  • 8/22/2019 Volet

    1/4810

    fre protection

    www.france-air.com Guide created by France Air 2010. All rights reserved.

    orcades

    technical description

    Orcadesair intake openingframe

    Fire class Launching mechanism complies to the NFS 61-937

    according to the tests of the CNPP relative to the launchingmechanisms for remote controlled opening in front.

    Dimensions

    advantagesCareful design (grille Cyclades for interior face option).

    Good thermal isolation for a maximum comfort.

    Good air and waterproofness (covering vanes).

    Installation possible on door (with kit).

    Motorizable by electrical jack (factory or on work site).

    Launching by pneumatic jack.

    range Air intake wall opening frames with free area, matching to the

    dampers for the corridors.

    Wall opening frames of 1m2 of free area or of SGO

    for stairwells. 2 versions :

    - Insulated.- Insulated : enabling to get a cfcientK = 1,55 W/m2/ C.

    Dimensions : range enabling free passing from 10 dm2 to 1 m2(see selection chart).

    Launching by electromagnetic jack by pulse or break 24or 48 Vcc or by pneumatic launching.Possibility of double launching by adding a thermal fusecalibrated at 70 C depending on implantation.

    Bipolar or unipolar contacts.

    application Remote controlled grilles used on vertical face of building,

    for natural air intake, of smoke extraction process in ERP andcollective housing (premises, stairwells, corridors).

    construction / composition

    Grille with articulated vanes, made of aluminium frame inwhich aluminium blades pivot.

    The standard nish is anodised natural silver (paint option).

    The blades are synchronised by a linkage and opened by a spring.They will be kept closed in position.

    The water proofness and airtightness is ensured by the coveringof the vanes. In the insulated version, the airtightness is reinforced

    by a gasket. In the insulated version, the blades are doubled with an expanded

    polystyrene M1 (K = 1,55 W/m2/C) of 23 mm, locked up in to aPVC case.

    Launching deviced :

    The facade wall opening frame Orcades is equipped with anelectromagnetic magnet ensuring the launching by pulse or bybreak 24 Vcc or 48 Vcc (power 3,5 W or 1,6 W).

    The launching can also be done by pneumatic jack.

    It is equipped with a manual rearmament control. It can be equipped with a double launching by adding

    a thermal fuse calibrated at 70 C.

    options Electric rearmament jack.

    Bipolar contacts.

    Thermal fuse (double launching fuse and coil).

    Assembly kit for thin wall : door and exterior woodwork.

    packaging On pallet.

    specications The facade wall opening frame will have articulated vanes in

    aluminium and will be perfectly air and water proof in closedposition. The free area will be tested in factory..

    Mechanism complying to NF S 61-937.

    Type Orcades, France Air brand.

    *

    * Free movement

    The installation of Orcades with a frame is highly recommendedto maintain the rigidity of the set.

    Electric features - electric version

    Power coil by pulse = 3,5 W. Power coil by break = 1,6 W.

    nominal

    dimensions

    overall

    dimensions

    reservation

    dim.

    without

    frame

    reservation

    dim.

    without

    frame

    depth grilles*

    Cyclades

    Extra

    grilles

    Cyclades

    Light and

    Medium

    Ln Ln + 80 Ln + 50 Ln + 5 100 Ln + 136 Ln + 110

    Hn Hn + 80 Hn + 50 Hn + 5 100 Hn + 137 Hn + 110

    (dimensions in mm.)* The dimensions o the grilles are oreseen or an installation with rame.

    Connection

    boxLaunchingdevice

    Openingsprings

  • 8/22/2019 Volet

    2/4811

    fre protection

    Guide created by France Air 2010 All rights reserved. www.france-air.com

    orca

    des

    tting and connection Functioning principle

    Assembled on a facade, in a low part of the premises, Orcades ensures fresh air intake.

    Installation advice

    The facade wall dampers Orcades are attached to a concretewall (mechanism interior side) with the help of sealing frameor in a metallic wall.

    Caution, foresee the clearance of the blades (140 mm)towards the exterior of the building.

    Caution, complying to 6 o the appendix A che VIII, allthe elements contributing to the rearmament (handle tomanipulate and hanging system by magnetic coil) have tobe at an inerior height o 3m in regards to the foor.

    Connection electric version

    Two compression glands are delivered to receive the remote control

    and signalling cables.The wiring has to be done according to the opposite diagram.

    Connection pneumatic version

    Copper pipe 6 mm to link to the Orcades. Service pressure 4 Ps 6 bars.

    Selection of the Orcades

    All the Orcades are with horizontal blades.

    Free area (rearmament manual / rearmament by jack) no difference of SLC between a standard Orcades and an insulated Orcades.

    Particular dimensions or air intake in stairwells 1min SGO.

    Dimensions or air intake in corridor or airintake in premises.

    Non existing dimension.

    Hn

    in dm2number of

    blades

    Ln

    330 475 600 725 850 975 1100 1225 1350

    350 2 8,8 / i 11,4 / i 14,0 / i 16,7 / i 19,3 / i 21,9 / i 24,6 / i 24,2 / i

    475 3 13,1 / i 16,9 / i 20,9 / i 24,8 / i 28,7 / i 32,6 / i 36,6 / i 40,5 / i

    600 4 11,3 / 9,4 17,3 / 15,5 22,5 / 20,7 27,7 / 25,9 32,9 / 31,1 38,2 / 36,3 43,4 / 41,5 48,6 / 46,7 53,8 / 51,9

    725 5 14,0 / 11,8 21,6 / 19,3 28,1 / 25,8 34,6 / 32,3 41,1 / 38,8 47,6 / 45,3 54,1 / 51,8 60,6 / 58,3 67,1 / 64,8

    850 6 16,8 / 14,2 25,9 / 23,3 33,7 / 31,0 41,4 / 38,8 49,2 / 46,6 57,0 / 54,3 64,8 / 62,1 72,6 / 69,9 80,4 / 77,7

    975* 7 19,6 / 16,5 30,2 / 27,1 39,2 / 36,1 48,3 / 45,2 57,4 / 54,3 66,5 / 63,4 75,5 / 72,4 84,6 / 81,5 93,7 / 90,6

    1100 8 22,4 / 18,9 34,4 / 30,9 44,8 /41,3 55,2 / 51,6 65,5 / 62,0 75,9 / 72,4 86,3 / 82,7 96,6 / 93,1 107,0 / 103,5

    1250 9 25,2 / 21,3 38,7 / 34,8 50,4 / 46,4 62,0 / 58,1 73,7 / 69,7 85,3 / 81,4 97,0 / 93,0 108,6 / 104,7

    1350 10 28,0 / 23,6 43,0 / 38,6 55,9 / 51,6 68,9 / 64,5 81,8 / 77,5 94,8 / 90,4 107,7 / 103,3 120,6 / 116,3*: maximum height o product enabling the air passage surace to be 1m maximum rom foor.i: closing motorization impossible on these dimensions

    SGO

    Hn

    in dm2number of

    blades

    Ln

    330 475 600 725 850 975 1100 1225 1350

    350 2 0,11 0,15 0,18 0,21 0,25 0,28 0,32 0,35475 3 0,17 0,23 0,28 0,33 0,38 0,43 0,49 0,54

    600 4 0,16 0,25 0,32 0,40 0,47 0,55 0,62 0,70 0,77

    725 5 0,20 0,30 0,39 0,48 0,57 0,66 0,75 0,85 0,94

    850 6 0,21 0,33 0,43 0,53 0,63 0,72 0,82 0,92 1,02

    975* 7 0,25 0,38 0,50 0,61 0,72 0,84 0,95 1,07 1,18

    1100 8 0,28 0,43 0,56 0,69 0,82 0,95 1,08 1,21 1,34

    1250 9 0,32 0,49 0,63 0,78 0,92 1,07 1,21 1,36

    1350 10 0,35 0,54 0,70 0,86 1,02 1,18 1,34 1,51*: maximum height o product enabling the air passage surace to be 1m maximum rom foor.i: closing motorization impossible on these dimensions

  • 8/22/2019 Volet

    3/4812

    fre protection

    www.france-air.com Guide created by France Air 2010. All rights reserved.

    specific accessories specific accessories

    Sealing rame

    The sealing frame is the linking element to x the Orcadesopening frame to the wall.

    Its use is recommanded for concrete wall assemblies.The frame is supplied in a kit with assembly instructions.

    Covering grilles Cyclades

    The grilles Cyclades Light/Medium/Extra will be xed with 4screws into the wall. These screws maintainthe grilles frame against the wall.

    The grille Cyclades Light has a xed core.The Cyclades Medium and Extra have openingcores.

    Position contact

    Inverter contact stand by position (closed) or securityposition (open), unipolar or bipolar.

    Launching plunger Launching plunger by pulse or break, 24 Vcc, 48 Vcc.

    Additional contacts

    Possibility of adding contacts on Orcades that have alreadybeen installed, or by way of polar contact, or by wayof unipolar contacts (if the delivered Orcade possesses nocontact).

    Brac et

    Screw oramper xat on

    Sea ng eet

    Assembly kit or door installations

    It is a set of parts enabling to sandwich a 50 mm panel.Orcades xing system on xed wall.

    Caution : you have to foresee a rear covering box (Orcadeswill exceed the wall) to be able to add a covering grille.

    Rearmament jack kit

    The rearmament jack can be assembled in factory ordelivered, on already installed Orcades.

    They enable an electric closing of the wall opening frameafter an opening (all or none).

    Technical information :- supply voltage : 24 Vcc.- jack consumption : 1,25 A.- circuit : 80 mm.- power : 400 N.

    This jack must be ordered with a supply case that will beable to control several wall opening frames equipped with

    jack (case to choose according to the number of jackequipped Orcades on the work site).

    Insulation kit

    Possibility of insulating the Orcades blades not insulated onthe work site.

    orcades

  • 8/22/2019 Volet

    4/4813

    fre protection

    Guide created by France Air 2010 All rights reserved. www.france-air.com

    commissioning and connection

    Maintenance

    Maintenance : according to norm NF S 61-933 Cleaning of the set (dust) at the start of the installation.

    Functioning, foresee periodical trials, according to normNF S 61-933.

    Denitions : Free area of a wall damper : interior geometric area (provided

    that the wall damper opens at at least 60). Useful area of wall damper : the useful area of wall opening

    frame is equal to the free area of this wall damper affectedof a coefcient of 0,5.

    UDP : Passage unit. QE = extract air ow.

    QI = insufation air ow.

    Smoke extraction of corridors

    regulation reminders

    Smoke extracton of premises

    Smoke extraction of stairs

    To limit or avoid the stairwells lling up with smoke, they can be, depending on the case, smoke extracted by a natural ushingor a pressurising application in relation to the damaged premises.

    The DENFC will be placed on the high part of the stairwell, and an air intake, of equal surface, will be placed at the low part of the cage.The manual control of the smoke extraction system is placed on the stairwell, at the level of the building entrance.

    selection smoke extraction mechanical/natural smoke extraction mechanical/natural smoke extraction

    mechanical extraction natural insufation natural extraction natural insufation

    positionin the corridor

    IT 246 - The air intakes and the smoke evacuations are distributed, taking into account the localisation of the risks.

    IT 246 6.2If the air intake is carried outby the wall opening frames,their free area taken intoaccount has to be situated

    in the inferior half of thepremises.

    IT 246 6.1A wall opening frame can count on air intake grille and/or smoke extraction; the area taken into account has to bepositioned in the superior half of the corridor and has to be atmore that 1.8m of the oor, the free area taken into account

    for the air intake has to be outside of the previously denedevacuation zone.

    sizing wall opening frame Qe = 0,5 m3/s/UDPNominal section :

    with VMAX = 5 m/s

    QI = QE IT 246 6.1Each air intake and each smoke evacuation has a free areaof minimum 10 dm2 by passage circulation unit.

    SN =QE

    VMAX

    selection smoke extraction mechanical/natural smoke extraction mechanical/natural smoke extraction

    mechanical extraction natural insufation natural extraction natural insuffation

    positionin the premises

    IT 246If the air intake is carried outby the wall dampers, theirfree area taken into accounthas to be situated in the infe-rior half of the premises

    IT 7.1.3.The outlets must be positio-ned in the zone lled withsmoke. The smoke evacua-tions, for roof with a slopeinferior to 10% have to besituated at a maximum dis-tance of all premises contourpoints with d 4 x H and 30 m with H average height.For all roofs with a slopesuperior to 10 %, the smokeevacuations must be embed-ded at the highest possible,at a height to the averageheight under roof or ceiling.

    The air intake must be donein the free height of smokeHP (at low parts of thecirculation).

    sizing of wall dampers Nominal section :with VMAX = 5 m/s

    QI = QE IT 246The useful area of the walldampers will be obtained

    affecting a coefcient of 0,5of the free area.

    The geometric area of the airentrances have to be at leastequal to the geometric area

    of the outlets ensuring theextraction.

    SN = QE VMAX

    Sizing of a wall damper and a natural smoke and heat extraction device

    orca