Connection” link, this way it will appear the following screens:

Fig. 6-8 Connection Status in Win XP Fig. 6-9 Local Area Connection Status Win 7

Page 37: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

34 © ZIGOR

5. As soon as it appears these screens, click in the “Properties” dialog:

Fig. 6-10 Connection Properties in Win XP Fig. 6-11 Local Area Connection Properties in Win 7

6. Select the “Internet Protocol (TCP/IP)” line in the both systems, with the difference of the Win 7

have to be selected the Version 4 (TCP/IPv4), once the line is selected click on the “Properties” dialog, it will be shown:

Fig. 6-12 Internet Protocol (TCP/IP) properties in Win XP

Fig. 6-13 Internet Protocol Win 7

Page 38: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 35

7. Select the option “Use the following IP address” and introduce the information that it was written down in the beginning of this explanation, the only data has to change is the “IP address”, in this dialog has to be introduced 3 identical numbers to the information copied from the inverter solar, and vary the last one; in the previous figure, there was placed the number 102 as an example, this is different from the number 101 that is indicated in the solar inverter information by defect. Once the information is introduced and pressing OK, you can access from your internet explorer, directly to the Webserver system, writing the next direction in you explorer: http://192.168.33.101.

6.1.5 Login page When the appropriate IP is introduced in the explorer, it will appear a login page where it will ask for a login. Write “user” as the user name and “solar” in the password for entering to the system manager.

Fig. 6-14 Login page

6.1.6 Start menu This is the first page that the user sees when the user name and the password are introduced correctly. From this page, parameters of emphasized information are accessible. There are different zones:

• Submenus top bar. • A status diagram with its most important characteristics. • Generation graphs about the last days/months with their benefits and occurred events.

It also has a section which it shows the weather forecast for the next months (with a previous configuration so this is able to display the forecast for the right place). In the top, there is a box to refresh the screen. If this box is not active, the information will only get one time, so after a period of time the information will not be updated. If it is active, the information will be updated but the computer will work slowly.

Page 39: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

36 © ZIGOR

Fig. 6-15 Start menu

6.1.7 Status menu In this menu there is the intrinsic system information and the status in which the inverter is: start or stop. In other hand, it shows the number of events. This menu is the same than the measures menu of the display. In the left side of the screen is located a status tree with four sections:

• System, • DC input, • Inverter, • DC output.

Choosing any section, it will appear the corresponding measures in the right side.

Fig. 6-16 Status menu

Page 40: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 37

6.1.8 Energy menu This menu shows the system generation in real time. This can be daily, monthly, yearly or total. Also discloses parameters such as CO2 reduction and economic benefit of the ZIGOR SOLAR XTR3.

Fig. 6-17 Energy menu

6.1.9 Settings menu In this menu it is possible to modify some parameters of the system, of the input of the panels, of the inverter and the AC output.

Fig. 6-18 Settings menu

Page 41: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

38 © ZIGOR

6.1.10 Alarm menu This menu shows the inverter status respect of alarms and events that are occurring or have occurred at any time. There are three different submenus give us the information: • Active, shows the existing alarms at the moment. • History (event log), shows the alarms that have occurred before. • Configuration

Fig. 6-19 Alarm menu

In the upper right side there are the follow icons:

Fig. 6-20 Alarm menu (save icons)

Pressing the save button exists the option to save the alarms in three formats, CSV, Excel or pdf. It will appear one screen asking where we want to save these files (hard disk, pendrive...). Pressing the print button it will print the alarms, if there is one printer or similar equipment installed for these type of works.

Page 42: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 39

Fig. 6-21 Alarm event log screen

6.1.11 Control menu From this panel it can be controlled some system parameters: • Start/ stop (equivalent to 5.2 part of this manual) • Reset

Fig. 6-22 Control menu

Page 43: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

40 © ZIGOR

6.1.12 Network menu From this panel it is possible to modify all the parameters referent to the communication network.

Fig. 6-23 Network menu

From this screen it can be modified, for example, the IP of our unit or other factors of the network (DHCP that have been mentioned before). It is the same menu that appears in the LCD screen.

6.2 Communications protocol The inverter ZIGOR SOLAR XTR3 has the ability to communicate through the communication protocols SNMP and Modbus (RTU, ASCII and TCP) by pin RJ45 Ethernet and 2 RJ11 jacks available to the communications card as shown in figure:

Fig. 6-24 Terminales de comunicación

6.2.1 SNMP Communication Protocol ZIGOR SOLAR XTR3 is allowed to communicate via Ethernet using SNMP protocol and can transmit data from the equipment to be monitored at a remote location. The objects defined in the MIB file is the set of system variables that the SNMP manager can ask the agent. SNMP is accessed by both the variables of the system both for status and for configuration. For more information on the SNMP protocol ZIGOR SOLAR XTR3 please see our communication´s manual.

RJ11 RJ45

Page 44: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 41

6.2.2 Modbus Communication Protocol ZIGOR SOLAR XTR3 team enables communication via Modbus RTU, ASCII and TCP. The selection of the desired protocol can be done in the inverter´s display. ZIGOR SOLAR XTR3´s communication card has a RJ45 Ethernet input, through which we can communicate the inverter to a computer using Modbus TCP and SNMP. The communication card has two RJ11 jacks for communicating with Modbus RTU and ASCII. With these 2 pins we can make a daisy chain configuration. The polarization of the RJ11 is shown below in the following table:

PIN number Polarity

2 BUS M+ 3 GND BUS M 4 BUS M-

For more information on the communication settings and maps Modbus and / or the MIB for SNMP communications refer to our catalog.

Page 45: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

42 © ZIGOR

7 TROUBLESHOOTING The PV Inverter is supplied with a self-diagnosis system that identifies automatically a large number of anomalies and displays these on the LCD screen. It is therefore possible to isolate technical problems very quickly and to differentiate between the Service Codes relating to the installation from those internal anomalies of the PV Inverter. Whenever the self-diagnosis system identifies a specific problem, the corresponding Service Code is displayed on the LCD screen. Table 1. The error code of the PV Inverter and a description of the error code Information error appears in Events Warning the second led lights, yellow led, and error appears in Events Alarm the third led lights (red led) and error appears in Events. Though this error is solved it is necessary reset the failure from the display: “Orders”

The inverter indicates Error Number Designation Description Remedy

Warning 1 High Vp The photovoltaic voltage

(DC) above the maximum limits of the inverter.

1. Disconnect ALL the PV (+) or PV (-)

2. Wait for a few seconds. 3. After the LCD turns off,

reconnect and check again. 4. If the same error occurs again, contact with the local distributor.

Warning 2 Ve min The photovoltaic voltage (DC) below the minimum

limits of the inverter.

Wait for generating more energy. If the error doesn’t stop, contact

with the local distributor.

Warning 3 Low Rais Insulation resistance under 500KΩ

1. Disconnect ALL the PV (+) or PV (-)

2. Wait for a few seconds. 3. After the LCD turns off,

reconnect and check again. 4. If the same error occurs again, contact with the local distributor.

Alarm 4 COM failure Communications failure between DSP and the inverter

Warning 5 Island The inverter detects that there is no reference grid voltage.

Disconnect the AC circuit breaker. Then check the configuration of the peripheral AC system and the grid conditions. If the failure reoccurs, ask the local distributor for help.

Alarm 6 Inv failure The Inverter has not operated or does not operate correctly.

Seek the help to the local distributor.

Alarm 7 Vbus Min The internal DC BUS is lower than expected

Seek the help to the local distributor.

Alarm 8 Vbus Max The internal DC BUS is higher than expected

Seek the help to the local distributor.

Warning 9 PLL fail Vgrid synchronization fail Seek the help to the local distributor.

Alarm 10 Overtemperature The internal temperature of the inverter is too high.

1. Try reducing the atmospheric temperature. 2. Move the PV Inverter to a cooler place. 3. If the error code reappears, seek the help to the local distributor.

Alarm 11 Precharge failure Bus capacitor’s precharge failure

Seek the help to the local distributor.

Page 46: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 43

Warning 12 Derating Power limitation in accordance with the working temperature.

1. Try reducing the atmospheric temperature. 2. Move the PV Inverter to a cooler place. 3. If the error code reappears, seek the help to the local distributor.

Alarm 13 DC current DC current outside inverter limits.

Information 14 Relay The output relay switches

Warning 15 Grid dip The system detects a grid dip. Wait until the grid returns

Warning 16 Low Vgrid Input AC voltage value low. Disconnect the AC circuit breaker. Then check the configuration of the peripheral AC system and the grid conditions. If the failure reoccurs, ask the local distributor for help. Warning 17 High Vgrid Input AC voltage value high.

Warning 18 Frequency Margin The PV Inverter phase

cannot be in phase with the grid.

Disconnect the AC circuit breaker. Then check the configuration of the peripheral AC system and the grid conditions. If the failure reoccurs, ask the local distributor for help.

Alarm 19 I Leak The system detects a leak in the DC power.

1. Disconnect ALL the PV (+) or PV (-) 2. Wait for a few seconds. 3. After the LCD turns off, reconnect or check again. 4. If the same error occurs again, contact the local distributor.

Information 20 Remote start System remote start.

Information 21 Stop System stop

Page 47: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

44 © ZIGOR

8 TECHNICAL SPECIFICATIONS

Unit Model ZIGOR SOLAR XTR3 10kW

ZIGOR SOLAR XTR3 13kW

ZIGOR SOLAR XTR3 15kW

ZIGOR SOLAR XTR3 20kW

Conversion mode Inverter

technology Sinusoidal wave, current source, high frequency PWM

Insulation method Design without transformer

DC input data

Nominal DC voltage 640 Vdc

Max. DC input voltage 1000 Vdc

Operating range 300 VDC - 800Vdc

Max. DC input current (Each MPPT follower) 12 A 15.6 A 18 A 25 A

Shorcircuit current of DC input 37 A 48 A 56 A 76 A

MPPT follower 3

AC output data

Nominal AC power 10 kW 13 kW 15 kW 20 kW

Nominal AC voltage 3 x 400 Vac Output connection method 3 phases - 3 wires or 3 phases - 4 wires

AC voltage range 400V -20% + 20% ( selectable each country)

Nominal AC current 14.5 A 19 A 22 A 29 A

Frequency 50 / 60 Hz Power factor >0.99 at nominal AC current

Max current at failure 32 A

Max curren at short circuit 32 A

Max protection at overcurrent 32 A

Current distortion < 3% Efficiency data

Maximum conv. efficiency 97%

Euro efficiency 96%

Environmental

Temperature Operation

-20ºC / +60ºC* -4ºF – 122ºF

Enviromental recomendable temperature of storage

0ºC - 40ºC

32ªF - 104ºF

Humidity 0 to 90% (without condensation) Maximum altitude 2000 m

Noise level < 50dBA Communications

Interface TCP/IP Ethernet,RJ11, USB

Protocol ModBus (RTU, TCP/IP, ASCII), SNMP

Page 48: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

© ZIGOR 45

Front panel

LCD DC input voltage/ DC input current/ DC input power/ AC output voltage/ AC output current/

AC output frequency/ AC output current/ AC energy performance/ Interior Temperature /Heat dissipater temperature /Status message/Error message

Red Earth failure or DC input insulation failure LED Yellow The grid specifications do not coincide with the standard PV Inverter input Green The power of the solar cell is greater or lower than 5% of the PV Inverter output power

Keyboard UP KEY/DOWN key/LEFT key/RIGHT key/ INTRO key Protection

Network Over/Undervoltage, Over/underfrequency, Earth failure, DC insulation failure, Island Short-circuit DC input: Input diode/Electronic circuit

AC output: Output relay/Electronic circuit Overtemperature ≥ 60°C (140°F) system will stop

Mechanical data

Height x Width x Depth 665 x 480 x 220 Weight 39kg

Protection class IP 54 Refrigeration Optimised refrigeration

AC connection Connector DC connection Multi-contact type Certification

Safety VDE 4105, EN 62109-1, EN 62109-2, IEC 60146, G83/1-1, G59/2, IEC 62116, UL 1741(1), CEI 0-21

EMI/EMC EN 61000-6-2, EN 61000-6-3, EN 61000-3-2, EN 61000-3-3, IEEE 1547

Marks VDE, CE, ENEL

* The inverter will limit power at high operating temperatures.

(1) Manufactured under UL1741 Note:

• The technical specifications may be modified without warning • For any other technical requirement or modification of existing characteristics please consult ZIGOR.

Page 49: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

Operating Manual ZIGOR SOLAR XTR3

46 © ZIGOR

9 WARRANTY ZIGOR, guarantees that ZIGOR SOLAR XTR3 units leave the factory in perfect working order and free of any defects for a period of 24 months to be counted as of the date of sale of the apparatus, shown in the delivery note and/or invoice. ZIGOR guarantees the Purchaser the correct operation of the unit against manufacturing and/or workmanship defects. No servicing and/or travelling is included, this being at the expense of the buyer. When required, parts will be replaced with other new or repaired parts and the parts replaced shall become the property of ZIGOR. Any defect that may arise due to an accident, disaster or inadequate use, mistreatment, non authorised modifications or causes of a similar nature, as well as those deriving from the use of accessories not purchased from or installed by or any of this company's sales outlets or authorised services is excluded.

The installation of elements inside the unit by personnel other than those authorised by ZIGOR, shall render the warranty null and void. ZIGOR will not accept responsibility for the repair of equipment if any of the seals installed for internal checks is broken.

The Spanish Standardisation and Certification Association (AENOR) certifies that the “Quality Assurance ” and “Environmental Management Systems” adopted by ZIGOR Corporación, S.A. for the design, development, production and after sales service for electronic equipment for the conversion of direct and alternating current as well as electronic projections, communications systems, telemanagement applications and electrical and electronic turnkey projects, is an agreement with the requirements of the Spanish Standards UNE-EN ISO 9001:2008 and UNE-EN ISO 14001:2004 respectively.

Page 50: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They
Page 51: ZIGOR SOLAR XTR3 - SM Systems · ZIGOR SOLAR XTR3 systems must be handled carefully and in the horizontal position, any other position may cause damage and loss of guarantee. They

30201003MAOP

www.zigor.com

Consulte nuestra web para contactar con la red de delegaciones comerciales Refer to our website in order to contact the commercial branches network

Veuillez consulter notre page web pour contacter nos délégations commerciales Consulte a nossa web para contatar com a rede de degaçoes comerciais