xi#zhang,#chi#kong#wong# university#of#macau · xi#zhang,#chi#kong#wong# university#of#macau. ieee...
TRANSCRIPT
IEEE 2011 Electrical Power and Energy Conference
Xi Zhang, Chi Kong Wong University of Macau
IEEE 2011 Electrical Power and Energy Conference
Contents �
Introduc-on
Index Formula?on & Comparison
Simula?on Results and Discussion
Conclusion �
IEEE 2011 Electrical Power and Energy Conference
Introduc-on� Voltage stability problem is one of the major concerns in power system
Damage of voltage collapse several blackouts (Japan, USA, France)
2003 North-‐East USA blackout :
• leading to 80% load loss in New York • affec?ng 55 million people in 8 states
• causing great economic losses
IEEE 2011 Electrical Power and Energy Conference
Introduc-on� Voltage stability analysis (sta?c)
Transfer limit �
Collapse point�
Stable: high V & low I�
Unstable: low V & high I�
Sta-c view point �
voltage stability index (VSI) �
Transfer limit �
Voltage collapse �
Sta?c load �
P-V curves�
IEEE 2011 Electrical Power and Energy Conference
P
Introduc-on� Voltage stability analysis (dynamic)
Network and motor P-V curve�
Dynamic problem by nature �
Example: induction motor �
disturbance� s� Q� V�
Pe s � Another stable point �
Pe s � Motor stalling�Transfer limit�
Voltage collapse�
Transfer limit �
Voltage collapse�
Voltage collapse occurs
before transfer limit�
IEEE 2011 Electrical Power and Energy Conference
Introduc-on� Though transfer limit is not the collapse point, it is s?ll cri?cal and is iden?fied by VSI.
Voltage stability index (VSI) Derived under sta?c load Load increase: P & Q in propor?on
Objec?ve Sta?c VSIs are compared under dynamic load �
Sta?c load: constant Z, I, P�
Dynamic load: restore power �
P & Q in propor?on �
Q sharply, P — �
IEEE 2011 Electrical Power and Energy Conference
Contents �
Introduc?on
Index Formula-on & Comparison
Simula?on Results and Discussion
Conclusion �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Four line VSIs
Line index�
FVSI� Lmn � LVSI� LQP�
Power flow �Sta?c load �Indicate
transfer limit of a line�
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Fast Voltage Stability Index (FVSI)
Two bus system�
Sending end �
Receiving end �
quadra?c equa?on of �
discriminant larger than 0�
FVSI<1� Transfer limit �1 �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Line Stability Index (Lmn)
Two bus system�
Sending end �
Receiving end �
quadra?c equa?on of �
discriminant larger than 0�
Lmn<1�Transfer
limit �1 �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� On Line Stability Index (LVSI)
Two bus system�
Sending end �
Receiving end �
quadra?c equa?on of �
discriminant larger than 0�
LVSI<1� Transfer limit �1 �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Line Stability Factor (LQP)
Two bus system�
Sending end �
Receiving end �
quadra?c equa?on of �
discriminant larger than 0�
LQP<1� Transfer limit �1 �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Comparison of FVSI, Lmn, LVSI and LQP
FVSI�
Lmn �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Comparison of FVSI, Lmn, LVSI and LQP
Index �FVSI�
(simplified) �FVSI� Lmn � LVSI� LQP�
Formulation �
Rela?ve variables �
Q V � Z X �
Q V δ �Z X R �
Q V δ �X θ �
P V δ �R θ �
P Q V �X �
Q � P � Q & P �
Sta?c load: constant Z, I, P�
Dynamic load: restore power �
P & Q in propor?on �
Q sharply, P — �
LQP best for dynamic loads �
IEEE 2011 Electrical Power and Energy Conference
Index Formula-on & Comparison� Comparison of FVSI, Lmn, LVSI and LQP
Index � Formula?on � Assump?ons�
FVSI�(simplified) �
δ=0�
FVSI� no �
Lmn � no �
LVSI� no �
LQP� R/X<<1�
Critical value: 1 � transfer limit�
always satisfied �
large for heavy load lines �
When θ-δ 90°, cos(θ-δ) 0, in the denominator �
IEEE 2011 Electrical Power and Energy Conference
Contents �
Introduc?on
Index Formula?on & Comparison
Simula-on Results and Discussion
Conclusion �
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Power system for case study�
IEEE 39 bus system�
39 buses 34 lines�
10 generators 19 load buses �
Dynamic load: induc?on motor
motor stalling voltage collapse
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 1 (motor stalls before transfer limit) �
IEEE 39 bus system�
sta?c load increase at all
buses
VSIs reach 1.0 first on line 2423 aler 10s �
Motor at bus 24 stalls first
6.61s�
induc?on motor: 40%
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 1 (motor stalls before transfer limit) �
Motor stalling (voltage collapse) �
VSIs reach 1.0
Transfer limit�
Before
transfer limit�
VSIs on line 2423 & slip of bus 24 �
FVSI Lmn �
LQP is larger than others �
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 1 (motor stalls before transfer limit) �
Motor stalling (voltage collapse) �
P injected to 24�
Q injected to 24 stop �
V 24 �
V angle difference as P�
Close to collapse limit: �
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 1 (motor stalls before transfer limit) �
LVSI for a healthy line 1617�
LVSI reaches 1.0 at 3.2s �
When θ-δ 90°, cos(θ-δ) 0, in the denominator �
Voltage collapse at 6.6s �
Mis-‐iden?fy�
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 2 (motor stalls aler transfer limit) �
IEEE 39 bus system�
sta?c load increase at bus 28
VSIs reach 1.0 first on line 2829
before 101s �
Motor at bus 28 stalls first 101.06s�
induc?on motor: 40%
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 2 (motor stalls aler transfer limit) �
VSIs on line 2829 & slip of bus 28 �
ABer
transfer limit�
FVSI Lmn �
Motor stalling (voltage collapse) �
LQP reaches 1 earlier than others �
VSIs reach 1.0
Transfer limit�
Simplified FVSI small δ is large�
IEEE 2011 Electrical Power and Energy Conference
Simula-on Results and Discussion� Case 2 (motor stalls aler transfer limit) �
Motor stalling (voltage collapse) �
P injected to 28�
Q injected to 28 stop �
V 28 �
δ when P fail to restore �
Close to collapse limit: �
IEEE 2011 Electrical Power and Energy Conference
Contents �
Introduc?on
Index Formula?on & Comparison
Simula?on Results and Discussion
Conclusion �
IEEE 2011 Electrical Power and Energy Conference
Conclusion � Comparison of 4 line VSIs FVSI, Lmn, LVSI and LQP under dynamic load is discussed FVSI and Lmn are equivalent simplified FVSI & LVSI have limita?ons LQP perform beoer under dynamic load
• FVSI and Lmn directly involve Q • LVSI directly involve P • LQP directly involves Q & P
Useful to choose Proper index for dynamic voltage collapse predic?on �
IEEE 2011 Electrical Power and Energy Conference