transformer protection2009 9-2

Upload: muazaminu1422

Post on 03-Apr-2018

220 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/28/2019 Transformer Protection2009 9-2

    1/94

    Introduction The development of modern power systems has

    been reflected in the advances in transformerdesign. This has resulted in a wide range oftransformers with sizes ranging from a few kVA toseveral hundred MVA being available for use in a

    wide variety of applications.

    The considerations for a transformer protectionpackage vary with the application and importanceof the transformers.

  • 7/28/2019 Transformer Protection2009 9-2

    2/94

    Introduction Small distribution transformers can be protected

    satisfactorily, from both technical and economicconsiderations, by the use of fuse or over current relay.

    This result in time-delayed protection. However, time-delayed fault clearance is unacceptable

    on larger power transformers, due to systemoperation/stability and cost

  • 7/28/2019 Transformer Protection2009 9-2

    3/94

    Introduction Transformer faults are generally classified into six

    categories: Winding and terminal faults

    Core faults

    Tank and transformer accessory faults

    On-load tap changer faults

    Abnormal operation conditions

    Sustained or uncleared external faults

  • 7/28/2019 Transformer Protection2009 9-2

    4/94

    Transformer faultsWinding fault

    A fault on transformer winding is controlled inmagnitude by the following factor:

    Source impedance

    Neutral earthing impedance

    Transformer leakage reactance

    Fault voltage

    Winding connection

  • 7/28/2019 Transformer Protection2009 9-2

    5/94

    Transformer faults Star-Connected Winding with Neutral Point Earthed

    through an impedance.

    The winding earth fault current depends on the earthingimpedance value and is also proportional to the distanceof the fault from neutral point, since the fault voltage

    will be directly proportional to this distance

  • 7/28/2019 Transformer Protection2009 9-2

    6/94

    Transformer faults

    Earth fault current in resistance-earth star winding

  • 7/28/2019 Transformer Protection2009 9-2

    7/94

    Transformer faults

    Earth fault current in solidly earthed starwinding

  • 7/28/2019 Transformer Protection2009 9-2

    8/94

    Transformer faultsPhase to Phase Fault

    Fault between phases with in transformerare relatively rare; if such a fault doesoccur it will give rise to a substantialcurrent comparable to earth fault

    currents.

  • 7/28/2019 Transformer Protection2009 9-2

    9/94

    Transformer faults Interturn faults

    In low voltage transformers, Interturn insulationbreakdown is unlikely to occur unless the mechanicalforce on winding due to external short circuits hascaused insulation degradation, or insulating oil hascaused contaminated by moisture.

    In high voltage transformers, connected to an

    overhead transmission system will be subjected to steepfronted impulse voltages, arising from lightning strikes,faults and switching operations, caused Interturnisolation breakdown.

  • 7/28/2019 Transformer Protection2009 9-2

    10/94

    Transformer faults Interturn faults

    A short circuit of a few turns of winding will give riseto a heavy fault current in the short-circuited loop, butthe terminal current will be small, because of high ratioof transformer between the whole winding and theshort-circuited turns.

  • 7/28/2019 Transformer Protection2009 9-2

    11/94

    Transformer faults Core faults

    A conducting bridge across the laminated structuresof the core can permit sufficient eddy-current to flow tocause serious overheating.

    The bolts that clamp the core together are alwaysinsulated to avoid this trouble. If any portion of the coreinsulation become defective, the resultant heating may

    reach a magnitude sufficient to damage the winding.

    The additional core loss, although causing severe localheating.

  • 7/28/2019 Transformer Protection2009 9-2

    12/94

    Transformer faultsTank faults

    Loss of oil through tank leaks willultimately produce a dangerous condition,either because of a reduction in windinginsulation or because of overheating on

    load due to the loss of cooling

  • 7/28/2019 Transformer Protection2009 9-2

    13/94

    Transformer faults External Applied Conditions

    Sources of abnormal stress in a

    transformer are: Overload

    System faults

    Over voltage

    Reduced system frequency

  • 7/28/2019 Transformer Protection2009 9-2

    14/94

    Transformer faults Overload

    Overload causes increased copper loss and a

    consequent temperature rise. System faults

    System short circuits produce a relatively

    intense rate of heating of the feeding

    transformers, the copper loss increasing inproportion to square of the per unit fault current.

  • 7/28/2019 Transformer Protection2009 9-2

    15/94

    Transformer faults

    Transformer

    reactance (%)

    Fault current

    (Multiple of rating

    Permitted fault

    duration

    (seconds)

    4 25 25 20 2

    6 16.6 2

    7 14.2 2

    The typical duration of external short-circuits that a

    transformer can sustain without damage if the current is

    limited only by the self-reactance is shown in table

  • 7/28/2019 Transformer Protection2009 9-2

    16/94

    Transformer faults Over voltage

    Transient surge voltages Transient overvoltages arise from faults, switching

    and lightning disturbances and are liable to causeinterturn faults.

    Power frequency overvoltagePower frequency overvoltage causes both an increase in

    stress on the insulation and a proportionate increase inthe working flux, this lead to a rapid temperature rise inthe bolts, destroying their insulation if the conditioncontinues.

  • 7/28/2019 Transformer Protection2009 9-2

    17/94

    Transformer faults Reduced system frequency

    Reduction of system frequency has an effect with regardto flux density, similar to that of overvoltage.

    If follows that a transformer can operate with somedegree of overvoltage with a corresponding increase infrequency, but operation must not be continued with ahigh voltage input and low frequency.

    Operation can not be sustained when the ratio of voltageto frequency with these quantities given values in per unitof their rated valued, exceeds unity by more than a smallamount, for instance if V/f = 1.1

  • 7/28/2019 Transformer Protection2009 9-2

    18/94

    Transformer faults Magnetizing inrush current

    The phenomenon of magnetizing inrush is a

    transient condition that occurs primarily when atransformer is energized.

    It is not a fault condition, and therefore transformerprotection must remain stable during the inrush

    transient.

  • 7/28/2019 Transformer Protection2009 9-2

    19/94

    Magnetizing inrush When a transformer is first energized, a transient

    magnetizing or exciting inrush current may flow. Thisinrush current, which appears as an internal fault tothe differentially connected relays, may reach

    instantaneous peaks of 8 to 30 times those for fullload.

  • 7/28/2019 Transformer Protection2009 9-2

    20/94

    The factors controlling the duration and

    magnitude of the magnetizing inrush The factors controlling the duration and magnitude of

    the magnetizing inrush are:

    Size and location of the transformer bank

    Size of the power system Resistance in the power system from the source to the

    transformer bank

    Type of iron used in the transformer core and itssaturation density

    Prior history, or residual flux level, of the bank

    How the bank is energized

  • 7/28/2019 Transformer Protection2009 9-2

    21/94

    Magnetizing inrush current

  • 7/28/2019 Transformer Protection2009 9-2

    22/94

    Transformer faults

    Magnetizing inrush current

    Under normal steady-state conditions the magnetizing currentassociated with the operation flux level is relative small

  • 7/28/2019 Transformer Protection2009 9-2

    23/94

    Transformer faults

    Magnetizing inrush currentHowever, if a transformer winding is energized at a voltage zero, with

    no remnant flux, the flux level during the first voltage cycle (2* normalflux) will result in core saturation and a high non-sinusoidalmagnetizing current waveform

    T f f lt

  • 7/28/2019 Transformer Protection2009 9-2

    24/94

    Transformer faults

    Magnetizing inrush current

    The energizing conditions that result in an offset current produce awaveform that is asymmetrical. Such a wave typically contains botheven and odd harmonics.

  • 7/28/2019 Transformer Protection2009 9-2

    25/94

    Transformer faults

    Harmonic content

    Componenttypical value

    DC55%

    2nd63%

    3rd26.8%

    4th5.1%

    5th4.1%

    6th3.7%

    7th2.4%

    Magnetizing inrush current

    Typical inrush currents contain substantial amounts of second and third

    harmonics and diminishing amounts of higher order.

  • 7/28/2019 Transformer Protection2009 9-2

    26/94

    Transformer faults

    Magnetizing inrush current

    This current is referred to as magnetizing inrush and maypersist for several cycles.

  • 7/28/2019 Transformer Protection2009 9-2

    27/94

    Transformer Protection

    The problems relatingto transformersrequire some means

    of protection. In thetable, summaries theproblems and thepossible form of

    protection that maybe used.

    Fault Type Protection Used

    Primary winding

    Phase-phase fault

    Differential;

    Overcurrent

    Primary winding

    Phase-earth fault

    Differential;

    Overcurrent

    Secondary windingPhase-phase fault

    Differential

    Secondary winding

    Phase-earth fault

    Differential;

    Restricted Earth

    Fault

    Interturn Fault Differential; Bucholz

    Core Fault Differential; Bucholz

    Tank Fault Differential,

    Bucholz; Tank-Earth

    Overfluxing Overfluxing

    Overheating Thermal

  • 7/28/2019 Transformer Protection2009 9-2

    28/94

    Transformer Protection Transformer over current protection

    Fuses: Fuses commonly protect small distributiontransformers typically up to ratings of 1 MVA at

    distribution voltages.The fuse must have a rating well above the maximumtransformer load current in order to withstand the shortduration overloads that may occur. Also, the fuses must

    withstand the magnetizing inrush currents drawn whenpower transformers are energized.

  • 7/28/2019 Transformer Protection2009 9-2

    29/94

    Transformer protection Transformer over current protection.

    Overcurrent relays: overcurrent relays are also usedon larger transformers provided withstand circuitbreaker control.

    The time delay characteristic should be chosen todiscriminate with circuit protection on the secondary

    side.

  • 7/28/2019 Transformer Protection2009 9-2

    30/94

    Transformer protection Restricted earth fault protection

    This is particularly the case for a star-connectedwinding with an impedance-earthed neutral,because of faults in the winding produce very littlecurrent in primary winding, making faultdetection by primary current measurementdifficult.

    This is a unit protection scheme for one windingof the transformer. If can be the high impedancetype or the biased low impedance type.

  • 7/28/2019 Transformer Protection2009 9-2

    31/94

    Transformer protection

    Restricted earth fault protectionFor the high-impedance type, the residual current of

    three current transformer is balance against the output ofcurrent transformer in neutral conductor.

  • 7/28/2019 Transformer Protection2009 9-2

    32/94

    Transformer protection Restricted earth fault protection

    In the biased low-impedance version, the three

    phase current and neutral current become the biasinput to a differential element.

    The system is operative for fault with in theregion between current transformers, that is the

    fault on the star winding in question. The systemremain stable for all fault outside this zone.

  • 7/28/2019 Transformer Protection2009 9-2

    33/94

    Transformer protection Differential protection

    A differential system can be arranged to cover the complete transformer.

  • 7/28/2019 Transformer Protection2009 9-2

    34/94

    Transformer protection Differential protection

    The principle current transformer on the primary and secondary side

    are connected to form a circulating current system.

  • 7/28/2019 Transformer Protection2009 9-2

    35/94

    Transformer protection Differential protection

    In applying the principles of differential protection totransformer, a variety of consideration have to be taken to

    account.Correction for possible phase shift across the transformer winding(phase correction)

    The effect of the Varity of earthing and winding arrangement.( filterof zero sequence currents)

    Correction for possible unbalance of single from CTs on either sideof the winding . (ration correction )

    The effect of magnetising inrush during initial energization.

    The possible occurrence of overfluxing.

  • 7/28/2019 Transformer Protection2009 9-2

    36/94

    Differential protection Phase correctioncorrect operation of transformer differential

    protection requires that the transformer primaryand secondary current, are measured by the relay,are in phase.

    If the transformer is connected delta/star,balance three-phase through current suffers aphase change of 30 degree.

    If left uncorrected, this phase difference wouldlead to the relay seeing through current as anunbalanced fault current, and result in relayoperation.

  • 7/28/2019 Transformer Protection2009 9-2

    37/94

    Differential protection

    Phase correction

  • 7/28/2019 Transformer Protection2009 9-2

    38/94

    Differential protection Phase correction

    Electromechanical and static relay use appropriateCT/ICT connections to ensure that the primary and

    secondary current applied to the relay are in phase.For digital and numerical relay, it is common to use star-

    connected line CTs on all winding the transformer andcompensate for the winding phase shift in software.

    Depending on relay design, the only data required in suchcircumstances may be the transformer vector groupdesignation. Phase compensation is then performedautomatically.

  • 7/28/2019 Transformer Protection2009 9-2

    39/94

    Differential protection Filtering of zero sequence current

    The differential protection will see zero sequence

    differential current for an external fault and ifcould incorrectly operate as a result.

    This is achieved by use of delta-connected lineCTs or interposing CTs for older relays. For

    digital/numerical relays, the required filtering isapplied in relay software.

  • 7/28/2019 Transformer Protection2009 9-2

    40/94

    Differential protection Ratio correction

    Correct operation of the differential elementrequires that current in the differential element

    balance under load and through fault conditions.As the primary and secondary line CTs ration

    may not exactly match the transformer areprovided with ratio correction factors for each ofCT inputs.

    The connection factors may be calculatedautomatically by the relay from knowledge of theline CT ratio and the transformer MVA rating.

  • 7/28/2019 Transformer Protection2009 9-2

    41/94

    Differential protection Bias setting

    Bias is applied to transformer differential protection forthe same reason as any unit protection scheme to ensure

    stability for external fault while allowing sensitive setting topick up internal faults.

    Some relay use a bias characteristic with three sections.The first section is set higher than the transformermagnetising current. The second section is set to allow for

    off-nominal tap setting while the third has larger bi asslope beginning well above rated current to cater for heavythrough-fault condition.

  • 7/28/2019 Transformer Protection2009 9-2

    42/94

    Differential protection

    Bias setting

  • 7/28/2019 Transformer Protection2009 9-2

    43/94

    Differential protection Transformer with multiple winding

    The unit protection principle remains valid for asystem having more than two connections, so atransformer with three or more winding can still beprotected by the same application.

  • 7/28/2019 Transformer Protection2009 9-2

    44/94

    Differential protection

    Transformer with multiple winding

    when the power transformer has only one of its three windingconnected to a source of supply with the other two winding feedingload, a relay with only two sets of CT input can be used.

  • 7/28/2019 Transformer Protection2009 9-2

    45/94

    Differential protection

    Transformer with multiple winding

    when more than one source of fault current in feed exists, these is adanger in the scheme of current circulating between the two paralleledset of CTs without producing any bias it is therefore important a relayis used with separate CT input for the two secondaries.

  • 7/28/2019 Transformer Protection2009 9-2

    46/94

    Differential Protection

    Transformer with multiple winding

    when the third winding consists of a delta-connections brought out, thetransformer may be regarded as a two winding transformer for protectionpurpose and protection .

  • 7/28/2019 Transformer Protection2009 9-2

    47/94

    Differential protection Stabilisation during magnetizing inrush conditionThe inrush current, although generally resembling

    an in-zero fault current, differs greatly when thewaveform are compared. The difference in the

    waveform can be used to distinguish between theconditions.

    Normal fault current do not contain second or othereven harmonics.

    The output of a CT that is energized into steady state saturation

    will contain odd harmonics but even harmonics.

  • 7/28/2019 Transformer Protection2009 9-2

    48/94

    Differential protection Stabilisation during mangnetising inrush

    conditionThe second harmonic is therefore an

    attractive basis for a stabilising bias againstinrush effect. The differential current is passed

    through a filter that extracts the second

    harmonics.

    This component is then applied to produce a restrainingquantity sufficient to overcome the operating tendencydue to the whole of the inrush current that flows in theoperating circuit.

  • 7/28/2019 Transformer Protection2009 9-2

    49/94

    Transformer protection Over fluxing protection

    Over fluxing arises principally from the following

    system conditions. High system voltage

    Low system frequency

    Geomagnetic disturbances

    The latter result in low frequency earth currentscirculating through a transmission system.

  • 7/28/2019 Transformer Protection2009 9-2

    50/94

    Transformer protection Over fluxing protectionSince momentary system disturbance can cause

    transient over fluxing that is not dangerous time delay

    tripping is required.The protection is initiated if a defined V/f threshold isexceeded.

    Geomagnetic disturbance may result in over fluxingwithout the v/f being exceeded. Some relays provide a 5th

    harmonic detection features, which can be used to detectsuch a condition, as levels of this harmonic rise under overfluxing conditions.

  • 7/28/2019 Transformer Protection2009 9-2

    51/94

    Oil and gas deviceAll faults below oil on an oil-immersed transformer

    result in localised heating and breakdown of the oil;some degree of arcing will always take place in a

    winding fault and the resulting composition of the oilwill release gas.

  • 7/28/2019 Transformer Protection2009 9-2

    52/94

    Buchholz protection Buchholz protection is normally provided on all

    transformers fitted with a conservator.

    A typical buchholz relay will have two contacts. One isarranged to operate for low accumulation of gas, theother for bulk displacement of oil in the event of aheavy internal faults.

  • 7/28/2019 Transformer Protection2009 9-2

    53/94

  • 7/28/2019 Transformer Protection2009 9-2

    54/94

    Buchholz protection

  • 7/28/2019 Transformer Protection2009 9-2

    55/94

    Buchholz protection The device will therefore see the following fault

    conditions, all of which are of low order ofurgency.

    Hot spots on the core due to short circuit oflamination insulation

    Core bolt insulation failure

    Faulty joints

    Inter turn faults or other winding faults involvingonly lower power in feeds

    Loss of oil due to leakage

  • 7/28/2019 Transformer Protection2009 9-2

    56/94

    Buchholz protectionWhen a major winding fault occurs, this causes a surgeof oil which displaces the lower float and thus causeisolation of transformer.

    This action will take place for All severe winding faults, either to earth or interphase

    Loss of oil if allowed to continue to a dangerousdegree.

  • 7/28/2019 Transformer Protection2009 9-2

    57/94

    BUCHHOLZ

    alarms for Local winding overheating -alarm

    Local core overheating (short circuited

    laminations) Bad contacts or joints

    Partial discharge

    Broken down core bolt insulation

  • 7/28/2019 Transformer Protection2009 9-2

    58/94

    BUCHHOLZ

    trips for Detection of loss of or low oil due to

    1.Leaky pipe joints

    2.Tank faults

    3. Contraction of oil under low

    temperatures and light load

    major internal faults (inter-turn faults or

    faults involving earth) which result in oil

    surges to the conservator.

  • 7/28/2019 Transformer Protection2009 9-2

    59/94

    Over temperature Generally regarded as overload protection also deals

    with failure of or interference with pumps and fans orshutting of valves to pumps

    Winding hot spot temperature is the main issue, butboth oil and winding temperature are usuallymeasured and used to:

    initiate an alarm

    trip circuit breakers

    control fans and pumps

  • 7/28/2019 Transformer Protection2009 9-2

    60/94

    Over temperature Two temperatures must be monitored:

    Winding temperature(WTI) -(short

    thermal ) this can rise rapidly, without

    much of an increase in oil temperature

    Oil temperature (OTI) -(long thermal )

    this can rise slowly to a critical point

    without an unacceptable winding

    temperature increase

  • 7/28/2019 Transformer Protection2009 9-2

    61/94

    Typical alarm and trip levelswinding alarm - 90C to 110C

    winding trip - 110C to 135C

    oil alarm - 80C to 95C

    oil trip - 95C to 115C

  • 7/28/2019 Transformer Protection2009 9-2

    62/94

    OVERCURRENT & EARTH FAULT

    PROTECTION RELAYSUsed in transformers up to approximately

    50MVA

    For 10MVA transformers provides mainprotection

    For 50MVA transformers provides backup

    protection onlyCommon at voltages up to about 66kV

  • 7/28/2019 Transformer Protection2009 9-2

    63/94

    Over current (O/C) ProtectionAn over current relay sees phase currents

    and hence all types of fault

    Over current relay settings must be above transformer emergency overload as with

    fuses, this determines the fundamental

    limit to their sensitivity

  • 7/28/2019 Transformer Protection2009 9-2

    64/94

    Over current (O/C) ProtectionA suitable margin should also be allowed in the

    current setting for:

    growth in load -always relay reset ratio -optional

    cold load pick-up -optional (often a relay

    feature)

    transformer taps -optional

  • 7/28/2019 Transformer Protection2009 9-2

    65/94

    Over current (O/C) ProtectionAn instantaneous O/C element can

    usually be used to provide very fast

    clearance for faults close to the HV terminal

    Must be set such that LV faults are not

    seen -discrimination

  • 7/28/2019 Transformer Protection2009 9-2

    66/94

    Earth Fault (E/F) ProtectionAn earth fault (E/F) relay sees either

    transformer neutral or residual (sum of

    three phases) current, depending on CTlocationhence sees earth faults only.

    E/F relays can be set well below load 10% of

    load typical.

  • 7/28/2019 Transformer Protection2009 9-2

    67/94

    Interposing current transformers

  • 7/28/2019 Transformer Protection2009 9-2

    68/94

    Interposing current transformers

  • 7/28/2019 Transformer Protection2009 9-2

    69/94

    Interposing current transformers

  • 7/28/2019 Transformer Protection2009 9-2

    70/94

  • 7/28/2019 Transformer Protection2009 9-2

    71/94

  • 7/28/2019 Transformer Protection2009 9-2

    72/94

  • 7/28/2019 Transformer Protection2009 9-2

    73/94

  • 7/28/2019 Transformer Protection2009 9-2

    74/94

  • 7/28/2019 Transformer Protection2009 9-2

    75/94

  • 7/28/2019 Transformer Protection2009 9-2

    76/94

  • 7/28/2019 Transformer Protection2009 9-2

    77/94

  • 7/28/2019 Transformer Protection2009 9-2

    78/94

  • 7/28/2019 Transformer Protection2009 9-2

    79/94

  • 7/28/2019 Transformer Protection2009 9-2

    80/94

  • 7/28/2019 Transformer Protection2009 9-2

    81/94

  • 7/28/2019 Transformer Protection2009 9-2

    82/94

  • 7/28/2019 Transformer Protection2009 9-2

    83/94

  • 7/28/2019 Transformer Protection2009 9-2

    84/94

  • 7/28/2019 Transformer Protection2009 9-2

    85/94

  • 7/28/2019 Transformer Protection2009 9-2

    86/94

  • 7/28/2019 Transformer Protection2009 9-2

    87/94

    Transformer protection

  • 7/28/2019 Transformer Protection2009 9-2

    88/94

    Transformer protection

  • 7/28/2019 Transformer Protection2009 9-2

    89/94

  • 7/28/2019 Transformer Protection2009 9-2

    90/94

  • 7/28/2019 Transformer Protection2009 9-2

    91/94

  • 7/28/2019 Transformer Protection2009 9-2

    92/94

  • 7/28/2019 Transformer Protection2009 9-2

    93/94

  • 7/28/2019 Transformer Protection2009 9-2

    94/94