    VIBRATION ISOLATIONProduct Selection Guidefor HVAC Equipment

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    2/24

    Table of ContentsVibration Isolation and Control .............................................................................................

    Equipment Types- Refrigeration Machines and Chillers ..................................................................................- Air Compressors and Vacuum Pumps ...............................................................................- Pumps ................................................................................................................................

    - Axial, Plenum, Cabinet, and Centrifugal Inline Fans ..........................................................- Centrifugal Fans .................................................................................................................- Cooling Towers ...................................................................................................................- Boilers ................................................................................................................................- Propeller Fans ....................................................................................................................- Ducted Rotating Equipment ...............................................................................................- Packaged AH, AC, H and V Units .......................................................................................- Engine-Driven Generators ..................................................................................................- Heat Pumps, Fan Coils, Computer Room Units .................................................................- Condensing Units ...............................................................................................................- Packaged Rooftop Equipment ............................................................................................

    Products- ASHRAE TYPE 1: Fiberglass or Neoprene Pad ................................................................. -KIP Fiberglass Pad | NP Neoprene Pad | NG Neoprene Pad | RSP Neoprene Pad- The Fiberglass Advantage ..................................................................................................- ASHRAE TYPE 2: Floor Isolator or Hanger ........................................................................ -AC Fiberglass Mount | RD Neoprene Mount | RQ Neoprene Mount

    -FH Fiberglass Hanger | RH Neoprene Hanger - ASHRAE TYPE 3: Spring Floor Isolator or Hanger ............................................................ -FDS Free-Standing Isolator | SL Housed Isolator | SM Housed Isolator

    -SFH Fiberglass Hanger | SRH Neoprene Hanger | SH Hanger - ASHRAE TYPE 4: Restrained Spring Isolator .................................................................... -Titan | FMS | FLS | FLSS | FRS | FHS- ASHRAE TYPE 5: Thrust Restraints .................................................................................. -HSR- ASHRAE TYPE 6: Air Mounts ............................................................................................ -KAM | CAM

    KINFLEX Flexible Connectors ..............................................................................................

    BASE TYPE A: Direct Isolation .............................................................................................BASE TYPE B: Structural Rails ............................................................................................ -SBB | SFBBASE TYPE C: Concrete Inertia Base .................................................................................BASE TYPE D: Curb-Mounted Base .................................................................................... -KSR | KSCR | ESR

    ESSR Sound and Vibration Curb .........................................................................................

    Riser Supports, Anchors, and Guides ..................................................................................

    Seismic Restraint ..................................................................................................................

    Piping/Hanger Selection Data (U.S) .....................................................................................Piping/Hanger Selection Data (SI) ........................................................................................

    Isolation Notes for Speci c Equipment .................................................................................

    2

    345

    6788991010111111

    12

    1213

    14

    15

    16

    16

    16

    1717

    17

    18

    18

    19

    20

    2122

    Back

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    3/24

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    4/24

    Equipment Type:

    Refrigeration Machines and Chillers*

    EquipmentCategory

    ReciprocatingCentrifugal, scrollScrew

    Absorption Air-cooled recip., scroll Air-cooled screw

    ASHRAEType

    444444

    BaseType

    A A A A AB

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    444444

    BaseType

    A A A A AB

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    444444

    BaseType

    A A A A AB

    Up to 20 ft (6 m)

    ASHRAEType

    211414

    BaseType

    A A A A A A

    Slab on Grade

    ASHRAE TYPE 1:Fiberglass or Neoprene PadSee page 12 for more details

    KINETICS TM KIP Fiberglass PadKINETICS TM NP Neoprene Pad

    KINETICSTM

    NG Neoprene PadKINETICS TM RSP Neoprene Pad

    Isolator De .

    4" (102)2" (51)4" (102)2" (51)4" (102)4" (102)

    Isolator De .

    2" (51)2" (51)4" (102)2" (51)2" (51)4" (102)

    Isolator De .

    1" (25)1" (25)2" (51)1" (25)2" (51)2" (51)

    Isolator De .

    1/4" (6)1/4" (6)1" (25)1” (25)1/4" (6)1" (25)

    KIP

    ASHRAE TYPE 2:Floor Isolator or Hanger See page 13 for more details

    KINETICS TM AC Fiberglass MountKINETICS TM RD Neoprene Mount

    KINETICSTM

    RQ Neoprene MountKINETICS TM FH Fiberglass Hanger KINETICS TM RH Neoprene Hanger

    RQ

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMS

    KINETICSTM

    FLSKINETICS TM FLSS

    TITAN

    BASE TYPE A:Direct Isolation

    No base, isolators attached directlyto equipment.

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structural Rail BaseKINETICS TM SFB Structural Beam Base

    RSP FH

    *Data from 2015 ASHRAE Handbook. See back cover for additional notes on Refrigeration Machines.

    3

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    5/24

    Equipment Type:

    Air Compressors and Vacuum Pumps*

    EquipmentCategory

    Tank-mounted horizontal ≤7.5 HP ≥11 HPTank-mounted verticalBase-MountedLarge Reciprocating

    ASHRAEType

    33333

    BaseType

    ACCCC

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    33333

    BaseType

    ACCCC

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    33333

    BaseType

    ACCCC

    Up to 20 ft (6 m)

    ASHRAEType

    33333

    BaseType

    ACCCC

    Slab on Grade

    Isolator De .

    2" (51)2" (51)2" (51)2" (51)2" (51)

    Isolator De .

    2" (51)2" (51)2" (51)2" (51)2" (51)

    Isolator De .

    1" (25)1" (25)1" (25)1" (25)1" (25)

    Isolator De .

    1" (25)1" (25)1" (25)1" (25)1" (25)

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICSTM

    FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS

    BASE TYPE C:Concrete Inertia BaseSee page 17 for more details

    KINETICS TM CIB

    BASE TYPE A:Direct Isolation

    No base, isolators attached directly toequipment.

    SFH

    *Data from 2015 ASHRAE Handbook. See back cover for additional notes on Compressors .**For seismic & wind applications, use ASHRAE TYPE 4

    4

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICSTM

    TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    6/24

    Equipment Type:

    Pumps*

    EquipmentCategory

    Close-Coupled ≤5.6 HP ≥7.5 HPLarge Inline 3.7 to 19 HP ≥22 HPEnd Suction/Split Case ≤30 HP 37 to 93 HP ≥110 HPPackaged Pump Systems

    ASHRAEType

    33

    33

    3333

    BaseType

    CC

    A A

    CCCC

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    33

    33

    3333

    BaseType

    CC

    A A

    CCC A

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    33

    33

    3333

    BaseType

    CC

    A A

    CCC A

    Up to 20 ft (6 m)

    ASHRAEType

    23

    33

    3333

    BaseType

    BC

    A A

    CCC A

    Slab on Grade

    Isolator De .

    1" (25)2" (51)

    2" (51)4" (102)

    2" (51)4" (102)4" (102)4" (102)

    Isolator De .

    1" (25)2" (51)

    2" (51)2" (51)

    2" (51)2" (51)4" (102)2" (51)

    Isolator De .

    1" (25)1" (25)

    2" (51)2" (51)

    1" (25)1" (25)2" (51)1" (25)

    Isolator De .

    1/4" (6)1" (25)

    1" (25)2" (51)

    1" (25)1" (25)1" (25)1" (25)

    BASE TYPE A:Direct Isolation

    No base, isolators attached directlyto equipment.

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structrual Rail BaseKINETICS TM SFB Structural Beam Base

    BASE TYPE C:Concrete Inertia BaseSee page 17 for more details

    KINETICS TM CIB

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS SFH

    ASHRAE TYPE 2:Floor Isolator or Hanger See page 13 for more details

    KINETICS TM AC Fiberglass MountKINETICS TM RD Neoprene MountKINETICS TM RQ Neoprene MountKINETICS TM FH Fiberglass Hanger KINETICS TM RH Neoprene Hanger

    RQFH

    *Data from 2015 ASHRAE Handbook. See back cover for additional notes on Pumps .**For seismic & wind applications, use ASHRAE TYPE 4

    5

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    7/24

    Equipment Type:

    Axial, Plenum, Cabinet, and Centrifugal Inline Fans*

    EquipmentCategory

    Up to 22 in. diameter 24 in. diameter and up ≤2.0 in. SP Up to 300 301 to 500 500 and up ≥2.1 in. SP Up to 300 301 to 500 500 and up

    ASHRAEType

    3

    333

    333

    BaseType

    C

    CCB

    CCC

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    3

    333

    333

    BaseType

    A

    CCB

    CCC

    20 to 30 ft (6 - 9 m) ASHRAE

    Type

    3

    333

    333

    BaseType

    A

    CBB

    CCC

    Up to 20 ft (6 m) ASHRAE

    Type

    2

    333

    333

    BaseType

    A

    BBB

    CCC

    Slab on GradeIsolator De .

    1" (25)

    4" (102)4" (102)2" (51)

    4" (102)4" (102)4" (102)

    Isolator De .

    1" (25)

    4" (102)4" (102)2" (51)

    4" (102)4" (102)2" (51)

    Isolator De .

    1" (25)

    4" (102)2" (51)1" (25)

    4" (102)2" (51)2" (51)

    Isolator De .

    1/4" (6)

    4" (102)1" (24)1" (24)

    4" (102)2" (51)1" (25)

    R P M

    R P M

    BASE TYPE A:Direct Isolation

    No base, isolators attached directlyto equipment.

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structrual Rail BaseKINETICS TM SFB Structural Beam Base

    BASE TYPE C:Concrete Inertia BaseSee page 17 for more details

    KINETICS TM CIB

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS SFH ASHRAE TYPE 2:Floor Isolator or Hanger See page 13 for more details

    KINETICS TM AC Fiberglass MountKINETICS TM RD Neoprene MountKINETICS TM RQ Neoprene MountKINETICS TM FH Fiberglass Hanger KINETICS TM RH Neoprene Hanger

    RQ FH

    *Data from 2015 ASHRAE Handbook.**For seismic & wind applications, use ASHRAE TYPE 4

    6

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITAN

    KINETICSTM

    FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    8/24

    Equipment Type:

    Centrifugal Fans*

    EquipmentCategory

    Up to 22 in. diameter 24 in. diameter and up ≤30 HP Up to 300 301 to 500 500 and up ≥37 HP Up to 300 301 to 500 500 and up

    ASHRAEType

    3

    333

    333

    BaseType

    B

    BBB

    CCC

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    3

    333

    333

    BaseType

    B

    BBB

    CCC

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    3

    333

    333

    BaseType

    B

    BBB

    CCC

    Up to 20 ft (6 m)

    ASHRAEType

    2

    333

    333

    BaseType

    B

    BBB

    CCC

    Slab on Grade

    Isolator De .

    2" (51)

    4" (102)4" (102)2" (51)

    4" (102)4" (102)4" (102)

    Isolator De .

    1" (25)

    4" (102)4" (102)1" (25)

    4" (102)4" (102)2" (51)

    Isolator De .

    1" (25)

    4" (102)2" (51)1" (25)

    4" (102)2" (51)2" (51)

    Isolator De .

    1/4" (6)

    4" (102)2" (51)1" (25)

    4" (102)2" (51)1" (25)

    R P M

    R P M

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structrual Rail BaseKINETICS TM SFB Structural Beam Base

    BASE TYPE C:Concrete Inertia BaseSee page 17 for more details

    KINETICS TM CIB-LKINETICS TM CIB-HKINETICS TM CIB-SS

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS SFH

    ASHRAE TYPE 2:Floor Isolator or Hanger See page 13 for more details

    KINETICS TM AC Fiberglass MountKINETICS TM RD Neoprene MountKINETICS TM RQ Neoprene Mount

    KINETICS TM FH Fiberglass Hanger KINETICS TM RH Neoprene Hanger

    RQ FH ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

    *Data from 2015 ASHRAE Handbook. See back cover for additional notes on Fans .**For seismic & wind applications, use ASHRAE TYPE 4

    7

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    9/24

    Equipment Type:

    Cooling Towers and Boilers*

    Cooling TowersRPM

    Up to 300301 to 500501 and up

    Boiler TypeFire-tubeWater-tube, copper n

    ASHRAEType

    444

    44

    BaseType

    A A A

    BB

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    444

    41

    BaseType

    A A A

    B A

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    444

    41

    BaseType

    A A A

    B A

    Up to 20 ft (6 m)

    ASHRAEType

    111

    11

    BaseType

    A A A

    A A

    Slab on Grade

    Isolator De .

    4" (102)4" (102)1" (25)

    4" (102)1” (25)

    Isolator De .

    4" (102)4" (102)1" (25)

    4" (102)1/4” (6)

    Isolator De .

    4" (102)4" (102)1" (25)

    1" (25)1/4" (6)

    Isolator De .

    1/4" (6)1/4" (6)1/4" (6)

    1/4" (6)1/4" (6)

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHS

    KINETICSTM

    FRS

    TITAN

    ASHRAE TYPE 1:Fiberglass or Neoprene PadSee page 12 for more details

    KINETICS TM KIP Fiberglass PadKINETICS TM NP Neoprene PadKINETICS TM NG Neoprene PadKINETICS TM RSP Neoprene Pad

    KIP RSP

    BASE TYPE A:Direct Isolation

    No base, isolators attached directlyto equipment.

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structrual Rail BaseKINETICS TM SFB Structural Beam Base

    *Data from 2015 ASHRAE Handbook. See back cover for additional notes on Cooling Towers .

    8

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    10/24

    Equipment Type:

    Propeller Fans and Ducted Rotating Equipment*

    Propeller Fans

    Wall-MountedRoof-Mounted

    Ducted Rotating Equip.

    Small fans,fan-poweredboxes

    ASHRAEType

    14

    33

    BaseType

    AD

    A A

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    14

    33

    BaseType

    AB

    A A

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    11

    33

    BaseType

    A A

    A A

    Up to 20 ft (6 m)

    ASHRAEType

    11

    33

    BaseType

    A A

    A A

    Slab on Grade

    Isolator De .

    1/4” (6)2” (51)

    1" (25)1" (25)

    Isolator De .

    1/4” (6)4" (102)

    1" (25)1" (25)

    Isolator De .

    1/4” (6)1/4” (6)

    1" (25)1" (25)

    Isolator De .

    1/4" (6)1/4" (6)

    1" (25)1" (25)

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

    ASHRAE TYPE 1:Fiberglass or Neoprene PadSee page 12 for more details

    KINETICS TM KIP Fiberglass PadKINETICS TM NP Neoprene PadKINETICS TM NG Neoprene PadKINETICS TM RSP Neoprene Pad

    KIP RSP

    BASE TYPE A:Direct Isolation

    No base, isolators attached directly toequipment.

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS SFH

    ≤636 cfm≥637 cfm

    *Data from 2015 ASHRAE Handbook.

    9

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    11/24

    Equipment Type:

    Packaged AH, AC, H and V Units; Engine-Driven Generators*

    Horsepowerand Other

    ≤7.5 HP≥11 HP≤4 in. SP

    >15>4 in. SP

    ASHRAEType

    3333333

    BaseType

    AC A ACCC

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    3333333

    BaseType

    A A A ACCC

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    3333333

    BaseType

    A A A ACCC

    Up to 20 ft (6 m)

    ASHRAEType

    3333333

    BaseType

    A A A ABBB

    Slab on Grade

    Isolator De .

    1" (25)4" (102)4" (102)2" (51)4" (102)4" (102)4" (102)

    Isolator De .

    1" (25)4" (102)4" (102)2" (51)4" (102)4" (102)2" (51)

    Isolator De .

    1" (25)4" (102)4" (102)2" (51)4" (102)2" (51)2" (51)

    Isolator De .

    1" (25)1" (25)1" (25)1" (25)1" (25)1" (25)1" (25)

    RPM

    AllUp to 300301 to 500500 and upUp to 300301 to 500500 and up

    Packaged AH, AC, H

    and V Units

    BASE TYPE A:Direct Isolation

    No base, isolators attached directlyto equipment.

    BASE TYPE B:Structur al Steel Rails or BaseSee page 17 for more details

    KINETICS TM SBB Structrual Rail BaseKINETICS TM SFB Structural Beam Base

    BASE TYPE C:Concrete Inertia BaseSee page 17 for more details

    KINETICS TM CIB

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator KINETICS TM SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    FDS SFH

    *Data from 2015 ASHRAE Handbook. See Back for additional notes on Air-Hand ling Eq uipmen t .**For seismic & wind applications, use ASHRAE TYPE 4

    10

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLSKINETICS TM FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    12/24

    Equipment Type:

    Heat Pumps, Fan-Coils, Computer Room Units; CondensingUnits; Packaged Rooftop Equipment*

    EquipmentType

    Heat Pumps, Fan-Coils,Computer Room Units

    Condensing Units

    Packaged RooftopEquipment

    ASHRAEType

    3

    4

    N/A

    BaseType

    A/D

    A/D

    N/A

    30 to 40 ft (9-12 m)

    Equipment Location

    Floor Span

    ASHRAEType

    3

    4

    N/A

    BaseType

    A

    A

    N/A

    20 to 30 ft (6 - 9 m)

    ASHRAEType

    3

    4

    3

    BaseType

    A

    A

    D

    Up to 20 ft (6 m)

    ASHRAEType

    3

    1

    1

    BaseType

    A

    A

    A/D

    Slab on Grade

    Isolator De .

    2" (51)

    2" (51)

    N/A

    Isolator De .

    1" (25)

    2" (51)

    N/A

    Isolator De .

    1" (25)

    1" (25)

    1" (25)

    Isolator De .

    1" (25)

    1/4" (6)

    1/4" (6)

    FDS SFH

    ASHRAE TYPE 1:Fiberglass or Neoprene PadSee page 12 for more details

    KINETICS TM KIP Fiberglass PadKINETICS TM NP Neoprene PadKINETICS TM NG Neoprene Pad

    KINETICSTM

    RSP Neoprene Pad

    KIP

    ASHRAE TYPE 3:Spring Floor Isolator or Hanger See page 14 for more details

    KINETICS TM FDS Free-Standing Isolator KINETICS TM SL Housed Isolator KINETICS TM SM Housed Isolator

    KINETICSTM

    SFH Fiberglass Hanger KINETICS TM SRH Neoprene Hanger KINETICS TM SH Hanger

    ASHRAE TYPE 4:Restrained Spring Isolator See page 15 for more details

    KINETICS TM TITANKINETICS TM FMSKINETICS TM FLS

    KINETICSTM

    FLSSKINETICS TM FHSKINETICS TM FRS

    TITAN

    BASE TYPE A:Direct Isolation

    No base, isolators attached directly toequipment.

    BASE TYPE D:Curb-Mounted BaseSee page 18 for more details

    KINETICS TM KSR Isolation RailKINETICS TM KSCR Isolation CurbKINETICS TM ESR Isolation Curb

    RSP

    *Data from 2015 ASHRAE Handbook. See back for additional notes on Packaged Rooftop Equipment .

    11

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    13/24

    ASHRAE TYPE 1: Fiberglass or Neoprene Pad

    KINETICS TM KIPFiberglass Isolation Pad

    Description : A high-density matrix of compressedmolded berglass; individually coated with a exible,moisture-impervious elastomeric membrane, designedto allow controlled air movement in the ber media.

    Application : Recommended as support mounts forhigh speed fans, pumps, and chillers, on grade, havingoperating speeds of 1750 RPM and higher.

    Capacity : Provide load-bearing capacities from 5 to500 PSI (0.35 to 35 kg per sq. cm) of pad surface area.

    KINETICS TM RSPNeoprene Isolation PadDescription : Elastomer in-shear, 50 durometer pads

    Appl ication : Isolate noise, shock, and high frequency vibration produced by mechanical,industrial, or process equipment located on grade, structural slab, or in other non-critical areas.

    Capacity : Designed to permit 60 psi (4.2 kg/cm 2) loading at a maximum rated de ection of0.15" (4 mm)

    Dimensions : 18" x 18" x 3/4" (457 mm x 457 mm x 19 mm) thick sheets, scored into2" x 2" x 3/4" (51 mm x 51 mm x 19 mm) thick pads

    KINETICS TM NP and NGNeoprene Isolation Pads

    Description : 45 to 65 durometer single ribbed orcrossed, double ribbed elastomer-in-shear pads, incombination with steel shims when required, havingminimum static de ections as tabulated.

    Application : Isolate noise, shock, and high frequencyvibration, generated by mechanical equipment andindustrial machinery located on a grade-supportedstructural slab.

    Capacity : Designed to permit 60 or 120 PSI(4.2 or 8.4 kg/cm 2) loading at maximum ratedde ections.

    Dimensions : Pads are available in 4", 6", or 9"(102, 152, 228 mm) squares with capacities from 400to 9,700 lbs. (181 to 4400 kg), or in full 18" (457 mm)square sheets which can be cut or drilled to meet eld

    requirements.De ection : NP Pads 0.04" to 0.09" (1 mm to 2 mm)NG Pads 0.13" to 0.19" (3 mm to 5 mm)

    The Fiberglass AdvantageKinetics Noise Control manufactures both

    berglass and neoprene isolators. Fiberglass

    isolators offer the following advantages:• UV resistant for outdoor use• Constant location performance through

    seasonal temperature changes• Varying densities and sizes to suit a

    variety of load requirements• Constant pad performance, unaffected by

    age or high temperatures

    12

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    14/24

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    15/24

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    16/24

    KINETICS TM TITANVibration Isolator /RestraintPatent PendingDescription : Comprised of two interfacing but independent elements;two or more high de ection, free-standing, housed, large diameter,\laterally stable steel springs, and a seismically rated housing.

    The steel springs and elastomeric snubber element are eachreplaceable without having to lift or otherwise remove the supported equipment.

    Appl ication : Recommended for equipment mounted on a structural frame or concrete inertia base wherethe top plate of the isolator can be fully utilized.

    Capacity : up to 23,200 lbs. (10,523 kg) De ection : up to 4 in. (102 mm)

    KINETICS TM FLS/FLSSRestrained Spring IsolatorsDescription : Free-standing, large diameter, laterallystable steel springs assembled into welded steel housing

    assemblies fabricated to limit vertical movement of theisolated equipment. The housings provide a constantfree and operating height to facilitate installation.

    Appl ication : Recommended for the isolation of vibrationproduced by equipment carrying a large uid load whichmay be drained, such as boilers and chillers, and for theisolation of outdoor components such ascooling towers and air-cooled condens-ers.

    Capacity : up to 23,200 lbs. (10,523 kg)De ection : up to 4 in. (102 mm)

    KINETICS TM FMS(U.S. Patent No. 7,028,969 )

    Modular Restraint /Isolator Description : The unit is comprised of arestraint module and an optional vibration isolationmodule. This modular design allows the engineer todesign for seismic or wind forces independent of theload and de ectionrequirements of the vibration isolator.

    Appl ication : Ideal for cooling towers, chillers, boilersor other equipment where the potential for wide weightvariations during service is anticipated.

    Capacity : up to 23,200 lbs. (10,523 kg)De ection : up to 4 in. (102 mm)

    KINETICS TM FRSRestrained Spring Isolator Description : Free-standing, large diameter, stablesteel springs assembled into top and bottom loadplate assemblies, which providevertical restraint in the event loadis removed or external forces areapplied.

    Appl ication : Recommended for thesupport of vertical pipe risers; andair-cooled condensers, fans, and otherrooftop equipment subject to weightchange or external forces.

    Capacity : 35 lbs. to 3,500 lbs. (16 kg to1,588 kg)De ection : 1 in. to 2 in. (25 mm to 51 mm)

    KINETICS TM FHSRestrained Spring Isolator Description : A KINETICS TM FDSFree-Standing Isolator with a steel hous-ing assembly to limit lateral and verticalmovement of the supported equipment during an earth-quake without degrading the vibration isolation of thespring during normal equipment operating conditions.

    Appl ication : Recommended for mechanical equip-ment located near critically quiet areas when there is

    a possibility that the equipment to be isolated will besubjected to the external forces associated with anearthquake.

    Capacity : up to 5,800 lbs. (2,631 kg)De ection : up to 4 in. (102 mm)

    ASHRAE TYPE 4: Restrained Spring Isolator

    15

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    17/24

    KINETICS TM KAM and CAM

    Air Vibration Iso lation Mounts

    Description : Pneumatic, elastomeric vibration mounts.The CAM is available in four (4) sizes supporting loadsup to 7,500 lbs. The KAM is available in seven (7) sizeswith capacities from 500 to 22,000 lbs. per mount.

    Appl ication : Recommended for mechanical equipmentand industrial process equipment requiring low naturalfrequency isolation, as well as protecting sensitiveequipment from disturbing oor-borne vibration.

    ASHRAE TYPE 5:Thrust RestraintKINETICS TM HSR

    Thrust Restraint

    Description : A high de ection, large diameter, laterallystable steel coil spring assembled into a threaded rodand bracket assembly.

    Appl ication : Used to counteract the discharge forcecreated by fans during operation. Recommended for all

    fan heads, suspended fans, and all base-mounted andsuspended air-handling equipment operating at 2 inchesor greater total static pressure (TSP). HSR ThrustRestraints are always installed in pairs and often work inconjunction with inertia bases for oor-mounted fans tocounteract fan thrust.

    Capacity : 35 to 1,975 lbs. (16 to 896 kg)

    De ection : 1 in. to 2 in. (25 mm to 51 mm)

    ASHRAE TYPE 6: Air Springs

    KINETICS TM KINFLEXFlexible ConnectorsDescription : Prevent stresses due to expansion andcontraction, isolate against the transfer of noise andvibration, and compensate for misalignment.

    Appl ication : Used on both hot and chilled watercirculation lines, suction and discharge sides ofpumps, and header connections.

    KINFLEX Seismic V-Loops solve the problemsof pipe motion caused by thermal pipe growth andthe movements associated with seismic activity.Seismic V-loops limit amount of space required forinstallation and hold in more heat then to traditionallarge pipe loops.

    16

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    18/24

    BASE TYPE A: Direct IsolationUsed when equipment is unitary and rigid and does not require additional support. Direct isolation can be usedwith large chillers, some fans, packaged air-handling units, and air-cooled condensers. If there is any doubt thatthe equipment can be supported directly on isolators, use structural bases (type B) or inertia bases (type C), orconsult the equipment manufacturer.

    BASE TYPE B: Structural RailsKINETICS TM SFBStructural Frame BaseDescription : Welded structural frame bases withchannels, angles, or WF beams, which are completewith outboard height-saving isolator brackets andprelocated equipment anchor bolts.

    Appl ication : Recommended for support andisolation of reciprocating chillers, close coupledpumps, vent sets, packaged air handling units,centrifugal fans, evaporative condensers, andsimilar types of equipment.

    KINETICS TM SBBStructural Beam BaseDescription : Structural steel beam sections, withwelded-on isolator support brackets, and pre-locatedand drilled anchor bolt holes for bolting to equipmentto be supported.

    Appl ication : Recommended for support andisolation of absorption chillers, hermetic centrifugalchillers, package boilers, cooling towers, and similartypes of equipment.

    BASE TYPE C: Concrete Inertia Base

    KINETICS TM CIBConcrete Inertia BaseDescription : A unique structural design which integrates perimeter channels, isolator support brackets,reinforcing rods, anchor bolts and concrete ll into a controlled load transfer system, utilizing steel in tensionand concrete in compression, resulting in high strength and stiffness with minimum steel frame weight.

    Appl ication : Recommended for use with open-type centrifugal chillers, reciprocating air and refrigerationcompressors, chillers, and heat pumps, close-coupled and base-mounted pumps, centrifugal fans, internalcombustion engines, and similar types of equipment.

    17

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    19/24

    KINETICS TM KSRRoof Curb RailDescription : Noise and vibration control roofcurb rail featuring horizontal and vertical seismicand wind restraints, multiple spring de ectionoptions, custom taylored t (compatible withmost curb-mounted equipment), and continuousair- and water-tight seal.

    Appl ication : Recommended for support andisolation for unitary-packaged air-handling andrefrigeration equipment, and exhaust fans,ordinarily mounted directly on non-isolated roofcurb systems.

    KINETICS TM KSCR and ESRVibration Isolation CurbsDescription : Complete assemblies designed toresiliently support equipment at the speci edelevation and which constitute a fully enclosedair and weather-tight system.

    Standard Features• Seismic and wind restraint• Up to 4" (102 mm) de ection, powder-coated steel

    springs with 50% overload capacity• Supply and return exible connector support• Environmentally inert elastomeric seal for an air and

    water-tight closure between the curb and rail• High pro le, non-interference aluminum rail (only KSCR)• Accessible ports for each isolator to inspect, level, or

    change springs after equipment placement (only ESR)Options• De ections over 4" (102 mm)• Interface for sloped or multi-pitched roofs• Additional height for plenums & silencers• Exterior thermal insulation• Acoustical treatments• Certi cation of seismic and wind load engineering

    Vibration from fans and compressors (source 1)and vibration from casing- radiated noise caused byduct turbulence and the airborne noise of the fansand compressors (source 2) are controlled with highde ection, laterally stable coil spring isolators andhigh frequency neoprene noise pads.

    Duct-borne noise from the supply and return air fans(source 3) are controlled using an aerodynamicacoustical silencer on the supply fan and anacoustical plenum on the return air side both withminimal pressure drop.

    Breakout noise through the bottom of the rooftopunit (source 4) is controlled by the NOISEBLOCK™STL acoustical panel located in the oor of theESSR.

    KINETICS TM ESSRSound and Vibration Isolation CurbKINETICS TM ESSR is the only isolated curb system that addresses all four noise sources associated with packagedrooftop equipment. The ESSR incorporates all the features of our ESR vibration isolation curb with our aerodynamicacoustical silencers; return air plenums and NOISEBLOCK™ STL panels. This gives you a noise control systemthat addresses all the noise and vibration concerns of your packaged rooftop equipment: vibration from the rotatingequipment and casing radiation, duct-borne noise from supply and return fans, and breakout noise from the fans andcompressors into the space below.

    18

    BASE TYPE D: Curb-Mounted Base

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    20/24

    Riser Supports , Anchors, and GuidesKINETICS TM riser supports, anchors, and guides isolate the pipe from the structure to minimize noiseand vibration transmission, while also allowing the pipe to expand and contract with minimal changein the support forces. Kinetics offers engineering services to assist in the design of your riser system.

    19

    Riser Guide

    Riser Isolator

    Riser Anchor

    Riser Hanger

    KPG

    FDS

    KRG

    KPA

    SFH

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    21/24

    Seismic Restraint

    KINETICS TM QuakeLoc TM

    Seismic Cable Restraint KitsPiping, duct, electrical cable trays, and suspended equipment

    • Reduces Installation Time and Cost• Contractor Friendly Design• IBC Code Compliant

    AccessoriesKHRC Adjustable Angle Rod Stiffeners : Securely attach a

    length of steel angle to a conventional hanging threaded rod.KSBC Seismic Beam Clamp : Attach seismic restraints to roofor oor support I-beams.

    Suspended Equipment Example

    KINETICS TM HS SeriesSeismic SnubbersDescription : Heavy structural steel assemblies designed to minimizeequipment motion within the product’s design capabilities without failing.

    Seismic Snubbers are designed to be used in pairs and serve to keepsupported equipment contained when the equipment is subjected tolateral or vertical forces along any axis.

    KINETICS TM Seismic Mounting BracketsKINETICS TM KSMS : Solid-mount equipment to the building structureKINETICS TM KSMG : Resiliently mount and restrain equipment to the building structureKINETICS TM KSMF : Solid-mount mushroom fans to the curb

    Seismic restraint systems limit movement and keep equipment captive during a seismic event. Proper utilization ofthese systems can reduce the threat to life and minimize long-term costs due to equipment damage and associatedloss of service. Additional seismic restraint products can be found within ASHRAE Type 4 (page 15) and Base Type D(page 18).

    20

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    22/24

    PIPING/HANGER SELECTION DATA (U.S.)

    Piping Weight and Spacing - Water Pipe Size (in.)Pipe ScheduleMax. Spacing (ft.)Insulation (in.)*Wt. per Lin. Ft. (lb.) Pipe Water

    Insulation TotalWt. @ 10 ft. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended. Rod Size (in.)**Wt. @ 20 ft. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (in.)**Max. Spacing (ft.)Wt. @ Max. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1

    SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (in.)**

    242032

    1.5

    94.9184.0

    10.7289.62896

    3500-

    30001.00

    -

    ----

    32-

    -

    ---

    202030

    1.5

    78.8126.1

    9.0213.92139

    2200250022500.88

    -

    ----

    30-

    -

    ---

    183028

    1.5

    82.299.8

    8.2190.21902

    2200200022500.88

    -

    ----

    28-

    -

    ---

    163027

    1.5

    62.779.2

    7.3149.21492

    1700200016000.75

    2984

    3500-

    30001.00

    27-

    -

    ---

    143025

    1.5

    54.759.8

    6.5121.01210

    1250120012500.75

    2419

    2465250025000.88

    253024

    3500

    -35001.00

    2.54011

    1.0

    5.82.1

    1.19.090

    125120100

    0.38-

    ----

    1199

    125

    1201000.38

    24010

    1.0

    3.71.5

    0.96.161

    7070

    1000.38

    -

    ----

    1061

    70

    701000.38

    1.540

    91.0

    2.70.9

    0.84.4-

    -----

    ----9

    40

    70

    70-0.38

    1.2540

    71.0

    2.30.6

    0.73.6-

    -----

    ----7

    26

    35

    35-0.38

    140

    71.0

    1.70.4

    0.62.7-

    -----

    ----7

    19

    35

    35-0.25

    84019

    1.5

    28.621.7

    4.254.5545

    600720500

    0.50-

    ----

    191036

    1000

    120012500.62

    64017

    1.5

    19.012.5

    3.434.9349

    370465500

    0.50-

    ----

    17594

    600

    7207500.50

    54016

    1.5

    14.78.7

    3.026.4264

    370465250

    0.50-

    ----

    16421

    500

    4655000.50

    44014

    1.0

    10.85.5

    1.517.8178

    245220250

    0.50-

    ----

    14250

    370

    4652500.50

    34012

    1.0

    7.63.2

    1.312.1121

    125120100

    0.38-

    ----

    12145

    245

    2202500.38

    124023

    1.5

    53.748.5

    6.0108.21082

    1250102510000.62

    2163

    2200250022500.88

    232487

    2865

    250025000.88

    104020

    1.5

    40.634.2

    5.179.9799

    800850750

    0.621598

    1700200016000.75

    201598

    1700

    200016000.75

    Piping Weight and Spacing - SteamPipe Size (in.)Pipe ScheduleInsulation (in.)*Wt. per Ft. (lbs.) Pipe Insulation TotalWt. @ 10 ft. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (in.)**

    Wt. @ 20 ft. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (in.)**Max. Spacing (ft.)Wt. @ Max. Spacing (lb.)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (in.)**

    2420

    2.094.9

    14.5109.41094

    1250120012500.62

    218722002500

    22501.00

    394266

    ----

    2020

    2.078.8

    12.391.1911

    1000102510000.62

    182222002000

    22500.88

    393552

    ----

    1830

    2.082.2

    11.293.4934

    1000102510000.62

    186722002000

    22500.88

    373454

    ----

    1630

    2.062.7

    10.172.8728

    800720750

    0.62

    145617002000

    16000.75

    352548

    2865250027501.00

    1430

    2.054.7

    8.963.6636

    625720750

    0.62

    127312502000

    16000.75

    322036

    2200200022501.00

    2.540

    1.55.8

    1.87.676

    7070

    1000.38

    ---

    --

    14107

    125120100

    0.38

    240

    1.53.7

    1.65.353

    7070

    1000.38

    ---

    --

    1369

    7070

    1000.38

    1.540

    1.52.7

    1.44.141

    3535

    -0.38

    ---

    --

    1250

    7070

    -0.38

    1.2540

    1.52.3

    1.33.636

    3535

    -0.38

    ---

    --

    1036

    3535

    -0.38

    140

    1.51.7

    1.22.9

    -

    ----

    ---

    --9

    26

    3535

    -0.25

    840

    2.028.6

    5.934.6346

    370465500

    0.50

    691625720

    7500.62

    24829

    1000850

    10000.62

    640

    2.019.0

    4.823.8238

    245220250

    0.50

    477500720

    5000.50

    21501

    500720500

    0.50

    540

    2.014.7

    4.218.9189

    245220250

    0.50

    ---

    --

    19359

    370465500

    0.50

    440

    1.510.8

    2.513.3133

    125120100

    0.38

    ---

    --

    17227

    245220250

    0.50

    340

    1.57.6

    2.19.797

    125120100

    0.38

    ---

    --

    15145

    245220100

    0.38

    1240

    2.053.7

    8.261.9619

    625720750

    0.62

    123812502000

    12500.75

    301857

    2200200022500.88

    1040

    2.040.6

    7.147.7477

    500720500

    0.50

    95410001025

    10000.62

    261240

    1250200012500.75

    *Insulation weight based on industry standard insulation.**Rod size recommendation and max. hanger spacing based on MSS SP-69 Approx imate Flanged Fitt ing Weig hts (lb.)

    Pipe Size

    (In.)11.52

    2.534568

    10121416182024

    BonnetCheck

    Valve--

    26364680

    120155300450675900

    1200137117723000

    BonnetGate

    Valve927375066

    109140170250470690950

    1250165020003100

    Elbow812182733567897

    160260390520725980

    13001850

    Tee1118243540749111718229040060075093011001850

    Flange44579

    15192332527093

    120140175250

    21

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    23/24

    PIPING/HANGER SELECTION DATA (SI)

    Piping Weigh t and Spacing - Water Pipe Size (mm)Pipe ScheduleMax. Spacing (m)Insulation (mm)*Wt. per M (kg) Pipe Water

    Insulation TotalWt. @ 3 m Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended. Rod Size (mm)**Wt. @ 6 m Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (mm)**Max. Spacing (m)Wt. @ Max. Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1

    SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (mm)**

    61020

    9.838

    141.3274.0

    15.9431.21294

    3500-

    300025

    -

    ----

    9.8-

    -

    ---

    50820

    9.138

    117.3187.8

    13.4318.5955

    220025002250

    22-

    ----

    9.1-

    -

    ---

    45730

    8.538

    122.4148.6

    12.2283.2850

    220020002250

    22-

    ----

    8.5-

    -

    ---

    40630

    8.238

    93.3117.9

    10.9222.1666

    170020001600

    191332

    3500-

    300025

    8.2-

    -

    ---

    35630

    7.638

    81.489.0

    9.7180.1540

    125012001250

    191080

    246525002500

    227.6

    1371.7

    3500

    -350025

    6440

    3.425

    8.63.1

    1.613.340

    125120100

    10-

    ----

    3.444.9

    125

    12010010

    5140

    3.025

    5.52.2

    1.39.027

    7070

    10010

    -

    ----

    3.027.7

    70

    7010010

    3840

    2.725

    4.01.3

    1.26.5-

    -----

    ----

    2.718.1

    70

    70-10

    3240

    2.125

    3.40.9

    1.05.3-

    -----

    ----

    2.111.8

    35

    35-10

    2540

    2.125

    2.50.6

    0.94.0-

    -----

    ----

    2.18.6

    35

    35-6

    20340

    5.838

    42.632.3

    6.281.1243

    600720500

    13-

    ----

    5.8469.9

    1000

    1200125016

    15240

    5.238

    28.318.6

    5.152.0156

    370465500

    13-

    ----

    5.2269.4

    600

    72075013

    12740

    4.938

    21.912.9

    4.539.3118

    370465250

    13-

    ----

    4.9190.9

    500

    46550013

    10240

    4.325

    16.18.2

    2.226.580

    245220250

    13-

    ----

    4.3113.4

    370

    46525013

    7640

    3.725

    11.34.8

    1.918.054

    125120100

    10-

    ----

    3.765.8

    245

    22025010

    30540

    7.038

    80.072.1

    9.0161.1483

    125010251000

    16966

    220025002250

    227.0

    1128.1

    2865

    2500250022

    25440

    6.138

    60.550.9

    7.6119.0357

    800850750

    16714

    170020001600

    196.1

    724.8

    1700

    2000160019

    Piping Weigh t and Spacing - SteamPipe Size (mm)Pipe ScheduleInsulation (mm)*Wt. per m (kg) Pipe Insulation TotalWt. @ 3 m Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (mm)**

    Wt. @ 6 m Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (mm)**Max. Spacing (m)Wt. @ Max. Spacing (kg)KNC Hanger Model No. SH/SRH/SFH -1 SH/SRH/SFH -2 SH/SRH/SFH -4Recommended Rod Size (mm)*

    6102051

    141.321.6

    162.9489

    125012001250

    16

    978

    220025002250

    2511.9

    1935

    ----

    5082051

    117.318.3

    135.6407

    100010251000

    16

    814

    220020002250

    2211.9

    1611

    ----

    4573051

    122.416.7

    139.1417

    100010251000

    16

    834

    220020002250

    2211.3

    1567

    ----

    4063051

    93.415.0

    108.4325

    800720750

    16

    650

    170020001600

    1910.71156

    286525002750

    25

    3563051

    81.413.394.7284

    625720750

    16

    568

    125020001600

    199.8

    924

    220020002250

    25

    644038

    8.62.7

    11.334

    7070

    10010

    -

    ----

    4.349

    125120100

    10

    514038

    5.52.47.924

    7070

    10010

    -

    ----

    4.031

    7070

    10010

    384038

    4.02.16.118

    3535

    -10

    -

    ----

    3.723

    7070

    -10

    324038

    3.41.95.316

    3535

    -10

    -

    ----

    3.016

    3535

    -10

    254038

    2.51.84.3

    -

    ----

    -

    ----

    2.712

    3535

    -6

    2034051

    42.68.8

    51.4154

    370465500

    13

    308

    625720750

    167.3

    376

    1000850

    100016

    1524051

    28.37.1

    35.4106

    245220250

    13

    212

    500720500

    136.4

    227

    500720500

    13

    1274051

    21.96.2

    28.184

    245220250

    13

    -

    ----

    5.8163

    370465500

    13

    1024038

    16.13.7

    19.859

    125120100

    10

    -

    ----

    5.2103

    245220250

    13

    764038

    11.33.1

    14.443

    125120100

    10

    -

    ----

    4.666

    245220100

    10

    3054051

    80.012.292.2277

    625720750

    16

    554

    125020001250

    199.1

    842

    220020002250

    22

    2544051

    60.510.571.0213

    500720500

    13

    426

    100010251000

    168.0

    562

    125020001250

    19

    *Insulation weight based on industry standard insulation.**Rod size recommendation and max. hanger spacing based on MSS SP-69 Approx imate Flan ged Fitting Weights (kg)

    Pipe Size

    (mm)2538516476

    102127152203254305356406457508610

    BonnetCheck

    Valve--

    11.816.320.136.354.470.3

    136.1204.1306.2408.2544.3621.9803.8

    1360.8

    BonnetGate

    Valve4.112.216.822.730.049.463.577.1113.4213.2313.0430.9567.0748.4907.2

    1406.1

    Elbow3.65.48.2

    12.215.025.435.444.072.6

    117.9176.9235.9328.9444.5589.7839.1

    Tee5.08.2

    10.115.918.133.641.353.182.6

    131.5181.4272.2340.2421.8499.0839.1

    Flange1.81.82.33.24.16.88.6

    10.414.523.631.842.254.463.579.4113.4

    22

  • 8/17/2019 Vibration Isolator - Kinetic Noise Control

    24/24

    Isolation Notes for Specic Equipment*Kinetics Noise Control strongly recommends 2015 ASHRAEHandbook, Chapter 48 Noise and Vibration Control as acompanion to this product selection guide.

    Refrigeration MachinesLarge centrifugal, screw, and reciprocating refrigerationmachines may generate very high noise levels; special attentionis required when such equipment is installed in upper-story loca-tions or near noise-sensitive areas. If equipment is located near

    extremely noise-sensitive areas, follow the recommendations ofan acoustical consultant.

    CompressorsThe two basic reciprocating compressors are duct structures. (1)single- and double-cylinder vertical, horizontal or L-head, whichare usually air compressors; and (2) Y, W, and multi-head ormulti-cylinder air and refrigeration compressors. Single- and dou-ble-cylinder compressors generate high vibratory forces requiringlarge inertia bases (type C) and are generally not suitable for up-per-Story locations. If this equipment must be installed in an up-per-story location or at-grade location near noise-sensitive areas,the expected maximum unbalanced force data must be obtainedfrom the equipment manufacturer and a vibration specialist con-sulted for design of the isolation system.

    When using Y, W, and multi-head and multi-cylinder compressors,obtain the magnitude of unbalanced forces from the equipmentmanufacturer so the need for an inertia base can be evaluated.

    Base-mounted compressors through 5 hp and horizontaltank-type air compressors through 10 hp can be installed directlyon spring isolators (type 3) with structural bases (type B) if re-quired, and compressors 15 to 100 hp on spring isolators (type 3)with inertia bases (type C) with a mass I to 2 times the compressormass.

    PumpsConcrete inertia bases (type C) are preferred for all exible-coupled pumps and are desirable for most close-coupled pumps,although steel bases (type B) can be used. Close-coupled pumpsshould not be installed directly on individual isolators (type A)because the impeller usually overhangs the motor support base,causing the rear mounting to be in tension. The primary require-ments for type C bases are strength and shape to accommodatebase elbow supports. Mass is not usually a factor, except forpumps over 75 hp, where extra mass helps limit excess move-ment due to starting torque and forces. Concrete bases (type C)should be designed for a thickness of one-tenth the longest di-mension with minimum thickness as follows: (1) for up to 30 hp, 6in; (2) for 40 to 75 hp, 8 in; and (3) for 100 hp and up, 12 in.

    Pumps over 75 hp and multistage pumps may exhibit excessivemotion at start-up (“heaving”); supplemental restraining devicescan be installed if necessary. Pumps over 125 hp may generatehigh starting forces; a vibration specialist should be consulted.

    Cooling TowersThese are normally isolated with restrained spring isolators (type4) directly under the tower or tower dunnage. High de ectionisolators proposed for use directly under the motor-fan assembly

    must be used with extreme caution to ensure stability and safetyunder all weather conditions.

    Packaged Rooftop Air-Conditioning EquipmentThis equipment is usually installed on lightweight structures thatare susceptible to sound and vibration transmission problems.The noise problems are compounded further by curb-mountedequipment, which requires large roof openings for supply andreturn air.

    Type D vibration isolators are shown for all spans up top 20 ft,but extreme care must be taken for equipment located on spansof over 20 ft, especially if construction is open web joists or thin,lightweight slabs. The recommended procedure is to determinethe additional de ection caused by equipment in the roof. If ad-ditional roof de ection is 0.25 in. or less, the isolator should beselected for 10 times the additional roof de ection. If additionalroof de ection is over 0.25 in, supplemental roof stiffening shouldbe installed to bring the roof de ection down below 0.25 in, or theunit should be relocated to a stiffer roof position.

    For mechanical units capable of generating high noise levels,mount the unit on a platform above the roof deck to provide anair gap (buffer zone) and locate the unit away from the associatedroof penetration to allow acoustical treatment of ducts before theyenter the building.Some rooftop equipment has compressors, fans, and otherequipment isolated internally. This isolation is not always reliablebecause of internal short-circuiting, inadequate static de ection,or panel resonances. It is recommended that rooftop equipmentover 300 lb be isolated externally, as if internal isolation was notused.

    Fans and Air-Handling EquipmentConsider the following in selecting isolation systems for fans andair-handling equipment:

    1. Fans with wheel diameters of 22 in. and less and all fansoperating at speeds up to 300 rpm do not generate large vibra-tory forces. For fans operating under 300 rpm, select isolator

    de ection so the isolator natural frequency is 40% or less thanthe fan speed. For example, for a fan operating at 275 rpm, 0.4x 275 = 110 rpm. Therefore, an isolator natural frequency of 110rpm or lower is required. This can be accomplished with a 3 in.de ection isolator (type 3).

    2. Flexible duct connectors should be installed at the intake anddischarge of all fans and air-handling equipment to reducevibration transmission to air duct structures.

    3. Inertia bases (type C) are recommended for all class 2 and 3fans and air-handling equipment because extra mass allowsthe use of stiffer springs, which limit heaving movements.

    4. Thrust restraints (type 5) that incorporate the same de ectionas isolators should be used for all fan heads, all suspendedfans, and all base-mounted and suspended air-handling equip-ment operating at 2 in. or more total static pressure. Restraint

    movement adjustment must be made under normal operationalstatic pressures.

    *Reprinted with permission from 2015 ASHRAE Handbook.