UPS sizing rev 1.3 1 Show information... Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key. Click the APC logo link to jump back to the previous showed slide. Click the left margin area to jump to the index (“List of contents”) From the index -links, you may jump to any other subjects. - use the APC-return logo to return to the index slide again .

Upload: suzanna-norris

Post on 02-Jan-2016

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

1

Show information...Show information...

•Navigation links: Move the cursor across the links and wait for the “hand” symbol

•- then click left mouse key.

•Click the APC logo link to jump back to the previous showed slide.

•Click the left margin area to jump to the index (“List of contents”)

•From the index -links, you may jump to any other subjects.

• - use the APC-return logo to return to the index slide again .

Page 2: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

2

UPSUPSSizingSizing

Page 3: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

3

List of contentsList of contents

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Page 4: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

4

AC Load SpecificationAC Load Specification

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

AC load spec.

Page 5: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

5

The complete AC load specification includes:

AC Load SpecificationAC Load Specification

UPS load specifications

Example

kVA….……17

kW……..…...

Iload……………

PF…….….0,8

CF……..…3,5

kVA : Apparent power load (S) - kVA

kW : True power load (P) - kW

Iload : Phase current, IL1, IL2, IL3 - on load

PF : Power factor

CF : Crest factor

AC load spec.

Page 6: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

6

DP300E output specificationDP300E output specificationProduct range...Product range...

UPS load specifications:

VA……………. ?

W……………... ?

Iload………...… ?

PF……………. ?

CF……………. ?

DP300E output specifications:

kVA……...10 - 480

kW…..…..10 - 480

Iout…...14,5 - 693A

Pfinductive load…...0,8

Pfcapacitive load…..0,9

PFSMPS..…0,6 - 1,0

CF……Unlimited

DP310E - DP3480E UPS load ?

AC load spec.

Page 7: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

7

Load power - kVA and kWLoad power - kVA and kW

Apparent load

UPS load specifications

kVA …………….

kW …………….

Iload ……….……

PF ………...…..

CF ……...…….

AC load spec.

kWkVA =

PF

kW = kVA x PF

True load

P = I x V x PF

Page 8: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

8

Load phase current - ILoad phase current - IL1, L1, IIL2, L2, IIL3 L3

The max phase current is the highest possible load current from one phase

This value is very important when sizing the UPS

UPS load specifications

kVA…..……..

kW……..……

Iload……………

PF…………..

CF………….

IL1, IL2, IL3 , find max ILoad

Max loadphase current

Iload1

Iload2

Iload3

AC load spec.

Page 9: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

9

Power factor - PFPower factor - PF

W PF =

VA

Indicate the PF load working area when quoting to avoid later mistakes

Please consult APC if the load PF is outside the Silcon DP300E series specifications

AC load spec.

UPS load specifications

kVA …………….

kW …………….

Iload ……….……

PF ………...…..

CF ……...…….

Power factor is defined as “True power” divided by “Apparent power”

DP300E output capability:PFinductive load……… 0,8PFcapacitive load…….. 0,9PF SMPS…………… 0,6 - 1,0

Page 10: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

10

Crest factor - CFCrest factor - CF

Ipeak

CF = IRMS

Silcon DP300E series has a CF limiting feature which ensures that a load specified with a high CF will be limited to approximately a value of 3

- and the inverter will cope with this without derating

The consequence of above is that you can...

AC load spec.

UPS load specifications

kVA …………….

kW …………….

Iload ……….……

PF ………...…..

CF ……...…….

Page 11: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

11

Required information...Required information...

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Required info.

Page 12: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

12

Let´s make it...Let´s make it...

Step

By

Step

Required info.

Page 13: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

13

Required load informationRequired load information- finding the right UPS size...- finding the right UPS size...

Required info.

What is the right DP300E UPS size…?

kVA/ kW!

Max phase current

Max phase kVA load

orMax total kVA load at symmetrical load

Max kW load

and PF

1

2

3

one of these...

Page 14: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

14

When max load When max load currentcurrent is specified... is specified...

The Silcon DP300E series output capability is always specified at unity PF

The highest phase current therefore determines the UPS size Do the following if the max. load current is included in the

customers specification:

LOAD:

Max specified current:

3 x I load max >

DP300E - UPS:

Full load output current

3 x I out max

For 3-phase systems the current from the phase with the biggest load has to be used.

Required info.1

Page 15: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

15

Max. Max. kVAkVA load and load and PFPF specified specified

For 3-phase systems: - multiply highest loaded phase by 3

By symmetrical load, use the total kVA load

By unsymmetrical load, use the highest phase kVA load.

LOAD:

Max specified kVA:

SVA max >

DP300E - UPS:

Output power

Sout max

Required info.2

Page 16: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

16

Max. kW load only specified...Max. kW load only specified...

You need to know both kW and PF...

The kW as the only load specification is not sufficient information - unless the PF is unity !

LOAD:

>

Required info.

kWkVA =

PF

DP300E - UPS:

Output power

Sout max

3

Page 17: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

17

Inrush CurrentInrush Current

Equipment Inrush current/nom current Duration Power Factor

normal service

Computer CPU 6 to 10 2 to 8 cycles ind. 0,8 - 0,9

Computer Peripherals (printers etc.) - old computers 4 to 8 1 to 15 sec. 0,8 - 0,9

Incandescent lights 6 to 18 2 to 8 cycles 0,9 - 1,0

Motors 4 to 8 1 to 15 sec. 0,7 - 0,8

Battery chargers 6 to 10 2 cycles 0,6 - 0,8

Unregulated DC power supply 6 to 10 2 cycles 0,7 - 0,8

Transformer 6 to 10 2 cycles same as load

Required info.

Computer Peripherals (printers etc.) - modern computers 3 to 6 1 to 10 sec. 0,9 - 1,0

Page 18: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

18

Example 1...Example 1...

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Example...

Page 19: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

19

Example 1... Example 1... Power sizing the UPS...Power sizing the UPS...

kVA-loadPower factor on mixed loads

60 kVA/ kWPF =1

60 kVA/48 kW

PF = 0.8

Legacy UPS

system

?

DP300E

? 60 kVA60 kVA

UPS size = kVA load

Load 1: (8 kW / 0,8) = …..…….. 10 kVA

Load 2: (18 kW / 0,9) = ………. 20 kVA

Load 3: (30 kW / 1) = ……..…... 30 kVA

Sum of loads…... 56 kW…….……..……. Sum of loads…... 56 kW…….……..……. 60 kVA60 kVA

??70 kVA/ 56 kW

PF = 0,8

Legacy UPS system

?70kVA

UPS size = kVA and kW load

Example...

Page 20: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

20

Example 2... Example 2... Power sizing the UPS...Power sizing the UPS...

kW-load

Load 1: = …………..…..….. 10 kW

Load 2: =…………..………. 20 kW

Load 3: = ………..……..….. 30 kW

Sum of loads…………………………. 60 kWSum of loads…………………………. 60 kW

60 kVA/ kWPF =1

75 kVA/ 60 kW

PF = 0,8

Legacy UPS system

?DP300E

?75kVA

60 kVA

UPS load = Loads/ PF (0.8)

UPS load = Loads/ PF (1)

Power factor on loads = 1

Example...

Page 21: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

21

Silcon DP300E - Silcon DP300E - Power sizing the UPSPower sizing the UPS

Power sizing the DP300E UPSPower sizing the DP300E UPS Calculate the UPS-load in kVA

Define highest phase load

Choose the DP300E having its full load output power equal to - or bigger than the load

Additional considerations..

• Overload capacity• Redundancy• …….

- see the Power Binderfor further details

Additional considerations..

• Overload capacity• Redundancy• …….

- see the Power Binderfor further details

Page 22: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

22

Now - your turn...Now - your turn...

Page 23: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

23

Task 1Task 1

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Task 1

Page 24: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

24

Task 1 - Task 1 - Specify the UPSSpecify the UPS

Supply voltage…….3x400V - 50Hz

Supply current…….3x36A

Power Factor……….PF= 0,8

Crest Factor………...CF 3,2

Load specifications:

Task 1

Page 25: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

25

Silcon DP340EComments

• Ignore the PF and CF values

• In the Spec. Sheet /Quick Reference is found that:

• A Silcon DP320E has Iout 1/1 = 3 x 29A

• A Silcon DP340E has Iout 1/1= 3 x 57,7A

A Silcon DP320E is to small !

Task 1 - Task 1 - SolutionSolution

Solution:Solution:

Load specifications:

Supply voltage…….3x400V - 50Hz

Supply current…….3x36A

Power Factor……….PF= 0,8

Crest Factor………...CF 3,2

Task 1

Page 26: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

26

Task 2Task 2

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Task 2

Page 27: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

27

Task 2 - Task 2 - Specify the UPSSpecify the UPS

Supply voltage….….3x400V - 50Hz Phase current:I L1……………….12A PF 0,9 CF 2,7I L2……………….18A PF 0,8 CF 2,9I L3……………….17A PF 0,8 CF 3,0

Load specifications:

Task 2

Page 28: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

28

Solution: Silcon DP320EComments:

• Ignore the PF and CF values

• Take the highest phase current and compare it with the full load output currents listed in the data sheets

• Silcon DP310E has a full load output current of 3 x 14,5A

• I L2 requires 18A - so DP310E is not sufficient

A Silcon DP320E has to be used.

Task 2 - Task 2 - SolutionSolution

Solution:Solution:

Task 2

Load specifications

Supply voltage….….3x400V - 50Hz Phase current:

IL1……………….12A PF 0,9 CF 2,7IL2……………….18A PF 0,8 CF 2,9IL3……………….17A PF 0,8 CF 3,0

Page 29: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

29

Task 3Task 3

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Task 3

Page 30: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

30

Task 3 - Task 3 - Specify the UPSSpecify the UPS

Supply voltage….….3x400V - 50Hz

Phase power:P L1………………. 103 kW PF 0,9P L2………………. 106 kW PF 0,8P L3………………. 100 kW PF 0,8

Load specifications:

Task 3

Page 31: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

31

Solution: Silcon DP3480E

Comments:

• Phase PL2 has the highest kVA load

• SL2 = PL2/PFL2 = 106/ 0.8 = 132,5 kVA

• 3 x 132,5 = 397,5kVA

A Silcon DP3480E is the solution

Task 3 - Task 3 - SolutionSolution

Solution:Solution:

Task 3

Load specifications:

Supply voltage….3x400V - 50Hz Phase power:P L1………………. 103 kW PF 0,9P L2………………. 106 kW PF 0,8P L3………………. 100 kW PF 0,8

Page 32: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

32

Task 4Task 4

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Task 4

Page 33: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

33

Task 4 - Task 4 - Specify the UPSSpecify the UPS

Supply voltage….….3x380V - 50Hz

Phase power VA:S L1………………. 103 kVA PF 0,9S L2………………. 106 kVA PF 0,8S L3………………. 100 kVA PF 0,8

Load specifications:

Task 4

Page 34: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

34

Solution: Silcon DP3320E

Comments:

• Phase SL2 has the highest kVA load and decides the UPS size

• Stotal = 3 x SL2 = 3 x 106 = 318 kVA

A Silcon DP3320E is the solution

Task 4 - Task 4 - SolutionSolution

Solution:Solution:

Task 4

Load specifications:

Supply voltage….….3x380V - 50Hz Phase power VA:S L1………………. 103 kVA PF 0,9S L2………………. 106 kVA PF 0,8 S L3………………. 100 kVA PF 0,8

Page 35: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

35

Task 5Task 5

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review

Head linesHead lines

Task 5

Page 36: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

36

Task 5 - Task 5 - Specify the UPSSpecify the UPS

Supply voltage….….3x380V - 50Hz Phase power W:P L1………………. 35 kW PF 0,8P L2………………. 38 kW PF 0,8P L3………………. 40 kW PF 0,8

The motor load is included in the above spec.

Load specifications:

Task 5

•A 25 kW 3-phase motor (PF=0,8) is connected to the UPS (Inrush current is 6 x nominal in 15 sec. )

•The demand is that the motor has to be able to start in battery operation

Page 37: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

37

Solution: Silcon DP3160E…?

Comments:

• Phase L3 having the highest load

• SL3 = PL3/ PFL3 = 40/ 0,8 = 50 kVA

• 3 x 50 = 150 kVA

A Silcon DP3160E cut be the solution. But we have to check if the motor is able to start on battery operation...

Task 5 - Task 5 - SolutionSolution

Solution:Solution:

Task 5

Load specifications:

Supply voltage….….3x380V - 50Hz Phase power W:P L1………………. 35 kW PF 0,8P L2………………. 38 kW PF 0,8P L3………………. 40 kW PF 0,8

Page 38: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

38

CurrentL1 = 35 kW/ PF 0,8 / 220 V = 198,9 ACurrentL2 = 38 kW/ PF 0,8 / 220 V = 215,9 ACurrentL3 = 40 kW/ PF 0,8 / 220 V = 227,3 A

Current Motor = 25 kW/ PF 0,8 / 380V x 1,732 = 47,5 A

Inrush Motor = 47,5 A x 6 = 285 A

Inrush & load = 227,3 + (285-47,5) = 465 A

Task 5 - Task 5 - SolutionSolutionLoad specifications:

Supply voltage….….3x380V - 50Hz Phase power W:P L1………………. 35 kW PF 0,8P L2………………. 38 kW PF 0,8P L3………………. 40 kW PF 0,8

Task 5

Page 39: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

39

Solution: Silcon DP3240E

Comments

•DP3160E have 150% overload capacity of 346,5 A

•DP3240E have 150% overload capacity of 519 A

•A Silcon DP3160E can’t handle the start up of the Motor

A Silcon DP3240E is the solution

Task 5 - Task 5 - SolutionSolutionLoad specifications:

Supply voltage….….3x380V - 50Hz Phase power W:P L1………………. 35 kW PF 0,8P L2………………. 38 kW PF 0,8P L3………………. 40 kW PF 0,8

Task 5

Page 40: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

40

Solution: Silcon DP3240E

Comments•DP3160E have 150% overload capacity of 346,5 A

•DP3240E have 150% overload capacity of 519 A

•A Silcon DP3160E can’t handle the start up of the Motor

A Silcon DP3240E is the solution

Overload alarm...Overload alarm...Load specifications:

Supply voltage….….3x380V - 50Hz Phase power W:P L1………………. 35 kW PF 0,8P L2………………. 38 kW PF 0,8P L3………………. 40 kW PF 0,8

Task 5

Please observe….The Silcon DP3240E will generate an overload alarm

whenever the motor starts!!!

Page 41: UPS sizing rev 1.3 1 Show information... Navigation links: Move the cursor across the links and wait for the “hand” symbol - then click left mouse key

UPS sizing rev 1.3

41

ReviewReview

Review

AC Load Specification

Required information

Examples...

Task 1...

Task 2...

Task 3...

Task 4...

Task 5...

Review