yx8000 sensorless vector type inverter manual manual yx8000.pdf · stop parameter storage,...

94

Upload: others

Post on 14-Oct-2020

22 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,
Page 2: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 1 -

Before the words

Thank you for the use of Shen Zhen Yuan Xin Electric Technology CO.,LTD of the YX8000 series inverter.

YX8000 High Performance Vector Type Inverter is ShenZhen YuanXin Electric Technology CO.,LTD to adopt new ideas independently developed a series of high performance, low noise, current vector type inverter. In improving the stability of the added under the condition of simple PLC, practical PID regulation ( with constant pressure water supply function ), flexible input / output terminals, parameter modification, since the identification signal transmission failure, power outages and stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control, field bus control and a series of practical operation, control function. For equipment manufacturers and end customers to provide high integration solutions, to reduce the purchase and operating costs, enhance the reliability of the system is of great help.

In the use of YX8000 series inverter before, please users and relevant technical personnel carefully read the instructions, to ensure the correct installation and operating YX8000 series inverter, the inverter to play its best performance.

The specification are subject to change, please refer to the latest version, without traffic.

Target readers The instruction manual for the following staff reading Inverter installation,Engineering technical personnel,Design personnel. Book Agreement

Sign Agreement

Inspection Due to the absence of the requested operation, may cause moderate damage or injuries.

Danger Due to the absence of the requested operation, may result

in death or serious injury.

Page 3: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 2 -

—Contents—

Chapter 1 Introduction

1.1 Unpacking Inspection ---------------------------------------------------------------------(4)

1.2 Safety Rules -------------------------------------------------------------------------------(4)

1.3 Notes on Usage ---------------------------------------------------------------------------(6)

1.4 Notes Regarding Disposal---------------------------------------------------------------(7)

Chapter 2 Models and Specifications

2.1 Models -------------------------------- -----------------------------------------------------(8)

2.2 Specifications -----------------------------------------------------------------------------(8)

2.3 Parts of Inverter ---------------------------------------------------------------------------(10)

2.4 Dimensions --------------------------------------------------------------------------------(11)

2.5 Optional Parts------------------------------------------------------------------------------(12)

Chapter 3 Installation and Wire Connection

3.1 Installation ----------------------------------------------------------------------------------(13)

3.2 Removing and Mounting Front Cover of Inverter-------------------------------------(14)

3.3 Wire Connection ---------------------------------------------------------------------------(14)

3.4 Main Circuit Wiring -----------------------------------------------------------------------(19)

3.5 Basic Wiring Diagram ---------------------------------------------------------------------(19)

3.6 Control Circuit Terminal Wiring ---------------------------------------------------------(20)

3.7 EMC Installation Instruction --------------------------------------------------------------(21)

Chapter 4 Running of Inverter

4.1 Running of Inverter ------------------------------------------------------------------------ (23)

4.2 Operation and Using of the Keyboard -- -------------------------------------------------(25)

4.3 Running Status ------------------------------------------------------------------------------(29)

4.4 Rapid Debugging-----------------------------------------------------------------------------(30)

Chapter5 Function Parameter Table

5.1 Symbol Description -------------------------------------------------------------------------(31)

5.2 YX8000 general series function parameter list ------------------------------------------(31)

Chapter 6 Function Code Description

6.1 Basic Running Function Parameter (P0 Group)------------------------------------------(45)

Page 4: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 3 -

6.2 Frequency Setting Function Parameter (P1 Group)-------------------------------------(50)

6.3 Start/Brake Parameter(P2 Group ----------------------------------------------------------(51)

6.4 Auxiliary Function Parameter(P3 Group)------------------------------------------------(53)

6.5 PLC Program Control Operation Parameters(P4 Group)-------------------------------(55)

6.6 PID Closed Loop control Parameters(P5 Group)--------------------------------------(58)

6.7 Terminal Function Parameter(P6 Group)------------------------------------------------(61)

6.8 Display and Control Parameter(P7 group)----------------------------------------------(67)

6.9 Motor Parameter(P8 Group)------------------------------------------------------------(68)

6.10 Motor Parameter(P9 Group)-----------------------------------------------------------(69)

6.11 Fault and Protect Parameters(PA Group)----------------------------------------------(71)

6.12 Serial Communication Parameters(PB group)----------------------------------------(73)

6.13 Swing Frequency and Supplementary Parameters (PC Group)-----------------(76)

6.14 Inverter PG closed loop and its Parameters(PD Group)-----------------------------(78)

6.15 Factory Parameter(PE Group)-----------------------------------------------------------(79)

Chapter 7 Troubleshooting

7.1 Fault Alarm and Troubleshooting --------------------------------------------------------(80)

7.2 The Common Faults and Processing methods ------------------------------------------(82)

Chapter 8 Preservation and Maintenance

8.1 Preservation and Maintenance -----------------------------------------------------------(83)

8.2 Periodic Preservation and Maintenance-------------------------------------------------(83)

Chapter 9 Serial Port Communication Protocol of RS485

9.1 Communication Overview----------------------------------------------------------------(84)

9.2 Communication Protocol Specification--------------------------------------------------(84)

9.3 Content of the Protocol --------------------------------------------------------------------(85)

9.4 Application Mode---------------------------------------------------------------------------(85)

9.5 Bus Structure---------------------------------------------------------------------------------(85)

9.6 Protocol Instructions ------------------------------------------------------------------------(85)

9.7 Communication Frame Structure----------------------------------------------------------(85)

9.8 Command Code and Communication Data Description -------------------------------(87)

Page 5: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 4 -

Chapter 1 Introduction 1.1 Unpacking Inspection

Upon unpacking, please confirm the following: Any damage occurred during transportation; Check whether

the model and specifications on the nameplate of inverter are in accordance with your order.

If there is any error, please contact us or distributors.

Inverter type description

Fig 1-1 Inverter type description

The model and specifications on the nameplate of inverter on the bottom right of inverter.

1.2 Safety Rules Inspection

Inspection

1. Please do not install the damaged inverter, otherwise there is a danger of injury.

Installation

Inspection

1. Handling, please hold the bottom of the body, otherwise there is a danger of a body falling foot injury.

2. Please install the inverter on metal or other nonflammable material, otherwise there is a danger of fire.

3. Please install cooling fans when two inverters are installed in a same cabinet, keep the air intake temperature

under 40 , otherwise, there is a danger of fire.

Cable connection and distribution

Danger

1. Wire-connection job can only be done when the mains are cut off, otherwise, there is a danger of shock or fire.

2. Only qualified personnel can perform wire-connection job, otherwise, there is a danger of shock or fire.

Inverter series

Voltage

level

Code

380V 4

Inputvoltage Code

Single phase S

Three phase T

Code Inverter type

G Constanttorque

P Fan pump type

YX8000- 4 T 0015 M

Code Motor Power

0007 0.75KW

0015 1.5KW

0075 7.5KW

Page 6: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 5 -

3. The earth terminal of frequency inverter must be connected to earth reliably, otherwise, there is a danger of

shock or fire.

(Please use the 3rd grounding method specially for 380V)

4. After connects emergency stop terminal, please make sure it is effective, otherwise, there is a danger of injury.

(The user is responsible for the connection)

5. Please don’t touch the output terminals, don’t connect the output terminals with the shell, don’t short connect

the output terminals, otherwise, there is a danger of shock or short circuit.

Attention

1. Please confirm the mains supply is in accordance with rated voltage of inverter, otherwise, there is a danger of

injury or fire.

2. Please don’t make voltage withstanding test to the inverter. It may damage the semiconductor and other

components.

3. Please connect the braking unit or resistance according to the wiring diagram; otherwise, there is a danger of

fire.

4. Please use screw drivers with appointed moment of force to tighten the terminals, otherwise, there is a danger of

fire.

5. Please don’t connect input mains cable with output terminals of U/V/W. It may damage the inverter.

6. Please don’t connect shifting capacitor or LC/RC noise filter with output loop. It may damage the inverter.

7. Please don’t connect solenoid switch or solenoid contactor with output loop. When inverter is running with load,

the action of such swith and contactor will cause surge current. It may trigger over current protection of inverter.

8. Please just disassemble the terminals cover when wiring, don't disassemble the front cover of inverter. It may

damage the inverter.

Maintenance and inspection

Danger

1. Please do not touch the control terminals when it is live, otherwise there is a danger of shock.

2. Please make sure the terminals cover is assembled before power up. Before disassembling the terminals cover,

please make sure the power is cut off, otherwise, there is a danger of shock.

3. Only qualified personnel can perform the maintenance and inspection job, otherwise, there is a danger of shock.

Attention

1. The keyboard, control circuit board, and driver circuit board were integrated with CMOS circuit. Please be

careful when using. Please don not touch these circuit boards by fingers.

2. Please don’t change the cable connection when power on.

Page 7: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 6 -

1.3 Notes on Usage In the use of YX8000 series inverter, please pay attention to the following points:

1. Constant torque low speed running

When the inverter outputs to a common motor at low speed for a long term, the output rated torque should be

derated due to the worsening radiating effect. If low speed constant torque long term running is required, then a

special variable frequency motor is needed.

2. Confirm motor’s insulation

Before usingYX8000 series inverter, please confirm the motor is insulated; otherwise, the equipment may be

damaged. Please confirm motor’s insulation termly when motor is working under bad condition.

3. Negative torque load

To some application situation such as lifting load, negative torque load may occur. Braking unit and resistor should

be connected with inverter, or over current or over voltage fault may happen.

4. The mechanical resonance point of load

The inverter may encounter the mechanical resonance point of load within certain output frequency range. Jump

frequencies have to be set to avoid it.

5. Capacitor and varistor

Because the inverter outputs PWM pulse wave, capacitor and varistor should not be connected with the output

terminals of the inverter, or the inverter may trip or components may be damaged,as shown in Fig.1-3.

Fig. 1-3 Capacitor connection with inverter output prohibited

6. Motor derating

When basic frequency is set to be lower than rated frequency, motor derating is necessary in order to avoid motor

overheating.

7. Running at frequency above 50Hz

If running at frequency above 50Hz, besides the increment of vibration and noise, the ranges of running speed of

motor shaft and mechanical device have to be guaranteed. Be sure to make an enquiry first.

8. The electro-thermal protective value of motor

If the applicable motor is selected as per requirements, the inverter can perform the thermal protection to the motor.

If the ratings of applied motor are not in compliance with the inverter, be sure to adjust the protective value to

guarantee the safe running of motor.

9. Altitude and derating

When the altitude is higher than 1000m, the cooling effect of inverter is deteriorated because of the rareness of air,

derating must be considered.

Page 8: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 7 -

Fig.1-4 indicates the relationship between the altitude and rated current of frequency inverter.

10. On the level of protection

YX8000 Inverter protection grade IP20 is in the selection of state display unit or the keyboard case reach.

1.4 Notes Regarding Disposal When you dispose frequency inverter, pay attention to:

The capacitors in the main circuits may explode when they are burned. Poisonous gas may be generated when

front panel is burned.

Please dispose the inverter as industrial rubbish.

Page 9: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 8 -

Chapter 2 Models and Specifications 2.1 Models

YX8000 series inverter input is 380V. The range of applicable motor is from 0.75KW to 500KW. Models of

YX8000 series are shown in Table 2-1. Table 2-1. Models description

Voltage level Models Rated capacity(KVA)

Ratedoutput

current(A)

Applicable

motor(KW) YX8000-4T0007G 1.5 2.5 0.75 YX8000-4T0015G 2.5 4.0 1.5 YX8000-4T0022G 3.0 6.0 2.2 YX8000-4T0037G 5.9 9.6 3.7 YX8000-4T0055G 8.5 14.0 5.5 YX8000-4T0075G 11 17.0 7.5 YX8000-4T0110G 17 25 11 YX8000-4T0150G 21.7 32 15 YX8000-4T0185G 25.7 39 18.5 YX8000-4T0220G 29.6 45 22 YX8000-4T0300G 39.5 60 30 YX8000-4T0370G 49.4 75 37 YX8000-4T0450G 60 91 45 YX8000-4T0550G 73.7 112 55 YX8000-4T0750G 99 150 75 YX8000-4T0900G 116 176 90 YX8000-4T1100G 138 210 110 YX8000-4T1320G 167 253 132 YX8000-4T1600G 200 304 160 YX8000-4T1850G 234 355 187 YX8000-4T2000G 248 377 200 YX8000-4T2200G 280 426 220 YX8000-4T2500G 318 474 250 YX8000-4T2800G 342 520 280 YX8000-4T3150G 390 600 315 YX8000-4T3500G 435 660 350 YX8000-4T4000G 493 750 400

380V Three phase

YX8000-4T4500G 560 850 450

2.2 Specifications Items Specifications

Rated voltage/Frequency three phase 380V;50Hz/60Hz Input

Range Voltage: ±20% voltage unbalance rate:<3%; frequency: ±25% Rated voltage 0~380V

Frequency range 0Hz~500Hz Frequency resolution 0.01Hz

Output

Overload ability 150% rated current for1minute, 180% rated current for3 seconds Modulation modes Optimized space voltage vector SVPWM modulation

Control mode Sensorless vector control (with optimal low frequency deadtime compensation)

Frequency precision Digital setting: The highest frequency×± 0.01% Analog setting:The highest frequency ×±0.2%

Page 10: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 9 -

Frequency resolution Digital setting: 0.01Hz; Analog setting:The highest frequency× 0.1% Start frequency 0.40Hz~20.00Hz Torque boost Auto torque boost, manual torque boost 0.1%~30.0%

V/F curve Five ways: constant torque V/F curve, One kind of user defined V/F curve, Three kinds of down torque curve(2.0/1.7/1.2 times the power)

Acc./Dec. curve Two ways: linear Acc./Dec.,S-curve Acc./Dec.;Seven kinds of Acc./Dec. time, time unit(minute/second) optional, max.Time: 6000 minutes.

DC braking DC braking start frequency:0~15.00Hz braking time:0~60.0 second braking current:0~80%

Energy consuming braking

Energy consuming braking unit built-in,external braking resistor can be

Jog running Jog frequency range:0.1Hz~50.00Hz, JOG Acc./Dec. time: 0.1~60.0s PI built-in Easily constitute a close loop control system Multi-stage speed running

Multi-stage speed running available through built-in PLC or control terminals

Textile swing frequency Swing frequency available with preset and centre frequency adjustable Auto voltage regulation When the grid voltage changes, to maintain constant output voltage Auto energy saving running

Saving energy by auto optimizing V/F curve according tothe load

Auto current limitting Auto current limitting to prevent frequent overcurrent fault trip Fixed-length control Inverter stops when reaches the preset length

Control function

Communication RS485 standard communication port available, support MODBUS communication protocol of ASCII and RTU, master-slave multi-machine interaction function available

Operation command channel

Control panel; control terminal; serial port ; 3 channels switchable

Frequency setting channel

Control panel potentiometer; 、control panel keys;function code digital; serial port; terminal up/down; analog voltage; analog current; pulse; combination setting; all channels switchable

Switch input channel FWD/REV command; 8channels programmable switch inputs; 35 kinds of function can be set separately

Analog input channel 4~20mA: 0-10V: 2 optional analog inputs

Analog output channel 4~20mA or 0~10V optional, setting frequency and output frequency ,etc. can be output

Operation function

Switch/pulseoutput channel

Programmable open collector output:relay output :0~20KHz pulse output:

LED digital display Display setting frequency, output voltage, output current, etc. External meter display Display output frequency, output current, output voltage, etc. Key lock All the keys can be locked

Control panel

Parameter copy Function code parameters are able to be copied between inverters when use remote control panel。

Protection function Overcurrent protection:overvoltage protection:undervoltage protection:overheating protection:overload protection,etc.

Optional parts Braking unit; remote control panel; cable; panel mounting feet, etc.

Environment Indoors, free from direct sunlight,dust, corrosive gas, oil mist,steam, waterdrop or salt, etc

Altitude Lower than 1000m (derating is necessary above 1000m) Ambient temperature

-10~+40

Humidity <90%RH, no condensation Vibration Lower than 5.9m/s (0.6g)

Environment

Storage temperature

-20~+60

Protection level IP20(In the selection of state display unit or the keyboard state) Structure

Cooling Forced air cooling Installation Wall mounted

Page 11: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 10 -

2.3 Parts of Inverter

2.3.1 Dimensions

D

HH1

W1W

Fig. 2-1 Schematic diagram of mounting dimensions

Wall Mounted Frequency Inverter:

Type of Inverter

G type W1

(mm) W

(mm) H1

(mm)H

(mm)D

(mm)

Doameter of

mounting hole(mm)

YX8000-4T0007G

YX8000-4T0015G YX8000-4T0022G

108 120 158 170 140 Φ5

YX8000-4T0037G 128 140 188 200 160 Φ5

YX8000-4T0055G YX8000-4T0075G

165 180 240 255 183.5 Φ6

YX8000-4T0110G YX8000-4T0150G

150 245 373 388 242 Φ7

YX8000-4T0185G YX8000-4T0220G

180 261 422 440 271 Φ9

YX8000-4T0300G 200 291 500 520 280 Φ10 YX8000-4T0370G YX8000-4T0450G

300 348 563 587 300 Φ10

YX8000-4T0550G 278 395 598 618 310 Φ10

Page 12: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 11 -

Cabinet Type Frequency Inverter:

2.4 Dimension of Operational Panel 2.4.1 Digital display operation panel

Dimension figure of Digital display operation panel is shown in Fig.2-2

Fig. 2-2 Dimension of Digital display operation panel

Applicable Models:

YX8000 series G type YX8000 series P type YX8000-4T0007G~4T0075G YX8000-4T0015P~4T0110P

2.4.2 LCD + digital display operation panel Dimension and Moulting dimension of LCD + digital display operation panel are shown in Fig. 2-3.

Fig.2-3 Dimension and Moulting dimension of LCD + digital display operation panel

YX8000-4T0750G YX8000-4T0900G YX8000-4T1100G YX8000-4T1320G

282 482 632 652 310 Φ10

Type of Inverter

G type W

(mm) H

(mm) D

(mm)

YX8000-4T1600G YX8000-4T1850G YX8000-4T2000G YX8000-4T2200G

600 1440 400

YX8000-4T2500G YX8000-4T2800G YX8000-4T3150G

855 1365 412

YX8000-4T3500G YX8000-4T4000G YX8000-4T4500G

914 1875 430

Page 13: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 12 -

Moulting dimension of LCD + digital display operation panel: 85mm × 156mm Applicable Models:

YX8000 series G type YX8000 series P type YX8000-4T0110G~4T4500G YX8000-4T0150P~4T4500P

Operation panel does below operations on frequency inverter: function parameters setting and condition monitoring. Among them, LED digital displays the current status of function parameters,LCD notes and illustrates the parameter status. 2.5 Optional Parts: The following options, if necessary, please to my company ordered another。

2.5.1 Remote control panel Type: YX8000-YK01( no LED display ) and YX8000-YK02( LED display )

RS 485 communication is applied between remote control panel and inverter which are connected by a 4-core

cable via RJ45 network port.

The maximum connection distance is 500 M.The inverter supports local control panel and remote control panel

used at the same time, no priority, both can control the inverter . Hot Plug In for remote control panel is available.

The following functions are available by using remote control panel:

(1) Control slave inverter to run, stop, jog run, fault reset, chang setting frequency, change function parameters and

running direction.

(2) Monitor slave inverter’s running frequency , setting frequency , output voltage, output current, busbar voltage,

etc.

2.5.2 Communication cable for remote control panel Type:YX8000-YK02

Standard options:1m, 2m, 5m, 10m, 20m,More than 20m can be customized. For the remote keyboard and

inverter host connection

2.5.3 Field bus adaptor The inverter can be connected into MODBUS field bus network via adaptor as a slave station in the network.

The function as follow:

(1) To send command to inverter such as start, stop, jog running, etc.

(2) To send speed or frequency signal to inverter.

(3) To read status from inverter.

(4) To fault reset for the inverter.

Please refer to Chapter 9 for communication protocol

2.5.4 Braking Resistors

YX8000 series inverters under15KW have built-in braking units.If energy consuming braking is needed. Please

choose braking resistors according to Table 2-3. The wire connection of braking resistors are shown in Fig. 2-2.

Page 14: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 13 -

Fig.2-2 The wire connection of braking resistors

Table 2-2 Braking resistors selection table

Model Applicable motor (KW) Resistance (Ω ) Resistance power (W)

YX8000-2S0004G 0.4 200 100

YX8000-2S0007G 0.75 150 200

YX8000-2S0015G 1.5 100 400

YX8000-2S0022G 2.2 70 500

YX8000-4T0007G 0.75 300 400

YX8000-4T0015G 1.5 300 400

YX8000-4T0022G 2.2 200 500

YX8000-4T0037G 4.0 200 500

YX8000-4T0055G 5.5 30 1000

YX8000-4T0075G 7.5 30 1000

Chapter 3 Installation and Wire Connection 3.1 Mounting Space and Direction

YX8000 series frequency inverter are wall mounting type and they should be installed vertically,which is good for air circulation and heat dissipation.Enough space should be left around the inverter as is shown in fig.3-1. Ventilation fan position refers to fig.3-2 in installation environment.

If several inverters are installed,please refer to fig.3-3 and fig.3-4. When inverters are mounted up and down, an air flow diverting plate should be fixed as shown in Fig.3-3 to ensure good heat dissipation.

Fig.3-1 Installation distance Fig.3-2Ventilation fan position

Page 15: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 14 -

Fig.3-3 Mounting of multiple inverters 1 Fig. 3-4 Mounting of multiple inverters 2

3.2 Connection Diagram of peripheral unit

Fig.3-5 Connection Diagram of peripheral unit

3.3 Terminal Diagram 3.3.1 Main circuit terminal

Fig.3-6 Terminal diagram of main circuit terminal (Triple phase 0.75~3.7 kW)

Fig.3-7 Terminal diagram of main circuit terminal (Triple phase 5.5~15 kW)

Page 16: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 15 -

Fig.3-8 Terminal diagram of main circuit terminal (18.5KW~90kW)

Fig.3-9 Terminal diagram of main circuit terminal (4.0~5.5kW)

Fig.3-10 Terminal diagram of main circuit terminal (185KW~220kW)

3.3.2 Main circuit terminal features

3.3.3 Control loop terminal

Fig.3-11 7.5KW and under CN1 terminal block diagram

+10V CI A01-I A02-V 485- X7 X5 X3 X1 Y1 +24V PGA+ PGB+

VI GND A01-V 485+ GND X6 X4 X2 Y2 COM PE PGA- PGB-

Fig.3-12 11kW and under CN1 terminal block diagram Table 3-1 CN 1 terminal function

Sort Terminal Name Function Description Specification

485+ RS485 differential signal positive

terminal Communication

485-

RS485 communication port RS485 differential signal

negative terminal

Twisted or shielded wire needed

Y1 Open collector output

terminal 1

Can bedefined as multifunctionalon-off output terminal by

programming, refer to Chapter 6.5P4.10

(Common port:COM)

Optocoupler isolated output Working voltage: 9~30V Max.outputcurrent:50mA

Name of Terminal Function Specification R、S、T Three-phase power input terminals P+、P- External braking unit reserve terminals P+、PB Reserved external braking resistor terminals P1、(+) Reserved External DC reactor terminals

(-) DC negative busbar output terminals U、V、W Three-phase AC output terminals

E ground terminals (PE)

+10V CI A01-I A02-V 485- X7 X5 X3 X1 COM PGA+ PGB+

VI GND A01-V 485+ GND X6 X4 X2 Y1 +24V PGA- PGB-

Page 17: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 16 -

Y2 Open collector output

terminal 1

Can bedefined as multifunctionalon-off output terminal by

programming, refer to Chapter 6.5P4.11

(Common port:COM)

Optocoupler isolated output Working voltage: 9~30V Max.output current:50mA

Y3 Open collector output

terminal 3

Can be defined as multifunctionalPulse output terminal by

programming, Refer to Chapter 6.5P4.21/P4.22

(Common port:COM)

Max. output frequency: 20KHzoutput freq range defined by P4.21

VI Analog inputVI Analog voltage input (Grounding: GND)

Input voltage range:0~10V (input resistance:47KΩ) Resolution: 1/1000

Analog input

CI Analog inputCI

Analog voltage/current input, Choose voltage or current input

by Setting JP3 jumper. Factory default: voltage input

(Grounding:GND)

Input voltage range:0~10V (input resistance:47KΩ )

Input current range:0~20mA(input resistance:500Ω )

Resolution: 1/1000

AO1 Analog output AO1Analog voltage output, indicating

7quantities(Grounding: GND)Voltage output range:0~10V

AM1 Analog output AM1Analog current output, indicating

7quantities(Grounding: GND)Current output range:4~20mAAnalog output

AO2 Analog output AO2Analog voltage output, indicating

7quantities(Grounding: GND)Voltage output range:0~10V

X1 Multifunctional input terminal 1

X2 Multifunctional input

terminal 2

X3 Multifunctional

input terminal 3

X4 Multifunctional

input terminal4

X5 Multifunctional input

terminal 5

X6 Multifunctional input

terminal 6

Multifunctional input terminal

X7 Multifunctional input

terminal 7

Can be defineda smultifunctionalon-off input terminal by

programming, refer to Chapter 6.5 P4. (Common port:COM)

Optocoupler isolated input Input resistance:2KΩ

Max. input frequency:200HzInput voltage range:9~30V

24V +24V power sourceSupply +24V power (negativet erminal:COM)

Max.outputcurrent:100mA

10V +10V power sourceSupply+10Vpower(negativet erminal:GND)

Max. outputcurrent: 50mA

GND +10Vcommon portGrounding of analog signal and+10V power source

Power source

COM +24Vcommon portDigital signal input, output common port

Terminal COM and GND are Isolated inside

PGA+ Positive pulse encoder signal A phase

PGA- Codedisc signal A

Negative pulse encoder signal A phase

code signal

PGB+ Codedisc signal B Positive pulse encoder signal B phase

Connect signal of differential input pulse encoder, power voltage range: +8V ~

24V

Page 18: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 17 -

PGB- Pulse encoder signal negative Bphase

Table 3-2 CN2 terminal function

Sort Terminal Name Function Description Specification TA/RA

TB/RB Relay

output terminal TC/RC

MultifunctionalRelay output

terminal

Can be defined as multifunctionalRelay output terminal by

programming, refer to Chapter 6.7P6. 12, P6. 13

TA-TC: NC, TA-TB:Normally open contact Capacity: AC250V/2A (COSΦ=1) AC250V/1A (COSΦ=0.4) DC30V/1A

3.3.4 Analog Input/Output Terminal Wiring (1) Analog voltage signal input through VI terminal as follow wiring:

(2) Analog output terminal AO wiring Analog output terminal can be connected with external analog meter indicating various physical quantity, jumper selection for output voltage (0~10V) or output current (0~20mA) as follow wiring.

Fig. 3-14 Analog output terminal wiring Notes:

(1) Filter capacitor or common-mode inductor can be installed between VI And GND terminal or CI and

GND terminal when using analog input mode.

(2) Please use shielded cable and do well grounding , keep the wire as short as possible in order to prevent

external interference when using analog input/output mode.

3.3.5Communication Terminal Wiring The inverter supplies standard RS 485 communication port. It can constitute a single host-single slave control system or a single host-multi slaves system.The upper

computer(PC/PLC)can real time monitor the inverter in the control system and achieve complicated control function such as remote control and spermatic,etc (1) Remote control panel can be connected with inverter via RS485 port by plugging in the remote control panel into RS485 port without any parameter setting. The local control panel of inverter and remote control panel can work at the same time.

+

VI

GNDPE

YX8000

Shielded cable

proximal grounding

0~+10V

Fig. 3-13 VI terminal wiring

Analog voltage output

Analog current output

Analog meter

AO1

GND

Inverter

IAO1

V

IAO1

V

JP2

Page 19: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 18 -

(2) Inverter RS 485 port and upper computer wiring as follow:

Fig. 3-15 RS485-(RS485/232)-RS232 communication wiring

(3) Multi inverters can be connected together via RS485, controlled by PC/PLC as a host shown as Fig.3-16. It

also can be controlled by one of inverters as a host shown as Fig.3-17.

Fig. 3-16 PLC communication with multi inverters

The more inverters connected , the more serious the communication interference becomes.Please make wiring as

above and do well grounding for inverters and motors,or adopt the following measures to prevent interference as

even above wiring can’t work.

(1) Separately power supply to PC/PLC or isolated the power of PC/PLC.

(2) Use EMIFIL to the wire or reduce carrier frequency properly

3.3.6 Encoder Wiring

Fig.3-17 differential output encoder wiring diagram

YX8000 Panel

PLC Host

+485- PE +485- PE

YX8000 Panel

YX8000 Panel

+485- PE +485- PE

+485- PE

YX8000 Panel

YX8000

Page 20: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 19 -

3.4 Wiring Diagram

3pb power 380±15% 50/60Hz

R

S

T

X1

X2

X3

X6

COM

PE

PE

0-10V 0/4-20mA input

Freq.&PID set

+10V set freq.

VI analog input

V/I input Transform jump line

GND

V I

Relay output

Multi-function input terminals

3

2

6

DC reactor inner 18.5KW-90KW

P1 (+) (-)

P

N

P

PB

Note:bigger than 18.5KW external braking unit

Braking resistor

+24V

PE

TA

TB

TC

J2

YX8000

CI

X55

X44

X77

Y1Open collector

output

COM

Y2Open collector

output

COM

Y3 Open collector output

COM

485+485-

485+

485-

~Analog output

0-10V

AO2

GND

~ Analog output 0-10V

AO1

GND

~ Analog output 0-20mA

AM1

GND

M

U

V

W

PG

PGA+

PGA-

PGB+

PGB-

PE

Fig.3-18 wiring diagram

3.5 Specification table of Breaker、Cable、Contactor、Reactor 3.5.1 Specification of Breaker、Cable、Contactor

Model Breaker(A) iput/output

line(copper wire cable)

Contactor rated currentA(voltage

380or220V) YX8000-4T0055G/4T0075P 25 4 16 YX8000-4T0075G/4T0110P 40 6 25 YX8000-4T0110G/4T0150P 63 6 32 YX8000-4T0150G/4T0185P 63 6 50 YX8000-4T0185G/4T0220P 100 10 63 YX8000-4T0220G/4T0300P 100 16 80 YX8000-4T0300G/4T0370P 125 25 95 YX8000-4T0370G/4T0450P 160 25 120 YX8000-4T0450G/4T0550P 200 35 135 YX8000-4T0550G/4T0750P 200 35 170 YX8000-4T0750G/4T0900P 250 70 230 YX8000-4T0900G/4T1100P 315 70 280 YX8000-4T1100G/4T1320P 400 95 315 YX8000-4T1320G/4T1600P 400 150 380 YX8000-4T1600G/4T1850P 630 185 450

Page 21: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 20 -

Model Breaker(A) iput/output

line(copper wire cable)

Contactor rated currentA(voltage

380or220V) YX8000-4T1850G/4T2000P 630 185 500 YX8000-4T2000G/4T2200P 630 240 580 YX8000-4T2200G/4T2500P 800 150x2 630 YX8000-4T2500G/4T2800P 800 150x2 700 YX8000-4T2800G/4T3150P 1000 185x2 780 YX8000-4T3150G/4T3500P 1200 240x2 900

3.5.2 Specification of Input ac reactor、Output ac reactor and dc reactor

3.6 Main Loop Connection 3.6.1 Main loop power side connection 3.6.1.1 Breaker MCCB suitable for inverter power should be inserted between three-phase AC power and power input

terminals (R, S, T). The capacity of MCCB should be 1.5~2 times as the inverter rated current.please refer to "circuit breakers, cables, contactors specifications list" for details.

3.6.1.2 Electromagnetic contactor In order to effectively remove the input power in the event of a failure,electromagnetic contactor can be

installed in the input side to control the on and off of the main loop power and so as to ensure safty. 3.6.1.3 Input AC reactor AC reactor should be accessed in the input side, in order to protect rectifier part components from the

damage of large currents flowing into the input power circuit as high-voltage grid feeding, but also to improve the input power factor.

3.6.1.4 input side noise filter When using inverter,Electric wire may cause disturbances to nearby electronic systems. You can use this filter

to reduce interference, as shownbelow:

Fig.3-19 Main loop power side connection diagram

Input ac reactor Output ac reactor dc reactor Capacity kW current

(A)

inductance(mH)

current(A)

inductance(uH)

current(A)

inductance(mH)

YX8000-4T0300G/4T0370P 60 0.24 63 90 80 0.86

YX8000-4T0370G/4T0450P 75 0.235 80 80 100 0.70

YX8000-4T0450G/4T0550P 91 0.17 100 60 120 0.58

YX8000-4T0550G/4T0750P 112 0.16 125 40 146 0.47

YX8000-4T0750G/4T0900P 150 0.12 160 35 200 0.35

YX8000-4T0900G/4T1100P 180 0.10 200 30 238 0.29

YX8000-4T1100G/4T1320P 220 0.09 224 20 291 0.24

YX8000-4T1320G/4T1600P 265 0.08 280 16 326 0.215

YX8000-4T1600G/4T1850P 300 0.07 315 13 395 0.177

YX8000-4T1850G/4T2000P 360 0.06 400 11 494 0.142

YX8000-4T2000G/4T2200P 400 0.05 560 9 557 0.126

YX8000-4T2200G/4T2500P 560 0.03 600 8 700 0.10

YX8000-4T2500G/4T2800P 640 0.0215 630 5.5 800 0.08

YX8000-4T2800G/4T3150P 754 0.15 720 5.5 1000 0.04

YX8000-4T3150G/4T3500P 1180 0.01 1250 4 1540 0.015

Page 22: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 21 -

3.6.2 Main loop inverter side connection 3.6.2.1 DC reactor There is built-in dc reactor in the whole series of YX8000 inverter(18.5~90kw). DC reactor can improve the

power factor, can avoid the access of the high-capacity transformer and destroy rectifer bridge by the excessive inputted currrent, can avoid the grid voltage mutation or harm to dc circuit caused by the phase harmonic load.

3.6.2.2 Brake unit and brake resistor For YX8000 inverter under 15kw, brake unit is built in. In order to release the energy in braking runtime,

braking resistor must be connected in P+,PB end. Braking resistor wiring length should be less than 5m. Braking resistor temperature will be increased because of the release of energy, when installing the braking

resistor should pay attention to safety protection and good ventilation. YX8000 inverter above 18.5kw require external braking unit. In order to release the energy in braking

runtime braking resistor must be connected in P+,PB end. The connection length between Inverter P +, P-end and brake unit P +, P-end should be less than 5 m. The

wiring length between brake unit P +, PB and braking resistor P +, PB end should be less than 10 m. Note:Don’t reverse the polarity of P+,P-;P+,P - end are not allowed to directly connect braking

resistor, otherwise it will damage the inverter or fire hazards. 3.6.3 Main loop motor side connection

3.6.3.1 Output reactor

When the distance between the inverter and motor exceeds 50m,overcurrent protection can easily occur due

to large current leakage caused by parasitic capacitance effect of long cable to ground.At the same time in order

to avoid the motor insulation damage,output reactor are needed for compensation.

3.7 EMC Installation Instruction Inverter outputs PWM wave, it will produce electromagnetic noise.To reduce the interference, EMC

installation will be introduced in this section from noise suppression, wire connection,grounding, leakage current

and filter of power supply

3.7.1 Noise Suppression

(1) Noise Type

Noise is unavoidable during inverter operation.Its influence over peripheral equipment is related to the noise

type,transmission means, as well as the design, installation,wiring and grounding of the driving system

(2) Noise Suppression Methods

Path Noise suppression methods

If closed loop is formed between the peripheral equipment and the inverter wiring, the grounding leakage

of the inverter will make the equipment operation error.

Solution: Remove the grounding of the peripheral equipment.

When peripheral equipment share the same power source with the inverter, the noise transmitted through

the power line may make the equipment operation error.

Solution: Mount a noise filter at inverter side, or isolate the peripheral equipment with an isolated

Page 23: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 22 -

transformer or power filter.

④⑤⑥

Electronic equipment such as computers, measuring meters, sensors and radio equipment, when in the

same cabinet with inerter, with their wiring close to the inverter, may lead to operation error due to radio

interference.

Solution:(1)The susceptible equipment and its signal lines should be kept away from the inverter. Use

shielded cable for the signal line. Ground the shielding coat. Protect the signal cable with a metal pipe

and keep it off the inverter input/output cable. When crossing of the signal line and the inverter

input/output cables is inevitable, make sure it is orthogonal.

(2)mount radio noise filter or linear noise filter (choke coil) to the input/output side of the inverter t

suppress the radio noise.

(3)The shielding coat for the cable connecting inverter and the motor should be thick. The wiring can

be arranged through thick pipe (2mm or thicker) or cement trench. The cable should be through a metal

pipe, and has its shielding coat grounded. You may use the 4-core cable as the motor power cable.

Ground one core at inverter side, with the other end of it connected to the motor case.

①⑦⑧

When the signal cables are parallel to, or bound together with the power cables, the static and

electromagnetic induction will cause the noise transmit through the signal cable, thus affecting the

related equipment.

Solution: (1) Avoid laying the signal cable parallel to the power cable, or bind them together. (2) Keep the

susceptible peripheral equipment away from the inverter. (3)Keep the susceptible signal far away from

the input/output cables of inverter. Shielded cables should be used as the signal or power cable. Let them

trough metal pipes respectively would achieve better effect. The metal pipes should be at least 20cm

away from each other.

Table3-3 Noise suppression method

3.7.2 Wiring Connection and Grounding

(1) Please try not to wire motor cable (from inverter to motor) in parallel with power cable and keep at least 30cm from each other .

(2) Please try to arrange the motor cable through Control signal cable metal pipe or in metal wiring groove. Fig. 3-20 Orthogonal wiring

(3) Please use shielded cables control signal cable, and connect the shielding coat to PE terminal of inverter with proximal grounding to inverter.

(4) PE grouding cable should be directly connected to the earth plate. (5) The control signal cable should not be in parallel with strong electricity cable(power cable/motor cable).They

should not be bent together and should be kept away at least 20cm from each other. If cable crossing is inevitable, please make sure it is orthogonal as Fig.3-20

(6) Please ground the control signal cable separately with power cable/motor cable. (7) Please don’t connect other devices to inverter power input terminals(R/S/T ).

Power cable/Motor cable

Page 24: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 23 -

Chapter 4 Running and Operating Instructions of

Frequency Converter 4.1 Running of frequency converter 4.1.1 Command Channel of the running frequency converter

The frequency converter could control its running actions such as start, stop and inching through three channels

command.

Operation panel

Use the keys on the keyboard to operate.

Control terminals

Use the control terminals(FWD, REV, COM) to constitute two-line control. Or use one of the X1~X6, FWD and

COM to constitute three-line control.

Serial port

The upper computer or other equipment which can communicate with the native could control the start and stop of

the frequency converter. The selection of command channel can be done through the setting of function code

P0.02.

Attention: Please debug the switching in advance to confirm whether it can meet the needs of system when

command channel is switched. Otherwise there is a risk of damage to equipment and body.

4.1.2 Given channel by converter frequency

There are eight given physical channels by frequency under normal operation mode, as follow:

0: Given by keyboard simulation potentiometer

1: Given by keyboard operation frequency

2: Set by analog quantity VI

3: Set by analog quantity CI

4: VI+ CI

5: Set by multi-speed operation

6: Set by PID control

7: Set by telecommunication

4.1.3 The working state of frequency converter

The working state of frequency converter is divided into down state and running state.

Down state: After the frequency converter is power on and initialized, it will enter the standby mode immediately

if there is no input run command or the stop command is carried out in service.

Running state: the frequency converter enter the running state immediately after it received a run command.

4.1.4 The operational mode of frequency converter

According to the priority, the operational modes of the YX8000 frequency converter are divided into five types, as

follows: inching operation→closed-loop operation→PLC operation→multi- speed operation→ normal operation,

as shown in figure 4-1.

0: inching operation

In the down state, the converter operate according to the inching frequency(such as pressing the key on

the cancode ) after received the inching operation command(see the function code P3.03~ P3.05).

1: closed-loop operation

The frequency converter will enter closed-loop operation mode when a valid parameter (P0.00=6) of the

closed-loop operation control is set. Regulating the given feedback quantity (such as integral differential operation,

see the P5 group function code), the PID regulator will output basic instruction of output frequency.

FWD STOPRESET

REV JOG

REVJOG

Page 25: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 24 -

Multi-function terminal(such as the 27 function) can invalidate the closed-loop operation mode and switch to a

lower level operation mode.

2: PLC operation

The frequency converter will enter PLC operation mode when a valid parameter (P4.00 units digit≠0) of the PLC

function is set. The frequency converter will run according to the preset operation mode(see the P4 group function

code). Multi-function terminal(such as the 27 function) can invalidate the PLC operation mode and switch to a

lower level operation mode.

3: Multi- speed operation

The nonzero combination of multi-function terminals(such as the 1, 2, 3 function) can choose multistage frequency

1~14 (P3.08~P3.15) to run the multi-speed operation.

4: normal operation

The simple-open loop operation mode of general-purpose inverter.

The above five operation modes can run according to a variety of frequency except the inching operation.In

addition, PLC operation, multi-speed operation and normal operation can run the the pendulum frequency

adjustment.

Fig. 4-1 The logic diagram of the frequency converter’s running states

JOG running

PLC running

Close loop running

Normalrunning

Multi-stage speed running

Power on

Stopping state

Is there a JOG command

s running command effective

Is close loop effective

Is PLC effective?

Are multi-stage freq. Terminal valid?

Is terminal closed and PLC invalid?

s terminal closed and close loop invalid?

High priority level

Low priority level

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

Page 26: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 25 -

4.2 Operation and use of the keyboard 4.2.1 keyboard layout

The operation panel and the control terminals of the frequency converter can control the start, speed governing,

closing down, braking, the setting of operating parameters and peripheral equipments, as show in figure 4-2.

Fig. 4-2 The diagram of operating keyboard

4.2.2 Description of keyboard function

There are eight keys and one analog potentiometer on the keyboard of the frequency converter. The functions are

shown in the follow table.

Key Name Description

Forward running

key Press the key to run the machine under the operation way of keyboard.

Stop/Reset

During normal operation, the frequency converter will close down according to the given setting after pressing the key if the run command channel is set to the

effective way of stop.Besides, it will return to the normal state of downtime after pressing the reset key if it is in the failure state.

Function/Data To enter or exit the programming state.

Jog

Press the key to jog under the operation way of keyboard. If the P9.08 equals 1,press the key to enter the reversal operation.

Increase Increase the data or function code.

Page 27: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 26 -

Reduce Reduce the data or function code.

Shifting /

Monitoring The key can choose modified bits in the edit state while it could switch the

monitoring parameters of display status in other states.

Storage/

Switch Enter the next level menu or storage function code data in the edit state.

+

Combination

The left shift cycle can choose the display parameters.

Attention: Before pressing the REV/JOG , the DATA/ENTER should press first

+

Combination

The frequency converter will stop free if the RUN and STOP/RST are pressed together.

analog

potentiometer

If the P0.01equals zero and the selected keyboard analog potentiometer is given, adjusting the analog potentiometer can control the output frequency of the frequency converter

4.2.3 Description of LED digital tube and indicator lights

1) Description of status indicator lamp

Item Description

LED digital display Display the current running status parameters and setting parameters.

FWD

Forward indicator. The frequency converter output positive phase

sequence and the motor forward if it is on.

REV

Reverse light. The frequency converter output anti- phase

sequence and the motor reverse if it is on.

The frequency converter is in Dc braking state if the FWD and REV indicator lights go on together.

ALM The light is on when the failure alarm of the frequency converter

occurs.

DISPLAY

FUNCTIONS status indicator lamp

MOD

The control indicator lights of keyboard operation, Terminal operation and telecommunication. If the light is out, the frequency converter is in keyboard control state. Lights flashing shows that it is in terminal

operation control state. If the light is on, the frequency converter is in remote control operation state

2) Description of unit indicator light

Symbolic features Description of symbol content

Hz Frequency Units

Page 28: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 27 -

A Current unit

V voltage unit

3) Digital display area

The five LED indicators can show different monitoring data such as the given frequency and output frequency.

Also, it can show the alarm code.

4.2.4 Operation procedure

4.2.4.1 Parameter setting

The three-level menu:

1. Function code group (primary level)

2. Function code label (secondary level)

3. Function code setting value (third-level menu)

Introductions: Pressing the MENU/ESC or DATA/ENTER key can return to the level 2 in the three-level menu operation. The difference between the two keys is that press DATA/ENTER to store the preset parameters in control panel and then back to the second menu,automatically transferring to the next function code;pressing MENU/ESC is to directly back to the second menu without storing parameter and keep rest on the current function code.

For example: function code P3.03 is set to 08.50Hz from 05.00Hz. Take function code P3.03 is set to 08.50Hz from 05.00Hz. for instance.

Fig.4-3 Edit parameter operation exam

Page 29: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 28 -

Fig.4-4 Display status of operation panel programming

In the status of three-level menu, if parameter does not have a flicker bit, that means the function code can’t

be modified.The probable cause may be:

1)The function code is non-modifiable parameter. Such as the actual detection parameter,operation record

parameter and so on.

2) The function code can’t be modified in running status and modification needs to shut down.

4.2.4.2 Fault reset

The fault information will be displayed once the frequency inverter has any fault.The user can reset the fault

by STOP/RESET key or terminal function(P6 group).The frequency inverter is under standby mode after the reset.

If the frequency inverter is under fault mode and the user did not reset, the frequency inverter is under operation

protection mode and can not run.

4.2.4.3 Parameter copy(retention)

Please refer to the function description of LCD external keyboard.

4.2.4.4 Motor parameter self-study

When non-PG vector control mode is selected, the nameplate parameters must be the input accurately so that

the frequency inverter will match standard motor parameters according to the nameplate parameters. You are

suggested to perform the motor parameters self-study in order to obtain excellent control performance. The

procedure is:

Fist select the operation route(P0.02)at keyboard command channel.

Then input the following motor parameters:

P8.01:rated power of the motor

P0.06:rated frequency of the motor

P8.02:rated speed of the motor

P0.07:rated voltage of the motor

P8.03:rated current of the motor

Note:under self-study mode, the motor should be separated from load, otherwise, the parameters you obtain

by self-study may be incorrect.Set P8.00 to 1.Please see function code P8.00 for detailed parameters self-studying

process.Then press FWD on the keyboard,frequency inverter will automatically figure out the following

parameters:

Page 30: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 29 -

P8.04:motor stator resistance

P8.05:motor rotor resistance

P8.06:inductance motor stator/rotor

P8.07:mutual inductance of motor stator/rotor

P8.08:No-load current;finish the self-study of motor parameters.

4.2.4.5 Password setting:

YX8000 series frequency inverter have the function of password protection. If Pd.00 is nonzero,it is the user

password,and then exit the function code editing mode, the password production takes effect. When you enter

function code mode by pressing MENU/ESC, it displays “0.0.0.0.0”. The operator must input the correct user

password, otherwise you can not enter.

If you want to cancel password protection function, set Pd.00 at 0. The user password has no protection

function to the parameter setting in the shortcut menu.

The password protection takes effect 1 min after you exit function code editing mode. Once the password

takes effect, press MENU/ESC to enter function code editing mode, it displays “0.0.0.0.0”.Then operator must

input the correct password, otherwise you can not enter.

4.3 Operating state 4.3.1 Power on initialization

Under the power on process, the system starts initializing and LED displays“-Y-H-”and all 7lights are on.

Then the frequency inverter is in standby mode after its initialization.

4.3.2 Standby mode

It may display multiple mode parameters under stop or operation mode. Yu may select whether to display the

parameter according to binary system by function code P7.02(operational parameters),P7.03(stop parameter)

Under stop mode, there are 9 parameters for you to select whether to display:the frequency,bus voltage,

switching value input mode, open collector output mode, PID setting, PID feedback, analog input VI

voltage,analog CI voltage, multi-speed phases.You may select whether to display by function code P7.02

(transform into binary system)press > >to shift the selected parameter orderly, and press DATA/ENTER +

REV/JOG to shift the selected parameter towards left.

4.3.3 Motor parameter self-study

Please refer to function code P8.00 for detailed instruction.

4.3.4 Operation

Under operation mode, there are 14 mode parameter for option whether to display or not.They are:running

frequency,set frequency,bus voltage,output voltage,output current,output power,output torque, PID setting,

PID feedback,switching value input mode,open-collector output mode,analog input VI voltage,analog input CI

voltage,multi-speed phases.You may select whether to display by function code P7.03(transform into binary

system),press > > to shift the selected parameter orderly,and press DATA/ENTER + REV/JOG to shift the

selected parameter towards left.

4.3.5 Fault

YX8000 series frequency inverter provide information of kinds of faults.Please refer to YX8000 series

frequency inverter faults and countermeasures.

Page 31: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 30 -

4.4 Rapid debugging

Fig.4-5 Flow chart of rapid debugging

Page 32: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 31 -

Chapter 5 Function Parameter Table 5.1 Symbol Description “”:means that the parameter can be revised during running state. “×”: means that the parameter can not be revised during running state. “”:means read-only parameter which can not be revised. 5.2 YX8000 General Series Function Parameter Table

Func Code Name Parameter List Factory

Defaults Change No.

P0 Group: Basic Function Parameter

P0.00 Freq control channel selection

0:Keyboard simulation potentiometer given 1:Keyboard given operating frequency 2:Analogue VI setting 3:Analogue CI setting 4:Analogue VI+ CI setting 5:Multi-speed operation setting 6:PID control setting 7:Remote communication setting 8: Max ( VI, CI )

0 0.

P0.01 Keypad and terminal UP/DOWN setting

0:Effective,power-down memory 1:Effective,no memory after power down 2:Invalid UP/DOWN setting 3:Effective runtime setting,reset when stop

0 1.

P0.02 Operating command mode selections

0:Control panel mode 1:Terminal control mode 2:Serial port control mode

0 × 2.

P0.03 Running frequency digital setting 0.00 Hz~P0.05(The maximum output freq.) 50.00Hz 3.

P0.04 Control mode selection

0:Vector control without PG 1:V/F control 2:Torque control(same as 0) 3:PG closed loop vector control

0 × 4.

P0.05 Maximum output frequency 10.00~600.00Hz 50.00Hz × 5.

P0.06 Motor rated frequency 010.00~600.00Hz Model Setting × 6.

P0.07 Motor rated voltage 0000~400V Model setting 7.

P0.08 Upper limit freq. P0.09~P0.05(The maximum output freq.) 50.00Hz 8.

P0.09 Lower limit freq. 0.00Hz~P0.08(Operation freq. limit) 0.00Hz 9.

P0.10 Acceleration time1 0.1~3600.0s Model Setting 10.

P0.11 Deceleration time1 0.1~3600.0s Model Setting 11.

P0.12 Direction selection 0:Default direction operation 1:Opposite direction operation 2:Ban reverse run

0 × 12.

P0.13 G \ P models setting 0:G-type machine;1:P-type machine 0 × 13.

P0.14 V / F curve setting 0:straight line V/F curve 1:2.0 power down torque V / F curve 0 × 14.

P0.15 Torque boost 0.0%:(Automatic)0.1%~30.0% 0.0% 15.

P0.16 Torque boost cut-off 0.0%~50.0%(Relative motor rated freq.) 20.0% × 16.

Page 33: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 32 -

Func Code Name Parameter List Factory

Defaults Change No.

P0.17 V/F slip compensation limit 0.0~200.0% 0.0% 17.

P0.18 Carrier freq setting 1.0~15.0kHz Model setting 18.

P0.19 Function parameter recovery

0:Non-operation 1:Restore defaults 2:malfunction archives elimination

0 × 19.

P1 Group: Frequency reference function parameter

P1.00 VI min given 0.00V~10.00V 0.00V 20.

P1.01 Corresponding

setting.to VI min given

-100.0%~100.0% 0.0% 21.

P1.02 VI max given 0.00V~10.00V 10.00V 22.

P1.03 Corresponding setting to VI max given -100.0%~100.0% 100.0% 23.

P1.04 VI input-filtering time 0.00s~10.00s 0.10s 24.

P1.05 CI min given 0.00V~10.00V 0.00V 25.

P1.06 Corresponding

setting.to CI min given

-100.0%~100.0% 0.0% 26.

P1.07 CI max given 0.00V~10.00V 10.00V 27.

P1.08 Corresponding

setting.to CI max given

-100.0%~100.0% 100.0% 28.

P1.09 CI input-filtering time 0.00s~10.00s 0.10s 29.

P1.10 Retention 0000~65535 0000 × 30.

P1.11 Retention 0000~65535 0000 × 31.

P2 Group: Start/Brake function parameter

P2.00 Start running mode 0:Direct starting 1:Start after dc brake 2:Start after rotating speed tracking

0 × 32.

P2.01 Start freq. 0.00~10.00Hz 0.00Hz 33.

P2.02 Start freq.running duration 0.0~50.0s 0.0s 34.

P2.03 Dc braking current as start 0.0~150.0% 0.0% 35.

P2.04 Dc braking time as start 0.0~50.0s 0.0s 36.

P2.05 Stop mode selection 0:Dec stop 1:Free Stop 0 37.

P2.06 Start freq.of brake as stop 0.00~P0.05(maximum output freq.) 0.00Hz 38.

P2.07 Waiting time of brake as stop 0.0~50.0s 0.0s 39.

P2.08 DC brake current as stop 0.0~150.0% 0.0% 40.

P2.09 DC brake time as stop 0.0~50.0s 0.0s 41.

Page 34: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 33 -

Func Code Name Parameter List Factory

Defaults Change No.

P2.10 Energy consumption

brake valve value voltage

115.0~140.0%(Standard busbar voltage)(380V series) 130.0% 42.

P2.11 Terminals running

protection selection as power on

0:Invalid terminal operation command as power on 1:Valid terminal operation command as power on

0 43.

P2.12 Lower limit freq. operation mode

0:Run in lower limit freq. 1:Run at zero frequency 0 × 44.

P2.13 Retention 0000~65535 0000 × 45.

P3 Group :Auxiliary running parameter

P3.00 FWD/REV dead time 0000.0~3600.0S 0.0S 46.

P3.01 AVR function selection 0:Null 1:The whole effective 2:Only invalid when it slows down

2 47.

P3.02 Energy-saving operation selection

0:Inaction 1:Automatic energy saving operation 0 × 48.

P3.03 Inching operation frequency 0.00~P0.05(Maximum output freq.) 5.00Hz 49.

P3.04 Inching acceleration time 0.1~3600.0s Model

Setting 50.

P3.05 Inching deceleration time 0.1~3600.0s Model

Setting 51.

P3.06 Acceleration time 2 0.1~3600.0s Model Setting 52.

P3.07 Deceleration time 2 0.1~3600.0s Model Setting 53.

P3.08 Multi-velocity 0 -100.0~100.0% 0.0% 54.

P3.09 Multi-velocity 1 -100.0~100.0% 0.0% 55.

P3.10 Multi-velocity 2 -100.0~100.0% 0.0% 56.

P3.11 Multi-velocity 3 -100.0~100.0% 0.0% 57.

P3.12 Multi-velocity 4 -100.0~100.0% 0.0% 58.

P3.13 Multi-velocity 5 -100.0~100.0% 0.0% 59.

P3.14 Multi-velocity 6 -100.0~100.0% 0.0% 60.

P3.15 Multi-velocity 7 -100.0~100.0% 0.0% 61.

P3.16 Jump frequency 0.00~P0.05(Maximum output freq.) 0.00Hz 62.

P3.17 Jump frequency range 0.00~P0.05(Maximum output freq.) 0.00Hz 63.

P4 Group PLC program control operation parameters

P4.00 Simple PLC running mode selection

0:Inaction 1:Shut down after single cycle 2:Keep the final value after single cycle 3:Continuous cycle

0 × 64.

Page 35: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 34 -

Func Code Name Parameter List Factory

Defaults Change No.

P4.01 Selection of restart way

after simple PLC was interrupted

0:Start again from the first segmant 1:Continue to run from the phase frequency of interrupt time 2:Continue to run from the operating frequency of interrupt time

0 × 65.

P4.02 PLC status parameters

pwer-down storage selection

0:Non storage 1:Storage 0 × 66.

P4.03 Stage time unit selection

0: second 1: minute

0 × 67.

P4.04 Stage 1 freq. setting

(Multistage frequency 8)

000.00~P0.05(Maximum output freq.) 020.00HZ 68.

P4.05 Stage 1 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 69.

P4.06 Stage1 ACC time 0000.1~3600.0S 0010.0S 70.

P4.07 Stage1 DEC time 0000.1~3600.0S 0010.0S 71.

P4.08 Stage1 running time 0000.0~6500.0 0020.0 72.

P4.09 Stage2 freq. setting

(Multistage frequency 9)

000.00~P0.05(Maximum output freq.) 025.00HZ 73.

P4.10 Stage 2 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 74.

P4.11 Stage2 ACC time 0000.1~3600.0S 0010.0S 75.

P4.12 Stage2 DEC time 0000.1~3600.0S 0010.0S 76.

P4.13 Stage2 running time 0000.0~6500.0 0020.0 77.

P4.14 Stage3 freq. setting

(Multistage frequency 10)

000.00~P0.05(Maximum output freq.) 030.00HZ 78.

P4.15 Stage 3 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 79.

P4.16 Stage3 ACC time 0000.1~3600.0S 0010.0S 80.

P4.17 Stage3 DEC time 0000.1~3600.0S 0010.0S 81.

P4.18 Stage3 running time 0000.0~6500.0 0020.0 82.

P4.19 Stage4 freq. setting

(Multistage frequency 11)

000.00~P0.05(Maximum output freq.) 035.00HZ 83.

P4.20 Stage 4 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 84.

P4.21 Stage4 ACC time 0000.1~3600.0S 0010.0S 85.

P4.22 Stage4 DEC time 0000.1~3600.0S 0010.0S 86.

P4.23 Stage4 running time 0000.0~6500.0 0020.0 87.

P4.24 Stage5 freq. setting

(Multistage frequency 12)

000.00~P0.05(Maximum output freq.) 040.00HZ 88.

Page 36: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 35 -

Func Code Name Parameter List Factory

Defaults Change No.

P4.25 Stage 5 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 89.

P4.26 Stage 5 ACC time 0000.1~3600.0S 0010.0S 90.

P4.27 Stage 5 DEC time 0000.1~3600.0S 0010.0S 91.

P4.28 Stage 5 running time 0000.0~6500.0 0020.0 92.

P4.29 Stage6 freq. setting

(Multistage frequency 13)

000.00~P0.05(Maximum output freq.) 045.00HZ 93.

P4.30 Stage 6 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0 94.

P4.31 Stage6 ACC time 0000.1~3600.0S 0010.0S 95.

P4.32 Stage6 DEC time 0000.1~3600.0S 0010.0S 96.

P4.33 Stage6 running time 0000.0~6500.0 0020.0 97.

P4.34 Stage6 freq. setting

(Multistage frequency 14)

000.00~P0.05(Maximum output freq.) 050.00HZ 98.

P4.35 Stage6 freq. setting

(Multistage frequency 14)

0:Foreward 1:Reverse 2:Be determined by the run command

0 99.

P4.36 Stage7 ACC time 0000.1~3600.0S 0010.0S 100.

P4.37 Stage7 DEC time 0000.1~3600.0S 0010.0S 101.

P4.38 Stage7 running time 0000.0~6500.0 0020.0 102.

P5 Group PID Closed loop control parameters

P5.00 PID given channel selection

0: Keypad reference(P5.01) 1:Analog channel VI reference 2:Analog channel CI 0 ~ 10V reference 3:Remote communications reference 4:Multi segment reference 5:Analog channel CI 4 ~ 20 mA reference

0 103.

P5.01 Keypad Preset PID reference 0.0%~100.0% 0.0% 104.

P5.02 PID feedback source selection

0:Analog channel VI feeback 1:Analog channel CI feeback 2:VI+CI feeback 3:Remote communications feeback 4:Analog channel CI 4 ~ 20mA feeback

0 105.

P5.03 PID output characteristics selection

0: positive characteristic 1: negative characteristic 0 106.

P5.04 Proportional gain(Kp) 0.00~100.00 1.00 107.

P5.05 Integral time(Ti) 0.01~10.00s 0.10s 108.

P5.06 Derivative time(Td) 0.00~10.00s 0.00s 109.

P5.07 Sampling period(T) 0.01~100.00s 0.10s 110.

P5.08 PID control deviation limit 0.0~100.0% 0.0% 111.

P5.09 Feedback

disconnection detection value

0.0~100.0% 0.0% 112.

Page 37: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 36 -

Func Code Name Parameter List Factory

Defaults Change No.

P5.10 Feedback

disconnection detection time

0.0~3600.0s 1.0s 113.

P5.11 Feedback

disconnection action selection

0:Invalid 1:Shunt-down alarm 2:Run according to the frequency of P0.03 3:Run according to upper limit freq. 4:Run according to half of the upper limit freq.

0 114.

P5.12 Sleep Frequency P0.09( lower limit freq.) ~P0.05(When set to 0 hz sleep function is invalid) 000.00 115.

P5.13 Sleep latency 000.0~120.0S 030.0S 116.

P5.14 Awakening threshold 000.0~100.0%(Feedback value relative to the percentage of full scale) 0.10.0% 117.

P6 Group:Terminal control function parameter

P6.00 X1 Terminal function selection

0: No function 1: Forward run 2: Reverse run 3: Three-wire operation control 4: Inching forward 5:Inching reversedly 6: Free stop 7: Fault reset 8: External fault input 9: Increasing frequency setting(UP) 10: Decreasing frequency setting(DOWN) 11:Clear frequency fluctuation setting 12: Multi-speed terminal 1 13: Multi-speed terminal 2 14: Multi-speed terminal 3 15: ACC and DEC time selection 16: PID pause control 17: Swing freq pause( Stop at the current frequency) 18: Swing freq reposition(Back to the center frequency) 19: Ban ACC and DEC 20: Ban torque control 21: Clear frequency change settings temporarily 22: Simple PLC program reset 23:Simple PLC program run pause 24:Auxiliary frequency source selection 25:Multi-speed terminal 4 26:Simple PLC program reset at stop state 27:Simple PLC program failure

1 × 118.

P6.01 X2 Terminal function selection Same as X1 terminal function 4 × 119.

P6.02 X3 Terminal function selection Same as X1 terminal function 7 × 120.

P6.03 X4 Terminal function selection Same as X1 terminal function 0 × 121.

P6.04 X5 Terminal function selection Same as X1 terminal function 0 × 122.

P6.05 X6 Terminal function selection Same as X1 terminal function 0 × 123.

P6.06 X7 Terminal function selection Same as X1 terminal function 0 × 124.

P6.07 Switching value filtering times 1~10 5 125.

Page 38: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 37 -

Func Code Name Parameter List Factory

Defaults Change No.

P6.08 Terminal control operation mode

0:Two-wire control 1 1:Two-wire control 2 2:Three-wire control 1 3:Three-wire control 2

0 × 126.

P6.09 Terminal UP/DOWN frequency increment

rate of change 0.01~50.00Hz/s 0.50Hz/s 127.

P6.10 Y1 output selection

0: No output 1:Motor forward operation 2:Motor reverse operation 3:Fault output 4:Frequency level detection FDT output 5:set freq. to 6:Zero-speed operation 7:Upper limit freq. reaches 8:Lower limit freq. reaches 9: Set Lower limit freq.to 10:FDT freq. reaches 11:Simple PLC program run loop termination

1 128.

P6.11 Y2 output selection Same as Y1 output selection 00 129.

P6.12

Y3 output selection Or relay output

selection(RA、RB、RC)

Same as Y1 output selection 00 130.

P6.13 Relay output selection(TA、TB、TC) Same as Y1 output selection 03 131.

P6.14

AO1 output selection (Factory AO1 output

voltage is 0 ~ 10V. For AO1 output 0 ~ 20mA

or 4 ~ 20mA, JP2 jumper jumps to IS

side;If AO1 outputs 4 ~ 20mA P6.15 shall be

set to 2.00)

00:Running freq. 01:Set freq. 02:Running speed 03:Output current 04:Output voltage 05:Output power 06:Output torque 07:Analog VI input value 08:Analog CI input value 09~10:Retention

0 132.

P6.15 AO1 Output limit 0.0%~100.0% 0.0% 133.

P6.16 The lower limit

corresponding to AO1 output

0.00V ~10.00V 0.00V 134.

P6.17 AO1 output upper limit 0.0%~100.0% 100.0% 135.

P6.18 The upper limit

corresponding to AO1 output

0.00V ~10.00V 10.00V 136.

P6.19 FDT detection value 0.00~ P0.05(Maximum output freq.) 50.00Hz 137.

P6.20 FDT hysteresis measurements 0.0~100.0%(FDT level) 5.0% 138.

P6.21 Freq. arrival(FAR)check out the amplitude 0.0~100.0%(Maximum output freq.) 0.0% 139.

P6.22 TA\TB\TC closing delay 0000.0S~6553.5S 0000.0S 140.

P6.23 TA\TB\TC off-delay 0000.0S~6553.5S 0000.0S 141.

Page 39: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 38 -

Func Code Name Parameter List Factory

Defaults Change No.

P6.24 RA\RB\RC closing delay 0000.0S~6553.5S 0000.0S 142.

P6.25 RA\RB\RC off-delay 0000.0S~6553.5S 0000.0S 143.

P6.26 AO2 output selection (0~10V voltage)

00:Operating freq. 01:Set freq. 02:operating speeds 03: Output current 04:Output voltage 05:Output power 06:Output torque 07:Analog VI input value 08:Analog CI input value 09~10:Retention

0 144.

P6.27 AO2 output limit 0.0%~100.0% 0.0% 145.

P6.28 Lower limit

corresponding to output AO2

0.00V ~10.00V 0.00V 146.

P6.29 AO2 output upper limit 0.0%~100.0% 100.0% 147.

P6.30 The upper limit

corresponding AO2 output

0.00V ~10.00V 10.00V 148.

P7 Group Display control parameters

P7.00 LCD display language

selection (retention)

0:Chinese 1:English 0 149.

P7.01 Keypad display selection

0:Irfpa keyboard priority in use 1:Local and external keypad display simultaneously, Only irfpa buttons in force. 2:Local and external keypad display simultaneously,only the native buttons in force.3:Local and external keypad display simultaneously and both keys are valid(logical relationship between the two)

0 150.

P7.02 The displayed

parameters of running status selection

0~0x7FFF BIT0:Operating freq. BIT1:Setting freq. BIT2: Bus voltage BIT3:Output voltage BIT4:Output current BIT5:Operating speed BIT6:Output power BIT7:Output torque BIT8:PID given value BIT9:PID feeback value BIT10:Input terminal status BIT11:Output terminal status BIT12:Analog quantity VI value BIT13:Analog quantity CI value BIT14:The current number of multistage speedBIT15:Retention

0xFF 151.

Page 40: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 39 -

Func Code Name Parameter List Factory

Defaults Change No.

P7.03 The displayed parameters of the stop condition selection

1~0x1FF BIT0:Set freq. BIT1:Bus voltage BIT2: Input terminal status BIT3:Output terminal status BIT4:PID given value BIT5:PID feedback value BIT6:Analog quantity AI1 value BIT7:Analog quantity AI2 value BIT8:The current number of multistage speedBIT9~ BIT15: Retention

0xFF 152.

P7.04 The displayed coefficient of motor speed

0000.0~1000.0% rotational speed of machines=120*operation freq.*P7.06/pole number

0100.0% 153.

P7.05 Software version 154.

P7.06 Retention 155.

P8 Group Motor paramenters

P8.00 Self learning of motor

parameter

0:No operation 1:Comprehensive self learning parameters 2: Self learning of static parameters

0 × 156.

P8.01 Motor rated power 0.75~500kW Model setting × 157.

P8.02 Motor rated speed 0~36000rpm Model setting × 158.

P8.03 Motor rated current 0.1~850.0A Model setting × 159.

P8.04 Motor stator resistance 0.001~65.535Ω Model setting 160.

P8.05 Motor rotor resistance 0.001~65.535Ω Model setting 161.

P8.06 Motor stator and rotor inductance 0.1~6553.5mH Model

setting 162.

P8.07 Motor stator and rotor mutual inductance 0.1~6553.5mH Model

setting 163.

P8.08 Motor no-load current 0.01~655.35A Model setting 164.

P9 Group Vector control and enhancing function parameters

P9.00 Speed loop proportion gain 1 0~100 20 165.

P9.01 Speed loop integral time 1 0.01~10.00s 0.50s 166.

P9.02 Low switching frequency 0.00Hz~P3.05 5.00Hz 167.

P9.03 Speed loop proportion gain 2 0~100 15 168.

P9.04 Speed loop integral time 2 0.01~10.00s 1.00 169.

P9.05 High switching frequency P3.02~P0.05(The maximum frequency) 10.00Hz 170.

Page 41: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 40 -

Func Code Name Parameter List Factory

Defaults Change No.

P9.06 VC slip compensation coefficient 50%~200% 100% 171.

P9.07 Torque upper limit setting 0.0~200.0%(Inverter rated current) 150.0% 172.

P9.08 REV/JOG function selection

0:Inching operation 1:Forward reverse switching 2:Clear UP / DOWN setting

0 × 173.

P9.09 STOP/RST Stop function selection

0:Applies only to control panel 1 : Simultaneously effective for Panel and terminal control 2 : Simultaneously effective for panel and communication control 3:Effective for all control model

0 174.

PA Group Protection function parameter

PA.00

Motor overload protection

mode selection

0:No protection 1:common motors(With low speed compensation) 2:Variable frequency motor (Without low speed compensation)

2 × 175.

PA.01 Motor overload

protection current

20.0%~120.0%(Motor rated current) 100.0% 176.

PA.02

Instantaneous frequency reduction point when power

supply drop

70.0~110.0%(Standard busbar voltage) 80.0% 177.

PA.03 Instantaneous

frequency decrease rate when power supply

drop 0.00Hz~P0.05(Maximum frequency) 0.00Hz 178.

PA.04 Overvoltage stall protection

0:Forbid protection 1:Permit protection 0 179.

PA.05 Overvoltage stall protection voltage

110~150%(380V series)

120% 180.

PA.06 Current limiting choice 0:Current limiting is steadily valid 1:Current limiting at constant speed is invalid 0 164

PA.07 Automatic current limit levels 100~200%

G type:160%

P type:120%

181.

PA.08 Frequency decrease rate as current limiting 0.00~100.00Hz/s 10.00Hz/s 182.

PA.09 Automatic reset failure times 0~3 0 183.

PA.10 Interval Time Setting

of failure automatic reset

0.1~100.0S 1.0s 184.

PA.11 The first two types of failure

0~24 0:Fault-free 1: Frequency converter speed running over current(E-01) 2:Inverter slow running over current(E-02)3:Inverter constant speed operation over current(E-03)

185.

Page 42: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 41 -

Func Code Name Parameter List Factory

Defaults Change No.

PA.12 Previous fault type 186.

PA.13 Current fault type

4 : Frequency converter speed operating overvoltage(E-04) 5:Inverter deceleration operating overvoltage(E-05) 6 : The inverter constant speed operating overvoltage(E-06) 7:Over voltage inverter control power(E-07)8:Inverter overheat(E-08) 9: frequency overload(E-09) 10:Motor overload(E-10) 11:Undervoltage in operation(E-11) 12:Inverter modules protection(E-12) 13:External equipment failure(E-13) 14:The current detects circuit fault(E-14) 15 : RS232/485 communication malfunction(E-15) 16:System interference(E-16) 17:E2PROM read or write error(E-17) 18: Motor parameter self-learning over-current fault(E-18) 19:The input phase lack protection(E-19) 20:overcurrent fault of inspection speed restart(E-20) 21:PID feedback disconnection fault(E-21)

187. 3

PA.14 The current fault operation frequency 0.00Hz 188.

PA.15 The current fault output current 0.0A 189.

PA.16 The current fault busbar voltage 0.0V 190.

PA.17 Current fault input terminal status 0 191.

PA.18 Current fault output terminal status 0 192.

PA.19 Input phase lack

protection function selection

0:Invalid input phase lack protection function 1:Valid input phase lack protection function 193.

PB Group Serial Communications

Pb.00 The machine communication address 1~247,0:broadcast address 1 194.

Pb.01 Communication baud rate setting

0:1200bps 1:2400bps 2:4800bps 3:9600bps 4:19200bps 5:38400bps

3 195.

Page 43: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 42 -

Func Code Name Parameter List Factory

Defaults Change No.

Pb.02 Data bits calibration set

0: No parity(N,8,1)for RTU 1: Even parity check(E,8,1)for RTU 2: Odd check(O,8,1)for RTU 3: No parity(N,8,2)for RTU 4: Even parity check(E,8,2)for RTU 5: Odd check(O,8,2)for RTU 6: No parity(N,7,1)for ASCII 7: Even parity check(E,7,1)for ASCII 8: Odd check(O,7,1)for ASCII 9: No parity(N,7,2)for ASCII 10: Even parity check(E,7,2)for ASCII 11: Odd check(O,7,2)for ASCII 12: No parity(N,8,1)for ASCII 13: Even parity check(E,8,1)for ASCII 14: Odd check(O,8,1)for ASCII 15: No parity(N,8,2)for ASCII 16: Even parity check(E,8,2)for ASCII 17: Odd check(O,8,2)for ASCII

0 196.

Pb.03 Communication response time delay 0~200ms 5ms 197.

Pb.04 Communication timeout failure time 0.0(Invalid),0.1~100.0s 0.0s 198.

Pb.05 Transmission error handling

0:Alarm and free parking 1:No alarm and continue running 2:No alarm and stop in stopping mode(Only communication control mode) 3:No alarm and stop in stopping mode(all the control mode)

1 199.

Pb.06 Transmission response handling

0:Respose as writing operation 1:No respose as writing operation 0 200.

PC Group The swing frequency and supplementary functions

PC.00 Inhibition of low oscillation freq. threshold point

0~500 5 201.

PC.01 Inhibition of high oscillation freq. threshold point

0~500 100 202.

PC.02 Inhibition of oscillation amplitude limit value 0~10000 5000 203.

PC.03 Dividing freq. inhibition of high oscillation frequency

0.00Hz~P0.05(The maximum freq.) 12.50Hz 204.

PC.04 Oscillation suppression 0:Inhibition of oscillation is valid 1:Inhibition of oscillation is invalid 1 205.

PC.05 PWM selection 0:PWM mode1 1:PWM mode2 2:PWM mode3

0 206.

PC.06 PWM mode1 speeding up boundary frequency 0~50.0 14.0 159

PC.07 PWM mode1 slowing up boundary frequency 0~50.0 11.0 160

Page 44: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 43 -

Func Code Name Parameter List Factory

Defaults Change No.

PC.08 Torque setting mode selection

0:Keyboard sets torque(Pd.07)(100% relative to P3.07 torque upper limit)

1:Analog quantity AI1 sets torque(100% relative to P3.07 torque upper limit) 2:Analog quantity AI2 sets torque(100% relative to P3.07 torque upper limit) 3:Analog quantity AI1+AI2v(100% relative to

P3.07 torque upper limit) 4: Multi-stage torque setting(100% relative to P3.07 torque upper limit) 5:Remote communication sets torque(100% relative to P3.07 torque upper limit)

0 161

PC.09 Keyboard sets torque -100.0%~100.0% 0 162

PC.10 Upper limit frequency setting source selection

0:Keyboard sets an upper limit freq.(P0.05)1:Analog quantity AI1 sets an upper limit freq.(100% corresponds to the maximum freq.) 2:Analog quantity AI2 sets an upper limit freq.(100% corresponds to the maximum freq.) 3:Multi stage sets an upper limit frequency(100% corresponds to the maximum freq.) 4:Remote communication sets an upper limit frequency(100% corresponds to the maximum freq.)

0 163

PC.11 Swing freq. range 0.0~100.0%(The relative freq. setting) 0.0% 207.

PC.12 A sudden jump freq. range 0.0~50.0%(The relative swing freq. range) 0.0% 208.

PC.13 Swing freq. rise time 0.1~3600.0s 5.0s 209.

PC.14 Swing freq. fall time 0.1~3600.0s 5.0s 210.

PD Group:Inverter PG loop and its parameters

Pd.00 User password 0~65535 0 211.

Pd.01 The rectifier module temperature 0~100.0 212.

Pd.02 The invertor module temperature 0~100.0 213.

Pd.03 Cumulative operation time 0~65535h 0 214.

Pd.04 Function parameter copy (retention) 215

Pd.05 PG encoder pulse number 50~9999 1000 216

Pd.06 PG encoder direction 0:forward direction;1:reverse direction 0 217

Pd.07 PG encoder

disconnected action selection

0:continue running;1:shut down 1 218

Pd.08 PG encoder

disconnection detection time

2.0~10.0S 2.0 219

Pd.09 Zero speed detection 0:Prohibit disconnection protection;1~999 RPM 0 220

Page 45: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX8000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 44 -

Func Code Name Parameter List Factory

Defaults Change No.

Pd.10 Retention

PE Group Factory function parameter

PE.00 Factory password 0~65535 ***** 165

Page 46: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 45 -

Chapter 6 Function Code Description 6.1 Basic running function parameter (P0 Group)

Func Code Name Illustration Setting range Default value

P0.00 Freq control channel selection

0:Keyboard simulation potentiometer given 1:Keyboard given operating frequency2:Analogue VI setting 3:Analogue CI setting 4:Analogue VI + CI setting 5:Multi-speed operation setting 6:PID control setting 7:Remote communication setting 8: Max ( VI, CI )

0~7 0

Select the A frequency command input channel. There are 7 main given frequency channels: 0:keyboard simulation potentiometer given 1:Keyboard given operating frequency By modifying the function code P0.00 "running frequency digital set" values, to achieve the purpose of the keyboard setting frequency.Use、 key to fine-tune the numerical value. 2:Analogue VI setting 3:Analogue CI setting 4:Analogue VI + CI setting Frequency is set by analog input terminal. YX8000 series inverter standard configuration provides two-way

analog input terminals. VI is 0 ~ 10V voltage input, CI can be both 0 ~ 10V voltage input 0~20mA and 4~20mA current input. Current and voltage input can be switched by the jumper JP1. Note:When the VI is 0 ~ 20mA input, the20mA corresponding voltage is 5V.

The setted 100.0% of the analog input corresponds to the maximum frequency (functional code P0.05);-100.0% corresponds to the reversed maximum frequency(functional code P0.05).

5:Multi-speed operation setting Choose the frequency setting mode, frequency converter running in multistage speed way. You need to set

up "section of the speed control" parameters of P3 and P6 group to determine the corresponding relation of a given percentage and a given frequency.

6:PID control setting Choice of this parameter means inverter runs in process PID control mode. At this time, you need to set up

P9 group "PID control group".The frequency value affected by PID function is the inverter operation frequency and the meaning of PID given source、given quantity、feedback source is stated in P9 group“PID function”.

7:Remote communication setting frequency instruction is given by the upper machine through communication mode. Please refer to the

communication protocol for more details. 8: Max ( VI, CI ).

Func Code Name Illustration Setting range Default

value

P0.01 Keyboard and

terminal UP/DOWN setting

0:Effective,power-down memory 1:Effective,no memory after power down 2:Invalid UP/DOWN setting 3:Effective runtime setting,clear zero as stop

0~3 0

Inverter’s frequency can be set through keyboard “∧”,“∨”and terminals UP/DOWN(Increasing frequency setting / Decreasing frequency setting),which own the highest authority and can be combined with any other frequency channels。It mainly completes fine-tuning output freq. in the process of control system debugging.

0:Effective,power-down memory. Frequency instructions can be set and stored after power down,and automatically combines with the current frequency as power on again.

1:Effective,no memory after power down. Frequency instructions can be set,but can’t be stored after power

Page 47: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 46 -

down. 2:Invalid,Frequency values set by keyboard and terminal UP/DOWN automatically clear zero. Keyboard

and terminal UP/DOWN is invalid. 3:The setting of “∧”, “∨”and UP/DOWN function is effective in operation,The setting of “∧”, “∨”and

UP/DOWN function clears zero as shut down. Note:Frequency values set by keyboard and terminal UP/DOWN automatically clear zero after user

restores the default value of frequency converter function parameters Func Code Name Illustration Setting

range Default value

P0.02 Operation instruction channel

0:keyboard instruction channel(LED extinguishing) 1:terminal instruction channel(LED flickering) 2:Communications Directive channel(LED shining)

0~2 0

Choose control intruction channel. Control command include:start、stop、foreward、reverse、inching、fault reset and so on. 0:Keyboard command channel(“MOD”go out);

FWD、STOP/RESETon the keyboard control run command. If multifunction button REV/JOG is set to switching function FWD/REV( P7.03 set to 1), it can change the running direction. Pressing the button FWD and STOP/RESET in running status can make the inveter freely stop.

1:terminal instruction channel(“MOD” flickering); Run command is controlled by the FWD, REV , FJOG, RJOG of multifunction input terminal.

2:Communications Directive channel(“MOD”shining); Run command is controlled by the upper machine through through the communication mode.

Func Code Name Illustration Setting range Default value

P0.03 Freq set by keypad 0.00 Hz~P0.05(Max freq.) 0.00~P0.05 50.00Hz When "keyboard operation frequency reference" is chosen as the frequency instruction, its code value is the

initial value set for frequency number. Func Code Name Illustration Setting

range Default value

P0.04 Control mode selection

0:Vector control without PG 1:V/F control 2:Torque control(same as 0) 3:PG closed loop vector control

0~3 0

Operation mode selection: 0:Vector control without PG It refers to open-loop vector and applies to high performance and general situations without PG encoder.One

frequency inverter can only drive one motor, such as machine tool,centrifugal machine,wire drawing machine and injection molding machine.

1:V/F control It’s suitable for situations that require less control accuracy,such as fans and pumps and available for

situation that one inveter drives multiple motors. 2:Torque control(same as 0) It’s suitable for wire-wound and wire drawing situations that require less torque control accuracy.Under

torque control mode,the load of the motor determines the rotating speed,which will no longer be determined by the time.

3. PG closed loop vector control It’s suitable for situations that have demanding requirement on velocity control accuracy, such as electric

drive.Rotary encoder is needed if using this kind of inverter and the relevant parameter controlled by PG closed loop needs to be adjusted.

Note:Motor parameter is a sef-learing requirement for using vector control. Only getting the exact motor parameters can give a full play to the superiority of the vector control mode. Better performance can be obtained by adjusting the speed regulator parameters (P9).

Page 48: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 47 -

Func Code Name Illustration Setting range Default value

P0.05 Max output freq. 10.00~600.00Hz 10.00~600.00 Hz 50.00Hz It’s used to set the highest output frequency. Pls note that it is the basis of setting frequency and also the

foundation of ACC/DEC speed. Func Code Name Illustration Setting range Default value

P0.06 Motor rated freq. 10.00~600.00Hz 10.00~600.00Hz 50.00Hz The rated frequency on the nameplate of load motor should be entered into this parameter, which is the

foundation of V/F vurve setting.Users must correctly input the parameters. Func Code Name Illustration Setting range Default value

P0.07 Motor rated voltage 000~400V 000~400V 380V The rated voltage on the nameplate of load motor should be entered into this parameter, which is the

foundation of V/F curve setting.Users must correctly input the parameters. Func Code Name Illustration Setting range Default value

P0.08 Upper freq. P0.09~P0.05(Max freq.) P0.09~P0.05 50.00Hz It is the upper limit value of output freq. This value should be less than or equal to the maximum output

frequency. Func Code Name Illustration Setting range Default value

P0.09 Lower running freq.

0.00Hz~P0.08(Upper freq.) 0.00~P0.08 0.00Hz

It is the lower limit value of output freq. Among them, max output freq.≥upper limit freq.≥lower freq. Func Code Name Illustration Setting range Default value

P0.10 ACC time 0 0.1~3600.0s 0.1~3600.0 Depends on model type

P0.11 DEC time 0 0.1~3600.0s 0.1~3600.0 Depends on model type

Acceleration time refers to the required time t1 of inverter speeding up from 0Hz up to the max output freq. (P0.05)

Deceleration time refers to the required time t2 of inverter slowing down from the max output freq. (P0.05) to 0Hz. As shown below:

The set acc time

Actual dec time

The set dec time

time

MAXf

SETf

Output freq.

Actual acc time

Fig.6-1 ACC/DEC time

When the preset frequency equals to the max freq., the actual ACC and DEC time is in line with the given

ACC and DEC time. When the preset frequency is less than the max freq.,the actual ACC time is less than the set ACC and DEC

Page 49: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 48 -

time. the actual ACC and DEC time = the stated ACC and DEC time×(the stated freq./ the max freq.) It’s possible to choose ACC and DEC time by multifunctional digital input terminal group(P6 group). For 5.5kW models and under, the factory value of ACC and DEC time is 10.0s;as to 7.5kW-55kW models,

the factory value of ACC and DEC time is 20.0s;for 75kW models and above, the factory value of ACC and DEC time is 40.0s.

Func Code Name Illustration Setting range Default value

P0.12 Direction selection 0:Default direction operation 1:Opposite direction operation 2:Ban reverse run

0~2 0

0:Default direction operation. Inverter runs according to the actual direction after power on. 1:Opposite direction operation. The motor rotation direction can be changed under the condition of without

changing any other parameters by changing the function code.Its function is equivalent to that the conversion of rotation direction can be achieved by adjusting any of the two lines of motor line (U, V, W).

Note:Parameter is initialized, the motor running direction will restore to the original state.When system is well debugged,inverters should be used with caution in the occasion that prohibits altering motor rotation.

2:Ban reverse run. It’s suitable for the specific condition that prohibits reverse run. Func Code Name Illustration Setting range Default value

P0.13 Model selection 0:G type inverter 1:P type inverter

0~1 0

0:Applicable to constant torque load of the specified rated parameters. 1:Applicable to variable torque load of the specified rated parameters.(load of fans and pumps) YX8000 series frequency inverter has the advantages of both G type and P type,namely motor power

adaptive to constant torque load (G type) is one class smaller than motor power adaptive to the load of fans and pumps (P type).

Factory parameter is set to G type,P type selection is as follows: e.g.:YX8000-4T0220G has been set to 22kw G type when delivery.If 30kw P type is expected,users need to

do the following: (1) Set the function code to 1; (2) Reinstall motor parameters in P8 group.

This function code is effective for V/F control(P0.04=1),but ineffective for vector control.

Func Code Name Illustration Setting range Default value

P0.14 V/F curve setting 0:straight line V/F curve 1:2.0 power down torque V / F curve

0~1 0

For fans and pumps-type load,You may choose V/F control. 0:straight line V/F curve,suitable for common constant torque load. 1:2.0 power down torque V / F curve,suitable for centrifuge load of fans and pumps.

bf

bV

bf3/1

Fig. 6-2 Sketch map of V/F curve

Page 50: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 49 -

Func Code Name Illustration

Setting range

Default value

P0.15 Torque boost 0.0%:(automatic)0.1%~30.0% 0.0~30.0 0.0% P0.16 Cutoff point of

torque boost 0.0%~50.0%(relative to motor rated freq.)

0.0~50.0 20.0%

Toruqe boost mainly applies to under cut-off freq.Once lifted, V/F curve is shown in below figure.Torque boost helps to improve V/F low-freq. torque characteristics. Choose torque volume according to load.Large load can increase the lift,but torque should not be too large.Excessive torque boost is prone to overheating when over-excitation operation,because large output current reduces efficinency.

When the torque boost is set to 0.0%, the inverter is automatic torque boost. Cut-off point of torque boost: torque boost is effective under this frequency,but inefective if beyond this

frequency.

Fig. 6-3 Manual torque boost

Func Code Name Illustration Setting range

Default value

P0.17 V/F slip compensation limit

0.0~200.0% 0.0~200.0 0.0%

This parameter can be set to compensate for changes in motor speed generated by the load under V/F

control,which can improve the mechanical properties of the motor hardness and 100.0% corresponding motor's

rated slip frequency. Func Code Name Illustration Setting range Default value

P0.18 Carrier freq.setting 1.0~15.0kHz 1.0~15.0 Model setting

1KHz

10KHz

15KHz

Noise leakage

current

Thermal

degradation

big

small big big

small small

Carrier freq.

Electro magnetic

noise

Fig.6-4 Effect of carrier freq. on the environment

Relationship table of inverter type and carrier freq.

Carrier freq.Model type

Highest carrier freq.(KHz)

Lowedst carrier freq. (KHz)

Factory value (KHz)

G type:0.4~11kW P type:0.75~15kW

15 0.5 8

G type:15~55kW P type:18.5~75kW

8 0.5 4

Page 51: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 50 -

G type:75~300kW P type:90~315kW

6 0.5 2

This function is mainly used to improve noise as motor running and problems like interference of frequency converter to the outside world.

Advantages of high carrier frequency:the current wave is ideal with less current harmonics and small noise. Disadvantage of high carrier frequency:larger switch loss,larger temperature rise,the output capacity of the

frequency inverter is influenced and it should be derated with high carrier frequency; in the mean time, the leakage current increases and the extral electromagnetic interference is reinforced.

It is contrary to the above situation with low carrier frequency. If the carrier frequency is too low,that will result in instability in the low-frequency operation,the decrease of torque and even oscillation.

The carrier freq. has been properly set before leaving the factory. In general, users do not need to modity theparameter.

Func Code Name Illustration Setting range Default value

P0.19 Function parameter recovery

0:Non-operation 1:Restore defaults 2:malfunction archives elimination

0~2 0

1:The inverter will restore the default values for all parameters. 2:The inverter will clear recent fault files.

After the selected function operation is completed, the function code is automatically restored to 0.

6.2 Frequency reference function parameter(P1 Group) Func Code Name Illustration Setting range Default

value P1.00 VI lower limit value 0.00V~10.00V 0.00~10.00 0.00V

P1.01 VI corresponding lower limit setting -100.0%~100.0% -100.0~100.0 0.0%

P1.02 VI upper limit value 0.00V~10.00V 0.00~10.00 10.00V

P1.03 VI corresponding upper limit setting -100.0%~100.0% -100.0~100.0 100.0%

P1.04 VI input filter time 0.00s~10.00s 0.00~10.00 0.10s The function code defines the relationship between the analog input voltage and the set value corresponding

to the analog input. When the analog input voltage exceeds the range of the set maximum input or minimum input, Other parts will be calculated by the maximum input or the minimum input.

Whe current input becomes the analog input, the corresponding voltage to 0mA ~ 20mA current is 0V ~ 5V. In different applications, analog set 100% corresponding to the nominal value is different. Please refer to the

specific description of each application part. The following figure illustrates circumstances of several settings: Note:The lower limit value of the VI value must be less than or equal to the upper limit value of VI.

Corresponding set

100.0%

0V AI

-100.0%

(0mA)

10V

(20mA)

Freq.PID given PID feedback

Fig.6-5 Correspondence between analogue reference and the set value

Page 52: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 51 -

Filter time of VI input: It determines the sensitivity of the analog input.In order prevent the interference of

analgue causing malfunction, this parameter can be increased. In hence, Anti-interference ability is enhanced,

but the sensitivity of analog input is reduced.

Func Code Name Illustration Setting range Default

value P1.05 CI lower limit value 0.00V~10.00V 0.00~10.00 0.00V

P1.06 CI corresponding lower limit setting -100.0%~100.0% -100.0~100.0 0.0%

P1.07 CI upper limit value 0.00V~10.00V 0.00~10.00 10.00V

P1.08 CI corresponding upper limit setting -100.0%~100.0% -100.0~100.0 100.0%

P1.09 CI input filter time 0.00s~10.00s 0.00~10.00 0.10s The setting method for CI function is similar with that of VI function. Analog VI can support 0 ~ 10 v, 0 to

20 mA, and 4 ~ 20 mA input. When 0~20mA and 4~20mA is selected as the input in CI function, the corresponding voltage to 20mA is 5V and the corresponding voltage to 4mA is 1V.

6.3 Start/Brake function parameter(P2 Group) Func Code Name Illustration Setting range Default value

P2.00 Start running mode

0:Direct starting 1:Start after dc brake 2:Start after rotating speed tracking

0~2 0

0:Direct starting:Start from the starting frequency 1:Start after dc brake:firstly DC brake(Pay attention to set parameters P2.03、P2.04),and then start the

motor from the starting frequency. It’s applicable to the situation that small inertia load may reverse when starting. 2:Start after rotating speed tracking:Frequency converter first calculates the speed and direction of the

motor, and then begins to run from the current speed to the set frequency, to achieve a smooth start implemented on the rotating motor. The way is suitable for instantaneous power failure to start again of large inertia load

Func Code Name Illustration Setting range Default value

P2.01 Start freq. of direct start 0.00~10.00Hz 0.00~10.00 0.00Hz P2.02 Retention time start

freq. 0.0~50.0s 0.0~50.0 0.0s

The sest appropriate starting frequency can increase the starting torque. The inverter output frequency becomes the starting frequency in the retention time of the starting frequency and then runs from start frequency to the target frequency. If the target frequency (frequency order) is less than the starting frequency, frequency converter will not run and will be in the standby state. Starting frequency is not affected by the lower limit freq.

starting frequency does not work in forward and reverse switching process. Func Code Name Illustration Setting range Default value

P2.03 Brake current before start 0.0~150.0% 0.0~150.0 0.0%

P2.04 Brake time before start 0.0~50.0s 0.0~50.0 0.0s Frequency inverter starts DC brake first according to the set DC braking current before start.It starts to

accelerate through DC braking time before start. If the DC brake time is set to 0, DC braking is invalid. The greater the DC braking current is , the greater the braking force is. DC braking current before start refers

to the percentage relative to converter rated current. Func Code Name Illustration Setting range Default value

P2.05 Stop mode selection 0:Dec stop 1:Free Stop 0~1 0

0:Dec stop After the stop command is enabled,frequency ivnerter reduces the output frequency in accordance with DEC

mode defined ACC and DEC time.inverter will shut down after the frequency drops to 0. 1:Free Stop After the stop command is enabled, The inverter output immediately terminate.Load free stops by the mechanical inertia.

Page 53: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 52 -

Func Code Name Illustration Setting range Default value

P2.06 Start freq.of brake as stop 0.00~10.00Hz 0.00~10.00 0.00Hz P2.07 Waiting time of brake as

stop 0.0~50.0s 0.0~50.0 0.0s

P2.08 DC brake current as stop 0.0~150.0% 0.0~150.0 0.0% P2.09 DC brake time as stop 0.0~50.0s 0.0~50.0 0.0s

Start freq.of brake as stop:It starts DC brake,when reaching this frequency in the process of DEC stop. Waiting time of brake as stop:Before the start of the outage DC brake, inverter blockades output and restart

DC brake after the delay,to prevent overcurrent fault of starting DC brake at high speed. DC brake current as stop:it refers to the added amount of DC braking. Current increases, the DC braking

effect is stronger. DC brake time as stop:the duration of DC braking value. When time is 0, DC braking is invalid and the

inverter stops according to the set deceleration time.

Fig.6–6 Start after DC braking Fig.6-7 DEC stop+DC braking Func Code Name Illustration Setting range Default

value 115.0 ~ 140.0% ( Standard busbar voltage)(380V series) 115.0~140.0 130.0%

P2.10

Energy consumption

brake valve value voltage

115.0~140.0%(Standard busbar voltage)(220V series) 115.0~140.0 120.0%

The function code is the starting busbar voltage that sets dynamic braking. This value can be adjusted

properly for effective braking load. Func Code Name Illustration Setting range Default value

P2.11 Terminal function test selection as

power on

0:Invalid terminal operation command as power on 1:Valid terminal operation command as power on

0~1 0

When the running command channel is terminal controlled, the system automatically detects the status of the terminal operation as power on.

0:Invalid terminal operation command as power on. Inverter will not run, even terminal operation command is detected to be effective as power on.System is in running protection status till withdrawing this terminal.Then inverter will run by enabling the terminal.

1:Valid terminal operation command as power on. If terminal operation command is detected to be effective as power on. The system will automatically start the inverter after the completion of the initialization

Note: The user must carefully select this function for that may cause serious consequences. Func Code Name Illustration Setting range Default value

P2.12 Lower limit freq. operation mode

0:Run in lower limit freq. 1:Run at zero frequency 0~1 0

Page 54: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 53 -

When inverter is in service and the inverter output frequency is less than the lower limit frequency, the actual operation frequency can be

adjusted througth the set of P2.12 paramenters.

6.4 Frequency reference function parameter(P3 Group) Func Code Name Illustration Setting range Default

value P3.00 FWD/REV dead time 0.0~3600.0s 0.0~3600.0 0.0s

Set the transition time in the output zero frequency in the FWD/REV transition process. As fig.6-8 shown below:

Fig.6-8 FWD/REV dead time

Func Code Name Illustration Setting range Default value

P3.01 AVR function selection

0:Null 1:The whole effective 2:Only invalid when it slows down

0~2 2

This is auto voltage regulation function. When the AVR function is invalid, the output voltage will vary with the input voltage (or DC bus voltage);When the AVR function is valid, the output voltage won’t vary with the input voltage (or DC bus voltage). The output voltage will remain almost constant in the output range.

Note:When inverter is decelerating to stop, it will stop in a shorter DEC time without overpressure by turning off the automatic voltage regulator AVR function.

Func Code Name Illustration Setting

range Default value

P3.02 Energy-saving operation selection

0:Inaction 1:Automatic energy saving operation 0~1 0

When motor is running with light load or no-load, the inverter will detect the load current and adjust output appropriately so as to save energy. This function is mainly used in application with stable load and running speed.

Note:This function is especially effective for fan and pump load. Func Code Name Illustration Setting range Default value

P3.03 Inching operation frequency 0.00~Max freq.(P0.05) 0.00~P0.04 5.00Hz

P3.04 Inching acceleration time 0.1~3600.0s 0.1~3600.0 Determined by

model P3.05 Inching deceleration

time 0.1~3600.0s 0.1~3600.0 Determined by model

Define the rated frequency and ACC/DEC time in inching operation.Inching operation process performs the start and stop operation according to the direct starting mode and DEC stop mode.

Inching acceleration time refers to the time needed for maximum output frequency(P0.05)accelerated from 0 hz.

Inching deceleration time refers to the time needed for maximum output frequency(P0.05)decelerated from 0 hz.

For 5.5kW model and under, the ex-factory value ofACC/DEC time is 10.0s;As to 7.5kW- 55kW model, the

Page 55: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 54 -

ex-factory value ofACC/DEC time is 20.0s;for 75kW model and under, the ex-factory value ofACC/DEC time is 40.0s.

Func Code Name Illustration Setting range Default value

P3.06 Multi-velocity 0 -100.0~100.0% -100.0~100.0 0.0% P3.07 Multi-velocity 1 -100.0~100.0% -100.0~100.0 0.0% P3.08 Multi-velocity 2 -100.0~100.0% -100.0~100.0 0.0% P3.09 Multi-velocity 3 -100.0~100.0% -100.0~100.0 0.0% P3.10 Multi-velocity 4 -100.0~100.0% -100.0~100.0 0.0% P3.11 Multi-velocity 5 -100.0~100.0% -100.0~100.0 0.0% P3.12 Multi-velocity 6 -100.0~100.0% -100.0~100.0 0.0% P3.13 Multi-velocity 7 -100.0~100.0% -100.0~100.0 0.0%

Statement:The symbol of multi-velocity determines the running direction. A negative value as the multi-velocity shows reverse direction. Frequency setting 100% corresponds to the maximum frequency (P0.04)

When X1=X2=X3=X4=OFF,frequency input mode is determined by code.When X1、X2、X3、X4 terminals are not all “off”,multi-velocity is in service and the priority of the multistage speed is higher than the keyboard input, simulation, communication frequency.At most 15 segmants can be chosen through X1、X2、X3、X4 assembly code.

Fig.6-09 Multi-velocity operational logic diagram

Startup stop channel selection in multi-velocity segment runtime is also determined by the function code P0.02. A multi speed control process is shown in figure 6-09. relationships between S1, S2, S3, S4 terminals and multi-velocity segment is shown in the following table.(“OF”means invalid terminal input;“ON”means valid terminal input)

Relationships between S1, S2, S3, S4 terminals and multi-velocity segment

S1 OF ON OF ON OF ON OF ON OF ON OF ON OF ON OF

S2 OF OF ON ON OFF OF ON ON OF OF ON ON OF OF ON

S3 OF OF OF OF ON ON ON ON OF OF OF OF ON ON ON

S4 OF OF OF OF OF OF OF OF ON ON ON ON ON ON ON

stage 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Page 56: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 55 -

Func Code Name Illustration Setting range Default

value P3.14 Jump freq.1 0.00~P0.05(Max freq.) 0.00~P0.05 0.00Hz P3.15 Jump freq. range 0.00~P0.05(Max freq.) 0.00~P0.05 0.00Hz

When the set frequency is in the hopping frequency range, the actual operation frequency will run in the hopping frequency boundary closer to the set frequency . It helps the frequency inverter to avoide mechanical resonance poin of the load by setting hopping frequency.One hopping frequency point can be set in this inverter.If hopping frequency is set to 0 , this function does not work.

Fig.6-10 Schematic diagram of hopping frequency

6.5 Simple PLC program control operation parameters(P4 Group)

A simple PLC function is a multi speed generator. The frequency converter can automatically change operation frequency and direction according to the running time, so as to meet the requirements of the production process.

Func Code Name Illustration Setting range Default

value P4.00

Simple PLC operation mode selection

0:Inaction 1:Shut down after single cycle 2:Keep the final value after single cycle 3:Continuous cycle

0~3

0

0:Inaction. PLC mode of operation is invalid 1:Shut down after single loop. As shown in Figure 6-11,when inverter automatically stops after one loop , it

needs to give out the operation command of restart.

T1 T2 T3 T4 T5 T6 T7

a1F1

a2 F2

d3 a3 F3

a4F4

d5

a5

F5

F6d7 F7

d7

SimplePLC operationa6

RUN cmd Fig.6-11 PLC halt mode after single loop

Page 57: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 56 -

2:Retention of final value after single loop. As shown in figure 6-12, after completing a loop frequency converter automatically keep the operation of frequency and direction in the last period and won’t be decelerating to stop until stop command is inputted.

3:continuous loop. As shown in figure 6-13, frequency converter automatically start next cycle after completing a loop,till stop command inputted.

Func Code Name Illustration Setting range Default

value

P4.01 Selection of restart way

after simple PLC interrupt run

0 : Start again from the first segment 1:Continue to run from the phase frequency of interrupt time 2 : Continue to run from the operating frequency of interrupt time

0~3 0

0:Start again from the first segment. Machine halt when the shutdown command, failure or power outage cause machine halt, inverter starts running from the first period of operation.

1:Continue to run from the phase frequency of interrupt time. When the shutdown command and fault

cause machine halt, frequency converter automatically records the operation time of the current stage and automatically enter into this stage after restart.The frequency defined after this segment continues to run remaining time, as shown in figure 6-14.

2:Continue to run from the operating frequency of interrupt time. When frequency inverter stops in service,it records not only the operational time of the current stage but also

the operational frequency of halt time.The inverter will firstly restore to the operational frequency of halt time after restart and continue operation of the next stages, as shown in figure 6- 15.

T1 T2 T3 T4 T5 T61 T7

a1 F1 a2

F2

d3 a3 F3

a4 F4

d5

a5 F5

F6 d7 F7 a6

RUN cmd

Fig. 6-12 PLC retention mode after sigle loop

STOP cmd

RUN cmd

First cycle Second cycle T1 T2 T3 T4 T5 T6 T7 T1 T2 T3 T4 T5 T6 T7 T1

F1 d1

d1d2PLC run

F2

F3

F4

F5

F6

F7

F1

F2

F3

F4

F5

F6

F7

F1

Fig. 6-13 PLC continuous loop mode

Page 58: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 57 -

Fig. 6-15 PLC start-up mode 2

Func Code Name Illustration Setting range Default

value P4.02

PLC status parameters power-down storage selection

0:Non storage 1:Storage 0~1 0

0:Non storage. Inverter won’t memory PLC running status as power down and restart from the first stage as

power on. 1:Storage. Inverter will memory PLC running status as power down including the operational frequency,

phase frequency and running time and restart operation according to the PLC start-up mode in P4.01 as power on. Func Code Name Illustration Setting range Default

value P4.03

Stage time unit selection

0: second 1: minute

0~1 0

0:second. 1:minute. The unit applies only to the time definition in PLC operation stage. (1) When PLC running time of a certain period of time is set to zero, the segment will be invalid. (2) Controls like pause, failure and operation can be performed in PLC process through terminals. Please see P6

terminal function parameter group for details. Func Code Name Illustration Setting range Default value

P4.04 Stage 1 freq. setting (Multistage freq.8)

000.00~P0.05(max output freq.) 000.00~P0.05

020.00HZ

P4.05 Stage 1 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0~2

0

P4.06 Stage1 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.07 Stage1 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.08 Stage1 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.09 Stage2 freq. setting

(Multistage freq. 9) 000.00~P0.05(max output freq.) 000.00~P0.05

025.00HZ

P4.10 Stage2 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0~2

0

P4.11 Stage2 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S

a1:Stage1ACC time a2:Stage 2ACC time a3:Stage 3 ACC time d2:Stage 2DEC time F1:Stage 1freq. F2:Stage 2freq. F3:Stage 3freq.

Output freq.Hz Interrupt signal

a1

F1

d2

a2 F2

a3 F3

stage1 stage2

Run time

stage2

surplus time

Time

Fig.6-14 PLC start-up mode 1

Output freq.Hz Interrupt signal

a1

F1

d2

a2 F2a3

F3

Stage 1 Stage 2

Run time

Stage2

Surplustime

Time

d2

a1:Stage1 ACC time a2:Stage 2 ACC time a3:Stage 3 ACC time d2:Stage 2DEC time F1:Stage 1freq. F2:Stage 2freq. F3:Stage 3freq.

Page 59: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 58 -

P4.12 Stage2 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.13 Stage2 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.14 Stage3 freq. setting

(Multistage freq. 10) 000.00~P0.05(max output freq.) 000.00~P0.05

030.00HZ

P4.15 Stage 3 running direction selection

0:Foreward 1:Reverse 2:Be determined by the run command

0~2

0

P4.16 Stage3 acceleration time 0000.1~3600.0S 0000.1~3600.0S 0010.0S

P4.17 Stage3 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.18 Stage3 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.19 Stage4 freq. setting

(Multistage freq. 11) 000.00~P0.05(max output freq.) 000.00~P0.05

035.00HZ

P4.20 Stage 4 running direction selection

0:Foreward 1:Reverse 2 : Determined by operation command

0~2

0

P4.21 Stage4 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.22 Stage4 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.23 Stage4 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.24 Stage5 freq. setting

(Multistage freq. 12) 000.00~P0.05(max output freq.) 000.00~P0.05

040.00HZ

P4.25 Stage5 running direction selection

0:Foreward 1:Reverse 2:Determined by operaion command

0~2

0

P4.26 Stage5 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.27 Stage5 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.28 Stage5 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.29 Stage6 freq. setting

(Multistage freq. 13) 000.00~P0.05(max output freq.) 000.00~P0.05

045.00HZ

P4.30 Stage6 running direction selection

0:Foreward 1:Reverse 2:Determined by operaion command

0~2

0

P4.31 Stage6 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.32 Stage6 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.33 Stage6 running time 0000.0~6500.0 0000.0~6500.0 0020.0 P4.34 Stage6 freq. setting

(Multistage freq.14) 000.00~P0.05(max output freq.) 000.00~P0.05

050.00HZ

P4.35 Stage6 freq. setting (Multistage freq. 14)

0:Foreward 1:Reverse 2:Determined by operaion command

0~2

0

P4.36 Stage7 ACC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.37 Stage7 DEC time 0000.1~3600.0S 0000.1~3600.0S 0010.0S P4.38 Stage7 running time 0000.0~6500.0 0000.0~6500.0 0020.0

There are seven stages of simple PLC operation, The above function code defines the operating frequency, direction,ACC/DEC time and run-time of the seven stages and the operational phase frequency can be defined as a multi-speed frequency 7~14. Please refer to P3 function code interpretation.

The direction of the various stages can be defined as forward, reverse and it can be determined according to the operation command.Run commond includes keypad, terminal and serial communication.Please refer to P0.02 interpretation for details.

6.6 PID closed loop parameters(P5 Group)

PID control is a common method used for process control.It’s used by doing Proportional, integral, differential calculation on the residual quantity between the feedback signal of controlled quatity and target signal, to adjust the output frequency of the inverter and to constitute the negative feedback system,so that the controlled quantity on the target volume is stable. It’s suitable for flow control, pressure control and temperature control.Basic control principle is shown in below figure.

Page 60: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 59 -

Fig.6-16 Process PID functional block diagram

Func Code Name Illustration Setting range Default

value

P5.00 PID given source selection

0:Keypad reference(P5.01) 1:Analog channel VI reference2:Analog channel CI 0 ~ 10V reference 3 : Remote communications reference 4:Multi segment reference 5:Analog channel CI 4 ~ 20 mA reference

0~5 0

When PID is chosen as the frequency source,namely 6 is chosen as P0.00,this function will work.The parameter determines the given channel of process PID.

Relative value is set to be the target volume of process PLD with the set 100% corresponding to 100% of the feedback signal in controlled system.

System is always operating according to the relative value(0~100.0%) Note:Multistage can be realized by setting parameters in PA group.

Func Code Name Illustration Setting range Default

value

P5.01 Keypad Preset PID reference 0.0%~100.0% 0.0~100.0 0.0%

When choosing P5.00=0,the target source is keypad reference and therefore parameters need to be set. The reference value of this parameter is the feedback value of the system.

Func Code Name Illustration Setting range Default

value

P5.02 PID feedback source selection

0:Analog channel VI feedback 1:Analog channel CI feedback 2:VI+CI feedback 3:Remote communications feedback 4:Analog channel CI 4 ~ 20mA feedback

0~3 0

This parameter helps to choose PID feedback channel.

Note:a given channel can’t coincide with the feedback channel. Otherwise,PID can not effectively

control. Func Code Name Illustration Setting range Default

value

P5.03 PID output characteristics selection

0: positive characteristic 1: negative characteristic 0~1 0

PID output is positive characteristic:When the feedback signal is greater than a PID reference,PID can only reach balance by decreasing output frequency, such as PID winding tension control

PID output is negative characteristic:When the feedback signal is greater than a PID reference,PID can only reach balance by increasing output frequency, such as PID unwinding tension control

Func Code Name Illustration Setting range Default

value P5.04 Proportion gain(Kp) 0.00~100.00 0.00~100.00 1.00 P5.05 Integral time(Ti) 0.01~10.00s 0.01~10.00 0.10s P5.06 Differential time(Td) 0.00~10.00s 0.00~10.00 0.00s

Page 61: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 60 -

Proportion gain(Kp):It determines the regulation intension of the whole PID regulator. The higher P is,the greater adjust strength is.This parameter is represented by 100. When the deviation between PID feedback quantity and the given quantity is 100%, PID controller for adjusting the amplitude of the output frequency command is the maximum frequency(Ignore integral and differential effect).

Integral time(Ti):It determines the speed of integral regulating on the deviation between PID feedback quantity and the given quantity. The integration time is when the deviation between PID feedback quantity and the given quantity is 100%,Integral regulator continues adjusting as going though that time(Ignore the proportional and differential effective)and the adjustment amount reaches the max frequency (P0.04).The shorter integral time is, the greater adjust strength is.

Differential time(Td):used to adjust the strength of the change rate of the deviation between PID feedback value and given value. Differential time refers that if the feedback value change 100% within the time, then the adjustment value of the differential regulator is the max frequency(P0.04)(proportional and differential effect is neglected)。The longer the differential time is, the larger the adjust strength is.

PID is the commonest control way in the process control and each part plays its own function. See the introduction of operating principle and adjusting method:

Proportional control(P):if there is the deviation between the feedback and given value, the output and deviation are proportional adjustment. If the deviation is constant, then the adjustment value is constant. The proportional adjustment can response the feedback change quickly, but can not reach non-error control only by proportional adjustment. The more the proportional gain is, the faster the adjustment speed of the system is, but the excessive may cause vibration. The adjusting method: set a longer integral time set the differential time as 0,run the system only by the proportional adjustment and change the given value, then check the stable deviation (static error) between the feedback signal and given value. If the static error is in the change direction of the given value (such as increase of the given value, the feedback is always less than the given value under stable mode), the proportional gain is increasing, and on the contrary, the proportional gain is reducing. Repeat the above procedure till that it reaches lower static error( non-error is hard).

Integral time(I):If there is deviation between the feedback and given value, the output adjustment is continuously increasing. If the deviation remains, proceed to increase the adjustment value till no deviation. The integral regulator can eliminate the static error effectively. Repeat overshoot may occur and the system is not stable till vibrating occurs if the integral regulator is too strong. Because the characteristics of the oscillation caused by excessive integral effect are: the feedback signal is around the given value and the amplitude increasing till the vibration, the parameter of the integral time is generally adjusted from up to down. During the process, monitor the effect of the system adjustment till the stable speed of the system satisfies the requirements.

Differential time(D):If the deviation between the feedback and given value changes,the output and the change rate of deviation are proportional adjustment value, which is only relevant to the direction and the value of deviation change and is not relevant to the direction and value of the deviation. The function of differential adjustment is that it can adjust according to the change trend to control the change of the feedback signal. Please use the differential adjustment prudently because the integral regulator is easy to enlarge the interference of the system, especially for the interference of the higher changing frequency.

Func Code Name Illustration Setting range Default

value P5.07 Sampling period(T) 0.01~100.00s 0.01~100.00 0.10s P5.08 Limit deviation of PID

control 0.0~100.0% 0.0~100.0 0.0%

Sampling period(T):refers to the sampling period of the feedback value and the regulator calculates once

in each sampling period. The longer the period is, the slower the response is. Limit deviation of PID control:refers to the permissive max deviation between PID output value and given

value of closed loop. As indicated in the figure below, PID regulator stops adjusting within the limit deviation. The proper setting of the function can adjust the precision and stability of PID system.

Page 62: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 61 -

Fig.6-17 Relationship between limit deviation and output frequency

Func Code Name Illustration Setting range Default

value

P5.09 detected value upon feedback break

0.0~100.0% 0.0~100.0 0.0%

P5.10 Detecting time upon feedback break

0.0~3600.0s 0.0~3600.0 10.0s

Detected value upon feedback break:the detected value is correspond to the full range(100%). The system is detecting the feedback value of PID and if the feedback value is less or equivalent to detected value upon feedback break, the system starts detecting and timing. If the detecting time is beyond the detecting time upon feedback break, the system reports PID feedback break error.

Func Code Name Illustration Setting range Default

value

P5.11 Feedback disconnection action selection

0:Invalid 1:Shunt-down alarm 2 : Run according to the frequency of P0.03 3:Run according to upper limit freq. 4:Run according to half of the upper limit freq.

0~4 0

When the feedback value of PID is less than the detection valve value set by P5.09,The cumulative delay P5.10 seconds determines the feedback break.The action after feedback break is chosen by parameter P5.11.

0:Stop 1: Run according to the frequency of P0.03 2:Run according to upper limit freq. 3:Run according to half of the upper limit freq.

Func Code Name Illustration Setting range Default

value

P5.12 Sleep Frequency P0.09(fL) ~P0.05(When set to 0 hz, sleep function is invalid) P0.09~P0.05 000.00

P5.13 Sleep latency 000.0~120.0S 000.0~120.0S 030.0S

P5.14 Awakening threshold 000.0~100.0%(Feedback value relative to the percentage of full scale)

000.0~100.0% 0.10.0%

P5.12 parameters set the lowest running frequency before sleep mode. P5.13 parameters set the time that frequency inverter needs for continuous run in sleep frequency before entering sleep state .P5.14 parameters set the conditions that frequency inverter resumes from sleep state to normal operation.When the output frequency of the frequency inverter drops to the frequency of P5.12 parameters,frequency inverter goes to sleep state via the time set by P5.13 parameters and the output frequency drops to 0.00Hz.When feedback value is lower than Recovery threshold of P5.14(relative to the percentage of full scale), frequency inverter backs to normal PID regulator state.

6.7 Frequency reference function parameter(P6 Group)

There are 7 multi-functional digital input terminals and 2 analog input terminals in the standard unit of

YX8000 series frequency inverter.

Page 63: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 62 -

Func Code Name Illustration Setting

range Default value

P6.00 X1 Terminal function selection Programmable multifunction terminal 0~27 1

P6.01 X2 Terminal function selection Programmable multifunction terminal 0~27 4

P6.02 X3 Terminal function selection Programmable multifunction terminal 0~27 7

P6.03 X4 Terminal function selection Programmable multifunction terminal 0~27 0

P6.04 X5 Terminal function selection Programmable multifunctional terminal 0~27 0

P6.05 X6 Terminal function selection Programmable multifunctional terminal 0~27 0

P6.06 X7 Terminal function selection Programmable multifunctional terminal 0~27 0

The parameters are used to set the functions of these multifunctional input terminals.

Func Code Function Illustration

0 No function The frequency inverter fails to reactuate even signal is inputted.the used terminal can be set as no-function to prevent malfunction.

1 Forward run 2 Reversal run

FWD/REV is controlled by external terminals.

3

Three-wire operation Sin terminal selection

The running mode of the freq. inverter is confirmed to be three-wire control mode though this terminal. Please refer to introduction of P6.08 Three-wire functional code about three-wire control.

4 Forward inching

5 Reversal inching

Please refer to the instruction of P3.03、P3.04、P3.05 to see the specific inching freq. and ACC/DEC time.

6 Free stop

As the command takes effect,freq. inverter blocks output immediately and the stop process of motor is not controlled by the freq. inverter.It’s recommended to adopt this mode for super inertia load and without requirements to stop time. The mode las the same meaning with free stop described in P2.05.

7 Fault reset External fault reset is applicable to remote fault reset and has the same function with STOP/RST on the keyboard.

8 External fault input

The freq. inverter reports the external fault and stops since the signal takes effect.

9 Increase frequency(UP)

10 Reduce frequency(DOWN)

11 Clear freq. fluctuation setting

The two functions are mainly used to modify the given freq. by external terminals. When digital set is set as the frequency source,the given frequency can be modified UP and DOWN.

It’s used to clear up the given frequency value set by UP/DOWN so as to recover the given freq. to the specified freq. given by the freq. instruction route.

12 Multi-speed terminal 1

13 Multi-speed terminal 2

14 Multi-speed terminal 3

14-level speed can be set by the combination of the three terminals Note:1 is the lower level,4 is the higher level among the multi-speed terminals.

Multi-speed4 Multi-speed 3 Multi-speed 2 Multi-speed 1 BIT3 BIT2 BIT1 BIT0

15 terminal of ACC and DEC time selection

Select ACC/DEC time group though the digital state of this terminal: Terminals ACC/DEC time option Relative parameter OFF ACC/DEC time 0 P0.10、P0.11 ON ACC/DEC time 1 P3.06、P3.07

16 PID pause control

The freq. inverter remains the current freq. output if PID is invalid temporarily.

17 Swing freq pause

The freq. inverter proceeds to run at the current freq. after its pause at the current output and the cancellation of this function.

Page 64: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 63 -

Func Code Function Illustration

18 Swing freq reset

The setting freq. of the inverter backs to the center req.

19 ACC and DEC forbidden

To ensure that the freq. inverter not be influenced by external signal( except the stop command) and remains the current output freq.

20 Torque control forbidden

The freq. inverter shifts torque control mode to speed control mode.

21 Clear freq. change settings temporarily

The freq. set by UP/DOWN can be cleared when the terminal is closed.It recovers the given freq.to the specified freq. given by the freq. instruction route. When the terminal is off, it backs to the freq. set by UP/DOWN

22 Simple PLC program reset

When the terminal is closed loop, PLC program segment return to the first phase operation.

23 Simple PLC program run pause

It is used to carry out the pause control on running PLC process. When the terminal is running effectively at zero frequency, PLC operation is not timed. After ineffective automatic speed tracking start and continue to run the PLC.

24 Auxiliary frequency source selection

25 Multi-speed terminal 4

with above 12、13 and 14 item constitute a 14 segment multi-speed control

26 Simple PLC program reset at stop state

During shutdown of PLC operation mode, if this functional terminal is valid it will clear the running stage,running time,operating frequency and other information memoried as PLC stops.

27 Simple PLC program failure

It is used for flexible switching to low level operation mode under PLC operating

status.

Func Code Name Illustration Setting range Default

value P6.07 Switching value filtering times 1~10 1~10 5

Set the filtering time of S1~S7.The parameter should be increased to avoid fault action under severe

interference. Func Code Name Illustration Setting

range Default value

P6.08 Terminal control operation mode

0:Two-wire control 1 1:Two-wire control 2 2:Three-wire control 1 3:Three-wire control 2

0~3 0

The parameter defines four modes of the frequency inverter controlled by external terminals. 0:two-wire control.The mode is the most common two-wire mode and the forward and reversal of the motor are decided by FWD and REV terminals.

Fig.6-18 Two-wire control

1:Two-wire control 2. FWD defined by this mode is enabling terminal and the direction is defined by REV

state.

Fig.6-19 Two-wire control 2

K2 K1 Command

0 0 Stop

0 1 FWD

1 0 REV

1 1 stop

YX8000

FWD

REV

COM

K1

K2

K2 K1 Command

0 0 Stop

1 0 Stop

0 1 Fwd

1 1 Rev

YX8000

FWD

REV

COM

K1

K2

Page 65: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 64 -

2:Three-wire control 1。The mode Xn is enabling terminal and run command is from FWD, while the

direction is controlled by REV. Xn is normal closed input.

Fig. 6-20 Thre wire control mode1

Therein:K:FRW and REV switch SB1:Run key SB2:Stop key Sin is defined as a function of the terminal corresponding to the 3rd function "three-wire operation." 3:Three-wire control2. Xn under this mode is the enabling terminal and the run command is from SB1 or

SB2,and the two terminals control the run direction simultaneously. Stop command is from the normal input SB2.

Fig.6-21 Three-wire control mode 2 Therein:SB1:FRW key SB2:Stop key SB3:REV key Xn is defined as a function of the terminal corresponding to the 3rd function "three-wire operation." Prompt:under two-wire run mode,When FWD/REV is effective,if the stop command is from other

sources and the frequency inverter stops, the frequency inverter can not run after cancel the stop command even if the FWD/REV is still effective. FWD/REV needs to be activated again if you want to restart the frequency inverter. Func Code Name Illustration Setting range Default

value

P6.09 UP/DOWN change rate of frequency increment

0.01~50.00Hz/s 0.01~50.00 0.50Hz/s

Change rate of the frequency is set by UP/DOWN terminal.

There are 3 multifunctional digital output terminals, 2 multifunctional relay output terminals and 2 multifunctional analogue output terminals in the standard unit of YX8000 series frequency inverter.

Func Code Name Illustration Setting range Default

value P6.10 Y1 output selection Open-collector output 0~11 1 P6.11 Y2 output selection Open-collector output 0~11 1

P6.12 Y3 output selection Or relay output selection(RA、

RB、RC)

Open-collector output 0~11 1

P6.13 Relay output selection(TA、TB、TC)

Open-collector output 0~11 3

Open-collector output function table: Func Code Function Illustration

0 No output Output terminal has no function

YX8000

Xn

K Derection

Select

0 STOP

1 FWD

FWD

REV

COM

Xn

YX8000SB1

SB2

K

Page 66: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 65 -

1 Inverter forward operation It shows the freq inverter is under forward operation, then it outputs ON signal if there is freq. output.

2 Inverter reverse operation It shows freq. inverter is under reversal operation, then it outputs ON signal if there is freq. output.

3 Fault output It outputs ON signal when there is any fault.

4 Frequency level detection FDT output

Please refer to the detailed description of function code P6.19、P6.20.

5 set freq. to Please refer to the detailed description of function code P6.21

6 Zero-speed operation When the output freq. is less than starting freq.,it outputs ON signal

7 Upper limit freq. arrives When the running freq. arrives to the upper limit of the freq.,it

outputs ON signal.

8 Lower limit freq. arrives When the running freq. arrives to the lower limit of the freq. it

outputs ON signal. 9 Retention Retention

10 Simple PLC program run loop termination

After the end of a cycle PLC program is effective.

Func Code Name Illustration Setting

range Default value

P6.14 AO1 output selection Multifunctional analog output 0~10 0

AO1 output is 0~10V voltage as leaving factory,If AO1 needs to ouput0~20mA or 4~20mA,JP2 jumper

jumps to IS side; if AO1 needs to output 4~20mA, P6.16 should be set as 2.00V. Setting value Function Scope

0 Running freq. 0~max output freq. 1 Setting freq. 0~max output freq. 2 Motor speed 0~twice rated speed of the motor 3 Output current 0~twice rated current of the freq. inverter 4 Output voltage 0~1.5 rated voltage of the freq. inverter 5 Output power 0~twice rated power 6 Output torque 0~twice rated current of the motor 7 Analog VI input 0~10V 8 Analog CI input 0~10V/0~20mA或4~20mA

9~10 Retention Retention

Func Code Name Illustration Setting range Default

value P6.15 AO1 Output limit 0.0%~100.0% 0.0~100.0 0.0% P6.16 The lower limit corresponding to

AO1 output 0.00V ~10.00V 0.00~10.00 0.00V

P6.17 AO1 output upper limit 0.0%~100.0% 0.0~100.0 100.0% P6.18 The upper limit corresponding to

AO1 output 0.00V ~10.00V 0.00~10.00 10.00V

The above functional codes define the relationship between the output value and analog output value. The

extra is counted according to the upper or lower limit output when the output value is over than the max output or min output scope.

When the analog output is current output,1mA is corresponding to 0.5V voltage.

In different occasions, the corresponding analog output value of 100% of the output value diversifies.Please

refer to the instruction in each application part. Below figures illustrate several setting conditions:

Page 67: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 66 -

Fig.6-22 Relationship between the given value and analog output

Func Code Name Illustration Setting range Default

value P6.19 FDT level

measurements 0.00~P0.05(Max freq.) 0.00~ P0.05 50.00Hz

P6.20 FDT hysteresis measurements 0.0~100.0%(FDT level) 0.0~100.0 5.0%

Set the detection value of the output frequency and the lagged value removed by output action.See below figure:

Func Code Name Illustration Setting range Default

value

P6.21 Freq. arrival(FAR)check out the amplitude 0.0~100.0%(Max freq.) 0.0~100.0 0.0%

When the output frequency of the inverter reaches the given frequency value,The detection amplitude of this

function is adjustable. See below figure:

Fig.6-24 The arrival of frequency to the detection amplitude

Func Code Name Illustration Setting range Default

value P6.22 TA\TB\TC closing delay 0000.0S~6553.5S 0000.0S~6553.5S 0000.0S P6.23 TA\TB\TC off-delay 0000.0S~6553.5S 0000.0S~6553.5S 0000.0S

P6.22 is used to define the closing delay when the electric relay TA\TB\TC is effective. P6.23 is used to define the off-delay when the electric relay TA\TB\TC is ineffective.

Func Code Name Illustration Setting range Default

value P6.24 RA\RB\RC closing delay 0000.0S~6553.5S 0000.0S~6553.5S 0000.0S P6.25 RA\RB\RC off-delay 0000.0S~6553.5S 0000.0S~6553.5S 0000.0S

Output freq. FDT1 level

time

time

Y

FDT1 lag

Fig. 6-23 Frequency level detection

time

output Set freq

time

Y

Detection range

Page 68: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 67 -

P6.22 is used to define the closing delay when the electric relay TA\TB\TC is effective. P6.23 is used to define the off-delay when the electric relay TA\TB\TC is ineffective.

Func Code Name Illustration Setting

range Default value

P6.26 AO2 output selection Multifunctional analog output

0~10 0

AO2 output is 0~10V voltage. Setting value Function Scope

0 Operating freq. 0~ max output freq. 1 Setting freq. 0~max output freq. 2 Motor speed 0~2 times rated speed of the motor 3 Output current 0~2 times rated current of the inverter 4 Output voltage 0~1.5 times rated voltage of the inverter 5 Output power 0~2 times rated power 6 Output torque 0~2 times rated current of the motor 7 Analog VI input 0~10V 8 Analog CI input 0~10V/0~20mA or 4~20mA

9~10 Retention Retention

Func Code Name Illustration Setting range Default

value P6.27 AO2 output limit 0.0%~100.0% 0.0~100.0 0.0% P6.28 Lower limit corresponding to

output AO2 0.00V ~10.00V 0.00~10.00 0.00V

P6.29 AO2 output upper limit 0.0%~100.0% 0.0~100.0 100.0% P6.30 The upper limit corresponding

AO2 output 0.00V ~10.00V 0.00~10.00 10.00V

The above function codes define the relationship between the output value and analog output value. The extra is counted according to the upper or lower limit output when the output value is over than the maximum output or minimum output scope.

The analog output value corresponding to 100% of the output value is different in various conditions.Please see the illustration of each application for details.

Below figures state the situation of several settings:

Fig.6-25 The corresponding relationship between given value and analog value

6.8 display and control parameter(P7 group)

Func Code Name Illustration Setting

range Default value

P7.01 LCD displayed language selection (retention)

0:Chinese 1:English 0~1 0

It is effective for LCD external keyboard to select the display language on LCD. Func Code Name Illustration Setting

range Default value

P7.02 Keypad display

selection

0: External keypad priority in use 1:Local and external keypad display simultaneously,2 : Local and external keypad display simultaneously,only the native buttons in force. 3:Local and external keypad display simultaneously and both keys are valid(logical relationship between the two)

0~3 0

Page 69: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 68 -

This function sets display key role in logic the local keyboard and external keypad. relationship. Func Code Name Illustration Setting range Default value

P7.03 The displayed parameters of running status selection 0~0x7FFF 0~0x7FFF 0xFF

YX8000 series frequency inverters are under operation mode,the parameter display of the frequency inverter is influenced by the functional code, i.e., an 16-bit binary number. If any bit is 1, the corresponding parameter may be under operation and you can examine by 》/SHIFT. If the bit is 0, the corresponding parameter is not available. Please convert the binary number to hex and input the functional code when the functional code is P7.03.

See the display content of low 8-bit below: BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0

Output torque

Output power

Running speed

Output current

Output voltage

Bus voltage

Setting freq.

Running freq.

See the display content of high 8-bit below: BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8

Retention Current phase of multispeed

Analog AI2 value

Analog AI1 value

Output terminal

state

Input terminal

state

PID feedback

value

PID given value

Input and output terminal status is displayed by decimal,The order of output terminal status is: BIT3 BIT2 BIT1 BIT0

S4 S3 S2 S1 When the input terminal is ON,the corresponding place is 1 and OFF is 0.This value helps to understand the preset status of the digital input signal.

The order of input terminal status is: BIT3 BIT2 BIT1 BIT0

RA/RB/RC TA/TB/TC Y2 Y1 When the output terminal is ON,the corresponding place is 1 and OFF is 0. This value helps to understand the preset status of the digital output signal.

Func Code Name Illustration Setting range Default

value P7.04 The displayed parameters under

stop mode 0~0x1FF 0~0xFF 0xFF

The function setting is the same as P7.03.If the YX8000 series frequency inverter is under stop state, the parameter display is controlled by the function code.

See the display content of low 8-bit: BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0

Analog AI2 value

Analog AI1 value

PID feedback

value

PID given value

Output terminal

state

Input terminal

state

Bus voltage

Setting freq.

See the display content of high 8-bit: BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8

Retention Retention Retention Retention Retention Retention Retention Current phase of

multi-speed

Func Code Name Illustration Setting range Default

value

P7.05 The displayed coefficient of motor speed

0.1~999.9% 0.1~999.9% 100.0%

Rotate speed=120*running freq.*P7.04/motor number of pole-pairs,the functional code is used to rectify the

deviation displayed by rotate speed scale and makes no difference to the actual rotate speed.

6.9 Motor parameter(P8 Group)

Func Code Name Illustration Setting range Default

value

P8.00 Self study of motor

parameter

0:No operation 1:Comprehensive self learning parameters 2: Self learning of static parameters

0~2 0

0:no operation,namely forbidding self study

Page 70: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 69 -

1:self study of parameter You must isolate the load to make the motor static before the paramter self-studying. You must input the correct nameplate of the motor(P8.01-P8.02), otherwise the result of the parameter

self-study may be inaccurate. Prior to the parameter self-studying, you should set the ACC/DEC time(P0.10、P0.11),properly based on

the inertia of the motor, otherwise over-current or over-voltage may occur during the self-studying process. Set P8.00 to 1 and press DATA/ENTER, then the motor starts the parameter self-studying, with the LED

displaying “-FUN-”and flashing. Next press FWD to start up, then it displays “FUN-0”,and the motor starts to run as it displays “FUN-1”,with the“RUN/TUNE”light flashing.As self-study ends, it displays “-END-”.At last it lacks to the stop mode interface. Press MENU/ESC and exit from parameter self-studying mode when the “-TUN-“ flashing.

You may press STOP/RST to stop the operation during self-studying process .Note: Keyboard control is the only way to control the start-up or stop of self-study; then the functional code recovers to zero after the self-study.

2:Static parameter self-study It is unnecessary to isolate the load from the motor during the static parameter self-study. Prior to the

parameter self-study, you must input the correct nameplate parameter(P8.01-P8.02).After the self-study, it can detect the stator resistance, rotor resistance and the leakage inductance of motor, while it can not detect the mutual inductance of the motor and non-load current. The user may input the corresponding values based on your experience.

Func Code Name Illustration Setting range Default value

P8.01 Motor rated power 0.4~900.0kW 0.4~900.0 Model setting P8.02 Motor rated speed 0~36000rpm 0~36000 Model setting P8.03 Motor rated current 0.1~2000.0A 0.1~2000.0 Model setting

Note:Please set the above parameters according to the nameplate of the motor. The fine control performance of vector control requires accurate motor parameters.

YX8000 series frequency inverter provides self-studying function.The self-study of precise parameters comes from the accurate setting of motor nameplate.

Please ensure that the power of the frequency inverter matches with power of the motor in order to guarantee the control performance. If the display is large, the control performance of the frequency inverter reduced obviously.

Note:It’s possible to initialize the parameters P8.02~ P8.08 by resetting the rated power of the motor(P8.01).

Func Code Name Illustration Setting range Default value

P8.04 Motor stator resistance 0.001~65.535Ω 0.001~65.535 Model setting P8.05 Motor rotor resistance 0.001~65.535Ω 0.001~65.535 Model setting P8.06 Motor stator and rotor

inductance 0.1~6553.5mH 0.1~6553.5 Model setting

P8.07 Motor stator and rotor mutual inductance

0.1~6553.5mH 0.1~6553.5 Model setting

P8.08 Motor no-load current 0.01~655.35A 0.01~655.35 Model setting

After the normal end of motor parameter self-study,the setting values of P8.04-P8.08 will update

automatically. These parameters are the reference parameters of high-performance vector control and can bring

direct effect on the control performance.

Note:Users don’t change the parameters in this group at will.

6.10 Motor parameter(P9 Group)

Func Code Name Illustration Setting range Default value

P9.00 Speed loop proportion gain 1 0~100 0~100 20

P9.01 Speed loop integral time 1 0.01~10.00s 0.01~10.00 0.50s

P9.02 Shifting low frequency 0.00Hz~P3.05 0.00~P3.05 5.00Hz P9.03 Speed loop proportion

gain 2 0~100 0~100 15

Page 71: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 70 -

P9.04 Speed loop integral time 2 0.01~10.00s 0.01~10.00 1.00s

P9.05 Shifting high frequency P3.02~P0.05(Max freq.) P3.02~P0.04 10.00Hz

The above parameters are only applicable to vector control mode and invalid for V/F control.Under shifting frequency 1(P9.02),the speed loop PI parameter is:P9.00 and P9.01.If the shifting frequency is over 2(P9.05),the speed loop PI parameters are:P9.03 and P9.04. And between them, PI parameters are obtained from the linear change of the two groups. See the figure below:

Fig.6-26 Diagram of PI parameters The speed cycle dynamic response characteristics of the vector control can be adjusted by setting the

proportion coefficient and integral time of the speed regulator.The dynamic response of speed cycle can be sped up either by the increase of proportion gain or reducing of the integral time, but it is easy to cause system oscillation over-strike either by higher proportion gain or less integral time. Smaller proportion gain is also easy to cause stable oscillation in the system and speed static error may occur.

Speed loop PI parameters have a lot to do with the inertia of the system, so adjust it to satisfy kinds of demands based on the default PI parameters to different load characteristics.

Func Code Name Illustration Setting range Default value

P9.06 VC slip compensation coefficient

50%~200% 50~100 100%

The slip compensation factor is used to adjust the slip frequency of the vector control and improve the speed

control precision of the system, so proper adjustment of the parameter can control the speed static error

effectively.

Func Code Name Illustration Setting range Default value

P9.07 Torque upper limit setting 0.0~200.0%(rated current) 0.0~200.0 150.0%

Set that100.0% is corresponding to the rated output current. Func Code Name Illustration Setting

range Default value

P9.08 REV/JOG function selection 0:Inching operation 1:Forward reverse switching 2:Clear UP / DOWN setting

0~2 0

REV/JOG is multifunctional key.Parameter setting can define the function of REV/JOG. 0:Inching operation.The key REV/JOG carry out inching operation. 1:FRW/REV shift.The key REV/JOG switch the command direction of the frequency,which is only valid

under keypad command channel. 2:Clear UP/DOWN setting.The key REV/JOG clears the value set by UP/DOWN.

Func Code Name Illustration Setting

range Default value

P9.09 STOP/RESET Stop function selection

0:Applies only to control panel 1:Simultaneously effective for Panel and terminal control 2:Simultaneously effective for panel and communication control 3:Effective for all control model

0~3 0

The functional code defines the effective option of STOP/RESET stop function. As for fault reset,the key STOP/RESET is valid in any conditions.

P9.00,P9.01

P9.03,P9.04

PI parameter

f

Page 72: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 71 -

6.11 Fault and protectional parameters(PA Group)

Func Code Name Illustration Setting range Default

value

PA.00 Motor overload

protection mode selection

0:No protection 1:Ordinary motors(With low speed compensation) 2:Variable frequency motor(Without low speed compensation)

0~2 2

0:No protection There is no overload protection characteristics for motor (be cautious).

1:Ordinary motors((With low speed compensation)Since ordinary motor cooling effect at low speed is poor, Corresponding electronic thermal protection value is also adjusted properly. The low speed compensation characteristic mentioned here refers to the de-rating of overload protection valve value in motors whose running freq. is under 30Hz.

2:Variable frequency motor(Without low speed compensation)The protection value doesn’t need to be adjusted during low-speed operation because the heat dissipation of the variable frequency motor is not affected by the rotate speed.

Func Code Name Illustration Setting range Default

value PA.01 Motor overload

protection current 20.0%~120.0% 20.0~120.0 100.0%

Fig.6-27 Motor overload protection coefficient setting The value can be defined by the formula below: Motor overload protection current=(permissible max load current / current of the freq. inverter)*100%. General definition allows a maximum load current of to be the motor rated current. When the rated current value of the load motor doesn’t match the rated current of the frequency inverter,Overload

protection on the motor can be achieved by setting the value of PA.00~PA.01 Func Code Name Illustration Setting range Default

value

PA.02 Lower freq. point upon momentary power-fail

70.0~110.0%(standard bus voltage) 70.0~110.0 80.0%

PA.03 Descend rate of freq. upon momentary power-fail 0.00Hz~P0.04(max freq.) 0.00~P0.04 0.00Hz

If the descend rate of the frequency upon momentary power-fail is 0, this function is invalid. Lower freq. point upon momentary power-fail:when the bus voltage descends to the lower frequency point

upon momentary power-fail after the power-fail, the frequency inverter starts to lower the running frequency according to the descend rate(PA.03)of frequency upon power-fail to make the motor under power generation mode so that the feedback power can remain the bus voltage to ensure the normal operation of the frequency inverter until the next power-on.

Note: adjustment of the two parameters can avoid production downtime caused by the protection of the frequency inverter when the power system is shifted. Func Code Name Illustration Setting range Default

value

PA.04 Overvoltage stalling protection

0:Forbidden protection 1:Permissible protection 0~1 0

PA.05 Overvoltage stalling protection voltage

110~140%(Standard busbar voltage) (380V type)

110~150 120%

Page 73: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 72 -

During the deceleration running of the frequency inverter, the actual descent rate of the motor speed may be lower than the descend rate of output frequency because of the influence of load inertia.Then the motor feedbacks power to the frequency inverter to increase the bus voltage. It may cause the increase of bus voltage to lead the overvoltage error of the frequency inverter if no any action.

Overvoltage stalling protection: under operation of the frequency inverter, the system detects the bus voltage and compares it with overvoltage stalling point defined by PA.05(corresponding to standard bus voltage).If it surpasses the overvoltage stalling point, the output frequency of the frequency inverter stops descending and then proceeds to descend until it is detected that the bus voltage is lower than the overvoltage stalling point. See the figure below:

Fig. 6-28 Over-voltage stalling function

Func Code Name Illustration Setting range Default value

PA.06 Current limiting choice

0:Current limiting is steadily valid 1:Current limiting at

constant speed is invalid

0~1 0

PA.07 Automatic current-limiting level 100~200% 100~200 G type:160%

P type:120%

PA.08 Freq. decrease rate as current limiting 0.00~100.00Hz/s 0.00~100.00 10.00Hz/s

Under the operation mode, if the frequency inverter loads too much, the actual increasing rate of the motor speed is lower than the increasing rate output frequency. It may cause acceleration over-current error and lead the fault of the frequency converter if no any action.

The auto current-limiting function can detect the output current under operation mode of the frequency inverter and compare it with the current-limiting point defined by PA.07. If it surpasses the current-limiting point, the output frequency of the frequency inverter lowers according to the descend rate(PA.08)of over-current frequency. And it recovers the normal operation when it is detected that the output current is lower than current-limiting point. See the figure below:

Page 74: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 73 -

Fig.6-29 Over-current stalling function Func Code Name Illustration Setting range Default

value PA.09 Automatic reset failure number 0~3 0~3 0 PA.10 Interval Setting of failure

automatic reset time 0.1~100.0s 0.1~100.0 1.0s

Automatic reset failure number:You may set the number of automatic reset when the frequency inverter selects error automatic reset.And if the number of automatic reset is over the value, the frequency inverter will be in error standby mode and need manual interference.

Interval Setting of failure automatic reset time:select the interval from the beginning of the fault to the reset action. Func Code Name Illustration

Setting range

Default value

PA.11 The first two types of failure 0~24 PA.12 Previous fault type 0~24 PA.13 Current fault type 0~24

It records the latest 3 fault types of the inverter:0 is fault-free,1~24 is the 24 different kinds of fault.See fault analysis for details.

Func Code Name Illustration Setting

range Default value

PA.14

The current fault operation frequency

The output freq.of the current fault

PA.15 The current fault output current

The output current of the current fault

PA.16 The current fault busbar voltage

The bus voltage of the current fault

PA.18

Current fault input terminal status

This value is decimal digit, showing all digital input terminal status in the recent failure respectively:

BIT3 BIT2 BIT1 BIT0S4 S3 S2 S1

When the output terminal is ON,its correspond is 1;if the output terminal is OFF, its correspond 0. This value helps to understand the current state of the digital input signal.

PA.19

Current fault output terminal status

This value is decimal digit, showing all digital input terminal status in the recent failure respectively:

BIT3 BIT2 BIT1 BIT0RA/RB/RC TA/TB/TC Y2 Y1

When the output terminal is ON,its correspond is 1;if the output terminal is OFF, its correspond 0. This value helps to understand the current state of the digital input signal.

6.12 Serial communication parameters(PB group)

Func Code Name Illustration Setting range Default value

Pb.00 Communication address of the equipment

0~247,0 is the broadcast address 0~247 1

When the host is in the editing frame and set the communication address of the slave at 0,i.e., broadcast communication address,all the slaves on MODBUS accept the frame, but no response. Note: address of slaves cannot be set at 0.

The communication address of this equipment is unique in the communication network,which is the

foundation to achieve the point-to-point communication between upper computer.

Page 75: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 74 -

Func Code Name Illustration Setting range Default

value

Pb.01 Communication baud rate setting

0:1200bps 1:2400bps 2:4800bps 3:9600bps 4:19200bps 5:38400bps

0~5 3

The parameter is used to set the speed of the transmission between the upper computer and the frequency inverter.Note: the baud rate of the upper computer and the frequency inverter you set must be consistent. Otherwise, the communication can not be performed. The higher the baud rate is, the faster the communication speed is.

Func Code Name Illustration Setting

range Default value

Pb.02 Data bits calibration set

0: No check(N,8,1)for RTU 1: Even parity check(E,8,1)for RTU2: Odd check(O,8,1)for RTU 3: No parity(N,8,2)for RTU 4: Even parity check(E,8,2)for RTU5: Odd check(O,8,2)for RTU 6: No parity(N,7,1)for ASCII 7: Even parity check(E,7,1)for ASCII8: Odd check(O,7,1)for ASCII 9: No parity(N,7,2)for ASCII 10: Even parity check(E,7,2)for ASCII11: Odd check(O,7,2)for ASCII 12: No parity(N,8,1)for ASCII 13: Even parity check(E,8,1)for ASCII14: Odd check(O,8,1)for ASCII 15: No parity(N,8,2)for ASCII 16: Even parity check(E,8,2)for ASCII17: Odd check(O,8,2)for ASCII

0~17 0

The data form of the upper computer and the frequency inverter must be consistent. Otherwise the communication

can not be performed.

11-bits(for RTU)

Page 76: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 75 -

10-bits(for ASCII)

Func Code Name Illustration Setting range Default value

Pb.03 response delay in the communication

0~200ms 0~200 5ms

Response delay: refers to the interval when the frequency inverter ends the acception of the data and sends

response to the upper computer. If the response delay is less than the system processing time, the respond delay

should be subject to the system needs delay holding after the data process until the respond time is up, it will send

the data toward the upper computer. Func Code Name Illustration Setting range Default value

Pb.04 Failure time of the communication overtime

0.0 s(Invalid),0.1~100.0s 0~100.0 0.0 s

When the functional code is set at 0.0s, the communication overtime parameter is invalid.

When the functional code is set at its valid value, the system reports the communication fault, if the interval

between one communication and the next communication surpasses the communication overtime.

Generally, set the functional code at 0. If the parameter is set in continuous communication system, the

communication state can be monitored. Func Code Name Illustration Setting range Default value

Pb.05 Transmission error handling

0:Alarm and free stop 1:No alarm and continue running2:No alarm and stop in stop mode( limit under communication control mode) 3:No alarm and stop in stop mode(under all the control mode)

0~3 1

The frequency inverter can select shielding communication error stop or continuous by setting the communication error handling under abnormal condition.

Func Code Name Illustration Setting range Default value

Pb.06 Transmission response handling

0:Response as writing operation 1:No response as writing operation

0~1 0

When the functional code is set at 0,the frequency inverter can respond to READ/WRITE command from

the upper computer.

When the functional code is set at 1, the frequency inverter only can respond to READ command from the

upper computer and no response to WRITE command.I can promote the communication efficiency by this mode.

Page 77: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 76 -

6.13 Swing frequency and supplementary function parameters(PC Group)

Func Code Name Illustration Setting range Default value

PC.00 Inhibition of oscillation

freq. threshold point 0~500 0~500 5

PC.01 Inhibition of oscillation freq. threshold point 0~500 0~500 100

Current oscillation often occurs in some frequency phases for most motors, which lead the motor unstable operation or even cause over-current of the frequency inverter.If PC.04=0, it enables oscillation inhibition, when PC.00 and PC.01 are lower, the inhibition effect is obvious and the current increase is obvious; while they are set higher,the inhibition effect is weak.

Func Code Name Illustration Setting range Default value

PC.02 Inhibition of oscillation amplitude limit value 0~10000 0~10000 5000

Voltage increase upon oscillation inhibition can be limited by setting PC.02. Func Code Name Illustration Setting range Default value

PC.03 Demarcation of high and low freq. of restrain oscillation

0.00~P0.04(Max freq.) 0.00Hz~P0.04 12.50Hz

PC.03 is the demarcation point of PC.00 and PC.01. Func Code Name Illustration Setting range Default value

PC.04 Oscillation suppression

0:Oscillation inhibition is valid 1:Oscillation inhibition is invalid

0~1 1

0:Oscillation inhibition is valid. 1:Oscillation inhibition is invalid. The function of oscillation inhibition is corresponding to VF control. Current oscillation often occurs to

common motor running with no or light load to cause the abnormal operation of the motor, even over-current of the frequency inverter. If PC.04=0, it enables restrain oscillation, then the frequency inverter will restrain the oscillation of the motor according to the parameters in PC.00 and PC.03 groups.

Func Code Name Illustration Setting range Default value

PC.05 PWM mode selection 0: PWM mode 1 1: PWM mode 2 2: PWM mode 3

0~2 0

0:PWM mode 1,the normal PWM mode, with lower noise under lower frequency and with higher noise under higher frequency.

1:PWM mode 2. The motor runs with lower noise under this mode, but with high temperature, so the frequency inverter needs to be derated under this mode.

2:PWM mode 3. The motor runs with higher noise under this mode, but with better restrain effect on motor oscillation.

Func Code Name Illustration Setting range Default

value

PC.06

PWM mode1 speeding up boundary frequency

0~50.0 0~50.0 14.0

PC.07

PWM mode1 slowing up boundary frequency

0~50.0 0~50.0 11.0

When frequency inverter is in PWM mode 1, sometimes motor vibrates at low frequency, which could be

tackled by skipping PC.06 and PC.07. When vibrating at some frequency point, vibration can be retrained by

adjusting PC.06 frequency lower than that frequency point, where PC.06 should be larger than PC.07 for fear of

frequency shifting to PWM mode.

Page 78: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 77 -

Func code Name Illustration Setting range Default

value

PC.08 Torque setting mode selection

0:Keyboard setting(Pd.07)(100% relative to P3.07 torque upper limit) 1:Analog quantity VI setting(100% relative to P3.07 torque upper limit) 2:Analog quantity CI setting(100% relative to P3.07 torque upper limit) 3:Analog quantity VI+CI(100% relative to P3.07 torque upper limit) 4: Multi-stage torque setting(100% relative to P3.07 torque upper limit) 5:Remote communications setting(100% relative to P3.07 torque upper limit)

0~5 0

PC.09 Torque set by Keyboard

-100.0%~100.0% -100.0%~100.0% 50.0%

Only if P0.04=2,the torque control is valid.Under torque control, the frequency inverter output the torque according to the preset command and the output frequency is limited by the upper limit frequency. If the load speed is greater than the preset upper limit frequency, the output frequency is limited and the output torque will be different from the preset value.Under torque control, the torque set by PC.08 is torque command.If the torque command is set by keypad(PC.08 is 0),torque command can be obtained by setting PC.09. When the torque is set as a negative number, The motor will reverse.

The torque control and speed control can be shifted by multifunctional input terminal. If the preset torque is greater than the load torque, the output frequency of the frequency inverter will increase.

The frequency inverter will run at the upper limit frequency when the output frequency is up to the upper limit. If the preset torque is less than load torque, the frequency inverter will descend. The frequency inverter will

run at the lower limit frequency when the output frequency is at the lower limit. 100% set by PC.09 corresponds to upper limit setting of the torque, namely P9.07,The preset torque value

can be modified by adjusting PC.08、P9.07. Note:Under stop mode, the frequency inverter shifts from torque control to speed control

automatically. Func Code Name Illustration Setting range Default

value

PC.10

Setting source selection for the upper limit frequency

0:Keyboard sets an upper limit freq.(P0.08) 1:Analog quantity VI sets an upper limit freq.(100% corresponds to the maximum freq.) 2:Analog quantity CI sets an upper limit freq.(100% corresponds to the maximum freq.) 3:Multi stage sets an upper limit frequency(100% corresponds to the maximum freq.) 4:Remote communication sets an upper limit frequency(100% corresponds to the maximum freq.)

0~4 0

Setting source option of multiple upper frequency can be achieved by PC.10.Especially under torque control, the output frequency of the frequency inverter can be changed by modifying the upper limit frequency.

Func Code Name Illustration Setting range Default

value PC.11 Swing freq.

amplitude 0.0~100.0%(The relative freq. setting) 0.0~100.0 0.0%

PC.12 Kick frequency amplitude

0.0~50.0%(The relative swing freq. range) 0.0~50.0 0.0%

PC.13 Swing freq. rise time 0.1~3600.0s 0.1~3600.0 5.0s PC.14 Swing freq. descend

time 0.1~3600.0s 0.1~3600.0 5.0s

Page 79: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 78 -

The Swing frequency is applicable to industrials such as textile and chemical fiber and fields such as traveling and winding.

Swing frequency function refers to that the output of the frequency inverter swings around the setting frequency.See the trace of the running frequency in the figure below, where the swing amplitude can be set by PC.11; when PC.11 is 0, the amplitude is 0 and the swing frequency is invalid.

Output freq.

time

Center freq.

Swing AM

Kick AM

Swing down time Swing up time

Accelerate with acc time

Decelerate dec time

Swing upper freq.

Swing lower freq.

Fig.6-30 Operation diagram of swing frequency

Swing freq. amplitude:the running frequency of swing frequency is controlled by the upper and lower limit of frequency values. AW to center frequency:AW=center frequency×amplitude PC.11.

Kick frequency=AW×kick freq. amplitude PC.12.When the swing frequency runs,the kick frequency is corresponding to the value of amplitude. Swing freq. rise time:the time of the swing frequency runs from the lowest point to the highest one. Swing freq. descend time:the time of the swing frequency runs the highest point to the lowest one.

6.14 Swing frequency and supplementary function parameters(PD Group)

Func Code Name Illustration Setting range Default

value Pd.00 User password 0~65535 0~65535 0

Set any non-zero number and then the password protection takes effect. 00000:clearing the previous user password and the password protection is invalid. The recovery of factory

setting also can clear the password.

When the users set the pass word and takes effect, the users can not enter the parameter menu if put the incorrect pass word. Only with the correct password, the users cn check and modify the parameters. Please remember the user password you set.

The password protection takes effect 1 minute after you exit from the functional editing mode. Press MENU/ESC to enter the functional editing mode since the password takes effect,it displays“0.0.0.0.0”. The operator must input the correct pass word, otherwise fails to enter.

Func Code Name Illustration Setting range Default

value Pd.01 Rectifier module

temperature 0~100.0

Pd.02 Inversion module temperature

0~100.0

Pd.03 Accumulated operation time of the equipment

0~65535h

The above functional codes only can be examined but can not be modified. Rectifier module temperature:refers to the temperature of the rectifier module. For different models, the

over-temperature protection value of rectifier module may diversify. Inversion module temperature:indicates the temperature of module IGBT,For different models, the

over-temperature protection value of inversion module may diversify. Accumulated operation time of the equipment:indicates the accumulated running time by now.

Func Code Name Illustration Setting range Default

value Pd.05 PG encoder pulse number 50~9999 50~9999 1000

Page 80: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 79 -

Please fill in the correct parameters according to the the pulse number of per revolution of the chosen PG

encoder.Especially in vector control with speed sensor, be sure to fill in the correct parameters.

Func Code Name Illustration Setting range Default

value Pd.06 PG encoder direction 0:forward direction;1:reverse

direction 0~1 0

If the direction of interface board of the frequency inverter and PG wirring order matches the direction of

frequency inverter and motor linking order,select “0” as setting value(FWD), otherwise select “1”(REV).

The change of this parameter enables to adjust the corresponding relationship of wiring direction without

rewiring.

Func Code Name Illustration Setting range Default

value Pd.07 PG encoder disconnected

action selection 0:continue running;1:free stop 0~1 0

0:Keep on running

1:Coast to stop

In the operation of vector control with PG,if PG break,frequency inverter alarm displays E-25 and frequency

inverter stops output,motor coasts to stop.

Func Code Name Illustration Setting range Default

value

Pd.08 PG encoder disconnection detection time 2.0~10.0S 2.0~10.0S 2.0S

Confirm the consistent detection time of the fault as coder break.

Func Code Name Illustration Setting range Default

value

Pd.09 Zero speed detection 0: Prohibit disconnection protection 0~999RPM 0.0~999.9RPM 0

Zero speed detection value is designed to detect the PG break.

when the zero speed detection value is 0, the protection function as PG break is under an embargo.

When the given frequency is larger than zero speed detection value and the feedback speed of PG is less than

it, lasting the time set by Pd.08,the protection function as coded disc break will act.

6.15 Factory parameter(PE Group)

This is the factory parameter group.Users don’t try to open the parameter of this group, otherwise, it will

cause the problem like abnormal operation and damage of frequency inverter.

Page 81: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 80 -

Chapter 7 Troubleshooting 7.1 Fault Alarm and Troubleshooting

When the inverter is abnormal, protection function acts: LED displays fault code and the content, fault relay acts, the inverter stops output and the motor coasts to stop. YX8000 series inverter’s fault contents and troubleshooting is shown in Table 7-1. After fault alarm occurs, fault phenomenon should be recorded in detail, the fault should be processed according to Table 7-1. When in need of technical assistance, please contact your supplier.

Table 7-1 Alarms and troubleshooting Fault code

Type of faults Possible fault reasons Troubleshooting

Acc time is too short Adjust acc time V/F curve setup is not suitable Adjust V/F curve Restart the motor in running Setup start mode as speed tracking restrart

Torque boost setup is too big Adjust torque boost orset as auto mode E-01 Acc overcurrent

Inverter capacity is too low Select inverter with proper capacity

Dec time is too short Adjust Dec time

Potential load or load inertia is too big Add suitable braking device E-02 Dec overcurrent

Inverter capacity is too low Select inverter with proper capacity

Load mutation Check load

Acc or Dec time is too short Adjust Acc or Dec time

Input voltage abnormal Check input power supply

Load abnormal check load

E-03 Overcurrent at constant speed

running

Inverter capacity is too low Select inverter with proper capacity

Input voltage abnormal Check input power supply

Acc time is too short Adjust Acc time E-04 Acc overvoltage

Restart the motor in running Setup start mode as speed tracking restart

Dec time is too short Adjust the Dec time E-05

Dec overvoltage Potential load or load inertia is too big Add suitable braking device

Input voltage abnormal Check input power supply

Acc or Dec time is too short Adjust the Acc or Dec time

Abnormal change of input voltage Mount input reactor E-06

Overvoltage at constant speed

running Load inertia is too big Add suitable braking device

E-07 Overvoltage of

control power

supply

Input voltage abnormal Check input power supply

Air duct obstruction Clean air duct

Environment temperature is too high Improve the ventilation or decrease the

carrier frequency

Fan damaged Replace a new fan

E-08 Inverter overheat

Inverter module abnormal Contact supplier

Acc time is too short Adjust Acc time

DC braking value is too high Decrease DC braking current and increase

braking time

V/F curve setup is not suitable Adjust V/F curve Restart the motor in running Setup start mode as speed tracking restrart Mains voltage is too low Check mains voltage

E-09 Inverter

overload

Too heavy load Select inverter with proper capcity

Page 82: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 81 -

V/F curve setup is not suitable Adjust V/F curve

Mains voltage is too low Check mains voltage

General motor runs at low speed with

heavy load for long term

Use a special motor for long term running

Wrong setting of motor overload

protection factor

Set the factor right

E-10 Motor overload

Motor chocked or sudden change of

load

Check load

E-11

Undervoltage in

running

Mains voltage is too low Check mains voltage

Inverter overcurrent Refer to overcurrent troubleshooting

Output 3-phase fault or ground short Re-wiring

Air duct obstruction or fan damaged Clean air duct or replace a new fan

Environment temperature too high Decrease environment temperature

Control board connecting wire or

plug-in unit loose

Check and re-wiring

Current waveform abnormal due to

output missing phase, etc.

Check wiring

Auxiliary power damaged, or driving

voltage undervoltage

Contact supplier

E-12 Inverter module

protection

Control board abnormity Contact supplier

E-13 Peripheral fault Close external fault terminals Check the reason

Loose wiring or terminal connections Check and re-wiring

Auxiliary power source damaged Contact supplier

Hall component damaged Contact supplier E-14

Current detecting

circuit fault

Abnormal amplifier circuit Contact supplier

Wrong baud rate setting Set baud rate properly

Serial port communication fault Press key to reset or contact

supplier Improper fault alarm parameter setting Revise function code P3.09~P3.12

E-15 RS232/485

Communication fault

Upper computer doesn’t work Check upper computer and connecting cable

Serious interference Press key to reset or install input

power source filter E-16 System interference

DSP read/write error Reset or contact supplier

E-17 E2PROM

error

Read/write error of control parameter press key to reset or install input

power source filter

E-18 Motor parameter

overcurrent fault

Power range of Motor and inverter do

not match

Contact supplier

press key to reset

E-19 Input phase loss

protection

One of R, S, T port has no voltage press key to reset

check voltage of R, S, T

E-20 overcurrent fault

when restart

Overcurrent when inverter restart and

check speed

press key to reset

adjust relevant parameters

E-21 PID feedback

breakdown fault

1:PID feedback breakdown

2:PID feedback source disappear

1:Check the signal wire of PID feedback

2:check the source of PID feedback

STOPRESET

STOPRESET

STOPRESET

STOPRESET

STOPRESET

STOPRESET

Page 83: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 82 -

7.2 The common failures and its treatment

Frequency converter may encounter the following fault conditions in the course running, please refer to the

following simple method for fault analysis:

Power on without display:

Check if the input power is in line with rated voltage by multimeter. If you have any questions please check

the power supply and rule out.

Check whether the three-phase rectifier bridge is in good condition. If the rectifier bridge has blasted, please

seek service.

Check whether the CHARGE lamp is light. If the light has gone, fault generally focus on the rectifier bridge

or buffer resistance. If the light is on, the fault may be on switch power supply.Please seek service.

Power air switch tripping after power on:

Check whether there is power grounding or short circuit conditions and eliminate the existing problems.

Check to see if the rectifier bridge has been broken down, if damaged, seek service.

The motor fails to rotate after frequency inverter running:

Check whether there is a balanced three-phase output among U, V, W. If there is, lines or damage itself, the

motor or motor blocked due to mechanical trouble.Please rule out.

If there is output but three-phase imbalance, it should be that inverter drive board or output module is damaged,

please seek service. If due to stops up transfers, Please rule out.

If there is no output voltage, output module and drive board might be damaged. Please seek service.

inverter showing normal as power on and Power air switch tripping after running:

See if there are any short circuit between the output module and condition.If yes, please seek service.

Check whether there is a short circuit or ground between motor lead.If yes, Please rule out.

If trip occasionally and there is a relatively far distance between motor and frequency converter, consider to

add the output AC reactor.

Attention

(1) Reset the inverter after throughly investigating the cause of fault and clearing, otherwise, the inverter may be

damaged.

(2) If it can’t be reseted or fault occurs again after reset, please check the cause of fault, continuous reset may

damage inverter.

(3) Reset the inverter after waiting for 5min when overload or overheat protection occurs.

Page 84: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 83 -

Chapter 8 Preservation and Maintenance

8.1 Preservation and Maintenance

Potential hazards exist due to aging, wear and tear of inverter internal components as well as environmental influences to the inverter, such as temperature, humidity particles etc.. Therefore, daily inspection, periodic preservation and maintenance must be performed to the inverter and its driving mechanism during their storage and operation. 8.1.1 Daily Maintenance

The following must be verified before starting up: (1) No abnormal vibration and no abnormal noise. (2)No abnormal heat. (3)No abnormal ambient temperature. (4)The ammeter satisfy the specification (5)Fan is working in good condition

8.2 Periodic Preservation and Maintenance 8.2.1 Periodic Maintenance

Cut off the power when inverter is maintained termly, check after the main circuit power indicator light is off. The checking content is shown in Table 8-1.

table 8-1 Periodic inspections 8.2.2 Termly maintaining

In order to let inverter work well for a long term, user must maintain the inverter termly. The replace time of element of inverter is shown in Table 8-2.

Table 8-2 converter parts replacement time

Device name Standard years change Cooling fans 2-3 years

Electrolytic capacitors 4-5 years Printed circuit board 5-8 years

Fuse 10 years The working condition of the inverter as following: (1) Environment temperature: average 30. (2) Load coefficient: under 80%. (3) Running time: under 12 hour everyday.

Checking item Checking content Troubleshooting Screws of control terminals and main circuit terminals

The screws are loose or not

If loose, tighten them with screw driver

heatsink Whether there is dust Clean thoroughly the dust

Printed circuit board Whether there is dust Clean thoroughly the dust

Cooling fans Whether there is abnormal vibration or abnormal noise

Replace cooling fans

Power elements Whethere there is dust Clean thoroughly the dust

Electrolytic capacitor Whether there is discoloring, peculiar smell

Replace electrolytic capacitor

Page 85: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 84 -

Chapter 9 Serial Port Communication Protocol Of

RS485

9.1 Communication overview Our YX8000 series of inverters provide users with a common industrial control RS485 communication

interface, in which the MODBUS standard protocol is used for communication. The inverters can be used as slave

connected to the host (such as PLC controller, PC), both of which have the same communication interface and

protocol, for the purpose of centralized monitoring of the inverters. Or one inverter can be used as host and other

inverters as slaves, all connected with RS485 communication interface, to achieve multi-machine interaction of the

inverters. And with this communication interface, a Keyboard can also be connected to inverters for remote

operation.

The MODBUS communication protocol of the inverter supports two transmitting ways: RTU mode and ASCII,

and either can be chosen. The following is a detailed description of the communication protocol of the inverter.

9.2 Communication protocol specification 9.2.1 Communications networking methods

(1) networking methods with inverter as slave:

Fig. 9-1 networking of slaves

(2) The networking of multi-machine interaction:

Fig.9—2 The networking of multi-machine interaction

9.2.2 Communication protocol

The inverter can either used as a host or slave in RS485 network. It can be used for controlling our other inverters as host to achieve multi-level linkage, or controlled by host (PC or PLC) as a slave. The specific communication mode as follows:

a) inverter is used as slave, in point-to-point communication of master-slave mode. Host sends commands from broadcast address, while slave doesn’t answer.

b) inverter is used as host, sending commands from broadcast address, while slave doesn’t answer. c) The address, baud rate and data format of the inverter can be setup by using the keyboard or the serial

communication. d) message of error is reported by slave, in the recent response frame against host polling.

PC as host

232-485 Conversion

YX8000

RS485

RS232

Single host

single slaves

PC as host PLC as host

232-485 Conversion

YX8000 YX8000 YX8000 YX8000

OR

RS232

RS485

Single host

Multi slaves

Host YX8000

Slave YX8000 Slave YX8000 Slave YX8000 Slave YX8000

RS485

Page 86: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 85 -

9.2.3 Communication Interface

The communication is using RS485 interface, with asynchronous serial and half-duplex transmission. The

default communication protocol in ASCII mode.

The default data format: 1 start bit, 7 data bits, 2 stop bits.

The default rate is 9600bps. Communication parameter settings reference P3.09 ~ P3.12 function code. 9.3 Contents

MODBUS Serial Protocol defines the content and application form if the frame of asynchronous transmission in serial communication, including: host polling and broadcast frame, the response frame form of slaves; the frame content organized by the host includes: slave address( or broadcast address), command execution, data and error check etc. The response of slave adopts the same structure including: action confirmation, returning data and error check. If there is any error when the slave is receiving frame or can not accomplish the action, required by host, it will organize an error frame to feed backed to the host.

9.4 Application mode YX8000 series frequency Inverters can access the “unit-host and multi-slave” control network with

RS232/RS485 bus. 9.5 Bus structure

(1) Interface RS485 hardware interface

(2) Transmission mode Asynchronous serial and semi-duplex, only the host or slave can send and the other can receive the data

simultaneously. During the serial asychronous communication, the data is transmitted frame by frame in the form of message.

(3) Topology structure Uni-host and multi-slave system. Set the slave address between 1-24 and 0 is the broadcast communication

address. The address of each slave in the network is unique, which is the foundation to ensure MODBUS serial communication. 9.6 Protocol Specification

The protocol of the series of frequency converters is an asynchronous serial master-slave protocol and only one unit (the host) can build the protocol (called “inquiry/command”). Other equipments (slaves) only can respond to the “inquiry/command” by providing data, or take actions according to the “inquiry/command” of the host. The host here refers to the PC, industrial control device, or programmable logic controller (PLC) etc. Slave refers to the series of frequency inveters or other control devices with similar protocol. The host can communicate with a single slave or send broadcast information all slaves. The slave should respond a message (response) to single “inquiry/command” of the host. And for the broadcast information, the slaves need not respond the information to the host. 9.7 Frame structure

The communication data of the MODBUS protocol of the series of YX8000 series frequency ivnerters has two forms,RTU (Remote Control Unit) and ASCII (American Standard Code for Information International interchange).

See the form of each byte in RTU mode below: Coding system: 8-bit binary system, in each 8-bit frame field, there are two hex characters, hex 0-9,A-F. See the form of each byte in ASCII mode below: Coding system: the protocol is hex. The meaning of ASCII information: “0”~ “9”. “A” ~ “F” each hex is indicated by corresponding character information in ASCII.

Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’ ‘8’ ‘9’

ASCII

CODE

0x30 0x31 0x32 0x33 0x34 0x35 0x36 0x37 0x38 0x39

Character ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’

The bit of bytes including: start bit, 7/8 data bit, check bit and stop bit. See the description of bytes bit below: 11-bit character frame:

Start bit Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8

No parity bit Even parity bitOdd parity bit

Stop bit

Page 87: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 86 -

10-bit character frame

Start bit Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7

No parity bit Even parity bit Odd parity bit

Stop bit

In RTU mode, new frame usually starts at the transmission time of at least 3.5 bytes. The transmission time of 3.5 bytes can be easily controlled on the internet whose transmission speed is calculated by baud rate. And then the date fields are in order: slave address, operation command code, data and CRC check word, the transmission byte in each field is hex 0…9, A…F , the internet always is monitoring the activity of the communication bus. Each internet device will confirm the byte as receive the first field (address information). As the last byte finished, an interval occurs between it and a similar transmission time of 3.5 byte to indicate the end of the frame. After that, a new frame will be transmitted.

The information of a frame must be transmitted by a continuous data flow. If there is ainterval over 1.5 bytes

prior to the end of the transmission, the receiver will clear the incomplete information and mistakes the last byte for the address of a new frame. Similarly, if the interval between the start of a new frame and the previous frame is less than 3.5 bytes, the receiver mistakes it for the continuing of the previous one. So the mistake of frame finally cause incorrect CRC test value and communicaiton error.

Standard structure of RTU frame: Frame START T1-T2-T3-T4(Transmission time of 3.5 bytes)

Slave ADDR Communication address:0~247(decimal system)(0 is the broadcast address)

Functional field CMD 03H:read slave paramter; 06H:write slave parameter

DATA field DATA(N-1)

… DATA(0)

2*N a data with n bytes, it is the main content of the communication and also is the core of data exchange in the communicaiton

CRC CHK low bit

CRC CHK high bit Check value:CRC calibration value(16BIT)

Frame END T1-T2-T3-T4(Transmission time of 3.5 bytes)

In ASCII mode, the frame start is “:” (0x3A) and the END default is “ CRLF” (“0x0D””0x0A”). In ASCII mode,all the data bytes are transmitted by ASCII code except the frame start and end: sending high 4-bit byte first and then sending low 4-bit byte. The data is 8-bit in length under ASCII mode. For ‘A’~‘F’, the capital letter of ASCII is adopted. Then the data is tested by LRC check which covering from the slave address to the data information. The checksum is the complement code of bytes sum ( the carry bit is neglected) all data involved in the check.

Standard structure of ASCII:

START ‘:’(0x3A) Address Hi Address Lo

Communication address: 8-bit address is combined by2 ASCII codes

Function Hi Function Lo

Function code: 8-bit address is combined by2 ASCII codes

DATA(N-1) …

DATA(0)

Data content: nx8-bit address is combined by2 ASCII codes n<=16,the max is

32 ASCII codes LRC CHK Lo LRC check code:

Slave add

Start:“0x3A”

Function code

data checkEnd:

“0x0D”“0x0A”

MODBUS message

ASCII data frame format

Slave add

Start,at least 3.5 characters

of free

Function code

data check

End,at least 3.5 characters

of free

MODBUS message

RTU data frame format

Page 88: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 87 -

LRC CHK Hi 8-bit check code is combined by 2 ASCII codes

END Hi END Lo

END character: END Hi=CR(0x0D),END Lo=LF(0x0A)

9.8 Command code and communication data 9.8.1Command code: 03H(0000 0011), read N words ( 16 words can be continuously read) For example: 01H is the slave address and the internal memory is 0004, 2 words can be continuously read. See the structural description of this frame below:

RTU host command information START T1-T2-T3-T4(Transmission time of 3.5 bytes) ADDR 01H CMD 03H

HIGH BIT OF START ADDR 00H LOW BIT OF START ADDR 04H

HIGH BIT OF DATA NUMBER 00H LOW BIT OF DATA NUMBER 02H

LOW BIT OF CRC CHK 85H HIGH BIT OF CRC CHK CAH

END T1-T2-T3-T4(Transmission time of 3.5 bytes) RTU slave response message

START T1-T2-T3-T4(Transmission time of 3.5 bytes) ADDR 01H CMD 03H BYTE NUMBER 04H HIGH BIT OF DATA ADDR 0004H 00H LOW BIT OF DATA ADDR0004H 00H HIGH BIT OF DATA ADDR 0005H 00H LOW BIT OF DATA ADDR0005H 00H LOW BIT OF CRC CHK 43H HIGH BIT CRC CHK 07H END T1-T2-T3-T4(Transmission time of 3.5 bytes)

ASCII HOST command information START ‘:’

‘0’ ADDR ‘1’ ‘0’ CMD ‘3’ ‘0’ HIGH BIT OF START ADDR ‘0’ ‘0’ LOW BIT OF START ADDR ‘4’ ‘0’ HIGH BIT OF DATA NUMBER ‘0’ ‘0’ LOW BIT OF DATA NUMBER ‘2’

LRC CHK Lo ‘F’ LRC CHK Hi ‘6’ END Lo CR END Hi LF

ASCII slave responding information START ‘:’

‘0’ ADDR ‘1’ ‘0’ CMD ‘3’ ‘0’ BYTE NUMBER ‘4’ ‘0’ HIGH BIT OF DATA ADDR 0004H ‘0’ ‘0’ LOW BIT OF DATA ADDR0004H ‘2’ ‘0’ HIGH BIT OF DATA ADDR 0005H ‘0’

Page 89: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 88 -

‘0’ LOW BIT OF DATA ADDR 0005H ‘0’

LRC CHK Hi ‘F’ LRC CHK Lo ‘6’ END Lo CR END Hi LF 9.8.2 Command code: 06H(0000 0110), write a word For example: write 5000 (1388H) to the slave addr. 02H frequency inverter to 0008H. See the structural description of the frame:

RTU host command information START T1-T2-T3-T4(Transmission time of 3.5 bytes) ADDR 02H CMD 06H HIGH BIT OF START ADDR 00H LOW BIT OF START ADDR 08H HIGH BIT OF DATA CONTENT 13H LOW BIT OF DATA CONTENT 88H LOW BIT OF CRC CHK 05H HIGH BIT OF CRC CHK 6DH END T1-T2-T3-T4(Transmission time of 3.5 bytes)

RTU slave response information START T1-T2-T3-T4(Transmission time of 3.5 bytes) ADDR 02H CMD 06H HIGH BIT OF START ADDR 00H LOW BIT OF START ADDR 08H HIGH BIT OF DATA CONTENT 13H LOW BIT OF DATA CONTENT 88H LOW BIT OF CRC CHK 05H HIGH BIT OF CRC CHK 6DH END T1-T2-T3-T4(Transmission time of 3.5 bytes)

ASCII host command information START ‘:’

‘0’ ADDR

‘2’ ‘0’

CMD ‘6’ ‘0’ HIGH BIT OF DATA ADDR ‘0’ ‘0’ LOW BIT OF DATA ADDR ‘8’ ‘1’ HIGH BIT OF DATA CONTENT ‘3’ ‘8’ LOW BIT OF DATA CONTENT ‘8’

LRC CHK Hi ‘5’ LRC CHK Lo ‘5’ END Lo CR END Hi LF

ASCII slave response information START ‘:’

‘0’ ADDR

‘2’ ‘0’

CMD ‘6’ ‘0’ HIGH BIT OF START ADDR ‘0’ ‘0’ LOW BIT OF DATA ADDR ‘8’

Page 90: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 89 -

‘1’ HIGH BIT OF DATA CONTENT ‘3’ ‘8’ LOW BIT OF DATA CONTENT ‘8’

LRC CHK Hi ‘5’ LRC CHK Lo ‘5’ END Lo CR END Hi LF 9.8.3 Frame error verification mode

The error verification mode of the frame mainly includes the verifications of two parts: i.e,bit check of the byte ( even/ odd parity check) and the whole data check of the frame (CRC check or LRC check). 9.8.3.1 Byte bit check

The user can elect different check mode or no check as required, which may influence the verfication bit place of each byte.

The meaning of even parity check: add an even parity bit prior to the data transmission used to indicate that the number of “1” in the data is odd or even. The check bit is 0 if it is even, “1” for the odd. It is used to remain the parity of the data.

The meaning of odd parity check: add an odd parity bit prior to the data transmission used to indicate that the number of “1” in the data is odd or even. The check bit is 0 if it is odd, “1” for the even. It is used to remain the parity of the data.

For instance, if you want to transmit “11001110”. There are 5 “1”, the even parity bit is “1” if use even parity check ,while the odd parity bit is “0” if use odd parity check. The parity check bit is put in the place if the check bit of the frame during data transmission, then the receiver also needs parity check. If the parity of the received data is inconsistent with the preset one, communication error occurred. 9.8.3.2 CRC (Cyclical Redundancy Check)

Using RTU form, the frame contains frame error detection based on CRC algorithm. CRC detected all the content of the frame. CRC contains two bytes and 16-bit binary value. It is added into the frame after calculated by the transmission device. The receiver will calculate the CRC of the frame it received and compare it with the one it received. Transmission error occurs of the two CRC values are not equivalent.

CRC is saved to 0xFFFF firstly, and then use a continuous over 6-bit byte to process the present value in the register. Then only 8-bit data in each character is valid to CRC while the start bit, end bit and parity check bit are invalid.

During the CRC production, each 8-bit character is individually different or (XOR)from the content in the register, and the result moves toward the lowest effective bit while the highest effective bit is filled with 0. LSB is picked up to detect. If LSB is 1, the individual value in the register is different from the preset one;if LSB is 0, no this performance. The whole process needs to be repeated for 8 times. As the last bit (8th bit) finished, the next 8-bit is individually differrent from the preset value in the register. At last, the value in the register is the CRC value after the performance of all bytes.

The algorithm of CRC adopts the international standard CRC check rule. The user may refer to the relevant CRC algorithm to edit the proper CRC algorithm as required when editing the CRC algorithm.

Here provides a simple function of CRC for your reference ( C-language programming): Unsigned int crc_cal_value(unsigned char “data_value, unsigned char data_lengty)

int i; unsigned int crc_value=0xffff; while(data_length--)

crc_value^=*data_value++;

for(i=0;i<8;i++)

if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001; else crc_value=crc_value>>1; return(crc_value);

In the stair logic, CKSM calculates CRC value accoridng to the frame content by LUT which is simple and

Page 91: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 90 -

fast, but needs larger ROM space, so please be prudent to use in the environment where the space is required. 9.8.3.3 ASCII mode check (LRC check)

LRC check is the accumulated value from ADDRESS to DATA CONTENT, such as the above check code in 11.6.2: 0×02×0×06+0×00+0×08+0×13+0×88+0×AB, and then select the compliment of 2=0×55. 9.8.4 Definition of data addr.

This part is the definition of the communication data addr. Which is used to control the operation of the frequency converter and obtain the state information and the relevant parameter setting etc.

(1) Indicating rules of the parameter addr. With the functional code, but it needs to be conveted to hex. If the code of H5.05 is 58, the hex indication of

the functional addr. Is 003AH. The scopes of high and low byte are: high-bit-00~01; low-bit byte——00~FF. Note: PE Group: the parameters set by the manufacturer, so they are unreadable or unchangeable; some

parameters cannot be modified when the frequency converter is under operation; some parameters never can be modified in any state; the setting scope, unit and relevant instructions should be noted if you want to change the functional code.

In addition, because EEPROM is saved frequently, it may decrease the service life if EEPROM. For users, some functional codes are unnecessary to save under communication mode and just need to modify the value in RAM to satisfy the application requirements. You can achieve the function only by changing 0 in the highest bit of the functional code to 1. For instance, the functional code H0.07; the address can only be used write in RAM, but without read function, i.e. it is invalid address for read.

(2) Address instruction of other functions

Function Address

definition Data meaning instruction R/W feature

0001H:forward operation 0002H:reversal operation 0003H:forward inching 0004H:reversal inching 0005H:stop 0006H:free stop(urgent stop) 0007H:error default

Communicaiton Control command

1000H

0008H:stop inching

W

0001H:under forward operation 0002H:under reversal operation 0003H:under standby mode

Frequency inverter state 1001H

0004H:error

R

Address of communication setting value

2000H

The communication setting value scope(-10000~10000)

Note: the communication setting value is the relative percentage(-100.00%~100.00%),and can be used for write action.When set it as the frequency source, the corresponding value is the percentage of the max frequency(P0.04);when it is used as the PID given or feedback value,the corresponding value is the percentage of PID. Among them, both PID given and feedback value are calculated in the form of percantage

W

3000H Running speed R 3001H Preset speed R 3002H Bus voltage R 3003H Output voltage R 3004H Output current R 3005H Running rotational speed R 3006H Output power R 3007H Output torque R 3008H PID given value R 3009H PID feedback value R

Operation/stop Parameter address instruction

300AH Flag state of terminal input R

Page 92: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 91 -

300BH Flag state of terminal output R 300CH Analog VI value R 300DH Analog CI Analog R 300EH Retation R 300FH Retation R 3010H Retation R 3011H Retation R 3012H Multi-speed and the present phase R

Error address 5000H

The error code is consistent withth error type code in the functional code menu. But the returning data here to the upper computer is hex data, but no the error character.

R

ModBus communication error address

5001H

0000H:No error 0001H: passward error 0002H: command code error 0003H:CRC ECC error 0004H:Illegal address 0005H:Illegal data 0006H:Null parameter change 0007H:System locked 0008H: inverter being busy(EEPROM being storing)

R

9.8.5 Extraneous response of error information

When communication is connected and an error comes into being, now the inverter will respond error code

to the host control system in a fixed format of response.No matter is the command code of inverter communication

is “03”or“06”,the command byte of fault response replies host control system according to “06”and the data

address is fixed 0x5001.

For example:

RTU Slave fault response message

START T1-T2-T3-T4(Transmission time of 3.5 bytes) ADDR 01H CMD 06H HIGH BIT OF FAULT RETRUN ADDR

50H

LOW BIT OF FAULT RETURN ADDR

01H

HIGH BIT OF ERROR CODE 00H LOW BIT OF ERROR CODE 05H LOW BIT OF CRC CHK 09H HIGH BIT OF CRC CHK 09H END T1-T2-T3-T4( Transmission time of 3.5 bytes )

Page 93: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,

YX3000 Sensorless Vector Type Inverter Manual www.yuanxindrive.com

- 92 -

ASCII Slave fault response message

START ‘:’ ‘0’

ADDR ‘1’ ‘0’

CMD ‘6’ ‘5’ HIGH BIT OF FAULT RETRUN ADDR ‘0’ ‘0’ LOW BIT OF FAULT RETURN ADDR ‘1’ ‘0’ HIGH BIT OF ERROR CODE ‘0’ ‘0’ LOW BIT OF ERROR CODE ‘5’

LRC CHK Hi ‘A’ LRC CHK Lo ‘3’

END Lo CR END Hi LF

Meaning of error code:

Error code Instruction 1 Password error 2 Command code error 3 CRC ECC error

4 Illegal address 5 Illegal data

6 Null paramter change

7 System locked 8 Freq. inverter is busy(EEPROM is storaging)

Page 94: YX8000 Sensorless Vector Type Inverter Manual manual YX8000.pdf · stop parameter storage, injection molding machine energy saving control, swing frequency control, RS485 control,