undersanding power factor
TRANSCRIPT
-
8/14/2019 Undersanding Power Factor
1/35
Understanding PowerFactor
Presented by
Scott Peele PE
-
8/14/2019 Undersanding Power Factor
2/35
Understanding Power Factor
Definitions
kVA, kVAR, kW, Apparent Power vs. True Power
Calculations Measurements Power Factor Correction
Capacitors
System Impacts I2 R losses, Chapter 9 NEC
Equipment sizing
Power Factor Charges
Problems with adding Caps
Harmonic resonance
Volt rise
Power Factor vs Load Factor
-
8/14/2019 Undersanding Power Factor
3/35
What is Power Factor
Power Factor is the cosine of the
phase angle between current andvoltage.
Power Factor is the ratio of true
power to apparent power.
-
8/14/2019 Undersanding Power Factor
4/35
Understanding Alternating Current
AC
-200
-150
-100
-50
0
50
100
150
200
0
60 Hertz/second
Duration
Time
169 volts
120 Volts RMS
One Cycle
.01666 secondsVoltageL
evel
Magnitude
-
8/14/2019 Undersanding Power Factor
5/35
Phase Angle
-200
-150
-100
-50
0
50
100
150
200
0
Duration
Degrees
90
120 Volts RMS
One Cycle
180
270
360
o
o
o
o
VoltageL
evel
Magnitude
-
8/14/2019 Undersanding Power Factor
6/35
Three Basic Circuits or Loads
Resistive
Inductive Capacitive
Or any combination Resistive Inductive
Inductive Capacitive
Resistive Capacitive
Resistive Inductive Capacitive
-
8/14/2019 Undersanding Power Factor
7/35
Types of Loads
Resistive Incandescent LampResistance heat
Inductive Motors Contactor Coils Relays (coils)
Capacitive Capacitors Start Capacitors Run Capacitors Power FactorCorrection Capacitors
-
8/14/2019 Undersanding Power Factor
8/35
Resistive Loads
In Phase
-200
-150
-100
-50
0
50
100
150
200
0
voltage
Curre
n
t
Level
Magnitude
Duration
Time
-
8/14/2019 Undersanding Power Factor
9/35
Inductive Loads
Lagging
-200
-150
-100
-50
0
50
100
150
200
0
Voltag
e
Curre
n
t
Magnitude
Level
Duration
Time
-
8/14/2019 Undersanding Power Factor
10/35
Capacitive Loads
Leading
-200
-150
-100
-50
0
50
100
150
200
0
Voltag
e
Curre
nt
Magnitude
Level
Duration
Time
-
8/14/2019 Undersanding Power Factor
11/35
What is Power
Power is measured in Watts.
Volts X Amps X Power Factor = Watts Watts only equals Volts X Amps when the
Power Factor is 1 or unity.
Most of the time the Power Factor is lessthan 1.
Power = Watts : True Power Volts X Amps = VA : Apparent Power
-
8/14/2019 Undersanding Power Factor
12/35
Understanding Right Triangles
Right Angle 900
A=Sid
eOppos
ite
B= Side Adjacent
C
=Hyp
otenuse
-
8/14/2019 Undersanding Power Factor
13/35
Power Triangle
True power
Apparent power
Power Factor =
Adjacent side
Hypotenuse
=
Cos
A=SideOpposite
B= Side Adjacent
C=Hyp
otenu
se
CosPower Factor =
-
8/14/2019 Undersanding Power Factor
14/35
True power
Apparent powerPower Factor =
Right Angle 900
A=Sid
eOppos
ite
B= Side Adjacent
C
=Hyp
otenuse
True Power
Appa
rentPo
wer
Re
activePo
wer
-
8/14/2019 Undersanding Power Factor
15/35
Understanding Power Triangle
A=Reac
tivePow
er
VAR,
kV
AR
Rea
ctance
B= True Power
Watts, KW, Power
C=Apparent
Powe
r
VA(V
olts
Amps)
,kVA
,
-
8/14/2019 Undersanding Power Factor
16/35
Graphical representation of resistance,
reactance, and impedance
InductiveMotors
R
Impedanc
e
Inductive
Rea
ctance
Resistance
XZ
-
8/14/2019 Undersanding Power Factor
17/35
Graphical representation of resistance,
reactance, and impedance
Capacitors
R
Impedance Capacitive
Reactan
ce
Resistance
XZ
-
8/14/2019 Undersanding Power Factor
18/35
Inductive
Motors
Real - WATTS kW (KWH over Time)
Apparen
tPower
VAorkVA
Imag
inary
kVAR
ReactanceImaginary
True PowerCosine ofPOWER FACTOR
CapacitiveCapacitors
10 HP 460 V l 4 P l M
-
8/14/2019 Undersanding Power Factor
19/35
10 HP 460 Volt 4 Pole Motor
Transformer
Conductor
LoadPowerFactor VA Amps Watts VAR
AmpsReactive
AmpsResistive
125% 0.82 13203 16.6 10883 7476 9.4 13.7
115% 0.81 12240 15.4 9972 7099 8.9 12.5
100% 0.79 10830 13.6 8592 6593 8.3 10.8
75% 0.73 8771 11.1 6397 6002 7.5 8.0
50% 0.61 7105 8.9 4323 5639 7.1 5.4
25% 0.40 5886 7.4 2331 5405 6.8 2.9
min load 0.17 5399 6.8 911 5322 6.7 1.1
Motor
= KW Load (resistive) = KVAR Load (reactive)
10 HP E Fl
-
8/14/2019 Undersanding Power Factor
20/35
Transformer
Conductor
10 HP Energy Flow
A=ReactivePow
er
VAR
=6593
B= True Power
Watts =8592
C=App
arentP
ower
VA=1083
0
Power Factor = .79
Measured Amps = 13.6
Reactive Amps = 8.3
Resistive Amps = 10.8Motor
= KW Load (resistive) = KVAR Load (reactive)
10 HP Addi C it
-
8/14/2019 Undersanding Power Factor
21/35
Motor
Transformer
10 HP Adding Capacitance
Conductor
Measured Amps = 10.8
Measured Amps = 13.6
Measured Amps = 8.3
A
=ReactivePow
er
VAR
=6593
B= True Power
Watts =8592
C=App
arentPo
wer
VA=1083
0
Watts =8592
VA =8595
VA
R
=1
= KW Load (resistive) = KVAR Load (reactive)
10 HP E S i
-
8/14/2019 Undersanding Power Factor
22/35
Transformer
10 HP Energy Savings
Conductor
200 Feet of #12 Gauge wire
Saving are calculated on I2 R losses.
Using a # 12 gauge wire from Table 9 in the NEC
the resistance is 2 ohms per 1000 feet. 200 @
2 Ohms/1000 is .5 ohms. Using this the total saving
will be approx. 11.8 watts. NOTE: This is only if the
capacitor is at the motor.I2 X R = Watts
Motor
= KW Load (resistive) = KVAR Load (reactive)
2.8 2 X .5 = 3.92
3 X 3.92 = 11.76
10 HP Capacitor Sizing
-
8/14/2019 Undersanding Power Factor
23/35
Transformer
Conductor
10 HP Capacitor Sizing
Utility Meter
I2 R Savings
Capacitor to large then var flow in both
directions and one may increase cost.
I2 R Losses
Motor
= KW Load (resistive) = KVAR Load (reactive)
-
8/14/2019 Undersanding Power Factor
24/35
Power Factor PenaltyBased on one month operation at 8 hours a day
Example of Power Factor Charge
PF Charge Factor
NC Charge $0.40 kW Charge $10.25
Max Billing kW 8.592 kWh Charge $0.03854
Power Factor 0.79
Calc kVA 10.8759 kW 8.6
Calc kVAR 6.6681 kWh 2064
PF Charge $0.54
kW Charge $88.15
kWh Charge $79.55
Total Charge $168.23
Less than .85 then a $0.40 charge
For kVar (kW X.62)
In this Case $0.54
-
8/14/2019 Undersanding Power Factor
25/35
10 Horse Power Motor
VA Watts VAR
0
2000
4000
6000
8000
10000
12000
14000
0.82 0.81 0.79 0.73 0.61 0.40 0.17
Power Factor
VA Watts VAR
125%
115%
100%
75%
50%25% Min
10 HP Voltage Rise
-
8/14/2019 Undersanding Power Factor
26/35
Transformer
10 HP Voltage Rise
Conductor
200 Feet of #12 Gauge wire
kVAR * Xsource/kVA/100 = Voltage Rise %
Note This does not include the wire inductance
that will cause some additional rise in voltage.
Motor
= KW Load (resistive) = KVAR Load (reactive)
System VAR Requirements
-
8/14/2019 Undersanding Power Factor
27/35
MVAR
MW
Power
Plant
Generator Transmission Circuit
Distribution Circuit
T/D
Substation
Substation
Capacitor
Bank
Residential
Load
Industrial
Load
Commercial
Load
L L L
System VAR Requirements(Met by Power Plant Generator)
KVAR
KW
= KW Load (resistive) = KVAR Load (reactive)
System VAR Requirements
-
8/14/2019 Undersanding Power Factor
28/35
MW
Power
Plant
GeneratorTransmission Circuit
Distribution Circuit
T/D
Substatio
n
SubstationCapacitor
Bank
Residential
Load
Industrial
Load
Commercial
Load
L L L
System VAR Requirements(Met by Power T/D Substation)
KVAR
KW
= KW Load (resistive) = KVAR Load (reactive)
System VAR Requirements
-
8/14/2019 Undersanding Power Factor
29/35
MW
Power
Plant
Generator Transmission Circuit
Distribution Circuit
T/D
Substation
SubstationCapacitor
Bank
Residential
Load
Industrial
Load
Commercial
Load
L L L
System VAR Requirements(Met by T/D Sub and Feeder Capacitors)
FeederCapacitor
Bank
KVAR
KW
= KW Load (resistive) = KVAR Load (reactive)
Things We ha e Talked Abo t And
-
8/14/2019 Undersanding Power Factor
30/35
Things We have Talked About And
Other Things to Talk About Phase Angle
Power Factor I2R Loss
Power Factor Penalty
Voltage Rise
Harmonic resonance
Load Factor --- Power Factor
Harmonic Resonance
-
8/14/2019 Undersanding Power Factor
31/35
Harmonic Resonance
3 PHASE AC
X Source
INPUT
Equivalent Circuit
X T X Source
X T
X C
HarmonicSource
Harmonic Filters
-
8/14/2019 Undersanding Power Factor
32/35
Harmonic Filters
L
L
3
2
L1
XF
XC
L2 L3L1
Power Factor Vs Load Factor
-
8/14/2019 Undersanding Power Factor
33/35
Power Factor Vs Load Factor
They have no relation
Load Factor is kW at 100% operationYielding so many kWh vs. Actual kWh
Example
Hours in a Month = 30 X 24 = 720 Hours
Load is at 8 kW
8 X 720 = 5760 kWh
Actual kWh by load is 3240
Load Factor then is 3240/5760
Load Factor = .56
Understanding Power Factor
-
8/14/2019 Undersanding Power Factor
34/35
Understanding Power Factor
Definitions
kVA, kVAR, kW, Apparent Power vs. True Power
Calculations Measurements Power Factor Correction
Capacitors System Impacts
I2 R losses, Chapter 9 NEC
Equipment sizing
Power Factor Charges
Problems with adding Caps Harmonic resonance
Volt rise
Power Factor vs Load Factor
-
8/14/2019 Undersanding Power Factor
35/35
Questions