tried. tested. trusted. - rs components · trusted. in safety testing, the bottom line is human...

20
Tried. Tested. Trusted. Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: [email protected] Web: www.seaward.co.uk Seaward, Clare, Rigel Medical, Cropico, Seaward Group USA are all part of the Seaward Group Portable Appliance Testing A Guide to

Upload: others

Post on 14-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

Tried. Tested. Trusted.

Seaward, Bracken Hill, South West Industrial Estate,Peterlee, County Durham, SR8 2SW United Kingdom

Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227Email: [email protected] Web: www.seaward.co.uk

Seaward, Clare, Rigel Medical,Cropico, Seaward Group USA

are all part of the Seaward Group

Portable Appliance Testing AGuide to

Page 2: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

Tried. Tested. Trusted.Contents

02 - 03 Introduction

04 - 05 PAT System

06 - 07 PAT Software

08 - 09 Test n Tag System

10 1 - The legal requirement to test

12 2 - The identification of equipment

13 3 - Testing standards and the tests required

15 4 - Competence and training

17 5 - On-site testing hazards

18 6 - The inspection process

20 7 - Combined inspection and test procedure

23 8 - Electrical Test

27 9 - Special equipment

28 10 - Frequency of testing

30 11 - Record keeping

32 12 - Interpretation of results

32 13 - Special notes

36 Appendix

Page 3: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

Acts, Regulations and DirectivesThe Electrical Equipment (safety) Regulations1994 (“the 1994 Regulations”), which aremade under section 11(1) of the ConsumerProtection Act 1987 (“the Act”) and section2(2) of the European Communities Act 1972implement into UK law the modified LowVoltage Directive. The 1994 Regulations applyto all electrical equipment and cover domesticelectrical equipment and equipment that isintended for use in the workplace.

The Health and Safety at Work Act 1974(HSW Act 1974) Sect 6.1 (c) requires that itshall be the duty of any person who designs,manufacturers, imports or supplies any articlefor use at work to supply adequate informationabout the use for which the article is designedand has been tested, and about anyconditions necessary to ensure that it will besafe when being used, cleaned, set,maintained, dismantled and disposed of.

The Electricity at Work Regulations 1989 applyto every type of electrical equipment and state:

“As may be necessary to prevent danger, allsystems shall be maintained so as to prevent,so far as is reasonably practical, such danger”(Regulation 4(2)).

The EC “Provision and Use of WorkEquipment Regulations 1998” places generalduties on employers and lists minimumrequirements for work equipment to deal withselected hazards whatever the industry.

The Regulations implement an EC Directiveaimed at the protection of workers and the“general duties” will require the need to:

(a) Make sure that equipment is suitable forthe use for which it is provided.

(b) Take into account the working conditionsand hazards in the workplace.

(c) Ensure equipment is used only for theoperations for which, and under conditionsfor which, it is suitable.

(d) Ensure that equipment is maintained in anefficient state, in efficient working order andin good repair.

2 3

(e) Provide equipment that conforms to ECproduct safety directives

(f) Plus certain other general duties andspecific requirements etc.

The words “Work equipment” broadly defineeverything from a hand held tool to machinesof all kinds.

The Approved Code of Practice and Guidancedocument to the Provision and Use of WorkEquipment Regulations 1998 (LL2) states that‘efficient’ relates to how the condition of theequipment might affect health and safety; it isnot concerned with productivity.

Objectives of this guideThe objectives of this Practical Guide are toprovide the information required to ensure thesafety of the test person whilst conducting thetests and to assist that person to manage thetest location to prevent danger to others whomay be affected by their activities.

This Guide does not replace the requirement

for the test person to be competent to test,but is designed to assist that competentperson to conduct the testing activity in a safemanner under a variety of circumstances.

Such a competent person will be able to utilisethis Guide by successfully adapting theprinciples described to ensure safety in hisparticular test environment and circumstances.

The duties of manufacturers, hirers andmaintainers are each considered in addition tothose of the user and where necessaryreferences will be made to Statutory Law andApproved Codes of Practise (ACoP).

The booklet will explain logically the legalrequirement to test, who should perform thetests and what equipment should be tested. Itis also necessary to examine where and howthe tests may be performed safely and howoften they should be carried out.

Record keeping is outlined and guidance isgiven on the interpretation of results underSection 11 “RECORD KEEPING”.

Tried. Tested. Trusted.In safety testing, the bottom line

is human life. So it’s our business

to know your work inside out.

This guide is what we know about

the procedures of PAT testing.

Page 4: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

4 5

Tried. Tested. Trusted.PAT SYSTEM

Smart technology and an intimate

knowledge of the job result in

Testers designed for easier work

and better profits.

Today’s world moves at an unprecedented

pace: things change every day. Everything’s

smarter, smaller and faster. This is good news

for us, and for you. It means we’re developing

and manufacturing better equipment and can

incorporate technologies like Bluetooth data

transfer and PDA test management databases.

And we’re not confined to supplying test

equipment. We can now help your business or

institution become more efficient and effective.

We call it PATSolutions. This groundbreaking

process involves everything from choosing your

PAT Tester to following up with calibration

services and training courses. It streamlines

your processes, reduces costs, increases

productivity and improves profits.

Seaward offers everythingfrom Bluetooth technologyto a basic PASS/FAIL tester.Our revolutionary PAT Testerrange includes hand-heldformats capable of carryingout a variety of full andcomprehensive tests.

Because of our experience inthe field, we’ve been able todevelop a range of PATTester accessories whichhelps you save time andreduces the need forrepetition. Now, for example,you can print labels directlyfrom the tester, label theappliance, scan, store andretrieve information. Andthat’s just a small sample ofwhat you can do.

Use mobile technology forremote working. Transferringrecords to the PDA for re-test and results back toPATGuard databases tocreate up-to-date records.

Our PATGuard software rangeis highly functional, easy touse and helpful; superblyuser-friendly in fact. It’savailable in different versionsdepending on what you need.Our software packages utilisefull test records, schedulingand pre-emptive automatednotification. All features, wehardly need add, which addvalue to your business.

TestersPrinters

& AccessoriesMobile Testing

SoftwareAsset Management

Software

TEST INFORMATION

RE-TEST INFORMATION

TEST INFORMATION

Page 5: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

6 3

Tried. Tested. Trusted.PAT Software

PATGuard 2. New generation

software that takes the stress

out of the Testing process.

At Seaward, we focus on more than tester

improvement. We offer a total solution, which

makes PAT Testing a lot quicker and easier.

From test and measurement equipment,

right through to software and accessories.

Our PATGuard 2 software is functional, easy to

use and helpful. It comes in three versions, each

providing an optimum solution to a particular

requirement. PATGuard 2 and our Work About 2

software bring added value to your customer

offer. Proactive and user friendly, it presents you

with a totally connected system which lets its

various parts ‘talk to each other’. It can email

you to warn you when it’s time to re-test, for

instance. Features like this cut admin time and

let you get on with what you’re good at.

Provides clear information on test user activity Bluetooth technology for wireless data transfer

Page 6: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

8 9

Tried. Tested. Trusted.Tried. Tested. Trusted.Test n tag system

Fast, automatic printing of

appliance test labels direct

from the test instrument.

Work is hard enough without the complications

of using inferior products. Which is why at

Seaward everything we do is designed to make

your work easier and more efficient. Our new

generation Test n Tag printers are perfectly

equipped to help. Up to the minute Bluetooth

technology means information can be

transferred immediately from your tester.

Moments later, a tamper and waterproof label

can be printed, with or without your logo. Of

course we ensure your new printer is tough

enough to last a very long time and clever

enough to manage its own power usage.

Printers like these will not only shorten the time

you spend at each test site, they will make the

process of test n tagging much easier.

Page 7: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

10

Tried. Tested. Trusted.

11

The HirerThe ‘hirer’ of equipment has a general responsibilityunder the HSW Act 1974 (Section 6) to ensurethat the article remains safe for each customer touse; the hirer also has a specific duty with regardto electrical equipment under the Electricity at WorkRegulations 1989 (EAWR 1989).

Regulation 2 (EAWR 1989) – An Electrical SystemRegulation 2 (EAWR 1989) defines an electricalsystem as all equipment which is or can beconnected to a source of electrical energy and theterm includes both the source and the equipment.

The same Regulation defines electrical equipmentas anything used, intended to be used or installedfor use to generate, provide, transmit, transform,rectify, convert, conduct, distribute, control, store,measure or use electrical energy.

Regulation 4(2) (EAWR1989) – Maintenance of a systemRegulation 4(2) (EAWR 1989) requires that allsystems are maintained where this will preventdanger. Regulation 29 states that it shall be adefence if it can be proved that all reasonablesteps were taken and all due diligence wasexercised to avoid the commission of an offenceunder certain regulations.

The clear intention of the (EAWR 1989) is to ensurethat a managed system is installed and maintainedto prevent an accident, hence a prospectiveapproach is required.The prime method to accurately decide whenmaintenance is necessary to prevent danger is toperform regular inspections and testing of the

equipment concerned; consequently there is alegal requirement to inspect and test anyequipment which may be connected to anelectrical supply.

A similar requirement falls upon the repairer ofelectrical equipment to perform safety testing afterrepair to ensure that any repair activity has notinadvertently introduced a danger to thesubsequent user.

Users of Electrical EquipmentThe ‘user’ of an article may be an employee. Usersof electrical equipment have a responsibility toensure that equipment they use has no obviousvisual damage or defects. The employer has aresponsibility to provide and maintain a safe plantfor every employee to use (HSW Act 1974 Section2(a)). This requirement is endorsed by the (EAWR1989) Regs 4(1) and 4(2) with specific referenceto electrical equipment. The (EAWR 1989) Reg3(1) also places the same duties upon the self-employed.

It can be seen that the duty to test in order toensure safety is extremely comprehensive andincludes all work situations where electricalequipment is present, but there is no definitiverequirement for a record book kept of the user’sinspections.

AdministratorsThe IET Code of Practice gives advice to personsmanaging maintenance schemes. Administratorsor managers of premises are required tounderstand and apply the legislation and assessthe risks in respect of electrical equipment andappliances within their charge. Administrators have

The SupplierThe ‘supplier’ of electrical equipment has a dutyto test under the HSW Act 1974 Section 6. Thisrequires that every supplier should ensure that thearticle he supplies is designed and constructed tobe safe and he should carry out or arrange fortesting or examination of the item to verify that thedesign safety standards have been met.

The term ‘supplier’ refers to the designer and/ormanufacturer or to the hirer of an article and theresponsibility for safety is corporate. If the supplierof an article has imported the item, then he bearsfull responsibility for the safety of the article as ifhe were the manufacturer.

The ImporterThe ‘importer’ of an article may rely on assurancesthat the equipment is made to international safetystandards if those standards are equivalent to therequired UK standards. However; the foreignmanufacturer should be able to demonstrate safetyby supplying details of his national standard. If asuitable equivalent foreign standard does not exist,the foreign manufacturer should be able to statethe safety test parameters to which the article hasbeen subjected in order that the importer maycompare such data with the required UK standards.

It should be noted that whilst the importer mayrefer the testing activity back to the foreignmanufacturer or engage a suitable UK testingestablishment, this does not transfer theresponsibility for the product’s safety. In cases ofdoubt over safety performance, the importershould be prepared to undertake the testinghimself or engage a competent organisation totest on his behalf.

1 – THE LEGAL REQUIREMENT TO TEST

The 1994 Regulations affect all persons whosupply electrical equipment. They affect:

manufacturers; importers into the EEA; wholesalers, distributors; retailers (including mail order traders); persons who hire out electrical equipment

in the course of business; persons (including auctioneers) who supply

second hand electrical equipment in the course of business;

persons who, in the course of business,let accommodation which contains electrical equipment.

The legal reference requiring testing to be carriedout will vary in accordance with the tester'soccupational function.

The ManufacturerThe ‘manufacturer’ is the person, whetherestablished in the EEA or not, who is primarilyresponsible for designing and manufacturingequipment so that it complies with the safetyrequirements of the 1994 Regulations.A manufacturer may suitably locate the testingfunction at the end of a production line and thetests performed should demonstrate that the'article' meets his published specification whichin turn should comply with applicable harmonised,international or national standards.Should the manufacturer operate correctivefeedback loops to both the design and productiondepartments then the safety testing function couldform part of a quality assurance system.

Page 8: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

12 13

Stationary Equipment or AppliancesThis equipment has a mass exceeding 18kg andis not provided with a carrying handle e.g.refrigerator, washing machine.

Fixed Equipment/AppliancesThis is equipment or an appliance which isfastened to a support or otherwise secured in aspecific location e.g. bathroom heater, towel rail.

Appliances or Equipment for Building-inThis equipment is intended to be installed in aprepared recess such as a cupboard e.g. built-incooker.

Information Technology EquipmentThis equipment includes electrical businessequipment such as computers, mains poweredtelecommunications equipment and otherequipment for general business use e.g. printers,photo-copiers, typewriters etc.

Extension Leads and RCD Extension LeadsExtension leads are used where an item ofequipment requires connection to a mains supplybut a convenient outlet is not available. An RCDextension lead is an extension lead that is fitted witha residual current device.

Multiway Adaptors and RCD AdaptorsMultiway adaptors are used where sufficient mainsoutlets are not available. RCD adaptors are used toprovide protection for users of portable equipment,particularly when used outdoors.

Identification NumbersEach item of portable or transportable, hand heldor stationary equipment should carry its own

Movable Equipment (Transportable)This equipment is either:

18kg or less in mass and not fixed,e.g. electric fire or:

Equipment with wheels, castors or othermeans to facilitate movement by theoperator as required to perform its intendeduse e.g. air conditioning unit.

Such equipment may be considered“transportable” rather than portable, but will stillbe connected to its supply where applicable by aflexible cord and plug. The risk of damage whichmay cause the safety of transportable equipmentto be compromised can be high. Also, the use ofsome transportable equipment carries a high riskdue to the very nature of its use (e.g. a highpressure steam/water cleaner) and in suchcircumstances transportable equipment canpresent a greater hazard than most portableequipment, therefore the requirement to periodicallytest must also apply to transportable equipment.

Hand Held Equipment or AppliancesThis is portable equipment intended to be held inthe hand during normal use e.g. drill, hair dryer.

The risk of damage which may cause the safetyof hand held equipment to be compromised canbe high. Also, the use of some hand heldequipment carries a high risk due to the very natureof its use i.e. the user is in direct contact with theequipment

a legal responsibility to ensure that the electricalequipment in their charge is safe.

The Test OperativeThe person performing the inspections and testson an item of equipment should be competent tocarry out the inspections and tests, assess theresults and the conditions in which the item isbeing used and state whether the item is safe forcontinued use. Training and experience will bothbe necessary.

2 - THE IDENTIFICATION OF EQUIPMENT

DefinitionsSeveral types of electrical equipment are definedin the IET Code of Practice for In-service Inspectionand Testing of Electrical Equipment.

Portable EquipmentAn appliance of less than 18kg in mass that isintended to be moved whilst in operation, or anappliance which can be easily be moved whilst inoperation, or an appliance which can easily bemoved from one place to another e.g. vacuumcleaner, toaster, food mixer, etc.

Hence it may be regarded that portable equipmentis designed to be carried or moved from place toplace between periods of use and the powerconnection will be made by a “flexible cord” whichwill terminate in a plug for connection to the fixedsupply.

Tried. Tested. Trusted.

unique identification number. If the supply cord isnon-detachable, then the cord will automaticallybe tested with the equipment. If a detachablesupply cord is used, then it may either be identifiedwith the number of its associated appliance or ifthe cord is likely to be moved between appliancesor is one of a central pool of leads it should bearits own unique identification number.

Whichever system is used, it is important that supplycords can be identified or are traceable to aparticular appliance and can thus be regularly tested.

‘Private’ EquipmentIt should be noted that ‘private’ equipment usedat work (e.g. electric fires, mains radios, electrickettles, coffee makers etc.) will carry an equalpotential for danger to those items owned by theemployer and if such equipment is allowed on site,its safety becomes the responsibility of theemployer (i.e. the duty holder) and such equipmentshould be added to the list of items to be regularlytested.

3 – TESTING STANDARDS ANDTHE TESTS REQUIRED

Type Approval TestsElectrical equipment that is constructed to meetthe safety provisions of one of the following in anaccepted hierarchy of standards and requirementswill be taken to satisfy the safety requirements ofthe Regulations.

Harmonised StandardsElectrical equipment which complies with the safetyprovisions of Harmonised Standards will bepresumed to comply with the safety requirements

Page 9: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

of the Regulations.

The EEC body responsible for the “harmonisation”of member country’s standards is the ‘ComiteeEuropeen de Normalisation Electrotechnique’(CENELEC) who issue harmonised standards (EN)which are then implemented identically in theeighteen member countries.

International StandardsWhere no relevant harmonised standard exists,electrical equipment which complies with thespecification of a standard published by theInternational Electrotechnical Commission (IEC)(details of which have been published by theEuropean Commission in the Official Journal) willbe presumed to comply with the safety provisionsof the Regulations

The international authority with regard to electricalstandards is the International ElectrotechnicalCommission (IEC). An IEC Standard expresses,as nearly as possible, an international consensusof opinion on the subject dealt with and the wishis expressed that all National Committees shouldadopt the text of the Standard for their nationalrules in so far as national conditions will permit.

There is therefore no compulsion placed on aNational Committee to adopt any IEC Standard.Nevertheless while the IEC standard work is veryimportant in its own right there is a further aspectwhich makes it more so. IEC Standards are moreusually the “reference document” for the basis ofharmonisation of the corresponding NationalStandards.

14

National StandardsWhere no relevant harmonised standard orinternational standard exists, electrical equipmentwill be presumed to comply with the safetyprovisions of the 1994 Regulations, if it isconstructed to conform to the safety provisionsof either:

A published British standard: or A published standard of the Member State

of the manufacturer.

Routine In-Service TestingUK legislation does not specify the requirementsfor in-service testing. Subsequently, a practical'commonsense' approach is required. The testsperformed should reflect the Type Approval testsapplicable to the type of unit being tested. Routinesafety inspections and tests should be designedto show that the unit's original design safetyfeatures are still operative and are of such integritythat the equipment is likely to remain safe at leastuntil the next scheduled test date. The IET Codeof Practice for In-service Testing and Inspectionof Electrical Equipments give guidance on suitabletests. This prospective assessment may require anelement of judgment on behalf of the test personand guidance on this matter and on the level ofcompetence required to make the judgement iscovered in Section 4 "COMPETENCE ANDTRAINING".A few standards relevant to more commonequipment are detailed in Appendix I. The systemof national and international standards is displayedin Fig 1.

15

Tried. Tested. Trusted.

IT EquipmentThe standards noted in Fig 1 show how theharmonised standard EN 60950, ‘The safety ofinformation technology equipment includingelectrical business equipment’, is applied byvarious member countries. It should be noted thatthe standards quoted are design standards anddo not address in-service safety testing. SomeType Approval (TA) tests require the removal of

IN-SERVICE INSPECTION AND TESTING

Codes of Practice E.G IET Code of Practice for In-service Testing and

Inspection of Electrical Equipment

H.S.E Guidance Notes

Industry Guidance E.G Electrical Equipment Association

Recommendations for periodic safety checks forbusiness equipment

Fig 1.

EQUIPMENT PUT IN-SERVICE

TYPE APPROVAL AND PRODUCTION TESTING

National Standards E.G BS EN 60950

International standards E.G IEC 60950

Harmonised standards E.G EN 60950

certain types of components and all TA tests areconducted under laboratory conditions. Whilstthe TA tests will provide reference data, theycannot be emulated in the field or on a routinebasis and such adherence is not expected.

The Electrical Equipment Association (EEA) haswritten a guidance document coveringrecommendations for periodic safety checks forbusiness equipment built to EN 60950/IEC60950/BS EN 60950. The application of therecommendation is examined in Sections 6 and 13.

Essential Type Approval Safety TestsThe Type Approval Safety tests required by variousdesign standards are essentially:

(a) Protective conductor (earth) continuity.(b) High voltage withstand test (dielectric

strength, hipot or ‘flash’ testing).(c) Touch current or protective conductor

current.(d) Insulation resistance (not common to all

standards).

When the equipment under test containsintegrated circuits or other sensitive components,high voltage testing may damage thesecomponents. It can therefore be seen that thetests required will vary according to the type ofequipment being tested and a full explanation isgiven in Section 6 “THE INSPECTION PROCESS”.

4 – COMPETENCE AND TRAINING

The UserUsers may require training in identification ofdefects that can occur in electrical equipment.

Page 10: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

16 17

Users should be aware that:a) Equipment that is faulty or suspected of

being faulty should not be used.b) Equipment that is faulty should be labelled

and removed from service immediately.c) The administrator or manager should be

notified.

The Administrator or ManagerAdministrators or managers of premises arerequired to know their legal responsibilities as laiddown in the Electricity at Work Regulations 1989and have a legal responsibility to ensure thatequipment in their charge is safe.

Administrators may require training to allow themto carry out risk assessments, maintain records ofinspections, tests and repairs of equipment andmanage the inspections and tests at appropriateintervals. Administrators are required to interpretthe recorded results and take appropriate actionsor to provide relevant information and reports toa more senior person within the organisation.Competence to interpret records and results isachieved by appropriate training and experience.

The Test OperativeIn the context of safety testing, the term“competence” refers to a person’s ability to performthe task without danger to themselves or othersand to make a valid judgement based on theresults, as to whether the unit under test is safeto use and is likely to remain safe at least until thenext scheduled test date.

It will be appreciated that the test person willrequire certain knowledge and information to

Safety in Area of Work ActivityThe HSW Act 1974 Section 2 requires everyemployer to maintain a safe place of work and asafe system of work for his employees. The (EAWR1989) Reg. 4(3) requires that every work activityon or near a system shall be carried out in such amanner as not to give rise, so far as is reasonablypractical, to danger. This Regulation has a wideapplication and includes work of a non-electricalnature where there is a risk of electrical injury.

It can be seen that both the person conductingon-site testing and the supervisor of the area wherethe testing takes place, have a clear legalresponsibility to ensure both the test person’ssafety and that of other persons who may be inthe area. It should be remembered that the (EAWR1989) Sect 3 addresses such duties to theemployee, the employer and the self-employed inso far as they relate to matters which are “withintheir control”.

The safety of ‘other persons’ in the area is bestachieved by excluding them from the immediatevicinity of the test process. This Controlling actionmay require physical barriers and warning noticesto EN 50191 or other means such as control of thearea by a second person.

The EAWR 1989 Reg. 4(4) requires that allprotective equipment such as special tools,protective clothing and insulating materials shall besuitable for the use for which they are provided,and should be properly used and maintained.

Tried. Tested. Trusted.

enable such valid prospective judgements to bemade. In addition the test person will require boththe knowledge and the information necessary tomake judgements regarding the testing processand its safety and the skill and ability to put suchjudgements into practice, thus producing a safesystem of work. Training and experience will bothbe necessary.

It is suggested that the following criteria areconsidered:

(a) An adequate knowledge and practical experience of electricity and its hazards

(b) A clear understanding of precautions required to avoid danger

(c) The ability to recognise at all times whether it is safe for work to continue

(d) The ability to identify equipment and appliancetypes to determine the test procedures and frequency of inspection and testing

(e) Adequate understanding of the operating principles of both the test equipment and the unit under test

(f) The ability to create test records and take responsibility for the work

(g) Adequate knowledge of the required safetystandards

(h) Adequate knowledge of possible hazards at a “strange” site

The tester’s skill and ability should encompass:

(a) Adequate experience of relevant electrical work

(b) Adequate experience of appliance testing and the test equipment

(c) Adequate training where (b) cannot be otherwise satisfied

(d) Experience in the interpretation of results(e) Practical “technical” experience of the type

of equipment being tested

Suitable sources of information may include:

(a) Employer’s safety manuals or instructions(b) Equipment manufacturer’s handbooks(c) British Standards (see Appendix 1)(d) Health and Safety Executive (HES)

Guidance Notes (see Appendix 2)(e) IET Guidance e.g. “Code of Practice for In-

Service Inspection and Testing of Electrical Equipment”

Managers and Supervisors responsible for testingpersonnel should adjust their degree of supervisionto take into account any inadequacy of the testperson. The (EAWR 1989) Reg. 3 places a dutyon the self employed to assess their owncompetence and subsequently to work within theirlimitations.

5 - ON-SITE TESTING HAZARDS

Where safety testing has to be carried out “on-site”, care will be required to avoid possiblehazards both to the test person and others in thevicinity. Where these hazards could cause adanger during testing, the equipment should betransferred to an alternative location or to aproperly designated test area as defined by EN50191 ‘Erection and Operation of Electrical TestInstallations’.

Page 11: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

18

plugged in and switched on. The check involvesa visual inspection of the mains plug, mains flexand the appliance for obvious signs of damage ordegradation. An assessment should also be madeof the suitability of the environment and thepurpose for which the equipment is to be used.User checks are an important safety precautionas the user of the equipment is most familiar withits operation. User checks do not need to berecorded unless a problem is discovered, in whichcase the equipment should be labelled to show itis not to be used and removed from service assoon as possible. The administrator or managershould be notified.

Formal Visual InspectionIn practice, many equipment defects can be foundduring a formal visual inspection. Many potentialhazards arise due to the way in which a piece ofequipment is used or abused. For example,portable equipment may be prone to beingdropped, or a piece of movable equipment with along trailing mains flex may be damaged as theequipment is moved around. Potential hazardssuch as enclosure damage, damage to the mainsflex, signs of over heating, incorrectly fitted mainsplugs, incorrect fuses etc. can be identified by athorough visual examination.

A formal visual inspection carried out by a personcompetent will make the greatest contribution tominimising risk and eliminating potential safetyhazards. Advice on the frequency of formal visualinspections is given in Table D.

A formal visual inspection should include aninspection of the following:

19

1) Manufacturer’s instructionsa. The equipment should be installed and

used in accordance with the manufacturer’s instructions.

b. The correct voltage, frequency and current requirements should be verified.

c. Requirements for ventilation or heat dissipationshould be met.

2) Environmenta. Suitability of the equipment for the environment

or purpose for which the equipment is being used e.g. risk of mechanical damage, exposureto weather, temperature, fluids, corrosives, flammable materials.

3) Switching of equipmenta. The inspector should determine whether

there are suitable means of disconnecting the equipment from the mains supply under normal use, to carry out maintenance and in the event of an emergency (if applicable to the equipment).

4) User feedbacka. Where possible the user of the equipment

should be consulted as to whether there are any known problems or faults. The usermay be aware of intermittent problems thatmay not be apparent during the inspection.

5) The equipment enclosure/casinga. Physical damage such as cracks or chemical

corrosion. Particular attention should bepaid to areas around switches, fuses, protectivecovers and mains couplers where damage mayresult in live parts becoming exposed.

Tried. Tested. Trusted.

b. Signs of overheating.c. Signs of ingress of fluids or foreign bodies.

6) Mains plugsa. Correct fit in the mains outlet – not loose

and can be removed without difficulty.b. Cracks or damage.c. Signs of overheating.d. Properly tightened terminal screws on

rewirable plugs.e. Correct wiring on rewirable plugs.f. Mains flex is properly secured by the

cable grip.g. Correct fuse rating and type.

7) Mains cordsa. Damage, cuts or fraying. Extension leads

should be checked along the entire length.b. Joints or connections which are unsafe

e.g. taped joints.c. Appropriate length.d. Correct rating for the equipment.

8) RCD protected adaptors or extension leadsa. Operation of the RCD should be confirmed.

Operator accessible fuses on the outside of theequipment should be checked for correct type andrating. If the equipment manufacturer has specifieda particular rating for the plug fuse, this should alsobe checked. If the manufacturer has not specifieda fuse rating for the plug the preferred fuse size isdetailed in Table H related to the cross-sectional areaof the cord conductors. Ensure that properlymanufactured cartridge fuses are used and that fuseshave not been replaced with a metal bar, wrappedin metallic foil or similar non standard method.

6 -THE INSPECTION PROCESS

This section of the Guide is intended tosupplement the Operating Instructions of aPortable Appliance Tester and should be used inconjunction with those instructions.

WarningModern electronic equipment may employ semi-conductor devices which could be damaged bycertain tests. Before such equipment is tested theequipment manufacturer should be asked to definewhich tests should not be undertaken.

Reasons for the TestsThe aim of this section is to explain thefundamental reasons for the tests performed andto offer practical guidance on test procedures.Such guidance can only be given in general termsand appropriate training is essential in order toaddress specific problems. Inspection and testingshould only be carried out by persons competentto do so.

The tests to be performed should reflect the TypeApproval tests applicable to the type of unit to betested. Routine Safety tests should confirm thatthe original design safety still exists and is of suchintegrity; that the unit under test is likely to remainsafe at the very least until the next scheduled testdate. This latter criterion may require the testperson to make a prospective judgement; thisaction is considered in Section 12“INTERPRETATION OF RESULTS”.

User CheckUser checks are performed before equipment is

Page 12: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

20 21

Note: The requirements of a formal visualinspection will vary according to the equipmentbeing inspected and the environment in which itis used. The ‘prompts’ built into Seaward PortableAppliance Testers (Supernova Plus, Europa Plusand PrimeTest range) are intended to provideguidance and should not be taken as acomprehensive list of items to be checked duringa formal visual inspection.

Classes of Equipment ConstructionBefore an item of equipment can be tested theconstruction class must be determined in orderto identify the appropriate tests. The equipmentto be tested will normally be constructed in oneof three basic classes, designated Class I, II or III.Constructional methods are summarised below,full details can be found in BS2754.

Class I equipment is constructed such thatprotection against electric shock does not rely onbasic insulation alone. In addition to basic insulationaround live internal parts, exposed conductiveparts are connected to the protective conductorin the supply. Class I equipment relies upon aconnection to the protective conductor to preventexposed conductive parts becoming live in theevent of an insulation failure.

Class II equipment is constructed such thatprotection against electric shock does not rely onbasic insulation alone. In addition to basic insulationaround live internal parts, supplementary insulationis provided, there being no provision for connectionof exposed conductive parts to the protectiveconductor. Such equipment is often described as“double insulated” and should carry the symbol

Tried. Tested. Trusted.

Class III equipment is equipment in whichprotection against electric shock relies on a supplyfrom a separated extra-low voltage source (SELV).In a SELV supply the voltage is less than 50V rmsand no exposed conductive parts are connected tothe protective conductor.

Note: Not all double insulated equipment bearsthe mark, however, if the mark is applied theequipment must be double insulated. For thepurposes of electrical safety testing, if a piece ofequipment does not bear the , it should betreated as Class I.

7 - COMBINED INSPECTION AND TESTING PROCEDURE

Safety ConsiderationsInspection and testing should only be carried outby a person who is competent to perform theinspection and testing and interpret the resultsobtained.

Preliminary InspectionBefore inspection and testing is carried out thetest operative should obtain a copy of any previoustest records if they are available. This will allow anassessment to be made of any degradation of theequipment under test.

Before attempting to carry out any electrical safetytests, the following preliminary inspection shouldbe carried out:

(a) Ensure that the equipment can be disconnected from the mains supply and otherpower sources. If permission is received,

disconnect the equipment from the supply. (b) Disconnect the equipment for all other

equipment, communication links and telecomlines.

(c) Where the equipment under test has the provision to supply mains power to other accessories (for example a monitor powered from PC base station) the mains connection can remain in place during the tests.

(d) Ensure that equipment is not in contact with extraneous metalwork such as parts of office furniture.

(e) Thoroughly inspect the equipment under test for damage, as described in Formal Visual Inspection.

(f) Inspect the mains plug as described in Formal Visual Inspection.

(g) Inspect the mains cord as described in Formal Visual Inspection.

(h) Assess the suitability of the equipment for the environment.

(i) Where possible, consult the user as to whether there are any known problems with the equipment.

Note: Special care should be taken whereequipment is powered from an uninterruptible power supply (UPS) or has internal battery backup.

In-Service TestsThe IET “Code of Practice for In-Service Inspectionand Testing of Electrical Equipment” recommendsa system of periodic inspection and testing, withup-to-date records, as a means of demonstratingcompliance with the Electricity at Work Regulations1989. Most companies and organisations that wishto comply with the requirements of the Electricity

at Work Regulations 1989 will carry out in-servicetests.

The order in which the tests are performed isimportant to the safety of the test operative.The testing sequence of Seaward PortableAppliance Testers is designed to contribute towardsa safe system of work. The sequence shouldalways be:

1. Earth continuity test2. Insulation resistance test3. Protective conductor/touch current test or

alternative/substitute leakage test4. Functional check

An insulation test should always be carried outbefore attempting any tests which involve applyingmains power to the equipment under test as itmay detect a dangerous insulation failure.

The recommendations given by the IET Code ofPractice for In-Service Testing of ElectricalEquipment are as follows:

Class I Appliances Earth continuity test Insulation resistance test or protective

conductor current test or alternative/substituteleakage

Functional checks

Class II Appliances Insulation resistance test or touch current

test or alternative/substitute leakage test Functional checks

Page 13: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

22 23

Note: Many Seaward portable appliance testersare equipped with an RCD trip time test for testingthe operation of RCDs in accordance with therecommendations of the IET Code of Practice forIn-Service Testing of Electrical Equipment.

Testing After RepairThe IET Code of Practice for In-Service Testing ofElectrical Equipment recommends that equipmentwhich has been repaired should be inspected andtested either in accordance with the manufacturer’sproduction tests or in-service tests. The decisionis based upon the type of equipment and thenature of the repair.

Class I Appliances Earth continuity test Insulation resistance test Dielectric strength test Protective conductor current test Functional checks

Class II Appliances Insulation resistance test Dielectric strength test Touch current test Functional checks

Testing after repair is performed to ensure that therepair has not compromised the electrical safety

components or wiring not intended to provide aprotective earth connection. In appropriate use ahigh test current may damage the equipment undertest. If in doubt, a low test current should be used.

The continuity test is made between all accessibleearthed metal parts of the equipment and the earthpin of the plug when testing equipment with amains cord and between the earth pin of the mainsinput socket and all exposed metal parts whentesting equipment without a mains cord. Theresistance measurement should be observed whileflexing the cable and an inspection of the flexiblecable terminations at the equipment and the plugor flex outlet should be made. Variations inmeasured resistance should be investigated.The measured resistance should not exceed thevalues given below:

Note: Nominal values for resistance of theprotective conductor of the supply cord are givenin Table E.

Where possible it is advisable to test equipmenttogether with its supply cord. If the mains cord isnot detachable, no practical alternative exists.

Care should be taken to ensure that testconnections to the equipment under test makeclean metal-to-metal contact otherwise contact

Tried. Tested. Trusted.

Appliance cord testsA 3-core appliance cord should be tested as aClass I appliance and the following tests shouldbe made: Earth continuity Insulation resistance Wiring polarity check

A 2-core appliance cord should be tested as aClass II appliance and the following tests shouldbe made: Insulation resistance Wiring polarity check

Note: Seaward portable appliance testers areequipped with appliance cord tests thatautomatically perform all of the recommendedtests, including wiring polarity.

Extension leads, multiway adaptorsand RCD adaptors.Extension leads and multiway adaptors are testedas a Class I appliance and the following testsshould be performed: Earth continuity Insulation resistance Wiring polarity check

When the extension lead or multiway adaptor isfitted with an RCD, the RCD must have a ratedresidual operating current (the current at which theRCD is designed to operate) not exceeding 30mA.

The IET Code of Practice for In-Service Testing ofElectrical Equipment also recommends that theoperation of the RCD should be checked usingan RCD test instrument to determine that the triptime is within the limits specified below:

For appliances witha supply cord

For appliances without a supply cord

Appliance mainscords

(0.1) + R ohm where R is theresistance of the protectiveconductor of the supply cord

0.1 ohm

(0.1) + R ohm where R is theresistance of the protectiveconductor of the supply cord

Rated residualoperating current

Satisfactoryresult

RCD to BS 4293 andRCD-protected-socket-outlets to BS 7288

RCDs to BS EN 61008

30mA

30mA

Device should trip in less than

200ms

Device should trip in less than

300ms

of the electrical equipment and this is reflected bythe recommended electrical tests. For example,the earth continuity test will demonstrate that allprotective earth connections have been replacedwhen the appliance is reassembled. Similarly, thedielectric strength test is a useful means ofensuring that all insulating materials has beencorrectly reassembled and that the insulation onlive conductors has not been damaged duringreassembly, for example, when wires are trappedor damaged by fixing screws.

8 - ELECTRICAL TESTS

Earth ContinuityThis test is performed on Class I equipment ormains cords and is used to verify the integrity ofthe connection between the protective conductorand all exposed metal parts intended to beconnected to the protective conductor.

The IET Code of Practice for In-service Inspectionand Testing of Electrical Equipment recommendseither of the following:

A continuity measurement with a short circuit testcurrent within the range 20mA to 200mA. orA continuity measurement with a test current notless than 1.5 times the rating of the fuse and nogreater than 25A for a period of between 5 and20 seconds.

Note: Some appliances, for example IT equipment,may have accessible metal parts which areconnected to earth for functional or shieldingpurposes only. If the high current test option aboveis used, the test current will flow through sensitive

Page 14: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

24

EN 60950 may be damaged by the 500V DCtest voltage.

An alternative/substitute leakage, an insulationresistance test at a reduced test voltage suchas 250V DC or a protective conductor/touchcurrent measurement, may be moreappropriate.

TABLE AINSULATION RESISTANCE LIMITS

This test should be performed with the equipmentswitch ON. Some electronic equipment may containmains filter circuits connected between live/neutral andearth. Such devices could cause the insulationresistance to be less than specified. Themanufacturer/supplier must be consulted in thesecases as to the acceptable value of insulationresistance.

Insulation Resistance Heating andCooking AppliancesFor equipment such as portable cookers the insulationresistance when cold can be very low. Switching onthe appliance for a period of time drives out any

25

absorbed moisture enabling more realistic resistancesto be obtained.

Alternative or Substitute Leakage MeasurementAlternative or substitute leakage is measured using atechnique similar to that used when measuringinsulation resistance. A test voltage is applied betweenboth live conductors (phase and neutral) and theprotective conductor (earth) during a Class I test or atest probe connected to the equipment enclosureduring a Class II test. The resultant current is measuredand then scaled to indicate the current that would flowat the nominal supply voltage.

The test voltage is 50Hz AC and normally in the rangeof 40V to 250V. The test voltage is current limited andso there is no hazard to the test operative. As the testvoltage has the same nominal frequency as the mainssupply the leakage paths are similar to those foundwhen the equipment is in operation. Similarly, becausethe test voltage is not greater than the nominal supply

voltage of the equipment under test measurements arenot affected by transient suppressors, MOVs or othervoltage limiting devices.

Portable appliance testers automatically make thenecessary connection between the live and neutralconductors and apply the correct scale factor to themeasured current. The equipment under test must beswitched ON during the test.

Dielectric Strength TestThis test is also known as the “high voltage leakage test”, “hipot test” or “flash test” and is a Type Approval test or Production test. Test voltages of 1500VAC and 3000V AC are available on selected Seawardtesters that include this test. The 1500V AC is appliedat the mains plug of the appliance under test, betweenthe protective earth conductor and the live/neutralconductors connected together. The 3000V AC test isapplied between the live/neutral conductors connectedtogether at the mains plug and a high voltage test probe

TABLE B

DIELECTRIC STRENGTH TESTS

Standard Basic Insulation Supplementary Insulation Reinforced Insulation

EN 60335 Safety of HouseholdElectrical AppliancesEN 60065Audio, Video and SimilarElectronic Apparatus –Safety RequirementsEN 60950Safety of InformationTechnology Equipment,Including ElectricalBusiness Equipment

1000V

1500V

1500V

2500V

2500V

1500V

2500V

2500V

3000V

Warning: During flash testing, close proximity to the high level of charge present could cause damage to certain typesof electronic equipment which incorporate semi-conductor devices. The advice of the equipment manufacturer shouldalways be sought before testing when such conditions are suspected.

Table B defines the test voltages for a range of appliances.

Tried. Tested. Trusted.

resistance may introduce significant errors.It is possible for Class I equipment to haveconductive metal parts which are not accessibleto the operator, accessible metal parts withprotection against electric shock being providedby double or reinforced insulation or to have‘unearthed’ metal parts which are in casual orfortuitous contact with earthed metal. In this caseno earth continuity test is specified.

Insulation ResistanceInsulation resistance is measured by applyinga test voltage of 500V DC and measuring theresistance. When testing a Class I appliancethe voltage is applied between both liveconductors (phase and neutral) and theprotective conductor (earth). When testing aClass II appliance, the test voltage is appliedbetween both live conductors (phase andneutral) and a test probe. The test probeshould be applied to any exposed metal partsor any suspect parts of the enclosure whereconductive material may have accumulated.Multiple tests may be required.

Modern portable appliance testers produce atest voltage which is current limited. Thevoltage is not dangerous but could beuncomfortable. Appliances should not betouched during an insulation test.

This test may not be suitable for certain typesof appliance. In the case of equipment fittedwith mains filters, voltage limiting devices orsurge protection it may not be possible toobtain a satisfactory insulation resistancemeasurement with a 500V DC test voltage.IT equipment which does not comply with BS

Insulation Resistance

Class I heating and cookingwith a rating greater than 0.3Mohmor equal to 3kW

All other Class I equipment 1.0Mohm

Class II equipment 2.0Mohm

Class III equipment 0.25Mohm

Appliance class

Page 15: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

26 27

early warning of bearing failure in an electricalmachine or shorted turns within a transformer, bothconditions indicating the need for maintenance.Abnormally low power could be the indication of anopen circuit, ruptured fuse or other form of fault.

Protective Conductor/Touch Current MeasurementThe protective conductor / touch current ismeasured from live parts to protective earth for ClassI equipment, or from live parts to accessible metalparts of the enclosure on Class II equipment undernormal operating conditions. This test is analternative to the insulation test where the insulationtest is inappropriate. This test will provide evidenceof possible deterioration of certain componentsunder load and may indicate that the method ofconnection of the equipment to the supply isinappropriate.

Note: Should the equipment contain a mainsinterference suppression capacitor or filter, someresidual leakage will be measured; this will notnecessarily indicate a fault condition.

Note: The insulating barrier should be labelled.

It will be noted that the flash test conducted on a ClassI transformer will have additionally proved the insulationbetween the primary winding and the earthed screen,thus ensuring primary/secondary isolation.

The flash test conducted on a Class II transformerwill not have tested the integrity of the insulatingbarrier between primary and secondary windings.An Insulation test will therefore be required betweenthe input and output connections.

(ii) TEST EQUIPMENTSafety test equipment such as the PAT is in itselfan item of portable equipment and will thereforerequire safety testing in accordance with the criteriadescribed under the heading “FREQUENCY OFTESTING”.

The PAT should be calibrated annually or inaccordance with the manufacturer’s instruction. Acalibration certificate states that the test instrumentis within specification at the time the calibration isperformed. The certificate does not guarantee the

applied to the enclosure of the appliance under test.No other connection is necessary.EN 60335 “Safety of household and similar electricalappliances” allows a high voltage leakage current of0.75m A/kW with an overall maximum of 5mA.As Seaward testers are intended to test equipment witha maximum power consumption of approximately 3kVAthe pass level defaults to 3mA. Equipment to BS 2769“Hand held electric motor operated tools” requires a‘flash’ test voltage of 1.5kV and the maximum permittedleakage is 0.75mA. The test should be conducted withthe unit under test switched ON.For In-service testing as defined by the IET ‘Codeof Practice for In-service Inspection and Testing ofElectrical Equipment’ this test is not recommended.

Preload CheckSeaward portable appliance testers automaticallyperform a pre-check before tests which involvesapplying mains power to the equipment under test.This is included to protect the test person frompotential hazards produced by a very lowimpedance or short circuit being present betweenLIVE and NEUTRAL. The test should be conductedwith the equipment switched ON.

Load TestA Load test is again not a ‘required’ safety test,however it can provide useful information regardingthe operation of the equipment under test. The PATwill apply the supply voltage to the equipment undertest and measure the power consumption in kVAor load current in amperes.

The test is included since a higher power thanexpected from the specification may indicatereduced functional efficiency. A significant changefrom a previously recorded figure may provide an

Class IFig. 3

Primary

L

NE

Secondary

Earthed Screen

Class IIFig. 4

Primary

L

N

Secondary

Tried. Tested. Trusted.

Warning: Special care should be taken duringtests where the equipment under test isenergised. Portable tools and rotating machinesetc. should be rendered safe before thecomplete test sequence begins. All suchmachines should therefore be physically secureand have their cutting, grinding, drilling bits etc.removed where possible; where guards areprovided they should be in place.

9 – SPECIAL EQUIPMENT

(i) TransformersModern low voltage transformers should bemanufactured to EN 61558 which allows eitherClass I or Class II construction. The transformershould be treated as any other piece of portableequipment and tested as previously described.An additional test may be required to ensure thatthe primary voltage does not appear on thesecondary winding by carrying out a primary tosecondary Insulation Test.

The two methods of construction:

Portable or hand-held Class I equipment/0.75 mA

Class I heating appliances/0.75 mA or 0.75 mA per kW, whichever is greater,with a maximum of 5 mA

Other Class I equipment/3.5 mA

Class II equipment/0.25 mA

Class III equipment/0.5 mA

TABLE C

PROTECTIVE CONDUCTOR/TOUCH CURRENT LIMITS

APPLIANCE CLASS / MAXIMUM CURRENT

Page 16: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

28

testing programme.

Where an employee is permitted to bring his ownportable or transportable electrical equipment ontoa site or into a Works, that employee under theH&SW Act 1979 and EAWR 1989 has an additionalduty in that the equipment is to some extent “withinhis control”. The employer must, however, monitorthe employee’s provision and use of suchequipment and where applicable, must include theitems in the schedule of appliances to be tested.

PRINCIPLE FOR FREQUENCY OF TESTINGThe underlying principle for frequency of testing isthat the duty holder (i.e. the person with theequipment “within his control”) with the advice ofthe competent test person when necessary mustassess the need for testing the equipment againstthe following:

(1) Type of equipment (portable, hand-held or transportable)

(2) Style of use (continuous, infrequent, rough)(3) Age of the equipment(4) If regularly moved or transported and by

what means (5) Type and competence of personnel using

the equipment(6) Environment of usage (outdoors, construction

sites, hazardous atmospheres etc)(7) Results of previous tests(8) Manufacturer’s recommendations(9) Effect of any modifications or repairs to

the equipment

The inspection and test periods recommended by theIET Code of Practice for In-Service Inspection andTesting of Electrical Equipment are defined in Table D.

29

Tried. Tested. Trusted.

performance of the test equipment at any timeafter that.

In addition, the IET Code of Practice for In-ServiceInspection and Testing of Electrical Equipmentrecommends that test equipment is checked atregular intervals using a verification device such asthe Seaward PAT Checkbox. A record of theperformance checks should be kept.

10 – FREQUENCY OF TESTING

REGULAR TESTING RESPONSIBILITIESThere are no absolute rules regarding how oftenan item of electrical equipment should be tested.HSE Guidance Notes advise “regular testing” andthis is generally interpreted as a requirement forannual testing. However, circumstances andconditions of use will vary. The competent testperson should be able to advise on the frequencyof testing resulting from his own experience anddiscussions with the user or duty holder (who maybe a non-technical person) regarding the “lifestyle”of the equipment.

During the course of production or after completionof assembly a manufacturer may subject a pieceof equipment to a range of tests. Likewise therepairer of equipment should test after repair. Ahirer should test each piece of equipment beforeeach hire contract.

Personnel responsible for the safe use of electricalequipment, for example contractors, managers ofelectrical /electronics laboratories (test equipmentand tools) office managers (electrical officemachines) are each regarded by the EAWR as‘duty holders’ and should operate a routine safety

Note: (1) S Stationary equipmentIT Information technology equipmentM Movable equipmentP Portable equipmentH Hand-held equipment

(2) User checks are not recorded unless a fault is found(3) The formal visual inspection may form part of the

combined inspection and tests when they coincide and must be recorded.

(4) If class of equipment is not known, it must be tested as Class I

(5) The results of combined inspections and tests are recorded

(6) For some equipment such as children’s rides a daily checkmay be necessary

(7) Equipment in hotels refers to equipment used by hotel staff.Equipment provided in hotel rooms is tested as equipmentused by the public.

(+) By supervisor/teacher/member of staff# 110V earthed centre tapped supply 230V portable or hand-

held equipment must be supplied via a 30 mA r.c.d. and theintervals between inspections and tests reduced

The information on suggested initial frequencies above is more detailed and specificthan HSE Guidance, but is not considered inconsistent with it.

Class I Class II Note 4

Type ofPremises

1

1

2

3

4

5

6

2 3 4 5 6 7

Type ofEquipment

Note 1

Not recorededunless a fault

is found

Formal VisualInspection

Note 3

CombinedInspection andTesting Note 5

Formal VisualInspection

Note 3

CombinedInspection andTesting Note 5

ConstructionSites110V equipment

SIT

M#P#H#

NoneNone

WeeklyWeeklyWeekly

1 month1 month1 month1 month1 month

3 months3 months3 months3 months3 months

3 months3 months3 months3 months3 months

1 month1 month1 month1 month1 month

12 months12 months12 months6 months6 months

12 months12 months12 months6 months6 months

NoneNone

3 months3 months3 months

3 months3 months1 month1 month1 month

12 months12 months3 months3 months4 months

24 months24 months24 months24 months6 months

24 months24 months24 months24 months6 months

12 months12 months6 months6 months6 months

12 months12 months12 months12 months12 months

48 months48 months48 months48 months48 months

NoneNoneNoneNoneNone

NoneNoneNoneNoneNone

12 months12 months12 months12 months12 months

48 months48 months24 months24 months12 months

48 months48 months24 months24 months12 months

NoneNone

1 month1 month1 month

MonthlyMonthlyWeeklyWeeklyWeekly

NoneNone

4 months4 months4 months

24 months24 months12 months12 months6 months

24 months24 months12 months12 months6 months

WeeklyWeekly

Before UseBefore UseBefore Use

Note 6+Note 6+Note 6+Note 6+Note 6+

WeeklyWeeklyWeeklyWeekly

Before Use

NoneNone

WeeklyWeekly

Before Use

NoneNone

WeeklyWeekly

Before Use

SITMPH

SITMPH

SITMPH

SITMPH

SITMPH

Industrialincludingcommercialkitchens

Equipmentused by thepublic

Schools

Hotels(See note 7)

Offices andShops

TABLE DSUGGESTED INITIAL FREQUENCY OF INSPECTION AND TESTING OF EQUIPMENT

User Checks

Page 17: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

30

On successful completion of the tests a label shouldbe attached to the tested equipment showing:(a) The date tested(b) The identity of the test person(c) The date for re-testSuch information will enable the duty holder tomanage this aspect of the overall safety of the areawith his control.

A convenient method of labelling equipment mayincorporate a bar code. The Seaward Supernovaand Europa range of instruments can be used witha Bar Code Reader and collect Appliance numberand test codes without the need for manual datainput. Another advanced method of data collectionfrom the appliance is the use of SeawardBraincells. This is a revolutionary method whichallows the test record to be kept with the applianceand updated by the Seaward PAT. Braincells aresmall discs attached to the appliance which theSeaward PAT reads from and writes to after test.A full range of labels and data collectionaccessories are available from Seaward.

Data Transfer Between PAT and PCAdvanced Seaward PAT Testers such as theSupernova Plus, Europa Plus, PrimeTest 300 andPrimeTest 350 range contain output ports whichallow the tester to be connected to a PC runningPATGuard software. Selected appliances fromvarious locations can have their test data sentdirectly to the PAT (this is called Upload) which afterdisconnection from the PC may then be taken tothe location where the appliances are to be tested.Simply by inputting the appliance number, the PATwill search the upload memory in an attempt toidentify that particular appliance. If the appliance

31

Due to the large number of appliances, and thedetails that must be recorded, a computerdatabase is likely to be the most effective andefficient method of data collection and storage.

A comprehensive software package such asSeaward’s PATGuard will enable the user to setup a detailed database of all items at any particularlocation easily.

By recording the information outlined in (c) aboveworking documents can be produced which are auseful aid to proficiency and safety. For example awork schedule can be generated grouping productsby test date, task sheets can be printed providingthe person conducting the tests with a list of allitems due for testing, together with their location,identification number etc.

Use of Advanced Portable Appliance TestersWhere advanced portable appliance testers suchas Seaward’s Supernova Plus, Europa Plus,PrimeTest 300 and PrimeTest 350 testers are used,data can be transferred directly from the instrumentto the database providing automatic creation orupdate of records.

In such situations reports of untested appliancesand those which failed the tests can be producedand submitted to the duty holder for the appropriateaction to be taken, this insures the investigation isthorough and avoids oversight.

Action on Completion of TestsAny equipment found unsafe must immediately beremoved from use, labelled with its fault andtransferred to the repair facility and the appropriateperson informed.

Tried. Tested. Trusted.

Alternatively, a test programme using ‘on issue’ or ‘onreturn’ to or from a central pool or store, could beused where applicable to meet the required objectives.

It must be emphasised that Table D is producedfor guidance only, and an individual judgementmust be made by considering the actual conditionspertaining to any particular situation, in order toassess the hazard and reduce the subsequent riskof electric shock. For example there is a greatdeal of equipment used in offices not hand heldand the methods of use and the environment inwhich it is used leads to a lower level of risk thanin other sectors such as in industry or construction.There are however types of portable equipmentin offices together with their leads and plugs whichcould result in high levels of risk of electric shockif not inspected and tested and subsequentlyproperly maintained.

LONG TERM SAFETY OF APPLIANCESThe requirement is not only to determine theimmediate safety of the unit under test but toascertain so far is reasonably practicable, that theunit will remain safe under the expected conditionsof use at least until the next scheduled test date.Such a judgement may rely heavily upon thecompetence of the test person to offer soundpractical advice.

11 - RECORD KEEPING

IMPLICATION OF REGULATION 29In any proceedings for an offence consisting of acontravention of the EAWR 1989 Rep 4 (4).5 and8 to 16 inclusive (i.e. those Regulations requiring

“absolute” compliance). Regulation 29 states thatit shall be a defence for any person to prove thatthey took all reasonable steps and exercised all duediligence to avoid the commission of that offence.The most effective method for the duty holder toprove to a Court that he “exercised all duediligence” etc. is to produce proper records of themeasures taken to prevent the accident. Hencefull and accurate records made at the time oftesting become essential, and the managedsystem designed to achieve this must be in placebefore the accident.

The HSE Memorandum of Guidance on theseRegulations advises that records of maintenanceincluding tests should be kept throughout theworking life of the equipment.

Step by Step ApproachA step by step approach would include thefollowing:

(a) Conduct a survey to identify all portable and transportable appliances which exist with the duty holder’s control.

(b) Each appliance should be marked with a unique identification code, cross referencing test results and inspection details.

A register of all equipment should then be createdto include the following details:1. Identification number2. Location in which the equipment is kept3. A description of the appliance4. Serial number5. Periods between tests6. Any other details

Page 18: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

32 33

is identified the pre-determined sequence of testswill be suggested to the user, if this is acceptedthe instrument will then automatically conduct thetests and record the results.

The advantage of this approach is that it helpsavoid uncertainty as to which tests should beconducted on a particular appliance.

12 - INTERPRETATION OF RESULTS

Although the Supernova Plus, Europa Plus,PrimeTest 300 and PrimeTest 350 tester rangehave been programmed with PASS/FAIL levels,this does not remove the responsibility for finalassessment from the test person as PASS/FAILvalues are only for general equipment types.These testers allow for other values to be set forspecific equipment.

The PAT may indicate that the equipment has“Passed” the required tests, but comparison withpreviously recorded test figures may show achange in certain individual parameters. Acompetent test person should be able to judgethe significance of such changes, in particularwhen measured values are close to acceptablelimits, and recommend preventative maintenancewhere danger might otherwise occur.

Such decisions may require an understanding ofthe methods of construction employed, thecharacteristics of the supply to which theequipment may be connected and the likelyconsequence of further deterioration which maydepend to an extent upon the conditions underwhich the equipment could be used.

Tried. Tested. Trusted.

13 - SPECIAL NOTES

This guide only examines the main aspects to beconsidered when undertaking electrical safetytesting activity. The individual nature of testingactivities required by different organisations to solvetheir specific problems makes a more detailedapproach impractical.Electrical Medical Equipment“Electrical Medical Equipment” designed to meetthe requirements of IEC60601-1 and required tobe connected to the human body to diagnose,treat or monitor the patient, is designed toextremely rigid and precise safety standards. Theelectrical safety testing of such equipment shouldbe left to specialists in that particular field and it istherefore considered to be an inappropriate subjectfor this booklet which has been written to providegeneral advice. Seaward’s Rigel range of electricalmedical safety testers such as the Rigel 288, 266and 277 are designed specifically for thedemanding tests required by electrical medicalequipment.

Safety Checking of Business EquipmentThe Information Technology Safety TechnicalSub-Committee of the EEA, in consultation withthe HSE, has issued recommendationsregarding the periodic safety checking ofbusiness equipment (manufactured to EN60950). Where the recommendations provideadditional information to that of this booklet theissues addressed are noted below:

(a) Do not disconnect fibre optic cables unless required by the manufacturer’s instructions

(b) Under no circumstances look directly into

the end of a fibre optic cable or connector (although possibly not within the visibly spectrum, the radiation may still cause eye damage).

(c) Do not attempt to electrical safety test an uninterruptible power supply (UPS) without advice from the manufacturer (they are designed to provide mains power at their output after disconnection of the mains input).

Action where “NO TESTING” is discoveredIt should be realised that the HSE Factories Inspector or the Local Council Environment Health Officer (EHO) will not normally prosecutean individual or company for making a mistake(e.g. inadequate frequency of testing). If “no-testing” is discovered, it is usual for theinspector or EHO to issue an ImprovementNotice which will require a managed testingsystem to be installed within a set time (usuallyone month); alternatively if an accident had beencaused by an appliance which had never beentested, a subsequent prosecution is more likelyand in such circumstances the company andperhaps individuals may face prosecution.

Page 19: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

34 35

Tried. Tested. Trusted.

Nominalconductor

c.s.a

mm2

Nominalconductorresistance

at 20°C

mΩ /metre

Length

metres

Resistanceat 20°C

Maxcurrentcarryingcapacity

A

Approx No.of wires inconductor

1.01.52.02.53.04.05.0

2639526578104130

1.01.52.02.53.04.05.0

19.529.339

48.858.578

97.5

1.01.52.02.53.04.05.0

15.623.431.239

46.862.478

1.01.52.02.53.04.05.0

13.320

26.633.339.953.266.5

1.01.52.02.53.04.05.0

8121620243240

6

10

13

15

20

0.75

1.0

1.25

1.5

2.5

26

19.5

15.6

13.3

8

0.21

0.21

0.21

0.26

0.26

24

32

24

30

50

TABLE ESUPPLY LEAD RESISTANCENominal resistance of appliance supply cable protective conductors (cables to BS6500).

Max. dia. ofindividual

wirein conductor

mm

Conductor size (mm2) 0.5 0.75 1.0 1.25 1.5

3/(5)

12

(b)

20

13

25

13

25

13

25

Recommended fuse (BS1363 Pt 3) (a)

Recommended max test current taking account of temperature limit (a)

TABLE FCord conductors, plug fuses and earth continuity test currents.

Notes:

(a) Equipment manufacturers may specify smaller fuses than BS1363 Pt 3.

However the earth conductor in a detached cord may be tested at a current up to the

maximum test current allowed.

(b) BS1363 Pt 3 recommends a 13A fuse for use with a 0.75mm conductor.

However this would require a test current of 25A which would raise the conductor to too high

a temperature for the associate insulation. The fuse rating for a 0.75mm2 conductor should

therefore not exceed 10A.

Table E gives figures for the nominal resistance of the protective conductor per metre length and forvarious lengths of cable that may be fitted as supply leads to appliances. Once an Earth Bond Test hasbeen performed the approximate resistance of the protective conductor can be found and deductedfrom the test results to give a more realistic figure for the resistance of the earth bonding of the appliance.

Page 20: Tried. Tested. Trusted. - RS Components · Trusted. In safety testing, the bottom line is human life. So it’s our business to know your work inside out. This guide is what we know

36 37

Tried. Tested. Trusted.

APPENDIX 1

EN 60335 Safety of household and similarelectrical appliances.

BS1363-1 13A fused plugsBS2754 Memorandum. Construction of

electrical equipment for protectionagainst electric shock.

EN 50144 Hand-held electric motor-operatedtools.

EN 60335 Safety of household and similarelectrical appliances

EN 61558 Safety of power transformers,power supply units and similar.

EN 60309 Plugs, socket-outlets and couplersfor industrial purposes

EN 60320 Appliance couplers for householdand similar general purposes.

BS4343 Luminaires EN 60598 Safety of Luminaires EN 61010-1 Safety requirements for electronic

measuring apparatus. EN 61557 Electrical safety in low voltage

distribution systems. Equipmentfor testing, measuring andmonitoring of protective devices.

BS6500 Flexible cords rated up to300/500V for use with appliancesand equipment intended fordomestic, office and similarenvironments.

EN 60065 Safety requirements for mains-operated electronic and relatedapparatus for household andsimilar general use.

EN 60950 Specification for safety ofinformation technology equipment

including business machinesEN 50191 Erection and Operation of

Electrical Installations

APPENDIX 2

HSE Guidance NotesHS(G) 13 Electrical TestingHS(R) 18 Administrative guidance on the

application of the EC ‘Low VoltageDirective’

HS(R) 25 Memorandum of guidance on theElectricity at Work Regulations 1989

PM29 Electrical hazards from steam/waterpressure cleaners

PM32 The safe use of portable electricalapparatus

PM38 Selection and use of portable electrichandlamps

GS27 Protection against electric shockGS37 Flexible leads, plugs and sockets.

IET DocumentationCode of Practice for In-service Inspection andTesting of Electrical Equipment

LEGISLATIONThe Health and Safety at Work etc. Act 1974ISBN 0 10 5437743The Electricity at Work Regulations 1989(S.I.1989 No 635)ISBN 0 11 096635X

The Plugs and Sockets etc. (Safety) Regulations1987 (S.I.1987 No.603)ISBN 0 11 0766032

For further information contact: Seaward. Bracken Hill, South West Industrial Estate,Peterlee, Co. Durham. SR8 2SW, EnglandTel: +44 (0) 191 586 3511Fax: +44 (0) 191 586 0227Email: [email protected]: www.seaward.co.uk

Due to a policy of continuous developmentSeaward Electronic Ltd reserves the right toalter the equipment without prior notice and nopart of this publication shall be deemed to partof any contract for the equipment unlessspecifically referred to as an inclusion withinsuch contract.

© Seaward Electronic Ltd. 2007