user manual
TRANSCRIPT
DACHENG
DCSF-C SERIES SERVO MOTOR
User Manual
(Ver8.34)
Zhejiang Dacheng Electric Co., LTD
DDAACCHHEENNGG Dacheng Electric
2
Contents
Chapter 1 Introduction
1.1 Name plate
1.2 Naming rules
1.3 Standard Specification
Chapter 2 System Installation
2.1 Connecting and Installation
2.2 Confirmation Items
2.3 Attention for Using
Cautions 2.4 Installation Method
Chapter 3 System Wiring
3.1Standard Wiring
3.2 Wiring Specification
3.3 Wiring method
3.4 Considerations
3.5 Terminals
3.5.1 DCSF-C Terminals
3.5.2 Encoder Signal Input Terminal CN1(15 cores)
3.5.3 AI/ AO Terminal CN2(44cores)
3.5.4 Telecommunication Terminal CN3(9 cores) 3.6Input/ Output Interface Type
3.6.1 DI Interface
3.6.2 AI Interface
3.6.3 Encoder Signal Output
3.6.4Encoder Z Signal Collector Unconnected Output Interface
Chapter 4 Keyboard Operation Parameter and Display
4.1 Panel Instruction
4.2 Menu Operation Instruction
4.3 Specific Operation Instruction
4.4 Control Parameter
4.5 Alarm Parameter
Chapter 5 Standard Control Wiring
5.1 Speed Control
5.1.1 Internal Speed Control(Pr90=0)
5.1.2 External Analogue Speed Control(Pr90=2)
External Analogue Torque Control(Pr90=3)
5.1.3 Preinstall Curve Speed Control(Pr90=4)
DDAACCHHEENNGG Dacheng Electric
3
5.1.4 Computer Speed Control(Pr90=8)
5.1.5 Location Control(Pr90=6)
5.1.6 Location Curve Control((Pr90=5)
5.1.7 Pressure Closed Loop Control(Pr90=9)(Applicable for Injection Machine) 5.1.8 Braking Resistor Configuration Table 5.1.9Injection Machine Servo Configuration Table
Chapter 6 Supervisory Software
6.1 Brief Introduction
6.2 Software Installation
DDAACCHHEENNGG Dacheng Electric
4
Brief introduction to DCSF-C series ac servo controller DCSF-C series servo drivers are the products that we have co-developed with
Harbin Institute of Technology and we have the proprietary intellectual property rights. The series of servo drivers adopt the latest Digital Signal Processing Chips of American TI company and CPLD as core control chip. The implement of the advanced vector algorithms together with our successful experience in automatic control field has helped realize the design optimization of servo driver’s software and hardware. Adaptive control algorithm can adapt parameters dynamically and improve the accuracy and speed of system control according to the change of controlled objects. Besides, we use the imported IPM to ensure the perfect protection, reliable operation and stable performance. Our company has proved the reliability of our servo drivers through a large number of product application, thus to guarantee you use our DCSF-C series servo drivers in a safe and reliable way. Power grade: 100W-15kW single phase 220V, three phase 380 V optional Power grade: 100W-15kW single phase 220V, three phase 380 V optional Position transducer: incremental photoelectric encoder, rotary transformer available Protection functions: over voltage, under voltage, short circuit, over current, over
load, encoder anomaly and so on Speed mode: +10V---- -10V different bipolar analog input 8 segments internal speed control 5 segments speed curve control RS232 digital speed control Position mode (mixed logic) Pulse+ directional level control (mixed logic) Two-way orthogonal pulse position input control(pulse phase displacement) (mixed logic) RS232 digital position control Frequency dividing output of encoder pulse 1-4096 Internal electronic gear Digital input & output: 7 ways input, 4 ways output Analog voltage output: -10V---+10V for the users to use instead of external power supply Internal braking, feedback energy absorption circuit The currency of current loop and speed loop can be up to 20kHz. RS232 real-time digital control
DDAACCHHEENNGG Dacheng Electric
5
Thank you very much for choosing our DCSF-C series servo motors. Please read the instruments carefully before your operation of our products. please contact us, if you have any question or suggestion.
Tel:0575-82165222 Fax:0575-82168183
Servo Production Section of Zhejiang Dacheng Electric
http://www.zjdacheng.cn
Please pay special attention to these warning signs while reading this manual: Warning: wrong operation may cause disastrous results----death or serious injury
Careful: wrong operation may make the operators hurt or get the equipment damaged
Attention: improper operation may damage the product or equipment.
Safety Rules
The design and manufacturing of our products are not to use in the
machinery or systems that threaten people’s safety. when choosing our products for your machines or systems, you must
take safety measures into consideration during designing and
manufacturing, to avoid accidents caused by improper operations. 。
Inspection
The damaged or faulted products can’t be used.
Transportation
The products must be stored and transported according to the given
terms.
the products can’t be piled in excess to prevent fall.
DDAACCHHEENNGG Dacheng Electric
6
the products should be packed perfect during transshipment.
While moving the machines, you mustn’t drag the power cord, motor shafts or the encoders.
Both servo motors and servo drivers can’t burden the external forces
or bumps.
Installation
Servo drivers and motors:
The machines can’t be fit on or near inflammables to prevent fires. Vibration should be avoided, and shock is forbidden.
Installation is prohibited, when there’s any damage or loss of parts.
Servo drivers:
The machine must be installed in the control cabinet with enough
safety production level.
Enough space must be kept between other equipments.
Good radiation condition must be available.。
Prevent dust, caustic gas, electric conduction objects, liquid or flammable explosive materials getting in.
Servo motor:
The installment must be firm to prevent loose caused by vibration.。
liquid invasion must be prevented, which may cause damage to machines
and encoders.
Any knock to the motors or motor shafts is forbidden to avoid damage
to encoders.
The motor shafts can’t bear the load pasts the limits. Connection
The personnel taking part in the connection or inspection must be well
qualified.
Connection and inspection can’t be done until 5 minutes later.
The servo drivers and motors must be well earthed.
There is probable bombs or operation accidents if the voltage or power
polarity is wrong.
Earthing can be done after the installment.
Ensure the power cord insulative; avoid pressing the power cord to
avoid electric shock.
Connection must be right and firm, otherwise, running errors may occur
or equipments may be damaged because of poor contact.
Don’t apply the reverse polarity to U、V、W terminators or connect
alternating current.
Servo motors and drivers should be connected directly, and electric
DDAACCHHEENNGG Dacheng Electric
7
capacity, the inductance or the filter can’t be put in.
Prevent the electric conduction fastener and the electricity end from
entering into the machine.
The electric wire and the heat non-resistant body cannot draw close
to radiator of the servo driver and the servo machinery.
The freewheel diodes can’t be applied reversed, which are joined up
in parallel to DC relays to output signals.
Debugging and running
Before energizing, make sure servo drivers and motors are properly
installed, well fixed, and the voltage and connection are right.
While debugging, the machine should firstly have no-loading running
to make sure the parameters right, then take load debugging to avoid the damage
to machinery and equipments caused by wrong operation.
Application
A emergency circuit should be plugged in, so that the equipment can
stop and the power supply be off immediately
Before resetting an alarm, you must make sure the running signal is
off other wise the machine will restart suddenly.
The servo drivers must be used together with the specified and assorted
motors.
Don’t turn on and off the power supply frequently, which may damage the system.
The servo drivers and motors may feel hot after continuous running.
Don’t touch the drivers, radiators or machines Don’t adapt servo systems. Fault handling
even if the servo drivers are off power, the high pressure will still
last for a period of time. So please don’t take the power cord apart
in five minutes or touch the terminal plate.
people taking part in disassembly and repair should have relevant
knowledge and operation capacity.
After alarming, faults must be cleared. And reset the alarm before
reset the machine.
while the power is on after momentary interruption, keep away from the
machine, because it may start abruptly.(The design of the machine should make
sure that no danger be caused when restarting.)
System matching
DDAACCHHEENNGG Dacheng Electric
8
The rated torque of the servo motors must be higher than effective
continuous load torque.
The ratio of load inertia and the motor inertia should be smaller than
the recommended value.
The servo driver and motor should be a match.
Chapter 1 Brief Introduction
1.1 Name plate
1.2 Naming rules for different models
DCSF-C150S220V40 Servo Driver
Series C、 D、 U、Y Series
Power Grade 100W-15kW
Voltage Grade 220V/380V
Version V1.0-V8.0
DCSF-C: Universal Servo Driver
DCSF-D: High Performance Servo Driver
DCSF-U: Dedicated Servo Driver (made to order by customers)
DCSF-Y: Servo Driver for Hydraulic Pressure Only
DDAACCHHEENNGG Dacheng Electric
9
1.3 Standard Specification
Model DCSF-C150 DCSF-C200 DCSF-C750 DCSF-C1100
Single phase AC220V Three phase
220V
Three phase
AC380V
Input Power
50/60Hz
Power 100W-1.5KW 1.5KW-2.2KW 2.2KW-5.5KW 5.5KW-15KW
Control Method ①Location Control②Speed Control③Torque Control④JOG Running
Regenerative Braking Internal
Control Input ①forward rotation servo enabled②backward rotation servo enabled
③ forward rotation driven prohibited④ backward rotation driven
prohibited⑤Speed option 1 ⑥Speed option 2 ⑦Speed option 3⑧
Torque/speed limited option
Control Output ①Servo Ready ②Servo Alarm③positioning completed④speed arrival
⑤zero speed
Impulse
frequency
Max Input0~500kHz(displacement input),Max Input0~200kHz(collector
input)
Electronic
gear
1/50≤1~30000/1~30000≤500
Control
precision
0.036
Input method ① Pulse + symbol ②forward pulse/reverse pulse ③two phase A/B
orthogonal pulse(positive logic )
④ pulse + symbol ⑤forward pulse/backward pulse ⑥two phase A/B
orthogonal pulse(negative logic )
Programmable
Speed
Control
8 bit field internal programmable speed control
Feedback
impulse
2500 line/revolution, 10000 impulse/revolution
Location
control
Torque limit 0~±10VDC(max value match max torque)
Speed control Speed scope 1:5000
DDAACCHHEENNGG Dacheng Electric
10
Speed
response
frequency
500Hz
Speed
fluctuation
rate
<±0.03%(load 0~100%);<±0.02%(power supply -15~+10%)
Torque rate 0~±10VDC(max value matching rated torque)
Analog Input 0~±10VDC(source impedance less than 10kΩ) Torque
control Speed limit 0~±10VDC(max value matching rated speed)
Surveillance function Running speed, current location, command pulse accumulation ,
location deviation, motor torque, motor current, bus voltage, running
status, input/ output terminal signal and so on
Protecting function Over speed 、 main power source over-voltage or under-voltage,
over-load, over-current, encoder anomaly, main circuit overheat,
location out-of- tolerance and so on
Appropriate load inertia Less than 15 times the rotor inertia(when load inertia is 5 times
more than rotor inertia, you should connect external braking
resister.)
Temperature At running:0~5 At store:-20~75
Humidity 40%~90%(free from condensation)
Air pressure 86~106kPa
Environmental
condition
Vibration ≤5G
Cooling mode Cold wind
Chapter 2 System Installation
2.1 Wiring and Installation
1、 Have PE end grounded firmly and no other grounding method. Otherwise, it may
cause electric shock.
2、 Please connect wires correctly. Misconnecting U\V\W can make the machine unable
to work properly.
3、 Don’t use “On/Off” of the power to start/ stop the servo drivers.
4、 Please use servo enabled switches to start / stop the motor.
5、 Before starting cabling, changing wiring, inspection, maintenance, or moving,
please firstly cut off the power. After three minutes, measure with a voltmeter,
DDAACCHHEENNGG Dacheng Electric
11
and operate after confirming safety.
The interval between other equipments should be over 10mm for abstraction of
heat.
Special warning for wiring: 1、the three-phase power cord from motor to driver can’t be connected wrong, (blue, white, red -----U V W) 2、the encoder wire from the motor to encoder must get connected before energization. It is forbidden to connect after energization. 3、The controller should match the motor. Don’t change the motor or driver.
2.2 Confirmation items
After the arrival, please open the package and check the following contents.
confirmation item confirmation method
Make sure the model is what you have
ordered Confirm by name plate and model
Check if the product is damaged or notLook at the appearance to check if there’s
something broken
Check if the shaft of the motor is free
to rotate
Rotate with hand. Pivoted means normal.
But, braking servo motor can’t do this.
Check if the screws get off or loose Take a look
If you find anything unusual, please contact our distributors or offices at once.
2.3 Attention for using
Installation environment
1、 Protecting Servo controllers must be installed in well-protected cabinets and they should
be kept away from corrosive matters, flammable gases, conductive materials,
metal powder, oil and liquids.
2、 Temperature\ humidity Ambient temperature should be no higher than 50C and
long-term continuous working temperature should be below 40 C and good
ventilation should be provided for abstraction of heat.
3、 Vibration and shock Drivers should be installed to avoid vibration, shock absorption
measures to be taken.
Environment condition
1、 Usage temperature and humidity 0--55(free from freezing) below 90%FS(free from condensation)
2、 Storage temperature -20--85 below 90%FS(free from condensation)
3、 Altitude
DDAACCHHEENNGG Dacheng Electric
12
Lower than 5000m
Cautions 1、 The storage and installation of this product must satisfy environmental
requirements. And original package is necessary.
2、 The stacking of our products is limited. it’s improper to stack too many together to prevent pressure damage or fall.
3、 The products must be installed with fire prevention materials. Don’t install on flammable items or near to prevent fires.
4、 It’s forbidden to drag all the cords from servo controllers and encoders
5、 After cutting off the power supply, there’s high voltage in most big
capacitances. Reconnect the power five minutes later. Don’t get the power on
and off frequently in a short time.
Fig. 2.1 Servo driver installation Diagram
2.4 installation method
1、 Installation direction The normal installation direction of the servo driver is upright vertical.
2、 Installation and fix Tighten the four M6 fixed screws in the rear part of the servo driver while
installing.
Installation spacing
Look at Diagram 2.1 for reference of the space between the drivers and other
equipments.
3、 Radiation The servo drives take use of natural cooling. The cooling fans should
DDAACCHHEENNGG Dacheng Electric
13
be installed in the cabinets to ensure adequate ventilation
conditions. Installation cabinet environment
During installation of electrical control cabinet, prevent dust or iron
filings entering into the servo drivers and causing short circuit.
Chapter 3 System Wiring 3.1 Standard wiring
DDAACCHHEENNGG Dacheng Electric
14
Fig.2.2 Servo Controller Standard Wiring
3.2 Wiring Specification
DDAACCHHEENNGG Dacheng Electric
15
1、 We suggest you use insulating cold pressure terminals and make sure firm connection.
2、 We suggest you use three phase isolation transformer for power supply. 3.3 Wiring Method
1、 For the input and output signal wire and encoder wire, please use the shielded one. The length should be: input wire: within 5m; encoder signal wire: within
15m. Condition permitting, the shorter the wire is, the better.
2、 One end of the grounding wire should be earthed. And the diameter of the wire must be no less than 1mm.
3、 In the environment with serious disturbance, noise filter is suggested to be installed. While installing, pay attention to the following items:
Try to install the noise filter, the servo driver and the supervisory
controller as close as possible.
You must fit in the coils of the relay, electromagnetic contactor and
brake the surge suppressors.
Don’t make the main circuit and the signal wires go through the same
pipeline, nor tie them together.
4、 When there are intensive interference sources used nearby(such as welding machines, high-power machine tools and so on), use isolation transformers
with input power source.
5、 Please fit a no-fuse breaker to cut off the external power supply when there’s a trouble in running.、
3.4 Cautions
1、match the wiring of U、V、W with terminal A,B,C respectively. You can not make
the motor run backward by changing the wiring of three phase terminals.。
2、Because of a lot of electrolyte and capacitance in the servo drivers, there
is still high voltage in the internal circuit even if the power is off. So please
electrify servo drivers five minutes later. Please cut off the power supply if you
don’t use the machine for a long time. Definition of rotating direction: Facing
the machine shaft, rotating shaft rotating in an anticlockwise direction is called
Forward Rotation; on the other hand, it is Backward Rotation.
3.5 Terminal
3.5.1 DCSF-C terminal
Terminal
mark Signal name Function
R
S
T
Main circuit
power Three phase AC220V 50Hz
P+ Rectify anode
output Braking output , connect braking devices between P+
DDAACCHHEENNGG Dacheng Electric
16
BP Control
terminal
U Output machine
power U phase
V Output machine
power V phase
W Output machine
power W phase
PG Grounding Grounding
Wrong wiring of U、V、W will make the motor unable to run properly. So please be
sure to wire correctly.
Special Attention needed: PB,P are terminals of external braking resistors.
Generally, there’s no need to connect external braking resistors when PB, P
terminals are impending. When there’s too much regenerative energy during slowing
down, which can’t be absorbed completely, AL-05 will be overloaded and give an alarm.
Increase deceleration time. If there is still alarm, attach braking resistors to
PB and P Terminals, who range from 100 to 200Ω, and the power is from 100 to 500
W. the smaller the resistance value is, the larger the current is , the power of
the braking resistor needed is larger. However, too small resistance value can cause
damage to the driver. So make trials from big resistance value to smaller ones, until
it doesn’t alarm. The connection of external braking resistor must be done 10min
after driver’s power outage and the internal high voltage has gone. Because PB and
P are connected with internal high voltage circuit, so please don’t touch the
Terminal PB and Terminal P in case of electric shock. And avoid collision between
Terminal PB, Terminal P and other terminals to prevent damage to drivers because
of short circuit.
3.5.2 Encoder Signal Input Terminal CN1(15 cores)
Terminal
No. Symbol Signal Name Function
1 A+ Encoder A+ Input Connect with Photoelectric Encoder A+
2 A- Encoder A- Input Connect with Photoelectric Encoder A-
3 B+ Encoder B+ Input Connect with Photoelectric Encoder B+
4 B- Encoder B- Input Connect with Photoelectric Encoder B-
5 Z+ Encoder Z+ Input Connect with Photoelectric Encoder Z+
6 Z- Encoder Z- Input Connect with Photoelectric Encoder Z-
7 U+ Encoder U+ Input Connect with Photoelectric Encoder U+
8 U- Encoder U- Input Connect with Photoelectric Encoder U-
9 V+ Encoder V+ Input Connect with Photoelectric Encoder V+
10 V- Encoder V- Input Connect with Photoelectric Encoder V-
11 W+ Encoder W+ Input Connect with Photoelectric Encoder W+
DDAACCHHEENNGG Dacheng Electric
17
12 W- Encoder W- Input Connect with Photoelectric Encoder W-
14 +5V 5V power supply Supply photoelectric encoder of servo
motor with +5V power source
15 GND
(+15V) GND(+15V) (The motor adopts rotating transformer)
3.5.3 AI/ AO Terminal CN2(44cores)
Terminal
No.
Symbol Signal Name Function
1 Z+ Encoder splitting Z+ output
2 Z- Encoder splitting Z- output
3 CZ Z Collector open-drain output
4 GND
5 IN0 Digital input port 0 Servo forward running drive
En
6 IN1 Digital input port 1 Servo backward running drive
En
7 IN2 Digital input port 2 Speed option 1
8 IN3 Digital input port 3 Speed option 2
9 IN4 Digital input port 4 Speed option 3
10 IN5 Digital input port 5
11 IN6 Digital input port 6
12 COM+
13 GND
14 +24V 24v power supply output 300mA
15 Reserve
16 A+ Encoder splitting A+ output
17 A- Encoder splitting A- output
18 OUT1 Digital Output Port 1
19 OUT2 Digital Output Port 2
20 OUT3 Digital Output Port 3
21 OUT4 Digital Output Port 4
22 COM-
23 AD1 Analog speed input
24 AGND Analog Ground
25 AD2 Analog Running Torque Input
26 AGND Analog Ground
27 +10V Internal +10V Analog Power supply 100mA
DDAACCHHEENNGG Dacheng Electric
18
28 Reserve
29 -10V Internal -10V Analog Power Supply 100mA
30 Reserve
31 B+ Encoder splitting B+ output
32 B- Encoder splitting B- output
33 PLUS+ Position Pulse Input A+
34 PLUS- Position Pulse Input A-
35 PDIR+ Position Pulse Input B+
36 PDIR- Position Pulse Input B-
37 PCLR+ Position Clear Input CLR+
38 PCLR- Position Clear Input CLR-
39 Reserve
40 Reserve
41 Reserve
42 Reserve
43 Reserve
44 Reserve
3.5.4 Telecommunication Terminal CN3(9 cores)
1 Reserve
2 TXD Send
3 RXD Accept
4 Reserve
5 GND Ground wire
6 Reserve
7 Reserve
8 Reserve
9 Reserve
3.6 Input/ Output Interface Type
3.6.1 DI Interface
DDAACCHHEENNGG Dacheng Electric
19
Fig.3.6.1.1 DI Interface
A Relay Connection
B Photoelectric coupler connection
Fig.3.6.1.2 DO Interface
1、 OUT1,OUT2,OUT3,OUT4 Max. load current: 100mA,Max. working voltage: 32V。
2、Customers can provide the external power source. Pay special attention to the
power polarity while wiring. Wrong polarity connection can cause damage to drivers.
3、In case of lagging load such as relays, connect antiparallel freewheel diodes
at the two ends. Attention: inverse wiring can cause damage to the drivers.
4、Output transistors are Darlington ones. While conducting, the pressure drop
between the collector and the emitter is around 1v, which can’t satisfy the
DDAACCHHEENNGG Dacheng Electric
20
low-level requirement. So don’t connect the transistors with integrated
circuit.
3.6.2 AI Interface
Fig3.6.2Analog difference-mode input
1、 Analog ground wire connecting with the negative input end at the controller side. 2、 The input voltage should be within the range of -10V-+10V, otherwise, the driver
may be damaged.
3、 Shielded wire for connecting id preferred. Try to make the wire as short as possible to decrease the noise disturbance3.6.3 Encoder signal output Encoder
signal is put out by way of differentially driven. The Ground wire of the
controller and driver must be grounded safely3、When using rotating transformers,
the signal has turned into the one that is compatible for rotating encoder.
4、While rotating transformer is used, the 15th foot of the plug is not the ground
wire, but the +15V signal.
DDAACCHHEENNGG Dacheng Electric
21
Fig 3.6.3 encoder output interface
3.6.4 Z signal of encoder through open collector output
Fig3.6.4 Z signal of encoder through open collector output
The signal of Z phase in encoder through open collector output when Z signal appears,
start output, or otherwise it will be cut off.
While the pulse of the encoder’s signal of Z phase is very narrow, high-speed Opt
coupler is advised.(such as453,pc9000,4504)
3.6.5 input interface of pulse
1、In order to transmit data correctly, the difference drive method is adopted.
2、Under the difference drive method, adopting AM26C31,75176 or RS422
similar line drivers
3、Adopting the single-ended drive, the supply of external power are provided by
users, do not apply the reverse polarity to the actuator unit.
DDAACCHHEENNGG Dacheng Electric
22
Fig. 3.6.5 input interface of pulse
PUL+/PUL-,DIR+/DIR-:
The power supply is ok when input TTL differential method:
The power supply is ok when input the differential method is TTL
When input the single-ended drive, we have to connect 24v to the other end of
resistance in switching tube, and link GND to the outflow end of current if
using internal 24V; while using external power, don’t connect the internal
24v to the external power,, and voltage drop of user’s switching tube is lower
than 1V , increasing external resistance value appropriately if it is higher
than this value .The choice of external resistance value
R=(12~24V)/(10~20ma),the resistance power is 1W.For single-ended method, it
must be done to connect GND to reference ground of Console, either internal
or external power supply.
There are six kinds of pulse input, as shown in the list below:
Pulse instruction
type Mark Description
Pulse group mark PUL
DIR
Positive logic( PUL mark +DIR pulse)*2
Forward pulse group
Reverse pulse group
PUL
DIR
Positive logic(forward pulse/ reverse pulse)*2
A phase pulse group
B phase pulse group
PUL
DIR
Positive logic(two phase instruction pulse)*4
Pulse group mark PUL
DIR
negative logic(PUL mark +DIR pulse)*2
Forward pulse group
Reverse pulse group
PUL
DIR
Reverse logic(forward pulse/ reverse pulse)*2
A phase pulse group
B phase pulse group
PUL
DIR
Negative logic(two phase instruction pulse)*4
Chapter four The illustration and operating data of Keyboard
4.1 Panel Description
The panel is composed of six LED displays and 5 keys
DDAACCHHEENNGG Dacheng Electric
23
Key Name Introductions
MENU:For choose the mode of the first floor or from another layer
return to the first layer
multiply key: represent add serial number or numerical increment
Reduced key: represent reduce serial number or numerical decrease
Start button: starting motor
Enter key: for fixing next layer or setting parameter values
4.2 Operating instructions of menu
Enter or quit menu or back to the previous menu by pushing MENU button
The first level:
five kinds of mode
DSP---:display mode
PRG---:parameter setting mode
JOG---:running mode
AUT---:zeroing mode
EEP---:parameter Management Mode
The second level
1、DSP Show Selection
1:SPd Display Speed (r/min)
2:Cod Display Encode (Pulse Count)
3:dCU Bus Voltage (V)
4:I-b b Phase current
5:CoJ Pole Position
6:I-q q Shaft Current
7:I-d d Shaft Current
8:I-A A Phase Current
9:CdH Feedback pulse high 5 bytes
10:CdL Feedback pulse low 5 bytes
11:PdH Control pulse high 5 bytes
12:PdL Control pulse low 5 bytes
13:Cnt position curve segment
14:Ad1 analog signal 1(analog collecting digital value)
15:Ad2 analog signal 2(analog collecting digital value)
16:Iod terminator input state
MENU ↑ ↓ OK
↑
↓
OK
MENU
DDAACCHHEENNGG Dacheng Electric
24
Show 1 for the high level signal, No show for the low level signal
2、PRG parameter setting selection:Pr01-Pr198
3、JOG trial operation:(pushing button,the motor sets up,pushing
button,then stop working)
4、AUT((the second level) zeroing:
AJ automatic measuring angles
pushing button,automatic measuring zero
angles of magnetic pole
pushing button,The motor stop measuring zero
angles of magnetic pole
LJ measuring angle by hand
pushing button, set up,pushing button
adjust zeroing angle
pushing button,The motor stop measuring zero
angles of magnetic pole
AL Zeroing of Current Sensor
pushing button,The motor stop adjusting zero
angles of Current Sensor automatically
io digital output testing
pushing button,automatic output testing
5、EEP backup and restore::SA Storing,LF adjust default value,bF backup,HF
restore,Er software version(see8.08)
Parameter management method details
EEP-SA write parameter Write the parameters of list in EEPROM parameter
zone
EEP-BF parameter backup Write the parameters of list to EEPROM backup zone
EEP-HF restore parameter Read the data of EEPROM backup zone in the
OK
OK
OK
↓ ↑
OK
OK
DDAACCHHEENNGG Dacheng Electric
25
parameter table
EEP-LF restore default values Read the default values of parameter in the
parameter table
EEP-Er the date of software
version Show the production software version
4.3 operating instructions
in the first menu, pushing b button,Choose any kinds of 5 modes。
Finished by pushing button
Enter the second menu.。Pushing \ button again, to modify parameter
or function If finished, pushing
Button .If Modification completed, please push button,and return
to the previous page,Then pushing
Button to choose ERP,pushing button then
pushing button to choose EEP-SA again,pushing button to
write
the parameters of list in EEPROM parameter zone, in order to save the parameter in
after power failure.
the digitals have changed more rapidly if clicking button again
and again when modification. It helps to modify big numbers quickly.
4.4 control parameters(it is useful if tick”*”)
Serial
number name unit
default
value range
notes
Pr-01 Test running speed r/min 200 unchanging
Pr-02 Maximum speed
limits r/min 1500 0-5000 *
Pr-03 encoder electrical
angle
0.144angl
e 1200 0-2500 *
Pr-04 U phase current zero 0 ±5000
Pr-05 U phase current zero 0 ±5000
Pr-06 analog signal 1 gain 1000 1-5000
Pr-07 analog signal 1 zero 0 ±5000
Pr-08 analog signal 2
gain
1000 0-5000
Pr-09 analog signal 2
zero
0 ±5000
Pr-10 internal speed 1 r/min 100 ±5000 *
Pr-11 Internal speed 2 r/min 200 ±5000 *
↓ ↑
↓ ↑
OK MENU
↓ ↑
OK
OK ↓ ↑
↓ ↑
OK
DDAACCHHEENNGG Dacheng Electric
26
Pr-12 Internal speed 3 r/min 300 ±5000 *
Pr-13 Internal speed 4 r/min 400 ±5000 *
Pr-14 analog signal 1
filtering
0.1ms 1 1-50
Pr-15 analog signal 2
filtering
0.1ms 1 1-50
Pr-16 internal speed 5 r/min 500 ±5000 *
Pr-17 Internal speed 6 r/min 600 ±5000 *
Pr-18 Internal speed 7 r/min 700 ±5000 *
Pr-19 Internal speed 8 r/min 800 ±5000 *
Pr-20 speed loop Kp 0.001 500 0-5000
Pr-21 speed loop ki 0.0001 10 0-5000
Pr-22 speed loop kc 0.001 200 0-5000
Pr-23 speed loop kd 0.001 0 0-1000
Pr-24 maximum limit of
positive current in
speed loop
500
0-5000
Pr-25 maximum limit of
negative current in
speed loop
-500
-5000-0
Pr-26 Response frequency
of speed loop
10 1-50
Pr-27 acceleration time ms 100 0-30000
Pr-28 deceleration time ms 100 0-30000
Pr-29 minimum limit of
analog speed
r/min 0
±100
0
unrestraine
d
Pr-30 current loop kp 0.001 900 0-5000
Pr-31 current loop ki 0.0001 200 0-5000
Pr-32 current loop kc 0.001 400 0-5000
Pr-33 current loop kd 0.001 100 0-1000
Pr-34 maximum limit of
current loop and
positive current
1000
0-5000
Pr-35 maximum limit of
current loop and
negative current
-1000
-5000-0
Pr-36 maximum limit of
current loop and
positive weak
magnet
900
0-5000
DDAACCHHEENNGG Dacheng Electric
27
Pr-37 maximum limit of
current loop and
positive weak
magnet
-900
-5000-0
Pr-38 Encoder output
frequency
1 1-4096
Pr-39 carrier
frequency0-10khz
1-8khz 2-6khz
3-4khz
hz 0
0-3
Pr-40 rated current
(current
protection)
ampere 5
1-20
Pr-41 the auto-zero motor
choice
0 0:below
1kw
1:above
1kw
Pr-42 maximum speed for
position control
200 -5000-+50
00 *
Pr-43 the rate of location
curve change
200 -5000-+50
00 *
Pr-44 return time of
location curve
change
0.1s 10
0-1000 *
Pr-45 default display of
nixie tube
1 1-16
The details
seen 4.2
Pr-46 maximum speed limit
of torque
200 -3000-300
0
Pr-47 direct-current and
bus voltage gain
100 1-200
Pr-48 direct-current and
bus voltage zero
0 -3000-300
0
Pr-49 retain
Pr-50 the goal of speed
curved section 1
100 0-5000 *
Pr-51 add-subtract time
of speed curved
section 1
10ms 100
0-30000 *
Pr-52 the goal of speed
curved section 2
200 0-5000 *
Pr-53 add-subtract time
of speed curved
section 2
10ms 100
0-30000 *
Pr-54 the goal of speed 300 0-5000 *
DDAACCHHEENNGG Dacheng Electric
28
curved section 3
Pr-55 add-subtract time
of speed curved
section 3
10ms 100
0-30000 *
Pr-56 the goal of speed
curved section 4
400 0-5000 *
Pr-57 add-subtract time
of speed curved
section 4
10ms 100
0-30000 *
Pr-58 the goal of speed
curved section 5
500 0-5000 *
Pr-59 add-subtract time
of speed curved
section 5
10ms 100
0-30000 *
Pr-60 holding time of
speed curved
section 1
10ms 100
0-30000 *
Pr-61 holding time of
speed curved
section 2
10ms 100
0-30000 *
Pr-62 holding time of
speed curved
section 3
10ms 100
0-30000 *
Pr-63 holding time of
speed curved
section 4
10ms 100
0-30000 *
Pr-64 holding time of
speed curved
section 5
10ms 100
0-30000 *
Pr-65~
69
retain
Pr-70 Position kp 50 1-200
Pr-71 Position kc 10 1-200
Pr-72 electronic gear
numerator
1 1-30000
Pr-73 electronic gear
denominator
1 1-30000
DDAACCHHEENNGG Dacheng Electric
29
Pr-74 Input pulse type:
1 : orthogonal AB
pulse (positive)
2:positive pulse+
direction
(positive)
3:positive pulse +
reverse pulse
(positive)
4 : orthogonal AB
pulse (negative)
5:Pulse + direction
(negative)
6:positive pulse +
reverse pulse
(negative)
1
1-6
Pr-75 type of the Encoder
output pulse
0:orthogonal pulse
dividing frequency
1:pulse + direction
channels
2:synchronization
between positive
and reverse pulse
3:Synchronous of
orthogonal pulse
0 0-3
Pr-76~
89
retain
Pr-90 Selection of
Control Mode
( 0internal speed
control 2
modulating control
3 torque control
4preset the speed
control of velocity
curve 5 position
curve control 6
position control 7
he position
controlled by
computer 8 speed
controlled by
computer
0 0 0-8
DDAACCHHEENNGG Dacheng Electric
30
Pr-91 On Mode ( 1 : Not
Displayed 0 :
Display)
0 0
Pr-92 the display of
manually zero(1:
current0:angle)
0 0
Pr-93 0 : The maximal
efficiency control
1the maximum power
control
0
Pr-94 0:pc not on-line
1:pcon-line
*
Pr-95 0light change
8rotary change
above5.5kw
Pr-96~99 retain
Pr-100 the cycles of the
position curve 0
*
Pr-101 The cycles
deviation of the
position curve 0
*
Pr-102 the speed of
position curved
section 0
*
Pr-103 retain *
Pr-104 the cycles of the
position curved
section 1
*
Pr-105 The cycles
deviation of the
position curved
section 1
*
Pr-106 the speed of the
position curved
section 1
*
Pr-107 retain *
Pr-108 the cycles of the
position curved
section 2
*
Pr-109 The cycles
deviation of the
position curved
section 2
*
DDAACCHHEENNGG Dacheng Electric
31
Pr-110 the speed of the
position curved
section 2
*
Pr-111 retain *
Pr-112 the cycles of the
position curved
section 3
*
Pr-113 The cycles
deviation of the
position curved
section 3
*
Pr-114 the speed of the
position curved
section 3
*
Pr-115 retain *
Pr-116 the cycles of the
position curved
section 4
*
Pr-117 The cycles
deviation of the
position curved
section 4
*
Pr-118 the speed of the
position curved
section 4
*
Pr-119 retain *
Pr-120 the cycles of the
position curved
section 5
*
Pr-121 The cycles
deviation of the
position curved
section 5
*
Pr-122 the speed of the
position curved
section 5
*
Pr-123 retain *
Pr-124 the cycles of the
position curved
section 6
*
Pr-125 The cycles
deviation of the
position curved
section 6
*
DDAACCHHEENNGG Dacheng Electric
32
Pr-126 the speed of the
position curved
section 6
*
Pr-127 retain
Pr-128 the cycles of the
position curved
section 7
*
Pr-129 The cycles
deviation of the
position curved
section 7
*
Pr-130 the speed of the
position curved
section 7
*
Pr-131 retain
Pr-132 the cycles of the
position curved
section 8
*
Pr-133 The cycles
deviation of the
position curved
section 8
*
Pr-134 the speed of the
position curved
section 8
*
Pr-135 retain
Pr-136 the cycles of the
position curved
section 9
*
Pr-137 The cycles
deviation of the
position curved
section 9
*
Pr-138 the speed of the
position curved
section 9
*
Pr-139 retain
Pr-140 the cycles of the
position curved
section 10
*
Pr-141 The cycles
deviation of the
position curved
section 10
*
DDAACCHHEENNGG Dacheng Electric
33
Pr-142 the speed of the
position curved
section 10
*
Pr-143 retain
Pr-144 the cycles of the
position curved
section 11
*
Pr-145 The cycles
deviation of the
position curved
section 11
*
Pr-146 the speed of the
position curved
section 11
*
Pr-147 retain
Pr-148 the cycles of the
position curved
section 12
*
Pr-149 The cycles
deviation of the
position curved
section 12
*
Pr-150 the speed of the
position curved
section 12
*
Pr-151 retain
Pr-152 the cycles of the
position curved
section 13
*
Pr-153 The cycles
deviation of the
position curved
section 13
*
Pr-154 the speed of the
position curved
section 13
*
Pr-155 retain
Pr-156 the cycles of the
position curved
section 14
*
Pr-157 The cycles
deviation of the
position curved
section 14
*
DDAACCHHEENNGG Dacheng Electric
34
Pr-158 the speed of the
position curved
section 14
*
Pr-159 retain
Pr-160 the cycles of the
position curved
section 15
*
Pr-161 The cycles
deviation of the
position curved
section 15
*
Pr-162 the speed of the
position curved
section 15
*
Pr-163 retain
Pr-164 the cycles of the
position curved
section 16
*
Pr-165 The cycles
deviation of the
position curved
section 16
*
Pr-166 the speed of the
position curved
section 16
*
Pr-167 retain
Pr-168 the cycles of the
position curved
section 17
*
Pr-169 The cycles
deviation of the
position curved
section 17
*
Pr-170 the speed of the
position curved
section 17
*
Pr-171 retain
Pr-172 the cycles of the
position curved
section 18
*
Pr-173 The cycles
deviation of the
position curved
section 18
*
DDAACCHHEENNGG Dacheng Electric
35
Pr-174 the speed of the
position curved
section 18
*
Pr-175 retain
Pr-176 the cycles of the
position curved
section 19
*
Pr-177 The cycles
deviation of the
position curved
section 19
*
Pr-178 the speed of the
position curved
section 19
*
Pr-179 retain
Pr-180
-198
retain
4.5Alarm parameters
name description
AL-01 Module protection
AL-02 Over speed Protection
AL-03 wiring error of encoder
AL-04 the wiring error of motors
AL-05 overvoltage protection
AL-06 over-current protection
AL-07 zero-coding error
AL-08 zero error for the electrical wiring,
AL-09 renewable electrical braking
AL-10 no signal of encode
AL-11~12 reserve
PID adjust introductions:
1 Speed Kp:the greater the value, the higher the gain, the greater the rigidity.
the determination Of parameter calculating according to specific type and load of
the servo drivers. Under normal circumstances, the greater the load of inertia, the
greater the value. There are no shocks in the system, the larger setting as much
as possible.
2、Speed Ki:the greater the value, the faster the rate, the greater the rigidity.
the determination Of parameter calculating according to specific type and load of
the servo drivers. Under normal circumstances, the greater the load of inertia, the
smaller the value. There are no shocks in this system ,the larger setting as much
as possible.。
3、Location Kp:the greater the value, the higher the gain, the greater the rigidity.
DDAACCHHEENNGG Dacheng Electric
36
Under the same frequency instruction pulse,the smaller the position lag.
There are no shocks in this system, the larger set as much as possible.
4、Current Kp:the greater the value, the higher the gain, the smaller the current
tracking error. However, the higher the gain, will have noise or vibration. This
parameter has something to do with servo driver and mnotors, having nothing to do
with loading.There are no shocks in this system, the larger setting as much as
possible.
5、Current Ki:the greater the value, the faster the rate, the smaller the current
tracking error. However, the higher the gain, will cause the noise or vibration.
This parameter has something to do with servo driver and mnotors, having nothing
to do with loading. Under normal circumstances, the smaller the electromagnetic
motor constant, the smaller the integration time constant. There are no shocks in
this system, the larger setting as much as possible.
6、Feed forward set Methods: The speed can be fed through the open-loop control of
the servo system to accelerate the speed of response, when speeding up the feed
forward gain to reduce the accumulation of position loop error, thus speeding up
the error rate of compensation .In theory analysis, the current speed gain increases,
the smaller the total error value of location loop, that is, the smaller the integral
role. But too much feed forward gain easily lead to oscillations and location
overshoot, In addition, the actual system in the ideal differential link doesn’t
exist, so the link can not gain too much, at the same time, in order to ensure accuracy
of the positioning servo system, integral control is essential points
DDAACCHHEENNGG Dacheng Electric
37
Chapter five Standard control wiring
5.1 Speed control
5.1.1 Internal speed control(Pr90=0)
DDAACCHHEENNGG Dacheng Electric
38
S1, S2, S3 description
0 0 0 choose internal speed 1 Pr10
0 0 1 choose internal speed 2 Pr11
0 1 0 choose internal speed 3 Pr12
0 1 1 choose internal speed 4 Pr13
1 0 0 choose internal speed 5 Pr16
1 0 1 choose internal speed 6 Pr17
1 1 0 choose internal speed 7 Pr18
1 1 1 choose internal speed 8 Pr19
DDAACCHHEENNGG Dacheng Electric
39
5.1.2 the external simulate rate-controlling(Pr90=2)
the external simulate torque controlling(Pr90=3)
DDAACCHHEENNGG Dacheng Electric
40
5.1.3 Preset rate-controlling curve (Pr90=4)
Note: the speed section controlled by the parameters Pr-50~64
DDAACCHHEENNGG Dacheng Electric
41
5.1.4 controlling of computer rate(Pr90=8)
1:The communications are RS232, agreement is:57600, n,8,1 2:Communicationformat:0x55+controlsignal(1byte)(00110011)+High-speed+low-speed
DDAACCHHEENNGG Dacheng Electric
42
bytes +0xAA
5.1.5Position control(Pr90=6)
the choice of the input mode(Pr74) ①pulse + mark ②positive pulse +reverse pulse ③ two-phase A/B orthogonal pulse
DDAACCHHEENNGG Dacheng Electric
43
(positive logic)④ pulse + mark ⑤ positive pulse /reverse Pulse
⑥two-phase A / B orthogonal pulse (negative logic)
5.1.6 the control of position curve(Pr90=5)(to realize the synchronization of XY
axis in CNC machine tools if use two servos)
Note: the location controlled by the parameters Pr-100 ~ 180,If use two servos can
be realized the synchronization of XY axis in CNC machine tools while simultaneously
DDAACCHHEENNGG Dacheng Electric
44
reach the location of mutual connection and synchronization signal.
5.1.7 Pressure Closed Loop Control(Pr90=9)(Applicable for Injection Machine)
Note: This function controlled by the parameters Pr80, Pr81, Pr82, Pr83, Pr84 ,Pr85, Pr86.
DDAACCHHEENNGG Dacheng Electric
45
5.1.8 Braking Resistor Configuration Table Motor Power(kW)
Renewable Resistor
Power(W) Renewable Resistor Maximum(Ω)
Renewable Resistor Minimum (Ω)
1.5 300 400 130 2.2 300 250 130 3.7 500 150 78 5.5 800 100 39 7.5 1000 75 39 11 1500 50 26 15 2000 40 26 18.5 4000 32 20
Note: This table is just for the reference, details are determined on the value of load inertia matched by motor. 5.1.9Injection Machine Servo Configuration Table
The Maximum
mould locking force
of Injection Machine (T)
System Pressure (MPa)
Matching Oil Pump
Matching
Motor
Matching
Driver
Matching transducer
55 16 QT42-31.5F-
A
DCM-UBF190P75 DCSF-U1100S380V8.34
HUBA511.943003742
80 16 QT42-31.5F-
A
DCM-UBF190P11
0 DCSF-U1500S380V8.34
HUBA511.943003742
120 16 QT52-50F-A DCM-UBG190P11
0 DCSF-U1500S380V8.34
HUBA511.943003742
150 16 QT52-63F-A DCM-UBG190P15
0 DCSF-U1800S380V8.34
HUBA511.943003742
200 16 QT52-63F-A DCM-UBG190P18
0 DCSF-U2200S380V8.34
HUBA511.943003742
250 16 QT52-63F-A DCM-UBG190P22
0 DCSF-U3000S380V8.34
HUBA511.943003742
280 16 QT62-125F-A DCM-UBG190P30
0 DCSF-U3700S380V8.34
HUBA511.943003742
320 16 QT62-125F-A DCM-UBG190P37
0 DCSF-U4500S380V8.34
HUBA511.943003742
380 16 QT62-125F-A DCM-UBG190P45
0 DCSF-U5500S380V8.34
HUBA511.943003742
Note: This table is just for the reference, details are determined on the value of oil pump output matched by motor.
DDAACCHHEENNGG Dacheng Electric
46
Chapter VI Monitoring software 6.1 Summary DCSFC series AC servo driver is high-performance servo controller independently developed by our company , this software is the monitoring software can be used for
monitoring synchronous development of DCSFC series AC servo drivers ,so that we
can clearly observe the various parameters and status of motor running , while the
software also has real-time control functions, for providing services for a variety
of applications of computer control systems
6.2 software Installation
The software for the green software, it runs as long if only it is easily copied ,
USB communications is available
Open” DCSFC”, the following dialog appears:
to choose the communication interface and baud rate. Entering the following
interface by click "OK "button:
Technical Department
2008-07-21