welcome to airah wa’s site visit centigrade’s …...key considerations prior to commissioning...

42
Centigrade’s Testing & Training Facility Sponsored by: Welcome to AIRAH WA’s Site Visit

Upload: others

Post on 24-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Centigrade’s Testing & Training Facility

Sponsored by:

Welcome to AIRAH WA’s Site Visit

Page 2: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Upcoming AIRAH WA Events

AIRAH WA Members’ Annual Lunch Tuesday, October 16Aloft Hotel, RivervaleLimited places remain

AIRAH WA Site Visit Tuesday, November 13iFLY TBC

AIRAH WA President ShoutNorthbridge Brewing CoTuesday, November 27

AIRAH WA Members’ Golf Day Thursday, March 21, 2019Maylands Peninsula Golf Course

www.airah.org.au

Page 3: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Presenting:

Michael Anthony, M. AIRAH; Tony Anderson, M.AIRAH;

David Lee, M. AIRAH; Michael Snook, Affil.AIRAH;

David Hammond, Stud.AIRAH; Nathan Johnsen, Affil.AIRAH; Thomas Fellows, Stud.AIRAH

and Scott Hobbs

Page 4: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Effective Airside Commissioning

Michael Snook Affil. AIRAHDavid Hammond Stud. AIRAH

Presenter
Presentation Notes
DH MS Introduction ourselves Aim of presentation Better understanding of the airside commissioning process Tips on interpreting the commissioning documentation How effective airside commissioning can result in power savings
Page 5: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

What is Commissioning?

• “The advancement of an installation from the state of static completion to full working order to specified requirements. It includes setting to work of an installation, and regulation of all the system flowrates.” CIBSE Commissioning Code A:1996 (2006)

Presenter
Presentation Notes
MS Put in layman’s terms 2 weeks before PC, 14 hour days
Page 6: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Why is Effective HVAC Commissioning Important?

Courtesy HVAC HESS, 2013

Presenter
Presentation Notes
DH As an industry we are focusing on improving our energy efficiency and reducing our overall impact on building energy consumption. Effective commissioning of plant is a key step to ensure final system performance is as close to engineered design as possible.
Page 7: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Key Considerations Prior to Commissioning Air Systems

• Type of facility HVAC system is serving• Allowable tolerances / permissible deviations from design

requirements• Access to equipment• Site cleanliness • Commissioning timeframe• Schedule clashes

Presenter
Presentation Notes
DH Type of facility is going to affect not only how commissioning will be undertaken (i.e PPE in hospital facility, testing procedures etc), but will determine the importance of items such as pressure gradients, tightness of air balance and other various items. Access to balance dampers / fans required to commission. These issues should be identified throughout all phases of construction and remediated prior to commissioning phase MS Site cleanliness- will filters be blocked, will we be pushing air into clean areas, coanda effect dirtying supply air grilles
Page 8: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Common Issues Faced at Precommissioning

• Site not ready (Builder, Installation, No power)• Volume control dampers not open• Fans not bump tested / fan rotation backwards• Implementation of a commissioning management plan allows

the roles and responsibilities of each stakeholder to be clearly defined.

Presenter
Presentation Notes
DH Sometimes stakeholders, builders or project managers will not be aware of what is required in the commissioning phase. Often commissioning can’t start until shortly before PC which doesn’t allow much time to rectify any issues. Sometimes dampers aren’t fully open which can lead to false index’s. This is especially time consuming on large systems and can result in a second initial scan. Grilles not cut in, floors being painted, variations etc. A commissioning management plan is the most effective way to co ordinate peripheral trades and subcontractors which will optimise commissioning timeframes.
Page 9: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Hierarchy of Airside Commissioning

Presenter
Presentation Notes
MS
Page 10: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Primary Data

• A full system pitot traverse gives the most accurate representation of system performance

• Pitot traverse relies on an average measurement of velocity pressure at a section of duct with a laminar flow characteristic

• Where duct velocities are below 3.5m/s, a hotwire anemometer is the preferable choice₁

Presenter
Presentation Notes
MS Base data in which secondary data ties into Velocity pressure becomes low so manometer loses accuracy
Page 11: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Pitot Tube Operating Principle

Presenter
Presentation Notes
MS Comparing total pressure to static pressure, gives velocity pressure
Page 12: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Pitot Tube Operating Principle

Courtesy BSRIA BG 49/2015

Presenter
Presentation Notes
MS Barometric pressure and temperature affects air density
Page 13: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Test Point Locations

Courtesy BSRIA BG 49/2015

Presenter
Presentation Notes
MS Objective is to ensure test point is as laminar as possible.
Page 14: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Courtesy BSRIA BG 49/2015

Presenter
Presentation Notes
MS
Page 15: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Courtesy BSRIA BG 49/2015

Presenter
Presentation Notes
MS
Page 16: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Methods to Ensure Accurate Traverse Measurements

• Favour pitot tube over hotwire anemometer where there is a risk of air swirl

• Correctly measure internal duct dimensions• Space test points methodically• Log-Tchebycheff Method of Traverse vs Equal Duct Method

Presenter
Presentation Notes
MS Can be affected by turbulence and backwards air swirls Studies show 6% higher measurement using equal duct method
Page 17: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Secondary / Tertiary Data

• Supports primary data (Traverse)• External static pressure (Fan Curve)• Static profile of air system (E.G Coil ∆𝑃𝑃)• Fan running current• Air Balance• Tying several data types together ensures a true

representation of system performance has been shown.

Presenter
Presentation Notes
MS Important that manufacturers data is accurate and reliable
Page 18: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Fan Curves

Presenter
Presentation Notes
MS
Page 19: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Proportional Air Balancing

• “The process of bringing the fluid flow rates throughout a distribution system into balance with one another, in their correct proportions and within tolerances specified by the designer” BSRIA BG 49-2015

Presenter
Presentation Notes
DH This involves bringing all air terminals within defined tolerances of each other. The preferred method is the index method. This involves leaving one outlet wide open.
Page 20: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Setting Fan Volume

• Following pre commissioning, fan is set to 110% of design for proportional balancing as a rule of thumb

• Use of affinity laws / static pressures handy in setting flowrate at this stage

Presenter
Presentation Notes
DH Before proportional balancing starts, the fan volume is set to 110% as a rule of thumb. This is because as dampers are closed the volume will reduce. To minimise unnecessary duct traverses, the use of static pressure and affinity laws are quite handy.
Page 21: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Initial Scan

• Knowing air volume from main traverse, each terminal is measured

• The difference between traverse reading and sum of outlet readings is recorded.

• An “index” is identified, and a proportional balance is undertaken to bring all outlets to within a specified tolerance of design.

Presenter
Presentation Notes
DH The difference between the initial scan and the traverse is not too important at this stage unless the factor is excessive which may indicate an air leak. This could be from torn flex, an uncapped spigot or an unconnected piece of duct.
Page 22: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

System Index

• The air outlet with the highest pressure loss at the design air volume.

• Important to consider whether the index makes sense in relation to the rest of the system.

• Important to physically check the duct and cushion head interface before proceeding with air balance

Presenter
Presentation Notes
DH The system index is found in the initial scan. It is the air outlet with the highest pressure loss at design air volume. Check for unnecessary bends in the flexible duct, long duct runs or twisted flex that may cause the pressure loss. Once an index has been identified it is important to consider if it makes sense. If the outlet is the first off the dropper then it is most likely not the index.
Page 23: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Is this an index?

Presenter
Presentation Notes
MS This false system index caused an additional 70Pa to be added to the system. A pitot traverse of the VAV box would have shown there was duct leakage. VAV System not achieving static pressure in Vmax, several boxes were not achieving. Following recommissioning of system, Static pressure setpoint was reduced 70Pa and AHU was able to achieve setpoint with all VAV boxes in Vmax condition
Page 24: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Correction Factors

• A correction factor adjusts the measured readings at the terminals to reflect the true system volume.

• Correction factors account for:• Air leakage rate• Back pressure Induction within Balometer• Takes into account free area of register when using vane or

deflection anemometers• Correction factors between 0.8 and 1.2 are generally

considered acceptable (BSRIA BG 49-2015)

Presenter
Presentation Notes
DH Correction factors are by no means set in stone- each system must have a correction factor established via a pitot traverse to cast aside any prejudice as what the factor “should” be.
Page 25: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Factor Caused By Hood Backpressure

Courtesy Shaun Matthews Use of Correction Factors When Commissioning Air Systems, 2016

Presenter
Presentation Notes
DH This image illustrates the effect of hood back pressure on the volume though an air terminal. This factor would most likely be caused by a low system pressure. As the hood is placed up to the terminal the resistance pushes air elsewhere. The volume measured through the hood is a true volume of what is passing through the hood while it is in place, but as it is creating extra resistance, once the restriction of the hood is removed, the outlet will be supplying more air. This behaviour is particularly noticeable with the smaller low flow hoods.
Page 26: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Factor Caused By Hood Backpressureand Cushion Head Leakage

Courtesy Shaun Matthews Use of Correction Factors When Commissioning Air Systems, 2016

Presenter
Presentation Notes
DH The backpressure of the hood once fitted over the grille is pushing more air out of the cushion head interface.
Page 27: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Correction Factors

• Not an arbitrary figure to cover up lack of volume or poor air balance

• Technicians need to understand why there is a deviation between measured volume at diffusion and at duct traverse.

• Common cause of falsified commissioning data and substandard airside commissioning.

• Must be verified when finalising system.

Presenter
Presentation Notes
MS Correction factors should be re verified at final scan as they change in the balancing phase.
Page 28: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 1: Typical Cleanroom AHU Supply Air

Presenter
Presentation Notes
MS
Page 29: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 1: Typical Cleanroom AHU Supply Air

True volume measured at laminar traverse point

Presenter
Presentation Notes
MS
Page 30: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 1: Typical Cleanroom AHU Supply Air

Factor Ties ATBS to DTS

Corrected balometer volume equals duct traverse volume

Presenter
Presentation Notes
MS
Page 31: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Likely causes of factor

• Factor is typical for a HEPA terminal outlet, generally caused by instrument (+ / - 3%)

• User factor• Minimal leakage on ductwork upstream of HEPA terminals due

to high static pressure on supply air ductwork

Presenter
Presentation Notes
MS
Page 32: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 2: Typical AHU with Swirl Diffusion

Presenter
Presentation Notes
DH
Page 33: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 2: Typical AHU with Swirl Diffusion

True supply air volume measured at laminar traverse point

Presenter
Presentation Notes
DH
Page 34: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 2: Typical AHU withSwirl Diffusion

Volume corrected to traverse

Presenter
Presentation Notes
DH We apply a factor to the balometer readings to tie the secondary data – being the air balance– to the duct traverse
Page 35: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Likely Causes of Factor

• Swirl diffusion pattern inducting air within balometer• Backpressure exerted by balometer causing restriction• High backpressure of swirl diffuser causing minor leakage

within cushion head- diffuser interface• Instrument factor (+ / - 2%)• User factor

Presenter
Presentation Notes
DH Swirl diffusion moves air parallel to the ceiling hitting the hood bag which forces it to change direction. This increases the back pressure and creates turbulent air within the hood. The turbulent air moves over the velocity matrix which is what causes a lower reading. One user factor is the direction the hood is facing when placed up to the diffusion. This can give a different reading depending on which direction the hood is facing.
Page 36: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Case 3: Hood Factor Used (No Traverse)

Presenter
Presentation Notes
DH Using the data from the previous job, what happens when a hood factor is used without a traverse.
Page 37: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

What if a hood factor of “1.0” was used

Volume readon balometernot corrected to a traverse

Presenter
Presentation Notes
DH Without a duct traverse, each air terminal is adjusted to design volume using the balometer with a factor of one. This is incorrect as we know from the previous example that this particular job had a factor of 1.08.
Page 38: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

What if a factor of “1.0” was used

• Established 1879L/s on balometer• AHU would have to be sped up 8% to achieve this.• If a traverse was taken, AHU would likely be supplying 8%

more air than what was measured.

Presenter
Presentation Notes
DH The result of using a hood factor of 1.0 without tying it into a traverse is that the air handler would likely have been sped to achieve design on the balometer. As this sheet shows, if a traverse of the supply air duct was taken the volume would be 8% percent higher than what was established on the balometer.
Page 39: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

What does this mean?

• Swirl diffusion induction and back pressure within balometercausing 8% differentiation between true traverse volume and volume read on balometer.

• By compensating for a false reading, a power increase of 25% will be experienced as fan motor speed is increased 8%.

Presenter
Presentation Notes
DH What does this all mean? For this example, the swirl diffusion causes induction and back pressure within the hood causing an 8% difference between the traverse reading and the balometer reading. Compensating for the false reading by speeding up the fan by 8% percent will result in a 25% power increase.
Page 40: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Why is this important?

• Key aim for any building design is to minimise energy consumption over an asset’s lifecycle

• In facilities where maintaining specific pressure gradients is important, major issues can arise where true air volumes have not been established via a pitot traverse

• Control oscillation can occur as system is incorrectly commissioned

• Higher maintenance costs• Cost of retrocommissioning vs energy savings

Presenter
Presentation Notes
MS Never getting to static pressure setpoint in VAV systems. CHW coil carryover Poor dehumidification due to high coil velocities Higher pressure drops over filters / coils Noise Air drafts
Page 41: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

References

-Alnor HVAC Assessment Handbook, 2007, USA-BSRIA BG49-2015, 2015, UK-CIBSE Commissioning Code A:1996. Chartered Institute of Building Services Engineers, (2006), UK-CIBSE Commissioning Code M. Chartered Institute of Building Services Engineers, (2003), UK-AIRAH Technical Handbook. Australian Institute of Refrigeration, Air Conditioning and Heating, 2013, Australia-Matthews. S (2016) The Use of Correction Factors When Commissioning Air Systems. Commissioning Specialists Association, West Sussex, UK-Heating, Ventilation and Air Conditioning High Efficiency Systems Strategy, 2013-P.L Lagus, P.W Butler, K.M Fleming (2006) A Comparison of Tchebycheff, Equal Area and Tracer Gas Air Flow Rate Measurements-NSW Office of Environment and Heritage (2015) HVAC Optimisation Guide, Sydney, Australia

Page 42: Welcome to AIRAH WA’s Site Visit Centigrade’s …...Key Considerations Prior to Commissioning Air Systems • Type of facility HVAC system is serving • Allowable tolerances

Thank you for attending, please stay for refreshments.

Thanks to our sponsor