Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial December 18, 2012 Randy Wachal Manitoba HVDC Research Centre [email protected]

Upload: duongliem

Post on 06-Mar-2018

229 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial December 18, 2012

Randy Wachal Manitoba HVDC Research [email protected]

Page 2: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Acknowledgements:NSERC Power System Simulation Chair program at

University of Manitoba ..

MHRC Staff Dr. Farid Mosallat and Juan Carlos Garcia

Cigre DC Grid Working Groups B4-55, 56 57 58 59 and 60 ..

ABB Siemens and Alstom Grid

Page 3: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC Tutorial

VSC Converter Theory Basics VSC Control and Modelling VSC system simulations Start –up; DC Fault DC Grid Test Case Cigre B4-57/58

Page 4: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Introductory Basics: LCC Single line

Page 5: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC: Single Line Diagram Format

Page 6: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Symmetrical HVDC Monopole

Page 7: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC: Unsymmetrical Monopole

Page 8: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC: Bipole Configuration

Page 9: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

LCC - VSC ComparisonLCC HVDC

Mature Technology “Requires” strong ac system Lower losses 0.8% per converter

Requires 60% reactive powerAC-DC system interactions Harmonics Commutations failureSpecial Transformers Multi terminal operation possible but hardControlled DC Current to zero (Idref=0) Dc voltage + to - as alpha changes

rectifier to inverter

VSC HVDCRapid growth Helps ac system

Control real and reactive power independently

Losses reducing 1.1- 1.2% per converter

No Commutation failureLess Special TransformersFlexible Dispatch Harmonics with MMC no issueDC Grid (multi-terminal) possible DC voltage is a constant polarityDC Line faults are problematic

Page 10: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Multi Terminal For LCC: Rect α < 90 Vdc +ve INV α > 90 Vdc -ve To change Conv 2 from

Rect to Inv you must flip the thyristor

For VSC: Power Flow is controlled

by control signals only

f f

f

S1

S4S3

S2

Page 11: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC Technology is very flexible

VSC technology can control two variables togetherreal power and reactive power

VSC can generate an AC Waveform…. Black start or island mode possible

Many dispatch options available • Real Power set point in or out + or -• Use power to control DC voltage Vdc• In island mode : use power to control frequency

• Reactive Power Q set point in or out + or –

• Use Q to control Vac magnitude Grid or islanded Mode…

• Other control targets are possible..

Page 12: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

We tend to think of LCC from AC side to rectifier and generate Dc voltage

For VSC ; think from the DC side.. Assume DC Capacitors are charged The capacitor voltages are used to piecewise build ac voltageWe the ac voltage waveform and the ac system voltage now we can transfer energy to charge Dc capacitor(s)

VSC Operation

Page 13: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Use DC capacitor voltage (Ud) to build an ac Voltage waveform Uc

Exchange P based on δ•↑ δ P into Converter Ud ↑•↓ δ P from Converter Ud ↓

Exchange Q based on |Uc| •↑ |Uc| Q flows into system •↓ |Uc| Q flows from system

Transfer P & Q across Reactor

Page 14: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

History of VSC Development: ABB, Siemens and Alstom Grid

• VSC Rapid Growth and continue to change • Many projects but few projects have the same

design• An MMC type configuration appears to be the

“winner” but many marketplace has variations • Not unlike LCC technology 25 years ago

• The Final VSC configuration is not decided • and may never occur.

Page 15: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial
Page 16: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial
Page 17: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

PWM Based VSC

ABB slide

Page 18: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

½ Bridge Multi Module Converter MMC

Siemens Slide

Page 19: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

½ Bridge MMC with PWM CTLC

Page 20: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Full Bridge MMC

IET ACDC 2012 Tutorial Gole - Wachal

Page 21: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

One possible Hybrid Configuration

IET ACDC 2012 Tutorial Gole - Wachal

Page 22: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC Control and Modelling

• Control system organization • Look at impact of diode in configuration • High Level Control

D Q controller development Development of Voltage reference signals based on dispatched orders

Lower level control Valve fire pulses (IGBT firing pulses) Capacitor energy balancing

Page 23: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Models For VSC MMC system

EMT and RMS transient (Dynamic and loadflow) type models are required

Lots of VSC configurations to consider • PWM based (all series devices in Valve switch together)

• ½ bridge MMC• ½ bridge MMC with PWM (cascaded two level converter CTLC)

• Full bridge MMC• Hybrid mixtures of series valves, ½ and full bridges

Page 24: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Traditional ‘emt’ solution methods not effective Emt simulation speed is dependent on number of electrical

nodes (size of simulation matrix)

MMC configurations increase electrical nodes exponentially • LCC and PWM VSC

• 6 nodes per 3 phase valve • entire valve arm (xx series devices) switch together

• MMC • Valve may have 400 levels (each switching independent)• 400*6 = 2400 nodes for 1 converter

Compare 6 to 2400 …… simulation issue is evident …

Page 25: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC System Control Model & Levels • Dispatch What is the target of Converter ?

• Power Set or Dc voltage (grid mode) • Ac voltage reference or MVar set (grid mode) • Frequency reference (P) and Ac Voltage (Q) (island

mode) • Other P& Q strategy

• High Level Controls • Based on dispatch set points (Inputs) • Droop setting to allow autonomous control • d-q control will generate Vref a, b and c (outputs)• Voltage and current limits applied

• Lower Level Controls • Inputs Vref signals • Valve specific configurations

(½ bridge MMC, ½ bridge MMC with PWM, full bridge, etc.) • Capacitor balancing algorithm(s) • Circulating current suppression algorithm(s) • Generates gate pulses and the ac waveforms

Page 26: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Control Hierarchy

Natural separation occurs Higher Lower level Controls

Regardless of Dispatch Orders Higher Level controls develop

Vref A Vref B and Vref C outputs

Regardless of converter valve implementation Lower Level controls use the VREF inputs to generate the gate pulses to produce

Va Vb and Vc

Lower level controls are unique for valve topology and will have ancillary control - Capacitor balance - Circulating current suppression

Vabc Ref

Page 27: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Impact for VSC System Models• Dispatch and Higher Levels Controls remain same regardless of

Converter implementation • Generic or public domain models • Vendor specific (IP) models

• Lower Level Controls unique for different types of converter • Different Power electronics and control algorithm • Different Capacitor balance algorithm • Different Circulation Current suppression algorithm • Generic or public domain models • Vendor specific (IP) models • Different level of details for each lower level models

• Full emt , detailed equivalent, firing pulse RMS

From a Simulation Study Point View Choose the appropriate Lower Level Model for your study … How ???

Page 28: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

New Model Techniques required Computationally efficient model developed by Simulation Chair University of Manitoba

Ic24

Ic23

Ic22

Ic21

Ic20

Ic19

Ic18

Ic17

Ic16

Ic15

Ic14

Ic13

Ic12

Ic11

Ic10

Ic9

Ic8

Ic7

Ic6

Ic5

Ic4

Ic3

Ic2

Ic1

FP15

FP16

FP14

FP13

FP17

FP18

FP20

FP19

FP23

FP24

FP22

FP21

Vc24

Vc23

Vc22

Vc21

Vc19

Vc20

Vc18

Vc17

Vc16

Vc15

Vc14

Vc13

Vc12

Vc11

Vc10

Vc9

Vc8

Vc7

Vc6

Vc5

Vc4

Vc3

Vc2

Vc1

FP3

FP4

FP2

FP1

FP5

FP6

FP8

FP7

FP11

FP12

FP10

FP9

N1

N1

n2l

i1l

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

Thevenin equivalent

U. N. Gnanarathna, A. M. Gole, and R. P.Jayasinghe, "Efficient Modeling of Modular Multilevel HVDC Converters (MMC) on Electromagnetic Transient Simulation Programs," IEEE Transactions on Power Delivery, vol.26, no.1, pp.316-324, Jan. 2011

100’s of nodes into 2 nodes

It makes possible the simulation of Multilevel converters with only a PC-

+

Ic(38)Vc(38)

TU(38)TL(38)

Veq

Req

-

+

Ic(38)Vc(38)

TU(38)TL(38)

Veq

Req

Page 29: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Start up Concerns

Initial Energization • Transformer• MMC Capacitors (Precharge capacitors to 1.41*ELL via diodes)

• DC Line or DC Cable

Use start-up resistor to limit current. Short resistor with by pass switch Deblock pulses Conv 1 and then Conv 2 Ramp power to desired setpoints

Page 30: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Session 3: VSC system start up

1000 kmZ Z

SCR: 2.5SCR: 2.5

P=900 MW

P control@ 900 MW

Vdc control@ 640 kV

P=966 MW

T1 T2

Page 31: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Session 3: VSC system start up

Start up sequence

[s] 0.00 0.50 1.00 1.50 2.00 2.50

-10.0

10.0

(kA)

Iac T2 (Sending end)

-100

700

(kV)

Edc2 (+) (Vdc control end)

-1.0

7.0

(kA)

Idc 2 -> 1

-0.10k

1.00k

(MW

)

(-) P1 P2

Close AC brk

Bypass Pre R

De-blockTerminal 1

De-blockTerminal 2 Ramp up

Page 32: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Summary Issues VSC Start-up

During start-up energization of both transformers and all capacitors therefore Larger Inrush

Inrush resistor commonly added with bypass switchDiodes: with no firing pulse and diodes will conduct

resulting in a Dc voltageVDC=1.41 peak of Vac L-L

(charge capacitors and line (or Cable)

rww1

Page 33: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

VSC scheme with overhead line (based on Caprivi)

no Dc Fast (4 msec) breaker installed Resonant DC Breaker (50-75 msec installed)

On DC fault.. Block firing pulse.. MMC capacitors cannot discharge into line but diodes will continue to commutate and feed DC fault (as 6P LCC rectifier)

Open AC breaker .. Remove 6p rectifier diode current DC line will discharge slowly.. Based on the R/L circuit of the

Dc line will keep the post fault DC current present for seconds up to a couple of minutes .

A dc switching action is required to allow Dc fault recovery

DC Line Fault

Page 34: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Start up sequence

[s] 2.60 2.80 3.00 3.20 3.40 3.60 3.80 4.00

-10.0

10.0

(kA)

Iac T2 (Sending end)

-2.0

12.0

(kA)

DC fault current

-100

700

(kV)

Edc2 (+) (Vdc control end)

-1.0

7.0

(kA)

Idc 2 -> 1

-0.2k

1.0k

(MW

)

(-) P1 P2

DC Line Fault - restartFault

detectionValve

blocking MRTBreclose

Fault clearing(MRTB)

AC Brk close

AC Brk open Valve

deblock Ramp up

JCGA1

Page 35: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Summary for VSC Dc Line Faults

• Pulse Blocking removes discharge of capacitors quickly • AC breaker is required to open to remove 6P diode

current. • For a weak ac system .. DC fault draws fault current from

AC bus. dc fault = ac fault • Post fault residual dc current requires resonant Dc breaker• For recovery inrush.. MMC capacitors are already charged• Power ramp rate is determined by ac system strength not

dc controls .

Page 36: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Neutral Return

• Eliminate ground currents • Increased line losses• DC voltage offset at

remote station.. Requires more dc insulation

• Neutral current can be controlled to zero by bipole controller

• During pole outage, the pole conductor can be used to reduce losses.

Page 37: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

DC Grid Modelling Test System (B4-58)

B4-57 has developed T-line and cable parameters for test case

A base PSCAD and EMPT-RV test cases are available.

Models are changing ..

Test Case alternatives• Monopole• Bipole with neutral return • Bipole with ground/ sea

electrodes.

Page 38: Voltage Source Converter (VSC) IEEE PES Winnipeg …sites.ieee.org/winnipeg/files/2012/12/2012-12-18-pes-presentation.pdf · Voltage Source Converter (VSC) IEEE PES Winnipeg Tutorial

Thank you…

Questions?