what's new in the title 24 2013 code? - california lighting

138
RESEARCH INNOVATION PARTNERSHIP 633 Pena Drive, Davis, CA, 95618 | cltc.ucdavis.edu | PH: 530-747-3838, FAX:530-747-3812 What’s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements Kelly Cunningham, Outreach Director [email protected] California Lighting Technology Center University of California, Davis RESEARCH INNOVATION PARTNERSHIP 633 Pena Drive, Davis, CA, 95618 | cltc.ucdavis.edu | PH: 530-747-3838, FAX:530-747-3812

Upload: others

Post on 11-Sep-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: What's New in the Title 24 2013 Code? - California Lighting

RESEARCH INNOVATION PARTNERSHIP 633 Pena Drive, Davis, CA, 95618 | cltc.ucdavis.edu | PH: 530-747-3838, FAX:530-747-3812

What’s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements

Kelly Cunningham, Outreach Director [email protected] California Lighting Technology Center University of California, Davis

RESEARCH INNOVATION PARTNERSHIP 633 Pena Drive, Davis, CA, 95618 | cltc.ucdavis.edu | PH: 530-747-3838, FAX:530-747-3812

Page 2: What's New in the Title 24 2013 Code? - California Lighting

Mission To accelerate the development and deployment of energy-efficient lighting and daylighting technologies in partnership with utilities, manufacturers, end users, builders, designers, researchers, academics, and governmental agencies.

MISSION-DRIVEN ACTIVITIES:

• Research & Development

• Demonstration & Outreach

• Education & Training

Page 3: What's New in the Title 24 2013 Code? - California Lighting

Lighting & Energy Efficiency Luminous Efficacy

– One time, long duration change – Reduction of baseline

• Light Source Efficacy • Luminaire Efficacy • Application Efficacy

Lighting Controls – Continuous, real-time change – Fluctuations from base line

• Occupancy / Vacancy • Daylighting • Demand Response • Tuning • Personal Control

Page 4: What's New in the Title 24 2013 Code? - California Lighting

Adaptive Lighting Systems…

automatically adjust their light output… – Total Luminous Flux – Spectral Power Distribution – Candle Power Distribution

based on sensor input from the space they serve…

– Occupancy / Vacancy – Daylight – DR Signals

to optimize space and building performance.

– Comfort – Energy Savings – Peak Demand Reduction

Page 5: What's New in the Title 24 2013 Code? - California Lighting

Integrated Control Strategy

During occupancy focus on comfort – Adjust fenestration for daylight penetration

– Adjust electric lighting for daylight contribution

– Offer manual control options

– Adjust electric lighting for demand response signal

– Adjust HVAC

During vacancy focus on energy efficiency – Adjust fenestration for cooling/heating loads

– Turn electric lighting off or dim down

– Adjust electric lighting for demand response signal

– Adjust HVAC

Page 6: What's New in the Title 24 2013 Code? - California Lighting

General Requirement Updates

Page 7: What's New in the Title 24 2013 Code? - California Lighting

Navigating the 2013 Code

Occupancies Mandatory Prescriptive Performance Additions

General Provisions 100.0, 100.1, 100.2, 110.0, 110.10

Nonresidential, High-Rise Residential, and Hotels/Motels

General 140.0 140.2 140.1 141.0

Indoor Lighting (conditioned)

110.9, 120.8, 130.0, 130.1, 130.4 140.3 (c), 140.6 140.1 141.0

Indoor Lighting (unconditioned)

110.9, 120.8, 130.0, 130.1, 130.4 140.3 (c), 140.6 NA 141.0

Outdoor Lighting 110.9, 130.0, 130.2, 130.4 140.7 NA 141.0

Signs

Indoor and Outdoor 130.0, 130.3 140.8 NA 141.0

Low-Rise Residential

General 150.0 150.1 (a,c) 150.1(a,b) 150.2

Indoor Lighting 110.9, 130.0, 150.0 (k) 150.1 (a,c) 150.1(a,b) 150.2

Outdoor Lighting 110.9, 130.0, 150.0 (k) 150.1 (a,c) 150.1(a,b) 150.2

Page 8: What's New in the Title 24 2013 Code? - California Lighting

The Core Process

1. Plan for all mandatory requirements

2. Choose either prescriptive or performance approach

3. Calculate allowed lighting power for chosen method

4. Calculate proposed installed lighting power including applicable controls credits

If proposed installed lighting power is LESS than the allowed lighting power, the space is Title 24 compliant!

Page 9: What's New in the Title 24 2013 Code? - California Lighting

Navigating the 2013 Code

Mandatory Measures (Sections 120.0 through 130.5) Measures required regardless of compliance method selected. These requirements are enforced for all newly constructed nonresidential buildings, high-rise residential buildings, hotels/motels that are mechanically heated or mechanically cooled, and all building additions or alterations.

Performance Approach (Section 140.1) Allows compliance through a variety of design strategies and provides greater flexibility than the prescriptive approach. These requirements are applicable when the building designer uses an energy commission-certified compliance software program to demonstrate that the proposed building energy consumption, including lighting power, meets the energy budget.

Prescriptive Approach (Sections 140.2 through 140.8) Each individual energy component of the proposed building must be a prescribed minimum efficiency. This approach offers less design flexibility, but is simpler to implement. There are three possible approaches to allowed lighting power under the prescriptive approach: the Complete Building Method, the Area Category Method, and the Tailored Method.

Page 10: What's New in the Title 24 2013 Code? - California Lighting
Page 11: What's New in the Title 24 2013 Code? - California Lighting
Page 12: What's New in the Title 24 2013 Code? - California Lighting

PRIMARY FUNCTION AREA ALLOWED LIGHTING

POWER (W/ft2)

2013 2008

Office Area: >250 square feet 0.75 0.9

<250 square feet 1 1.1 Parking Garage Area: Parking Area 0.14 0.2

Dedicated Ramps 0.3 0.6

Retail Merchandise Sales, Wholesale Showroom Areas 1.2 1.6

Selected changes from 2008 – 2013

Page 13: What's New in the Title 24 2013 Code? - California Lighting

Power Adjustment Factors

The wattage of installed lighting may be reduced by the product of the number of watts controlled times the applicable Power Adjustment Factor when calculating the installed lighting power for that space.

Example:

– A 500 sf open office uses 500W of lighting. If occupant sensing controls are used (PAF = 0.2), that office is then considered to have:

– 500W – (500W*0.2) = 400W of installed lighting power

Page 14: What's New in the Title 24 2013 Code? - California Lighting

PAFs for 2013 code: Table 140.6-A

Page 15: What's New in the Title 24 2013 Code? - California Lighting

More alterations will be required to meet new-construction standards for both lighting power density (LPD) and mandatory controls.

Exceptions do exist for buildings with fewer than 40 ballasts being replaced and spaces where less than 10% of the lighting is affected.

Consistent with proposed changes to ASHRAE 90.1-2010

Alterations

Page 16: What's New in the Title 24 2013 Code? - California Lighting

Luminaire alterations

Page 17: What's New in the Title 24 2013 Code? - California Lighting

Modifications-in-place

New category added: Luminaire modifications-in place

– Replace lamps & ballasts (preserve luminaire listing)

– Changing the number of light sources IN the luminaire

– Optical system changes

– Replace whole luminaire, one-for-one

Page 201 in code

If the modification is part of a larger remodel or the luminaire moves, this is not a valid category

Page 18: What's New in the Title 24 2013 Code? - California Lighting

Luminaire modifications-in place

Page 19: What's New in the Title 24 2013 Code? - California Lighting

Luminaire modifications-in place are NOT

Without these …

These …

Images: Lutron

Image: ChinaLEDLight.biz

Page 20: What's New in the Title 24 2013 Code? - California Lighting

What should they look like?

20

Source Luminaire Controls + +

Image: Cree Image: Cree Image: Enlighted

Page 21: What's New in the Title 24 2013 Code? - California Lighting

Certification and Permit Process

Page 22: What's New in the Title 24 2013 Code? - California Lighting

Building Commissioning

Must be included in the design and construction process for all nonresidential buildings

– Design Phase: Design Review – Document commissioning measures in construction documents

For buildings larger than 10,000 sf, additional measures are required

– Summary of Commissioning Requirements – Owner’s Project Requirements document – Basis of Design document – Commissioning Plan – Functional Acceptance Test Reports – System Document and Training documents – System Operations Training – Commissioning Report

Page 23: What's New in the Title 24 2013 Code? - California Lighting

Expanded Acceptance Test Requirements

Lighting controls acceptance test technicians must be Certified Lighting Controls Acceptance Test Technicians (CLCATT)

Acceptance tests expanded

– Automatic Daylighting Controls

– Indoor Shut-off controls

– Demand Response Controls

– Outdoor Shut-off Controls

Page 24: What's New in the Title 24 2013 Code? - California Lighting

Expanded Acceptance Test Requirements

Industry Coverage by Certification Provider(s). The Certification Provider(s) approved by the Energy Commission, in their entirety, shall provide reasonable access to certification for technicians representing the majority of the following industry groups: electrical contractors, certified general electricians, professional engineers, controls installation and start-up contractors and certified commissioning professionals who have verifiable training, experience and expertise in lighting controls and electrical systems. The Energy Commission will determine whether in their entirety reasonable access to certification is provided by considering factors such as certification costs commensurate with the complexity of the training being provided, certification marketing materials, prequalification criteria, class availability, and curriculum.

Page 25: What's New in the Title 24 2013 Code? - California Lighting

Acceptance Test Technicians

For all lighting controls requiring acceptance testing, alterations and new constructions:

– Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of Part 6.

– Automatic daylight controls comply with Section 130.1(d) and NA7.6.1.

– Lighting shut-OFF controls comply with Section 130.1(c) and NA7.6.2.

– Demand responsive controls comply with Section 130.1(e) and NA7.6.3.

– Outdoor lighting controls comply with the applicable requirements of Section 130.2(c) and NA7.8.

Image: Lutron

Page 26: What's New in the Title 24 2013 Code? - California Lighting

Electrical Power Distribution Systems

New chapter!

– Service metering

– Disaggregation of circuits

– Voltage drop

– Receptacle control

– DR

– EMCS

Requirements start at > 50 kVA

See Table 130.5-B

Page 27: What's New in the Title 24 2013 Code? - California Lighting

Demand Response

• Buildings > 10,000 ft2

• Alterations that increase the connected load within a space in a building that > 10,000 ft2

• Reduce lighting power at least 15%

• Spaces that are non-habitable or with a lighting power density of < 0.5 W/ft2 shall not be used to comply with the DR requirement

In the code: 130.1 (e)

Page 28: What's New in the Title 24 2013 Code? - California Lighting

Mandatory Device Requirements

Lighting devices regulated by California Appliance Efficiency Standards, Title 20 and Certified to the Energy Commission:

– Fluorescent lamp ballasts

– Lighting control devices and lighting control systems

– Track lighting: integral current limiters and supplementary overcurrent protection panel

– High efficacy LED light sources

– Ballasts for residential recessed luminaires

RE

S S

PEC

IFIC

Page 29: What's New in the Title 24 2013 Code? - California Lighting

Indoor Lighting Controls Requirements

Page 30: What's New in the Title 24 2013 Code? - California Lighting

Mandatory Device Requirements

Majority of lighting control devices are now regulated by the California Appliance Efficiency Standards, Title 20:

– Time switch controls – Daylighting controls – Dimmers – Occupant sensing devices – Part-night outdoor lighting controls

Page 31: What's New in the Title 24 2013 Code? - California Lighting

Area controls

• All luminaires must have manual switching

• Each area of a building must be separately controlled

– An area is defined by floor-to-ceiling partitions

• Up to 0.2 watts of egress lighting may remain on during occupied times.

– Down from 0.3 watts in 2008

Page 32: What's New in the Title 24 2013 Code? - California Lighting

Area controls

• Controls must be readily accessible and located in the same area as or viewable from the controlled lighting

• If controlling dimmable luminaires, dimmer switch must allow manual on and off in addition to dimming

• A few exceptions: large retail, industrial and entertainment venues as well as public bathrooms with 2+ stalls

Page 33: What's New in the Title 24 2013 Code? - California Lighting

Separately controlled lighting systems

• General lighting must be separately controlled

• Floor and wall display, window display, case display, ornamental, and special effects lighting must be separately controlled

• Track lighting: general, display, ornamental, and special effects lighting must be separately controlled

Image credit: Acuity

Page 34: What's New in the Title 24 2013 Code? - California Lighting

Multi-level lighting control requirements

Changes from 2008:

• Areas with LPD greater than 0.5 W/sf now, was 0.8 W/sf

• Requirements based on source type, was only one

control step between 30% and

70% of full output

• Additional control strategy required, previously no additional

requirements

• There are some exceptions

Page 35: What's New in the Title 24 2013 Code? - California Lighting

Multi-level lighting controls: 2013 details

Areas ≥ 100 ft2 with connected lighting load > 0.5 W/ft2 must meet control and uniformity requirements of Table 130.1-A

Must also use one of the following control strategies:

• Manual dimming • Lumen maintenance • Tuning • Automatic daylighting • Demand response

Page 36: What's New in the Title 24 2013 Code? - California Lighting

Lumen Maintenance

“a strategy used to provide a precise, constant level of lighting from a lighting system regardless of the age of the lamps or the maintenance of the luminaires.”

Compares the amount of light currently produced to the amount of light produced when the luminaire was brand new

Often specified as L70 – the number of hours it takes for the lumen output to shrink to 70% of initial output

36

Page 37: What's New in the Title 24 2013 Code? - California Lighting

Tuning

“the ability to set maximum light levels at a lower level than full lighting power.”

Project spotlight: Davis downtown café sets maximum light levels for all luminaires at 70% of full power to curb over-lighting

Download the project overview: http://cltc.ucdavis.edu/publication/brighter-brew-mishkas-cafe-makes-switch-leds

37

Page 38: What's New in the Title 24 2013 Code? - California Lighting

Table 130.1-A

Page 39: What's New in the Title 24 2013 Code? - California Lighting

What does multi-level lighting look like?

+ Sensor Luminaire

Image: Wattstopper

Image: Cree

Page 40: What's New in the Title 24 2013 Code? - California Lighting

What does multi-level lighting look like?

Sensor integrated with luminaire

Image: Finelite

Page 41: What's New in the Title 24 2013 Code? - California Lighting

What does multi-level lighting look like?

Networked system

Image: Enlighted

Page 42: What's New in the Title 24 2013 Code? - California Lighting

What does multi-level lighting NOT look like?

Page 43: What's New in the Title 24 2013 Code? - California Lighting

Multi-level exceptions

Classrooms with connected load of ≤ 0.7 W / ft2 must have at least one control step between 30–70% of full power.

Areas with only one luminaire and no more than two lamps are exempt

Page 44: What's New in the Title 24 2013 Code? - California Lighting

Shut-off Controls

Indoor lighting must have controls that:

– Automatically turn off lighting when unoccupied

– Controls each floor of a building separately

– Controls each space of a building separately

Shut-off controls exceptions

– Where the lighting is in use 24/7, 365 days a year

– Lighting for emergency egress

– Electrical equipment rooms

Page 45: What's New in the Title 24 2013 Code? - California Lighting

Occupant sensing controls required to shut off all lighting when area is vacant

– Offices 250 ft2 or smaller

– Multipurpose rooms 1000 ft2 or smaller

– Classrooms

– Conference rooms

Page 46: What's New in the Title 24 2013 Code? - California Lighting

Egress

Reduced exception for egress lighting

2008: 0.3 W/sf anywhere

2013: Maximum security and egress lighting allowance of 0.2 W/sf when a building is occupied

– General and egress lighting must be shut off during unoccupied times

– Exception: Offices are allowed up to 0.05 W / ft2 for lighting during unoccupied periods, but only along emergency egress areas designated on the building plans

Page 47: What's New in the Title 24 2013 Code? - California Lighting

Time-switch controls

• Countdown timer switches may only be used in:

– Single-stall bathrooms < 70 ft2

– Closets < 70 ft2

– Aisles in server rooms, max 30 min time out

• Automatic time-switch controls:

– Lighting to remain on for no more than two hours

– Must have an automatic holiday shut-off

– Does not apply to retail spaces, restaurants, grocery stores, churches, and theatres

Page 48: What's New in the Title 24 2013 Code? - California Lighting

Time-switch controls

If an automatic time-switch control, other than an occ sensor, is used to comply with this section it should have an override that :

– Allows lighting to remain on for no more than two hours

• Does not apply to retail spaces, restaurants, grocery stores, churches, and theatres

– Has an automatic holiday shut-off

• Exception: retail stores, places of worship, theaters (i.e. places where people go on holidays)

Page 49: What's New in the Title 24 2013 Code? - California Lighting

Guest rooms in hotels / motels

Key card activated hotel and motel guest rooms: Lighting OFF after 30 minutes

Hotel/motel rooms: allows for one high efficacy luminaire with a switch within 6 ft of door

Page 50: What's New in the Title 24 2013 Code? - California Lighting

Partial ON/OFF: Changes from 2008

Specific requirements for partial ON/OFF occupancy sensors; none required in 2008

– Parking garages – Other indoor parking areas – Indoor loading and unloading zones – Library book stacks* – Stairwells and corridors* – Warehouse aisle ways and open areas*

* in addition to automatic time switch controls

Page 51: What's New in the Title 24 2013 Code? - California Lighting

100% Power 25 fcd

40% Power 13 fcd

20% Power 4.0 fcd

Adaptive corridor with multi-level controls

Page 52: What's New in the Title 24 2013 Code? - California Lighting

Case Study: Latham Square, Oakland, CA

• Commercial office building in downtown Oakland

• 14 stories and 130,000 ft2

• Case study install on 12 floors

• Corridor occupancy rate: 8%

• 175 luminaires replaced in corridors

• 86% reduction in energy use

– 113,724 kWh annually

– $23,803 in energy and maintenance costs over the life of the fixtures

Page 53: What's New in the Title 24 2013 Code? - California Lighting

Reduce to at least 50% on vacancy

Areas where partial ON/OFF occupant sensing controls are required in addition to partial OFF:

– Stairwells

– Corridors

– Aisle ways and open areas in warehouses

– Library book stack aisles, 10 feet or longer

Page 54: What's New in the Title 24 2013 Code? - California Lighting

Reduce on vacancy, rather than off

Areas where partial ON/OFF occupant sensing controls are required instead of partial OFF:

– ≥ 50% reduction: Stairwells and common area corridors in high-rise residential buildings and hotel/motels

– One step between 20-50%: Indoor parking and loading/unloading areas

• Control ≤ 500W per zone

Image credit: Philips

Page 55: What's New in the Title 24 2013 Code? - California Lighting

Exceptions: Reduce on vacancy, rather than off

Areas where partial ON/OFF occupant sensing controls are required instead of partial OFF:

– Stairwells: Where lighting power ≤ 80% the allowed power, 40% reduction is OK

– Parking/loading: metal halide with a lamp + ballast mean efficacy of > 75 lm/w, one control step from 20-60% OK

Page 56: What's New in the Title 24 2013 Code? - California Lighting

UC Davis: Bi-level Stairwells UC Davis installed 999 LED units

Assumed 20% occupancy rate

22W high / 5W low

PIR sensor times out after 5 min

Energy use reduction: 85%

7,008 hours in standby mode

1,752 hours in active mode

Page 57: What's New in the Title 24 2013 Code? - California Lighting

UC Davis: Adaptive Stairwells

Incumbent technology:

Page 58: What's New in the Title 24 2013 Code? - California Lighting

Campus Stairwell Demonstrations

LaMar Voyager Bi-Level (VOB) Fixture

Average Energy Savings: 50%

Page 59: What's New in the Title 24 2013 Code? - California Lighting

Reduce to at least 40% power on vacancy

Aisle ways and open areas in warehouses where installed lighting power ≤ 80% the value allowed under the Area Category Method

Accommodates MH or HPS lighting in warehouses Image credit: Philips

Image credit: Philips

Page 60: What's New in the Title 24 2013 Code? - California Lighting

Daylighting Controls: Changes from 2008

• Manual controls requirement removed; automatic controls now required in all spaces

• Area size exemptions removed

• Calculation method for daylit zones = simplified!

• Parking garages are now included; previously exempt

Page 61: What's New in the Title 24 2013 Code? - California Lighting

Minimum daylighting for large spaces

Large enclosed spaces, such as large retail warehouses, are required to have a minimum amount of daylight available. The minimum requirements apply to both conditioned and unconditioned spaces that are:

1. In Climate Zones 2–15 2. Have a floor area greater than 5,000 sq ft 3. Have a ceiling height greater than 15 ft 4. Have a general LPD greater than 0.5 W/sq ft

Buildings that meet the above criteria must have: • At least 75% of the floor space of

the building in a primary sidelit zone or skylit zone

• No more than 5% of the roof area may contain skylights

Section 140.3 (c)

Page 62: What's New in the Title 24 2013 Code? - California Lighting

Daylight Zones

Regions within a building that are close enough to a source of daylight that daylight harvesting is possible are considered within a “daylight zone.”

• Skylit Zone: An area illuminated by one or more skylights

• Primary Sidelit Zone: A daylit area directly adjacent to one or more windows

• Secondary Sidelit Zone: An area not directly adjacent to a window that still receives some daylight through its proximity to the window

All daylight zones must be marked on the building floor plans.

Section 130.1 (d)1

Page 63: What's New in the Title 24 2013 Code? - California Lighting

Skylit Zone

When determining the skylit zone, the shape of the zone is the same as the geometric shape of the opening of the skylight. For example, a rectangular skylight creates a rectangular daylight zone, and a circular skylight creates a circular zone.

Calculation Steps:

1. Multiply the average ceiling height of the building by 0.7

2. Add this value in all directions around the skylight (starting at the edge of the rough opening)

3. Subtract any area in which a permanent obstruction would block daylight (taller than half the distance from the floor to the bottom of the skylight)

Section 130.1 (d)1

Page 64: What's New in the Title 24 2013 Code? - California Lighting

Calculating the Skylit Zone

Section 130.1 (d)1

Page 65: What's New in the Title 24 2013 Code? - California Lighting

Primary Sidelit Zone

The primary sidelit zone is directly adjacent to windows and projects inside the space a certain distance.

Calculation Steps

1. Determine the window head height for each window

2. The length of the zone is one window head height into the area adjacent to the window

3. The width of the zone is the width of the window plus half the window head height one each side of the window

4. Subtract any area on a plan that is blocked by a permanent obstruction that is six feet or taller.

Window Head Height = Vertical distance from the finish floor level to the top of a window.

Section 130.1 (d)1

Page 66: What's New in the Title 24 2013 Code? - California Lighting

Secondary Sidelit Zone

Secondary sidelit zones are extensions of primary sidelit zones. They represent areas where daylight is present but may provide less illumination because of their distance from windows.

Calculation Steps

1. Add one additional window head height to the same dimensions determined for the primary sidelit zone

2. Subtract any area that is blocked by a permanent obstruction that is six feet or taller

Section 130.1 (d)1

Page 67: What's New in the Title 24 2013 Code? - California Lighting

Calculating the Sidelit Zones

Section 130.1 (d)1

Page 68: What's New in the Title 24 2013 Code? - California Lighting

Daylighting Controls

• Luminaires in primary sidelit and skylit areas must have photocontrols

• Luminaires that fall in both sidelit and skylit zones are controlled by skylit zone

• Show primary sidelit and skylit zones on the plans

• When using the prescriptive method, the automatic daylighting controls requirements for primary sidelit zones also apply to general lighting luminaires that are at least 50% in a secondary sidelit zone.

Page 69: What's New in the Title 24 2013 Code? - California Lighting

Daylighting Controls

• Daylit zones should be controlled with the multi-level steps in Table 130.1-A unless LPD < 0.3 W/sf

• Light levels provided at night should be available at all other times

• When sufficient daylight is available, lighting power must be reduced by at least 65%

Page 70: What's New in the Title 24 2013 Code? - California Lighting

Wow. That’s a lot. EVERYWHERE?

Exceptions: Multi-level controls are not required when

• Controlled lighting LPD < 0.3 W/ft2

• Skylights are replaced or added but general lighting is not altered

• Rooms with < 120 W in the daylit zones

• Rooms with a total glazing of < 24 ft2

Page 71: What's New in the Title 24 2013 Code? - California Lighting

Daylighting for Parking Garages

• Show primary and secondary zones on plans

• Automatic controls required in both primary and secondary zones, control each zone separately

• When ample daylight is available in primary zone, lighting power consumption = ZERO

• There are partial on/off requirements for occupancy as well (at least one step, 20–50%)

Page 72: What's New in the Title 24 2013 Code? - California Lighting

Controls for Parking Garages

General lighting must have at least one control step from 20–50% of design lighting power

No more than 500 W of rated lighting power controlled together

Parking garage areas with ≥ 36 ft2 of glazing or opening must have automatic daylighting controls.

Images Courtesy of Lithonia Lighting

Page 73: What's New in the Title 24 2013 Code? - California Lighting

Sign Lighting Controls

Indoor:

– Automatic time-switch OR astronomical time-switch control

Outdoor:

– Photocontrol + automatic time-switch OR astronomical time-switch control

– Outdoor signage that is on day and night must be capable of dimming by 65%.

Electronic Message Center (EMC)

– EMCs with a > 15 kW load shall be DR enabled to reduced ≥ 30%

Page 74: What's New in the Title 24 2013 Code? - California Lighting

Outdoor Lighting Control Requirements

Page 75: What's New in the Title 24 2013 Code? - California Lighting

Additions and Alterations

Any alteration that increases the connected lighting load must meet all mandatory, prescriptive, or performance measures that are required.

Section 141.0 (b)2J

No req. Mandatory Controls §130.0, 130.2, 130.4

+ Performance/Prescriptive

Requirements Lighting power density allowances of §140.7

Mandatory Controls §130.0, 130.2, 130.4

Page 76: What's New in the Title 24 2013 Code? - California Lighting

Outdoor lighting

• Title 24 2008 required photocontrol devices for all outdoor lighting.

• In addition to photocontrols, the 2013 standards require automatic scheduling controls

– Astronomical time-switch controls allowed as an alternative to photocontrol devices.

• Outdoor lighting must be circuited and independently controlled from other electric loads.

Page 77: What's New in the Title 24 2013 Code? - California Lighting

Lighting mounted ≤ 24 ft above the ground

Motion controls required: • Automatic lighting controls with auto-on when the areas are occupied

• Automatic step dimming or continuous dimming when areas are vacant

• No more than 1,500 W of lighting with a mounting height of 24 ft and under may be controlled together

Full Dimmed Images Courtesy of Lithonia Lighting

Page 78: What's New in the Title 24 2013 Code? - California Lighting

Outdoor lighting ≤ 24 ft

A few exceptions apply:

• Pole-mounted luminaires with a maximum rated wattage of 75 W

• Non-pole-mounted luminaires with a maximum rated wattage of 30 W

• Linear lighting with a maximum rated wattage of 4 W per linear ft. of luminaire

Page 79: What's New in the Title 24 2013 Code? - California Lighting

Frontage areas, lots, sales canopies

A part-night outdoor lighting control, or

Auto-on motion sensor that automatically reduces lighting power by at least 40% when spaces are vacant

Images Courtesy of Lithonia Lighting

Page 80: What's New in the Title 24 2013 Code? - California Lighting

Frontage areas, lots, sales canopies

A part-night outdoor lighting control must have all of the following:

– sunrise and sunset prediction accuracy within +/- 15 minutes and timekeeping accuracy within five minutes per year

– ability to setback or turn off lighting at night as required in Section 130.2(c), by means of a programmable timeclock or motion sensing device

– when controlled with a timeclock, capable of being programmed to allow the setback or turning off of the lighting to occur as determined by the user

Page 81: What's New in the Title 24 2013 Code? - California Lighting

Facades, outdoor dining, ornamental

A part-night outdoor lighting control, or

Auto-ON motion sensors that reduce lighting power by at least 40% but no more than 80%, or

A centralized time-based zone lighting control capable of automatically reducing lighting power by at least 50%

Image Courtesy of Lithonia Lighting

Page 82: What's New in the Title 24 2013 Code? - California Lighting

Outdoor lighting

All outdoor incandescent luminaires rated over 100 W and installed for non-residential use must be controlled by a motion sensor in addition to photocontrols and scheduling controls.

Left and Right Images Courtesy of Lithonia Lighting

Page 83: What's New in the Title 24 2013 Code? - California Lighting

(Backlight), Uplight and Glare Control

2013 code requires all outdoor luminaires ≥ 150 W to comply with the IES BUG system for assessing and limiting backlight, uplight and glare.

There are no Backlight requirements in Section 130.2 of Part 6

Change from the older cutoff system in 2008 standards, which applied to luminaires ≥ 175 W

Page 84: What's New in the Title 24 2013 Code? - California Lighting

Backlight, Uplight, and Glare (BUG) ratings

The BUG system is used to evaluate luminaire performance in relation to lighting trespass, sky glow, and high angle brightness. This is necessary in order to reduce light pollution, which has a negative effect on wildlife and the surrounding environments.

Backlight: includes all illumination that is in the space between the ground and 80 degrees above ground. Backlighting causes light trespass, which occurs when light is cast in unwanted areas due to poor control.

Uplight: is defined as all light spanning across the sky. This causes artificial sky glow, the illumination of the night sky due to excess lighting.

Glare: is any overlapping light between the uplight and the backlight which can be visually disabling and offensive.

Page 85: What's New in the Title 24 2013 Code? - California Lighting

Uplight Control

Where can I find OLZ definitions? Section 10-114 – Determination of outdoor lighting zones and administrative rules for use Table 10-114-A – Lighting zone characteristics and rules for amendments by local jurisdictions Page 32-33

Page 86: What's New in the Title 24 2013 Code? - California Lighting

Glare Control

Page 87: What's New in the Title 24 2013 Code? - California Lighting

Residential Requirements

Page 88: What's New in the Title 24 2013 Code? - California Lighting

2008 Title 24 Standards by Area

• LIGHTING DESIGN GUIDE Kitchen • > 50% of installed wattage must be high efficacy

Bathroom, garage, laundry room, utility room, closets

• High efficacy or • Manual-on vacancy sensor

All other interior rooms • High efficacy or • Manual-on vacancy sensor or • Dimmer

Outdoor Lighting

• High efficacy or • Low efficacy controlled by a manual on/off switch and both:

• Motion sensor without bypass switch and • One of the following: integral photocontrol, astronomical time

clock, energy management control system

Common Areas • High efficacy or vacancy sensor

Residential Parking

• Lots for < 7 cars must comply with Outdoor Lighting requirements • Garages for < 7 cars must comply with Garage requirements • Lots and garages for more than 7 vehicles must comply with

Nonresidential Lighting Standards

Page 89: What's New in the Title 24 2013 Code? - California Lighting

2013 Title 24 Standards by Area

• LIGHTING DESIGN GUIDE Kitchen • > 50% of installed wattage must be high efficacy

Bathroom • One high efficacy fixture and • Manual-on vacancy sensor or high efficacy for all other fixtures

Garage, laundry room, utility room, closets

• High efficacy and • Manual-on vacancy sensor

All other interior rooms • High efficacy or • Manual-on vacancy sensor or • Dimmer

Outdoor Lighting

• High efficacy or • Low efficacy controlled by a manual on/off switch and both:

• Motion sensor without bypass switch and • One of the following: integral photocontrol, astronomical time

clock, energy management control system

Common Areas

• High efficacy or vacancy sensor in areas where common space ≤ 20% of floor area

• In common areas that > 20% of floor area, occupancy responsive adaptive corridor and stairwell lighting is required

Residential Parking

• Lots for < 7 cars must comply with Outdoor Lighting requirements • Garages for < 7 cars must comply with Garage requirements • Lots and garages for 8 vehicles or more must comply with

Nonresidential Lighting Standards

Page 90: What's New in the Title 24 2013 Code? - California Lighting

High efficacy, by the code

Page 91: What's New in the Title 24 2013 Code? - California Lighting

High efficacy, by the code

What is never high efficacy?

• Any luminaire that does not qualify by Energy Commission definition or is not certified to the Commission

• Any luminaire containing medium screw-base socket (E24/E26)

• Any luminaire containing any line-voltage lamp socket (except GU-24 under certain conditions)

• Track lighting where track heads or lamps can be changed to a source other than LED

2013 High Efficacy: LED

Lamp Power Min. System Efficacy

5W or less 30 lm/W

5W – 15W 45 lm/W

15W – 40W 60 lm/W

Over 40W 90 lm/W

Page 92: What's New in the Title 24 2013 Code? - California Lighting

Appendix JA8

• Joint Appendix JA8 of the 2013 code sets new quality standards for LED luminaires designed for residential use.

• To qualify as high efficacy, CRI ≥ 90, and a CCT of 2700K – 4000K

Page 93: What's New in the Title 24 2013 Code? - California Lighting

Two strategies, three main technologies

High-efficacy luminaires are designed and built to operate only energy-efficient light sources, such as fluorescent T8 lamps, compact fluorescent lamps (CFLs), LEDs and high intensity discharge (HID) lamps.

Occupancy/vacancy sensors and daylight sensors are all devices that automatically turn lights off (or dim them) in response to conditions that they “sense” or “see.”

Dimmers, which are already common in many residential applications, allow room occupants to lower lighting levels (and thus energy use) as desired.

Con

trols

S

ourc

es

Page 94: What's New in the Title 24 2013 Code? - California Lighting

2013 High Efficacy, According to the Standards

In the 2013 code: Table 150.0-A and Section 150(k) 1

Page 95: What's New in the Title 24 2013 Code? - California Lighting

Efficacy = initial lumens ÷ luminaire total rated system input power

What is never high efficacy?

• Any luminaire that does not qualify by Energy Commission definition or is not certified to the Commission

• Any luminaire containing medium screw-base socket (E24/E26)

• Any luminaire containing any line-voltage lamp socket (except GU-24 under certain conditions)

• Track lighting where track heads or lamps can be changed to a source other than LED

2013 High Efficacy, According to the Standards

2013 high efficacy: other sources

Lamp Power Min. System Efficacy

5W or less 30 lm/W

5W – 15W 45 lm/W

15W – 40W 60 lm/W

Over 40W 90 lm/W

In the 2013 code: Table 150.0-A and 150.0-B and Section 150(k) 1

Page 96: What's New in the Title 24 2013 Code? - California Lighting

Energy Commission Appliances Database

http://www.appliances.energy.ca.gov/AdvancedSearch.aspx

Page 97: What's New in the Title 24 2013 Code? - California Lighting

IES Illuminance Recommendations

Category Space Illuminance

A Public spaces 3 footcandles (30 lux)

B Simple orientation for short visits 5 footcandles (50 lux)

C Working spaces where simple visual tasks are performed 10 footcandles (100 lux)

D Performance of visual tasks of high contrast and large size 30 footcandles (300 lux)

E Performance of visual tasks of high contrast and small size, or visual tasks of low contrast and large size

50 footcandles (500 lux)

F Performance of visual tasks of low contrast and small size 100 footcandles (1,000 lux)

G Performance of visual tasks near threshold

300 to 1,000 footcandles (3,000 to 10,000 lux)

Page 98: What's New in the Title 24 2013 Code? - California Lighting

Examples of Illuminance Levelsv

Category Building Types

A (3fc) Movie theater, observatory

B (5fc) Public auditorium, night club, arcade

C (10fc) Art gallery, restaurant, parking garage, public restroom

D (30fc) Coliseum/arena, school gymnasium, chapel, grocery store, commercial building

E (50fc) School, medical laboratory, computer processing office, vehicle repair center

F (100fc) Hospital facilities, veterinary clinic

G (800fc) Operating table

Page 99: What's New in the Title 24 2013 Code? - California Lighting

High-Efficacy Luminaires

Light Emitting Diodes • Newer technology with a great deal

of confusion

• Efficacies are improving

• Quality is not consistent

• Look for product that clearly meets lumen/Watt requirements

• Follow the Design Lights Consortium Qualified Products List for non-res product evolution

• Follow utility rebate program guidelines for res products

Typically Compliant • High-efficacy fixtures with

electronic ballasts

• Pin-based CFL fixtures with electronic ballasts (4 pin)

• Fixtures with high-intensity discharge (HID) lamps

Not Usually Compliant • Any fixture with

incandescent lamps

• Any fixture with a screw base, regardless of what source it is (even CFL or LED!)

Note: Ballast wattage is not included when determining lamp efficacy.

Page 100: What's New in the Title 24 2013 Code? - California Lighting

Replacement Lamp Technologies in Use

A

BR

PAR

CFL

LED A*

Wattage 40-100 W 30-150 W 50-150 W 5-40 W 2.3-23 W

Efficacy 10-17 lm/W 7-12 lm/W 6-15 lm/W 50-70 lm/W 33-97 lm/W

Price** < $1 $4-7 $6-8 $1-8 $10-50

Application General Lighting Downlights, Spotlights

Downlights, Spotlights

General Lighting

General Lighting

*August 17, 21013 Product review of 286 A-lamps listed in the Lighting Facts database **Approximate price ranges

Page 101: What's New in the Title 24 2013 Code? - California Lighting

Choosing the Right Luminaire

Specify the right lumens/watt ratio • Depending on what lamp wattage is

chosen (with the same number of fixtures) you could have a much brighter space or a much darker space in comparison to an existing incandescent space.

For example:

8 (65 watt) BR lamps x 750 lumens = 7100 lumens

5 (26 watt) CFL lamps x 1300 lumens = 6500 lumens

10 (13 watt) CFL lamps x 600 lumens = 6000 lumens

Specify the appropriate light output • You should be able to “lumen

match” the low-efficacy fixtures by specifying systems that use less

• Warmer lamp colors (CCT 2700–3000K) are the closest match to incandescent.

2013 Update • In the 2013 code, in order to

qualify as high efficacy, LED luminaires must be > 90 CRI and 2700–4000K (indoor) or 2700–5000K (outdoor)

Page 102: What's New in the Title 24 2013 Code? - California Lighting

Applications between conditioned and unconditioned spaces • Approved for IC and label certifying

AT according to ASTM E283 • Gasket or caulking between housing

and ceiling – all air leak paths through luminaire assembly or ceiling opening must be sealed

IC applications: • Ballasts that are rated for higher

operating ranges • Fixture configurations that limit heat

to the ballast

Electronic ballasts • Certified to the Energy Commission • Mandated in all high-efficacy

luminaires of 13W or higher • Output frequency of no less than 20

kHz

In the 2008 and 2013 Code: Recessed Fixtures

In the 2008 code: 150 (k)12 and 150 (k)4

In the 2013 code: 150(k)8 and 150(k)1 D

Page 103: What's New in the Title 24 2013 Code? - California Lighting

• Have a minimum rated life of 30,000 hours when operated at or below a specified maximum case temperature

• Must not exceed maximum ballast case temperature

• Have a ballast factor of not less than 0.90 for non-dimming ballasts

• Have a ballast factor of not less than 0.85 for dimming ballasts

• Allow ballast maintenance and replacement from below the ceiling without cutting holes in ceiling

• Same in 2008 and 2013

Recessed Luminaires in Insulated Ceilings

In the 2008 code: 119 (n) and 150 (k)12

In the 2013 code: 110.9 (f) and 150 (k)8

Page 104: What's New in the Title 24 2013 Code? - California Lighting

What is a GU-24 replacement lamp?

1.Lead Wire

2.Fixing Hole I

3.Fixing Holes II

4.Base

5.Prongs

6.Replacement Ballast

7.Replacement Lamp

8.Lamp Base

9.Lamp Holder

10.Thread

Page 105: What's New in the Title 24 2013 Code? - California Lighting

• Factory-installed GU-24 lamp holder

• No other types of line voltage sockets in the luminaire

• Manufacturer does not provide adaptors to convert other line voltage lamp holder

• Luminaire rated only for high efficacy systems

• NO GU-24 low efficacy lamps

• NO GU-24 low efficacy luminaires

• NO GU-24 modular adaptors or luminaire conversions

• Quick-connects to GU-24 are allowed

• In 2008 code: no recessed downlights with GU-24 sockets that could receive a compact fluorescent lamp

High Efficacy GU-24 Qualifications

In the 2008 code: 150 (k)2

In the 2013 code: Table 150 A

Page 106: What's New in the Title 24 2013 Code? - California Lighting

No “Permanent” Adaptors If a luminaire has a screw-base socket, or an adaptor with a screw-base socket, it is NOT high efficacy, regardless of manufacturer claims.

Page 107: What's New in the Title 24 2013 Code? - California Lighting

The ENERGY STAR definition of high efficacy has been updated to match Title 24 and guarantees a minimum standard of quality. There is no way to tell old ENERGY STAR fixtures from new ones.

Sample qualifications for ENERGY STAR rated products • For lamps shipped with the fixtures,

the average rated life of the lamp must be > 10,000 hours.

• All qualified light fixtures carry a two-year warranty

• The CRI of lamps shipped with fixtures is more than 80 for CFL lamps and more than 75 for linear fluorescent lamps.

Airtight Label: ASTM E283 The ASTM E283 label certifies a fixture as being airtight in accordance with ASTM E283 testing and Title 24.

Fixture Labels for Compliance and Quality

U.S. government-backed label earned by products that prevent air pollution by meeting strict energy efficiency guidelines set by the U.S. Environmental Protection Agency and U.S. Department of Energy.

Page 108: What's New in the Title 24 2013 Code? - California Lighting

Indoor Vacancy Sensor Specifications

• Must be manual-on/automatic-off (can also be turned off manually)

• Time delay cannot be greater than 30 minutes

• Cannot be locked in a permanent “on” state (no “on” override)

• No more than 1 W consumed by the indicator light

• Specify with no minimum load amount

Optional features to consider • Energy-efficient LED night-light

• Impact-resistant lens and switch

In the 2008 code: 119 (j)

In the 2013 code: 110.9 (b) In Title 20: 1605.3 (g) 8

Page 109: What's New in the Title 24 2013 Code? - California Lighting

2008 Dimmer Requirements

• Reduce power consumption by a minimum of 65% at the lowest level

• If the dimmer controls incandescent or fluorescent lamps, provide electrical outputs to lamps for reduced flicker

• Be UL listed by a rating lab recognized by the International Code Council (ICC)

• For wall box dimmers designed to be used in a 3 or more-way circuit with non-dimmable switches, the level set by the dimmer shall not be overridden by any of the switches in the circuit.

In the 2008 code: see 119 (k) in regards to power reduction

In the 2013 code: 150 (k)

Page 110: What's New in the Title 24 2013 Code? - California Lighting

2008 Dimmer Requirements

• The dimmer and all of the switches in the circuit shall have the capability of turning lighting OFF if it is ON, and turning lighting ON to the level set by the dimmer if the lighting is OFF.

• Stepped dimmers will include an off position to turn lights completely off.

In the 2008 code: see 119 (k) in regards to power reduction

In the 2013 code: 150 (k)

Page 111: What's New in the Title 24 2013 Code? - California Lighting

2013 Dimmer Requirements

• Comply with Title 20

• Very subtle differences in language

• The dimmer shall: • Reduce power consumption by a minimum of 65%

percent at its lowest level;

• Include an off position which produces a zero lumen output; and not consume more than 1 W per lighting dimmer switch leg when in the off position.

• Same: • Reduce flicker through

dimming range

• For 3-way, do not override level set by dimmer and all switches should turn light off

In the 2008 code: see 119 (k) in regards to power reduction

In the 2013 code: 150 (k) In Title 20: 1605.3 (f)

Page 112: What's New in the Title 24 2013 Code? - California Lighting

Dimmer Specifications

Specify the correct load amount • Line voltage

• Low voltage

• 3-way dimmers (ex. hallway applications)

Pair LED luminaires and lamps carefully with dimmers, check manufacturer websites and spec sheets for compatibility

In the 2008 code: see 119 (k) in regards to power reduction

In the 2013 code: 150 (k)

Page 113: What's New in the Title 24 2013 Code? - California Lighting

Permanently Installed Night Lights

• Shall contain only high-efficacy lamps with no line voltage lamp holder

• Shall consume no more than 5 watts

• No screw-base lamp holders

• Indicator lights that are integral to lighting controls shall consume no more than 1 watt

• Also applies to night-lights integral to permanently installed luminaires or exhaust fans

In the 2008 code: 150 (k) 5

In the 2013 code: 150 (k) E

Page 114: What's New in the Title 24 2013 Code? - California Lighting

Wattage • No limit to number of watts, but

must be at least 50% high efficacy

• Quantity of fixtures is not regulated by code

• If a fixture can accept multiple lamp wattages, its wattage for the sake of code compliance is the highest re-lamping rated wattage designated by the manufacturer on a permanent, factory-installed Underwriters Laboratory label

Lighting Controls • High-efficacy and low-efficacy light

fixtures must be controlled separately

• Nook lighting must be on a separate switch in order to be counted as an “other space” and not part of the kitchen

• Recommended to separately switch different layers of the kitchen lighting

2008 and 2013 Kitchen: Mandatory Requirements

In the 2008 code: 150(k) 8

In the 2013 code: 150(k) 3

Page 115: What's New in the Title 24 2013 Code? - California Lighting

2008 Kitchen: Additional Low-Efficacy Wattage Additional low-efficacy wattage “bonuses” • Up to 50 watts per dwelling in units < 2,500 sq. ft.

• Up to 100 watts per dwelling in units > 2,500 sq. ft.

The bonuses are available if the following conditions are met: • In kitchens, all low-efficacy luminaires must be controlled by a vacancy sensor, dimmer,

EMCS, or multi-scene programmable control,

and

• in garages, laundry rooms, closets over 70 square feet, and utility rooms, all luminaires must be high efficacy and employ vacancy sensors.

In the 2008 code: 150(k) 8

Page 116: What's New in the Title 24 2013 Code? - California Lighting

2013 Kitchen: Additional Low-Efficacy Wattage Additional low-efficacy wattage “bonuses” • Up to 50 watts per dwelling in units < 2,500 sq. ft.

• Up to 100 watts per dwelling in units > 2,500 sq. ft.

The bonuses are available if the following conditions are met: All lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also controlled by vacancy sensors or dimmers.

In 2013 the code: 150(k) 2

Page 117: What's New in the Title 24 2013 Code? - California Lighting

Special Circumstances

Appliances • Lighting that is part of an appliance is not

regulated by the code

Blank Electrical Boxes • Calculated and treated as 180 watts of low-

efficacy lighting

Internal Cabinet Lighting • Not considered part of the kitchen lighting for

calculating 50% • No more than 20W per linear foot of illuminated

cabinet • Lighting installed inside a cabinet may only be

used to illuminate the inside of the cabinet

In the 2008 code: 119 (j)

In the 2013 code: 110.9 (b) In Title 20: 1605.3 (g) 8

Page 118: What's New in the Title 24 2013 Code? - California Lighting

Cabinets: Measurement Methods for 2013

The length of an illuminated cabinet shall be determined using one of the following measurements, regardless of the number of shelves or the number of doors per cabinet section:

A. One horizontal length of illuminated cabinet; or

B. One vertical length, per illuminated cabinet section; or

C. No more than one vertical length per every 40 horizontal inches of illuminated cabinet.

In 2013 the code: 150(k) 4

Page 119: What's New in the Title 24 2013 Code? - California Lighting

Cabinets: Measurement Methods for 2013

The length of an illuminated cabinet shall be determined using one of the following measurements, regardless of the number of shelves or the number of doors per cabinet section:

C. No more than one vertical length per every 40 horizontal inches of illuminated cabinet.

In 2013 the code: 150(k) 4

Page 120: What's New in the Title 24 2013 Code? - California Lighting

Kitchen: Sample Floor Plan and Calculation

298 Square Feet

Page 121: What's New in the Title 24 2013 Code? - California Lighting

Lighting High efficacy or controlled with a vacancy sensor Controls The first switch does not need to be a fluorescent light fixture. High-efficacy and low-efficacy light fixtures must be controlled separately. Quantity The quantity of light fixtures is not regulated by the code.

Vacancy Sensor • Vacancy sensors must be manual

on/off and automatic off • Sensors cannot have an override

allowing the light fixture to be continuously on

• The maximum time delay to turn off is 30 minutes after the last detected motion

• Closets < 70 sq ft are exempt from controls requirement

2008 Bathrooms, Garages, Laundry Rooms, Closets, and Utility Rooms: Requirements

In the code: see 150(k) 10

Page 122: What's New in the Title 24 2013 Code? - California Lighting

Lighting At least one luminaire has to be high efficacy Controls All other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors. Quantity The quantity of luminaires is not regulated by the code. (for all of the residence)

2013 Bathrooms

In the 2013 code: see 150(k) 5

Page 123: What's New in the Title 24 2013 Code? - California Lighting

Lighting & Controls All lighting must be high efficacy, and shall be controlled by either dimmers or vacancy sensors.

Exceptions • Closets less than 70 sq ft • Detached storage buildings less

than 1,000 square feet located on a residential site

2013 Bathrooms, Garages, Laundry Rooms, Closets, and Utility Rooms: Requirements

In the 2013 code: see 150(k) 6

Page 124: What's New in the Title 24 2013 Code? - California Lighting

Kitchen: Sample Floor Plan and Calculation

228 Square Feet

Page 125: What's New in the Title 24 2013 Code? - California Lighting

• High efficacy, vacancy sensor, or dimmer

• High-efficacy and low-efficacy light fixtures must be controlled separately

• Vacancy sensors must be manual on/off and automatic off

• Switched outlets (half-hots) do not require special controls

• Ceiling fans with incandescent light kits need one switch for the fan and one dimmer/vacancy sensor for the lights.

• High-efficacy: only one switch is needed, two are shown for flexibility

2008 and 2013 Bedrooms

In the 2008 code: see 150(k) 7 and 11

In the 2013 code: see 150(k) 7

Page 126: What's New in the Title 24 2013 Code? - California Lighting

• High efficacy, vacancy sensor, or dimmer

• Switched outlets (half-hots) do not require special controls

• Decorative option: use incandescent fixtures and dimmer(s)

• Ceiling fans with low-efficacy light kits need one switch for the fan and one dimmer/vacancy sensor for the lights (with high-efficacy kits, only one switch is needed)

2008 and 2013 Living and Dining Rooms

Page 127: What's New in the Title 24 2013 Code? - California Lighting

Attic • If an vacancy sensor cannot “see”

the entire attic, the occupant could be left in the dark

• High efficacy, dimmer or vacancy sensor

• Sensors must be manual on/off and automatic off

Enclosed Patio • An enclosed (unconditioned) patio

is considered an “other space”

• High-efficacy and low-efficacy light fixtures MUST be controlled separately

• High efficacy, or include a dimmer or vacancy sensor

2008 and 2103 Attics and Enclosed Patios

Page 128: What's New in the Title 24 2013 Code? - California Lighting

• High efficacy, vacancy sensor or dimmer • Vacancy sensors must view the entire space (this application

may require three-way switching as shown)

2008 and 2013 Hallways

Page 129: What's New in the Title 24 2013 Code? - California Lighting

• Do not apply to landscape lighting that is not attached to the building, residential parking lots, or garages for eight or more vehicles

• Must be high-efficacy, or controlled by a manual on/off switch, motion sensor, and a method automatically turn off lights during daytime

• Low-efficacy outdoor luminaires may have a temporary override switch which bypasses the motion sensing function for up to six hours provided that the override switch automatically reactivates the motion sensor

• Outdoor luminaires in or around swimming pools or water features are exempt from Title 24

• A manual off/on switch (no override to on)

• Must have automatic on/off operation and photocells to keep lights off during daylight hours

• Must comply with the maximum 30-minute shut-off requirement

• Must view the space that it illuminates

Override Switch Low-efficacy outdoor luminaires may have a temporary override switch which bypasses the motion sensing function for up to six hours, provided that the override switch automatically reactivates the motion sensor.

2008 and 2013 Outdoor Lighting: Requirements

Page 130: What's New in the Title 24 2013 Code? - California Lighting

• LEDs are ideal for cold outdoor environment, as CFLs often are not compatible with cold temperatures.

• LEDs’ lifespan is significantly longer than other lamp sources, requiring less maintenance.

• Although not required by the standards when using a high-efficacy fixture, including a motion sensor will provide light to occupants upon entering the space when no immediate access to a switch is available.

• For outdoor areas close to bedroom windows, high-efficacy luminaires are preferred over low-efficacy luminaires with motion sensors that may be triggered in the middle of the night.

Front Porch Lighting Plan

Page 131: What's New in the Title 24 2013 Code? - California Lighting

• Provide adequate lighting to support the function of the space and specific tasks performed within it.

• Although not required by the standards when using a high-efficacy fixture, including a motion sensor (as shown) will provide light to occupants where there is not immediate access to a switch in a transitional space.

• Motion sensor coverage should not be too large, or lights will be triggered by street traffic or a neighbor’s motion. Most sensors have a sensitivity control to adjust the degree of motion and light that triggers them.

• In addition to the motion sensor and one of the three other lighting control options, the owner also must be provided with a manual on/off switch for low-efficacy luminaires.

Front Porch Lighting Plan

Page 132: What's New in the Title 24 2013 Code? - California Lighting

2008 Internally Illuminated Address Signs

• Cannot exceed 12 watts per sq. ft. internal illumination • Cannot exceed 2.3 watts per sq. ft. external illumination

Alternatives when equipped only with one or more of the light sources

In the 2008 code: see 150(k) 14

• High-pressure sodium • Metal halide lamps (with minimum efficiency) • Neon or cold cathode lamps (with minimum

efficiency) • Fluorescent lamps (with a minimum CRI)

• LEDs (with minimum efficiency) • Compact fluorescent lamps

(not with screw-base socket) • Electronic ballasts (minimum 20 kHz)

Page 133: What's New in the Title 24 2013 Code? - California Lighting

2008 Internally Illuminated Address Signs

Consume no more than 5 watts of power

OR

Comply with the nonresidential sign lighting Standards in §140.8:

• Cannot exceed 12 watts per sq. ft. internal illumination • Cannot exceed 2.3 watts per sq. ft. external illumination

• Alternatives when equipped only with one or more of the light sources

• High-pressure sodium • Metal halide lamps (with minimum efficiency) • Neon or cold cathode lamps (with minimum efficiency) • Fluorescent lamps (with a minimum 80 CRI) + Electronic ballasts (minimum 20 kHz) • Compact fluorescent lamps with no screw-base sockets • LEDs (with minimum efficiency)

In the 2008 code: see 150(k) 14

Page 134: What's New in the Title 24 2013 Code? - California Lighting

2008 Low-rise Multi-family Common Areas

A multi-family complex consists of four or more dwelling units. A low-rise is considered a building with three or fewer stories. • All hardwired lighting must be high efficacy or

controlled by a occupant sensor

• The occupant sensor must be directly on the walkway and/or view the entire space

If the building has more than three stories the common areas must comply with the nonresidential code.

In the 2008 code: see 150(k) 16

Page 135: What's New in the Title 24 2013 Code? - California Lighting

2008 Low-rise Multi-family Common Areas

• In buildings where common areas constitute > 20% of the floor space: • Lighting must comply with the

nonresidential standards

• Lighting in corridors and stairwells must be controlled by occupancy sensors that reduce lighting power by at least 50%

In buildings with common areas that are ≤ 20% of the floor space:

• All hardwired lighting must be high efficacy or controlled by an occupancy sensor

In the 2008 code: see 150(k) 16

Credit: The Hanover Co.

Page 136: What's New in the Title 24 2013 Code? - California Lighting

Residential Lots and Garages • Residential standards apply to parking

lots, carports and parking garages (attached and detached from dwelling unit) for seven or fewer vehicles per site

• Parking lots and carports must meet the residential outdoor lighting requirements

• Parking garages must meet the residential indoor lighting requirements: high efficacy or controlled by a manual-on occupant sensor

Non-residential Lots and Garages • Non-residential standards apply to

parking lots, carports and parking garages (attached and detached from dwelling unit) for eight or more vehicles

• Must meet the lighting requirements for non-residential buildings

• Must meet the power density limits for non-residential lighting standards

• Light fixtures must be controlled by a photocontrol or time switch that turns lights off when daylight is present

• Fixtures with lamps rated over 175 watts are designated as “cutoff,” limiting light emitted upwards

• Uniform lighting is desired to help eliminate shadows in corners and provide a sense of safety

2008 Parking Lots and Garages

In the 2008 code: see 150(k) 11

Page 137: What's New in the Title 24 2013 Code? - California Lighting

Residential Lots and Garages • Residential standards apply to parking

lots, carports and parking garages (attached and detached from dwelling unit) for seven or fewer vehicles per site

• Parking lots and carports must meet the residential outdoor lighting requirements or the non-res requirements

• Parking garages must meet the residential indoor lighting requirements: high efficacy and controlled by a vacancy sensor

Non-resential Lots and Garages • Non-residential standards apply to

parking lots, carports and parking garages (attached and detached from dwelling unit) for eight or more vehicles

• Must meet the power density limits for non-residential lighting standards

• Light fixtures must be controlled by a photocontrol or time switch that turns lights off when daylight is present

• New construction or major alterations are required to comply with Backlight, Uplight, Glare ratings per IES TM-15-11

• Pole mounted luminaire > 75W and < 24 ft must include motion sensors that reduce lighting levels on vacancy.

• Other conditions apply, see sections: 110.9, 130.0, 130.2, 130.4, 140.7 & 141.0

2013 Parking Lots and Garages

In the 2013 code: see 150(k) 6

Page 138: What's New in the Title 24 2013 Code? - California Lighting

Resources

For more information: California Energy Commission: Building Efficiency Standards http://www.energy.ca.gov/title24/2013standards/index.html California Energy Commission: 2013 Nonresidential Compliance Manual http://www.energy.ca.gov/2013publications/CEC-400-2013-002/CEC-400-2013-002-SD.pdf California Lighting Technology Center, UC Davis http://cltc.ucdavis.edu/title24