SECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here ) Copyright 2020 - 2020 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Fencing Systems: Complete with hardware, posts, rails, gates, and accessories necessary for a structurally integrated installation. 1. Security fences and gates. (Palisade-EZ Series) 2. Welded wire fences and gates. (Prism 3-D Series) 3. Barriers and perimeter security fence systems. (Guardian Series Security Mesh) 4. Residential ornamental fence systems. (TruView Residential Series) 5. Commercial ornamental fence systems. (UpGrade-C Commercial Series) 6. Industrial ornamental fence systems. (UpGrade-I Industrial Series) 7. Heavy industrial ornamental fence systems. (UpGrade-H Industrial Series) 1.2 RELATED SECTIONS A. Section 31 20 00 - Earth Moving. B. Section 03 30 00 - Cast-in-Place Concrete. 1.3 REFERENCES A. American Concrete Institute: 1. ACI 301 - Specifications for Structural Concrete. B. ASTM International (ASTM): 1. ASTM A53 - Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless. 2. ASTM A123 - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products. 3. ASTM A500 - Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes. 4. ASTM A501 - Standard Specification for Hot-Formed Welded and 32 31 00 -1

Upload: others

Post on 08-Dec-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

SECTION 32 31 00FENCES AND GATES - SECURITY AND ORNAMENTAL

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2020 - 2020 ARCAT, Inc. - All rights reserved

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Fencing Systems: Complete with hardware, posts, rails, gates, and accessories necessary for a structurally integrated installation.1. Security fences and gates. (Palisade-EZ Series)2. Welded wire fences and gates. (Prism 3-D Series)3. Barriers and perimeter security fence systems. (Guardian Series Security Mesh)4. Residential ornamental fence systems. (TruView Residential Series)5. Commercial ornamental fence systems. (UpGrade-C Commercial Series)6. Industrial ornamental fence systems. (UpGrade-I Industrial Series)7. Heavy industrial ornamental fence systems. (UpGrade-H Industrial Series)

1.2 RELATED SECTIONS

A. Section 31 20 00 - Earth Moving.

B. Section 03 30 00 - Cast-in-Place Concrete.

1.3 REFERENCES

A. American Concrete Institute:1. ACI 301 - Specifications for Structural Concrete.

B. ASTM International (ASTM):1. ASTM A53 - Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-

Coated, Welded and Seamless.2. ASTM A123 - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron

and Steel Products.3. ASTM A500 - Standard Specification for Cold-Formed Welded and Seamless Carbon

Steel Structural Tubing in Rounds and Shapes.4. ASTM A501 - Standard Specification for Hot-Formed Welded and Seamless Carbon

Steel Structural Tubing.5. ASTM A653 - Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron

Alloy-Coated (Galvannealed) by the Hot-Dip Process.6. ASTM A924 - Standard Specification for General Requirements for Steel Sheet,

Metallic-Coated by the Hot-Dip Process.7. ASTM A1064 - Standard Specification for Carbon-Steel Wire and Welded Wire

Reinforcement, Plain and Deformed, for Concrete.8. ASTM B117 - Standard Practice for Operating Salt Spray (Fog) Apparatus.9. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded

Bars, Rods, Wire, Profiles, and Tubes.10. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron

and Steel.

32 31 00 -1

Page 2:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

11. ASTM C33 - Standard Specification for Concrete Aggregates.12. ASTM C150 - Standard Specification for Portland Cement.13. ASTM D523 - Standard Test Method for Specular Gloss.14. ASTM D714 - Standard Test Method for Evaluating Degree of Blistering of Paints.15. ASTM D1044 - Standard Test Method for Resistance of Transparent Plastics to

Surface Abrasion by the Taber Abraser.16. ASTM D1654 - Standard Test Method for Evaluation of Painted or Coated Specimens

Subjected to Corrosive Environments.17. ASTM D1737 - Method of Test for Elongation of Attached Organic Coatings with

Cylindrical Mandrel Apparatus.18. ASTM D2247 - Standard Practice for Testing Water Resistance of Coatings in 100

percent Relative Humidity.19. ASTM D2794 - Standard Test Method for Resistance of Organic Coatings to the

Effects of Rapid Deformation.20. ASTM D3359 - Standard Test Methods for Measuring Adhesion by Tape Test.21. ASTM D3363 - Standard Test Method for Film Hardness by Pencil Test.22. ASTM D4141 - Standard Practice for Conducting Black Box and Solar Concentrating

Exposures of Coatings.23. ASTM F1043 - Standard Specification for Strength and Protective Coatings on Steel

Industrial Fence Framework.24. ASTM F2408 - Ornamental Fences Employing Galvanized Steel Tubular Pickets.25. ASTM G12 - Standard Test Method for Nondestructive Measurement of Film

Thickness of Pipeline Coatings on Steel.26. ASTM G23 - Standard Practice for Operating Light-Exposure Apparatus (Carbon-Arc

Type) With and Without Water for Exposure of Nonmetallic Materials.27. ASTM G154 - Standard Practice for Operating Fluorescent Ultraviolet (UV) Lamp

Apparatus for Exposure of Nonmetallic Materials.

1.4 SUBMITTALS

A. Submit under provisions of Section 01 30 00 - Administrative Requirements.

B. Product Data: Product performance data indicating compliance with this specification.1. Manufacturer's data sheets on each product to be used.2. Preparation instructions and recommendations.3. Storage and handling requirements and recommendations.4. Typical installation methods.5. product literature, shop drawings, and.

C. Shop Drawings: Including but not limited to details of layout, locations, components, materials, dimensions, sizes, weights, finishes of components, installation and operational clearances, gate swings, post sizes, spacing, mesh type where applicable, gate details/dimensions, details of post anchorage, and post attachment/bracing and relationship with adjacent construction.

D. Verification Samples: Two representative units of each color and finish.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with a minimum 5 years documented experience.

B. Installer Qualifications: Company experienced in the installation of the type of construction involved and the materials and techniques specified with minimum 5 years documented experience with projects of similar scope and complexity.

C. Source Limitations: Provide fence system and gates, as a complete unit produced by a

32 31 00 -2

Page 3:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

single manufacturer, including necessary erection accessories, fittings and fastenings.

D. Field Quality Control: To be conducted by manufacturer's technical specialist.

E. Mock-Up: Construct a mock-up with actual materials in sufficient time for Architect's review and to not delay construction progress. Locate mock-up as acceptable to Architect and provide temporary foundations and support.1. Intent of mock-up is to demonstrate quality of workmanship and visual appearance.2. If mock-up is not acceptable, rebuild mock-up until satisfactory results are achieved.3. Retain mock-up during construction as standard for comparison with completed work.4. Do not alter or remove mock-up until work is completed or removal is authorized.

1.6 PRE-INSTALLATION CONFERENCE

A. Convene a conference approximately two weeks before scheduled commencement of the Work. Attendees shall include Contractor, installer, manufacturer's representative and trades involved. Agenda shall include schedule, responsibilities, critical path items and approvals.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Deliver materials to site in manufacturer's original, unopened pallets and packaging, with labels clearly identifying product name and manufacturer.

B. Deliver fence materials, gates, posts, and accessories to project site, completely pre-finished. Upon receipt at the job site, all materials shall be checked to ensure that no damages occurred during shipping.

C. Handle fence components to protect finish coating from any scuffs, abrasion or other damage during unloading and installation. Excessive damage to factory applied coatings will be cause for rejection.

D. Handle and store materials in strict compliance with manufacturer's written instructions and recommendations, protected from theft and damage due to weather, excessive temperature, and construction operations.

1.8 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.9 WARRANTY

A. Manufacturer's Warranty: Provide manufacturer's standard limited warranty against defects in materials and workmanship as follows.1. Automation Components: 2 year warranty.2. Gate Components: 2 year warranty.3. Fence Components: 20 year warranty.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: Betafence, which is located at: 3309 S. Kaufman St.; Ennis, TX 75119; Toll Free Tel: 888-650-4766; Tel: 972-878-7000; Fax: 972-878-4703; Email:request info ([email protected]); Web:https://www.betafence.com/en/available/americas

B. Substitutions: Not permitted.

32 31 00 -3

Page 4:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

C. Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.

2.2 SECURITY FENCES AND GATES (Palisade-EZ Series)

A. Security Fences and Gates:1. Basis of Design: Palisade-EZ Series, Defender Security Arch Top 2-Rail Style

Ornamental Fence Systems as manufactured by Betafence.2. Basis of Design: Palisade-EZ Series, Landmark Security Arch Top 3-Rail Style

Ornamental Fence Systems as manufactured by Betafence.3. Basis of Design: Palisade-EZ Series, Landmark Security Arch Top 4-Rail Style

Ornamental Fence Systems as manufactured by Betafence.4. Basis of Design: Palisade-EZ Series as manufactured by Betafence, Style as

scheduled and indicated on Drawings.5. Panels, Rails and Posts: Shipped from factory pre-cut to lengths as scheduled and

indicated on Drawings.6. Panel Width: Standard panel is 8 ft (2438 mm) wide.7. Panel Height: 7 ft (2134 mm).8. Panel Height: 8 ft (2438 mm).9. Panel Height: 9 ft (2743 mm).10. Panel Height: 10 ft (3048 mm).11. Panel Height: 12 ft (3658 mm).12. Panel Height: As scheduled and indicated on Drawings.

B. Steel Posts, Rails and Corrugated Panels:1. Minimum Yield Strength, ASTM A924: 45000 psi (310 MPa).2. Finish, ASTM A653: Hot-dip galvanized, G-90 designation; minimum zinc coating

weight of 0.90 oz per sq ft (275 g per sq m).

C. Panels: Corrugated.1. Width: 2.70 inches (69 mm).2. Wall Thickness: .072 inch (1.8 mm).3. Corrugations: 5-15/16 inches (151 mm) on center.4. Panel Air Space: No greater than 3-1/4 inches (83 mm).5. Panel Tops: Splayed Point (Security Arch) top design.6. Panel Tops: Pinnacle top design.7. Panel Tops: As scheduled and indicated on Drawings.8. Security Fasteners: Tamperproof, fastening each panel to rail.

D. Rails: Steel tubes; Palisade-EZ rails shipped from factory pre-punched to accept fasteners.1. Dimensions: Nominal 2 inches (51 mm) square.2. Wall Thickness: 14 gauge (1.9 mm).

E. Posts: Steel tubes.1. Dimensions: Nominal 4 inches (102 mm) square.2. Wall Thickness: 11 gauge (3 mm).3. Post Caps: Press on type steel caps, zinc plated in compliance with ASTM B633.4. Panel Hangers: Stainless steel.5. Fasteners: Stainless steel.6. Brackets: Finish and color to match fence panels.7. Panels, Rails and Posts shall be pre-cut to specified lengths. Palisade-EZ rails shall

be pre-punched to accept the tamperproof security fasteners.

F. Swing Gates:1. Design: As indicated on submittals and Drawings.2. Frame Members: MIG welded; 2 inches (51 mm) TS x 14 gauge (1.9 mm).3. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

32 31 00 -4

Page 5:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

operation and allow future adjustment.4. Gate Frames and Infill Panels: Style, finish and color to match fence panels.5. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.6. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.7. Latch: Capable of retaining gate in closed position; with provision for padlock.

G. Cantilever Gates:1. Design: As indicated on submittals and Drawings.2. Frame Members: MIG welded.3. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.4. Gate Frames and Infill Panels: Style, finish and color to match fence panels.5. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.6. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

H. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied TGIC polyester powder coating of the Super-Durable class.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 95

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 9 N m resistance of organic

coatings to the effects of rapid deformation (impact).4. Film Hardness, ASTM D3363: Minimum 2H hardness as measured by pencil test.5. Solar Concentration Exposure, ASTM D4141: Coating must test to a minimum of 50

percent gloss retention at 1400 MJ per sq m, with no film failure, chalking, cracking or checking and no more than 10 percent fading as measured by Conducting Black Box and Solar Concentrating Exposures of Coatings Test, Method C (equivalent to EMMAQUA NTW).

6. Film Thickness, ASTM G12: 2.0 mils (0.05 mm); 2 - 4 mils (0.05 - 0.1 mm) as measured by manufacturer's powder coat measurement and inspection procedures.

7. Flexibility, ASTM D1737: No breaks, flakes or cracks on Q-panel 5B; 100 percent adhesion to the substrate.

8. Gloss 60 Angle, ASTM D523: 50 - 60.9. Abrasion Resistance, ASTM D1044: 0.0032 oz (90 - 95 mg) weight loss.10. Accelerated Weathering, ASTM G23: 1000 hrs, 70 percent gloss retention, DeltaE

less than 2.0.11. Humidity, ASTM D2247: 1000 hours, no blisters.12. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage

Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

13. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

14. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape

32 31 00 -5

Page 6:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

(Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance: Minimum of 7 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D1654.

I. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.3 WELDED WIRE FENCES AND GATES (Prism 3-D Series)

A. Basis of Design: Prism 3-D Series Fence Systems as manufactured by Betafence.1. Design Requirements: Fencing system, foundation and installation engineered to

withstand 90 mph wind load.2. Panels and Posts: Shipped from factory pre-cut to lengths as scheduled and indicated

on Drawings.3. Panel Width: Standard panel is 8.2 ft (2500 mm) wide.4. Panel Height: 4 ft (1219 mm), with 2 reinforcement ribs.5. Panel Height: 5 ft (1524 mm), with 3 reinforcement ribs.6. Panel Height: 6 ft (1829 mm), with 3 reinforcement ribs.7. Panel Height: 8 ft (2438 mm), with 4 reinforcement ribs.8. Panel Height: As scheduled and indicated on Drawings.

B. Wire Mesh Panels: Horizontal and vertical wires welded to form 2 x 6 inches (51 x 152 mm) rectangles.1. Panel Construction: Resistance welded as per ASTM A1064 using 6 gauge (0.1921)

galvanized steel wire.2. Wire Tensile Strength: 70000 psi (483 MPa) minimum.3. Wire Break Strength: 2100 lbs (952 kg) minimum.4. Vertical Wires of Mesh: Extend 1 inch (25 mm) from the last or first horizontal wire

thereby creating a spiked top or bottom, depending on position when installed.

C. Square Tubular Posts:1. Minimum Yield Strength: 33000 psi (227 MPa) minimum.2. Finish: Factory galvanized to meet requirements of ASTM A653 with minimum zinc

coating weight of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

D. Fittings and Fasteners:1. Post Caps: Press on type steel caps.

a. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps galvanized to ASTM A123, finished to match fence finish and color.

2. Post Brackets: Galvanized steel.3. Post Brackets: As scheduled and indicated on Drawings.4. Fasteners: Stainless steel.5. Fasteners: Galvanized steel.6. Fasteners: Zinc plated.7. Fasteners: Nylon face mount brackets, finished to match fence finish and color.8. Fasteners: As scheduled and indicated on Drawings.

32 31 00 -6

Page 7:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

E. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.6. Frame Members: MIG welded.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

F. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied polyester powder coating.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 90

percent as measured by tape test, Method B.3. Film Thickness, ASTM G12: Min 2.0 mils (0.05 mm).4. Gloss 60 Angle, ASTM D523: Min 50.5. Accelerated Weathering, ASTM G154: 1000 hours after test, UVA 340 cycle of 4h

irradiation at 60 degrees (0.89 W per sq m per Nm) plus 4h condensation at 40 degrees.

6. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

7. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

8. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance:1) ASTM D1654: The required is minimum of seven on the scribed edge.2) ASTM D714: Minimum blister rating of eight on unscribed.

G. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).

32 31 00 -7

Page 8:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

c. Maximum Size Aggregate: 1 inch (25 mm).5. Footings:

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.4 BARRIERS AND PERIMETER SECURITY FENCE SYSTEMS (Guardian Series Security Mesh)

A. Barriers and Perimeter Security Fences:1. Basis of Design: Guardian 2000 Mesh Fence Systems as manufactured by Betafence.2. Basis of Design: Guardian 5000 High Security Mesh Fence Systems as manufactured

by Betafence.3. Basis of Design: Guardian Series Security Mesh as manufactured by Betafence, Style

as scheduled and indicated on Drawings.

B. Fence Framework:1. Square Tubular Posts:

a. Fabrication: Material greater than 3/16 inch (4.8 mm), and larger than 6 inches (152 mm) O.D. formed per ASTM A53, ASTM A500 Grade B, or ASTM A501, with minimum yield strength of 46000 psi (317 MPa).

b. Minimum Yield Strength, ASTM F2408: 45000 psi (310 MPa) minimum.c. Finish, ASTM A123: Hot dipped galvanized in accordance with ASTM A123.

2. Round Tubular Posts: Fabrication.a. Material for post and rails up to and including 5 inches (127 mm) O.D. to meet

the requirements of ASTM F1043, Group IC.b. Material for post larger than 5 inches (127 mm) O.D. to meet the requirements

of ASTM F1043, Group IA.

C. Panels: Panel joint extrusion manufactured per ASTM B221 to manufacturer's standard, size and shape as shown on the Drawings.

D. Security Mesh:1. Infill Panel Type: DutyGuard Welded Wire.2. Infill Panel Type: SecuriGuard Woven Wire.3. Infill Panel Type: SentryGuard Expanded Metal.4. Infill Panel Type: LouverMesh 75.5. Infill Panel Type: LouverMesh 94.6. Infill Panel Type: As scheduled and indicated on Drawings.

E. Fittings and Fasteners:1. Post Caps:

a. Description: Press on type steel caps.b. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps

galvanized to ASTM A123, finished to match fence finish and color.2. Rail Attachments / Brackets: Galvanized steel.3. Rail Attachments / Brackets: Stainless steel.4. Rail Attachments / Brackets: As scheduled and indicated on Drawings.5. Fasteners: Stainless steel.6. Fasteners: Galvanized steel.7. Fasteners: Zinc plated.8. Fasteners: As scheduled and indicated on Drawings.

F. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.

32 31 00 -8

Page 9:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

6. Frame Members: MIG welded.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

G. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied TGIC polyester powder coating of the Super-Durable class.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 90

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 9 N m resistance of organic

coatings to the effects of rapid deformation (impact).4. Film Hardness, ASTM D3363: Minimum 2H hardness as measured by pencil test.5. Solar Concentration Exposure, ASTM D4141: Coating must test to a minimum of 50

percent gloss retention at 1400 MJ/m2 with no film failure, chalking, cracking or checking and no more than 10 percent fading as measured by Conducting Black Box and Solar Concentrating Exposures of Coatings Test, Method C (equivalent to EMMAQUA NTW).

6. Film Thickness, ASTM G12: 2.0 mils (0.05 mm); 2 - 4 mils (0.05 - 0.1 mm) as measured by manufacturer's powder coat measurement and inspection procedures.

7. Flexibility, ASTM D1737: No breaks, flakes or cracks on Q-panel 5B; 100 percent adhesion to the substrate.

8. Gloss 60 Angle, ASTM D523: 50 - 60.9. Abrasion Resistance, ASTM D1044: 0.0032 oz (90 - 95 mg) weight loss.10. Accelerated Weathering, ASTM G23: 1000 hrs, 70 percent gloss retention, DeltaE

less than 2.0.11. Humidity, ASTM D2247: 1000 hours, no blisters.12. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage

Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

13. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

14. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance: Minimum of 7 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D1654.

H. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.

32 31 00 -9

Page 10:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.5 RESIDENTIAL ORNAMENTAL FENCE SYSTEMS (TruView Residential Series)

A. Residential Ornamental Fence Systems:1. Basis of Design: TruView Residential Series, Pinnacle 2-Rail Style Ornamental Fence

Systems as manufactured by Betafence.2. Basis of Design: TruView Residential Series, Pinnacle 3-Rail Style Ornamental Fence

Systems as manufactured by Betafence.3. Basis of Design: TruView Residential Series, Summit 2-Rail Style Ornamental Fence

Systems as manufactured by Betafence.4. Basis of Design: TruView Residential Series, Summit 3-Rail Style Ornamental Fence

Systems as manufactured by Betafence.5. Basis of Design: TruView Residential Series, Landmark 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.6. Basis of Design: TruView Residential Series, Landmark 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.7. Basis of Design: TruView Residential Series as manufactured by Betafence, Style as

scheduled and indicated on Drawings.8. Panels, Rails and Posts: Shipped from factory pre-cut to lengths as scheduled and

indicated on Drawings.9. Fencing System Design: Fully rakeable with no welds and pickets to mechanically

connected to rails.10. Panel Width: Standard panel is 8 ft (2438 mm) wide.11. Panel Height: Nominal 6 ft (1829 mm).12. Panel Height: Nominal 8 ft (2438 mm).13. Panel Height: As scheduled and indicated on Drawings.

B. Pickets: 5/8 inch (16 mm) square tubing.1. Wall thickness: 18 gauge.2. Spacing: 3.85 inches (98 mm) gap.3. Minimum Yield Strength: 33000 psi (227 MPa) minimum.4. Finish: Factory galvanized to meet requirements of ASTM A653 with minimum zinc

coating weight of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

C. Post and Rails: Per ASTM F2408 and shall be pre galvanized to meet requirements of ASTM A653 with a minimum zinc coating weight of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.1. Rails: 1.10 x 1.18 inches (28 x 30 mm) formed channel with 16 gauge wall thickness.2. Posts: 2 inches (51 mm) square tubing with 14 gauge wall thickness.3. Post Caps:

a. Description: Press on type steel caps.b. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps

galvanized to ASTM A123, finished to match fence finish and color.4. Panel Hangers: Galvanized steel.5. Panel Hangers: As scheduled and indicated on Drawings.6. Fasteners: Stainless steel.

32 31 00 -10

Page 11:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

7. Fasteners: Galvanized steel.8. Fasteners: Zinc plated.9. Fasteners: As scheduled and indicated on Drawings.10. Picket Finials: Types 1, Round point; cast alloy.11. Picket Finials: Type 2, Spear point; cast alloy.12. Picket Finials: Type 3, Fleur de Lis; cast alloy.13. Picket Finials: As scheduled and indicated on Drawings.

D. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.6. Fabrication: MIG welded at factory; frame uprights assembled in the field.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

E. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied powder coating.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 90

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 40 in-lbs (4.5 N-m) resistance of

organic coatings to the effects of rapid deformation (impact).4. Film Thickness, ASTM G12: 2.0 mils (0.05 mm); 2 - 4 mils (0.05 - 0.1 mm) as

measured by manufacturer's powder coat measurement and inspection procedures.5. Gloss 60 Angle, ASTM D523: 75 - 80.6. Accelerated Weathering, ASTM G154: 1000 hrs; 0.89 W per sq m per nm, for UVA

340 cycles of 4 hrs irradiation at 60 degrees (16 degrees C) and 4 hrs condensation at 40 degrees F (4.4 degrees C).

7. Pretreatment: Fence sheeting and framework prepared and cleaned using 5 stage Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

8. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

9. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

32 31 00 -11

Page 12:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

b. Performance: Minimum of 5 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D714.

F. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.6 COMMERCIAL ORNAMENTAL FENCE SYSTEMS (UpGrade-C Commercial Series)

A. Commercial Ornamental Fence Systems:1. Basis of Design: UpGrade-C Commercial Series, Pinnacle 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.2. Basis of Design: UpGrade-C Commercial Series, Pinnacle 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.3. Basis of Design: UpGrade-C Commercial Series, Pinnacle 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.4. Basis of Design: UpGrade-C Commercial Series, Summit 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.5. Basis of Design: UpGrade-C Commercial Series, Summit 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.6. Basis of Design: UpGrade-C Commercial Series, Summit 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.7. Basis of Design: UpGrade-C Commercial Series, Landmark 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.8. Basis of Design: UpGrade-C Commercial Series, Landmark 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.9. Basis of Design: UpGrade-C Commercial Series, Landmark 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.10. Basis of Design: UpGrade-C Commercial Series as manufactured by Betafence, Style

as scheduled and indicated on Drawings.11. Panels, Rails and Posts: Shipped from factory pre-cut to lengths as scheduled and

indicated on Drawings.12. Panel Width: Standard panel is 8 ft (2438 mm) wide.13. Panel Height: 4 ft (1219 mm).14. Panel Height: 5 ft (1524 mm).15. Panel Height: 6 ft (1829 mm).16. Panel Height: 7 ft (2134 mm).17. Panel Height: 8 ft (2438 mm).18. Panel Height: As scheduled and indicated on Drawings.

B. Pickets: 3/4 inch (19 mm) square tubing.1. Wall Thickness: 16 gauge.2. Wall Thickness: 18 gauge.3. Wall Thickness: As scheduled and indicated on Drawings.4. Spacing: 4-19/32 inches (116 mm) on center.5. Minimum Yield Strength, ASTM F2408: 45000 psi (310 MPa) minimum.6. Finish: Factory galvanized meeting ASTM A653 requirements with zinc coating weight

of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

32 31 00 -12

Page 13:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

C. Post and Rails: Per ASTM F2408 and shall be pre galvanized to meet requirements of ASTM A653 with a minimum zinc coating weight of 0.90 oz per sq ft (275 g per sq m) coating designation G-90 or equivalent.1. Rails: 1-1/2 inches (37 mm) formed channel with 15 gauge wall thickness.2. Posts: 2-1/2 inches (64 mm) square tubing.

a. Tube Wall Thickness: 12 gauge.b. Tube Wall Thickness: 14 gauge.c. Tube Wall Thickness: As scheduled and indicated on Drawings.

3. Post Caps:a. Description: Press on type steel caps.b. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps

galvanized to ASTM A123, finished to match fence finish and color.4. Panel Hangers: Galvanized steel.5. Panel Hangers: Stainless steel.6. Panel Hangers: As scheduled and indicated on Drawings.7. Fasteners: Stainless steel.8. Fasteners: Galvanized steel.9. Fasteners: Zinc plated.10. Fasteners: As scheduled and indicated on Drawings.11. Picket Finials: Types 1, Round point; cast alloy.12. Picket Finials: Type 2, Spear point; cast alloy.13. Picket Finials: Type 3, Fleur de Lis; cast alloy.14. Picket Finials: As scheduled and indicated on Drawings.

D. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.6. Fabrication: MIG welded at factory; frame uprights assembled in the field.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

E. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied TGIC polyester powder coating of the Super-Durable class.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 95

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 9 N m resistance of organic

coatings to the effects of rapid deformation (impact).4. Film Hardness, ASTM D3363: Minimum 2H hardness as measured by pencil test.5. Solar Concentration Exposure, ASTM D4141: Coating must test to a minimum of 50

percent gloss retention at 1400 MJ/m2 with no film failure, chalking, cracking or checking and no more than 10 percent fading as measured by Conducting Black Box and Solar Concentrating Exposures of Coatings Test, Method C (equivalent to

32 31 00 -13

Page 14:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

EMMAQUA NTW).6. Film Thickness, ASTM G12: 2.0 mils (0.05 mm); 2 - 4 mils (0.05 - 0.1 mm) as

measured by manufacturer's powder coat measurement and inspection procedures.7. Flexibility, ASTM D1737: No breaks, flakes or cracks on Q-panel 5B; 100 percent

adhesion to the substrate.8. Gloss 60 Angle, ASTM D523: 50 - 60.9. Abrasion Resistance, ASTM D1044: 0.0032 oz (90 - 95 mg) weight loss.10. Accelerated Weathering, ASTM G23: 1000 hrs, 70 percent gloss retention, DeltaE

less than 2.0.11. Humidity, ASTM D2247: 1000 hours, no blisters.12. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage

Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

13. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

14. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance: Minimum of 7 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D1654.

F. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.7 INDUSTRIAL ORNAMENTAL FENCE SYSTEMS (UpGrade-I Industrial Series)

A. Industrial Ornamental Fence Systems:1. Basis of Design: UpGrade-I Industrial Series, Pinnacle 2-Rail Style Ornamental Fence

Systems as manufactured by Betafence.2. Basis of Design: UpGrade-I Industrial Series, Pinnacle 3-Rail Style Ornamental Fence

Systems as manufactured by Betafence.3. Basis of Design: UpGrade-I Industrial Series, Pinnacle 4-Rail Style Ornamental Fence

Systems as manufactured by Betafence.4. Basis of Design: UpGrade-I Industrial Series, Summit 2-Rail Style Ornamental Fence

Systems as manufactured by Betafence.5. Basis of Design: UpGrade-I Industrial Series, Summit 3-Rail Style Ornamental Fence

Systems as manufactured by Betafence.6. Basis of Design: UpGrade-I Industrial Series, Summit 4-Rail Style Ornamental Fence

Systems as manufactured by Betafence.7. Basis of Design: UpGrade-I Industrial Series, Landmark 2-Rail Style Ornamental

32 31 00 -14

Page 15:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

Fence Systems as manufactured by Betafence.8. Basis of Design: UpGrade-I Industrial Series, Landmark 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.9. Basis of Design: UpGrade-I Industrial Series, Landmark 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.10. Basis of Design: UpGrade-I Industrial Series, Defender 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.11. Basis of Design: UpGrade-I Industrial Series, Defender 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.12. Basis of Design: UpGrade-I Industrial Series, Defender 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.13. Basis of Design: UpGrade-I Industrial Series as manufactured by Betafence, Style as

scheduled and indicated on Drawings.14. Panels, Rails and Posts: Shipped from factory pre-cut to lengths as scheduled and

indicated on Drawings.15. Panel Width: Standard panel is 8 ft (2438 mm) wide.16. Panel Height: 4 ft (1219 mm).17. Panel Height: 5 ft (1524 mm).18. Panel Height: 6 ft (1829 mm).19. Panel Height: 7 ft (2134 mm).20. Panel Height: 8 ft (2438 mm).21. Panel Height: 10 ft (3048 mm).22. Panel Height: As scheduled and indicated on Drawings.

B. Pickets: 1 inch (25 mm) square tubing.1. Wall Thickness: 16 gauge.2. Spacing: 4-27/32 inches (123 mm) on center.3. Minimum Yield Strength, ASTM F2408: 45000 psi (310 MPa) minimum.4. Finish: Factory galvanized to meet requirements of ASTM A653 with minimum zinc

coating weight of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

5. Finish: Factory galvanized meeting ASTM A653 requirements with zinc coating weight of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

6. Finish: As scheduled and indicated on Drawings.

C. Post and Rails: Per ASTM F2408 and shall be pre galvanized to meet requirements of ASTM A653 with a minimum zinc coating weight of 0.90 oz per sq ft (275 g per sq m) coating designation G-90 or equivalent.1. Rails: 1-1/2 inches (37 mm) formed channel with 15 gauge wall thickness.2. Posts: 2-1/2 inches (64 mm) square tubing.

a. Tube Wall Thickness: 12 gauge.b. Tube Wall Thickness: 14 gauge.c. Tube Wall Thickness: As scheduled and indicated on Drawings.

3. Rails: 2 inches (51 mm) formed channel with 13 gauge wall thickness.4. Posts: Steel tubing.

a. Tube Dimensions: 2-1/2 inches (64 mm) square, 12 gauge.b. Tube Dimensions: 3 inches (76 mm) square 14 gauge.c. Tube Dimensions: As scheduled and indicated on Drawings.

5. Post Caps:a. Description: Press on type steel caps.b. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps

galvanized to ASTM A123, finished to match fence finish and color.6. Panel Hangers: Galvanized steel.7. Panel Hangers: Stainless steel.8. Panel Hangers: As scheduled and indicated on Drawings.9. Fasteners: Stainless steel.

32 31 00 -15

Page 16:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

10. Fasteners: Galvanized steel.11. Fasteners: Zinc plated.12. Fasteners: As scheduled and indicated on Drawings.13. Picket Finials: Types 1, Round point; cast alloy.14. Picket Finials: Type 2, Spear point; cast alloy.15. Picket Finials: Type 3, Fleur de Lis; cast alloy.16. Picket Finials: As scheduled and indicated on Drawings.

D. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.6. Fabrication: MIG welded at factory; frame uprights assembled in the field.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.c. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.d. Hinge Pins: Non-removable.

E. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied TGIC polyester powder coating of the Super-Durable class.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 95

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 9 N m resistance of organic

coatings to the effects of rapid deformation (impact).4. Film Hardness, ASTM D3363: Minimum 2H hardness as measured by pencil test.5. Solar Concentration Exposure, ASTM D4141: Coating must test to a minimum of 50

percent gloss retention at 1400 MJ/m2 with no film failure, chalking, cracking or checking and no more than 10 percent fading as measured by Conducting Black Box and Solar Concentrating Exposures of Coatings Test, Method C (equivalent to EMMAQUA NTW).

6. Film Thickness, ASTM G12: 2.0 mils (0.05 mm); 2 - 4 mils (0.05 - 0.1 mm) as measured by manufacturer's powder coat measurement and inspection procedures

7. Flexibility, ASTM D1737: No breaks, flakes or cracks on Q-panel 5B; 100 percent adhesion to the substrate.

8. Gloss 60 Angle, ASTM D523: 50 - 60.9. Abrasion Resistance, ASTM D1044: 0.0032 oz (90 - 95 mg) weight loss.10. Accelerated Weathering, ASTM G23: 1000 hrs, 70 percent gloss retention, DeltaE

less than 2.0.11. Humidity, ASTM D2247: 1000 hours, no blisters.12. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage

Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

13. Curing: Heat cure in accordance with powder manufacturer's prescribed cure

32 31 00 -16

Page 17:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

schedule to crosslink and bond finish to metal substrate.14. Chemical Resistance, ASTM B117:

a. Procedure to Test Corrosion Resistance:1) Preparation of Test Specimens: Perform a single scribe the length of the

specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance: Minimum of 7 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D1654.

F. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

2.8 HEAVY INDUSTRIAL ORNAMENTAL FENCE SYSTEMS (UpGrade-H Industrial Series)

A. Heavy Industrial Ornamental Fence Systems:1. Basis of Design: UpGrade-H Industrial Series, Pinnacle 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.2. Basis of Design: UpGrade-H Industrial Series, Pinnacle 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.3. Basis of Design: UpGrade-H Industrial Series, Pinnacle 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.4. Basis of Design: UpGrade-H Industrial Series, Summit 2-Rail Style Ornamental Fence

Systems as manufactured by Betafence.5. Basis of Design: UpGrade-H Industrial Series, Summit 3-Rail Style Ornamental Fence

Systems as manufactured by Betafence.6. Basis of Design: UpGrade-H Industrial Series, Summit 4-Rail Style Ornamental Fence

Systems as manufactured by Betafence.7. Basis of Design: UpGrade-H Industrial Series, Landmark 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.8. Basis of Design: UpGrade-H Industrial Series, Landmark 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.9. Basis of Design: UpGrade-H Industrial Series, Landmark 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.10. Basis of Design: UpGrade-H Industrial Series, Defender 2-Rail Style Ornamental

Fence Systems as manufactured by Betafence.11. Basis of Design: UpGrade-H Industrial Series, Defender 3-Rail Style Ornamental

Fence Systems as manufactured by Betafence.12. Basis of Design: UpGrade-H Industrial Series, Defender 4-Rail Style Ornamental

Fence Systems as manufactured by Betafence.13. Basis of Design: UpGrade-H Industrial Series as manufactured by Betafence, Style as

scheduled and indicated on Drawings.14. Panels, Rails and Posts: Shipped from factory pre-cut to lengths as scheduled and

32 31 00 -17

Page 18:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

indicated on Drawings.15. Panel Width: Standard panel is 8 ft (2438 mm) wide.16. Panel Height: 4 ft (1219 mm).17. Panel Height: 5 ft (1524 mm).18. Panel Height: 6 ft (1829 mm).19. Panel Height: 7 ft (2134 mm).20. Panel Height: 8 ft (2438 mm).21. Panel Height: 10 ft (3048 mm).22. Panel Height: As scheduled and indicated on Drawings.

B. Pickets: 1 inch (25 mm) square tubing.1. Wall Thickness: 14 gauge.2. Spacing: 4-27/32 inches (123 mm) on center.3. Minimum Yield Strength, ASTM F2408: 45000 psi (310 MPa) minimum.4. Finish: Factory galvanized meeting ASTM A653 requirements with zinc coating weight

of 0.60 oz per sq ft (183 g per sq m) coating designation G-60 or equivalent.

C. Post and Rails: Per ASTM F2408 and shall be pre galvanized to meet requirements of ASTM A653 with a minimum zinc coating weight of 0.90 oz per sq ft (275 g per sq m) coating designation G-90 or equivalent.1. Rails: 1-1/2 inches (37 mm) formed channel with 15 gauge wall thickness.2. Posts: 2-1/2 inches (64 mm) square tubing, 14 gauge wall thickness.3. Rails: 2 inches (51 mm) formed channel with 13 gauge wall thickness.4. Posts: Steel tubing.

a. Tube Dimensions: 2-1/2 inches (64 mm) square, 12 gauge.b. Tube Dimensions: 3 inches (76 mm) square 14 gauge.c. Tube Dimensions: As scheduled and indicated on Drawings.

5. Post Caps:a. Description: Press on type steel caps.b. Finishing: Zinc plated to ASTM B633, Service class II or malleable steel caps

galvanized to ASTM A123, finished to match fence finish and color.6. Panel Hangers: Galvanized steel.7. Panel Hangers: Stainless steel.8. Panel Hangers: As scheduled and indicated on Drawings.9. Fasteners: Stainless steel.10. Fasteners: Galvanized steel.11. Fasteners: Zinc plated.12. Fasteners: As scheduled and indicated on Drawings.13. Picket Finials: Types 1, Round point; cast alloy.14. Picket Finials: Type 2, Spear point; cast alloy.15. Picket Finials: Type 3, Fleur de Lis; cast alloy.16. Picket Finials: As scheduled and indicated on Drawings.

D. Gates:1. Operation: Swing gates, design as indicated on submittals and Drawings.2. Operation: Slide gates, design as indicated on submittals and Drawings.3. Operation: Cantilever gates, design as indicated on submittals and Drawings.4. Operation: Overhead track gates, design as indicated on submittals and Drawings.5. Operation: Function and design as indicated on submittals and Drawings.6. Fabrication: MIG welded at factory; frame uprights assembled in the field.7. Reinforcement: Truss rods or cables as required to prevent gate sag, permit smooth

operation and allow future adjustment.8. Gate Frames and Infill Panels: Style, finish and color to match fence panels.9. Gate Posts and Foundations: Dimensions as determined by Engineer, based on gate

size, local wind loading requirements, and installation type.10. Gate Keepers: Mechanical device for securing free end of gate when in fully open

32 31 00 -18

Page 19:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

position; one provided for each gate leaf over 5 ft (1524 m) wide.11. Latch: Capable of retaining gate in closed position; with provision for padlock.12. Hinges: Manufacturer's standard hinges, structurally capable of supporting gate leaf

and allow opening and closing without binding.a. Design: Non-lift-off type hinge permitting gate to swing 180 degrees.b. Hinge Pins: Non-removable.

E. Finishes: Posts, post caps, rails, panels, brackets and security mesh finished with a factory applied TGIC polyester powder coating of the Super-Durable class.1. Color: Black.2. Adhesion Resistance, ASTM D3359: Minimum coating retention of not less than 95

percent as measured by tape test, Method B.3. Impact Resistance, ASTM D2794: Pass, minimum 9 N m resistance of organic

coatings to the effects of rapid deformation (impact).4. Film Hardness, ASTM D3363: Minimum 2H hardness as measured by pencil test.5. Solar Concentration Exposure, ASTM D4141: Coating must test to a minimum of 50

percent gloss retention at 1400 MJ/m2 with no film failure, chalking, cracking or checking and no more than 10 percent fading as measured by Conducting Black Box and Solar Concentrating Exposures of Coatings Test, Method C (equivalent to EMMAQUA NTW).

6. Film Thickness, ASTM G12: 2.0 mils (0.05 mm) minimum.7. Flexibility, ASTM D1737: No breaks, flakes or cracks on Q-panel 5B; 100 percent

adhesion to the substrate.8. Gloss 60 Angle, ASTM D523: 50 - 60.9. Abrasion Resistance, ASTM D1044: 0.0032 oz (90 - 95 mg) weight loss.10. Accelerated Weathering, ASTM G23: 1000 hrs, 70 percent gloss retention, DeltaE

less than 2.0.11. Humidity, ASTM D2247: 1000 hours, no blisters.12. Film Thickness: 2 - 4 mils (0.05 - 0.1 mm) as by manufacturer's powder coat

measurement and inspection procedures.13. Pretreatment: Fence sheeting and framework prepared and cleaned using 7 stage

Zinc Phosphate wash line; removes foreign material and prepares the surface to comply with requirements of coating systems as specified above.

14. Curing: Heat cure in accordance with powder manufacturer's prescribed cure schedule to crosslink and bond finish to metal substrate.

15. Chemical Resistance, ASTM B117:a. Procedure to Test Corrosion Resistance:

1) Preparation of Test Specimens: Perform a single scribe the length of the specimen, within 1 inch (25 mm) of any edge and deep enough to expose the base metal.

2) Expose specimen for 1000 hrs according to ASTM B117 using 5 percent salt solution and 95 degrees F (35 degrees C) operational temperature.

3) After exposure, remove specimens and wipe dry; immediately apply tape (Permacel 99 or equal) over scribed are by pressing down firmly against the coating; sharply pull tape off at a right angle to surface being tested.

b. Performance: Minimum of 7 on the scribed edge and minimum blister rating of eight within the test specimen field in accordance with tables in ASTM D1654.

F. Concrete Footings: Complying with ACI 301 for cast-in-place concrete.1. Portland Cement: Complying with ASTM C150.2. Aggregates: Complying with ASTM C33.3. Water: Potable.4. Concrete Mixes: Normal-weight concrete air entrained.

a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Slump: 3 inches (75 mm).c. Maximum Size Aggregate: 1 inch (25 mm).

32 31 00 -19

Page 20:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

5. Footings:a. Compressive Strength, 28 days: Over 3000 psi (20.7 MPa).b. Footing sizes as determined by Engineer.

PART 3 EXECUTION

3.1 EXAMINATION

A. Verify areas to receive fencing. Do not proceed with preparation or installation until unacceptable conditions have been corrected have been prepared using the methods recommended by the manufacturer and deviations from manufacturer's recommended tolerances are corrected. Commencement of installation constitutes acceptance of conditions.

B. If preparation is the responsibility of another installer, notify Architect in writing of deviations from manufacturer's recommended installation tolerances and conditions.

3.2 INSTALLATION

A. Installation of Fences and Gates: Install in accordance with manufacturer's instructions, approved submittals and in proper relationship with adjacent construction at locations indicated on the Drawings.1. Install gates level, plumb, and secure for full opening without interference. Attach

hardware using tamper-resistant or concealed means. Install ground-set items in concrete for anchorage. Adjust gate to operate smoothly, easily, and quietly throughout entire operational range. Confirm that latches and locks engage accurately and securely without forcing or binding.

2. Install fencing to withstand wind load as specified.3. Space posts at dimensions indicated on Drawings.4. Attach fence rails to posts using panel hanger brackets or nylon face mount brackets

supplied by manufacturer.5. Handle fence components to protect finish coating from any scuffs, abrasion or other

damage during installation. Excessive damage to factory applied coatings will be cause for rejection.

6. Avoid unnecessary cutting, drilling and welding of pre-finished fence components. If necessary to cut drill, weld or otherwise modify product due to field conditions.

7. Field welding of panels to posts is unacceptable as it will cause significant damage to the galvanizing and powder coat protective finishes.

B. Installation of Concrete Footings:1. Place concrete around posts and vibrate or tamp for consolidation.2. Verify that posts are set plumb, aligned, and at correct height and spacing, and

stabilized in position during placement and finishing operations until concrete is sufficiently cured.

3. Protect portion of posts above ground from concrete splatter.

3.3 CLEANING AND PROTECTION

A. Clean and protect products in accordance with the manufacturer's recommendations.

B. Touch-up, repair or replace damaged products before Substantial Completion.1. Touch-up any necessary areas by lightly sanding; apply a zinc-rich cold galvanizing

primer followed by a high quality acrylic lacquer paint to match finish.2. Touch-up paint available from manufacturer.

C. Level uneven areas due to excavations created by fence installations.

32 31 00 -20

Page 21:  · Web viewSECTION 32 31 00 FENCES AND GATES - SECURITY AND ORNAMENTAL Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2020 - 2020 ARCAT, Inc. - All

END OF SECTION

32 31 00 -21