transformer basics
DESCRIPTION
Presentation on transformersTRANSCRIPT
1
TRANSFORMER BASICSFECA Clearwater FL June 11, 2009
Transformer Applications – FECA Agenda
08:30-10:00 Transformer Overview - Basic Construction - Lightning / LV Surges - Voltage Regulation / Flicker - Life Cycle Costing / DOE Efficiency Ruling
10:00-10:15 Break
10:15-12:15 Insulation Life (C57.91) + TAP Simulations - The “Meaning of Life”- the C57.91 Loading Guide
- Over Head – Residential + flicker - Padmount – Residential + fusing + Short Circuit
- Padmount 3Φ + harmonics - Vault 3Φ + vault restrictions - Substation/Power Transformers - Ratings/Cooling Modes – Settings - Contingency Modeling
1:00 – 2:45 Power Transformer Maintenance, Monitoring & DGA
2:45 – 3:00 Exams/Discussions/wrap-up
Revised June 2009 dad
June 11, 2009
Generation Step Up - GSU
Generation…
Transmission…
Substation…
Distribution - Outdoors
Distribution - Downtown
Distribution - Indoors
Transformer Function
• Converts electricity from high voltage and low current Converts electricity from high voltage and low current to low voltage and high current … to low voltage and high current … or … vice versaor … vice versa
• Electricity is better generated and used at low voltage, Electricity is better generated and used at low voltage, and better transported at high voltage…and better transported at high voltage…
• Transformers are the basic links of a T&D system…Transformers are the basic links of a T&D system…
• Electricity and Magnetism work together to produce Electricity and Magnetism work together to produce “transformer action”…“transformer action”…
• Thin Electrical Grade Steel provides an excellent path Thin Electrical Grade Steel provides an excellent path for magnetic flux…for magnetic flux…
Distribution – Wound Core
Basic Distribution Transformer Core Loop
Distribution – ‘Stacking a Core’
Wound Coil - Note “LV Crossovers” Shell Type … Note ‘Core Grounding’
Core and Coil (LV Side) Core and Coil (HV Side)
Distribution – Shell Type - Interlaced LV windings
Interlaced SPS Shell Type C&C Cross-section
core & coil
- excellent Short Circuit strength...
- natural impedance's typically 1.5-2.0% for SPS construction...
P SSS S P SSS S
Distribution – Non-Interlaced LV windings
Non-Interlaced SPS Shell Type C&C Cross-section
core & coil
- excellent Short Circuit strength...
- natural impedance's typically 1.5-2.0% for SPS construction...
P SS P SS
Distribution – Core Type
Core Type C&C Cross-section
P P P PS S S S
core & coil
- good dielectric strength...
- typically good on thermal performance...- natural impedance's typically 2.5-3.5%...
- MUST be interlaced...
Distribution - 3Φ 5 Legged Construction
3 Phase 5-Legged C&C Cross-section
3 Φ core & coil
P SPS P SPSSP S P
Power – Stacked Core Form
Power – Stacked Core Form
Stacked Core – Core Cutting
Power – Disk Windings
Disk Windings
Power Transformer – Disk Winding
Power – Disk Windings
Power – Disk Windings
Power Transformer – Clean Room
Power Transformer – 667MVA 1Φ
Power – Pan-Cake Windings
Pan-Cake Windings
Power – Shell Form Construction
Transformer Function
• Converts electricity from high current and low voltage Converts electricity from high current and low voltage to low current and high voltage … to low current and high voltage … or … vice versaor … vice versa
• Electricity is better generated at low voltage, and Electricity is better generated at low voltage, and better transported at high voltage…better transported at high voltage…
• Transformers are the basic links of a T&D system…Transformers are the basic links of a T&D system…
• Electricity and Magnetism work together to produce Electricity and Magnetism work together to produce “transformer action”…“transformer action”…
Transformers – Basic Equations
Ampere’s Law
Faraday’s Law of Induction
Gauss’s Law for Electricity
Gauss’s Law for Magnetism
Maxwell’s EquationsDifferential form - General Case
x H = J +
x E = -
· D = ρ
· β = 0
δD δt
δβ δt
∆
∆
∆
∆
H = Magnetic Field Strength J = current densityE = Electric Field β = Magnetic FieldD = Electric Displacement ρ = Charge Density
where,
Transformers – Electric and Magnetic Fields
When a wire is connected to an AC power source, current flows When a wire is connected to an AC power source, current flows through it and a magnetic field is created around the wire… through it and a magnetic field is created around the wire…
Transformer – Ratings
• Transformers are rated in Volt-Amperes @ a specified Maximum Average Winding Temperature Rise in degrees Centigrade.
For example, a 25 kVA 65 Deg C rise transformer is rated to transform 25,000 Volt Amperes from one voltage/current level to another voltage/current level WITHOUT exceeding an Average Winding Rise of 65 Deg C above the Ambient.
• Liquid Filled (Mineral Oil or Natural Esters) Distribution Transformers are rated in kVA at 65 Deg C. Typically 10-167 kVA 1Φ or 15-2500 kVA 3Φ.
• Power Transformers are usually specified in MVA (million volt amperes). Multiple ratings can be specified at either or both 55 and/or 65 Degree C Rise.
Power Transformers can have multiple ratings based on optional cooling systems such as Fans or Pumps. For example OA/FA/FA (or under the new EIC definitions ONAN/ONAF/ONAF) for the ratings based on ‘Natural Air/Oil Cooling/Forced Air Cooling/and a second stage of Fans’.
kVA/MVA is a ‘Thermal’ Statement!!!
Transformers – Turns Relationships
Vpri
Npri=
Vsec
Nsec
N = turns ratio = Npri
Nsec
Vpri = Vsec x N and Isec = Ipri x N
= volts per turn
Transformer - Turns/Volts/Current
N = 3240 108
= 30 : 1
Isec = 25,000 VA
240 V= 104.7 Amps
Ipri = 25,000 VA
7200 V= 3.47 Amps
120
120
2407200
25 kVA
3240 turns 108 turns
Transformer - Core Loss & Exciting Current
A
vw
Iex
NL Watts
Vrated
%Iex = Iex
Irated
x 100
Rated Voltage is put across the LV terminals with the PrimaryOpen... the No Load Loss and Exciting Current are measured...
Transformer - Core Losses
No Load Loss = Hysteresis Loss + Eddy Current Losses
Hysteresis Loss is caused by the energy used in lining upthe magnetic domains in the core...
Eddy Currents are circulating currents in the core due toinduction. The thicker the core lamination, the more EddyCurrent losses...
Hysteresis Loss is a functionof the area enclosed by theHysteresis Loop...
β
H= magnetic field intensity = mmf = Ampere Turns
flux density = kl/in2
Transformer – Winding Measurements
A
vw
Irated
LL Watts
VIZ
%IZ = VIZ
Vrated
x 100
Rated Current is put into the HV terminals with the LV Shorted... the Load Loss and Impedance Voltage (IZ) are measured...
low impedancebolted short...
Transformer – Winding Measurements
Load Loss = Ip2Rp + Is
2Rs + Stray Losses
Stray Losses = Eddy (skin effect) Losses + Circulating Current Losses + Non-current carrying parts being influenced by leakage flux
Load Losses produce heating within the windings and resistance losses increase with temperature...
In order to cool the windings, oil ducts are inserted within the windings to allow the oil to circulate and transfer the heat to the tank walls and cooling fins...
Transformer – Eddy Current Losses
“No-Mag” plates (304L) are used in larger kVA transformers to reduce Eddy Current Losses due to High Current Flow…
Transformers - Voltage Regulation
%IR = LL
kVA x 10 %IX = IZ2 IR2
pf = power factor q = 1 pf2
%Reg = pf x IR + q x IX +( pf x IX - q x IR)2
200x K
where, K = p.u. load
Transformers – Resistance & Reactance in Ohms
then, ISC AMPS = kV x 1000
Ztscalar
In addition to the TRANSFORMER, the LV Fault Current is also limited by the Impedances of the SYSTEM to/from the Transformer, the LV circuit to/from the Fault, and the impedance of the FAULT… complexity is added with Line-Line and/or Line to Neutral Faults and the connections (Y-Y or Y-D)... And of course the transformation base levels…
Ztvector = Rt + j Xt (vector form)
Ft = [ kV2 / kVA ] x 10
Rt = Ft x %IR = ohms resistance
Xt = Ft x %IX = ohms reactance
Ztscalar = √ Rt2 + Xt
2 (scalar form)
…which of course is “Ohms Law”
θtscalar = tan-1(Xt/Rt ) (scalar form)
Transformers - Efficiency
Efficiency =
% Eff = 100 x K x kVA / (kVA x K + (NL + LL x K2))
OR
where K = per unit Load…
Power OUT
Power IN
Transformers – Distribution Polarity
H1 H2 H1 H2
X3 X2 X1 X1 X2 X3ADDITIVE SUBTRACTIVE
> 200kVA
> 8,660kV
Transformer Polarity indicates the direction of current flow through the HV windings with respect to the direction of the current flow through the LV windings…
Polarity is either “ADDITIVE” or “SUBTRACTIVE”
40
Lightning Surges and Protection
Lightning – Stroke Density Map
Lightning – Stroke Current Magnitude
Lightning Stroke Current Magnitude
0
0.2
0.4
0.6
0.8
1
1.2
1 10 100 1000
Stroke Current (KA)
Prob
abili
ty <
Abc
issa
Lightning Stroke Current magnitude is a probability distribution.
Lightning - Transformer Failures
Lightning is the most common cause of Transformer Failures...
Wildlife is the most common cause of Transformer Outages...
Transformer Outages1995-1996
0.00%2.00%4.00%6.00%8.00%
10.00%12.00%14.00%16.00%
Anim
al
Def
ectiv
e Eq
uip
Ligh
tnin
g
Tree
Unk
now
n
Stor
m
Con
nect
or
Ove
rload
OH
Sec
UG
Sec
UG
PR
I
Hum
an E
rror
- Pub
Misc
Vehi
cle
Hum
an E
rror
- FPC
Dig
-In
Emer
g- C
ust
Con
st E
quip
Emer
g FP
C
R/W
Cause Code
Pct
0.00%
20.00%
40.00%
60.00%
80.00%
100.00%
120.00%
Cum
ulat
ive
Pct
Lightning
Lightning acts as a current source which deposits a large charge of electrons on the power line. This charge appears as a current wave propagating along the power line.
The current wave has a very steep wave front, i.e., high di/dt. The power system is highly inductive. The voltage produced is V=L di/dt. This can result in voltages approaching 1 million volts.
Such voltages will fail the insulation system of transformers and other equipment.
Lightning – Arrester Discharge Voltage
Lightning Arresters act to limit the voltage between conductors. This is accomplished by transferring charge (current) between conductors. The arrester is modeled electrically as a non-linear resistor.
Voltage
Current
Typical MOV Arrester characteristics 10 kA = 30 kV
MOV Arrester
Linear Resis
torSilicon Carbide Arrester
Lightning – Arrester Lead Lengths
MOV Arrester
Voltage AcrossTransformer
#6 CopperLead Length +/- 6 feet
Arrester Voltage= + Lead Voltage
- The Lead Inductance of #6 Copper is typically 4 microhenerys per foot (uh/ft)...
- The di/dt for Florida Lightning averages 20 kA per microsecond...
- Lead Length voltage is V = L di/dt = 4 uh x 20 kA/usec = 8 kV per Foot.
Lead Length Voltage = 6 feet x 8 kV/ft = 48 kV
Transformer Voltage = 30 kV + 48 kV = 78 kVfor a 10 kA stroke with a 20 kA/usec rise time.
The Transformer BIL for 12470 GRDY/7200 is 95 kV...
The probability of a stroke > 10 kA is 95%...
kV
Current
30kV
Arrester – Lead Length Reduction
Reduction of lead length voltage is accomplished by use of either Tank Mountedor Internal Under Oil Arresters.
Tank mounted or under oil arresters cannot be used on wye-delta banks due tosingle phase switching over voltages. Under Oil arresters are used only onsingle bushing transformers.
MOV Arrester Voltage AcrossTransformer
= Arrester Voltage
48
Low Side / Secondary Surges
Lightning – Transformer Winding Failures
Lightning on the High Voltage winding can produce 2 failuremodes
- Layer to Ground (anywhere in the winding)
- Layer to Layer at the H1 end of winding
Lightning on the Low Voltage winding can produce layer-to-layerfailures at either end of the High voltage winding or layer-to-groundin the Low Voltage winding.
Lightning – Poletype Winding Failures
TRANSFORMER FAILURE CAUSESPOLE TYPE (167 UNITS)
HVPROB43%
LEAD2%
LVPOS17%
LVPROB19%
NONE4%
SEC10%OVRLOAD
5%
Lightning – Padmount Winding Failures
TRANSFORMER FAILURE CAUSESPAD-MOUNTED (84 UNITS)
LEAD1%
LVPOS18%
LVPROB36%
NONE11%
OVRLOAD1%
SEC21%
HVPROB12%
Low Side Surges
• 5% of Stroke Currents Exceed 85 kA
• 50% Exceed 35 kA
• 35-50% of Surges enter on the LV side
• The Average LV Surge is 1500 amps/transformer/year?
• The Majority do not exceed 5000 amps?
Distribution – Core Type
Core Type C&C Cross-section
P P P PS S S S
core & coil
- good dielectric strength...
- typically good on thermal performance...- natural impedance's typically 2.5-3.5%...
- MUST be interlaced...
Distribution – Non-Interlaced LV windings
Non-Interlaced SPS Shell Type C&C Cross-section
core & coil
- excellent Short Circuit strength...
- natural impedance's typically 1.5-2.0% for SPS construction...
P SS P SS
Distribution – Shell Type - Interlaced LV windings
Interlaced SPS Shell Type C&C Cross-section
core & coil
- excellent Short Circuit strength...
- natural impedance's typically 1.5-2.0% for SPS construction...
P SSS S P SSS S
Lightning – ‘Anonymous’ Winding Failures
H2
H1
HVLV LV
“The Anonymous Failure Mode”
Lightning – ‘Anonymous’ Winding Failures
P SS P SS
During the 1960’s, the Transformer Manufacturers switched from Conductor wound Copper LV windings to Aluminum Sheet wound construction… COST $$$
Driven by COST, the practice of NON-INTERLACED Construction found favor with those Manufacturers who could make this change…
During the 1970’s, the installed failure rate of distribution transformers began to rise dramatically!!!
Teardown analysis began to show a special failure signature which became known as “The Anonymous Failure”… this is a “turn-turn” or “layer-layer” dielectric failure near the grounded end of a single bushing transformer…
And this seemed to be associated with the Non-Interlaced Shell Type Construction…
Lightning – ‘Anonymous’ Winding Failures
H2
H1
HVLV LV
• Layer to Layer failures near the grounded end of the HV winding is a “signature” of a low side surge occurrence...
“The Anonymous Failure Mode”
Lightning – ‘Anonymous’ Winding Failures
• The majority of LV surges probably enter the Transformer through the LV ground connections... either due to Primary Arrester operation or from the ground following direct or nearby strokes...
E = Ldidt = the voltage developed across
the ground leads...
Arrester
Lightning – ‘Anonymous’ Winding Failures
LV LV
HV
• Surge currents flowing through the LV windings of a Non-Interlaced LV winding produce a high magnetic field across the primary coil...
Lightning – ‘Anonymous’ Winding Failures
kV
H2 H1
• The rapidly changing magnetic field induces a very high voltage in the primary winding...
290 kV winding voltageto ground...
10 kVA 95kV BIL
• The lightning arrester connected across H1 to H2 does not see any voltage...
HV winding layers
Lightning – ‘Anonymous’ Winding Failures
kV
H2 H1
10 kVA 95kV BIL
HV winding layers
Layer to Layer Voltage
Peak 80 kV
• The high layer to layer stress in the HV winding will cause coil failure near either end of the coil... but usually at or near the grounded end of the winding...
Lightning – Low Side Surges
LV
HV
• Surge currents flowing through the LV windings of an Interlaced LV winding cancel and produce a weak magnetic field across the primary coil...
LV LV LV
Lightning – Low Side Surges
kV
H2 H1
290 kV winding voltageto ground...
HV winding layers
Non-Interlaced
Interlaced3 kV to ground...
• Interlacing the LV winding balances the winding and significantly reduces the stress due to LV Surges...
Lightning – Low Side Surges
kV
H2 H1
10 kVA 95kV BIL
HV winding layers
Layer to Layer Voltage
Peak 80 kVNon-Interlaced
InterlacedPeak 1 kV
• Interlacing the LV winding balances the winding and significantly reduces the stress due to LV Surges...
Lightning – Low Side Surges
• Non-Interlaced LV windings are the major cause of Distribution Transformer (DT) Lightning Failures...
• Small kVA’s are MORE susceptible because of more turns...
• Primary Arresters DO NOT Protect the HV against LV Surges...
• Interlacing or LV Arresters reduces DT Failure Rate...
interlaced types non-interlaced types
0.5 %
1.0 %
FailureRate
Lightning - Summary
• The proper application and choice of Arresters can reduce the failure rate significantly… especially in the Southeastern USA…
• Arrester Lead length can be very important…
• About 50% of lightning surges come from the low side… on the smaller kVA transformers, Interlaced windings and/or LV Arresters can reduce winding failures…
68
Starting Transformers and Motors
Motor Starting Issues
• The current required to start equipment such as Electric Motors or Transformers requires a starting current, typically known as ‘Inrush’ or ‘locked rotor current’…
• For fusing, the typical ‘inrush’ rule is to keep the fuse melt beyond 8-12 times rated current at 0.1 second (about 6 cycles)…
• The short term voltage drop or ‘Flicker’ is a function of the required ‘Locked Rotor’ current required to start the equipment… a number of papers and information is available to the user on this issue…
• In addition to the impact on the local low voltage circuits, starting equipment such as large motors can cause voltage quality issues on the primary circuits of the distribution feeders… which can affect associated equipment…
• Some electronic systems may be sensitive to these changes!
Transformers – Resistance & Reactance in Ohms
then, ISC AMPS = kV x 1000
Ztscalar
In addition to the TRANSFORMER, the LV Fault Current is also limited by the Impedances of the SYSTEM to/from the Transformer, the LV circuit to/from the Fault, and the impedance of the FAULT… complexity is added with Line-Line and/or Line to Neutral Faults and the connections (Y-Y or Y-D)... And of course the transformation base levels…
Ztvector = Rt + j Xt (vector form)
Ft = [ kV2 / kVA ] x 10
Rt = Ft x %IR = ohms resistance
Xt = Ft x %IX = ohms reactance
Ztscalar = √ Rt2 + Xt
2 (scalar form)
…which of course is “Ohms Law”
θtscalar = tan-1(Xt/Rt ) (scalar form)
Motor Start – calculations
The voltage drop across the transformer:
%T = [1-Zm/sqrt((Rm+Rt)^2 + (Xm+Xt)^2))] x100 where, Zm is the motor impedance is calculated as, Zm = (line-line voltage rating of the motor) / LRA LRA = locked rotor amps PF = motor starting power factor Rm = Zm x PF ohms Xm = sqrt( 1-PF^2) ohms To translate the %Impedance ( %IZ ) into Real and Reactive components, we use the transformer impedance factor, Ft. Ft = [ [(Secondary voltage in kV)^2] / kVA rating of Transformer ] x 10 Rt = Ft x %IR ohms Xt = Ft x %IX ohms %IR and %IX are calculated from the Load Loss watts (LL) and Impedance (%IZ) of the specific transformer. %IR = LL / (kVA x 10) %IX = sqrt[ %IZ^2 - %IR^2 ] The voltage drop across the secondary conductor is:
%C = [ [ Rc x LRA x PF ] + [ Xc x LRA x sqrt(1-PF^2) ] ] x 100 / LV where LV is the line-line secondary voltage, typically 240 volts and,
Rc = conductor resistance in ohms per 100 feet x [ 2 x length /100 ] Xc = conductor reactance in ohms per 100 feet x [ 2 x length /100 ] The conductor length is multiplied by 2 as the current must have a return path. If the return path conductor is not the same size and characteristics as the line conductor the calculation must be adjusted accordingly.
Flicker
Flicker is typically the voltage drop caused by the Locked Rotor Current required to start a air-conditioner compressor motor.
The duration of this current for residential air conditioners varies from4 to 20 cycles. A voltage drop occurs in each component of the system,i.e., Transformer and Conductors, based on the magnitude of the currentand the impedance of the components.
The most common occurrence is during the startup of residential air conditioners. Customers see this as a dimming of the lights or, underextreme conditions, as a shrinking of the TV picture.
Customer sensitivity varies based on individual perception, themagnitude and duration of the voltage dip, and the type oflight source.
Flicker – Motor Starting Current 15-20 cycles
RAYSAC
Measured : 02/14/97 11:47:57
Channel A (V) Channel A (I) Sec.0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45
VoltsY1
-400
-300
-200
-100
0
100
200
300
400Amps
Y2
-300
-200
-100
0
100
200
300
Motor Start – Single Phase
Capacitor Start motors utilize a capacitor in series with thestart winding to provide phase shift in the current throughthe start winding. This phase shift causes an angular displacement in the magnetic fields between the Run and Start windings resulting in a torque on the rotor.
Rotor
Start Winding
Run Winding
Run Winding
Start Winding
The larger the Capacitor - the larger the phase shift - the larger the starting torque - the shorter the starting cycle
Motor Start – Permanent Split Capacitor Motor
Run Capacitor
Start Run
Line
The Start winding and Run Capacitor remain energized at all times
Motor Start – Conventional 3 wire Hard Start
Potential Relay
Run Capacitor
Start Capacitor
Start Run
Line
The Potential Relay removes capacitor with StartWinding back E.M.F.
Residential Air Conditioners
Residential Air Conditioners use one of two types of Motors
- Permanent Split Capacitor
- Capacitor Start / Capacitor Run
Residential Air Conditioners use one of two types of Compressors
- Reciprocating (Piston)
- Scroll (new High Efficency units)
Motor Sizing rules are Different for Different Compressors
Motor Start Flicker – Field Test Data
AC Starting Characteristics
0.0
50.0
100.0
150.0
200.0
250.0
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5
Tons
LRA
RECIP Test DataRecip RegressionScroll Test DAtaScroll Regression
Motor Start Flicker – Kickstart TO-5
Motor Start Flicker – Kickstart TO-5
Potential Relay
Run Capacitor
Start Capacitor
Start Run
Line
The Potential Relay removes capacitor with Startand Run Winding back E.M.F.
Flicker – Kickstart Motor Starting Current 4-6 cycles
RAYG4KS
Measured : 02/25/97 16:39:47
Channel A (V) Channel A (I) Sec.0.00 0.05 0.10 0.15 0.20 0.25
VoltsY1
-400
-300
-200
-100
0
100
200
300
400Amps
Y2
-400
-300
-200
-100
0
100
200
300
400
Compressor/Motor Start Flicker – Summary
• Compressor Flicker is a momentary (5-30 cycle) voltage drop caused by Motor Start… such as a Residential Air Conditioner…
• Compressor Flicker is ‘as perceived by the user’… Not everyone can notice it… once seen, the mind can ‘tune-in’ to it…
• Flicker is a function of the required ‘Locked Rotor’ Starting Amperes… the High Efficiency ‘Scroll Type’ Compressors require Higher Starting Amps… thus going to Higher Efficiencies can cause other issues!
• Adding extra Capacitive Reactance will not reduce the magnitue of the required starting current, but can reduce the amount of time required to get the compressor started… thus reducing the ‘perception of Flicker’…
83
Transformer Costs and Efficiencies
Quantifying Transformer Costs
• Capital Vs. Expense Dollars
• Financial Math Relationships
• Cost of Losses – the A and B Factors
• Band of Equivalence
• DOE Efficiency Rules
Capital Dollars
The purchase cost of a transformer is amortized over theexpected life. This is done by applying a Fixed ChargeRate (FCR) to the purchase price...
Price x FCR = Annualize Fixed Cost
The result is an annual cost which is uniform for the life ofthe unit...
FCR (%) = Fixed Charge Rate - The cost of carrying a capital investment made up of:- The weighted cost of capital (stocks, bonds)- Depreciation on the investment- Taxes (Income, Ad valorem, Gross Receipts)- Insurance
Expense Dollars
Expense costs such as Cost of Losses or future Change-Out are levelized to an annual form with the Capital Recovery Factor which considers only the cost of money and time…
Change Out Cost x CRF = Annualize Change Out Cost
The result is an annual cost which is uniform for the life ofthe unit...
CRF (%) = A/P = i(1+i)n /((1+i)n-1)
Note: In ANNUAL form Expense and Capital are equal!
Basic Financial Math
Annuity
Present Value
FutureValue
Compound Interest Factor F/P = (1+i)n
Capital Recovery FactorA/P = i(1+i)n /((1+i)n-1)
Present Value FactorP/F = 1/(1+i)n
Present Worth FactorP/A = ((1+i)n-1)/i(1+i)n
Compound Amount FactorF/A = (1+i)n-1/i
Sinking Fund FactorA/F = i/((1+i)n-1)
Moving Money (Value) through Time
Cost of Transformer Losses
The cost to operate a Transformer over it’s life is affectedby the Cost to Supply the capacity, or Demand (SC $/kW-yr),and the Cost incurred to supply the Energy (EC $/kW-Hour).
The No Load losses are continuous as long as the transformeris connected to the system, typically 8760 hours/year.
The Load Losses vary with transformer load and are affected by the annual load factor and the timing of the system peak.
AOC = Price x FCR + A x NL + B x LL
The Annual cost of ownership (AOC) is:
NOTE: draft C57.12.33 Loss Evaluation methodology currently under development by the IEEE…
The ‘A’ Factor
A = $ per No Load (excitation) Loss Watt
A =
where,
SC = Avoided Cost of System Capacity ($/kW-yr) - - The levelized avoided (incremental) cost of generation, transmission, and primary distribution capacity required to supply the next kW of load to the distribution transformer coincident with the peak load.
SC + 8760 x EC
1000 $/watt
EC = Avoided Cost of Energy ($/kWh-yr) - - The levelized avoided (incremental) cost for supplying the next kWh, which may be produced by the utility’s generating units or purchased from an energy supplier.
The ‘B’ Factor
B = $ per Load (winding) Loss Watt
B =
where,
( SC x RF + 8760 x LsF x EC) x PL2
1000 $/watt
PL = Equivalent Annual Peak Load “ON THE TRANSFORMER”
RF = Peak Loss Responsibility Factor - Defines the relationship between thetransformer peak load and the transformer load at the time of system peak load.
LsF = Loss Factor - A ratio of the annual average load losses to the peak value of load losses on the transformer. LsF = [Σ(K2
n*tn)/t]/K2peak
NOTE: An empirical relationship for loss factor for RESIDENTIAL transformers is the Propst/Ganger relationship: LsF = 0.15 (Load Factor) + 0.85 (Load Factor)2
Evaluation Forms
The Transformer Evaluation Equation may be written as: Total Owning Cost (TOC) = F x Price + A x NL + B x LL Where the factor F is a multiplier against the Price and is used toexpress the owning cost equation in three forms: Type description F form . - EFC Equivalent First Cost 1.0 Capital form - PW Present Worth FCR/CRF Expense form - AC Annual FCR Annuity form
Band of Equivalence
• The BOE was described by the Shincovich and Stephens (EEI 1981)as a way to address the uncertainty of the future estimates on factorssuch as Energy Costs, Loading, etc… 1% was suggested!
• “Uncertainty” of course can result in HIGHER or LOWER future costs!
• However, this idea has been expanded as a tool to force lower first pricesat the expense of future costs… 3-10% BOE is not uncommon! • BOE reduces the actual value of the Loss Evaluation Factors… Typically, a 3% BOE effectively reduces the A&B Factors by ½ or more!
Variances would be better addressed with tools such as Crystal Ball… or the Economics Variance module in TAP…
A & B Variance
LCC – Mild Steel Tank vs. Stainless
95
DOE Transformer Efficiencies – 2010 Rule
Energy Policy and Conservation Act
The Energy Policy and Conservation Act (EPCA) of 1975 established an energy conservation program for major household appliances. The National Energy Conservation Policy Act of 1978 amended EPCA to add Part C of Title III, which established an energy conservation program for certain industrial equipment. The Energy Policy Act of 1992 amended EPCA to add certain commercial equipment, including distribution transformers.
The Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Program conducts the program that develops equipment energy conservation standards and has overall responsibility for rulemaking activities for distribution transformers in fulfillment of the law.
http://www.eere.energy.gov/buildings/appliance_standards/
Energy Policy and Conservation Act
Distribution Transformers The first step in developing energy conservation standards was the Secretarial determination in 1997 that, "Based on its analysis of the information now available, the Department has determined that energy conservation standards for transformers appear to be technologically feasible and economically justified, and are likely to result in significant savings" 62 FR 54809 (October 22, 1997). The Department of Energy (DOE) conducted two rulemakings for Distribution Transformers:
• an energy conservation standard• a test procedure
http://www.eere.energy.gov/buildings/appliance_standards/
Energy Policy and Conservation Act
• In response, NEMA developed the TP-1 Minimum EfficiencyGuidelines in the early 1990’s… note: basically a 3 year payback!
• In August 2006, the DOE published the Notice of Proposed Rulemaking with a recommendation for to the Trial Standard Level 2 (TSL-2)…
• Mixed responses… some opposed mostly based on increased cost and material availability… some saying it doesn’t go far enough…
http://www.eere.energy.gov/buildings/appliance_standards/
Trial Standard Levels
Efficiency = Power OUT / Power IN
%E = 100 x kVA x 0.5 / [ kVA x 0.5 + ((NL + LL x 0.9 x 0.52)/1000)]
Where NL and LL are in watts…
Note: 0.9 = Load Loss Temp correction from 85 to 55 deg C…
KVA NEMA TP1 TSL-2 TSL-3 TSL-410.0 98.40% 98.40% 98.43% 98.46%15.0 98.60% 98.56% 98.59% 98.62%25.0 98.70% 98.73% 98.76% 98.79%37.5 98.80% 98.85% 98.99% 99.14%50.0 98.40% 98.90% 99.04% 99.19%75.0 99.00% 99.04% 99.18% 99.33%
100.0 99.00% 99.10% 99.24% 99.39%167.0 99.10% 99.21% 99.35% 99.50%
75.0 98.70% 98.91% 99.09% 99.27%112.5 98.80% 99.01% 99.19% 99.37%150.0 98.90% 99.08% 99.26% 99.44%225.0 99.00% 99.17% 99.35% 99.53%300.0 99.00% 99.23% 99.41% 99.59%500.0 99.10% 99.32% 99.50% 99.68%750.0 99.20% 99.24% 99.42% 99.60%
1000.0 99.20% 99.29% 99.47% 99.65%1500.0 99.30% 99.36% 99.42% 99.48%2000.0 99.40% 99.40% 99.46% 99.50%2500.0 99.40% 99.44% 99.50% 99.55%
•TSL-1 = NemaTP1•TSL-2 = 1/3 between TP1 and TSL-4•TSL-3 = 2/3 between TP1 and TSL-4•TSL-4 = minimum Life Cycle Cost•TSL-5 = max Energy Savings with no change in LCC•TSL-6 = max Energy Savings
Final Rule – October 12, 2007
“Effective January 1, 2010, Liquid Filled Distribution Transformers manufactured for sale in the United States MUST meet or exceed the following Efficiency levels…”
Efficiency = Power OUT / Power IN @ 50% Load
%Eff = 100 x kVA x 0.5 / [ kVA x 0.5 + ((NL + LL x 0.9 x 0.52)/1000)] where NL and LL are in watts…
Note: 0.9 = Load Loss Temp correction from 85 to 55 deg C…
DOE Final Rule
• Similar rules are in place for Medium Voltage Dry type Transformers…
• The DOE rule resolves the issue between Single and Three Phase designs by using the same Efficiency Value for the Single Phase design for the equivalent 3 Phase kVA… For example, the required efficiency value for a 3Φ 150 kVA transformer is the same as a 50 kVA 1Φ unit…. (3 x 50 = 150 kVA)…
• Pre-Existing Distributor Stock, Re-manufactured units, and Transformers intended for Mining Operations are excluded from the rule…
• For Liquid Filled Transformers, the relationships to the Trial Standard Levels are…
• 1Φ 10-167 kVA slightly above TSL-4• 1Φ 250-833 kVA between TSL2 and TSL3
• 3Φ 45-300 kVA TSL-2• 3Φ 500 kVA between NEMA TP-1 & TSL-2• 3Φ 750 kVA slightly greater than TSL-3• 3Φ 1000-2500 kVA TSL-3
For the final rule, DOE set average A & B values of A=3.85 and B=1.16 $/watt 1Φ and B=1.93 $/watt 3Φ
DOE Projected Benefits
Energy Saved Quads = 1.77 2.39 3.15 3.63 6.9 9.77
TSL-1 TSL-2 TSL-3 TSL-4 TSL-5 TSL-6
CO2 (Mt) reductions = 123.1 167.3 218.5 252.7 483.1 679.5
NOX (kt) reductions = 34.1 46.4 60.9 71 134.9 188
Hg (t) reductions = 3 3.7 4.3 4.9 6.4 6.5
NOTE: The QUAD is used by the U.S. Department of Energy in discussing world and national energy budgets. One Quad = 1015 BTU. The global primary energy production in 2004 was 446 quads…
Conclusion
Q/A?Don A. Duckett, P.E.Technical Sales EngineerHD Supply Utilities
(407) [email protected]