Quickstart
Type 8025 UNIVERSAL
English - Deutsch - Français
We reserve the right to make technical changes without notice.Technische Änderungen vorbehalten.Sous réserve de modifications techniques.
© Bürkert SAS, 2012 - 2019
Operating Instructions_1903/04 00564360 ORIGINAL_FR
3
1 AbouttheQuickstArt.....................................................................4
2 intendeduse.............................................................................................5
3 bAsicsAfetyinformAtion............................................................5
4 GenerAlinformAtion........................................................................6
5 descriptionoftherAtinGplAte............................................7
6 technicAldAtA........................................................................................7
7 instAllAtionAndwirinG.............................................................. 11
8 AdjustmentAndcommissioninG....................................................37
9 pAckAGinG,trAnsport.................................................................. 46
10 storAGe......................................................................................................46
11 disposAlofthedevice................................................................ 46
Type 8025 UNIVERSAL
English
4
About the Quickstart
Type 8025 UNIVERSAL
CAUTION
warnsagainstapossiblerisk. Failuretoobservethiswarningcanresultinsubstantialorminorinjuries.
NOTICe
warnsagainstmaterialdamage.
Indicatesadditionalinformation,adviceorimportantrecommendations.
ReferstoinformationcontainedintheseQuickstartorinotherdocuments.
Indicatesaninstructiontobecarriedouttoavoidadanger,awarningorapossiblerisk.
→ Indicatesaproceduretobecarriedout.
1.2 Definition of the word "device"Theword"device"usedwithinthisQuickstartreferstothetrans-mittertype8025UNIVERSALwithserialnumbershigherorequalto20000.
1 AboUT ThE QUIckSTARTTheQuickstartdescribesthelifecycleofthedevice.PleasekeepthisQuickstartinasafeplace,accessibletoallusersandanynewowners.
theQuickstartcontainsimportantsafetyinformation.
Failuretocomplywiththeseinstructionscanleadtohazardoussituations.Payattentioninparticulartothechapters"3Basicsafetyinformation"and"2Intendeduse".
Whatevertheversionofthedevice,thisQuickstartmustbereadandunderstood.
TheQuickstartexplainshowtoinstall,set,andstart-upthedevice.
AdetaileddescriptionofthedevicecanbefoundintherelatedOperatingInstructionsavailableontheinternetunder:www.burkert.com
1.1 Symbols used
DANger
warnsagainstanimminentdanger. Failuretoobservethiswarningresultsindeathorinseriousinjury.
WArNINg
warnsagainstapotentiallydangeroussituation. Failuretoobservethiswarningcanresultinseriousinjuryorevendeath.
English
5
Intended use
Type 8025 UNIVERSAL
2 INTENDED USE
useofthedevicethatdoesnotcomplywiththeinstructionscouldpresentriskstopeople,nearbyinstallationsandtheenvironment.
Thetransmitter8025UNIVERSALhasbeendesignedtoprocessafrequencysignal,receivedfromaflowsensorconnectedtothetransmitter.
UsethedeviceincompliancewiththecharacteristicsandcommissioninganduseconditionsspecifiedinthecontractualdocumentsandintheOperatingInstructions.
Neverusethedeviceforsecurityapplications. Usethedeviceonlyincombinationwithforeigndevicesorfor-eigncomponentsrecommendedorapprovedbyBürkert.
Protectthedeviceagainstelectromagneticinterference,ultra-violetraysand,wheninstalledoutdoors,theeffectsofclimaticconditions.
Onlyoperateadeviceinperfectworkingorder. Store,transport,installandoperatethedeviceproperly. Onlyusethedeviceasintended.
3 bASIc SAfETy INfoRmATIoNThissafetyinformationdoesnottakeintoaccountanycontingenciesoroccurrencesthatmayariseduringinstallation,useandmainte-nanceofthedevice.
Theoperatingcompanyisresponsiblefortherespectofthelocalsafetyregulationsincludingforthestaffsafety.
dangerduetoelectricalvoltage. Ifa12...36VDCenergizedversionisinstalledeitherinawetenvironmentoroutdoors,alltheelectricalvoltagesmustbeofmax.35VDC.
Beforecarryingoutworkonthesystem,disconnecttheelectri-calpowerforalltheconductorsandisolateit.
Allequipmentconnectedtothedevicemustbedoubleinsu-latedwithrespecttothemainsaccordingtothestandardIEC61010-1:2010.
Observeallapplicableaccidentprotectionandsafetyregula-tionsforelectricalequipment.
variousdangeroussituations
Toavoidinjury: Donotusethedeviceinexplosiveatmospheres. Donotusethedeviceinanenvironmentincompatiblewiththematerialsitismadeof.
Donotsubjectthedevicetomechanicalstress.
English
6
General information
Type 8025 UNIVERSAL
variousdangeroussituations
Toavoidinjury: Donotmakeanymodificationstothedevice. Preventanyunintentionalpowersupplyswitch-on. Onlyqualifiedandskilledstaffcancarryouttheinstallationandmaintenancework.
Guaranteeadefinedorcontrolledrestartingoftheprocess,afterapowersupplyinterruption.
Observethegeneraltechnicalrules.
NOTICe
elements/componentssensitivetoelectrostaticdischarges
Thedevicecontainselectroniccomponentssensitivetoelectro-staticdischarges.Theymaybedamagediftheyaretouchedbyanelectrostaticallychargedpersonorobject.Intheworstcasesce-nario,thesecomponentsareinstantlydestroyedorgooutoforderassoonastheyareactivated.
Tominimiseorevenavoidalldamageduetoanelectrostaticdischarge,takealltheprecautionsdescribedinstandardEN61340-5-1.
Alsoensurethatyoudonottouchanyoftheliveelectricalcomponents.
4 GENERAL INfoRmATIoN
4.1 manufacturer's address and international contacts
Tocontactthemannufacturerofthedevice,usefollowingaddress:
BürkertSAS
RueduGiessen
BP21
F-67220TRIEMBACH-AU-VAL
YoumayalsocontactyourlocalBürkertsalesoffice.
Theaddressesofourinternationalsalesofficesareavailableontheinternetat:www.burkert.com
4.2 Warranty conditionsTheconditiongoverningthelegalwarrantyistheconforminguseofthedeviceinobservanceoftheoperatingconditionsspecifiedintheOperatingInstructions.
4.3 Information on the InternetYoucanfindtheOperatingInstructionsandtechnicaldatasheetsregardingthetype8025UNIVERSALat:www.burkert.com
English
7
Description of the rating platE
Type 8025 UNIVERSAL
5 DEScRIpTIoN of ThE RATING pLATE
LFLOW 8025 PANEL SUPPLY: 12-36V... 210 mADO1: 5-36V... 100mA AO1:4-20mA DO2&3: 2xRelay 30V and 42V peak or 60V... max. IP20
S/N 20 000
00564417 W46MA
Mad
e in
Fra
nce
1
11
6
781213
3 5
10
42
9
1. Measuredvalue
2. Typeofthedevice,housing
3. SpecificationsofthedigitaloutputDO1(transistor)
4. SpecificationsoftheanalogueoutputAO1
5. Supplyvoltageandmax.currentconsumption
6. Protectionclassofthedevice
7. Manufacturingcode
8. Conformitymarking
9. Certification
10.Warning:Beforeusingthedevice,takeintoaccountthetech-nicalspecificationsdescribedinthisQuickstart.
11.SpecificationsoftherelayoutputsDO2andDO3
12.Serialnumber
13.ArticlenumberFig. 1 : Rating plate of the device (example)
6 TEchNIcAL DATA
6.1 conditions of use
Ambianttemperature –10...+60°C
Airhumidity <80%,noncondensatedheightaboveseelevel max.2000moperatingconditions Continuousoperationequipmentmobility Fixeddeviceuse Indoorandoutdoor
(Protectthedeviceagainstelectro-magneticinterference,ultravioletraysand,wheninstalledoutdoors,againsttheeffectsofclimaticconditions)
installationcategory CategoryIaccordingtoUL/EN61010-1degreeofpollution Degree2accordingtoUL/EN61010-1
protectionratingaccordingtoIEC/EN60529
• wall-mountedversion • IP651),devicewired,cableglandstightened,coverlidscrewedtightandentryitemnutsofthecableglandstightenedatascrewingtorqueof1.5N·m
• panelversion • frontsideIP651),rearsideIP201)1)notevaluatedbyUL
English
8
Technical data
Type 8025 UNIVERSAL
6.2 conformity to standards and directives
Theappliedstandards,whichverifyconformitywiththeEUdirec-tives,canbefoundontheEU-typeexaminationcertificateand/ortheEUdeclarationofconformity(ifapplicable).
ul-certification
DeviceswithvariablekeyPU01orPU02areUL-certifieddevicesandcomplyalsowiththefollowingstandards:
• UL61010-1
• CAN/CSA-C22.2n°61010-1
identificationonthedevice certification variablekey
UL-recognized PU01
MeasuringEquipmentEXXXXXX®
UL-listed PU02
6.3 mechanical data
part material
Housingandcover,wall-mountedversion ABSCableglands,wall-mountedversion PAOpenhousing,panelversion PCFoil polyester4screws StainlesssteelCableclips PA
6.4 Dimensions→ Pleaserefertothetechnicaldatasheetsrelatedtothedeviceat:
www.burkert.com
6.5 Electrical data
powersupply12...36vdc • filteredandregulated
• max.tolerance12VDC:–5%or+10%
• max.tolerance36VDC:±10%
• Connectiontomainsupply:permanent(throughexternalSELV(safetyextra-lowvoltage)andthroughLPS(limitedpowersource)
powersource(notsupplied) • LimitedpowersourceaccordingtoUL/EN60950-1standards
• orlimitedenergycircuitaccordingtoUL/EN61010-1,Paragraph9.4
115/230vAcpowersupply• frequency • 50/60Hz• suppliedvoltage • 27VDC,regulated• maximumcurrent • 250mA• integratedprotection • 250mAtime-delayfuse• power • 6VA
English
9
Technical data
Type 8025 UNIVERSAL
currentconsumption(withouttheconsumptionofthe4...20mAoutput)
• versionwithoutrelays,energizedwith12...36VDC
• versionwithrelays,ener-gizedwith12...36VDC
• versionwithoutrelays,energizedwith115/230VAC
• versionwithrelays,ener-gizedwith115/230VAC
• 50mA(at12VDC)and30mA(at36VDC)
• 70mA(at12VDC)and45mA(at36VDC)
• 35mA
• 50mA
digitaloutputdo1(transistor)
• type
• function
• frequency(f)
• Electricaldata
• dutycycleif0.6<f<300Hz
• dutycycleif300<f<1500Hz
• dutycycleif1500<f<2200Hz
• protection
polarized,potential-free
• NPN/PNP(wiringdependent),opencollector
• pulseoutput(bydefault),userconfigurable
• 0.6...2200Hz
• 5...36VDC,100mAmax.,voltagedrop2.7VDCat100mA
• >0.45
• >0.4
• <0.4
• galvanicallyisolated,andprotectedagainstover-voltages,polarityreversalsandshort-circuits
English
10
Technical data
Type 8025 UNIVERSAL
digitaloutputsdo2anddo3(relays)
• operating
• electricaldataoftheload(nonULdevices)
• electricaldataoftheload(ULdevices)
• max.breakingcapacity
• lifespan
• hysteresis(bydefault),usercon-figurable,normallyopen
• 230VAC/3Aor40VDC/3A
• max.30VACand42Vpeak,3Aormax.60VDC,1A
Tousetherelayoutputsinawetlocation,observethefollowingDANGERsafetyinstruction.
• 750VA(resistiveload)
• min.100000cyclescurrentoutputAo1
• specification
• max.loopimpedance
• 4...20mA,sinkorsource(wiringdependent),22mAtoindicateafault(canbeactivated)
• 1300 Wat36VDC,1000 Wat30VDC,750 Wat24VDC,300 Wat15VDC,200 Wat12VDC
• 900 Wifthedeviceisenergizedwith115/230VAC
DANger
dangerduetotheoperationoftherelayoutputsofauldeviceinawetlocation.
IfaULdeviceisusedinawetlocation:
- energizetherelayoutputswithanalternatingvoltageofmax.16Vrmsand22.6Vpeak.
- orenergizetherelayoutputswithadirectvoltageofmax.35VDC.
6.6 Specifications of the connected flow sensor
signaloriginatingfromtheremotesensor
• type
• frequency
• max.voltage
• pulse,sine-wave(typicalsensitivity50mVpeak-to-peakat250Hz),"on/off",orstandardvoltage0...5VDC
• 0.6Hzto2.2kHz,canbeadjusted
• 36VDCinputimpedance dependsonthepositionofselector
"LOAD"ontheelectronicboardofthe8025.Seechap.7.4.11
English
11
Installation and wiring
Type 8025 UNIVERSAL
powersupply suppliedbythetransmitterdependingonthepositionofselector"SENSORSUPPLY"ofthe8025,either:
• 5VDC,30mAmax.
• (L+)-12V:supplyvoltage(L+)ofthetransmitterminus12VDC(minus12.5VDCmax.),80mAmax.
• L+:supplyvoltage(L+)ofthetransmitter(minus1.5VDCmax.),140mAmax.(ifthedeviceisener-gizedwith12...36VDC),80mAmax.(ifthedeviceisener-gizedwith115/230VAC)
7 INSTALLATIoN AND WIRING
7.1 Safety instructions
DANger
riskofinjuryduetoelectricalvoltage. Ifa12...36VDCenergizedversionisinstalledeitherinawetenvironmentoroutdoors,alltheelectricalvoltagesmustbeofmax.35VDC.
Disconnecttheelectricalpowerforalltheconductorsandiso-lateitbeforecarryingoutworkonthesystem.
Allequipmentconnected to thewall-mountedorpanel versionoftheflowtransmitter8025UNIVERSALmustbedoubleinsu-lated in relation to themains inaccordancewith IECstandard61010-1:2010.
Observeallapplicableaccidentprotectionandsafetyregula-tionsforelectricalequipment.
WArNINg
riskofinjuryduetonon-conforminginstallation. Theelectricalinstallationcanonlybecarriedoutbyqualifiedandskilledstaffwiththeappropriatetools.
Fitacircuitbreakeroraswitchtotheelectricalinstallationinwhichthedeviceisinstalled.
Installthecircuitbreakerorswitchinaplacewhichiseasytoreach.
Identifythecircuitbreakerorswitchastheelectricalpowercut-offsystemforthedevice.
English
12
Installation and wiring
Type 8025 UNIVERSAL
WArNINg
riskofinjuryduetonon-conforminginstallation. Installappropriateoverloadsafetydevices.Foraversionener-gizedby115/230VAC,insertovercurrentprotectivedevicesintheliveconductorandintheneutralconductor.
Donotenergizeadevice,version12...36VDC,withanalter-natingvoltageorwithadirectvoltagehigherthan36VDC.
ObservethestandardNFC15-100/IEC60364.
WArNINg
riskofinjuryduetounintentionalswitchonofpowersupplyoruncontrolledrestartingoftheinstallation.
Takeappropriatemeasurestoavoidunintentionalactivationoftheinstallation.
Guaranteeasetorcontrolledrestartingoftheprocesssubse-quenttoanyinterventiononthedevice.
NOTICe
riskofdamagetothedeviceiftheincorrectsupplyvoltageisapplied.
Energizethedevicewithasupplyvoltageinaccordancewiththepositionoftheselector.SeeFig.11,chap.7.4.5.
Protectthisdeviceagainstelectromagneticinterference,ultravioletraysand,wheninstalledoutdoors,theeffectsoftheclimaticconditions.
7.2 Installation of a panel version
InstallthepanelversionofthedeviceinacabinetwithaprotectionclassatleastIP54toensureadegreeofpol-lution2insidethecabinet.
→ Tocuttheopeninginthecabinetdoor,usethesupplieddrillingjig,respectingthedimensionsindicatedinFig.2.
95807650
95 80 76 50
Fig. 2 : Dimensions of the drilling jig [mm]
→ Insertthe4screwsinthehousing(fromthefront).
→ Insertthesealontheexternalthreadsofthe4screws(rearofthehousing).
→ Puttheassemblyonthecutout,electronicsturnedtotheinsideofthecabinet.
→ Putthe4washersonthe4screws.
→ Putanutoneachofthe4screwsandtightenthenutstosecurethedevicetothecabinet.
English
13
Installation and wiring
Type 8025 UNIVERSAL
Seal
Nut
Washer
Screws
Cableclip
Fig. 3 : Installation of a 8025, panel version
7.3 Installation of a wall-mounted version
NOTICe
riskofmaterialdamageifthecableglandsarenottightlyscrewedonthehousing
Beforeinstallingthewall-mountedhousingonitssupport,tightenthenutsoftheentryitemofthecablesglandsatatorqueof1.5N·m.
Theflowtransmitterinawall-mountedversionhas4holesinthebottomofthehousing.
→ Removethecoveringstripscoveringthescrews.
CoveringstripsENTER
0....9
FLOW
Nutoftheentryitem
Fig. 4 : Location of the fastening nuts and the covering strips
→ Loosenthe4screwsandopenthecovertogetaccesstotheholes[1].
English
14
Installation and wiring
Type 8025 UNIVERSAL
DANger
riskofinjuryduetoelectricalvoltage. Observeallapplicableaccidentprotectionandsafetyregula-tionsforelectricalequipment.
DANger
dangerduetotheoperationoftherelayoutputsofauldeviceinawetlocation.
IfaULdeviceisusedinawetlocation:
- energizetherelayoutputswithanalternatingvoltageofmax.16Vrmsand22.6Vpeak.
- orenergizetherelayoutputswithadirectvoltageofmax.35VDC.
NOTICe
riskofdamagetothedeviceiftheincorrectsupplyvoltageisapplied.
Energizethedevicewithasupplyvoltageinaccordancewiththepositionoftheselector.SeeFig.11,chap.7.4.5.
Thedevicecanbedamagedifitisnottight.
• Insertthesuppliedstoppergasketsintotheunusedcableglandstoensurethetightnessofthedevice.
1 1
1 1
106 mm
230V
L N
230V
T 25
0 m
A
5 6 7 8 9 10
L N
230V
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
10
6 m
m
Fig. 5 : Installation of a wall-mounted version
→ SecurethehousingtothesupportrespectingthedimensionsindicatedinFig.5.
→ Wireaccordingtoinstructionsinchap.7.4.
→ Closethehousingandtightenthe4screwsofthecover.
7.4 Wiring
DANger
riskofinjuryduetoelectricalvoltage. Ifa12...36VDCenergizedversionisinstalledeitherinawetenvironmentoroutdoors,alltheelectricalvoltagesmustbeofmax.35VDC.
Disconnecttheelectricalpowerforalltheconductorsandiso-lateitbeforecarryingoutworkonthesystem.
AllequipmentconnectedtothedevicemustbedoubleinsulatedinrelationtothemainsinaccordancewithIECstandard61010-1:2010.
English
15
Installation and wiring
Type 8025 UNIVERSAL
Onlymovetheselectorswhenthepowersupplyisoff.
Protectthisdeviceagainstelectromagneticinterference,ultravioletraysand,wheninstalledoutdoors,theeffectsoftheclimaticconditions.
Foracorrectoperationofthedevice,respectthefollowingrecommendationsduringtheelectricalinstallation:
• Makesuretheinstallationisequipotential.Seechap.7.4.2.
• Donotinstallthecablesnearhighvoltageorhighfrequencycables;ifacombinedinstallationcannotbeavoided,aminimumclearanceof30cmshouldberespected.
Foradevicefedat12...36VDC,respectthefollowingrecommendationsfortheelectricalinstallation:
• Useafilteredandregulated12...36VDCpowersupply.Thecircuithastobesafetyextralowvoltage(SELV),withasafeenergylevel.
Thepowersupplyofthedevicecanbedamagedifitisnotprotected.
• Protectthedevicepowersupplybymeansofa300mAfuseandaswitch.
Thepowersupplyofatransistoroutputcanbedamagedifitisnotprotected.
• Protectthepowersupplyofeachtransistoroutputbymeansofa125mAfuse.
Therelayscanbedamagedifnotprotected.
• Protecttherelaysbymeansofamax.3Afuseandacircuitbreaker(dependingontheprocess).
• Donotapplybothadangerousvoltageandasafetyextra-lowvoltagetotherelays.
7.4.1 Specifications of the connection cables
Tab. 1 : Specifications of the cables and wires for the direct wiring to the terminal blocks of a panel-mounted version
specificationofthecablesandthecon-ductors(notsupplied)
recommendedvalue
Shieldedcable yesLengthofthecable max.50mOperatingtemperature,ULdevice min.90°COperatingtemperature,nonULdevice min.80°CCrosssectionoftheconductors 0.2...1.5mm2
English
16
Installation and wiring
Type 8025 UNIVERSAL
Tab. 2 : Specifications of the cables and wires for the wiring through the M16x1,5 cable glands
specificationofthecablesandthecon-ductors(notsupplied)
recommendedvalue
Shieldedcable yesLengthofthecable max.50mExternaldiameterofthecable,if1cablepercablegland
4...8mm
Operatingtemperature,ULdevice min.90°COperatingtemperature,nonULdevice min.80°CCrosssectionoftheconductors 0.2...1.5mm2
7.4.2 Equipotentiality of the installationToensuretheequipotentialityoftheinstallation(powersupply-device-fluid):
→ Connecttogetherthevariousearthspotsintheinstallationtoeliminatethepotentialdifferencesthatmayoccurbetweendif-ferentearthes.
→ Observefaultlessearthingoftheshieldofthepowersupplycable,atbothends.
→ Connectthenegativepowersupplyterminaltotheearthtosup-presstheeffectsofcommonmodecurrents.Ifthisconnectioncannotbemadedirectly,a100nF/50Vcapacitorcanbefittedbetweenthenegativepowersupplyterminalandtheearth.
→ Specialattentionhastobepaidifthedeviceisinstalledonplasticpipesbecausethereisnodirectearthingpossible.Properearthingisperformedbyearthingtogetherthemetallicinstrumentssuchaspumpsorvalves,thatareascloseaspos-sibletothedevice.Ifnosuchinstrumentisnearthedevice,insertmetallicearthringsinsidetheplasticpipesupstreamanddownstreamthedeviceandconnectthesepartstothesameearth.Theearthingringsmustbeincontactwiththefluid.
+-
(*)
Flowsensor
8025UNIVERSAL
Powersupply
PlasticpipeValve,pump,...(orearth
rings,notprovided,insertedintothepipe)
Powercableshield
(*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth.
Fig. 6 : Equipotentiality skeleton diagram with pipes in plastic
English
17
Installation and wiring
Type 8025 UNIVERSAL
+-
(*)
Flowsensor
8025UNIVERSAL
Powersupply
Metalpipe
Powercableshield
(*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth.
Fig. 7 : Equipotentiality skeleton diagram with pipes in metal
English
18
Installation and wiring
Type 8025 UNIVERSAL
7.4.3 Terminal assignment and use of the selectors
2
B
1
5
A
C
D
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
3
4
terminalblock1
• Iout:4...20mAoutput(AO1)
• L+:V+(positivevoltage)
• L-:0V(powersupplyground)
• PE:protectiveearth,factorywired
• P-:Negativetransistoroutput(DO1)
• P+:Positivetransistoroutput(DO1)
terminalblock2
PE:ShieldingsofboththepowersupplycableandtheAO1andDO1outputcables
terminalblock3:WiringoftherelayoutputDO2(ifthedevicehasrelays).
terminalblock4:WiringoftherelayoutputDO3(ifthedevicehasrelays).
terminalblock5"flowsensor":Wiringtheremoteflowsensor.Thewiringdependsonthetypeofoutputsignaloriginatingfromtheflowsensor:seechap.7.4.11.
Switch A :seeFig.14,page23
Switch B :seechap.7.4.11
Switch C :seeTab.3,page31
Switch D :seechap.7.4.11
Fig. 8 : Terminal assignment of a panel version or a wall-mounted version, 12...36 V DC
English
19
Installation and wiring
Type 8025 UNIVERSAL
230V
L N
230V
T 25
0 m
A
5 6 7 8 9 10
L N
230V
1
B
2
3
A
C
D
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD+5V
L+(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
4
5
E
6 7
8
English
20
Installation and wiring
Type 8025 UNIVERSAL
terminalblock1
PE:factorywiredshield
terminalblock2
• Iout:4...20mAoutput(greenwire,factorywired)
• L+:V+(redwire,factorywired)
• L-:0V(blackwire,factorywired)
• PE:protectiveearth,factorywired
• P-:negativetransistoroutput(brownwire,factorywired)
• P+:positivetransistoroutput(whitewire,factorywired)
terminalblock3"flowsensor":Wiringtheremoteflowsensor.Thewiringdependsonthetypeofoutputsignaloriginatingfromtheflowsensor:seechap.7.4.11
Switch A :seeFig.14,page23
Switch B :seechap.7.4.11
Switch C :seeTab.3,page31
Switch D :seechap.7.4.11
Switch E :seechap.7.4.5
terminalblock4:WiringoftherelayoutputDO2(ifthedevicehasrelays)
terminalblock5:WiringoftherelayoutputDO3(ifthedevicehasrelays)
terminalblock6
• Terminal5:4...20mAoutput(AO1)
• Terminal6:positive27VDCpowersupply,availabletoenergizeanexternalinstrument
• Terminal7:0V(earthofthepowersupplyavailabletoenergizeanexternalinstrument)
• Terminal8:protectiveearth:shieldsoftheAO1andDO1outputcables
• Terminal9:Negativetransistoroutput(DO1)
• Terminal10:Positivetransistoroutput(DO1)
terminalblock7:Wiringofthe115/230VACpowersupply
Mark 8 :time-delayfusetoprotectthe115/230VACpowersupply
Fig. 9 : Terminal assignment of a wall-mounted version, 115/230 V AC
English
21
Installation and wiring
Type 8025 UNIVERSAL
7.4.4 Wiring a panel version
Onlymovetheselectorswhenthepowersupplyisoff.
→ Installthedeviceasdescribedinchap.7.2.
→ Settheselectors"SENSORTYPE","SENSORSUPPLY"and"LOAD":seechap.7.4.11.
→ Beforewiringthedeviceinsertthesup-pliedcableclipsintotheslotsoftheelec-tronicboard.
Fig. 10 : Inserting the cable clips
→ Wireaccordingtochap.7.4.6,7.4.7,7.4.10and7.4.11.
→ Securethepowersupplycable,theflowsensorconnectioncableand,dependingontheversion,therelayconnectioncables,withthecableclips.
7.4.5 Wiring a wall-mounted version
Onlymovetheselectorswhenthepowersupplyisoff.
Insertthesuppliedstoppergasketsintotheunusedcableglandstoensurethetightnessofthedevice.
• Unscrewtheunusedcablegland.
• Removethetransparentdisk.
• Insertthesuppliedstoppergasket.
• Screwthenutofthecablegland.
→ Installthedeviceasdescribedinchap.7.3.
→ Settheselectors"SENSORTYPE","SENSORSUPPLY"and"LOAD":seechap.7.4.11.
→ Ifthewall-mountedversionisenergizedwitha115/230VAC
powersupply,setselector E asshowninFig.11.
Selector E makesitpossibletoconfigurethesupplyvoltageofthedeviceina115/230VACversion.
→ Energizethedevicewitha230VACvoltage.
→ Energizethedevicewitha115VACvoltage.
E
230V115V
Fig. 11 : Selector of the supply voltage on a 115/230 V AC version
English
22
Installation and wiring
Type 8025 UNIVERSAL
→ Loosenthenutsofthecableglands.
→ Inserteachcablethroughanutthanthroughthecablegland,usingthecableglandsasshowninFig.12.
Flowsensorcable
Cablesoftheoutputs
Powersupplycable12...36VDCor115/230VAC
Fig. 12 : Using the cable glands
→ Removethetwoterminalblocks(marked6and7inFig.9)fromthehousing.
→ Beforewiringthedeviceinsertthesup-pliedcableclipsintotheslotsoftheelec-tronicboardandofthe115/230VACpowersupplyboardifthedevicehassuchaboard.
Fig. 13 : Inserting the cable clips
→ Dependingontheoperatingvoltageofthedevice,wireaccordingtochap.7.4.6to7.4.11.
→ Insertthetwoterminalblocks(marked6and7inFig.9)intotheiroriginalposition.
→ Lettingthehousingstaycompletelyopen,securethepowersupplycable,theflowsensorconnectioncableand,dependingontheversion,therelayconnectioncables,withthecableclips.
→ Tightenthecableglandsmakingsurethecableinthehousingislongenoughtoallowcompleteopeningofthehousing.
→ Closethecover.
→ Tightenthe4screws.
→ Putthecoveringstripsonthehousing.
English
23
Installation and wiring
Type 8025 UNIVERSAL
7.4.6 Wiring the Ao1 current output of a panel version or a wall-mounted version, 12...36 V Dc
Onlymovetheselectorswhenthepowersupplyisoff.
The4...20mAoutputcanbewiredineithersourcingorsinkingmode.
Useswitch A toconfigurethewiringofthe4...20mAcurrentoutputinsinkingorsourcingmode.
A
SOURCE SINKCURRENT
SOURCE SINKCURRENT
→ Wirethecurrentoutputinsinkingmode.
→ Wirethecurrentoutputinsourcingmode.
Fig. 14 : Using the sink/source switch
A
12-36 V DC+-
300 mA
I
+-
(*)
CURRENTSOURCE SINK
PE PEPE
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
Powersupply4...20mAinputatexternal
instrument
Setthe A switchontheleft.
*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth
Fig. 15 : Wiring of the 4...20 mA output (AO1) in sourcing mode
English
24
Installation and wiring
Type 8025 UNIVERSAL
A
CURRENTSOURCE SINK
PE PEPE
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
12-36 V DC+-
300 mA
I
+-
(*)Powersupply
4...20mAinputatexternalinstrument
Setthe A switchontheright.
*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth
Fig. 16 : Wiring of the 4...20 mA output (AO1) in sinking mode
7.4.7 Wiring the Do1 transistor output of a panel version or a wall-mounted version, 12...36 V Dc
PE PEPE
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
300 mA+-
12-36 V DC
(*) +
-
+- 5-36 VDC
PLC
Powersupplyofthedevice
*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth
Fig. 17 : NPN wiring of the DO1 transistor output
English
25
Installation and wiring
Type 8025 UNIVERSAL
Powersupplyofthedevice
PLC
PE PEPE
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
300 mA
(*) +
-
+- 5-36 VDC+
-
12-36 V DC
*)Ifadirectearthconnectionisnotpossible,fita100nF/50Vcapacitorbetweenthenegativepowersupplyterminalandtheearth
Fig. 18 : PNP wiring of the DO1 transistor output
English
26
Installation and wiring
Type 8025 UNIVERSAL
7.4.8 Wiring the Ao1 current output of a wall-mounted version, 115/230 V Ac
Onlymovetheselectorswhenthepowersupplyisoff.
The4...20mAoutputcanbewiredineithersourcingorsinkingmode.
• Setthe A switchontheleft.
• Setselector E dependingonthevalueofthepowersupply.230V
L N
230V
T 25
0 m
A
5 6 7 8 9 10
L N
230V
A
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
E
+ -
4...20mAinputatexternalinstrument
Connectionofthepowersupplyforthe8025
Fig. 19 : Wiring of the 4...20 mA output (AO1) of a wall-mounted version, 115/230 V AC, in sourcing mode
English
27
Installation and wiring
Type 8025 UNIVERSAL
• Setthe Aswitchontheright.
• Setselector E dependingonthevalueofthepowersupply.
230V
L N
230V
T 25
0 m
A
5 6 7 8 9 10 L N
230V
A
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
E
+ -
4...20mAinputatexternalinstrument
Connectionofthepowersupplyforthe8025
Fig. 20 : Wiring of the 4...20 mA output (AO1) of a wall-mounted version, 115/230 V AC, in sinking mode
English
28
Installation and wiring
Type 8025 UNIVERSAL
7.4.9 Wiring the Do1 transistor output of a wall-mounted version, 115/230 V Ac
Onlymovetheselectorswhenthepowersupplyisoff.
Setofselector E dependingonthevalueofthepowersupply.
230V
L N
230V
T 25
0 m
A
5 6 7 8 9 10 L N
230V
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
E
+
-
+- 5-36 VDC
PLC
Connectionofthepowersupplyforthe8025
PowersupplyforthePLC
Fig. 21 : NPN wiring of the DO1 transistor output of a wall-mounted version, 115/230 V AC
English
29
Installation and wiring
Type 8025 UNIVERSAL
Setselector E dependingonthevalueofthepowersupply.
230V
L N
230VT
250
mA
5 6 7 8 9 10 L N
230V
CURRENTSOURCE SINK
BINARY
PE PEPEPE
DI1DI2DI3DI4DO4ISOG
FLOW
SENSOR
L+ L- PE P- P+
NC
IoutPULSE
DO1Supply
12..36Vdc
UnivBatch
(AO1)
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
SENSOR
SUPP
LYLO
AD
+5VL+
(L+)-12V COIL/PNP39K
4702.2K
SENSOR TYPECOIL NPN/PNP
DO2
DO3
OFFON
E
+
-
+- 5-36 VDC
PLC
Connectionofthepowersupplyforthe8025
PowersupplyforthePLC
Fig. 22 : PNP wiring of the DO1 transistor output of a wall-mounted version, 115/230 V AC
English
30
Installation and wiring
Type 8025 UNIVERSAL
7.4.10 Wiring the relay outputs Do2 and Do3 of the panel or a wall-mounted version
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+- DO2
DO3
OFFON
230 V AC
m3 A
3 A 230 V AC
Fig. 23 : Wiring of the DO2 and DO3 relay outputs
7.4.11 connecting the flow sensor to the transmitter
Beforeconnectingtheflowsensortothetransmitter8025UNIVERSAL:
• setselector"SENSORTYPE"dependingontheoutputsignalprovidingfromtheflowsensor.SeeFig.24andTab.3,page31.
• iftheselector"SENSORTYPE"isseton"NPN/PNP",settheselector"SENSORSUPPLY"dependingonthetransmittersupplyvoltage.SeeFig.25.
• setselector"LOAD"dependingonthetypeofsignalsentoutbytheflowsensorandontheloadwantedonterminal1"PULSEINPUT"ofterminalblock"FLOWSENSOR".SeeTab.3,page31.
Selector D makesitpossibletoconfigurethetypeofsignalthe8025UNIVERSALreceivesfromtheflowsensor.
→ Settheselectorontheright(defaultposition)whenthesignalfromtheflowsensorwhichisconnectedtothe8025UNIVERSALiseither:
• apulsesignal,NPNorPNP
• an"on/off"signal(Reedrelayforexample)
• a0...5VDCstandardvoltagesignal(TTL,forexample)
→ Settheselectorontheleftwhenthesignalfromtheflowsensorwhichisconnectedtothe8025UNIVERSALisasine-wavesignal(coil)
DSENSOR TYPECOIL NPN/PNP
SENSOR TYPECOIL NPN/PNP
Fig. 24 : Using selector "SENSOR TYPE"
English
31
Installation and wiring
Type 8025 UNIVERSAL
Whenselector"SENSORTYPE"aboveisseton"NPN/PNP",
selector B makesitpossibletoconfigurethesupplyvoltagefortheflowsensor.
SENSORSU
PPLY+5V
L+(L+)-12V
B
→ Ifthe8025UNIVERSALisenergizedwitha115/230VACpowersupply,setselector"SENSORSUPPLY"on"L+"(defaultposition).
→ Ifthe8025UNIVERSALisenergizedwitha12...36VDCpowersupply,setthevoltageselector"SENSORSUPPLY"dependingonthevoltagesupplyneededbytheremoteflowsensor:"+5V","L+"or"(L+)-12V"(defaultposition).
Fig. 25 : Using selector "SENSOR SUPPLY"
Tab. 3 : Default positions of selectors "SENSOR SUPPLY", "LOAD" and "SENSOR TYPE"
selector defaultposition
SENSORSUPPLY( B ) L+
LOAD( C ) 2.2K
SENSORTYPE( D ) NPN/PNP
English
32
Installation and wiring
Type 8025 UNIVERSAL
Tab. 4 : Position of selectors "SENSOR TYPE" and "LOAD" and terminal assignment of terminal block "FLOW SENSOR" depending on the signal emitted by the flow sensor
typeofsignalemittedbytheflowsensor
selector"sensor
type"
( D )
selector"sensorsupply"
( B )
selector"loAd"
C
LOAD
COIL/PNP39K
4702.2K
terminalassignmentofterminalblock"flowsensor"
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
sine-wave(coil)
→ Settheselectoron"COIL"(Fig.24)
→ Anyposition
→ Setselector"LOAD"on"39K":theinputimpedanceonterminals1and2ofterminalblock"FLOWSENSOR"willthenbe39kW
21 3 PE
NC39 kΩ
8025
Flowsensor
English
33
Installation and wiring
Type 8025 UNIVERSAL
typeofsignalemittedbytheflowsensor
selector"sensor
type"
( D )
selector"sensorsupply"
( B )
selector"loAd"
C
LOAD
COIL/PNP39K
4702.2K
terminalassignmentofterminalblock"flowsensor"
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
pulse,PNP
→ Settheselectoron"NPN/PNP"(Fig.24)
→ SettheselectorasshowninFig.25
→ Setselector"LOAD"on"39K":theinputimpedanceonterminals1and2ofterminalblock"FLOWSENSOR"willthenbe39kW
21 3 PE
39 kΩ
8025
Flowsensor
English
34
Installation and wiring
Type 8025 UNIVERSAL
typeofsignalemittedbytheflowsensor
selector"sensor
type"
( D )
selector"sensorsupply"
( B )
selector"loAd"
C
LOAD
COIL/PNP39K
4702.2K
terminalassignmentofterminalblock"flowsensor"
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
0...5VDCstandardvoltagesignal(TTL,forexample)
→ Settheselectoron"NPN/PNP"(Fig.24)
→ SettheselectorasshowninFig.25
→ Setselector"LOAD"on"39K":theinputimpedanceonterminals1and2ofterminalblock"FLOWSENSOR"willthenbe39kW
21 3 PE
39 kΩ
8025
Flowsensor
English
35
Installation and wiring
Type 8025 UNIVERSAL
typeofsignalemittedbytheflowsensor
selector"sensor
type"
( D )
selector"sensorsupply"
( B )
selector"loAd"
C
LOAD
COIL/PNP39K
4702.2K
terminalassignmentofterminalblock"flowsensor"
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
pulse,NPN
→ Settheselectoron"NPN/PNP"(Fig.24)
→ SettheselectorasshowninFig.25
→ Setselector"LOAD":
• eitheron"2.2K":theloadresistanceRisthen2.2kW
• eitheron"470":theloadresistanceRisthen470W
21 3 PE
8025
R
+3 V
Flowsensor
English
36
Installation and wiring
Type 8025 UNIVERSAL
typeofsignalemittedbytheflowsensor
selector"sensor
type"
( D )
selector"sensorsupply"
( B )
selector"loAd"
C
LOAD
COIL/PNP39K
4702.2K
terminalassignmentofterminalblock"flowsensor"
FLOW
SENSOR
SUPPLY
NC COIL
PULS
EIN
PUT
NPN/
PNP
21 3 PE
+-
"on/off"signal(Reedrelayforexample)
→ Settheselectoron"NPN/PNP"(Fig.24)
→ SettheselectorasshowninFig.25
→ Setselector"LOAD":
• eitheron"2.2K":theloadresistanceRisthen2.2kW
• eitheron"470":theloadresistanceRisthen470W
21 3 PE
8025
R
+3 V
...
Flowsensor
English
37
Adjustment and commissioning
Type 8025 UNIVERSAL
8 ADjUSTmENT AND commISSIoNING
8.1 Safety instructions
WArNINg
riskofinjuryduetononconformingoperating.
Nonconformingoperatingcouldleadtoinjuriesanddamagethedeviceanditssurroundings.
Theoperatorsinchargeofoperatingmusthavereadandunder-stoodthecontentsofthisQuickstart.
Inparticular,observethesafetyrecommendationsandintendeduse. Thedevice/installationmustonlybeoperatedbysuitablytrainedstaff.
WArNINg
dangerduetononconformingcommissioning.
Nonconformingcommissioningcouldleadtoinjuriesanddamagethedeviceanditssurroundings.
Beforecommissioning,makesurethatthestaffinchargehavereadandfullyunderstoodthecontentsofthisQuickstart.
Inparticular,observethesafetyrecommendationsandintendeduse. Thedevice/theinstallationmustonlybecommissionedbysuit-ablytrainedstaff.
Beforecommissioningthedevice,entertheKfactorofthefittingused.Seechap."8.7EnteringtheKfactorofthefittingused".
8.2 operating levels of the device Thedevicehastwooperatinglevels:theProcesslevelandtheCon-figurationlevel.Tab. 5 : Default settings of the device
function defaultvalueLANGUAGE EnglishUNIToftheflowrate l/minUNITofthetotalizers litreOUTPUTAO1 4mA=0.000
20mA=0.000ERR.22mAdisabled
OUTPUTDO1 pulsePU=0.00litre
OUTPUTSDO2andDO3
Hysteresis,notinverted2-=3-=0.0002+=3+=0.000
timedelays2and3=0
KFACTOR 1
FILTER 2,fast
CUT-OFF 0.000
BACKLIGHT level9,activatedfor30s
FLOW-WARNING W-=W+=0.000
VOLUME-WARNING 000000
English
38
Adjustment and commissioning
Type 8025 UNIVERSAL
LANGUAGE
Processlevel
Parametersmenu TestMenu
UNit
K-FACtOR
OUtPUt
FiLtER
tOtAL
CUt-OFF
BACKLit
END
12.6 L/MiN
16.45 MA
87654 L
231 L.
CAL AO1
FREQUENC.
FLOw
wARNiNG
END
0......9
0......9
0......9
0......9
ENTER
ENTER
SAVE N/Y
>5s
>5s
Configurationlevel
0......9
>2s
Toresetthedailytotalizer(iden-tifiedbyadotafterthevolumeunits).
+
>2s
MEAS. OVF
DiSP. OVF
AO1 LOSt
END
Informationmenu1)
0......9
Processlevel
ENTER
1)AccessiblewhenthedevicestatusLEDisorangeorred.
English
39
Adjustment and commissioning
Type 8025 UNIVERSAL
8.3 Description of the navigation keys and the status LEDs
• Selectingthedisplayedparameter
• Confirmingthesettings
StatusLEDofrelayDO3(LEDON=contactclosed)
• Readingthemessages
• Scrollingthroughtheparameters
• Selectingthefigureontheleft
• Scrollinguptheparameters
• Incrementingthefigureselected
DevicestatusLED:seefol-lowingtable.
StatusLEDofrelayDO2(LEDON=contactclosed)
English
40
Adjustment and commissioning
Type 8025 UNIVERSAL
devicestatusled statusofthedevice
Green Thedeviceoperatescorrectly.
Orange Awarningmessageisgenerated.
→ Pressthe keyfor2secondsintheProcessleveltoaccessthemessage.SeethecompleteOperatingInstructionsforthemeaning.
Furthermore,arelayoutput(DO2orDO3)orthetransistoroutputDO1switchesifitisconfiguredinthe"WARNING"mode(seethecompleteOperatingInstructions)
Red Anerrormessagehasbeengeneratedandthecurrentoutputsendsouta22mAcurrent(ifparameter"ERR.22mA"issetto"ENABLED".SeethecompleteOperatingInstructions.
→ Pressthe keyfor2secondsintheProcessleveltoaccessthemessage.SeethecompleteOperatingInstructionsforthemeaning.
Blinking,whateverthecolour Acheckforthecorrectbehaviouroftheoutputsisrunning(seethecompleteOperatingInstructions).
English
41
Adjustment and commissioning
Type 8025 UNIVERSAL
8.4 Using the navigation keys
youwantto... press...movebetweenparameterswithinaleveloramenu.
• togotothenextparameter.
• 0......9 togotothepreviousparameter.accesstheParametersmenu. ENTER
+ simultaneouslyfor5s,intheProcesslevel
accesstheTestmenu.0......9 + +
ENTER
simultaneouslyfor5s,intheProcesslevel
accesstheInformationmenu.for2s,intheProcesslevel,whenthedevicestatusLEDisorangeorred.
resetthedailytotalizer.0......9 + simultaneouslyfor2s,whenthedailytotalizerisdisplayedintheProcesslevel
selectthedisplayedparameter. ENTER
confirmthedisplayedvalue. ENTER
modifyanumericalvalue.• 0......9 toincreasetheblinkingdigit.
• toselectthedigitattheleftoftheblinkingdigit.
• 0......9 + tomovethedecimalpoint.
English
42
Adjustment and commissioning
Type 8025 UNIVERSAL
8.5 Details of the process levelThislevelisactivebydefaultwhenthedeviceisenergized.
12.6 L/MiN
16.45 MA
87654 L
231 L.
0......9
>2s
Resettingthedailytotalizer.
Valueofthemeasuredflowrate,displayedintheunitchoseninthe"UNIT"parameteroftheParametersmenu.
Valueofthecurrentoutput,proportionaltothemeasuredflowrate.
Valueofthemaintotalizer,volumeoffluidcountedbythedevicesincethelastreset.
Valueofthedailytotalizer(identifiedbyadotafterthevolumeunits),volumeoffluidcountedbythedevicesincethelastreset.
0......9
+
0 L/MiN.
Thedisplayedflowrateissetto0(adotisdisplayedaftertheflowrateunitswhenthefunctionCUT-OFFisactive)becausethemeasuredflowrateisbelowthethresholdvaluedefinedinthe"CUT-OFF"parameteroftheParametersmenu.
or
English
43
Adjustment and commissioning
Type 8025 UNIVERSAL
8.6 Details of the parameters menu
LANGUAGE
Processlevel
UNit
K-FACtOR
OUtPUt
FiLtER
tOtAL
CUt-OFF
BACKLit
END 12.6 L/MiN
0......9
Choosingthedisplaylanguage.
SAVE N/Y
Choosingtheflowrateunit,thenumberofdecimalsandtheunitthetotalizersaredisplayedin.
EnteringtheKfactorofthefittingusedorhavingitdefinedthroughaTeach-Inprocedure.
Parameterizingthe4...20mAcurrentoutput(AO1)andconfiguringthetransistoroutput(DO1)and,ifthedeviceisequippedwith,the2relayoutputs(DO2andDO3).
Choosingthefilterlevelofthemeasuredflowrate,onthedisplayedflowrateandtheAO1currentoutput.
Resettingbothtotalizers.
Enteringthemeasuredflowratevaluebelowwhichthedevicesetsthemeasuredflowrateto0witheffectonthedisplay,theoutputsandthetotalizers.
SettingthebrightnessofthedisplayandhowlongitstaysON,ordeactivatingthebacklight.
SavingthechangesmadewithintheParametersmenuornot.Ifthechangesaresaved,thedeviceoperateswiththenewsettings.
English
44
Adjustment and commissioning
Type 8025 UNIVERSAL
8.7 Entering the k factor of the fitting usedThedevicedeterminestheflowrateinthepipeusingthefittingKfactor.
TheKfactorofthefittingusedcanbeenteredhere.ThedevicemayalsodeterminetheKfactorusingaTeach-Inprocedure:SeethecompleteOperatingInstructions.
ThedevicewillusethenewKfactorassoonas"SAVEYES"isconfirmedwhenleavingtheParametersmenu.
TheKfactorofthefittingusedisintheOperatingInstructionsofthefitting.
TheOperatingInstructionsoftheBürkertfittingscanbefoundontheinternetatwww.burkert.com.
ThedisplayshowstheKfactorofthefitting,lastenteredordeterminedusingaTeach-Inprocedure.
→ Edittheparameter.
K-FACtOR K=10.000
REtURN
→ EntertheKfactor(valuebetween0.01and99999.9)ofthefittingused.
→ Confirmthedisplayedvalue.
K=2.8500
OUtPUt VALiD N/YIsonlydisplayediftheKfactorhasbeenchanged.
→ ConfirmtheenteredKfactorornot.
Fig. 26 : Entering the K factor of the fitting used
English
45
Adjustment and commissioning
Type 8025 UNIVERSAL
8.8 Details of the Test menu
CAL AO1
Processlevel
FREQUENC.
FLOw
wARNiNG
12.6 L/MiNEND
0......9
Adjustingthe4...20mAoutput.
SAVE N/Y
Readingtherotationalfrequencyofthepaddlewheel.
Simulatingaflowratetocheckthecorrectoperatingoftheoutputs.
SavingthechangesmadewithintheTestmenuornot.Ifthechangesaresaved,thedeviceoperateswiththenewsettings.
FLOw-w.
VOLUME-w.
REtURN
Settingtheflowratethresholdvaluesforwhichawarningmessageisgenerated.
Settingathresholdvalueofthedailytotalizer,forwhichawarningmessageisgenerated.
0......9
English
46
Packaging, Transport
Type 8025 UNIVERSAL
9 pAckAGING, TRANSpoRT
NOTICe
damageduetotransport
Transportmaydamageaninsufficientlyprotecteddevice. Transportthedeviceinshock-resistantpackagingandawayfromhumidityanddirt.
Donotexposethedevicetotemperaturesthatmayexceedtheadmissiblestoragetemperaturerange.
Protecttheelectricalinterfacesusingprotectiveplugs.
10 SToRAGE
NOTICe
poorstoragecandamagethedevice. Storethedeviceinadryplaceawayfromdust. Storagetemperatureofthedevice:–10...+60°C.
11 DISpoSAL of ThE DEVIcE→ Disposeofthedeviceanditspackaginginanenvironmentally-
friendlyway.
NOTICe
damagetotheenvironmentcausedbypartscontaminatedbythefluid.
Complywiththenationaland/orlocalregulationswhichconcerntheareaofwastedisposal.
English
www.burkert.com