W6210A,D and W7210A,DSolid State Economizer Logic Module
APPLICATIONW6210A,D and W7210A,D Solid State Economizer� Logic Modules are used with solid state C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and Honeywell Series 62 and Series 72 actuators to proportion outdoor and return air dampers for economizer control in commercial HVAC equipment.
FEATURES� Operates from the cooling space thermostat to provide
a totally integrated control system.� Solid state control package provides accuracy,
reliability and stability.� Combines solid state enthalpy or dry bulb changeover
control, minimum damper position potentiometer and compressor staging relay functions.
� Optional differential enthalpy control provides greater economizer savings than single enthalpy control by selecting the most economical air for cooling. Differential enthalpy control uses two sensor inputs, one in return air and one in outdoor air then economizer control selects the air with the lower enthalpy.
� Housed in high-impact, glass-fiber reinforced plastic case.
� Enthalpy setpoint (A-D) on W6210 and W7210 Solid State Economizer Logic Module controls the combination of air temperature and humidity suitable for free cooling.
� All models include a built-in adjustable potentiometer to set minimum damper position and minimum amount of outdoor air admitted to meet minimum ventilation requirements. Terminals included for connecting optional S963B1128 Remote Minimum Position Potentiometer for remote damper control.
� LED indicates when free cooling is available.� Mount on the sheet metal duct. Mounting screws
included.� W6210A and W7210A accept inputs from discharge air
temperature sensors or mixed air temperature sensors, and C7400 Enthalpy Sensors or C7650A Dry Bulb Temperature Sensors and optional remote minimum position damper potentiometers.
� W6210D and W7210D return to mechanical cooling when outdoor air enthalpy reaches preset high limits.
ContentsApplication ........................................................................ 1Features ........................................................................... 1Specifications ................................................................... 2Ordering Information ........................................................ 2Installation ........................................................................ 3Settings and Adjustments ................................................. 5Checkout and Troubleshooting ......................................... 22
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 2
ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive NorthMinneapolis, Minnesota 55422-4386
In Canada�Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONSModels: See Table 1.
Dimensions: See Fig. 1.
Electrical Ratings (W6210/W7210 with C7400):Input Voltage: 24 Vac, 50/60 Hz.Power Consumption:
W6210: 7 VAW7210: 4.5 VA.
Relay Contact Rating at 24 Vac: 1.5A run, 3.5A inrush.
Temperature Ratings:Operating Ambient: -25°F to +125°F (-32°C to +52°C).
Humidity: 5 to 95 percent relative humidity (RH).
Approvals: Underwriters Laboratories Inc.: Flammability Rating UL94V-5V.
W6210D/W7210D Maximum Outdoor Enthalpy Switching:See Table 2.
Enthalpy Input (C7400):2-wire (18, 20, 22 AWG) connection.Can be mounted up to 200 ft (61m) from logic module.
Dry Bulb Temperature Input (C7650A):Two-wire (18, 20, 22 AWG) connection.Can be mounted up to 200 ft (61m) from logic module.
Minimum Position Potentiometer:Resistance: 250 ohms.Minimum Setting: 0 to 100 percent of motor stroke.
Accessories:32004783-001 Weather Shield for Economizers.4074EJM 620 ohm Resistor, Jumper, and 1.2K ohm Checkout
Resistor.C7046A Discharge Air Temperature Sensor.C7150B Mixed Air Temperature Sensor.C7400 Solid State Enthalpy Sensor.C7650A Dry Bulb Temperature Sensor.T675 or T6031 Remote Bulb Control for low ambient lockout.S963B1128 Remote Minimum Position Potentiometer to
provide remote control of damper position.ST6008 Energy Management Timer for occupied/unoccupied
control.
Fig. 1. W6210/W7210 dimensions in in. (mm).[W7210 shown]
2-10VOUT
24 VACHOT
24 VACCOM
1
TR1 COM
+
+
–
+
B
A D
C
TRHOT
24 VAC
SO
SR
5
2
4
T1
P1
3
T
P
MINIMUMPOSITION
OPEN
FREECOOLING
W72
10 A
100
1
5 3/16(132)
4 11/16 (119)
3/4 (19)1 9/16(40)
5/8 (16)
C8380A
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
3 63-2528�2
Table 1. W6210 and W7210 Economizer Models.
a W6210D and W7210D have high enthalpy limit and default to mechanical cooling when outdoor enthalpy reaches the preset limit. Do not use a dry bulb sensor for high temperature limit. See Fig. 16 through 18 for parallel wiring options.
Table 2. W6210, W7210D Free Cooling Mode Switching.
INSTALLATIONWhen Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
IMPORTANTAll wiring must agree with applicable codes, ordinances and regulations.
CAUTIONElectrical Shock or Equipment Damage Hazard.Can shock individuals or short equipment circuitry.Disconnect all power supplies before installation.Motors with auxiliary switches can have more than one disconnect.
Location and Mounting
W6210/W7210 Economizer Control PackageW6210 and W7210 Economizers mount directly on the sheet metal duct. They can also be panel mounted. When planning the installation, allow enough clearance for maintenance and service. Mount W6210/W7210 Economizer Control Packages in a location protected from rain and snow. Secure the W6210/W7210 to the sheet metal using three mounting screws (supplied). See Fig. 2.
Fig. 2. Mounting W6210/7210 on sheet metal.
ModelFor Use with
ActuatorDischarge Air
Temperature Input
Minimum Position Potentiometer
Adjustment
Terminals for Remote Minimum Damper Position Output Relays
W6210A Honeywell Series 62 C7150B or C7046A Sensor Yes Yes 2 spdt
W6210Da Honeywell Series 62 C7150B or C7046A Sensor Yes Yes 2 spdt
W7210A Honeywell Series 72 C7150B or C7046A Sensor Yes Yes 2 spdt
W7210Da Honeywell Series 72 C7150B or C7046A Sensor Yes Yes 2 spdt
Outdoor RH
(percent)
Into Free Cooling (LED On)
on Decreasing Outdoor Enthalpy
Out of Free Cooling (LED Off)
on Increasing Outdoor Enthalpy
25 83°F±0.5°F 85°F±0.5°F
50 78°F±0.5°F 80°F±0.5°F
60 76°F±0.5°F 78°F±0.5°F
75 73°F±0.5°F 75°F±0.5°F
C8381A
W62
10 A
100
3
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 4
C7400 Enthalpy SensorOUTDOOR AIR SENSING
1. Mount the C7400 Enthalpy Sensor in any orientation where it is exposed to freely circulating air and protected from rain, snow, and direct sunlight.
2. Connect it to the SO and + terminals of the W6210A,D or W7210A,D.
RETURN AIR SENSING1. Differential enthalpy control requires a second C7400
Enthalpy Sensor in the return air duct.2. Connect this sensor to the SR and + terminals of the
W6210A,D or W7210A,D.
C7650A Dry Bulb Temperature Sensor
IMPORTANTDo not use the C7650A with the W6210D or W7210D.
OUTDOOR AIR SENSING1. Mount the C7650A Dry Bulb Sensor in any orientation
that exposes it to freely circulating air and protects it from rain, snow, and direct sunlight.
2. Connect it to the SO and + terminals of the W6210A or W7210A.
RETURN AIR SENSING1. Differential dry bulb control requires a second C7650A
Dry Bulb Temperature Sensor in the return air duct.2. Connect it to the SR and + terminals of the W6210A or
W7210A.
Wiring
CAUTIONElectrical Shock or Equipment Damage Hazard.Can shock individuals or short equipment circuitry.Disconnect all power supplies before installation.Motors with auxiliary switches can have more than one disconnect.
IMPORTANTAll wiring must comply with applicable local codes, ordinances and regulations.
NOTE: Refer to Fig. 7 through 20 for typical wiring diagrams.
Table 3. Applicable Wiring Diagrams.
Logic Module Actuator Enthalpy Changeover Figure Comments
W6210A,D Honeywell Series 62 Single 7 Single-stage cooling system
9 Two-stage cooling system
Single or Differential 11 Single-stage cooling system
13 T7400/W7400 System
W7210A,D Honeywell Series 72 Single 8 Single-stage cooling system
10 Two-stage cooling system
Single or Differential 12 Single-stage cooling system
14 T7400/W7400 System
15 T775 Controller
ALL n/a n/a 19 W7100 Controller
20 W973 Logic Panel
3 S963 remote damper control
Parallel Wiring
W7210A,D Honeywell Series 72 Single or Differential 16 Honeywell Series 72 Direct Coupled Actuators
17 Honeywell Series 72 Modutrol Motors
Honeywell M7415 18 M7415 Motors
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
5 63-2528�2
Fig. 3. S963B1128 Remote Minimum Position Potentiometer used with W6210/W7210
for remote damper control.
Optional Applications
Remote Minimum Position ControlRemote control of outdoor air dampers is desirable when temporary additional ventilation is required. The potentiometer in the W6210/W7210 controls the minimum position of the dampers. The addition of an S963B1128 Remote Minimum Position Potentiometer allows occupants to open dampers beyond minimum position for additional ventilation. Connect the potentiometer as shown in Fig. 3.
SETTINGS AND ADJUSTMENTSPotentiometers with screwdriver adjustment slots, located on the face of the device, provide adjustments for minimum damper position and enthalpy changeover. See Fig. 4.
Fig. 4. Location of enthalpy setpoint potentiometer, minimum position
potentiometer and LED.(W7210 shown)
Adjusting Minimum Damper PositionThe minimum position potentiometer keeps the outdoor air damper from closing completely during system operation to provide ventilation.
Minimum Position Adjustment1. Disconnect mixed air sensor from terminals T and T1.2. Make sure either the factory-installed jumper is in place
across terminals P and P1 or, if remote damper position is required, that it is wired according to Fig. 3 and turned fully clockwise .
3. Connect 24 Vac across terminals TR and TR1.4. Adjust the potentiometer on the W6210/W7210 face
with a screwdriver for desired minimum position.
Outdoor Enthalpy Changeover SetpointThe outdoor enthalpy changeover setpoint returns the outdoor air damper to minimum position when enthalpy rises above its setpoint. Enthalpy setpoint scale markings, located in the W6210/W7210, are A, B, C, and D. See Fig. 6 for the corresponding control point. The factory-installed 620 ohm jumper must be in place across terminals SR and +.
M11159
P1P
W6210/W7210 ECONOMIZER
R
MINIMUM POSITIONADJUSTMENT
W B
CWCLOSE
CCWOPEN
S963B1128 REMOTEMINIMUM POSITIONPOTENTIOMETER
135 OHM
OPEN
CW
2-10VOUT
24 VACHOT
24 VACCOM
1
TRCOM1
+
+
B
A D
C
TRHOT
24 VAC
SO
SR
5
2
4
T1
P1
3
T
P
MINIMUMPOSITION
OPEN
FREECOOLING
W72
10 A
100
1
ENTHALPYCHANGEOVERSETPOINT
MINIMUMDAMPERPOSITION SETTING
LED LIGHTSWHENOUTDOOR AIRIS SUITABLE FORFREE COOLING
M11162A
+
–
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 6
Differential Enthalpy Changeover SettingDifferential enthalpy control uses two C7400 Enthalpy Sensors connected to one economizer module. The economizer compares outdoor air to the return air instead of to a set point (as with single enthalpy). Turn the setpoint potentiometer fully clockwise to the D setting. The economizer selects the lower enthalpy air (return or outdoor) for cooling for example, when outdoor air has lower enthalpy than return air, the outdoor air damper opens to bring in outdoor air for free cooling.
High Enthalpy LimitW6210D and W7210D Economizer Logic Modules have a high outdoor air enthalpy limit feature when used in differential enthalpy mode. The limit feature prevents using high enthalpy outdoor air when return air enthalpy is higher than that of outdoor air (see Table 2).
Integrated Economizer System (Fig. 5)
Operation: Single (Outdoor) EnthalpyThe purpose of an economizer is to use outdoor air for cooling, whenever possible, to reduce compressor operation.
The W6210/W7210 Economizer System, when wired as shown in Fig. 7 through 14, responds to a signal from the cooling thermostat. This system uses Solid State C7400 Enthalpy Changeover Sensor or the C7650A Dry Bulb Temperature Sensor. The C7400 responds to both dry bulb temperature and humidity, allowing use of outdoor air at
higher temperatures for free cooling when humidity is low. The C7650A responds to only dry bulb temperature and should be used only in dry, arid climates.
The economizer functions as a true first stage of cooling and provides maximum fuel economy during the cooling cycle. The economizer is automatically locked out during heating. It holds the outdoor air damper at the minimum position setting.
When the space thermostat calls for cooling, the system operates as follows:
Outdoor Air Enthalpy Is Below Setpoint1. The outdoor air damper is proportioned open (and the
return air damper is proportioned closed) to maintain between 50°F and 56°F at the mixed/discharge air sensor.
2. During economizer operation, mechanical cooling is operated by the second stage of cooling on the space thermostat.
Outdoor Air Enthalpy Is Above Setpoint1. The outdoor air damper closes to its minimum position.2. A call for cooling from the space thermostat brings on
mechanical cooling.3. During the unoccupied period, the actuator spring return
moves the outdoor air damper to the fully closed position.
NOTE: See Fig. 5 for representative locations of economizer system devices.
Fig. 5. Location of C7400 Outdoor and Return Air Sensors, C7150 Mixed Air Sensor, andC7046 Discharge Air Sensor in an economizer system.
DISCHARGEAIR SENSOR
C7046A
DIRECT EXPANSIONCOIL
C7400
ENTHALPYSENSOR
C7400 ENTHALPYSENSOR
RETURN AIR
OUTDOORAIR
C7150B
MIXED AIRSENSOR
SPACE THERMOSTATOR T7400/W7400PROGRAMMABLESINGLE ZONE SYSTEM
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400 ENTHALPY SENSORS ARE CONNECTED TO THE W6210/W7210 ECONOMIZER CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY.
M11161
1
1
1
SERIES62 OR 72ACTUATOR
W6210ORW7210
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
7 63-2528�2
Fig. 6. W6210 and W7210/C7400 performance characteristics for enthalpy changeover settings.
CONTROLCURVE
ABCD
CONTROL POINTAPPROX. °F (°C)
AT 50% RH
73 (23)70 (21)67 (19)63 (17)
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
90100
8070
60
50
40
30
20
10
ENTHALP
Y—BTU
PER P
OUND D
RY AIR
85(29)
90(32)
95(35)
100(38)
105(41)
110(43)
35(2)
35(2)
40(4)
40(4)
105(41)
110(43)
45(7)
45(7)
50(10)
50(10)
55(13)
55(13)
60(16)
60(16)
65(18)
65(18)
70(21)
70(21)
75(24)
75(24)
80(27)
80(27)
85(29)
90(32)
95(35)
100(38)
APPROXIMATE DRY BULB TEMPERATURE—°F (°C)
A
A
B
B
C
C
D
D
M11160
RE
LATI
VE
HU
MID
ITY
(%)
1
1
HIGH LIMIT CURVE FOR W6210D,W7210D.
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 8
Fig. 7. W6210A,D used in single-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.
M11151B
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
9
9
6
TR TR1
SO
SR
+
+
W6210A,D
+
C
G
W1
Y1
R
W2
RC
G
X
W1
Y1
W2
C7400ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
8
8
7
7
2
51K
4
5
T
6
1S
1S1
MINIMUM POSITIONADJUSTMENT
C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
HONEYWELLSERIES 62ACTUATOR
(ML6275,ML6285,M6275,M6285)
24 VAC HOT
24 VAC COM
OPEN
OPEN
WIPER
CLOSED
500 OHM
CLOSE
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
9 63-2528�2
Fig. 8. W7210A,D used in single-stage cooling system with single enthalpy changeover and Honeywell Series 72 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
M11152A
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
9
9
6
TR TR1
SO
SR
+
+
+
–
W7210A,D
+
C
G
W1
Y1
R
W2
RC
G
X
W1
Y1
W2
C7400ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
8
7
7
8
2
51K
4
5
T
6
1S
2-10VOUT
1S1
MINIMUM POSITIONADJUSTMENT
C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
HONEYWELLSERIES 72ACTUATOR
(ML7275,ML7285,ML7295A,CM7275,M7285)
24 VAC HOT
24 VAC COM
+
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 10
Fig. 9. W6210A,D used in two-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.
M11153C
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
6
8
7
TR TR1
SO
SR
+
+
W6210A,D
+
C
G
W1
Y1
R
W2
RC
G
X
W1
Y1
Y2
W2
C7400OUTDOORAIR ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
2
51K
COOL 2Y2
4
5
T
6
7
8
1S
1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
W
R
T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT
RH
HONEYWELLSERIES 62ACTUATOR
(ML6275,ML6285,M6275,M6285)
24 VAC HOT
24 VAC COM
CLOSE
OPEN
OPEN
WIPER
CLOSED
500 OHM
MINIMUM POSITIONADJUSTMENT
9
9
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
11 63-2528�2
Fig. 10. W7210A,D used in two-stage cooling system with single enthalpy changeover and Honeywell Series 72 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
M11154B
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
6
8
7
TR TR1
SO
SR
+
+
W7210A,D
+
C
G
W1
Y1
R
W2
RC
G
X
W1
Y1
Y2
W2
C7400OUTDOORAIR ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
2
51K
COOL 2Y2
4
5
T
6
7
8
1S
1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
W
R
T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT
RH
MINIMUM POSITIONADJUSTMENT
9
9
1 2
+
–
2-10VOUT
24 VAC HOT
24 VAC COM
HONEYWELLSERIES 72ACTUATOR
(ML7275,ML7285,ML7295A,CM7275,M7285)
+
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 12
Fig. 11. W6210A,D used in single-stage cooling system with differential enthalpy changeover and Honeywell Series 62 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
W
R
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE OUTDOOR AIR ENTHALPY IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS.BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
C7400OUTDOORAIRENTHALPYSENSOR
C7400RETURNAIRENTHALPYSENSOR
1
1
2
3
4
TR TR1
SO
SR
+
+
W6210A,D
+
C
G
W1
Y1
Y2
R
W2
S
+
RC
G
X
W1
Y1
Y2
W2
RH
T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
2
5
6
8
7
1K
4
5
T
6
7
8
1S
1S1
C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR
24 VAC HOT
24 VAC COM
CLOSE
OPEN
500 OHM
MINIMUM POSITIONADJUSTMENT
OPEN
WIPER
CLOSED
M11157C
HONEYWELLSERIES 62ACTUATOR
1 2
9
9
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
13 63-2528�2
Fig. 12. W7210A,D used in single-stage cooling system with differential enthalpy changeover and Honeywell Series 72 Actuator.
L1 (HOT)
L2
FDR
FDR
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
W
R
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE OUTDOOR AIR ENTHALPY IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.
FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
M11158A
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4 2K
S
C7400OUTDOORAIRENTHALPYSENSOR
C7400RETURNAIRENTHALPYSENSOR
1
1
2
3
4
9
9
8
7
TR TR1
SO
SR
+
+
W7210A,D
+
C
G
W1
Y1
Y2
R
W2
S
+
RC
G
X
W1
Y1
Y2
W2
RH
T6031 AMBIENT LOCKOUT CONTROL 50˚F SETPOINT
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
2
5
6
1K
4
5
T
6
7
8
1S
1S1
C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR
HONEYWELLSERIES 72ACTUATOR
(ML7275,ML7285,ML7295A,CM7275,M7285)
24 VAC HOT
24 VAC COM
MINIMUM POSITIONADJUSTMENT
+
–
2-10VOUT
5
2
+
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 14
Fig. 13. W6210A,D used with T7400/W7400 System and Honeywell Series 62 Actuator.
L1 (HOT)
L2
FDR
3K1
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
W
R
14 23 R
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
USE R8222N WITH PILOT DUTY CONTACTS FOR 3K. CONTACTS 3K1, 3K2 MAKE WHEN ENTHALPY IS BELOW SETPOINTAND ECONOMIZER IS USED FOR FIRST STAGE OF COOLING.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
THE COMMON FOR THE W6210A,D IS DIFFERENT FROM THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS. BE SURE TO CONNECT EACH ONE TO A DIFFERENT CIRCUIT.
M11155C
T7400 THERMOSTAT
T7400/W7400 SYSTEM
P1P
T1
1
3 4
2
5
2K
S
C7400ENTHALPYSENSOR
1
1
2
3
4
6
TR TR1
SO
SR
+
+
W6210A,D
+
C
G
W1
Y1
Y2
R
W2
T6031 LOCKOUT 50 F SETPOINT
3
2
6
5
7
61K
COOL 2
4
5
T
6
7
8
8
1S
1S1
C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR
W7400 CONTROL MODULE
T7400B ONLY;T7047C1025 ORT7022A1010REMOTE SENSOR
620 OHMRESISTOR
3K RELAY
3K2
1
WALLPLATE OR Q7400 SUBBASE
HONEYWELLSERIES 62ACTUATOR
(ML6275,ML6285,M6275,M6285)
CLOSE
OPEN
OPEN
WIPER
CLOSED
500 OHM
24 VAC HOT
24 VAC COM
GND
TR
TR
RH
RC
4
3
2
1
A
COM
B
Y1
Y2
W1
W2
G
RC
RH
RC
24 VAC
T7400
ECONO.AUXRELAY
ENTHALPYSWITCH
6
5
MINIMUM POSITIONADJUSTMENT
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
15 63-2528�2
Fig. 14. W7210A,D used with T7400/W7400 System and Honeywell Series 72 Actuator.
L1 (HOT)
L2
FDR
3K1
FAN
FANDELAYRELAY
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
W
R
14 23 R
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
USE R8222N WITH PILOT DUTY CONTACTS FOR 3K. CONTACTS 3K1, 3K2 MAKE WHEN ENTHALPY IS BELOW SETPOINTAND ECONOMIZER IS USED FOR FIRST STAGE OF COOLING.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
M11156A
T7400 THERMOSTAT
T7400/W7400 SYSTEM
P1P
T1
1
3 4
2
5
2K
S
C7400ENTHALPYSENSOR
1
1
2
3
4
8
8
TR TR1
SO
SR
+
+
W7210A,D
+
C
G
W1
Y1
Y2
R
W2
T6031 LOCKOUT 50˚F SETPOINT
3
2
6
6
5
7
61K
COOL 2
4
5
T
6
7
1S
1S1
C7150B MIXEDAIR ORC7046A DISCHARGE AIR SENSOR
T7400B ONLY;T7047C1025 ORT7022A1010REMOTE SENSOR
620 OHMRESISTOR
3K RELAY
3K2
1
WALLPLATE OR Q7400 SUBBASE
HONEYWELLSERIES 72ACTUATOR
(ML7275,ML7285,ML7295A,CM7275,M7285)
24 VAC HOT
24 VAC COM
GND
TR
TR
RH
RC
4
3
2
1
A
COM
B
Y1
Y2
W1
W2
G
RC
RH
RC
24 VAC
T7400
ECONO.AUXRELAY
ENTHALPYSWITCH
6
5
W7400 CONTROL MODULE
MINIMUM POSITIONADJUSTMENT
+
–
2-10VOUT
+
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 16
Fig. 15. W7210A,D used with T775 Controller and Honeywell Series 72 Actuator.
L1 (HOT)
L2
FAN
COOL 1
HVAC EQUIPMENTTERMINAL STRIP
M15298
P1P
T1
1
3 4
2
5
2K
S
1
2
4
6
TR TR1
SO
SR
+
+
W7210A,D
+
C
G
Y1
R
C7400OUTDOORAIR ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
3
51K
COOL 2Y2
T
1S
1S1C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
W
R
T6031 AMBIENT LOCKOUT CONTROL 50 F SETPOINT
HONEYWELLSERIES 72ACTUATOR
(ML7275,ML7285,ML7295A,CM7275,M7285)
24 VAC HOT
24 VAC COM
MINIMUM POSITIONADJUSTMENT
7
NOCOM
NC
NCCOM
NO
NCCOMNO
T775 THERMOSTAT
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT EQUIPMENT TRANSFORMER IS SIZED FOR THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH, WHICH CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY IF A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR DIFFERENTIAL ENTHALPY.
T775 REQUIRES A MINIMUM OF THREE RELAY OUTPUTS: TWO FOR COOLING AND ONE FOR FAN CONTROL.A MAXIMUM OF ONE STAGE OF HEATING IS POSSIBLE WHEN THE SYSTEM IS WIRED IN THIS FASHION.
FOR THE ML7295A,C USE THE 4-20 MA MODEL ACTUATOR. THESE MODELS HAVE 500 OHM INPUT IMPEDENCE, WHICH ALLOWS THE ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
1
2
3
4
5
6
7
8
8
+
–
2-10VOUT
+
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
17 63-2528�2
Fig. 16. W7210A,D controlling parallel wired Honeywell Series 72 Direct Coupled Actuators.
L1 (HOT)
L2
FDR
FDR
FAN
HEAT 1
HEAT 2
COOL 1
COOL 2
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15299
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
1
3
6
TR TR1
SO
SR
+
+
+
–
W7210A,D
+
C
G
W1
Y1
Y2
R
W2
RC
G
X
W1
RH
Y1
Y2
W2
C7400ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
8
7
7
8
2
51K
4
5
T
6
1S
2-10VOUT
1S1
MINIMUM POSITIONADJUSTMENT
C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
24 VAC HOT
24 VAC COMRED
BLACK
WHITE
BROWN
RED
BLACK
WHITE
BROWN
ML7285
ML7285
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 18
Fig. 17. W7210A,D controlling parallel wired Honeywell Series 72 Modutrol� Motors.
L1 (HOT)
L2
FDR
FDR
FAN
HEAT 1
HEAT 2
COOL 1
COOL 2
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15300
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
1
3
6
TR TR1
SO
SR
+
+
+
–
–
W7210A,D
+
C
G
W1
Y1
Y2
R
W2
RC
G
X
W1
RH
Y1
Y2
W2
C7400ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
8
7
7
8
2
51K
4
5
T
6
1S
2-10VOUT
1S1
MINIMUM POSITIONADJUSTMENT
C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
24 VAC HOT
24 VAC COM
T1
T2
T1
T2
+
–
+
SERIES 72MODUTROLMOTOR
SERIES 72MODUTROLMOTOR
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
19 63-2528�2
Fig. 18. W7210A,D controlling parallel wired M7415 Economizer Motors.
L1 (HOT)
L2
FDR
FDR
FAN
HEAT 1
HEAT 2
COOL 1
COOL 2
HVAC EQUIPMENTTERMINAL STRIP
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED BY A 24 VAC INPUT.
RELAYS 1K AND 2K ACTUATE WHEN THE ENTHALPY SENSED BY THE C7400 IS HIGHER THAN THE ENTHALPY SETPOINT A-D.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING THERMOSTAT.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A AND A INSTEAD OF THE TIMER.M15301
T7300 OR T874THERMOSTAT
P1P
T1
1
3 4
2
5
2K
S
1
1
2
3
4
1
3
6
TR TR1
SO
SR
+
+
+
+
+
–
–
–
W7210A,D
+
C
G
W1
Y1
Y2
R
W2
RC
G
X
W1
RH
Y1
Y2
W2
C7400ENTHALPY SENSOR
UNOCCUPIED
OCCUPIED
ST6008TIMER
8
7
7
8
2
51K
4
5
T
6
1S
2-10VOUT
1S1
MINIMUM POSITIONADJUSTMENT
C7150B MIXED AIR OR C7046ADISCHARGE AIR SENSOR
620 OHMRESISTOR
24 VAC HOT
24 VAC COMTR
TR1
P1
P
TR
TR1
P1
P
Q769C
Q769C
M7415
M7415
1 2
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 20
Fig. 19. W6210, W7210 used with W7100 Controller.
GNDTR
TR
W
RBY
109
24 VAC
ECONO
CHANGEOVER
BCA
6COOL
BCA
5COOL
BCA
4COOL
BCA
3COOL
BCA
2COOL
BCA
1COOL
1
3 4
2
5
2K
W6210/W7210 ECONOMIZER
1K
1S
1S1
HONEYWELLACTUATOR
1
3
2
1
2
3
W
R
AT72A (40 VA)TRANSFORMER
L2
L1(HOT)
W7100
COOL 6
COOL 5
COOL 4
COOL 3
COOL 2
COOL 1
POWERSUPPLY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
510 OHM 1/4 WATT. 5 PERCENT RESISTOR (CONTAINED IN 4074EFV BAG ASSEMBLY) ELIMINATES ECONOMIZER DELAYS.
ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL. M20058
T6031 AMBIENT LOCKOUT CONTROL
50 F SETPOINT
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
21 63-2528�2
Fig. 20. W6210, W7210 used with W973 Logic Panel.
1
3 4
2
5
2K
W6210/W7210 LOGIC MODULE
1K1S
1S1
HONEYWELLACTUATOR
1
2
1
2
W
R
L2L1(HOT)
COOL 3
COOL 2
COOL 1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL.
M20059
2 1COOL
3 HEAT 3 COOL
2 1HEAT
MOD-HEAT
WH BH RH
MOD-COOL
RC BC WC
T T1 3 4 2 5 1 TR TR
SENSOR STAT 24 VACC +20 H N
W973B LOGIC PANEL
T6031 AMBIENT LOCKOUT CONTROL
50 F SETPOINT
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
63-2528�2 22
CHECKOUT AND TROUBLESHOOTING
CAUTIONEquipment Damage Hazard.Excessive force can damage potentiometer controls.Use a small screwdriver when adjusting enthalpy changeover and minimum damper position controls.
To check the motor, jumper T to T1 to bypass the mixed air sensor.
Use Table 4 and Fig. 21 for checkout.
Fig. 21. Meter location for checkout and troubleshooting.
1
+
+
B
A D
CTR TR1
S
5
2
4
T1
P1
3
T
P
MINIMUMPOSITION
OPEN
FREECOOLING
ENTHALPYCHANGEOVERSETPOINT
LED LIGHTS WHEN OUTDOOR AIRIS SUITABLE FOR FREE COOLING
M11163A
S
+1
1
2
2
620 OHMJUMPER
DCMILLIAMMETER
INSERT DC MILLIAMMETER BETWEEN SO AND S FORCHECKOUT AND TROUBLESHOOTING.
JUMPER USED FOR SINGLE ENTHALPY CONTROL.
C7400
W6210
O
SR
W6210A,D AND W7210A,D SOLID STATE ECONOMIZER LOGIC MODULE
23 63-2528�2
Table 4. W6210A,D and W7210A,D Economizer Connected to Honeywell Actuator.
Checkout Procedure Proper Response
1. a. Disconnect power at TR and TR1. �
b. Disconnect P to P1 jumper.
c. Jumper TR to 1.
d. Jumper T1 to T.
e. If connected, remove C7400 Enthalpy Sensor from terminals SO and +. Ensure factory-installed 620 ohm resistor is connected to terminals SR and +.
� LED is off.
f. Apply power (24 Vac) to terminals TR and TR1. � Motor is in closed position.
2. Disconnect factory-installed 620 ohm resistor from terminals SR and +.
� LED turns on (A models only; for D models, go to step 3).� Motor drives toward open.
3. Simulate high and low enthalpy (single enthalpy sensor):
a. Reconnect factory-installed 620 ohm resistor across terminals SR and +.Connect 1.2K ohm 4074EJM Checkout Resistor across terminals SO and +.
�
b. Turn enthalpy setpoint potentiometer to A. � LED turns on, indicating low enthalpy.� Motor drives toward open.
c. Turn enthalpy setpoint potentiometer to D. � LED turns off, indicating high enthalpy.� Motor drives toward closed.
d. Disconnect the 1.2K ohm checkout resistor. �
4. a. To verify sensor operation, reconnect the + lead of the outdoor enthalpy sensor to the + terminal of the W6210/W7210 Economizer.
�
b. Connect a dc milliammeter between terminals SO of the W6210/W7210 and terminal S of the enthalpy sensor. (Connect the positive meter lead to terminal S of the enthalpy sensor.)
� Milliammeter indicates between 3 and 25 mA when the sensor is operating properly.
� If the milliammeter indicates zero, the sensor may be wired backward.
c. When using differential enthalpy, check the return air enthalpy sensor by connecting a dc milliammeter between terminal SR of the W6210/W7210 and terminal S or the return air enthalpy sensor. (Connect the positive meter lead to terminal S of the return air enthalpy sensor.)
� Milliammeter indicates between 3 and 25 mA when the sensor is operating properly.
� If the milliammeter indicates zero, the sensor may be wired backward.
63-2528�2 B.B. Rev. 9-01 www.honeywell.com/building/componentsPrinted in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Home and Building Control Home and Building Control Honeywell International Honeywell Europe S.A.Honeywell Latin AmericanHoneywell Honeywell Limited-Honeywell Limitée Home and Building Control 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate ParkwayGolden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200