variable speed pump controller and integrated …€¦ · air pollution: the air may contain dry...

78
VARIABLE SPEED PUMPING SYSTEMS INSTRUCTION MANUAL VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED AJUSTABLE FREQUENCY DRIVE INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE. HV 2.1-3.11 DESCRIPTION: Microprocessor based pump controller and adjustable speed drive for variable volume pumping systems. The controller consists of the following components: microprocessor, operator interface with alphanumeric display, and membrane keypad. OPERATIONAL LIMITS: See the control panel nameplate for operating voltage, current draw, as well as information on the equipment to be connected to the control panel. SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THE INSTRUCTION MAY RESULT IN A SAFETY HAZARD! WARNING LABEL #S11550 INSTALLED IN THIS LOCATION. IF MISSING IT MUST BE REPLACED. INSTRUCTION MANUAL 210 980-2 HV 120-1-ENBG 26.03.2003 HV3.15-3.22

Upload: others

Post on 16-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

VARIABLE SPEED PUMPING SYSTEMSINSTRUCTION MANUAL

VARIABLE SPEED PUMP CONTROLLER ANDINTEGRATED AJUSTABLE FREQUENCY DRIVE

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

HV 2.1-3.11

DESCRIPTION: Microprocessor based pumpcontroller and adjustable speed drive for variablevolume pumping systems. The controller consistsof the following components: microprocessor,operator interface with alphanumeric display, andmembrane keypad.

OPERATIONAL LIMITS: See the control panelnameplate for operating voltage, current draw, aswell as information on the equipment to beconnected to the control panel.

SAFETY INSTRUCTION

This safety alert symbol will be used in thismanual to draw attention to safety relatedinstructions. When used, the safety alertsymbol means ATTENTION!BECOME ALERT! YOUR SAFETY IS INVOLVED!FAILURE TO FOLLOW THE INSTRUCTION MAYRESULT IN A SAFETY HAZARD!

WARNING LABEL #S11550INSTALLED IN THIS LOCATION.IF MISSING IT MUST BEREPLACED.

INSTRUCTION MANUAL

210 980-2HV 120-1-ENBG26.03.2003

HV3.15-3.22

Page 2: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

2

Index

1 Important safety instructions ........................................................................5

2 System Design................................................................................................7

3 Pressure tank ................................................................................................8

4 Technical Data - Frequency Inverter And General Data .................................9

5 Dimensions and Weights .............................................................................11

6 Mounting the Technovar..............................................................................12

6.1Mounting the Technovar on the pump.................................................126.1.1 Components included............................................................................................ 126.1.2 Mounting .............................................................................................................. 136.1.3 Mounting the thermistor ....................................................................................... 23

6.2 Electric installation and wiring.............................................................246.2.1 Means of protection .............................................................................................. 246.2.2 Wiring the Technovar to the motor ....................................................................... 24

6.3 Main Voltage Terminals .......................................................................25

6.4 Control Terminals .................................................................................266.4.1 Control terminals ................................................................................................... 276.4.2 Dip-Switch on the controller board........................................................................ 286.4.3 Main parts from the control card........................................................................... 28

6.5 Front plate............................................................................................29

7 Language Selection......................................................................................30

8 Typical applications .....................................................................................31

8.1 Control .................................................................................................31

8.2 The Main Menu Setting........................................................................31

8.3 Single Pump – Pump Protection...........................................................348.3.1 To set run out protection....................................................................................... 34

8.4 Single Pump – System Curve Compensation........................................368.4.1 Entering the compensation values ......................................................................... 37

8.5 Multiple Pump - Constant Pressure and System Curve Compensation 38

9 Parameters of the main menu .....................................................................43

10 Settings at Secondary Menu .......................................................................46

10.1 JOG-MODE..........................................................................................46

10.2 Window - %........................................................................................47

10.3 Ramp Hysteresis .................................................................................47

10.4 Ramp 1: Fast running up time:...........................................................47

10.5 Ramp 2: Fast running down time:......................................................47

10.6 Ramp 3: Slow running up time: .........................................................48

10.7 Ramp 4: Slow running down time: ....................................................48

Page 3: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

3

Ramp – Window .........................................................................................48

10.8 Maximum Frequency..........................................................................48

10.9 Minimum Frequency ..........................................................................49

10.10 Operation at the minimum frequency .............................................49

10.11 Delay time for shut off at minimum frequency ...............................49

10.12 Boost ................................................................................................49

10.13 Sensor – Adjust.................................................................................50

10.14 Sensor - Curve ..................................................................................50

10.15 Setting of the measuring range .......................................................50

10.16 Operation Mode ...............................................................................50

10.17 Control Response .............................................................................51

10.18 Start Value........................................................................................52

10.19 2nd Required Value............................................................................52

10.20 Configuration of 1st relay .................................................................53

10.21 Submenu Offset ...............................................................................5310.21.1 Source of the Offset input ................................................................................. 5310.21.2 1st Offset level .................................................................................................... 5310.21.3 2nd Offset level ................................................................................................... 5410.21.4 INTENSITY 1 ....................................................................................................... 5410.21.5 INTENSITY 2 ....................................................................................................... 54

10.22 Submenu Sequence control .............................................................5410.22.1 Lift Value ........................................................................................................... 5510.22.2 Fall Value ........................................................................................................... 5510.22.3 Release frequency of the following controller.................................................... 5610.22.4 Switch Interval ................................................................................................... 5610.22.5 Source of required value.................................................................................... 5710.22.6 Synchronous Control ......................................................................................... 5710.22.7 Pump status indication ...................................................................................... 5810.22.8 Error Signals for Data Bus Interruptions............................................................. 58

10.23 Submenu - RS 485 Interface .............................................................5910.23.1 Pump Address.................................................................................................... 5910.23.2 ADC Reference................................................................................................... 59

10.24 Compensation Frequency.................................................................59

10.25 Lift-Intensity .....................................................................................60

10.26 Analog - Output ...............................................................................60

10.27 Unit...................................................................................................61

10.28 Automatic test run ...........................................................................61

10.29 Submenu for manual test run ..........................................................6110.29.1 Activate manual test run.................................................................................... 6110.29.2 Test Frequency................................................................................................... 6110.29.3 Boost ................................................................................................................. 61

10.30 Submenu - Error ...............................................................................6210.30.1 Conveyor Limit................................................................................................... 6210.30.2 Delay Time ......................................................................................................... 62

Page 4: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

4

10.30.3 Automatic Error reset......................................................................................... 6210.30.4 Erase Error memory ........................................................................................... 63

10.31 Operating Hours...............................................................................63

10.32 Display - Contrast .............................................................................63

10.33 Set Password ....................................................................................63

10.34 Operating Lock .................................................................................63

10.35 Internal Heater .................................................................................63

10.36 Setting Default Values......................................................................6410.36.1 Default Values Europe ....................................................................................... 6410.36.2 Default Values USA............................................................................................ 64

10.37 Saving...............................................................................................64

11 Error Signals................................................................................................65

11.1 Low Water ..........................................................................................65

11.2 Conveyor Control ...............................................................................65

11.3 Overheating – Motor ..........................................................................65

11.4 Overheating – Inverter .......................................................................65

11.5 Over voltage.......................................................................................65

11.6 Under voltage.....................................................................................66

11.7 Limit ...................................................................................................66

11.8 Short Circuit .......................................................................................66

11.9 Overload.............................................................................................66

11.10 Pressure Sensor Error I < 4 mA ......................................................66

11.11 Additional Error signals:...................................................................67

12 RS 485 - Interface........................................................................................67

13 Auxiliary Texts.............................................................................................68

14 Maintenance ...............................................................................................73

14.1 Notes ..................................................................................................73

Follow the Pump Operating and Maintenance InstructionsWe reserve the right to alter specifications

Page 5: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

5

1 Important safety instructions

In addition to the instructions contained in these operating instructions please payattention to universal safety and accident prevention regulations.

The TECHNOVAR drive head must be disconnected from the power supply before any workcan be carried out in the electrical or mechanical part of the system.Installation, maintenance and repair work may only be carried out by trained, skilled andqualified personnel.Unauthorized modifications or changes to the system make all guarantees null and void.When in operation, the motor can be stopped by remote control, whereby the drive head andthe motor remain under voltage. For safety reasons, the unit has to be disconnected from thepower supply when carrying out work on the machinery as locking out the equipment byswitching off the release mechanism or set value cannot prevent accidental starting of themotor.

When the drive head is connected to power supply, the components of thepower unit as well as certain components of the master control unit are alsoconnected to the power supply.

Touching these components seriously endangers life !

Before removing the frequency inverter cover the system must bedisconnected from the power supply. After switching off the power supplywait at least 5 minutes before starting work on or in the TECHNOVAR drivehead (the capacitors in the intermediate circuit have to be discharged by theinstalled discharge resistors first).

Voltages of up to 800 volts are possible (if there are faults it can be higher)

All work, carried out when the frequency inverter is open, may only beperformed by qualified authorized staff.

Furthermore, care must be taken not to short circuit the neighbouringcomponents when connecting the external control wires and that opencable ends which are not in use are isolated.

Page 6: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

6

The TECHNOVAR drive head contains electronic safety devices whichswitch off the control element in the event of faults, whereby themotor has zero current but remains energized and comes to a halt. Themotor can also be halted by mechanical blocking. If it is switched offelectronically the motor is disconnected from the mains voltagethrough the electronics of the frequency converter but is not potential-free in the circuit.In addition voltage fluctuations, especially power failures can cause thesystem to switch off itself.

The system may only be put into operation when it has been earthened. In addition,equipotential bonding of all pipes must be ensured.

Warns that failure to observe the precautions may cause electrical shock.Failure to follow these instructions could result in serious personal injury or death.

Warns that failure to follow these instructions could result in serious personalinjury or death as well as property damage.

Repair of faults can cause the motor to start up again!

Page 7: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

7

2 System Design

The following diagrams show typical single pump and multi-pump systems using theTechnovar control unit. Connection can be made directly to a water supply or water can bedrawn from a break tank or well. In the case of break tanks and wells, level switches, shouldbe used to shut down the pumps when water is low. In the direct connection, a pressureswitch on the suction side should be used.

Single Pump Layout

Multiple Pump Layout

(1) pump with drive head

(2) diaphragm tank

(3) distribution panel

(4) gate valve

(5) non return valve

(8) incoming pressure control

(9) pressure gauge

(14) pressure transmitter

3

Page 8: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

8

3 Pressure tank

A diaphragm pressure tank is used on the discharge side of the pump or pumps to maintainpressure in the line when there is no demand. This will keep the pumps from continuing torun. With the Technovar control unit, it is not necessary to have a large tank for supplypurposes.In selecting a tank, make sure it is permit and suitable for systems pressure. The tank shouldhave a capacity of more than 10% of the maximum system flow rate g/min of one pump (alsoin a multiple pump system!).

Pre charge the tank to the following:

Required pressure

Note: De-pressurize the tank prior to charging to ensure accuracy of thepre-charged pressure.

Pre charge pressure (psi)

Page 9: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

9

4 Technical Data - Frequency Inverter And General Data

TECHNOVAR Technovaroutput tothe Motor

Supply Voltage

ModelNo.

nominalHorsepower

Max. Current

HV 2.1 2 7 A *1x220...240VAC ±15%

HV 2.2 3 10 A *1x220...240VAC ±15%

HV 3.2 3 5,7 A 3x380...460VAC ±15%

HV 3.3 4 7,3 A 3x380...460VAC ±15%

HV 3.4 5 9 A 3x380...460VAC ±15%

HV 3.5 7.5 13,5 A 3x380...460VAC ±15%

HV 3.7 10 17 A 3x380...460VAC ±15%

HV 3.11 15 23 A 3x380...460VAC ±15%

HV 3.15 20 30 A 3x380...460VAC ±15%

HV 3.18 25 37 A 3x380...460VAC ±15%

HV 3.22 30 43 A 3x380...460VAC ±15%

Note: Consult local authorities in your jurisdiction for fuse sizing.* Output voltage is 3 phase and requires a motor suitable for 220-240V/3/60 input power

Mains frequency: 48....62 Hz

Max. frequency: See chapter 10.8Min. frequency: 0 – f-max see chapter 10.9Electrical efficiency: > 95%

PleaseNote!

If the motor and control unit are assembled separately keep themotor cable as short as possible in order to avoid electromagneticemissions and capacitive currents. The length may not exceed 66 m.and a shielded cable has to be used.

Protection against: Short circuit, under- and over voltage, overheating of the electronics(overload) and additional external protective functions via PTC (motor temperature) andlow water switch.A mains filter is fitted to ensure interference immunity.

Page 10: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

10

The HV-series frequency converter complies with the general EMV provisions and has beentested according to the following standards:

� Radio Interference Suppression EN 50082 Part 2EN 55011

� High Frequency Field Interference ENV 50204� Electrostatic Discharge EN 61000-4

Ambient temperature: +5° C ... +40°CStorage temperature: -25° C ... +55° C (+70°C during max. 24 hours.)Humidity: RH max. 50% at 40°C, Unlimited

RH max. 90% at 20°C, max. 30 days per year75% average per year (Class F, DIN 40 040)Condensation is not permitted !

Air pollution: The air may contain dry dust as found in workshops where there isno excessive quantity of dust due to machines. Excessive amountsof dust, acids, corrosive gases, salts etc. are not permitted

Altitude:: max. 3280 ft. above sea level At higher altitudes the max. availablepower has to be reduced. Please ask the manufacturer for furtherdetails.

Class of protection : IP 54 3.15-3.22Nema 4 bis 3.11

Page 11: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

11

5 Dimensions and Weights

HV2.1/2.2/3.2/3.3/3.4 HV 3.5/3.7/3.11

all measurements in inches

Motorfancover max. 7.9 Ø Type: Weight: Type: Weight:

[lbs] [lbs]HV 2.1 13 HV 3.4 13HV 2.2 13 HV 3.5 22HV 3.2 13 HV 3.7 22HV 3.3 13 HV 3.11 22

Type Weight[lbs]

HV3.15 64HV3.18 64HV3.22 64

Motorfancover max. 15.2 Ø

HV 3.15/ 3.18/ 3.22

Page 12: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

12

6 Mounting the Technovar

6.1 Mounting the Technovar on the pump

6.1.1 Components included

Thermal resistorScrew M5x90

Mounting clampcable gland

Page 13: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

13

6.1.2 Mounting

HV2.1-3.11

Fix the display with the 4 Screws.

Mounting:

� Remove the 3 screws from the Technovar cover.� Place the Technovar fan cover on the motor .� Hang the 4 clamps by the Motor fan cover and mounted with the 4 screws.� Mounted the cover with the 3 screws.

Displaychangeableto 180°

Thermistor

4 Mountingclamps

4 ScrewsM5x90

Don’t forget the gaskets for the 3 screws .Ensure that there is no water on the unit before you open the cover.

Page 14: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

14

If you use a motor with bis HV2,2kW, you have to use amounting ring.

Mounting ring

Page 15: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

15

Wall mounting kit HV2.1-3.11

Included components for wallmounted kit HV2.1-3.11

1 mounting plate with fan Picture 1 A4 M3x 8mm screws (self threading) for kit HV2.1-3.4 Picture 2 B or M4x15mm screws (self threading) for kit HV3.5-3.11 Picture 2 B1 Molex connector Mod. 6471-021 Picture 2 C1 Cable gland M12x1,5 Picture 2 D1 counter nut M12x1,5 Picture 2 E

not included: Dowels and mounting screws for mounting the kit on the wall.Recommended diameter for this screws: � 5-6mm for kit HV2.1-3.4

� 6-8mm for kit HV3.5-3.11

Picture 1 Picture 2

A

B C D E

Page 16: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

16

Picture 3 Picture 4

Picture 5

Picture 6 Picture 7

Picture 8 Picture 9

Open

Screw M3x8mm or M4x15mm(self threading)

+ plus pole

Molex connector

cable gland forfan cable

red

black

plus pole/ red Black / minus

Page 17: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

17

Free space for wallmounting

MOUNTING INSTRUCTIONS

BEFORE REMOVING THE FREQUENCY INVERTER COVER THE SYSTEM MUST BE DIS-CONNECTEDFROM THE POWER SUPPLY. AFTER SWITCHING OFF THE POWER SUPPLY WAIT AT LEAST 5MINUTES BEFORE STARTING WORK ON OR IN THE TECHNOVAR DRIVE HEAD.

Mounting the mounting plate on the HV 2.1-3.11Place the heat sink of the Technovar on the mounting plate and fix them together by using the 4 selfthreading M3x8mm respective M4x15mm screws (Picture 3).

Connecting the fan-cableRemove the 3 screws holding the top cover of the Technovar and lift it carefully (picture 4).NOTE: Take care with the connection cable to the display and the Ground-cable!Left the cover aside.Mount the included cable gland (Picture 2D/2E) on the cover plate and put the cable through the cablegland. (Picture 7).Connect the fan cable with the Molex connector (Picture 5) and then plug it into the right connectionon the control card (Picture 6).NOTE: Take care of at the correct polarity: Red cable – plus pole

Black cable – minus pole

Fix the length of the cable inside the Technovar and tighten the cable gland to have ensure the IP55class of protection.

Note: You have to leave a free space in front of the Technovar forconfiguration and for dismounting the cover.

free space required for cooling and mounting

Page 18: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

18

Afterwards replace the top cover and be careful with the connection cable to the display and theEarth-cable. At last fix the 3 screws of the top cover.

In Pictures 8 and 9 you can see the Technovar with the mounted wallmounting-kit.

Mark the 4 holes according to the dimension drawing (see next page) on the wall and drill it with adrilling machine. Mount the whole Technovar unit on the wall by using suitable screws.

Dimension drawing (HV2.1-3.4) (inches)

Dimension drawing (HV3.5-3.11)

Page 19: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

19

Wall mounting – kit 15/22kW

Picture 1 Picture 2E

Included Components for wallmounted kit4 long screw M6x25 Picture 1 A4 washer Picture 1 B4 short screw M6x12 Picture 1 C4 washer Picture 1 D1 AC-fan incl. connection cable Picture 21 fan board incl. 3 fuses T 1A/500V Picture 3 and 3 G2 cable connector Picture 71 2 wire cable with connector Picture 7 and 81 cable gland for fan-cable Picture 121 wallmounted component Picture 13

A

B D

F

F

C

Page 20: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

20

Picture 3 Picture 4

Picture 5 Picture 6

Picture 7 Picture 8

Picture 9 Picture 10

G

L1

L2

L3

U2

V2

W2

L3

L2

L1

Page 21: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

21

Picture 11 Picture 12

12

Picture 13 Picture 14

Mounting the wallmounted kit on the Technovar

BEFORE REMOVING THE FREQUENCY INVERTER COVER THE SYSTEM MUST BE DIS-CONNECTEDFROM THE POWER SUPPLY. AFTER SWITCHING OFF THE POWER SUPPLY WAIT AT LEAST 5MINUTES BEFORE STARTING WORK ON OR IN THE TECHNOVAR DRIVE HEAD.

Mounting the fan-boardLoosen the 4 main screws from the Technovar cover and also the 8 screws holding thecontrol-card.Then remove the Technovar cover carefully. (Take care with the control-card and the GND-Cable.)Picture 3 shows you the fan-board (incl. the 3 fuses 1A/500V- picture 3/G) that you can fixwith the 3 plastic-distances in the 3 holes which are made for. (Picture 4)The power supply for the fan-board comes from the connections L1, L2, L3 on the primary-side from the rectifier-board.Please fasten the connection screw as well and connect the right cable with the rightconnectionCompare the cable number and the connection number. (Picture 5).

Connecting the control-cable

Page 22: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

22

Connect the included 2-wire.black cable with the fan-board (Picture 6) an take it upside tothe internal fan. Then place the cable beside the internal fan and fix it with the two cable-connectors which are shown in Picture 7.Next put the cable through the hole at the front of the Technovar and pull it below thecontrol card at the bottom (Picture 8).On the frontside of the control-card is an connector for plug in the control cable what you seein Picture 9.

Mounting the fan on the Technovar

Place the Technovar at the AC-fan that you can see the LCD-Display at the front and thepieces for the wallmounted component are on the side (Picture 11).Then put the fan-cable through the hole and fix it with the included cable gland from picture12. Look that the cable goes between the heat sink and isn´t fixed from it (Picture 12).

Connect the fan-cable at the connection clamps U2, V2, W2 on the fan board and screw theGND-cable with the GND screw (Picture 10).Next take the four long screws M6x25mm and the lock washers (see picture 1/A and B) and fixthe Technovar on the AC-fan with the nuts you can see in picture 2/E.At least put the wall mounted component (Picture 13) behind the Technovar and fix this 2components with the four short screws M6x12mm and the lock washers (see Picture 1/C andD) what you see in picture 14.

!! PLEASE NOTE: The fan is only running with the TECHNOVAR (Run Signal).Connect the fan cable so that the fan can blow from the carrier-sheed through the heat sink.

Dimension drawing

Page 23: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

23

6.1.3 Mounting the thermistorVariant A:

Variant B:

1. Open the cover of the conduit box and remove also the terminal block inside.2. Fix the thermistor (Variant A or B)3. Electrical connection of the motor cables see chapter 6.2.4. Electrical connection to the Technovar see chapter 6.2

motor

thermistor

terminal block

rubber gasket

cover of theconduit box

Thermistor

Page 24: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

24

6.2 Electric installation and wiring

6.2.1 Means of protection

Ask your power supply company which means of protection are required.

Applicable: AC and DC current-operated circuit breaker (FI), TN systems, protectivecircuits.

When using a FI protection switch, make sure that it also releases in the event ofa DC fault, use for each Technovar a separate FI-switch!

6.2.2 Wiring the Technovar to the motor

Remove the 3 screws holding the top cover of the Technovar. Lift off the top carefully, takeoff the connection cable to the display carefully remove the ground screw and left aside.On the next page you can see:

(1) control card with all terminals for the control signals and the RS485 interface(2) main card with all power components and terminals for power supply and motor

connections

Page 25: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

25

6.3 Main Voltage Terminals

supply cableThe main power cable is connected to the terminals labeled L1, N for the 1x230 VAC, singlephase unit or L1, L2, L3 for the 3x400VAC, three phase unit.

Power supply1x230 VAC Motor connection

Control terminals

RS485 interface

Power supply3x400 VAC

Motor connection

RS485 interface

Control terminals

HV2.1 / HV2.2 HV 3.2 – 3.11

RS485 interface

Motor connection

Controlterminals

Power supply3x400 VAC

HV 3.15/ 3.18/ 3.22

Page 26: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

26

6.4 Control Terminals

All externally used cables have to be shielded. Do not connect the ground of the electroniccomponents to other potentials (all electronic ground and GND of the RS 485-interface areconnected together internally).

For external off/on switches, contacts suitable for switching <10 VDC are necessary.

If unshielded control cables are used, signal interference may occur and interfere withthe function of the inverter.

Terminal: X1/ 1 GND2 Actual value input 4...20mA, 50 Ohm load resistance3 Power supply for external control 15VDC, max. 100mA4 GND5 External on/off (release) Ri=10kOhm, 5 Volt DC

(gold plated contact necessary!)6 GND7 Low water; Ri=10kOhm, 5 Volt DC

(e.g. incoming pressure switch or water level switch)8 Thermo switch or PTC (in motor terminal box) Ri=10k, 5 VDC9 Thermo switch or PTC10 GND11 Analog output 0...10 V, max. 2mA12 Current signal input 4...20mA13 Voltage signal input 0....10V or 2......10V14 Digital input

Terminal: X2/ 1 Fault signal relay NC max. 250VAC 1A free of inductivity(for dry 2 Fault signal relay CC max. 250VAC 1A free of inductivityContacts) 3 Fault signal relay NO max. 250VAC 1A free of inductivity

4 Pump operationsignal relay

NC max. 250VAC 1A free of inductivity

5 Pump operationsignal relay

CC max. 250VAC 1A free of inductivity

6 Pump operationsignal relay

NO max. 250VAC 1A free of inductivity

!! Fault relay (X2/2 - X2/3) is closed, when there is no error!!

Terminal: X5-6/ 1 RS 485 SIO - LOW2 RS 485 SIO + HIGH3 RS 485 GND4 RS 485 + 5 VDC max. 20mA out

For supply of external interfaceconverter

Page 27: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

27

6.4.1 Control terminals

When connecting the variable speed pumps (max. 4 pumps) via the interface RS 485, theterminals X5/1/2/3 or X6/1/2/3 of each Technovar are to be connected together by means of ashielded cable and programmed accordingly (� Programming Sequential Operations).

Page 28: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

28

6.4.2 Dip-Switch on the controller board

SW4: DIP-Switch to select the switching frequency

!!Attention!!Before switching, disconnect the power supply, otherwise theTechnovar could be destroyed.

SW4 Switching frequency1 2

OFF OFF 8kHz (standard)ON OFF 5kHzOFF ON 4kHzON ON 2.5kHz

6.4.3 Main parts from the control card

RS-4

85 t

erm

inal

s

Control terminalblocks

24V output(max. 800mA)

for external fan

40 pin connection(to power board) Dip-switch

Main supply3x400 V

Motor connection

Pin connection(to Display)

Page 29: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

29

HV 3.15/ 3.18/ 3.22

6.5 Front plateHV3.15/ 3.18/ 3.22

LCDPush buttons RS-485

terminals

40 pin connection(to power board)

24V output(max. 1A) forexternal fan

Dip-switch

Con

trol

ter

min

al b

lock

s

Page 30: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

30

HV 2.1-3.11

7 Language Selection

The information on the display can be called up in German, English, Italian, French, Spanish,Portuguese or Dutch.To select the desired language proceed as follows:Briefly press + simultaneously (in 1st display); � the actual language will now appearin the second line and the desired language can be selected with the button or . Afterthe language has been selected, press button briefly and the first menu window of themain window will appear again. If only the language is changed it is not necessary to SAVE.

ON

OFF

Select

Power Run Fault

Page 31: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

31

8 Typical applications

8.1 ControlBy means of the built-in Technovar controller acc. to constant pressure by pressuretransmitter and/or acc. to constant flow by flow-meter or orifice plate with differentialpressure transmitter and differential pressure transmitter or - if required - acc. to externalmanual control by reference 4 - 20 mA DC (only for special applications).

8.2 The Main Menu SettingThere are ten display screens in the main menu which will allow you set the required systempressure, save it, and turn the system on. Several of these display screens were already usedduring the test run. After power has been turned on, the “Power on” light should illuminateand the display should show “No Autostart – disable inverter”.

Instructions:

Check the green POWER light NO Autostartdisable inverter

Press the button to advance the display to INVERTER STOPON -> START

Press to advance the display to REQUIRED VALUEX.XX psi

REQUIRED VALUESet the desired set pressure with either or . If several pumps are connected via the RS-485 interface, one pump must be ready for operation when the set pressure is changed,otherwise the set value will not be accepted by the follow-up pumps. Afterwards the newrequired pressure has to be saved in all pumps.

Press to confirm and the display changes to AUTO – STARTOFF

AUTO – STARTSelect (ON) with the button or (OFF) with . Auto-start ON starts the pump automaticallyagain after an interruption of the power supply (power failure).At the Auto-start setting OFF, the pump must be restarted manually by pressing the buttons

(OFF) and then (ON) after power failure.

Press and the display changes to: ERROR 1...................

Last error

Note: All errors are only readable

Press the button to change toError before last error:

ERROR 2...................

Page 32: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

32

Press the button to change toerror before error 2:

ERROR 3...................

Press the button to change toerror before error 3:

ERROR 4...................

Press the button to change toerror before error 4:

ERROR 5...................

Press the to advance the display to: TOTAL RUN TIME0000:00

Press the button and the display will change to SAVE ??? +

Simultaneously press buttons and until...SAVE ???SAVED

appears and the display jumps back to Window 1“INVERTER STOP” after few seconds.

Warning: After each change of a setting, this has to be saved (newvalues are stored in an EEPROM).Otherwise the changes will be lost in case of a power supplyfailure!

Page 33: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

33

ITT

IND

UST

RIES

x.xx

psi

Requ

ired

Valu

e 1

126

,9 p

siA

uto

- S

tart

ON

Erro

r 1

Erro

r 2

Erro

r 3

Erro

r 4

Erro

r 5

Tota

l Run

Tim

e00

00 :

00Sa

ve ?

?+

��

Pass

wor

d00

00JO

G -

Mod

e0

.0 H

z 3

19,5

psi

Win

dow

5 %

Ram

p H

yste

resi

s80

%Ra

mp

14.

0 Se

cRa

mp

24.

0 Se

cRa

mp

370

Sec

Ram

p 4

70 S

ecM

ax. F

req

uenc

y60

.0 H

zM

in. F

requ

ency

0.0

Hz

Con

fig. F

min

F ->

0St

op -

Del

ay F

min

0 Se

kBo

ost

5.0

%Se

nsor

Adj

ust

?ou

t of

ran

geSe

nso

r -

Curv

eLi

near

Sens

or R

ange

20 m

A =

362

,6 p

siM

ode

Cont

rolle

rRe

gula

tion

Mod

eN

orm

alSt

art

Valu

ed

isab

led

Con

fig. R

eq. V

al. 2

OFF

Rela

y C

onfig

.Ru

n M

otor

SUBM

ENU

Off

set

Off

set

- In

put

OFF

Leve

l 10.

0 %

Leve

l 20.

0 %

Inte

nsity

1+

0.0

%

Inte

nsity

2+

0.0

%

SUBM

ENU

Seq

. Con

trol

Act

u. V

alu

e In

c.5

psi

Act

u. V

alue

Dec

.2,

1psi

Enab

le S

eq. C

TL.

58.

0 H

z

Swit

ch In

terv

al1

2 ho

urs

Sour

ce R

eq. V

alu

eO

FF

SUBM

ENU

Syn

ch. C

ontr

olSy

nchr

on. L

imit

0.0

Hz

Sync

hron

- W

indo

w2.

0 H

zPu

mp

- Se

que

nce

Adr

1

f

ault

Busa

rbit

- D

iag.

0

SUBM

ENU

RS4

85 -

Inte

rfac

e

Pum

p - A

ddre

ssO

FF

AD

C Re

fere

nce

Loca

l

Lift

- A

mou

nt0.

0 %

Ana

log

- O

utA

ctua

l Val

ueD

imen

sion

Uni

tps

iTe

st R

un

afte

r 10

0 h.

SUBM

ENU

Test

Run

Test

Run

man

.�

�+

Test

- F

req

uenc

y3

0.0

Hz

Boos

t Te

st -

Run

10.0

%

SUBM

ENU

Erro

rs

Conv

eyo

r -

Lim

itdi

sab

led

Del

ay T

ime

2 Se

c

Erro

r -

Rese

tdi

sab

led

Cle

ar E

rror

s00

00

Ope

rati

ng H

ours

0000

h.

Dis

p. -

Con

tras

t50

%Se

t Pa

ssw

ord

0066

Hea

ting

ON

Def

ault

Eu

rope

+�

Def

ault

USA

+�

SUBM

ENU

Def

ault

Valu

esSa

ve ?

?+

��

Lock

Fun

ctio

nO

FF

Star

t

Freq

u. -

Lift

ing

37.0

Hz

Page 34: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

34

8.3 Single Pump – Pump Protection

The Technovar has the ability to protect the pump by shutting off in low/no suction or run outconditions.

Note: Low/no suction protection depends on the installation of a suction linepressure switch, or float switch for a tank. This switch is connected tothe Technovar. The cut out setting for a suction pressure switch shouldbe greater than the minimum incoming pressure, required by the pump.

Note: Run out protection is available for one pump systems and multiple pumpsystems with a common suction pipe. (described at chapter ”ConveyorLimit” 11.30.1 In multiple pump systems with separate suction pipes,you can not avoid dry running by measuring the system pressure,because the pressure is produced from another pump in the system.

8.3.1 To set run out protection

Hold the button for 3 seconds and the display changes to PASSWORD0000

Password:The password protection prevents untrained personal from accidentally changing of the basesettings:

Set ‘Password 0066’ by pressing or PASSWORD0066

You will now be able to access all of the alternate menus for all Technovar optional controls.

After entering the password you have to confirm by pressingthe button to advance the display to the next window

JOG – MODE0.0 Hz X.XX psi

JOG-MODEActual outgoing frequency and actual analog input are shown. By pressing or in thismenu, the internal controller of the Technovar will be shut off and the inverter changes tomanual mode. With the buttons and you can set any constant speed. Setting of 0,0 Hzstops the inverter. If the JOG-MODE is left at a frequency higher than 0,0 Hz the inverter willcontinue its normal automatic operation.

Press the button repeatedly until you reach SUBMENUERRORS

Hold the button down for 3 seconds to enter thesubmenu, until the display changes to

CONVEYOR-LIMITdisabled

Page 35: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

35

CONVEYOR-LIMITDisabled or adjustable between disabled...NORMALIZE. To disable the conveyor limit, press

till “disabled” is shown on the display. An adjusted value >0 has to be reached till theprogrammed. “DELAY TIME”.

If this value is not reached, the failure “CONVEYOR CONTROL ERROR” will be indicated andthe pump will stop.

Press once the button and change to DELAY TIME2 Sec.

DELAY TIMEThe delay time is adjustable between 0 and 100 Sec. for switch-off of the Technovar in case of lowwater, (Terminal X1/6-X1/7) and conveyor limit.

Press to advance the display to ERROR-RESETdisabled

ERROR-RESETif you want to have an automatic error reset for 5 times (not for errors in the control-port),you have to set a delay time for the automatic reset (range: 0-250 sec.).That means after a non fatal error, the Technovar will be restarted after the set delay time.After five consecutive errors the converter switches off.To disable this function press until “disabled” appears. (The internal counter of the automatic resets will be reduced by one each operating hour).

Note: “Fatal” errors will always shut down the system at the first time.

Hold down the key for 3 sec. to leave the submenu andthe display changes to

SUBMENUERRORS

Press the button repeatedly until you reach SAVE ??? +

Press both buttons until the display changes to SAVE ???SAVED

After a moment, the screen will automatically return to the 1st window.

ITT INDUSTRIESX.XX psi

Page 36: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

36

8.4 Single Pump – System Curve Compensation

The Technovar can automatically compensate for system friction losses due to increased flow.Tables are available in most pump catalogs, indicating the amount of friction losses that canbe expected in various sizes of pipes at different flow rates. Use these tables to determine thefriction losses for the pipe size you are using at maximum flow rate.This Diagram shows a typical system curve. The system pressure set point is shown at shutoffand pressure increase is shown for increasing flow.Calculate the pressure required to overcome friction losses at maximum flow.

Page 37: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

37

8.4.1 Entering the compensation values

Hold the button for 3 seconds and the display changes to PASSWORD0000

Password:The password protection prevents untrained personal from accidentally changing of the basesettings:

Set ‘Password 0066’ by pressing or . PASSWORD0066

You will now be able to access all of the alternate menus for all Technovar optional controls.

Press the button repeatedly until you reach FREQU.-LIFTING37.0 Hz

FREQUENCY-LIFTINGAdjustable between 6 Hz and the set MAXIMUM FREQUENCY, this setting states at whichoutput frequency the set pressure should be increased. That is the speed at which the pumpworks at the set pressure and at delivery rate 0(can be read in the JOG MODE).

Press the button to change to LIFT-INTENS.0.0 %

LIFT-ITENS.Increasing value, when the reaches its maximum speed (maximum volume).

Enter settings as follows:1. Setting the set pressure (see: Inverter main menu).

2. Enter frequency at zero demand and actual pressure = set pressure � FREQU. LIFTING

3. Set desired lifting at maximum speed (in %) of set pressure.

Increasing values up to 200% are allowed. If your friction losses are above 200% of your setpressure, bigger pipes should be used.

Press the button repeatedly until you reach SAVE ??? +

Press both buttons until the display changes to SAVE ???SAVED

All new settings are stored.After a moment, the screen will automatically return to the 1st display.

ITT INDUSTRIESX.XX psi

Page 38: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

38

8.5 Multiple Pump - Constant Pressure and System Curve Compensation

When two, three or four Technovar controlled pumps are connected in a system, they can beprogrammed to work together to maintain system pressure up to the maximum flow rate ofall pumps combined. As the first pump reaches its maximum speed and flow, the second willautomatically turn on (and so on). In addition, the sequence of the pump that will run first(lead pump) can be automatically varied to reduce premature wear of any pump in thesystem.

Hold the button for 3 seconds and the display changes to PASSWORD0000

Password:The password protection prevents untrained personal from accidentally changing of the basesettings:

Set ‘Password 0066’ by pressing or . PASSWORD0066

You will now be able to access all of the alternate menus for all Technovar optional controls.

Press the button repeatedly until you reach MODE:Controller

Use and to change the setting to: MODE:Multicontroller

MODE:Controller:If only one TECHNOVAR pump is in operation set the Controller for a stand alone controllerfunction. If more than one pump are working together, connected via the RS485 interface(follow-up pump control), the Multicontroller must be set with the buttons or .Synch. Controller:The Synchronous Controller mode is working in the same way like the Multicontroller. Theonly difference is, that all pumps in the multi pump system are running at the samefrequency.Actuator:The Actuator application is only used if you have an external controller and the Technovar isused as a standard frequency converter. In the Actuator-Mode, the internal controller is shutoff, and the output frequency is proportional to the input signal (X1/2) � 4-20 mA = 0 -fmax. The frequency changes with the programmed ramps 1 and 2. The functions of lowwater, thermal protection and external ON/OFF are still working.

Page 39: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

39

...... = fmax

If Manual control is selected, the parameter REQUIRED VALUE will change to Manualcontrol LOCAL, where the actual frequency and the actual value is displayed (according tothe JOG-MODE in the submenu).Now the frequency can be changed with the and buttons, and the speed of the pumpwill change with the fasten ramps1 and 2. After selecting the right frequency, it can besaved with the standard SAVE-parameter.After a supply failure, the pump will then run with this selected frequency (depending onthe parameter AUTO-START).

In the first window, the actual frequency is displayed. The frequency can be changedbetween the set minimum and maximum frequency. (CONFIG. FMIN is not active in thismode!).

Attention Driving the pump in a not allowed speed range can damage the motor or theTechnovar-head!

Press the button five times and you reach SUBMENUSeq. Control

Hold down the button for 3 seconds until the displaychanges to

ACTU. VALUE INC.5 psi

ACTUAL PRESSURE INCREASE (=LIFT VALUE):This value, together with the fall value (ACTUAL VALUE DECREASE) determines theincrease of the required value after starting of the following pumps (see example)

Page 40: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

40

Generally a slight pressure drop is allowed on the first pump before the next is started.This allows for brief systems fluctuations without pump cycling. Once the next pumpstarts, however, you will want the system to resume its normal set pressure.

To do this, enter the amount of pressure drop you willallow before the next pump starts (= value ofparameter ACTUAL VALUE DECREASE). The diagramshows the pressure drop and increase.

To increase the pressure even more to compensate forsystem loss at higher flows, enter the total of thesystem drop allowed before next pump starts and theincreased pressure (ACTUAL VALUE INCREASE) desired.

Application example:1) Pump 1 reaches the speed of ENABLE SEQ: CONTROL or more2) Pressure falls and reaches the start-value of the 2nd pump

(= REQUIRED VALUE – ACTUAL VALUE DECREASE)3) Pump 2 is switched on automatically4) The required value is calculated new, after the start of the 2nd pump in the following

way!

New required value = REQUIRED VALUE – ACTUAL VALUE DECREASE + ACTUAL VALUE INCREASE

Generally:k ... Number of active pumpsP = Pset + (k-1)*[lift value – fall value]

� Lift value = Fall value � Pressure constant when pumps switch on� Lift value > Fall value � Pressure rises when lag-pump switches on� Lift value < Fall value � Pressure falls when lag-pump switches on

Enter the required value by pressing the and button ACTU. VALUE INC.7,1 psi

Press the button to confirm and change to ACTU. VALUE DEC.2,1 psi

ACTUAL PRESSURE DECREASE (= Fall value):This value determines amount of pressure drop you willallow before the next pump starts.

Page 41: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

41

Enter the required value by pressing the and button ACTU. VALUE DEC.5 psi

Press the button to change to ENABLE SEQ. CTL58.0 Hz

ENABLE SEQUENCE CONTROL: (Release frequenz)The follow-up pump only starts, when the start-value (SET VALUE – ACTUAL VALUEDECREASE) is reached and the lead pump has reached the programmed release-frequency.(Adjustable from 0.0 Hz to 70 Hz).Normally this start frequency is set 1 to 2 Hz lower than the MAX. FREQUENCY If you don’twant to start a following pump this value has to be set higher than the MAX. FREQUENCY.

Enter the required value by pressing the and button ENABLE SEQ. CONTROL59.0 Hz

Note: In the standard multicontroller mode, the next pump will not start until both thesystem pressure drop and release frequency first pump speed have been reached.In the synchronous control mode, the first pump only has to reach the releasefrequency, then the next pump will start.

Press button briefly to advance to SWITCH INTERVAL12 hours

SWITCH INTERVAL:For changeover of the master pump and follow-up pumps, in order to achieve evenoperating hours. Adjustable between 1 hour and 100 operating hours of the Technovar. Ifan interval of more than 100 is selected, the automatic changeover is deactivated.Manual changeover of the master pump in the 1st display by pressing the -button.

Enter the required value by pressing or button SWITCH INTERVAL24 hours

After pressing the button for 3 seconds, you leave the submenu and the display changes to

SUBMENUSeq. Control

Page 42: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

42

Press the button again briefly to advance to SUBMENURS485-Interface

Hold the again for 3 seconds to enter the submenu andthe display changes to

PUMP-ADDRESSOFF

PUMP-ADDRESS:If only one pump is used, the setting remains OFF. If several pumps are connected via the RS-485 interface (max. 4) each pump must be allocated its own address number (1-4)(each number may only be allocated once!).

Use the and button to select a “PUMP-ADDRESS” PUMP-ADDRESS1

Hold the button for 3 seconds to return to SUBMENURS485-Interface

Press the button repeatedly until you reach SAVE ??? +

Press both buttons until the display changes to SAVE ???SAVED

All settings are stored.

After a moment, the screen will automatically return to the 1st display.

ADR X (X) P XX.XX psi

Note: Repeat this steps for each pump in the system. Use a differentaddress number for each pump!

Page 43: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

43

9 Parameters of the main menu

After connection of the Technovar unit to the power supply the following possibledisplays become visible.

SW-Ver: VOG 120Date: xxxx

The current software version with the date ofprogramming is displayed for about three seconds.

The following two displays are depending on the selected mode:

a) Active MODE = Controller:

1. ITT INDUSTRIESXX.X psi

This window is mentioned several times in theOperating Instructions as 1st display at Mode Controller

Continue by pressing the -button

2. REQUIRED VALUE 1X.XX psi

Set the desired set pressure with either or and then briefly press the -button.

If several pumps are connected via the RS-485 interface, one pump must be ready foroperation when the set pressure is changed, otherwise the set value will not be accepted bythe follow-up pumps. Afterwards the new required pressure has to be saved in all pumps.

If you want to change to Required Value 2 you have to close the external contact,connected to X1/10-X1/14.

After closing this contact, the display changes from Required value 1 to

2.1 REQUIRED VALUE 2ADC-X XX.X psi

In this window, there is shown the condition ofthe second Required value.

ADC-X: This parameter shows you the source of the external or internal valueXX.X Bar: shows the actual value of the Required Value 2.

Continue by pressing the -button

b) Active MODE = Actuator:

1. ITT INDUSTRIESFrequency XX.X Hz

This window is mentioned several times in theOperating Instructions as 1st display at the Mode

Actuator.Continue by pressing the -button

2. REQUIRED VALUE 1X.XX psi

Set the desired set pressure with either or and then briefly press the -button.

If several pumps are connected via the RS-485 interface, you have to set this parameter oneach pump!

Page 44: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

44

c) Active MODE = Synch. Controller or Multicontroller:

1. ADR (X) P XXX.X psi

This window is mentioned several times in theOperating Instructions

as 1st display at the Synch. Controller or Multicontroller mode.

Continue by pressing the -button

2. REQUIRED VALUE 1X.XX psi

Set the desired set pressure with either or andthen briefly press the -button.

If several pumps are connected via the RS-485 interface, one pump must be ready foroperation when the set pressure is changed, otherwise the set value will not be accepted bythe follow-up pumps. Afterwards the new required pressure has to be saved in all pumps.

If you want to change to Required Value 2 you have to close theexternal contact, connected to X1/10-X1/14.

After closing this contact, the display changes from Required value 1 to

2.1 REQUIRED VALUE 2ADC-X XX.X psi

In this window, there is shown the condition ofthe second Required value.

ADC-X: This parameter shows you the source of the external or internal valueXX.X Bar: shows the actual value of the Required Value 2.

Continue by pressing the -button

d) Active MODE = Actuator local:

1. ITT INDUSTRIESFrequency XX.X Hz

This window is mentioned several times in theOperating Instructions as 1st display at the Mode

Actuator local.Continue by pressing the -button

2. ACTUATOR LOCAL X.X Hz X.XX psi

Set the desired set pressure with either or andthen briefly press the -button. If several pumps are

connected via the RS-485 interface, you have to set this parameter on each pump!

Press the button on the Technovar to change to

!! The following displays of the main menu are valid for all selected Modes !!

3. AUTO - STARTON

Select (ON) with the button or (OFF) with .

AUTO-START ON starts the pump automatically again after a failure of the power supply.If AUTO-START is OFF, the Technovar has to be restarted by pressing the buttons (OFF)and then (ON) after a power supply failure.

Page 45: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

45

If the AUTO-START is OFF, the unit will not start again in cases of a failure or disconnection.After restarting is following message is shown:

3.1 NO AUTOSTARTdisable inverter

To restart the unit, press at first the and than to start the button.

Press and the display changes to

Note: All errors are only readable

4. E R R O R 1.........................

Here, the last error is shown

Press the button to change to

5. E R R O R 2.........................

Shows the error before the last error

Press the button to change to

6. E R R O R 3.........................

Shows the error before error 2

Press the button to change to

7. E R R O R 4.........................

Shows the error before error 3

Press the button to change to

8. E R R O R 5.........................

Shows the error before error 4

Press the button to change to

9. TOTAL RUN TIME0000:00

Runtime of the motor.This time is reset together with the

operating hours.

Press the button to change to

Please Note : All changes have to be saved, that they will not be lost in case of shut off of the power supply !!

10. SAVE ??? +

Simultaneously press buttons and until...:

Page 46: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

46

11. SAVE ???SAVED

appears on the display. After fiveseconds the display jumps back to the1st display.

These parameters can also be set during operation; To do so, briefly press thebutton and repeat steps 1 – 10.

Please Note: often shown display

12. INVERTER LOCKEDenable inverter

This message appears when the connection ofterminal X1/4-X1/5 is open (external release contact).

10 Settings at Secondary Menu

Important: Before entering the secondary menu these instructions mustbe read carefully to prevent incorrect settings which will causemalfunction.

Secondary Menu:

Stop motor by pressing OFFINVERTER STOP

ON -> START

Press for 3 seconds to change toPASSWORD

0000

Set ‘Password 0066’ by pressing PASSWORD

0066

Confirm by pressing and the firstwindow of the sub menu is shown

J O G – MODE0.0Hz X.XX psi

In the following paragraphs all possible settings are listed (in the display, there isshown the European default setting).

10.1 JOG-MODEDisplay and Manual Operation Mode

J O G – MODE0.0Hz X.XX psi

Actual outgoing frequency and actual analog input areshown. By pressing or in this menu, the

Note: The password must be entered at each entry

Page 47: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

47

internal controller of the Technovar will be shut off and the inverter changes to manualmode. With the buttons and you can set any constant speed.Setting of 0,0 Hz stops the inverter. If the JOG-MODE is left at a frequency higher than 0,0Hz the inverter will continue its normal automatic operation.

Press on the Technovar to change to

10.2 Window - %

WINDOW5%

This value indicates the max. variation of the outgoingpressure (see diagram “Ramp window”).

Possible setting: between 0% - 100% of required pressure.

Press on the Technovar to change to

10.3 Ramp Hysteresis

RAMP HYSTERESIS80%

Level, where the fast ramp changes to the slowramp (see diagram “Ramp window” )Possible setting: between 0%..100% of the window

Press on the Technovar to change to

10.4 Ramp 1: Fast running up time:Time setting at Ramp 1, 2, 3, or 4 will influence the control of the pump andMUST NOT BE CHANGED at normal operation. Possible setting of each ramp 0,05 - 1000sec.

RAMP 14.0 Sec

Excessively fast running up time may overload theinverter in the starting moment.

Excessively slow running up time may cause a break down of the outgoing pressure duringoperation.

Press on the Technovar to change to

10.5 Ramp 2: Fast running down time:

RAMP 24.0 Sec

Excessively fast running down time tends to causeoscillation or hunting or can cause an error

(OVERVOLTAGE) during ramp down of the pump.Excessively slow running down time tends to generate over pressure.

Press on the Technovar to change to

Page 48: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

48

10.6 Ramp 3: Slow running up time:The following ramps 3 and 4 determine the speed of the internal Technovar controllerand depend on the system, which should be controlled.

RAMP 370 Sec

A too slow running up time can cause a break of theoutgoing pressure during variation of the demand.

A too fast running up time may lead to oscillation and/or overload of the inverter.

Press on the Technovar to change to

10.7 Ramp 4: Slow running down time:

RAMP 470 Sec

A too fastA too slow

setting leads to oscillationsetting delays the switching off too much

Ramp – Window

Press on the Technovar to change to

10.8 Maximum Frequency

MAX. FREQUENCY60.0 Hz

Possible setting between 40 and 70 Hz.Attention: Settings higher than 60 Hz may overload themotor!

Settings of 10% above nominal frequency cause 33% more power consumption!

Press on the Technovar to change to

Page 49: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

49

10.9 Minimum Frequency

MIN. FREQUENCY0.0 Hz

Here you can set the minimum frequency between 0,0and Max.frequency.

Attention!: If there is set f>fmin in the parameter CONFIG. FMIN the pump will not stop inthe normal mode. It will keep running with the set minimum frequency.!! Possibility of overheating of the pump !!

Press on the Technovar to change to

10.10 Operation at the minimum frequency

CONFIG FMINf => fmin

If you have selected „f->0“ the frequency will godown to the selected minimum frequency.

Then the inverter will keep running for the selected time and after this time the Technovarwill stop automatically.

If the selection is „f->fmin“ you can not run the pump below the set minimum frequency. Inthe controller, actuator and multi controller mode the pump will never run below the setminimum frequency (the pump will only stop with an external on/off-(terminals X1/4 andX1/5) or in case of a failure.

Press on the Technovar to change to

10.11 Delay time for shut off at minimum frequency

STOP-DELAY FMIN5 s

After running the pump for this selected time atminimum frequency, the pump will stop, if parameter

CONFIG. FMIN it set to f � 0 Adjustable between 0 and 100s.

Press on the Technovar to change to

10.12 Boost

BOOST5.0 %

The stated value determines the course of theU/f-curve.

Setting of the motor starting voltage in % of rated voltage.Settings of 0...25% of maximum output voltage are possible. However, care should be takenthat settings are kept as low as possible so that the motor does not become thermallyoverloaded at lower frequencies.

Press on the Technovar to change to

Page 50: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

50

10.13 Sensor – Adjust

SENSOR_ADJUST?Out of range

Zero point adjustment of the transmitterDepressurise the system and press buttons +

simultaneously. After adjustment "adjusted" appears on the display. If “out of range” is shownon the display, no adjustment is possible

Press on the Technovar to change to

10.14 Sensor - Curve

SENSOR-CURVELinear

Function of the input signal (4...20mA) of theTechnovar to the actual measured value.

Application:linear:Pressure control, differential pressure control, level, temperature and flow control(inductive or mechanical).quadratic: Flow control with an orifice plate together with a differential pressure transmitter.

Press on the Technovar to change to

10.15 Setting of the measuring range

SENSOR RANGE20mA = 362,6 psi

Setting the end value of the measuring transmitter,e.g. 362 psi = 20mA of the pressure transmitter

Adjustable range: 20 mA = 100%; corresponds to the possible adjustable ranges:PSI: 2.9 to 1450; GAL/MIN: 9 to 10560FT: max 3345 ft. 0 to100 %; without unit: max 1000;

Press on the Technovar to change to

10.16 Operation Mode

MODE:Controller

Select with the and buttons

If only one TECHNOVAR pump is in operation set the Controller. If more than one pump worktogether via the RS485 interface (follow-up pump control), the Multicontroller must be setwith the buttons or .

Synch. Controller:The Synchronous Controller mode is working in the same way like the Multicontroller. Theonly difference is, that all pumps in the multipump system are running at the same frequency.Actuator:

Page 51: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

51

The Actuator application is only used if you have an external controller and the Technovar isused as a standard frequency converter. In the Actuator-Mode, the internal controller is shutoff, and the output frequency is proportional to the input signal (X1/2) � 4-20 mA = 0 - fmax.The frequency changes with the programmed ramps 1 and 2. The functions of low water,thermal protection and external ON/OFF are still working.

If MANUAL CONTROL is selected, the parameter REQUIRED VALUE will change to MANUALCONTROL in the main menu, where the actual frequency and the actual value is displayed(according to the JOG-MODE in the submenu).Now the frequency can be changed with the and . buttons, and the speed of the pumpwill change with the fasten ramps. After selecting the right frequency, it can be saved withthe standard SAVE.After a supply failure, the pump will then run with this selected frequency (depending on theparameter AUTO-START).The frequency can be changed between the set minimum and maximum frequency.

In the 1st display, there is shown the actual frequency.

NOTE: CONFIG. FMIN will not work in this mode.

Attention Driving the pump in a not allowed speed range can damage the motor or theTechnovar-head!

Press on the Technovar to change to

10.17 Control Response

REGULATION MODENormal

Normal: Speed is increased with falling actual valuesignals. (e.g.: Control at constant output pressure).

Inverse: Speed is reduced with falling actual value signal, (e.g.: Control at constantsuction pressure or at constant level).

Press on the Technovar to change to

Page 52: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

52

10.18 Start Value

START VALUEdisabled

This parameter gives you the start value after pumpstop in percentage of the required value (adjustable

between disabled and sensor range).e.g.required value: 72 PSIstart value: 36 PSIIf the pump system reaches the required pressure of 72 PSI and there is nomore consumption, the Technovar shuts off the pump. When the consumption increasesand the pressure goes down to or below the start value, 36 PSI, the pump will start.

Press on the Technovar to change to

10.19 2nd Required Value

CONFIG. REQ. VAL.2OFF

With this parameter CONFIG. REQ. VAL.2 you canselect an independent 2nd required value. The change

Between 1st and the 2nd required value can be done over the digital input, terminal X1/14on the control card. If this input is connected to Ground, 2nd required value active.

Possible selections:

OFF : actual value 2 is not active (no change after closing the input X1/14)INT : internal required value 2, function and setting according to

existing required value.EXT ADC-I : the required value 2 is made from the value of the current signal

(4-20mA) at the terminals X1/12, X1/10. 20mA is equal to the programmed SENSOR RANGE. If the incoming current signal is below 4mA, there will be shown an error message on the display, but no failure is indicated (failure relay is not closed). In this case the required value 2 will be 0.

EXT ADC-U 0-10V or the required value 2 is made from the value of the voltage signalEXT ADC-U 2-10V (0-10V or 2-10V) at the terminals X1/13, X1/10 (Ground).

10 V is equal to the programmed SENSOR RANGE.

Setting the required value2:The active required value is shown in the actual display of the parameter required value.Is the 2nd required value active (digital input, terminal X1/14, closed), in the first line, there isshown Required value 2. The second line will show the source of the 2nD value, which isselected in the parameter CONFIG. REQ VAL:2(INT or EXT-ADC-I or EXT-ADC-U) and also the actual value of this input.INT : you can select your value with the up- and down buttonsEXT: only display of the value of the 2nd analog input signal.In case of saving, every time both required values are saved.

Press on the Technovar to change to

Page 53: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

53

10.20 Configuration of 1st relay

RELAY CONFIG.Run Motor

Possible selections with buttons and .Simple Multicontr. � allows to start / stop a

constant speed pump

Run Motor � motor run indication (over the relay)

If you have selected Simple Multicontr. two parameters get new functions. The start level of theslave pump you enter at the parameter Enable Seg. Ctl. and the stop value in the parameterSynchron. Limit.e.g. if the speed controlled pump reaches the start level, the relay will be switched on, and will beswitched off, when the output frequency falls below the stop level.Press on the Technovar to change to

10.21 Submenu Offset

S U B M E N UOffset

Press for about 3 seconds to enter thesubmenu and the display changes to

10.21.1 Source of the Offset input

OFFSET INPUTOff

The second additional input can be used as requiredvalue 2 and also for an Offset ofthe 1st required value.

There are three possibilities for the source of the OFFSET INPUT:

OFF : Offset deactivatedEXT ADC-I : Offset will be calculated according to the current input (4-20mA) at the

terminals X1/12 (X1/10=Ground).

Note: If the incoming current signal is below 4mA, there will be an error message onthe display, but no failure is shown (failure relay is not closed). In this case theOFFSET INPUT works like external signal=0.

EXT ADC-U 0-10V: Offset will be calculated according to the voltage input (0-10V or 2-EXT ADC-U 2-10V 10V) at terminals X1/13 (X1/10=Ground)

Press on the Technovar to change to

10.21.2 1st Offset level

Page 54: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

54

LEVEL 1XX.X %

The level 1 is the start level of the 1st Offset.(adjustable between 0 and 100% of the additionalanalog input).

Press on the Technovar to change to

10.21.3 2nd Offset level

LEVEL 2XX.X %

The level 2 is the start level of the 2nd Offset.(adjustable between 0 and 100% of the additionalanalog input).

Press on the Technovar to change to

10.21.4 INTENSITY 1

INTENSITY 1+XX.X %

This is the intensity of the 1st Offset of the requiredvalue at the zero point of the second analog inputSetting range: -200% up to +200% of the sensor range.

Press on the Technovar to change to

10.21.5 INTENSITY 2

INTENSITY 2+XX.X %

This is the intensity of the 2nd Offset of the requiredvalue at the maximum point of the second analog

Input. Setting range: -200% up to +200% of the sensor range.

To leave the submenu press the longer than 3 sec. to change to

S U B M E N UOffset

Press on the Technovar to change to

10.22 Submenu Sequence control

S U B M E N USeq. Control

Programming Sequential Operations

Up to four pumps can be connected using the integrated RS-485 interface (Connection of theterminals /1, /2 and /3 of the terminal blocks X5 or X6 of each pump together). However, thefollowing additional programming must be carried out in the submenu:

Page 55: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

55

Press for about 3 seconds to enter the submenu and the display changes to

10.22.1 Lift Value

ACTU. VALUE INC.5 psi

Adjustable between 0.0 to the pre-selectedSensor range

Application Example:1) Pump 1 reaches fmax (maximum speed)2) Pressure falls and reaches the start-value of the 2nd pump

(= REQUIRED VALUE – ACTU. VALUE DEC.)3) Pump 2 is switched on automatically4) The required value is calculated new, after the start of the 2nd pump in the following

way!

New required value = REQUIRED VALUE – ACTU. VALUE DEC. + ACU. VALUE INC.

Generally:k ... Number of active pumps (k >1)p = pset + (k-1)*[lift value – fall value]

� Lift value = Fall value � Pressure constant when pumps switch on� Lift value > Fall value � Pressure rises when lag-pump switches on� Lift value < Fall value � Pressure falls when lag-pump switches on

Press on the Technovar to change to

10.22.2 Fall Value

For calculation of the set pressure after start of pumps 2 to 4

ACTU. VALUE DEC.2.1 psi

Adjustable from 0,0 to pre-selected Sensor rangedetermines the start-value of the 2nd pump and the

Page 56: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

56

other following pumps. (Start-Value = REQUIRED VALUE –ACT. VALUE DEC.)

Press on the Technovar to change to

10.22.3 Release frequency of the following controller

ENABLE SEQ. CTL.58.0 Hz

Release of the follow-up pump only when the start-value is reached and the lead pump

has reached the programmed frequency. (Adjustable from 0.0 Hz to 70 Hz).If you do not want to start a following pump this value has to be set higher than themaximum frequency.This parameter is also used to start a constant speed pump, when Simple Multicontr. isset). When this frequency level is reached, the potential free contact of the relay X2/5 –X2/6 will be closed.

Press on the Technovar to change to

10.22.4 Switch Interval

SWITCH INTERVAL12 hours

for changing the master pump and follow-up pump inorder to achieve even operating hours of the pumps

Adjustable between 1 hour and 100 hours. If it is set higher than 100 hours, the automaticchangeover is deactivated).Manual change of master pump in the 1st display with the -button.

Press on the Technovar to change to

Page 57: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

57

10.22.5 Source of required value

SOURCE REQ. VALUEOFF

for selecting the address of the source of therequired value. Five adjustments are possible:

OFF, ADR1,ADR2, ADR3 and ADR4. If an additional (INT or EXT-ADC-I or EXT-ADC-U) inputis active, you must enter here the address where this input is connected.At active Multicontroller or Synch. Controller there is shown the active value in a bracket inthe middle of the display. If the sign “#” is shown in the second line of the display, the pumpwill work with a required value from a other pump in the multipump system. On the pump,which is the source of the required value, there is no “#” shown.

Press on the Technovar to change to

10.22.6 Synchronous Control

If the synchronous control is active the activated pumps try to regulate the set pressuretogether (all pumps run at the same frequency). The 2nd pump starts, when the 1st pumpreaches the release frequency (ENABLE SEQ: CONTR) The pumps will now attempt tomaintain pressure by running synchronously. The follow-up pump will than be stopped,when both pump together run below the set SYNCHRON. LIMIT. This creates the hysteresiseffect.

S U B M E N USynch. Control

Press for about 3 seconds to enter thesubmenu and the display changes to

10.22.6.1 Synchronous Limit

SYNCHRON. LIMIT0,0 Hz

Frequency threshold adjustable between 0,0 Hz andthe set maximum frequency.

Switch off threshold of the first follow-up pump. The switch off thresholds of the otherpumps are each higher by the SYNCHRON-WINDOW.This parameter is also used for the stop value for the external constant speed pump atactivated Simple Multicontroller in the parameter configuration relay.

Press on the Technovar to change to

10.22.6.2 Synchronous Window

SYNCHRON-WINDOW2.0 Hz

Frequency offsetAdjustable between 0...10 Hz

Threshold lift for switching off the next follow-up pump.

Setting the Synchronous Threshold:1. Set the desired set value and close the outgoing valves for no flow.2. Start the first pump in JOG Mode (1st Window in the submenu), increase the

frequency, till you reach the required value. Read the frequency ( = f0 )

Page 58: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

58

3. Set the synchronous threshold (f0 + 2-3 Hz)4. Set the synchronous offset to 1-2 Hz

(depending on the pump curve and operating point).

To leave the submenu press the longer than 3 sec. to change to

S U B M E N USynch. Control

Press on the Technovar to change to

10.22.7 Pump status indication

PUMP – SEQUENCEAdr1 disabled

Shows the status of the individual drives- for follow-up pump switching- (adjustable from addresses 1 to 4, address 5 is

reserved for an external control device)- for master function / take over of master function if

there is any malfunction of the master drive.- Information concerning the actual sequential status

of each pump.

The following diagnosis parameters can be also be read in this display window:

hold Px Pump is stopped (control released)run Px Pump is running (control released)

stop Px Pump is stopped, because f< start frequency of the previouspump

Disabled Converter not ready to start (no release)Error Converter errorFault Polling failure (RS-485)

(interface connection wrong or not connected)Detected Polling successful (RS-485)

AdrX * “*” -> Address of the pump that is being read

Press on the Technovar to change to

10.22.8 Error Signals for Data Bus Interruptions

BUSARBIT-DIAG.0

Counts the number of synchronising attempts overthe RS-485 interface.

To leave the submenu press the longer than 3 sec. to change to

S U B M E N USeq. Control

Page 59: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

59

Press on the Technovar to change to

10.23 Submenu - RS 485 Interface

S U B M E N URS 485-Interface

Press for about 3 seconds to enter thesubmenu and the display changes to

10.23.1 Pump Address

PUMP-ADDRESSOFF

If only one pump is used, the setting remains OFF. Ifseveral pumps are connected via the RS-485

interface (max. 4) each pump must be allocated its own address number.

Each address may only be used once!

Press on the Technovar to change to

10.23.2 ADC Reference

ADC REFERENCELocal

Reference for the local ADC (Analog/Digital-Converter)or SIO (RS485 interface).

LOCAL: Actual value from transmitter (Terminal X1/ 1-2)REMOTE: Actual value via RS-485 (Terminal X2/ 1-2-3)

To leave the submenu press the longer than 3 sec. to change to

S U B M E N URS 485-Interface

Press on the Technovar to change to

10.24 Compensation Frequency

Control according to a unit curve (increase of the set pressure, depending upon thedelivery rate or speed).

FREQU. – LIFTING37.0 Hz

Adjustable between 6 Hz and the set MAXIMUMFREQUENCY, this setting states at which frequency the

set pressure should be increased. That is the speed at which the pump works at the setpressure and at flow rate=0 (can be read in the JOG MODE).Press on the Technovar to change to

Page 60: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

60

10.25 Lift-Intensity

LIFT – AMOUNT0.0 %

Adjustable from 0% to 99,9%; this value states howmuch the set value should be continually

increased, till the maximum speed (maximum volume) is reached.1. Setting the set pressure (see: Inverter main menu)2. Enter frequency for demand = 0 and set pressure = Actual Value

(see: Jog Mode ) � FREQU. LIFTING3. Set desired lift at maximum speed, in % of set pressure.

Figure: Lift-Intensity

Press on the Technovar to change to

10.26 Analog - Output

ANALOG - OUTActual value

Analog output 0 - 10V = 0 - 100% (max. 2 mA)Possible settings:� Actual value (signal at terminal X1/3)� Output frequency (0 - fmax)

Press on the Technovar to change to

Page 61: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

61

10.27 Unit

DIMENSION UNITpsi

Adjustable units: psi, bar, m3/h, g/min, ft, mH2O,% or without unit can be changed with or .

Press on the Technovar to change to

10.28 Automatic test run

TEST RUNafter 100 h.

Adjustable between 10...100 operating hours. Thetest run starts the pump at the set time after the

last stop for 20 seconds to a speed of 30 Hz.Deactivating test run: Set 100 hours, keep button depressed, briefly press the button in addition, -> deactivated then appears in the display.Reactivate the test run: Select test run and set the desired hours using the button .

The test run is only active, when the pump is stopped!

Press on the Technovar to change to

10.29 Submenu for manual test run

S U B M E N UTEST RUN man.

Press for about 3 seconds to enter thesubmenu and the display changes to

10.29.1 Activate manual test run

TEST RUN man. +

By simultaneously pressing + a test run willbe released.

The Technovar speeds up to the test frequency with ramp1 and then decreases the speed tillstop with ramp2.Press on the Technovar to change to

10.29.2 Test Frequency

TEST-FREQUENCY30.0 Hz

Frequency for manual test run.Can be set from 6.0 Hz up to 70,0 Hz

Press on the Technovar to change to

10.29.3 Boost

BOOST TEST-RUN10.0 %.

Start voltage in % of rated voltage in order toensure that the motor starts safely.Adjustable between 0% and 25%

Page 62: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

62

To leave the submenu press the longer than 3 sec. to change to

S U B M E N UTEST RUN man.

Press on the Technovar to change to

10.30 Submenu - Error

S U B ME N UERRORS

Press for about 3 seconds to enter thesubmenu and the display changes to

10.30.1 Conveyor Limit

CONVEYOR-LIMITdisabled

Disabled or adjustable between 0.00...SENSORRANGE. To disable the conveyor limit, press till

“disabled” or “0 bar” is shown on the display.An adjusted value >0 has to be reached till the programmed “DELAY TIME”.If this value is not reached; the failure “VAL. RANGE CONTR.” will be indicated and thepump will stop.

Press on the Technovar to change to

10.30.2 Delay Time

DELAY TIME2 Sec

Adjustable between 0...100 Sec.Delayed switch-off of the Technovar in case of low

water, (terminals X1/6-X1/7 opened) and also for the conveyor limit.

Press on the Technovar to change to

10.30.3 Automatic Error reset

ERROR – RESETOFF

The parameter can be set OFF (no automatic reset)or, if you want to have an automatic error reset for

5 times, a delay time of the automatic reset (0-250 sec.).e.g. ERROR-RESET = 5 secondsThe Inverter will reset the failure 5 times with a 5 second interval. After the 5th restart, the Technovar will shut down and an error message will appear on the screen.

The last five error signals are always stored in the memory Error 1 to 5 (main menu)

Press on the Technovar to change to

Page 63: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

63

10.30.4 Erase Error memory

CLEAR ERRORS0000

The error memory can be deleted by entering apassword. If you want to know that, please contactyour distributor!

To leave the submenu press the longer than 3 sec. to change to

S U B ME N UERRORS

Press on the Technovar to change to

10.31 Operating Hours

OPPERATING HOURS0000 h.

operating time of the control unit (Technovar-supply O.K.) Reset by simultaneously pressing the

buttons + until TIMER – RESET appears.

Press on the Technovar to change to

10.32 Display - Contrast

DISP. CONTRAST50 %

Can be adjusted between 10...100%. For improvedclarity of the display, depending on the installationposition.

Press on the Technovar to change to

10.33 Set Password

SET PASSWORD0066

The pre-set password can be changed if necessary.

Press on the Technovar to change to

10.34 Operating Lock

LOCK FUNCTIONOFF

When activated [ON], it is not able to make anychanges in the main menu. Only ON/OFF (start and

stop) with buttons and are possible.In order to change the desired set value, the lock function must be switched off [OFF], thatthe set pressure can be changed in the main menu.

Press on the Technovar to change to

10.35 Internal Heater

HEATINGON

Standstill heating in TECHNOVAR head!In order to prevent condensation in the control unit

Page 64: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

64

(depending on ambient conditions), a heating resistance (approx. 10 watt) is switched on,when the motor is at a standstill provided that HEATING ON was selected and the supply ofthe Technovar is O.K.

Press on the Technovar to change to

10.36 Setting Default Values

S U B M E N UDEFAULT VALUES

Press for about 3 seconds to enter thesubmenu and the display changes to

10.36.1 Default Values Europe

DEFAULT EUROPE +

Load the DEFAULT – PARAMETERS for Europe(e.g.: maximum frequency 50 Hz, display unit = bar)

Loading Parameter : Press buttons + for approx. 5 seconds.

Press on the Technovar to change to

10.36.2 Default Values USA

DEFAULT USA +

Load the DEFAULT – PARAMETER for the USA(e.g.: max. frequency 60 Hz, display unit = psi)

Loading Parameter : Press buttons + for approx. 5 seconds.

Attention After reloading the default settings the display is flashing, to deactivate theflashing press the until you reach the parameter “SAVE” (see next chapter)

To leave the submenu press the longer than 3 sec. and change to

S U B M E N UDEFAULT VALUES

Press on the Technovar to change to

10.37 Saving

SAVE ??? +

All values must be saved (stored in an EEPROM) afterchanging. If they are not saved, all changes will be

lost in case of a power failure! Saving: Press + till the message “SAVED” is shown on the display.

After saving, the display changes automatically to the 1st display after a few seconds.

Page 65: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

65

11 Error Signals

11.1 Low Water

LACK OF WATER :E R R O R

Remedy:Check suction pressure or tank level!

If suction pressure or tank level is normal the unit restarts itself. If there is no suctionpressure switch (e.g. circulating systems), bridge terminals X1/6 and X1/7.

11.2 Conveyor Control

VAL.RANGE CONTR.E R R O R

The set minimum pressure threshold formonitoring pump delivery (delivery

threshold) was not achieved within the set delay time.At error reset ON the system is only shut down after 5 attempts of starting. If the deliverythreshold is set at <0, this function is deactivated.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.

11.3 Overheating – Motor

MOTOR OVERHEATE R R O R

Possible causes: insufficient coolingAmbient temperature is too high, motor

overloaded. After the cause has been remedied, the malfunction can be reset by cutting offthe power supply for >30 seconds or pressing all three buttons ( , and ) together forabout 5 seconds.

11.4 Overheating – Inverter

INVERT. OVERHEADE R R O R

Possible causes: dirty dissipater or lack ofcooling air.

After the cause of the overheating has been remedied, the malfunction can be reset bycutting off the power supply for >30 seconds or pressing all three buttons ( , and )together for about 5 seconds.

11.5 Over voltage

OVERVOLTAGEE R R O R

Possible cause: Check mains supply, supplyvoltage too high, peak voltage owing to

switching heavy loads on the network, or RAMP 2 is to fast! Find the cause and takecountermeasures (e.g. network filter, RC-elements).After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and ) together for about 5seconds.

Page 66: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

66

11.6 Under voltage

ITT INDUSTRIESUNDERVOLTAGE

Possible cause: Check mains supply, faultyfuse or phase unsymmetry.

After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.

11.7 Limit

ITT INDUSTRIESOverloaded

Possible causes: false data settings or thepump is working at a capacity significantly in

excess of its performance data. If the limit signal remains, OVERLOADED will appear after afew seconds and the frequency converter will stop.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.

11.8 Short Circuit

OUTPUT SHORTE R R O R

This error means a too fast current peak atthe unit-output.

Possible reasons for this error!Connection cable between the control unit and the motor is damaged or the motor isdefective.Disconnect the system from the power supply and remedy the fault.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.

11.9 Overload

OVERLOADEDE R R O R

Possible cause: Pump is jammed!Foreign body in the pumps, mechanical seal

defective (stiff) or the pump was idle for a long period of time.Ramp 1 too fast:Maximum frequency too high:Boost too low:Defective non-return valve – Pump runs in reverse when switched off (OFF).De-energise and get the pump running again or if necessary call customer service.After the cause has been remedied, the malfunction can be reset by cutting off the powersupply for >30 seconds or pressing all three buttons ( , and. ) together for about 5seconds.

11.10 Pressure Sensor Error I < 4 mA

ACT. VALUE SENSORE R R O R

Possible cause: Defective pressuretransmitter or broken cable (damaged cable)

Page 67: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

67

Check the pressure transmitter!After the cause has been remedied, the malfunction can be reset by cutting off thepower supply for >30 seconds or pressing all three buttons ( , and. ) together forabout 5 seconds.

All error signals are given at terminal X2/1, X”/2 and X2/3 (changeover contact).If no Error is active, the relay switches on and terminals X2/2 and X2/3 are closed.

Attention If "AUTO - START ON" and "ERROR-RESET – ON" are programmed, the unitcan start again automatically after a power failure.

11.11 Additional Error signals:

ERROR 1 : EEPROM-ERROR (corresponding data block malfunction)

ERROR 2 : Security error / Software protection error

ERROR 4 : Buttonboard error (e.g.: jammed key)

ERROR 5 : EPROM-error

ERROR 6 : Program error: Watchdog error

ERROR 7 : Program error: Processor pulse error

ERROR 8 : Program error: invalid processor command

These ERROR signals can be reset by cutting off the power supply for >30 seconds orpressing all three buttons ( , and. ) together for about 5 seconds.If the error signal should appear again, contact customer service and provide a detaileddescription of the error.

12 RS 485 - Interface

Standardized Bus-Interface for communication between the inverters (Technovar Drive heads)and/or an overruling external control system.

The data protocol complies with ISO 1745 for RS 485 interfaces and contains the followingconfigurations:

Data rate : 9600 Baud (1 Startbit, 8 Data, 1 Stopbit)

An interface inverter RS 232/RS 485 is necessary in case communication with a V24 interface ofa PC or another external control system is wanted.

All parameters can be approached via the standard interface. The inline structure of theTechnovar Drive head can be obtained upon request.

1A fist1E Status word:

Page 68: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

68

BIT0...BIT7 Inverter faultBIT8 FreeBIT9 fist<than set starting pressureBIT10 Pump Stop/StartBIT11 Pump runsBIT12 lead/lag operation active (activ=1)

1F Control Word:

0000 Inverter stop0001 Inverter start0002 Parameter – Save

0100 Master overrules0200 Requirement reset0300 Master overrules and requirement reset

For further information see:

serial data transmission – RS485TECHNOVAR – Protocol 120

13 Auxiliary Texts

All auxiliary texts that are available in texts in the display window are listed here. To call themup press the buttons + ; each auxiliary text then appears as "running text" in the secondline of the window.

Window Text: Auxiliary Text:

ITT INDUSTRIESx.xx psi

No auxiliary text available! Pressing buttons and provides LANGUAGE SELECTION

REQUIRED VALUEx.xx psi

Input or displayed of the desired value

REQUIRED VALUE 2x.xx psi

Input or displayed of the desired value 2

AUTO – STARTOFF

ON -> Autostart enabled; OFF -> Autostart disabled

Page 69: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

69

ERROR 1..............

Last error

ERROR 2..............

4th recorded ERROR

ERROR 3..............

3rd recorded ERROR

ERROR 4..............

2nd recorded ERROR

ERROR 5..............

1st recorded ERROR

TOTAL RUN TIME0000:00

Total motor run time hh:mm

SAVE ??? +

Press [ + ] to save parameter values

PASSWORD0000

Enter Password

JOG - MODE0.0Hz xx.xx psi

JOG MODE: Frequency controlled by [ ] or [ ];(no control)

W I N D O W5%

Desired window width around the desired value(in % from the desired value)

RAMP HYSTERESIS80%

% of half desired window width related to hysteresis

RAMP 14.0 Sec

Ramp 1: acceleration time(actual value outside operating window)

RAMP 24.0 Sec

Ramp 2: deceleration time(actual value outside operating window)

RAMP 370 Sec

Ramp 3: acceleration time(actual value within window)

RAMP 470 Sec

Ramp 4: deceleration time(actual value within window)

Page 70: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

70

MAX. FREQUENCY60.0 Hz

Maximum output frequency(Range: 40...70Hz)

MIN. FREQUENCY0.0 Hz

Minimum output frequency(Range: 0... MAX. FREQUENCY)

CONFIG FMINf -> 0

Configuration behaviour at minimum frequency

STOP-DELAY-FMIN0 Sec

Delay for pump stop, when f -> 0 is chosen

BOOST5.0 %

Extra power at pump start

SENSOR_ADJUST?Out of range

Sensor zero adjustment press [ + ]

SENSOR-CURVELinear

Sensor characteristic curve

SENSOR RANGE20mA = 362,6 psi

Normalise to max. SENSOR VALUE

MODE::Controller

CONTROLLER -> Standard control;ACTUATOR -> Frequency set point as ADC – VALUE;

MULTICONTROLLER -> control of up to 4 pumpsSYNCH. CONTROLLER -> synchronous regulationMANUAL CONTROL -> frequency set point using keyboard

REGULATION MODENormal

Pumping regulation mode:NORMAL -> Regulation normal;INVERS -> Regulation inverse

START VALUEdisabled

Start value

CONFIG. 2nd REQ. VALUEOFF

Configuration of a second value

RELAY CONFIGURATIONRun Motor

Relay configuration

S U B M E N UOffset

SUBMENU Offset; to entry push [SELECT] for at least 1sec.

Page 71: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

71

OFFSET INPUTOFF

Selection of offset input

LEVEL 1XX.X %

Start level for offset 1

LEVEL 2XX.X %

Start level for offset 2

INTENSITY 1XX.X %

Intensity of offset 1

INTENSITY 2XX.X %

Intensity of offset 2

S U B M E N USeq. Control

SUBMENU Seq. Control; to entry push [ ] for at least1 sec.

ACTU. VALUE INC.5 psi

Actual value increase at switching of additional pump

ACTU. VALUE DEC.2,1 psi

Actual value decrease for consecutive pumps

ENABLE SEQ. CTL.58.0 Hz

Freq. Limit enable sequence control

SWITCH INTERVAL12 hours

Lead lay sequence changeover time

SOURCE REQ. VALUEOFF

Source of required value at active multicontroller

S U B M E N USynch. Control

SUBMENU Synchronous regulation; to entry push [ ]at least 1 sec..

SYNCHRON. LIMIT0,0 Hz

Frequency limit to enable the synchronous regulation

SYNCHRON-WINDOW2.0 Hz

Frequency window for the frequency limit whichactivates the synchronous regulation

PUMP – SEQUENCYAdr1 fault

Diagnostics: Pump sequence and status

Page 72: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

72

BUSARBIT-DIAG.0

Diagnostics: Bus arbitation (this pump)

S U B M E N URS 485-Interface

SUBMENU Serial Interface; to entry push [ ] at least 1 sec..

PUMP-ADDRESSOFF

SIO-Address of the pump

ADC REFERENCELocal

Actual value or frequency reference enabled by thelocal ADC or by SIO

FREQU. – LIFTING37 Hz

Frequency limit for desired value lift

LIFT – AMOUNT0.0 %

Lift amount in % of desired value point(at maximum frequency)

ANALOG – OUTActual value

Meter output: ACTUAL FREQUENCY(corresp. to max. output frequency);ACTUAL VALUE (corresp. to max. desired pressure)

DIMENSION UNITpsi

Displayed dimension unit

TEST RUNafter 100 h.

Time interval for test run(10...100h...deactivated [ + ])

S U B M E N UTEST RUN man.

SUBMENU Pump test run manual; to entry push [ ]at least 1 sec..

TEST RUN man +

Start test – run with [ + ]

TEST-FREQUENCY30.0 Hz

Test – run frequency

BOOST TEST-RUN10 %

Test – run boost

S U B ME N UERRORS

SUBMENU Errors: to entry push [ ] at least 1 sec.

CONVEYOR-LIMITDisabled

Conveyor limit: In case fall short of turn off

Page 73: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

73

DELAY TIME2 Sec

Delay for the error registration when the water islacking end for the conveyor control

ERROR – RESETOFF

Automatic Error Reset

CLEAR ERRORS0000

Clear error history

OPERATING HOURSxxxx h.

Total inverter operating time(Reset counters: press [ + ])

DISP. CONTRAST50 %

Display contrast

SET PASSWORD0066

Modify Password

LOCK FUNCTION OFF

ON -> Keypad locked;OFF -> changes are allowed

HEATINGOFF

Anti condensation heater

S U B M E N UDEFAULT VALUES

SUBMENU Load DEFAULT PARAMETERS; to entry push[ ] at least 1 sec.

DEFAULT EUROPE +

Load EUROPEAN DEFAULT PARAMETERS with [ + ]

DEFAULT USA +

Load USA DEFAULT PARAMETERS with [ + ]

SAVE ??? +

Press [ + ] to save parameter values

14 Maintenance

The TECHNOVAR control unit does not require special maintenance.However, the cooling fan and the vents should be free of dust occasionally.

14.1 NotesWhen replacing the control card in a plant with more than one pump ensure, that thesame control card version (V/STK/X) is used in all Technovar units.For further information, please ask your distributor!

Page 74: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

74

ITT

IND

UST

RIES

x.xx

psi

Requ

ired

Val

ue 1

126,

9 ps

iA

uto

- Sta

rtO

NEr

ror

1Er

ror

2Er

ror

3Er

ror

4Er

ror

5To

tal R

un T

ime

0000

: 00

Save

??

+�

Pass

wo

rd0

000

JOG

- M

ode

0.0

Hz

319

,5 p

siW

indo

w5

%Ra

mp

Hys

tere

sis

80 %

Ram

p 1

4.0

Sec

Ram

p 2

4.0

Sec

Ram

p 3

70 S

ecRa

mp

470

Sec

Max

. Fre

quen

cy60

.0 H

zM

in. F

requ

ency

0.0

Hz

Conf

ig. F

min

F ->

0St

op

- D

elay

Fm

in0

Sek

Boos

t5.

0 %

Sens

or A

djus

t ?

out

of

rang

eSe

nso

r -

Cur

veLi

near

Sens

or R

ange

20 m

A =

362

,6 p

siM

ode

Cont

rolle

rRe

gula

tion

Mod

eN

orm

alSt

art

Valu

ed

isab

led

Con

fig. R

eq. V

al. 2

OFF

Rela

y C

onfi

g.Ru

n M

oto

rSU

BMEN

UO

ffse

t

Off

set

- In

put

OFF

Leve

l 10.

0 %

Leve

l 20.

0 %

Inte

nsity

1+

0.0

%

Inte

nsity

2+

0.0

%

SUBM

ENU

Seq

. Con

tro

l

Act

u. V

alue

Inc.

5 ps

i

Act

u. V

alue

Dec

.2,

1psi

Enab

le S

eq.

CTL.

58.

0 H

z

Switc

h In

terv

al12

hou

rs

Sour

ce R

eq. V

alu

eO

FF

SUBM

ENU

Sync

h. C

ontr

olSy

nch

ron.

Lim

it0.

0 H

z

Sync

hron

- W

indo

w2

.0 H

zPu

mp

- Seq

uen

ceA

dr

1

f

ault

Busa

rbit

- D

iag.

0

SUBM

ENU

RS4

85 -

Inte

rfac

e

Pum

p - A

ddre

ssO

FF

AD

C R

efer

ence

Loca

l

Lift

- A

mou

nt0

.0 %

Ana

log

- O

ut

Act

ual V

alue

Dim

ensi

on

Uni

tps

iTe

st R

un

afte

r 10

0 h

.

SUBM

ENU

Test

Run

Test

Run

man

.�

�+

Test

- F

req

uenc

y30

.0 H

z

Boos

t Te

st -

Run

10.0

%

SUBM

ENU

Erro

rs

Conv

eyor

- Li

mit

disa

bled

Del

ay T

ime

2 Se

c

Erro

r -

Rese

tdi

sabl

ed

Cle

ar E

rro

rs00

00

Ope

rati

ng H

our

s00

00 h

.D

isp.

- C

ontr

ast

50 %

Set

Pass

wo

rd00

66

Hea

ting

ON

Def

ault

Eu

rope

+�

Def

ault

USA

+�

SUB

MEN

UD

efau

lt Va

lues

Save

??

+�

Lock

Fun

ctio

nO

FF

Star

t

Freq

u. -

Lift

ing

37.0

Hz

Page 75: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

75

ALABAMAMangham & Associates, Inc.Irondale (Birmingham)Phone: 205/956-2362FAX: 205/956-2477ALASKAColumbia Hydronics Co.Seattle, WAPhone: 206/988-6993FAX: 206/988-3938ARIZONAJ & B Sales CompanyPhoenixPhone: 602/258-1545FAX: 602/258-9719ARKANSASJohnson & Scott, Inc.Little RockPhone: 501/803-9520FAX: 501/803-9521Hydronic Technology Inc.Shreveport, LAPhone: 318/797-1500FAX: 318/797-1509Boone & Boone Sales Co., Inc.Tulsa, OKPhone: 918/664-9756FAX: 918/664-1675CALIFORNIACalifornia Hydronics Corp.Hayward (San Francisco)Phone: 510/293-1993FAX: 510/293-3080Rocklin (Sacramento)Phone: 510/293-1993FAX: 916/632-4765San JosePhone: 408/295-5874FAX: 408/297-8596Dawson Co.Altadena (Los Angeles)Phone: 626/797-9710FAX: 626/798-4659San DiegoPhone: 858/541-7867FAX: 858/541-0333COLORADOMcNevin CompanyDenverPhone: 303/322-0165FAX: 303/322-0374CONNECTICUTThe Bernard M. Packtor Co.Hamden (New Haven)Phone: 203/288-5241FAX: 203/287-1798

DELAWARER. D. Bitzer Co., Inc.Bensalem, PAPhone: 215/604-6600FAX: 215/604-6601Cummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156FLORIDAGeorge A. Israel Jr., Inc.JacksonvillePhone: 904/355-7867FAX: 904/355-0077MiamiPhone: 305/592-5343FAX: 305/591-4356OrlandoPhone: 407/423-5078FAX: 407/423-0918TallahasseePhone: 850/656-2055FAX: 850/656-1475TampaPhone: 813/839-2161FAX: 813/832-3182GEORGIAClary & Associates, Inc.AtlantaPhone: 404/873-1861FAX: 404/873-1867

George A. Israel Jr., Inc.Jacksonville, FLPhone: 904/355-7867FAX: 904/355-0077Tallahassee, FLPhone: 850/656-2055FAX: 850/656-1475HAWAIIDawson Co.Altadena (Los Angeles) CAPhone: 626/797-9710FAX: 626/798-4659IDAHOGritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364Columbia Hydronics Co.Vancouver, WAPhone:360/883-2600FAX: 360/883-2607

ILLINOISBornquist, Inc.ChicagoPhone: 773/774-2800FAX: 773/763-6534Blackmore & Glunt, Inc.Maryland Hghts. (St. Louis) MOPhone: 314/878-4313FAX: 314/878-6029Sandberg Co., Inc.East MolinePhone: 309/796-2371FAX: 309/796-2330Hydronic & Steam Equip. Co., Inc.Indianapolis, INPhone: 800/669-4926317/577-8326FAX: 317/577-7109INDIANAHydronic & Steam Equip. Co., Inc.IndianapolisPhone: 800/669-4926Phone: 317/577-8326FAX: 317/577-7109EvansvillePhone: 800/473-2753Phone: 812/473-0330FAX: 812/479-7650Ft. WaynePhone: 260/489-5785FAX: 260/489-4369South BendPhone: 800/932-6490Phone: 574/234-6005FAX: 574/234-6611Sandberg Co., Inc.East Moline, ILPhone: 309/796-2371FAX: 309/796-2330Blackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755IOWAProducts, Inc.Des MoinesPhone: 515/288-5738FAX: 515/288-2574Sandberg Co., Inc.East Moline, ILPhone: 309/796-2371FAX: 309/796-2330Verne Simmonds Co.Omaha, NEPhone: 402/592-3131FAX: 402/592-0853

Page 76: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

76

KANSASBlackmore & Glunt, Inc.Lenexa (Kansas City)Phone: 913/469-5715FAX: 913/469-1085KENTUCKYBlackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755

Hydronic & Steam Equip. Co.,Inc.Evansville, INPhone: 800/473-2753812/473-0330FAX: 812/479-7650Johnson & Scott, Inc.Nashville, TNPhone: 615/254-5454FAX: 615/242-9243LOUISIANAHydronic Technology Inc.New OrleansPhone: 800/365-6746Phone: 504/827-1163FAX: 504/827-1167ShreveportPhone: 800/673-5737Phone: 318/797-1500FAX: 318/797-1509MAINEF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965MARYLANDCummins-Wagner Co., Inc.Annapolis JunctionPhone: 800/966-1277Phone: 301/490-9007FAX: 301/490-7156Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842MASSACHUSETTSF.I.A., Inc.Woburn (Boston)Phone: 781/938-8900FAX: 781/933-3965The Bernard M. Packtor Co.Hamden (New Haven) CTPhone: 203/288-5241FAX: 203/287-1798Albany, NYPhone: 518/459-1060FAX: 518/458-8776

MICHIGANR. L. Deppmann Co.Southfield (Detroit)Phone: 248/354-3710FAX: 248/354-3763Grand RapidsPhone: 616/656-0821FAX: 616/656-0830BridgeportPhone: 989/652-3049FAX: 989/652-3324Hydro-Flo Products, Inc.Brookfield (Milwaukee) WIPhone: 262/781-2810FAX: 262/781-2228MINNESOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588MISSISSIPPIHydronic Technology Inc.New Orleans, LAPhone: 800/365-6746Phone: 504/827-1163FAX: 504/827-1167Johnson & Scott, Inc.Little Rock, ARPhone: 501/803-9520FAX: 501/803-9521MISSOURIBlackmore & Glunt, Inc.Lenexa (Kansas City) KSPhone: 913/469-5715FAX: 913/469-1085Maryland Hgts. (St. Louis)Phone: 314/878-4313FAX: 314/878-6029MONTANAColumbia Hydronics Co.SpokanePhone: 509/242-1118FAX: 509/242-1120NEBRASKAVerne Simmonds Co.OmahaPhone: 402/592-3131FAX: 402/592-0853NEVADADawson Co.Las Vegas, NVPhone: 702/735-1226FAX: 702/735-1232Gritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364

NEW HAMPSHIREF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965NEW JERSEYWallace-Eannace Assoc., Inc.Franklin LakesPhone: 201/891-9550FAX: 201/891-4298R. D. Bitzer Co., Inc.Bensalem, PAPhone: 215/604-6600FAX: 215/604-6601NEW MEXICOBoyd Engineering Co., Inc.AlbuquerquePhone: 505/275-1250FAX: 505/275-1193NEW YORKWallace-Eannace Assoc., Inc.PlainviewPhone: 516/454-9300FAX: 516/454-9307Frank P. Langley Co., Inc.E. RochesterPhone: 585/248-5010FAX: 585/381-0512Amherst (Buffalo)Phone: 716/691-7575FAX: 716/691-7347Johnson CityPhone: 607/766-9950FAX: 607/766-9948The Bernard M. Packtor Co.AlbanyPhone: 518/459-1060FAX: 518/458-8776Syracuse Thermal Products,Inc.East SyracusePhone: 315/437-7321FAX: 315/437-7429NORTH CAROLINAJames M. Pleasants Co., Inc.GreensboroPhone: 800/365-9010Phone: 336/378-9911FAX: 336/378-2588CharlottePhone: 704/545-0145FAX: 704/545-2917RaleighPhone: 919/845-1960FAX: 919/845-1925WilmingtonPhone: 910/794-5447FAX: 910/794-5449

Page 77: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

77

NORTH DAKOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588OHIOBlackmore & Glunt, Inc.CincinnatiPhone: 513/489-5225FAX: 513/489-8755R. L. Deppmann Co.Macedonia (Cleveland)Phone: 330/468-1102FAX: 330/468-1113Steffens-Shultz, Inc.ColumbusPhone: 614/274-5515FAX: 614/274-0126DaytonPhone: 937/278-7903FAX: 937/278-7825OHIO (Cont’d.)Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842OKLAHOMABoone & Boone Sales Co., Inc.Oklahoma CityPhone: 405/525-7475FAX: 405/521-1448TulsaPhone: 918/664-9756FAX: 918/664-1675OREGONColumbia Hydronics Co.Vancouver, WAPhone:360/883-2600FAX: 360/883-2607PENNSYLVANIAR. D. Bitzer Co., Inc.BensalemPhone: 215/604-6600FAX: 215/604-6601Thermoflo Equipment Co., Inc.PittsburghPhone: 412/366-2012FAX: 412/367-0842Frank P. Langley Co., Inc.Amherst (Buffalo) NYPhone: 716/691-7575FAX: 716/691-7347RHODE ISLANDF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965

SOUTH CAROLINAJames M. Pleasants Co., Inc.Greensboro, NCPhone: 800/365-9010Phone: 336/378-9911FAX: 336/378-2588ColumbiaPhone: 803/798-1405FAX: 803/798-1323GreenvillePhone: 864/232-0200FAX: 864/232-0025SOUTH DAKOTABernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588Verne Simmonds Co.Omaha, NEPhone: 402/592-3131FAX: 402/592-0853TENNESSEEJohnson & Scott, Inc.NashvillePhone: 615/254-5454FAX: 615/242-9243Cordova (Memphis)Phone: 901/388-2919FAX: 901/388-0989Clary & Associates, Inc.Atlanta, GAPhone: 404/873-1861FAX: 404/873-1867James M. Pleasants Co., Inc.Greensboro, NCPhone: 800/365-9010336/378-9911FAX: 336/378-2588KnoxvillePhone: 865/584-5054FAX: 865/584-8385TEXASBoyd Engineering Co., Inc.Albuquerque, NMPhone: 505/275-1250FAX: 505/275-1193Oslin Nation CompanyDallasPhone: 214/631-5650FAX: 972/988-1446Ft. WorthPhone: 817/590-2500FAX: 817/590-2508

TEXAS (Cont’d.)Oslin Nation Company (Cont’d)HoustonPhone: 713/699-3500FAX: 713/699-8213San AntonioPhone: 800/243-7756Phone: 210/342-5544FAX: 210/342-2818UTAHGritton & Associates, Inc.Salt Lake CityPhone: 801/486-0767FAX: 801/485-6364VERMONTF.I.A., Inc.Woburn (Boston) MAPhone: 781/938-8900FAX: 781/933-3965The Bernard M. Packtor Co.Albany, NYPhone: 518/459-1060FAX: 518/458-8776VIRGINIATLA, Inc.RichmondPhone: 804/321-4444FAX: 804/321-3112Virginia BeachPhone: 757/497-3567FAX: 757/490-7362Cummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156WASHINGTONColumbia Hydronics Co.SeattlePhone: 206/988-6993FAX: 206/988-3938SpokanePhone: 509/242-1118FAX: 509/242-1120VancouverPhone:360/883-2600FAX: 360/883-2607WASHINGTON, DCCummins-Wagner Co., Inc.Annapolis Junction, MDPhone: 800/966-1277301/490-9007FAX: 301/490-7156

Page 78: VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED …€¦ · Air pollution: The air may contain dry dust as found in workshops where there is no excessive quantity of dust due to machines

Operating Instruction

78

WEST VIRGINIABlackmore & Glunt, Inc.Cincinnati, OHPhone: 513/489-5225FAX: 513/489-8755TLA, Inc.Richmond, VAPhone: 804/321-4444FAX: 804/321-3112Thermoflo Equipment Co., Inc.Pittsburgh, PAPhone: 412/366-2012FAX: 412/367-0842WISCONSINHydro-Flo Products, Inc.Brookfield (Milwaukee)Phone: 262/781-2810FAX: 262/781-2228Bernard J. Mulcahy Co., Inc.Eagan, MNPhone: 651/686-8580FAX: 651/686-8588WYOMINGGritton & Associates, Inc.Salt Lake City, UTPhone: 801/486-0767FAX: 801/485-6364J. E. McNevin Co.Denver, COPhone: 303/322-0165FAX: 303/322-0374