PRODUCT DATA 63-2528-2 fi U.S. Registered Trademark Copyright ' 2001 Honeywell All Rights Reserved W6210A,D and W7210A,D Solid State Economizer Logic Module APPLICATION W6210A,D and W7210A,D Solid State Economizer™ Logic Modules are used with solid state C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and Honeywell Series 62 and Series 72 actuators to proportion outdoor and return air dampers for economizer control in commercial HVAC equipment. FEATURES Operates from the cooling space thermostat to provide a totally integrated control system. Solid state control package provides accuracy, reliability and stability. Combines solid state enthalpy or dry bulb changeover control, minimum damper position potentiometer and compressor staging relay functions. Optional differential enthalpy control provides greater economizer savings than single enthalpy control by selecting the most economical air for cooling. Differential enthalpy control uses two sensor inputs, one in return air and one in outdoor air then economizer control selects the air with the lower enthalpy. Housed in high-impact, glass-fiber reinforced plastic case. Enthalpy setpoint (A-D) on W6210 and W7210 Solid State Economizer Logic Module controls the combination of air temperature and humidity suitable for free cooling. All models include a built-in adjustable potentiometer to set minimum damper position and minimum amount of outdoor air admitted to meet minimum ventilation requirements. Terminals included for connecting optional S963B1128 Remote Minimum Position Potentiometer for remote damper control. LED indicates when free cooling is available. Mount on the sheet metal duct. Mounting screws included. W6210A and W7210A accept inputs from discharge air temperature sensors or mixed air temperature sensors, and C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and optional remote minimum position damper potentiometers. W6210D and W7210D return to mechanical cooling when outdoor air enthalpy reaches preset high limits. Contents Application ........................................................................ 1 Features ........................................................................... 1 Specifications ................................................................... 2 Ordering Information ........................................................ 2 Installation ........................................................................ 3 Settings and Adjustments ................................................. 5 Checkout and Troubleshooting ......................................... 22

Upload: others

Post on 19-Mar-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

PRODUCT DATA

63-2528-2

® U.S. Registered TrademarkCopyright © 2001 Honeywell � All Rights Reserved

W6210A,D and W7210A,DSolid State Economizer Logic Module

APPLICATIONW6210A,D and W7210A,D Solid State Economizer� Logic Modules are used with solid state C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and Honeywell Series 62 and Series 72 actuators to proportion outdoor and return air dampers for economizer control in commercial HVAC equipment.

FEATURES� Operates from the cooling space thermostat to provide

a totally integrated control system.� Solid state control package provides accuracy,

reliability and stability.� Combines solid state enthalpy or dry bulb changeover

control, minimum damper position potentiometer and compressor staging relay functions.

� Optional differential enthalpy control provides greater economizer savings than single enthalpy control by selecting the most economical air for cooling. Differential enthalpy control uses two sensor inputs, one in return air and one in outdoor air then economizer control selects the air with the lower enthalpy.

� Housed in high-impact, glass-fiber reinforced plastic case.

� Enthalpy setpoint (A-D) on W6210 and W7210 Solid State Economizer Logic Module controls the combination of air temperature and humidity suitable for free cooling.

� All models include a built-in adjustable potentiometer to set minimum damper position and minimum amount of outdoor air admitted to meet minimum ventilation requirements. Terminals included for connecting optional S963B1128 Remote Minimum Position Potentiometer for remote damper control.

� LED indicates when free cooling is available.� Mount on the sheet metal duct. Mounting screws

included.� W6210A and W7210A accept inputs from discharge air

temperature sensors or mixed air temperature sensors, and C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and optional remote minimum position damper potentiometers.

� W6210D and W7210D return to mechanical cooling when outdoor air enthalpy reaches preset high limits.

ContentsApplication ........................................................................ 1Features ........................................................................... 1Specifications ................................................................... 2Ordering Information ........................................................ 2Installation ........................................................................ 3Settings and Adjustments ................................................. 5Checkout and Troubleshooting ......................................... 22

Page 2: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 2

ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Home and Building Control Sales Office (check white pages of your phone directory).2. Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive NorthMinneapolis, Minnesota 55422-4386

In Canada�Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONSModels: See Table 1.

Dimensions: See Fig. 1.

Electrical Ratings (W6210/W7210 with C7400):Input Voltage: 24 Vac, 50/60 Hz.Power Consumption:

W6210: 7 VAW7210: 4.5 VA.

Relay Contact Rating at 24 Vac: 1.5A run, 3.5A inrush.

Temperature Ratings:Operating Ambient: -25°F to +125°F (-32°C to +52°C).

Humidity: 5 to 95 percent relative humidity (RH).

Approvals: Underwriters Laboratories Inc.: Flammability Rating UL94V-5V.

W6210D/W7210D Maximum Outdoor Enthalpy Switching:See Table 2.

Enthalpy Input (C7400):2-wire (18, 20, 22 AWG) connection.Can be mounted up to 200 ft (61m) from logic module.

Dry Bulb Temperature Input (C7650A):Two-wire (18, 20, 22 AWG) connection.Can be mounted up to 200 ft (61m) from logic module.

Minimum Position Potentiometer:Resistance: 250 ohms.Minimum Setting: 0 to 100 percent of motor stroke.

Accessories:32004783-001 Weather Shield for Economizers.4074EJM 620 ohm Resistor, Jumper, and 1.2K ohm Checkout

Resistor.C7046A Discharge Air Temperature Sensor.C7150B Mixed Air Temperature Sensor.C7400 Solid State Enthalpy Sensor.C7650A Dry Bulb Temperature Sensor.T675 or T6031 Remote Bulb Control for low ambient lockout.S963B1128 Remote Minimum Position Potentiometer to

provide remote control of damper position.ST6008 Energy Management Timer for occupied/unoccupied

control.

Fig. 1. W6210/W7210 dimensions in in. (mm).[W7210 shown]

2-10VOUT

24 VACHOT

24 VACCOM

1

TR1 COM

+

+

+

B

A D

C

TRHOT

24 VAC

SO

SR

5

2

4

T1

P1

3

T

P

MINIMUMPOSITION

OPEN

FREECOOLING

W72

10 A

100

1

5 3/16(132)

4 11/16 (119)

3/4 (19)1 9/16(40)

5/8 (16)

C8380A

Page 3: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

3 63-2528�2

Table 1. W6210 and W7210 Economizer Models.

a W6210D and W7210D have high enthalpy limit and default to mechanical cooling when outdoor enthalpy reaches the preset limit. Do not use a dry bulb sensor for high temperature limit. See Fig. 16 through 18 for parallel wiring options.

Table 2. W6210, W7210D Free Cooling Mode Switching.

INSTALLATIONWhen Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3. Installer must be a trained, experienced service technician.

4. After installation is complete, check out product operation as provided in these instructions.

IMPORTANTAll wiring must agree with applicable codes, ordinances and regulations.

CAUTIONElectrical Shock or Equipment Damage Hazard.Can shock individuals or short equipment circuitry.Disconnect all power supplies before installation.Motors with auxiliary switches can have more than one disconnect.

Location and Mounting

W6210/W7210 Economizer Control PackageW6210 and W7210 Economizers mount directly on the sheet metal duct. They can also be panel mounted. When planning the installation, allow enough clearance for maintenance and service. Mount W6210/W7210 Economizer Control Packages in a location protected from rain and snow. Secure the W6210/W7210 to the sheet metal using three mounting screws (supplied). See Fig. 2.

Fig. 2. Mounting W6210/7210 on sheet metal.

ModelFor Use with

ActuatorDischarge Air

Temperature Input

Minimum Position Potentiometer

Adjustment

Terminals for Remote Minimum Damper Position Output Relays

W6210A Honeywell Series 62 C7150B or C7046A Sensor Yes Yes 2 spdt

W6210Da Honeywell Series 62 C7150B or C7046A Sensor Yes Yes 2 spdt

W7210A Honeywell Series 72 C7150B or C7046A Sensor Yes Yes 2 spdt

W7210Da Honeywell Series 72 C7150B or C7046A Sensor Yes Yes 2 spdt

Outdoor RH

(percent)

Into Free Cooling (LED On)

on Decreasing Outdoor Enthalpy

Out of Free Cooling (LED Off)

on Increasing Outdoor Enthalpy

25 83°F±0.5°F 85°F±0.5°F

50 78°F±0.5°F 80°F±0.5°F

60 76°F±0.5°F 78°F±0.5°F

75 73°F±0.5°F 75°F±0.5°F

C8381A

W62

10 A

100

3

Page 4: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 4

C7400 Enthalpy SensorOUTDOOR AIR SENSING

1. Mount the C7400 Enthalpy Sensor in any orientation where it is exposed to freely circulating air and protected from rain, snow, and direct sunlight.

2. Connect it to the SO and + terminals of the W6210A,D or W7210A,D.

RETURN AIR SENSING1. Differential enthalpy control requires a second C7400

Enthalpy Sensor in the return air duct.2. Connect this sensor to the SR and + terminals of the

W6210A,D or W7210A,D.

C7650A Dry Bulb Temperature Sensor

IMPORTANTDo not use the C7650A with the W6210D or W7210D.

OUTDOOR AIR SENSING1. Mount the C7650A Dry Bulb Sensor in any orientation

that exposes it to freely circulating air and protects it from rain, snow, and direct sunlight.

2. Connect it to the SO and + terminals of the W6210A or W7210A.

RETURN AIR SENSING1. Differential dry bulb control requires a second C7650A

Dry Bulb Temperature Sensor in the return air duct.2. Connect it to the SR and + terminals of the W6210A or

W7210A.

Wiring

CAUTIONElectrical Shock or Equipment Damage Hazard.Can shock individuals or short equipment circuitry.Disconnect all power supplies before installation.Motors with auxiliary switches can have more than one disconnect.

IMPORTANTAll wiring must comply with applicable local codes, ordinances and regulations.

NOTE: Refer to Fig. 7 through 20 for typical wiring diagrams.

Table 3. Applicable Wiring Diagrams.

Logic Module Actuator Enthalpy Changeover Figure Comments

W6210A,D Honeywell Series 62 Single 7 Single-stage cooling system

9 Two-stage cooling system

Single or Differential 11 Single-stage cooling system

13 T7400/W7400 System

W7210A,D Honeywell Series 72 Single 8 Single-stage cooling system

10 Two-stage cooling system

Single or Differential 12 Single-stage cooling system

14 T7400/W7400 System

15 T775 Controller

ALL n/a n/a 19 W7100 Controller

20 W973 Logic Panel

3 S963 remote damper control

Parallel Wiring

W7210A,D Honeywell Series 72 Single or Differential 16 Honeywell Series 72 Direct Coupled Actuators

17 Honeywell Series 72 Modutrol Motors

Honeywell M7415 18 M7415 Motors

Page 5: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

5 63-2528�2

Fig. 3. S963B1128 Remote Minimum Position Potentiometer used with W6210/W7210

for remote damper control.

Optional Applications

Remote Minimum Position ControlRemote control of outdoor air dampers is desirable when temporary additional ventilation is required. The potentiometer in the W6210/W7210 controls the minimum position of the dampers. The addition of an S963B1128 Remote Minimum Position Potentiometer allows occupants to open dampers beyond minimum position for additional ventilation. Connect the potentiometer as shown in Fig. 3.

SETTINGS AND ADJUSTMENTSPotentiometers with screwdriver adjustment slots, located on the face of the device, provide adjustments for minimum damper position and enthalpy changeover. See Fig. 4.

Fig. 4. Location of enthalpy setpoint potentiometer, minimum position

potentiometer and LED.(W7210 shown)

Adjusting Minimum Damper PositionThe minimum position potentiometer keeps the outdoor air damper from closing completely during system operation to provide ventilation.

Minimum Position Adjustment1. Disconnect mixed air sensor from terminals T and T1.2. Make sure either the factory-installed jumper is in place

across terminals P and P1 or, if remote damper position is required, that it is wired according to Fig. 3 and turned fully clockwise .

3. Connect 24 Vac across terminals TR and TR1.4. Adjust the potentiometer on the W6210/W7210 face

with a screwdriver for desired minimum position.

Outdoor Enthalpy Changeover SetpointThe outdoor enthalpy changeover setpoint returns the outdoor air damper to minimum position when enthalpy rises above its setpoint. Enthalpy setpoint scale markings, located in the W6210/W7210, are A, B, C, and D. See Fig. 6 for the corresponding control point. The factory-installed 620 ohm jumper must be in place across terminals SR and +.

M11159

P1P

W6210/W7210 ECONOMIZER

R

MINIMUM POSITIONADJUSTMENT

W B

CWCLOSE

CCWOPEN

S963B1128 REMOTEMINIMUM POSITIONPOTENTIOMETER

135 OHM

OPEN

CW

2-10VOUT

24 VACHOT

24 VACCOM

1

TRCOM1

+

+

B

A D

C

TRHOT

24 VAC

SO

SR

5

2

4

T1

P1

3

T

P

MINIMUMPOSITION

OPEN

FREECOOLING

W72

10 A

100

1

ENTHALPYCHANGEOVERSETPOINT

MINIMUMDAMPERPOSITION SETTING

LED LIGHTSWHENOUTDOOR AIRIS SUITABLE FORFREE COOLING

M11162A

+

Page 6: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 6

Differential Enthalpy Changeover SettingDifferential enthalpy control uses two C7400 Enthalpy Sensors connected to one economizer module. The economizer compares outdoor air to the return air instead of to a set point (as with single enthalpy). Turn the setpoint potentiometer fully clockwise to the D setting. The economizer selects the lower enthalpy air (return or outdoor) for cooling for example, when outdoor air has lower enthalpy than return air, the outdoor air damper opens to bring in outdoor air for free cooling.

High Enthalpy LimitW6210D and W7210D Economizer Logic Modules have a high outdoor air enthalpy limit feature when used in differential enthalpy mode. The limit feature prevents using high enthalpy outdoor air when return air enthalpy is higher than that of outdoor air (see Table 2).

Integrated Economizer System (Fig. 5)

Operation: Single (Outdoor) EnthalpyThe purpose of an economizer is to use outdoor air for cooling, whenever possible, to reduce compressor operation.

The W6210/W7210 Economizer System, when wired as shown in Fig. 7 through 14, responds to a signal from the cooling thermostat. This system uses Solid State C7400 Enthalpy Changeover Sensor or the C7650A Dry Bulb Temperature Sensor. The C7400 responds to both dry bulb temperature and humidity, allowing use of outdoor air at

higher temperatures for free cooling when humidity is low. The C7650A responds to only dry bulb temperature and should be used only in dry, arid climates.

The economizer functions as a true first stage of cooling and provides maximum fuel economy during the cooling cycle. The economizer is automatically locked out during heating. It holds the outdoor air damper at the minimum position setting.

When the space thermostat calls for cooling, the system operates as follows:

Outdoor Air Enthalpy Is Below Setpoint1. The outdoor air damper is proportioned open (and the

return air damper is proportioned closed) to maintain between 50°F and 56°F at the mixed/discharge air sensor.

2. During economizer operation, mechanical cooling is operated by the second stage of cooling on the space thermostat.

Outdoor Air Enthalpy Is Above Setpoint1. The outdoor air damper closes to its minimum position.2. A call for cooling from the space thermostat brings on

mechanical cooling.3. During the unoccupied period, the actuator spring return

moves the outdoor air damper to the fully closed position.

NOTE: See Fig. 5 for representative locations of economizer system devices.

Fig. 5. Location of C7400 Outdoor and Return Air Sensors, C7150 Mixed Air Sensor, andC7046 Discharge Air Sensor in an economizer system.

DISCHARGEAIR SENSOR

C7046A

DIRECT EXPANSIONCOIL

C7400

ENTHALPYSENSOR

C7400 ENTHALPYSENSOR

RETURN AIR

OUTDOORAIR

C7150B

MIXED AIRSENSOR

SPACE THERMOSTATOR T7400/W7400PROGRAMMABLESINGLE ZONE SYSTEM

FOR DIFFERENTIAL ENTHALPY, THE TWO C7400 ENTHALPY SENSORS ARE CONNECTED TO THE W6210/W7210 ECONOMIZER CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY.

M11161

1

1

1

SERIES62 OR 72ACTUATOR

W6210ORW7210

Page 7: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

7 63-2528�2

Fig. 6. W6210 and W7210/C7400 performance characteristics for enthalpy changeover settings.

CONTROLCURVE

ABCD

CONTROL POINTAPPROX. °F (°C)

AT 50% RH

73 (23)70 (21)67 (19)63 (17)

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

90100

8070

60

50

40

30

20

10

ENTHALP

Y—BTU

PER P

OUND D

RY AIR

85(29)

90(32)

95(35)

100(38)

105(41)

110(43)

35(2)

35(2)

40(4)

40(4)

105(41)

110(43)

45(7)

45(7)

50(10)

50(10)

55(13)

55(13)

60(16)

60(16)

65(18)

65(18)

70(21)

70(21)

75(24)

75(24)

80(27)

80(27)

85(29)

90(32)

95(35)

100(38)

APPROXIMATE DRY BULB TEMPERATURE—°F (°C)

A

A

B

B

C

C

D

D

M11160

RE

LATI

VE

HU

MID

ITY

(%)

1

1

HIGH LIMIT CURVE FOR W6210D,W7210D.

Page 8: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 8

Fig. 7. W6210A,D used in single-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.

M11151B

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

9

9

6

TR TR1

SO

SR

+

+

W6210A,D

+

C

G

W1

Y1

R

W2

RC

G

X

W1

Y1

W2

C7400ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

8

8

7

7

2

51K

4

5

T

6

1S

1S1

MINIMUM POSITIONADJUSTMENT

C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

HONEYWELLSERIES 62ACTUATOR

(ML6275,ML6285,M6275,M6285)

24 VAC HOT

24 VAC COM

OPEN

OPEN

WIPER

CLOSED

500 OHM

CLOSE

1 2

Page 9: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

9 63-2528�2

Fig. 8. W7210A,D used in single-stage cooling system with single enthalpy changeover and Honeywell Series 72 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.

M11152A

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

9

9

6

TR TR1

SO

SR

+

+

+

W7210A,D

+

C

G

W1

Y1

R

W2

RC

G

X

W1

Y1

W2

C7400ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

8

7

7

8

2

51K

4

5

T

6

1S

2-10VOUT

1S1

MINIMUM POSITIONADJUSTMENT

C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

HONEYWELLSERIES 72ACTUATOR

(ML7275,ML7285,ML7295A,CM7275,M7285)

24 VAC HOT

24 VAC COM

+

1 2

Page 10: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 10

Fig. 9. W6210A,D used in two-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.

M11153C

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

6

8

7

TR TR1

SO

SR

+

+

W6210A,D

+

C

G

W1

Y1

R

W2

RC

G

X

W1

Y1

Y2

W2

C7400OUTDOORAIR ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

2

51K

COOL 2Y2

4

5

T

6

7

8

1S

1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

W

R

T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT

RH

HONEYWELLSERIES 62ACTUATOR

(ML6275,ML6285,M6275,M6285)

24 VAC HOT

24 VAC COM

CLOSE

OPEN

OPEN

WIPER

CLOSED

500 OHM

MINIMUM POSITIONADJUSTMENT

9

9

1 2

Page 11: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

11 63-2528�2

Fig. 10. W7210A,D used in two-stage cooling system with single enthalpy changeover and Honeywell Series 72 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.

M11154B

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

6

8

7

TR TR1

SO

SR

+

+

W7210A,D

+

C

G

W1

Y1

R

W2

RC

G

X

W1

Y1

Y2

W2

C7400OUTDOORAIR ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

2

51K

COOL 2Y2

4

5

T

6

7

8

1S

1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

W

R

T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT

RH

MINIMUM POSITIONADJUSTMENT

9

9

1 2

+

2-10VOUT

24 VAC HOT

24 VAC COM

HONEYWELLSERIES 72ACTUATOR

(ML7275,ML7285,ML7295A,CM7275,M7285)

+

Page 12: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 12

Fig. 11. W6210A,D used in single-stage cooling system with differential enthalpy changeover and Honeywell Series 62 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

W

R

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE OUTDOOR AIR ENTHALPY IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

C7400OUTDOORAIRENTHALPYSENSOR

C7400RETURNAIRENTHALPYSENSOR

1

1

2

3

4

TR TR1

SO

SR

+

+

W6210A,D

+

C

G

W1

Y1

Y2

R

W2

S

+

RC

G

X

W1

Y1

Y2

W2

RH

T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

2

5

6

8

7

1K

4

5

T

6

7

8

1S

1S1

C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR

24 VAC HOT

24 VAC COM

CLOSE

OPEN

500 OHM

MINIMUM POSITIONADJUSTMENT

OPEN

WIPER

CLOSED

M11157C

HONEYWELLSERIES 62ACTUATOR

1 2

9

9

Page 13: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

13 63-2528�2

Fig. 12. W7210A,D used in single-stage cooling system with differential enthalpy changeover and Honeywell Series 72 Actuator.

L1 (HOT)

L2

FDR

FDR

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

W

R

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE OUTDOOR AIR ENTHALPY IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.

FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.

M11158A

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4 2K

S

C7400OUTDOORAIRENTHALPYSENSOR

C7400RETURNAIRENTHALPYSENSOR

1

1

2

3

4

9

9

8

7

TR TR1

SO

SR

+

+

W7210A,D

+

C

G

W1

Y1

Y2

R

W2

S

+

RC

G

X

W1

Y1

Y2

W2

RH

T6031 AMBIENT LOCKOUT CONTROL 50˚F SETPOINT

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

2

5

6

1K

4

5

T

6

7

8

1S

1S1

C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR

HONEYWELLSERIES 72ACTUATOR

(ML7275,ML7285,ML7295A,CM7275,M7285)

24 VAC HOT

24 VAC COM

MINIMUM POSITIONADJUSTMENT

+

2-10VOUT

5

2

+

1 2

Page 14: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 14

Fig. 13. W6210A,D used with T7400/W7400 System and Honeywell Series 62 Actuator.

L1 (HOT)

L2

FDR

3K1

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

W

R

14 23 R

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

USE R8222N WITH PILOT DUTY CONTACTS FOR 3K. CONTACTS 3K1, 3K2 MAKE WHEN ENTHALPY IS BELOW SETPOINTAND ECONOMIZER IS USED FOR FIRST STAGE OF COOLING.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS. BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.

M11155C

T7400 THERMOSTAT

T7400/W7400 SYSTEM

P1P

T1

1

3 4

2

5

2K

S

C7400ENTHALPYSENSOR

1

1

2

3

4

6

TR TR1

SO

SR

+

+

W6210A,D

+

C

G

W1

Y1

Y2

R

W2

T6031 LOCKOUT 50 F SETPOINT

3

2

6

5

7

61K

COOL 2

4

5

T

6

7

8

8

1S

1S1

C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR

W7400 CONTROL MODULE

T7400B ONLY;T7047C1025 ORT7022A1010REMOTE SENSOR

620 OHMRESISTOR

3K RELAY

3K2

1

WALLPLATE OR Q7400 SUBBASE

HONEYWELLSERIES 62ACTUATOR

(ML6275,ML6285,M6275,M6285)

CLOSE

OPEN

OPEN

WIPER

CLOSED

500 OHM

24 VAC HOT

24 VAC COM

GND

TR

TR

RH

RC

4

3

2

1

A

COM

B

Y1

Y2

W1

W2

G

RC

RH

RC

24 VAC

T7400

ECONO.AUXRELAY

ENTHALPYSWITCH

6

5

MINIMUM POSITIONADJUSTMENT

Page 15: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

15 63-2528�2

Fig. 14. W7210A,D used with T7400/W7400 System and Honeywell Series 72 Actuator.

L1 (HOT)

L2

FDR

3K1

FAN

FANDELAYRELAY

HEAT 1

HEAT 2

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

W

R

14 23 R

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

USE R8222N WITH PILOT DUTY CONTACTS FOR 3K. CONTACTS 3K1, 3K2 MAKE WHEN ENTHALPY IS BELOW SETPOINTAND ECONOMIZER IS USED FOR FIRST STAGE OF COOLING.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.

M11156A

T7400 THERMOSTAT

T7400/W7400 SYSTEM

P1P

T1

1

3 4

2

5

2K

S

C7400ENTHALPYSENSOR

1

1

2

3

4

8

8

TR TR1

SO

SR

+

+

W7210A,D

+

C

G

W1

Y1

Y2

R

W2

T6031 LOCKOUT 50˚F SETPOINT

3

2

6

6

5

7

61K

COOL 2

4

5

T

6

7

1S

1S1

C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR

T7400B ONLY;T7047C1025 ORT7022A1010REMOTE SENSOR

620 OHMRESISTOR

3K RELAY

3K2

1

WALLPLATE OR Q7400 SUBBASE

HONEYWELLSERIES 72ACTUATOR

(ML7275,ML7285,ML7295A,CM7275,M7285)

24 VAC HOT

24 VAC COM

GND

TR

TR

RH

RC

4

3

2

1

A

COM

B

Y1

Y2

W1

W2

G

RC

RH

RC

24 VAC

T7400

ECONO.AUXRELAY

ENTHALPYSWITCH

6

5

W7400 CONTROL MODULE

MINIMUM POSITIONADJUSTMENT

+

2-10VOUT

+

Page 16: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 16

Fig. 15. W7210A,D used with T775 Controller and Honeywell Series 72 Actuator.

L1 (HOT)

L2

FAN

COOL 1

HVAC EQUIPMENTTERMINAL STRIP

M15298

P1P

T1

1

3 4

2

5

2K

S

1

2

4

6

TR TR1

SO

SR

+

+

W7210A,D

+

C

G

Y1

R

C7400OUTDOORAIR ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

3

51K

COOL 2Y2

T

1S

1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

W

R

T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT

HONEYWELLSERIES 72ACTUATOR

(ML7275,ML7285,ML7295A,CM7275,M7285)

24 VAC HOT

24 VAC COM

MINIMUM POSITIONADJUSTMENT

7

NOCOM

NC

NCCOM

NO

NCCOMNO

T775 THERMOSTAT

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED FOR THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.

1S IS AN ELECTRONIC SWITCH, WHICH CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.

T775 REQUIRES A MINIMUM OF THREE RELAY OUTPUTS: TWO FOR COOLING AND ONE FOR FAN CONTROL.A MAXIMUM OF ONE STAGE OF HEATING IS POSSIBLE WHEN THE SYSTEM IS WIRED IN THIS FASHION.

FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.

1

2

3

4

5

6

7

8

8

+

2-10VOUT

+

Page 17: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

17 63-2528�2

Fig. 16. W7210A,D controlling parallel wired Honeywell Series 72 Direct Coupled Actuators.

L1 (HOT)

L2

FDR

FDR

FAN

HEAT 1

HEAT 2

COOL 1

COOL 2

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15299

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

1

3

6

TR TR1

SO

SR

+

+

+

W7210A,D

+

C

G

W1

Y1

Y2

R

W2

RC

G

X

W1

RH

Y1

Y2

W2

C7400ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

8

7

7

8

2

51K

4

5

T

6

1S

2-10VOUT

1S1

MINIMUM POSITIONADJUSTMENT

C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

24 VAC HOT

24 VAC COMRED

BLACK

WHITE

BROWN

RED

BLACK

WHITE

BROWN

ML7285

ML7285

1 2

Page 18: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 18

Fig. 17. W7210A,D controlling parallel wired Honeywell Series 72 Modutrol� Motors.

L1 (HOT)

L2

FDR

FDR

FAN

HEAT 1

HEAT 2

COOL 1

COOL 2

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15300

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

1

3

6

TR TR1

SO

SR

+

+

+

W7210A,D

+

C

G

W1

Y1

Y2

R

W2

RC

G

X

W1

RH

Y1

Y2

W2

C7400ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

8

7

7

8

2

51K

4

5

T

6

1S

2-10VOUT

1S1

MINIMUM POSITIONADJUSTMENT

C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

24 VAC HOT

24 VAC COM

T1

T2

T1

T2

+

+

SERIES 72MODUTROLMOTOR

SERIES 72MODUTROLMOTOR

1 2

Page 19: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

19 63-2528�2

Fig. 18. W7210A,D controlling parallel wired M7415 Economizer Motors.

L1 (HOT)

L2

FDR

FDR

FAN

HEAT 1

HEAT 2

COOL 1

COOL 2

HVAC EQUIPMENTTERMINAL STRIP

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.

ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.

1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.

RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.

FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.

FOR T7300 ONLY.

FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15301

T7300 OR T874THERMOSTAT

P1P

T1

1

3 4

2

5

2K

S

1

1

2

3

4

1

3

6

TR TR1

SO

SR

+

+

+

+

+

W7210A,D

+

C

G

W1

Y1

Y2

R

W2

RC

G

X

W1

RH

Y1

Y2

W2

C7400ENTHALPY SENSOR

UNOCCUPIED

OCCUPIED

ST6008TIMER

8

7

7

8

2

51K

4

5

T

6

1S

2-10VOUT

1S1

MINIMUM POSITIONADJUSTMENT

C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR

620 OHMRESISTOR

24 VAC HOT

24 VAC COMTR

TR1

P1

P

TR

TR1

P1

P

Q769C

Q769C

M7415

M7415

1 2

Page 20: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 20

Fig. 19. W6210, W7210 used with W7100 Controller.

GNDTR

TR

W

RBY

109

24 VAC

ECONO

CHANGEOVER

BCA

6COOL

BCA

5COOL

BCA

4COOL

BCA

3COOL

BCA

2COOL

BCA

1COOL

1

3 4

2

5

2K

W6210/W7210 ECONOMIZER

1K

1S

1S1

HONEYWELLACTUATOR

1

3

2

1

2

3

W

R

AT72A (40 VA)TRANSFORMER

L2

L1(HOT)

W7100

COOL 6

COOL 5

COOL 4

COOL 3

COOL 2

COOL 1

POWERSUPPLY

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

510 OHM 1/4 WATT. 5 PERCENT RESISTOR (CONTAINED IN 4074EFV BAG ASSEMBLY) ELIMINATES ECONOMIZER DELAYS.

ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL. M20058

T6031 AMBIENT LOCKOUT CONTROL

50 F SETPOINT

Page 21: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

21 63-2528�2

Fig. 20. W6210, W7210 used with W973 Logic Panel.

1

3 4

2

5

2K

W6210/W7210 LOGIC MODULE

1K1S

1S1

HONEYWELLACTUATOR

1

2

1

2

W

R

L2L1(HOT)

COOL 3

COOL 2

COOL 1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL.

M20059

2 1COOL

3 HEAT 3 COOL

2 1HEAT

MOD-HEAT

WH BH RH

MOD-COOL

RC BC WC

T T1 3 4 2 5 1 TR TR

SENSOR STAT 24 VACC +20 H N

W973B LOGIC PANEL

T6031 AMBIENT LOCKOUT CONTROL

50 F SETPOINT

Page 22: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

63-2528�2 22

CHECKOUT AND TROUBLESHOOTING

CAUTIONEquipment Damage Hazard.Excessive force can damage potentiometer controls.Use a small screwdriver when adjusting enthalpy changeover and minimum damper position controls.

To check the motor, jumper T to T1 to bypass the mixed air sensor.

Use Table 4 and Fig. 21 for checkout.

Fig. 21. Meter location for checkout and troubleshooting.

1

+

+

B

A D

CTR TR1

S

5

2

4

T1

P1

3

T

P

MINIMUMPOSITION

OPEN

FREECOOLING

ENTHALPYCHANGEOVERSETPOINT

LED LIGHTS WHEN OUTDOOR AIRIS SUITABLE FOR FREE COOLING

M11163A

S

+1

1

2

2

620 OHMJUMPER

DCMILLIAMMETER

INSERT DC MILLIAMMETER BETWEEN SO AND S FORCHECKOUT AND TROUBLESHOOTING.

JUMPER USED FOR SINGLE ENTHALPY CONTROL.

C7400

W6210

O

SR

Page 23: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE

23 63-2528�2

Table 4. W6210A,D and W7210A,D Economizer Connected to Honeywell Actuator.

Checkout Procedure Proper Response

1. a. Disconnect power at TR and TR1. �

b. Disconnect P to P1 jumper.

c. Jumper TR to 1.

d. Jumper T1 to T.

e. If connected, remove C7400 Enthalpy Sensor from terminals SO and +. Ensure factory-installed 620 ohm resistor is connected to terminals SR and +.

� LED is off.

f. Apply power (24 Vac) to terminals TR and TR1. � Motor is in closed position.

2. Disconnect factory-installed 620 ohm resistor from terminals SR and +.

� LED turns on (A models only; for D models, go to step 3).� Motor drives toward open.

3. Simulate high and low enthalpy (single enthalpy sensor):

a. Reconnect factory-installed 620 ohm resistor across terminals SR and +.Connect 1.2K ohm 4074EJM Checkout Resistor across terminals SO and +.

b. Turn enthalpy setpoint potentiometer to A. � LED turns on, indicating low enthalpy.� Motor drives toward open.

c. Turn enthalpy setpoint potentiometer to D. � LED turns off, indicating high enthalpy.� Motor drives toward closed.

d. Disconnect the 1.2K ohm checkout resistor. �

4. a. To verify sensor operation, reconnect the + lead of the outdoor enthalpy sensor to the + terminal of the W6210/W7210 Economizer.

b. Connect a dc milliammeter between terminals SO of the W6210/W7210 and terminal S of the enthalpy sensor. (Connect the positive meter lead to terminal S of the enthalpy sensor.)

� Milliammeter indicates between 3 and 25 mA when the sensor is operating properly.

� If the milliammeter indicates zero, the sensor may be wired backward.

c. When using differential enthalpy, check the return air enthalpy sensor by connecting a dc milliammeter between terminal SR of the W6210/W7210 and terminal S or the return air enthalpy sensor. (Connect the positive meter lead to terminal S of the return air enthalpy sensor.)

� Milliammeter indicates between 3 and 25 mA when the sensor is operating properly.

� If the milliammeter indicates zero, the sensor may be wired backward.

Page 24: W6210A,D and W7210A,D Solid State Economizer …...W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE 3 63-2528Š2 Table 1. W6210 and W7210 Economizer Models. a W6210D and W7210D

63-2528�2 B.B. Rev. 9-01 www.honeywell.com/building/componentsPrinted in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.

Home and Building Control Home and Building Control Honeywell International Honeywell Europe S.A.Honeywell Latin AmericanHoneywell Honeywell Limited-Honeywell Limitée Home and Building Control 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate ParkwayGolden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200