yaskawa ac drive gt 1
TRANSCRIPT
1
YASKAWAYASKAWAYASKAWAYASKAWA
YASKAWA INVERTER
YASKAWAYASKAWAYASKAWAYASKAWA
THANK YOU
For further information please contact usFor further information please contact us
2
YASKAWAYASKAWAYASKAWAYASKAWA
Market of General purpose InvertersMarket of General purpose Inverters
IntroductionIntroduction
YASKAWAYASKAWAYASKAWAYASKAWA
4
109109109109 127127127127 144144144144 151151151151 166166166166
120120120120109109109109118118118118
9898989893939393
840
751767715644
0000
50505050
100100100100
150150150150
200200200200
250250250250
300300300300
350350350350
2002200220022002 2003200320032003 2004200420042004 2005200520052005 2006200620062006 2007200720072007 2008200820082008
00001001001001002002002002003003003003004004004004005005005005006006006006007007007007008008008008009009009009001000100010001000
202225
262 260
Drives Industry Market Growth in JapanDrives Industry Market Growth in Japan
Hu
nd
red
millio
n ye
nUn
its
x1
0,0
00
Drives up to 75 kW
Hundred million
Tens of thousands
Export
Domestic
23% 24%
27% 26%
3%
51%
15%
31%
up to 0.75 kW
0.75 kW to 4 kW
4 kW to 15 kW
15 kW to 75 kW
Units Amount
Shipments by capacity in 2008
Data from JEMA
286
3
YASKAWAYASKAWAYASKAWAYASKAWA
5
TotalTotalTotalTotalTotalTotalTotalTotal1.813million1.813million1.813million1.813million1.813million1.813million1.813million1.813million
FujiFujiFujiFujiFujiFujiFujiFuji24.3%24.3%24.3%24.3%24.3%24.3%24.3%24.3%
MitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishi30.5%30.5%30.5%30.5%30.5%30.5%30.5%30.5%
ToshibaToshibaToshibaToshibaToshibaToshibaToshibaToshiba9.5%9.5%9.5%9.5%9.5%9.5%9.5%9.5%
HitachiHitachiHitachiHitachiHitachiHitachiHitachiHitachi5.9%5.9%5.9%5.9%5.9%5.9%5.9%5.9%
OthersOthersOthersOthersOthersOthersOthersOthers6.0%6.0%6.0%6.0%6.0%6.0%6.0%6.0%
TotalTotalTotalTotalTotalTotalTotalTotal2,342M US$2,342M US$2,342M US$2,342M US$2,342M US$2,342M US$2,342M US$2,342M US$
YaskawaYaskawaYaskawaYaskawaYaskawaYaskawaYaskawaYaskawa12.8%12.8%12.8%12.8%12.8%12.8%12.8%12.8%
FujiFujiFujiFujiFujiFujiFujiFuji9.6%9.6%9.6%9.6%9.6%9.6%9.6%9.6%
MitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishiMitsubishi9.8%9.8%9.8%9.8%9.8%9.8%9.8%9.8%
OthersOthersOthersOthersOthersOthersOthersOthers25.8%25.8%25.8%25.8%25.8%25.8%25.8%25.8%
WorldWorld
YaskawaYaskawaYaskawaYaskawaYaskawaYaskawaYaskawaYaskawa23.7%23.7%23.7%23.7%23.7%23.7%23.7%23.7%
ABBABBABBABBABBABBABBABB10.0%10.0%10.0%10.0%10.0%10.0%10.0%10.0%
Rockwell Rockwell Rockwell Rockwell Rockwell Rockwell Rockwell Rockwell 12.1%12.1%12.1%12.1%12.1%12.1%12.1%12.1%
SiemensSiemensSiemensSiemensSiemensSiemensSiemensSiemens7.9%7.9%7.9%7.9%7.9%7.9%7.9%7.9%
※※※※Data estimated by Sales Promotion Section
ToshibaToshibaToshibaToshibaToshibaToshibaToshibaToshiba--------SchneiderSchneiderSchneiderSchneiderSchneiderSchneiderSchneiderSchneider7.2%7.2%7.2%7.2%7.2%7.2%7.2%7.2%
C.TC.TC.TC.TC.TC.TC.TC.T4.8%4.8%4.8%4.8%4.8%4.8%4.8%4.8%
Inverter Market Shares Inverter Market Shares (FY (FY 2009 2009 ))
JapanJapan
unitsunitsunitsunitsunitsunitsunitsunits
※※※※This share represents No. of unitsproduced in Japan.
YASKAWAYASKAWAYASKAWAYASKAWA
6
Yaskawa
14.1%
A
13.0%
B
12.8%C
12.5%
D
11.4%
E
8.6%
G
2.8%
F
7.8%
H
1.7%
Others
15.2%
\ 395.9 billion
2009
17.4%
15.8%12.8%
17.0%11.0%
Japan
USAEurope
China Asia
*Data has been gathered and analyzed by Yaskawa.
No.1 Global ShareNo.1 Global Share(fiscal year 2009)
Global Share by RegionGlobal Share by Region
4
YASKAWAYASKAWAYASKAWAYASKAWA
7
VS-610
VS-610B
VS-616T
Thyristor inverter (current type)
Thyristor inverter (current type)
PWM transistor inverter (analog)
Varispeed G7
Varispeed A1000
VS mini V1000
VS mini J1000
World’s
First
World’s
First
1000th1000th GenerationGeneration
**** 3-level
World’s
First
Year of 1968
1974
1980
VS-616HⅡⅡⅡⅡ PWM transistor inverter (digital)
1984
VS-616GⅡⅡⅡⅡ, GⅡⅡⅡⅡLN PWM transistor inverter (IGBT, low-noise type)
1987
3rd Generation
VS-616G3, etc.PWM transistor inverter
1989
5th Generation
VS-616G5, etc.PWM transistor inverter
1995
1969
World’s
First
VS-616G, H PWM transistor inverter (analog)
Year of 2000
2009
2008
2008
Year of 2000 to 2010
History of Yaskawa GeneralHistory of Yaskawa General--purpose Inverterspurpose Inverters
YASKAWAYASKAWAYASKAWAYASKAWA
8
RELIABILITY OF THE YASKAWA INVERTER
Yaskawa Japan produced the inverter unit about 60,000 units per month. We made the
follow up record from field trouble for every month.
The calculation is base on “Fit” unit. (where; 1Fit = 10-9Hrs.)
For the Yaskawa Inverter ,the reliability target is 250 Fit and has been achieved the target.
Example of Reliability; (Some customer adopt 100 units in their factory which operated 8000 Hrs/Yr.)
The reliability result =100 units*250Fit*8000Hrs(1yr Operating Hrs)
(base on 100 units)
=102units*250*10-9*8*103
= 0.2 unit/Yr
= 1units/5Yrs.
5
YASKAWAYASKAWAYASKAWAYASKAWA
9
Inverter Principle and CharacteristicsInverter Principle and Characteristics
YASKAWAYASKAWAYASKAWAYASKAWA
What’s a drive?What’s a drive?
AC voltageRectifier Circuit (converter section
changing AC to DC)
DC Bus (capacitors smooth out the waveform)
Inverter Circuit (inverter section changes DC back
into AC)AC voltage
Control circuit section
Constant
frequency,
constant
voltage
Variable frequency, variable voltage
Motor
Basic Circuitry in an Inverter Drive
A device that converts frequency and voltageA device that converts frequency and voltage
Inverter ConfigurationInverter Configuration
6
YASKAWAYASKAWAYASKAWAYASKAWAActual Output Voltage Waveform
Basic wave
EDC
Output voltage (V) is low when frequency (f) is low.
0
0
Output voltage (V) is high when frequency (f) is high.
EDC
The waveform created in the switching patterns on the previous page is a square wave. A sine
wave, however, is more preferable for accurate motor control.
In the diagram below, IGBT switching creates the waveform, a technique called, “pulse width
modulation” (PWM). PWM is capable of creating a waveform very similar to a sine wave.
V
V
YASKAWAYASKAWAYASKAWAYASKAWA
12
Control Method Output Frequency Features
PA M M ethodPA M M ethodPA M M ethodPA M M ethod (Pulse Amplitude Modulation)
・ Voltage control is
needed for the converter.
・ Motor current distortion is excessive, resulting in torque ripple.
PW M M ethodPW M M ethodPW M M ethodPW M M ethod (Sinusoidal Wave Approximate) PWM:
Pulse Width Modulation
When the above Output power frequency is 60 Hz, the number of pulses per cycle is
14. Therefore, carrier wave (carrier frequency) is obtained as 60×14 = 840 Hz.
Since the actual inverter has this carrier frequency of 15 kHz, the number of pulses
per cycle is 250 pulses (15000÷60).
・ Frequency and voltage
can be controlled only in the inverter section.
・ Smooth operation is possible at a low speed.
EdEd
(Ed: DC voltage)
Output Voltage Waveform
Ed
Ed
Average Output Voltage
VoltageVoltage--type Inverter Control Methodtype Inverter Control Method
7
YASKAWAYASKAWAYASKAWAYASKAWA
13
Name Diode Thyristor GTO
(Gate Tum Off Thyristor)
Bipolar Power Transistor
IGBT (Insulated Gate Bipolar
Tr.)
Power MOS FET (Power Metal Oxide
Semiconductor. Field Effect Tr.)
Sy
mb
ol
Ch
ara
cte
ris
tic
s
Vo
ltag
e,
Cu
rre
nt
Wav
efo
rm
Fea
ture
s,
Ap
plic
ati
on
General high-voltage,
large-current rectifier
circuits
High-voltage,
large-current converter
section
Inverter section, chopper
section attached with
commutation circuit
High-voltage,
large-current inverter
section, chopper
section
Medium voltage,
medium current
high-speed switching,
inverter section
Medium voltage,
medium current
high-speed switching,
inverter section
Low-voltage, small-
current high-speed
switching, inverter
section
Main Semiconductor Power Elements Used for InvertersMain Semiconductor Power Elements Used for Inverters
Anode
Cathode Gate
Collector
BaseEmitter
Drain
Gate
Source
YASKAWAYASKAWAYASKAWAYASKAWAMain Circuit and Control Circuit
AC
AC
DC
IMT
Pulse train output
R
S
Voltage
CurrentVoltage
Current
Multi-function analog
output (output frequency,
current, etc.)
Fault output
Multi-function contact
output (running, speed
agree, etc.)
Multi-functioninput
Sequencecommon
Analog input (speed setting)
Pulse train input
DigitalOperator
Analogmonitor
AC
power
supply
Inp
ut
term
inals
Ou
tpu
tte
rmin
als
Rectifier circuit(diodes)
Inverter conversion
circuit (IGBTs)
FWD run
REV run
Serial communication input
Voltage
Current
Smoothing circuit or DC bus
(capacitors)
8
YASKAWAYASKAWAYASKAWAYASKAWA
15
Varispeed G7
Specifications V/f Control V/f Control with PG Feedback
Open-loop Vector Control
Flux Vector Control
Basic Control
Voltage/frequency control (open-loop)
Voltage/frequency control with speed
compensation
Current vector control without PG
Current vector control with PG
Speed Detector Not needed
Needed (pulse generator)
Not neededNeeded
(pulse generator)
Option Card for Speed Detection Not needed Needed Not needed Needed
Speed Control Range 1:40 1:40 1:200 1:1000
Starting Torque 150% at 3 Hz 150% at 3 Hz 150% at 0.3 Hz 150% at 0 min-1
Speed Control Accuracy ±±±±2 to 3% ±±±±0.03% ±±±±0.2% ±±±±0.02%
Torque Limit Disabled Disabled Enabled Enabled
Torque Control Disabled Disabled Enabled Enabled
Typical Applications
Multi-drives Replacement for existing
motor of which motor constants are unknown
Auto-tuning is enabled only for line resistance.
Simplified feedback control
Applications where pulse generator is attached on the machine shaft
Any variable speed drives
Simplified servo drives
High-accuracy speed control
Torque control
Features of Control ModeFeatures of Control Mode
YASKAWAYASKAWAYASKAWAYASKAWA
16
Operation CharacteristicsOperation Characteristics
9
YASKAWAYASKAWAYASKAWAYASKAWA
17
(a) Proper Acceleration Time (b) Short Acceleration Time
AccelerationAcceleration
Output Frequency f
Motor speed N
Overload capacity when inverter
capacity is equal to motor capacity
Rated Current
Excessive Slip
Overload capacity when inverter
capacity is increased
Rated Current
0
0 0
0
YASKAWAYASKAWAYASKAWAYASKAWA
18
Inverter Output Frequency[Dotted line shows the set
accel. ratio.]
Motor Speed
Motor Current
Accel. time becomes longer automatically.
Peak current is limited to within the specified value.
Stall Prevention during AccelerationStall Prevention during Acceleration
t
10
YASKAWAYASKAWAYASKAWAYASKAWA
19
Inverter Output Frequency
Load
Stall Prevention during RunningStall Prevention during Running
To avoid overloading by rapid
fluid temperature in hydraulic
machines. Avoid overloading by
decreasing output frequency.
t
YASKAWAYASKAWAYASKAWAYASKAWA
20
DC Voltage
Inverter Output Frequency
Motor Current
RUN Signal
Actual Stall Prevention FunctionActual Stall Prevention Function
Edc.
OV,OA
11
YASKAWAYASKAWAYASKAWAYASKAWA
21
Inverter Output Frequency[Dotted line shows the set decel. ratio.]
Motor Speed
DC Voltage
DC bus voltage is limited to within specified value.
Decel. time becomes longer automatically.
Stall Prevention during DecelerationStall Prevention during Deceleration
t
YASKAWAYASKAWAYASKAWAYASKAWA
22
t
DC Injection Braking Time
t
DC
Current
N
N
t
DC Injection BrakingStarting Frequency
N, f
DC
Current
DC Injection
Braking Time
N
FF
F
(a) Frequency Deceleration
(Example of DC
Injection Braking
Before Stop)
(b) All-area DC Injection Braking (c) Coasting to a Stop
DC Injection BrakingDC Injection Braking
0 0 0
N, f N, f
Free Run
12
YASKAWAYASKAWAYASKAWAYASKAWA
23
Circuit Pattern Input Current Waveform Input Current SpectrumHarmonics
Content
No countermeasures taken
Harmonics Order
88%
AC reactor inserted
38%
DC reactor inserted
33%
P
N
P
N
P
N
+
+
+
Typical Inverter Input Current WaveformTypical Inverter Input Current Waveform
in Each Power Supply Method (1)in Each Power Supply Method (1)
1 5
1 5 7 11
1 5 7 11
YASKAWAYASKAWAYASKAWAYASKAWA
24
Circuit Pattern Input Current Waveform Input Current SpectrumHarmonics Contents
12-phase rectification
Harmonics Order
12%
PWM control converter
3%
P
N
P
N
+
+
1
1
Typical Inverter Input Current WaveformTypical Inverter Input Current Waveform
in Each Power Supply Method (2)in Each Power Supply Method (2)
13
YASKAWAYASKAWAYASKAWAYASKAWA
Inverter Drive Units SelectionInverter Drive Units Selection
YASKAWAYASKAWAYASKAWAYASKAWA
26
Motor Type
Motor Output
Inverter Output
Inverter Model
Peripheral units, Options
Enclosure
インバータの機種選定インバータの機種選定インバータの機種選定インバータの機種選定
Check Item
What to DecideCapacity SelectionCapacity Selection
Machine specifications
Operation method
Load type and characteristics
Inverter capacity selection
Inverter model selection
Motor selection
Peripheral units, options
Investment effect
Investment effect
Inverter selection
Final specifications
14
YASKAWAYASKAWAYASKAWAYASKAWA
From General IndustrialFrom General Industrial--use to Consumer Equipmentuse to Consumer Equipment
GeneralGeneral--purpose Inverter Series purpose Inverter Series
Varispeed G7
Varispeed A1000
Varispeed V1000
Varispeed J1000
High-graded Function Current Vector Control (0.4 to 300 kW)
High Performance Vector Control (0.4 to 630 kW)
Compact Vector Control Control (0.1 to 18.5 kW)
Compact V/f control Drive (0.1 to 5.5 kW)
YASKAWAYASKAWAYASKAWAYASKAWA
(1) Power supply transformer
(2) Circuit breaker or
(3) Leakage breaker
(4) Contactor(6)Noise filter
(5) AC reactor
(10) Braking resistor unit
(7) DC reactor
(8) Noise filter
(9) Contactor
Peripheral Devices and Their ConnectionsPeripheral Devices and Their Connections
(11) Contactor for commercial power backup
(12) Zero phase reactor
(13) Thermal
relay
(14) Motor
15
YASKAWAYASKAWAYASKAWAYASKAWA
29
No. Name Purpose and Selecting Points
1 Power transformer ・・・・Transformer capacity >>>> Inverter capacity ×××× 1.5
2 Circuit breaker・・・・Breaks accidental current (shortcircuit current). ・・・・Rated current >>>> inverter rated current ××××1.5 → Described in the inverter catalog.
3 Leakage breaker
・・・・Grounding protection・・・・High frequency leak current protection for electric shock accident & leakage current fire.
1. Use a breaker provided with countermeasures for high frequency leakage current. 2. Increase sensitivity current.3. Decrease inverter carrier frequency.
4 Contactor
・・・・Since the inverter has the contactor function, any contactor is not needed except for special cases.
・・・・When a braking resistor is used, insert a contactor to make thermal trip circuit.・・・・Perform RUN/STOP at the inverter side and set the contactor to “Always ON” to use.
57
AC reactorDC reactor
・・・・For high frequency current suppression and improvement of power factor・・・・Install a reactor to protect the inverter when the power supply capacity is large.
68
Noise filter orZero-phase reactor
・・・・Prevent radio noise generated by inverter section
910
Braking unitBraking resistor unit
・・・・Used when an electrical brake is needed (when the required braking torque exceeds 20%).
1112
Contactor for commercial power backup
・・・・Used for backup at inverter failure or when commercial power supply is used for normal operations.
13 Thermal relay・・・・Not needed when one motor is driven by one inverter. (Connected when more than two motors are used.)
How to Select Peripheral DevicesHow to Select Peripheral Devices
YASKAWAYASKAWAYASKAWAYASKAWA
30
Inverter Functions and AdvantagesInverter Functions and Advantages
16
YASKAWAYASKAWAYASKAWAYASKAWA
31
No. Advantage Technical Details Main Precautions
1
Can control speeds
of the specified
constant-speed
type motors.
Number of revolutions changes
when squirrel-cage-type motor
terminal voltage and frequency
are changed.
Since a standard motor has
temperature rise that becomes
greater at a low speed, torque must
be reduced according to frequency.
2
Soft start/stop enabled. Accel/decel time can be set freely
from a low speed.
(0.01 to 6000 seconds).
Set proper accel/decel time after
performing load operation.
3
Highly frequent
start/stop enabled.
Little motor heat generation since
smooth accel/decel is enabled with
little current.
Motor or inverter capacity frame
must be increased depending on the
accel/decel capacity. Check the
accel/decel time and load J.
4
FWD/REV run enabled without main
circuit contactor.
Because of phase rotation changes
by transistor, there are no moving
parts like conventional contactors
so that interlock operation can be
assured.
When applying the inverter to an
elevating unit, use a motor with a
brake to hold mechanically for
stand still.
Advantages of Inverter Applications (1)Advantages of Inverter Applications (1)
Cushion Startt
f
FWD Run
REVRun
Cushion Stop
Inverter
RUN CommandFWD Run
REVRun
t
f
YASKAWAYASKAWAYASKAWAYASKAWA
32
No. Advantage Technical Details Main Precautions
5
Can apply an electrical brake. Since mechanical energy is converted into
electrical energy and absorbed in the
inverter at decel, the motor can auto-
matically provide braking force.
DC current is applied to the motor around
zero-speed so that it becomes dynamic
braking, to completely stop the motor.
Braking force is approx. 20% when
only the inverter is used.
Attaching a braking resistor
(optional) externally can increase
the braking force.
Pay attention to the capacity of the
resistor.
6
Can control speeds of the
motor under adverse
atmosphere.
Since the inverter drives squirrel-cage
motors, it can be used easily for
explosionproof, waterproof, outdoor or
special types of motors.
An explosionproof motor in
combination with an inverter is
subject to explosionproof
certification.
7
High-speed rotation enabled. Commercial power supply can provide up
to 3600 min-1 (2-pole at 60Hz) or 3000 min-
1 (2-pole, at 50Hz).
A general-purpose inverter can increase
frequency up to 400 Hz (12000 min-1) while
a high-frequency inverter can increase it
up to 3000 Hz (180000 min-1).
The speed of a general-purpose
motor cannot be increased by
simply increasing the frequency.
(It can be applied without being
changed if frequency is approx. 120
Hz.)
Mechanical strength and dynamic
balance must be examined. 60Hz 120Hz 400Hz
Electrical Braking
Advantages of Inverter Applications (2)Advantages of Inverter Applications (2)
f
t
V
f
17
YASKAWAYASKAWAYASKAWAYASKAWA
33
No. Advantage Technical Details Main Precautions
8
The speeds of more than one motor
can be controlled by one inverter.
The inverter is a power supply unit
to the motor, therefore, as many
motors as the capacity allows can
be connected.
These motors do not have to be the
same capacity.
The number of motor revolutions
differs depending on each motor
characteristics or load ratio even at
the same frequency.
(Among general-purpose motors,
speed deviation of 2 to 3% can be
considered.)
Synchronous motors have the same
number of revolutions.
9
Power supply capacity can be small
when the motor is started up.
Large current (5 or 6 times larger
than the motor rating) does not
flow as with a commercial power
supply start.
Current can be limited to at most
100 to 150% by low-frequency start.
Transformer capacity (kVA)
= 1.5 ×××× inverter output capacity
10Number of revolutions becomes
constant regardless of power supply
frequency.
Output freq. can be set regardless
of power supply freq. 50/60Hz.
Inverter
Advantages of Inverter Applications (3)Advantages of Inverter Applications (3)
IM
IM
IM
YASKAWAYASKAWAYASKAWAYASKAWA
34
Inverter Output Voltage
Inverter Output Current
Inverter Input Current
150%
150%100% Current
100% Current
100% Voltage (100% Speed)
t
Motor and Power Supply CurrentMotor and Power Supply Current
in Inverter Drivesin Inverter Drives
t
t0
18
YASKAWAYASKAWAYASKAWAYASKAWA
35
Applied Load Concept of Energy-saving
Fans Pumps Blowers (Any Variable Torque Load)
Replace with a more efficient motor.
Reduce a redundancy of the facility for the actual loads.
Abate the head loss at valves or dampers.
(2)
(1)
(1)
Extruders Conveyors, etc. (Any Constant Torque Load)
Change to more efficient drives.
Replace the primary voltage control, secondary resistance
control, eddy-current coupling (VS motors) with a more efficient
control method(Frequency Control).
(3)
Cranes Elevators, etc.
Collect the regenerative energy at lowering by using the inverter
power supply regenerative function.
(4)
Rewinders Collect the regenerative energy of the rewinders.
Replace with a more efficient motor.
(4)
(2)
General Machines Reduce the starting energy.
(Use the inverter as a starter to stop the operations positively
whenever the load ratio is low.)
(5)a
Optimum EnergyOptimum Energy--saving Plan for Facilitysaving Plan for Facility
YASKAWAYASKAWAYASKAWAYASKAWA
36
Chapter 7 Chapter 7
Harmonics, Noise & Surge VoltageHarmonics, Noise & Surge Voltage
19
YASKAWAYASKAWAYASKAWAYASKAWA
37
Noise Harmonics
Frequency Band High frequency
(10 kHz or more) 40th to 50th harmonics (up to several kHz)
Main Source Inverter section Converter section
Transmission Path ・・・・Electric wire (conduction)
・・・・Space (radiation)
・・・・Induction (electrostatic,
electromagnetic
Electric wire
Influence Distance, wiring distance Line impedance
Generating Amount ・・・・Voltage variation ratio
・・・・Switching frequency
Current capacity
Failure ・・・・Sensor malfunction
・・・・Radio noise
・・・・Overheat of capacitor for P.F improvement
・・・・Overheat of generator
Corrective Actions ・・・・Change the wiring route.
・・・・Install a noise filter.
・・・・Install INV. in a screened
box
・・・・Install a reactor.
・・・・12-phase rectification
・・・・Sinusoidal wave power regeneration
converter 主な
主な主な主な
Difference between Harmonics and NoiseDifference between Harmonics and Noise
YASKAWAYASKAWAYASKAWAYASKAWA
38
Co
mm
erc
ial
Po
wer
+
Sm
oo
thin
g
Cap
acit
or
Converter Section
Motor
Bridge Rectifier
MMMM
Harmonics Current Generated by Rectifier Circuit
Noise Generated by High-speed Switching
Harmonics and Noise SourcesHarmonics and Noise Sources
Inverter Section
20
YASKAWAYASKAWAYASKAWAYASKAWA
39
Without Filter →
(a) Test Circuit
[Inverter Output] [Motor Input]
(b) Result of Waveform Observation
(5µs/div, 250/div)
Expanded Diagram
With Filter →
Inverter Output Motor Input
IM
Surge Voltage Suppression by FilterSurge Voltage Suppression by Filter
Filter
Expanded Diagram
PWM Inverter
YASKAWAYASKAWAYASKAWAYASKAWA
40
The solution to 400V class inverter drive problems
1. Low surge voltageSuppresses motor surge voltage, eliminating theneed for the motor surge voltage protection.
2. Low electrical noise (Radiated, Conductive)
3. Low acoustic noise
4. Electrolytic corrosion of motor bearings due to shaft voltage
Features of 3Features of 3--level control level control
21
YASKAWAYASKAWAYASKAWAYASKAWA
41
(b) Example of Shaft Voltage Measurement (between Shafts) (c) Shaft Voltage Waveform
(Hz)
Commercial Power Supply Drives
Actual Measurement of Shaft VoltageActual Measurement of Shaft Voltage
Commercial Power
Drives
(Direct-coupling Side)(Opposite to Direct-
coupling Side)
Sh
aft
Vo
lta
ge
(mV
)
Inverter
Inverter Drives
V: Measuring DeviceR: Non-inductive Resistor (1kΩ)
(Stator)
(Rotor)
(a) Example of Shaft Voltage Measuring Circuit
Inverter: PWMMotor: 3.7 kW, 200 V, 4 polesV/f characteristics: Constant torque
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 42
Improving output voltage
Reducing
component losses
Speed
sensor
Drive section
AC power supply
Processing
section
New Inverter Technology
⑤⑤⑤⑤ New power conversion method
How to improve inverter efficiency
①①①① Reducing loss
②②②② Improving PWM control
③③③③ Improving inverter output voltage waveform
④④④④ Improving the drive’s input power factor
Improving input power
factor
Improving PWM control
New power conversion
method
The diagram below illustrates five steps that can be taken to improve motor control and inverter drive
performance: ①①①① Reducing the loss generated in the inverter unit; ②②②② and ③③③③ concern circuitry and the
control method used for high-efficiency performance; ④④④④ covers improvements to drive’s power supply side;
⑤⑤⑤⑤ involves a new approach to power conversion.
Motor
22
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 43
8.6%
60.8%
5.3%
0.2%
0.8%
1.0%8.1%
15.3%
Rectifier diode IGBTs Smoothing capacitors MCMain circuit fuse
Discharge resistance
Control power supply
Others
Reducing Inverter Component Loss
12.4%
43.6%7.6%
0.2%
1.1%
1.5%
11.6%
22.0%
BEFORE NOW
Improving the switching characteristics of the IGBT device has reduced the power loss to the
half of what it was 10 years ago. In addition to reducing power consumption for the control
power supply and control circuit, inverter efficiency is 9o% better than in the past.
One way to improve inverter efficiency is to reduce loss from various components. The circle graphs
below show the amount of loss generated from each component in the drive. About 10 years ago, the
loss generated from IGBT (Insulated Gate Bipolar Transistor) switching in the main circuit exceeded
60% of all loss. Recent improvements in switching technology have now minimized loss from IGBTs
down to 40%.
Rectifier diode IGBTs Smoothing capacitor MCMain circuit fuse
Discharge resistance
Control power supply
Others
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 44
Improvements with PWM Control
High-efficiency PWM control: 2-phase modulation
(b) 3-phase modulation
Output voltage Output current
(a) 2-phase modulation
Output voltageOutput current
Switching loss is not generated in the 2-phase
modulation method since IGBT switching does not
occur in this area.
Employing 2-phase modulation can reduce
IBGT switching loss by approximately 30%.
The high carrier frequency used in PWM (pulse width modulation) increases the amount of IGBT
switching loss. Yaskawa has created a 2-phase modulation method to minimize this switching loss.
As shown below, the 2-phase modulation method stops switching when current is large. This way, one
of the 3 phases is always in the stopped status. Using this 2-phase PWM control method can reduce
the switching loss by approx. 30%.
23
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 45
Improving the Output Voltage Waveform
Common Problems
① Motor insulation damaged by surge voltage
② Peripheral devices malfunctioning due to noise
generated by the inverter
③ Earth leakage breaker malfunctioning due to leakage
current
④ Motor bearings corroded by shaft current
Solved with Solved with
33--level control! level control!
Although high carrier PWM control makes the output current waveform very close to sinusoidal, the
actual voltage waveform created is still a group of square waves. The surge voltage generated at rising
and falling edges of this square waves causes trouble. A surge suppression filter is normally attached
between the inverter and the motor in order to prevent the motor insulation from being damaged by
surge voltage. This filter is called RLC filter, and is is composed of a resistor, reactor, and a capacitor.
A large filter is not needed if the inverter and motor are close together. If they are far apart, however, a
large capacity filter is needed. For example, with the motor capacity of 75 kW, the filter consumed
power is 0.3 kW, 1.4 kW and 12.6 kW when the wiring length is 30 m, 100 m and 300 m, respectively.
As the distance gets longer, the required capacity is sharply increased. Additionally, the size of the
filter also becomes larger, it will be necessary to examine where to install. To omit this filter, 3-level
control inverters have been devised. Using these inverters can solve the problem of ①①①①. Furthermore,
this control method can reduce the remaining 3 failures (②②②②, ③③③③ and ④④④④) at the same time.
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 46
What Is 3-Level Control?
Varispeed G7: 3-level controlConventional Drives: 2-level control
VPN /2
++++
0000
----
VPN /2
VPN
++++
----
VPN : DC bus bar voltage = AC input voltage ×××× √2222
VPN
U V W
PPPP
NNNN
VPN
U V W
PPPP
NNNN
0000
Volt
ag
econ
trol
by
12
tran
sist
ors
Volt
ag
e co
ntr
ol
by 6
tra
nsi
stors
Circuit
configu-
ration
Phase
voltage
Line
voltage Volt
ag
e fl
uct
uati
on
re
du
ced
to h
alf
of
con
ven
tion
al
mod
el
A
B
C
D
E
F
VPN
24
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 47
(a) Circuit configuration during for one phase (b) Switching patterns
A B C D Potential
ON ON OFF OFF Level P
OFF OFF ON ON Level N
OFF ON ON OFF Level O
Principle of 3-Level Control MethodIn conventional 2-level control, 2 transistors are used for each phase, making a total of 6 transistors for 3
phases to switch DC bus bar voltage VPN. Phase voltage turns ON and OFF depending on the size of VPN,
and changes according to it. In the 3-level control, 4 transistors are used per phase, for a total of 12
transistors for 3 phases. The illustrations below shows how transistors switching works during one phase.
In this figure, voltage P appears in phase U when transistors A and B turn ON. Then O appears in phase U
through diodes E and F when transistors B and C turn ON. N appears when transistors C and D turn ON.
It means that phase U can take three states: P, N, and O. This is how 3-level control was named. While
voltage fluctuates between P and N in 2-level control, it fluctuates between P & O, and between O & N in 3-
level control. Therefore, phase voltage turns ON and OFF depending on the size of VPN/2, which is half of
VPN during 2-level control. This creates an output waveform very close to a perfect sine wave. Surge voltage
is cut in half when voltage fluctuation becomes half, which means that noise and leakage current is also cut
in half, resulting in reduction of shaft current.
A
B
C
D
VP N
MotorVP N
2
VPN
2
VPN : DC bus bar voltage
P
N
O
PVPN
2O
N
E
F
(phase U appears below)
Phase U
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 48
Comparison of Surge Voltage Waveform in 3-level Control Method
Suppression effect
VPN
770 V peak
0
VPN
1200 V peak
0
(a) 2-level control surge voltage waveform (b) 3-level control surge voltage waveform
The following figures show the output voltage waveforms of 400 V class inverter 2-level control and
3-level control, respectively. In the 2-level control method, the peak value of the waveform is almost
1200 V, while it is limited to 770 V in the 3-level control method. Since this value is lower than the
insulation voltage of the 400 V class motor, the existing motors can be driven by an inverter without
using surge suppression filters.
25
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 49
Comparison of Radiation Noise in 3-level Control Method
20
030
40
60
80
100
Lev
el
dBµ
V/m
50 70 100 200 300
Frequency (MHz)
Max. 20 dB down20
0
40
60
80
100
Lev
el
dBµ
V/m
30 50 70 100 200 300
Frequency (MHz)
These graphs show noise levels. In the frequency bandwidth between 30 MHz and 300 MHz, the
noise level is limited to 20 dB at the maximum. This reduces the effects on surrounding peripheral
devices caused by noise.
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 50
Comparison of Leakage Current in 3-level Control Method
11111111AAAA
5555AAAA
(a) Leakage current in 2-level control method (b) Leakage current in 3-level control method
The graphs below compare leakage current in 2-level and 3-level control. Leakage current in the 3-level control method is almost the half of that in the 2-level control method. Less leakage current means fewer faults with the leakage breaker.
26
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 51
No Surge Suppression Filter Needed Because of Surge Reduction
Configuration of surge suppression filter
Reactor
AC
pow
er
sup
ply
Surge suppression filter
Wiring distance
Heat energyHeat energy
Not needed!
Motor
InverterVarispeed G7
Capacitors
Resistors
Cf: Capacitor size is determined by cable type or wiring length
E: DC bus bar voltage (600 V at 440 Vac input)
fi: Inverter carrier frequency
××××2: Multiplied by 2 for charging and discharging of capacitor
Consumed power WR of the resistor is
calculated as follows:
WR = Cf・・・・E2・・・・fi××××2
3-level control contributes to energy saving because there is no need for a surge
suppression filter that would otherwise consume power.
YASKAWAYASKAWAYASKAWAYASKAWA
No. U030701-Page 52
0
10
20
30
40
50
60
70
80
90
Operating conditions: Motor specifications: 440 V, 75 kW
When 100sq polyethylene sheath cable is used
Consumed power WR of
resistor for wiring distance
0 200 400 600 800 1000
Wiring length (m)
Consu
med
pow
er o
f re
sist
or
WR
(kW
)
15
Long distance drastically Long distance drastically
increases power consumptionincreases power consumption
Long distance drastically Long distance drastically
increases power consumptionincreases power consumption
How wiring length affects power consumption of a surge suppression filter resistor
Energy saved because no filter is used
Power Consumption of Surge
Suppression Filter
27
YASKAWAYASKAWAYASKAWAYASKAWA
Maintenance and Inspection Maintenance and Inspection
YASKAWAYASKAWAYASKAWAYASKAWA
Failure PatternsFailure Patterns
Initial Failure Period
Accidental Failure Period Wear-out Failure Period
t
Specified Failure Ratio
Service Lifetime
Failu
re
Ratio
λ (
t)
0ta tb
28
YASKAWAYASKAWAYASKAWAYASKAWA
55
Place Item Checking ItemSchedule
Daily Periodical1-yr 2-yr
WholePeripheral environment Ambient temperature, humidity, dust, hazardous gases, oil mist, etc.
Whole unit No excessive vibration or noise. Power supply voltage Check that main circuit voltage or control voltage is normal.
Main Circuit
Whole① Megger check between main circuit terminal and ground terminal② No loose connections③ No traces of overheating in components④ Clean.
Connected conductor, Power supply
① No distortion in conductor② No breakage or deterioration (cracks, discoloration, etc.) in cables
Transformer, Reactor No odor, excessive beats or noise Terminal stand No damages
Smoothing capacitor① No liquid leakage② No projection (safety valve) or bulge③ Measure electrostatic capacity and insulation resistance.
Relay, Contactor① No chattering at operations② Timer operation time③ No roughness on contacts
Resistor ① No crack in resistor insulating material② No disconnection
Control Circuit, Protective
Circuit
Operation check① Balance of output voltage between each phase by inverter single-unit operation② No failure in protective or display circuit by sequence protection test
Component check
Whole ① No odor or discoloration② No excessive corrosion
Capacitor No traces of liquid leakage or deformation
Cooling System Cooling fan
① No excessive vibration or noise② No loose connections③ Clean the air filter.
Display Display ① All lamps lights correctly.② Clean.
Meter Indicated values are correct.
(From JEMA Information)Daily Inspection and Periodical InspectionDaily Inspection and Periodical Inspection
YASKAWAYASKAWAYASKAWAYASKAWA
56
NameNameNameNameStandard Standard Standard Standard
Replacement Replacement Replacement Replacement PeriodPeriodPeriodPeriod
MethodMethodMethodMethod
Cooling fanCooling fanCooling fanCooling fan 2 to 3 years2 to 3 years2 to 3 years2 to 3 years Replace.Replace.Replace.Replace.
Smoothing capacitorSmoothing capacitorSmoothing capacitorSmoothing capacitor 5 years5 years5 years5 years Replace on investigation.Replace on investigation.Replace on investigation.Replace on investigation.
Breaker, relayBreaker, relayBreaker, relayBreaker, relay ---- Determine what to do on Determine what to do on Determine what to do on Determine what to do on investigation.investigation.investigation.investigation.
TimerTimerTimerTimer ---- Determine after checking the Determine after checking the Determine after checking the Determine after checking the operation times.operation times.operation times.operation times.
FuseFuseFuseFuse 10 years10 years10 years10 years Replace.Replace.Replace.Replace.
Aluminum capacitor Aluminum capacitor Aluminum capacitor Aluminum capacitor on PC boardon PC boardon PC boardon PC board 5 years5 years5 years5 years Replace on investigation.Replace on investigation.Replace on investigation.Replace on investigation.
Note : Operational Conditions
・・・・ Ambient temperature : Annually 30 in average
・・・・ Load ratio : 80% or less
・・・・ Operation ratio : 12 hours or less per day
Component Replacement Guidelines Component Replacement Guidelines
29
YASKAWAYASKAWAYASKAWAYASKAWA
57
* Clamp meters available on markets have differences in characteristics between manufacturers.
Especially, measured values tend to be extremely small at low frequency.
Precautions on MeasurementPrecautions on Measurement
Inverter Approximate Waveform Element Meter
Input Voltage All effective
values
Moving iron type
voltmeter
Current All effective
values
Moving iron type
ammeter
Output Voltage Fundamental
wave effective
value
Rectifier type
voltmeter (Model
YEW2017, etc.)
Current All effective
values
Moving iron type
ammeter *
YASKAWAYASKAWAYASKAWAYASKAWA
58
Purpose and Types of Protective FunctionsPurpose and Types of Protective Functions
Inverter Protection
Pro
tecti
on
Warn
ing
Motor Overheat Protection
Others
Operation status is not proper.
Prediction of protective
function operation
Overcurrent OC
Overvoltage OV
Grounding GF
Main circuit undervoltage UV1
Cooling fin overheat OH
Braking transistor error rr
Inverter overload OL2
Motor overload OL1
Overtorque detection OL3/OL4 lit
CPU error CPF
Overtorque detection OL3/OL4 (blinking)
Undertorque detection UL3/UL4 (blinking)
Inverter overheat prediction OH2
Radiation fin overheat prediction OH
30
YASKAWAYASKAWAYASKAWAYASKAWA
59
Main circuit overvoltage : OVApprox. 410 V(Approx. 820 V)
Approx. 380 V(Approx. 760 V)
Voltage at stall prevention during deceleration
Approx. 365 V(Approx. 730 V)
Voltage at braking
Approx. 190 V(Approx. 380 V)
Main circuit
undervoltage : UV1 ※※※※
DC Voltage
Voltage in the parentheses shows 400-V series.
Inverter output overcurrent : OC
Overload anti-time-interval characteristics
Stall prevention level during running ※※※※
Inverter rated output current
Current
200%
160%
100%
Stall prevention level during acceleration ※※※※
150%
Level at Which Protective Function OperatesLevel at Which Protective Function Operates
※※※※ Can be changed.
YASKAWAYASKAWAYASKAWAYASKAWA
NOTE :