transmission-line protection a direction

Upload: umer-ehsan

Post on 26-Feb-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Transmission-Line Protection a Direction

    1/10

    IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013 955

    Transmission-Line Protection: A DirectionalComparison Scheme Using the Average of

    Superimposed ComponentsS. M. Hashemi, M. Tarafdar Hagh, Member, IEEE, and H. Seyedi

    AbstractIn this paper, a new protection scheme for transmis-sion lines is presented. The method has some advantages in com-parison with conventional line protection schemes. Faster fault de-tection and instantaneous coverage of almost 100% of the line arethe main advantages of the new method. A full-cycle averaging

    window is used for fault detection. While the power system is innormal operation conditions, this average is approximately equalto zero. As soon as the faulty signals enter the window, the averageis changed to a nonzero value. It is shown that the product of thisaverage value for voltage and current of the faulty phase, in a spe-

    cific time interval after fault inception, is negative for the forwardfaults and positive for the reverse faults. The fault is detected bycommunication between the local and the remote relays. Simula-tion and experimental results show the efficiency of the proposedmethod in fast detection of line faults in less than a half cycle.

    Index TermsDirectional comparison, protection, relaying, su-

    perimposed component, transmission line.

    I. INTRODUCTION

    T RANSMISSION lines are prevalently protected by dis-tance relays as the main protection, and overcurrent re-lays as the backup protection. Both distance and overcurrent

    protections use fundamental or power frequency components

    to detect the faults. In microprocessor relays, the extraction of

    fundamental frequency voltages and currents is, conventionally,

    provided by phasor estimation methods such as the Fourier al-

    gorithm [1], [2]. The common required time for fault detection

    in these relays is approximately one to two cycles. Fast detec-

    tion and clearing of faults improves the stability of power sys-

    tems, especially in extremely high voltage (EHV) transmission

    lines. Therefore, the trend is toward faster protection schemes

    in modern integrated power systems.

    Superimposed components are changesin voltage and current

    signals with respect to the normal or steady-state conditions.

    These changes cause voltage and current traveling waves (TWs)to propagate away from the fault location. Protection schemes

    using TWs are capable of detecting the fault in the first millisec-

    onds following the fault inception [3], [4]. TW-based protec-

    tion has some outstanding features, such as immunity to power

    Manuscript received May 08, 2012; revised September 07, 2012; acceptedOctober 16,2012. Date of publication February 05,2013; date of current versionMarch 21, 2013. Paper no. TPWRD-00476-2012.

    The authors are with the Faculty of Electrical and Computer Engineering,University of Tabriz, Tabriz 51666-15813, Iran (e-mail: [email protected]; [email protected]; [email protected]).

    Color versions of one or more of the figures in this paper are available onlineat http://ieeexplore.ieee.org.

    Digital Object Identifier 10.1109/TPWRD.2012.2226609

    swings, current-transformer (CT) saturation, and long lines ca-

    pacitance which make it more robust than traditional distance

    protection [5]. TW-based protection may determine the fault di-

    rection by comparing the polarities of superimposed quantities

    of voltages and currents. Besides, the protection can measure

    the fault distance using the time difference between forward and

    backward TWs. A common feature is observed among many

    TW-based protection schemes in the literature [6][9]. These

    schemes usually require high sampling frequency between sev-eral hundreds of kilohertz to 1 MHz, which is more than the

    sampling rate of conventional digital relays [7]. Furthermore,

    limitations in the bandwidth of conventional VTs and CTs, are

    also introduced and there are some difficulties in measuring su-

    perimposed components for TW applications [10], [11].

    Superimposed-based protection is not limited to TWs. It is

    shown in [12][14] that distance protection using superimposed

    components, so-called delta quantities, instead of fundamental

    frequency impedance, may solve some problems in the conven-

    tional distance relaying. Superimposed currents are proposed

    in [15] for the phase comparison protection to remove the

    sensitivity of this protection to heavy load conditions. In [16],

    superimposed components are used for providing high-speeddirectional comparison bus protection. The transient energy

    produced by superimposed components is used in [17] for

    directional comparison relaying. Positive-sequence superim-

    posed components are used in [18] for directional protection

    of EHV transmission lines. In [19], it has been shown that su-

    perimposed-based directional comparison offers some benefits

    compared with the line differential protection.

    This paper introduces a directional comparison protective

    scheme using the average value of superimposed components.

    The method is able to detect the faulty phase and the fault

    direction in less than a half-cycle. Applying the sampling rate

    of 64 samples/cycle makes the proposed method compatiblewith the commercial relays. Moreover, using the average of

    voltage and current signals in a full cycle for fault detection, the

    buffer size applied in the proposed method is reduced compared

    with some superimposed-based protection schemes where the

    samples of two or four full cycles are required to be saved [11],

    [20].

    II. BRIEF REVIEW ON THE FAULT SUPERIMPOSEDCOMPONENTS

    Consider a simple transmission system, shown in Fig. 1(a).

    This fault can be modeled by a voltage source, which is equal

    in magnitude and opposite in sign to the prefault voltage at

    the fault point [2]. According to the superposition theorem, the

    0885-8977/$31.00 2013 IEEE

  • 7/25/2019 Transmission-Line Protection a Direction

    2/10

    956 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

    Fig. 1. Simple transmission system with (a) steady-state (prefault) and (b) su-perimposed-state representation. A three-phase fault is assumed to occur in theforward direction, with respect to the relay R.

    changes in the relay point (R) voltage and current might be com-

    puted by zeroing all prefault voltage sources and representing

    all network components and loads with their impedances [21].

    The obtained circuit, which is depicted in Fig. 1(b), is known

    as a superimposed network. For simplicity, only the inductive

    portion of impedances is considered in Fig. 1(b). Therefore, the

    postfault voltage and current at any point of the network can be

    acquired by superposition of their prefault values and superim-

    posed values, as

    (1)

    where is the superimposed voltage. A similar relation

    may be written for the current. The superimposed components

    contain dc offset, harmonics, and high-frequency transients.

    Their salient feature is that the product of superimposed voltage

    and current at the relay point is negative for the forward faults

    and positive for the reverse faults. These properties, providing

    an excellent criterion for directional comparison relaying,form the basis of TW-based protective schemes [2]. In digital

    protection, the superimposed components may be extracted

    by subtracting each sample from its corresponding sample in

    the previous cycle. This process extracts the superimposed

    components in only one cycle after fault inception, and the

    relay would take its decision in this interval.

    III. PROPOSEDPROTECTIVEMETHOD

    In the steady-state conditions, the voltage and current signals

    in the transmission lines are almost pure sinusoidal. This im-

    plies that the average value of voltage and current signals, in

    steady-state conditions, is almost equal to zero. Referring to (1),

    it may be concluded that the average value of postfault voltage

    (or current) is equal to that of superimposed voltage (or current)

    (2)

    where denotes the average value of the periodic signal

    , with the period , which is represented in the continuous

    time form by . In the discrete time

    form, the average value can be represented as

    (3)

    where is the number of samples per cycle. Selecting a data

    window with the length of one cycle, the above equation may be

    Fig. 2. Output of the averagingfilter for a typical current waveform.

    called the averaging filter. The filter proceeds sample by sample

    along the input signal. While the protected transmission system

    operates in healthy conditions, the input signal, whether voltage

    or current, has a pure sinusoidal waveform, and the output of the

    filter is near zero. As soon as the faulty samples enter the filter,

    its output changes to a nonzero value. As mentioned before,this value is equal to the average of the superimposed compo-

    nents. Referring to Fig. 1(b), the superimposed components can

    be considered as the zero-state response of the electric circuit.

    According to the electrical circuit theory, this response consists

    of two parts, which are transient and steady-state responses, re-

    spectively. For example, if the transmission line is modeled by

    a series branch, the superimposed current consists of one

    decaying dc component and one steady-state sinusoidal com-

    ponent. The average of this current is, therefore, equal to its dc

    value. However, as shown in Fig. 2, since the input signal passes

    sample by sample through the averaging filter, one cycle should

    be elapsed after the fault inception instant in order for that outputoffilter to become equal to the signal dc value. Moreover, the

    output of the filter during this cycle has an interesting feature

    which is investigated for forward and reverse faults, as follows.

    A. Forward Faults

    Considering Fig. 1, suppose that a three-phase fault occurs

    in the forward direction, with respect to the relay R, at point F.

    Shifting the time origin to the fault inception instant, the super-

    imposed voltage and current can be computed as

    (4)

    (5)

    (6)

    The discrete time representations of (5) and (6), assuming

    and

    can be written as

    (7)

    (8)

  • 7/25/2019 Transmission-Line Protection a Direction

    3/10

    HASHEMIet al.: TRANSMISSION-LINE PROTECTION 957

    Fig. 3. One-line diagram of a simple transmission system with (a) steady-state(prefault) and (b) superimposed-state representation. A three-phase fault is as-sumed to occur in the reverse direction, with respect to the relay R.

    B. Reverse Faults

    For the reverse faults condition, Fig. 3 can be investigated

    (9)

    (10)

    (11)

    Here, assuming

    and , the discrete time

    representations of (9) and (10) can be written as

    (12)

    (13)

    Comparing (7), (8), (12), and (13) and considering that

    , and are positive values, it can be realized that

    the sign of in the forward faults is opposite that sign in

    the reverse faults, while the sign of is similar in both

    forward and reverse faults. This property may be used as a cri-

    terion for discriminating between the forward and the reverse

    faults. For this purpose, let us compute the product of

    and . For the forward faults, we have

    (14)

    For the reverse faults

    (15)

    The sign of in the first cycle after fault

    inception is given in Table I, where it can be shown that this

    sign is dependent on the sample number . Moreover, is re-

    stricted by the number of samples per cycle and the value of

    fault inception angle . For particular values of , the interval

    TABLE IDETERMINING THESIGN OF IN THEFIRST CYCLEAFTER

    FAULT INCEPTION

    where the sign of is invariant, becomes veryshort and may include only one or two samples. It means that

    the dependability of the relay would decrease. Since the value

    of is variable, can be controlled only by . In other words,

    for increasing the interval where the sign of

    is negative for forward faults and positive for reverse faults, the

    sampling frequency should be increased. As before, this incre-

    ment is a shortcoming for practical implementation in the con-

    ventional relays. This problem can be solved by the proposed

    method, as follows.

    The average value of the voltage and current signal in each

    phase is calculated using (3). Assume is the number of super-

    imposed samples entering the averaging window. The output ofthe window for forward faults is given by (16) and (17) at the

    bottom of the next page. For the reverse faults, similar equations

    result by replacing in (16) with , and in (17) with

    . It can beshown that the first interval after the fault incep-

    tion instant, where the sign of

    is invariant, is equal to for and

    for . Comparing these values with

    Table I demonstrates that the interval becomes almost twice. In

    Fig. 4, theproduct of (16) and(17) is compared with (14) fortwo

    different fault inception angles. It is shown that the mentioned

    interval is extended. The proposed method consists of (16) and

    (17)of the following stages. The rate of sampling is assumed tobe 64 samples/cycle. The relay detects the fault using eight con-

    secutive superimposed samples.

    1) Phase Selection: Phase selectivity provides the capability

    of single-phase automatic reclosing. On overhead lines, most

    faults are of a transient nature and disappear when the infeed is

    switched off. Therefore, following the fault clearance, the line

    can be returned to service [12]. This means that the single-phase

    tripping is preferred for single-phase-to-ground faults. Single-

    phase automatic reclosing basically improves the transient sta-

    bility of power systems. The process of phase selection in the

    proposed method is performed by comparing the absolute value

    of the average of superimposed currents in the eight consecutive

    windows with a threshold value. This value can be selected sim-

    ilar to the setting of overcurrent relays. It means that assuming

  • 7/25/2019 Transmission-Line Protection a Direction

    4/10

    958 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

    Fig. 4. Normalized values of (14) and (16) (17) for various fault inceptionangles. (a) . (b) .

    theminimumfault current level of 1.25 times the maximumload

    current, the threshold value may be set to , where

    is the rated current in the secondary side of CT which is typi-

    cally 5 A. (The division to is because of the averaging nature

    of the proposed method.) Single-phase tripping is executed by

    the proposed algorithm if a single-phase fault is detected for the

    first time. Otherwise, all three phases should be tripped.

    2) Detecting the Fault Direction: A flowchart of the pro-

    posed directional relaying is shown in Fig. 5. When a short-cir-

    cuit fault occurs, it changes the output of the averagingfilter to a

    nonzerovalue. However, because of VT and CT errors and some

    environmental noises, during normal operation of the system

    and in the absence of any fault, this output may not be exactly

    equal to zero. A threshold level is, therefore, needed to detect

    the fault conditions. This threshold for the current signals is se-

    lected as the aforementioned value (i.e., ), and for the

    voltage signals, is assumed to be , where is the rated

    voltage in the secondary side of VT which is typically 110 V.Provided that the average of superimposed voltages and currents

    Fig. 5. Directional relaying by the proposed method in phase A. A similarprocess is performed in phases B and C.

    exceeds their corresponding thresholds, the relay computes the

    sum of and the sum of in the eight con-

    secutive windows. The product of these values forms the

    basis of directional relaying: The negative indicates forward

    faults, while the positive indicates reverse faults (Fig. 5). In

    very rare situations where the value of becomes almost zero

    , the fault direction is detected in one or two subse-

    quent windows.

    3) Communication With the Remote Relay: So far, the relay

    discriminates between forward and reverse faults. Additional

    discrimination should be performed between the internal faults

    (i.e., the faults between the close-in and the remote bus and the

    external faults, that is, the faults beyond the remote bus). This

    can be provided by communication between local and remote

    relays. Assume the forward direction for the local and the re-

    mote relays as depicted in Fig. 6. If one relay detects a fault that

    is in the forward direction, it will wait for the permissive signal

    from the remote bus relay. The internal fault is, therefore, de-

    tected if both relays detect the fault in the forward direction.This provides extremely fast protection for the entire line.

    (16)

    (17)

  • 7/25/2019 Transmission-Line Protection a Direction

    5/10

    HASHEMIet al.: TRANSMISSION-LINE PROTECTION 959

    Fig. 6. Directional comparison relaying by the proposed method.

    Fig. 7. First simulated system.

    TABLE IISIMULATION RESULTS FOR THE STUDY ON THE EFFECT

    OFFAULTLOCATION OF THE PROPOSED METHOD

    IV. SIMULATION RESULTS

    The proposed method is tested on two different systems under

    several operating conditions. The results are given in the fol-

    lowing subsections A and B.

    A. System I

    This system is a part of an Iranian 230-kV transmission net-

    work, depicted in Fig. 7. The system data are given in Table X.

    The system is simulated in PSCAD/EMTDC where the voltage

    and current signals in the relay point are used for running

    the proposed scheme in MATLAB. The frequency-dependentmodel is used for transmission lines in order to increase the

    accuracy of simulation. Performance of the proposed method

    is evaluated in many various conditions which are summarized

    as follows.

    1) Effect of Fault Location: Various types of fault in dif-

    ferent points of the transmission line are tested. Table II shows

    that the proposed algorithm is able to detect the fault in less

    than a half cycle. In this table and the following tables, Ag,

    AB, ABg, and ABC stand for single-phase-to-ground, double-

    phase, double-phase-to-ground, and three-phase faults, respec-

    tively. Moreover, F and R denote forward and reverse, and the

    negative locations represent the faults occurring in the reverse

    direction. For the fault Ag at 10 km far from bus B, the details of

    waveforms are shown in Fig. 8, where the system frequency is

    Fig. 8. Simulation result of an Ag fault in the forward direction. (a) Voltageand current of phase A. (b) Averages of the superimposed voltage and current.

    50 Hz. For the internal faults as , both relays R and R should

    detect the fault in the forward direction while for the external

    faults as , relay R, on the contrary of relay R , should detectthe fault in the reverse direction. Neglecting the delay of the

    communication channel, the total time required for fault detec-

    tion is determined by the relay with longer operating time.

    2) Effect of Fault Resistance: The presence of resistance

    in the fault path causes the dc component of fault current in

    (7) and (10) (i.e., the term to decay exponentially).

    Since the fault resistance is remarkable in the case of earth

    faults, performance of the proposed method is tested on some

    single-line-to-ground faults with fault resistances between 5 to

    100 . As shown in Table III, the proposed method seems to not

    be sensitive to the fault resistance.

    3) Effect of Fault Inception Angle: The presence of the dccomponent in the fault current depends on the fault inception

    angle. In other words, it would be some angles, or equally some

    instants, that the corresponding fault current does not have any

    dc value. Nevertheless, as the averaging window moves sample

    by sample, it needs at least one full cycle to compute the new

    dc value after fault inception. In this interval, the estimated dc

    component changes from zero to a nonzero value and returns to

    zero at the end of one cycle. Fig. 9 represents an example of this

    condition for a reverse three-phase fault at 0.204 s.

    Theeffect of the fault inceptionangle on the proposed method

    can be considered in Table IV. In order to cover the entire in-

    terval of 0 to , the fault inception instant is gradually in-

    creased in one full cycle. The results of Table IV demonstrate

    that the required time for fault detection has increased in some

  • 7/25/2019 Transmission-Line Protection a Direction

    6/10

    960 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

    TABLE IIISIMULATIONRESULTS FOR THE STUDY ONEFFECT OFFAULT RESISTANCE

    ON THEPROPOSED METHOD

    Fig. 9. Example of zero dc current for a particular fault inception angle. Onlyphase A is represented.

    inception angles. However, the delay, in the worst condition, is

    less than half a cycle.

    4) Effect of Noisy Fault Signals: Since the nature of the pro-

    posed method is averaging signals during one full cycle, it is

    expected that the noise effect on the proposed method is not

    considerable. This is due to the fact that the average of white

    noise is zero. Various faults with different signal-to-noise ratios

    (SNRs) are tested, and the results are shown in Table V. For this

    purpose, the Gaussian white noise with the signal-to-noise ratio

    (SNR) of 60, 40, and 20 dB are added to the main signals. For

    increasing the security of the proposed method in the presence

    of noise-polluted signals, the value of thresholds should be set

    more accurately. The inception instant of all faults in Table V is

    0.2 s.

    B. System II

    The purpose of simulation studies in this case is to evaluate

    the performance of the proposed method in situations where the

    line distance protection, as the prevailing protection in trans-

    mission lines, is encountered with challenges and difficulties.

    The IEEE Power System Relaying Committee (PSRC) proposes

    the system depicted in Fig. 10 for testing most transmission-

    line protection applications [22]. The system is simulated in

    TABLE IVSIMULATIONRESULTS FOR THE STUDY ONEFFECT OFFAULTINCEPTION

    ANGLE ON THE PROPOSED METHOD

    TABLE VSIMULATIONRESULTS IN THECASE OFNOISYSIGNALS

    the Electromagnetic Transients Porgram (EMTP). It should be

    noted that for each of the following cases, according to [22],

    some changes on the topology of Fig. 10 are applied. Thesystem

    frequency is 60 Hz, and the sampling rate is 64 samples/cycle.

    Referring to Table X, the protection in two challenging con-

    ditions (i.e., the presence of short line and the maximum line

    loading) has been considered in the previous subsection. The

    other cases are investigated as follows.

  • 7/25/2019 Transmission-Line Protection a Direction

    7/10

    HASHEMIet al.: TRANSMISSION-LINE PROTECTION 961

    Fig. 10. IEEE PSRC recommended model for testing transmission-line protec-tion in EMTP.

    TABLE VISIMULATIONRESULTS FOREVALUATING THE PROPOSED METHOD IN

    DOUBLE-CIRCUITLINES

    1) Double-Circuit Lines: Mutual inductive coupling be-

    tween transmission lines on the same tower or parallel alongthe same right of way introduces some errors in the impedance

    measured by distance relays. These errors are negligible in

    positive- and negative-sequence impedances. Nevertheless, as

    the zero-sequence mutual impedance of parallel lines can be

    50% to 70% of zero-sequence self-impedance, the impact of

    mutual coupling is more significant in the case of ground faults

    [12], [23]. Therefore, the performance of the proposed method

    in parallel lines is evaluated only for the earth faults. For this

    purpose, the switch SW in Fig. 10 remains open and the relay

    is tested for faults on 66% of the lower line AB, and

    on 11% of the upper line AB. The results are given in Table VI.

    2) Three-Terminal Lines: Sometimes, usually due to eco-nomic restrictions, transmission lines are tapped to provide in-

    termediate connections to loads, or to reinforce the underlying

    lower voltage network through a transformer. These connec-

    tions introduce some problems in distance protection, especially

    when sources of generation exist behind the tap points [24]. The

    fundamental problem with this line configuration is the inter-

    mediate infeed to the fault location from the third terminal [12].

    Besides, the application of travelling-wave-based protection in

    three-terminal lines requires careful study, since the travelling

    waves are strongly affected by the connected taps.

    To create this condition in Fig. 10, the upper line AB is

    opened and the switch SW is closed. The tap point is located

    at 33% of the length of line AB. Afterwards, the performance

    of relays R1 and R2 is evaluated for the faults located at F1

    TABLE VIISIMULATIONRESULTS FOREVALUATING THE PROPOSED METHOD IN

    THREE-TERMINAL LINES

    TABLE VIIISIMULATIONRESULTS FOREVALUATING THEPROPOSED METHOD INPOWER

    SWING CONDITIONS

    (at 66% of the length of line AB) and F3 (at 33% of the length

    of line BD). As considered in Table VII, the results show the

    efficiency of the proposed algorithm in this case.

    3) Power Swings:From the reliability point of view, the dis-

    tance relays have two fundamental problems in the presence of

    power swings. The first problem is the possibility of detecting

    power swing as a fault, which causes the loss of security. For

    preventing these conditions, distance relays are equipped withthe power swing blocking (PSB) units, which blind the relay

    to see the faults while the power swing persists. This function,

    however, leads to the second problem, which is loss of de-

    pendability for the faults occurring during a power swing. The

    problem is considerable only for symmetrical or three-phase

    faults [25], since asymmetrical faults can be detected by other

    protective approaches, like applying the negative-sequence

    components. The proposed method is, however, immune to

    the power swing conditions. According to [22], power swing

    can be created in Fig. 10 by applying a three-phase fault at

    bus A and removing the fault before the generator loses

    synchronism. The second cited problem is investigated by

    applying three-phase faults at points and (defined in

    Subsection B.2), where the results are presented in Table VIII.

  • 7/25/2019 Transmission-Line Protection a Direction

    8/10

    962 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

    TABLE IXSIMULATIONRESULTS FOREVALUATING THEPROPOSED METHOD INSERIES-COMPENSATEDLINES

    Fig. 11. Experimental prototype setup.

    4) Series-Compensated Lines: Compensation of transmis-sion lines by series capacitors imposes some significant effects

    on both directionality and reach of distance relays. The details

    are out of the scope of this paper and can be found in [26] and

    [27]. These effects become more severe in double-circuit se-

    ries-compensated lines. In Fig. 10, the source -connected line

    is removed and thedouble-circuitline AB is compensated by the

    degrees of 70%.

    The performance of relays and is tested for the faults

    at points and , where the results are given in Table IX.

    With protection of series-compensated lines, the location of the

    fault hasa key role, since the well-known phenomena of voltage

    and current inversions are affected by the fault location. Forthe sake of briefness, these phenomena are not investigated fur-

    ther. However, they are considered in Table IX. The presence of

    metaloxide varistors (MOVs) is also considered in this table.

    As shown, the presence of two capacitors in the path of reverse

    faults at point , in some situations, makes the direction de-

    tected by relays and inversed. However, since this inver-

    sion occurs for both relays, it does not impact the fault detection

    criterion used by the proposed method. It should be noted that

    this condition is only present in double-circuit series-compen-

    sated lines. Our extensive studies show that this inversion is not

    present in single-circuit series-compensated lines.

    It is remarkable that, in comparison with Fig. 2, the output of

    the averaging filter in series-compensated lines is equal to that of

    the zero-state response of the second-order circuit composed by

    Fig. 12. Experimental results of an SLG fault on phase A: (a) three-phase volt-ages, (b) three-phase currents at the relaying point, (c) averages of voltage andcurrent of the faulty phase, (d) output of the proposed method in simulation, (e)experimental averages of voltage and current computed by the relay, and (f) theexperimental result of the fault direction by the relay.

    the series capacitor and the line series impedance which consists

    of subsynchronous oscillations.

    V. EXPERIMENTALRESULTS

    The proposed method is tested, also, on an experimental

    prototype setup, which is depicted in Fig. 11. The relay is de-

    signed using an AVR microcontroller (ATMEGA32A). In order

    to make the laboratory tests compatible with the real world,

    the real voltage and current signals saved by a fault recorder

  • 7/25/2019 Transmission-Line Protection a Direction

    9/10

    HASHEMIet al.: TRANSMISSION-LINE PROTECTION 963

    Fig. 13. Experimental results of an SLG fault on phase C: (a) three phase volt-ages, (b) three-phase currents at the relaying point, (c) averages of voltage andcurrent of the faulty phase, (d) output of the proposed method in simulation,(e) experimental averages of voltage and current computed by the relay, (f) andexperimental result of the fault direction by the relay.

    TABLE XPARAMETERS OF THESYSTEMI

    have been used. These data include three-phase voltages and

    currents measured at the relaying point in the substation of one

    side of the line. These voltages and currents are saved into a

    personal computer and played back as the inputs of the relay.

    Considering restrictions in the space of this paper, only the

    results of two single-phase-to-ground (SLG) faults are pre-

    sented here. All faults are internal and, therefore, the protective

    relays of the line had to trip the line. Fig. 12 shows the result

    of an SLG fault on phase A. The voltages and currents of three

    phases, which are acquired by the fault recorder, are depicted

    in Fig. 12(a) and (b), respectively.

    The averages of voltage and current of phase A, which

    are used for the detection of fault direction, are depicted in

    Fig. 12(c). The output of the proposed method, which is pro-

    vided by simulation, is represented in Fig. 12(d). In thisfigure,

    the fault direction signal is 0, where there is no fault or there

    is a reverse fault. As soon as a forward fault is detected by the

    relay, this signal becomes 1. The results of the experimental test

    are shown in Fig. 12(e) and (f), where the relay has detected

    the fault direction within less than a quarter of a cycle after the

    fault inception.

    Another experimental test is carried out for an SLG fault on

    phase C, where the obtained results are shown in Fig. 13.

    VI. CONCLUSION

    This paper presents a high-speed directional comparison pro-

    tective scheme for transmission lines, using the average value

    of superimposed components. Extensive simulation studies are

    performed to evaluate the proposed method in different oper-

    ating conditions, including double-circuit lines, three terminal

    lines, power swing conditions, and series-compensated lines.

    The impact of important parameters, such as fault resistance,fault location, fault inception angle, and noise-polluted fault sig-

    nals on the protection systems are also considered in evaluating

    the proposed method. The obtained simulation results, in addi-

    tion to the experimental results, show that the proposed method

    is competent for being applied to line protection.

    REFERENCES

    [1] A. G. Phadke and J. S. Thorp, Com puter Relaying for Po wer Systems,2nd ed. Hoboken, NJ: Wiley, 2009.

    [2] A. T. Johns and S. K. Salman, Digital Protection for Power Systems.London, U.K.: Peregrinus, 1995.

    [3] M. Vitins, A fundamental concept for high speed relaying, IEEE

    Trans. Power App. Syst, vol. PAS-100, no. 1, pp. 163173, Jan. 1981.[4] D. W. P. Thomas, M. S. Jones, and C. Christopoulos, Phase selectionbased on superimposed components, inProc. Inst. Eng. Technol. Gen.Transm. Distrib., May 1996, vol. 143, no. 3, pp. 10111018.

    [5] X. Dong, Y. Ge, and J. He, Surge impedance relay, IEEE Trans.Power Del., vol. 20, no. 2, pt. 2, pp. 12471256, Apr. 2005.

    [6] C. Aguilera, E. Ordua, and G. Ratt, Directional travelingWave-protection based on slope change analysis, IEEE Trans. Power Del.,vol. 22, no. 4, pp. 20252033, Oct. 2007.

    [7] E. Vzquez, J. Castruita, O. L. Chacn, and A. Conde, A new ap-proach traveling-wave distance protectionPart I: Algorithm, IEEETrans. Power Del., vol. 22, no. 2, pp. 795800, Apr. 2007.

    [8] P. Jafarian and M. Sanaye-Pasand, A traveling-wave-based protectiontechnique using wavelet/PCA analysis,IEEE Trans. Power Del., vol.25, no. 2, pp. 588599, Apr. 2010.

    [9] A. Sharafi, M. Sanaye-Pasand, and P. Jafarian, Ultra-high-speed pro-tection of parallel transmission lines using current travelling waves,

    Inst. Eng. Technol. Gen. Transm. Distrib., vol. 5, no. 6, pp. 656666,2011.

    [10] C. Xianghui, Z. Xiangjun, M. Hongjiang, L. Zewen, L. Ling, and D.Feng, Rogowski sensor for power grid traveling wave based fault lo-cation, inProc. Inst. Eng. Technol. 9th Int. Conf. Develop. Power Syst

    Protect., Glasgow, U.K., Mar. 2008, pp. 438443.[11] P. Jafarian and M. Sanaye-Pasand, High-speed superimposed-based

    protection of series-compensated transmission lines, Inst. Eng.Technol. Gen. Transm. Distrib., vol. 5, no. 12, pp. 12901300, 2011.

    [12] G. Ziegler, Numerical Distance Protection; Principles and Applica-tions. Erlangen, Germany: Publicis, 2006.

    [13] C. Dzienis, M. Kereit, J. Blumschein, and M. Claus, An experi-mental analysis of high-speed-distance protection, inProc. Int. Symp.

    Modern Electric Power Syst., Poland, 2010, pp. 18.[14] Z. Li, X. Lin, H. Weng, and Z. Bo, Efforts on improving the per-

    formance of superimposed-based distance protection, IEEE Trans.

    Power Del., vol. 27, no. 1, pp. 186194, Jan. 2012.[15] G. Ziegler, Numerical Differential Protection. Erlangen, Germany:

    Publicis, 2005.

  • 7/25/2019 Transmission-Line Protection a Direction

    10/10

    964 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

    [16] M. R. D. Zadeh, T. S. Sidhu, and A. Klimek, Implementation andtesting of directional comparison bus protection based on IEC61850process bus, IEEE Trans. Power Del., vol. 26, no. 3, pp. 15301537,Jul. 2011.

    [17] J. Tan, D. Tholomier, G. Bin, and W. Hua, Sensitivity and stability ofsuperimposed component based directional comparison protection, in

    Proc. Ca n. Co nf. Elect. C omput. Eng., 2007, pp. 280283.[18] H. Gao and P. A. Crossley, Design and evaluation of a directional

    algorithm for transmission-line protection based on positive sequencefault components, in Proc. Inst. Elect. Eng., Gen. Transm. Distrib.,Nov. 2006, vol. 153, no. 6, pp. 711718.

    [19] D. Tholomier, S. Richards,and A. Apostolov, Whichone is better-linedifferential or directional comparison?, in Proc. 9th Int. Conf. De-velop. Power Syst. Protect. Inst. Eng. Technol., Montreal, QC, Canada,2008, pp. 8691.

    [20] A. P. Apostolov, D. Tholomier, and S. H. Richards, Superimposedcomponents based sub-cycle protection of transmission lines, in Proc.

    IEEE Power Eng. Soc. Power Syst. Conf. Expo., New York, 2004, pp.592597.

    [21] H. Saadat, Pow er Sys tem Analys is. New York: McGraw-Hill, 1999.[22] Power Syst. Relaying Comm., EMTP reference models for transmis-

    sion line relay testing, Final, Tech. Rep., 2005. [Online]. Available:www.pes-psrc.org

    [23] H. Seyedi and L. Behroozi, New distance relay compensation al-gorithm for double-circuit transmission line protection, Inst. Eng.

    Technol. Gen. Transm. Distrib., vol. 5, no. 1, pp. 10111018, 2011.[24] S. H. Horowitz and A. G. Phadke, Power System Relaying, 3rd ed.

    Hoboken, NJ: Wiley, 2008.[25] C. Pang and M. Kezunovic, Fast distance relay scheme for detecting

    symmetrical fault during power swing,IEEE Trans. Power Del., vol.25, no. 4, pp. 22052212, Oct. 2010.

    [26] P. M. Anderson, Power System P rotection. New York: IEEE, 1999.[27] P. Jena and A. K. Pradhan, A positive-sequence directional relaying

    algorithm for series-compensated line,IEEE Trans. Power Del., vol.24, no. 4, pp. 22882298, Oct. 2010.

    S. M. Hashemi received the B.Sc. degree in elec-trical engineering from the Bu-Ali Sina University,Hamedan, Iran, and is currently pursuing the M.Sc.degree in electrical engineering at the University ofTabriz, Tabriz, Iran.

    His research interests include power systemprotection,flexible ac transmission systems, HVDC,power system operation, and electricity markets.

    M. Tarafdar Hagh(S98M06) received the M.Sc.(Hons.) andPh.D.degrees in power engineering fromthe University of Tabriz, Tabriz, Iran, in 1992 and2000, respectively.

    He has been with the Faculty of Electrical andComputer Engineering, University of Tabriz, since2000, where he is currently a Professor. He haspublished more than 150 papers in power systemand power electronics-related topics. His interesttopics include power system operation, flexible actransmission systems,and power quality.

    H. Seyediwas born in Iran in 1979. He received theB.Sc., M.Sc., and Ph.D. degrees in electrical engi-neering from the University of Tehran, Tehran, Iran,in 2001, 2003, and 2008, respectively,.

    Currently, he is with the faculty of Electrical andComputer Engineering, University of Tabriz, Tabriz,Iran. His areas of interest include digital protectionof power systems and power system transients