Electronic Control LCE Manuale Utente User Manual Benutzerhandbuch LCE IT-EN-DE MC00003_04-IT-EN-DE - 10/2015 Le unità regolate Units regulated Unidades reguladas Einheiten geregelt RKB RKE 3V RKE-BP RKH RKS 3V Firmware 2.4 True life inside air and water handling for a confortable life

Upload: others

Post on 27-Sep-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Electronic Control LCE Manuale Utente

User Manual

Benutzerhandbuch

LCE

IT-EN-DE

MC00003_04-IT-EN-DE - 10/2015

Le unità regolate

Units regulated

Unidades reguladas

Einheiten geregelt

RKB

RKE 3V

RKE-BP

RKH

RKS 3V

Firmware 2.4

True life inside

air and water handling

for a confortable life

Page 2: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 1 / 6

firmware 2.4

IT

Specifiche controllo:

Selezione automatica / manuale delle velocità

Gestione valvola freddo / promiscua

Gestione valvola calda

Gestione resistenza ON-OFF

Post ventilazione

Gestione serranda free-cooling

Gestione allarmi

o Errore sonda

o Surriscaldamento resistenza

o Allarme filtro sporco

Programmazione settimanale

ON-OFF remoto

Display remoto con sensore interno

Logica di controllo

Nei seguenti diagrammi viene illustrata la logica di controllo estiva-invernale

Heating

Heating logic

Ventilation

+

2°C

Tsp-Te

Tsp-Treg

Cooling logic

Ventilation

By-pass

+ By-pass

Cooling

2°C Tsp-Te

Tsp-Treg

Cooling modulation

By-pass

Cooling modulation

+

Heating modulation

Ventilation

2°C

1°C

1°C

Heating

Heating modulation + By-pass

By-pass

2°C

Ventilation

Cooling

By-pass 0

.5°C

0.5

°C

Treg = temperatura sonda di regolazione (di mandata o ambiente su display remoto)

Tsp = temperatura di set point

Te = temperatura sonda aria esterna

Page 3: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 2 / 6

firmware 2.4

IT

Programmazione settimanale

Per ogni giorno della settimana è possibile scegliere tra 4 programmi:

Programma P1: l’u ità vie e accesa i due fasce orarie ad ese pio u a al atti o e u a alla sera

Programma P2: l’u ità vie e accesa i u a sola fascia oraria

Programma P3: l’u ità vie e accesa tutto il giorno

Programma P4: l’u ità vie e spe ta tutto il gior o

Display

Icone:

A3-A6: Programma settimanale attivo

A7-A10: Velocità ventilatore

A11: ON: OFF manuale

LAMPEGGIANTE: OFF da programma settimanale

A12, A13, A15: modo operativo / durante settaggio: set visualizzato

A16: ON: allarme attivo

LAMPEGGIANTE: allarme riamabile

A17: Free cooling / Free heating attivo

A19: Ora visualizzata

A29-A35: Giorno della settimana

On-Off

On-Off è gestito nei seguenti modi:

Off da ingresso digitale ha priorità su tutto

Off da tastiera remota:

1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo

2) Se le fasce orarie sono abilitate, l'on/off da tastiera remota è temporaneo fino al successivo

evento (in questo caso il profilo selezionato lampeggia). Il set utilizzato è l’ulti o selezio ato dalle fasce orarie. In caso di black-out l’u ità riparte co le fasce orarie.

Off da BMS via MODBUS

Off da fasce orarie

Page 4: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 3 / 6

firmware 2.4

IT

Tastiera

Pressione breve:

Set orologio

Pressione lunga:

Cambio On/Off

Pressione lunga:

Abilita disabilita fasce orarie

Pressione breve:

Cambio velocità ventilatore

Pressione lunga:

Cambio modo

Pressione breve:

Menù setpoint

e allarme.

Pressione breve:

Menù ““ Pressione lunga:

Temperatura esterna

giorni della settimana (1= lunedì)

Lista Menu Prg

Premere i sie e Esc e “et

Prof: in questa sezione vi sono le impostazioni per la programmazione settimanale:

o ST1: ora inizio 1° fascia 1° programma

o EN1: ora fine 1° fascia 1° programma

o SE1 (estate): set-point 1° fascia 1° programma

o SE1 (inverno): set-point 1° fascia 1° programma

o ST2: ora inizio 2° fascia 1° programma

o EN2: ora fine 2° fascia 1° programma

o SE2 (estate): set-point 2° fascia 1° programma

o SE2 (inverno): set-point 2° fascia 1° programma

o ST: ora inizio 2° programma

o END: ora fine 2° programma

o SET (estate): set-point 2° programma

o SET (inverno): set-point of 2° programma

Day: in questa sezione si associa il giorno al programma

o Mon: Programma Lunedì, possibili valori

P1 l’u ità vie e accesa i due fasce orarie

P2 l’u ità vie e accesa i una sola fasce orarie

P3 l’u ità vie e accesa tutto il gior o

P4 l’u ità vie e spe ta tutto il gior o

o Tue: Programma Martedì

o Wed: Programma Mercoledì

o Thu: Programma Giovedì

o Fri: Programma Venerdì

o Sat: Programma Sabato

o Sun: Programma Domenica

Auto: Set cambio modo estate inverno

o SAUT: Set cambio modo estate inverno in automatico da temperatura esterna

o dAUT: Differenziale cambio modo estate inverno in automatico da temperatura esterna

Page 5: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 4 / 6

firmware 2.4

IT

Serv: in questa sezione si va a configurare il controllo

o PWD: in serire password per service (1)

o Pcfg: configurazione impianto

0= sistema a 2 tubi, batteria unica promiscua

1= sistema a 2 tubi, batteria fredda + resistenza

2= sistema a 4 tubi, batteria fredda + batteria calda

o Rprop: sonda di regolazione

0= sonda mandata aria

1= sonda interna al display

Menu Set

Premere Set

Set-point estivo manuale

Set-point invernale manuale

Cartella allarmi:

o Er01: Errore sonda di regolazione:

L’u ità vie e spe ta

Allarme a riarmo automatico

o Er02: Allarme sonda aria esterna:

Free-cooling disattivato

Allarme a riarmo automatico

o Er03: Errore sonda Display:

“e Rprop= l’u ità vie e spe ta

“e Rprop= l’allar e o vie e visualizzato

o Er04: Allarme filtro sporco:

Sola visualizzazione

o Er05: Surriscaldamento resistenza elettrica:

Resistenza disattivata

Ventilatori attivati

Modbus

Tipo di modbus Holding Register

Commando di lettura: 03 (03Hex)

Commando di scrittura: 16 (10Hex)

Come modificare i protocolli di comunicazione Modbus:

collegarsi via Modbus tramite la RS-485 con i protocolli di default:

indirizzo= 1

baud rate= 9600

parità= EVEN

Bit di dati= 8 (non modificabile)

Bit di stop= 1 (non modificabile)

modificare secondo le necessità i protocolli ai seguenti indirizzi:

53274= indirizzo (1-255)

53275= baud rate

3= 9600 baud (default)

4= 19200 baud

5= 38400 baud

6= 58600 baud

7= 115200 baud

53276= parità

1= EVEN (default)

2= NONE

3= ODD

per memorizzare è necessario riavviare il dispositivo.

Esempio cablaggio rete

Cable

Grigio: GND Bianco: +

Nero: -

Page 6: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 5 / 6

firmware 2.4

IT

1.1. Variabili utente:

MODBUS Tipo: HOLDING REGISTER

Commando di lettura: 03 (03Hex)

Commando di scrittura: 16 (10Hex)

Indirizzo

Scrittura/Lettura Descrizione MOD BUS Valore Um Default Min Max

53274 Modbus protocol controller address 1

1 1 255

53275

Modbus baud rate protocol

3= 9600 baud (default)

4= 19200 baud

5= 38400 baud

6= 58600 baud

7= 115200 baud

3

3 3 7

53276

Modbus parity protocol

1= EVEN (default)

2= NONE

3= ODD

1

1 1 3

Indirizzo

Scrittura/Lettura Descrizione SET Valore Um Default Min Max

16389 3 Point Valve Cooling

Proportional Band 2 °C 20 1 100

16390 3 Point Valve Heating

Proportional Band 2 °C 20 1 100

16391 Fan Auto:

Differential Medium Speed 2 °C 20 1 100

16392 Fan Auto:

Differential Maximum Speed 2 °C 20 1 100

16393 Heater Differential 2 °C 20 1 100

16394 Heater Post Ventilation Time 60 Sec 60 10 500

16395 FreeCooling Differential 1 °C 10 1 100

16396 FreeHeating Differential 1 °C 10 1 100

16397 Free Cooling Hysteresis 0.5 °C 5 1 15

16398 Cambio modo:

0 = Cool; 1 = Heat; 2 = Auto 2

2 0 2

16399

Stato On Off (Memorized into

EEprom)

0 = Off; 1 = On

0

0 0 1

16400

Controllo ventilatore

0 = Min; 1 = Med; 2 = Max; 3 =

Auto

3

3 0 3

16401 Setpoint Freddo 26.0 °C 260 50 350

16402 Setpoint Caldo 20.0 °C 200 50 350

16403 Profilo 1: Inizio banda 1 08:00 HH:MM 480 0 Profilo 1: Fine Banda 1

16404 Profilo 1: Fine banda 1 12:00 HH:MM 720 Profilo 1: Inizio banda 1 1439

16405 Profilo 1: Inizio banda 2 14:00 HH:MM 840 0 Profilo 1: Fine Banda 2

16406 Profilo 1: Fine banda 2 17:00 HH:MM 1020 Profilo 1: Inizio banda 2 1439

16407 Profilo 2: Inizio banda 08:00 HH:MM 480 0 Profilo 2: Fine Banda

16408 Profilo 2: Fine banda 17:00 HH:MM 1020 Profilo 2: Inizio banda 1439

16409 Profilo 1: Set Banda Freddo 1 26.0 °C 260 Profilo 1: Set Banda Caldo 1 350

16410 Profilo 1: Set Banda Freddo 2 26.0 °C 260 Profilo 1: Set Banda Caldo 2 350

16411 Profilo 2: Set Banda Freddo 26.0 °C 260 Profilo 2: Set Banda Caldo 350

16412 Profilo 1: Set Banda Caldo 1 20.0 °C 200 50 Profilo 1: Set Banda Freddo 1

16413 Profilo 1: Set Banda Caldo 2 20.0 °C 200 50 Profilo 1: Set Banda Freddo 2

Page 7: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Manuale Utente

Light control manual-ITA-neutro_03.docx Rev. 04 IT 6 / 6

firmware 2.4

IT

16414 Profilo 2: Set Banda Caldo 20.0 °C 200 50 Profilo 2: Set Banda Freddo

16415 Selezione Profilo Lunedì

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16416 Selezione Profilo Martedì

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16417 Selezione Profilo Mercoledì

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16418 Selezione Profilo Giovedì

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16419 Selezione Profilo Venerdì

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16420 Selezione Profilo Sabato

1 = P1; 2 = P2; 3 = P3; 4 = P4 2

2 1 4

16421 Selezione Profilo Domenica

1 = P1; 2 = P2; 3 = P3; 4 = P4 4

4 1 4

16422 Abilitazione Profilo

0 = Off; 1 = On 0

0 0 1

16423 Setpoint antigelo (rev 2.1) 5.0 °C 50 -50 150

16424 Differenziale antigelo (rev 2.1) 1.0 °C 10 1 50

Indirizzo Lettura Descrizione Ingressi-Uscite Valore Um Default Min Max

8192 State On-Off digital input (DI1)

0 = On; 1 = Off 0

0 0 1

8960 Sonda temperatura di regolazione 17.5 °C 0 -500 1100

8961 Velocità attuale del ventilatore

0 = Off; 1 = Min; 2 = Med; 3 = Max 0

0 0 3

8962 Posizione valvola tre vie fredda o

promiscua 0.0 % 0 0 1000

8963 Posizione valvola tre vie caldo 0.0 % 0 0 1000

8964 Stato batteria elettrica

0 = Off; 1 = On 0

0 0 1

8965 Stato serranda Bypass

0 = Off; 1 = On 0

0 0 1

8966 Temperatura esterna 11.2 °C 0 -500 1100

8968 Stato On Off 0

0 0 1

Indirizzo Lettura

Descrizione

Allarmi

0= Non attivo

1= Attivo

2=Reset manuale Valore Um Default Min Max

9000 Errore sonda temperatura di

regolazione 0

0 0 1

9001 Errore sonda temperatura esterna 0

0 0 1

9002 Errore sonda temperatura tastiera 0

0 0 1

9003 Allarme filtri ostruiti 0

0 0 1

9004 Allarme batteria elettrica (Reset

Manuale) 0

0 0 2

9005 Allarme antigelo (rev 2.1) 0 0 0 1

Indirizzo Lettura Descrizione Versione Valore Um Default Min Max

9471 Versione applicativo (Software) 2.1 21

Note:

(diviso 10, °C) dividere il valore per 10, il risultato sarà in gradi centigradi con una cifra decimale (Es: 175= 17.5°C)

(diviso 10, %) dividere il valore per 10, il risultato sarà in percentuale con una cifra decimale (Es: 505= 50.5%)

(HH:MM) minuti a partire da mezzanotte dove 0= 00:00 e 1439= 23:59 (Es: 120= 02:00; 1170= 19:30)

Page 8: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 1 / 6

firmware 2.4

EN

Control features:

Automatic / Manual 3 speed fan

3 point cooling / changeover floating valve

3 point heating floating valve

ON-OFF Electric heater

Post ventilation

Free cooling - Free heating damper

Alarm management and diagnostic

o Sensor failure

o Heater over temperature

o Dirty filter alarm

Clock program management

Remote ON-OFF

Remote display with internal sensor

Control logic

In the following diagrams is explained the summer-winter control logic

Heating

Heating logic

Ventilation

+

2°C

Tsp-Te

Tsp-Treg

Cooling logic

Ventilation

By-pass

+ By-pass

Cooling

2°C Tsp-Te

Tsp-Treg

Cooling modulation

By-pass

Cooling modulation

+

Heating modulation

Ventilation

2°C

1°C

1°C

Heating

Heating modulation + By-pass

By-pass

2°C

Ventilation

Cooling

By-pass 0

.5°C

0.5

°C

Treg = regulation probe temperature

Tsp = Set point temperature

Te = External probe temperature

Page 9: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 2 / 6

firmware 2.4

EN

Weekly program

For each day of the week it is possible to select between 4 programs:

Program P1: the unit is turned ON in two different time range (for example one in the morning and

one in the afternoon)

Program P2: the unit turned ON in a single time range

Program P3: the unit is turned ON all the day

Program P4: the unit is turned OFF all the day

Display

Icons:

A3-A6: Active weekly program

A7-A10: Fan speed

A11: ON: Manual OFF

BLINKING: Weekly program OFF

A12, A13, A15: Working mode / while setting: visualizing set point

A16: ON: active alarm

BLINKING: resettable alarm

A17: Freecooling/Freeheating

A19: Clock time viewing

A29-A35: Day of the week

On-Off

The unit can be turned On-Off in the following way:

Off by digital input, main priority

Off by Remote keyboard:

1) While weekly program is not active, the unit is definitively On/Off

2) While weekly program is active, the unit can be temporarily turned On/Off till next event (in case

of this the active profile led blinks). The set point is the same of the last time range. In case of

blackout the unit restarts with the weekly program activated.

Off by BMS via MODBUS

Off by weekly program

Page 10: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 3 / 6

firmware 2.4

EN

Keyboard

Short press:

Fan speed change

Short press:

Clock Set

Long press:

Toggle On/Off

Long press :

Enable / disable clock program

Short press:

Setpoint and

alarm menu

Long press:

Actual setpoint Short press:

menu

days of the week (1 = Monday)

Long press:

Summer / winter

change

Menu Prg List

Press together utto Es a d “et

Prof: in this section there are the settings for the weekly program

o ST1: start time of1st range of 1st

program

o EN1: end time of 1st

range of 1st

program

o SE1 (summer): set-point of 1st

range of 1st

program

o SE1 (winter): set-point of 1st

range of 1st

program

o ST2: start time of 2nd

range of 1st

program

o EN2: end time of 2nd

range of 1st

program

o SE2 (summer): set-point of 2nd

range of 1st

program

o SE2 (winter): set point of 2nd

range of 1st

program

o ST: start time of 2nd

program

o END: end time of 2nd

program

o SET (summer): set-point of 2nd

program

o SET (winter): set-point of 2nd

program

Day: i this se tio there’s the progra assig e t for each day

o Mon: Monday program, possible value

P1 the unit is turned ON in two different time range

P2 the unit turned ON in a single time range

P3 the unit is turned ON all the day

P4 the unit is turned OFF all the day

o Tue: Tuesday program

o Wed: Wednesday program

o Thu: Thursday program

o Fri: Friday program

o Sat: Saturday program

o Sun: Sunday program Auto: Automatic summer/winter changeover parameters

o SAUT: Fresh air temperature set point for automatic changeover

o dAUT: Season changeover differential

Page 11: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 4 / 6

firmware 2.4

EN

Serv: in this section there is the controller configuration

o PWD: insert service password (1)

o Pcfg: plant configuration

0= 2 pipes system, unique changeover coil

1= 2 pipes system, cooling coil + electric heater

2= 4 pipes system, cooling coil + heating coil

o Rprop: regulation probe

0= supply air sensor

1= display sensor

Menu Set List

Press button Set

Manual summer set-point

Manual winter set-point

Alarm folder:

o Er01: Regulation sensor failure; effects:

The unit is turned off

Automatic reset alarm

o Er02: External air sensor failure; effects:

Free-cooling mode disabled

Automatic reset alarm

o Er03: Display sensor failure; effects:

If Rprop=1 the unit is turned off

If Rprop=0 alarm not shown

o Er04: Dirty filter alarm; effect

None

o Er05: Electric heater over-temperature; effects:

Electric heater disabled

Fan activated

Modbus Modbus type Holding Register

Read command: 03 (03Hex)

Write command: 16 (10Hex)

To modify the modbus communication protocols do as follows:

connect via Modbus through the RS-485 port with default protocols:

address= 1

baud rate= 9600

parity= EVEN

Word length= 8 (not editable)

Stop bits= 1 (not editable)

modify as you need the protocols writing the following address:

53274= address (1-255)

53275= baud rate

3= 9600 baud (default)

4= 19200 baud

5= 38400 baud

6= 58600 baud

7= 115200 baud

53276= parity

1= EVEN (default)

2= NONE

3= ODD

To activate the changes reboot the controller.

Net wiring example

Cable

Gray: GND White: +

Black: -

Page 12: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 5 / 6

firmware 2.4

EN

1.1. User variables:

MODBUS Point Type: HOLDING REGISTER

Read command: 03 (03Hex)

Write command: 16 (10Hex)

Address

write/read

Description

MODBUS Value Um Default Min Max

53274 Modbus protocol controller

address 1

1 1 255

53275

Modbus baud rate protocol

3= 9600 baud (default)

4= 19200 baud

5= 38400 baud

6= 58600 baud

7= 115200 baud

3

3 3 7

53276

Modbus parity protocol

1= EVEN (default)

2= NONE

3= ODD

1

1 1 3

Address

write/read

Description

SET Value Um Default Min Max

16389 3 Point Valve Cooling

Proportional Band 2 °C 20 1 100

16390 3 Point Valve Heating

Proportional Band 2 °C 20 1 100

16391 Fan Auto:

Differential Medium Speed 2 °C 20 1 100

16392 Fan Auto:

Differential Maximum Speed 2 °C 20 1 100

16393 Heater Differential 2 °C 20 1 100

16394 Heater Post Ventilation Time 60 Sec 60 10 500

16395 FreeCooling Differential 1 °C 10 1 100

16396 FreeHeating Differential 1 °C 10 1 100

16397 Free Cooling Hysteresis 0.5 °C 5 1 15

16398 User Working Mode:

0 = Cool; 1 = Heat; 2 = Auto 2

2 0 2

16399

On Off Status (Memorized into

EEprom)

0 = Off; 1 = On

0

0 0 1

16400

Fan Control

0 = Min; 1 = Med; 2 = Max; 3 =

Auto

3

3 0 3

16401 Setpoint Cooling 26.0 °C 260 50 350

16402 Setpoint Heating 20.0 °C 200 50 350

16403 Profile 1: Start band 1 08:00 HH:MM 480 0 Profile 1: End band 1

16404 Profile 1: End band 1 12:00 HH:MM 720 Profile 1: Start band 1 1439

16405 Profile 1: Start band 2 14:00 HH:MM 840 0 Profile 1: End band 2

16406 Profile 1: End band 2 17:00 HH:MM 1020 Profile 1: Start band 2 1439

16407 Profile 2: Start band 08:00 HH:MM 480 0 Profile 2: End band

16408 Profile 2: End band 17:00 HH:MM 1020 Profile 2: Start band 1439

16409 Profile 1: Set Cool Band 1 26.0 °C 260 Profile 1: Set Heat Band 1 350

16410 Profile 1: Set Cool Band 2 26.0 °C 260 Profile 1: Set Heat Band 2 350

16411 Profile 2: Set Cool Band 26.0 °C 260 Profile 2: Set Heat Band 350

16412 Profile 1: Set Heat Band 1 20.0 °C 200 50 Profile 1: Set Cool Band 1

Page 13: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE User Manual

Light control manual-ENG-neutro_03.docx Rev. 04 EN 6 / 6

firmware 2.4

EN

16413 Profile 1: Set Heat Band 2 20.0 °C 200 50 Profile 1: Set Cool Band 2

16414 Profile 2: Set Heat Band 20.0 °C 200 50 Profile 2: Set Cool Band

16415 Monday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16416 Tuesday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16417 Wednesday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16418 Thursday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16419 Friday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16420 Saturday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 2

2 1 4

16421 Sunday Profile Selection

1 = P1; 2 = P2; 3 = P3; 4 = P4 4

4 1 4

16422 Profile Enabled

0 = Off; 1 = On 0

0 0 1

16423 Antifreeze Setpoint (rev 2.1) 5.0 °C 50 -50 150

16424 Antifreeze Differential (rev 2.1) 1.0 °C 10 1 50

Address

read

Description

Input-Output Value Um Default Min Max

8192 State On-Off digital input (DI1)

0 = On; 1 = Off 0

0 0 1

8960 Regulation Sensor Temperature 17.5 °C 0 -500 1100

8961 Current Fan Speed

0 = Off; 1 = Min; 2 = Med; 3 = Max 0

0 0 3

8962 Three Point Cold or Changeover

Valve Estimated Position 0.0 % 0 0 1000

8963 Three Point Hot Valve Estimated

Position 0.0 % 0 0 1000

8964 Heater Status

0 = Off; 1 = On 0

0 0 1

8965 External Bypass Status

0 = Off; 1 = On 0

0 0 1

8966 Fresh Air Temperature 11.2 °C 0 -500 1100

8968 On Off Status 0

0 0 1

Address

read

Description

Allarm

0= Not Active

1= Active

2=Manual Reset Value Um Default Min Max

9000 Suplpy Air Sensor Error 0

0 0 1

9001 Fresh Air Sensor Error 0

0 0 1

9002 SKW Display Sensor Error 0

0 0 1

9003 Filter Alarm 0

0 0 1

9004 Heater Overheating Alarm

(Manual Reset) 0 0 0 2

9005 Antifreeze Alarm (rev 2.1) 0

0 0 1

Address

read

Description

Version Value Um Default Min Max

9471 Application version 2.1 21

Note:

(divided 10, °C) divide the value by 10, the result is in degree Celsius with one decimal place (Es: 175= 17.5°C)

(divided 10, %) divide the value by 10, the result is in percentage with one decimal place (Es: 505= 50.5%)

(HH:MM) minutes starting from midnight where 0= 00:00 e 1439= 23:59 (In example: 120= 02:00; 1170= 19:30)

Page 14: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 1 / 6

firmware 2.4

DE

EE Steuerungen:

Automatischer/ manueller 3 Geschwindigkeiten Lüfter

3-PunktKühlung/ Wechselventil

3-Punkt Heizung Schwimmerventil

ON-OFF Elektroheizer

Nachlüftung

Free Cooling/Free HeatingSchieber

Alarmmanagement und-diagnose o Fehler Temperaturfühler

o Überhitzung Heizer

o Alarm verschmutzter Filter

Uhr-Programmierung

ON-OFF Fernbedienung

Fernanzeige auf Display mit Innensensor

Steuerlogik

In den folgenden Diagrammen wirden die Sommer-Winter Steuerlogik gezeigt

Heating

Heating logic

Ventilation

+

2°C

Tsp-Te

Tsp-Treg

Cooling logic

Ventilation

By-pass

+ By-pass

Cooling

2°C Tsp-Te

Tsp-Treg

Cooling modulation

By-pass

Cooling modulation

+

Heating modulation

Ventilation

2°C

1°C

1°C

Heating

Heating modulation + By-pass

By-pass

2°C

Ventilation

Cooling

By-pass 0

.5°C

0.5

°C

Treg = Regulierung Messtemperatur

Tsp = Eingestellte Temperatur (Set Point)

Te = gemessene Außentemperatur

Page 15: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 2 / 6

firmware 2.4

DE

EE Wochenprogrammierung

Man kann für jeden Tag der Woche aus 4 Programmen vorwählen:

Programm P1: Das Gerät wird zu zwei Zeitbereichen eingeschaltet(Z. B. am Morgen und am Abend)

Programm P2: Das Gerät wird nur zu einem Zeitbereich eingeschaltet

Programm P3: Das Gerät bleibt den ganzen Tag eingeschaltet

Programm P4: Das Gerät bleibt den ganzen Tag ausgeschaltet

Bildschirmanzeige

Ikonen:

A3-A6: Wochenprogramm aktiviert

A7-A10: Geschindigkeit Ventilator

A11: ON: Handeinstellung OFF

BLINKEND: Wochenprogramm OFF A12, A13, A15: Betriebsmodus / während Einstellung: Anzeige der Set Points

A16: ON: Alarm aktiviert

BLINKEND: Alarmzurücksetzbar

A17: FreeCooling/ Free Heating aktiviert

A19: Uhrzeit-Anzeige

A29-A35: Wochentag

Ein-Aus

Die Ein-Aus wird auf folgende Weise verwaltet:

Aus den digitalen Eingang hat Vorrang vor allen

Aus von Remote-Tastatur:

1) Wenn die Zeitschlitze deaktiviert sind, ist der Ein / Aus durch Ferntastatur endgültige

2) Wenn die Zeitschlitze aktiviert ist, ist das Ein / Aus von Fernbedien bis zum nächsten Ereignis (in diesem Fall das ausgewählte Profil blinkt) vorübergehend. Der verwendete Satz der letzten

Zeitschlitze ausgewählt. Im Falle eines Stromausfalls startet das Gerät mit den Bändern.

Aus BMS über Modbus

Aus Zeitbänder

Page 16: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 3 / 6

firmware 2.4

DE

EE Tastatur

Short press:

Fan speed change

Short press:

Clock Set

Long press:

Toggle On/Off

Long press :

Enable / disable clock program

Short press:

Setpoint and

alarm menu

Long press:

Actual setpoint Short press:

menu

days of the week (1 = Monday)

Long press:

Summer / winter

change

Menüprogrammliste

Gleichzeitig Esc und “et drücken

Prof: In diesem Abschnitt finden Sie die Einstellungen für die Wochen-Programmierung

o ST1: Uhrzeit Beginn 1. Zeitbereich 1. Programm

o EN1: Uhrzeit Ende 1. Zeitbereich 1. Programm

o SE1 (Sommer): Set Point 1.Zeitbereich 1. Programm o SE1 (Winter): Set Point 1. Zeitbereich 1. Programm

o ST2: Uhrzeit Beginn 2. Zeitbereich 2. Programm

o EN2: Uhrzeit Ende2. Zeitbereich 2. Programm

o SE2 (Sommer): Set Point 2. Zeitbereich 2. Programm

o SE2 (Winter): Set Point 2. Zeitbereich 2. Programm

o ST: UhrzeitBeginn 2. Programm

o END: UhrzeitEnde 2. Programm

o SET (Sommer): Set Point 2. Programm

o SET (Winter): Set Point 2. Programm

Day: In diesem Abschitt finden Sie die Programmzuweisung für jeden Tag o Mon: ProgrammMontag, mögliche Werte

P1 Das Gerät wird zu zwei Zeitbereichen eingeschaltet

P2 Das Gerät wird nur zu einem Zeitbereich eingeschaltet

P3 Das Gerät bleibt den ganzen Tag eingeschaltet

P4 Das Gerät bleibt den ganzen Tag ausgeschaltet

o Tue: Programm Dienstag

o Wed: Programm Mittwoch

o Thu: Programm Donnerstag

o Fri: Programm Freitag

o Sat: Programm Samstag

o Sun: Programma Sonntag

Auto: Sollwert Modus-Schalter Sommer Winter o SAUT: Sollwert-Modus automatisch an Sommer Winter Außentemperatur

o dAUT: Differential-Modus Schalt automatisch von Sommer-Winter-Outdoor-Temperatur

Page 17: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 4 / 6

firmware 2.4

DE

EE Serv:In diesem Abschnitt wird die Steuerung konfiguriert

o PWD: Service-Passwort eingeben (1)

o Pcfg: Konfiguration der Anlage

0=System mit 2 Leitungen, Mischspirale

1= System mt 2 Leitungen, Kühlspirale+ Heizspirale

2= System mit 4 Leitungen Kühlspirale+ Heizspirale

o Rprop: Regelfühler

0= Luftfühler

1= Bildschirmsensor

Menü-Einstellung

Set drücken

Set Point Sommer Handbetrieb

Set PointWinter Handbetrieb

Alarmliste: o Er01: Fehler Regelfühler:

Gerät schaltet sich aus

Automatische Zurücksetzung des Alarms

o Er02: Alarm Luftfühler:

Free Cooling deaktiviert

Automatische Zurücksetzung des Allarms

o Er03: Fehler Bildschirmsensor:

Bei Rprop=1 wird das Gerät ausgeschaltet

Bei Rprop=0 wird der Alarm nichtauf dem Bildschirm angezeigt

o Er04: Alarm verschmutzter Filter:

Alarm wir nur angezeigt

o Er05: Überhitzung Elektroheizer:

Elektroheizer deaktiviert

Ventilatoren aktiviert

Modbus Modbus Typ: Holding Register

Lesebefehl: 03 (03Hex)

Schreibbefehl: 16 (10Hex)

Wie man die Kommunikationsprotokolle Modbus verändert:

Verbinden Sie sich über Modbus und RS-485 mit den Standardprotokollen:

Adresse= 1

Baud-Rate= 9600

Parität= EVEN

Bitbreite= 8 (nicht editierbar)

Stop bits= 1 (nicht editierbar)

Verändern Sie die Protokolle an den folgenden Adressen nach Ihrenm Bedarf:

53274= Adresse (1-255)

53275= Baud-Rate

3= 9600 Baud (Standard)

4= 19200 Baud

5= 38400 Baud

6= 58600 Baud

7= 115200 Baud

53276= Parität

1= EVEN (Standard)

2= NONE

3= ODD

Das Gerät muss neu gestartet werden , um die Änderungen zu speichern.

Beispiel Kabelnetz

Supervisor

Gerät 1 Gerät 2 Gerät 3 Gerät n

Kabel

Grau: GND Weiss: +

Schwarz: -

Page 18: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 5 / 6

firmware 2.4

DE

EE

1.1. Benutzervariablen:

MODBUS Point Typ: HOLDING REGISTER

Lesebefehl: 03 (03Hex)

Schreibbefehl: 16 (10Hex)

Adresse

schreiben/lesen

Beschreibung

MODBUS Wert Um Standard Min Max

53274 Modbus

Protokoll Controller Adresse 1

1 1 255

53275

Modbus Baud-Rate Protokoll

3= 9600 Baud (Standard)

4= 19200 Baud

5= 38400 Baud

6= 58600 Baud

7= 115200 Baud

3

3 3 7

53276

Modbus Parität Protokoll

1= EVEN (Standard)

2= NONE

3= ODD

1

1 1 3

Adresse

schreiben/lesen

Beschreibung

SET Wert Um Standard Min Max

16389 3 Point Ventil Kühlung

Proportionalband 2 °C 20 1 100

16390 3 Point Ventil Heizen

Proportionalband 2 °C 20 1 100

16391

Automatische Lüfter:

Durchschnittsgeschwindigkeit

Differenz

2 °C 20 1 100

16392 Automatische Lüfter:

Maximaler Differenzgeschwindigkeit 2 °C 20 1 100

16393 Heizung Differenz 2 °C 20 1 100

16394 Heizung Nachlüftung Zeit 60 Sec 60 10 500

16395 Freecooling Differenz 1 °C 10 1 100

16396 FreeHeating Differenz 1 °C 10 1 100

16397 Free Cooling Hysterese 0.5 °C 5 1 15

16398 Benutzer Arbeitmodus:

0 = cool; 1 = heatHeiß; 2 = Auto 2

2 0 2

16399 On Off Status (gespeichert in EEprom)

0 = Off; 1 = On 0

0 0 1

16400 Lüftersteuerung

0 = Min; 1 = Med; 2 = Max; 3 = Auto 3

3 0 3

16401 Set Point Kühlung (Cooling) 26.0 °C 260 50 350

16402 Set Point Heizung (Heating) 20.0 °C 200 50 350

16403 Profil 1: Start band 1 08:00 HH:MM 480 0 Profil 1: End band 1

16404 Profil 1: End band 1 12:00 HH:MM 720 Profil 1: Start band 1 1439

16405 Profil 1: Start band 2 14:00 HH:MM 840 0 Profil 1: End band 2

16406 Profil 1: End band 2 17:00 HH:MM 1020 Profil 1: Start band 2 1439

16407 Profil 2: Start band 08:00 HH:MM 480 0 Profil 2: End band

16408 Profil 2: End band 17:00 HH:MM 1020 Profil 2: Start band 1439

16409 Profil 1: Set Cool Band 1 26.0 °C 260 Profil 1: Set Heat Band 1 350

16410 Profil 1: Set Cool Band 2 26.0 °C 260 Profil 1: Set Heat Band 2 350

16411 Profil 2: Set Cool Band 26.0 °C 260 Profil 2: Set Heat Band 350

16412 Profil 1: Set Heat Band 1 20.0 °C 200 50 Profil 1: Set Cool Band 1

16413 Profil 1: Set Heat Band 2 20.0 °C 200 50 Profil 1: Set Cool Band 2

Page 19: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

Light Electronic Control LCE Benutzerhandbuch

Light-control manual-DE Rev. 04 DE 6 / 6

firmware 2.4

DE

EE 16414 Profil 2: Set Heat Band 20.0 °C 200 50 Profil 2: Set Cool Band

16415 Montag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16416 Dienstag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16417 Mittwoch Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16418 Donnerstag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16419 Freitag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 1

1 1 4

16420 Samstag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 2

2 1 4

16421 Sonntag Profil Auswahl

1 = P1; 2 = P2; 3 = P3; 4 = P4 4

4 1 4

16422 Profil aktiviert

0 = Off; 1 = On 0

0 0 1

16423 Antifrost Sollwert (rev 2.1) 5.0 °C 50 -50 150

16424 Antifrost Differenzial (rev 2.1) 1.0 °C 10 1 50

Adresse

lesen

Beschreibung

Input-Output Wert Um Standard Min Max

8192 Status On-Off Digitaler Eingang (DI1)

0 = On; 1 = Off 0

0 0 1

8960 Regelfühler 17.5 °C 0 -500 1100

8961 Aktuelle Lüftergeschwindigkeit

0 = Off; 1 = Min; 2 = Med; 3 = Max 0

0 0 3

8962 3-Punkt Kühlung oder Wechselventil

Geschätzte Position 0.0 % 0 0 1000

8963 3- Punkt Heizung Ventil Geschätzte

Position 0.0 % 0 0 1000

8964 Heizer Status

0 = Off; 1 = On 0

0 0 1

8965 Außenüberbrückung Status

0 = Off; 1 = On 0

0 0 1

8966 Außentemperatur 11.2 °C 0 -500 1100

8968 On Off Status 0

0 0 1

Adresse

lesen

Beschreibung

Alarm

0= Not Active

1= Active

2=Manual Reset Wert Um Standard Min Max

9000 Fehler

Luftauslassfühler 0

0 0 1

9001 Fehler Außenraumfühler 0

0 0 1

9002 Fehler SKW -Fühler 0

0 0 1

9003 Filter Alarm 0

0 0 1

9004 Heizer Alarm (manuelle

Zurücksetzung) 0

0 0 2

9005 Antifrost Alarm (rev 2.1) 0 0 0 1

Adresse

lesen

Beschreibung

Version Wert Um Standard Min Max

9471 Anwendungsversion 2.1 21

Anmerkung:

(geteilt durch 10, °C) den Wert durch 10 teilen, es wird ein Ergebnis in Celsiusgrad mit einer Kommazahl erhalten (z. B.: 175= 17.5°C)

(geteilt 10, %) den Wert durch 10 teilen, es wird ein Ergebnis in Prozent mit einer Kommazahl erhalten(z. B.: 505= 50.5%)

(HH:MM) Minuten ab Mitternacht, wobei 0= 00:00 und 1439= 23:59 bedeuten(z. B.: 120= 02:00; 1170= 19:30)

Page 20: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

firmware 2.4 Rev. 04 A

Descrizione

Description

Beschreibung

Collegamenti

Wiring

Verdrahtung

Parametri

Parameters

Parameter

Valvola calda

Heating valve

Heißwasserventil

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

N= Neutro – Neutral - Neutral Y1= Apre – Open - Öffnen

Y2= Chiude – Close - Schließen

N

Y2

Y1

3

2

3-POINT

230Vac

1

(Password= 1) = 2

Valvola fredda

Cooling valve

Kaltwasserventil

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

N= Neutro – Neutral - Neutral Y1= Apre – Open - Öffnen

Y2= Chiude – Close - Schließen

N

Y2

Y1

7

6

3-POINT

230Vac

1

(Password= 1) = 2

Valvola promiscua

Unique changeover valve

Einzigartige Umschaltventil

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

N= Neutro – Neutral - Neutral Y1= Apre – Open - Öffnen

Y2= Chiude – Close - Schließen

N

Y2

Y1

7

6

3-POINT

230Vac

1

(Password= 1) = 0

Page 21: True life insidearchivio.lmfclima.it/wp-content/uploads/2015/11/AMF0007049.pdf1) Se le fasce orarie sono disabilitate, l'on/off da tastiera remota è definitivo 2) Se le fasce orarie

firmware 2.4 Rev. 04 B

Valvola freddo +

Resistenza Post riscaldamento

Cooling valve + electric post heater

Kaltwasserventil +

ON-OFF Elektroheizer

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

12

13 TH

1

2

230Vac

N= Neutro – Neutral - Neutral Y1= Apre – Open - Öffnen Y2= Chiude – Close - Schließen

N

Y2

Y1

7

6

3-POINT

230Vac

1

(Password= 1) = 1

Serranda By-Pass (MBP)

By-Pass damper

Bypass-Klappe

1

2 4

5

230Vac

Pressostati filtri

Filter pressure switches

Druck verschmutzter filter

11

10

2

3

2

3

Sonda temp. mandata (BTM)

Supply air temperature sensor

Zuluft temperatur sensor

14

15

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

Sonda temp. esterna (BTE)

Fresh air temperature sensor

Externer temperatur sensor

16

17

Esterna

Immisione

Ripresa ambiente

Espulsione

Supply

Return

Fresh air

Exhaust

OFF da remoto (On-Off)

Remote OFF

Remote OFF

8

9

Off

8

9

On