wind turbine modeling
TRANSCRIPT
[email protected] http://www.powerworld.com
2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330
2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330
Transient Stability Analysis with PowerWorld Simulator
T12: Wind Turbine Modeling
2 © 2012 PowerWorld Corporation T12: Wind Turbine
• Over the last decade wind turbine capacity has grown to the point where they need to be explicitly considered in system-wide transient stability studies
Need for Wind Turbine Models
http://www.awea.org/publications/reports/AWEA-Annual-Wind-Report-2009.pdf
Growth in US Wind Capacity
3 © 2012 PowerWorld Corporation T12: Wind Turbine
• A wind farm usually consists of many small turbines in a collector system
• Each turbine’s voltage is usually less than 1 kV (usually 600 V) with a step-up transformer (usually to 34.5 kV)
• Usually, the wind farm is modeled in aggregate, but how accurate such aggregate models are is an open question
• PowerWorld Simulator provides support of each of the four major types of wind turbine models used in transient stability studies – Type 1: Induction generator with fixed rotor resistance – Type 2: Induction generators with variable rotor resistance – Type 3: Doubly-fed induction generators – Type 4: Full converter generators
• New wind turbines are either Type 3 or Type 4
Wind Turbine Modeling
4 © 2012 PowerWorld Corporation T12: Wind Turbine
• Wind turbines are represented as generators in the power flow – Type 1 and 2 units operate at fixed real/reactive
power with the unit supplying real power and consuming reactive power; usually there are compensating capacitors
– Type 3 and 4 are treated as regular PV buses
Wind Turbine Modeling: Power Flow Solution
5 © 2012 PowerWorld Corporation T12: Wind Turbine
• Wind Turbines do not have an “exciter”, “governor”, or “stabilizer”
• However, modeling is very analogous – Wind Machine Model = Machine Model – Wind Electrical Model = Exciter – Wind Mechanical Model = Governor – Wind Pitch Control = Stabilizer – Wind Aerodynamic Model = Stabilizer
• Simulator will show wind models listed as though they are Exciters, Governors, and Stabilizers – Obviously you should not use a synchronous machine
exciter in combination with a wind machine model and wind governor!
Wind Generator Models
6 © 2012 PowerWorld Corporation T12: Wind Turbine
• Old Type 1 models as induction machine – MOTOR1, GENIND – CIMTR1, CIMTR2, CIMTR3, CIMTR4
• GE-specific Type 2 wind turbine model – GENWRI, EXWTG1, WNDTRB
• GE-specific Type 3 wind turbine model – GEWTG, EXWTGE, WNDTGE – Detailed model for GE 1.5, 1.6 and 3.5 MW turbines
Generic Wind Turbine Models Type 1 Type 2 Type 3 Type 4
GE DYD PSS/E DYR GE DYD PSS/E DYR GE DYD PSS/E DYR GE DYD PSS/E DYR
Machine WT1G WT1G1 WT2G WT2G1 WT3G WT3G1, WT3G2
WT4G WT4G1
“Exciter” WT2E WT2E1 WT3E WT3E1 WT4E WT4E1
“Governor” WT1T WT12T1 WT1T WT12T1 WT3T WT3T1 WT4T
“Stabilizer” WT1P W12A1 WT1P WT12A1 WT3P WT3P1
7 © 2012 PowerWorld Corporation T12: Wind Turbine
• Voltage control of wind turbines depends on the type • Type 1 squirrel cage induction machines- no direct
voltage control • Type 2- wound rotor induction machines with variable
external resistance, no direct voltage control, but external resistance system usually modeled as an exciter
• Type 3 and Type 4- have the ability to perform voltage or reactive power control, similar to synchronous machines. Common control modes are constant power factor control, coordinated control across a wind farm to maintain a constant interconnection point voltage, and constant reactive power control
Wind Turbine Voltage Control
Glover, Sarma, Overbye, Power System Analysis and Design
8 © 2012 PowerWorld Corporation T12: Wind Turbine
• Types 1 and 2- Induction machine models, stator windings are connected to the rest of the network, rotor currents are induced by the relative motion between the rotating magnetic field due to the stator currents and the rotor
• Slip is the difference between the synchronous speed and the rotor speed, defined using motor convention as
Wind Turbine Modeling
s r
s
n nSn−
=
• Synchronous speed is ns an rotor speed is nr, per unit Ra jXa
+
-
Vt
I jXm
jX1
R1/S
Equivalent circuit for a single cage induction machine
Glover, Sarma, Overbye, Power System Analysis and Design
9 © 2012 PowerWorld Corporation T12: Wind Turbine
Type 1 Wind Model- WT1G Power Speed Curve
Type 1 generators usually operate with a small negative slip since the wind turbine causes the machine to spin slightly faster than synchronous speed
Real Power
Real Pow er
Slip10.950.90.850.80.750.70.650.60.550.50.450.40.350.30.250.20.150.10.050-0.05-0.1-0.15-0.2-0.25-0.3-0.35-0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95
Rea
l Pow
er
2.8
2.6
2.4
2.2
2
1.8
1.6
1.4
1.2
1
0.8
0.6
0.4
0.2
0-0.2
-0.4
-0.6
-0.8
-1
-1.2
-1.4
-1.6
-1.8
-2
-2.2
-2.4
-2.6
-2.8
Values are calculated between a Slip of -1 and 1
10 © 2012 PowerWorld Corporation T12: Wind Turbine
• Type 2 models augment Type 1 by allowing for variable rotor resistance control in the wound rotor induction generator
• By using turbine speed and electrical power output as inputs to the control system, the wind turbine can provide a more steady power output during wind variation
Type 2 Wind Models
Real Power
Real Pow er
Slip10.950.90.850.80.750.70.650.60.550.50.450.40.350.30.250.20.150.10.050-0.05-0.1-0.15-0.2-0.25-0.3-0.35-0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95
Rea
l Pow
er
1.6
1.4
1.2
1
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1
-1.2
-1.4
-1.6
Real Power
Real Pow er
Slip10.950.90.850.80.750.70.650.60.550.50.450.40.350.30.250.20.150.10.050-0.05-0.1-0.15-0.2-0.25-0.3-0.35-0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.9-0.95
Rea
l Pow
er
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
-0.1
-0.2
-0.3
-0.4
-0.5
-0.6
-0.7
-0.8
-0.9
external resistance = 0.05
external resistance = 0.99 pu
11 © 2012 PowerWorld Corporation T12: Wind Turbine
• Models Doubly-Fed Asynchronous Generators (DFAGs) or Doubly-Fed Induction Generators (DFIGs)
• In addition to the stator windings, rotor windings are connected to the AC network through a converter
• Allows separate control of both real and reactive power • Allows a much wider speed range • No electrical coupling with the turbine dynamics • The DFAG dynamics are well approximated as a voltage-source
converter (VSC)
Type 3 Wind Models
V θ∠
jXeq
High/Low Voltage Management
1
eqX−
Isorc
Iq
Ip
Eq
I
Type 3 DFAG Model, Voltage Source Converter (VSC)
Output from reactive power control system
Network
Glover, Sarma, Overbye, Power System Analysis and Design
12 © 2012 PowerWorld Corporation T12: Wind Turbine
• Physically, these models usually consist of a wound rotor induction machine coupled with a voltage-source converter AC excitation system
• Electrical performance is dominated by the converter which acts on a much faster time scale than transient stability level dynamics – Machine model consists of a synthesized voltage behind a
reactance – Rotor dynamics are not important electrically
• Modeling – Represents the generator by a machine model – Reactive power control by an exciter model – Mechanical control by a governor model – Blade pitch control by a stabilizer model
Type 3 Wind Models
13 © 2012 PowerWorld Corporation T12: Wind Turbine
• Generator 3 will be modeled using a GEWTG machine, which models a 85 MW aggregation of GE 1.5 MW DFIGs
• Exciter model EXWTGE will be used to model the reactive power control of the wind turbine
• Governor model WNTDGE will be used to model the inertia of the wind turbine and its pitch control
• Generators 1 and 2 remain unchanged • Open the case which has these settings,
wscc_9bus_Type3WTG.pwb
Type 3 Wind Model Example
wscc_9bus_Type3WTG
14 © 2012 PowerWorld Corporation T12: Wind Turbine
States of Exciter\EField_Gen Bus1 #1 States of Exciter\Sensed Vt_Gen Bus1 #1States of Exciter\VR_Gen Bus1 #1 States of Exciter\VF_Gen Bus1 #1
20191817161514131211109876543210
2.5
2.4
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1
0.9
Mech Input_Gen Bus1 #1 MW Terminal_Gen Bus1 #1 Mech Input_Gen Bus 3 #1MW Terminal_Gen Bus 3 #1 Mech Input_Gen Bus 2 #1 MW Terminal_Gen Bus 2 #1
20191817161514131211109876543210
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
V (pu)_Bus Bus1 V (pu)_Bus Bus 2 V (pu)_Bus Bus 3V (pu)_Bus Bus 4 V (pu)_Bus Bus 5 V (pu)_Bus Bus 6V (pu)_Bus Bus 7 V (pu)_Bus Bus 8 V (pu)_Bus Bus 9
20191817161514131211109876543210
1.051
0.950.9
0.850.8
0.750.7
0.650.6
0.550.5
0.450.4
0.350.3
0.250.2
0.150.1
0.050
• Set up Plot Definitions as desired • Click “Run transient Stability”
Type 3 Wind Model Example
Wind turbine MW Mechanical input and terminal output Voltage recovery
Generator 3 EXWTGE states
wscc_9bus_Type3WTG
15 © 2012 PowerWorld Corporation T12: Wind Turbine
States of Governor\Pitch_Gen '3' '1'States of Governor\Pitch Control_Gen '3' '1'States of Governor\Pitch Compensation_Gen '3' '1'States of Governor\Mech Speed_Gen '3' '1'
20191817161514131211109876543210
3
2.8
2.6
2.4
2.2
2
1.8
1.6
1.4
1.2
1
0.8
0.6
0.4
0.2
0
• During the fault the wind turbine terminal bus voltage will be quite low. This will cause the turbine’s Low Voltage Power Logic (LVPL) to reduce the real power current to zero.
Type 3 Wind Model Example
• This will cause the wind turbine pitch control system to begin to pitch the blades to reduce the mechanical power into the rotor. This pitch control occurs slowly.
States of Governor\Turbine Pow er, Gen '1' '1'
20191817161514131211109876543210
0.158
0.156
0.154
0.152
0.15
0.148
0.146
0.144
0.142
0.14
0.138
0.136
0.134
0.132
0.13
0.128
0.126
0.124
0.122
0.12
• Once the fault is cleared, this current is ramped back up, subject to a rate limit.
Generator 1 Turbine Power
Pitch
wscc_9bus_Type3WTG
16 © 2012 PowerWorld Corporation T12: Wind Turbine
• The way load dynamics are modeled often has a significant impact on the results of transient stability studies
• So far, we have mostly been looking at generator models, but many load models are also available in Simulator
• The default (global) models are specified on the Options, Power System Model page as constant impedance loads – Used when no other model is specified – Discussed in the Transient Stability Basics section
• Simulator makes it very easy to add complex load models • More detailed models are added by selecting “Stability Case Info”
from the ribbon, then Case Information, Load Characteristics Models. • Models can be specified for the entire case (system), or individual
areas, zones, owners, buses or loads. • To insert a load model, right-click and select “Insert”
to display the Load Characteristic Information dialog.
Example: Impact of a Complex Load
17 © 2012 PowerWorld Corporation T12: Wind Turbine
• Add a CLOD model to the system – Go to the Load Characteristic page
in Model Explorer – Right-click and choose “insert” to
open the Load Characteristic information dialog
• In the dialog, click “System” in the Element Type box to apply the load model to all buses in the system
• Click “Insert” to select the model type. Use CLOD (see [1]), which models the load as a combination of large and small induction motors, constant power and discharge lighting loads
Complex Load Example
Applies at the system level
Insert a CLOD model
[1] J.A. Diaz de Leon II, B. Kehrli, “The Modeling Requirements for Short-Term Voltage Stability Studies,” Power Systems Conference and Exposition (PSCE), Atlanta, GA, October, 2006, pp. 582-588.
18 © 2012 PowerWorld Corporation T12: Wind Turbine
• The case with these settings is wscc_9bus_Type3WTG_CLOD • Run the simulation • Compare the plots obtained with and without the CLOD load
model
Complex Load Example
States of Governor\Turbine Pow er_Gen '1' '1'
20191817161514131211109876543210
0.1510.151
0.150.15
0.1490.1490.1480.1480.1470.1470.1460.1460.1450.1450.1440.1440.1430.1430.1420.1420.1410.141
0.140.14
0.139
V (pu)_Bus '1' V (pu)_Bus '2' V (pu)_Bus '3' V (pu)_Bus '4'V (pu)_Bus '5' V (pu)_Bus '6' V (pu)_Bus '7' V (pu)_Bus '8'V (pu)_Bus '9'
20191817161514131211109876543210
1.051
0.950.9
0.850.8
0.750.7
0.650.6
0.550.5
0.450.4
0.350.3
0.250.2
0.150.1
0.050
Plots after inserting system-level CLOD model
wscc_9bus_Type3WTG_CLOD
19 © 2012 PowerWorld Corporation T12: Wind Turbine
V (pu)_Bus Bus1 V (pu)_Bus Bus 2 V (pu)_Bus Bus 3V (pu)_Bus Bus 4 V (pu)_Bus Bus 5 V (pu)_Bus Bus 6V (pu)_Bus Bus 7 V (pu)_Bus Bus 8 V (pu)_Bus Bus 9
20191817161514131211109876543210
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
• On the Simulation page, increase the time for when the line is opened from 1.12 seconds to 1.155 seconds
• Open the Events tab on the Results page • The Transient Contingency events are
there, but there are also under voltage load trip events present
Complex Load Example
wscc_9bus_Type3WTG_CLOD
20 © 2012 PowerWorld Corporation T12: Wind Turbine
Mech Input_Gen Bus 2 #1 Mech Input_Gen Bus 3 #1 Mech Input_Gen Bus1 #1
Time (Seconds)20191817161514131211109876543210
Mec
hani
cal P
ower
(MW
)
160
140
120
100
80
60
40
20
0
Mech Input_Gen Bus 2 #1 Mech Input_Gen Bus 3 #1 Mech Input_Gen Bus1 #1
Time (Seconds)20191817161514131211109876543210
Mec
hani
cal P
ower
(MW
)
1601501401301201101009080706050403020
• In the PowerWorld CLOD model, under-voltage motor tripping may be set by the following parameters
– Vi = voltage at which trip will occur (default = 0.75 pu) – Ti (cycles) = length of time voltage needs to be below Vi before trip will occur
• In the example, under voltage trips occurred at bus 5 and bus 8 when the fault clearing time was increased to 1.155
• Verify that increasing the clearing time further to 1.2 causes additional under-voltage trips of loads at buses 6, and an over-frequency trip of Generator 2
Complex Load Example
cleared at 1.2 seconds Generator Pmech
cleared at 1.155 seconds
wscc_9bus_Type3WTG_CLOD
21 © 2012 PowerWorld Corporation T12: Wind Turbine
States of Exciter\EField_Gen Bus1 #1 States of Exciter\Sensed Vt_Gen Bus1 #1States of Exciter\VR_Gen Bus1 #1 States of Exciter\VF_Gen Bus1 #1
20191817161514131211109876543210
32.82.62.42.2
21.81.61.41.2
10.80.60.40.2
0-0.2
V (pu)_Bus Bus1 V (pu)_Bus Bus 2 V (pu)_Bus Bus 3V (pu)_Bus Bus 4 V (pu)_Bus Bus 5 V (pu)_Bus Bus 6V (pu)_Bus Bus 7 V (pu)_Bus Bus 8 V (pu)_Bus Bus 9
20191817161514131211109876543210
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
Complex Load Example
Voltages
Generator exciter states
Plots when fault is cleared at 1.2 seconds
Large and Small Induction Motor Loads experience under voltage trips at buses 5,6, and 8 at about 2 seconds after the line opens
Generator 2 opens due to over frequency at 4.2 seconds after the line recloses
wscc_9bus_Type3WTG_CLOD
22 © 2012 PowerWorld Corporation T12: Wind Turbine
• CLOD model under-voltage tripping can be turned off by setting its parameter Vi to zero
• Re-open the CLOD dialog, and set Vi to zero
Complex Load Example
• Run the simulation, clearing the fault at 1.2 seconds
• Compare the plots
Voltages with under-voltage tripping turned OFF
Voltages with under-voltage tripping turned ON (default)
wscc_9bus_Type3WTG_CLOD
V (pu)_Bus Bus1 V (pu)_Bus Bus 2 V (pu)_Bus Bus 3V (pu)_Bus Bus 4 V (pu)_Bus Bus 5 V (pu)_Bus Bus 6V (pu)_Bus Bus 7 V (pu)_Bus Bus 8 V (pu)_Bus Bus 9
20191817161514131211109876543210
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
V (pu)_Bus Bus1 V (pu)_Bus Bus 2 V (pu)_Bus Bus 3V (pu)_Bus Bus 4 V (pu)_Bus Bus 5 V (pu)_Bus Bus 6V (pu)_Bus Bus 7 V (pu)_Bus Bus 8 V (pu)_Bus Bus 9
20191817161514131211109876543210
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
Set to zero to turn off under-voltage tripping
Mech Input_Gen Bus 2 #1 Mech Input_Gen Bus 3 #1Mech Input_Gen Bus1 #1
Time (Seconds)20191817161514131211109876543210
Mec
hani
cal P
ower
(MW
)
1601501401301201101009080706050403020100
-10
23 © 2012 PowerWorld Corporation T12: Wind Turbine
• Completely asynchronous by design, called a “full converter model”
• The wind turbine’s output is completely decoupled from the network using an AC-DC-AC converter
• This decoupling allows considerable freedom in selecting what type of electric machine is used – Machine could be a conventional synchronous generator,
permanent magnet synchronous generator, or squirrel cage induction machine
– No electrical coupling with the turbine dynamics • Represented as a VSC, like Type 3, but with Ip and Iq as direct
control variables and without effective reactance • Modeled
– Machine/Exciter combination WT4G1/WT4E1 (PSSE) – Machine/Exciter/Governor WT4G, WT4E, and WT4T (PSLF)
Type 4 Wind Models