VLT2800Series
W a rn in g s/a la rm m e ssa g e s .................................................................................... 8 2
W a rn in g w o rd s, ex te n d e d statu s w o rd sa n d a la rm w o rd s ..................................... 8 7
S p e c ia l c o n d itio n s .................................................................................................. 8 8
Te m p e rature-rela ted sw itch in g freq u e n c y .............................................................. 8 8D e ratin g fo r lo n g m o tor c a b le s ............................................................................. 8 9
G a lva n ic iso la tio n (P E L V ) ...................................................................................... 8 9
U L S tan d a rd ........................................................................................................... 8 9
G e n e ra l tec h n ic a l d a ta ........................................................................................... 9 0
Te ch nica l d ata, A C lin e su p p ly 1 x 2 2 0 - 2 4 0 V / 3 x 2 0 0 -2 4 0 V ........................... 9 5
Te c h n ic a l d a ta , A C lin e su p p ly 3 x 3 8 0 - 4 8 0 V .................................................... 9 6
A va ila b le litera tu re ................................................................................................. 9 7
S u p p lie d w ith th e u n it ............................................................................................ 9 7
Fa c to ry S e ttin g s ..................................................................................................... 9 8
M G .2 8 .A 4 .2 G - V L T is a re g is te re d D a n fo s s tra d e m a rk2
-
7/26/2019 VLT2800[1].pdf
3/106
VLT2800Series
Softwareversion
D o c u m e n t V e rs io n N u m b e r 4 .0 0 .
195NA009.1
3
VLT 2800 Series
Operating instructions
Software version: 2.2x
Thes e o pera ting ins truc tions ca n be us ed for a ll VLT 2800
Series adjustable frequency drives (AFD) with software
version 2.2x.
The softw a re vers ion number ca n be s een from pa ra meter
640 Software version no.
NOTE!
Ind icates som ething to b e no ted by the read er.
Ind icates a ge ne ral w arning .
In d ica tes a hig h -vo lta g e w a rn in g .
M G .2 8 .A 4 .2 G - V L T is a re g is te re d D a n fo s s tra d e m a rk 3
IntroductiontoVLT2800
-
7/26/2019 VLT2800[1].pdf
4/106
VLT2800Series
General warning
T he voltag e of the ad justab le freq ue ncy
drive is da ng erou s w h en ever the drive is
co n n e cte d to th e A C lin e. In co rre ct in sta l-
la tio n o f th e m o to r o r d riv e m a y c a u s e d a m a g e to
th e eq uipm en t, seriou s injury or de ath. C o m ply w ith
th e safety instruc tion s in this m an ua la s w e ll as loca l
a nd na tion al rules an d safety reg ulation s.
These rules concern your safety:
1. D isco nn ect the ad justab le freq uen cy d rive from
the A C line if rep air w o rk is to b e carried ou t.
W ait 4 m inu tes to allow fo r elec trica l d isch arg e
be fore rem oving m otor and A C line con nectors.
2 . T h e [S T O P /R E S E T ] k ey o n th e c o n tro l p a n e l o f
the ad justab le freq ue nc y d rive d oe s no t d isco n-
n e c t th e e q u ip m e n t fro m th e A C lin e . D o n o t u s e
it as a safety sw itch .
3 . T h e u n it m u s t b e g ro u n d e d c o rre c tly. T h e u s e r
m ust be protected aga inst sup ply voltage and the
m otor p rotected ag ainst o verloa d in acc ord an ce
w ith ap p lica b le n atio n al an d lo ca l reg u latio ns.
4 . T h e g ro u n d le a k a g e c u rre n ts a re h ig h e r th a n 3 .5
m A .
5. P rotection ag ainst m otor overloa d is no t inc lud ed
in th e fac to ry se ttin g . If th is fu n ctio n is re q u ired ,s e t p a ra m e te r 1 2 8 M otor thermal protection to
ETR trip or ETR warning. F o r N o rth A m e ric a :
Th e E TR func tion s provide class 20 overload p ro-
tection for the m otor, in acc ord anc e w ith N E C
req uirem en ts.
6 . D o n o t re m o v e th e te rm in a l p lu g s fo r th e m o to r
and A C line sup p ly w h ile the ad justab le fre-qu ency drive is con nected to the A C line. E nsure
th a t th e A C lin e s u p p ly h a s b e e n d is c o n n e c te d
a n d th a t 4 m in u te s h a s p a s s e d b e fo re re m o v in g
m o to r a n d A C lin e p lu g s .
7. Th e ad justab le freq ue nc y d rive ha s voltag e inp uts
in a d d itio n to L 1 , L 2 a n d L 3 , w h e n e ve r th e D C -
bu s term ina ls are used . E nsu re tha t all voltag e
in p u ts h a v e b e e n d is c o n n e c te d a n d th a t 4 m in -
utes has pa ssed be fore rep air w ork be gins.
Warnings againstunintended start:
1 . T h e m o to r c a n b e b ro u g h t to a s to p b y m e a ns o f
d ig ita l c o m m a n d s , b u s c o m m a n d s , re fe re n c e s o r
a loc al stop w h ile the d rive is co nn ected to the
A C line. Th ese stop func tion s are no t suf cient to
ensu re tha t no un inten d ed start w ill oc cur.
2 . T h e m o to r m a y s ta rt w h ile p a ra m e te rs a re b e in g
c h a n g e d . A lw a y s a c tiv a te th e s to p k e y [S T O P /
R E S E T ] b y p re s sin g it b e fo re d a ta is m o d i e d .
3 . A m o to r th a t h a s b e e n s to p p e d m a y s ta rt if fa u lts
oc cu r in the electron ics of the d rive, or if a tem p o-
rary overloa d or fau lt c lears in the A C line orm otor con nection .
195N A 139.10
Warning:It can be extrem ely dangerous to touch the electrical partseven w hen the m ains supply has been disconnected.Also ensure that other voltage inputs are disconnectedfrom load sharing, for exam ple (sharing of D C interm ediatecircuit).
For VLT 2800: w ait at least 4 m inutes.
M G .28.A4.2G - VLT is a registered D anfoss trade m ark4
-
7/26/2019 VLT2800[1].pdf
5/106
VLT2800Series
Control unit
The controlpanel is divided into four function group s:
1. S ix-digit LED display.
2. Keys for changing param eters and shifting display
functions..
3. Indicator lam ps.
4. Keys for local operation.
Alldata is displayed on a six-digit LE D. The LED can
show one item ofoperating data continuously during
norm aloperation. There are three indicator lam ps
for indication ofAC line connection (O N ), w arning
(W AR N IN G ) and alarm (ALA R M ). M ostof the ad-
justable frequency drive param eters can be changed
via the controlpanel. This function can be pro-
gram m ed as Lockedin param eter 018,Lock for data
changes, to prevent tam pering or localdata entry.
Control keys
[QUICK MENU]allow s access to the param eters in
the Q uick m enu. This m enu is for initial setup ofthe
drive. The [Q U IC K M EN U ] key is also used to can-
cela change of param eter values and to toggle
betw een D isplay m ode and Q uick m enu m ode.
[CHANGE DATA] is used to change a setting. The
[C H AN G E DATA ] key is also used to con rm a pa-
ram eter change.
[+] and [-]are used to scrollthrough param eters and
to change param eter values. These keys are also
used in D isplay m ode to select a value for display.
The[QUICK MENU]+[+] keys pressed at the sam e
tim e give access to allparam eters by entering M enu
m ode. See Menu mode.
[STOP/RESET] is used to stop the connected m otor
or to reset the ad justable frequency drive after a trip.
The key can be selected as A ctive [1] or N otactive
[0]via param eter 014 Localstop/reset. In D isplay
m ode, the display w ill ash ifthe stop function is ac-
tivated.
NOTE!
If the [STO P/R ESET] key has b een selected
as Not active[0] in param eter 014 Local stop/
resetand there is no stop com m and via the digital
inputs or serial com m unication, the m otor can only
be stopped by disconnecting the AC line voltage to
the adjustable frequency drive.
[START] is used for starting the adjustable fre-
quency drive. It is alw ays available, but the [START]
key cannot override a stop com m and issued through
term inal 27 or a digital com m unication bus (see con-
nection exam ples).
Manual initialization
To m anually initialize the adjustable frequency drive
to factory default settings, rst disconnect AC line
voltage. H old the [Q U IC K M E N U] + [+]+ [C H AN G E
DATA ] keys dow n w hile sim ultaneously reconnecting
the AC line voltage. R elease the keys. The drive
has now been program m ed for factory settings.
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 5
IntroductiontoVLT2800
-
7/26/2019 VLT2800[1].pdf
6/106
VLT2800Series
Display readoutstates
Display mode
In norm al operation, one item ofoperating data can
be selected for continuous display.
U se the [+]and [-]keys to select from the follow ing
options for display:
- O utput frequency [H z]
- O utput current [A]
- O utput voltage [V]
- Interm ediate circuit voltage [V]
- O utput pow er [kW ]
See Status messagesfor code explanations.
Quick menu
U se the [Q U IC K M EN U ] key to access the 12 m ost
im portant param eters ofthe adjustable frequency
drive. A fter program m ing the Q uick m enu param e-
ters,the adjustable frequency drive is, in m ost
cases, ready for operation. S ee Programming the
adjustable frequency drive.
The Q uick m enu param eters are:
Par. 102 Motor power PM,N
Par. 103 Motor voltage UM, N
Par. 104 Motor frequency f M, N
Par. 105 Motor current IM, N
Par. 106 Rated motor speed nM, N
Par. 107 Automatic motor adaption.
Par. 204 Minimum reference Ref MIN
Par. 205 Maximum reference Ref MAX
Par. 207 Ramp-up time
Par. 208 Ramp-down time
Par. 002 Local/remote operationPar. 003 Local reference
Param eter 102 - 106 can be read outfrom the m otor
nam eplate.
Menumode
To enter the M enu m ode,press [Q U IC K M EN U ] + [+]
at the sam e tim e.
In M enu m ode,m ost of the adjustable frequency
drive param eters can be changed. Scrollthrough theparam eters using the [+]and [-]keys. The current
param eter num ber w ill ash w hile scrolling through
the m enu item s.
The display exam ple show s that the setting in pa-
ram eter 102 Motor power PM,Nis 0.75. In order tochange the value of 0.75,press [C H AN G E DATA ].
U se the [+]and [-]keys to change the param eter
value.
W hen, for a given param eter, the display show s
three dots at the right,itm eans that the param etervalue has m ore than three digits. In order to see the
value, press [C H AN G E DATA].
The display show s that in param eter 128,Motor
thermal protection,the second [2] selection is active,
Thermistor trip.
Programming the adjustable frequency drive
NOTE!
The m otor
m ust be stopped to change param eter data.
Program the drive in accordance w ith the follow ing
procedure:
1. P ress the [Q UIC K M EN U ] key to enter the Q uick
m enu.
M G .28.A4.2G - VLT is a registered D anfoss trade m ark6
-
7/26/2019 VLT2800[1].pdf
7/106
VLT2800Series
2. Scrollthrough the Q uick m enu using the [+] and
[-]keys.
3. C hange the data values by rst pressing
[C H AN G E [DATA] key4. and then change the param eter value w ith the [+]
and [-]keys.
5. P ress [C H AN G E DATA ] again to acceptthe
change or [Q U IC K M EN U ] to cancelthe change.
Press [Q UIC K M EN U ] once m ore to exit Q uick
m enu m ode and enter D isplay m ode. (The drive
w illdefault from Q uick m enu m ode to D isplay
m ode in 2 m inutes ifno activity has taken place.)
NOTE!
Enter param eters 102 through 106 data,
at m inim um , to ready the drive for operation.D ata for param eters 102 through 106 can be read
from the m otor nam eplate.
Automatic motor tuning
Autom atic m otor tuning (AM T) m easures stator re-
sistance R S w ithout the m otor axle turning. This
m eans that the m otor is not delivering any torque.
AM T can optim ize adjustm ent ofthe adjustable fre-
quency drive to the m otor. For bestpossible tuning,
it is recom m ended that AM T b e perform ed on a cold
m otor. R epeated AM T runs can cause m otor heat-
ing, resulting in an increase in the stator resistance.As a rule, how ever, this is notcritical. (See param e-
ter 107, Automatic motor tuning, AMT, description
for m ore detailbefore running AM T.)
Perform AM T in accordance w ith the follow ing proce-
dure:
1. P ress the [Q UIC K M EN U ] key to enter Q uick
m enu m ode
2. U se the [+]key to scrollto param eter 107.
3. In param eter 107,Automatic motor tuning, "107"
w illnow ash.4. P ress [C H AN G E DATA] and use the [+]key to se-
lect data value [2], Optimization on (AMT
START). [2]w illnow ash.
5. Press [START] key to activate AM T. "107" w ill
now ash and dashes w illm ove from left to right
in the data value eld.
6. W hen "107" appears once m ore w ith the data
value [0], AM T is com plete. Press [STO P/R ESET]
to save the m otordata into the drive m em ory.
7. "107" w illthen continue to ash w ith the data
value [0]. Press [Q UIC K M EN U ] to exit M enu
m ode and enter D isplay m ode.
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 7
IntroductiontoVLT2800
-
7/26/2019 VLT2800[1].pdf
8/106
VLT2800Series
Operation& Display
001001 Language
(LANGUAGE)
Value:
English (EN G LISH ) [0]
G erm an (D EU TS C H ) [1]
French (FR AN C AIS) [2]
D anish (DAN SK ) [3]
Spanish (ESP AN O L) [4]
Italian (ITALIAN O ) [5]
Function:
This param eter is used to choose the language
show n in the display w henever an optionalLC P con-
trolunit is connected.
Description of choice:
C hoose the language to display. The factory setting
m ay vary.
002002 Local/remoteoperation
(OPERATION SITE)
Value:
R em ote operation (R EM O TE) [0]
Local operation (LO C AL) [1]
Function:
There is a choice betw een tw o m odes ofoperation
for the adjustable freq uency d rive: Remote operation
[0] or Local operation[1]. See also param eter 013
Local controlifLocal operation[1] is selected.
Description of choice:
IfRemote operation[0] is selected, the adjustable
frequency drive is controlled via:
1. the controlterm inals or serial com m unication.
2. the [STA RT] key. This cannot, how ever, override
stop com m ands transm itted via the digital inputs
or via serial com m unication (see param eter 505
Start).
3. the [STO P/R ESET] and [JO G ] keys, on the condi-
tion thatthese are active. (See param eters 014
Local stopand 015 Local jog.)
If Local operation[1]is selected, the adjustable fre-
quency drive is controlled via:
1. the [STA RT] key. This cannot, how ever, override
stop com m ands via the digital inputs (see param -
eter 013 Local control).
2. the [STO P/R ESET] and [JO G ] keys, on the condi-
tion that these are active. (See param eters 014
and 015.)
3. the [FW D /R EV] key,on the condition that it hasbeen selected as active in param eter 016 Local
reversing, and that param eter 013 Local controlis
setatLocal control and open loop[1] or Local
control as parameter 100[3]. Param eter 200 Out-
put frequency rangeis set at Both directions[4].
4. param eter 003 Local referencew here the refer-
ence can be set using the [+]and [-]keys.
5. an external controlcom m and that can be con-
nected to the digital inputs (see param eter 013
Local control).
NOTE!The [JO G ] and [FW D /R EV] keys
are located on the optional LC P controlunit.
003003 Local reference
(LOCAL REFERENCE)
Value:
Par. 013 Local controlm ustbe set to [1] or [2]:
0 - fM AX(par. 202) 000,000.000
Par. 013 Local controlm ustbe setto [3] or [4] and
param eter 203 Reference/feedback rangeto [0]:
R efM IN-R efM AX(par. 204-205) 000,000.000
Par. 013 Local controlm ustbe setto [3] or [4] and
param eter 203 Reference/feedback rangeto [1]:
-RefM AX- + RefM AX(par. 204-205) 000,000.000
Function:
In this param eter, the local reference can be set
m anually. The unit of the localreference depends on
the con guration selected in param eter 100 Configu -
ration.
Description of choice:
In order to protectthe localreference, param eter
002 Local/remote operationm ustbe set to Local op-
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark8
-
7/26/2019 VLT2800[1].pdf
9/106
VLT2800Series
eration[1]. Localreference cannot be set via serial
com m unication.
004004 ActiveSetup
(ACTIVE SETUP)
Value:
Factory Setup (FAC TO RY SETU P) [0]
Setup 1 (SETU P 1) [1]
Setup 2 (SETU P 2) [2]
Setup 3 (SETU P 3) [3]
Setup 4 (SETU P 4) [4]
M ultiSetup (M U LTI SETU P) [5]
Function:
The active operational Setup is selected here. All
param eters can be program m ed in four individual
Setups. Selections betw een Setups can be m ade in
this param eter via a digital input or via serial com -
m unication.
Description of choice:
Factory Setup[0]contains the factory-set param eter
values. Setups 1-4[1]-[4] are four individual Setups
w hich can be selected for active operation. Multi
Setup[5]is used for rem ote-controlled selection be-
tw een the four Setups via a digital input or via serial
com m unication.
005005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FAC TO RY SETU P) [0]
Setup 1 (SETU P 1) [1]
Setup 2 (SETU P 2) [2]
Setup 3 (SETU P 3) [3]
Setup 4 (SETU P 4) [4]
Active Setup (AC TIVE SETU P) [5]
Function:
You can select w hich Setup you w antto program .
You can program a Setup during operation (from the
controlpanel or the serial com m unication port). It is,
for exam ple, possible to p rogram Setup 2[2], w hile
the active Setup is set to Setup 1[1] in param eter
004 Active Setup. You cannot,how ever, change
Factory Setup[0].
Description of choice:
Factory Setup[0]contains the factory-set data andcan be used as a source of data or to reset to a
know n status. Setup 1-4[1]-[4] are individual Setups
that can be program m ed freely during operation. If
Active Setup[5] is selected, the program m ing Setup
w illbe equalto param eter 004 Active Setup. EachSetup 1-4initially has the Factory S etup.
NOTE!
If data is m odied or copied to the active
Setup,the m odications have an im m ediate
effect on the units operation.
006006 Setupcopying
(SETUP COPY)
Value:
N o copying (N O C O PY)
[0]
C opy to Setup 1 from #
(C O PY TO SETU P 1 ) [1]
C opy to Setup 2 from #
(C O PY TO SETU P 2) [2]
C opy to Setup 3 from #
(C O PY TO SETU P 3) [3]
C opy to Setup 4 from #
(C O PY TO SETU P 4) [4]
C opy to allSetups from # (C O PY TO ALL) [5]
Function:
You can copy from the selected active S etup in pa-
ram eter 005 Programming setupto the selected
Setup in this param eter.
NOTE!
C opying is only possi-
ble in [STO P/R ESET] w ith the m otorstopped.
Description of choice:
C opying begins w hen the required copying function
has been selected and the [C H AN G E DATA ] key has
been pushed. The display indicates w hen copying is
in progress. Press [O K] to com plete copying for the
optional LC P.
007007 LCP copy
(LCP COPY)
Value:
N o copying (N O C O PY) [0]
U pload allparam eters (U PL. ALL PA R .) [1]
D ow nload allparam eters (DW N L. ALL PA R .) [2]
D ow nload size-independent param eters
(DW N L. O U TP IN D. PA R .) [3]
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 9
Progr
amming
-
7/26/2019 VLT2800[1].pdf
10/106
VLT2800Series
Function:
Param eter 007 LCP copyis used if the LC P control
panelis to be used to transfer settings. U se this
function if allparam eter Setups 1-4 are to be copiedfrom one unit to another by connecting the LC P con-
trolpanel to different drives.
Description of choice:
Select Upload all parameters[1]to transfer allpa-
ram eter values to the LC P. Select Download all
parameters[2] to transfer param eter values to the
unit on w hich the controlpanel has been connected.
SelectDownload power-independent parameters[3]
if only the pow er-independent param eters are to be
dow nloaded. Use this facility w hen dow nload ing to a
unit w ith a different rated pow er size than the unit
from w hich the param eter Setup originates.
NOTE!
U pload/dow nload can only be perform ed in
stop m ode. D ow nload can only be perform ed
to an adjustable frequency drive w ith the sam e soft-
w are version num ber, see param eter 626 Database
identification no.
008008 Display scaling of output frequency
(FREQUENCY SCALE)Value:
0.01 - 100.00 1.00
Function:
In this param eter, the factor is selected by w hich the
outputfrequency is to be m ultiplied . The value is
show n in the display, provided param eters 009-012
Display readouthave been setto Output frequency x
scaling[5].
Description of choice:
Set the required scaling factor.
009009 Largedisplay readout
(DISPLAY LINE 2)
Value:
N o readout (N O N E) [0]
R esulting reference % ]
(R EFER EN C E [% ]) [1]
R esulting reference [unit]
(R EFER EN C E [U N IT]) [2]
Feedback [unit] (FEED B AC K [U N IT]) [3]
Frequency [H z] (FR EQ U EN C Y [H Z]) [4]
O utput frequency x scaling
(FR EQ U EN C Y X SC AL.) [5]
M otor current [A] (M O TO R C U R R EN T [A]) [6]
Torque [% ] (TO R Q U E [% ]) [7]Pow er [kW ] (PO W E R [K W ]) [8]
Pow er [H P] (PO W E R [H P]) [9]
M otor voltage [V]
(M O TO R VO LTAG E [V]) [11]
D C link voltage [V]
(D C LIN K VO LTAG E [V]) [12]
Therm al load m otor[% ]
(TH ER M . LO AD M O TO R [% ]) [13]
Therm al load [% ]
(TH ER M . LO AD [% ]) [14]
R unning hours [H ours]
(RU N H O U R S [H O U R S]) [15]D igital input[B in]
(D IG IT A L IN PU T[B IN ]) [16]
Analog input 53 [V]
(AN A.IN P . 53 [V]) [17]
Analog input 60 [m A]
(AN A. IN P. 60 [M A]) [19]
Pulse reference [H z]
(PU LSE R EFER EN C E [H Z]) [20]
External reference [% ]
(EXT .R EFER EN C E [% ]) [21]
Status w ord [H ex] (STATU S W O RD [H EX]) [22]
H eatsink tem perature [
C ](H EA TS IN K TEM P.[
C ]) [25]
Alarm w ord [H ex] (ALA R M W O R D [H EX]) [26]
C ontrol w ord [H ex] (C O N TR O L W O RD [H EX])[27]
W arning w ord [H ex]
(W AR N IN G W O RD [H EX]) [28]
Extended status w ord [H ex]
(EXT .STATU S W O RD [H EX]) [29]
C om m unication option card w arning
(C O M M .O PT .W AR N [H EX]) [30]
Pulse count
(PU LSE C O U N T) [31]
Function:
In this param eter you can select the data value that
you w ish to display in the LC P controlunit display
line 2 w hen the adjustable frequency drive is
sw itched on. The display w illalso be included in the
scrollbar in display m ode. In param eters 010-012
Display readoutyou can select a further three data
values, w hich are displayed in display line 1.
Description of choice:
No readoutcan only be selected in param eters 010-
012 Small display readout.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark10
-
7/26/2019 VLT2800[1].pdf
11/106
VLT2800Series
Resulting reference [%]gives, as a percentage, the
resulting reference in the range from M inim um refer-
ence, R efM INto M axim um reference, R efM AX.
Reference [unit]gives the resulting reference w ith
unit H z in Open loop. In Closed loopthe reference
unit is selected in param eter 416 Process units.
Feedback [unit] gives the resulting signal value
using the unit/scaling selected in param eter 414 Min-
imum feedback, FBLOW,415 Maximum feedback,
FBHIGHand 416 Process units.
Frequency [Hz]gives the output frequency of the ad-
justable frequency drive.
Output frequency x scaling [-]equals the present
outputfrequency fMm ultiplied by the factor setin pa-
ram eter 008 Display scaling of output frequency.
Motor current [A]gives the phase current ofthe m o-
torm easured as an effective value.
Torque [%]denotes the m otors present load in rela-
tion to the m otors rated torque.
Power [kW]gives the present pow er thatthe m otoris
absorbing in kW .
Power [HP]gives the present pow er that the m otoris
absorbing in H P.
Mot or voltage[V]gives the voltage supplied to the
m otor.
DC link voltage [V]gives the interm ediate circuit volt-
age ofthe adjustable frequency drive.
Thermal load motor [%]gives the calculated/esti-
m ated load on the m otor. 100 % is the cut-outlim it.
Thermal load [%]gives the calculated/estim ated
therm al load on the adjustable frequency drive. 100
% is the cut-outlim it.
Running hours [Hours]gives the num ber of hours
that the m otorhas run since the last reset in param -
eter 619 Reset of running hours counter.
Digital input [Binary code]gives the signal status
from the 5 digital inputs (18, 19,27,29 and 33). Ter-
m inal18 correspond s to the biton the extrem e left.
0 = no signal, 1 = signal connected.
Analog input 53 [V]gives the voltage value ofterm i-
nal53.
Analog input 60 [mA]gives the present value ofter-
m inal 60.
Pulse reference [Hz]gives the reference in H z con-
nected to term inal 33.
External reference [%]gives the sum ofexternal ref-
erences as a percentage (sum ofanalog/pulse/serial
com m unication) in the range from M inim um refer-
ence,R efM INto M axim um reference, R efM AX.
Status word [Hex]gives one or several status condi-
tions in a H ex code. See Serial com municationinthe Design Guidefor further inform ation.
Heatsink temp.[
C]gives the present heatsink tem -
perature ofthe adjustable frequency drive. The
cut-outlim it is 90-100
C ,w hile cutting back in oc-
curs at70 5
C .
Alarm word [Hex]gives one or several alarm s in hex
code. See Serial com municationin the Design
Guidefor further inform ation.
Control word [Hex]gives the controlw ord for the ad-
justable frequency drive. See Serial com munication
in the Design Guidefor further inform ation.
Warning word [Hex]gives one or several w arnings in
hex code. See Serial com municationin the Design
Guidefor further inform ation.
Extended status word [Hex]gives one or several sta-
tus m odes in H ex code. See Serial com munication
in the Design Guidefor further inform ation.
Communi cation option card warning [Hex]gives a
w arning w ord if there is a fault in the com m unicationbus. O nly active if com m unication options are in-
stalled.
If there are no com m unication options 0 H ex is dis-
played.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 11
Progr
amming
-
7/26/2019 VLT2800[1].pdf
12/106
VLT2800Series
Pulse countgives the num ber ofpulses thatthe unit
has registered .
010010 Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009 Large display readout
Reference [% ] [1]
Function:
Select the rst ofthree data values to be displayed
in the optionalLC P controlunit display, line 1,posi-
tion 1. This is a useful function, e.g. w hen setting
the PID regulator, as it gives a view ofprocess reac-
tions to reference changes. The display readout is
activated by pushing the [D ISPLA Y M O D E] key.
Description of choice:
See param eter 009 Large display readout.
011011 Small display readout1.2
(DISPLAY LINE 1.2)
Value:
See param eter 009 Large display readout
M otor current [A][6]
Function:
See the functional description given under param eter
010 Small display readout.
Description of choice:
See param eter 009 Large display readout.
012012 Small display readout1.3
(DISPLAY LINE 1.3)
Value:
See param eter 009 Large display readout
Pow er [kW ][8]
Function:
See the functional description given under param eter
010 Small display readout.
Description of choice:
See param eter 009 Large display readout.
013013 Local control
(LOC CTRL/CONFIG.)
Value:
Localnotactive (D ISAB LE) [0]
Localcontroland open loop
(LO C C TR L/O PEN LO O P) [1]
R em ote-operated controland open loop
(LO C +D IG C TR L/AS P100) [2]
Localcontrolas param eter 100
(LO C C TR L/AS P100) [3]
R em ote-operated controlas param eter 100(LO C +D IG C TR L/AS P100) [4]
Function:
Select the required function w hen, in param eter 002
Local/remote op eration, Loc al operation[1] has been
chosen.
Description of choice:
If Local not active[0]is selected, itis notpossible to
set a reference via param eter 003 Local reference.
To select Local not active[0], param eter 002 Local/
remote operationm ustbe setto
Remote operation[0].
Local control and open loop[1]is used if the m otor
speed is to be set via param eter 003 Local refer-
ence. W hen this choice is m ade, param eter 100
Co nfigurationautom atically shifts to Speed regula-
tion, open loop[0].
Remote-operated control and open loop[2]functions
in the sam e w ay as Local control and open loop[1];
how ever, the unit can also be controlled via the digi-
tal inputs.
Local control as parameter 100[3]is used w hen the
m otorspeed is to be set via param eter 003 Local
reference, but w ithout param eter 100 Co nfiguration
autom atically shifting to Speed regulation, open loop
[0].
Remote-operated control as parameter 100[4]
w orks the sam e w ay as Local control as parameter
10 0[3]; how ever, the unit can also be controlled via
the digitalinputs.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark12
-
7/26/2019 VLT2800[1].pdf
13/106
VLT2800Series
Shifting from Remote o perationto Local operationin
param eter 002 Local/remote operation, w hile this pa-
ram eter 013 is set to Remote-operated control andopen loop[1]: The present m otor frequency and di-
rection ofrotation w illbe m aintained. If the present
direction ofrotation does notrespond to the revers-
ing signal (negative reference), the reference w illbe
set to 0.
Shifting from Local operationto Remote operationin
param eter 002 Local/remote control, w hile this pa-
ram eter 013 is set to Remote-operated control and
open loop[1]: The con guration selected in param e-
ter 100 Co nfigurationw illbe active. The transition
w illbe sm ooth.
Shifting from Remote controlto Local controlin
param eter 002 Local/remote operation, w hile this pa-
ram eter 013 is set to Remote-operated control as
parameter 100[4]: the present reference w illbe
m aintained. If the reference signal is negative, the
localreference w illbe set to 0.
Shifting from Local operationto Remote operationin
param eter 002 Local/remote operation, w hile param -
eter 013 is set to Remote-operated control as
parameter 100[4]: The local reference w illbe re-placed by the rem ote-operated reference signal.
014014 Local stop
(LOCAL STOP)
Value:
N ot active (D ISAB LE ) [0]
Active (EN AB LE) [1]
Function:
In this param eter, the localstop function ofthe
[STO P/R ES ET] key can be engaged or disengaged
on the controlpanel and on the LC P controlpanel.
Description of choice:
IfNot active[0]is selected in this param eter, the
[STO P ]-key w illbe inactive.
NOTE!
IfNot active[0]is selected, the m otor can-
notbe stopped by m eans ofthe [STO P]-key.
015015 Local jog
(LOCAL J OGGING)
Value:
N ot active (D ISAB LE) [0]
Active (EN AB LE) [1]
Function:
In this param eter, the jog function on the LC P con-
trolpanel can be engaged/disengaged.
Description of choice:IfNot active [0]is selected in this param eter, the
[JO G ]-key w illbe inactive.
016016 Local reversing
(LOCAL REVERSING)
Value:
N ot active (D ISAB LE) [0]
Active (EN AB LE) [1]
Function:
In this param eter you can select/deselect the revers-
ing function on the LC P controlpanel. The key can
only be used ifparam eter 002 Local/remote opera-
tionis set to Local operation[1] and param eter 013
Local controlto Local control, open loop[1] or Local
control as parameter 100[3].
Description of choice:
W hen Disable[0]is selected, the [FW D /R EV] key
w illbe disabled. S ee also param eter 200 Output fre-
quency range.
017017 Local reset of trip
(LOCAL RESET)
Value:
N ot active (D ISAB LE) [0]
Active (EN AB LE) [1]
Function:
The reset function of the [STO P/R ESET] key on the
controlpanelcan be engaged/disengaged.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 13
Progr
amming
-
7/26/2019 VLT2800[1].pdf
14/106
VLT2800Series
Description of choice:
IfNot active[0]is selected in this param eter, the re-
set function w illbe inactive.
NOTE!
SelectNot active[0], only if an external reset
signal has been connected via the digital in-
puts.
018018 Lock for data changes
(DATA CHANGE LOCK)
Value:
N ot locked (N O T LO C KED ) [0]
Locked (LO C KED ) [1]
Function:
In this param eter, itis possible to lockthe controls
to disable data changes via the controlkeys.
Description of choice:
If Locked[1] is selected, data changes in the param -
eters cannot be m ade; how ever, it w illstillbe
possible to m ake data changes via serial com m uni-
cation. Param eter 009-012 Display readoutcan be
changed via the controlpanel.
019019 Operating modeatpower-up,local opera-
tion
(POWER UP ACTION)
Value:
Auto restart, use saved reference (AU TO
RESTART) [0]
Forced stop,use saved reference (LO C AL=STO P)[1]
Forced stop,set ref. to 0 (LO C AL=STO P ,R EF=0)[2]
Function:
Setting ofthe required operating m ode w hen the AC
line voltage is engaged . This function can only beactive if Local operation[1]has been selected in pa-
ram eter 002 Local/remote operation.
Description of choice:
Auto restart, use saved ref.[0]is selected ifthe unit
is to start using the localreference (set in param eter
003 Local reference) and the start/stop state given
via the controlkeys im m ediately prior to the A C line
voltage being cutout.
Forced stop, use saved ref.[1]is selected if the unit
is to rem ain stopped w hen the line voltage is en-
gaged, untilthe [START]-key is activated. After a
startcom m and the m otor speed is ram ped up to the
saved reference in param eter 003 Local reference.
Forced stop, set ref. to 0[2] is selected if the unit is
to rem ain stopped w hen the line voltage is cut backin. Param eter 003 Local referenceis to be zeroed.
NOTE!
In rem ote operation (param eter 002 Local/
remote operation) the start/stop state at the
tim e ofAC line connection w illdepend on the exter-
nalcontrolsignals. IfPulse start[8]is selected in
param eter 302 Digital input, the m otor w illrem ain
stopped after line connection.
024024 User-definedQuick Menu
(USER QUICK MENU)
Value:
N ot active (D ISAB LE) [0]
Active (EN AB LE) [1]
Function:
In this param eter you can optout ofthe standard
setup of the Q uick m enu key on the controlpanel
and the LC P controlpanel.
U sing this function, in param eter 025 Quick Menu
setupthe user can select up to 20 p aram eters for
the Q uick M enu key.
Description of choice:
If not active[0] is selected, the standard setup ofthe
Q uick M enu key is active.
IfActive[1] is selected, the user-de ned Q uick M enu
is active.
025025 Quick MenuSetup
(QUICK MENU SETUP)
Value:
[Index 1 - 20]Value: 0 -999 000
Function:
In this param eter you de ne w hich param eters are
required in the Q uick M enu w hen param eter 024
User-defined Quick M enuis set to Active[1].
U p to 20 param eters can be selected for the user-
de ned Q uick M enu.
NOTE!
Please note that this param eter can only
be set using an LC P controlpanel. See Order
form.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark14
-
7/26/2019 VLT2800[1].pdf
15/106
VLT 2800 Series
Description of choice:
The Q uick M enu is set up as follow s:
1. Select param eter 025 Quick Menu setupand
press [C H AN G E DATA].2. Index 1 indicates the rst param eter in Q uick
M enu. You can scrollbetw een the index num bers
using the [+ /-]keys. Select Index 1.
3. U sing [< >]you can scrollbetw een the three g-
ures. Press the [
-
7/26/2019 VLT2800[1].pdf
16/106
VLT 2800 Series
Load and Motor
100100 Configuration
(CONFIGURATION)
Value:
Speed regulation, op en loop
(SP EED O PEN LO O P) [0]
Speed regulation, closed loop
(SP EED C LO SED LO O P) [1]
Process regulation, closed loop
(PR O C ES S C LO SE D LO O P) [3]
Function:
This param eter is used to select the con guration to
w hich the unit is to be adapted. The param eters not
used in a given con guration are hidden (not active).
Description of choice:
IfSpeed regulation, open loop[0]is selected, nor-
m alspeed controlis ob tained (w ithout feedback
signal) w ith autom atic load and slip com pensation to
ensure a constant speed at varying loads. C om pen-
sations are active, butm ay b e disabled in param eter
134 Load compensationand param eter 136 Slip
compensationas required.
IfSpeed regulation, closed loop[1]is selected, bet-
ter speed accuracy is obtained. A feedback signalm ustbe added,and the P ID regulator m ustbe setin
param eter group 400 Special functions.
IfProcess regulation, closed loop[3]is selected, the
internal process regulator is activated to enable pre-
cise regulation ofa process in relation to a given
process signal. The process signal can be set to the
relevant process unit or as a percentage. A feed-
back signal m ustbe added from the process and the
process regulator m ustbe set in param eter group
400 Special functions.
101101 Torque characteristic
(TORQUE CHARACT)
Value:
C onstant torque
(C O N ST AN T TO RQ U E) [1]
Variable torque low
(TO R Q U E: LO W ) [2]
Variable torque m edium
(TO R Q U E: M ED ) [3]
Variable torque high
(TO R Q U E: H IG H ) [4]
Variable torque low w ith C T start
(VT LO W C T START) [5]
Variable torque m edium w ith C T start(VT M ED C T S TAR T) [6]
Variable torque high w ith C T start
(VT H IG H C T START) [7]
Special m otor m ode
(SPEC IAL M OTO R M O D E) [8]
C T = C onstant torque
Function:
This param eter enables a choice ofprinciple for
adap tation ofthe U /fratio ofthe adjustable fre-
quency drive to the torque characteristic ofthe load.See par. 135 U/f ratio.
Description of choice:
IfConstant torque[1] is selected, a load-dependent
U /fcharacteristic is obtained, in w hich outputvoltage
and outputfrequency increase w ith increasing loads
in order to m aintain constant energy to the m otor.
SelectVariable torque low[2], Variable torque
medium [3] or Variable torque high[4], ifthe load is
square (centrifugal pum ps,fans).
If a higher break-aw ay torque is required than the
three previous choices provide, selectVariable
torque - low with CT start[5], - medium with CT start
[6] or high with CT start[7].
NOTE!
Load and slip com pensation are notactive
ifvariable torque or special m otor m ode have
been selected.
Select Special motor mode[8], if a special U /fset-
ting is needed that is to be adapted to the present
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark16
-
7/26/2019 VLT2800[1].pdf
17/106
VLT 2800 Series
m otor. The break points are set in param eters 423-
428 Voltage/frequency.
NOTE!
If a value setin the nam e-plate param eters
102-106 is changed, param eters 108 Stator
resistanceand 109 Stator reactancechange auto-
m atically.
102102 Motorpower PM,N
(MOTOR POWER)
Value:
0.25 - 11 kW Depends on unit
Function:
H ere you m ust seta pow er value [kW ] P M ,N,corre-
sponding to the m otors rated pow er. The factory
sets a rated pow er value [kW ] P M ,N, thatd epends on
the type ofunit.
Description of choice:
Set a value thatm atches the nam eplate data on the
m otor. Settings betw een one size below and one
size over the factory setting are possible.
N orth Am erican H P to kW
C onversion C hartH P kW
1/2 0.37
3/4 0.55
1 0.75
1 1/2 1.1
2 1.5
3 2.2
4 3.0
5 4
7 1/2 5.5
10 7.5
103103 Motorvoltage UM,N
(MOTOR VOLTAGE)
Value:
For 200 V units: 50 - 999 V 230 V
For 400 V units: 50 - 999 V 400 V
Function:
This is w here to set the rated m otorvoltage U M ,Nfor
either star Y or delta 1 .
Description of choice:
Select a value that corresponds to the nam eplate
data on the m otor,regardless ofthe adjustable fre-
quency drives AC line voltage.
104104 Motor frequency fM,N
(MOTOR FREQUENCY)
Value:
24-1000 H z 60 H z
Function:
This is w here to select the rated m otor frequency
fM ,N.
Description of choice:
Select a value that corresponds to the nam eplate
data on the m otor.
105105 Motor current IM,N
(MOTOR CURRENT)
Value:
0.01 - IM AX Depends on choice of m otor
Function:
The nom inal, rated current of the m otorIM ,Nform s
part of the units calculation for features such as
torque and m otortherm al protection.
Description of choice:
Set a value that corresponds to the nam eplate data
on the m otor. Set the m otor current IM ,Ntaking into
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 17
Progr
amming
-
7/26/2019 VLT2800[1].pdf
18/106
VLT 2800 Series
account w hether the m otor is star-connected Y or
delta-connected 1 .
106106 Rated motor speed
(MOTOR NOM.SPEED)
Value:
100 - fM ,Nx 60 (m ax. 60000 rpm )
D epends on param eter 102 Motor power, PM, N
Function:
This is w here to setthe value thatcorresp onds to
the rated m otorspeed nM ,Nthat can be seen from
the nam eplate data.
Description of choice:
Select a value thatcorresponds to the nam eplate
data on the m otor.
NOTE!
The m ax. value equals fM ,Nx 60. fM ,Nto be
set in param eter 104 Motor frequency, f M, N.
107107 Automatic motor tuning, AMT
(AUTO MOTOR TUN.)
Value:
O ptim isation off(AM T O FF) [0]O ptim isation on (AM T STA RT) [2]
Function:
- For AM T to de ne the m otor param eters acccu-
rately, the correct nam eplate data for the m otor
connected to the adjustable frequency drive m ust
be keyed into p aram eters 102 to 106.
- Alarm s w illappear in the display iffaults arise
during tuning ofthe m otor. See Warnings/alarms
messagesin this m anual.
- As a rule, the A M T function can m easure the R S
values for m otors that are 1-2 tim es larger or
sm aller than the adjustable frequency drives
nom inal size.
- If you w ish to interrupt autom atic m otor tuning,
press the [STO P/R ESET] key.
NOTE!
AM T m ay notbe perform ed on m otors con-
nected in parallel, nor m ay setup changes be
m ade w hile AM T is running.
See Automatic motor tuningin this m anual for the
AM T procedure.
Description of choice:
SelectOptimization on[2] as partofthe AM T proce-
dure if you w ant the adjustable frequency drive to
perform autom atic m otor tuning.
108108 Stator resistance RS
(STATOR RESISTAN)
Value:
0.000 - X.XXX
Depends on choice of m otor
Function:
After setting ofparam eters 102-106 Nameplate data,
a num ber of adjustm ents ofvarious param eters iscarried outautom atically,including stator resistance
R S. A m anually entered R Sm ust apply to a cold m o-
tor. The shaft perform ance can be im proved by
ne-tuning R Sand XS, see procedure below .
NOTE!
Param eters 108 Stator resistance RSand 109
Stator reactance XSare norm ally notto be
changed if nam eplate data has been set.
Description of choice:
R Scan be set as follow s:
1. U se the factory settings ofR Sw hich the ad-
justable frequency drive itself chooses on the
basis ofthe m otornam eplate data
2. The value is stated by the m otor supplier.
3. The value is obtained through m anual m easure-
m ents: R Scan be calculated by m easuring the
resistance R PH ASE -PH AS Ebetw een tw o phase ter-
m inals. W here R PH AS E-PH ASE is low er than 1-2
O hm s (typical for m otors > 7.5 H P,400 V), a spe-
cial O hm -m eter should be used (Thom son-bridge
or sim ilar). RS
=0.5 x RPHASE-PHASE
4. R Sis set autom atically w hen A M T has been com -
pleted. See param eter 107 Auto motor tuning.
109109 Stator reactance XS
(STATOR REACTANCE)
Value:
0.00 - X,XX
Depends on choice of m otor
Function:
After setting ofparam eters 102-106 Nameplate data
,
stator reactance XSis calculated autom atically by the
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark18
-
7/26/2019 VLT2800[1].pdf
19/106
VLT 2800 Series
adjustable frequency drive. Shaft perform ance can
be im proved by ne tuning X S,see options below .
NOTE!
Param eter 109 Stator reactance XSis
norm ally notchanged if nam eplate data has
been program m ed.
Description of choice:
XScan be set as follow s:
1. U se the factory settings ofXSprogram m ed into
the ad justable frequency drive from the m otor
nam eplate data.
2. The value stated by the m otorsupplier.
3. The value is obtained through m anual m easure-
m ents X Sis obtained by connecting a m otorto
AC line and m easuring the phase-phase voltage
U Mand the idle current 8.
119119 High start torque
(HIGH START TORQ.)
Value:
0.0 - 0.5 sec. 0.0 sec.
Function:
To ensure a high starttorque approx. 1.8 x IIN V . can
be perm itted for m ax 0.5 sec. The current is,
how ever, lim ited by the adjustable frequency drive in-
verters safety lim it 0 sec. corresponds to no high
starttorque.
Description of choice:
Set the necessary tim e for w hich a high starttorque
is required.
120120 Startdelay(START DELAY)
Value:
0.0 - 10.0 sec. 0.0 sec.
Function:
This param eter enables a delay ofthe start-up tim e
after the conditions for starthave been ful lled.
W hen the tim e has passed, the output frequency w ill
startby ram ping up to the reference. Select the
m ode ofstartdelay in param eter 121 Start function.
Description of choice:
Set the necessary tim e before com m encing to accel-
erate.
121121 Start function
(START FUNCTION)
Value:
D C hold during startdelay tim e
(D C H O LD /D ELA Y TIM E) [0]
D C brake during startdelay tim e
(D C B R AK E/D ELA Y TIM E) [1]
C oasting during startdelay tim e
(C O AST/D ELA Y TIM E) [2]
Start frequency/voltage clockw ise(C LO C K W ISE O PE R A TIO N ) [3]
Startfrequency/voltage in reference direction
(VE RTIC AL O PER A TIO N ) [4]
Function:
C hoose the required m ode during the startdelay
tim e (param eter 120 Start delay time).
Description of choice:
Select DC hold during start delay time[0] to ener-
gize the m otorw ith a D C hold voltage during the
startdelay tim e. Set voltage in param eter 137 DChold voltage.
C hoose DC brake during start delay time[1] to ener-
gize the m otorw ith a D C brake voltage during the
startdelay tim e. Set voltage in param eter 132 DC
brake voltage.
C hoose Coasting during start delay time[2] and the
m otorw illnotbe controlled by the drive during the
start delay tim e (inverter turned off).
C hoose Start frequency/voltage clockwise[3] to ob-
tain the function described in param eters 130 Start
frequencyand 131 Voltage at startduring startdelay
tim e. Regardless ofthe value assum ed by the refer-
ence signal, the outputfrequency equals the setting
in param eter 130 Start frequencyand the output
voltage w illcorrespond to the setting in param eter
131 Voltage at start.
This functionality is typically used in hoist applica-
tions. It is used in particular in applications in w hich
a cone anchor m otor is applied, w here the direction
ofrotation is to startclockw ise follow ed by the refer-
ence direction.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 19
Progr
amming
-
7/26/2019 VLT2800[1].pdf
20/106
VLT 2800 Series
SelectStart frequency/voltage in reference direction
[4]to obtain the function described in param eter 130
Start frequencyand 131 Voltage at startduring thestartdelay tim e.
The direction ofm otor rotation w illalw ays follow the
reference direction. If the reference signal eq uals
zero, the output frequency w illequal0 H z,w hile the
outputvoltage w illcorrespond to the setting in pa-
ram eter 131 Voltage at start. If the reference signal
is different from zero, the outputfrequency w illeq ual
param eter 130 Start frequencyand the output volt-
age w illequalparam eter 131 Voltage at start. This
functionality is used typically for hoist applications
w ith counterw eight. It is used in particular for appli-
cations in w hich a cone anchor m otor is applied.
The cone anchor m otor can b reak aw ay using pa-
ram eter 130 Start frequencyand param eter 131
Voltage at start.
122122 Function at stop
(FUNCTION AT STOP)
Value:
C oasting (C O AST) [0]
D C hold (D C H O LD ) [1]
Function:
D eterm ines the function ofthe drive after the output
frequency has becom e low er than the value in pa-
ram eter 123 Min. frequency for activation of function
at stopor after a stop com m and and w hen the out-
putfrequency has been ram ped dow n to 0 H z.
Description of choice:
SelectCoasting[0] if the unit is to let goof the m o-
tor(inverter turned off).
Select D C hold [1] if param eter 137 DC hold voltage
is to be activated.
123123 Min. frequency for activation of function at
stop
(MIN.F.FUNC.STOP)
Value:
0.1 - 10 H z 0.1 H z
Function:
C hoose the output frequency at w hich the function
selected in param eter 122 Function at stopis to be
activated.
Description of choice:
Set the required output frequency.
126126 DC brake time
(DC BRAKING TIME)
Value:
0 - 60 sec. 10 sec
Function:
Select the D C brake tim e atw hich param eter 132DC brake voltageis to be active.
Description of choice:
Set the required tim e.
127127 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 (O FF) - par. 202 Output frequency high limit,
fMA X O FF
Function:
In this param eter, the D C brake cut-in frequency is
set at w hich the D C brake is to be activated in con-
nection w ith a stop com m and .
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark20
-
7/26/2019 VLT2800[1].pdf
21/106
VLT 2800 Series
Description of choice:
Set the required frequency.
128128 Thermal motor protection
(MOT.THERM PROTEC)
Value:
N o protection (N O PRO TE C TIO N ) [0]
Therm istor w arning
(TH ER M ISTO R W AR N ) [1]
Therm istor trip (TH ER M ISTO R TR IP) [2]
ETR w arning 1 (ETR W AR N IN G 1) [3]
ETR trip 1 (ETR TR IP 1) [4]
ETR w arning 2 (ETR W AR N IN G 2) [5]
ETR trip 2 (ETR TR IP 2) [6]
ETR w arning 3 (ETR W AR N IN G 3) [7]
ETR trip 3 (ETR TR IP 3) [8]
ETR w arning 4 (ETR W AR N IN G 4) [9]
ETR trip 4 (ETR TR IP 4) [10]
Function:
The adjustable frequency drive can m onitor the m o-
tortem perature in tw o different w ays:
- Via a PTC therm istor thatis m ounted on the
m otor. The therm istor is connected betw een ter-
m inal 50 (+10V) and one ofthe digital input
term inals 18,19,27 or 29. See param eter 300Digital inputs.
- Therm al load calculation (ETR - Electronic Ther-
m al R elay), based on present load and tim e. This
is com pared w ith the rated m otorcurrent IM ,Nand
rated m otorfrequency fM ,N.The calculations take
into accountthe need for low er loading at low
speeds due to the m otors internal ventilation be-
ing reduced.
ETR functions 1-4 do notbegin to calculate the load
untilyou sw itch to the Setup in w hich they havebeen selected. This m eans that you can use the
ETR function even w hen changing betw een tw o or
m ore m otors.
Description of choice:Select No protection[0] if you do notw ant a w arning
or trip w hen a m otoris overloaded.
Select Thermistor warning[1]if you w ant a w arning
w hen the connected therm istor becom es too w arm .
Select Thermistor trip[2]if you w ant a trip w hen the
connected therm istor becom es too w arm .
Select ETR WARNINGifyou w ant a w arning w hen
the m otor is overloaded according to the calcula-
tions. You can also program the adjustable frequency
drive to give a w arning signal via the digital output.
SelectETR Tripif you w ant a trip w hen the m otor is
overloaded according to the calculations.
Select ETR warning 1-4if you w ant a w arning w hen
the m otoris overloaded according to the calculations.
You can also program the adjustable frequency drive
to give a w arning signal via one ofthe digital out-
puts. SelectETR Trip 1- 4if you w ant a trip w hen the
m otoris overloaded according to the calculations.
NOTE!
This function cannot protectthe individual
m otors in the case ofm otors linked in parallel.
130130 Start frequency
(START FREQUENCY)
Value:
0.0 - 10.0 H z 0.0 H z
Function:
The startfrequency is active for the tim e set in pa-
ram eter 120 Start delay, after a start com m and . The
output frequency w illjum pto the next preset fre-
quency. C ertain m otors,such as conical anchor
m otors,need an extra voltage/start frequency
(boost) at startto disengage the m echanical brake.
To achieve this param eters 130 Start frequencyand
131 Initial voltageare used.
Description of choice:
Set the required startfrequency. It is a precondition
thatparam eter 121 Start function, is set to Start fre-
quency/voltage c lockwise[3] or Start frequency
voltage in reference direction[4] and that in param e-
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 21
Progr
amming
-
7/26/2019 VLT2800[1].pdf
22/106
VLT 2800 Series
ter 120 Start delaya tim e is set and a reference
signal is present.
131131 Initial voltage
(INITIAL VOLTAGE)
Value:
0.0 -200.0 V 0.0 V
Function:
Initial voltageis active for the tim e set in param eter
120 Start delay, after a startcom m and. This param -
eter can be used for exam ple for lifting/dropping
applications (conical anchor m otors).
Description of choice:
Set the required voltage necessary to cutout the
m echanical brake. It is assum ed thatparam eter 121
Start function, is setto Start frequency/voltage clock-
wise[3] or Start frequency/voltage in reference
direction[4] and thatin param eter 120 Start delaya
tim e is set, and that a reference signal is present.
132132 DC brake voltage
(DC BRAKE VOLTAGE)
Value:
0 -100% of m ax. D C brake voltage 0%
Function:
This param eter sets the D C brake voltage at w hich it
is to be activated at stop w hen the D C brake
frequency set in param eter 127 DC brake cut-in fre-
quencyis reached, or ifDC braking inverseis active
via a digital inp ut or via serial com m unication. S ub-
sequently,the D C brake voltage w illbe active for the
tim e set in param eter 126 DC brake time.
Description of choice:
To be set as a percentage value of the m ax. D C
brake voltage, w hich depends on the m otor.
133133 Start voltage
(START VOLTAGE)
Value:
0.00 - 100.00 V Depends on unit
Function:
A higher starttorque can be obtained by increasing
the start voltage. Sm all m otors (< 1.0 H P) norm ally
require a high startvoltage.
Description of choice:The factory setting w illbe suitable for m ost ap plica-
tions. The value m ay need to be increase gradually
for high torque application.
W arning: U se of exaggerated start
voltage m ay lead to over-energizing and
overheating the m otor. The drive m ay trip.
134134 Load compensation
(LOAD COMPENSATIO)
Value:
0.0 - 300.0% 100.0%
Function:
In this param eter, the load characteristic is set. B y
increasing the load com pensation, the m otoris given
an extra voltage and frequency sup plem ent at
increasing load s. This is used e.g. in m otors/applica-
tions in w hich there is a big difference betw een the
full-load current and idle-load current ofthe m otor.
NOTE!
If this value is set too
high, the drive m ay trip due to overcurrent.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark22
-
7/26/2019 VLT2800[1].pdf
23/106
VLT 2800 Series
Description of choice:
If the factory setting is notadequate, load com pen-
sation m ust be set to enable the m otorto startat the
given load.
W arning: S etto 0% in connection w ith
synchronous and parallel-coupled m otors
and in the cases ofquick load changes.
Too high load com pensation m ay lead to instability.
135135 U/f-ratio
(U/F RATIO)
Value:
0.00 - 20.00 at H z Depends on unit
Function:
This param eter enables a linear shift in the ratio be-
tw een output voltage (V) and outputfrequency (f) to
ensure correct energizing ofthe m otor and thus opti-
m um dynam ics, accuracy and ef ciency. The V/
f-ratio only affects the voltage characteristic ifCon-
stant torque[1] has been selected in param eter 101
Torque characteristic.
Description of choice:
C hange the V/f-ratio only if itis notpossible to set
the correct m otor data in param eters 102-109. The
value program m ed in the factory settings is based
on idle operation.
136136 Slip compensation
(SLIP COMP.)
Value:
-500 -+500% of rated slip com pensation
100%
Function:
Slip com pensation is calculated autom atically,on the
basis ofsuch data as the rated m otor speed nM ,N.In
this param eter, the slip com pensation can be ne
tuned, thereby com pensating for tolerances on the
value for nM ,N.Slip com pensation is only active if a
selection has been m ade ofSpeed regulation, open
loop[0]in param eter 100 Co nfigurationand Constant
torque[1] in param eter 101 Torque characteristic.
Description of choice:
Key in a % value.
137137 DC hold voltage
(DC HOLD VOLTAGE)
Value:
0 -100% of m ax. D C hold voltage 0%
Function:
This param eter is used to keep the m otor (holding
torque) at start/stop.
Description of choice:
This param eter can only be used if a selection has
been m ade of D C hold in param eter 121 Start func-
tionor122 Function at stop. Set as a percentage
value of the m ax. DC hold voltage, w hich depend s
on the choice ofm otor.
138138 Brake cut out value
(BRAKE CUT OUT)
Value:
0.5 - 132.0/1000.0 H z 3.0 H z
Function:
Select the frequency at w hich the external brake is
released, via the output de ned in param eter 323
Relay output 1-3or341 Digital outp ut, terminal 46.
Description of choice:
Set the required frequency.
139139 Brake cut in frequency
(BRAKE CUT IN)
Value:
0.5 - 132.0/1000.0 H z 3.0 H z
Function:
Select the frequency at w hich the external brake is
activated; this takes place via the outputde ned in
param eter 323 Relay output 1-3or341 Digital output
terminal 46.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 23
Progr
amming
-
7/26/2019 VLT2800[1].pdf
24/106
VLT 2800 Series
Description of choice:
Set the required frequency.
140140 Current, minimum value
(CURRENT MIN.VAL.)
Value:
0 % ofW ithin - 100 % ofW ithin 0 %
Function:
This is w here the user selects the m inim um m otor
current running for the m echanical brake to be re-
leased. C urrent m onitoring is active from stop until
the point w hen the brake is released .
Description of choice:
This is an extra safety precaution, aim ed at guaran-
teeing thatthe load is notlost during a lifting/
low ering operation.
142142 Spread reactance XL
(LEAK. REACTANCE)
Value:
0.000 - XXX.XXX
Depends on choice of m otor
Function:
After setting param eters 102-106 Nameplate data, a
num ber ofadjustm ents ofvarious param eter is m ade
autom atically,including the spread reactance X L.
The shaft perform ance m ay be im proved by ne tun-
ing the spread reactance XL
NOTE!
Param eter 142 Spread reactance XLis nor-
m ally notchanged if the nam eplate data have
been set in param eters 102-106.
Description of choice:
XLcan be set as follow s:
1. The value stated by the m otorsupplier.
2. U se the factory settings ofXLw hich the drive it-
self chooses on the basis ofthe m otor nam eplate
data.
143143 Internal fan control
(FAN CONTROL)
Value:
Autom atic (AU TO M A TIC ) [0]
Alw ays sw itched on (ALW A YS O N ) [1]
Alw ays sw itched off(ALW A YS O FF) [2]
Function:
This param eter can be set so that the internal fan is
autom atically sw itched on and off. You can also set
the internal fan to b e perm anently sw itched on or off.
Description of choice:
IfAutomatic[0]is selected, the internal fan is
sw itched on or offdepending on the am bient tem -
perature and the loading ofthe adjustable frequency
drive.
IfAlways switched on[1] or Always switched off [2]
is selected, the internal fan w illbe perm anently
sw itched on or off, respectively.
NOTE!
IfAlways switched off [2] is selected in com bi-
nation w ith high sw itch frequency, long m otor
cables or high outputpow er,the adjustable fre-
quency drives life span is reduced. This applies in
particular to 1.5,2,4 and 5 H P units.
144144 Gain AC brake
(GAIN AC BRAKE)
Value:
1.00 - 1.50 1.30
Function:This param eter is used to set the A C brake. U sing
par. 144 itis possible to adjust the size ofthe gener-
ator torque that can be applied to the m otorw ithout
the interm ediate circuit voltage exceeding the w arn-
ing level.
Description of choice:
The value is increased ifa greater possible brake
torque is required. If 1.0 is selected, this corre-
sponds to the AC brake being inactive.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark24
-
7/26/2019 VLT2800[1].pdf
25/106
VLT 2800 Series
NOTE!
If the value in par. 144 is increased, the
m otor current w illsim ultaneously increase sig-
ni cantly w hen generator loads are applied. The
param eter should therefore only be changed if it is
guaranteed during m easurem ent that the m otor cur-
rent in alloperating situations w illnever exceed the
m axim um perm itted current in the m otor.Please
note: that the current cannotbe read outfrom the
display.
146146 Reset voltage vector
(RESET VECTOR)
Value:*O ff (O FF) [0]
R eset (R ES ET) [1]
Function:
W hen the voltage vector is reset itis set to the sam e
starting point each tim e a new process com m ences.
Description of choice:
Select reset (1) w hen running unique processes
each tim e they arise. This w illenable repetitive pre-
cision w hen stopping to be im proved. S elect O ff (0)
for exam ple for lifting/low ering operations or syn-
chronous m otors. It is an advantage that the m otor
and the adjustable frequency drive are alw ays syn-
chronized.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 25
Progr
amming
-
7/26/2019 VLT2800[1].pdf
26/106
VLT 2800 Series
References & Limits
200200 Output frequency range
(OUT FREQ. RNG/ROT)
Value:
O nly clockw ise, 0 - 132 H z
(132 H Z C LO C K W ISE) [0]
B oth directions, 0 - 132 H z
(132 H Z B O TH D IR EC T) [1]
Anti-clockw ise only,0 - 132 H z
(132 H Z C O U N TER C LO C K) [2]
C lockw ise only,0 - 1000 H z
(1000 H Z C LO C K W ISE) [3]
B oth directions, 0 - 1000 H z
(1000 H Z B O TH D IR EC T) [4]
Anti-clockw ise only,0 - 1000 H z
(1000 H Z C O U N TER C LO C K) [5]
Function:
This param eter guarantees protection against un-
w anted reversing. Furtherm ore, the m axim um output
frequency can be selected thatw illapply regardless
ofthe settings ofother param eters. This param eter
has no function ifProcess regulation, closed loop
has been selected in param eter 100 Co nfiguration.
Description of choice:
Select the required direction ofrotation as w ellas
the m axim um output frequency. Please note thatif
Clockwise only[0]/[3] orAnti-clockwise only[2]/[5] is
selected , the outputfreq uency w illbe lim ited to the
range fM IN-fM AX. IfBoth directions[1]/[4] is selected,
the outputfreq uency w illbe lim ited to the range
fM AX(the m inim um frequency is ofno signicance).
201201 Output frequency low limit, fMIN
(MINOUTPUT FREQ)
Value:
0.0 - fM AX 0.0 H z
Function:
In this param eter, a m inim um m otorfrequency lim it
can be selected thatcorresp onds to the m inim um
speed at w hich the m otor is allow ed to run. IfBoth
directionshas been selected in param eter 200 Out-
put frequency range, the m inim um frequency is of no
signicance.
Description of choice:
The value chosen can range from 0.0 H z to the fre-
quency set in param eter 202 Output frequency high
limit, f MAX.
202202 Output frequency high limit, fMAX
(MAX. OUTPUT FREQUENCY)
Value:
fM IN- 132/1000 H z (par. 200 Output frequency
range)
132 H z
Function:
In this param eter, a m axim um outputfrequency lim it
can be selected thatcorresponds to the highest
speed at w hich the m otor is allow ed to run.
NOTE!
The output frequency ofthe drive can
never assum e a value higher than 1/10 of the
sw itching frequency (param eter 411 Switching fre-
quency).
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark26
-
7/26/2019 VLT2800[1].pdf
27/106
VLT 2800 Series
Description of choice:
A value can be selected from fM INto the value cho-
sen in param eter 200 Output frequency range.
203203 Reference range
(REFERENCE RANGE)
Value:
M in. reference - M ax reference (M IN - M AX) [0]
-M ax. reference - M ax. reference (-M AX - +M AX)[1]
Function:
In this param eter you select w hether the reference
signal m ust be positive or w hether it can be both
positive and negative. The m inim um lim it m ay be anegative value, unless in param eter 100 Co nfigura-
tiona selection has been m ade ofSpeed regulation,
closed loop. You should selectMin ref. - Max. ref.
[0], ifProcess regulation, closed loop[3] has been
selected in param eter 100 Co nfiguration.
Description of choice:
Select the required range.
204204 Minimum reference, RefMIN
(MIN.REFERENCE)
Value:
Par. 100 Co nfig.= Open loop[0].
-100,000.000 - par. 205 R efM AX 0.000 H z
Par. 100 Co nfig.= Closed loop[1]/[3].
-Par. 414 Minimum feedback- par. 205 RefMA X
0.000 H z
Function:
M inim um reference is an expression ofthe m inim um
possible value ofthe totalofallreferences. If in pa-
ram eter 100 Co nfiguration
, Speed regulation, closed
loop[1] or Process regulation, closed loop[3] is
selected, the m inim um reference is lim ited by param -
eter 414 Minimum feedback. M inim um reference is
ignored ifthe localreference is active.
The reference unit can be de ned from the follow ing
table:
Par. 100 Co nfiguration U nit
O pen loop [0] H z
Speed reg,closed loop [1] rpm
Process reg,closed loop [3] Par. 416
Description of choice:
The m inim um reference is preset if the m otor has to
run at a m inim um speed, regardless of w hether the
resulting reference is 0.
205205 Maximumreference, RefMAX
(MAX.REFERENCE)
Value:
Par. 100 Co nfig.= Open loop[0].
Par. 204 RefMIN- 1000.000 H z 50.000 H z
Par. 100 Co nfig.= Closed loop[1]/[3].
Par. 204 R efM IN- Par. 415 Max. feedback
50.000 H z
Function:
The m axim um reference gives the highest value that
can be assum ed by the sum of allreferences. If
Closed loop[1]/[3]is selected in param eter 100 Con-
figurationthe m axim um reference cannot exceed the
value in param eter 415 Maximum feedback.
M axim um reference is ignored if the local reference
is active.
The reference unit can be de ned from the follow ing
table:
Par. 100 Co nfiguration U nit
O pen loop [0] H z
Speed reg,closed loop [1] rpm
Process reg,closed loop [3] Par. 416
Description of choice:
M axim um reference is set, if the speed ofthe m otor
is to be the m ax. of the set value, regardless ofthe
w hether the resulting reference is greater than the
m axim um reference.
206206 Ramp type
(RAMP TYPE)
Value:
Linear (LIN EA R ) [0]
Sine-shaped (S-SH APED ) [1]
Sine 2- shaped (S 2) [2]
Function:
You can choose betw een a linear, a sine-shaped
and a sine2-shaped ram p process.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 27
Progr
amming
-
7/26/2019 VLT2800[1].pdf
28/106
VLT 2800 Series
Description of choice:
Select the required ram p type depending on require-
m entsfor the acceleration/deceleration process.
207207 Ramp-up time 1
(RAMP-UP TIME 1)
Value:
0.02 - 3600.00 sec 3.00 sec
Function:
The ram p-up tim e is the acceleration tim e from 0 H z
to the rated m otor frequency fM ,N(param eter 104
Motor frequency, fM, N). It is assum ed that the output
current w illnotreach the current lim it (set in param e-
ter 221 Current limit ILIM
).
Description of choice:Set the required ram p-up tim e.
208208 Ramp-downtime 1
(RAMP DOWN TIME 1)
Value:
0.02 - 3600.00 sec 3.00 sec
Function:
The ram p-dow n tim e is the deceleration tim e from
the rated m otorfrequency fM ,N(param eter 104 Motorfrequency, f M, N) to 0 H z,provided no overvoltage
arises in the inverter because ofgenerating opera-
tion ofthe m otor.
Description of choice:Set the required ram p-dow n tim e.
209209 Ramp-up time 2
(RAMP UP TIME 2)
Value:
0.02 - 3600.00 sec. 3.00 sec
Function:
See description ofparam eter 207 Ramp-up time 1.
Description of choice:Set the required ram p-up tim e. Shift from ram p 1 to
ram p 2 by activating Ramp 2via a digitalinput.
210210 Ramp-downtime 2
(RAMP DOWN TIME 2)
Value:
0.02 - 3600.00 sec. 3.00 sec
Function:
See description ofparam eter 208 Ramp-down time1.
Description of choice:
Set the required ram p-dow n tim e. Shift from ram p 1
to ram p 2 by activating Ramp 2via a digitalinput.
211211 J og ramp time
(J OG RAMP TIME)
Value:
0.02 - 3600.00 sec. 3.00 sec
Function:
The jog ram p tim e is the acceleration/deceleration
tim e from 0 H z to the rated m otor freq uency fM ,N
(param eter 104 Motor frequency, f M, N). It is assum ed
that the outputcurrent w illnotreach the current lim it
(set in param eter 221 Current limit ILIM).
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark28
-
7/26/2019 VLT2800[1].pdf
29/106
VLT 2800 Series
The jog ram p tim e starts if a jog-signal is given via
the LC P controlpanel, one ofthe digital inputs orthe
serial com m unication port.
Description of choice:
Set the required ram p tim e.
212212 Quick-stopramp-downtime
(Q STOP RAMP TIME)
Value:
0.02 - 3600.00 sec. 3.00 sec
Function:
The quick-stop ram p-dow n tim e is the deceleration
tim e from the rated m otor frequency to 0 H z, pro-
vided no overvoltage arises in the inverter because
ofgenerating operation ofthe m otor,or if the gener-
ated current exceeds the current lim it in param eter
221 Current limit ILIM.Q uick-stop is activated via one
ofthe digital inputs or the serial com m unication.
Description of choice:
Set the required ram p-dow n tim e.
213213 J og frequency
(J OG FREQUENCY)
Value:
0.0 - Par. 202 O utput frequency high lim it, fM AX
10.0 H z
Function:
Jog frequency fJO Gm eans a xed outputfrequency
that the adjustable frequency drive supplies to the
m otor w hen the Jog function is activated. Jog can
be activated via the digital inputs, serial com m unica-
tion or via the LC P controlpanel, on the cond ition
that this is active in param eter 015 Local jog.
Description of choice:
Set the required frequency.
214214 Reference function
(REFERENCE FUNCTION)
Value:
Sum (SU M ) [0]
R elative (R ELA TIVE) [1]
External/preset (EXTER N AL/PR ESET) [2]
Function:
It is possible to de ne how preset references are to
be added to the other references; for this purpose,
use Sumor Relative. It is also possible by using theExternal/presetto select w hether a shift betw een ex-
ternal references and preset references is required.
External reference is the sum ofthe analog refer-
ences, pulse references and any references from
serial com m unication.
Description of choice:
IfSum[0]is selected, one ofthe adjusted preset ref-
erences (param eters 215-218 Preset reference) is
sum m arized as a percentage ofthe reference range
(R efM IN-R efM AX), added to the other external refer-
ences.IfRelative[1] is selected, one ofthe added preset
references (param eters 215-218 Preset reference) is
sum m arized as a percentage ofthe sum of present
external references.
IfExternal/preset[2]is selected, it is possible via a
digital inp ut to shift betw een external references or
preset references. Preset references w illbe a per-
centage value ofthe reference range.
NOTE!
If Sum or R elative is selected, one ofthe
preset references w illalw ays be active. If the
preset references are to be w ithoutin uence, they
m ust be set to 0% (factory setting).
215215 Preset reference1 (PRESET REF. 1)
216216 Preset reference2 (PRESET REF. 2)
217217 Preset reference3 (PRESET REF. 3)
218218 Preset reference4 (PRESET REF. 4)
Value:
-100.00% to +100.00% 0.00%
ofthe reference range/external reference
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark 29
Progr
amming
-
7/26/2019 VLT2800[1].pdf
30/106
VLT 2800 Series
Function:
Four different preset references can be program m ed
in param eters 215-218 Preset reference.
The preset reference is stated as a percentage ofthe reference range (R efM IN-R efM AX) or as a per-
centage ofthe other external references, depending
on the choice m ade in param eter 214 Reference
function. The choice betw een preset references can
be m ade via the digital inputs or via serial com m uni-
cation.
Preset ref., m sb Preset ref. lsb
0 0 Preset ref. 1
0 1 Preset ref. 2
1 0 Preset ref. 31 1 Preset ref. 4
Description of choice:
Set the options for the preset reference(s).
219219 Catch up/Slow down reference
(CATCH UP/SLWDWN)
Value:
0.00 - 100% of the given reference 0.00%
Function:
In this param eter, the percentage value can be set
w hich w illeither be ad ded to or deducted from the
rem ote-controlled references.
The rem ote-controlled reference is the sum ofpreset
references, analog references, pulse reference and
any references from serial com m unication.
Description of choice:
IfCatch upis active via a digital input,the percent-
age value in param eter 219 Catch up/Slow down
referencew illbe added to the rem ote-controlled ref-erence.
IfSlow downis active via a digitalinput,the percent-
age value in param eter 219 Catch up/Slow down
referencew illbe deducted from the rem ote con-
trolled reference.
221221 Current limit, ILIM
(CURRENT LIMIT)
Value:
0 - XXX.X % ofpar. 105 160 %
Function:
In this param eter, the m axim um outputcurrent ILIMis
set. The factory-set value corresponds to the m axi-
m um outputcurrent IM AX. If the current lim it is to be
used as m otorprotection, set the rated m otorcur-
rent. If the current lim it is set above 100% (the ratedoutput current of the drive, IIN V .), the unit can only
handle a load interm ittently,i.e. for shortperiods at
a tim e. A fter the load has been higher than IIN V .,it
m ust be ensured thatfor a period the load is low er
than IIN V .. Please note that if the current lim it is set
at a low er value than IIN V .,the acceleration torque
w illbe reduced to the sam e extent.
Description of choice:
Set the required m axim um output current ILIM.
223223 Warning: Low current, ILOW
(WARN. CURRENT LO)
Value:
0.0 - par. 224 Warning: High current, IHIGH 0.0 A
Function:
If the outputcurrent falls below the preset lim it ILO W
a w arning is given.
Param eters 223-228 Warning functionsare out of
function during ram p-up after a startcom m and and
after a stop com m and or during stop. The w arningfunctions are activated w hen the outputfrequency
reaches the resulting reference. The signal outputs
can be program m ed to give a w arning signal via ter-
m inal 46 and via the relay output.
Description of choice:
The low er signal lim it ofthe outputcurrent ILAVm ust
be program m ed w ithin the norm al w orking range of
the unit.
= factory setting. () = display text []= value for use in com m unication via serial com m unication port
M G .28.A4.2G - VLT is a registered D anfoss trade m ark30
-
7/26/2019 VLT2800[1].pdf
31/106
VLT 2800 Series
224224 Warning: High current, IHIGH
(WARN. CURRENT HI)
Value:
Par. 223 Warn.: Low current, ILOW-IM AX IM AX
Function:
If the output current exceeds the preset lim it IH IG Ha
w arning is given.
Param eters 223-228 Warning functionsdo notw ork
during ram p-up after a startcom m and, after stop
com m and or during stop. The w arning functions are
activated w hen the output frequency reaches the
resulting reference. The signal outputs can be pro-
gram m ed to give a w arning signal via term inal 46
and via the relay output.
Description of choice:
The output currents upper signal lim it IH IG Hm ustbe
program m ed w ithin the adjustable frequency drives
norm aloperating range. See draw ing at param eter
223 Warning: Low current, ILOW.
225225 Warning: Low frequency, fLOW
(WARN.FREQ. LOW)
Value:
0.0 - par. 226 Warn.: High frequency, f HIGH0.0 H z
Function:
If the outputfrequency falls below the preset lim it
fLO W,a w arning is given.
Param eters 223-228 Warning functionsare out of
function during ram p-up after a startcom m and,after
stop com m and or during stop. The w arning functions
are activated w hen the output frequency reaches the
resulting reference. The signal outputs can be pro-
gram m ed to give a w arning signal via term inal 46
and via the relay output.
Description of choice:
The low er signal lim it ofthe outputfrequency fLO W
m ust be program m ed w ithin the norm aloperating
range ofthe adjustable frequency drive. See draw -
ing at param eter 223 Warning: Low current, ILOW.
226226 Warning: High frequency fHIGH
(WARN.FREQ.HIGH)
Value:Par. 200 Frequency range= 0-132 H z [0]/[1].
par. 225 fLO W- 132 H z 132.0 H z
Par. 200 Frequency range= 0-1000 H z [2]/[3].
par. 225 fLO W- 1000 H z 132.0 H z
Function:
If the output frequency exceeds the preset lim it fH IG H
a w arning is given.
Param eters 223-228 Warning functionsdo notw ork
during ram p-up after a startcom