TRANSIENT HARMONIC ANALYSIS OF TRANSFORMER A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Bachelor of Technology In Electrical Engineering By Nikhil Mallikarjun(10502040) Devdutta Sahoo(10502044) Department of Electrical Engineering National Institute of Technology Rourkela 2009

Upload: hoangnga

Post on 11-Feb-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

TRANSIENT HARMONIC ANALYSIS OF TRANSFORMER

A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE

REQUIREMENTS FOR THE DEGREE OF

Bachelor of Technology

In

Electrical Engineering

By

Nikhil Mallikarjun(10502040)

Devdutta Sahoo(10502044)

Department of Electrical Engineering

National Institute of Technology

Rourkela

2009

Page 2: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

TRANSIENT HARMONIC ANALYSIS OF TRANSFORMER

A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE

REQUIREMENTS FOR THE DEGREE OF

Bachelor of Technology

In

Electrical Engineering

By

Nikhil Mallikarjun(10502040)

Devdutta Sahoo(10502044)

Under the Guidance of

Prof. Sharmili Das

Department of Electrical Engineering

National Institute of Technology

Rourkela

2009

Page 3: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

National Institute of Technology

Rourkela

Certificate

This is to certify that the thesis entitled “TRANSIENT HARMONIC ANALYSIS

OF TRANSFORMER” submitted by Shri Nikhil Mallikarjun and Shri Devdutta Sahoo in partial

fulfillment of the requirements for the award of Bachelor of Technology Degree in Electrical

Engineering at the National Institute of Technology, Rourkela (Deemed University) is an

authentic work carried out by them under my supervision and guidance.

To the best of my knowledge, the matter embodied in the thesis has not been

submitted to any other University/Institute for the award of any Degree or Diploma.

Date : Prof. Sharmili Das

Place: Dept. of Electrical Engg.

National Institute of technology

Rourkela-769008

Page 4: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

ACKNOWLEDGEMENT

We would like to articulate our deep gratitude to our project guide Prof. Sharmili Das

who has always been our motivation for carrying out the project. We wish to extend our sincere

thanks to Prof. B.D. Subudhi, Head of our Department, for his invaluable guidance.

It is our pleasure to refer “Microsoft Word” exclusive of which the compilation of this

report would have been impossible. Also it would not have been possible to complete the project

without the simulation software”MATLAB”.

A project of this nature could never have been attempted with our reference to and

inspiration from the works of others whose details are mentioned in references section. We

acknowledge our indebtedness to all of them. Last but not the least, our sincere thanks to all our

friends who have patiently extended all sorts of help for accomplishing this undertaking.

Nikhil Mallikarjun

Devadutta Sahoo

Page 5: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

ABSTRACT

The project focuses on the harmonic analysis of transformer during the switching transient

period. Analysis is made using Discrete Time Fourier Transforms (DTFT). Measuring

fundamental and second harmonics of differential current, an algorithm based on the Discrete

Fourier Transform and an amplitude estimator are used to simulate and list various harmonic

components of current and flux. Generalized functions for describing the relationships between

resultant flux and harmonic components are derived. This is important to find these relations for

further use in detecting non-linearity and elimination of harmonic components.

Page 6: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

PROJECT DEFINITION:

This project will focus on carrying a transient analysis of a transformer. The components of

current and magnetizing flux are derived and the hysteresis loop is to be plotted. The current and

flux relations with respect to time are simulated for different conditions of phase angle and

Residual Flux. Generalized functions for describing the relationships between resultant flux and

harmonic components were derived.

AIMS:

• Determine the relationship between Magnetizing Field (H) and harmonic components of flux.

• Determine the magnitude and relative percentages of the different harmonic components of

current in a single-phase transformer in variation with respect to the phase angle (switching

constant) and Residual Flux.

• Simulate the harmonic distribution and hysteresis relations derived from above.

Page 7: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

INTRODUCTION

A literature survey to document the transient behavior of CT's behavior was conducted.

Harmonic analysis of current transformer is made using Discrete Time Fourier Transforms

(DTFT). Measuring fundamental and second harmonics of differential current, an algorithm

based on the Discrete Fourier Transform and an amplitude estimator which uses 20 samples in

order to find the magnitudes of harmonics are used. Magnitudes of harmonic frequencies are

obtained by discrete Fourier transform, using a sliding window of one cycle.

Harmonic analysis shows high even harmonics in current. Even harmonics are the characteristic

harmonics of transformer saturation and they are used to restrain the operation of differential

protection of the transformer during energizing. Even harmonics are not common in power

systems and basically depict the asymmetry between the positive and negative half-cycle of

waveform.

Transients and Switching transients

Transients: It means any sudden change in the circuit, i.e. either closing the circuit or opening the

circuits. The transients are two types in power transformer, switching transients and over-voltage

transients. Due to transients the behavior of a system has got two components, steady state and

transient. Sometimes the initial transient of a system has a very high value, it is known as inrush.

Page 8: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Transients in a 1-φ R-L circuit in switching operation

The equation of the given circuit is

Ri + L (di/dt) = Vmax (sin(wt + α)) (1)

I(t) = Imax (sin(wt + α- φ)) + A e-(R/L)t

(2)

& A = -I max (sin(α- φ)) (3)

φ = atan(wL/R)

Imax = Vm/ (R2

+ (w L) 2

)1/2

And If α = φ;

There will be no transient; the current has got only steady part.

Case 1:

Initial inrush will be minimum,

When switching angle = power factor angle

And inrush will be maximum, when α - φ = 90

II Switching of a 1-φ Transformer:

Neglecting the leakage reactance of the primary and secondary & assuming the no-load, the

transformer primary side emf equation can be written as: -

Vs = rpip + Ip(dip/dt) +es’; (4)

ep -> Primary induced voltage

es -> Secondary induced voltage

es’ -> equivalent Secondary induced voltage

ep = -(dλ/dt)

λ = npφm; (5)

φm = f(ip);

Solving eqn (4) & (5), the behavior of current transient of transformer can be predicted, but for

that φm has to be determined correctly. φm is dependent of the nature of the core, since it is non-

linear in nature, it introduces certain complexity. So overall eqn (4) & (5) and the non-linear

nature of transformer core determines the initial transient or inrush nature.

Page 9: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Introduction

Transformer exhibit inrush phenomenon during initial energization.

Due to flux symmetry or temporary over fluxing, which gives rise to high current at the initial

energization of a transformer core. The saturation of one or more cores results in high magnitude

of current.

Being high magnitude of current, the transformer energizing current is full of harmonics.

Both even and odd harmonics occur during energization.

They can excite system resonance resulting in dynamic over voltage.

Factors:

Point on voltage wave switching

Magnitude and polarity of remnant flux

Total resistance of primary winding circuit

Inductance of the air core

Geometry of the transformer core

Maximum flux carrying capability of the core material

Impacts

Large inrush current causes the voltage dips in the supply system. Which leads to mal

operation of sensitive electronics equipment and interrupt manufacturing process.

It will be highly unbalanced among 3-φ, unbalance caused by inrush current could easily

result in motor tripping.

The waveform of an inrush current is far from sinusoidal containing a lot of high

frequency component; such harmonics excite resonances in the system causing

significant magnification of voltage or currents at various locations in the system which

can damage sensitive electronics equipment, surge suppressor over heating, capacitor

fuse blowing and failure.

The dc component of the inrush current can lead to oscillatory torque in motors resulting

in increase in motor vibration and aging.

Page 10: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Mitigation

Over sizing fuse

Series resistance insertion

Ground resistor insertion

Controlled closing or controlled energization or point on voltage wave switching.

Soft starting

Inrush analysis can be carried out in four steps these are

Identification

Determination and discrimination

Calculation

Mitigation

This current has been a problem in the design and performance of differential protective relays

used in power transmission and distribution system. Power transformers play an important role in

power system, so in order to ensure the safe operation of these transformers.

Calculation

Inrush magnetizing current and its waveform is calculated ->

Numerical analysis using

MATLAB

Transformer equivalent model can be represented as

Ri + [L (i) + LL](di/dt) = (2)1/2

Emax (sinwt);

The magnitude and peak of inrush current waveform is dependent

On instant of switching

Remnant flux density

For a single phase transformer, equation can be written as

Ri + L di +dλm/dt = Emax sin(wt);

Neglecting L

Ri +dλm/dt = Emax sin(wt);

λm = Nφm

Page 11: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

φm = f(im)

dφm = [(Emax sin(wt) – Ri)dt]/N;

dBm =d(φm)A;

Bm = Bm + dBm; as Hm = F(Bm)

Im = (Hml)/N;

So, the value of current can be determined by solving above equation.

Generally an inrush current transient is 10 to 20 times the rated value and it lasts for 20 to 3600

cycles.

Without considering Residual Flux

Considering Residual Flux

Transformer Rating -> 150 MVA, 500 KV

ASSUMPTION

i> Residual flux is generally in the range between 20 to 70%

ii> Flux Pattern is like one near zero and other two +/- values.

This method is applicable to both 1φ and 3φ transformer circuit.

The basic assumptions behind induced flux linkage (prospective flux) are the integral of the

applied voltage and it lags it by 90.

As given by the equation:

Ri + L (di/dt) +dλm/dt = Emax sin(wt)dt;

Neglecting the drops

Or, ∫ φm dt = 1/N∫ Emax sin(wt)dt;

Or, φt = φr + 1/N∫ Emax sin(wt)dt;

Page 12: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

If residual flux left in the core, then flux builds up from that level and sinusoidal flux wave

symmetry will be dc offset by the residual flux amount. In order to limit such asymmetry, at the

instant of energization the residual flux should be equal to the applied flux (i.e. prospective flux).

So that flux wave follows the normal pattern without any offset.

Case 1: Single phase transformer

As given in the equation & the figure given above, without residual flux, flux will maintain

steady state if it starts from zero.

i.e. if φt = 0.0, at (t=0 & φr=0) -> steady state symmetry (no inrush)

Here α = 90.

In case of loaded circuit optimal instant of switiching is

Page 13: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

α = θ -> w.r.t. flux wave

α = 90 + θ -> w.r.t. voltage wave

Case 2: Single phase transformer with residual flux

As given previously the reason behind magnetic asymmetry which resulted either due to residual

flux or point on switching voltage wave. Point on voltage switching means the different instant

on voltage wave at which the transformer is re-energized, depending on that instant flux builds

up from a particular dc offset level.

i.e. minimum, when Vs(t) = Emax -> α = 90;

& maximum, when Vs(t) = 0.0 -> α = 0 or α = 180 and φt = 2φmax or -2φmax;

For the remnant flux case, when transformer is re-energized, the flux builds up from the previous

remnant value and the maximum value of remnant to which the flux builds up depends upon the

instant of switching.

At, Worst switching -> φt = φr + 2φmax;

This asymmetry can be nullified if transformer is switched on when;

The applied flux value is same as residual flux

i.e. α = sin-1

(φr/φmax) -> w.r.t. flux wave

α = 90 + sin-1

(φr/φmax) -> w.r.t. voltage wave

Where

α -> Switching instant optimal

θ -> power factor angle.

Page 14: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Simulation

MATLAB MODEL

Continuous

pow ergui

iexc2

iexc2

iexc1

iexc1

iexc

iexc

i+

-

i1 2

Tr1

t

T

Scope5

Scope4

Scope2Scope1

Scope

4

Multimeter

Demux

Clock

CB2

CB1

N

A

B

C

Source1

N

A

B

C

Source

<>

Page 15: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.0

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-100

0

100

200

300

400

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

20

40

60

80

100

Frequency (Hz)

DC component = 56.69 , THD= 246.07%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

5

10

15

20

25

30

35

Frequency (Hz)

DC component = 18.64 , THD= 261.56%

Mag

Page 16: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-50

0

50

100

150

200

250

300

350

Flux vs. Current

-50 0 50 100 150 200 250 300 350-1000

-500

0

500

1000

1500

2000

Page 17: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 18: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.05

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-100

0

100

200

300

400

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

20

40

60

80

100

120

Frequency (Hz)

DC component = 63.68 , THD= 241.67%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

Frequency (Hz)

DC component = 19.88 , THD= 262.87%

Mag

Page 19: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-50

0

50

100

150

200

250

300

350

Flux vs. Current

-50 0 50 100 150 200 250 300 350-1000

-500

0

500

1000

1500

2000

Page 20: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 21: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.1

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-100

0

100

200

300

400

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

20

40

60

80

100

120

140

Frequency (Hz)

DC component = 70.78 , THD= 237.40%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

Frequency (Hz)

DC component = 21.06 , THD= 263.80%

Mag

Page 22: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-50

0

50

100

150

200

250

300

350

400

Flux vs. Current

-50 0 50 100 150 200 250 300 350 400-1000

-500

0

500

1000

1500

2000

Page 23: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 24: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.15

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-100

0

100

200

300

400

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

Frequency (Hz)

DC component = 78.07 , THD= 233.12%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

Frequency (Hz)

DC component = 22.21 , THD= 264.28%

Mag

Page 25: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-50

0

50

100

150

200

250

300

350

400

Flux vs. Current

-50 0 50 100 150 200 250 300 350 400-1000

-500

0

500

1000

1500

2000

Page 26: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 27: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.2

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

Frequency (Hz)

DC component = 85.49 , THD= 228.95%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

Frequency (Hz)

DC component = 23.31 , THD= 264.52%

Mag

Page 28: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-50

0

50

100

150

200

250

300

350

400

450

Flux vs. Current

-50 0 50 100 150 200 250 300 350 400 450-1000

-500

0

500

1000

1500

2000

Page 29: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 30: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.3

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

Frequency (Hz)

DC component = 100.5 , THD= 221.27%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

Frequency (Hz)

DC component = 25.35 , THD= 264.77%

Mag

Page 31: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

Flux vs. Current

-100 0 100 200 300 400 500-1000

-500

0

500

1000

1500

2000

Page 32: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 33: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.35

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

Frequency (Hz)

DC component = 108.1 , THD= 217.72%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

Frequency (Hz)

DC component = 26.28 , THD= 264.85%

Mag

Page 34: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

Flux vs. Current

-100 0 100 200 300 400 500-1000

-500

0

500

1000

1500

2000

Page 35: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 36: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.4

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

Frequency (Hz)

DC component = 115.8 , THD= 214.17%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

Frequency (Hz)

DC component = 27.2 , THD= 264.70%

Mag

Page 37: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

Flux vs. Current

-100 0 100 200 300 400 500-1000

-500

0

500

1000

1500

2000

Page 38: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 39: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.45

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

Frequency (Hz)

DC component = 123.7 , THD= 210.73%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

Frequency (Hz)

DC component = 28.08 , THD= 264.49%

Mag

Page 40: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

Flux vs. Current

-100 0 100 200 300 400 500 600-1000

-500

0

500

1000

1500

2000

Page 41: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 42: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.5

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

Frequency (Hz)

DC component = 131.6 , THD= 207.36%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 28.92 , THD= 264.20%

Mag

Page 43: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

Flux vs. Current

-100 0 100 200 300 400 500 600-1000

-500

0

500

1000

1500

2000

Page 44: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 45: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.55

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

Frequency (Hz)

DC component = 139.6 , THD= 204.06%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 29.74 , THD= 263.82%

Mag

Page 46: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

Flux vs. Current

-100 0 100 200 300 400 500 600-1000

-500

0

500

1000

1500

2000

Page 47: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 48: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.6

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

Frequency (Hz)

DC component = 147.5 , THD= 200.99%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-50

0

50

100

150

200

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 30.5 , THD= 263.63%

Mag

Page 49: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

Flux vs. Current

-100 0 100 200 300 400 500 600-1000

-500

0

500

1000

1500

2000

Page 50: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

Page 51: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.7

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-200

0

200

400

600

800

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

300

Frequency (Hz)

DC component = 163.6 , THD= 194.97%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-100

0

100

200

300

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 31.93 , THD= 263.04%

Mag

Page 52: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

700

Flux vs. Current

-100 0 100 200 300 400 500 600 700-1000

-500

0

500

1000

1500

2000

2500

Page 53: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

2500

Page 54: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.75

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-200

0

200

400

600

800

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

300

Frequency (Hz)

DC component = 171.9 , THD= 191.97%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-100

0

100

200

300

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 32.61 , THD= 262.64%

Mag

Page 55: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

700

Flux vs. Current

-100 0 100 200 300 400 500 600 700-1000

-500

0

500

1000

1500

2000

2500

Page 56: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

2500

Page 57: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Phase Angle = 0, Residual Flux = 0.8

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048-200

0

200

400

600

800

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

50

100

150

200

250

300

Frequency (Hz)

DC component = 180 , THD= 189.08%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-100

0

100

200

300

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

10

20

30

40

50

60

Frequency (Hz)

DC component = 33.25 , THD= 262.29%

Mag

Page 58: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Current vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-100

0

100

200

300

400

500

600

700

Flux vs. Current

-100 0 100 200 300 400 500 600 700-1000

-500

0

500

1000

1500

2000

2500

Page 59: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Flux vs. Time

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-1000

-500

0

500

1000

1500

2000

2500

Page 60: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

0.034 0.036 0.038 0.04 0.042 0.044 0.046 0.048 0.05-10

-5

0

5

10

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

0.5

1

1.5

Frequency (Hz)

Fundamental (60Hz) = 6.241 , THD= 24.35%

Mag

0.05 0.052 0.054 0.056 0.058 0.06 0.062 0.064 0.066-10

-5

0

5

10

Time (s)

FFT window: 1 of 9 cycles of selected signal

0 200 400 600 800 10000

0.5

1

1.5

Frequency (Hz)

Fundamental (60Hz) = 6.621 , THD= 24.73%

Mag

Phase Angle = 90;̊ Residual Flux = 0.0

Page 61: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-6

-4

-2

0

2

4

6

-6 -4 -2 0 2 4 6-6

-4

-2

0

2

4

6

Current vs. Time

Flux vs. Current

Page 62: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16-6

-4

-2

0

2

4

6

Flux vs. Time

Page 63: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Tabulation

ɸr DC offset

(0 Hz)

Fund h1 (60

Hz)

h2 (120 Hz) h3 (180 Hz)

0.0 56.69 104.14 75.23 47.26

0.05 63.68 116.36 83.00 50.45

0.10 70.78 128.67 90.49 53.09

0.15 78.07 141.11 97.69 55.13

0.20 85.49 153.61 104.55 56.59

0.30 100.52 178.52 117.20 58.00

0.35 108.10 190.87 122.97 58.01

0.40 115.84 203.27 128.35 57.48

0.45 123.65 215.60 133.32 56.47

0.50 131.56 227.90 137.86 55.00

0.55 139.58 240.14 141.96 53.07

0.60 147.51 252.13 145.68 50.91

0.70 163.63 275.82 151.72 45.43

0.75 171.85 287.52 153.99 42.10

0.80 180.04 298.96 155.81 38.59

Page 64: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Calculation

Resultant Flux vs. DC offset (0 Hz)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.850

100

150

200

y = 2.9e+004*x10 - 1.2e+005*x9 + 2e+005*x8 - 1.7e+005*x7 +

8.3e+004*x6 - 2.1e+004*x5 + 2e+003*x4 + 1.4e+002*x3 - 7.6*x2 +

1.4e+002*x + 57

data 1

10th degree

Page 65: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Resultant Flux vs. Fundamental Harmonic (h1 – 60 Hz)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8100

120

140

160

180

200

220

240

260

280

300

y = 4.1e+004*x10 - 1.7e+005*x9 + 2.8e+005*x8 - 2.5e+005*x7 +

1.3e+005*x6 - 3.6e+004*x5 + 5.4e+003*x4 - 3.2e+002*x3 + 21*x2 +

2.4e+002*x + 1e+002

data 1

10th degree

Page 66: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Resultant Flux vs. 2nd

Harmonic (h2 – 120 Hz)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.870

80

90

100

110

120

130

140

150

160

y = - 2.1e+004*x10 + 9.4e+004*x9 - 1.7e+005*x8 + 1.8e+005*x7 -

1.1e+005*x6 + 4e+004*x5 - 9.1e+003*x4 + 1.1e+003*x3 -

1.2e+002*x2 + 1.6e+002*x + 75

data 1

10th degree

Page 67: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Resultant Flux vs. 3rd

Harmonic (h3 – 180 Hz)

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.835

40

45

50

55

60

y = - 4.7e+004*x10 + 2e+005*x9 - 3.4e+005*x8 + 3.2e+005*x7 -

1.8e+005*x6 + 5.8e+004*x5 - 1.1e+004*x4 + 1e+003*x3 -

1.6e+002*x2 + 70*x + 47

data 1

10th degree

Page 68: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Results:

The Generalized Functions where calculated to be:

Resultant Flux vs. DC offset (0 Hz) -> 2.9e + 004*x10

– 1.2e + 005*x9 + 2e + 005*x

8 – 1.7e +

005*x7

+ 8.3e + 004*x6

– 2.1e + 004*x5

+ 2e + 003*x4

– 1.4e + 002*x3 – 7.6*x

2 + 1.4e + 002*x

+ 57

Resultant Flux vs. Fundamental Harmonic (h1 – 60 Hz) -> 4.1e + 004*x10

– 1.7e + 005*x9 +

2.8e + 005*x8 – 2.5e + 0.005*x

7 + 1.3e + 005*x

6 – 3.6e + 0.004*x

5 + 5.4e + 003*x

4 – 3.2e +

002*x3 + 21*x

2 + 2.4e + 002*x

+ 1e + 002

Resultant Flux vs. 2nd

Harmonic (h2 – 120 Hz) -> -2.1e + 004*x10

+ 9.4e + 004*x9 – 1.7e +

005*x8 + 1.8e + 005*x

7 + 1.1e + 005*x

6 + 4e + 004*x

5 – 9.1e + 003*x

4 + 1.1e + 003*x

3 – 1.2e +

002*x2

+ 1.6e + 002*x + 75

Resultant Flux vs. 3rd

Harmonic (h3 – 180 Hz) -> -4.7e + 004*x10

+ 2e + 005*x9 – 3.4e +

005*x8 + 3.2e + 005*x

7 - 1.8e + 005*x

6 + 5.8e + 004*x

5 – 1.1e + 004*x

4 + 1e + 003*x

3 – 1.6e +

002*x2

+ 70*x + 47

Exponential Form:

Resultant Flux vs. DC offset (0 Hz) -> 1.1e5x

- 11e4x

+46e3x

- 1.3e002

e2x

+ 3e002

ex – 1.5e

002

Resultant Flux vs. Fundamental Harmonic (h1 – 60 Hz) -> 1.4e5x

– 17e4x

+ 92e3x

– 2.9e002

e2x

+ 6.1e002

ex – 2.9e

002

Resultant Flux vs. 2nd

Harmonic (h2 – 120 Hz) -> 3.3e5x

- 39e4x

+ 1.9e002

e3x

- 5 e002

e2x

+ 7.2

e002

ex - 3 e

002

Resultant Flux vs. 3rd

Harmonic (h3 – 180 Hz) -> 9.3e5x

– 95e4x

+ 4 e002

e3x

– 8.5 e002

e2x

+ 9.2

e002

ex - 3.3 e

002

Page 69: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

Conclusion

The study of inrush currents and its effects on harmonics was carried out in detail. The harmonic

distortion was simulated using MATLAB for various residual fluxes; the relationships for

characteristics of current and flux were plotted over time. Generalized functions for describing

the relationships between resultant flux and harmonic components were derived.

Future Plans:

Harmonic components are identified to get the non-linearity of the core, this can be used in the

elimination of the harmonics.

Page 70: TRANSIENT HARMONIC ANALYSIS OF TRANSFORMERethesis.nitrkl.ac.in/1334/1/final.pdf · transient harmonic analysis of transformer a thesis submitted in partial fulfillment of the requirements

REFERENCES

[1] Transformer Engineering: Design and Practice, S.V.Kulkarni and S.A.Khaparde, Indian

Institute of Technology, Bombay (Mumbai), India. 2004 by Marcel Dekker, Inc.

[2] Influence of design and operating practices on excitation on generator step-up transformer.

G.W. Alexander, S. L. Corbin, and McNutt. IEEE Transactions on Power Apparatus and

Systems, Vol. PAS-85, No. 8, August 1966, pp. 901–909.

[3] Tian Mingxing School of Information and Electrical Engineering, Li Qunfeng – R & D

Department – Harmonic analysis of a exciter’s exciting current on a brushless AC Generator

with a rotary rectifier.

[4] Harmonic Power Flow Determination using FFT, Timothy A. George, IEEE

[5] Measurement and characterization of Harmonic and high frequency distribution in an

industrial load.

[6] C-L Huang C. E. Lin, C.L Cheng and J.C. Yeh. Investigation of magnetization inrush current

in transformer. (i) Numerical Simulation. IEEE Transactions on Power Delivery, 8(1):246-254,

Jan 1993

[7] C-L Huang C. E. Lin, C.L Cheng and J.C. Yeh. Investigation of magnetization inrush current

in transformer. (ii) Harmonic Analysis. IEEE Transactions on Power Delivery, 8(1):256-263, Jan

1993