· web viewthe approach obtained is a function of thermal conditions and tower capability....
TRANSCRIPT
K Handouts
Faculty Dr Parin Shah amp Prof Ronak Patel
Lecture No 1-2
Introduction of Boilers Indian Boilers Regulation (IBR) Boiler Systems Boiler
Types and Classifications Fire tube boilers Water tube boilers Packaged Boiler
Stoker Fired Boiler Chain-Grate or Travelling-Grate Stoker Boiler Spreader Stoker
Boiler Pulverized Fuel Boiler Fluidized Bed Boiler
A boiler is an enclosed vessel that provides a means for combustion heat to be
transferred into water until it becomes heated water or steam The hot water or steam
under pressure is then usable for transferring the heat to a process Water is a useful
and cheap medium for transferring heat to a process When water is boiled into steam
its volume increases about 1600 times producing a force that is almost as explosive
as gunpowder This causes the boiler to be extremely dangerous equipment that must
be treated with utmost care
The process of heating a liquid until it reaches its gaseous state is called evaporation
Heat is transferred from one body to another by means of (1) radiation which is the
transfer of heat from a hot body to a cold body without a conveying medium (2)
convection the transfer of heat by a conveying medium such as air or water and (3)
conduction transfer of heat by actual physical contact molecule to molecule
Indian Boiler Regulation
The Indian Boilers Act was enacted to consolidate and amend the law relating to
steam boilers Indian Boilers Regulation (IBR) was created in exercise of the powers
conferred by section 28 amp 29 of the Indian Boilers Act
IBR Steam Boilers means any closed vessel exceeding 2275 liters in capacity and
which is used expressively for generating steam under pressure and includes any
mounting or other fitting attached to such vessel which is wholly or partly under
pressure when the steam is shut off
The boiler system comprises of feed water system steam system and fuel system
The feed water system provides water to the boiler and regulates it automatically to
meet the steam demand Various valves provide access for maintenance and repair
The steam system collects and controls the steam produced in the boiler Steam is
directed through a piping system to the point of use Throughout the system steam
pressure is regulated using valves and checked with steam pressure gauges The fuel
system includes all equipment used to provide fuel to generate the necessary heat
The equipment required in the fuel system depends on the type of fuel used in the
system The boiler system comprises of feed water system steam system and fuel
system The feed water system provides water to the boiler and regulates it
automatically to meet the steam demand Various valves provide access for
maintenance and repair The steam system collects and controls the steam produced
in the boiler Steam is directed through a piping system to the point of use
Throughout the system steam pressure is regulated using valves and checked with
steam pressure gauges The fuel system includes all equipment used to provide fuel to
generate the necessary heat The equipment required in the fuel system depends on the
type of fuel used in the system
Lecture No 3-4 Performance Evaluation of Boilers
Boiler Efficiency Direct Method Indirect Method Examples related to these
methods
Boiler Efficiency Thermal efficiency of boiler is defined as the percentage of heat input that is effectively utilised to generate steam There are two methods of assessing boiler efficiency
1) The Direct Method Where the energy gain of the working fluid (water and steam) is compared with the energy content of the boiler fuel
2) The Indirect Method Where the efficiency is the difference between the losses and the energy input
Advantages of direct method
Plant people can evaluate quickly the efficiency of boilers
Requires few parameters for computation
Needs few instruments for monitoring
Disadvantages of direct method
Does not give clues to the operator as to why efficiency of system is lower
Does not calculate various losses accountable for various efficiency levels
Lecture No 5-6 Boiler Blowdown
Conductivity as Indicator of Boiler Water Quality Intermittent Blowdown
Continuous Blowdown Blowdown calculations Benefits of Blowdown
When water is boiled and steam is generated any dissolved solids contained in the water
remain in the boiler If more solids are put in with the feed water they will concentrate
and may eventually reach a level where their solubility in the water is exceeded and they
deposit from the solution Above a certain level of concentration these solids encourage
foaming and cause carryover of water into the steam The deposits also lead to scale
formation inside the boiler resulting in localized overheating and finally causing boiler
tube failure It is therefore necessary to control the level of concentration of the solids
and this is achieved by the process of blowing down where a certain volume of water is
blown off and is automatically replaced by feed water - thus maintaining the optimum
level of total dissolved solids (TDS) in the boiler water Blow down is necessary to
protect the surfaces of the heat exchanger in the boiler However blow down can be a
significant source of heat loss if improperly carried out
Conductivity as Indicator of Boiler Water Quality
Since it is tedious and time consuming to measure total dissolved solids (TDS) in boiler
water system conductivity measurement is used for monitoring the overall TDS present
in the boiler A rise in conductivity indicates a rise in the contamination of the boiler
water
Conventional methods for blowing down the boiler depend on two kinds of blowdown -
intermittent and continuous
Intermittent Blowdown
The intermittent blown down is given by manually operating a valve fitted to discharge
pipe at the lowest point of boiler shell to reduce parameters (TDS or conductivity pH
Silica and Phosphates concentration) within prescribed limits so that steam quality is not
likely to be affected In intermittent blowdown a large diameter line is opened for a short
period of time the time being based on a thumb rule such as ldquoonce in a shift for 2
minutesrdquo
Intermittent blowdown requires large short-term increases in the amount of feed water
put into the boiler and hence may necessitate larger feed water pumps than if continuous
blow down is used Also TDS level will be varying thereby causing fluctuations of the
water level in the boiler due to changes in steam bubble size and distribution which
accompany changes in concentration of solids Also substantial amount of heat energy is
lost with intermittent blowdown
Continuous Blowdown
There is a steady and constant dispatch of small stream of concentrated boiler water and
replacement by steady and constant inflow of feed water This ensures constant TDS and
steam purity at given steam load Once blow down valve is set for a given conditions
there is no need for regular operator intervention
Even though large quantities of heat are wasted opportunity exists for recovering this
heat by blowing into a flash tank and generating flash steam This flash steam can be used
for pre-heating boiler feed water or for any other purpose
Benefits of Blowdown
Good boiler blow down control can significantly reduce treatment and operational costs
that include
Lower pre-treatment costs
Less make-up water consumption
Reduced maintenance downtime
Increased boiler life
Lower consumption of treatment chemicals
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
meet the steam demand Various valves provide access for maintenance and repair
The steam system collects and controls the steam produced in the boiler Steam is
directed through a piping system to the point of use Throughout the system steam
pressure is regulated using valves and checked with steam pressure gauges The fuel
system includes all equipment used to provide fuel to generate the necessary heat
The equipment required in the fuel system depends on the type of fuel used in the
system The boiler system comprises of feed water system steam system and fuel
system The feed water system provides water to the boiler and regulates it
automatically to meet the steam demand Various valves provide access for
maintenance and repair The steam system collects and controls the steam produced
in the boiler Steam is directed through a piping system to the point of use
Throughout the system steam pressure is regulated using valves and checked with
steam pressure gauges The fuel system includes all equipment used to provide fuel to
generate the necessary heat The equipment required in the fuel system depends on the
type of fuel used in the system
Lecture No 3-4 Performance Evaluation of Boilers
Boiler Efficiency Direct Method Indirect Method Examples related to these
methods
Boiler Efficiency Thermal efficiency of boiler is defined as the percentage of heat input that is effectively utilised to generate steam There are two methods of assessing boiler efficiency
1) The Direct Method Where the energy gain of the working fluid (water and steam) is compared with the energy content of the boiler fuel
2) The Indirect Method Where the efficiency is the difference between the losses and the energy input
Advantages of direct method
Plant people can evaluate quickly the efficiency of boilers
Requires few parameters for computation
Needs few instruments for monitoring
Disadvantages of direct method
Does not give clues to the operator as to why efficiency of system is lower
Does not calculate various losses accountable for various efficiency levels
Lecture No 5-6 Boiler Blowdown
Conductivity as Indicator of Boiler Water Quality Intermittent Blowdown
Continuous Blowdown Blowdown calculations Benefits of Blowdown
When water is boiled and steam is generated any dissolved solids contained in the water
remain in the boiler If more solids are put in with the feed water they will concentrate
and may eventually reach a level where their solubility in the water is exceeded and they
deposit from the solution Above a certain level of concentration these solids encourage
foaming and cause carryover of water into the steam The deposits also lead to scale
formation inside the boiler resulting in localized overheating and finally causing boiler
tube failure It is therefore necessary to control the level of concentration of the solids
and this is achieved by the process of blowing down where a certain volume of water is
blown off and is automatically replaced by feed water - thus maintaining the optimum
level of total dissolved solids (TDS) in the boiler water Blow down is necessary to
protect the surfaces of the heat exchanger in the boiler However blow down can be a
significant source of heat loss if improperly carried out
Conductivity as Indicator of Boiler Water Quality
Since it is tedious and time consuming to measure total dissolved solids (TDS) in boiler
water system conductivity measurement is used for monitoring the overall TDS present
in the boiler A rise in conductivity indicates a rise in the contamination of the boiler
water
Conventional methods for blowing down the boiler depend on two kinds of blowdown -
intermittent and continuous
Intermittent Blowdown
The intermittent blown down is given by manually operating a valve fitted to discharge
pipe at the lowest point of boiler shell to reduce parameters (TDS or conductivity pH
Silica and Phosphates concentration) within prescribed limits so that steam quality is not
likely to be affected In intermittent blowdown a large diameter line is opened for a short
period of time the time being based on a thumb rule such as ldquoonce in a shift for 2
minutesrdquo
Intermittent blowdown requires large short-term increases in the amount of feed water
put into the boiler and hence may necessitate larger feed water pumps than if continuous
blow down is used Also TDS level will be varying thereby causing fluctuations of the
water level in the boiler due to changes in steam bubble size and distribution which
accompany changes in concentration of solids Also substantial amount of heat energy is
lost with intermittent blowdown
Continuous Blowdown
There is a steady and constant dispatch of small stream of concentrated boiler water and
replacement by steady and constant inflow of feed water This ensures constant TDS and
steam purity at given steam load Once blow down valve is set for a given conditions
there is no need for regular operator intervention
Even though large quantities of heat are wasted opportunity exists for recovering this
heat by blowing into a flash tank and generating flash steam This flash steam can be used
for pre-heating boiler feed water or for any other purpose
Benefits of Blowdown
Good boiler blow down control can significantly reduce treatment and operational costs
that include
Lower pre-treatment costs
Less make-up water consumption
Reduced maintenance downtime
Increased boiler life
Lower consumption of treatment chemicals
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 3-4 Performance Evaluation of Boilers
Boiler Efficiency Direct Method Indirect Method Examples related to these
methods
Boiler Efficiency Thermal efficiency of boiler is defined as the percentage of heat input that is effectively utilised to generate steam There are two methods of assessing boiler efficiency
1) The Direct Method Where the energy gain of the working fluid (water and steam) is compared with the energy content of the boiler fuel
2) The Indirect Method Where the efficiency is the difference between the losses and the energy input
Advantages of direct method
Plant people can evaluate quickly the efficiency of boilers
Requires few parameters for computation
Needs few instruments for monitoring
Disadvantages of direct method
Does not give clues to the operator as to why efficiency of system is lower
Does not calculate various losses accountable for various efficiency levels
Lecture No 5-6 Boiler Blowdown
Conductivity as Indicator of Boiler Water Quality Intermittent Blowdown
Continuous Blowdown Blowdown calculations Benefits of Blowdown
When water is boiled and steam is generated any dissolved solids contained in the water
remain in the boiler If more solids are put in with the feed water they will concentrate
and may eventually reach a level where their solubility in the water is exceeded and they
deposit from the solution Above a certain level of concentration these solids encourage
foaming and cause carryover of water into the steam The deposits also lead to scale
formation inside the boiler resulting in localized overheating and finally causing boiler
tube failure It is therefore necessary to control the level of concentration of the solids
and this is achieved by the process of blowing down where a certain volume of water is
blown off and is automatically replaced by feed water - thus maintaining the optimum
level of total dissolved solids (TDS) in the boiler water Blow down is necessary to
protect the surfaces of the heat exchanger in the boiler However blow down can be a
significant source of heat loss if improperly carried out
Conductivity as Indicator of Boiler Water Quality
Since it is tedious and time consuming to measure total dissolved solids (TDS) in boiler
water system conductivity measurement is used for monitoring the overall TDS present
in the boiler A rise in conductivity indicates a rise in the contamination of the boiler
water
Conventional methods for blowing down the boiler depend on two kinds of blowdown -
intermittent and continuous
Intermittent Blowdown
The intermittent blown down is given by manually operating a valve fitted to discharge
pipe at the lowest point of boiler shell to reduce parameters (TDS or conductivity pH
Silica and Phosphates concentration) within prescribed limits so that steam quality is not
likely to be affected In intermittent blowdown a large diameter line is opened for a short
period of time the time being based on a thumb rule such as ldquoonce in a shift for 2
minutesrdquo
Intermittent blowdown requires large short-term increases in the amount of feed water
put into the boiler and hence may necessitate larger feed water pumps than if continuous
blow down is used Also TDS level will be varying thereby causing fluctuations of the
water level in the boiler due to changes in steam bubble size and distribution which
accompany changes in concentration of solids Also substantial amount of heat energy is
lost with intermittent blowdown
Continuous Blowdown
There is a steady and constant dispatch of small stream of concentrated boiler water and
replacement by steady and constant inflow of feed water This ensures constant TDS and
steam purity at given steam load Once blow down valve is set for a given conditions
there is no need for regular operator intervention
Even though large quantities of heat are wasted opportunity exists for recovering this
heat by blowing into a flash tank and generating flash steam This flash steam can be used
for pre-heating boiler feed water or for any other purpose
Benefits of Blowdown
Good boiler blow down control can significantly reduce treatment and operational costs
that include
Lower pre-treatment costs
Less make-up water consumption
Reduced maintenance downtime
Increased boiler life
Lower consumption of treatment chemicals
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 5-6 Boiler Blowdown
Conductivity as Indicator of Boiler Water Quality Intermittent Blowdown
Continuous Blowdown Blowdown calculations Benefits of Blowdown
When water is boiled and steam is generated any dissolved solids contained in the water
remain in the boiler If more solids are put in with the feed water they will concentrate
and may eventually reach a level where their solubility in the water is exceeded and they
deposit from the solution Above a certain level of concentration these solids encourage
foaming and cause carryover of water into the steam The deposits also lead to scale
formation inside the boiler resulting in localized overheating and finally causing boiler
tube failure It is therefore necessary to control the level of concentration of the solids
and this is achieved by the process of blowing down where a certain volume of water is
blown off and is automatically replaced by feed water - thus maintaining the optimum
level of total dissolved solids (TDS) in the boiler water Blow down is necessary to
protect the surfaces of the heat exchanger in the boiler However blow down can be a
significant source of heat loss if improperly carried out
Conductivity as Indicator of Boiler Water Quality
Since it is tedious and time consuming to measure total dissolved solids (TDS) in boiler
water system conductivity measurement is used for monitoring the overall TDS present
in the boiler A rise in conductivity indicates a rise in the contamination of the boiler
water
Conventional methods for blowing down the boiler depend on two kinds of blowdown -
intermittent and continuous
Intermittent Blowdown
The intermittent blown down is given by manually operating a valve fitted to discharge
pipe at the lowest point of boiler shell to reduce parameters (TDS or conductivity pH
Silica and Phosphates concentration) within prescribed limits so that steam quality is not
likely to be affected In intermittent blowdown a large diameter line is opened for a short
period of time the time being based on a thumb rule such as ldquoonce in a shift for 2
minutesrdquo
Intermittent blowdown requires large short-term increases in the amount of feed water
put into the boiler and hence may necessitate larger feed water pumps than if continuous
blow down is used Also TDS level will be varying thereby causing fluctuations of the
water level in the boiler due to changes in steam bubble size and distribution which
accompany changes in concentration of solids Also substantial amount of heat energy is
lost with intermittent blowdown
Continuous Blowdown
There is a steady and constant dispatch of small stream of concentrated boiler water and
replacement by steady and constant inflow of feed water This ensures constant TDS and
steam purity at given steam load Once blow down valve is set for a given conditions
there is no need for regular operator intervention
Even though large quantities of heat are wasted opportunity exists for recovering this
heat by blowing into a flash tank and generating flash steam This flash steam can be used
for pre-heating boiler feed water or for any other purpose
Benefits of Blowdown
Good boiler blow down control can significantly reduce treatment and operational costs
that include
Lower pre-treatment costs
Less make-up water consumption
Reduced maintenance downtime
Increased boiler life
Lower consumption of treatment chemicals
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
water level in the boiler due to changes in steam bubble size and distribution which
accompany changes in concentration of solids Also substantial amount of heat energy is
lost with intermittent blowdown
Continuous Blowdown
There is a steady and constant dispatch of small stream of concentrated boiler water and
replacement by steady and constant inflow of feed water This ensures constant TDS and
steam purity at given steam load Once blow down valve is set for a given conditions
there is no need for regular operator intervention
Even though large quantities of heat are wasted opportunity exists for recovering this
heat by blowing into a flash tank and generating flash steam This flash steam can be used
for pre-heating boiler feed water or for any other purpose
Benefits of Blowdown
Good boiler blow down control can significantly reduce treatment and operational costs
that include
Lower pre-treatment costs
Less make-up water consumption
Reduced maintenance downtime
Increased boiler life
Lower consumption of treatment chemicals
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 7-8 Boiler Water Treatment Deposit Control Impurities causing deposits Silica Internal Water Treatment External Water Treatment Ion-exchange process (Softener Plant) De-aeration Mechanical de-aeration Chemical de-aeration Reverse Osmosis Recommended boiler and feed water quality
Boiler Water Treatment Producing quality steam on demand depends on properly
managed water treatment to control steam purity deposits and corrosion A boiler is the
sump of the boiler system It ultimately receives all of the pre-boiler contaminants Boiler
performance efficiency and service life are direct products of selecting and controlling
feed water used in the boiler
When feed water enters the boiler the elevated temperatures and pressures cause the
components of water to behave differently Most of the components in the feed water are
soluble However under heat and pressure most of the soluble components come out of
solution as particulate solids sometimes in crystallized forms and other times as
amorphous particles When solubility of a specific component in water is exceeded scale
or deposits develop The boiler water must be sufficiently free of deposit forming solids
to allow rapid and efficient heat transfer and it must not be corrosive to the boiler metal
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 9-10 Energy Conservation Opportunities
Stack Temperature Feed Water Preheating using Economiser Combustion Air
Preheat Incomplete Combustion Excess Air Control Radiation and Convection Heat
Loss Automatic Blowdown Control Reduction of Scaling and Soot
Losses Reduction of Boiler Steam Pressure Variable Speed Control for Fans
Blowers and Pumps Effect of Boiler Loading on Efficiency Proper Boiler
Scheduling Boiler Replacement
Stack Temperature
The stack temperature should be as low as possible However it should not be so low
that water vapor in the exhaust condenses on the stack walls This is important in fuels
containing signficant sulphur as low temperature can lead to sulphur dew point
corrosion Stack temperatures greater than 200degC indicates potential for recovery of
waste heat It also indicate the scaling of heat transferrecovery equipment and hence
the urgency of taking an early shut down for water flue side cleaning
Feed Water Preheating using Economiser Typically the flue gases leaving a
modern 3-pass shell boiler are at temperatures of 200 to 300 oC Thus there is a
potential to recover heat from these gases The flue gas exit temperature from a boiler
is usually maintained at a minimum of 200 oC so that the sulphur oxides in the flue
gas do not condense and cause corrosion in heat transfer surfaces When a clean fuel
such as natural gas LPG or gas oil is used the economy of heat recovery must be
worked out as the flue gas temperature may be well below 200oC The potential for
energy saving depends on the type of boiler installed and the fuel used For a typically
older model shell boiler with a flue gas exit temperature of 260oC an economizer
could be used to reduce it to 200oC increasing the feed water temperature by 15oC
Increase in overall thermal efficiency would be in the order of 3 For a modern 3-
pass shell boiler firing natural gas with a flue gas exit temperature of 140oC a
condensing economizer would reduce the exit temperature to 65oC increasing thermal
efficiency by 5
Combustion Air Preheat
Combustion air preheating is an alternative to feedwater heating In order to improve
thermal efficiency by 1 the combustion air temperature must be raised by 20 oC
Most gas and oil burners used in a boiler plant are not designed for high air preheat
temperatures Modern burners can withstand much higher combustion air preheat so
it is possible to consider such units as heat exchangers in the exit flue as an alternative
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
to an economizer when either space or a high feed water return temperature make it
viable
Incomplete Combustion
Incomplete combustion can arise from a shortage of air or surplus of fuel or poor
distribution of fuel It is usually obvious from the colour or smoke and must be
corrected immediately
In the case of oil and gas fired systems CO or smoke (for oil fired systems only) with
normal or high excess air indicates burner system problems A more frequent cause of
incomplete combustion is the poor mixing of fuel and air at the burner Poor oil fires
can result from improper viscosity worn tips carbonization on tips and deterioration
of diffusers or spinner plates
With coal firing unburned carbon can comprise a big loss It occurs as grit carry-over
or carbon-in-ash and may amount to more than 2 of the heat supplied to the boiler
Non uniform fuel size could be one of the reasons for incomplete combustion In
chain grate stokers large lumps will not burn out completely while small pieces and
fines may block the air passage thus causing poor air distribution In sprinkler
stokers stoker grate condition fuel distributors wind box air regulation and over-fire
systems can affect carbon loss Increase in the fines in pulverized coal also increases
carbon loss
Excess Air Control
Excess air is required in all practical cases to ensure complete combustion to allow
for the normal variations in combustion and to ensure satisfactory stack conditions for
some fuels The optimum excess air level for maximum boiler efficiency occurs when
the sum of the losses due to incomplete combustion and loss due to heat in flue gases
is minimum This level varies with furnace design type of burner fuel and process
variables It can be determined by conducting tests with different air fuel ratios
Radiation and Convection Heat Loss
The external surfaces of a shell boiler are hotter than the surroundings The surfaces
thus lose heat to the surroundings depending on the surface area and the difference in
temperature between the surface and the surroundings The heat loss from the boiler
shell is normally a fixed energy loss irrespective of the boiler output With modern
boiler designs this may represent only 15 on the gross calorific value at full rating
but will increase to around 6 if the boiler operates at only 25 percent output
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Repairing or augmenting insulation can reduce heat loss through boiler walls and
piping
Automatic Blowdown Control
Uncontrolled continuous blowdown is very wasteful Automatic blowdown controls
can be installed that sense and respond to boiler water conductivity and pH A 10
blow down in a 15 kgcm2 boiler results in 3 efficiency loss
Reduction of Scaling and Soot Losses
In oil and coal-fired boilers soot buildup on tubes acts as an insulator against heat
transfer Any such deposits should be removed on a regular basis Elevated stack
temperatures may indicate excessive soot buildup Also same result will occur due to
scaling on the water side High exit gas temperatures at normal excess air indicate
poor heat transfer performance This condition can result from a gradual build-up of
gas-side or waterside deposits Waterside deposits require a review of water treatment
procedures and tube cleaning to remove deposits An estimated 1 efficiency loss
occurs with every 22oC increase in stack temperature
Reduction of Boiler Steam Pressure
This is an effective means of reducing fuel consumption if permissible by as much as
1 to 2 Lower steam pressure gives a lower saturated steam temperature and without
stack heat recovery a similar reduction in the temperature of the flue gas temperature
results
Steam is generated at pressures normally dictated by the highest pressure
temperature requirements for a particular process In some cases the process does not
operate all the time and there are periods when the boiler pressure could be reduced
The energy manager should consider pressure reduction carefully before
recommending it Adverse effects such as an increase in water carryover from the
boiler owing to pressure reduction may negate any potential saving Pressure should
be reduced in stages and no more than a 20 percent reduction should be considered
Variable Speed Control for Fans Blowers and Pumps
Variable speed control is an important means of achieving energy savings Generally
combustion air control is effected by throttling dampers fitted at forced and induced
draft fans Though dampers are simple means of control they lack accuracy giving
poor control characteristics at the top and bottom of the operating range In general if
the load characteristic of the boiler is variable the possibility of replacing the dampers
by a VSD should be evaluated
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Effect of Boiler Loading on Efficiency
The maximum efficiency of the boiler does not occur at full load but at about two-
thirds of the full load If the load on the boiler decreases further efficiency also tends
to decrease At zero output the efficiency of the boiler is zero and any fuel fired is
used only to supply the losses The factors affecting boiler efficiency are
As the load falls so does the value of the mass flow rate of the flue gases through the
tubes This reduction in flow rate for the same heat transfer area reduced the exit flue
gas temperatures by a small extent reducing the sensible heat lossBelow half load
most combustion appliances need more excess air to burn the fuel completely This
increases the sensible heat loss In general efficiency of the boiler reduces
significantly below 25 of the rated load and as far as possible operation of boilers
below this level should be avoided
Proper Boiler Scheduling
Since the optimum efficiency of boilers occurs at 65-85 of full load it is usually
more efficient on the whole to operate a fewer number of boilers at higher loads
than to operate a large number at low loads
Boiler Replacement
The potential savings from replacing a boiler depend on the anticipated change in
overall efficiency A change in a boiler can be financially attractive if the existing
boiler is
Old and inefficient
Not capable of firing cheaper substitution fuel
Over or under-sized for present requirements
Not designed for ideal loading conditions
The feasibility study should examine all implications of long-term fuel availability
and company growth plans All financial and engineering factors should be
considered Since boiler plants traditionally have a useful life of well over 25 years
replacement must be carefully studied
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 11-12 Pumps and Pumping System
Pump Types Centrifugal Pumps Pump Performance Curve Hydraulic power pump
shaft power and electrical input power
Pump Types
Pumps come in a variety of sizes for a wide range of applications They can be
classified according to their basic operating principle as dynamic or displacement
pumps Dynamic pumps can be sub-classified as centrifugal and special effect pumps
Displacement pumps can be sub-classified as rotary or reciprocating pumps
In principle any liquid can be handled by any of the pump designs Where different
pump designs could be used the centrifugal pump is generally the most economical
followed by rotary and reciprocating pumps Although positive displacement pumps
are generally more efficient than centrifugal pumps the benefit of higher efficiency
tends to be offset by increased maintenance costs
Since worldwide centrifugal pumps account for the majority of electricity used by
pumps the focus of this chapter is on centrifugal pump
Centrifugal Pumps
A centrifugal pump is of a very simple design The two main parts of the pump are the
impeller and the diffuser Impeller which is the only moving part is attached to a
shaft and driven by a motor Impellers are generally made of bronze polycarbonate
cast iron stainless steel as well as other materials The diffuser (also called as volute)
houses the impeller and captures and directs the water off the impeller
Pump Performance Curve
The pump is a dynamic device it is convenient to consider the pressure in terms of
head ie meters of liquid column The pump generates the same head of liquid
whatever the density of the liquid being pumped The actual contours of the hydraulic
passages of the impeller and the casing are extremely important in order to attain the
highest efficiency possible The standard convention for centrifugal pump is to draw
the pump performance curves showing Flow on the horizontal axis and Head
generated on the vertical axis Efficiency Power amp NPSH Required (described later)
are also all conventionally shown on the vertical axis plotted against Flow as
illustrated in Figure
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 13-14 System Characteristics
Static Head vs Flow Friction Head vs Flow System with High Static Head System
with Low Static Head Pump Curves Head- Flow Curve Pump operating point
In a pumping system the objective in most cases is either to transfer a liquid from a
source to a required destination eg filling a high level reservoir or to circulate liquid
around a system eg as a means of heat transfer in heat exchanger
A pressure is needed to make the liquid flow at the required rate and this must
overcome head lsquolossesrsquo in the system Losses are of two types static and friction
head
Static head is simply the difference in height of the supply and destination reservoirs
as in Figure In this illustration flow velocity in the pipe is assumed to be very small
Another example of a system with only static head is pumping into a pressurised
vessel with short pipe runs Static head is independent of flow and graphically would
be shown as in Figure
Figure Static Head Figure Static Head vs Flow
Pump Curves
The performance of a pump can be expressed graphically as head against flow rate
The centrifugal pump has a curve where the head falls gradually with increasing flow
This is called the pump characteristic curve
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Pump operating point
When a pump is installed in a system the effect can be illustrated graphically by
superimposing pump and system curves The operating point will always be where the
two curves intersect Fig
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 15-16 Factors Affecting Pump Performance
Matching Pump and System Head-flow Characteristics Effect of over sizing the
pump Energy loss in throttling
Matching Pump and System Head-flow Characteristics
Centrifugal pumps are characterized by the relationship between the flow rate (Q) they
produce and the pressure (H) at which the flow is delivered Pump efficiency varies with
flow and pressure and it is highest at one particular flow rate
The Figure below shows a typical vendor-supplied head-flow curve for a centrifugal
pump Pump head-flow curves are typically given for clear water The choice of pump for
a given application depends largely on how the pump head-flow characteristics match the
requirement of the system downstream of the pump
Effect of over sizing the pump
As mentioned earlier pressure losses to be overcome by the pumps are a function of flow
ndash the system characteristics ndash are also quantified in the form of head-flow curves The
system curve is basically a plot of system resistance ie head to be overcome by the pump
versus various flow rates The system curves change with the physical configuration of
the system for example the system curves depends upon height or elevation diameter
and length of piping number and type of fittings and pressure drops across various
equipment - say a heat exchanger
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
A pump is selected based on how well the pump curve and system head-flow curves
match The pump operating point is identified as the point where the system curve
crosses the pump curve when they are superimposed on each other
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 17-18 Efficient Pumping System Operation
Effect of speed variation Effects of impeller diameter change Pump suction
performance (NPSH)
Effect of speed variation
As stated above a centrifugal pump is a dynamic device with the head generated from a
rotating impeller There is therefore a relationship between impeller peripheral velocity
and generated head Peripheral velocity is directly related to shaft rotational speed for a
fixed impeller diameter and so varying the rotational speed has a direct effect on the
performance of the pump All the parameters shown in fig 62 will change if the speed is
varied and it is important to have an appreciation of how these parameters vary in order to
safely control a pump at different speeds The equations relating rotodynamic pump
performance parameters of flow head and power absorbed to speed are known as the
Affinity Laws
Pump suction performance (NPSH)
Liquid entering the impeller eye turns and is split into separate streams by the leading
edges of the impeller vanes an action which locally drops the pressure below that in
the inlet pipe to the pump
If the incoming liquid is at a pressure with insufficient margin above its vapour
pressure then vapour cavities or bubbles appear along the impeller vanes just behind
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
the inlet edges This phenomenon is known as cavitation and has three undesirable
effects
1) The collapsing cavitation bubbles can erode the vane surface especially when
pumping water-based liquids
2) Noise and vibration are increased with possible shortened seal and bearing life
3) The cavity areas will initially partially choke the impeller passages and reduce the
pump performance In extreme cases total loss of pump developed head occurs
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 19-20 Flow Control Strategies
Pump control by varying speed Pumps in parallel Stopstart control Flow control
valve By-pass control Fixed Flow reduction Meeting variable flow reduction
Energy Conservation Opportunities in Pumping Systems
Pump control by varying speed
To understand how speed variation changes the duty point the pump and system curves
are over-laid Two systems are considered one with only friction loss and another where
static head is high in relation to friction head It will be seen that the benefits are different
Example for the Effect of Pump Speed Change with a System with High Static
Head
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Energy Conservation Opportunities in Pumping Systems
Ensure adequate NPSH at site of installation
Ensure availability of basic instruments at pumps like pressure gauges flow
meters
Operate pumps near best efficiency point
Modify pumping system and pumps losses to minimize throttling
Adapt to wide load variation with variable speed drives or sequenced control
of multiple units
Stop running multiple pumps - add an auto-start for an on-line spare or add a
booster pump in the problem area
Use booster pumps for small loads requiring higher pressures
Increase fluid temperature differentials to reduce pumping rates in case of heat
exchangers
Repair seals and packing to minimize water loss by dripping
Balance the system to minimize flows and reduce pump power requirements
Avoid pumping head with a free-fall return (gravity) Use siphon effect to
advantage
Conduct water balance to minimise water consumption
Avoid cooling water re-circulation in DG sets air compressors refrigeration
systems cooling towers feed water pumps condenser pumps and process
pumps
In multiple pump operations carefully combine the operation of pumps to
avoid throttling
Provide booster pump for few areas of higher head
Replace old pumps by energy efficient pumps
In the case of over designed pump provide variable speed drive or downsize
replace impeller or replace with correct sized pump for efficient operation
Optimise number of stages in multi-stage pump in case of head margins
Reduce system resistance by pressure drop assessment and pipe size
optimisation
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 21-22 Fans and Blowers
Difference between Fans Blowers and Compressors Types of Fans Characteristics
and Typical Applications
Fans and blowers provide air for ventilation and industrial process requirements Fans
generate a pressure to move air (or gases) against a resistance caused by ducts
dampers or other components in a fan system The fan rotor receives energy from a
rotating shaft and transmits it to the air
Difference between Fans Blowers and Compressors
Types of Fans Characteristics and Typical Applications
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 23-24 Fan Performance Evaluation and Efficient System Operation
System Characteristics Fan Characteristics System Characteristics and Fan Curves
Fan Laws
System Characteristics and Fan Curves
Fan Laws
The fans operate under a predictable set of laws concerning speed power and
pressure A change in speed (RPM) of any fan will predictably change the pressure
rise and power necessary to operate it at the new RPM
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 25 Fan Design and Selection Criteria
Fan Performance and Efficiency Safety margin Installation of Fan System
Resistance Change
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in
proper selection of fan type and size The air-flow required depends on the process
requirements normally determined from heat transfer rates or combustion air or flue
gas quantity to be handled System pressure requirement is usually more difficult to
compute or predict Detailed analysis should be carried out to determine pressure drop
across the length bends contractions and expansions in the ducting system pressure
drop across filters drop in branch lines etc These pressure drops should be added to
any fixed pressure required by the process (in the case of ventilation fans there is no
fixed pressure requirement) Frequently a very conservative approach is adopted
allocating large safety margins resulting in over-sized fans which operate at flow
rates much below their design values and consequently at very poor efficiency
Once the system flow and pressure requirements are determined the fan and impeller
type are then selected For best results values should be obtained from the
manufacturer for specific fans and impellers
The choice of fan type for a given application depends on the magnitudes of required
flow and static pressure For a given fan type the selection of the appropriate impeller
depends additionally on rotational speed Speed of operation varies with the
application High speed small units are generally more economical because of their
higher hydraulic efficiency and relatively low cost However at low pressure ratios
large low-speed units are preferable
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 26-27 Flow Control Strategies
Pulley change damper control inlet guide vane control variable speed drive and
series and parallel operation of fans
Flow Control Strategies
Typically once a fan system is designed and installed the fan operates at a constant speed
There may be occasions when a speed change is desirable ie when adding a new run of duct
that requires an increase in air flow (volume) through the fan There are also instances when
the fan is oversized and flow reductions are required
Pulley Change
When a fan volume change is required on a permanent basis and the existing fan can handle
the change in capacity the volume change can be achieved with a speed change The simplest
way to change the speed is with a pulley change For this the fan must be driven by a motor
through a v-belt system The fan speed can be increased or decreased with a change in the
drive pulley or the driven pulley or in some cases both pulleys As shown in the Figure a
higher sized fan operating with damper control was downsized by reducing the motor (drive)
Damper Controls
Some fans are designed with damper controls Dampers can be located at inlet or outlet
Dampers provide a means of changing air volume by adding or removing system
resistance This resistance forces the fan to move up or down along its characteristic
curve generating more or less air without changing fan speed However dampers provide
a limited amount of adjustment and they are not particularly energy efficient
Variable Speed Drives
Although variable speed drives are expensive they provide almost infinite variability in
speed control Variable speed operation involves reducing the speed of the fan to meet
reduced flow requirements Fan performance can be predicted at different speeds using
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
the fan laws Since power input to the fan changes as the cube of the flow this will
usually be the most efficient form of capacity control However variable speed control
may not be economical for systems which have infrequent flow variations When
considering variable speed drive the efficiency of the control system (fluid coupling
eddy-current VFD etc) should be accounted for in the analysis of power consumption
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 28-29 Fan Performance AssessmentStatic Total and Velocity Pressure Measurements and Calculations
The fans are tested for field performance by measurement of flow head temperature on the fan side and electrical motor kW input on the motor side
Air flow measurement
Static pressure
Static pressure is the potential energy put into the system by the fan It is given up to
friction in the ducts and at the duct inlet as it is converted to velocity pressure At the
inlet to the duct the static pressure produces an area of low pressure
Velocity pressure
Velocity pressure is the pressure along the line of the flow that results from the air
flowing through the duct The velocity pressure is used to calculate air velocity
Total pressure
Total pressure is the sum of the static and velocity pressure Velocity pressure and
static pressure can change as the air flows though different size ducts accelerating and
de-accelerating the velocity The total pressure stays constant changing only with friction
losses The illustration that follows shows how the total pressure changes in a system
The fan flow is measured using pitot tube manometer combination or a flow sensor
(differential pressure instrument) or an accurate anemometer Care needs to be taken
regarding number of traverse points straight length section (to avoid turbulent flow
regimes of measurement) up stream and downstream of measurement location The
measurements can be on the suction or discharge side of the fan and preferably both
where feasible
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Measurement by Pitot tube
The Figure shows how velocity pressure is measured using a pitot tube and a
manometer Total pressure is measured using the inner tube of pitot tube and static
pressure is measured using the outer tube of pitot tube When the inner and outer tube
ends are connected to a manometer we get the velocity pressure For measuring low
velocities it is preferable to use an inclined tube manometer instead of U tube
manometer
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 30 Energy Savings Opportunities in fan operation
Energy Savings Opportunities
Minimizing demand on the fan
1 Minimising excess air level in combustion systems to reduce FD fan and ID fan
load
2 Minimising air in-leaks in hot flue gas path to reduce ID fan load especially in
case of kilns boiler plants furnaces etc Cold air in-leaks increase ID fan load
tremendously due to density increase of flue gases and in-fact choke up the
capacity of fan resulting as a bottleneck for boiler furnace itself
3 In-leaks out-leaks in air conditioning systems also have a major impact on
energy efficiency and fan power consumption and need to be minimized
The findings of performance assessment trials will automatically indicate potential areas
for improvement which could be one or a more of the following
1 Change of impeller by a high efficiency impeller along with cone
2 Change of fan assembly as a whole by a higher efficiency fan
3 Impeller derating (by a smaller dia impeller)
4 Change of metallic Glass reinforced Plastic (GRP) impeller by the more energy
efficient hollow FRP impeller with aerofoil design in case of axial flow fans
where significant savings have been reported
5 Fan speed reduction by pulley dia modifications for derating
6 Option of two speed motors or variable speed drives for variable duty conditions
7 Option of energy efficient flat belts or cogged raw edged V belts in place of
conventional V belt systems for reducing transmission losses
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 31 HVAC and Refrigeration system
Introduction to Refrigeration System Types of Refrigeration System
The Heating Ventilation and Air Conditioning (HVAC) and refrigeration system
transfers the heat energy from or to the products or building environment Energy in
form of electricity or heat is used to power mechanical equipment designed to transfer
heat from a colder low-energy level to a warmer high-energy level
Refrigeration deals with the transfer of heat from a low temperature level at the heat
source to a high temperature level at the heat sink by using a low boiling refrigerant
There are several heat transfer loops in refrigeration system as described below
Thermal energy moves from left to right as it is extracted from the space and expelled
into the outdoors through five loops of heat transfer
Indoor air loop In the leftmost loop indoor air is driven by the supply air fan
through a cooling coil where it transfers its heat to chilled water The cool air
then cools the building space
Chilled water loop Driven by the chilled water pump water returns from the
cooling coil to the chillerrsquos evaporator to be re-cooled
Refrigerant loop Using a phase-change refrigerant the chillerrsquos compressor
pumps heat from the chilled water to the condenser water
Condenser water loop Water absorbs heat from the chillerrsquos condenser and the
condenser water pump sends it to the cooling tower
Cooling tower loop The cooling towerrsquos fan drives air across an open flow of the
hot condenser water transferring the heat to the outdoors
Figure Heat Transfer Loops In Refrigeration System
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 32-33 Vapour Compression Refrigeration Alternative Refrigerants for
Vapour Compression Systems
Types of Refrigeration System
Vapour Compression Refrigeration
Heat flows naturally from a hot to a colder body In refrigeration system the opposite
must occur ie heat flows from a cold to a hotter body This is achieved by using a
substance called a refrigerant which absorbs heat and hence boils or evaporates at a
low pressure to form a gas This gas is then compressed to a higher pressure such that
it transfers the heat it has gained to ambient air or water and turns back (condenses)
into a liquid In this way heat is absorbed or removed from a low temperature source
and transferred to a higher temperature source
The refrigeration cycle can be broken down into the following stages
1 - 2 Low pressure liquid refrigerant in the evaporator absorbs heat from its
surroundings usually air water or some other process liquid During this process it
changes its state from a liquid to a gas and at the evaporator exit is slightly
superheated
2 - 3 The superheated vapour enters the compressor where its pressure is raised There
will also be a big increase in temperature because a proportion of the energy input
into the compression process is transferred to the refrigerant
3 - 4 The high pressure superheated gas passes from the compressor into the
condenser The initial part of the cooling process (3 - 3a) desuperheats the gas before
it is then turned back into liquid (3a - 3b) The cooling for this process is usually
achieved by using air or water A further reduction in temperature happens in the pipe
work and liquid receiver (3b - 4) so that the refrigerant liquid is sub-cooled as it
enters the expansion device
4 - 1 The high-pressure sub-cooled liquid passes through the expansion device which
both reduces its pressure and controls the flow into the evaporator
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Figure Schematic of a Basic Vapor Compression Refrigeration System
It can be seen that the condenser has to be capable of rejecting the combined heat
inputs of the evaporator and the compressor ie (1 - 2) + (2 - 3) has to be the same as
(3 - 4) There is no heat loss or gain through the expansion device
Alternative Refrigerants for Vapour Compression Systems
The use of CFCs is now beginning to be phased out due to their damaging impact on
the protective tropospheric ozone layer around the earth The Montreal Protocol of
1987 and the subsequent Copenhagen agreement of 1992 mandate a reduction in the
production of ozone depleting Chlorinated Fluorocarbon (CFC) refrigerants in a
phased manner with an eventual stop to all production by the year 1996 In response
the refrigeration industry has developed two alternative refrigerants one based on
Hydrochloro Fluorocarbon (HCFC) and another based on Hydro Fluorocarbon
(HFC) The HCFCs have a 2 to 10 ozone depleting potential as compared to CFCs
and also they have an atmospheric lifetime between 2 to 25 years as compared to 100
or more years for CFCs (Brandt 1992) However even HCFCs are mandated to be
phased out by 2005 and only the chlorine free (zero ozone depletion) HFCs would be
acceptable
Until now only one HFC based refrigerant HFC 134a has been developed HCFCs are
comparatively simpler to produce and the three refrigerants 22 123 and 124 have been
developed The use of HFCs and HCFCs results in slightly lower efficiencies as compared to
CFCs but this may change with increasing efforts being made to replace CFCs
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 34-35 Absorption Refrigeration Common Refrigerants and Properties
Selection of a Suitable Refrigeration System
Absorption Refrigeration
The absorption chiller is a machine which produces chilled water by using heat such as
steam hot water gas oil etc Chilled water is produced by the principle that liquid
(refrigerant) which evaporates at low temperature absorbs heat from surrounding when it
evaporates Pure water is used as refrigerant and lithium bromide solution is used as absorbent
Heat for the vapour absorption refrigeration system can be provided by waste heat extracted
from process diesel generator sets etc Absorption systems require electricity to run pumps
only Depending on the temperature required and the power cost it may even be economical
to generate heat steam to operate the absorption system
Common Refrigerants and Properties
A variety of refrigerants are used in vapor compression systems The choice of fluid
is determined largely by the cooling temperature required Commonly used
refrigerants are in the family of chlorinated fluorocarbons (CFCs also called Freons)
R-11 R-12 R-21 R-22 and R-502
Table Properties of Commonly used Refrigerants
RefrigerantBoiling Point
(oC)
Freezing Point (oC)
Vapor Pressure
(kPa)
Vapor Volume (m3 kg)
Enthalpy Liquid (kJ
kg)Vapor
(kJ kg)
R - 11 -2382 -1110 2573 061170 19140 38543
R - 12 -2979 -1580 21928 007702 19072 34796
R - 22 -4076 -1600 35474 006513 18855 40083
R - 502 -4540 --- 41430 004234 18887 34231
R - 7 (Ammonia)
-3330 -777 28993 041949 80871 48776
Table Performance of Commonly used Refrigerants
Refrigerant Evaporating Press (kPa)
Condensing Press (kPa)
Pressure Ratio
Vapor Enthalpy (kJ
kg)COP
carnot
R - 11 204 1255 615 1554 503
R - 12 1827 7446 408 1163 470
R - 22 2958 11921 403 1628 466
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
R - 502 3496 13086 374 1062 437
R - 717 2365 11665 493 1034 478
Selection of a Suitable Refrigeration System
A clear understanding of the cooling load to be met is the first and most important part of
designing selecting the components of a refrigeration system Important factors to be
considered in quantifying the load are the actual cooling need heat (cool) leaks and internal
heat sources (from all heat generating equipment) Consideration should also be given to
process changes and or changes in ambient conditions that might affect the load in the
future Reducing the load eg through better insulation maintaining as high a cooling
temperature as practical etc is the first step toward minimizing electrical power required to
meet refrigeration needs With a quantitative understanding of the required temperatures and
the maximum minimum and average expected cooling demands selection of appropriate
refrigeration system (single-stage multi-stage economized compression compound
cascade operation direct cooling secondary coolants) and equipment (type of refrigerant
compressor evaporator condenser etc) can be undertaken
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 36 Performance Assessment of Refrigeration Plants
The cooling effect produced is quantified as tons of refrigeration(TR)
1 TR of refrigeration = 3024 kCalhr heat rejected
The refrigeration TR is assessed as TR = Q xCp x (Ti ndash To) 3024
Where Q is mass flow rate of coolant in kghr
Cp is coolant specific heat in kCal kg deg C
Ti is inlet temperature of coolant to evaporator (chiller) in 0C
To is outlet temperature of coolant from evaporator (chiller) in 0C
The above TR is also called as chiller tonnage
The specific power consumption kWTR is a useful indicator of the performance
of refrigeration system By measuring refrigeration duty performed in TR and the
kiloWatt inputs kWTR is used as a reference energy performance indicator
In a centralized chilled water system apart from the compressor unit power is
also consumed by the chilled water (secondary) coolant pump as well condenser
water (for heat rejection to cooling tower) pump and cooling tower fan in the
cooling tower Effectively the overall energy consumption would be towards
Compressor kW
Chilled water pump kW
Condenser water pump kW
Cooling tower fan kW for induced forced draft towers
The specific power consumption for certain TR output would therefore have to
include
Compressor kWTR
Chilled water pump kWTR
Condenser water pump kWTR
Cooling tower fan kWTR
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 37 Factors Affecting Performance amp Energy Efficiency of Refrigeration
Plants Energy Saving Opportunities
a) Cold Insulation
Insulate all cold lines vessels using economic insulation thickness to minimize
heat gains and choose appropriate (correct) insulation
b) Building Envelope
Optimise air conditioning volumes by measures such as use of false ceiling and
segregation of critical areas for air conditioning by air curtains
c) Building Heat Loads Minimisation
Minimise the air conditioning loads by measures such as roof cooling roof
painting efficient lighting pre-cooling of fresh air by air- to-air heat exchangers
variable volume air system otpimal thermo-static setting of temperature of air
conditioned spaces sun film applications etc
e) Process Heat Loads Minimisation
Minimize process heat loads in terms of TR capacity as well as refrigeration level
ie temperature required by way of
i) Flow optimization
ii) Heat transfer area increase to accept higher temperature coolant
iii) Avoiding wastages like heat gains loss of chilled water idle flows
iv) Frequent cleaning de-scaling of all heat exchangers
f) At the Refrigeration AC Plant Area
i) Ensure regular maintenance of all AC plant components as per
manufacturer guidelines
ii) Ensure adequate quantity of chilled water and cooling water
flows avoid bypass flows by closing valves of idle equipment
iii) Minimize part load operations by matching loads and plant
capacity on line adopt variable speed drives for varying process load
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
iv) Make efforts to continuously optimize condenser and
evaporator parameters for minimizing specific energy consumption and
maximizing capacity
v) Adopt VAR system where economics permit as a non-CFC
solution
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 38-39 Introduction to Cooling Water System Cooling Tower Types-
Natural draft and Mechanical draft Cooling Tower Performance
Cooling towers are a very important part of many chemical plants The primary task of a
cooling tower is to reject heat into the atmosphere They represent a relatively
inexpensive and dependable means of removing low-grade heat from cooling water The
make-up water source is used to replenish water lost to evaporation Hot water from heat
exchangers is sent to the cooling tower The water exits the cooling tower and is sent back
to the exchangers or to other units for further cooling Typical closed loop cooling tower
system is shown in Figure
Cooling Tower Types
Cooling towers fall into two main categories Natural draft and Mechanical draft
Natural draft towers use very large concrete chimneys to introduce air through the media
Due to the large size of these towers they are generally used for water flow rates above
45000 m3hr These types of towers are used only by utility power stations
Mechanical draft towers utilize large fans to force or suck air through circulated water
The water falls downward over fill surfaces which help increase the contact time between
the water and the air - this helps maximise heat transfer between the two Cooling rates of
Mechanical draft towers depend upon their fan diameter and speed of operation
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Cooling Tower Performance
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 40-41 Factors Affecting Cooling Tower Performance Efficient System
Operation Performance Assessment of Cooling Towers Energy Saving Opportunities
in Cooling Towers
Factors Affecting Cooling Tower Performance
Capacity
Heat dissipation (in kCalhour) and circulated flow rate (m3hr) are not sufficient to
understand cooling tower performance Other factors which we will see must be
stated along with flow rate m3hr For example a cooling tower sized to cool 4540
m3hr through a 139oC range might be larger than a cooling tower to cool 4540 m3hr
through 195oC range
Range
Range is determined not by the cooling tower but by the process it is serving The
range at the exchanger is determined entirely by the heat load and the water
circulation rate through the exchanger and on to the cooling water
Range oC = Heat Load in kcalshour Water Circulation Rate in LPH
Thus Range is a function of the heat load and the flow circulated through the system
Wet Bulb Temperature
Wet bulb temperature is an important factor in performance of evaporative water
cooling equipment It is a controlling factor from the aspect of minimum cold water
temperature to which water can be cooled by the evaporative method Thus the wet
bulb temperature of the air entering the cooling tower determines operating
temperature levels throughout the plant process or system Theoretically a cooling
tower will cool water to the entering wet bulb temperature when operating without a
heat load However a thermal potential is required to reject heat so it is not possible
to cool water to the entering air wet bulb temperature when a heat load is applied
The approach obtained is a function of thermal conditions and tower capability
Energy Saving Opportunities in Cooling Towers
Follow manufacturerrsquos recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust
Optimise cooling tower fan blade angle on a seasonal andor load basis
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Correct excessive andor uneven fan blade tip clearance and poor fan balance
On old counter-flow cooling towers replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles
Replace splash bars with self-extinguishing PVC cellular film fill
Install new nozzles to obtain a more uniform water pattern
Periodically clean plugged cooling tower distribution nozzles
Balance flow to cooling tower hot water basins
Cover hot water basins to minimise algae growth that contributes to fouling
Optimise blow down flow rate as per COC limit
Replace slat type drift eliminators with low pressure drop self extinguishing
PVC cellular units
Restrict flows through large loads to design values
Segregate high heat loads like furnaces air compressors DG sets and isolate
cooling towers for sensitive applications like AC plants condensers of
captive power plant etc A 1oC cooling water temperature increase may
increase AC compressor kW by 27 A 1oC drop in cooling water
temperature can give a heat rate saving of 5 kCalkWh in a thermal power
plant
Monitor LG ratio CW flow rates wrt design as well as seasonal variations
It would help to increase water load during summer and times when approach
is high and increase air flow during monsoon times and when approach is
narrow
Monitor approach effectiveness and cooling capacity for continuous
optimisation efforts as per seasonal variations as well as load side variations
Consider COC improvement measures for water savings
Consider energy efficient FRP blade adoption for fan energy savings
Consider possible improvements on CW pumps wrt efficiency improvement
Control cooling tower fans based on leaving water temperatures especially in
case of small units
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 42-43 Introduction to Waste Heat Recovery Classification and
Application Benefits of Waste Heat Recovery
Waste heat is heat which is generated in a process by way of fuel combustion or
chemical reaction and then ldquodumpedrdquo into the environment even though it could still
be reused for some useful and economic purpose The essential quality of heat is not
the amount but rather its ldquovaluerdquo The strategy of how to recover this heat depends in
part on the temperature of the waste heat gases and the economics involved Large
quantity of hot flue gases is generated from Boilers Kilns Ovens and Furnaces If
some of this waste heat could be recovered a considerable amount of primary fuel
could be saved
Heat Losses ndashQuality
Depending upon the type of process waste heat can be rejected at virtually any
temperature from that of chilled cooling water to high temperature waste gases from
an industrial furnace or kiln Usually higher the temperature higher the quality and
more cost effective is the heat recovery In any study of waste heat recovery it is
absolutely necessary that there should be some use for the recovered heat Typical
examples of use would be preheating of combustion air space heating or pre-heating
boiler feed water or process water With high temperature heat recovery a cascade
system of waste heat recovery may be practiced to ensure that the maximum amount
of heat is recovered at the highest potential An example of this technique of waste
heat recovery would be where the high temperature stage was used for air pre-heating
and the low temperature stage used for process feed water heating or steam raising
Benefits of Waste Heat Recovery
Benefits of lsquowaste heat recoveryrsquo can be broadly classified in two categories
Direct Benefits
Recovery of waste heat has a direct effect on the efficiency of the process This is
reflected by reduction in the utility consumption amp costs and process cost
Indirect Benefits
a) Reduction in pollution A number of toxic combustible wastes such as carbon
monoxide gas sour gas carbon black off gases oil sludge Acrylonitrile and
other plastic chemicals etc releasing to atmosphere ifwhen burnt in the
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
incinerators serves dual purpose ie recovers heat and reduces the
environmental pollution levels
b) Reduction in equipment sizes Waste heat recovery reduces the fuel
consumption which leads to reduction in the flue gas produced This results in
reduction in equipment sizes of all flue gas handling equipments such as fans
stacks ducts burners etc
c) Reduction in auxiliary energy consumption Reduction in equipment sizes gives
additional benefits in the form of reduction in auxiliary energy consumption
like electricity for fans pumps etc
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No44 Development of a Waste Heat Recovery System Commercial Waste
Heat Recovery Devices
Understanding the process
Understanding the process is essential for development of Waste Heat Recovery
system This can be accomplished by reviewing the process flow sheets layout
diagrams piping isometrics electrical and instrumentation cable ducting etc
Detail review of these documents will help in identifying
a) Sources and uses of waste heat
b) Upset conditions occurring in the plant due to heat recovery
c) Availability of space
d) Any other constraint such as dew point occurring in an equipments etc
After identifying source of waste heat and the possible use of it the next step is to
select suitable heat recovery system and equipments to recover and utilise the same
Economic Evaluation of Waste Heat Recovery System
It is necessary to evaluate the selected waste heat recovery system on the basis of
financial analysis such as investment depreciation payback period rate of return etc
In addition the advice of experienced consultants and suppliers must be obtained for
rational decision
Next section gives a brief description of common heat recovery devices available
commercially and its typical industrial applications
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture No 45-46 Recuperators Heat Wheels Heat Pipe Economiser Plate heat
exchanger Waste Heat Boilers Heat Pumps Thermocompressor
Recuperators
In a recuperator heat exchange takes place between the flue gases and the air through
metallic or ceramic walls Duct or tubes carry the air for combustion to be pre-heated
the other side contains the waste heat stream A recuperator for recovering waste heat
from flue gases is shown in Figure
Heat Wheels
Heat wheel is finding increasing applications in low to medium temperature waste
heat recovery systems Figure is a sketch illustrating the application of a heat wheel
It is a sizable porous disk fabricated with material having a fairly high heat capacity
which rotates between two side-by-side ducts one a cold gas duct the other a hot gas
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
duct The axis of the disk is located parallel to and on the partition between the two
ducts As the disk slowly rotates sensible heat (moisture that contains latent heat) is
transferred to the disk by the hot air and as the disk rotates from the disk to the cold
air The overall efficiency of sensible heat transfer for this kind of regenerator can be
as high as 85 percent Heat wheels have been built as large as 21 metres in diameter
with air capacities up to 1130 m3 min
A variation of the Heat Wheel is the rotary regenerator where the matrix is in a
cylinder rotating across the waste gas and air streams The heat or energy recovery
wheel is a rotary gas heat regenerator which can transfer heat from exhaust to
incoming gases
Its main area of application is where heat exchange between large masses of air
having small temperature differences is required Heating and ventilation systems and
recovery of heat from dryer exhaust air are typical applications
Heat Pipe
A heat pipe can transfer up to 100 times more thermal energy than copper the best
known conductor In other words heat pipe is a thermal energy absorbing and
transferring system and have no moving parts and hence require minimum
maintenance
The Heat Pipe comprises of three elements ndash a sealed container a capillary wick
structure and a working fluid The capillary wick structure is integrally fabricated into
the interior surface of the container tube and sealed under vacuum Thermal energy
applied to the external surface of the heat pipe is in equilibrium with its own vapour
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
as the container tube is sealed under vacuum Thermal energy applied to the external
surface of the heat pipe causes the working fluid near the surface to evaporate
instantaneously Vapour thus formed absorbs the latent heat of vapourisation and this
part of the heat pipe becomes an evaporator region The vapour then travels to the
other end the pipe where the thermal energy is removed causing the vapour to
condense into liquid again thereby giving up the latent heat of the condensation This
part of the heat pipe works as the condenser region The condensed liquid then flows
back to the evaporated region A figure of Heat pipe is shown in Figure
Heat Pumps
In the various commercial options previously discussed we find waste heat being
transferred from a hot fluid to a fluid at a lower temperature Heat must flow
spontaneously ldquodownhillrdquo that is from a system at high temperature to one at a lower
temperature When energy is repeatedly transferred or transformed it becomes less
and less available for use Eventually that energy has such low intensity (resides in a
medium at such low temperature) that it is no longer available at all to perform a
useful function
It has been taken as a general rule of thumb in industrial operations that fluids with
temperatures less than 120oC (or better 150oC to provide a safe margin) as limit for
waste heat recovery because of the risk of condensation of corrosive liquids
However as fuel costs continue to rise even such waste heat can be used
economically for space heating and other low temperature applications It is possible
to reverse the direction of spontaneous energy flow by the use of a thermodynamic
system known as a heat pump
The majority of heat pumps work on the principle of the vapour compression cycle In
this cycle the circulating substance is physically separated from the source (waste
heat with a temperature of Tin) and user (heat to be used in the process Tout) streams
and is re-used in a cyclical fashion therefore called closed cycle In the heat pump
the following processes take place
1 In the evaporator the heat is extracted from the heat source to boil the
circulating substance
2 The circulating substance is compressed by the compressor raising its pressure
and temperature The low temperature vapor is compressed by a compressor
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
which requires external work The work done on the vapor raises its pressure
and temperature to a level where its energy becomes available for use
3 The heat is delivered to the condenser
4 The pressure of the circulating substance (working fluid) is reduced back to the
evaporator condition in the throttling valve where the cycle repeats
The heat pump was developed as a space heating system where low temperature
energy from the ambient air water or earth is raised to heating system temperatures
by doing compression work with an electric motor-driven compressor The
arrangement of a heat pump is shown in figure
Faculty Prof Ronak Patel
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 1-2
Introduction Air compressors account for significant amount of electricity used in Indian
industries Air compressors are used in a variety of industries to supply process
requirements to operate pneumatic tools and equipment and to meet instrumentation
needs Only 10-30 of energy reaches the point of end-use and balance 70-90 of
energy of the power of the prime mover being converted to unusable heat energy and
to a lesser extent lost in form of friction misuse and noise
Compressor Types
Compressors are broadly classified as Positive displacement compressor and Dynamic
compressor
Positive displacement compressors increase the pressure of the gas by reducing the
volume Positive displacement compressors are further classified as reciprocating and
rotary compressors
Dynamic compressors increase the air velocity which is then converted to increased
pressure at the outlet Dynamic compressors are basically centrifugal compressors and are
further classified as radial and axial flow types Flow and pressure requirements of a
given application determine the suitability of a particulars type of compressor
Positive Displacement Compressors
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Reciprocating compressors are the most widely used type for air compression They
are characterized by a flow output that remains nearly constant over a range of
discharge pressures Also the compressor capacity is directly proportional to the
speed The output however is a pulsating one
Reciprocating compressors are available in many configurations the four most widely
used of which are horizontal vertical and horizontal balance-opposed and tandem
Vertical type reciprocating compressors are used in the capacity range of 50 ndash 150
cfm Horizontal balance opposed compressors are used in the capacity range of 200 ndash
5000 cfm in multi-stage design and up to 10000 cfm in single stage designs
Reciprocating compressors are also available in variety of types
1048707Lubricated and non-lubricated
1048707Single or multiple cylinder
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 3-4
Compressor Performance
Capacity of a compressor is the full rated volume of flow of gas compressed and
delivered at conditions of total temperature total pressure and composition prevailing
at the compressor inlet It sometimes means actual flow rate rather than rated volume
of flow This also termed as Free Air Delivery (FAD) ie air at atmospheric
conditions at any specific location Because the altitude barometer and temperature
may vary at different localities and at different times it follows that this term does not
mean air under identical or standard conditions
Compressor Efficiency DefinitionsSeveral different measures of compressor efficiency are commonly used volumetric
efficiency adiabatic efficiency isothermal efficiency and mechanical efficiency
Adiabatic and isothermal efficiencies are computed as the isothermal or adiabatic power
divided by the actual power consumption The figure obtained indicates the overall
efficiency of compressor and drive motor
Isothermal Efficiency
Isothermal Efficiency=Actual measured input powerIsothermalPower
Isothermal power (kW) = P1 x Q1 x loger367
P1 = Absolute intake pressure kg cm2
Q1 = Free air delivered m3hr
r = Pressure ratio P2P1
Bureau of Energy Efficiency 533 Compressed Air System The calculation of isothermal
power does not include power needed to overcome friction and generally gives an
efficiency that is lower than adiabatic efficiency The reported value of efficiency is
normally the isothermal efficiency This is an important consideration when selecting
compressors based on reported values of efficiency
Volumetric Efficiency Compressor Displacement = Π x D2 x L x S x χ x n
Compressed Air System Components
Compressed air systems consist of following major components Intake air filters
inter-stage coolers after coolers air dryers moisture drain traps receivers piping
network filters regulators and lubricators
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Intake Air Filters Prevent dust from entering compressor Dust causes sticking
valves scoured cylinders excessive wear etc
Inter-stage Coolers Reduce the temperature of the air before it enters the next stage
to reduce the work of compression and increase efficiency They are normally water-
cooled
After Coolers The objective is to remove the moisture in the air by reducing the
temperature in a water-cooled heat exchanger
Air-dryers The remaining traces of moisture after after-cooler are removed using air
dryers as air for instrument and pneumatic equipment has to be relatively free of any
moisture The moisture is removed by using adsorbents like silica gel activated
carbon or refrigerant dryers or heat of compression dryers
Moisture Drain Traps Moisture drain traps are used for removal of moisture in the
compressed air These traps resemble steam traps Various types of traps used are
manual drain cocks timer based automatic drain valves etc
Bureau of Energy Efficiency 543 Compressed Air System
Receivers Air receivers are provided as storage and smoothening pulsating air
output - reducing pressure variations from the compressor
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 5-6
Need for cogeneration Thermal power plants are a major source of electricity supply in India The conventional
method of power generation and supply to the customer is wasteful in the sense that only
about a third of the primary energy fed into the power plant is actually made available to
the user in the form of electricity In conventional power plant efficiency is only 35
and remaining 65 of energy is lost The major source of loss in the conversion process
is the heat rejected to the surrounding water or air due to the inherent constraints of the
different thermodynamic cycles employed in power generation Also further losses of
around 10-15 are associated with the transmission and distribution of electricity in the
electrical grid
Principle of Cogeneration
Cogeneration or Combined Heat and Power (CHP) is defined as the sequential generation
of two different forms of useful energy from a single primary energy source typically
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
mechanical energy and thermal energy Mechanical energy may be used to drive an
alternator for producing electricity or rotating equipment such as motor compressor
pump or fan for delivering various services Thermal energy can be used either for direct
process applications or for indirectly producing steam hot water hot air for dryer or
chilled water for process cooling
Cogeneration provides a wide range of technologies for application in various domains of
economic activities The overall efficiency of energy use in cogeneration mode can be up
to 85 per cent and above in some cases
Classification of Cogeneration Systems
Cogeneration systems are normally classified according to the sequence of energy use and
the operating schemes adopted
A cogeneration system can be classified as either a topping or a bottoming cycle on the
basis of the sequence of energy use In a topping cycle the fuel supplied is used to first
produce power and then thermal energy which is the by-product of the cycle and is used
to satisfy process heat or other thermal requirements Topping cycle cogeneration is
widely used and is the most popular method of cogeneration
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 7-8
Topping Cycle
A gas turbine or diesel engine producing electrical or mechanical power followed by a heat
recovery boiler to create steam to drive a secondary steam turbine This is called a combined-
cycle topping system
The second type of system burns fuel (any type) to produce high-pressure steam that then
passes through a steam turbine to produce power with the exhaust provides low-pressure
process steam This is a steam-turbine topping system
A third type employs heat recovery from an engine exhaust andor jacket cooling system
flowing to a heat recovery boiler where it is converted to process steam hot water for further
use
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Factors Influencing Cogeneration Choice
The selection and operating scheme of a cogeneration system is very much site-specific
and depends on several factors as described below
Base electrical load matching
Base thermal load matching Electrical load matching
Thermal load matching
Important Technical Parameters for Cogeneration
While selecting cogeneration systems one should consider some important technical
parameters that assist in defining the type and operating scheme of different
alternative cogeneration systems to be selected
Heat-to-power ratio
Heat-to-power ratio is one of the most important technical parameters influencing the
selection of the type of cogeneration system The heat-to-power ratio of a facility
should match with the characteristics of the cogeneration system to be installed It is
defined as the ratio of thermal energy to electricity required by the energy consuming
facility Though it can be expressed in different units such as BtukWh kcalkWh
lbhrkW etc here it is presented on the basis of the same energy unit (kW)
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 9-10
Electrical system
Steam Turbine Steam turbines are the most commonly employed prime movers for cogeneration
applications In the steam turbine the incoming high pressure steam is expanded to a
lower pressure level converting the thermal energy of high pressure steam to kinetic
energy through nozzles and then to mechanical power through rotating blades
Extraction Condensing turbine In this type steam entering at High Medium Pressure
is extracted at an intermediate pressure in the turbine for process use while the remaining
steam continues to expand and condenses in a surface condenser and work is done till it
reaches the Condensing pressure(vacuum)
The overall thermal efficiency of an extraction condensing turbine cogeneration system is
lower than that of back pressure turbine system basically because the exhaust heat cannot
be utilized (it is normally lost in the cooling water circuit) However extraction
condensing cogeneration systems have higher electricity generation efficiencies
Gas Turbine
The fuel is burnt in a pressurized combustion chamber using combustion air supplied by a
compressor that is integral with the gas turbine In conventional Gas turbine gases enter
the turbine at a temperature range of 900 to 1000oC and leave at 400 to 500 oC The very
hot pressurized gases are used to turn a series of turbine blades and the shaft on which
they are mounted to produce mechanical energy Residual energy in the form of a high
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
flow of hot exhaust gases can be used to meet wholly or partly the thermal (steam)
demand of the site
Gas Turbine Efficiency Turbine Efficiency is the ratio of actual work output of the turbine to the net input energy
supplied in the form of fuel For stand alone Gas Turbines without any heat recovery
system the efficiency will be as low as 35 to 40 This is attributed to the blade
efficiency of the rotor leakage through clearance spaces friction irreversible turbulence
etc
Since Exhaust gas from the Gas Turbine is high it is possible to recover energy from the
hot gas by a Heat Recovery Steam Generator and use the steam for process
Net Turbine Efficiency
Above efficiency figures did not include the energy consumed by air compressors fuel
pump and other auxiliaries Air compressor alone consumes about 50 to 60 of energy
generated by the turbine Hence net turbine efficiency which is the actual energy output
available will be less than what has been calculated In most Gas Turbine plants air
compressor is an integral part of Turbine plant
Problems based on Economics of a Gas Turbine Based Co-generation
Calorific value ndash
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture11-12
Electric motors Types
Introduction Motors convert electrical energy into mechanical energy by the interaction between the
magnetic fields set up in the stator and rotor windings Industrial electric motors can be
broadly classified as induction motors direct current motors or synchronous motors All
motor types have the same four operating components stator (stationary windings) rotor
(rotating windings) bearings and frame (enclosure)
Motor Types Induction Motors
Induction motors are the most commonly used prime mover for various equipments in
industrial applications In induction motors the induced magnetic field of the stator
winding induces a current in the rotor This induced rotor current produces a second
magnetic field which tries to oppose the stator magnetic field and this causes the rotor to
rotate
The 3-phase squirrel cage motor is the workhorse of industry it is rugged and reliable
and is by far the most common motor type used in industry These motors drive pumps
blowers and fans compressors conveyers and production lines The 3-phase induction
motor has three windings each connected to a separate phase of the power supply
Direct-Current Motors
Direct-Current motors as the name implies use direct-unidirectional current Direct
current motors are used in special applications- where high torque starting or where
smooth acceleration over a broad speed range is required
Synchronous Motors
AC power is fed to the stator of the synchronous motor The rotor is fed by DC from a
separate source The rotor magnetic field locks onto the stator rotating magnetic field and
rotates at the same speed The speed of the rotor is a function of the supply frequency and
the number of magnetic poles in the stator
Motor Characteristics Motor Speed The speed of a motor is the number of revolutions in a given time frame typically
revolutions per minute (RPM) The speed of an AC motor depends on the frequency
of the input power and the number of poles for which the motor is wound
Power Factor
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
The power factor of the motor is given as kVAkW Cos Factor Power ==φ
As the load on the motor comes down the magnitude of the active current reduces
However there is no corresponding reduction in the magnetizing current which is
proportional to supply voltage with the result that the motor power factor reduces
with a reduction in applied load Induction motors especially those operating below
their rated capacity are the main reason for low power factor in electric systems
Motor Efficiency Two important attributes relating to efficiency of electricity use by AC Induction
motors are efficiency (η) defined as the ratio of the mechanical energy delivered at
the rotating shaft to the electrical energy input at its terminals and power factor (PF)
Motors like other inductive loads are characterized by power factors less than one
As a result the total current draw needed to deliver the same real power is higher than
for a load characterized by a higher PF
The efficiency of a motor is determined by intrinsic losses that can be reduced only by
changes in motor design Intrinsic losses are of two types fixed losses- independent of
motor load and variable losses - dependent on load
Fixed losses consist of magnetic core losses and friction and windage losses Magnetic
core losses (sometimes called iron losses) consist of eddy current and hysteretic losses in
the stator They vary with the core material and geometry and with input voltage
Friction and windage losses are caused by friction in the bearings of the motor and
aerodynamic losses associated with the ventilation fan and other rotating parts
Variable losses consist of resistance losses in the stator and in the rotor and
miscellaneous stray losses Resistance to current flow in the stator and rotor result in heat
generation that is proportional to the resistance of the material and the square of the
current (I2R) Stray losses arise from a variety of sources and are difficult to either
measure directly or to calculate but are generally proportional to the square of the rotor
current
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture13-14
Tests for Determining Efficiency
No Load Test The motor is run at rated voltage and frequency without any shaft load
Input power current frequency and voltage are noted The no load PF is quite low and
hence low PF watt meters are required From the input power stator I2R losses under no
load are subtracted to give the sum of Friction and Windage (FampW) and core losses
F amp W losses test is repeated at variable voltages It is useful to plot no-load input kW
versus Voltage the intercept is Friction amp Windage kW loss component
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
FampW and core losses = No load power (watts) ndash (No load current) 2 times Stator resistance
Stator and Rotor I2R Losses The stator winding resistance is directly measured by a
bridge or volt amp method The resistance must be corrected to the operating temperature
For modern motors the operating temperature is likely to be in the range of 1000C to
1200C and necessary correction should be made Correction to 750C may be inaccurate
The correction factor is given as follows
Rotor I2R losses = Slip times (Stator Input ndash Stator I2R Losses ndash Core Loss)
Accurate measurement of slip is possible by stroboscope or non-contact type tachometer
Slip also must be corrected to operating temperature
Factors Affecting Energy Efficiency amp Minimising Motor Losses in Operation Power Supply QualitySizing to Variable Load Industrial motors frequently operate under varying load conditions due to process
requirements A common practice in cases where such variable-loads are found is to
select a motor based on the highest anticipated load In many instances an alternative
approach is typically less costly more efficient and provides equally satisfactory
operation With this approach the optimum rating for the motor is selected on the
basis of the load duration curve for the particular application Thus rather than
selecting a motor of high rating that would operate at full capacity for only a short
period a motor would be selected with a rating slightly lower than the peak
anticipated load and would operate at overload for a short period of time
Power Factor Correction As noted earlier induction motors are characterized by power factors less than unity
leading to lower overall efficiency (and higher overall operating cost) associated with
a plantrsquos electrical system Capacitors connected in parallel (shunted) with the motor
are typically used to improve the power factor The impacts of PF correction include
reduced kVA demand (and hence reduced utility demand charges) reduced I2R losses
in cables upstream of the capacitor (and hence reduced energy charges) reduced
voltage drop in the cables (leading to improved voltage regulation) and an increase in
the overall efficiency of the plant electrical system
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
Lecture 15-16
A gas flare alternatively known as a flare stack is an elevated vertical conveyance
found accompanying the presence of oil wells gas wells rigs refineries chemical
plants natural gas plants and landfills They are used to eliminate waste gas which is
otherwise not feasible to use or transport They also act as safety systems for non-
waste gas and is released via pressure relief valve when needed to ease the strain on
equipment They protect gas processing equipments from being overpressured Also
in case of an emergency situation the flare system helps burn out the total reserve gas
Flare and vent systems exist in essentially all segments of the oil and gas industry and
are used for two basic types of waste gas disposal intermittent and continuous
Intermittent applications may include the disposal of waste volumes from emergency
pressure relief episodes operator initiated or instrumented depressurization events
(eg depressurization of process equipment for inspection or maintenance purposes
or depressurization of piping for tie-ins) plant or system upsets well servicing and
testing pigging events and routine blowdown of instruments drip pots and scrubbers
Continuous applications may include disposal of associated gas andor tank vapours at
oil production facilities where gas conservation is uneconomical or until such
economics can be evaluated casing gas at heavy oil wells process waste or byproduct
streams that either have little or no value or are uneconomical to recover
There are inconsistencies in what individual companies may include in their reported
vented and flared volumes and depending on the jurisdiction this information may
not be reported at all The vented and flared volumes reported in production accounting
statistics typically comprise where applicable casing gas venting waste associated gas
flows treater and stabilizer off-gas and gas volumes discharged during process upsets
and equipment depressurization events Storage and loadingunloading losses are
assumed to be generally excluded from reported vented volumes and therefore are
assessed separately
Miscellaneous vented and flared volumes not normally included in reported vented and
flared volumes may include instrument vent gas compressor start gas purge gas and
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-
blanket gas that is discharged directly to the atmosphere dehydrator still column off-gas
purge gas and releases from inspection and maintenance activities
Where vented and flared volumes are reported all measured quantities are usually
captured however flow meters are normally only installed on larger continuous vent
or flare systems if at all Where there is no measurement data the volumes may still
be estimated The problems here are the lack of detailed estimation guidelines the
lack of any formal tracking of the activity data needed to make many of these
estimates (eg frequency and details of equipment or piping blowdown events
frequency of compressor engine starts etc) and differences in which sources
individual operators are even considering
At gas processing plants acid gas volumes are normally reported separately from
other venting or flaring volumes however the latter amounts are reported as a single
aggregated value Venting and flaring from gas gathering systems is also reported as a
single aggregate value
Some operators have tended to use vented and flared entries as balancing terms to
achieve reasonable metering differences when completing production accounting
reports
The problems with conserving or vented and flared volumes may include small
volumes involved at individual sites inconsistencies in flow poor access to gas
gathering systems concerns about putting any back-pressure on the casing in order to
use the gas and operational difficulties associated with using this gas (eg freeze-up
problems in the winter) in the absence of any costly onsite dehydration facilities
The actual quantification of flows in a flare system allows a review of the economics
associated with conserving the flare gas The amount of residual flow in intermittent
flare systems is the sum of the purge gas flow rate and leakage rates into the flare
system
- Boiler Efficiency
- Conductivity as Indicator of Boiler Water Quality
-
- Intermittent Blowdown
- Continuous Blowdown
- Benefits of Blowdown
- Incomplete Combustion
- Excess Air Control
- Proper Boiler Scheduling
-
- Pump Types
- Matching Pump and System Head-flow Characteristics
-
- Fan Laws
- Flow Control Strategies
- Variable Speed Drives
- Table Properties of Commonly used Refrigerants
-
- Range
- Wet Bulb Temperature
- Heat Losses ndashQuality
-
- Benefits of Waste Heat Recovery
- Understanding the process
-
- A variation of the Heat Wheel is the rotary regenerator where the matrix is in a cylinder rotating across the waste gas and air streams The heat or energy recovery wheel is a rotary gas heat regenerator which can transfer heat from exhaust to incoming gases
-
- Lecture 1-2
- Introduction
- Gas Turbine Efficiency
-
- Net Turbine Efficiency
-
- Induction Motors
- Direct-Current Motors
- Synchronous Motors
-
- Tests for Determining Efficiency
-