  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    1/23

    Generator set technical manual 1

    VPOWER Engineering (Shen Zhen) Ltd.

    VPOWER GENERATOR SET

    Operation / Service /Maintenance Manual

    2014 Edition

    VPOWER GENERATION

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    2/23

    1

    Table of Contents

    Content

    Chapter 1 Weekly maintenance and safety regulation..... 2

    1 . Weekly maintenance work system. 2

    2 . Weekly maintenance work. 2

    3 . The normal working condition of the engine. 4

    4 . The generator test running. 4

    5 . Safety precautions and notices... 5

    6 . Wrong activation. . 6

    7 . Battery... 6

    Chapter 2 Commonly operation.. ... 8

    1 . Common Operation.. 8

    2 . The generator control panel . 9

    3 . control panel introduction..... 9

    4 . The Generator Controller DSE8610 Introduction. 10

    5 . The generator start and stop...... 17

    Chapter 3 Daily maintenance..... 18

    Chapter 4 Maintenance plan... 19

    Chapter 5 Troubleshooting.. ... 20

    Chapter 6 Connection documents of after-service. 22

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    3/23

    2

    Chapter 1 Weekly Maintenance And Safety regulation

    1 . Weekly maintenance work system:The following weekly maintenance work system is applicable for the running status of

    generator in common condition, but if the engine works in bad condition( such as

    dust flying upward, poor-ventilated environment), the maintenance period should

    been shortened.

    If around the engine engine, the generator should not been started.

    2 . Weekly Maintain work

    Preventative maintenance begines with day-to-day awareness of the condition of the

    engine and its systems.Before starting the engine,check the oil and coolant

    levels.Look for: Leaks

    Loose or damaged parts

    Worn or damaged belts

    Any change in engine appearance

    COOLING SYSTEM

    -- The coolant level must be checked daily and more often.

    -- The water level should be 2 below affusion mouth.

    -- If exchange the cooling water, inspect the proportion of antifreeze supplied.-- Inspect all the cooling piping and collet whether water leakage (like abrasion)

    -- If use heat-scattering water tank, make sure no substance block the heat-scattering

    sheet.

    -- If use the heat-exchanging device, make sure all vavles are in right position.

    Fill the cooling system with coolant to the bottom of the fill neck in the radiator

    fill or expansion tank.

    CAUTION:

    -- Any time a significant amount of coolant is added, the Diesel coolant Additive

    concentration must be checked. If the concentration is low, engine damage will

    result.

    NOTE:

    -- Some radiators have two fill necks, both of which must be filled when the cooling

    system is drained.

    Lubrication System

    -- Inspect the oil level of the lubricating oil to make sure it is within regulated scale

    standard.

    -- Inspect the oil quality of the lubricating oil to make sure whether water or fuel

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    4/23

    3

    mixing into.

    -- Inspect the lubricating system to make sure whether leakage exist.

    Fuel Oil System

    -- Inspect whether the valve of the fuel pipe is open.

    -- Inspect whether the fuel pipe leaks.

    -- Inspect the oil level of the fuel box to make sure that fuel should been supplied

    before it is exhausted.

    -- The vehicle must be level when checking the oil level to make sure the

    measurement is correct.

    CAUTION:

    Never oprate the engine with the oil level below the low mark or above the high

    mark.Wait at least 5 minutes after shutting off the engine to check the oil. Thisallows time for the oil to drain to the oil pan.

    -- Check the valve of the fuel oil pipeline to have to leak.

    Air cleaner System

    -- Inspect whether the air-cleaner device is clean and observe the indicator (if

    with)when generator running.

    -- Inspect the oil level of the oil tray of the wet air-cleaning device(if used).

    -- Under extremely dirty conditions an air pre-cleaner can be used. Clean the

    pre-cleaner jar and dry-type air cleaner dust pans daily or more often, as necessary,

    depending on operating conditions.

    The switch function of circuit.

    -- Inspect whether all the terminal indicator lights of the switch system of

    internal-combustion engine are ok.

    -- Check the engine monitor system daily (push button to test) per the manufacturers

    recommentation to verify proper operation.

    Battery

    -- Inspect whether the electricity bottle liquid is enough, and its proportion should be

    higher than 1.265. CAUTION:

    When using jumper cables to start the engine, make sure to connect the cables in

    parallel:positive(+) to positive(+) and negative (-) to negative(-). When using an

    external electrical source to start the engine, turn the disconnect switch to the OFF

    position. Remove the key before attaching the jumper cables.

    Belt

    -- Inspect the intensity of the strap of cooling fan and the charger(if one strap is

    found wore, the whole group should been changed)

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    5/23

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    6/23

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    7/23

    6

    DANGER

    The danger emblem indicates that if no close attention is paied to, it will cause

    people injury and death, generation damage.

    WANRNING

    The warning emblem indicates that if no close attention is paied to, it will cause

    serious people injury and death, generation damage.

    CAUTION

    The caution emblem indicates that if no close attention is paied to,it may cause

    people injury or generation damage.

    Remark :These emblems should been paied attention to during install,operation or

    maintenance,but it does not mean danger.

    These safety emblems should been pasted on the relative obvious position of the

    generator group to remind the operators or maintenance technician of paying

    attention to these potential danger. As to the explanation of these emblems,you can

    refer to all the safety precautions in this manual to make sure whether you have

    understood the meaning of these emblems like emblems loss or damage which

    should been exchanged quickly.

    6 . Wrong activation Warning

    Wrong activation may cause injury or death.

    When working around the generator, firstly should break the battery away from

    cable( remove cathode then connect)

    Make the generator switch at the position of OFF.when working around the

    facilityjoined with fuel generation, should remove activation electricity bottle and

    cable(remove before connecting) to make generator group impossible to work.

    If the above measurement is not taken, the generator group may been automatically

    switched or remote switch control activation.

    7 . Battery

    Warning

    The electrolyte can cause serious injury or death.

    -- It is necessary to wear protective glove and clothes because the electrolyte can

    cause permanent hurt to eyes,can burn skin and ablate clothes.

    Warning

    -- Exploding can cause serious injury or death,the relay of the battery charger can

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    8/23

    7

    cause sparking.

    -- The battery should been installed at well-ventilated place, and far away from

    flammable gas.The electrolyte of the battery can cause serious injury or death. the electrolyte can

    cause permanent hurt to eyes,can burn skin and ablate clothes. So when working

    around battery, should wear safety antiseptic glove. If electrolyte spatters to skin,

    should rinse for 15 minutes with sufficient clean water. If electrolyte spatters to

    eye, you should seek the first-aid kit for medicining. The battery cant be appened

    vitriol or it may cause the electrolyte metamorphosing.

    Exploding will cause serious hurt or death, the gas liberated by the battery may

    cause exploding, so around the battery smoking is prohibited and blaze or sparkle

    generation is prohibited. Especially when the battery is charging, you should avoid

    touching the terminal with tools, avoil exploding caused by sparkle. Before you

    move the battery, you should turn off the watch, finger ring and other bullion

    ornements. Do not connecte the anode and the cathode of the activation generation

    shortly. Do not tset the capacity of the electric-bottle in the way of short, the

    sparkle may emblaze the gas liberated by the battery or steam of fuel oil. The case

    contained battery should be put in the breezy place to avoid explosive

    gathering. Do not pull out the electric tie-in when charging to avoid sparkle

    generation.Before pulling out the electric tie-in, you should turn off the power of

    the charger first.The cathode of the power should be dismantled first and

    connected last.

    -- Removal: Disconnect the (-) negative battery cable first, then disconnect the (+)

    positive cable.

    -- Connect: Connect the (+) positive battery cable first, then connect the (-) negative

    cable.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    9/23

    8

    Chapter 2 Common Operation1. Common Operation

    Before starting the generator set, check for the following procedures. (Specialmaintenance procedures refer to CUMMINS Operation and maintenance

    Manual)

    Fuel oil system

    -- Check the oil level,The vehicle must be level when checking the oil level to make

    sure the measurement is correct.

    -- Operate the engine with the oil level between the low mark and the high mark.

    Cooling sytem

    -- The coolant level must be correct.

    --Fill the cooling system with coolant to the bottom of the fill neck in the raiator fill

    or expansion tank.

    --Some radiators have two fill necks, both of which must be filled when the cooling

    system is drained.

    --

    Any time a significant amount of coolant is added, the diesel coolant additive

    concentration must be checked. If the concentration is low, engine damage will

    result.

    --Do not add cold coolant to a hot engine. Engine castings can be damaged. Allow

    the engine to cool to below 50 before adding coolant.

    Air cleaner:

    --Clean the air cleaner jar and pans daily or more often, as necessary, depending on

    operating conditions.

    Other

    --Check the oil pressure indicators, temperature indicators, warning lights and other

    gauges to make sure they are operational.

    --Check the engine monitor system (push button to test) per the manufacturers

    recommendation to verify proper.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    10/23

    -- VPOWER-- Operation Manual --

    9

    2 . The generator control panelNote: panel electric elements arrangement may not agree with actual, please use the actualarrangement shall prevail.

    3. V500G CONTROL PANEL INTRODUCTION

    ymbol term Function and Operation

    W1 Genset ControllerDSE 8610

    The DSE8610 is an Automatic Engine ControlModule,designed to provide advanced load share functionality fordiesel and gas generating sets that include nonelectronicand electronic engines. The module also providesexcellent engine monitoring and protection features.

    The modules load share functions include, automaticsynchronizing with built in synchroscope and closingonto dead bus. Direct and flexible outputs from the

    module are provided to allow connection to the mostcommonly used speed governors and automatic voltageregulators (AVRs).

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    11/23

    -- VPOWER-- Operation Manual --

    10

    The module has been designed to combine a maximumof 16 generators and 16mains (utility) supplies up to amaximum of 20 in one system, e.g. 16 generators and4mains (utility) supplies (DSE8610 required tosynchronise with the mains).

    The module has the ability to monitor under/over

    generator volts, over current, under/over generatorfrequency, under speed, over speed, charge fail,emergencystop, low oil pressure, high engine temperature, fail tostart, low/highDC battery volts, fail to stop, generatorshort circuit protection, reverse power, generator phaserotation error, earth fault protection, loss of speed signal,fail to open, fail to close, out of sync,MPU open circuitfailure, negative phasesequence and loss of excitation.

    W2 EM133 The EM133 is a smart DIN Rail Tou Energy Meter. TheEM133 can serve any application from residential energymetering,through industrial emergy and harmonicanalysis through utility comprehensive substationautomation.

    PB1 Emergency StopButton

    When the Generator is abnormal, press the Emergencystop button would stop the Generator immediately.

    L Fault Light When the generator set occurred the fault, Light is on.

    B1 Buzzer When the generator set occurred the fault, Buzzer is on,Warning the worker to check the Generator, and removethe fault.

    A Charging Meter For battery charging meterSW1 Power Select

    Switch(OFF/ON)Turn to ON position, Open the Controller of DSE8610,Turn to OFF position, Close the Controller ofDSE8610

    SW2 Charging Switch Charging selector switch For battery charging (off / on)

    SW3 Freq. Select Switch This selection switch can change the Generator offrequency&voltage(50Hz-400V/60Hz-380V/60Hz-480V)

    SW4 Volt Trimmer(50Hz/400V)

    This knob can change the magnitude ofvoltage(50Hz/400V)

    SW5 Volt Trimmer(60Hz/380V)

    This knob can change the magnitude ofvoltage(60Hz/380V)

    SW6 Volt Trimmer(60Hz/480V)

    This knob can change the magnitude ofvoltage(60Hz/480V)

    4 . The Generator Controller DSE Model 8610 Introduction

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    12/23

    -- VPOWER-- Operation Manual --

    11

    4.1 ICON DESCRIPTIONS

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    13/23

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    14/23

    -- VPOWER-- Operation Manual --

    13

    4.2.2 AUTOMATIC MODE OF OPERATION

    Automatic mode is used to start the set in response to an external start requirement from another

    device. A number of options exist for the remote start input (selectable using 5xxx configuration

    software).

    Remote Start on Load input indicates to the controller that it should start the set, and run off load.

    Remote Start on Load input indicates to the controller that it should start the set, synchronise (if

    required) and share load with any other sets in the system.

    Remote Start on Load Demand input indicates to the controller that it should start the sets,

    synchronise (if required) and share load with any other sets in the system, automatically starting and

    stopping sets on changing load demand.

    This mode is activated by pressing the pushbutton. An LED indicator beside the button will

    illuminate to confirm this operation.

    Should the remote start input (if configured) become active then the following sequence is observed.

    To allow for short term or false remote start signals, the Start Delay timer is initiated. After this delay,

    if the pre-heat output option is selected then the pre-heat timer is initiated and the corresponding

    auxiliary output (if configured) will energise.

    After the above delays the Fuel Solenoid (or enable ECU output if configured) is energised, then

    one second later, the Starter Motor is engaged.

    NOTE:- If the unit has been configured for CAN Bus, compatible ECUs willreceive the start command via CAN Bus. Refer to the Manual CAN and DSE Wiring. PartNo. 057- 004 for more information on utilis ing DSE modules with electronicallycontrolled engines.

    The engine is cranked for a pre-set time. If the engine fails to fire during this cranking attempt then

    the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the

    NOTE: - If a digital input configured to panel lock is active, changing module modes will

    not be possible. Viewing the instruments and i is NOT affected by panel lock. If

    panel lock is active the Panel lock indicator (if conf igured) illuminates.

    NOTE:- If the Remote Start signal is removed during the Start Delay timer, the uni t wil l

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    15/23

    -- VPOWER-- Operation Manual --

    14

    set number of attempts, the start sequence will be terminated and Fail to Start fault will be displayed.

    When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency

    measured from the alternator output. Alternatively, a Magnetic Pickup mounted on the flywheel housing

    can be used for speed detection (This is selected by PC using the 5xxx series configuration software).

    Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for

    underspeed or overspeed detection.

    NOTE:-A load transfer wil l not be initiated until the Oil Pressure has risen. Thisprevents excessive wear on the engine.

    After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure, High

    Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise

    without triggering the fault.

    If the system has been started by a remote start off load input, the set will run off load.

    Otherwise, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise. After the

    Warm-up timer has expired then the module will close the load switching device.

    In the case of a single generator system, the Generator Contactor/Breaker will be instructed to

    close. The generator will then supply the requirements of the load.

    On a multi-set system, if the common generator bus is live, the 8610 module will first synchronise

    the generator to the bus before closing the Generator Contactor/Breaker.

    A token is held by the module that first closed onto the dead bus and as only one token exists for

    each multi-set system, this prevents other sets in the system from attempting to close their own

    breakers.

    For added security, the modules also monitor the bus. If this is found to be live, then the

    synchronisation process begins.

    Once the load switching device is closed, the 8610 will then ramp to share the load with the other

    generators in the system.

    NOTE:-A load transfer wil l not be initiated until the Oil Pressure has risen. Thisprevents excessive wear on the engine.

    When the Remote start signal is removed, the Stop delay timer is initiated. Once this has expired,

    the module will ramp the load from the generator to remaining set (Multi-set systems only). The

    Generator Contact/Breaker will open and the Cooling timer is then initiated, allowing the engine a

    cooling down period off load before shutting down. Once the Cooling timer expires, the FuelSolenoid

    is de-energised, bringing the generator to a stop.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    16/23

    -- VPOWER-- Operation Manual --

    15

    For full details of multi-set operation please refer to the manual The Guide to sync and load share

    Pt1

    Should the Remote Start signal be re-activated during the cooling down period, the set will return on

    load.

    NOTE:- When synchronising is enabled, the bus is checked before closing anyload switch ing device. If the bus is live, synchronis ing wi ll take place before any closuretakes place.

    - Synchronis ing can be disabled if the application does not require this funct ion.Contact your genset supplier in the first instance for further details.- The internal Scheduler can be configured to operate the system in the same manneras described for the Remote start input. Please refer to the 5xxx Configuration Softwaremanuals for full details on the feature.

    4.2.3 MANUAL C MODE OF OPERATION

    Manual mode is used to allow the operator to control the operation of the generator, and to

    provide fault finding and diagnostic testing of the various operations normally performed during

    Automatic mode operation.

    MANUAL, mode is selected by pressing the pushbutton. An LED besides the button will illuminate to

    confirm this operation. When the START ( I) button is operated, the module will initiate the start

    sequence.

    NOTE: - There is no Start Delay in this mode of operation.

    If the pre-heat output option has been selected, this timer will be initiated and the auxiliary output

    selected energised.

    After the above delay, the Fuel Solenoid (or ECU output if configured) is energised, and then one

    second later, the Starter Motor is engaged.

    The engine is cranked for a pre-set time. If the engine fails to fire during this cranking attempt then

    the starter motor is disengaged for the pre-set rest period. Should this sequence continue beyond the

    set number of attempts, the start sequence will be terminated and Fail to Start will be displayed.

    When the engine fires, the starter motor is disengaged and locked out at a pre-set frequency

    measured from the Alternator output. Alternatively, a Magnetic Pickup mounted on the flywheel housing

    can be used for speed detection (This is selected by PC using the 5xxx series configuration software).

    Rising oil pressure can also be used to disconnect the starter motor; however, it cannot be used forunderspeed or overspeed detection.

    After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure,

    NOTE:- If the unit has been configured for CAN Bus, compatible ECUs will receive

    the start command via CAN Bus. Refer to the Manual CAN and DSE Wiring. Part No. 057-004 for more information on uti lising DSE modules with electronically contro lledengines.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    17/23

    -- VPOWER-- Operation Manual --

    16

    High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to

    stabilise without triggering the fault.

    Once the engine is running, the Warm Up timer (if selected) is initiated, allowing the engine to

    stabilise before it can be loaded. Once the warm up timer has expired the generator is then

    available to go on load and the Generator Available LED will illuminate on the front panel.

    The generator will run off load unless:

    1. A Remote Start on load signal is applied

    2. An on-load run is configured in the scheduler.

    3. The Close Generator button is pressed.

    On a multi-set system, if the common generator bus is live, the 8610 module will first synchronise

    the generator to the bus before closing the Generator Contactor/Breaker to close.

    A token is held by the module that first closed onto the dead bus and as only one token exists,

    this prevents other sets in the system from attempting to close their own breakers.

    For added security, the modules also monitor the bus. If this is found to be live, then the

    synchronisation process begins.

    During the parallel run the module can be configured to either run at a fixed level output, such as

    when used in parallel with an infinite bus. Alternatively, it can be configured to load share with

    other generators on the bus. For full details of these mode please refer to the manual The Guide

    to sync and load share Pt1

    If the Open Generator button is pressed while in parallel, the module will ramp the load on the

    remaining generators and then open the generator contactor/breaker.

    If the Open Generator button is pressed and the generator is connected to the common generator

    bus then the load is ramped off the generator and the contactor/breaker is opened.

    IfAuto mode is selected and the remote start on load signal not active, and the scheduler is not

    calling for a run, then the Return Delay Timer will start.

    Once this has expired then the module will exit parallel operation and will ramp the load back to the

    remaining generators. It will then open the Generator Contactor /Breaker. The generator will then run

    off load allowing the engine a cooling period.

    Selecting STOP (O) de-energises the FUEL SOLENOID, bringing the generator to a stop.

    Detail data pls refer to DSE8610AUTOSTART CONTROL MODULEOPERATING MANUAL

    5 . The generator start/stop

    WARNING: - Operation of the STOP button in any mode will stop the generator operationand return the load switching sys tem to a safe state. This operation may lead to loss ofsupply to the load. It i s recommended that the STOP button is only operated once thegenerator is OFF LOAD and the mains supply provides power to the load.

    - Synchronis ing can be disabled if the application does not require this funct ion.Contact your genset supplier in the first instance for further details.

    - When synchronis ing is enabled, the bus is checked before closing any load witchingdevice. If the bus is li ve, synchronising will take place before any closure takes place.:- Upon closing the load switch ing device, the module checks that the bus becomes live.If it does not, an alarm is generated to indicate the problem.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    18/23

    -- VPOWER-- Operation Manual --

    17

    5.1 Manual Start

    Turn the select switch SW1 on the ON position and set the controller to MANUAL

    mode( ). Then press the Start button( ),The generator will running,observed the

    volt and RPM, They are normal , then press the load switch( ), The generator will

    with load output.

    5.2 Auto Start

    Turn the select switch on the ON position anf the set the controller to AUTO

    mode, Genset will start automatically when there is a main failure.

    5.3 The generator stop

    5.3.1 Manual stop

    Press down the controller stop button. The generator will stop.

    5.3.2 Auto stop

    While the controller is in AUTO mode. Genset will main comes back to normal.

    5.4. . The generator paralleling

    5.4.1 Manual paralleling:

    Turn the select switch SW1 on the ON position and set the controller to MANUAL

    mode( ). Then press the Start button( ),The generator will running,observed

    the volt and RPM, They are normal , then press the button ( ), The controller of the

    generator will automatically monitor the volt, RPM, phase angle on the MAINS, and

    auto close the Gen ACB.

    5.4.2 Auto paralleling:

    Turn the select switch SW1 on the ON position and set the controller to Auto

    mode( ).The genset will running when it received the remote starting signal.

    The controller of the generator will automatically monitor the volt, RPM, phase angle

    on the MAINS, and auto close the Gen ACB.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    19/23

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    20/23

    -- VPOWER-- Operation Manual --

    19

    Chapter 4 Maintenance plan

    1FUEL FILTER PRIME GENSET: Every 250~1000 hours replaced the fuel filter

    STAND BY GENSET: Half a year replaced the fuel filter

    ---TYPE: FS1006

    QUANTITY`: 2entries

    2OIL FILTER PRIME GENSET: Every 250~1000 hours replaced the oil filter

    STAND BY GENSET: Half a year replaced the oil filter---TYPE : LF3325QUQNTITY :

    5entries

    3WATER FILTER PRIME GENSET: Every 250 hours replaced the water filterSTAND

    BY GENSET: Half a year replaced the oil filter---TYPE : WF2076QUANTITY :

    2entries

    4BY PASS OIL FILTER PRIME GENSET: Every 250 hours replaced the by pass oil

    filterSTAND BY GENSET: Half a year replaced the by pass oil filter---TYPE : LF777

    QUANTITY : 2entries

    5AIR FILTER PRIME GENSET: Every 400 hours replaced the air filterSTAND BY

    GENSET: one year replaced the air filter, Also according to the filter indicator to replaced.

    ---TYPE : AH1135QUANTITY : 2entries

    6MIXING TANK WATER Check water level day to dayHalf a year replaced thecoolant water

    7REMOTE TANK WATER Check water level day to dayHalf a year replaced the

    coolant water

    8DAILY OIL TANK Check the oil level daily, added fuel oil in time.

    9LUBRICATION OIL Replacement of half a year.

    10

    THE GENERATOR SET IN A SMALL MAINTENANCE

    Please refer to EngineOpration and Maintenance Manual.

    11THE GENERATOR SET IN A HEAVY MAINTENANCEPlease refer to Engine

    Opration and Maintenance Manual.

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    21/23

    -- VPOWER-- Operation Manual --

    20

    Chapter 5 Troubleshooting

    Fllow the suggestions below for troubleshooting:

    Study the problem thoroughly.

    Refer to the engine system diagrams.

    Do the easiest and most logical things first.

    Find and correct the cause of the problem.

    Troubleshooting table

    FAILURE CAUSE CORRECTIONS

    Battery voltage too low or bad; Charge or replace;

    Battery connection broken, loose or corroded Check battery connections;

    Controler fuse bad; Replace the fuse;

    Emergency button have no reset Check and reset;

    Failure to shut off; Check,removed the failure and reset;

    Engine cant

    start

    Engine switch in OFF position Select switch to START position.

    Fuel pump manual override open; Check to make sure manual override

    screw is out to maximum travel;

    Fuel pump shut-off valve disc stuck; Check opening and closing of

    electrics;

    Fuel tankvents plugged; Remove,clean,or replace vents;

    Fuel drain lin restricted; Check fuel drain line for loops,

    crimps, or clamped points;

    Engine will not

    shut off

    Engine running on fumes drawn into air

    intake.

    Locate and isolate the source of

    fumes.

    Over current switch placed in OFF

    position;

    Select to ON position;No AC export

    Engine failure Contact the service.

    Oil pressure too low to shut down; Check the lubrication level;

    Engine temp too high to shut down; Check the air cleaner and fan belts

    Engine will

    shut down

    Coolant level too low to shut down; Check the coolant level.

    Engine cranking speed low; Check engine cranking RPM;

    Engine driven units engaged; Disengage engine driven units;

    Cold start aid needed or not working

    correctly;

    Install cold start aid. Check, repair, or

    replace if necessary.

    Fuel filter plugged; Replace fuel filter;

    Air in the fuel system Check for air in fuel, tighten fuel

    connections and and filter, check fuel

    tank stand pipe;

    Engine hard to

    start or will not

    start

    Fuel suction line restricted; Check fuel line for restrictions;

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    22/23

  • 8/10/2019 VPOWER Genset Operations, Service and Maintenance Manual

    23/23

    -- VPOWER-- Operation Manual --

    Chapter 6 Connection Documents of after-service

    VPOWER Engineering (Guang Zhou) Ltd.

    Room 2107, 21/F, Newpoly Tower, No.2 ZhongShan 6 road,Yuexiu District, GuangZhou,China.

    Post510180

    Tel208326 6748

    Fax208326 6948

    VPOWER Engineering (ShenZhen) Ltd.

    Building B7,North Yan Chuan Industrial Park,Songgang Town,Bao

    An,Shenzhen,Guangdong Province,PR China.

    Post518105

    Tel7552706 4703-4

    Fax7552706 5135

    VPOWER Holdings Ltd.

    Unit 3801B, Level 38, Tower 2, Metroplaza, No. 223 Hing Fong Road, Kwai Chung,Hong Kong.

    Tel08522687 6517

    Fax08522687 6854

    E-mail : [email protected]

    Design

    Manufacture

    Service

    Generator Set ManufacturerParallel Panel Manufacturer

    Power Quality & Saving System

    Power Monitoring System

    Environmental Management

    Filtering Equipment & System

    Genuine Engine Parts

    Engine Overhaul Services