© Burns Engineering Transmitters and Indicators for Temperature Measurement Transmitters and Indicators for Temperature Measurement Bill Bergquist, Sr. Applications Engineer Jeff Wigen, National Account Manager Jeff Bill 2 © Burns Engineering Transmitters and Indicators for Temperature Measurement What is a temperature transmitter? Why use a transmitter? Transmitter selection Ambient conditions Accuracy Location Indicators Options Communication types Wireless Installation Protection from EMI/RFI Ambient temperature limits Rail mount vs. head mount Calibration Matched calibration Specifications Accuracy and other performance characteristics Troubleshooting What we’ll discuss today Transmitters and indicators turned out to be a bigger topic than I thought when I began preparation for this presentation. What follows is information on the topics on which I get the most questions. 3 © Burns Engineering Transmitters and Indicators for Temperature Measurement An electronic device that converts the input from an RTD, thermocouple, or other temperature measuring device to a current output. Analog Converts a temperature measurement from an RTD or thermocouple to an analog value which is typically 4 - 20 mA of electrical current. Uses potentiometers to adjust output. Smart A smart or intelligent transmitter is an analog or digital device combined with a processing unit and a communication interface. Software or a communicator is used to calibrate and set functions. What is a Temperature Transmitter?

Upload: truongmien

Post on 17-Mar-2018

226 views

Category:

Documents


2 download

TRANSCRIPT

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Transmitters and Indicators for Temperature Measurement

Bill Bergquist, Sr. Applications EngineerJeff Wigen, National Account Manager

Jeff Bill

2

© Burns Engineering Transmitters and Indicators for Temperature Measurement

What is a temperature transmitter?Why use a transmitter?Transmitter selection

• Ambient conditions• Accuracy• Location• Indicators• Options• Communication types• Wireless

Installation• Protection from EMI/RFI• Ambient temperature limits• Rail mount vs. head mount

Calibration• Matched calibration

Specifications• Accuracy and other performance characteristics

Troubleshooting

What we’ll discuss today

   Transmitters and indicators turned out to be a bigger topic than I thought when I began preparation for this presentation.  What follows is information on the topics on which I get the most questions. 

3

© Burns Engineering Transmitters and Indicators for Temperature Measurement

An electronic device that converts the input from an RTD, thermocouple, or other temperature measuring device to a current output.

Analog• Converts a temperature measurement from an RTD or

thermocouple to an analog value which is typically 4 - 20 mA of electrical current. Uses potentiometers to adjust output.

Smart• A smart or intelligent transmitter is an analog or digital device

combined with a processing unit and a communication interface.

• Software or a communicator is used to calibrate and set functions.

What is a Temperature Transmitter?

4

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Zero• Temperature setting for 4 mA output level

Span• Temperature setting for 20 mA output level

Digital• Electronic circuits representing signals by discrete bands of analog levels, rather

than by a continuous range1.• One advantage of digital vs. analog circuits is that signals represented digitally

can be transmitted without degradation due to noise.Analog

• A signal that contains information using non-quantized variations in frequency and amplitude1.

Potentiometer (pot)• Variable resistor

Terminology

1Wikipedia

5

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Analog Transmitter

Calibrated using an ammeter, power supply, and screw driver

   For some applications, simple is better.  Measurement loops are easily fine tuned by turning the potentiometer screw.   

6

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Available in sizes and capabilities to suit every applicationProgrammed with PC, communicator or central control system

Smart Transmitter

  From a miniature head mounted device with minimal “extras” to a large head mounted transmitter with all the bells and whistles smart transmitters are designed to accommodate any temperature measurement requirement.  Programming is accomplished by a software package and interface device, a handheld communicator, or remotely through a central control system. 

7

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Improve measurement accuracy• Avoid lead wire error• Transmitter output is more accurate than most direct input cards on

controllers• Linearize the non-linear sensor measurement• Delay measurement – useful for environmental storage chambers

More robust signal over long distances

Local indication of temperature

Help protect measurement from electrical interferenceSensor leads act like an antenna for RFI/EMI. Transmitter circuitry is design to filter this noise. Mount transmitter as close as possible to the sensor. Especially important for thermocouples.

Why Use a Transmitter?

 Controllers, PLCs, and other devices have options to take a temperature measurement signal directly from a thermocouple or RTD so why use a transmitter?  There are several good reasons to include a transmitter in your measurement loop.  One of the most important is to minimize the sensor lead length to the controller.  Leads act as an antenna picking up interference from EMI/RFI, static, and other stray electrical noise.  Thermocouples are especially susceptible to this because of their low voltage output. 

8

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Standardize on a single input type for controllersAdd more functionality to the measurement point

Hot Backup®

Differential measurementMultiple inputAveragingRemote communicationAllows for fine tuning of measurement systemSensor diagnostics – monitors the sensor for indications of impending failure

Why Use a Transmitter?

  Some manufacturers offer features that monitor the sensor health and send an alert that maintenance is needed.  Others will automatically switch to a backup sensor if the primary sensor fails.    Other common features are multiple sensor inputs to perform differential temperature measurement or averaging of several points. 

9

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Lead Wire Error with RTDs

2 wire connection adds lead resistance in series with PRT element

  One important reason to use a transmitter is to help eliminate lead wire error in an RTD circuit.  Following is a discussion on the effect of lead resistance in RTDs.    Two wire circuits simply add the lead resistance to the sensing element resulting in very large errors.  These should not be used for any measurement that requires high accuracy. 

10

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Lead Wire Error with RTDs

3 wire connection relies on all 3 leads having equal resistance

  A three wire circuit will add no error if each of the three legs have the same resistance.  Unfortunately, in the real world, there is a difference and that causes an error. Adding a transmitter at the sensor location eliminates the lead error. 

11

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Lead Wire Error with RTDs

4 wire connection eliminates error

  The current potential method or 4 wire circuit is the most accurate and has no lead wire error associated with it.  Here there’s a trade‐off between running a 4 conductor cable to take the signal directly to a controller, or add a transmitter and use less expensive 2 conductor cable for the 4‐20 mA current.  A rule of thumb is if the sensor to controller distance is over 250ft then it is a good idea to add a transmitter.   

12

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Analog• Inexpensive• Simple calibration• Easily adjusted to match sensor calibration at end points (zero

and span) or a single intermediate point

Transmitter Selection

  Analog or Smart is the first decision to make when selecting a transmitter.  Decide if the extra features of a smart transmitter will be needed for your application or if a simple analog device will do.    Calibration of an analog transmitter is usually very simple requiring a power supply, ammeter, and screwdriver.  

13

© Burns Engineering Transmitters and Indicators for Temperature Measurement

SmartWide price rangeNumerous options Communications

• HART, Fieldbus, Profibus• Local• Remote

Ability to match sensor to transmitter using multiple calibration points or an interpolation equation such as the Calendar van Dusen

Transmitter Selection

 If a smart transmitter is desired then you will need to wade through the myriad of options available.  Here size does matter in that the larger devices have more options and are more expensive.  The two pictured above are identical except that one has HART communications capability and the other does not.  Both will mount in most connection heads and have several setup options available.  Programming is through a software/interface package or for the HART version a handheld communicator can be used.  

14

© Burns Engineering Transmitters and Indicators for Temperature Measurement

WirelessNetwork typeSecurityReliabilityMounting location – may require line-of-sight to receiver

Transmitter Selection

  Wireless transmitters are growing in popularity and manufacturers are sorting through all the communications possibilities and are settling a few configurations.  Some of the factors to consider are which network type will work best for you, security, and reliability.  We have all had a cell phone call drop out or a laptop PC wireless internet connection disconnect unexpectedly and those are concerns if using a wireless transmitter to control a process.   

15

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Head mounted

Installation

  Mounting the transmitter is determined by ambient conditions, accessibility to read the indicator, or hazardous atmospheres. 

16

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Installation

Typical wiring connections for a 4 wire RTD to a head mounted loop powered transmitter

• Power is 24 VDC

17

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Integrated into the sensor housing

Installation

Transmitter location

  Transmitters can be integrated into the sensor housing to create a compact package for restricted space locations. 

18

© Burns Engineering Transmitters and Indicators for Temperature Measurement

High density located in remote panel

Rail Mount

  If several measurement points are located close together a panel or rail mount transmitter may be a good solution.  Several can be installed in a very small space.  

19

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Remote mounted• Wall mount or pipe mount

Installation

  Ambient conditions can sometimes dictate the location of a transmitter.  High or low temperatures may damage the electronics or indicator requiring that the transmitter be mounted close by on a pipe or wall mount.   

20

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Hazardous locations – FM, CSA, ATEX, IECEx

Intrinsically safe installation

Installation

  Hazardous atmospheres will require specially rated enclosures and sensor assemblies.   

21

© Burns Engineering Transmitters and Indicators for Temperature Measurement

LED Indicator

Works well in low light conditionsCan be difficult to read in bright light

  Indicators are LED or LCD and the selection depends on where it will be used.  LEDs are generally difficult to read in bright light but are easily read in low light.  Opposite is true for LCD indicators.  

22

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Works well in bright lightMay require backlight to read in low light conditions

LCD Indicator

23

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Other considerations

Ambient temperature• Most are limited to -40°C to 85°C to protect the electronics –

indicators have more limited range• Accuracy is affected by the ambient temperature

Vibration• Remote mount may be necessary

Sanitary wash-down• Corrosion resistant coatings and waterproof heads

Safety Instrumented System (SIS)• Requires safety certified transmitter

Installation

24

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Other considerationsBattery power

• Useful for remote locations

Installation

  Battery powered transmitters/indicators are useful for remote locations or where a local indication of temperature is required.  Batteries typically last 2 years or more. 

25

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Generally a relatively low cost method to dramatically improve measurement accuracy.

Sensor is calibrated and that information is used to set the transmitter output.

Requires calibration of the RTDAnalog transmitter allows setting of Zero and span temperatures or one intermediate pointSmart transmitter - Full calibration with coefficients over service range for smart transmitters with curve matching capability

Matched Calibration

  At a minimum, the RTD resistance is checked in a temperature bath at the zero and span temperatures.  Those resistance values are used to adjust the transmitter output.  For those transmitters that have curve fitting capability, a full calibration of the RTD is performed and the resulting coefficients are entered into the transmitter.   

26

© Burns Engineering Transmitters and Indicators for Temperature Measurement

InterchangeabilityInterchangeability refers to the “closeness of agreement” between an actual R vs. T relationship and a predefined R vs. T relationship.

Terminology

  The largest sensor error is the interchangeability.  Matching the sensor calibration to a transmitter will eliminate about 85% of the error.  ASTM E1137 and IEC 60751 are the two most commonly used standards that define a nominal R vs. T relationship for RTDs.  All sensors are manufactured with 0°C as the starting point.  Variations in sensors result in the tolerance increasing as the temperature diverges from 0°C. 

27

© Burns Engineering Transmitters and Indicators for Temperature Measurement

-4

-3

-2

-1

0

1

2

3

4

-300 -200 -100 0 100 200 300 400 500 600 700 800

Temperature (°C)

Tole

ranc

e (±

°C)

IEC Class B

ASTM Grade B

IEC Class A ASTM Grade A

ASTM Grade A

IEC Class A

ASTM Grade B

IEC Class B

Interchangeability

  Note that the ASTM standard has slightly tighter tolerances for the two grades of sensors.  All RTDs are built with the tightest tolerance at 0°C and as the temperature diverges from 0°C the tolerance increases.  The vertical line on the graph represents 0°C and the tolerance on the y axis is expressed in ± °C from nominal.   

28

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Standard Tolerance Defining Equation¹ASTM E1137 Grade A ± [ .13 + 0.0017 | t | ]ASTM E1137 Grade B ± [ .25 + 0.0042 | t | ]IEC 607512 Class AA2 ± [ .1 + 0.0017 | t | ]IEC 60751 Class A ± [ .15 + 0.002 | t | ]IEC 60751 Class B ± [ .3 + 0.005 | t | ]IEC 607512 Class C2 ± [ .6 + 0.01 | t | ]

Note 1: | t | = absolute value of temperature of interest in °CNote 2: These tolerance classes are included in a pending change to

the IEC 60751 standard.

Interchangeability

  These equations can be used to calculate the interchangeability at any temperature.  Note that the temperature t is an absolute value in °C.  The resultant is the interchangeability in ± °C. 

29

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Examples:Temp. Grade A Class A Grade B Class B

0°C ±.13°C ±.15°C ±.25°C ±.30°C100°C ±.30°C ±.35°C ±.67°C ±.80°C200°C ±.47°C ±.55°C ±1.09°C ±1.30°C300°C ±.64°C ±.75°C ±1.51°C ±1.80°C400°C ±.81°C ±.95°C ±1.93°C ±2.30°C

Interchangeability

  Calculating the interchangeability at 200°C shows the difference between the grades or classes of sensors.  Grade A or Class A have the tighter tolerances.   

30

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Matched transmitter example:RTD in a process at 121°C using a transmitter with .1°C accuracy.

Grade B Grade A MatchedSensor at 121°C ±.76°C ±.34 ±.05Transmitter Accuracy ±.10°C ±.10 ±.10Combined System (RSS) ± .77°C ±.35°C ±.11°C

Match RTD to Transmitter

  In our example an accuracy improvement from ± .77°C down to ± .11°C was made by matching the sensor to the transmitter.  Matching is a very economical method to improve your system accuracy. 

31

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Analog transmitter potentiometers are used to make adjustments to the zero and span.

Match RTD to Transmitter

32

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Software is used for smart transmitter setup

Match RTD to Transmitter

33

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Match RTD to Transmitter

34

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Match RTD to Transmitter

  This screen shot shows a typical smart transmitter setup for entering the calibration coefficients and temperature coefficient from a calibrated RTD. 

35

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Callendar-Van Dusen Equation

Matched Calibration

T = temperature (°C)R = resistance at temperature TR0 = resistance at the ice pointα = constant (gives the linear approximation to the R vs. T curve)δ= constantβ= constant (b = 0 when T is >0°C)The actual values for the coefficients,α, δ, and β are determined by testing the RTD at four temperatures and solving the equations.

R/Ro = 1 + α [T - δ (T/100 - 1)- β (T/100 - 1) (T/100)3 ]

  The CVD equation is used in a lot of smart transmitters to interpolate between calibration points.  IPTS‐68 is still used for industrial applications because it is simpler to apply and still gives acceptable accuracy for numerous processes.   

36

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Insulation resistanceElectrical resistance between the sensing circuit and the metallic sheath of a PRT – should be at least 200 megohms at 20°C

Matched Calibration

  An important first electrical check that should be performed as part of any calibration.  If the sensor is out of spec a repeatable calibration cannot be performed.   

37

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Using an Ice Bath, check resistance at 0°C

Matched Calibration

 If the sensor passes the IR check then a check in an ice bath should be performed.  Crushed ice made with purified water is packed into an insulated container.  Purified water is added to fill in the gaps.  If the ice floats, you have added too much water.  Adding a stirring feature to keep the water flowing around the ice minimizes temperature gradients within the bath.  Each probe should be immersed at least 4”.  Do not use the probe to beat a hole in the ice.  You may damage the sensing element.  Use a scrap probe or similar rod to form the holes.   

38

© Burns Engineering Transmitters and Indicators for Temperature Measurement

• Use a high accuracy meter• Reading should be 100 ± 0.12 ohms for Class B and 100 ± 0.06 ohms for

Class A per the ASTM E 1137 or IEC 60751 standards• Outside this range and the probe should be replaced

Matched Calibration

  If the probe does not meet the resistance tolerance it should be replaced.  There is not any reliable and cost effective method to repair it.  Save the sensor for recycling!  There is $$ worth of platinum in each probe.  Save it up for a department lunch. 

39

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Equipment used

Matched Calibration

  Some of the equipment required for matching an RTD to a transmitter.   ‐Software and interface for PC programmable transmitters ‐Decade box and ammeter for analog transmitters with adjustment potentiometers. 

40

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Accuracy specifications – vary by manufacturer in how they are stated

Specifications

  Manufacturers seem to have many different ways to report transmitter performance.  Here are three that range from simple to complex.  Be careful when comparing devices to insure you get the performance you need.  

41

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Corroded terminals can cause high resistance in the leads

3-wire circuits are susceptible – accuracy depends on each conductor having exactly the same resistance

• Terminals clean and tight• Terminal block clean and dry, secured to head• Wires are tinned, or terminated with spade lug

4-wire circuits also compensate for some poor maintenance• Compensate fully for all lead wire resistance in the circuit

Troubleshooting

  As with anything eventually a transmitter will fail and some trouble shooting is necessary to see if it is an installation problem or if the device has failed.   

42

© Burns Engineering Transmitters and Indicators for Temperature Measurement

The good and bad

Troubleshooting

Conductive dust inside head

  High quality connecters, spade lugs, or tinned leads are good methods to connect a transmitter to a sensor.  The connection head shown in the lower right corner had a lot of electrically conductive dust in it that caused some electrical leakage between the terminals resulting in a bad temperature reading.   

43

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Wires connected securely with no stray strands

Troubleshooting

  A stray wire strand can easily short the terminals together on a transmitter or terminal block.   

44

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Most common failure mode is due to voltage spikes such as from welders and lightning• Causes output to lock. No response from the transmitter when the input

resistance is varied.

Troubleshooting

© Burns Engineering Transmitters and Indicators for Temperature Measurement

Questions?