user manual thermbox lot5

Upload: andykrsk

Post on 03-Mar-2016

14 views

Category:

Documents


0 download

DESCRIPTION

Инструкция термошкаф Emerson

TRANSCRIPT

EPC48180/1800-F1700A

ECM1500 Outdoor Cabinet

User Manual

VersionV1.0

Revision dateMay 31, 2012

BOMcustomization

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.Copyright 2009 by Emerson Network Power Co., Ltd.

All rights reserved. The contents in this document are subject to change without notice.Emerson Network Power Co., Ltd.

Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China

Homepage: www.emersonnetworkpower.com.cnE-mail: [email protected] Precautions

To reduce the chance of accident, please read the safety precautions very carefully before operation. The "Caution, Note, Warning, Danger" in this book and on the product do not represent all the safety points to be observed, and are only supplement to various safety points. Therefore, the installation and operation personnel must receive strict training and master the correct operations and all the safety points before operation.

When operating Emerson products, the operation personnel must observe the safety rules in the industry, the general safety points and special safety instructions specified in this book.If you purchase an outdoor power supply without SPD, you should install an SPD at the front-end of AC input, otherwise, the power supply system will generate over-voltage.

Electrical Safety

I. Hazardous voltage

Some components of the outdoor cabinet system carry hazardous voltage in operation. Direct contact or indirect contact through moist objects with these components will result in fatal injury.

Observe safety rules in the industry when installing the power supply system. The installation personnel must be licensed to operate high voltage and AC power.

In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets, bangles and rings.

When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment, precautions must be taken to keep moisture out of the power supply system.

"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during installation.

High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations.

To avoid electric shock hazard for outdoor environment and outdoor equipment, the non-professionals are prohibited to operate or maintain the outdoor power supply system.

II. Tools

In high voltage and AC operation, specialized tools must be used.

III. Thunderstorm

Never operate on high voltage, AC, iron tower or mast in the thunderstorm.

In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well earthed in time to avoid damage by lightning strikes.

IV. ESD

The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.

V. Short circuit

During operation, never short the positive and negative poles of the DC distribution unit of the outdoor cabinet system, or the non-earth pole of the outdoor cabinet system and the earth. The power supply system is a constant-voltage DC power device, short circuit will result in equipment burning and endanger human safety.

VI. Reverse connection

Never reverse-connect the AC input live line and neutral line, or else the system will be damaged.Check the polarity of the cable and connection terminal when performing DC live operations.

As the operation space in the DC distribution unit is very tight, please carefully select the operation space.

Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.

Use insulated tools.

In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of the human body and tool is reduced to a minimum.Battery

Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery connection method.

If customers prepare batteries themselves, the battery installation and maintenance should meet relevant safety standards.

Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs.

Before any operation on battery, pay attention to the following points:

1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.

2. Use specialized insulated tools.

3. Use eye protection device, and take preventive measures.

4. Wear rubber gloves and apron to guard against electrolyte overflow.

5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery upside down or slanted.Connection And Testing Of The Outdoor CabinetBefore installing subrack power supply in the cabinet, you should finish the connection and testing of the subrack power supply according to the corresponding subrack power supply user manual and then testing the outdoor cabinet.

OthersI. Sharp object

When moving equipment by hand, wear protective gloves to avoid injury by sharp object.

II. Power cable

Please verify the cable labels before connection.

III. Signal cables

The signal cables should be routed at least 150mm away from power cables.

Contents1Chapter 1 Overview

11.1 Model Description

11.2 Composition & Configuration

31.3 Operating Theory

41.4 Features

5Chapter 2 Installation

52.1 Safety Regulations

52.2 Installation Preparation

62.3 Mechanical Installation

62.3.1 Installing The Outdoor Cabinet

72.3.2 Opening And Closing Cabinet Door

82.4 Electrical Installation

82.4.1 Connecting Power Cables

102.4.2 Connecting Signal Cables

102.4.3 Sealing The Entry Holes

102.5 Battery Installation

112.6 Installation Check

12Chapter 3 Testing

123.1 Startup

123.2 Alarm Check And System Operation Status Check

123.3 Final Steps

13Chapter 4 Maintenance

134.1 Routine Maintenance

144.2 Replacing Parts Of Outdoor Cabinet

144.2.1 Replacing Environment Climate Control Unit

154.2.2 Replacing Fans

164.2.3 Replacing Door Status Sensor

174.2.4 Replacing TEC

18Appendix 1 Technical And Engineering Parameters

19Appendix 2 Schematic Diagram

Chapter 2 Overview

ECM1500 outdoor cabinet (outdoor cabinet for short) is a power supply system used outdoors. It provides outdoor protection and operation environment. It contains thermal control units and AC power distribution units. The cabinet can accommodate different Emerson subrack power supplies according to your requirement so as to form power supply systems with different capacities.

This chapter introduces the model description, composition & configuration, operating theory and features of the outdoor cabinet.2.1 Model Description

The outdoor cabinet is available in three models, configured with different models of thermal control unit (forced ventilation, heat exchanger and air-condition). Taking the forced ventilation model for example, the model description of the outdoor cabinet is given in Figure 1-1.

Figure 2-1 Model description

2.2 Composition & Configuration

Composition

The outdoor cabinet is composed of thermal control units, power distribution units and related structures. Three models of thermal control units are available: forced ventilation, heat exchanger and air-condition.

Configuration1. The configuration of the outdoor cabinet for the order is given in Table 1-1.Table 2-2 Configuration list of outdoor cabinet

ComponentConfiguration

Thermal control unitFan4 pieces

Environment climate control unit1 piece

air-condition 1 piece TEC

Power distribution unitAC power distributionTwo route 63A three-phase AC input MCB

Electrical plug connector 32A/380V, 3ph+N+PE for GensetThree route 32/1ph AC output MCBOne route 25A single-phase AC input MCB for heater

Residual current circuit breaker 16A with Euro-socket ~220V

DC power distributionTwo route 10A DC input MCB for TEC and fanThree route 32/1ph MCB for DC system

Power and reserved spaceSharing space: 15U, you can adjust space according to requirement

Door status sensor1 piece

The structure of the forced ventilation model outdoor cabinet is shown in Figure 1-2.

Figure 2-2 Structure of the forced ventilation model outdoor cabinet

2.3 Operating Theory

Heat dissipation theory for forced ventilation model outdoor cabinet

The cold air is sucked in through the front door air filter at the lower part of the outdoor cabinet. It passes through the battery compartment, user equipment and subrack power supply in turn. Finally, the hot air is discharged by the fans at the top of the outdoor cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown in Figure 1-3.

Figure 2-3 Heat dissipation access for forced ventilation model outdoor cabinet

Heat dissipation theory for heat exchanger model outdoor cabinet

A heat exchanger is fitted on the door of the outdoor cabinet. It can exchange the heat between the cold air outside the cabinet and the hot air inside the cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown in Figure 1-4.

Figure 2-4 Heat dissipation theory for heat exchanger model outdoor cabinet

Heat dissipation theory for air-condition model outdoor cabinet

An outdoor air-conditioner is fitted on the door of the outdoor cabinet to cool the cabinet. It is in this that the equipment and power modules in the cabinet are cooled. In case of air-conditioner fault or AC mains failure, the emergent ventilation units automatically startup to dissipate heat emergently, as shown in Figure 1-5.

Figure 2-5 Heat dissipation theory for air-condition model outdoor cabinet

2.4 Features Variable subrack power supply: The outdoor cabinet can accommodate standard 19 and 23 subrack power supply. Variable space: The power space, reserved space and the battery compartment space are interchangeable. You can adjust the space according to the actual requirement.

Thermal control unit: Three different models are available for your selection according to the local, environment and requirement.

Safety guideline: The equipment compartment satisfies IP*5 waterproof requirement and IP5* dustproof requirement.

Environment pollution level within the outdoor cabinets is 2.

Chapter 3 InstallationThis chapter introduces installation and cable connection. Strictly follow the instructions provided in this chapter to carry out the installation and cable connection.

3.1 Safety Regulations

Certain components in this power supply system have hazardous voltage and current. To ensure personnel safety, always follow the instructions below:

1. Only the trained personnel with adequate knowledge of the outdoor cabinet shall carry out the installation. The Safety Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during installation.

2. All external circuits below -48V connected to the power supply system must comply with the SELV requirement defined in IEC 60950.

3. To avoid electric shock, do not conduct any operation or maintenance within the outdoor cabinet under thunderstorm or humid weather.

4. Make sure that the outdoor cabinet is powered off before any operations can be carried out within the cabinet.

5. The power cables should be routed and protected properly, so that the cables are kept away from the operation and maintenance personnel.

3.2 Installation Preparation

Unpacking inspection

The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by representatives of both the user and Emerson Network Power Co., Ltd.

To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the equipment is correct and complete. Make sure that the equipment is delivered intact.

Preparing tools

The installation tools are given in Table 2-1. The tools must be insulated and ESD-proof processed before they are used.Table 3-1 Installation tools

ToolSpecificationToolSpecification

Combination wrench (hatch, club)Wrench set (10#, 13#, 16#, 18#, 21#)Box wrench16mm

Adjustable wrench200mmCross screwdriver 100mm, 200mm

Electrician diagonal pliers150mmSlotted screwdriver100mm, 200mm

Electrician sharp nose pliers150mmWire cuttersMaximum 300mm2

Steel tape5mHydraulic-pressure compaction pincherMaximum 300mm2

Electric knifeNormal typeDigital multimeterThree and a half bit digital display

GradienterNormal typeImpact electric drillWith 14 impact aiguille

BlinkersTo prevent splashPower socket With 5m cable

Fireproof mudConfigured in the accessoriesSafety shoesTo prevent puncture and for insulation

Hammer

3.3 Mechanical Installation3.3.1 Installing The Outdoor Cabinet

The outdoor cabinet must be installed directly onto the cement floor.

Step 1: Mark the specific installation position of the outdoor cabinet

It is recommended to determine the installation position in compliance with the clearance requirements given in Table 2-2.

Table 3-2 Installation clearances

FrontTopLeftRightBack

Clearances750mm700mm100mm100mm100mm

Step 2: Install expansion bolts

For forced ventilation model outdoor cabinet, by referring to Figure 2-1; for heat exchanger model and air-condition model outdoor cabinet, by referring to Figure 2-2, it is recommended to enlarge the installation size of the cabinet base because of the existence of the anti-toppling device (see Figure 2-3), determine the exact central points of the installation holes on the floor, and mark them with a pencil or oil pen. Use the electric drill (aiguille: 14) to dig holes (depth: 70mm) at the marked points. Clean the drilled holes off dust. Put the expansion bolts into the holes and knock them with a hammer till they are totally in.

Figure 3-1 Installation size 1 of the cabinet base (unit: mm)

Figure 3-2 Installation size 2 of the cabinet base (unit: mm)Step 3: Fix the cabinetMove the cabinet to the installation position. Make the installation holes on the base coincide with those dug on the floor. Screw the M10 anchor bolt down into the expansion pipe in the floor.

Pay attention to move the cabinet from the pallet in factory and install the anti-toppling device, as shown in Figure 2-3.

After installation, the cabinet should stand firmly no matter how it is shaken, then you can remove the anti-toppling device from the inside of the cabinet.

Figure 3-3 Anti-toppling device

3.3.2 Opening And Closing Cabinet Door

You need to open and close the cabinet door during the cabinet installation, operation and maintenance. Procedures for opening and closing the cabinet door are as follows:

Step 1: Insert the key into the keyhole, and turn the key clockwise until the door handle pops out.

Step 2: Turn the handle counter-clockwise 90, as shown in Figure 2-4. Pull the handle until the door opens.

Figure 3-4 Turning the handle

Step 3: Adjust the door stay bar to the position shown in Figure 2-5 to prevent the door from closing automatically.

Figure 3-5 Door stay bar

Step 4: Restore the door stay bar to its original position and close the door. Finally, turn the handle to its original position and press it down until a click is heard.

3.4 Electrical Installation

All the cables must be put through metal pipes for protection. The metal pipe should be connected to the PE bar reliably. Plastic coated metal hoses are recommended.

Earth cable and AC input cables enter the cabinet through the right side of the cabinet bottom. Signal cables, user equipment cables and DC cables enter the cabinet through the left side of the cabinet bottom.3.4.1 Connecting Power CablesConnecting earth cableStep 1: Cut the cable bushings covering the cabling holes (shown in Figure 2-6) on the bottom plate of the cabinet with an electrician knife.

Step 2: Lead the earth cable into the cabinet through a cabling hole, and route it along the cable holders, as shown in Figure 2-6. Step 3: Connect one end of the earth cable to the earth terminal in the cabinet, and solder the other end to the earth metal base reliably.

Step 4: Use nylon cable ties to tie the earth cable to the cable holders.

Figure 3-6 Positions of earth terminal and cabling hole

Connecting AC input cablesIf the outdoor cabinet has been installed Emerson matched subrack before delivery, the AC cable connection between subrack and cabinet should have been done by Emerson. You only need to connect the AC input cables according to the subrack user manual.

If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 220V AC power to the AC input MCB on the right side of the cabinet (shown in Figure 2-6), so as to ensure the cabinet operation.

Connecting DC cables

If the outdoor cabinet has been installed Emerson matched subrack before delivery, the DC cable connection between subrack and cabinet should have been done by Emerson. You only need to connect load cables according to the subrack user manual.

If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 48V DC power to DC input terminal on the left side of the cabinet (shown in Figure 2-7), so as to ensure the cabinet operation.

3.4.2 Connecting Signal CablesThe ECCU inside the outdoor cabinet provides four pairs of alarm output dry contacts for the user. All the dry contact outputs need to be led out from the ECCU. The silkprint of the alarm output dry contacts is shown in Figure 2-7.

Figure 3-7 Position of signal output

When connecting alarm cables, you should peel the signal cables and insert their ends into the corresponding terminals, and then tighten the screws on the terminals.The functions of the dry contact are given in Table 2-3.

Table 3-3 Dry contact functions

Port No.Definition Remark

1, 2Over temperature alarmNormally open (configurable)

3, 4Fan failureNormally open (configurable)

5, 6Door alarmNormally open (configurable)

7, 8General alarm (temperature low alarm, humidity high alarm, humidity low alarm, temperature and humidity sensor failure alarm, waterlogging alarm, smoke alarm)Normally open (configurable)

3.4.3 Sealing The Entry Holes

After cable connection, use fireproof mud to seal the cabling holes (shown in Figure 2-6).

3.5 Battery Installation

The battery compartment can accommodate a battery string of capacity not higher than 50Ah. Batteries are classified into front-terminal battery and general battery. Note

1. The batteries may carry dangerous current. Before connecting the battery cables, make sure all the battery input MCBs are off.

2. Make sure that the battery cable polarities are correct. Otherwise, both the battery and the cabinet will be damaged!3. Insulate the installation tools. Be careful not to damage the plastic battery case or the battery terminals during installation. Check before installation

1. Check that the battery shells are in good condition.

2. Check that the polarities of the terminals are in accordance with the polarity marks on the battery shell.

3. Check that the terminal screws are fastened.

Installation procedures

Note 1. When installing two battery strings or more, install the lower battery string first. While removing them, remove the upper battery string first.

2. This chapter is applicable to Emerson subrack and battery cables. It is a reference when you configure subrack and battery cables for yourself.

Step 1: Open the battery MCBs and AC input MCBs.

Step 2: Place the batteries one by one in the battery compartment from right to left, with distance between adjacent batteries at least 10mm.

Step 3: Remove the battery terminal covers, and connect the plate electrodes between the batteries in turn. Note that the mid-voltage sampling cable should be connected to the plate electrode between the second and the third batteries.

Step 4: Connect the positive battery cables (red) in the battery compartment to the battery positive terminals. Connect the negative battery cables (black) in the battery compartment to the battery negative terminals. Attach the acid and alkali integration box (battery accessory) to the internal side of the right panel of the cabinet.

Step 5: After installing the battery strings, use the 3M double-side adhesive tape pasted on the battery temperature sensor to paste the sensor onto the center of the upper-layer battery string.

Step 6: Measure the battery string voltage. If the voltage value is correct, replace the battery terminal covers.

3.6 Installation Check

After installation, check the installation against the list given in Table 2-4.Table 3-4 Installation check listCheck itemNo.Description

Cabinet installation1Check that the cabinet is level, upright and steadily fixed

2Check that all bolts are tightened, especially those in electrical connections, that all bolts have plain washers and spring washers, and that the washers are not reversed

3Check that there are no irrelevant materials in the cabinet, and clear them away if any

4Check that the cabinet paint is intact. If there are scratches, paint them immediately with antirust paint to prevent corrosion

5Clean up the cabinet

6Check that the door can move freely, the locks are in good condition and the door stay bar is fixed

7Check that the dummy plates are installed at the reserved space where no customer device is installed. Check that the burglarproof components (if configured) and battery baffles (if configured) are installed

Electrical connection1Verify the specifications of all MCBs and cables

2Check the correctness of bus bar connections, input and output cable connection, and connection between the power system and the system grounding

3Check the correctness of the batteries number and connection, and battery strings polarities

4Make sure all the cable connections are firm and reliable

5Check the connection point, line sequence and polarities of DC cables. Check the connection polarities of the batteries. Check that the connection points are fixed and the cable connections are correct and reliable

6Check that the cables are tidy, and the cable binding is normative

Chapter 4 Testing

This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing. This testing should be done after the subracks in the cabinet are tested.

4.1 Startup

Note Before the test, inform the chief manufacturer representative. Only the trained electrical engineer can maintain and operate this equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles and rings.During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries and property damage. Before the test, check the equipment to ensure the proper earthing.Make sure that the AC input and DC input are normal.

Forced ventilation check

After power-on, the heat control board enters self testing and the fans accelerate to full speed gradually. After a few minutes, the fans stop. If the environmental temperature is about 35C, the fans will operate at low speed.

Heat exchanger check

After power-on, the simple control unit enters self testing and the fans accelerate to full speed gradually. After a few minutes, the fans stop. If the environmental temperature is about 35C, the internal fans will operate at low speed and the external fans will stop.

Air-condition check

After power-on, the air-condition starts to operate. If the environmental temperature is about 35C, the internal fans of the air-condition will operate at low speed and the compressors of the external fans will stop.

4.2 Alarm Check And System Operation Status Check

Alarm checkDisconnect the thermal control units, so as to check that if the thermal control units can trigger thermal control unit alarm.

System operation status check

There should be no alarms during normal system operation.4.3 Final StepsOKComments

Disconnect all test equipment from the outdoor cabinet and make sure that materials irrelevant to the equipment have been all removed. (

Restore the outdoor cabinet to its original condition and close the cabinet door. (

Check and handover the equipment that the user has purchased. (

Note down all the operations taken, including time of the operation and name of the operator.(

If any defect is found in this equipment, inform the personnel responsible for the contract.

If repairing is needed, please fill in the FAILURE REPORT and send the report together with the faulty unit to the repairing center for fault analysis.

Chapter 5 MaintenanceThis chapter describes the routine maintenance, alarm and fault handling, and part replacement of the power supply system. Note1. The maintenance must be conducted in compliance with relevant safety rules.

2. Only the trained personnel with adequate knowledge about the outdoor cabinet shall work on the internal parts of the system. 5.1 Routine MaintenanceInspect the power supply system periodically and shoot the troubles in time if any. The routine maintenance items are given in Table 4-1.Table 5-1 Routine maintenance list

ItemPeriodInspection methodGuide

Thermal control unitOnce half a yearVisual inspectionCheck alarm and operation states. If the thermal control units run abnormally, refer this chapter to replace relevant components

Paint and galvanization layer on the cabinetOnce half a yearVisual inspectionIf there is any paint peeling or scratches, mend the painting immediately

Front door air filter (for forced ventilation model and air-condition model)Once half a yearVisual inspectionIf dust accumulated on the front door air filter, loosen the fixing screws of the air filter cover of the front door (shown in Figure 4-1). Then take off the air filter cover and brush off the dust. If the air filter is damaged, replace it. Finally, replace the air filter cover

Figure 5-1 Air filter5.2 Replacing Parts Of Outdoor Cabinet

5.2.1 Replacing Environment Climate Control Unit

Appearance and terminal layout

The appearance of the environment climate control unit is shown in Figure 4-2, and the terminal layout is shown in Figure 4-3.

Figure 5-2 Environment climate control unit

Figure 5-3 Terminal layout of the environment climate control unit

DIP switch description

DIP switch function description and setting method:

1. Bit 1 ~ 4 are used to set addresses of the environment climate control unit. OFF: 0, ON: 1. Default address: 16. The setting method of the environment climate control unit (ECCU for short) is given in Table 4-2.

Table 5-2 Setting method of ECCU address

Bit 4Bit 3Bit 21Bit 1Address

000016

00011

00102

111115

Bit 1 ~ Bit 4 have been set in factory. You can change the settings according to your communication requirement.

2. The function description and setting method of Bit 5 ~ Bit 8 are given in Table 4-3.

Table 5-3 Function sescription and setting method of Bit 5 ~ 8

Bit No.FunctionSetting methodDefault value

5Choose cabinet modelOFF: heat exchanger model

ON: forced ventilationON

6Choose dry contact alarm modeOFF: normal when open; alarm when closed

ON: normal when closed; alarm when openON

7*Choose sensorOFF: serial port termperature & humidity sensor ON: temperature sensorON

8Choose whether stopping fans when AC mains failsOFF: No

ON: YesOFF

Note*: When Bit 7 is placed to ON position, ECCU has no humidity acquisition function

Replacing procedures of the ECCU

Step 1: Loosen the two fixing screws to remove the cover, and then you can see the ECCU. The position of cover is shown in Figure 4-4.

Figure 5-4 Cover position

Step 2: Disconnect J15 terminal (shown in Figure 4-3), and then disconnect the rest connection terminals on the ECCU.

Step 3: Loosen the fixing screws on the ECCU. Replace the ECCU with a new one.

Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the LED_FAULT (shown in Figure 4-3) indicator show correctly. Under normal instance, the LED_FAULT indicator is power-off.

Step 5: Place the DIP switch to the correct position according to Table 4-2 and Table 4-3.

Step 6: Press the SW1 self-test button (shown in Figure 4-3) to ensure that the fan can start normally.

Step 7: Replace the cover of the ECCU.

5.2.2 Replacing Fans

Fan alarm circuit

The fan-cooling unit of the outdoor cabinet is mainly composed of 2 ~ 4 axial flow fans. The fan alarm circuit is shown in Figure 4-5.where the blue line is the alarm line.

Figure 5-5 Illustration of the fan alarm circuit

Fan replacing procedures

Follow the following procedures to replace the fan.

Step 1: Make sure that the fan-control terminals (J1 and J2 are hot pluggable) on the environment climate control unit are inserted firmly. The fan-control terminals are shown in Figure 4-3.

Step 2: Ensure that Bit 5 of SW100 switch is put to the ON position.

Step 3: Press the SW101 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables are perfect.

Step 4: Loosen the fixing screws at the cabinet top cover to open the top cover. (Opening the top cover, pull it forward and then lift up its front not more than 30. Otherwise the top cover will be fallen.)

Step 5: Disconnect the fan power terminals at the top of the cabinet. Use a multimeter to measure the voltage between the positive power cable and the negative power cable. Check if the voltage is close to the DC output voltage (54.0V).

If the fan power voltage is normal, the fans are damaged. Carry out the next step.

Step 6: Loosen the fixing screws of the fans and replace the fans, as shown in Figure 4-6.

Figure 5-6 Fan position

Step 7: Reconnect the fan power terminals, and press SW1 self-test button (shown in Figure 4-3) to ensure that the fan can startup normally.

Step 8: Replace the cabinet top cover.

5.2.3 Replacing Door Status Sensor

There is a door status sensor installed in the cabinet for detecting the close or open status of the cabinet door. The alarm will be eliminated only when the cabinet door is closed.

The door status sensor requires no particular maintenance; just replace it when it is damaged. If the door is closed, while the door status sensor alarm occurs, the sensor must have been damaged. The position of the sensor is shown in Figure 4-7.

Remove the sensor top cover and then the two screws. Replace the old sensor with a new one and finally fix the sensor and the signal cables with the screws.

Figure 5-7 Position of the door status sensor5.2.4 Replacing TECStep 1: Switch off the TEC MCB, as shown in Figure 4-8. Disconnect all the cable connectors.

Figure 5-8 AC input MCB position

Step 2: Loosen the fixing screws of TEC to remove and replace TEC.

Appendix 1 Technical And Engineering Parameters

Table 1 Technical parameters

Parameter categoryParameterDescription

EnvironmentalOperating temperature-10C ~ +45C (forced ventilation model), -40C ~ +45C (heat exchanger model), -40C ~ +50C (air-condition model)

Storage temperature-40C ~ +70C

Relative humidity5%RH ~ 100%RH

Altitude 2,000m (derating is required above 2,000m)

OthersNo conductive dust or erosive gases. No possibility of explosion

EMCConducted emissionClass A EN55022

Radiated emission

Immunity to EFTLevel 3 EN61000-4-4

(1) Immunity to ESDLevel 3 EN61000-4-2

(2) Immunity to SurgesLevel 4 EN61000-4-5

Immunity to radiationLevel 3 EN61000-4-3

Immunity to conductionLevel 3 EN61000-4-6

OthersSafety regulationCompliant with IEC60950-1, IEC60950-22

Insulation resistanceAt temperature of 15C ~ 35C and relative humidity not bigger than 90%RH, apply a test voltage of 500Vdc. The insulation resistances between AC circuit and earth, DC circuit and earth, and AC and DC circuits are all not less than 10M

Insulation strength(Remove the SPD, monitoring module and rectifiers from the system before the test.)

AC circuit to earth: 50Hz, 2,500Vac DC circuit to earth: 50Hz, 1,000Vac Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac

AC to DC circuits: 50Hz, 3,000VacFor all the three tests above, there should be no breakdown or flashover within 1min, with leakage current not bigger than 10mA

MTBF100,000hr

ROHSCompliant with R5 requirement

MechanicalDimensions (mm)Cabinet800 (W) 750 (D) 2500 (H)

Internal space of battery compartment613 (W) 575 (D) 400 (H)

Table 2 Spart part list

PartSpecification or modelBOM

FanDC axial flow fan32010191

FanDC centrifugal fan32010261

Appendix 2 Schematic Diagram

Figure 1 Schematic diagram of heating and cooling

Figure 2 Schematic diagram of AC Power Distribution Unit

Figure 3 Schematic diagram of forced ventilation model outdoor cabine

_1400076779.dwg

_1400324776.dwg