    1/66

    1

    CATALOGChapter1Introduction............................................................................................................................ 3

    1.1BriefIntroductionofPerformanceFeatures............................................................................. 3

    1.2SystemStructure....................................................................................................................... 3

    1.3OperatingMode ........................................................................................................................ 4

    1.4FunctionsandCharacteristics ................................................................................................... 6

    Chapter2InstallationInstruction ........................................................................................................... 8

    2.1UnloadingandUnpacking ......................................................................................................... 8

    2.2SiteSelection........................................................................................................................... 12

    2.3InstallationofUPS ................................................................................................................... 12

    2.4CableSelectionandConnection ............................................................................................. 13

    2.5BatteryConnection ................................................................................................................. 15

    Chapter3Operation ............................................................................................................................. 18

    3.1IntroductionofOperationInterface ....................................................................................... 18

    3.2

    Operation

    for

    Power

    on

    of

    Single

    Machine............................................................................. 193.3OperationforPoweroff.......................................................................................................... 27

    3.4OperationforEmergencyPoweroff....................................................................................... 28

    3.5OperationforMaintenanceBypass ........................................................................................ 28

    3.6EnquiryOperation ................................................................................................................... 29

    3.7OperationsforUserConfiguration.......................................................................................... 37

    Chapter4InstallationandOperationofParalleledMachine ............................................................... 49

    4.1InstallationofParalleledSystem............................................................................................. 49

    4.2On/OffofParalleledMachines................................................................................................ 50

    4.3EnquireOperationofParalleledSystem ................................................................................. 51

    Chapter5:UPSRepairingandMaintenance......................................................................................... 53

    5.1UPSRepairingandMaintenance............................................................................................. 53

    5.2Troubleshooting ...................................................................................................................... 545.3MaintenanceAssurance.......................................................................................................... 58

    5.4TechnicalSpecifications .......................................................................................................... 58

    Appendix1:LampSignalReferenceList ............................................................................................... 61

    Appendix2:PortofCommunicationInterface ..................................................................................... 63

    Appendix3:DialSwitchSetofModuleandCharger ............................................................................ 65

  • 8/13/2019 Usermanual-11295075930

    2/66

    2

    PREFACE

    Thankyouforusingourproducts.

    Our company is engaged in developing andmanufacturingproductsof uninterruptedpower

    system which is a kind of power product with high quality and can meet various performance

    requirements.

    Note:Thismanualcontains instructionofmounting,application,andoperationofUPS. Itshall read

    thismanualcarefullybeforemounting thesystemand it isnotallowed to takeanyoperationson

    UPSbefore finishing readingall safety instructionandoperation instruction.Thismanualcontains

    significant information,pleaseobey allwarningsandoperation instructions statedby themanual

    andmachine,andthemanualshallbekeptwell.

    SafetyTheuninterruptedpowersystemmustbegroundedbeforeoperation.

    Battery shall be replaced by qualified maintenance personal. The battery is toxic waste

    according to laws, so wasted battery shall be recovered by its classification in accordance with

    requirementofenvironmentalprotection.

    WarningSellingof thisproduct isonly forpartnerwhohasgeneral informationonUPSproducts. It is

    necessarytoknowsomeothermountingrequirementsormeasurestopreventaccident.

    Anycontentof themanualshallnotbemodifiedwithoutallowanceofmanufacturerandanyoffendersmustbeinvestigated.Ourcompanyreservestherightoffinalinterpretation.

  • 8/13/2019 Usermanual-11295075930

    3/66

    3

    Chapter1Introduction

    1.1Brief

    Introduction

    of

    Performance

    Features

    900II1060KVA(3/3)seriesisakindofhighfrequencyUPSwiththreeinletandthreeoutlet

    designedbyfulldigitalcontroltechnology.Thedesignofunitbreaksconventionaldesignthoughtof

    towertypemachine,replacedbyadvancedmodulardesignideawhichcanensurecompactnessof

    layoutandimprovereliabilityoftheunit.Electricalperformanceof900II1060KVA(3/3)seriesis

    advantageousandprotectionofsoftwareandhardwareofitisperfect.Itisapplicablefordifferent

    powergridandcansupplysafeandreliablepowerfordifferentloads.

    1.2SystemStructure

    Componentsofthesystemmainlyinclude:LCDdisplayscreen,communicationport,power

    module,charger,battery(optional),inputbreaker,outputbreaker,maintenancebypassbreaker,

    groundrow,Nrow,andsoon.Itssystemstructurechartisshowninfigure1.1andfigure1.2.

    Figure1.1Structureof900II1030KVAseries

  • 8/13/2019 Usermanual-11295075930

    4/66

    4

    Figure1.2Structureof900II4060KVAseries

    1.3OperatingMode

    900II1060KVAisakindofonlinedoubleconversionUPS,itsoperatingmodesareasfollows:

    Mainpowersupplymode Batterymode Bypassmode Maintenancemode(manualbypass) Frequencyconvertermode1.3.1Mainpowermode

    TheworkingmodethatalternatingcurrentpowerofrectifiercircuitforUPSissuppliedbymain

    power, direct current power for inverter is supplied after corrected by PFC power factor, and

    continuousanduninterruptedalternating currentpower for load isprovidedby inverter circuit is

    calledmainpowermode.Thechargerwillstartautomaticallyafterpoweronof invertertosupply

    powerforbattery.

  • 8/13/2019 Usermanual-11295075930

    5/66

    5

    AC/DCrectification

    Charger

    DC/DCboost

    BATTERY

    + -

    DC/ACinverter OutputMain powerinput

    Maintenancebypass

    Bypass

    Figure1.3WorkingProcessChartunderMainPowerMode

    1.3.2Batterymode

    Theworkingmode that battery power is boosted through battery booster circuit, and then

    suppliedtoloadthroughinvertercircuitiscalledbatterymode.Whenmainpowerfaultoccurs,the

    systemwillswitchtobatterymodeautomaticallyandpowersupplyforloadisnotinterrupted.When

    main power recoveries, the system will switch to main power mode automatically without any

    manualoperationandpowersupplyforloadisnotinterrupted.Switchingtimeofmainpowermode

    andbatterymodeis0ms.

    AC/DCrectification

    Charger

    DC/DCboost

    BATTERY

    + -

    DC/ACinverter Output

    bypass

    Maintenancebypass

    Mainpoweinput

    Figure1.4WorkingProcessChartunderBatteryMode

    1.3.3Bypassmode

    Iffaultsuchasinvertercircuitfaultandinvertercircuitoverload,orswitchingtobypassmode

    byhandoccurs,theUPSwillswitchtheloadfromsideofinvertertosideofbypassandpowersupply

    fortheloadisnotinterrupted.

  • 8/13/2019 Usermanual-11295075930

    6/66

    6

    AC/DCrectification

    Charger

    DC/DCboost

    BATTERY

    + -

    DC/ACinverter OutputMainpowerinput

    Maintenancebypass

    Bypass

    Figure1.5WorkingProcessChartunderBypassMode

    1.3.4Maintenancemode(manualbypass)

    IfitneedstomaintainorrepairtheUPS,itcanclosethemanualbypassswitchtoswitchtheUPS

    tothesideofmaintenancebypassandthepowersupplyforloadisnotinterrupted.Inthatcase,the

    mainpowerwillnotpasstheinternalcomponentsofmachinebutconnecttheinputterminaland

    outputterminaldirectlysothatwecanmaintainorrepairtheUPS.

    Figure1.6WorkingProcessChartunderMaintenanceBypassMode

    1.3.5Frequencyconvertermode

    UPScanbesettofrequencyconvertermodewhichcanprovidestableoutputfrequencyof50Hz

    or60Hz.Inputfrequencyrangeofmainpoweris40Hz 70Hz.UPSwilloutputthesetoutput

    frequencyandthebypassmodeisineffectiveunderfrequencytransformermode.Whenmainpower

    isabnormal,thesystemwillswitchtobatterymodeautomaticallyandstilloutputwiththeset

    outputfrequency.

    1.4FunctionsandCharacteristics

    DSPfulldigitalcontroltechnology; Pureonlinedoubleconversionframework,strongloadcapability; Input power factor is as high as more than 0.99, low harmonic current, environmental

    protection,highefficient,andenergysaving;

    Wide inputvoltagerange,50/60Hzpowersystemselfadoptionsuitableforallgridunderanycircumstance;

    Supportfrequencymodesof50Hzinput/60Hzoutputand60Hzinput/50Hzoutputwhich

  • 8/13/2019 Usermanual-11295075930

    7/66

    7

    canmeetspecialrequirementsofuser;

    AdvancedN+Xwirelessparallelconnectionredundanttechnique,highparallelreliabilityandsmallcirculation;

    Parallelmachinessharethebatterygroupwhichcansavecellinvestmentfromuser; Digitalchargerwithflexiblechargingparametersetandbatterypiecesselection; Advancedbatteryintelligentmanagementtechnologywhichcanprolongworkinglifeofbattery

    effectively;

    Supportcoldstartofbatteryandautomaticstartofnormalpowerwhichcanmeetusersapplicationrequirements;

    Easilydamagedcomponentsarecompletelyisolatedwithairfluewhichcanimprovereliabilityofthesystemeffectively;

    Easilydamagedcomponentscanbechangedinmodulelevel,fieldreplacementisfastandconvenientandmodulecostislow;

    Perfecthardwareandsoftwareprotectionfunction(breaker,Fuse,hardwareprotection,andsoftwareprotection),superselfdiagnosis,andrichhistoricrecordenquiry;

    5.7inchLCDtouchwidescreendisplay,friendlyhumanmachineinterface; Manycommunicationports,includingRS232,RS485,USB,drycontactcardandSNMPsmart

    cardtrough.

  • 8/13/2019 Usermanual-11295075930

    8/66

    8

    Chapter2Installation

    Instruction

    2.1UnloadingandUnpacking

    Usershallcheckthepackagetoconfirmitisundamagedafterreceivingtheproduct;thenopen

    thepackagetocheckwhethertheequipmentisundamaged,andpleasecontactthecarrieratonceif

    itisdamaged.

    2.1.1Openofcabinetpackage

    1)Putthepackingboxvertically;

    Figure2.1PackingBoxPlacement

    2)Openthetopplateofpackingboxandthentakeoutthefoam;

  • 8/13/2019 Usermanual-11295075930

    9/66

    9

    Figure2.2UnsealthePackingBox

    3)Unsealsideplatesofpackingboxandthentakeoutthefoams.

  • 8/13/2019 Usermanual-11295075930

    10/66

    10

    Figure2.3UnsealedCabinet

    Tips:Itshallbecarefulwhenunsealingtopreventscratchforthemachinebody.

    Checkwhetherthequalifiedcertificate,instructionbook,CDdisk,andkeysforfrontandback

    doorsarecompleteornotafteropeningthepackingbox.

    3.1.2Openofmodulepacking

    1)Placethepackingboxinstable;

  • 8/13/2019 Usermanual-11295075930

    11/66

    11

    Figure2.4OuterPackingofModule

    2)Cutofftheplasticbelts,removethescotchtape,andthenopenthepaperbox;

    paperbox Foampacking

    Figure2.5ModuleUnpacking

    3)Removecoveroffoampacking,theequipmentwithplasticpackingwillappear;

    Coveroffoampacking

    Paperbox

    Equipment

    Foampacking

    Figure2.6TakingoutofModule

  • 8/13/2019 Usermanual-11295075930

    12/66

    12

    4)Finally,takeouttheequipmentwithplasticpacking,andthenremovetheplasticpacking.

    Tips:appendixesalongwithcabinetandmodulesshallbekeptwell,especialthatthemanual

    andCD

    disk

    contain

    much

    important

    safety

    instruction,

    please

    do

    not

    operate

    the

    equipment

    beforereadingthewholesafeoperationinstruction.Allwarningsandoperationsshownby

    machineandmanualshallbeobeyedstrictly.

    2.2SiteSelection

    Placedlocationmustbestable; EnoughventilationspacemustbeleftbetweenallsurfacesofUPSandwalls; Befarawayfromhotsourceandcorrosivematerials,avoidthesunshine; Keep normal working temperature and elevation height (working temperature: 0

    40,itneedstobeappliedbyderatingifelevationheightexceeds1500m); Keep clean working environment, avoid environment with moisture, flammable gas,

    flammableliquid,orcorrosivematerial;

    Weightcapabilityoffloortomachineandbatterygroupshallbeconsideredbeforemounting.

    2.3InstallationofUPS

    1.PutUPSmachineinspecificlocation.

    LocationofplacingtheUPSshallbeproperinordertoensuresafetyapplicationofUPS.Itshall

    beplacedinplacewithcleanenvironmentwithoutmoisture,flammablegas,flammableliquidor

    corrosivematerialandsunshine.Usercanputitonassignedlocationwithassistantofhumanforce

    orequipmentandshallpayattentiontospacesbetweenUPSandsurroundingthingswhenmounting

    sothatitishelpfulforventilationandheatdissipation.Minimumspaceisshowninfigure2.7(unit:

    mm):

    Figure2.7CabinetPlacementChart

  • 8/13/2019 Usermanual-11295075930

    13/66

    13

    2.InsertthepowermoduleintoUPSinlocationshowninFigure1.1andthenfixthemodule

    withHuangguanscrew.

    Tips:

    1.Moduleissoheavythatitneedsmorethan2personstoputitintothecabinet.

    2.Itshallbeslowwheninsertingthemoduleuntilitisinsertedfully.

    2.4CableSelectionandConnection

    2.4.1Selectionofcable

    Whenselectingconnectingcableforthesystem,itissuggestedtoselectthewirediameterof

    cableaccordingtomaximumpowerconfigurationof900II1060KVAsystemandcomplyinglocal

    connectionrulesandenvironmentalcondition(temperatureandphysicalsupportmedia).Thecable

    shallbeselected

    according

    tomaximum

    steady

    state

    alternating

    and

    direct

    currents

    of900II

    10

    60KVA,anditsselectionconditionsarelistedintable2.1:

    Table2.1CableConfigurationTable

    Rated380Vinput

    UPSratedpower

    Inputcurrentwhenitis

    fullloadandcharger

    outputsmaximumpower

    Output

    currentwhen

    itisfullload

    Discharging

    currentof32

    pieces

    batteries

    10KVA 24A 15A 28A

    15KVA 31A 23A 41A

    20KVA 39A 30A 55A

    30KVA 53A 46A 83A40KVA 78A 61A 110A

    60KVA 107A 91A 165A

    2.4.2Connectionofcable

    Batteryinput(longtermmachine),mainpowerinput,bypassandoutputcableshallbe

    connectedwithUPSaccordingtothepathsshowninFigure2.8.

    Chart for System Base

    BatteryinletwiringchannelMainpowerinputinletwiringchannelBypasswiringinletchannelOutput

    inlet

    wiring

    channel

    Figure2.8InletandOutletWiringChannelof900II1060K

  • 8/13/2019 Usermanual-11295075930

    14/66

    14

    Connectionofcableis:

    1.Openthedistributionboardtoexposethecopperrows.

    Figure2.9FrontViewofCabinet

    2.Phasesshowninfollowingfigurearelinebanksofmainpowerinput,bypassinput,battery

    inputandoutputcableafterpassingtheinletandoutletwiringchannels.

    Figure2.10DistributionWiringDiagramof900II1030KVAseries

  • 8/13/2019 Usermanual-11295075930

    15/66

    15

    Figure2.11DistributionWiringDiagramof900II4060KVAseries

    Tip:pleasetightentheinputandoutputcablesandwiringrow.

    3.Recoverthedistributionpanel

    2.5Battery

    Connection

    2.5.1Batteryconnectionoflongtermmachine

    Batterygroupforthismachineispositiveandnegativebatterygroupframework,totalnumber

    ofbatterycanbeselectedfrom32to40(evennumber),andquantitiesofpositiveandnegative

    batteriesshallbethesame.

    Batteryconnectionchartisshowninfigure2.12:

    Figure2.12BatteryConnectionChart

  • 8/13/2019 Usermanual-11295075930

    16/66

    16

    Asshowninfigure2.12,connectallbatteriesinseries,andleadaNlinefrommiddleconnection

    pointofbatterygroups,soitshallbethreelinestogetherwithpositiveandnegativeendsofbattery

    grouptoconnectwithbatteryconnectingterminalsofUPS.Batteriesbetweenpositiveendof

    batterygroupandNlinearecalledpositivebatteries,andbatteriesbetweennegativeendofbatterygroupandNlinearecallednegativebatteries.Usercanselectthecapabilityandnumberofbattery

    accordingtoitsdemand.ItmustaddanalternatingcurrentbreakerbetweenbatterygroupandUPS

    toplayaroleofcurrentlimitingprotectionandopenandclosethebatterygroupwhenmaintaining.

    2.5.2Installationandmaintenanceofbatteryforstandardmachine

    1.Installationofbatterypack:

    1)Openthebatterypackpanelinfrontofcabinettoexposethebatterypack.

    Figure2.13BatteryPack

    Note:itneedstoturnonthechargersolelybeforeinstallingthebatteryforthefirsttimetoinspect

    whethertheoutputvoltageofchargerisnormal.

    2)Removethesetscrewsofbatterypackandextractthebatterypack.

    3)PutbatteriesintobatterypackasshowninFigure2.14(batterypositiveandnegative

    terminalsmustbelocatedontherightsideofthebatterypackwheninstallingthebatteries).

    +-+-+-+-+-+-+-+-

    Figure2.14RightViewofBatteryPack

    4)Putthebatterypackwithbatteriestocorrespondinglocationandlockthesetscrews.

  • 8/13/2019 Usermanual-11295075930

    17/66

    17

    5)Measurewhetherthevoltageofeverybatterypackisnormal,thenmeasurewhetherthe

    sideleadterminalisshortcircuit,ifallofthemisnormal,connectthebatterypackwithUPS

    accordingtotheconnectingmethodshowninfollowingfigure2.15

    Figure2.15ConnectingDiagramofBatteryPack

    6)Recoverthebatterypackpanel.

    Maintenanceofbatterypack:

    1) SwitchtheUPStomaintenancebypassmode.

    2) Removethebatterypackpaneltoexposethebatterypack.

    3) Cutofftheconnectinglineofbatterypack(asshowninFigure2.15).

    4) Takeawaythesetscrewofbatterypackandthentakeawaythebatterypack.

    5) Replacethebatteryaccordingtothedemand.

    6) Recoverthebatterypack.

    Thefollowingsafetynotesshallbenotedallthetimewhenmountingandmaintainingthe

    batteries:

    1).Electricshockmayoccurwhenmountingthebatteries,highshortcircuitcurrentmaycause

    fire;

    2).Voltage of battery groups can be 480Vdcwhichmay cause death, so please obey safety

    attentionsforvoltageoperation;

    3).Only

    qualified

    personal

    can

    mount

    and

    maintain

    the

    batteries;

    4).Wearprotectiveeyeweartopreventaccidentcausedbyelectricarc;

    5).Takeoffring,watch,necklace,bracelet,andotheraglets;

    6).Usetoolswithinsulatedhands;

    7).ItshallbreakdownthebreakerofbatterywhenconnectinglinesbetweenUPSandbattery.

    It must ensure that the sequence and polarity of connection are correct after finished

    connection;

    8).Pleasecontactcustomerservicedepartmentofourcompanyiftheuserneedstochangethe

    numberofusedbatteriesduringnormalapplication.Pleasedonotoperateitsolely.

  • 8/13/2019 Usermanual-11295075930

    18/66

    18

    Chapter3Operation

    ThischapterdescribesallenquiriesandsettingoperationsofUPStakenbyoperator,including

    startingofUPS,poweroffofUPS,allenquiryoperations,andparametersetting,etc.

    Tips:instructionmanualmustbereadcarefullybeforeimplementingthefollowingoperations

    toavoidpersonalinjuryorequipmentdamagecausedbymisoperation.

    3.1IntroductionofOperationInterface

    AsshowninFigure3.1,operationinterfacemainlycontains:LEDindicatorlight,5.7inch

    multifunctionalLCDtouchwidescreenandoperationbutton.

    FAULT

    BYPSS

    BATTERY

    NOMAL

    EPO

    TAB

    UP

    DOWN

    ENTER

    CANCEL

    COLD START

    IndicatorlightOperationbutton

    ColdstartLCDwidescreen

    Figure3.1MonitoringInterface

    DefinitionsoficonsonpanelsilkscreenandLCDscreenarelistedintable3.1:

    Table3.1Silkscreen/IconIllustration

    Monitoringpanel Icon/Silkscreen Meaning

    FAULT Warn

    BYPASS Powersuppliedbybypass

    BATTERY Powersupplierbybattery

    LEDindicatorlight

    NOMAL Powersuppliedbymainpower

    Setting

    Charger

    Battery

    On/Off

    Inputparameter

    Outputparameter

    Returntomaininterface

    Returntopreviousmenu

  • 8/13/2019 Usermanual-11295075930

    19/66

    19

    Pagedown

    Pageup

    History

    Selftestandmuteoff

    IconsonLCD

    touchscreen

    Recordenquiry

    TAB Switchoftouch/buttoncontrol

    UP Cursorup

    DOWN Cursordown

    ENTER Confirm

    CANCEL Return to touchcontrol from button

    control

    COLDSTART Coldstart

    Operationbuttons

    EPO Emergencypoweroff

    LCDscreensupportstwokindsofcontrolmodes,buttoncontrolandtouchcontrol.

    1.Buttoncontrol

    PressbuttonofTABunderanyinterfacetoswitchtobuttoncontrolmode,theselectedicon

    isdisplayedinreverse,movethecursorbypressingbuttonofUPorDOWN,pressENTERto

    selecttheiconwherecursorlocatesat,andpressCANCELtoreturntotouchscreencontrolmode.

    2.Touchcontrol

    TakeoperationsbyclickingcorrespondingiconsonLCDscreen.

    3.2OperationforPoweronofSingleMachine

    Note:

    Itshallcheckwhetherallscrewsarefastenedandallconnectionsarecorrectornotbefore

    startingthemachine.Input,output,andbatterybreakersshallbeinoffstate.

    Forlongtermmachine,itshallsetthechargerparameterss(inChapter3.7.9)beforestarting,

    andbatterypiecesandgroupsshallbematchwiththebatterygroup.(Setbyprofessionalpersonal

    ofourcompany)

    3.2.1Startundermainpowermode

    1.Startmainpowermodedirectly

    1)Connectthemainpower

    ClosetheinputandbypassbreakerandUPSconnecttothemainpowerandbypass.TheUPS

    screenstartstoworkandthenLOGOinterfaceoccurs.

  • 8/13/2019 Usermanual-11295075930

    20/66

    20

    Figure3.2LogoInterface

    Itwillberefreshedtomaininterfaceafter1s.

    Figure3.3MainInterface

    Clicktheiconofbatterytocheckwhetherthebatterysetismatchwithactualbattery

    configuration(detailoperationcanbeseenin3.6.5).

    2)StartUPS

    ClickiconofOn/OffinmaininterfacetopoptheinterfaceofOn/Off.

    IfitisthefirsttimetostarttheUPS,userneedtoentertheUPSonpassword,thenumberis

    19841219.Afterthistime,nopasswordisneededtostarttheUPS.

  • 8/13/2019 Usermanual-11295075930

    21/66

    21

    Figure3.4UPSONpassword

    ClickiconofINVONandthenUPSstartstopoweronundermainpower.

    Figure3.5On/OffInterface

    ProcessofstartingUPSundermainpowermodewillbefinishedafteratime,andthenthe

    indicatorlightinfrontpanelofpowermoduleison.

    Thechargerstartstopoweronautomaticallyafterthepowermoduleisstarted,andthe

    startingofchargermoduleisfinishedafteratime.

    3)Closebatteryandoutputbreakers

    Closethebatterybreak(longtermmachine)andoutputbreakerafterstartingofUPSunder

    mainpowerisfinished,andthentheUPSstartnormaloperation.

    EnergyflowafteritisstartedundermainpowermodeisshowninFigure3.6:

  • 8/13/2019 Usermanual-11295075930

    22/66

    22

    Figure3.6OperationsunderMainPower

    2.SwitchfrombypassmodetomainpowermodeIftheUPSisworkingunderbypassmode,clicktheOn/Officoninmaininterfacetopopthe

    On/Offinterface.

    Figure3.7On/OffInterface

    ClickiconofTOINV,theUPSwillbegintostartthemainpowermode,andstartingunder

    mainpowermodewillbefinishedafteratime.

    3.2.2Starting

    under

    battery

    mode

    Ifmainpowerisfault,UPScanbeturnedonbybatterymodedirectly.

    1.Closebatterybreaker,inputbreakerandbypassbreakerandconnectthebattery.

    2.PressbuttonofCOLDSTARTincontrolpaneltoturnontheLCDscreen.LCDscreendisplays

    maininterface.

    3.PressENTERfor2stobuildworkingpowerforpowermodule,andthenthefanofmodule

    startstorotate.Clickthebatteryicontocheckwhetherthebatterysetisthesamewithactual

    batteryconfiguration(Detailedoperationisshownin3.6.4and3.6.5).

  • 8/13/2019 Usermanual-11295075930

    23/66

    23

    Figure3.8MainInterface

    4.ClickOn/OfficoninmaininterfacetopoptheOn/Offinterface.ClickiconofINVON,andthestartingunderbatterymodewillbefinishedafteratime.

    Figure3.9On/OffInterface

    5.Closeoutputbreaker,andthentheUPSoutputisnormalandstartingbybatteryisfinished.

    Itsenergyflowisshowninfigure3.10:

  • 8/13/2019 Usermanual-11295075930

    24/66

    24

    Figure3.10BatteryMode

    3.2.3Startingunderbypassmode

    Itcanswitchtobypassmodedirectlyundermainpowermodeorunderthecasethatmain

    powerisavailablebuttheUPShasnotbeenstartedyet.

    1.Startthebypassmodefromstandbymode(mainpowerisavailablebuttheUPShasnotbeen

    startedyet).

    TheUPShasnotbeenstartedcurrently,anddisplayofitsmaininterfaceisshowninFigure3.11:

    Clickthebatteryicontocheckwhetherthebatterysetisthesamewithactualbattery

    configuration.

    Figure3.11MainInterface

    1)ClickOn/OfficoninmaininterfacetopoptheOn/Offinterface.

  • 8/13/2019 Usermanual-11295075930

    25/66

    25

    Figure3.12On/OffInterface

    2)ClickiconofBYPON,UPSwillenterthebypassmode,andthebypassmodeisstarted.The

    chargerwillstartautomaticallyafteratime.

    3)Closebatterybreaker(longtermmachine)andoutputbreaker,andthebypassstartstooutput

    normally.

    Itsenergyflowchartisshowninfigure3.13:

    Figure3.13BypassMode

    2.Switchtobypassfrommainpowermode

    TheUPSisworkingundermainpowermodecurrently,clickiconofOn/Offinmaininterfaceto

    poptheOn/Offinterface.

  • 8/13/2019 Usermanual-11295075930

    26/66

    26

    Figure3.14On/OffInterface

    ClickiconofTOBYP,andthenthesystemwillenterintobypassmode.

    3.2.4Startcharger

    1.ChargerwillstartautomaticallytochargethebatterywhenUPSisstartedundermainpower

    modeorbypassmode.

    2. If the charger isoff andneeds tobe restarted,when theUPS is inmain powermodeor

    bypassmode,itcanclicktheOn/OfficoninmaininterfacetopoptheOn/Offinterface,clickiconof

    CHGONbelowtheCHG_ON/OFF,andthenthechargerwillbestarted.

    3.Clicktheiconofchargerinmaininterfacetochecktheworkingstateofcharger.

    Figure3.15On/OffInterfaceofCharger

    3.2.5Startingbymanualselftest

    InordertoensurethebatterystateofUPSandprolongworkinglifeofbattery,itneedsto

    chargeandreleaseelectricityofthebatteryperiodicallytoensurethatthebatterycansupplypower

    forUPSnormallywhenmainpowerfailssuddenly.

    Clickiconofselftestandmuteoffinmainscreen,thepoppedinterfacesincludeTEST10S,

    TEST10M,TESTLOW,CLRTEST,andMUTE.Clickoneofthefirstthreeoptionstoselectthe

    selftesttime.Selectdifferentselftesttimesaccordingtothetimeofactualtestperiod.

  • 8/13/2019 Usermanual-11295075930

    27/66

    27

    Figure3.16SelftestandMuteoffInterface

    3.3OperationforPoweroff

    3.3.1Poweroffunderlinemode

    TheUPSisworkingundermainpowermodecurrently.

    ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.ClickiconofSHUTtoshut

    downtheUPS,andthechargerwillbeoffautomaticallyatthesametime.

    Figure3.17InterfaceofPoweroffunderMainPower

    3.3.2Poweroffunderbatterymode

    TheUPSisworkingunderbatterymodecurrently.

    ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.ClickiconofSHUTtoshut

    downtheUPS.

    3.3.3Poweroffunderbypassmode

    TheUPSisworkingunderbypassmodecurrently.

  • 8/13/2019 Usermanual-11295075930

    28/66

    28

    Click iconofOn/Off inmain interfacetopoptheOn/Off interface.Click iconofBYPOFFto

    shutdowntheUPS,andthechargerwillbeoffautomaticallyatthesametime.

    3.3.4Power

    off

    the

    charger

    1.Thechargerwillbeoffautomaticallyifthemachineispoweredoffundermainpowermode

    orbypassmode.

    2.Poweroffthechargerwhenthemachineisworkingundermainpowermodeorbypassmode:

    1)ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.

    Figure3.18PowerOffInterface

    2)ClickiconofCHGOFFbelowCHGON/OFFtopoweroffthecharger.

    3.4OperationforEmergencyPoweroff

    Emergencypoweroff(EPO)switchisusedtopowerofftheUPSunderemergencysituation

    (suchasfire,flood,etc.).PressbuttonofEPOinmonitoringpanel,theUPSwillcutoffoutputatonce

    andcutoffthepowerinseveralseconds.

    Ifitneedstopoweronthemachineagain,itshalltakethepoweronoperationaftercuttingoff

    themainpowerinputbreakerandbypassbreakerfor30s.

    3.5OperationforMaintenanceBypass

    3.5.1Startofmaintenancebypass

    1.SelectoptionofOn/OffinLCDmaininterface,selecticonofTOBYPinOn/Offinterface,and

    confirmtheUPSisworkingunderbypassmodeinLCDscreen.

  • 8/13/2019 Usermanual-11295075930

    29/66

    29

    Figure3.19BypassMode

    2.Openthecoverofmaintenancebypassbreaker,closethemaintenancebypassbreaker,cut

    offtheinput,output,andbatterybreakers,andthentheUPSentersintomaintenancebypassmode.

    Itsenergyflowisshowninfigure3.20,andthencutofftheinputandbypassbreakers.

    Figure3.20MaintenanceBypassMode

    3.5.2Exitofmaintenancebypassmode

    1.Closetheinputbreakerandbypassbreaker,thepowermodulebuildsworkingpowerand

    switchestobypassmodebyhand,chargerstartsautomatically.

    2.Closetheoutputbreakerandbatterybreaker,cutoffmaintenancebypassbreaker,putback

    thebaffleofmaintenancebypassbreakerback,andthenthewarningmaintenancecover isopen

    inLCDscreendisappears.

    3.SelectoptionofOn/OffinLCDmaininterface,selectTOINVinOn/Offinterface,thepower

    modulewillstarttheinverterafter20s,andthenUPSwillbeworkingundermainpowermode.

    3.6EnquiryOperation

    EnquiryoperationisaparametertoinquirytheworkingconditionandsettingofUPS.

  • 8/13/2019 Usermanual-11295075930

    30/66

    30

    3.6.1Enquiryofinputinformation

    ClickI\Pinmaininterfacetopoptheinputparameterinterface.Theinputparameter

    interfacewilldisplayinformationincludinginputvoltage,inputfrequency,bypassvoltage,bypass

    frequency,UPStemperature,etc.

    Figure3.21InputParameterInterface

    3.6.2Enquiryofoutputinformation

    ClickO/Pinmaininterfacetopoptheoutputparameterinterface,andtheninformation

    includingoutputvoltage,outputcurrent,outputfrequency,activepower,apparentpower,andload

    factorofthreephaseswillbedisplayed.

    Figure3.22OutputParameterDisplay

    3.6.3Enquiryofinformationofcharger

    Clickiconofchargerinmaininterfacetoinquiryinformationofcharger.

    Informationofchargerincludes:stateofchargerandparameterofcharger(canbeswitchedby

    buttonofpageuporpagedown).

    Theinterfaceofchargerstatewilldisplay:operatingmodeofcharger,chargertemperature,

    positive/negativechargervoltage,andpositive/negativechargercurrent.

  • 8/13/2019 Usermanual-11295075930

    31/66

    31

    Figure3.23InterfaceofChargerState

    Itcanswitchtointerfaceofchargerparameterbypressingbuttonofpageupordown,andthefollowinginformationwillbedisplayed:floatchargevoltage,evenchargevoltage,temperature

    compensationsetting,positive/negativechargingspeed,andmaximumpositive/negativecharging

    current.

    Figure3.24InterfaceofChargerParameter

    3.6.4Enquiryofbatteryinformation

    Clickiconofbatteryinmaininterfacetoenterintointerfaceofbatteryparameter.Itwilldisplay:

    piecesandgroupsofbattery,connectionstate,batteryvoltage,batterytemperature,batteryremain

    time,batteryremaincapability,batterytemperature,timeofnextselftest.

  • 8/13/2019 Usermanual-11295075930

    32/66

    32

    Figure3.25DisplayofInterfaceofBatteryparameter

    3.6.5Enquiryofcurrentwarn

    ClickiconofWARNinmaininterfacetopopcurrentwarninginformation.Itcanswitchthe

    warninterfacebetweenpowermoduleandchargerbybuttonofpageupandpagedown.

    Figure3.26WarnInterface

    3.6.6Enquiryofhistory

    ClickiconofHISTORYinmaininterfacetopoptheinterfaceofUPShistory.Itcontains:FAULT,

    WARNING,ATATUS,andOPERATE.

  • 8/13/2019 Usermanual-11295075930

    33/66

    33

    Figure3.27InterfaceofHistory

    1.FAULT:

    FAULTrecordsallfaultsoccurredduringoperationofUPS.

    Figure3.28InterfaceofFault

    2.WARNING

    WARNINGrecordsreasonsforallwarnswhenwarnsoccurredforUPS.

  • 8/13/2019 Usermanual-11295075930

    34/66

    34

    Figure3.29InterfaceofWarning

    FAULTandWARNINGcanrecord2100piecesatmostandtheearliestrecordswillbereplaced

    bynewrecordifnumberofallrecordsexceeds2100.Allrecordsarelistedbyinvertedorderoftime.

    3.OPERATE

    OPERATErecordsalloperationsofUPStakenbyuser.

    Figure3.30DisplayChartofInterfaceofOperate

    4.STATUS

    STATUSrecordsallworkingmodeofUPSunderdifferentperiods.

  • 8/13/2019 Usermanual-11295075930

    35/66

    35

    Figure3.31DisplayChartofInterfaceofStatus

    OPERATEandSTATUScansave768piecesatmostandtheearliestrecordswillbereplacedby

    newrecordifnumberofallrecordsexceeds768.Allrecordsarelistedbyinvertedorderoftime.

    5.Enquiryrecord

    Clickiconofenquiryrecordinfourinterfacesabovetopoptheinterfacesofrecordenquiry.

    Entertherecordtime,itcaninquiryrecordsbeforeandaftertheenteredtime.

    3.6.7Enquiryofcurrentinformation

    Clickiconofsettinginmaininterfacetopopthesettinginterface.

    Figure3.32SettingInterface

    ClickiconofSETINFOtopopthecurrentsettinginterfaceofUPS.Informationcontainedin

    theinterfaceincludes:cabinetNo.,statusofconvertermode,statusofcharger,statusofautostart,

    testmode,andcontacttelephone.

  • 8/13/2019 Usermanual-11295075930

    36/66

    36

    Figure3.33DisplayofCurrentSettingInterface

    Clickthepageuporpagedowntopopthewarrantyinterfacewhichcaninquirethewarrantyperiodofcomponentssuchasbatterytoremindtheusertoreplace.

    Figure3.34DisplayofWarrantyInterface

    3.6.8Enquiryofsysteminformation

    Clickiconofsettinginmaininterfacetopopthesettinginterface.ClickiconofSYSINFOto

    popthesysteminformationofthemachine,including:sequencenumber,model,softwareversion,

    producer,telephone,andwebsite.

  • 8/13/2019 Usermanual-11295075930

    37/66

    37

    Figure3.35InterfaceofSystemInformation

    3.7OperationsforUserConfiguration

    Warn:operationforuserconfigurationisusedforsettingUPSparameters,and

    nonprofessionalpersonalshallnottakeanysettingoperations.

    ClickiconofUSERCONFinsettinginterfacetopopthepasswordinputinterfaceofuserset.

    Figure3.36PasswordInputInterface

    Entercorrectpassword(initialpasswordis666666)topoptheuserconfigurationinterface,

    including:LANGUAGE,TIME,SELFTEST,PROTOCOL,PASSWORD,CALIB,andPHONE.

  • 8/13/2019 Usermanual-11295075930

    38/66

    38

    Figure3.37UserConfigurationInterface

    3.7.1Languageset

    LCDdisplayscreencanprovidethelanguageofEnglish.

    Figure3.38LanguageSetInterface

    3.7.2Timeset

    ClickiconofTIMESETinusersetinterfacetoenterintotimesetinterface.Itcanchangethe

    displayedtimeofUPSbyenteringcurrenttime.

  • 8/13/2019 Usermanual-11295075930

    39/66

    39

    Figure3.39TimeSetInterface

    3.7.3Autoselftestset

    ClickiconofSELFTESTinusersetinterfacetopoptheselftestsetinterface.

    Itsdisplayisshowninfigure3.40,autoselftestinterfaceincludes:onandoffofselftest,run

    cycleofselftest,anddurationofselftestforeverytime.

    Figure3.40SelftestSet

    Selectproperselftestdurationandtimebydemand.

    3.7.4ProtocolSet

    ClickiconofPROTOCOLinusersetinterfacetopoptheprotocolsetinterface.

  • 8/13/2019 Usermanual-11295075930

    40/66

    40

    Figure3.41ProtocolSetInterface

    Therearetwooptionalcommunicationports,RS232andRS485.

    ClickiconofRS232,andthencommunicationportsetinterfacewillbepopped.

    Figure3.42CommunicationPortSetInterface

    Portpropertyshallbesetbydemand.

    3.7.5Password

    set

    ClickiconofPASSWORDinusersetinterfacetopopthepasswordsetinterface.

  • 8/13/2019 Usermanual-11295075930

    41/66

    41

    Figure3.43PasswordSetInterface

    Thepasswordisrequiredwhenenteringuserconfigurationinterface.Enteroldpasswordandnewpasswordaccordingtorequirementtochangethepasswordof

    enteringUserConfigurationInterface(initialpasswordis666666).

    3.7.6Calibrate

    Ifthetouchclickisnotsosensible,itcanrecoverthesensitivityoftouchscreenthrough

    CALIBRATE.

    ClickiconofCALIBRATEinsetinterfacetopopthecalibrateinterfaceoftouchscreen.Click

    specifiedsiteaccordingtoorder,andthenthesensitivityoftouchscreenwillberecovered.

    Figure3.44CalibrateInterfaceofTouchScreen

    Note:objectusedtoclickthetouchscreenshallnotbetoosharpwhencalibrating,otherwise

    itwilldamagethescreen.

    3.7.7Telephoneset

    ItcanchangethecontacttelephoneofagencybyTELSET.

  • 8/13/2019 Usermanual-11295075930

    42/66

    42

    Figure3.45Telephonesetinterface

    3.7.8Muteoff

    Clickiconofbatteryselftestandmuteoffinmaininterfacetopopinterfaceofbatteryselftest

    andmuteoff.ClickMUTOFFinselftestinterfacetomutethewarningsound.

    Figure3.46InterfaceofSelftestandMuteoff

    3.7.9 Advanced setting

    Note:

    It

    is

    forbidden

    to

    enter

    the

    advanced

    setting

    interface

    without

    the

    allowance

    of

    the

    Customerservice,otherwisegreatdamagemayoccur.

    ClicktheiconofADVANCEDinsettinginterfacetopopthepasswordinputinterface.

  • 8/13/2019 Usermanual-11295075930

    43/66

    43

    Figure3.47Passwordinputinterface

    Entercorrectpassword(initialpasswordis19841219)topoptheadvancedsettinginterface.

    Figure3.48Advancedsettinginterface

    AdvancedsettingincludeMODELCHGCONFSYSCONFWARRANTYOPENSET

    OTHERSET COMDATAandOUTCOEF.

    1)MODELClicktheiconofMODELtopopthemodelsettinginterface.

  • 8/13/2019 Usermanual-11295075930

    44/66

    44

    Figure3.49Advancedsettinginterface

    RUNMODE:tochoosetheworkingmodeuserneeded,singleorparallel. INTYPE:tochoosetheinputtypebytheconditionuseroffered,ifthemainpowerand

    bypassarethesameACsource,choosesingle,ifnotchoosedouble.

    CABNUM:iftheuserwanttobuildaparallelsystem,thecabinetsshouldbesetthenumberfrom1to6,iftheuserjustwantasingleUPS,thenumbershouldbesetas1.

    OUTTYPE:wecansettheoutputtypeas3/3(3phaseinputand3phaseoutput)or3/1(3phaseinputand1phaseoutput).

    UPSS/N:thisnumberistheserial number and forbiddenbeingchanged.2. CHGCONFClicktheiconofMODELtopopthemodelsettinginterface.

    Wecanconfigurethechargerparameterandthebatteryparameterinthisinterface.

    Figure3.50Chargerconfigureinterface

    CHGSTATE: ifthisoptionissetasopen,thechargerisallowedtostart,otherwisethechargercannotstart.

    TEMPCMP:thisfunctionhasnotopenyet. BATNUM:forstandardmachine,thenumbershouldbesetas16,forlongbackupmachine,

    thenumberiscounttothemountofbatteriesuseroffered.

    BATGROUP:thisparameterrefertothenumberofbatterygroups. BATCAPACITY:itshouldmatchthebatterycapacityuseroffered. CHGRATE:chargercurrent=chargerrate*batterygroups*batterycapacity.

  • 8/13/2019 Usermanual-11295075930

    45/66

    45

    SYSCONFClicktheiconofSYSCONF topopthesystemconfigureinterface.

    Figure3.51Systemconfigure

    1)CONVERT:tostartthefrequencyconvertermodeornot.

    2)AUTOSTART:whenitisopen,theUPSwillstartautomaticallywhenthemainpowerresupply

    aftertheUPSshutdowninbatterymode.

    3) OUTFREQ:tosettheoutputfrequency,itcanbesetas50Hzor60Hz.

    4) OUTVOLT:tosettheoutputvoltage.

    5) BYPVOLT:tosettherangeofbypassvoltage, ifthebypasspowervoltage isbeyondit,UPS

    willbeforbiddentostartbypassmode.

    6) BYPFREQ:tosettherangeofbypassfrequency,ifthebypasspowerfrequencyisamongit,

    theoutputfrequencywilljustfollowthebypassfrequency,ifnot,theoutputfrequencywillbe50Hz

    or60Hz.

    4 WARRANTY

    ClicktheiconofWARRANTY topopthewarrantyinterface.

    Figure3.52Warrantyinterface

    ClicktheBAT orCAP tothewarrantysettinginterface.

  • 8/13/2019 Usermanual-11295075930

    46/66

    46

    Figure3.53BATwarrantyinterface

    Theninputthetimewhenthebattery(capacitance)isreplacedandthelifeofthebattery(capacitance),theUPSwillwarnyouifthebattery(capacitance)isuptothewarrantydate.

    WhenstartingtheUPSfirsttime,updatetheinstalltimeofthebatteryandcapacitance.

    5 OPENSET

    ClicktheiconofOPENSETtopoptheopensetinterface.

    Figure3.54Opensetinterface

    1)OPENPWD:ifitisopen,theuserneedinputthepasswordwhenstartingtheUPSnexttime,

    aftertheUPSisstarted,thissetwillturntocloseautomatically.

    2)LOCKPWD:ifitisopen,nopasswordsisneededtointerviewanyinterface.

    3)BYPENA:ifitisopen,bypassmodecannotbestarted.

    6 OTHERSET

    ClicktheiconofOTHERSETtopoptheothersetinterface.

  • 8/13/2019 Usermanual-11295075930

    47/66

    47

    Figure3.55Othersetinterface

    2. DEFAULT:restorethefactorysetting.3. FIRMWARE:toupdatetheSoftware.4. CLRLOG:clearhistory.7 COMDATA

    ClicktheiconofCOMDATAtopopthecomdatainterface.

    Figure3.56Comdatainterface

    ThesecondrowistheworkingmodeoftheUPS,1meansstandbymode,2meansbypass

    mode,3meansmainpowermode,4meansbatterymode.

    TheforthrowistheBUSvoltageoftheBUSline,whentheUPSworksnormally,theBUSline

    shouldbe360V.

    ThefifthrowistheinvertervoltageoftheUPS.

    Thesixthrowistheversionofthepowermodule

    8 OUTCONF

    ClicktheiconofOUTCONFtopoptheoutputparameterinterface.

  • 8/13/2019 Usermanual-11295075930

    48/66

    48

    Figure57Parametersetinterface

    Clickthemoduleneededtobeadjustedtopoptheparameterinterface

    1)INVVOLTSET:toadjusttheoutputvoltage.2)OUTVOLTSET:toadjustthedigitalwhichisdisplayedintheoutputinterface(chapter3.6.2)

    oftheLCDscreen.

  • 8/13/2019 Usermanual-11295075930

    49/66

    49

    Chapter4InstallationandOperationofParalleledMachine

    Themachinesupportsparalleledmachineextendedoperationwithmaximumextendednumber

    ofmachinesis6andmaximumextendedpoweris360KVA.

    4.1InstallationofParalleledSystem

    1.Connectthemainpowerinput,bypassinput,outputandbatteryofUPSwhichisreadyfor

    parallelaccordingtofigure4.1,andthenconnecttothemainpower,bypass,battery(onlyconnect

    thebatteryinparallelforstandardmachine)andload.

    Figure4.1ConnectionChartofParalleledMachines

    2.Asshowninfigure4.2,connecttheparalleledportsofcommunicationportsforUPSreadyfor

    parallelwithparallelwire,anditcanparallel6machinesatmost.

    Figure4.2CommunicationConnectionChartofParalleledMachines

    Note:

  • 8/13/2019 Usermanual-11295075930

    50/66

    50

    1.AlltheparalleledUPSshouldsharethesamebatteries,bypassandmainpower.Thesamephaseoftheoutputshouldbeconnectedinparallel.Otherwisegreatdamagemayoccur.

    2.Itneedstodetectwhetherthewiringiscorrectornotafterparallelofoutput,bypass,battery

    and

    load

    is

    finished.

    3.Lengthdifferenceofallthesinglemachineoutputlinesmustbelessthan10m.

    4.2On/OffofParalleledMachines

    4.2.1Parallelon/offofparalleledmachines

    Setthecabinetsnumberfrom1 n(n6)inmodelsettinginterface(asshowninchapter3.7.9).

    Closeallinputbreakers,bypassbreakers,batterybreakersandoutputbreakersofparalleled

    machines,anditsmaininterfaceisshownasfigure4.3:

    Figure4.3MainInterfaceofParalleledMachines

    ClickiconofOn/OfftopoptheOn/Offinterface.

    Figure4.4On/OffInterfaceofParalleledMachines

    ClickSYSTEMinOn/Offinterfacetotakeon/offoperationofparalleledmachines(samewith

    on/offoperationofsinglemachineinchapter3).

  • 8/13/2019 Usermanual-11295075930

    51/66

    51

    Figure4.5On/OffInterface

    Note:all

    breakers

    shall

    be

    closed

    when

    power

    on

    or

    power

    off

    the

    paralleled

    machines.

    4.2.2Singleon/offofparalleledmachines

    ClickiconofOn/OfftopoptheOn/Offinterface,asshownbelow:

    Figure4.6On/OffInterfaceofParalleledMachines

    SelectUPSn(n6)foron/offoperationtoenterintotheOn/OffinterfaceofUPS.

    Takeon/offoperation(samewithon/offoperationofsinglemachineinchapter3).

    4.3EnquireOperationofParalleledSystem

    4.3.1Informationenquireofsinglemachineforparalleledsystem

    ClickUPS n(n6)inmaininterfacetoenterintothesubordinateinterfaceofparalleled

    system.

  • 8/13/2019 Usermanual-11295075930

    52/66

    52

    Figure4.7InformationInterfaceofSingleMachine

    Thisinterfacecanenquiretheinformationoninputandoutputbatteryandchargerofthissinglemachine.

    4.3.2Informationenquireofwholeunitforparalleledsystem

    Clickrelatediconinmaininterfacetotaketheenquireoperation(samewiththatinchapter3).

  • 8/13/2019 Usermanual-11295075930

    53/66

    53

    Chapter5:

    UPS

    Repairing

    and

    Maintenance

    5.1UPSRepairingandMaintenance

    5.1.1PowerandfeaturesofloadshallbeconsideredwhenusingUPS

    RatedoutputpowerofUPSisthekeyparametertoexpresshowmuchpowerloadtheproduct

    candrive, it changes alongwith alteration of load power factor, for example, 1 KVAUPSmaybe

    cannotdrive1KVAload.UPSshallnotbeunderfullloadconditioninordertoprolongworkinglifeof

    UPS.Loadcapabilityof standbyUPS shallbe6070 of ratedpower,and thatofonlineUPS

    shallbe7080 ofratedpower.Atthesametime,theUPSshallnotworkunderoverunder

    loadingconditionforalongtime.

    5.1.2EnsureinductionstrokeprotectionofUPS

    Lightening stroke is the natural enemy of all electrical equipments, so it must ensure the

    effective shielding and groundprotectionofUPS against lightening stroke. Lightening strokemay

    causeinductivehighpotentialpulseduetoelectromagneticinduction.Thehighpotentialpulsemay

    enter into the UPS along with power line or communication line, while there are so many

    microelectronicdevices suchasCMOS integratedcircuitmodulesandCPUused forcontrol in the

    UPSwhichareverysensitivetoelectromagneticpulseoflightening,therefore,thedevicesarevery

    easytobedamaged.AlthoughourUPShaseffectiveshieldingandgoodprotectiongroundmeasure,

    user still needs to adopt lightening protection and overvoltage protection for power line and

    communicationline(suchasremotemonitoringsingleline).

    5.1.3Notesforusing,repairingandmaintenance

    ItmustobeytheproductintroductionwhenusingUPS.Relatedstipulationsinusingmanualcanensureallfiringlines,zerolines,andearthlinesmeetrequirements,sousershallnotchangeits

    orderwithoutallowance.

    Anyoperation shall strictly complywith correctorderofpoweron andoff. It shall avoidexcessive fluctuationofvoltageoutputofUPScausedbysudden increasingorreducingof loadso

    thattheUPScannotworkinnormal.

    It isstrictlyforbiddentopoweronandofftheUPSfrequently.Itrequiresfor30saftertheUPSispoweredoffandbeforestartingitagain,otherwise,faultmayoccurredforUPS. Itisforbiddentooperateunderoverload.MaximumstartingloadofUPSshallbecontrolledwithin80%,andtheinvertertubemaybedamagedunder invertercondition ifit isoperatedunder

    overloadcondition.Experienceproves that thebestoperationmode is tocontrol the loadwithin

    30~60%ofratedoutputpowerformostUPSpowers.

    Discharging requirement of battery: in general, the UPS is equipped with protectionmeasures for discharging of battery, but the battery will recover to certain voltage after it is

    discharged so that the protection is powered off, and it is not allowed to restart the machine,

    otherwise, itmaycauseoverdischargingofbattery.Thebattery shallbeusednormallyafter it is

    recharged.

    FornewboughtUPS (or forUPSstored fora longtime), itonlycanbeoperatedafterthebatteryischarged.Otherwise,thestandbytimewillnotbeensured.

  • 8/13/2019 Usermanual-11295075930

    54/66

    54

    ForUPSwithoutpoweroff for a long time, itsbattery shallbedischarged forevery3~6monthsandthenrechargedagain.Itcanprolongtheworkinglifeofbatterybythisway.

    For UPS stored for a long time, it shall be started and charged for every 3~6 months,otherwise,itmaydamagethehostandbatteryofUPS. ItshallmaintaintheUPSperiodically.Cleandustinsidethemachine,measurethevoltageofbatterygroup,checkrunningoffans,andinspectandadjustsystemparametersofUPS.

    5.1.4Batterymanagement

    This system allows the charging system to bewith high liability andwithouthigh frequency

    clutterwhichcanavoideffectofhighfrequencywavetobatterylife;avoidoverheatofbatterywhen

    charging,andprolongworkinglifeofbattery.

    User can set the battery parameter by monitoring display screen (battery management

    parametermustbesetbyprofessionalpersonal,pleasenotifythecustomerservicepersonalifuser

    needs to change theseparameters),and the system can take intelligentmanagement forbattery

    accordingtousersetandactualstatusofbatterygroup.

    Chargemodeofthisseriesofproductssystemisthreestagecharge:

    Stage1:recharge90%capabilityofbattery

    Chargewithequalizingchargingvoltageandmaximumchargingcurrent;

    Stage2:rechargethebalance10%capabilityofbattery

    Turntostage2toequalizingchargefor1minuteandfloatingchargefor1minutewhenvoltage

    reachesto13.85Vofeverybattery.

    Stage3:Maintainbatterycapability

    Itwillswitchtostage3afteritcontinuesfor360cycleinstage2andchargethebatterywith

    floatingchargesotatthebatteryquantitycanbemaintainedmorethan99%.

    Batterygroupof900II1060KseriesproductissharedbyallmodulesinUPS(includingcharging

    and discharging). It can use one group of battery or several groups of batteries to increase the

    standbytimeofsystemaccordingtousersrequirement.

    Tips: itmust takeoffmetalobjects suchas ringandwatchbefore replacing thebattery,use

    screwdriverwith insulatedhandle,donotputany toolorothermetalobjecton thebattery. It is

    normalphenomenontoappearsmallsparkatjointwhenconnectingthebattery,butitwillnotcause

    anyharmtopersonalsafetyandUPS.Donotcauseshortcircuitorreverseconnectiononpositive

    andnegativeofbattery.

    5.2Troubleshooting

    FaultsofUPScanbeknownbyinquiringhistoryrecordsofUPS,andcommonproblemsduring

    operationofUPScanbesolvedbycontrastingtable4.1.

    Table5.1Fault/WarnRemoval

    ProblemType Fault/Warning Solution

    Battery Overcharged Power off the charger and contact

    customerservicepersonal.

    Charger FailPower off the charger and contact

    customerservicepersonal

    Warningof

    charger

    Battery DisconnectedCheckwhetherchargerisstartedor

    not

  • 8/13/2019 Usermanual-11295075930

    55/66

    55

    Bat Num setting errorContactcustomerservicepersonal

    toresetthebatterypiece

    Over Temperature Unnecessarytosolveit

    ChargeVolt setting error

    ChargeCurr setting error

    Contactcustomerservicepersonal

    tochangetheset.

    Charger Fanlock

    Pleasecontactcustomerservice

    personalifthechargerfanis

    damaged

    Buck Soft Start FailPoweroffthechargerandcontact

    customerservicepersonal.

    Input Fuse Fail

    Output Fuse Fail

    Contactcustomerservicepersonal

    toreplacethefuse

    Charger ShortCircuit Poweroffthechargerandcontactcustomerservicepersonal

    Faultofcharger

    Battery ReverseCheck whether the battery

    connectioniscorrectandcorrectit

    Bus Volt High

    Bus Volt Low

    Bus Imbalance

    1. Check whether threephase

    normalpowerisinbalance.

    2.Checkwhetherthefluctuationof

    threephasenormalpowerisin

    normal.

    Bus Short circuit Contactcustomerservicepersonal

    Bus Softstart Fail

    Inv Softstart Fail

    Cutoff

    the

    input

    breaker,

    and

    start

    themachineafter30s.Please

    contactthecustomerservice

    personalifproblemstillexists.

    Inverter Volt High

    Inverter Volt Low Contact the customer service

    personal

    R phase Out Short

    S phase Out Short

    T phase Out Short

    RS phase Out Short

    ST phase Out Short

    TR phase Out Short

    1. Check whether the output

    connectionisshortcircuitornot.

    2.Checkwhethertheloadisshort

    circuitornot.

    R Reactive Abnormal

    S Reactive Abnormal

    UPSfault

    T Reactive Abnormal

    Contactthecustomerservice

    personal

  • 8/13/2019 Usermanual-11295075930

    56/66

    56

    Overload Fail

    1.Poweroffsecondaryload

    2. Reallocate the load so that

    outputs of three phases are

    balance.

    3.CutoffUPSinputbreakerfor30s,

    thenstartagain.

    Overtemp Fault

    Ensure environmental temperature

    iswithinworkingrangeofUPS.Cut

    off theUPS for30s, and then start

    again.

    Power Set Fault

    Inverter Fault

    Relay Stick Death

    Line SCR Fault

    Contactthecustomerservice

    personal

    Can Bus FaultCheckwhetherthecommunication

    lineisconnectedcorrectly

    Bypass wiring error

    Checkwhetherthebypassphase

    sequenceconnectionofcabinetis

    normalornot

    Power Set Fault

    Total Reactive Fault

    Contactthecustomerservice

    personal

    Id Error

    1.Checkwhethersetofdialswitch

    inbackofmoduleis1~2.

    2.Checkwhethersetofdialcodesinbackofmoduleisconflict.

    BypassPhaseError

    Line Phase Error

    Bypass Loss

    1.Checkwhethertheinputpoweris

    normal.

    2.Checkwhetherthethreephase

    inputlinesareconnectedcorrectly.

    Bypass Freq AbnormalCheck whether the input power is

    normal.

    N Line Loss

    1.Checkwhetherthebackterminal

    ofmoduleisnormal.

    2. Check whether the terminalconnected cabinet and module is

    normal.

    Input CB OpenCheckwhetherthe inputbreaker is

    closedornot.

    Output CB OpenCheckwhether the output breaker

    isclosedornot.

    Output OvervoltPleasecontactthecustomerservice

    personal.

    Maint CB Cover OpenUnnecessary for treatment under

    maintenancebypassmode

  • 8/13/2019 Usermanual-11295075930

    57/66

    57

    Maint CB Cover Open

    1.Unnecessaryfortreatmentunder

    maintenancebypassmode.

    2.Checkwhetherthescrewof

    maintenancecoverisfastenedornotunderotheroperationmode.

    Battery Volt Low

    1. Check whether the battery and

    chargerarenormalornot.

    2.Checkwhetherthebatteryset

    matcheswithactualconfiguration.

    3.Pleasedismantlethesecondary

    loadassoonaspossibleifitisunder

    batterymode.

    Battery Open

    1.Checkexternalbatterybreaker is

    closedornot

    2.Checkwhetherthebatteryis

    connectedwell

    Ovload Fail

    UPS Over Current

    UPS Over Load

    1.Closethesecondaryload

    2.Reallocatetheloadsothat

    outputsofthreephasesare

    balance.

    Eeprom FailForbiddentopoweron,andcontact

    thecustomerservicepersonal.

    UPS Fan LockContactthecustomerservice

    personalifitismodulefault.

    Epo Active

    ConfirmwhetherthebuttonofEPO

    ispressedornot.Pleasecheckthe

    screwinleft

    side

    ofmodule

    is

    fastenedornotifitisnotpressed.

    Charger OfflineCheckwhetherthechargeris

    mounted.

    Can Fail

    Comm Syn Sig Fail

    Comm Syn Pulse Fail

    Checkwhetherthecommunication

    lineisconnectedwellornot

    Id Error

    IDerrorofpowermodule

    Checkwhetherthesetofdialswitch

    inconnectingpanelin

    correspondingmodulelocationof

    cabinetiscorrectornot.

    R phase PFC Fail

    S phase PFC Fail

    T phase PFC Fail

    Bypass STS Open

    Bypass STS Short

    Contacttheconsumerservice

    personal

  • 8/13/2019 Usermanual-11295075930

    58/66

    58

    5.3MaintenanceAssurance

    Underconditionofcomplyingrulesofstorage,mounting,using,andoperation,wehaveliability

    todebug,repairorchangeelementsandcomponentstimelyfreeofchargeiftheproductis

    damagedduetopoorqualityorimproperoptionorcannotoperatenormallywithinthreeyearssince

    itisdelivered;wehaveresponsibilitytoprovidepaidlifemaintenancefortheproductifitisoutof

    thewarrantyperiod.

    Servicecommitmentofourcompanyis:warrantedforthreeyearsandmaintainedforalllife.

    Thefollowingcasesarenotincludedinwarrantyrange:

    1.Artificialfault;

    2.Outofwarrantyperiod;

    3.Productwhoseproductionserialnumberischangedorlost;

    4.Damageorlosscausedbyforcemajeureandexternalcauses;

    5.DismantleorchangetheUPSwithoutauthority;

    6.Breachoperation/applicationstipulationsofUPS;

    7.Thebatteryisdischargeddeeplyordamagedbymanual.

    5.4TechnicalSpecifications

    Table5.2TechnicalSpecifications

    Model 9010II 9015II 9020II 9030II 9040II 9060II

    Nominalcapacity 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA

    Input

    Ratedinputvoltage 380Vac

    Load50% 204~520Vac

    50% load70% 242~520Vac

    70% load100% 304~520Vac

    Inputmode Threephasefivewiresystem

    Inputpowerfactor 0.99

    Totalharmonic

    distortion(THDi)

    3%

    Ratedfrequency 50Hz/60Hzselfadoption

    ACmainpowerinput 40~70Hz

    Bypassvoltagerange 380Vac*(120%)Settable

    Output

    Outputpowerfactor 0.9

    Ratedvoltage 380VacStabilizedvoltage

    precision

    1%

    Dynamicvoltage

    transientrange

    5%(0100%loadfluctuation)

    Totalharmonic

    distortion(THDV)

    1%(resistiveload);

    3%(nonlinearload)

    Outputvoltagedirect

    currentcomponent

    100mv

    Outputcurrentpeak

    factor

    3:1

  • 8/13/2019 Usermanual-11295075930

    59/66

    59

    Model 9010II 9015II 9020II 9030II 9040II 9060II

    Outputfrequency Mainpowermode:synchronouswithmainpower;batterymode:

    50Hz/60Hz

    Batterymode 50Hz/60Hz

    Frequencytracking

    rate

    1Hz/s

    Phaselockaccuracy 1

    Inverteroverload

    capability

    100%150%,continuefor10s

    Mainpowermode

    Batterymode

    0ms

    Batterymode

    Mainpowermode

    0ms

    System

    Workingefficiencyof

    unit

    93%(50%load)

    Batteryconfiguration 192V~240V(positive/negativebatterygroupwith16,17,18,19and20

    piecesforeachgroupforoption,32pieces12V/7AHor12V/9AHare

    equippedforstandardmachine,thebatteryspacecanallow64pieces

    batteriesatmost)

    Maximumcharging

    current

    12A 24A

    Maximumparalleled

    machines

    6

    Workingtemperature

    range

    0~40

    Workingelevation

    height

    25A)classA

    UPScabinetsize 600mm*800mm*1280mm

    Weight(kg) 158 164 164 174 190 210

    Color Black

    Controlpanel 5.7inchmultifunctionalLCDtouchwidescreen

  • 8/13/2019 Usermanual-11295075930

    60/66

    60

    Model 9010II 9015II 9020II 9030II 9040II 9060II

    Audiblealarm Alarmofbatterymode;warnwhenvoltageofbatteryistoolow;alarmof

    fanfault,etc.

    Port USB,RS232,RS485anddrycontact(standardequipped)

    Optionalelement SNMPcard,Paralleledmachinecard

  • 8/13/2019 Usermanual-11295075930

    61/66

    61

    Appendix

    1:

    Lamp

    Signal

    Reference

    List

    Mode Fault/Warning StatusofLED Statusofbuzzer

    Phase sequence is error,

    and mainpowerbypass is

    abnormal

    Thefaultlight

    twinklesonce2sand

    lastsfor1/4s

    Buzzonce2sand

    lastfor1/4s

    Disconnectionofbattery Thefaultlight

    twinklesonce4sand

    lastsfor1/4s

    Buzzonce2sand

    lastfor1/4s

    Standbymode

    Nofault Allisoff Nosound

    Somemodule isunderfault

    mode

    Thebypasslightison,

    faultlighttwinkles

    once1sandlastsfor1/4s

    Buzzonce1sand

    lastfor1/4s

    Chargerisnotstarted Thebypasslightison,

    faultlighttwinkles

    once8sandlastsfor

    1/4s

    Buzzonce8sand

    lastfor1/4s

    Overload Thebypasslightison,

    faultlighttwinkles

    once2sandlastsfor

    1/4s

    Buzzonce2sand

    lastfor1/4s

    Phasesequenceiserror Thefaultlight

    twinklesonce2sand

    lastsfor1/4s

    Buzzonce2sand

    lastfor1/4s

    Disconnectionofbattery Thebypasslightison,

    faultlighttwinkles

    once4sandlastsfor

    1/4s

    Buzzonce4sand

    lastfor1/4s

    Bypassisnormal Thebypasslightison,

    faultlighttwinkles

    once4sandlastsfor

    1/4s

    Buzzonce4sand

    lastfor1/4s

    Bypassmode

    Nootherfault Thebypasslightison,

    faultlighttwinkles

    once2mandlastsfor

    1/4s

    Buzzonce2sand

    lastfor1/4s

    Somemodule isunderfault

    mode

    Thenormallightison,

    faultlighttwinkles

    once1sandlastsfor

    1/4s

    Buzzonce1sand

    lastfor1/4s

    Chargerisnotstarted Thenormallightison,

    faultlighttwinkles

    once8sandlastsfor

    1/4s

    Buzzonce8sand

    lastfor1/4sMainpower

    mode

    Overload Thenormallightison,

    faultlighttwinkles

    Buzzonce2sand

    lastfor1/4s

  • 8/13/2019 Usermanual-11295075930

    62/66

    62

    once2sandlastsfor

    1/4s

    Disconnectionofbattery Thenormallightison,

    faultlighttwinklesonce4sandlastsfor

    1/4s

    Buzzonce4sand

    lastfor1/4s

    Nootherfault Normallightison Nosound

    Somemodule isunderfault

    mode

    Faultlightisonallthe

    time

    Buzzallthetime

    Lowvoltageofbattery Battery light twinkles

    once1s

    Buzzonce1sand

    lastfor1/4s

    Overload Allisoff Buzzonce2sand

    lastfor1/4s

    Battery self

    test

    Othersarenormal Twinkle in turn for

    every2s

    Nosound

    Bypass and output are

    normal

    Bypass light is on,

    fault light isonallthe

    time

    BuzzallthetimeFaultmode

    Bypassandoutputare

    abnormal

    Faultlightisonallthe

    time

    Buzzallthetime

    Somemodule isunderfault

    mode

    Thenormallightison,

    faultlighttwinkles

    once1mandlastsfor

    1/4s

    Buzzonce1sand

    lastfor1/4sFrequency

    conversion

    mode

    Nofault Thenormallightison Nosound

    Poweroff Allisoff Nosound

    Communication is

    abnormal

    Allisoff Nosound

  • 8/13/2019 Usermanual-11295075930

    63/66

    63

    Appendix2:

    Port

    of

    Communication

    Interface

    Thereareseveralcommunicationportsfor900II1060KVAsystem,asshowninFigure1:

    Figure1Chartof900II1060KCommunicationPort

    1.SNMPNetworkCardPort(optionalfitting)

    TheLANportcommunicationneedstobesetas:

    Connectthecomputerandsystemwithnetworkcable.Itcanusetwistedpairnetworkcableto

    connectthecomputerdirectlyorusedirectnetworkcabletoconnectthecomputerthrough

    switchboard.

    2.RS232Port

    Itsmaximumtransmissionrangeis50mwhenthebaudrateis9600.

    RS232interfacedefinition(othersarenotconnected):

    Stitch 2 3 5

    Definition RXD TXD GND

    3.RS485Port

    Itsmaximumtransmissionrangeis500mwhenthebaudrateis9600.

    RS485providesdifferentportsfortwokindsofconnectingmodes,oneisRJ45networkcable

    port,andtheotherisdoublepinport.

    RJ45networkport(othersarenotconnected):

  • 8/13/2019 Usermanual-11295075930

    64/66

    64

    Stitch 3 5

    Definition A B

    Doublepinport:

    Stitch 1 2

    Definition A B

    4.USBPort

    TheUSBportisspecialportforUPSmart2000Imonitoringsoftware.

    5.InspectionPortofBatteryTemperature

    Thechargermodulecancollectbatterytemperatureatanytimetoprovidetemperature

    compensationthroughinspectionportofbatterytemperature.

    6.PassiveOutputDryContact

    900II1060KUPS isequippedwithadrycontactcardwhichcontains7groupsof independent

    passiveoutputdrycontactswiththreeconnectingterminalsforeverydrycontact,andfrom leftto

    right which are: normally closed terminal, common terminal, and normally open terminal. The

    passivedrycontactiscontrolledbyrelay,andthecommonterminalandnormallyclosedterminalof

    relaywillbeconnectedwhendefinedstatusofdrycontact isfalse;therelaywillstartoperationat

    oncewhendefinedstatusofdrycontactistrue,andthecommonterminalwillbedisconnectedwith

    normallyclosedterminalofrelay,andbeconnectedwithnormallyopenterminal.Usercanselectto

    connectthenormallyopenterminalornormallyclosedterminalaccordingtoactualdemand.

    Identifier Meaning

    INV Inverteroutput

    LINELOSS Mainpowerisabnormal

    OVERLOAD Overloadofoutput

    BYPASS Bypassoutput

    FAULT Systemfault

    BAT.LOW Warningofbatterylowvoltage

    ALARM Systemalarm

  • 8/13/2019 Usermanual-11295075930

    65/66

    65

    Appendix3:

    Dial

    Switch

    Set

    of

    Module

    and

    Charger

    1.DialSetofAddressforModuleInputPowerConnectorDependingonthepowersegment,theDIPswitchintheinputpowerconnectorcanbesetas

    follows:

    Dialswitch(0meansOFFand1meansON)

    1 2 3 4

    10KVA 1 0 0 0

    15KVA 1 0 0 0

    20KVA 1 0 0 0

    30KVA 1 0 0 0

    40KVAupper

    partmodule

    1 0 0 0

    40KVAlower

    partmodule

    0 1 0 0

    60KVAupper

    partmodule

    1 0 0 0

    60KVAlower

    partmodule

    0 1 0 0

    Figure2DialSetofAddress

    2.DialSetofHardwareProtectionforChargerSetthesetdialswitchofbatterypiecesofcommunicationportinterfacesothatitcanbethe

    samewithactualbatterypiecestoprotectthebattery.

    Dialswitchisprotectedbyacover,soitshalltakeawaythecoverbeforeadjustthebattery

    pieceofdialswitch.

    Dialswitchsetsforallbatterypiecesare:

    Dialswitch(0meansOFFand1meansON)

    1 2 3 4

    20piecesof

    batteries

    0 0 0 0

    19piecesof

    batteries

    1 0 0 0

    18piecesof

    batteries

    1 1 0 0

    17piecesof

    batteries

    1 1 1 0

  • 8/13/2019 Usermanual-11295075930

    66/66

    16piecesof

    batteries

    1 1 1 1

    Forexample,figure3refertothesetof16piecesofbatteries.

    Figure3Thesetof16piecesofbatteries