vector series - tropical marine air conditioning€™ vector series® air conditioner. ... the...

28
Direct Expansion Systems Revised: 4-15-04 L-2166 vector series Installation & Operation

Upload: phamliem

Post on 15-Jul-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

Direct Expansion SystemsRevised: 4-15-04L-2166

vector seriesInstallation & Operation

Page 2: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the
Page 3: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

3 ❖❖❖❖❖ EnglishL-2166

TABLE OF CONTENTS

IntroductionHow It Works ............................................................................................................................................... 4

InstallationUnpacking and Inspection .......................................................................................................................... 5Safety Considerations ................................................................................................................................ 5Placement of System ................................................................................................................................. 5Condensate Drains..................................................................................................................................... 6Blower Assembly ........................................................................................................................................ 6Mounting Brackets ...................................................................................................................................... 6Supply & Return Air Grilles and Transition Boxes ...................................................................................... 6Ducting........................................................................................................................................................ 6Seawater Pump and Plumbing .................................................................................................................. 7Electrical Connections, Grounding and Bonding ....................................................................................... 8Manual Control Panel (MCP) Installation ................................................................................................... 8Installation Checklist (Review prior to installation) ..................................................................................... 9

OperationMechanical Control Panel (MCP) Operation ............................................................................................ 10Quick Start Operations Checklist ............................................................................................................. 10

TroubleshootingGeneral Troubleshooting .......................................................................................................................... 11Digital Controls Troubleshooting .............................................................................................................. 12MCP Mechanical Control Panel Troubleshooting..................................................................................... 14

MaintenanceWinterization ............................................................................................................................................. 15

Manufacturers Limited Warranty Agreement 16

Description of Figures 17

Distributor Listing 25

Copyright 2004 Dometic Corporation, All Rights Reserved - Every precaution has been taken in the preparation of this manual to insure its accuracy. However, Dometic assumes noresponsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of this product and information contained herein.

IF YOU HAVE A DIGITAL CONTROLPlease refer to either the Elite Control manual or the Passport I/O Control manual for installation and operation of thosedigital control panels. Mechanical control information and wiring diagrams for both types of controls are in this manual.

Page 4: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

4 ❖❖❖❖❖ EnglishL-2166 Introduction

INTRODUCTION

Congratulations on the purchase of your Marine AirSystems’ Vector Series® air conditioner. No matter whichof the following features was the reason for your pur-chase of this air conditioner, we are sure it will meet yourneeds and will give you many years of efficient andtrouble free use. The Vector Series self-contained directexpansion air conditioners are designed for marineapplications incorporating the following features:

• High efficiency rotary (7-16K), scroll (24K), orreciprocating (24K) compressors

• Cupronickel condenser coil

• Enhanced fin designed evaporator coil

• 2" deep drain pan with multiple condensate drainlocations

• Anti-vibration base pad

• Pre-charged and pre-wired systems for easyconnections

• Remote mounted electrical box with fire retardantcover for access and service

• Rotatable blower assembly

• Charge Guard® ensures environmental protectionand system integrity

This manual is intended to provide the informationnecessary to ensure proper installation, operation, andmaintenance of the unit. The figures that are referencedthroughout this manual can be found immediately afterthe warranty section. Improper installation or misunder-stood operating procedures can result in unsatisfactoryperformance and/or premature failure of these units, sobefore proceeding please read this manual completely.

The Vector Series units are covered under the existingDometic Corporation (Dometic) warranty policy containedin this manual. In the interest of product improvement,Dometic’s specifications and design are subject tochange without prior notice.

Clean Air Act Amendments of 1990[Title VI - Section 608(C-1)]“Effective July 1, 1992, it shall be unlawful for anyperson, in the course of maintaining, servicing, repairing,or disposing of an appliance or industrial processrefrigeration, to knowingly vent or otherwise knowinglyrelease or dispose of any Class I* or Class II** sub-stance used as a refrigerant in such appliance (orindustrial process refrigeration) in a manner whichpermits such substance to enter the environment. De

minimis releases associated with good faith attempts torecapture and recycle or safely dispose of any suchsubstances shall not be subject to the prohibition setforth in the proceeding sentence.”

* Class I substances include CFC-12** Class II substances include HCFC-22

Marine Air SystemsMarine Air Systems (MAS) is a product of DometicCorporation. Dometic is a recognized leader in thedesign and manufacture of high-performance comfortcontrol systems, refrigeration products and batterycharging products for demanding environments, includingcommercial and recreational marine craft, vehicles andother applications. We offer an unparalleled scope ofproducts, dealer networks, applications support, engi-neering resources and production capabilities throughoutthe world. Our team has many years of experience in thedesign, manufacture, application and support of ourproducts. Our practical experience and design capabilityallows our application engineers and sales representa-tives to offer optimum solutions for your environmentalcontrol requirements. Product lines also include wellknown Cruisair, Grunert, and Sentry.

How It WorksYour self-contained air conditioner consists of four maincomponents and a refrigerant gas circulating through thesystem. The BLOWER draws warm cabin air across thefins on the EVAPORATOR where the heat from the air istransferred to the refrigerant in the evaporator coil. Asthe refrigerant evaporates from a liquid into a gas itabsorbs the heat from the cabin air. The COMPRESSORthen compresses the refrigerant gas and pumps itthrough the outer tube in the CONDENSER COIL. Theseawater pump circulates cool seawater through theinner tube in the condenser coil, this cools the refriger-ant and condenses it into a liquid. The heat from therefrigerant is exchanged to the seawater and dischargedoverboard. The liquid refrigerant is then passed throughthe EVAPORATOR COIL and the cycle repeats. Remov-ing heat from the cabin air lowers its temperature. Thecooled air is blown through the ducting and out thesupply air grille(s). For reverse cycle heating, the refriger-ant flows in the opposite direction through the reversingvalve. Heat is transferred from the seawater in thecondenser coil to the refrigerant and then to the airblowing through the evaporator into the cabin. Seawatertemperature will directly affect the a/c unit’s efficiency.This a/c unit can effectively cool your boat in watertemperatures up to 90°F (32.2°C)and heat in watertemperatures as low as 40°F (4.4°C). See Figure 1.

Page 5: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

5 ❖❖❖❖❖ EnglishL-2166 Installation

Unpacking and InspectionWhen the equipment is received, all items should becarefully checked against the packing list to ensure allcartons have been received. Move units in the normal“up” orientation as indicated by the arrows on eachcarton. Examine cartons for shipping damage, removingthe units from the cartons if necessary. If the unit isdamaged, the carrier should make the proper notation onthe delivery receipt acknowledging the damage.

CAUTION: When unpacking and installing the 3-knobcontrol (if mechanical option is used), care must betaken not to kink or break the copper cap tube whenuncoiling the sensing bulb. The cap tube is hollow andkinking or sharp bends will inhibit system operation.

Safety ConsiderationsVERY IMPORTANT: Never install your air conditionerin the bilge or engine room areas. Insure that theselected location is sealed from direct access tobilge and/or engine room vapors. Do not terminatecondensate drain line within three (3) feet of anyoutlet of engine or generator exhaust systems, nor ina compartment housing an engine or generator, norin a bilge, unless the drain is connected properly to asealed condensate or shower sump pump.

Installation and servicing of this system can be hazard-ous due to system pressure and electrical components.When working on this equipment, always observeprecautions described in the literature, tags and labelsattached to the unit. Follow all safety codes. Wear safetyglasses and work gloves and place a fire extinguisherclose to the work area. The following is a summary ofthe labels on the unit:

DangerElectrical shock hazard. Disconnect voltage at mainpanel or power source before opening any cover.Failure to comply may result in injury or death.

WarningThis component does not meet federal require-ments for ignition protection. Do not install inspaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel linefittings. Failure to comply may result in injury ordeath.

INSTALLATION

NoticeThis component is charged with hydrochloro-fluorocarbon(HCFC) refrigerant R22. Effective July 1, 1992 it shall beunlawful for any person to knowingly vent or otherwiseknowingly release any class 1 (CFC) or class 2 (HCFC)substance as a refrigerant in a manner which permitssuch substance to enter the atmosphere per the cleanair act of 1990. Public law 101-549 Title IV Section 608-C. Failure to comply may result in severe penalties,including fines and imprisonment.

WarningTo minimize the hazard of electrical shock andpersonal injury, this component must be effectivelygrounded. Refer to the installation guidelines forfurther information.

CautionHigh compressor temperature is normal.Do not touch.

Placement of SystemSelecting a good location for your air conditioner is themost important part of your preparations. Be sure toconsider the size of the area you are cooling, the airdistribution needs, and the size of the unit you havechosen. Keeping in mind that cool air has a tendency tofall, it is highly recommended that you locate the supplyair grille as high as possible in the cabin. See Figures 2and 3.

The Vector Series unit should be installed as low aspossible, BUT NEVER IN THE BILGE OR ENGINEROOM AREAS. INSURE THAT THE SELECTED LOCA-TION IS SEALED FROM DIRECT ACCESS TO BILGEAND/OR ENGINE ROOM VAPORS. Installing the unit aslow as possible (such as under a V-berth, dinette seat orbottom of a locker) and ducting the supply air as high aspossible, creates an ideal airflow condition. This type ofinstallation will prevent short or premature cycling.

The unit should be positioned on a firm, level, horizontalsurface and the condensate drain line should rundownward from the unit to a suitable drain location. Planall connections which must be made including ducting,condensate drain, seawater in and out, electrical powerconnections, location of control, and seawater pumpplacement, to assure easy access for routing andservicing.

Page 6: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

6 ❖❖❖❖❖ EnglishL-2166 Installation

Minimum Tools Required• Screws drivers

• Pliers

• Pipe wrenches

• Wire cutters/crimpers

• Drill and assorted bits

• Jig saw

• Duct tape

• Electrical tape

• Teflon tape

• Beding compound to seal thru hull fittings

• Hardware to secure unit, pump, strainer, grilles &control panel

Condensate DrainsThe condensate drain pan is 2" high with up to four drainlocations. During conditions of high humidity, condensatemay be produced at a rate of approximately 1/2 gallonper hour. With this in mind, it is important to routecondensate drains downward to a sump pump. It is notrecommended to route condensate drains to the bilge.After the condensate drain installation is complete, testthe installation by pouring a quart of water into the panand checking for good flow. See Figure 4.

For installation of the condensate drain:

1. Remove the aft facing watertight plug from the basepan of the a/c unit (see note).

2. Slip the solid washer and the liquid-seal washer ontothe PVC fitting in that order.

3. Connect the fitting through the exposed hole in thebase pan with the locking nut.

4. Securely tighten with two (2) wrenches to provide aproper seal.

5. Attach a 5/8" I.D. reinforced hose to the hose barb andsecure with stainless steel hose clamps.

6. Install the condensate drain hose downhill from theunit and aft to a sump.

7. Two drain fittings may be used and the hoses teedtogether provided there is a minimum 2" drop form thebottom of the base pan to the tee connection.

Note: The reason to use the "aft facing" drain location isso that water will tend to drain out of the pan when thevessel is under way. However, the boat owner shouldinspect the pan when the vessel is at rest. If water iscollecting in the pan along an edge other than "aftfacing", then the drain on that edge should also be

utilized. This will help to prevent water from standing inthe pan. See item 7 for instructions on connecting twodrain lines.

IMPORTANT! Do not terminate condensate drain linewithin three (3) feet of any outlet of engine or generatorexhaust systems, nor in a compartment housing anengine or generator, nor in a bilge, unless the drain isconnected properly to a sealed condensate or showersump pump.

Blower AssemblyWith the Vector Series you can achieve multi-directionalsupply air discharge from a single unit by rotating theblower to the desired location. It is ideal for tight installa-tions as 130° of rotation are available with which toposition the blower. Its advanced design allows theblower to be easily removed for rotating or servicing byremoving the two mounting ring screws and the screwsattaching the blower to the drain pan. Rotate the blowerto allow the most direct flow of air to the supply air grille.Reinstall the mounting screws. Plug any unused screwholes in the blower to prevent air loss.

Mounting BracketsThe a/c unit is supplied with a base pan that also servesas a condensate pan. Mounting clip brackets are pro-vided to secure the base pan onto a flat, horizontalsurface. See Figure 5.

Supply & Return Air Grillesand Transition BoxesInstall the supply air grille as high as possible in alocation that will provide uniform air distribution through-out the cabin, grille louvers should be directed upward.The return air grille should be installed as low and closeto the a/c unit as possible to insure direct uninterruptedairflow to the evaporator. The return air grille should havea minimum four inches (4") of clearance in front of it,free from any furniture or other obstructions. In noinstance should a supply air discharge be directedtowards a return air grille, as this will cause the systemto short cycle. Allow for adequate clearance behind thesupply air grille(s) for the transition box and ductingconnection. The table in Figure 8 shows minimum grillesizes. See the MAINTENANCE section of this manual forreturn air filter cleaning instructions.

DuctingGood airflow is critical for the performance of theentire system. It is highly dependent on the quality ofthe ducting installation. The ducting should be run asstraight, smooth and taut as possible minimizing thenumber of 90° bends (two tight 90° bends can reduceairflow by 25%). The table in Figure 8 shows minimum

Page 7: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

7 ❖❖❖❖❖ EnglishL-2166 Installation

duct diameters and their corresponding supply andreturn air grille minimum area in square inches. If atransition box is used, the total area of supply air ductsgoing out of the box should at least equal the area ofthe supply duct feeding the box. To calculate the squareinch area of a round duct, multiply the radius by itself (r2)and multiply that number by 3.1416(π). See Figure 8.

The following is a summary of proper ducting connections:

1. Pull back the fiberglass insulation exposing the innermylar duct hose.

2. Slide the mylar duct hose around the mount ring untilit bottoms out.

3. Screw 3 or 4 stainless steel sheet metal screwsthrough the duct hose into the transition ring.

Make sure to catch the wire in the duct hose with theheads of the screws. Do not use band clamps, as thehose will slide off.

4. Wrap duct tape around the ducting and ring joint toprevent any air leaks.

5. Pull the insulation back up over the mylar to the ringand tape this joint.

6. Remove excess ducting and use the same connectionmethod at the supply air grille.

All ducting should:

• Be appropriately sized for each application.

• Run as smoothly and taut as possible.

• Have as few bends or loops as possible.

• Be securely fastened to prevent sagging during boatoperation.

• Have all excess ducting lengths trimmed off.

• Not be flattened or kinked.

• Insulated when located in high heat load areas (hullside, mechanical compartments, etc.).

• Be properly protected against potential damagewhen routed through open areas.

Seawater Pump and PlumbingSeveral guidelines should be followed during the installa-tion of the seawater system. Since the circulation pumpis centrifugal and not self-priming, it must be mounted sothat it is always at least one foot below the water lineregardless of which tack the vessel is on. Pump may bemounted horizontally or vertically, however the dischargemust always be above the inlet. Pump head should berotated toward the direction of water flow. Install theseawater speed scoop intake as far below the water

line and as close to the keel as possible in anyapplication, but especially on a sailboat, to keep theintake in the water when the boat heels over so thatair does not get into the system. (See Figure 7 forproper installation.)

The speed scoop intake must face forward and not beshared with any other pump. A seawater strainer ismandatory between the shut off valve (seacock) and thepump to protect the pump from any foreign matter.Failure to install a seawater strainer will void thepump warranty. The seawater system should be in-stalled with an upward incline from the speed scoop &seacock, through the strainer, to the inlet of the pumpand then up to the inlet of the a/c unit’s condenser coil.The discharge from the a/c unit should then run to theseawater outlet thru-hull fitting which should be locatedwhere it can be visually checked for water flow and asclose as practicable to the waterline to reduce noise. Allhose connections shall be secured by means of double/reversed stainless steel hose clamps. Use teflon tape onall threaded connections. The following is a summary ofthe seawater system installation:

1. Install the speed scoop thru-hull inlet as close to thekeel and as far below the water line as possible, facingforward. Bed the scoop with a marine sealant de-signed for underwater use.

2. Install a bronze, full flow seacock on the speed scoopthru-hull inlet.

3. Install a seawater strainer below the level of the pumpwith access to filter.

4. Mount the pump above the strainer and at least onefoot below the waterline.

5. Connect the seacock and strainer with an uphill run ofreinforced marine grade hose.

6. Connect the discharge from the pump uphill to thebottom inlet of the a/c unit’s condenser coil with 5/8"hose. Connect the discharge from the condenser coilto the overboard discharge thru-hull fitting with 5/8"hose.

7. Avoid loops, high spots or the use of 90° elbows withseawater hose (each 90° elbow is equivalent to 2.5' ofhose and a 90° elbow on the pump outlet is equivalentto 20' of hose).

8. Double clamp all hose connections with stainless steelclamps, reversing the clamps.

9. Use teflon tape on all threaded connections.

10. Connect all metallic parts in contact with seawaterto the vessel’s bonding system including thespeed scoop inlet, strainer, pump and the airconditioner. Failure to do so will void warranty.

Page 8: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

8 ❖❖❖❖❖ EnglishL-2166 Installation

Electrical Connections, Groundingand BondingAll a/c units have a terminal strip mounted inside theelectric box. The terminal strip is labeled for properconnections of the electrical supply, ground wires andpump circuits. A wiring diagram is provided in theelectrical box and in this manual. The wiring diagram inthe electrical box supersedes the one in this manual andABYC standards. The correct size circuit breaker shouldbe used to protect the system as specified on the a/cunit’s data plate label. A minimum of 12 AWG boat cableshould be used to supply power to the a/c unit and theseawater pump. All connections shall be made with ringor captive fork terminals. Turn off a/c power supplycircuit breaker before opening electric box. SeeFigures 9, 10 and 11.

Each a/c unit installed requires its own dedicated circuitbreaker. If there is only one a/c unit installed, theseawater pump does not require a circuit breaker; thewiring from the seawater pump is connected to theterminal strip in the electric box. If two or more a/c unitsuse the same seawater pump, the pump wires will beconnected to a pump relay panel (PRP) which in turnhas its own dedicated circuit breaker sized for the pump(20 amp max). Please see the wiring diagram furnishedwith the PRP (NOTE: PRP triac must have its mountingscrew installed in order to dissipate heat). Electricalconnections in the bilge and/or below the waterlineshould use heat shrink type butt splices.

Field wiring must comply with ABYC electrical codes.Power to the unit must be within the operating voltagerange indicated on the data plate. Properly sized fusesor HACR circuit breakers must be installed for branchcircuit protection. See data plate for maximum fuse/circuitbreaker size (mfs) and minimum circuit ampacity (mca).All units must be effectively grounded to minimize thehazard of electrical shock and personal injury.

The following are to be observed:

1. AC (alternating current) grounding (green wire) mustbe provided with the AC power conductors andconnected to the ground terminal (marked “GRND”) atthe AC power input terminal block of the unit(s), perABYC standard E-8, or equivalent.

2. Connections between the vessel’s AC system ground-ing conductor (green wire) and the vessel’s DC (DirectCurrent) negative or bonding system should be madeas part of the vessel’s wiring, per ABYC standard E-9,or equivalent.

3. When servicing or replacing existing equipment thatcontains a chassis-mounted ground stud, the serviceperson or installer must check the vessel’s wiring forthe existence of the connection required in item 2above.

ABYC standards are available from:

American Boat and Yacht Council3069 Solomons Island Rd.Edgewater, MD 21036Telephone: (410) 956-1050

The a/c unit must be connected to the ship’s bondingsystem to prevent corrosion due to stray electricalcurrent or voltage. All pumps, metallic valves andfittings in the seawater circuit that are isolated from thea/c unit by PVC or rubber hoses must be individuallybonded to the vessels bonding system also. This willhelp eliminate any possibility of corrosion due to straycurrent or voltage.

FAILURE TO PROPERLY GROUND AND BOND THESYSTEM WILL VOID WARRANTY!

3 Phase NoticeIt is extremely important to insure that wiring and phasesequencing of a three phase power source is correct.Marine wiring standards call for power source phases L1,L2, and L3 to be color-coded BLACK, WHITE, and RED,respectively. These must be connected to the unit withthe proper sequence, otherwise, it will not operateproperly. If the wiring sequence is incorrect, the unit’scompressor (Scroll type only) and pump (if applicable)will run in the reverse direction at a significantly in-creased noise level.

Manual Control Panel (MCP)InstallationThe MCP should be located within cap tube length of thea/c unit. The 3 knob MCP is configured either vertically(shown) or horizontally. The cut out size is 2.5" by 7.0",see MCP (Figure 6) for orientation. Once the cut out ismade, carefully uncoil the copper cap tube with return airsensor (copper bulb) and route the control wires and captube through the hole and back to the a/c unit usingcaution not to kink the cap tube. Mount the return airsensor into the clips provided with the Vector Series unit.If the return air sensor cannot be mounted on theevaporator coil, mount it behind the return air grille. Thesensor must be mounted in the return air stream. Makeelectrical connections according to the wiring diagramfound in the electric box and/or in this manual. SeeFigure 11.

Page 9: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

9 ❖❖❖❖❖ EnglishL-2166 Installation

Installation Checklist(Review prior to installation)

Note: Refer to the Elite and Passport I/O manualsfor installation and operation of those digitalcontrols.

Seawater Cooling System❑ Speed scoop located as far below the water line and

as close to the keel as possible

❑ Shut off valve (sea cock) and speed scoop properlysealed and tight

❑ Seawater pump is at least one foot below water lineand securely mounted

❑ Strainer mounted below pump with access to filter

❑ Double/reversed stainless steel hose clamps on allhose connections

❑ Teflon tape on all threaded connections

❑ Hose runs uphill from speed scoop and sea cock tostrainer, pump and a/c unit, then downhill (if possible)from a/c unit to overboard discharge

❑ Water flowing freely from overboard discharge whilepump is running

❑ Pump relay panel, if used, must have its own circuitbreaker sized for the pump (20 amp max)

❑ All metal fittings should be bonded

Mounting❑ Not in engine room or bilge areas, must be sealed

away from exhaust or fumes

❑ Proper spacing allowed around unit

❑ Attached to solid level platform with hold down clipsprovided

❑ Condensate drain routed aft and down hill to a sealedsump (not bilge)

❑ Blower rotated toward supply air grille

Electrical❑ The wiring diagram is located in the electrical box. If

that diagram is damaged or if you need a copy, pleasecall Dometic with the unit part number, serial number,and wiring diagram number, all of which are located onthe unit data plate. See also Figures 9, 10 & 11.

❑ All butt connections on pumps wire tightly crimped andheat shrunk

❑ AC power source installed and grounded/bonded inaccordance with ABYC standards

❑ Control wires connected to terminal strip with captivefork or ring terminals

❑ Circuit breakers sized according to specifications onthe data plate label

❑ Digital display cable is connected at both ends

❑ Pump Relay Panel (if used) has a dedicated circuitbreaker sized for the pump but not to exceed 20 ampsmaximum.

Grilles and Ducting❑ Supply air grille mounted as high as possible

❑ Return air grille mounted as low and as close to thea/c unit as possible

❑ Return air grille mounted away from bilge vapors orexhaust fumes

❑ Ducting is pulled taut, straight, smooth and properlyconnected with no excess

Page 10: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

10 ❖❖❖❖❖ EnglishL-2166 Operation

Quick Start Operations Checklist❑ Ensure seawater intake ball valve (sea cock) is open.

❑ Turn on the a/c circuit breaker. If the seawater pumphas its own circuit breaker, turn that on.

❑ Turn the system on.

❑ Set the desired cabin temperature (set point).

❑ Check for a steady solid stream of water from theoverboard discharge.

❑ Verify that there is steady airflow out of the supply airgrille.

❑ If the unit does not appear to be operating properly,refer to troubleshooting guide lines.

Note: Do not turn the unit off and immediately turn itback on. Allow at least 30 seconds for refrigerantpressure equalization.

Mechanical Control Panel(MCP) Operation1. Ensure seawater intake ball valve (sea cock) is open.

2. Turn SYSTEM SWITCH control knob to OFF.

3. Turn on AC circuit breaker. If the seawater pump hasits own circuit breaker, turn that on too. Or, if the pumpis connected to a Pump Relay Panel (PRP), then turnon that circuit breaker also.

4. Turn the SYSTEM SWITCH control knob to START;this energizes the fan and seawater pump. TurnTHERMOSTAT control knob to the coolest position byrotating fully clockwise. If system has reverse cycle,turn knob counter-clockwise for heat.

5. Check for a steady solid stream of seawater from theoverboard discharge.

6. Turn FAN SPEED control knob clockwise to highestsetting for cooling or counter-clockwise for heating.

7. Verify that the fan is running and that there is steadyairflow out of the supply air grille.

8. Turn the SYSTEM SWITCH to RUN; this will start thecompressor. The indicator light on the control willilluminate.

9. To set the thermostat, allow sufficient time for the unitto cool/heat the area to the desired temperature. Whenthe area is sufficiently cooled/heated, turn the thermo-stat knob slowly toward the center position until itclicks once (the indicator light will turn off). Thethermostat is now set to maintain a constant tempera-ture. While heating, if the ambient temperature is lessthan 50°F, set the FAN SPEED control knob to low forfive to ten minutes until the unit begins to heat well,then increase the fan speed for more heat output andto prevent the system cycling on high pressure.

The thermostat on the MCP control panel serves to cyclethe compressor on and off and provide an automaticchangeover from cooling to heating (reverse cycle only)with a 3.5° differential. Rotating the thermostat to the leftafter it has been set for cooling will cause the unit toheat. If you rotate the thermostat to the right, the unit willcool. If the thermostat is left stationary after being set,the unit will cycle from cooling to neutral, or heating toneutral depending on the requirement.

Reverse cycle units have a reversing valve that must beenergized periodically to keep the internal parts movingfreely. To accomplish this, switch the A/C into HEAT for afew seconds once a month.

Note: Do not turn the unit off and immediately turn itback on. Wait at least 30 seconds.

OPERATION

Page 11: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

11 ❖❖❖❖❖ EnglishL-2166 Troubleshooting

TROUBLESHOOTING

General TroubleshootingAlso see specific digital or mechanical controltroubleshooting sections following these generalguidelines.

Fault: Will not start.

Possible Reason/Correction

1. A/C circuit breaker is off.

Turn circuit breaker on at ship’s panel.

2. Control is not turned on.

See mechanical control section of this manual forMCP controls, or see the digital control manual forElite or Passport I/O controls.

3. Wrong wiring at terminal strip.

Check wiring diagram and correct if necessary.

4. Push-on butt connectors becamedisconnected during installation.

Disconnect power supply and open electric box,check wiring diagram, correct if necessary

5. Input line voltage is insufficient.

Check power source (shore/generator) for propervoltage. Check wiring and terminals for proper sizesand connections. Verify with a volt-meter that thepower at the unit is the same as the power source.

Fault: Fan is not running.

Check specific control troubleshooting section

Fault: No cooling or heating.

Possible Reason/Correction

1. Temperature set point is satisfied.

Lower or raise set point.

2. Obstructed seawater flow.

Clean seawater strainer. Check for obstructions atspeed scoop thru-hull inlet. Check for a good steadyflow from the overboard discharge.

3. Seawater pump may be air-locked.

Remove hose from pump discharge to purge air fromline.

4. Loss refrigerant gas.

Check a/c unit for refrigerant oil leakage, call servicetechnician.

5. Seawater temperature too high for cooling ortoo low for heating.

Seawater temperature will directly affect a/c unit'sefficiency. This a/c unit can effectively cool your boatin water temperature up to 90°F (32.2°C) and heat (ifreverse cycle option is installed) in water as low as40°F (4.4°C).

6. Fan coil is iced (in cooling).

Check your specific control troubleshooting section.

7. Fan is not running.

Check your specific control troubleshooting section.

8. Seawater plumbing is air-locked.

Ensure that seawater plumbing is installed per theguidelines in this manual.

9. Digital control is programmed for Cool or Heatonly, or mechanical control thermostat isrotated to far towards either Cooler or Warmersetting.

See digital control manual for reprogramming or seemechanical control operation section in this manual.

10. High pressure switch open (in cooling) due toimproper seawater flow.

Strainer or intake may be plugged, sea cock may beclosed, check seawater hose for kinks or collapses.Verify pump operation. Check pump circuit breaker ifapplicable

11. High pressure switch open (in heating) due toimproper airflow.

Remove any obstructions in return air stream. Cleanreturn air filter and grille. Check for crushed orrestricted ducting, ducting must be as straight,smooth and taut as possible.

12. High-pressure switch is open in heating mode.

System may cycle on high-pressure if seawatertemperature is above 55°F (12.8°C).

13. Compressor's thermal overload is open due toeither of the above reasons.

Compressor needs to cool down. Turn system off fora while (it may take up to three hours to resetthermal overload).

Fault: No heating.

Possible Reason/Correction

1. Unit is “cool only”, or if reverse cycle, reversingvalve may be stuck.

Tap reversing valve lightly with rubber mallet whileunit is in heat mode. Call for service if that does notcorrect the problem.

Page 12: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

12 ❖❖❖❖❖ EnglishL-2166 Troubleshooting

Fault: Low airflow.

Possible Reason/Correction

1. Airflow is blocked.

Remove any obstructions in return air stream. Cleanreturn air filter and grille. Check for crushed orrestricted ducting, ducting must be as straight,smooth and taut as possible.

2. Fan Coil is iced.

See below.

Fault: Fan coil is iced.

Possible Reason/Correction

1. Thermostat set point is too low.

Raise set point.

2. Improper airflow.

Remove any obstructions in return air stream. Cleanreturn air filter and grille. Check for crushed orrestricted ducting, must be as straight, smooth andtaut as possible. See the Digital Controls Trouble-shooting section below for reprogramming options.

3. Supply air is short-cycling.

Redirect supply air so that is not blowing into thereturn air stream. Seal any air leaks on duct.

4. Humidity level too high.

Close hatches and doors.

5. When all else fails.

Switch a/c to heat until ice melts or use hair dryer tomelt.

Fault: Water coil is iced in the heatingmode.

1. Seawater temperature is below 40°F (4.4°C).

Shut down system to prevent damage to condenser.Allow coil to defrost.

Fault: System runs continuously.

Possible Reason/Correction

1. Set point temperature is improperly set: too lowfor cooling or too high for heating.

Raise or lower set point.

2. Porthole or hatches open.

Close all port holes and hatches.

3. Seawater temperature too high for cooling or tolow for heating.

Seawater temperature will directly affect the a/cunit's efficiency. This a/c unit can effectively coolyour boat in water temperatures up to 90°F (32.2°C)and heat (if reverse cycle option is installed) in wateras low as 40°F (4.4°C).

4. Improper air sensor location.

Check your specific control troubleshooting section.

Digital Controls Troubleshooting

Fault: Digital display panel is not lit.

Possible Reason/Correction

1. 8-pin display cable plugs are not makingcontact (unplugged, dirty, bent, or brokenpins).

With POWER OFF at the circuit breaker, removeconnector and inspect. If damaged, replace connec-tor or entire display cable.

Fault: Fan is not running or runscontinuously.

Possible Reason/Correction

1. Digital control is programmed for either fancycling with compressor or continuous fanoperation.

Elite Control: Press and hold the fan button for 5 sec-onds to change to "con" so fan will stay on continu-ously or to "cyc" so the fan cycles with the compressor.

Passport I/O Control: Reprogram parameter P-14.

Note: After the compressor cycles off, the fan willcontinue to run for 2 minutes in cool mode and 4minutes in heat mode regardless of parametersetting.

Fault: Fan is not running but thecompressor is.

Possible Reason/Correction

1. Failed triac on Passport I/O circuit board.

Send for repair or call local service technician (seeback of book for a listing).

Page 13: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

13 ❖❖❖❖❖ EnglishL-2166 Troubleshooting

Fault: Fan runs continuously although itis set to cycle with compressor.

Possible Reason/Correction

1. Failed triac on Passport I/O circuit board.

Send for repair or call local service technician (seeback of book for a listing).

Fault: No cooling or heating.

Possible Reason/Correction

1. Digital control programmed for heat or coolonly.

Elite Control: Press and release the Mode button(bottom right corner of display) until the desiredmode LED is lit.

Passport I/O Control: Reprogram parameter P-1.

2. "HPF" or "LPF" is displayed.

See below.

Fault: No heat.

Possible Reason/Correction

1. Digital Control may be set to Electric Heat, notReverse Cycle.

Elite Control: Reprogram parameter P-13

Passport I/O Control: Reprogram parameter P-15

Fault: Unit switches to heat while in coolmode.

Possible Reason/Correction

1. De-icing feature enabled due to coil icing up.

Elite Control: Reprogram parameter P-7

Passport I/O Control: Reprogram parameter P-8

Fault: Fan coil is iced.

Possible Reason/Correction

1. Improper airflow.

See the General Troubleshooting section above first,before reprogramming digital control.

Reprogram parameter P-7 for Elite or P-8 for PassportI/O. If de-icing cycle does not melt ice, switch a/c toheat until ice melts or use hair dryer to melt ice.

If problem persists, reprogram Low Fan Speed Limitfor maximum value. Set P-2 to 55 for Elite or set P-3to 64 for Passport I/O.

Fault: System runs continuously.

Possible Reason/Correction

1. Improper air sensor location.

Verify display head location with criteria found in thecontrol manual. Install alternate air sensor if neces-sary.

Fault: “HPF” is displayed.

Possible Reason/Correction

1. High-pressure switch is open (in cooling) dueto improper seawater flow.

Strainer or intake may be plugged, seacock may beclosed, check seawater hose for kinks or collapses.Verify pump operation; check pump circuit breaker ifapplicable.

2. High-pressure switch open (in heating) due toimproper airflow.

Remove obstructions in return air stream. Clean airfilter and grille. Check for crushed or restrictedducting, ducting must be as straight, smooth andtaut as possible.

If problem persists, reprogram Low Fan Speed Limitfor maximum value. Set P-2 to 55 for Elite or set P-3to 64 for Passport I/O. And, set the Reverse FanSpeeds During Heating Mode parameter to "rEF"(P-12 for Elite or P-13 for Passport I/O), or manuallyset fan speed to high.

Fault: “LPF” is displayed.

Possible Reason/Correction

1. Low-pressure switch is open due to low seawa-ter and/or low return air temperatures.

Try restarting the a/c unit, the optional low pressureswitch has a ten minute shutdown time delay thatmay be in affect.

2. Low pressure switch is open due to loss ofrefrigerant.

Check a/c unit for refrigerant oil leakage, call servicetechnician.

Fault: “ASF” is displayed.

Possible Reason/Correction

1. Indicates failed face plate air sensor, alternateair sensor or display cable.

Unplug alternate air sensor if installed or plug inalternate air sensor if not installed. Try anotherdisplay cable.

Page 14: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

14 ❖❖❖❖❖ EnglishL-2166 Troubleshooting

2. Damaged jack/socket in display head or oncircuit board.

Visually check to see that pins inside socket are notbent or corroded. Repair or replace display or circuitboard if needed.

Fault: “PLF” is displayed (Elite DigitalControl only).

Possible Reason/Correction

1. Indicates that seawater flow through the con-denser coil is insufficient.

Check for adequate seawater flow. Verify pumpoperation. Inspect the condenser coil, it may needcleaning (see maintenance section). Sensor may befaulty, replaced if necessary. Call for service tech.

MCP Mechanical Control PanelTroubleshooting

Fault: Fan is not running.

Possible Reason/Correction

1. MCP system switch is not set properly.

Set MCP system switch to “START” for fan only or“RUN” for cooling and heating (if reverse cycle).

2. MCP fuse blown.

Replace 10 amp fuse behind MCP panel

3. Wire became disconnected or loosened duringinstallation.

Reconnect or tighten, verify with wring diagram inthis manual.

Fault: System runs continuously.

Possible Reason/Correction

1. Improper MCP air sensor location.

Verify return air sensing bulb location with criteriafound in this manual.

Page 15: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

15 ❖❖❖❖❖ EnglishL-2166 Maintenance

MAINTENANCE

Reversing ValvesReverse cycle units have a reversing valve; the valvemust be energized periodically to keep the internal partsmoving freely. To do this, switch the a/c unit into heat fora few seconds once a month.

Seawater StrainerInsure that your pump receives adequate seawater flowby regularly cleaning the strainer basket. Periodicallycheck the overboard discharge for a steady stream ofwater. Check seawater intake speed scoop for obstruc-tions. Make sure hoses are not looped, kinked orcrushed.

Condenser Coil Cleaning1. With the system turned off at the circuit breaker on the

ship’s panel, disconnect the inlet and outlet connec-tions of the condenser coil.

2. Use chemical resistant hoses (MAS white PVC 5/8”I.D., etc.) to connect the inlet of the condenser coil tothe outlet of a chemical resistant, submersible pump(MAS P-500 pump, etc.) and let the hose connected tothe coil outlet flow freely into the container mentionedbelow.

3. Place a strainer or piece of screen over the inlet of thepump and submerse the pump into a container filledwith a 5% solution of muriatic or hydrochloric acid andfresh water or use a premixed over-the-countersolution. Use a large container as possible to hold thesolution (5-25 gallons).

CAUTION: Avoid spilling or splashing the solution.Follow all warnings and recommendations given by themanufacturer of any acids or premixed solutions.

4. Power the pump and circulate the solution through thecondenser coil for 15-45 minutes depending upon thesize of the coils and the extent of the contamination.Visual inspection of the solution in the containershould indicate when the contamination removal hasstopped.

5. Circulate fresh water through the coil to flush anyresidual acid from the system.

6. Restart the system and check operational parametersto ensure thorough cleaning has taken place. Addi-tional cleaning may be necessary with extremecontamination.

WARNING: For the purpose of protecting the environ-ment, dispose of any contaminated acid solutions inaccordance with federal, state and/or local regulations.

Return Air FiltersCheck the return air filter about once a month and cleanas necessary. To clean the filter, remove it from the unit,rinse with water, air dry and reinstall.

WinterizationThere are several methods of winterization, some ofwhich work better than others. The four various methodsemployed using a 50/50 nonpolluting biodegradableantifreeze/water solution are:

1. Pumping of antifreeze solution into the overboard thru-hull fitting, and discharging through the intake thru-hullfitting.

2. Use of the seawater pump to pump antifreeze solutionthrough the system and discharging through theoverboard thru-hull fitting. Close sea cock, removehose from strainer discharge, raise hose above pump(so pump does not lose its prime) and pour in anti-freeze solution. Pump solution through system. Thestrainer and hose to sea cock will also need to bedrained of water.

3. Use of pressurized air injected at the overboarddischarge fitting and the water being dischargedthrough the seawater intake fitting.

4. Use of pressurized air to force water from the intakethrough the overboard discharge.

Any method that causes the antifreeze solution to flowdownward is the method of choice. By this means, theantifreeze solution will displace any water trapped andeliminate the possibility of freezing in hidden areas. Inaddition, since the seawater pump utilizes a magneticallydriven impeller, the impeller should be removed from thewet end assembly, wiped with an alcohol solution, andstored in a warm, dry area until commissioning takesplace.

Note: Collect all discharged liquids and re-cycle or dispose of in a proper manner.

Page 16: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

16 ❖❖❖❖❖ EnglishL-2166

The following warranty is extended to cover marine airconditioners manufactured or supplied by DometicCorporation, and is subject to qualifications indicated.Dometic warrants for the periods set forth below thatproducts manufactured or supplied by it will be free fromdefects in workmanship and material, provided suchproducts are installed, operated, and maintained inaccordance with Dometic’s written instruction.

ALL IMPLIED WARRANTIES INCLUDING MERCHANT-ABILITY AND FITNESS FOR A PARTICULAR PURPOSE,ARE LIMITED TO THE TERMS AND PERIODS OFWARRANTY SET FORTH BELOW AND, TO THE EX-TENT PERMITTED BY LAW, ANY AND ALL IMPLIEDWARRANTIES ARE EXCLUDED.

Warranty with the Elite or Passport I/O digital controls(Coverage applies to units manufactured on or after 03/01/03 and applies only to units equipped with Elite or PassportI/O digital controls at the Dometic factory.): Componentscomprising of the Passport I/O circuit boards, Elite orPassport I/O digital displays, and associated cables arewarranted for a period of three (3) years from the date ofinstallation, but not to exceed four (4) years from the date ofmanufacture at the Dometic factory. All other componentscomprising a complete system (excluding pumps and pumprelay panels) on a new installation are warranted for aperiod of two (2) years from the date of installation, but notto exceed three (3) years from the date of manufacture atthe Dometic factory. Pumps and pump relay panels arewarranted for a period of one (1) year from the date ofinstallation, but not to exceed two (2) years from the date ofpurchase. OEM installed equipment warranties begin withthe purchase of the vessel, not from the date of installation.

Warranty with MCP (Mechanical Control Panel) control:Components comprising a complete system on a newinstallation are warranted for a period of one (1) year fromthe date of installation, but not to exceed two (2) years fromthe date of manufacture at the Dometic factory. OEMinstalled equipment warranties begin with the purchase ofthe vessel, not from the date of installation.

In addition, Dometic will pay labor costs and travel asoutlined in its Schedule of Limited Warranty Allow-

MANUFACTURERS LIMITED WARRANTY AGREEMENT

ances for removal and reinstallation of such componentsfor a period of one (1) year from the date of installation,but not to exceed two (2) years from the date of manu-facture at the Dometic factory. OEM installed equipmentwarranties begin with the purchase of the vessel, notfrom the date of installation. Warranty will be paid inaccordance with our established schedule of allowances.Compensation for warranty repairs is only made toDometic authorized service companies.

Dometic will repair, or replace at its option, componentsfound to be defective due to faulty materials or workman-ship, when such components, examined by an authorizedservice dealer or a factory service representative, arefound to have a defect for which the company is respon-sible. Refer to Manufacturer’s Limited Warranty Policyfor complete coverage and exclusions. Replacementcomponents are warranted for the duration of the remain-ing warranty period in effect on the original component.In the event that a unit has to be returned to the factory,it must be properly packaged to prevent shipping dam-ages. If packaging is not available, Dometic will provide itat no charge. The warranty may be voided on any pieceof equipment or component that is damaged due toimproper packaging.

This limited warranty is extended in lieu of all otherwarranties, agreements or obligations, expressed orimplied, concerning Dometic’s components. This warrantyis extended only to the original purchaser and is nottransferable. This warranty shall be governed by the lawsof the State of Florida and gives the original first enduser definite legal rights.

This warranty does not cover damages incidental and/orconsequential to the failure of Dometic’s equipmentincluding but not limited to; normal wear, accident,misuse, abuse, negligence, improper installation, lack ofreasonable and necessary maintenance, alteration, civildisturbance or acts of God.

No person or dealer is authorized to extend any otherwarranties or to assume any other liabilities on Dometic’sbehalf, unless made or assumed in writing by an officerof Dometic.

Page 17: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

17 ❖❖❖❖❖ EnglishL-2166

DESCRIPTION OF FIGURES

Fig 1. Overview of Vector Series

Fig 2. Placement of Vector Series

Fig 3. Spacing Allowances

Fig 4. Installation of Condensate Drain

Fig 5. Mounting Brackets

Fig 6. 3-Knob Control

Fig 7. Seawater Pump and Plumbing Configuration

Fig 8. Ducting and Grill Sizing

Fig 9. Wiring Diagrams for Digital Controls

Fig 10. Wiring Diagrams for Digital Controls

Fig 11. Wiring Diagrams for Mechanical Controls

Page 18: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

18L-2166

Fig 1. Overview of Vector Series

Fig 2. Placement of Vector Series

Page 19: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

19L-2166

Fig 3. Spacing Allowances

Page 20: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

20L-2166

Fig 5. Mounting brackets

Fig 4. Installation of condensate drain Fig 6. 3-Knob Control

Page 21: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

21L-2166

Fig 7. Seawater pump and plumbing configuration

Fig 8. Ducting and Grill Sizing

ledoM K5 K7 K01 K21 K61 K42

.aiDtcuD .aid"4 .aid"5 aid"6 aid"6 aid"7 aid"8

aerAtcuD niqs6.21 niqs6.91 niqs3.82 niqs3.82 niqs5.83 niqs3.05

ellirGA/R niqs46 niqs88 niqs031 niqs041 niqs861 niqs062

ellirGA/S niqs23 niqs44 niqs56 niqs07 niqs48 niqs031

Page 22: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

22L-2166

Fig 9. Wiring Diagrams for Digital Controls

Page 23: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

23L-2166

Fig 10. Wiring Diagrams for Digital Controls

Page 24: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

24L-2166

Fig 11. Wiring Diagrams for Mechanical Controls

Page 25: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

DISTRIBUTOR LISTING

AlabamaArkansasColoradoKansasLouisianaMississippiMissouriNevadaNew MexicoOklahomaTexasUtah

GeorgiaNorth FloridaNorth CarolinaSouth CarolinaTennessee

IllinoisIndianaIowaKentuckyMichiganMinnesotaN. DakotaOhioS. DakotaWisconsin

IdahoMontanaOregonWashingtonWyoming

AER Marine Supply2301 Nasa Road OneSeabrook, TX 77586Contact: Richard S. MillerTel: (800) 767-7606

(281) 474-3276Fax: (281) 474-2714E-mail: [email protected]

Beard Marine Savannah3101 River DriveSavannah, GA 31404Contact: Lynn StorkTel: (800) 286-2674

(912) 356-5222Fax: (912) 692-1006E-mail: [email protected]: www.beardmarine.com

Midwest Marine Supply24300 Jefferson AvenueSt. Clair Shores, MI 48080Contact: Dan GruningerTel: (586) 778-8950Fax: (586) 778-6108

American Marine Contractors8313 46th Place WestMukilteo, WA 98275Contact: Gene LawingTel: (206) 660-2240Fax: (425) 740-0246E-mail: [email protected]

DelawareMarylandPennsylvaniaVirginia

New YorkNew Jersey

ConnecticutMaineMassachusettsNew HamphsireRhode IslandVermont

ArizonaCaliforniaHawaiiMexico

Ocean Options - Mid Atlantic2830 Solomons Island RoadEdgewater, MD 21037Contact: Mike BowdenTel: (800) 400-8043

(410) 266-8033Fax: (410) 841-2461E-mail: [email protected]: www.oceanoptions.com

Marine Specialists2231 5th Avenue, Unit 17Ronkonkoma, NY 11779Contact: Mike BudneyTel: (631) 580-0545Fax: (631) 580-0551E-mail: [email protected]: www.marinespecialists.com

Ocean Options95 Riverside DriveTiverton, RI 02878Contact: Mike BowdenTel: (401) 624-7334Fax: (401) 624-8050E-mail: [email protected]: www.oceanoptions.com

Southern California MarineEnterprises1214 Rosecrans StreetSan Diego, CA 92106Tel: (888) 657-1606Fax: (619) 226-0496E-mail: [email protected]: www.southerncalmarine.com

INTERNATIONAL

Please contact us for international dealers & distributors.

Page 26: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the
Page 27: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the
Page 28: vector series - Tropical Marine Air Conditioning€™ Vector Series® air conditioner. ... The Vector Series units are covered under the existing ... taken not to kink or break the

L-2166

Dometic CorporationEnvironmental Systems2000 North Andrews Avenue Ext. • Pompano Beach • FL 33069-1497 USAPhone: 954-973-2477 • Fax: 954-979-4414Service Hot Line: 954-633-3150 • Service Fax: 954-973-8795

Fleets Industrial Estate • 26 Willis Way • Poole, Dorset BH15 3SU, EnglandPhone: +44(0)870 3306101 • Facsimile: +44(0)870 330610

Web: www.marineair.com • Email: [email protected]