vol1 p632-635

Upload: kjfens

Post on 30-Oct-2015

69 views

Category:

Documents


0 download

DESCRIPTION

Numerical Trafo Protn

TRANSCRIPT

  • 7/15/2019 Vol1 P632-635

    1/605

    MiCOM

    P631/P632/P633/P634Transformer Differential Protection Devices

    Technical Manual

    Volume 1 of 2

  • 7/15/2019 Vol1 P632-635

    2/605

  • 7/15/2019 Vol1 P632-635

    3/605

    MiCOM

    P631/P632/P633/P634Transformer Differential Protection Devices

    Technical Manual

  • 7/15/2019 Vol1 P632-635

    4/605

  • 7/15/2019 Vol1 P632-635

    5/605

  • 7/15/2019 Vol1 P632-635

    6/605

  • 7/15/2019 Vol1 P632-635

    7/605

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 11

  • 7/15/2019 Vol1 P632-635

    8/605

    12 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

  • 7/15/2019 Vol1 P632-635

    9/605

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 13

    1 Appl ication and Scope 1-1

    2 Technical Data 2-12.1 Conformity 2-12.2 General Data 2-12.3 Tests 2-22.3.1 Type tests 2-22.3.2 Routine Tests 2-52.4 Environmental Conditions 2-52.5 Inputs and Outputs 2-6

    2.6 Interfaces 2-82.7 Information Output 2-112.8 Settings 2-112.9 Deviations 2-122.9.1 Deviations of the Operate Values 2-122.9.2 Deviations of the Timer Stages 2-132.9.3 Deviations of Measured Data Acquisition 2-142.10 Recording Functions 2-152.11 Power Supply 2-162.12 Current Transformer Specifications 2-17

  • 7/15/2019 Vol1 P632-635

    10/605

    14 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3 Operation 3-13.1 Modular Structure 3-13.2 Operator-Machine Communication 3-33.3 Configuration of the Measured

    Value Panels(Function Group LOC) 3-4

    3.4 Serial Interfaces 3-73.4.1 PC interface (Function Group PC) 3-73.4.2 Communication Interface (Function Group COMM1) 3-9

    3.4.3 Communication Interface 2 (Function Group COMM2) 3-183.4.4 UCA2 Communication Interface (Function Group UCA2) 3-21

    3.4.5 IEC 61850 CommunicationInterface (Function groups IEC,GOOSE and GSSE) 3-22

    3.4.5.1 IEC 61850 CommunicationInterface

    (Function Group IEC) 3-22

    3.4.5.2 Generic Object OrientedSubstation Event

    (Function Group GOOSE) 3.25

    5.4.5.3 Generic Substation State Event (Function Group GSSE) 3-273.5 IRIG-B Clock Synchronization (Function Group IRIGB) 3-293.6 Configuration and Operating Mode

    of the Binary Inputs(Function Group INP) 3-30

    3.7 Measured data input (Function Group MEASI) 3-313.7.1 Direct Current Input 3-323.7.2 Input for Connection of a

    Resistance Thermometer

    3-36

    3.8 Configuration, Operating Mode,and Blocking of the Output Relays

    (Function Group OUTP) 3-37

    3.9 Measured data output (Function Group MEASO) 3-403.9.1 BCD Measured Data Output 3-433.9.2 Analog Measured Data Output 3-453.9.3 Output of External Measured

    Data3-51

    3.10 Configuration and Operating Modeof the LED Indicators

    (Function Group LED) 3-52

    3.11 Main Functions of the P63x (Function Group MAIN) 3-563.11.1 Conditioning of the Measured

    values3-56

    3.11.2 Phase Reversal Function 3-603.11.3 Selection of the Residual Current

    to be Monitored3-62

    3.11.4 Forming a Virtual Transformer End 3-643.11.5 Operating Data Measurement 3-663.11.6 Configuring and Enabling the

    Protection Functions3-79

    3.11.7 Activation of Dynamic Parameters 3-813.11.8 Multiple Blocking 3-823.11.9 Multiple Signaling of the

    Measuring Circuit MonitoringFunction

    3-84

    3.11.10 Blocked / Faulty 3-85

    3.11.11 Starting Signals and TrippingLogic

    3-86

    3.11.12 Time Tagging and ClockSynchronization

    3-90

    3.11.13 Resetting Mechanisms 3-92

  • 7/15/2019 Vol1 P632-635

    11/605

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 15

    3.11.14 Assigning CommunicationsInterfaces to PhysicalCommunications Channels

    3-93

    3.11.15 Test mode 3-943.12 Parameter Subset Selection (Function Group PSS) 3-95

    3.13 Self-Monitoring (Function Group SFMON) 3-973.14 Operating Data Recording (Function Group OP_RC) 3-1003.15 Monitoring Signal Recording (Function Group MT_RC) 3-1013.16 Overload Data Acquisition (Function Group OL_DA) 3-1023.17 Overload Recording (Function Group OL_RC) 3-1053.18 Fault Data Acquisition (Function Group FT_DA) 3-1083.19 Fault Recording (Function Group FT_RC) 3-1163.20 Differential Protection (Function Group DIFF) 3-122

    3.21 Ground Differential Protection (Br:Restricted earth fault protection)

    (Function Groups REF_1to REF_3)

    3-145

    3.22 Definite-Time OvercurrentProtection

    (Function Groups DTOC1to DTOC3)

    3-157

    3.23 Inverse-Time OvercurrentProtection

    (Function Groups IDMT1to IDMT3)

    3-167

    3-24 Thermal Overload Protection (Function Groups THRM1and THRM2)

    3-183

    3.25 Time-Voltage Protection (Function Group V) 3-1933.26 Over-/Underfrequency Protection (Function Group f) 3-1963.27 Overfluxing Protection (Function Group V/f) 3-2023.28 Current Transformer Supervision (Function Group CTS) 3-2103.29 Measuring-Circuit Monitoring (Function Groups MCM_1

    to MCM_4)

    3-218

    3.30 Limit Value Monitoring (Function Group LIMIT) 3-2213.31 Limit Value Monitoring of Phase

    Currents(Function Groups LIM_1 toLIM_3)

    3-224

    3.32 Programmable Logic (Function Group LOGIC) 3-227

  • 7/15/2019 Vol1 P632-635

    12/605

    16 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    4 Design 4-14.1 Designs 4-14.2 Modules 4-9

    5 Installation and Connection 5-15.1 Unpacking and Packing 5-15.2 Checking Nominal Data and Design Type 5-15.3 Location Requirements 5-25.4 Installation 5-35.5 Protective and Operational Grounding 5-145.6 Connection 5-155.6.1 Connecting Measuring and Auxiliary Circuits 5-15

    5.6.2 Connecting the IRIG-B Interface 5-185.6.3 Connecting the Serial Interfaces 5-18

    6 Local Contro l Panel 6-16.1 Display and Keypad 6-26.2 Changing between Display Levels 6-66.3 Display Illumination 6-76.4 Control at the Panel Level 6-76.5 Control at the Menu Tree Level 6-86.5.1 Navigation in the Menu Tree 6-86.5.2 Switching Between Address Mode and Plain Text Mode 6-96.5.3 Change-Enabling Function 6-106.5.4 Changing Parameters 6-13

    6.5.5 Setting a List Parameter 6-146.5.6 Memory Readout 6-156.5.7 Resetting 6-196.5.8 Password-Protected Control Actions 6-206.5.9 Changing the Password 6-21

    7 Settings 7-17.1 Parameters 7-17.1.1 Device Identification 7-27.1.2 Configuration Parameters 7-67.1.3 Function Parameters 7-507.1.3.1 Global 7-507.1.3.2 General Functions 7-557.1.3.3 Parameter Subsets 7-67

  • 7/15/2019 Vol1 P632-635

    13/605

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 17

    8 Information and Control Functions 8-18.1 Operation 8-18.1.1 Cyclic Values 8-18.1.1.1 Measured Operating Data 8-18.1.1.2 Physical State Signals 8-88.1.1.3 Logic State Signals 8-158.1.2 Control and Testing 8-338.1.3 Operating Data Recording 8-378.2 Events 8-388.2.1 Event Counters 8-388.2.2 Measured Event Data 8-398.2.3 Event Recording 8-42

    9 Commissioning 9-19.1 Safety Instructions 9-19.2 Commissioning Tests 9-3

    10 Troubleshoot ing 10-1

    11 Maintenance 11-1

    12 Storage 12-1

    13 Accessories and Spare Parts 13-1

    14 Order Information 14-114.1 Order Information for P631 in 40TE case 14-114.2 Order Information for P632 in 40TE case 14-214.3 Order Information for P633 in 40TE or 84TE case 14-314.4 Order Information for P634 in 84TE case 14-4

    AppendixA GlossaryB Signal ListC Terminal connection diagramsD Overview of Changes

    Address list:See chapters 7, 8 and 10, as well as the MiCOM S1 / S&R-103support software.

  • 7/15/2019 Vol1 P632-635

    14/605

    18 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

  • 7/15/2019 Vol1 P632-635

    15/605

    1 Application and Scope

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 1-1

    1 Application and Scope

    The P63x differential protection devices are designed for the fast and selective short-circuit protection of transformers, motors and generators and of other two-, three- orfour-winding end arrangements.

    The MiCOM P63x range features fast three-stage differential protection by applying atripping characteristic with two knee points and two high value settable differentialcurrent thresholds to enable rapid tripping in conjunction with inrush, overfluxing andthrough-stabilization. Amplitude and vector group matching is made by just entering thenominal values of each transformer end and the associated current transformers.A new (optional) overreaching current measuring circuit monitoring function will preventunwanted tripping by differential protection for faults in the CT's secondary circuit.

    When considering 1 circuit breaker arrangements and ring busbar arrangements it isalso possible to define a virtual end, where phase currents and the residual current fromtwo freely-selectable ends may be added geometrically (vector sum).

    A phase reversal function is available for applications in pumped storage power stations.

    In a device type where protection functions are available more than once they may eachbe freely assigned to individual winding ends.

    Moreover there are numerous backup protection and automatic control functionsavailable.

    The relevant protection parameters can be stored in four independent parametersubsets in order to adapt the protection device to different operating and power systemmanagement conditions.

  • 7/15/2019 Vol1 P632-635

    16/605

    Application and Scope(continued)

    1-2 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    General functionsGeneral functions are complete function groups, which may be individually configured orcancelled, depending on the application (e.g. included in or excluded from the devicesconfiguration).An exception is the MA I N function, which is always visible.

    A function is selected by a mouse click in the support software:

    Unused or cancelled function groups are hidden to the user, thus simplifying the menu.

    Communication functions and measured value functions may also be configured orexcluded.

    This concept provides a wide choice of functions and makes wide-ranging application ofthe protection device possible, with just one model version. On the other hand simpleand clear parameter settings and adaptations to each protection scheme can be made.The powerful programmable logic provided by the protection device also makes itpossible to accommodate special applications.

  • 7/15/2019 Vol1 P632-635

    17/605

    Application and Scope(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 1-3

    General Functions P631 P632 P633 P634

    87 DIFF Differential protection

    > Three-stage differential protection

    > Amplitude and vector group matching

    > Residual current filtering

    > Tripping characteristic with two kneepoints

    > Inrush stabilization

    > Overfluxing stabilization

    > Through stabilization

    2 ends 2 ends 3 ends 4 ends

    87 G REF_x Ground differential protection (Br:

    Restricted earth fault protection)

    - 2 3 3

    50 DTOCx Definite-time overcurrent protection 2 2 3 3

    51 IDMTx Inverse-time overcurrent protection 2 2 3 3

    49 THRMx Thermal overload protection 1 1 2 2

    27 / 59 V Time-voltage protection 1 1 1

    81 O/U f Over-/underfrequency protection 1 1 1

    24 U_f Overfluxing protection 1 1 1

    CTS Current transformer supervision optional optional optional optional

    MCM_x Measuring-circuit monitoring 2 2 3 4

    LIMIT, LIM_x Limit value monitoring 2 2 3 3

    LOGIC Programmable logic 1 1 1 1

    Communication Functions P63x

    COMM1, COMM2

    IRIGB

    IEC, GOOSE, GSSE

    2 information interfaces

    IRIG-B

    IEC 61850 communications protocol

    options

    Input/output functions P631 P632 P633 P634

    INP / OUTP Binary signal inputs / Output relays (maximum number) 4 / 14 34 / 22 40 / 30 34 / 22

    Measured Value Functions P631 P632 P633 P634

    MEASI / MEASO Analog input / output(20 mA and resistance thermometer inputs, 2 x 20 mAoutputs)

    - optional optional optional

    Measuring inputs P631 P632 P633 P634

    Phase currents 2 x 3 2 x 3 3 x 3 4 x 3Resultant current and neutral-point current - 2 3 3Voltage - 1 1 1

  • 7/15/2019 Vol1 P632-635

    18/605

    Application and Scope(continued)

    1-4 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Global functionsIn addition to the listed features and extensive self-monitoring, the P63x offers thefollowing global functions:

    Global functions

    PSS Parameter subset selectionSystem measurements to support the user during commissioning, testingand operation

    OP_RC Operating data recording(time-tagged event logging)

    OL_DA Overload Data Acquisition

    OL_RC Overload recording (time-tagged event logging)FT_DA Fault data acquisition for a particular, settable point in time during a faultFT_RC Fault recording (time-tagged event logging together with fault value

    recording of the three phase currents, the residual currents, the threephase-to-ground voltages, the neutral-point displacement voltage and thereference voltage before, during and after a fault).

    Further functions

    Further functions

    MAIN Main functionDVICE Device

    LED LED indicatorsLOC Local control panelPC PC link

    SFMON Comprehensive self-monitoringMT_RC Monitoring Signal Recording

  • 7/15/2019 Vol1 P632-635

    19/605

    Application and Scope(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 1-5

    Functional diagram

    Iph

    V

    IY,a

    IY,b

    Iph

    IY,c

    Iph

    Iph

    Ivirtual

    Communication

    to SCADA / Substation control / RTU / Modem ...via RS485 or Optical Fibre

    using IEC 60870-5-101, -103, Modbus, DNP3, Courierresp.

    via RJ45 or Fibre Optics using IEC 61850

    Recordingand

    DataAcquisition

    Transformer Differential

    Protection P63x

    always available

    optional or specific

    COMM1 COMM2 IECInter

    MiCOMIRIG-B Self

    Monitoring

    LIM-3 LIM-2 LIM-1 Metering

    Overload rec.

    Fault rec.

    LOGIC

    27, 59V

    81f

    24V/f

    87GREF_3

    87GREF_2

    87GREF_1

    50DTOC-3

    50DTOC-2

    50DTOC-1

    51IDMT-3

    51IDMT--2

    51IDMT--1

    49THRM2

    49THRM1

    87DIFF

    RTD,mA mA_OP

    BC_4

    BC _3

    BC_2

    BC_1

  • 7/15/2019 Vol1 P632-635

    20/605

    Application and Scope(continued)

    1-6 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    DesignThe MiCOM P631, P632, P633 and P634 protection devices are modular in design.The plug-in modules are housed in a robust aluminum case and electricallyinterconnected via one analog p/c board and one digital p/c board.

    Inputs and outputsThe nominal current and voltage values of the measuring inputs on the P63x can be setwith the function parameters.

    The nominal voltage range of the optical coupler inputs is 24 to 250 V DC. As an optionbinary signal input modules with a higher operate threshold are available.

    The auxiliary voltage input for the power supply is also designed for an extended range.

    The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. A 24 VDCversion is also available.

    All output relays can be utilized for signaling and command purposes.

    The optional PT 100 input is lead-compensated, balanced and linearized for PT 100resistance thermometers as per IEC 751.

    The optional 0 to 20 mA input provides open-circuit and overload monitoring, zerosuppression defined by a setting, plus the option of linearizing the input variable via20 adjustable interpolation points.

    Two selectable measured values (cyclically updated measured operating data andstored measured fault data) can be output as a burden-independent direct current viathe two optional 0 to 20 mA outputs. The characteristics are defined via 3 adjustableinterpolation points allowing a minimum output current (4 mA, for example) for slave-sideopen-circuit monitoring, knee-point definition for fine scaling, and a limitation to lowernominal currents (10 mA, for example). Where sufficient output relays are available,a selectable measured value can be output in BCD-coded form by contacts.

  • 7/15/2019 Vol1 P632-635

    21/605

    Application and Scope(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 1-7

    Control and display Local control panel

    17 LED indicators,12 with user-definable functional assignment

    PC interface

    Communication interfaces (optional)

    Information interfacesInformation is exchanged through the local control panel, the PC interface, or twooptional communication interfaces (channel 1 and channel 2).

    Using the first communication interface, the numerical protection device can be wired

    either to the substation control system or to a telecontrol system.The first communication interface is optionally available with a switcheable protocol(per IEC 60870-5-103, IEC 870-5-101, DNP 3.0, MODBUS or Courier) or as anIEC 61850 interface.

    The second communication interface (communication protocol per IEC 60870-5-103only) is designed for remote control.

    External clock synchronization can be accomplished by using the optional IRIG-B input.

  • 7/15/2019 Vol1 P632-635

    22/605

    Application and Scope(continued)

    1-8 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Overview of allfunction groups

    P631 P632 P633 P634

    IDMT1: Inverse-time overcurrent protection 1 9 9 9 9IDMT2: Inverse-time overcurrent protection 2 9 9 9 9IDMT3: Inverse-time overcurrent protection 3 - - 9 9OUTP: Binary outputs 9 9 9 9OP_RC: Operating data recording 9 9 9 9DIFF: Differential protection 9 9 9 9REF_1: Ground differential protection 1

    (Br: Restricted earth fault protection 1)- 9 9 9

    REF_2: Ground differential protection 2(Br: Restricted earth fault protection 2)

    - 9 9 9

    REF_3: Ground differential protection 3(Br: Restricted earth fault protection 3)

    - - 9 9

    INP: Binary input 9 9 9 9f: Over-/underfrequency protection - 9 9 9DVICE: Device 9 9 9 9GOOSE: Generic Object Orientated Substation Events

    (as of P63x 610)9 9 9 9

    LIMIT: Limit value monitoring 9 9 9 9MAIN: Main function 9 9 9 9LIM_1: Limit value monitoring 1 9 9 9 9LIM_2: Limit value monitoring 2 9 9 9 9LIM_3: Limit value monitoring 3 - - 9 9GSSE: IEC Generic Substation Status Events

    (as of P63x 610)9 9 9 9

    IEC: IEC 61850 Communication (as of P63x 610) 9 9 9 9IRIGB: IRIG-B interface 9 9 9 9COMM1: Communication interface 1 9 9 9 9COMM2: Communication interface 2 (as of P63x 602) 9 9 9 9LED: LED indicators 9 9 9 9LOGIC: Logic 9 9 9 9MEASO: Measured data output 9 9 9 9MEASI: Measured data input 9 9 9 9MCM_1: Measuring-circuit monitoring 1 (as of P63x 602) 9 9 9 9MCM_2: Measuring-circuit monitoring 2 (as of P63x 602) 9 9 9 9MCM_3: Measuring-circuit monitoring 3 (as of P63x 602) 9 9MCM_4: Measuring-circuit monitoring 4 (as of P63x 602) 9PC: PC link 9 9 9 9PSS: Parameter subset selection 9 9 9 9SFMON: Self-monitoring 9 9 9 9CTS: Current transformer supervision (as of P63x 606) 9 9 9 9FT_RC: Fault recording 9 9 9 9

    FT_DA: Fault data acquisition9

    9

    9

    9

    THRM1: Thermal overload protection 1 9 9 9 9THRM2: Thermal overload protection 2 - - 9 9V: Time-voltage protection - 9 9 9V/f: Overfluxing protection (as of P63x 602) 9 9 9 9OL_RC: Overload recording 9 9 9 9OL_DA: Overload data acquisition 9 9 9 9DTOC1: Definite-time overcurrent protection 1 9 9 9 9DTOC2 Definite-time overcurrent protection 2 9 9 9 9DTOC3: Definite-time overcurrent protection 3 - - 9 9MT_RC: Monitoring signal recording 9 9 9 9UCA2: Utility Communication Architecture 2.0

    (P63x 604/-605/-606 only)9 9 9 9

    LOC: Local control panel 9 9 9 9

  • 7/15/2019 Vol1 P632-635

    23/605

    2 Technical Data

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-1

    2 Technical Data

    2.1 Conformity

    NoticeApplicable to P631 / P632 / P634, version -305 -403/404/-610 andP633 version -305-404/405/406-610.

    Declaration of conformity(Per Article 10 of EC Directive 72/73/EC.)The products designated P631, P632, P633 and P634 Transformer DifferentialProtection Devices have been designed and manufactured in compliance with Europeanstandards EN 60255-6 and EN 60010-1 and with the EMC Directive and the LowVoltage Directive issued by the Council of the European Community.

    2.2 General Data

    General device dataDesignSurface-mounted case suitable for wall installation or flush-mounted case for19" cabinets and for control panels.

    Terminals

    PC interface (X6):EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin.

    Communication Interface:Optical fibers (X7 and X8): F-SMA optical fiber connection

    per IEC 60874-2 and DIN 47258 (for plastic fibers)oroptical fiber connection BFOC-ST

    connector 2.5

    per IEC 60874-10-1 and DIN 47254-1 (for glass fibers)

    (ST

    is a registered trademark of AT&TLightguide Cable Connectors)

    orLeads (X9 and X10): M2 threaded terminal ends for wire cross-sections

    up to 1.5 mm.

    or (for IEC 61850 only via

    100 Mbit/s Ethernet board) (X13): Glass fiber SC per IEC 60874-14-4 and RJ45 wire

    IRIG-B Interface (X11): BNC plug.

  • 7/15/2019 Vol1 P632-635

    24/605

    2 Technical Data(continued)

    2-2 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Current Measuring Inputs:Threaded terminals for pin-terminal connection: M5,self-centering with wire protection for conductor cross-sections 4 mm

    2

    orThreaded terminals for ring-terminal connection: M4

    Other Inputs and Outputs:Threaded terminals for pin-terminal connection: M3,self-centering with wire protection for conductor cross-sections from 0.2 to 2.5 mm2orThreaded terminals for ring-terminal connection: M4.

    Creepage Distances and Clearances

    Per EN 61010-1 and IEC 664-1.Pollution degree 3, working voltage 250 V,overvoltage category III, impulse test voltage 5 kV.

    2.3 Tests

    2.3.1 Type Tests

    Type testsAll tests per EN 60263-6

    or IEC 60255-26.

    Electromagneticcompatibility (EMC)

    Interference SuppressionPer EN 55022 or IEC CISPR 22, Class A.

    1 MHz Burst Disturbance TestPer IEC 255 Part 22-1

    or IEC 60255-22-1, Class III

    Common-mode test voltage: 2.5 kVDifferential test voltage: 1.0 kVTest duration: > 2 s, Source impedance: 200

    Immunity to Electrostatic DischargePer EN 60255-22-2

    or IEC 60255-22-2, severity level 3

    Contact discharge, single discharges: > 10Holding time: > 5 s

    Test voltage: 6 kVTest generator: 50 to 100 M, 150 pF / 330

    Immunity to Radiated Electromagnetic EnergyPer EN 61000-4-3

    and ENV 50204

    , severity level 3

    Antenna distance to tested device: > 1 m on all sidesTest field strength, frequency band 80 to 1000 MHz: 10 V / mTest using AM: 1 kHz / 80 %Single test at 900 MHz AM 200 Hz / 100 %

    For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition,

    respectively, was used in the test.

  • 7/15/2019 Vol1 P632-635

    25/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-3

    Electrical Fast Transient or Burst RequirementsPer IEC 60255-22-4, Class B.Power supply: Amplitude: 2 kV, Burst frequency: 5 kHzInputs and outputs: Amplitude: 2 kV, Burst frequency: 5 kHzCommunications: Amplitude: 1 kV, Burst frequency: 5 kHz

    Per EN 61000-4-4, severity level 4:

    Power supply: Amplitude: 4 kV, Burst frequency: 2.5 kHz and 5 kHzInputs and outputs: Amplitude: 2 kV, Burst frequency: 5 kHzCommunications: Amplitude: 2 kV, Burst frequency: 5 kHz

    Rise time of one pulse: 5 nsImpulse duration (50% value): 50 ns

    Burst duration: 15 msBurst period: 300 msSource impedance: 50 W

    Current/Voltage Surge Immunity TestPer EN 61000-4-5

    or IEC 61000-4-5, insulation class 4

    Testing of circuits for power supply and asymmetrical or symmetrical lines.Open-circuit voltage, front time / time to half-value: 1.2 / 50 sShort-circuit current, front time / time to half-value: 8 / 20 sAmplitude: 4 / 2 kVPulse frequency: > 5 / minSource impedance: 12 / 42

    Immunity to Conducted DisturbancesInduced by Radio Frequency FieldsPer EN 61000-4-6 or IEC 61000-4-6, severity level 3Test voltage: 10 V

    Power Frequency Magnetic Field ImmunityPer EN 61000-4-8 or IEC 61000-4-8, severity level 4Frequency: 50 HzTest field strength: 30 A / m

    Alternating Component (Ripple) in DC Auxiliary Energizing QuantityPer IEC 255-1112 %

    InsulationVoltage TestPer EN 61010-1 and IEC 255-5.2 kV AC, 60 s.Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supplyinputs. The PC interface must not be subjected to the voltage test.

    Impulse Voltage Withstand TestPer IEC 255-5.Front time: 1.2 sTime to half-value: 50 s

    Peak value: 5 kVSource impedance: 500 W

  • 7/15/2019 Vol1 P632-635

    26/605

    2 Technical Data(continued)

    2-4 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Mechanical robustness1(**)

    Vibration TestPer EN 60255-21-1 or IEC 255-21-1, test severity class 1Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 gFrequency range during transport: 10 to 150 Hz, 1 g

    Shock Response and Withstand Test, Bump TestPer EN 60255-21-2

    or IEC 255-21-2,

    acceleration and pulse duration:Shock Response tests are carried out to verify full operability (during operation),test severity class 1 ,5 g for 11 ms,

    Shock Withstand tests are carried out to verify the endurance (during transport),test severity class 1 ,15 g for 11 ms

    Seismic TestPer EN 60255-21-3

    or IEC 60255-21-3, test procedure A, class 1

    Frequency range:5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.

    Mechanical robustness2(**)

    Vibration TestPer EN 60255-21-1

    or IEC 255-21-1, test severity class 2

    Frequency range in operation: 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 gFrequency range during transport: 10 to 150 Hz, 2 g

    Shock Response and Withstand Test, Bump TestPer EN 60255-21-2

    or IEC 255-21-2,

    acceleration and pulse duration:Shock Response tests are carried out to verify full operability (during operation),test severity class 2,10 g for 11 ms;Shock Withstand tests are carried out to verify the endurance (during transport),test severity class 1,15 g for 11 msShock bump tests are carried out to verify permanent shock (during transport),test severity class 1,10 g for 16 ms

    Seismic TestPer EN 60255-21-3

    or IEC 60255-21-3, test procedure A, class 2

    Frequency range:5 to 8 Hz, 7.5 mm / 3.5 mm, 8 to 35 Hz, 20 / 10 m/s2, 3 x 1 cycle.

    (**)Mechanical robustness 2:Valid for with delivery date as of May 2005, if one of the following case variants isused:

    Flush mounted case, flush-mounting method 2 (with angle brackets and frame)

    Surface-Mounted Case

  • 7/15/2019 Vol1 P632-635

    27/605

    2 Technical Data(continued)

    P63X/EN M/Ca4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-5

    2.3.2 Routine Tests

    All tests per EN 60255-6

    or IEC 255-6and DIN 57435 Part 303.

    Voltage TestPer IEC 255-52.2 kV AC, 1 s.Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supplyinputs.The PC interface must not be subjected to the voltage test.

    Additional Thermal Test

    100% controlled thermal endurance test, inputs loaded.

    2.4 Environmental Conditi ons

    Environment

    TemperaturesRecommended temperature range: -5C to +55C (23F to 131F)Storage and transit: -25 C to +70 C (-13 F to +158 F)

    Ambient Humidity Range 75 % relative humidity (annual mean),56 days at 95 % relative humidity and 40 C (104F), condensation not permitted.

    Solar RadiationDirect solar radiation on the front of the device must be avoided.

  • 7/15/2019 Vol1 P632-635

    28/605

    2 Technical Data(continued)

    2-6 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    2.5 Inputs and Outputs

    Measuring inputsCurrentRated current: 1 or 5 A AC (settable).Nominal burden per phase: < 0.13 VA at Inom

    Load rating:continuous: 4 Inomfor 10 s: 30 Inomfor 1 s: 100 Inom

    Nominal surge current: 250 Inom

    VoltageNominal voltage Vnom: 50 to 130 V AC (adjustable)

    Nominal burden per phase: < 0.3 VA at Vnom = 130 V AC

    Load rating: continuous 150 V AC

    FrequencyNominal frequency fnom: 50 Hz and 60 Hz (adjustable)

    Operating range: 0.95 to 1.05 fnomFrequency protection: 40 to 70 Hz

    All other protection functions:Operating range: 0.95 to 1.05 fnomOverfluxing protection: 0.5 to 1.5 f

    nomBinary signal inputsThreshold Pickup and Drop-off Points as per Ordering Option18 V standard variant (VA,nom: = 24 to 250 V DC):

    Switching threshold in the range 14 V to19 V

    Special variant with switching thresholds from 58 to 72 % of the nominal supply voltage(i.e. definitively ,low for VA < 58 % of the nominal supply voltage,

    definitively ,high for VA > 72 % of the nominal supply voltage)

    "Special variant 73 V": Nominal supply voltage 110 V DC"Special variant 90 V": Nominal supply voltage 127 V DC"Special variant 146 V": Nominal supply voltage 220 V DC

    "Special variant 155 V": Nominal supply voltage 250 V DC

    Power consumption per inputStandard variant:VA = 19 ... 110 V DC: 0.5 W 30 %,

    VA > 110 V DC: VA 5 mA 30 %.

    Special variant:Vin > Switching threshold: VA 5 mA 30 %.

    NotesThe standard variant of binary signal inputs (opto couplers) is recommended in mostapplications, as these inputs operate with any voltage from 19 V. Special versions with

    higher pick-up/drop-off thresholds are provided for applications where a higher switchingthreshold is expressly required.

    The maximum voltage permitted for all binary signal inputs is 300V DC.

  • 7/15/2019 Vol1 P632-635

    29/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-7

    IRIG-B interfaceMinimum / maximum input voltage level(peak-peak): 100 mVpp / 20 Vpp.Input impedance: 33 k at 1 kHz.Electrical isolation: 2 kV

    Direct current inputInput current: 0 to 26 mAValue range: 0.00 to 1.20 IDC,nom (IDC,nom = 20 mA)

    Maximum permissible continuous current: 50 mAMaximum permissible input voltage: 17 VInput resistance: 100 Open-circuit monitoring: 0 to 10 mA (adjustable)Overload monitoring: > 24.8 mAZero suppression: 0.000 to 0.200 IDC,nom (adjustable)

    Resistance thermometerinputs

    Resistance thermometer: For analog module, PT 100 permitted only.Mapping curve as per IEC 751.

    Value range: -40.0 to +215.0C3-wire configuration: max. 20 per conductor.Open and short-circuited input permittedOpen-circuit monitoring: > +215 C and < -40 C

    Output relays Rated voltage: 250 V DC, 250 V ACContinuous current: 5 AShort-duration current: 30 A for 0.5 sMaking capacity: 1000 W (VA) at L/R = 40 msBreaking capacity: 0.2 A at 220 V DC and L/R = 40 ms

    4 A at 230 V AC and cos = 0.4

    BCD Measured DataOutput

    Maximum numerical value that can be displayed: 399

    Direct Current Output

    Value range: 0 to 20 mAPermissible load: 0 to 500 Maximum output voltage: 15 V

  • 7/15/2019 Vol1 P632-635

    30/605

    2 Technical Data(continued)

    2-8 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    2.6 Interfaces

    Local control panelInput or output:via seven keys and a 4 x 20 character-LCD display

    State and fault signals:17 LED indicators (13 permanently assigned, 4 freely configurable)

    PC interfaceTransmission rate: 300 to 115,200 baud (adjustable)

    Communication interfaces

    1 and 2The communication module can be provided with up to two communication channels,depending on the module variant. Channel 1 is designed for twisted pair connection orfiber optic connection, whereas Channel 2 is intended for twisted pair connection only.

    For communication interface 1, communication protocols based on IEC 60870-5-103,IEC 870-5-101, MODBUS or DNP 3.0 (as of version P63x -602 Courier) can be set.

    Communication interface 2 can only be operated with the interface protocol based onIEC 60870-5-103.

    For Wire LeadsPer RS 485 or RS 422, 2 kV isolationDistance to be bridgedPoint-to-point connection: max. 1200 mMultipoint connection: max. 100 m

    Transmission rate Communication Protocol

    BA-no. -910(one channel)

    300 to 19,200 baud (adjustable) IEC 60870-5-103

    BA-no. -921(two channels)

    300 to 64,000 baud(adjustable for COMM1)

    300 to 57,600 baud(adjustable for COMM2)

    Can be set by user for onechannel

    1) Distance to be bridged given for identical optical outputs and inputs at both ends, asystem reserve of 3 dB, and typical fiber attenuation.

  • 7/15/2019 Vol1 P632-635

    31/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-9

    Plastic Fiber ConnectionOptical wavelength: typically 660 nmOptical output: min. -7.5 dBmOptical sensitivity: min. -20 dBmOptical input: max. -5 dBmDistance to be bridged:

    1)max. 45 m

    Transmission rate Communication Protocol

    BA-no. -910(one channel)

    300 to 38,400 baud (adjustable) IEC 60870-5-103

    BA-no. -922

    (two channels)

    300 to 64,000 baud

    (adjustable for COMM1)300 to 57,600 baud(adjustable for COMM2)

    Can be set by user for one

    channel

    Glass Fiber Connection G 50/125Optical wavelength: typically 820 nmOptical output: min. -19.8 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBmDistance to be bridged:

    1)max. 400 m

    Glass Fiber Connection G 62.5/125

    Optical wavelength: typically 820 nmOptical output: min. -16 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBmDistance to be bridged:1) max. 1,400 m

    Glass Fiber Connection G 50/125 or G 62.5/125

    Transmission rate Communication Protocol

    BA-no. -910(one channel)

    300 to 38,400 baud (adjustable) IEC 60870-5-103

    BA-no. -924(two channels) 300 to 64,000 baud(adjustable for COMM1)300 to 57,600 baud

    (adjustable for COMM2)

    Can be set by user for onechannel

    1)Distance to be bridged given for identical optical outputs and inputs at both ends, a

    system reserve of 3 dB, and typical fiber attenuation.

  • 7/15/2019 Vol1 P632-635

    32/605

    2 Technical Data(continued)

    2-10 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    IRIG-B interfaceB122 formatAmplitude modulated signalCarrier frequency: 1 kHzBCD-coded variation data (daily)

    Data transmission usingthe IEC 61850 protocol

    Order ext. No. -936:Interface to connect a 100 Mbit/s Ethernet, glass fiber-SC and RJ45 wireorOrder ext. No. -937:Interface to connect a 100 Mbit/s Ethernet, glass fiber-SC and RJ45 wire

    For Wire Leadsper RJ45, 1.5 kV isolationDistance to be bridged: Max. 100 m

    Glass Fiber Connection G 50/125Optical wavelength: typically 1300 nmOptical output: min. -23.5 dBmOptical sensitivity: min. -31 dBmOptical input: max. -14 dBm

    Glass Fiber Connection G 62.5/125

    Optical wavelength: typically 1300 nmOptical output: min. -20 dBmOptical sensitivity: min. -31 dBmOptical input: max. -14 dBm

    The second communication interface (RS 485 connection, IEC 60870-5-103 protocol) isalso available.

  • 7/15/2019 Vol1 P632-635

    33/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-11

    2.7 Information Output

    Counters, measured data, signals and LED indications: see Chapter 8.

    2.8 Settings

    Typical characteristic dataMain functionMinimum output pulse duration for a trip command: 0.1 to 10 s (adjustable)

    Differential ProtectionOperate time at Id = 10 Idiff> with inrush restraint disabled, or at Id > Idiff>>>:

    at least 13 ms, typically 15 ms.Operate time at Id = 2.5 Idiff> with inrush restraint disabled:at least 19 ms, typically 21 ms.Operate time at Id = 2.5 Idiff> with inrush restraint enabled:

    at least 30 ms, typically 33 ms.

    Definite-time and inverse-time overcurrent protectionOperate time including output relay (measured value from 0 to 2-fold operate value):

    40 ms, approx. 30 msReset time (measured value drops from 2-fold operate value to 0):

    40 ms, approx. 30 msStarting resetting ratio: Approx. 0.95

    Time-Voltage ProtectionOperate time including output relay (measured value from nominal value to 1.2-foldoperate value or measured value from nominal value to 0.8-fold operate value):

    40 ms, approx. 30 msReset time (measured value from 1.2-fold operate value to nominal valueor measured value from 0.8-fold operate value to nominal value):

    45 ms, approx. 30 msResetting ratio for V: 1 to 10 % (adjustable)

    Overfluxing protectionStarting and measurement resetting ratio (hysteresis): 0.95

  • 7/15/2019 Vol1 P632-635

    34/605

    2 Technical Data(continued)

    2-12 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    2.9 Deviations

    2.9.1 Deviations of the Operate Values

    DefinitionsReference ConditionsSinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient

    temperature 20C (68F), and nominal auxiliary voltage VA,nom

    DeviationDeviation relative to the setting under reference conditions.

    Differential ProtectionMeasuring systemDeviation for Idiff: 0.2 Iref: 5 %

    Harmonic blocking:10 %

    Inrush Stabilization (Harmonic Restraint)Deviation: 10 %

    Ground differentialprotection (Br: Restricted earthfault protection)

    Measuring systemDeviation for Idiff: 0.2 Iref: 5 %

    Definite-time and inverse-time overcurrent protection

    Deviation: 5 %

    Thermal OverloadProtection

    Deviation: 5 %

    Frequency protectionOperate Valuesfnom = 50 Hz: Deviation: 30 mHzfnom = 60 Hz: Deviation: 40 mHz

    df/dt protectionOperate Valuesfnom = 50 Hz: Deviation: 0.1 Hz/sfnom = 60 Hz: Deviation: 0.1 Hz/s

    Time-Voltage ProtectionDeviation: 3 %

    Overfluxing protectionDeviation: : 3 %

    Direct current inputDeviation: 1 %

    Resistance thermometerDeviation: 2 or 1 %

  • 7/15/2019 Vol1 P632-635

    35/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-13

    Analog Measured DataOutput

    Deviation: 1 %Output residual ripple with max. load: 1 %

    2.9.2 Deviations of the Timer Stages

    DefinitionsReference ConditionsSinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient

    temperature 20 C (68F), and nominal auxiliary voltage VA,nom.

    DeviationDeviation relative to the setting under reference conditions.

    Definite-time stagesDeviation: 1 % or + 20 ms to 40 ms

    Inverse-time stages

    Deviation when I 2 Iref: 5 % + 10 to 25 ms

    or for IEC 'Extremely Inverse', thermal overload and V/f characteristics: 7.5 % + 10 to 20 ms

    Limit Value MonitoringLimit Value Monitoring is not designed to be a high-speed protection function; it is used

    for reporting purposes. This function is calculated approximately one time per second.Therefore, it is not accurate enough to provide meaningful data for the time deviation.

  • 7/15/2019 Vol1 P632-635

    36/605

    2 Technical Data(continued)

    2-14 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    2.9.3 Deviations of Measured Data Acquis ition

    DefinitionsReference ConditionsSinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient

    temperature 20 C (68F), and nominal auxiliary voltage VA,nom.

    DeviationDeviation relative to the setting under reference conditions.

    Measured Operating DataMeasuring Input CurrentsDeviation: 1 %

    Measuring Input VoltageDeviation: 0.5 %

    Internally formed restraining and differential currentsDeviation: 2 %

    FrequencyDeviation: 10 mHz

    Direct Current of Measured Data Input and OutputDeviation: 1 %

    TemperatureDeviation: 2 C

    Fault dataPhase and Star point currentsDeviation: 3 %

    Restraining and Differential CurrentsDeviation: 5 %

    Internal clockWith free running internal clock:

    Deviation: < 1 min/month

    With external synchronization (with a synchronization interval 1 min):Deviation: < 10 ms

    With synchronization via IRIG-B interface: 1 ms

  • 7/15/2019 Vol1 P632-635

    37/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-15

    2.10 Recording Functions

    Organization of the Recording Memories:

    Operating data memoryScope for signals: All operation-relevant signals from a total of 1024 different

    logic state signals

    Depth: The 100 most recent signals

    Monitoring signal memoryScope for signals: All signals relevant for self-monitoring from a total of

    1024 different logic state signals

    Depth: Up to 30 signals

    Overload memoryNumber: The 8 most recent overload events

    Scope for signals: All signals relevant for an overload event from a total of1024 different logic state signals

    Depth: 200 entries per overload event

    Fault memoryNumber: The 8 most recent fault events

    Scope for signals: Signals:All fault-relevant signals from a total of 1024 differentlogic state signals

    Depth for fault values:Sampled values for all measured currents and voltages

    Depth for signals Signals:200 entries per fault event

    Depth for fault values:

    Max. number of periods per fault set by the user; 820 periodsin total for all faults, that is 16.4 s (for fnom = 50 Hz) or 13.7 s

    (for fnom = 60 Hz)

  • 7/15/2019 Vol1 P632-635

    38/605

    2 Technical Data(continued)

    2-16 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Resolution of the Recorded Data

    SignalsTime resolution: 1 ms

    Fault valuesTime resolution: 20 sampled values per period

    Phase and Star pointcurrents

    Dynamic range: 33 Inom

    Amplitude resolution at Inom = 1 A: 2 mA r.m.s.

    at Inom = 5 A: 10.1 mA r.m.s.

    VoltageDynamic range: 150 V ACAmplitude resolution: 9.2 mVrms

    2.11 Power Supply

    Power supplyNominal auxiliary voltage VA,nom:

    48 to 250 V DC and 100 to 230 V AC or 24 V DC(ordering option)

    Operating range for direct voltage:0.8 to 1.1 VA,nom with a residual ripple of up to 12 % VA,nom

    Operating range for alternating voltage: 0.9 to 1.1 VA,nom

    Nominal burden where VA = 220 V DC and with maximum module configuration:

    For case: 40TE 84TE

    Relays de-energized,approx.:

    13 W 13 W

    Relays energizedapprox.:

    29 W 37 W

    Start-up peak current: < 3 A for duration of 0.25 msPermitted supply interruption: 50 ms for interruption of VA 220 V DC

  • 7/15/2019 Vol1 P632-635

    39/605

    2 Technical Data(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 2-17

    2.12 Current Transformer Specifications

    The following equation is used to calculate the specifications of a current transformer forthe offset maximum primary current:

    ( ) ( ) ' max1,iopnominomsat IkRRInRRV ++=

    with:Vsat: saturation voltage (IEC knee point)

    I'1,max: non-offset maximum primary current, converted to the secondary side

    Inom: rated secondary current

    n: rated overcurrent factor

    k: over-dimensioning factorRnom: rated burden

    Rop actual connected operating burden

    Ri internal burden

    The specifications of a current transformer can then be calculated for the minimumrequired saturation voltage Vsat as follows:

    ( ) ' max1,iopsat IkRRV +

    As an alternative, the specifications of a current transformer can also be calculated forthe minimum required rated overcurrent factor n by specifying a rated power P

    nom

    as

    follows:

    ( )( )

    ( )( ) nom

    'max1,

    inom

    iop

    nom

    'max1,

    inom

    iop

    I

    Ik

    PP

    PP

    I

    Ik

    RR

    RRn

    +

    +=

    +

    +

    With

    2nomii

    2nomopop

    2nomnomnom

    IRP

    IRP

    IRP

    =

    =

    =

    Theoretically, the specifications of the current transformer could be calculated for lack ofsaturation by inserting instead of the required over-dimensioning factor k its maximumvalue:

    k Tmax +1 1

    with: : system angular frequencyT1: system time constant

  • 7/15/2019 Vol1 P632-635

    40/605

    2 Technical Data(continued)

    2-18 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    However, this is not necessary. Instead, it is sufficient to calculate the over-dimensioning factor k such that the normal behavior of the analyzed protective functionis guaranteed under the given conditions.

    The transformer differential protection device is equipped with a saturation discriminator.This function will generate a stabilizing blocking signal if a differential current occurs as aconsequence of transformer saturation with an external fault (in contrast to an internalfault). For the passing maximum fault current in the case of an external fault,overdimensioning is, therefore, obviated.

    For the maximum fault current with an internal fault, static saturation up to a maximumsaturation factor fS of 4 is permissible. This corresponds to an overdimensioning

    factor k of 0.25.

    The implementation of these requirements is comparatively unproblematic astransformer differential protection would require overdimensioning in accordance with thetotal fault clearing time, which includes the total circuit-breaker open time for an externalfault.

    Current transformers should observe the error limit values for class 5P.

  • 7/15/2019 Vol1 P632-635

    41/605

    3 Operation

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-1

    3 Operation

    3.1 Modular Struc ture

    The P63x, a numeric device, is part of the MiCOM P 30 family of devices. The devicetypes included in this family are built from identical uniform hardware modules.Figure 3-1 shows the basic hardware structure of the P63x.

    3-1 Basic hardware structure

  • 7/15/2019 Vol1 P632-635

    42/605

    3 Operation(continued)

    3-2 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    The external analog and binary quantities electrically isolated are converted to theinternal processing levels by the peripheral modules T, Y, and X. Commands andsignals internally generated by the device are connected to the external plant viacontacts through the binary I/O modules X. The external auxiliary voltage is applied tothe power supply module V, which supplies the auxiliary voltages that are requiredinternally.

    Analog data is transferred from the transformer module T via the analog bus module B tothe processor module P. The processor module contains all the elements necessary forthe conversion of measured analog variables, including multiplexers and analog/digitalconverters. The analog data conditioned by the analog I/O module Y is transferred tothe processor module P via the digital bus module. Binary signals are fed to theprocessor module by the binary I/O modules X via the digital bus module.

    The processor handles the processing of digitized analog variables and of binary signals,generates the protective trip and signals, and transfers them to the binary I/O modules Xvia the digital bus module. The processor module also handles overall devicecommunication. As an option, communication module A can be mounted on theprocessor module to provide serial communication with substation control systems.

    The control and display elements of the integrated local control panel and the integratedPC interface are housed on control module L.

  • 7/15/2019 Vol1 P632-635

    43/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-3

    3.2 Operator-Machine Communication

    The following interfaces are available for the exchange of information between the userand the device:

    Integrated local control panel (LOC)

    PC interface

    Communication interface

    All settings and signals as well as all measurements and control functions are arrangedwithin the branches of the menu tree following a scheme that is uniform throughout thedevice family. The main branches are:

    Parameters branchAll settings are contained in this branch. This branch carries all settings, including thedevice identification data, the configuration parameters for adapting the device interfacesto the system, and the function parameters for adapting the device functions to theprocess. All values in this group are stored in non-volatile memory, which means thatthe values will be preserved even if the power supply fails.

    Operation branchThis branch includes all information relevant for operation such as measured operatingdata and binary signal states. This information is updated periodically and consequentlyis not stored. In addition, various controls are grouped here, for example those forresetting counters, memories and displays.

    Events branchThe third branch is reserved for the recording of events. All information in this group istherefore stored. In particular, the start/end signals during a fault, the measured faultdata, and the sampled fault waveforms are stored here and can be read out whenrequired.

    Settings and signals are displayed either in plain text or as addresses, in accordancewith the users choice. Chapters 7, 8 and 10 describe the settings, signals andmeasured values available with the P63x. The possible setting values can be found inthe P63x's data model file associated with the PC operating program (MiCOM S1).

    The configuration of the local control panel also permits the installation of MeasuredValue 'Panels on the LCD display. Different Panels are automatically displayed forspecific system operating conditions. Priority increases from normal operation tooperation under overload conditions and finally to operation following a short circuit inthe system. Thus the P63x provides the measured data relevant for the prevailingconditions.

  • 7/15/2019 Vol1 P632-635

    44/605

    3 Operation(continued)

    3-4 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3.3 Configuration of the Measured Value Panels (Function Group LOC)

    The P63x offers Measured Value Panels, which display the measured values relevant ata given time.

    During normal power system operation, the Operation Panel is displayed. As an eventoccurs, the display switches to the appropriate Event Panel - provided that measuredvalues have been selected for the Event Panels. In the event of overload event, thedisplay will automatically switch to the Operation Panel at the end of the event. In theevent of a fault, the Fault Panel remains active until the LED indicators or the faultmemories are reset.

    Operation Panel

    The Operation Panel is displayed after the set return time has elapsed, provided that atleast one measured value has been configured.

    The user can select which of the measured operating values will be displayed on theOperation Panel by means of an m out of n parameter. If more measured values areselected for display than the LC display can accommodate, then the display will switch tothe next set of values at intervals defined by the setting at LOC: Hold-Time forPanels or when the appropriate key on the local control panel is pressed.

    3-2 Operation Panel

  • 7/15/2019 Vol1 P632-635

    45/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-5

    Fault panelThe Fault Panel is displayed in place of another data panel when there is a fault,provided that at least one measured value has been configured. The Fault Panelremains on display until the LED indicators or the fault memories are cleared.

    The user can select the measured fault values that will be displayed on the Fault Panelby setting an 'm out of n' parameter. If more measured values are selected for displaythan the LC display can accommodate, then the display will switch to the next set ofvalues at intervals defined by the setting at LO C: Hol d- Ti me for Pa ne ls or whenthe appropriate key on the local control panel is pressed.

    3-3 Fault panel

  • 7/15/2019 Vol1 P632-635

    46/605

    3 Operation(continued)

    3-6 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Overload PanelThe Overload Panel is automatically displayed in place of another data panel when thereis an overload, provided that at least one measured value has been configured.The Overload Panel remains on display until the overload ends, unless a fault occurs.In this case the display switches to the Fault Panel.

    The user can select the measured values that will be displayed on the Overload Panelby setting a 'm out of n' parameter. If more measured values are selected for displaythan the LC display can accommodate, then the display will switch to the next set ofvalues at intervals defined by the setting at LO C: Hol d- Tim e fo r Pan el s or whenthe appropriate key on the local control panel is pressed.

    3-4 Overload Panel

  • 7/15/2019 Vol1 P632-635

    47/60504-610 3-7

  • 7/15/2019 Vol1 P632-635

    48/605

    3 Operation(continued)

    3-8 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3-5 PC interface settings

  • 7/15/2019 Vol1 P632-635

    49/605

    3 Operation(continued)

    /404-610 3-9

  • 7/15/2019 Vol1 P632-635

    50/605

    3 Operation(continued)

    3-10 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3-6 Communication interface 1, selecting the interface protocol

  • 7/15/2019 Vol1 P632-635

    51/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-11

    3-7 Communication interface 1, settings for the IEC 60870-5-103 interface protocol

  • 7/15/2019 Vol1 P632-635

    52/605

    3 Operation(continued)

    3-12 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3-8 Communication interface 1, settings for the IEC 870-5-101 interface protocol

  • 7/15/2019 Vol1 P632-635

    53/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-13

    3-9 Communication interface 1, settings for the ILS_C interface protocol

  • 7/15/2019 Vol1 P632-635

    54/605

    3 Operation(continued)

    3-14 04-610

    3-10 Communication interface 1, settings for the MODBUS protocol

  • 7/15/2019 Vol1 P632-635

    55/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-15

    3-11 Communication interface 1, settings for the DNP 3.0 protocol

  • 7/15/2019 Vol1 P632-635

    56/605

    3 Operation(continued)

    3-16 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3-12 Communication interface 1, settings for the COURIER protocol

  • 7/15/2019 Vol1 P632-635

    57/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-17

    Checking spontaneoussignals

    For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it ispossible to select a signal for test purposes. The transmission of this signal to the controlstation as sig. start or sig. end can then be triggered via setting parameters.

    3-13 Checking spontaneous signals

  • 7/15/2019 Vol1 P632-635

    58/605

    3 Operation(continued)

    3-18 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3.4.3 Communication Interface 2 (Function Group COMM2)

    Communication interface 2 supports the IEC 60870-5-103 interface protocol.

    In order for data transfer to function properly, several settings must be made in the P63x.

  • 7/15/2019 Vol1 P632-635

    59/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-19

    3-14 Settings for communication interface 2

  • 7/15/2019 Vol1 P632-635

    60/605

    3 Operation(continued)

    3-20 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Checking spontaneoussignals

    It is possible to select a signal for test purposes. The transmission of this signal to thecontrol station as sig. start or sig. end can then be triggered via setting parameters.

    Spontan.signal start

    Spontan.signal end

    3-15 Checking spontaneous signals

  • 7/15/2019 Vol1 P632-635

    61/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-21

    3.4.4 UCA2 Communication Interface (Funct ion Group UCA2)

    This function group is available only with the P63x -604/-605/-606 device.

    (As of device version P63x 610, the IEC 61850 communication interface is available:it uses function groups IEC, GOOSE and GSSE. A description is provided in thefollowing section).

    The communication protocol Utility Communication Architecture 2.0 is implemented withthe UCA2 function group and the Ethernet module (in the 10 MHz and 100 MHzvariants).

    Function group UCA2 is only available as an alternative to function group COMM1

    (hardware ordering option!). Pending the implementation of the IEC 61850 protocol,the use of UCA2 is reserved for specific projects.

    The UCA2 addresses for setting, information and control functions are described inchapters 7 and 8.

    (See also the detailed description of the UCA2 protocol implementation:P54x_EN_UC_B42.pdf).

  • 7/15/2019 Vol1 P632-635

    62/605

    3 Operation(continued)

    3-22 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3.4.5 IEC 61850 Communication Interface(Function groups IEC, GOOSE and GSSE)

    These function groups are available only with the P63x -610 device.

    The IEC 61850 communication protocol is implemented by these function groups and theEthernet module.

    Note:

    Function group IEC is only available as an alternative to function group COMM1(hardware ordering option!).

    3.4.5.1 IEC 61850 Communication Interface (Function Group IEC)

    IEC 61850IEC 61850 was created jointly by users and manufacturers as an international standard.The main target of IEC 61850 is interoperability of devices. This includes the capabilityof two or more intelligent electronic devices (IED), manufactured by the same companyor different companies, to exchange data for combined operation.

    Now this new communication standard IEC 61850 has created an open and commonbasis for communication from the process control level down to the network control level,for the exchange of signals, data, measured values and commands.

    For a standardized description of all information and services available in a field device adata model, which lists all visible functions, is created. Such a data model, specificallycreated for each device, is used as a basis for an exchange of data between the devices

    and all process control installations interested in such information. In order to facilitateengineering at the process control level a standardized description file of the device,based on XML, is created with the help of the data model. This file can be imported andprocessed further by the relevant configuration program used by the process controldevice. This makes possible an automated creation of process variables, substationsand signal images.

    The following documentation with the description of the IEC 61850 data model, used withthe P63x, is available:

    IDC file based on XML in the SCL (Substation Configuration Description Language)with a description of data, properties and services, available from the device, that areto be imported into the system configurator.

    PICS_MICS_ADL file with the following contents:

    PICS (Protocol Implementation Conformance Statement) with an overview ofavailable services.

    MICS (Model Implementation Conformance Statement) with an overview ofavailable object types.

    ADL (Address Assignment List) with an overview of the assignment of parameteraddresses (signals, measuring values, commands, etc.) used by the device withthe device data model as per IEC 61850.

  • 7/15/2019 Vol1 P632-635

    63/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-23

    Ethernet ModuleThe optional Ethernet module provides an RJ45 connection and a fiber optic interfacewhere an Ethernet network can be connected. The selection which of the two interfacesis to be used to connect to the Ethernet network is made by setting the parameterI E C : E t h e rn e t m e d i a . The optical interface of the Ethernet module is currentlyavailable with an SC connector (100 Mbit/s and 1300 nm). A variant with an STconnector is being developed. The RJ45 connector supports 10 Mbit/s and 100 Mbit/s.

    The optional Ethernet module additionally provides an RS485 interface for remoteaccess with the operating program MiCOM S1 (function group COMM2).

    Notes: The P63xmay only be equipped with theoptional Ethernet module as analternative to the standard optional communication module. Therefore theEthernet based communication protocol IEC 61850 is only available as an

    alternative to function group COMM1.

    The Ethernet module can only be applied in conjunction with the processormodule P (included in current hardware version) with the item number 9650135 or other processor modules available in the near future. When upgradingolder P63x hardware versions with an Ethernet module, which is technicallypossible, it must be kept in mind that such units are usually equipped with theprocessor module P, item number 0337 875. But this processor module Pdoes not support the Ethernet module and therefore the communicationsprotocol per IEC 61850 is also not supported. If such an upgrade is carriedout the processor module P must be exchanged. The processor module itemnumber can be checked by reading the device identification setting atD V I C E : M o d u l e v a r . s l o t 1 .

    Activating and EnablingThe IEC function group can be activated by setting the parameter I E C : Fu n c t i o ng r o up I EC . This parameter is only visible if the optional Ethernet communicationmodule is fitted to the device. After activation of IEC, all data points associated with thisfunction group (setting parameters, binary state signals etc.) become visible.The function can then be enabled or disabled by settingI E C : G e n e ra l e n a b l e U S E R .

    The parameter settings for function groups IEC, GOOSE and GSSE in the device are notautomatically activated. Activation occurs either when the command I E C : E n ab l ec o n f i gu r a t i o n is executed or automatically when the device is switched online atM A I N : D e v i c e o n - l i n e .

    Client Log-onCommunication in Ethernet no longer occurs in a restrictive master slave system, as iscommon with other protocols. Instead server or client functionalities, as defined in the'Abstract Communication Service Interface' (ACSI, IEC 61870-7-2), are assigned to thedevices. A 'server' is always that device which provides information to other devices.A client may log-on to this server so as to receive information, for instance 'reports'.In a network a server can supply any number of clients with spontaneous or cyclicinformation.

    In its function as server the P63x can supply up to 16 clients with information.

  • 7/15/2019 Vol1 P632-635

    64/605

    3 Operation(continued)

    3-24 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Clock SynchronizationWith IEC 61850 clock synchronization occurs via the SNTP protocol, defined as standardfor Ethernet. Here the P63x functions as a SNTP client.

    For clock synchronization one can select between the operating modes Broadcast fromSNTP Server orRequest from Server. With the first operating mode synchronizationoccurs by a broadcast message sent from the SNTP server to all devices in the network,and in the second operating mode the P63x requests the device specific time signalduring a settable cycle.

    Fault TransmissionTransmission of fault files is supported per "File Transfer".

    Transmission of "Goose

    Messages" The so-called "Goose Message" is a particular form of data transmission. Whereasnormal server-client-services are transmitted at the MMS and TCP/IP level, the "GooseMessage" is transmitted directly at the Ethernet level with a high transmission priority.Furthermore these "Goose Messages" can be received by all participants in therespective sub-network, independent of their server or client function. In IEC 61850"Goose Messages" are applied for the accelerated transmission of information betweentwo or more devices. Application fields are, for example, a reverse interlocking, a transfertrip or a decentralized substation interlock. In future the "Goose Message" will thereforereplace a wired or serial protective interface.

    According to IEC 61850 there are two types of "Goose Messages", GSSE andIEC-GOOSE. The GSSE is used to transmit binary information with a simpleconfiguration by 'bit pairs', and it is compatible with UCA2. However IEC-GOOSE

    enables transmission of all data formats available in the data model, such as binaryinformation, integer values or even analog measured values. But this will require moreextensive configuration with the help of the data model from the field unit situated on theopposite side. With IEC-GOOSE the P63x at this time supports sending and receiving ofbinary information.

    Communication with theOperating ProgramMiCOM S1 via the EthernetInterface

    Direct access by the operating program MiCOM S1 via the Ethernet interface on thedevice may occur through the "tunneling principle". Transmission is carried out by anEthernet Standard Protocol, but this is only supported by the associated operating

    program MiCOM S1 (specific manufacturer solution). Such transmission isaccomplished over the same hardware for the network, which is used for server-clientcommunication and "Goose Messages".Available are all the familiar functions offered by the operating program MiCOM S1 suchas reading/writing of setting parameters or retrieving stored data.

    The various settings, measured values and signals for function group IEC are describedin chapters 7 and 8.

  • 7/15/2019 Vol1 P632-635

    65/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-25

    3.4.5.2 Generic Object Oriented Substation Event (Function Group GOOSE)

    For high-speed exchange of information between individual IEDs (intelligent electronicdevices) in a local network, the P63x provides function group GOOSE (IEC-GOOSE) asdefined in the IEC 61850 standard. GOOSE features high-speed and securetransmission for trip commands, blocking, enabling, contact position signals and othersignals.

    "Goose Messages" are only transmitted by switches but not by routers. "GooseMessages" therefore remain in the local network to which the device is logged-on.

    Activating and EnablingFunction group GOOSE can be activated by setting the parameter

    GO OS E : F un c t i on g r ou p GOOS E . This parameter is only visible if the optionalEthernet communication module is fitted to the device. After activation of GOOSE, alldata points associated to this function group (setting parameters, binary state signalsetc.) become visible.The function can then be enabled or disabled by settingG O O S E : G e n e ra l e n a b l e U S E R .

    The parameter settings for function groups IEC, GOOSE and GSSE in the device are notautomatically activated. Activation occurs either when the commandI E C : E n ab l e c o n f i gu r a t i on is executed or automatically when the device isswitched online with M A I N : D e v i c e o n - l i ne . In addition function group IEC mustbe configured and enabled.

    Sending GOOSE

    With GOOSE the P63x can transmit up to 32 logic binary state signals. Selection ofbinary state signals is made by settingGO OS E : Ou t p u t n f c t . a s s i g . (n = 1 to 32). The assignment of data objectindexes to logic state signals is made in the range from 1 to 32 according to theassignment to GOOSE outputs.

    GOOSE is automatically sent with each new state change of a configured binary statesignal or an external device. There are numerous send repetitions in fixed ascendingtime periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, 2000 ms). If after2 seconds there is no further state change apparent, GOOSE is then sent cyclically at2-second intervals.

  • 7/15/2019 Vol1 P632-635

    66/605

    3 Operation(continued)

    3-26 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    In order to have unambiguous identification of GOOSE sent, characteristics such as theGoose ID number, MAC address, application ID and VLAN identifier must be enteredthrough parameter settings. Further characteristics are the 'Dataset ConfigurationRevision' with the fixed value "100" as well as the 'Dataset Reference', which is made upof the IED name (setting in function group IEC) and the fixed string"System/LLNO$GooseST".

    GOOSE-DataSet: LLN0$GooseST

    Goose ID: "Local IED"

    Server nameSYSTEM/GosGGI01/Out1/stVal

    Multicast MAC address: 01-0C-CD-01-00-00

    VLAN Identifier: 0

    GOOSE: Output 1 fct.assig.

    GOOSE: Output 2 fct.assig.

    GOOSE: Output 32 fct.assig.

    64Z6090A_EN

    Server nameSYSTEM/GosGGI01/Out2/stVal

    Server nameSYSTEM/GosGGI01/Out32/stVal

    Identification:

    Data range:

    Appl ication ID: 12288

    DataSet Cfg. Revision: 100

    DataSet Ref. : " Local IEDSystem/LLNO$GooseST"

    VLAN Priority: 4

    3-16 Basic structure of sent GOOSE

  • 7/15/2019 Vol1 P632-635

    67/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-27

    With GOOSE up to 16 logic binary state signals can be received. Configuration of thelogic state signals received (GO OS E : I n p u t n f c t . as s i g . , where n = 1 to 16) ismade on the basis of the selection table of the binary inputs (opto coupler inputs).

    For each state signal to be received from an external device the "Goose Message" mustbe selected that includes the information wanted by setting the Goose ID, the ApplicationID and the 'Dataset Reference'. With the further setting of the data object index and thedata attribute index through parameters, the required information from the chosenGOOSE will be selected. The device will not evaluate the identification features VLANidentifier and Dataset Configuration Revision that are also included in the GOOSEreceived.

    Each GOOSE includes time information on the duration of validity of its information.

    This corresponds to the double time period to the next GOOSE repetition. If the durationof validity has elapsed without having received this GOOSE again (i.e. because of acommunications fault), the received signals will automatically be set to their respectivedefault values GOO SE : Inp ut n def au l t or GOO SE : Ext .D ev . n def au l t(n = 1 to 16).

    The various settings, measured values and signals for function group GOOSE aredescribed in chapters 7 and 8.

    3.4.5.3 Generic Substation State Event (Function Group GSSE)

    For high-speed exchange of information between individual IEDs (intelligent electronicdevices) in a local network, the P63x provides, as an additional functionality, the function

    group GSSE (UCA2.0-GOOSE) as defined in the IEC 61850 standard. GSSE featureshigh-speed and secure transmission of logic binary state signals such as trip commands,blocking, enabling and other signals.

    Activating and EnablingFunction Group GSSE can be activated by setting the parameter GS S E : F un c t i o ng r o up G SS E . This parameter is only visible if the optional Ethernet communicationmodule is fitted to the device. After activation of GSSE, all data points associated to thisfunction group (setting parameters, binary state signals etc.) become visible.The function can then be enabled or disabled by settingG S S E : G e n e ra l e n a b l e U S E R .

    The parameter settings for function groups IEC, GOOSE and GSSE in the device are notautomatically activated. Activation occurs either when the command I E C : E n ab l ec o n f i gu r a t i on is executed or automatically when the device is switched online withMA I N : D ev i c e o n - l i ne . In addition the function group IEC must be configured andenabled.

  • 7/15/2019 Vol1 P632-635

    68/605

    3 Operation(continued)

    3-28 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    Sending GSSEWith GSSE up to 32 logic binary state signals can be sent. Selection of binary statesignals is made by settingGS S E : O u t pu t n f c t . a s s i g . (n = 1 to 32). Each state signal selected is to beassigned to a bit pair in GSSE (GS S E : O u t pu t n b i t pa i r (n = 1 to 32)), whichwill transmit this state signal.

    GSSE is automatically sent with each state change of a selected state signal. There willbe multiple send repetitions at ascending time periods. The first send repetition occursat the given cycle time set with the parameter G S S E : M i n . c y c l e . The cycles forthe following send repetitions result from a conditional equation with the increment setwith the parameter GS S E : I n c r em en t . Should no further state changes occur up tothe time when the maximum cycle time has elapsed (GS S E : Ma x . c y c l e ) , thenGSSE will be sent cyclically at intervals as set for the max. cycle time.

    In order to have unambiguous identification of a GSSE sent, the IED name is used whichwas set in function group IEC.

    Receiving GSSEWith GSSE up to 32 logic binary state signals can be received. Configuration of the logicbinary state signals received (GS S E : I n pu t n f c t . as s i g . , where n = 1 to 32) ismade on the basis of the selection table of the binary inputs (opto coupler inputs).

    For each state signal to be received, the GSSE message, which will include the requiredinformation, must be selected by setting the IED name (GS SE : I E D n am e) .Selection of information wanted from the selected GSSE will occur by setting the bit pair(GSSE: b i t pa i r ) .

    Each GSSE includes time information on the duration of validity of its information.This corresponds to the double time period to the next GSSE repetition. If the durationof validity has elapsed without having received this GSSE again (i.e. because of acommunications fault), the signals received will automatically be set to their respectivedefault value ( GS S E : I n pu t n d ef au l t (n = 1 to 32)).

    The various settings, measured values and signals for function group GSSE aredescribed in chapters 7 and 8.

  • 7/15/2019 Vol1 P632-635

    69/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-29

    3.5 IRIG-B Clock Synchronization (Funct ion Group IRIGB)

    If, for example, a GPS receiver with IRIG-B connection is available, the internal clock ofthe P63x can be synchronized to run on GPS time using the optional IRIG-B interface.It should be noted that the IRIG-B signal holds information on the day only (day of thecurrent year). Using this information and the year set at the P63x, the P63x calculatesthe current date (DD.MM.YY).

    Disabling or enabling theIRIG-B interface

    The IRIG-B interface can be disabled or enabled via a setting parameter.

    Synchronization readiness

    If the IRIG-B interface is enabled and receiving a signal, the P63x checks the receivedsignal for plausibility. Implausible signals are rejected by the P63x. If the P63x does notreceive a correct signal in the long run, synchronization will not be ready any longer.

    3-17 IRIG-B interface

  • 7/15/2019 Vol1 P632-635

    70/605

    3 Operation(continued)

    3-30 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-

    3.6 Configuration and Operating Mode of the Binary Inputs (Funct ion Group INP)

    The P63x has opto coupler inputs for processing binary signals from the substation.The functions that will be activated in the P63x by triggering these binary signal inputsare defined by the configuration of the binary signal inputs. The typical response time is< 10 ms, although for reliability it is recommended that the initiating signal is maintainedfor at least 30 ms.

    Configuring the binaryinputs

    One function can be assigned to each binary signal input by configuration. The samefunction can be assigned to several signal inputs. Thus one function can be activatedfrom several control points having different signal voltages.

    In this manual, we assume that the required functions (marked 'EXT' in the addressdescription) have been assigned to binary signal inputs by configuration.

    It should be noted that time-critical applications such as time synchronization commandsshould not be mapped to the binary signal inputs of the analog I/O module as these havean increased reaction time due to internal processing.

    Operating mode of thebinary inputs

    The operating mode for each binary signal input can be defined. The user can specifywhether the presence (active 'high' mode) or the absence (active 'low' mode) of avoltage should be interpreted as the logic '1' signal. The display of the state of a binary

    signal input 'low' or 'high' is independent of the setting for the operating mode of thesignal input.

    3-18 Configuration and operating mode of the binary signal inputs

  • 7/15/2019 Vol1 P632-635

    71/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-31

    3.7 Measured Data Input (Funct ion Group MEASI)

    The P63x has a measured data input function involving two inputs. Direct current is fedto the P63x through one of the inputs. The other input is designed to connect aresistance thermometer.

    The input current IDC is displayed as a measured operating value. The current that isconditioned for monitoring purposes (IDC,lin) is also displayed as a measured operatingvalue. In addition, it is monitored by the Limit Value Monitoring function to determinewhether it exceeds or falls below set thresholds (see "Limit Value Monitoring").

    The measured temperature is also displayed as a measured operating value andmonitored by the limit value monitoring function to determine whether it exceeds or falls

    below set thresholds (see "Limit Value Monitoring").

    Disabling or enabling themeasured data inputfunction

    The measured data input can be disabled or enabled via a setting parameter.

    3-19 Disabling or enabling the measured data input function

  • 7/15/2019 Vol1 P632-635

    72/605

    3 Operation(continued)

    3-32 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3.7.1 Direct Current Input

    External measuring transducers normally supply an output current of 0 to 20 mA that isdirectly proportional to the physical quantity being measured the temperature, forexample.If the output current of the measuring transducer is directly proportional to the measuredquantity only in certain ranges, linearization can be arranged, provided that themeasured data input is set accordingly. Furthermore, for certain applications it may benecessary to limit the range being monitored or to monitor certain parts of the range witha higher or lower sensitivity. By setting the value pair MEASI: IDC x andME AS I: IDC, l in x, the user specifies which input current IDC will correspond to thecurrent that is monitored by the Limit Value Monitoring function, i.e., IDC,lin. The resultingpoints, called "interpolation points", are connected by straight lines in an IDC-IDC,lin

    diagram. In order to implement a simple characteristic, it is sufficient to specify twointerpolation points, which are also used as limiting values (see figure 3-20). Up to20 interpolation points are available to implement a complex characteristic.When setting the characteristic the user must remember that only a monotonicallyincreasing curve is allowed (no peak or vee-shapes). If an invalid setting is entered, theSF MO N: In va li d s ca li ng ID C signal will be generated.

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    1.1

    1.2

    0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC/ IDC,nom

    IDClin / IDC,nom

    IDC1 IDC20

    IDClin1

    IDClin20

    D5Z52KDA19Z5266A_EN

    3-20 Example of the conversion of 4 to 10 mA input current to 0 to 20 mA monitored current, IDC,lin

  • 7/15/2019 Vol1 P632-635

    73/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-33

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2

    IDC / IDC,nom

    IDClin / IDC,nom

    D5Z52KEB

    IDC1 IDC2 IDC3 IDC4 IDC20

    IDC,lin1

    IDC,lin2

    IDC,lin3

    IDC,lin4

    IDC,lin20

    Interpolation points

    Enable IDC p.u.D5Z52KEB_EN

    3-21 Example of a characteristic with five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a broken

    line)

    Zero suppressionZero suppression is defined by setting M E A S I : E n ab l e I D C p . u . If the directcurrent does not exceed the set threshold, the per-unit input current IDC p.u. and the

    current IDC,lin will be displayed as having a value of 0 .

    Open-circuit and overload

    monitoring The device is equipped with an open-circuit monitoring function. If current IDC falls belowthe set threshold, ME AS I: ID C< op en ci rc ui t, the M EA SI : Op en ci rc .20 m A i n p . signal is issued.

    The input current is monitored in order to protect the 20 mA input against overloading.If it exceeds the fixed threshold of 24.8 mA, the M E A S I : O v e r l o ad 2 0m A i n pu tsignal is issued.

  • 7/15/2019 Vol1 P632-635

    74/605

    3 Operation(continued)

    3-34 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610

    3-22 Analog direct current input

  • 7/15/2019 Vol1 P632-635

    75/605

    3 Operation(continued)

    P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610 3-35

    Beyond the linearization described above, the user has the option of scaling thelinearized values. Thereby negative values, for example, can be displayed as well andare available for further processing by protection functions.

    3-23 Scaling of the linearized measured value

  • 7/15/2019 Vol1 P632-635

    76/605

    3 Operation(continued)

    3-36 P63X/EN M/Ba4 // AFSV.12.09701 D /// P631-305-403/404-610 // P632-305-403/404-610 // P633-305-404/405/406-610 // P634-305-403/404-610