    Manual 26260

    Governing Fundamentalsand Power Management

    This manual replaces manuals 01740 and 25195.

    Reference Manual

  • 8/6/2019 WW Governing Fundamentals

    2/76

    Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward isbelieved to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expresslyundertaken.

    Woodward 2004All Rights Reserved

  • 8/6/2019 WW Governing Fundamentals

    3/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward i

    Contents

    CHAPTER 1.INTRODUCTION TO GOVERNING ................................................ 1Introduction ............................................................................................................. 1Other References ................................................................................................... 1What is a Governor? ............................................................................................... 1Governor Components ........................................................................................... 3Development of the Modern Governor System ...................................................... 4CHAPTER 2.HYDRO-MECHANICAL GOVERNORS........................................... 5Basic Hydro-mechanical Governor Components ................................................... 5The Speeder Spring ............................................................................................... 5Thrust Bearing ........................................................................................................ 6Flyweights ............................................................................................................... 6Pilot Valve Plunger and Bushing ............................................................................ 8Oil Pumps ............................................................................................................... 9Direction of Rotation ............................................................................................. 10The Servo (Power) Piston .................................................................................... 11CHAPTER 3.DROOP .................................................................................. 13Introduction ........................................................................................................... 13Why Is Droop Necessary? .................................................................................... 13Speed Droop Operation ........................................................................................ 14Uses Of Droop ...................................................................................................... 15Isolated Systems .................................................................................................. 18CHAPTER 4.LINKAGE................................................................................ 22General ................................................................................................................. 22Governor Travel .................................................................................................... 23Linear Linkage Arrangements .............................................................................. 24Non-Linear Usage ................................................................................................ 25CHAPTER 5.MAGNETIC PICKUPS............................................................... 26Introduction ........................................................................................................... 26CHAPTER 6.LOAD SENSING,LOAD SHARING,BASE LOADING ................... 30Load Sensing ........................................................................................................ 30Load Gain Adjust Potentiometer .......................................................................... 30Balanced Load Bridge .......................................................................................... 31Power Output Sensor ........................................................................................... 34Isochronous Base Load ........................................................................................ 34CHAPTER 7.SYNCHRONIZATION ................................................................ 39What Is Synchronization? ..................................................................................... 39Why Is Synchronization Important? ...................................................................... 42How Is Synchronization Accomplished? .............................................................. 42Prediction of the Worst Case Phase Angle Difference () at the Instant ofBreaker Closure .................................................................................................... 44

  • 8/6/2019 WW Governing Fundamentals

    4/76

    Governing Fundamentals and Power Management Manual 26260

    ii Woodward

    Contents

    CHAPTER 8.MANAGING POWER FOR THE DESIRED RESULT ....................... 46Peaking or Peak Load Control ..............................................................................46Cogeneration ........................................................................................................51Single Engine AGLCBase Load Control .............................................................51Isolated Bus Isochronous Load Sharing System ..................................................57Multiple Engine AGLCBase Load Control ..........................................................60Automatic Paralleling System (2301A) to a Utility Using a Process-Import/ExportControl ..................................................................................................................63Automatic Paralleling System (2301A) to a Utility Using an Automatic PowerTransfer And Load (APTL) Control .......................................................................66

    Illustrations and Tables

    Figure 1-1. The Driver is the Governor ...................................................................2Figure 1-2. Speed Balance .....................................................................................2Figure 2-1. Speeder Spring ....................................................................................5Figure 2-2. Speeder Spring Deflection ...................................................................6Figure 2-3. Hydraulic Governor Ballhead ............................................................... 6Figure 2-4. Flyweight Action ...................................................................................7Figure 2-5. Flyweights to Minimize Friction ............................................................7Figure 2-6. Pilot Valve Operation Shown On Speed............................................8Figure 2-7. Oil Pumps .............................................................................................9Figure 2-8. Accumulator and Governor Relief Valve ............................................10Figure 2-9. Pump Rotation ...................................................................................10Figure 2-10. Spring Loaded Servo Piston ............................................................11Figure 2-11. Differential Power Piston ..................................................................12Figure 3-1. Response Curves of Governor without Droop or Compensation ...... 13Figure 3-2. Droop Feedback .................................................................................14Figure 3-3. Compensated Governor Schematic ...................................................15Figure 3-4. Comparison of 3% Droop Speed Settings for 50% and 100% Load . 16Figure 3-5. 3% and 5% Droop Curves .................................................................16Figure 3-6. Droop Mode .......................................................................................17Figure 3-7. Swing Machine ...................................................................................18Figure 3-8. Droop Units ........................................................................................19Figure 3-9. Base Load with 5% Droop .................................................................20Figure 3-10. Schematic of Droop Governor .........................................................21Figure 4-1. Linear Fuel Control .............................................................................22Figure 4-2. Non-Linear Fuel Control .....................................................................23Figure 4-3. Correct Use of Governor Travel .........................................................23Figure 4-4. Nonlinear Carburetor Linkage ............................................................25Figure 5-1. Magnetic Pickup .................................................................................26Figure 5-2. Low Reluctance Gear Position ...........................................................27Figure 5-3. High Reluctance Gear Position ..........................................................27Figure 5-4. Magnetic Pickup and Gear Dimensions .............................................28Figure 5-5. Generated Waveforms .......................................................................29Figure 6-1. Generator Load Sensor......................................................................30Figure 6-2. Balanced Load Bridge ........................................................................31

  • 8/6/2019 WW Governing Fundamentals

    5/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward iii

    Illustrations and Tables

    Figure 6-3. Basic Load Sensing Block Diagram ................................................... 32Figure 6-4. Load Sharing Diagram ....................................................................... 36Figure 6-5. Load Sharing Block Diagram ............................................................. 37Figure 6-6. Multiple Load Sharing Block Diagram ................................................ 38Figure 7-1. Number of Phases Must Match Number Of Phases .......................... 39Figure 7-2. Phase Rotation Must be the Same Rotation Of Phases .................... 40Figure 7-3. Voltage Difference (Generator to Generator) .................................... 40Figure 7-4. Voltage Difference (Generator to Bus) .............................................. 40Figure 7-5. Frequency Difference ......................................................................... 41Figure 7-6. Phase Difference................................................................................ 41Figure 7-7. Checking Phase Match ...................................................................... 43Figure 7-8. Checking Phase Rotation and Match ................................................ 43Figure 7-9. Phase Angle Relationship .................................................................. 45Figure 8-1. "Peaking" or Peak Load Control ........................................................ 47Figure 8-2. Base Loading ..................................................................................... 48Figure 8-3. Peak Shaving ..................................................................................... 48Figure 8-4. Import Power ...................................................................................... 49Figure 8-5. Import Power (Constant Level) .......................................................... 49Figure 8-6. Export Power ...................................................................................... 49Figure 8-7. Export Power (Constant Level) .......................................................... 50Figure 8-8. Import/Export Control ......................................................................... 50Figure 8-9. Zero Import/Export ............................................................................. 50Figure 8-10. Synchronizing to Utility or Plant Bus ................................................ 53Figure 8-11. Synchronizing Gen Set to Plant Bus or to Utility .............................. 54Figure 8-12. Single Engine AGLC Base Load ...................................................... 55Figure 8-13. Connections for Single Engine AGLC Base Load System .............. 56Figure 8-14. Using AGLC for Soft Load, Soft Unload, and Base Load to an

    Isolated Bus for Isochronous Load Sharing .................................... 58Figure 8-15. Connections Used with AGLC for Soft Loading, Unloading, and

    Base Loading with Isochronous Load Sharing Against an IsolatedBus ................................................................................................... 59

    Figure 8-16. Using the AGLC to Base Load Multiple Engines to a Utility ............ 61Figure 8-17. Connecting an AGLC to Base Load Multiple Engines to a Utility .... 62Figure 8-18. Using Process-Import/Export Control to Automatically Parallel ....... 64Figure 8-19. Connecting Process-Import/Export Control to Paralleling System .. 65Figure 8-20. Using APTL in Automatic Paralleling System .................................. 67Figure 8-21. Connecting APTL in Automatic Paralleling System ......................... 68

  • 8/6/2019 WW Governing Fundamentals

    6/76

    Governing Fundamentals and Power Management Manual 26260

    iv Woodward

  • 8/6/2019 WW Governing Fundamentals

    7/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 1

    Chapter 1.Introduction to Governing

    Introduction

    This manual combines former Woodward manuals 25195 (GoverningFundamentals) and 01740 (Power Management). Chapters 15 cover basicgoverning, and chapters 69 cover the principles of power management.

    Other References

    Other useful references you might find useful can be found on our website(www.woodward.com):

    Pub. No. Title25075A Commercial Preservation Packaging for Storage of Mechanical-Hydraulic

    Controls

    25070D Electronic Control Installation Guide25014C Gas Engine Governing25179C Glossary of Control Names50516 Governor Linkage for Butterfly Throttle Valves82715H Guide for Handling and Protection: Electronic Controls, PCBs, Modules82510M Magnetic Pickups and Proximity Switches for Electronic Controls25071J Oils for Hydraulic Controls83402 PID Control83408 PLCs for Turbine Control Systems50511A Prediction of Phase Angle at Breaker Closure50500D Simplified Unloading Scheme for Electric Governors01302 Speed Droop & Power Generation51214 Work versus Torque

    In addition, all product specifications, brochures, catalogs, and application notes

    (as well as many technical manuals) can be found on the website.

    What is a Governor?

    All power sources must be controlled in order to convert the power to usefulwork. The essential device which controls the speed or power output of anengine, turbine, or other source of power is called a governor. For simplicity,well call the source of power a prime mover.

    A governor senses the speed (or load) of a prime mover and controls the fuel (orsteam) to the prime mover to maintain its speed (or load) at a desired level. Insome cases the governor controls other factors that determine the speed or load

    of the prime mover. In all cases, a governor ends up controlling the energysource to a prime mover to control its power so it can be used for aspecific purpose.

  • 8/6/2019 WW Governing Fundamentals

    8/76

    Governing Fundamentals and Power Management Manual 26260

    2 Woodward

    ExampleIf youve ever driven a car, youve functioned as a governor when youcontrol the cars speed under varying driving conditions.

    Figure 1-1. The Driver is the Governor

    The driver (governor) adjusts the fuel to maintain a desired speed. If the speedlimit is 100 (this is the desired speed), you check the speedometer (the carsactual speed). If actual speed and desired speed are the same, you hold thethrottle steady. If not equal, you increase or decrease throttle position to makethe desired speed and the actual speed the same (see Figure 1-2).

    As the car starts uphill, the load increases and actual speed decreases. Thedriver notes that actual speed is less than desired speed and moves the throttleto increase speed back to the desired speed at the increased load.

    As the car goes downhill, the load decreases and actual speed increases. Thedriver notes that actual speed is greater than desired speed and decrease thethrottle to return to the desired speed with the decreased load.

    Figure 1-2. Speed Balance

  • 8/6/2019 WW Governing Fundamentals

    9/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 3

    If your car has a cruise control, the cruise control is a simple governor.

    Governor Components

    All governors have five fundamental components:

    A way to set the desired speed. (The driver sets the desired speedmentally.)

    A way to sense actual speed. (The driver refers to the speedometer).

    A way to compare the actual speed to the desired speed. (The drivercompares the two items mentally.)

    A way for the governor to change the fuel to the prime mover (moving therack or fuel valve). (The driver moves the throttle.)

    A way to stabilize the engine after a fuel change has been made.

    In the example, when the car went up a hill, the driver saw the actual speeddecrease and moved the throttle to increase the fuel. You will need to increasethe fuel an amount to cause the speed to increase. This will give the engineenough power to make the car return to the desired speed with a bigger load. Asyou see that the actual speed is about to reach the desired speed, you reducethe extra fuel to the exact amount needed to match (balance) the desired speedwith the actual speed. The governor does the same thing, using feedback. Thisfeedback closes the loopin the control system which controls the amount of fuelchange, based on the rate the desired speed is being reached. This preventslarge overshoots or undershoots of speed which is known as hunting, andstabilizes the engine. The opposite is true when the car goes down the hill orload is reduced.

    1. Speed SettingSetting the desired speed of a governor is necessary to efficiently controlprime movers. Modern governors have advanced systems of speed settingwhich can compensate for a variety of conditions when determining thedesired speed. Hydro-mechanical governors use what is known as aspeeder spring. The more force applied to this spring, the higher the desired

    speed setting is. Electronic controls use an electronic force (voltage andcurrent) to set speed. The more the force is increased, the more the outputto the fuel increases.

    Speed setting and the effect on sharing loads between engines will bediscussed in other chapters.

    2. Sensing SpeedThe governor must receive a force that is proportional to the speed of aprime mover. In hydro-mechanical governors, it is done by the centrifugalforce of flyweights being rotated from a drive system that is connected to theprime mover, and is directly related to the speed of the prime mover. Inelectronic controls, this force comes from sensing of the frequency of a

    magnetic pickup, alternator, or generator which is directly related to thespeed of the prime mover. The frequency is then changed to an electronicforce that the control can use. In both cases, the faster the engine runs, thestronger the speed sensing force becomes.

  • 8/6/2019 WW Governing Fundamentals

    10/76

    Governing Fundamentals and Power Management Manual 26260

    4 Woodward

    3. Comparing the Actual Speed to the Desired SpeedThe force of the desired speed setting and the force of the actual speedare compared or summed together. Desired speed setting is a force inone direction and actual speed is a force in the opposite direction. Whenthese opposing forces are the same value, their sum will be zero and at thatpoint the governor is controlling actual speed at the point of the desiredspeed setting. If the desired speed setting force is stronger than the actualspeed force, the governor will increase fuel. If the actual speed force is

    stronger than the desired speed setting force, the governor will decreasefuel. As fuel is increased or decreased, these forces will change until theybalance or sum to zero. In hydro-mechanical governors, these forces aresummed at the thrust bearing. In electronic controls, these forces aresummed at what is known as a summing point. Note that other forces canbe applied along with these forces to allow the governor to be stabilized andperform other functions (some of these are covered in later chapters).Remember that all forces applied to the thrust bearing or summing pointmust algebraically sum up to zero for the governor to control fuel at a steadystate.

    4. Ways for the Governor to Change Fuel to the Prime MoverThe hydro-mechanical governor or actuator normally has a rotational or

    linear output shaft that is connected to the prime movers fuel system. Whenthe governor needs to make a fuel correction to maintain speed (or load),the output shaft moves in the proper direction to correct the final fuel setting.For electronic controls, an electrical signal is sent to an actuator whichconverts this electrical signal to a mechanical force to move the fuel settingin the same way the hydro-mechanical governors do. Different types ofgovernors and actuators have different amounts of work output to meet thecontrol needs of various prime movers.

    5. Ways to Stabilize the Prime MoverStabilization is accomplished through a variety of ways, but all of them use afeedback system to apply a force to the thrust bearing or summingpoint. This feedback is normally in the form of either droop orcompensation, or in a combination of both. Droop or compensation isusually related to the amount the output shaft is told to move (Chapter 3describes the essential principle of droopfeedback).

    Note that in many prime mover systems (such as power generation), the speedof the prime mover is fixed. While the governor still controls the prime moversspeed setting mechanism, the end result of changes in the prime movers speedsetting under fixed-speed conditions is that an increase or decrease in the speedsetting causes the prime mover to take on a larger or smaller load.

    Development of the Modern Governor System

    The first modern governors were applied to controlling the speed and load ofwater wheels (which were used to power many of the early factories during theIndustrial Revolution. Early governors also controlled steam turbines. Thedevelopment of gasoline and diesel internal combustion engines required fasterand more complex governors. Electrical power generation created a muchgreater need for more precise governor control of speed and load.

    Hydro-mechanical governors became ever more complex to meet growing needsfor precise control. Since the 1970s, electronic controls have significantlyimproved and expanded the capabilities of governing systems, controlling notonly speed and load, but also electrical loads, exhaust emissions, and manyother parameters.

  • 8/6/2019 WW Governing Fundamentals

    11/76

    Manual 2

    Woodwar

    TNT

    Tdfoseso

    Tb

    TmaovSdussp

    260

    d

    H

    Basic

    e five fundaw lets take

    e key parts

    Speeder S

    Thrust Be

    Flyweights

    Pilot Valve

    Pilot Valve

    Oil Pumps

    Oil Pressu

    Servo (Po

    Compens

    Drive Shaf

    e speeder swn on the sp

    rce is usuallyt by a screwlenoids, dep

    e design or sllhead.

    e speeder saintain a morplied. Thereer the length

    me springssigned to bee the linear-teeder spring

    ydro-

    ydro-m

    ental compcloser look

    f a ballhead

    pring

    ring

    Plunger

    Bushing

    re Regulatio

    er) Piston

    tion

    t

    T

    ring is the peeder springset by the oadjustment,nding on the

    hape of a sp

    ring is genere rigid designare other sha.

    re designednon-linear dpe speeder

    .

    overning F

    Chapechan

    chanical

    nents of a gat how the b

    hydro-mecha

    e Spee

    rt that sets tcauses theerator for thknob, a levspecific gov

    igure 2-1. S

    eeder spring

    ally shaped iso that it wopes of spee

    to be close tpending on t

    spring. The

    undamental

    ter 2.ical G

    Govern

    vernor weresic hydro-m

    nical govern

    er Sprin

    e desired sovernor to indesired or r, an electric

    ernor.

    eeder Sprin

    is critical to t

    n a conical dnt buckle orer springs th

    a linear opehe specific gG type gove

    s and Power

    vernor

    r Comp

    mentioned inchanical gov

    r are:

    g

    eed. Applyicrease fuel.eference spmotor, air pr

    he proper op

    sign. This sflex to the sidat offer a vari

    ration, and sovernor. Mosrnor uses a n

    Manageme

    s

    nents

    Chapter 1.ernor works.

    ng more forchis initial

    eed. It can bssure, or

    ration of the

    ape helpse as force isable force

    me aret governorson-linear

    t

    5

  • 8/6/2019 WW Governing Fundamentals

    12/76

    Governing Fundamentals and Power Management Manual 26260

    6 Woodward

    Thrust Bearing

    The thrust bearing is the part where the force of the speeder spring and the forceof the flyweights sum together. If the speeder spring force and the flyweight forceare equal, there is no load on the thrust bearing.

    Figure 2-2. Speeder Spring Deflection

    A thrust bearing has a race on the top and a race on the bottom with the bearingin between the races. Since the flyweights rotate and the speeder spring doesnot rotate, the thrust bearing is necessary. The pilot-valve plunger moves withthe thrust bearing either directly or through a linkage. The pilot-valve plungerdoes not rotate.

    Flyweights

    There are two flyweights in most ballheads. The flyweights are rotated by a drivefrom the engine that is directly related to the speed of the engine.

    Figure 2-3. Hydraulic Governor Ballhead

  • 8/6/2019 WW Governing Fundamentals

    13/76

    Manual 2

    Woodwar

    Inincethspthgth

    argatruu

    IncothmiFrreo

    260

    d

    Figure 2-3, treases, the fntrifugal force thrust bearieed decreasrust bearing tvernor is run

    e vertical pos

    e tipped in, tvernor will inain the desirnning faster ttil the flyweig

    the most effintact the thrat any moveinimum amou

    iction in goveuction of fric

    tput change.

    e flyweightslyweights mo. This cause

    ng and raises. The flywe

    o lower the pat desired sition, closing

    e engine is rcrease fuel td speed sett

    han the desirhts and engi

    F

    Figure 2

    ient flyweighst bearing oent is conve

    nt of sliding f

    rnors is alsotion reduces

    overning F

    are pivotedve out (tip os the toesthe pilot valvights move iilot valve. Inpeed settingthe port in th

    unning belowincrease sp

    ing. If the flyed speed sete return to t

    igure 2-4. Fly

    -5. Flyweight

    t design, thea line at rig

    rted into a sliriction. Ther

    reduced by tthe deadban

    undamental

    t the lower ct) at the topf the flyweig

    e. The oppos(tip in) and rigure 2-4, this when the

    e pilot-valve

    the desiredeed until the

    eights are titing and thee desired sp

    weight Actio

    to Minimize

    toes of the flt angles to tght rotation oare other de

    e use of lowd between s

    s and Power

    omers. As spue to the incts to increas

    ite effect hapeduce the foe only timeflyweights arushing. If th

    speed settingflyweights anpped out, theovernor will

    eed setting.

    Friction

    weight are oeir plane off the thrust bsigns of flyw

    -friction bearieed change

    Manageme

    eedrease ofe the force opens whence on thehen thestraight up iflyweights

    and thed engineengine is

    decrease fue

    ffset andovement so

    earing with aights.

    ngs. Theand governo

    t

    7

    in

    l

  • 8/6/2019 WW Governing Fundamentals

    14/76

    Governing Fundamentals and Power Management Manual 26260

    8 Woodward

    Pilot Valve Plunger and Bushing

    The pilot-valve plunger is positioned by the force on the thrust bearing. It movesup and down inside the rotating pilot-valve bushing (due to the flyweights sensingspeed changes and tipping in or out). The pilot-valve bushing has high pressureoil coming from the oil pump into the bushing above the control land of the pilot-valve plunger.

    Figure 2-6. Pilot Valve Operation Shown On Speed

    The pilot-valve bushing has ports in it to allow the flow of oil to or from the powercylinder assembly. When the governor and engine are at the desired speedsetting, the pilot-valve-plunger control land is centered over the port in the pilot-valve bushing. This stops oil from flowing to or from the power cylinder assembly.

    If the flyweights tip in, due to a change in speed or load, the pilot-valve plungermoves down and let high-pressure oil into the power-cylinder assembly. This willincrease fuel.

    If the flyweights tip out, due to a change in speed or load, the pilot-valve plungermoves up to let oil drain from the power-cylinder assembly. This will decrease

    fuel.

    Pilot-valve-bushing ports have different sizes and shapes for different types ofgovernors to allow more or less oil flow, depending on the application.

    The pilot-valve bushing rotates and the pilot-valve plunger does not. Thisminimizes static friction (called sticktion) and allows the pilot-valve plunger tomove with very slight speed changes.

  • 8/6/2019 WW Governing Fundamentals

    15/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 9

    Oil Pumps

    Most hydro-mechanical governors and actuators use the governor drive to rotatea hydraulic pump which provides the pressure oil for the system controlled by thepilot valve. Woodward uses two different types of pumps. Most governors use thetwo- or three-gear positive displacement pump. The 3161 and TG governors andsome actuators use an internal gear oil pump.

    Figure 2-7. Oil Pumps

    The constant-displacement pump has one drive gear and one or two idler gearsthat rotate in a gear pocket. As the gears turn, oil is drawn from the oil supply andcarried in the space between the gear teeth and the walls of the gear pocket tothe discharge side of the pump. The oil is forced from the space around the gearteeth as the drive and idler gears are rotated and becomes pressurized.

    The hydraulic circuits connected to the pumps can be designed to allow eitherone direction of rotation or reversible rotation for use on diesel engines withdrives that run in both directions. Check valves are used to provide pump rotationin either direction. Plugs allow pump rotation in only one direction. Internal gearpumps allow rotation in only one direction. The pump must be removed from thegovernor and rotated 180 to change direction of rotation for internal gear pumps.

    The pumps are designed to provide more pressure and flow than needed withinthe governor. The extra flow of oil is returned to sump. Smaller governors use arelief valve. Most larger governors use an accumulator system which provides aspring-compressed reservoir of pressure oil for use during transits whichtemporarily exceed the output of the pump. SG, PSG, and EGB-2 governors userelief valves. A number of hydraulic actuators do not have accumulators.

    The relief valve shown in Figure 2-8 is typical of the valves used in SG, PSG,EGB-2 governors and many hydraulic actuators.

    Internal operating oil pressures are specified for each governor. Typicalpressures are 100 to 500 psi (690 to 3448 kPa). Different types of governorsoperate at different pressures. Check the specifications for your governorspressure. The higher pressures are created to get more output power from theservo controlled by the governor. Higher pressures may require the addition ofspecial heat exchangers to avoid damage to (break down of) the oil being used inthe governor.

  • 8/6/2019 WW Governing Fundamentals

    16/76

    Gove

    10

    Fig

    AccusideaccuWhebypaaccureliefshowgoveraltho

    The athe oiwithorotati

    rning Funda

    ure 2-8. AccR

    ulator functif the pump fiulator pistothe pressurs hole, the eulators thus

    valve to limitn are from thnors). UG angh the functi

    rrangementl pump permiut any changn does not a

    mentals an

    mulator andlief Valve

    on is shown irst fills the vas up againstincreases e

    xcess oil fronot only promaximum pr

    power cased 3161 goveon is similar.

    Dire

    f the four chts the governes being madffect the oil p

    Power Man

    Governor

    n Figure 2-8.rious oil pasthe downwarnough to mo

    the governide a reservssure in thetype of govenors use diff

    ction of

    ck valves oor drive shafe in or to theressure syst

    agement

    Figure

    Pressurizedages and thd force of the the pistonr pump returir for pressuhydraulic cirrnor (PG anderent styles o

    otation

    the suctionto be rotategovernor. Tm or govern

    2-9. Pump R

    oil on the disn forces theaccumulato

    up to uncovens to sump.e oil, but alsuit. The acclarger EGBf accumulato

    and dischargin either dir

    e direction oor operation.

    Manual

    Woo

    otation

    charge

    r springs.r theheact as a

    mulators

    rs,

    e sides ofection,f pump

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    17/76

    Manual 2

    Woodwar

    SreoloTro

    Ifroesh

    TpT

    STp

    Tfuvaplpfrpi

    260

    d

    me governorplace the twoe direction oation of the

    e internal geation in an in

    he plugs or iation, the gogine. This caown looking

    e governor pwer piston, a

    o types of p

    A spring l

    position.return sprifrom the p

    A Differendirections.

    ring-Loa

    e governor pwer piston, a

    e return spriel direction.lve plunger inger is abovwer piston em the goverton up, agai

    models areclosed checly. To changlugs must b

    ar pump rotaternal gear p

    ternal gearvernor will non also causeown on the

    The

    ilot valve plucting through

    wer pistons

    aded system

    hen pressurng (either puiston) causes

    ial Power/Se

    ed Power

    ilot valve plucting through

    Figure

    g continuallowever, theraised abov

    e center cancape to sumor pump willst the force

    overning F

    built withoutk valves, ande direction ochanged by

    es in one dirump, the pu

    ump are sett have any oidamage to tovernor.

    Servo (P

    ger controlsthe connecti

    are used in g

    where oil pr

    e oil under thhing directlythe position

    rvo piston us

    /Servo Pis

    ger controlsthe connecti

    -10. Spring

    pushes thepower pisto

    e its centerethe oil trappp. If the pilotbe directed tf the power

    undamental

    heck valves.the governorotation in tremoving th

    ection only.p is rotated

    up for the wril pressure ae governor.

    ower) Pi

    the movemeing linkage, c

    overnors:

    essure is use

    e power piston the pistoto move tow

    es pressure

    ton

    the movemeing linkage, c

    oaded Serv

    power pistonwill not movposition. O

    d in the circvalve plungeo the powerspring, in the

    s and Power

    In these unitr must alwayese governobase.

    o change dir180.

    ong directiond cannot conDrive rotatio

    ton

    nt of the powontrols the e

    d to increase

    n is directedor connecterd minimum

    il to move it

    nt of the powontrols the e

    Piston

    down in thee down unlely when theit between thr is lowered,iston and wildirection of i

    Manageme

    1

    s, two plugsbe rotated i

    rs, the

    ection of

    of pumptrol theis always

    er piston. Thgine fuel.

    the output

    to sump ad to linkagefuel.

    in both

    er piston. Thgine fuel.

    decreases the pilot-ilot-valvee plunger anressure oil

    ll push thecrease fuel.

    t

    1

    d

  • 8/6/2019 WW Governing Fundamentals

    18/76

    Gove

    12

    NotecentepistoThe omotiopress

    DiffThe gpowe

    The p

    fuel dthanarea.The pcenteIf thebottoagainpistooil). Tdirect

    NoteuncepistoTwovalvemodeThe ostoreminim

    rning Funda

    that the powred, permittinis, in effect,

    utput of then. It is desigure fail.

    rential Po

    overnor pilotr piston, acti

    ower piston r

    irection. A difn the other.This constaniston can onlr, allowing oil

    pilot-valve plside of the

    st the top sidare about th

    his gives it aion.

    that the powtered to peris hydraulic

    ifferent hydrplunger contl depends up

    utput of thein the gover

    um fuel in c

    mentals an

    r piston willg the oil flowhydraulically

    ower pistoned to move t

    wer/Servo

    -valve plungeg through th

    Figure 2-

    equires pres

    ferential typePressure oil it pressure puy move to deto drain to s

    unger is belopower pistone with the sme same, thelarger force

    r piston canit the oil flolly locked.

    ulic circuitsrol land and ton the size o

    ower pistonnor accumulse of govern

    Power Man

    ove only whrequired. Wilocked.

    an be a pushe fuel to the

    Piston

    r controls thconnecting

    1. Differenti

    ure oil to m

    piston hass constantlyshes the pistcrease fuelmp.

    its centerewith the largaller area.) Turface areand moves th

    move only wrequired. W

    re used for the power pisf the power p

    an be a pustor is suffici

    or failure.

    agement

    en the pilot-vh the plunge

    h-pull motionminimum po

    movementlinkage, cont

    l Power Pist

    ve in either t

    ore area onirected to th

    on in the dechen the pilot

    position, coer area. (Prehe pressuresis greater one piston in th

    en the pilot-ith the plung

    he oil passaton. The schiston.

    h-pull motionnt to move t

    alve plungerr centered, t

    or convertedsition should

    f the powerrols the engi

    on

    he increase

    one side of te side with threase fuel divalve is rais

    ntrol oil flowssure oil is alon both sid

    the bottom se increase fu

    alve plungerr centered, t

    es betweenme used in

    or a rotary me power pist

    Manual

    Woo

    is note power

    to a rotarythe oil

    iston. Thee fuel.

    r decrease

    e pistone smallerection.d above

    to thewayss of theide (controlel

    ishe power

    he pilotparticular

    otion. Oilon to

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    19/76

    Manual 2

    Woodwar

    DrfoDDrful2.Dr

    If,shSiorerec

    InTreDcospovua

    260

    d

    oop has manrm of droop,

    oop is defin

    oop is exprell load. The n5% is require

    oop is calcul

    %

    instead of aowing negati

    mple hydro-erate in droourns the speovered from

    ompensation.

    a system wite governorurned to the

    e to the comntinue to increed. The goershoot. It widershoot. Thplify until th

    Figure 3-1.

    y uses and angine-speed

    ed as a dec

    sed as a perrmal recom

    d to maintain

    ted with the

    roop =No

    ecrease in sve droop. Ne

    echanical gp. More comed setting toa change in

    Why

    hout droop, aill respond boriginal spee

    bined properease beyondernor againll over-correcis overcorrecengine trips

    Response C

    overning F

    ChapDr

    Introd

    pplications icontrol woul

    ease in spe

    centage of tended perc

    stability in a

    following for

    oad Speed Full Loa

    peed settinggative droop

    vernors havlex governo

    its original spspeed or loa

    Is Droo

    load increasincreasing td.

    ties of inertiathe originalill respond t

    t the speed ition of speedout on overs

    rves of Gov

    undamental

    ter 3.op

    ction

    the controld be unstabl

    d setting at

    e original spnt of droop i

    speed-droop

    ula:

    Full Load RateRated Sped

    an increase twill cause in

    the droop frs include teeed setting a. The tempo

    Necess

    e will cause the fuel until t

    and power lpeed setting

    o decrease sthe other di

    in both direcpeed.

    rnor without

    s and Power

    f engines. Win most cas

    the load inc

    ed setting frs 3% to 5%.governor.

    d Speedx 1

    akes place, ttability in a g

    nction built iporary droofter the engirary droop is

    ry?

    he engine tohe engine sp

    g, the engin, causing anpeed to correrection causitions (instabi

    Droop or Co

    Manageme

    1

    ithout somees.

    reases.

    m no load tminimum o

    00

    he governorovernor.

    and always, whiche hascalled

    slow down.eed has

    speed willovershoot inct for theg an

    lity) will

    pensation

    t

    3

    f

    is

  • 8/6/2019 WW Governing Fundamentals

    20/76

    Gove

    14

    This ispeedecresettin

    Sim

    As lodroopfeedbon thwhich

    ComFor ccompaddsspeespeecompknow

    rning Funda

    nstability prosetting is d

    ase causedg. This lower

    le Speed

    d is appliedfeedback le

    ack lever pulspeeder spmaintains th

    pensated

    mpensatedensation systto the force o

    is reached.setting had

    ensation systn as tempor

    mentals an

    lem can becreased. Why the increaspeed settin

    Spee

    Droop Go

    Figur

    to the engineer is connec

    ls up on the sing, the speee load at a lo

    Governor

    overnors, wem pushes uf the flyweigThis temporabeen reduceem is reducery droop.

    Power Man

    liminated wien the govered load, it wiprevents th

    Droop

    ernor

    e 3-2. Droop

    , the power ped to the popeeder sprind setting is dwer speed.

    en a load isp on the pilotts to close thry force addi. The force t

    d to zero as

    agement

    h droop. As tnor moves toll be correctie speed from

    peratio

    Feedback

    iston moveser piston an

    g to reduce itecreased, ca

    applied, the tvalve compe pilot valveion works inhrough the nhe engine re

    he load incrcorrect for tg to a lowerovershootin

    up to increasd speeder sps force. Withusing the dr

    emporary fornsation land

    before the ethe same waeedle valve oturns to spee

    Manual

    Woo

    ases, thee speedspeed.

    e fuel. Thering. Theless forceop action

    ce of the. This forceginey as if thef thed. This is

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    21/76

    Manual 2

    Woodwar

    TDrpofrerpIfnga

    IsMdr

    260

    d

    e Droop

    oop is a straisition. Normthe referencerence spee

    m at full load.

    he linkage isload to full lvernor outpujustment.

    olated Uniost governoroop operatio

    Figure 3-3.

    urve

    ght line functlly a droop g, from no loa

    d of 1236 rp

    changed, altad, the droot shaft travel

    tare capableis necessar

    overning F

    Compensat

    ion, with a ceovernor lowed to full load

    at no load

    ering the amp must be reto ensure sta

    Uses O

    of operatingfor many a

    undamental

    d Governor

    rtain speed rrs the speedThus, a 3%ould have a

    unt of goveret. Be sure tbility and all

    Droop

    in the isochrplications.

    s and Power

    Schematic

    eference forreference froroop governreference sp

    nor output sho use a leastw sufficient

    nous mode,

    Manageme

    1

    very fuelm 3% to 5%r with a

    eed of 1200

    aft travel fro2/3 of theroop range

    However,

    t

    5

  • 8/6/2019 WW Governing Fundamentals

    22/76

    Gove

    16

    FiguSp

    IsolatIn sinenginoriginthe sdroop

    settin

    IsolAn iscomor cosysteWithoisoch

    The iany ocapaisochloadtry totwo uenginThe ris sh

    rning Funda

    re 3-4. Comed Settings

    L

    ed, single-engle engine aes or the utilial speed afteeed decreasmode, if the

    g to return to

    ted Syste

    lated systeon load. Thibinations of

    ms are not c

    ut some forronous load

    ochronousther engine.ilities, no mo

    ronous modeharing contrcarry the entinits to sharee from either

    eason for onwn in the foll

    mentals an

    arison of 3%for 50% andoad

    gine applicatiplications, th

    ty. In isochror a load hases by a set poriginal spee

    the original s

    ms

    is an applicload could

    these and annected to a

    of isochronharing contr

    ode can alsowever, unlre than one. If two enginls are suppl

    ire load and tload, some atrying to take

    unit takingowing examp

    Power Man

    Droop100%

    F

    ons can opere engine opeous operatieen applied

    ercentage aftd is desired,

    peed when a

    tion where te electrical gy other mec

    ny other syst

    us load sharl, droop mus

    be used oness the govef the engine

    es operatinging power tohe other willdditional meall the load,

    ll the load ale:

    agement

    igure 3-5. 3

    ate in eitherration is notn, the speedup to 100% ler a load hathe operator

    load is appli

    o or more eenerators, panical loads

    ems or to a u

    ing scheme lit be used to

    one engine,rnors have isrunning in p

    in the isochrthe same lohed all of itsns must beor from moto

    d the other u

    and 5% Dro

    isochronousffected by areturns bac

    oad. In droopbeen applie

    must raise th

    ed.

    ngines are drmps, ship pr

    . These isolatility.

    ke the electrhare these l

    unning in paochronous loarallel can bnous moded, one of theload. In ordesed to keepring.

    nit dropping

    Manual

    Woo

    op Curves

    or droop.ny otherto theoperation,

    d. In thee speed

    iving aopellers,ed

    nicoads.

    rallel withad sharingin theithoutunits willr for theeach

    all the load

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    23/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 17

    If two isochronous units are to be coupled together on the same load and thespeed settings are not the same, the system will become unbalanced whencoupled together. Since there cannot be two different speeds on one systemcoupled together, one engine will have to decrease its actual speed and the otherwill have to increase its actual speed to an average speed between the two. Thegovernor on the engine that decreased speed will move to increase fuel to try tocorrect for the decrease in speed, and the governor on the other unit thatincreased speed will move to decrease fuel to try to correct for the increase in

    speed. The result will be that the engine with the higher speed setting willcontinue to take all of the load until it reaches its power limit, and the otherengine will shed all of its load and become motored (driven by the other engine).

    As seen by the example, units running in isochronous cannot share loads withoutan isochronous load sharing scheme.

    Using Droop to Share Loads

    If all engines in a droop system have the same droop setting, they will eachshare load proportionally. The amount of load each carries will depend on theirspeed settings. If the system load changes, the system speed/frequency will also

    change. A change in the speed setting will then be required to offset the effect ofdroop and return the system to its original speed/frequency. In order for eachengine in the system to maintain its proportion of the shared load, the operatorwill need to adjust the speed setpoint equally for each engine.

    If all engines in a droop system do not have the same droop setting, they will notshare loads proportionally with the same speed settings. If the system loadchanges, the system speed/frequency will also change but the percent of load oneach engine-generator set will not be changed proportionately.

    The operator will need to adjust the speed setpoint differently for each engine tomake them carry their proportional share of the load. This could result in runningout of speed setpoint adjustment on an engine before it is fully loaded and

    limiting the system load sharing capability. It is best to have the same percent ofdroop set on each engine (3% to 5% is recommended).

    Figure 3-6. Droop Mode

  • 8/6/2019 WW Governing Fundamentals

    24/76

    Gove

    18

    DroDroooperamode

    run atspeeof poin the(see

    Maxiswingabovsystethe drmachTheswingcapasuchexpe

    rning Funda

    p/Isochro

    /Isochronouted in the dr. It is known

    the speed/frsettings ofer. The outload demanigures 3-3 a

    um load formachine anthis maxim

    m load cannoop machineine can be m

    achine withmachine soility. This is

    things as effited to chang

    mentals an

    Is

    nous

    combines top mode ex

    as the swing

    equency of tach droop uut power of twhile maint

    nd 3-4).

    Figu

    this type of sthe total set

    m will resultt be alloweds. If it does, totorized.

    the highest othat the systot a rigid ruliency of diff

    e.

    Power Man

    lated Sy

    e first two mept for onemachine. In t

    e isochronoit are adjusthe swing maining consta

    re 3-7. Swin

    stem is limitpower outp

    in a decreasto decreasehe system fr

    utput capacitm will accep. Selection orent engines

    agement

    stems

    odes. All enghich is oper

    his mode, th

    s unit. The dd so that it ghine will cha

    nt speed/fre

    Machine

    ed to the cot of the drooin speed/freelow the coquency will i

    should nort the largest lf the swingand the amo

    ines in the syted in the isdroop mac

    roop percentenerates a snge to followuency of the

    bined outputmachines.

    quency. Thebined outpu

    ncrease and

    ally be operoad changesachine will dunt the load

    Manual

    Woo

    stem arechronousines will

    age andet amountvariationssystem

    of theload

    minimumt set forthe swing

    ated as thewithin itsepend onis

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    25/76

    Manual 2

    Woodwar

    S

    Pr(nse

    Drrelo

    DDrwichg

    3-

    260

    d

    stem Tie

    eviously theot tied to anot is parallele

    The utilityspeed/freunit canno

    When an iutility willgovernor sutility busis even frago to full lof a utility

    remain at

    oop provideserence to ded with the s

    roop Base

    oop base loall control theange in load.nerator set s

    7).

    to a Utilit

    se of droopther larger sy

    with a utility

    will basicallyuency for ant be parallele

    sochronousetermine thepeed referenill flow to th

    ctionally highad in an atte

    is a frequenc

    ull load.

    the solutioncrease as loeed setting

    Load

    d is the samrequency anThe speed

    upplies a fixe

    overning F

    Figure 3-8.

    y Grid

    has been disstem such a, there are a

    act as an isoy units beingd to the utilit

    ngine-generspeed/frequce be less thgenerator a

    er than the frmpt to increy which is to

    to this probled increases.ince the spe

    as droop, wd act as doend droop setd, or base a

    undamental

    roop Units

    cussed for sya utility). W

    few things to

    chronous uniparalleled to.

    ator set is coency of the gan the utilitynd motor theequency of tse the bus sstrong to inf

    m. Droop caThis allows t

    ed cannot ch

    ith the excepthe swing m

    tings are adjount, of po

    s and Power

    stems that wen an enginconsider:

    t. The utilityit. A simple i

    nected to aenerator. Shfrequency, punit. If the ge utility, theeed. Since t

    luence, the e

    ses the govhe governor tange.

    tion that theachine, absosted so thater to the utili

    Manageme

    1

    ere isolated-generator

    ill set theochronous

    tility bus, thuld thewer in thevernor spee

    governor willhe definitionngine will

    rnor speedo vary the

    tility or gridrbing anythe engine-y (see Figur

    t

    9

  • 8/6/2019 WW Governing Fundamentals

    26/76

    Gove

    20

    Basepowewherengin63 Hzfrequvarieincre

    powethe drhighewhich

    If thesimplminimIf theopenincredepe

    rning Funda

    on 5% droor output. Foll

    it crosses te-generator, the powerncy line is t, the amountses, the dro

    r and producoop will crosr output powit is not.

    engine-genedecrease t

    um power o

    engine gene, separatingse to the spds on where

    mentals an

    p, increasingwing the droe 60 Hz lineet is at 50%utput will bee amount ofof output pop line will cr

    a lower outs the lower utr. This condi

    Figure 3-

    rator set is toe speed settitput, then op

    ator set is ruthe engine ged setting pthe speed s

    Power Man

    the speed sop line from t(controlled bpower outputat 100%. Whpower output

    er will vary iss the highe

    ut or power.ility frequenction is often

    . Base Load

    be unloadedng slowly unen the tie br

    nning in a lonerator set fint. The amotting was wh

    agement

    tting to 61.5he 61.5 Hz sthe utility) it

    . If the speedere the drooproduced. If

    inversely. If tr utility frequ

    If the utility fy line farther

    istaken for

    with 5% Dro

    and disconnil the engineaker.

    ded conditiorom the utilitunt the frequen the tie br

    Hz will produetting to thecan be seensetting is inline crosses

    the utility free utility freqncy line clos

    equency decfrom zero, prgovernor pr

    op

    ected from thgenerator se

    and the tie, the frequeency increasaker opened

    Manual

    Woo

    ce 50%ointthat thereased tothe utilityuencyency

    er to zero

    reases,oducing aoblem,

    e utility,t is at

    breakercy willes.

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    27/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 21

    Figure 3-10. Schematic of Droop Governor

  • 8/6/2019 WW Governing Fundamentals

    28/76

    Governing Fundamentals and Power Management Manual 26260

    22 Woodward

    Chapter 4.Linkage

    General

    Linkage between the governor output and the engine fuel control system isresponsible for many unacceptable control conditions that appear to be governorconnected. When acceptable governor control deteriorates or changes, linkage isone of the first areas to troubleshoot. Loose or worn linkage not only can causeunacceptable governor control, but it can also present dangerous conditionsshould it fail completely and leave the engine uncontrolled. Good lockingmethods must be used at all linkage connections.

    There must be no lost motion or binding in the linkage attached between thegovernor and the engine. Binding or catches in the linkage can cause speedexcursions and other problems which may appear as being caused by thegovernor. Lost motion in the linkage will cause the governor to have to travel thedistance of the lost motion before any fuel change is made. The governor will

    become over-active in fuel control. This overly active governor will provide lessthan optimum control. An overactive governor will also cause excessive wear inlinkage and in the governor. The engine will tend to move up and down in speedor wander.

    Governor operation is based on the assumption that linkage is so arranged that agiven movement in the governor output will provide a proportional change in thefuel to the engine.

    Many fuel control systems provide a nearly linear response in engine output.(This is usually true of diesel engines.) Other fuel control systems provide anon-linear response to change in the control device position and engine outputs.(This is particularly true of carbureted engines with butterfly valves.) Allgovernors tend to provide nearly linear travel. Differences between the linearity ofgovernor travel and the linearity in the engine fuel control system or valve areaccomplished by the design of the linkage between the governor and the enginefuel system or valve.

    Figure 4-1. Linear Fuel Control

  • 8/6/2019 WW Governing Fundamentals

    29/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 23

    Figure 4-2. Non-Linear Fuel Control

    Governor Travel

    Design of the fuel linkage must provide for control of fuel from FUEL OFF toFULL FUEL within the limits of the travel of the governor output shaft. Thedesign must also provide for about 2/3 output shaft travel between NO LOAD

    and FULL LOAD. If less than 2/3 travel from no load to full load is not used, itmay not be possible to stabilize the engine. If a lot more than 2/3 travel from noload to full load is used, there may not be enough travel to be sure the fuel isshut off at minimum governor travel, and full fuel may not be reached atmaximum governor travel. This can make the engine appear sluggish. In bothcases, the misadjusted linkage can appear as a governor problem when it reallyis not a governor problem.

    Figure 4-3. Correct Use of Governor Travel

  • 8/6/2019 WW Governing Fundamentals

    30/76

    Governing Fundamentals and Power Management Manual 26260

    24 Woodward

    Linear Linkage Arrangements

    This Linkage design provides a large amount of engine fuel motion for a smallamount of governor motion.

    This Linkage design provides equal amounts of engine fuel motion and governormotion.

    This Linkage design provides a large amount of governor motion for a smallamount of engine fuel motion.

    A linear linkage arrangement is used in applications where the governor outputshaft positioning is directly proportional to the torque output of the engine. Alinear linkage is a linkage design which provides as much movement of thegovernor output shaft per increment of engine fuel movement at light loads as atheavy loads.

    Using less than the recommended amount of governor travel will providegovernor control which exhibits fast response and is, or tends to be, unstable.Droop load sharing could be impossible if too little governor output shaft travel isbeing used.

    Using a lot more than 2/3 of the governor travel may not let the fuel system be

    shut off or may not let the fuel system be opened to maximum.

    The linkage must be set up to shut fuel completely off and let fuel be opened tofull fuel. Use at least 2/3 of the full governor travel from zero load to 100% load.

  • 8/6/2019 WW Governing Fundamentals

    31/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 25

    Non-Linear Usage

    Butterfly carburetor valves present extremely non-linear control characteristics.At minimum positions (light load), the valve must move very little to change theamount of fuel flow a large amount. At higher loads, the valve must move a largeamount to have any effect on fuel flow. Since governor output travel is essentiallylinear, special linkage is necessary to make the two conditions compatible. Thisis called non-linear linkage. Non-linear linkage is also required on some dieselinjection systems, although these conditions are not usually as severe as theyare when controlling a butterfly carburetor valve. In all cases the linkage shouldbe designed to provide increased engine output in direct proportion to movementof the governor output.

    Figure 4-4. Nonlinear Carburetor Linkage

    When installing this linkage, make sure the following conditions are obtainedwhen the governor output is in the min fuel position:

    The governor lever and connection link are in line with the governor outputshaft and the point of attachment on the connecting link to the butterflycarburetor lever.

    The butterfly carburetor lever is 90 with the connecting link.

  • 8/6/2019 WW Governing Fundamentals

    32/76

    Governing Fundamentals and Power Management Manual 26260

    26 Woodward

    Chapter 5.Magnetic Pickups

    Introduction

    Figure 5-1. Magnetic Pickup

    A magnetic pickup (see Figure 5-1) is the device most often used to sense thespeed of a prime mover. It is basically a single pole, alternating current, electricgenerator consisting of a single magnet with a multiple-layer coil of copper wirewrapped around one pole piece. The field or flux lines of the magnet exit thenorth pole piece of the magnet, travel through the pole piece and air path tosurround the coil, returning to the south pole of the magnet. When a ferrousmaterial, such as a gear tooth, comes close enough to the pole piece (see Figure5-2) the reluctance path is decreased and the flux lines increase. When theferrous material is far enough away from the pole piece (see Figure 5-3), theoriginal air path is re-established, and the flux lines will decrease to the originallevel. This increase and decrease of flux induces an ac voltage into the coilaround the magnet.

  • 8/6/2019 WW Governing Fundamentals

    33/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 27

    Figure 5-2. Low Reluctance Gear Position

    Figure 5-3. High Reluctance Gear Position

  • 8/6/2019 WW Governing Fundamentals

    34/76

    Governing Fundamentals and Power Management Manual 26260

    28 Woodward

    The output of this single pole generator, known as a magnetic pickup (MPU),depends on the surface speed of the gear being monitored, the gap or clearancebetween the pole piece and the gear teeth, the dimensions of the magneticpickup and those of the gear (see Figure 5-4), and the impedance connectedacross the output coil of the magnetic pickup. The voltage wave form of theoutput depends on the shape and size of the gear teeth relative to the shape andsize of the end of the pole piece (see Figure 12-5). Any change in the reluctanceof the flux path, external to the magnetic pickup, caused by the addition or

    removal of ferrous material will cause an output voltage to be developed. Gearteeth, projections, or holes, can be used to change the reluctance. Spacingbetween the gear teeth, projections, or holes must be uniform. Differences inspacing will be seen as changes in frequency or speed.

    Figure 5-4. Magnetic Pickup and Gear Dimensions

    Additional information can be found in manual 82510, Magnetic Pickups andProximity Switches for Electronic Controls.

  • 8/6/2019 WW Governing Fundamentals

    35/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 29

    Figure 5-5. Generated Waveforms

  • 8/6/2019 WW Governing Fundamentals

    36/76

    Governing Fundamentals and Power Management Manual 26260

    30 Woodward

    Chapter 6.Load Sensing, Load Sharing, Base

    Loading

    Load SensingThe generator load sensor senses the load on a generator. To sense this load,current transformers (CTs) are placed around the power output leads comingfrom the generator. As load is applied to the generator, alternating current flowsthrough the generator lines and induces current into the CTs. The current in theCTs increases proportionally with the load on the generator (see Figure 6-1).

    Figure 6-1. Generator Load Sensor

    The induced current from the CTs is added vectorially and then is converted to adc voltage in the load sensor. However, since only real power is to be used indetermining the load sensor output, potential transformers are also connected tothe power output leads of the engine-generator. Only CT current which is inphase with the potential transformer voltage is used and converted to a dcvoltage in the load sensor. This dc voltage is proportional to the percent of loadon the generator. The generator load sensor dc voltage is applied across a "LoadGain Adjust" potentiometer (see Figure 6-2).

    Load Gain Adjust Potentiometer

    The Load Gain Adjust potentiometer provides a means of setting a specificvoltage, selected from the load sensor output, to represent the load on theengine-generator set. This load gain setting is normally at 6 Vdc for 100% of thesets rated load. The output of the generator load sensor is linear so that voltagesfrom 0 to 6 Vdc represent loads from 0% to 100% of the sets rated load. Thisload gain voltage is impressed across a balanced load bridge.

  • 8/6/2019 WW Governing Fundamentals

    37/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 31

    Balanced Load Bridge

    Isochronous

    The balanced load bridge (see R1, R2, R3 and R4, Figure 6-2) is a device similarto a Wheatstone bridge. In our bridge, R1=R2 and R3=R4. As long as the voltagedeveloped across R1 equals the voltage developed across R3, which also means

    that the voltage developed across R2 equals that across R4, there is no voltagedifferential across C. The output of the load bridge to the summing point is zero.This is true regardless of the load gain voltage. The control is in isochronous.The load does not affect the speed or frequency.

    Figure 6-2. Balanced Load Bridge

  • 8/6/2019 WW Governing Fundamentals

    38/76

    Governing Fundamentals and Power Management Manual 26260

    32 Woodward

    Droop

    The load bridge may be unbalanced by either changing the value of a resistor inone leg of the bridge or by applying an unbalancing voltage across one leg of theload bridge. If you unbalance the load bridge by paralleling R5 with R3, theresulting resistance of (R3, R5) is less than R4. The voltage developedacross.(R3, R5) will be less than that developed across R4. The voltagesdeveloped across R1 and R2 are each still at 1/2 the load gain voltage. A voltage

    is now present across C with a value that will be determined by the load gainvoltage and the amount of imbalance caused by R5 in parallel with R3. Thevoltage across C applied to the summing point will be negative with respect tocircuit common. C is not required to make the bridge work. The time to chargeand discharge the capacitor slows down the load bridge action. This is necessaryto ensure that the load bridge is not faster than the speed loop. If it is, oscillationwill result.

    At the summing point, the negative signal from the load bridge adds to thenegative signal from the speed sensor. To obtain a summing point balance, theamplifier will act to reduce the speed until the sum of the two negative inputsignals equals the positive input signal from the speed set adjust. The control isin droop. The speed or frequency will decrease proportionally with addition of

    load.

    To return the system to rated speed, it will be necessary to either increase thespeed set adjust voltage or to re-balance the bridge and return the system toisochronous control.

    Figure 6-3. Basic Load Sensing Block Diagram

  • 8/6/2019 WW Governing Fundamentals

    39/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 33

    Load Sharing

    The action of the load bridge is also used to bring about isochronous loadsharing. Instead of unbalancing the load bridge by changing the resistance ofone leg of the bridge, parallel one leg of a bridge from the control on one engine-generator set with the corresponding bridge leg of the control of a secondengine-generator set (see Figure 6-4). As long as both sets are providing thesame voltage across these connected lines, there will be no imbalance to the

    load bridge. The summing point is then returned to zero when the speed set andspeed sensor signals are equal.

    Take two engine-generator sets and adjust each sets load gain for 6 Vdc at100% of that sets rated output. The voltage developed across R3 of eachbalanced bridge will be 1/2 of that sets load gain voltage or 3 Vdc at 100% ofrated load. Start one set and load it to 100% of rated load. Start the second setand bring it on line at zero load. Simultaneously, when paralleling the two sets,connect the R3 leg of the balanced bridges of the two sets together by means ofthe load sharing lines (see Figure 6-4).

    The voltages across the two R3s are different at the time when set two is broughton line. The R3 of set one is at 3 Vdc, indicating 100% load, and that of set 2 is

    zero, indicating no load. These differences will balance out through R6 and R3 toa voltage between zero and 3 volts. Both load bridges will be unbalanced, but inthe opposite sense. The voltage developed across C of the first unit will call forreduced fuel and that of the second for increased fuel. This imbalance willdisappear as the two generator sets approach the same percentage of ratedoutput.

    Where both engine-generator sets are of the same output rating, the outputs ofthe two units will both come to 50% of their rated load. The load gains will bothbe at 3 Vdc and the voltages across the R1s and R3s will all be 1.5 Vdc. Thebridges of both sets are balanced. The bridge outputs are zero, and the sets arein isochronous load share at rated speed. Voltage across the load sharing lineswould be 1.5 Vdc.

    If the oncoming engine-generator set is rated at only one-half that of the first setsrating (say the first was rated at 100 kW and the second at 50 kW), balancedload would be achieved when each engine-generator set is carrying itsproportional share based on its rated output.

    Rated share X =100 KW Load

    100 KW + 50 KWor X = 2 / 3 or 66.67percent

    Load gain outputs would match at 2/3 of 6 Vdc or 4 Vdc. Voltages across the R1sand R3s would be 2 Vdc. The load bridges would return to balance when the firstmachine was carrying 66.67 kW and the second would be carrying 33.33 kW.The sets are in isochronous load share rated speed. Voltage across the load

    sharing lines would be 2 Vdc.

    This method of connecting the load bridge between controls of multiple engine-generator sets, which are supplying the same load, can be used to obtain loadsharing between a number of different sets (see Figures 6-5 and 6-6). Themaximum number of sets which can be controlled in this manner has not beendetermined. One known installation has 21.

  • 8/6/2019 WW Governing Fundamentals

    40/76

    Governing Fundamentals and Power Management Manual 26260

    34 Woodward

    Power Output Sensor

    The load sharing of mechanical loads or of mixed electrical and mechanical loadsuses a different type of load sensing. The most desirable method of sensing loadwould be to measure the torque on the engines, but this is difficult and requiresvery special measuring devices. The more common method, based on theassumption that power output is relative to actuator position, is to use a signaldeveloped from the control output (either current or voltage) to the actuator coil.Here, the current is the more desirable since force at the actuator is based onampere turns. If the actuator coil resistance changes with temperature, thechange does not affect the current load signal.

    Another signal that can be used is one developed from the fuel valve position.This method makes use of Hall effect devices or of either LVDTs or RVDTs(linear or rotary variable differential transformers). These devices requiremodulators/demodulators to supply an ac voltage to the position sensors and torectify the return signal. A dc signal is developed representing fuel valve position.For load sharing these dc voltages relative to output load do not have to beexactly linearly proportional to the load to be useful for load sharing. They doneed to be equal from each engine in the load sharing system for any particularpercent of each engine's load capability. Again, the sensor output is impressed

    on a load gain adjustment potentiometer.

    The above load sharing analysis can also be applied to a system using poweroutput sensors to accomplish load sharing. The summing point amplifier in thecontrol of each engine will integrate to a fuel position which brings the loadbridges in each control to balance. This will set the fuel system of each engine tothe same power output whether the load on a particular engine is electric,mechanical, or a combination of electric and mechanical. The actual load sharingwill depend on how closely the fuel systems of the different engines track for thesame percentage of rated load.

    Isochronous Base Load

    If an engine-generator set is under the control of a load sharing and speed controlor if it is in an isochronous load sharing system, connecting the system to a utilitywill fix the speed sensor input to the summing point. Since the speed set is also ata fixed setpoint and the system is in isochronous, one of two things will happen.Either the system will be motorized or it will go to overload. The summing point,having all inputs fixed, cannot correct what it sees as an imbalance. If the systemwas at a frequency slightly below that of the utility, the speed sensor will send asignal to the summing point in excess of the setpoint input. The amplifier willintegrate in a decreased-fuel direction, cutting fuel to the engine. The utility thenends up driving the system. If the system frequency was slightly higher than theutility, the speed signal to the summing point would be below the setpoint, resultingin increased fuel until the mechanical stops are reached.

  • 8/6/2019 WW Governing Fundamentals

    41/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 35

    To prevent these two conditions and to set the desired load, an auxiliary biassignal can be applied to the system load sharing lines. This will set a demand onthe generating system to generate a given portion of each engine-generatorsrated output. The action is the same as when load sharing units unbalance thebalanced load bridges. The load bridge outputs to the individual set summingpoints will be either positive or negative based on whether the engines are to pickup load or to shed load. Again, when the output of the engine-generators balancethe voltages on the load bridge, the system will be at the desired load. The

    summing point can now function to correct imbalances and the system is underisochronous base load control.

    If we now connect such an isochronous load sharing system to a utility, wherethe speed/frequency Is fixed by the utility, and we place a fixed bias signal onthat systems load sharing lines, all units in that system will be forced by loadbridge imbalance to carry the load demanded by the bias signal. This controlmethod opens many possibilities for load management through Isochronousbase loading.

  • 8/6/2019 WW Governing Fundamentals

    42/76

    Governing Fundamentals and Power Management Manual 26260

    36 Woodward

    Figure 6-4. Load Sharing Diagram

  • 8/6/2019 WW Governing Fundamentals

    43/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 37

    Figure 6-5. Load Sharing Block Diagram

  • 8/6/2019 WW Governing Fundamentals

    44/76

    Governing Fundamentals and Power Management Manual 26260

    38 Woodward

    Figure 6-6. Multiple Load Sharing Block Diagram

  • 8/6/2019 WW Governing Fundamentals

    45/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 39

    Chapter 7.Synchronization

    What Is Synchronization?

    We have talked about synchronizing one generator to another or to a utility, butwhat are we actually describing when we use the word "synchronization"?

    Synchronization, as normally applied to the generation of electricity, is thematching of the output voltage wave form of one alternating current electricalgenerator with the voltage wave form of another alternating current electricalsystem. For two systems to be synchronized, five conditions must be matched:

    The number of phases in each system

    The direction of rotation of these phases

    The voltage amplitudes of the two systems

    The frequencies of the two systems

    The phase angle of the voltage of the two systems

    The first two of these conditions are determined when the equipment is specified,installed, and wired. The output voltage of a generator usually is controlledautomatically by a voltage regulator. The two remaining conditions, frequencymatching and phase matching, must be accounted for each time the tie-breakeris closed, paralleling the generator sets or systems.

    Number of Phases

    Each generator set of the oncoming system must have the same number ofphases as those of the system to which it is to be paralleled (see Figure 7-1).

    Figure 7-1. Number of Phases Must Match Number Of Phases

    Rotation of Phases

    Each generator set or system being paralleled must be connected so that allphases rotate in the same direction. If the phase rotation is not the same, nomore than one phase can be synchronized (see Figure 7-2).

  • 8/6/2019 WW Governing Fundamentals

    46/76

    Gove

    40

    VoltThe vsmall

    syncis norIf twovoltagenersyste

    If, onsuchvolta

    rning Funda

    Figure 7-2.

    ge Match

    oltages genepercentage

    ronous genemally done b

    synchronoue will have aators. The dim efficiency (

    Figur

    the other haas a utility, ae of the bus

    Fi

    mentals an

    Phase Rotat

    rated by setsf the same v

    rator can bey the voltage

    generatorsvalue differe

    fference in vsee Figure 7

    7-3. Voltag

    d, a synchrodifference in(see Figure 7

    ure 7-4. Volt

    Power Man

    ion Must be t

    or systemsalue, usually

    ontrolled byregulator.)

    f unequal vont from the vltages result3).

    Difference (

    nous generatvoltages bef-4).

    age Differen

    agement

    he Same Ro

    eing parallel1% to 5%. T

    changing its

    ltage are parltage gener

    s in reactive

    Generator to

    or is parallelre parallelin

    e (Generato

    ation Of Pha

    ed must bee output vol

    excitation vol

    alleled, the cted by eitherurrents and l

    Generator)

    d to a largerwill not cha

    to Bus)

    Manual

    Woo

    ses

    ithin aage of a

    ltage. (This

    ombinedof the

    lowered

    systemge the

    26260

    dward

  • 8/6/2019 WW Governing Fundamentals

    47/76

    Manual 26260 Governing Fundamentals and Power Management

    Woodward 41

    In this instance, the power factor of the generator will be changed. If thegenerator voltage is much lower than the bus voltage, the generator could bemotored.

    An induction generator needs no voltage regulator because its output voltage willautomatically match the voltage of the system supplying its field voltage.

    Frequency Match

    The frequency of the oncoming generator must be very nearly the same as thatof the system it is being paralleled with, usually within 0.2% (see Figure 7-5).

    Figure 7-5. Frequency Difference

    If the oncoming generator is a synchronous type, this match is normallyaccomplished by controlling the speed of the prime mover driving the oncominggenerator.

    If the oncoming unit is an induction generator, frequency is determinedautomatically by the generator field voltage. Field voltage is supplied by thesystem to which the generator set is being paralleled. However, the field voltageis not applied to the generator until the tie breaker is closed. The generator mustbe kept close to synchronous speed prior to breaker closure. A speed belowsynchronous will cause the oncoming generator to act as a motor, and a speedmuch over 1.5% above synchronous will cause the induction machine to

    generate at full capacity.

    Phase Angle Match

    The phase relationship between the voltages of the systems to be paralleledmust be very close prior to paralleling. This match usually is within plus or minus10 degrees. If the oncoming generator is a synchronous type, phase matching,like frequency matching, is accomplished by controlling the speed of theoncoming generator's prime mover. If the machine to be paralleled with thesystem is an induction generator, the phase match will be automatic, since thesystem is supplying the generator field voltage.

    Figure 7-6. Phase Difference

  • 8/6/2019 WW Governing Fundamentals

    48/76

    Governing Fundamentals and Power Management Manual 26260

    42 Woodward

    For the synchronous generator, voltage, speed/frequency, and phase, must bematched each time before the paralleling breakers are closed. If the oncominggenerator is an induction-type with the armature rotating at synchronous speed,no difficulties will occur when the paralleling breakers are closed. Currently, mostinstallations use synchronous generators. The advantage of synchronousgenerators over induction generators is that synchronous systems allowindependent operation without a utility or other ac power source. Inductiongenerators can not operate without an external ac source.

    Why Is Synchronization Important?

    When two or more electrical generating sets or systems are paralleled to thesame power distribution system, the power sources must be synchronizedproperly. Without proper synchronization of the oncoming unit or system, powersurges and mechanical or electrical stress will result when the tie breaker isclosed. Under the worst conditions, the voltages between the two systems canbe twice the peak operating voltage of one of the systems, or one system canplace a dead short on the other. Extremely high currents can result from this,which put stress on both systems.

    These stresses can result in bent drive shafts, broken couplings, or brokenturbine quill shafts. Under some conditions, power surges can be started whichwill build on each other until both generating systems are disabled.

    These conditions are extreme. Stress and damage can occur in varying degrees.The degrading effects depend on the type of generator, the type of driver, theelectrical load, and on how poorly the systems are synchronized when thebreakers are closed.

    Modern systems often supply power to sophisticated and sensitive electronicequipment. Accurate synchronization is necessary to prevent expensive downtime and replacement costs.

    How Is Synchronization Accomplished?

    Normally, one generating system is used to establish the common bus, and theoncoming generator is then synchronized to that bus by changing the speed ofthe prime mover driving the oncoming generator.

    Manual Synchronization

    Manually synchronized systems rely on monitoring equipment to indicate to theoperator when the two systems are synchronized closely enough for safeparalleling. This equipment may include indicating lights, a synchroscope, asynch-check relay, or a paralleling phase switch.

    Figure 7-7 shows one method of using two 115 Vac lamps to check whether twovoltages are in or out of phase. When the voltages are in phase, the lamps willbe extinguished, and when the voltages are out of phase, the lamps willilluminate.

    Figure 7-8 shows another method, using four 115 Vac lamps, that will checkphase rotation as well as phase match. As before, when the voltages are inphase, all lamps will be off, and when the voltages are out of phase, all of thelamps will light. If pairs of lamps alternate light and dark (with two lamps darkwhile the other two are light) the phase sequence is not the same.

  • 8/6/2019 WW Governing Fundamentals

    49/76

    Manual 2

    Woodwar

    Thsy

    AAofumEps

    acTShbAfrco

    260

    d

    ese manualnds and skillstems.

    utomatic

    tomatic sync-line generatits normally

    onitor two ph

    rly automatictentiometer (all frequenc

    tive bus.

    e time for thinchronizingw closely thes.

    good governquency drift.uld result in

    Figu

    Figure 7-8.

    systems, whof the operat

    ynchroni

    hronizers moor and the vo

    onitor a sinses.

    synchronizeMOP). They

    drift to matc

    s type of unitepended onsynchronize

    r and an accWhen this wn unaccepta

    overning F

    e 7-7. Chec

    Checking Ph

    re the accuror, are givin

    ation

    nitor the voltltage of the sle phase. La

    rs worked thcorrected forh the phase

    to synchronihow closelyr had match

    urate frequeas the case,bly long sync

    undamental

    ing Phase M

    ase Rotation

    cy of synchrway to auto

    age of eitherame phasesrge generati

    ough the spspeed/frequ

    of the oncom

    e varied frothe governord the genera

    cy match ofthe time requhronizing tim

    s and Power

    atch

    and Match

    onization deatic synchr

    one or two pof the activeg systems n

    ed setting mncy only, an

    ing generator

    1/2 secondcontrolled sptor frequency

    en resulted iired to drift ine.

    Manageme

    4

    ends on thenizing

    ases of anbus. Smallrmally

    otor-operaterelied on a

    to that of th

    upward.eed, and onto that of th

    a very slowto phase

    t

    3

  • 8/6/2019 WW Governing Fundamentals

    50/76

    Governing Fundamentals and Power Management Manual 26260

    44 Woodward

    This method was later improved upon. The synchronizer would bring theoncoming unit into frequency match with the bus. Once the frequency wasmatched, the speed setting MOP was pulsed, adjusting generator speed to about0.5% above synchronous speed. The speed setting MOP was then run back toabout 0.2% below synchronous speed. This action was repeated untilsynchronization of phase angle occurred and the circuit breaker was then closed.

    A modern synchronizer compares the frequency and phase of the two voltages,

    and sends a correction signal to the summing point of the governor controllingthe prime mover of the oncoming generator. When the outputs of the twosystems are matched in frequency and phase, the synchronizer issues abreaker-closing signal to the tie-breaker, paralleling the two systems.

    These synchronizers may include voltage-matching circuits which send raise andlower signals to the voltage regulator of the oncoming generator. If the voltage ofthe oncoming generator does not match the bus within set limits, thesynchronizer will not allow a circuit breaker closure.

    This system is much faster than the earlier models and can even be used toforce an isolated engine-generator to track a utility without actually beingconnected to it.

    Prediction of the Worst Case Phase Angle Difference() at the Instant of Breaker Closure

    Worst case prediction of phase angle difference assumes there is no generatorspeed correction from the synchronizer after the breaker closure signal is issued(as in the permissive mode). In the run mode, the synchronizer continues toadjust generator speed toward exact phase match during the period the breakeris closing. This provides even better synchronization than the calculationsindicate.

    The following calculation can be performed to determine if the speed and phase

    match synchronizer will provide adequate synchronization before the breakercontacts engage in the permissive mode.

    Each generator system has a worst case or maximum-allowable relative phaseangle (wc) that can be tolerated at the time of breaker closure. If wc and the

    breaker time delay (Tb are known, the synchronizer's phase window (w) and

    window dwell time may be chosen to ensure that is less than wc when thegenerator breaker contacts engage. The synchronizer will not issue the breakerclosure command unless is within the window (w) and has been there forat least the window dwell time. The drawing (Figure 7-9) shows the relativevalues of and assumes the bus voltage is fixed and pointing straight up.

    The relative phase angle, at the instant the main generator breaker contacts

    engage, depends on many things. The worst case value would exist when thesynchronizer is in the permissive mode and therefore is not actively correctingthe phase angle during the windo