trajexia motion control system - omron · trajexia motion control system hardware reference manual...
TRANSCRIPT
Trajexia motion control systemTJ1-MC04, TJ1-MC16, TJ1-ML04, TJ1-ML16, TJ1-PRT, TJ1-DRT, TJ1-CORT, TJ1-FL02 GRT1-ML2
hardware reference manual
Cat. No. I51E-EN-05
Austria Tel: +43 (0) 2236 377 800www.omron.at
Belgium Tel: +32 (0) 2 466 24 80 www.omron.be
Czech Republic Tel: +420 234 602 602 www.omron-industrial.cz
Denmark Tel: +45 43 44 00 11 www.omron.dk
Finland Tel: +358 (0) 207 464 200www.omron.fi
France Tel: +33 (0) 1 56 63 70 00www.omron.fr
Germany Tel: +49 (0) 2173 680 00 www.omron.de
Hungary Tel: +36 1 399 30 50 www.omron.hu
Italy Tel: +39 02 326 81www.omron.it
Middle East & AfricaTel: +31 (0) 23 568 11 00www.omron-industrial.com
Netherlands Tel: +31 (0) 23 568 11 00 www.omron.nl
Norway Tel: +47 (0) 22 65 75 00 www.omron.no
Poland Tel: +48 (0) 22 645 78 60 www.omron.pl
Portugal Tel: +351 21 942 94 00 www.omron.pt
Russia Tel: +7 495 648 94 50 www.omron-industrial.ru
Spain Tel: +34 913 777 900 www.omron.es
Sweden Tel: +46 (0) 8 632 35 00 www.omron.se
Switzerland Tel: +41 (0) 41 748 13 13 www.omron.ch
Turkey Tel: +90 216 474 00 40 www.omron.com.tr
United Kingdom Tel: +44 (0) 870 752 08 61 www.omron.co.uk
OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.omron-industrial.com
Authorised Distributor:
Note:Although we do strive for perfection, Omron Europe BV and/or its subsidiary and affiliated companies do not warrant or make any representations regarding the correctness or completeness of information described in this catalogue. Product information in this catalogue is provided ‚as is‘ without warranty of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability, fitness for a particular purpose, or non-infringement. In a jurisdiction where the exclusion of implied warranties is not valid, the exclusion shall be deemed to be replaced by such valid exclusion, which most closely matches the intent and purpose of the original exclusion. Omron Europe BV and/or its subsidiary and affiliated companies reserve the right to make any changes to the products, their specifications, data at its sole discretion at any time without prior notice. The material contained in this catalogue may be out of date and Omron Europe BV and/or its subsidiary and affiliated companies make no commitment to update such material.
Cat. No. I51E-EN-04
Trajexia motion control system hardware reference manualCat. No. I51E-EN-04
HARD I
Revision 5.0
NotiOMRby a qThe fthis mheed
Defi
TradPROFMECDevicCIP isCANoModbTrajeMotioAll otment
publication may be reproduced, stored in a retrieval sys-r by any means, mechanical, electronic, photocopying, e prior written permission of OMRON. respect to the use of the information contained herein. nstantly striving to improve its high-quality products, the al is subject to change without notice. Every precaution of this manual. Nevertheless, OMRON assumes no s. Neither is any liability assumed for damages resulting tained in this publication.
WARE REFERENCE MANUAL
ceON products are manufactured for use according to proper procedures ualified operator and only for the purposes described in this manual.
ollowing conventions are used to indicate and classify precautions in anual. Always heed the information provided with them. Failure to
precautions can result in injury to people or damage to property.
nition of precautionary information
emarks and CopyrightsIBUS is a registered trademark of PROFIBUS International.
HATROLINK is a registered trademark of Yaskawa Corporation.eNet is a registered trademark of Open DeviceNet Vendor Assoc INC. a registered trademark of Open DeviceNet Vendor Assoc INC.pen is a registered trademark of CAN in Automation (CiA).usTCP is a registered trademark of Modbus IDA.xia is a registered trademark of OMRON.n Perfect is a registered trademark of Trio Motion Technology Ltd.her product names, company names, logos or other designations ioned herein are trademarks of their respective owners.
/i
WARNINGIndicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CautionIndicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury, or property damage.
© OMRON, 2010
All rights reserved. No part of this tem, or transmitted, in any form, orecording, or otherwise, without thNo patent liability is assumed withMoreover, because OMRON is coinformation contained in this manuhas been taken in the preparation responsibility for errors or omissionfrom the use of the information con
HARD II
Revision 5.0
AboThis mContrPleascarefattemread /i
Name
Trajextrol syQUICGUID
Trajextrol syWARREFEUAL
Trajextrol syPROGMANU
SigmDrive
SigmMECHinterfa
SigmDrive
JUNMdrive
060605 02-OY Describes the installation and operation of V7 Inverters
55 1-OY Describes the installation and operation of F7Z Inverters
60 Describes the installation and operation of G7 Inverters
80001 Describes the installation and operation of the MECHATROLINK-II application module
600-08 Describes the installation and operation of MECHATROLINK-II interfaces for G7 and F7 Inverters
600-03 Describes the installation and operation of MECHATROLINK-II interfaces for V7 Inverters
Describes the installation and operation of MECHATROLINK-II input and output modules and the MECHATROLINK-II repeater
Describes FINS communications proto-col and FINS commands
Describes the installation and operation of Omron slice I/O units
Describes the installation and operation of G-series Servo Drivers
Describes the installation and operation of Accurax G5 Servo Drivers
Describes the use of Trajexia Studio programming software
Contents
WARE REFERENCE MANUAL
ut this manualanual describes the installation and operation of the Trajexia Motion
ol System.e read this manual and the related manuals listed in the following table
ully and be sure you understand the information provided before pting to install or operate the Trajexia Motion Control units. Be sure to the precautions provided in the following section.
Cat. No. Contents
ia motion con-stemK START E
I50E Describes how to get quickly familiar with Trajexia, moving a single axis using MECHATROLINK-II, in a test set-up.
ia motion con-stem HARD-
E RENCE MAN-
I51E Describes the installation and hardware specification of the Trajexia units, and explains the Trajexia system philosophy.
ia motion con-stemRAMMING AL
I52E Describes the BASIC commands to be used for programming Trajexia, commu-nication protocols and Trajexia Studio software, gives practical examples and troubleshooting information.
a-II Servo r manual
SIEP S800000 15 Describes the installation and operation of Sigma-II Servo Drivers
a-III with ATROLINK ce manual
SIEP S800000 11 Describes the installation and operation of Sigma-III Servo Drivers with MECHA-TROLINK-II interface
a-V Servo r manual
SIEP S800000-44-O-OYSIEP S800000-46-O-OYSIEP S800000-48-O-OY
Describes the installation and operation of Sigma-V Servo Drivers
A series servo manual
TOEP-C71080603 01-OY Describes the installation and operation of JUNMA Servo Drivers
V7 Inverter TOEP C71
F7Z Inverter TOE S616-
G7 Inverter TOE S616-
JUSP-NS115 man-ual
SIEP C710
SI-T MECHATRO-LINK interface for the G7 & F7
SIBP-C730
ST-T/V7 MECHA-TROLINK interface for the V7
SIBP-C730
MECHATROLINK IO Modules
SIE C887-5
SYSMAC CS/CJ Series Communica-tions Commands
W342
Omron Smartslice GRT1-Series, slice I/O units, Operation manual
W455-E1
Omron G-series user’s manual
I566-E1
Omron Accurax G5 user’s manual
I572-E1
Trajexia Studio user manual
I56E-EN
Name Cat. No.
HARD III
Revision 5.0
FunDurincontrThis fcontrIn therelate/i
Verify
ajexia Studio software. Refer to the
d type the following commands:
erminal window. The version parameter returns number of the motion controller.SLOT(-1) in the terminal window. The t FPGA version number of the TJ1-MC__.
Func
Full s
Supp
Supp
Supp
SuppbusTC(excemandas se
SuppSigm
Supp
WARE REFERENCE MANUAL
ctions supported by unit versionsg the development of Trajexia new functionality was added to the oller unit after market release.unctionality is implemented in the firmware, and/or the FPGA of the oller unit. table below, the overview of the applicable functionality is shown d to the firmware and FPGA version of the TJ1-MC__.
the firmware and FPGA versions of the TJ1-MC__
Connect the TJ1-MC__ to TrProgramming Manual.Open the terminal window an
Type PRINT VERSION in the tthe current firmware version Type PRINT FPGA_VERSION parameter returns the curren
WARNINGFailure to read and understand the information provided in this manual may result in personal injury or death, damage to the pro-duct, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or opera-tions given.
tionality TJ1-MC__ Firmware version
TJ1-MC__ FPGAversion
upport TJ1-FL02 V1.6509 21 and higher
ort BASIC commands FINS_COMMS V1.6509 All versions
ort TJ1-DRT V1.6509 All versions
ort TJ1-MC04 andTJ1-ML04 V1.6607 21 and higher
ort TJ1-CORT, GRT1-ML2, Mod-P, Sigma-V series Servo Drivers
pt DATUM and REGIST BASIC com-s) and allow Inverters to be controlled rvo axes
V1.6652 21 and higher
ort for G-series Drivers, full support for a-V series Servo Drivers
V1.6714 21 and higher
ort for Accurax G5 Drivers V1.6720 21 and higher
Contents
HARDWARE REFERENCE MANUAL IV
Revision 5.0
1 Safety warnings and precautions................................................................................................................................................................ 11.1 Intended audience ............................................................................................................................................................................................................................11.2 General precautions .........................................................................................................................................................................................................................11.3 Safety precautions ............................................................................................................................................................................................................................11.4 Operating environment precautions..................................................................................................................................................................................................21.5 Application precautions.....................................................................................................................................................................................................................31.6 Unit assembly precautions................................................................................................................................................................................................................51.7 Conformance to EC Directives Conformance...................................................................................................................................................................................6
2 System philosophy....................................................................................................................................................................................... 72.1 Introduction .......................................................................................................................................................................................................................................72.2 Motion control concepts....................................................................................................................................................................................................................82.3 Servo system principles..................................................................................................................................................................................................................192.4 Trajexia system architecture .........................................................................................................................................................................................................222.5 Cycle time ......................................................................................................................................................................................................................................232.6 Program control and multi-tasking ..................................................................................................................................................................................................292.7 Motion sequence and axes.............................................................................................................................................................................................................302.8 Motion buffers ...............................................................................................................................................................................................................................402.9 Mechanical system .........................................................................................................................................................................................................................42
3 Hardware reference .................................................................................................................................................................................... 433.1 Introduction .....................................................................................................................................................................................................................................433.2 All units ..........................................................................................................................................................................................................................................463.3 Power Supply Unit (PSU) ...............................................................................................................................................................................................................573.4 TJ1-MC__ .....................................................................................................................................................................................................................................593.5 TJ1-ML__........................................................................................................................................................................................................................................703.6 GRT1-ML2 ....................................................................................................................................................................................................................................1433.7 TJ1-PRT .......................................................................................................................................................................................................................................1583.8 TJ1-DRT .......................................................................................................................................................................................................................................1623.9 TJ1-CORT ....................................................................................................................................................................................................................................1663.10 TJ1-FL02 ......................................................................................................................................................................................................................................170
A Differences between Sigma-II and Junma.............................................................................................................................................. 188Revision history .............................................................................................................................................................................................. 189
Safety
HARD 1
Revision 5.0
1
1.1This m(electinstal
1.2The uspeciBeformanuaviatiotheron livrepre
1.3
e positive and negative terminals of the bat-tteries, disassemble them, deform them by r throw them into a fire. xplode, combust or leak liquid.
must be taken by the customer to ensure f incorrect, missing, or abnormal signals gnal lines, momentary power interruptions, or
sult in serious accidents.
uits, interlock circuits, limit circuits, and similar st be provided by the customer as external cir-Trajexia motion controller. sult in serious accidents.
utput (I/O power supply to the TJ1) is over-ited, the voltage may drop and result in the off.As a countermeasure for such problems,
sures must be provided to ensure safety in the
go off due to overload of the output transistors ntermeasure for such problems, external st be provided to ensure safety in the system.
warnings and precautions
WARE REFERENCE MANUAL
Safety warnings and precautions
Intended audienceanual is intended for personnel with knowledge of electrical systems
rical engineers or the equivalent) who are responsible for the design, lation and management of factory automation systems and facilities.
General precautionsser must operate the product according to the performance fications described in this manual.e using the product under conditions which are not described in the al or applying the product to nuclear control systems, railroad systems, on systems, vehicles, safety equipment, petrochemical plants, and systems, machines and equipment that can have a serious influence es and property if used improperly, consult your OMRON sentative.
Safety precautions
WARNINGDo not attempt to take the Unit apart and do not touch any of the internal parts while power is being supplied. Doing so may result in electrical shock.
WARNINGDo not touch any of the terminals or terminal blocks while power is being supplied. Doing so may result in electric shock.
WARNINGNever short-circuit thteries, charge the baapplying pressure, oThe batteries may e
WARNINGFail-safe measures safety in the event ocaused by broken siother causes. Not doing so may re
WARNINGEmergency stop circsafety measures mucuits, i.e., not in the Not doing so may re
WARNINGWhen the 24 VDC oloaded or short-circuoutputs being turnedexternal safety measystem.
WARNINGThe TJ1 outputs will(protection).As a cousafety measures mu
Safety
HARD 2
Revision 5.0
ronment precautions
n the terminal block of the Power Supply Unit ed in this manual.esult in burning or malfunction.
nit in any of the following locations. in malfunction, electric shock, or burning.t to direct sunlight.t to temperatures or humidity outside the
in the specifications.t to condensation as the result of severe erature.t to corrosive or flammable gases.t to dust (especially iron dust) or salts.t to exposure to water, oil, or chemicals.t to shock or vibration.
d sufficient countermeasures when installing ing locations.
sufficient measures may result in malfunction.t to static electricity or other forms of noise.t to strong electromagnetic fields.t to possible exposure to radioactivity.to power supplies.
warnings and precautions
WARE REFERENCE MANUAL
1.4 Operating envi
WARNINGThe TJ1 will turn off the WDOG when its self-diagnosis function detects any error.As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
WARNINGProvide safety measures in external circuits, i.e., not in the Tra-jexia Motion Controller (referred to as "TJ1"), in order to ensure safety in the system if an abnormality occurs due to malfunction of the TJ1 or another external factor affecting the TJ1 operation.Not doing so may result in serious accidents.
WARNINGDo not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
CautionConfirm safety at the destination unit before transferring a program to another unit or editing the memory. Doing either of these without confirming safety may result in injury.
CautionUser programs written to the Motion Control Unit will not be auto-matically backed up in the TJ1 flash memory (flash memory func-tion).
CautionPay careful attention to the polarity (+/-) when wiring the DC power supply.A wrong connection may cause malfunction of the system.
CautionTighten the screws oto the torque specifiLoose screws may r
CautionDo not operate the UDoing so may result- Locations subjec- Locations subjec
range specified - Locations subjec
changes in temp- Locations subjec- Locations subjec- Locations subjec- Locations subjec
CautionTake appropriate ansystems in the followInappropriate and in- Locations subjec- Locations subjec- Locations subjec- Locations close
Safety
HARD 3
Revision 5.0
1.5
asures to ensure that the specified power with d frequency is supplied. Be particularly careful power supply is unstable. upply may result in malfunction.
kers and take other safety measures against ternal wiring. easures against short-circuiting may result in
to the Input Units in excess of the rated input
result in burning.
or connect loads to the Output Units in um switching capacity. ads may result in burning.
tional ground terminal when performing with-
e functional ground terminal may result in
class-3 ground (to 100Ω or less) when install-
class-3 ground may result in electric shock.
warnings and precautions
WARE REFERENCE MANUAL
Application precautions
CautionThe operating environment of the TJ1 System can have a large effect on the longevity and reliability of the system.Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the TJ1 System.Make sure that the operating environment is within the specified conditions at installation and remains within the specified condi-tions during the life of the system.
WARNINGDo not start the system until you check that the axes are present and of the correct type.The numbers of the Flexible axes will change if MECHATROLINK-II network errors occur during start-up or if the MECHATROLINK-II network configuration changes.Not doing so may result in unexpected operation.
WARNINGCheck the user program for proper execution before actually run-ning it in the Unit. Not checking the program may result in an unexpected operation.
CautionAlways use the power supply voltage specified in this manual. An incorrect voltage may result in malfunction or burning.
CautionTake appropriate methe rated voltage anin places where the An incorrect power s
CautionInstall external breashort-circuiting in exInsufficient safety mburning.
CautionDo not apply voltagevoltage. Excess voltage may
CautionDo not apply voltageexcess of the maximExcess voltage or lo
CautionDisconnect the funcstand voltage tests. Not disconnecting thburning.
CautionAlways connect to aing the Units. Not connecting to a
Safety
HARD 4
Revision 5.0
wiring before turning on the power supply. result in burning.
result in burning.
after checking the terminal block completely.
inal blocks, expansion cables, and other vices are properly locked into place. y result in malfunction.
erse effect will occur in the system before ing mode of the system. sult in an unexpected operation.
nly after transferring to the new CPU Unit the nd table memory required for operation. sult in an unexpected operation.
s, be sure to confirm that the rating of a new
sult in malfunction or burning.
warnings and precautions
WARE REFERENCE MANUAL
CautionAlways turn off the power supply to the system before attempting any of the following. Not turning off the power supply may result in malfunction or elec-tric shock.- Mounting or dismounting expansion Units, CPU Units, or any
other Units.- Assembling the Units.- Setting dipswitches or rotary switches.- Connecting or wiring the cables.- Connecting or disconnecting the connectors.
CautionBe sure that all mounting screws, terminal screws, and cable con-nector screws are tightened to the torque specified in this manual.Incorrect tightening torque may result in malfunction.
CautionLeave the dust protective label attached to the Unit when wiring. Removing the dust protective label may result in malfunction.
CautionRemove the dust protective label after the completion of wiring to ensure proper heat dissipation. Leaving the dust protective label attached may result in malfunc-tion.
CautionUse crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
CautionDouble-check all theIncorrect wiring may
CautionWire correctly. Incorrect wiring may
CautionMount the Unit only
CautionBe sure that the termitems with locking deImproper locking ma
CautionConfirm that no advchanging the operatNot doing so may re
CautionResume operation ocontents of the VR aNot doing so may re
CautionWhen replacing partpart is correct. Not doing so may re
Safety
HARD 5
Revision 5.0
precautions
erating in RUN mode when the power is ASIC program is set to Auto Run mode.
tatus-Words” of each GRT1-ML2 coupler.d to missing or incorrect I/O data.
atus of the connected MECHATROLINK-II program.sult in an unexpected operation.
is developed to exchange I/O data between and a CANopen network. t able to exchange motion commands. to exchange motion commands may result in n.
rly. of the unit may result in malfunction.
TJ1-TER supplied with the TJ1-MC__ to the
is properly mounted, the TJ1 will not function
warnings and precautions
WARE REFERENCE MANUAL
1.6 Unit assembly
CautionDo not pull on the cables or bend the cables beyond their natural limit. Doing so may break the cables.
CautionBefore touching the system, be sure to first touch a grounded metallic object in order to discharge any static build-up. Otherwise it might result in a malfunction or damage.
CautionUTP cables are not shielded. In environments that are subject to noise use a system with shielded twisted-pair (STP) cable and hubs suitable for an FA environment. Do not install twisted-pair cables with high-voltage lines.Do not install twisted-pair cables near devices that generate noise.Do not install twisted-pair cables in locations that are subject to high humidity.Do not install twisted-pair cables in locations subject to excessive dirt and dust or to oil mist or other contaminants.
CautionUse the dedicated connecting cables specified in operation manu-als to connect the Units.Using commercially available RS-232C computer cables may cause failures in external devices or the Motion Control Unit.
CautionOutputs may remain on due to a malfunction in the built-in transis-tor outputs or other internal circuits.As a countermeasure for such problems, external safety measures must be provided to ensure the safety of the system.
CautionThe TJ1 will start opturned on and if a B
CautionAlways check the “SNot doing so can lea
CautionAlways check the stdevices in a BASIC Not doing so may re
CautionThe TJ1-CORT unitthe Trajexia system The TJ1-CORT is noUsing the TJ1-CORTunexpected operatio
CautionInstall the unit propeImproper installation
CautionBe sure to mount theright most Unit.Unless the TJ1-TERproperly.
Safety
HARD 6
Revision 5.0
1.7
1.7.1
The c
EMCOMREMCmachstandused EMCDireccondiare inthat d
Low Alway1,500
1.7.2
The TTo enwith E1. T2. R
p
warnings and precautions
WARE REFERENCE MANUAL
Conformance to EC Directives Conformance
Concepts
oncepts for the directives EMC and Low Voltage are as follows:
DirectivesON devices that comply with EC Directives also conform to the related standards so that they can be more easily built into other devices or ines. The actual products have been checked for conformity to EMC ards. Whether the products conform to the standards in the system by the customer, however, must be checked by the customer. -related performance of the OMRON devices that comply with EC tives will vary depending on the configuration, wiring, and other tions of the equipment or control panel in which the OMRON devices stalled. The customer must, therefore, perform final checks to confirm evices and the over-all machine conform to EMC standards.
Voltage Directives ensure that devices operating at voltages of 50 to 1,000 VAC or 75 to VDC meet the required safety standards.
Conformance to EC Directives
rajexia Motion Controllers comply with EC Directives.sure that the machine or device in which a system is used complies C directives, the system must be installed as follows:
he system must be installed within a control panel.einforced insulation or double insulation must be used for the DC ower supplies used for the communications and I/O power supplies.
Syste
HARD 7
Revision 5.0
2
2.1fig. 1The s
• S• C• P• M• M
A cleneces
2.1.1
MotiThe M
ServDefinperioavaila
CyclIs theMC__"CPUSERV
CPUThe o
AXIS TYPEAXIS TYPE
OL LOOP
Servo Driver
MOTORPosition
LoopPosition
LoopSpeed LoopSpeed Loop
Torque Loop
Torque Loop
Servo Driver
MOTOR
ENC
Speed Loop
Torque Loop
ENC
AXIS TYPE
J1 ML__-
J1 FL02-
All otherServo Drivers
CPU t
First C
m philosophy
WARE REFERENCE MANUAL
System philosophy
Introductionystem philosophy is centred around the relationship between: ystem architectureycle timerogram control and multi-taskingotion sequence and axesotion buffers
ar understanding of the relationship between these concepts is sary to obtain the best results for the Trajexia system.
Glossary
on sequence otion Sequence is responsible for controlling the position of the axes.
o period es the frequency at which the Motion Sequence is executed. The servo d must be set according to the configuration of the physical axes. The ble settings are 0.5ms, 1ms or 2ms.
e time time needed to execute one complete cycle of operations in the TJ1-. The cycle time is divided in 4 time slices of equal time length, called Tasks". The cycle time is 1ms if SERVO_PERIOD=0.5ms or O_PERIOD=1ms and 2ms if the SERVO_PERIOD=2ms.
tasks perations executed in each CPU task are:
AXIS CONTR
Position Loop
Position Loop
Buffer & profile
gererator
Buffer & profile
gererator
Via
Program Buffer
BASIC PROGRAMSProcess 1
Process 2
Process 3
…
Process 14
Comms
TJ1-MC__
T
T
EthernetFINS
Ethernet
TJ1 PRT-
MC I/O
Profibus
BUILT-IN TJ1-ML16
ask Operation
PU task Motion SequenceLow priority process
Syste
HARD 8
Revision 5.0
ProgA pro
ProcIs a pare Lprocenumbassig
2.2The T1. P2. C3. E
This sBASI
CoorPositcoordconnecoord
The edefineuse o
Secon
Third
Fourth
CPU t
m philosophy
WARE REFERENCE MANUAL
ram gram is a piece of BASIC code.
ess rogram in execution with a certain priority assigned. Process 0 to 12 ow priority processes and Process 13 and 14 are High priority sses. First the process priority, High or Low, and then the process er, from high to low, will define to which CPU task the process will be ned.
Motion control conceptsJ1-MC__ offers these types of positioning control operations:oint-to-Point (PTP) controlontinuous Path (CP) controllectronic Gearing (EG) control.
ection introduces some of the commands and parameters used in the C programming of the motion control application.
dinate systemioning operations performed by the TJ1-MC__ are based on an axis inate system. The TJ1-MC__ converts the position data from either the cted Servo Driver or the connected encoder into an internal absolute inate system.
ngineering unit that specifies the distances of travelling can be freely d for each axis separately. The conversion is performed through the f the unit conversion factor, which is defined by the UNITS axis
d CPU task High priority process
CPU task Motion Sequence (only if SERVO_PERIOD=0.5ms)LED UpdateHigh priority process
CPU task External Communications
ask Operation
Syste
HARD 9
Revision 5.0
paramusingto zer
fig. 2A motakespoint.that isof relmove
2.2.1
In poaxis. • R• A• C• C
50 100A
MOVE(50)
MOVEABS(50)
MOVE(60)
MOVEABS(30)
m philosophy
WARE REFERENCE MANUAL
eter. The origin point of the coordinate system can be determined the DEFPOS command. This command re-defines the current position o or any other value.
ve is defined in either absolute or relative terms. An absolute move the axis (A) to a specific predefined position with respect to the origin A relative move takes the axis from the current position to a position defined relative to this current position. The figure shows an example
ative (command MOVE) and absolute (command MOVEABS) linear s.
PTP control
int-to-point positioning, each axis is moved independently of the other The TJ1-MC__ supports the following operations:elative movebsolute moveontinuous move forwardontinuous move reverse.
0
MOVE(30)
Syste
HARD 10
Revision 5.0
Relafig. 3To mo
commmoveSuppno. 0paramdecel1 willAt stasamemove
The mreleva/i
Definfig. 4The s
the timdefineto 10 to zerrate hdistansegmthe sp
50 100 A
MOVEABS(100) AXIS(0)MOVEABS(50) AXIS(1)
Param
UNITS
ACCE
DECE
SPEE
3 4 5 6A
ACCEL=10DECEL=10SPEED=10MOVE(40)
m philosophy
WARE REFERENCE MANUAL
tive and absolute movesve a single axis either the command MOVE for a relative move or the and MOVEABS for an absolute move is used. Each axis has its own characteristics, which are defined by the axis parameters.ose a control program is executed to move from the origin to an axis (A) coordinate of 100 and axis no. 1 (B) coordinate of 50. If the speed
eter is set to be the same for both axes and the acceleration and eration rate are set sufficiently high, the movements for axis 0 and axis be as shown in the figure.rt, both the axis 0 and axis 1 moves to a coordinate of 50 over the duration of time. At this point, axis 1 stops and axis 0 continues to to a coordinate of 100.
ove of a certain axis is determined by the axis parameters. Some nt parameters are:
ing movespeed profile in this figure shows a simple MOVE operation. Axis A is e, axis B is the speed. The UNITS parameter for this axis has been
d for example as meters. The required maximum speed has been set m/s. In order to reach this speed in one second and also to decelerate o speed again in one second, both the acceleration as the deceleration ave been set to 10 m/s2. The total distance travelled is the sum of ces travelled during the acceleration, constant speed and deceleration ents. Suppose the distance moved by the MOVE command is 40 m, eed profile is given by the figure.
0
50
B
eter Description
Unit conversion factor
L Acceleration rate of an axis in units/s2
L Deceleration rate of an axis in units/s2
D Demand speed of an axis in units/s2
0
10
1 2
B
Syste
HARD 11
Revision 5.0
fig. 5The taccelA is t
fig. 6
MoveThe fthe a• T• T• T• T
/i
3 4 5 6A
ACCEL=5DECEL=10SPEED=10MOVE(40)
3 4 5 6A
ACCEL=10DECEL=5SPEED=10MOVE(40)
Accele
m philosophy
WARE REFERENCE MANUAL
wo speed profiles in these figures show the same movement with an eration time respectively a deceleration time of 2 seconds. Again, Axis he time, axis B is the speed.
calculationsollowing equations are used to calculate the total time for the motion of xes.he moved distance for the MOVE command is D.he demand speed is V.he acceleration rate is a.he deceleration rate is d.
0
10
1 2
B
0
10
1 2
B
ration time =
Syste
HARD 12
Revision 5.0
ContThe FcontinFORWREVEaxis pand dBoth RAPIaxis aset by
2.2.2
Contistart aMC__• L• C• C
Accele
Decel
Decel
Const
Total t
m philosophy
WARE REFERENCE MANUAL
inuous movesORWARD and REVERSE commands can be used to start a uous movement with constant speed on a certain axis. The ARD command moves the axis in positive direction and the RSE command in negative direction. For these commands also the arameters ACCEL and SPEED apply to specify the acceleration rate emand speed.movements can be cancelled by using either the CANCEL or DSTOP command. The CANCEL command cancels the move for one nd RAPIDSTOP cancels moves on all axes. The deceleration rate is DECEL.
CP control
nuous Path control enables to control a specified path between the nd end position of a movement for one or multiple axes. The TJ1- supports the following operations:
inear interpolationircular interpolationAM control.
ration distance =
eration time =
eration distance =
ant speed distance =
ime =
Syste
HARD 13
Revision 5.0
Linefig. 7In ap
operamoveMOVcommmoveConscorremotioSPEEtakencommA is t
A
1
2
m philosophy
WARE REFERENCE MANUAL
ar interpolationplications it can be required for a set of motors to perform a move tion from one position to another in a straight line. Linearly interpolated s can take place among several axes. The commands MOVE and EABS are also used for the linear interpolation. In this case the ands will have multiple arguments to specify the relative or absolute for each axis.ider the three axis move in a 3-dimensional plane in the figure. It sponds to the MOVE(50,50,50) command. The speed profile of the n along the path is given in the diagram. The three parameters D, ACCEL and DECEL that determine the multi axis movement are from the corresponding parameters of the base axis. The MOVE and computes the various components of speed demand per axis.
he time axis, B is the speed axis.
B
3
Syste
HARD 14
Revision 5.0
Circufig. 8It ma
in an circulCons100,0trajecspecirotatioand Sprofile
CAMfig. 9Addit
to dean axThe sparamThe faxis,
2.2.3
Electlinkedopera• E• L• L• A
0 50
50
A
B
m philosophy
WARE REFERENCE MANUAL
lar interpolationy be required that a tool travels from the starting point to the end point arc of a circle. In this instance the motion of two axes is related via a ar interpolated move using the MOVECIRC command.ider the diagram in the figure. It corresponds to the MOVECIRC(-,-50,0,0) command. The centre point and desired end point of the tory relative to the start point and the direction of movement are fied. The MOVECIRC command computes the radius and the angle of n. Like the linearly interpolated MOVE command, the ACCEL, DECEL PEED variables associated with the base axis determine the speed along the circular move.
control
ional to the standard move profiles the TJ1-MC__ also provides a way fine a position profile for the axis to move. The CAM command moves is according to position values stored in the TJ1-MC__ Table array. peed of travelling through the profile is determined by the axis eters of the axis.
igure corresponds to the command CAM(0,99,100,20). A is the time B is the position axis.
EG control
ronic Gearing control allows you to create a direct gearbox link or a move between two axes. The MC Unit supports the following tions.lectronic gearboxinked CAMinked movedding axes
-50
Syste
HARD 15
Revision 5.0
Elecfig. 10The T
thereCONto linkIn the/i
A
2:11:1
1:2Axes
m philosophy
WARE REFERENCE MANUAL
tronic gearboxJ1-MC__ is able to have a gearbox link from one axis to another as if
is a physical gearbox connecting them. This can be done using the NECT command in the program. In the command the ratio and the axis to are specified. figure, A is the Master axis, and B is the CONNECT axis.
B
Ratio CONNECT command
0 1
1:1 CONNECT(1,0) AXIS(1)
2:1 CONNECT(2,0) AXIS(1)
1:2 CONNECT(0.5,0) AXIS(1)
Syste
HARD 16
Revision 5.0
Linkfig. 11Next
link thCAMaxis pconneIn thepositi
Linkfig. 12The M
masteconstbe paThe lA. TB. SC. MD. SE. M
A
B
A
E
D
m philosophy
WARE REFERENCE MANUAL
ed CAM controlto the standard CAM profiling tool the TJ1-MC__ also provides a tool to e CAM profile to another axis. The command to create the link is called
BOX. The travelling speed through the profile is not determined by the arameters of the axis but by the position of the linked axis. This is like cting two axes through a cam. figure, A is the Master axis (0) position, and B is the CAMBOX Axis (1) on.
ed moveOVELINK command provides a way to link a specified move to a r axis. The move is divided into an acceleration, deceleration and
ant speed part and they are specified in master link distances. This can rticularly useful for synchronizing two axes for a fixed period.abels in the figure are:ime axis.peed axis.aster axis (1).ynchronized.OVELINK axis (0).
B
C
Syste
HARD 17
Revision 5.0
Addifig. 13It is v
possilinkedusingof all masteIn the
A
A
A
BASE(0)ADDAX(2)FORWARDMOVE(100) AXIS(2)MOVE(-60) AXIS(2)
m philosophy
WARE REFERENCE MANUAL
ng axesery useful to be able to add all movements of one axis to another. One ble application is for instance changing the offset between two axes by an electronic gearbox. The TJ1-MC__ provides this possibility by the ADDAX command. The movements of the linked axis will consists movements of the actual axis plus the additional movements of the r axis. figure, A is the time axis and B is the speed axis.
B
B
B
Syste
HARD 18
Revision 5.0
2.2.4
CancIn nothe cucommcurre
OrigThe eincreman orwhereorigin
PrintThe Teventrisinginput,positipositiREGIThe poverhthe a
m philosophy
WARE REFERENCE MANUAL
Other operations
elling movesrmal operation or in case of emergency it can be necessary to cancel rrent movement from the buffers. When the CANCEL or RAPIDSTOP ands are given, the selected axis respectively all axes will cancel their
nt move.
in searchncoder feedback for controlling the position of the motor is ental. This means that all movement must be defined with respect to
igin point. The DATUM command is used to set up a procedure by the TJ1-MC__ goes through a sequence and searches for the
based on digital inputs and/or Z-marker from the encoder signal.
registrationJ1-MC__ can capture the position of an axis in a register when an occurs. The event is referred to as the print registration input. On the or falling edge of an input signal, which is either the Z-marker or an the TJ1-MC__ captures the position of an axis in hardware. This on can then be used to correct possible error between the actual on and the desired position. The print registration is set up by using the ST command.osition is captured in hardware, and therefore there is no software ead and no interrupt service routines, eliminating the need to deal with ssociated timing issues.
Syste
HARD 19
Revision 5.0
Mergfig. 14If the
a subof twoIn the
JoggJoggioperaRefer
2.3The sbriefly
2.3.1
The sloop sof thetarge
MERGE=0
MERGE=1
A
A
m philosophy
WARE REFERENCE MANUAL
ing moves MERGE axis parameter is set to 1, a movement is always followed by sequent movement without stopping. The figures show the transitions moves with MERGE value 0 and value 1. figure, A is the time axis and B is the speed axis.
ingng moves the axes at a constant speed forward or reverse by manual tion of the digital inputs. Different speeds are also selectable by input. to the FWD_JOG, REV_JOG and FAST_JOG axis parameters.
Servo system principleservo system used by and the internal operation of the TJ1-MC__ are described in this section.
Semi-closed loop system
ervo system of the TJ1-MC__ uses a semi-closed or inferred closed ystem. This system detects actual machine movements by the rotation motor in relation to a target value. It calculates the error between the t value and actual movement, and reduces the error through feedback.
B
B
Syste
HARD 20
Revision 5.0
2.3.2fig. 15Inferr
systeshow1. T
cob
2. TdaS
3. Tcop
4. Tfew
The lA. TB. SC. DD. PE. SF. SG. MH. EI. MJ. M
2.3.3
The sreferemotio
B
D
J
I
E F G
H
23
4
m philosophy
WARE REFERENCE MANUAL
Internal operation of the TJ1-MC__
ed closed loop systems occupy the mainstream in modern servo ms applied to positioning devices for industrial applications. The figure s the basic principle of the servo system as used in the TJ1-MC__.he TJ1-MC__ performs actual position control. The main input of the ntroller is the Following Error, which is the calculated difference
etween the demand position and the actual measured position.he Position Controller calculates the required speed reference output etermined by the Following Error and possibly the demanded position nd the measured position. The speed reference is provided to the ervo Driver.he Servo Driver controls the rotational speed of the servo motor rresponding to the speed reference. The rotational speed is
roportional to the speed reference.he rotary encoder generates the feedback pulses for both the speed edback within the Servo Driver speed loop and the position feedback ithin the TJ1-MC__ position loop.
abels in the figure are:J1-MC__.ervo system.emand position.osition control.peed reference.peed control.otor.ncoder.easured speed.easured position.
Motion control algorithm
ervo system controls the motor by continuously adjusting the speed nce to the Servo Driver. The speed reference is calculated by the n control algorithm of the TJ1-MC__, which is explained in this section.
A
C 1
Syste
HARD 21
Revision 5.0
fig. 16The mpositiThe FpositiErrorgain vcorreC is t• P
TFOApaca
• InToOInsyin
• DTchinODto
• OTthO
C
D
∑
∑
Kp
Ki
Kd
Kvff
Kov ∆∆
m philosophy
WARE REFERENCE MANUAL
otion control algorithm uses the demand position (A), the measured on (D) and the Following Error (B) to determine the speed reference. ollowing Error is the difference between the demanded and measured on. The demand position, the measured position and the Following are represented by the axis parameters MPOS, DPOS and FE. Five alues have been implemented for the user to be able to configure the
ct control operation for each application.he output signal.roportional gainhe proportional gain Kp creates an output Op that is proportional to the ollowing Error E.p = Kp · Ell practical systems use proportional gain. For many just using this gain rameter alone is sufficient. The proportional gain axis parameter is lled P_GAIN.tegral gainhe integral gain Ki creates an output Oi that is proportional to the sum f the Following Errors that have occurred during the system operation.i = Ki · ΣEtegral gain can cause overshoot and so is usually used only on stems working at constant speed or with slow accelerations. The tegral gain axis parameter is called I_GAIN.erivative gainhe derivative gain Kd produces an output Od that is proportional to the ange in the Following Error E and speeds up the response to changes error while maintaining the same relative stability.d = Kd · ∆Eerivative gain may create a smoother response. High values may lead oscillation. The derivative gain axis parameter is called D_GAIN.utput speed gainhe output speed gain Kov produces an output Oov that is proportional to e change in the measured position Pm and increases system damping.ov = Kov · ∆Pm
A B
Syste
HARD 22
Revision 5.0
Tgca
• STpFOTmg
The dFract/i
2.4The sconce• P• M• M• C• P
Thesparamdiffere
ork in a defined way. The programs are written C and control the application of the axes and e executed in parallel. The programs can be set tarted and stopped from other programs and . s to move the axes, control inputs and outputs BASIC commands.
ls the position of all 16 axes with the actions as
rsured Position (MPOS)anded Position (DPOS)opce
tween the BASIC commands and the Axis motion command is executed, the command is uring the next motion sequence, the profile ment according to the information in the buffer.ed, the motion command is removed from the
out in the forth CPU task. A set of BASIC re used to configure the communications. unication slave (as in the PROFIBUS essary to configure the communication in an
Gain
Propo
Integr
Deriva
Outpu
Speed
m philosophy
WARE REFERENCE MANUAL
he output speed gain can be useful for smoothing motions but will enerate high Following Errors. The output speed gain axis parameter is lled OV_GAIN.
peed feed forward gainhe speed feedforward gain Kvff produces an output Ovff that is roportional to the change in demand position Pd and minimizes the ollowing Error at high speed.vff = Kvff · ∆Pdhe parameter can be set to minimise the Following Error at a constant achine speed after other gains have been set. The speed feed forward ain axis parameter is called VFF_GAIN.
efault settings are given in the table along with the resulting profiles. ional values are allowed for gain settings.
Trajexia system architecture ystem architecture of the Trajexia is dependant upon thesepts:
rogram control otion Sequence otion buffers ommunicationeripherals
e concepts depend upon the value set in the SERVO_PERIOD eter. The relationship between the value of SERVO_PERIOD and the nt concepts of the system architecture are describes as follows.
2.4.1 Program control
Programs make the system win a language similar to BASImodules. 14 Programs can bto run at system power-up, sexecuted from Trajexia ToolsPrograms execute commandand make communication via
2.4.2 Motion sequence
The motion sequence controfollows: • Reading the Motion buffe• Reading the current Mea• Calculating the next Dem• Executing the Position lo• Sending the Axis referen• Error handling
2.4.3 Motion buffers
Motion buffers are the link becontrol loop. When a BASIC stored in one of the buffers. Dgenerator executes the moveWhen the movement is finishbuffer.
2.4.4 Communication
All communication is carried communication commands aWhen the Trajexia is a commcommunication) it is only nec
Default value
rtional gain 0.1
al gain 0.0
tive gain 0.0
t speed gain 0.0
feedforward gain 0.0
Syste
HARD 23
Revision 5.0
initiala tranBASI
2.4.5
All inpAOUTrajeBASIoutpu
2.5fig. 17All pr
time i• 2• 5
The pSERV
fig. 18The o
Cycle time = 1ms2 3 4
Cycle time = 2 ms2 3 4
CPU t
First C
Secon
Third
Fourth
m philosophy
WARE REFERENCE MANUAL
task. The values are exchanged from the configured global variables in sparent way. When the Trajexia is a communications master, the C communication commands are used to write and read.
Peripherals
uts and outputs are used with the set of parameters (IN, OP, AIN, T). The inputs and outputs are automatically detected and mapped in xia. Inverters are considered a peripheral device and have a set of C commands to control them. Various MECHATROLINK-II input and t modules can be connected to a TJ1-ML__ unit.
Cycle time ocesses in the Trajexia system are based on the cycle time. The cycle s divided into four CPU tasks:50µs time intervals for a SERVO_PERIOD of 0.5 and 1.0ms00µs time intervals for a SERVO_PERIOD of 2.0ms
rocesses that can be carried out in each time interval depends on the O_PERIOD that is set.perations executed in each CPU task are:
250µs
1
500 µs
1
ask Operation
PU task Motion SequenceLow priority process
d CPU task High priority process
CPU task 1 Motion Sequence (only if SERVO_PERIOD=0.5ms)LED Update.High priority process
CPU task External Communications
NoteThe Motion sequence execution depends on setting of the SERVO_PERIOD parameter.
Syste
HARD 24
Revision 5.0
2.5.1
The Splaceparammust The fafter
Examfig. 19The S
execuMotion sequenceLow priority task (0,1,2,3...)
High priority task (13,14)
LED refreshHigh priority task (13,14)Communication
Motion sequence 1ms
m philosophy
WARE REFERENCE MANUAL
Servo period
ERVO_PERIOD can be set at 0.5, 1 or 2ms. The processes that take within the cycle time depend on the setting of the SERVO_PERIOD eter. The SERVO_PERIOD parameter is a Trajexia parameter that
be set according to the system configuration. actory setting is 1ms (SERVO_PERIOD=1000). A change is set only a restart of the TJ1-MC__.
ple 1ERVO_PERIOD has a value of 0.5ms and the motion sequence is ted every 0.5ms.
NoteOnly the Sigma-III Servo Driver and the Sigma-V Servo Driver support the 0.5 ms transmission cycle.
CPU task 1
CPU task 2
CPU task 3
CPU task 4
Syste
HARD 25
Revision 5.0
Examfig. 20The S
executask 3run fa
Examfig. 21The S
execu
ServThe ndeterThereTJ1-M• S
T• In
T• I/
Ta
You mparaman incThe mtable SERV
Motion sequenceLow priority task (0,1,2,3...)
High priority task (13,14)
LED refreshHigh priority task (13,14)
Communication
1ms
Motion sequenceLow priority task (0,1,2,3...)
High priority task (13,14)
LED refreshHigh priority task (13,14)
Communication
2ms
m philosophy
WARE REFERENCE MANUAL
ple 2ERVO_PERIOD has a value of 1ms and the motion sequence is ted every 1ms. As the motion sequence is not executed during CPU , there is more time for the program execution. High priority programs ster.
ple 3ERVO_PERIOD has a value of 2ms and the motion sequence is ted every 2.0ms.
o period rulesumber of axes and MECHATROLINK-II devices in the Trajexia system mines the value of the SERVO_PERIOD system parameter. are 3 types of MECHATROLINK-II devices that are supported by the C__ units:
ervo Drivershe TJ1-MC__ considers Servo Drivers as axes.vertershe TJ1-MC__ does not consider Inverters as axes.O units and slice bus couplershe TJ1-MC__ does not consider I/O units (analog and digital, counter nd pulse) and slice bus couplers as axes.
ust obey the most restrictive rules when you set the SERVO_PERIOD eter. An incorrect value of the SERVO_PERIOD parameter results in orrect detection of the MECHATROLINK-II devices.ost restrictive rules are given in the tables below. For each unit the
lists the maximum number of devices the unit can control at the given O_PERIOD setting.
CPU task 1
CPU task 2
CPU task 3
CPU task 4
CPU task 1
CPU task 2
CPU task 3
CPU task 4
Syste
HARD 26
Revision 5.0
/i
Conf
Examfig. 22• 1
• 1• 3• S
TJ1-MTJ1-MSigm
SERV
0.5 m
1.0 m
2.0 m
ddress43
Axis 2 Axis 3 Axis 4
Address44
Address45
Terminator
Servo Driver
m philosophy
WARE REFERENCE MANUAL
iguration examples
ple 1x TJ1-MC__x TJ1-ML__x Sigma-II Servo DriverERVO_PERIOD = 1ms
C__ Supports 0.5ms SERVO_PERIOD with 3 axes.C__ Supports 0.5ms SERVO_PERIOD with 3 devices.
a-II supports 1ms SERVO_PERIOD. This is the limiting factor.
O_PERIOD TJ1-MC16 TJ1-MC04 TJ1-ML16 TJ1-ML04
s 8 axes 5 axes 4 devices 4 devices
4 non-axis devices
4 non-axis devices
s 16 axes 5 axes 8 devices 4 devices
8 non-axis devices
8 non-axis devices
s 16 axes 5 axes 16 devices 4 devices
8 non-axis devices
8 non-axis devices
A
Syste
HARD 27
Revision 5.0
Examfig. 23• 1
• 2• 1• S
TJ1-MTJ1-MSigm
3
11
Axis 4
Axis 12
Axis 5
Axis 13
Axis 6
Axis 14
Axis 7
Axis 15
ess Address 4D
Address 4E
Address 4F
Address 50
Terminator
Servo Drive
ess Address 45
Address 46
Address 47
Address 48
Terminator
m philosophy
WARE REFERENCE MANUAL
ple 2x TJ1-MC16x TJ1-ML166x Sigma-II Servo DriverERVO_PERIOD = 1ms
C16 supports 1ms SERVO_PERIOD with 16 axes. L16 supports 1ms SERVO_PERIOD with 8 devices.
a-II supports 1ms SERVO_PERIOD.
Address 49
Axis 0
Axis 8
Axis 1
Axis 9
Axis 2
Axis 10
Axis
Axis
Address 4A
Address 4B
Addr4C
Address 41
Address 42
Address 43
Addr44
Syste
HARD 28
Revision 5.0
Examfig. 24• 1
• 1• 8• 1• 3• S
TJ1-MlimitinSigmSI-T sMEC
Exam
fig. 25• 1• 1• 2• 1• 5• S
TJ1-MMECTJ1-MTJ1-FSigm
Address 41
Address 42
Address 43
Address 44
Address 45
Address 46
Address 47
Address 48
Address44
Address45
Address46
Address47
Axis 8Axis 7 Axis 1Axis 0
Axis 3 Axis 4 Axis 5 Axis 6
m philosophy
WARE REFERENCE MANUAL
ple 3x TJ1-MC16x TJ1-ML16x Sigma-II Servo Driverx F7Z Inverter with SI-T interfacex MECHATROLINK-II I/OsERVO_PERIOD = 2.0ms
L16 supports 2.0ms SERVO_PERIOD with 12 devices. This is the g factor.a-II supports 1.0ms SERVO_PERIOD.upports 1ms.
HATROLINK-II I/Os support 1.0ms.
ple 4
x TJ1-MC16x TJ1-ML16x TJ1-FL02x TJ1-PRT (does not influence in the SERVO_PERIOD)x Sigma-II Servo DriverERVO_PERIOD = 1.0ms
C16 supports 1.0ms SERVO_PERIOD with 9 axes (5 HATROLINK-II servo axes and 4 TJ1-FL02 axes)
L16 supports 1.0ms SERVO_PERIOD with 5 devicesL02 supports 0.5ms SERVO_PERIOD (2 axes each module)
a-II supports 1.0ms SERVO_PERIOD.
Address 61
Address 21
Address 62
Address 63
I/O Memory Allocations
0 31 32 95 96 159 160
Address43
Axis 2
Syste
HARD 29
Revision 5.0
2.6The T
2.6.1
The TprogrProce
2.6.2
The lToolsTJ1-Mafter
2.6.3fig. 26 Each
in theMotioTask High
fig. 27ExterupdaTrajeIn conavailataskstime aslot o
T #1 HT #2
Cycle time
COMS.
T #1 HT #2
Cycle time
COMS.
B
m philosophy
WARE REFERENCE MANUAL
Program control and multi-taskingrajexia system has program, processes and multi tasking control.
Program control
rajexia system can control 14 processes that are written as BASIC ams. When the program is set to run, the program is executed.sses 1 to 12 are low priority, 13 and 14 are high priority.
Processes
ow-priority process 0 is reserved for the "Terminal Window" of Trajexia . This terminal window is used to write direct BASIC commands to the C__ independent to other programs. These commands are executed
you press the Enter button.
Multi-tasking
cycle time is divided into 4 time slices called CPU tasks. Processes run first 3 CPU tasks according to the priority of the process.n sequence and low-priority processes (A) are executed in the Low (LT) period. priority processes (B) are executed in the high Task (HT) periods.
nal communication that are not related to the motion network are ted in the communications (COMS) period in the fourth CPU task. xia can control up to 14 programs at the same time. trast to low priority processes, a high priority process is always ble for execution during two of the four CPU tasks. The high-priority
are executed faster than the low-priority tasks, it is that they have more vailable for their execution. All the low-priority tasks must share one
f time and the high-priority task have their own two slots of time.
LT H
LT H
A
Syste
HARD 30
Revision 5.0
2.6.4fig. 28In the
HT pefor prthe LTIn theperio0 areIn theHT peused
2.7fig. 29Motio
actuaThe aTraje• T
is• T
(S
All noATYPEvery
The mperio
3
COMS. COMS.1411ms
140 (c/l)
1ms
COMS.
2 COMS. COMS.1 0 (c/l) 3 COMS.
1ms
2 1 0 (c/l)
1ms
COMS. COMS.11ms
0 (c/l)
1ms
COMS.14 1314 13
block
Speedcommand
Speedcommand
Speed loop
ON
OFFTorqueloop
M
E
Servo Drive
m philosophy
WARE REFERENCE MANUAL
Multi-tasking example
example 1, there are two high-priority processes, 13 and 14. The two riods are reserved for these processes, one for processes 13 and one
ocesses 14. The low-priority processes 3, 2, 1 and 0 are executed in period, one process per Cycle time here set to 1.0ms. middle example, there is only one high-priority process, 14. Both HT ds are reserved for this process. The low-priority processes, 3, 2, 1 and executed in the LT period, one process per cycle time. lower example, there are no high-priority processes. Therefore, the riods can be used for the low-priority processes. The LT period is also for the low-priority processes.
Motion sequence and axesn sequence is the part of the TJ1-MC__ that controls the axes. The l way that the motion sequence operates depends on the axis type. xis type can be set and read by the parameter ATYPE. At start-up the
xia system automatically detects the configuration of the axes. he default value for the parameter ATYPE for MECHATROLINK-II axes 41 (MECHATROLINK-II speed).he default value for the parameter ATYPE for the TJ1-FL02 axes is 44 ervo axis with an incremental encoder).
n allocated axes are set as a virtual axis. The value for the parameter E is 0. axis has the general structure as shown in fig. 29.
otion sequence which will be executed at the beginning of each servo d will contain the following elements:
2
3
14 114 13
143 COMS.
1ms
1421ms
3 2 1 COMS.
1ms
0 (c/l) 31ms
13 COMS.
1ms
21ms
•
•
Profile generatorProfile generator
+
-
Position loop
Demandedposition
Measuredposition
Followingerror
+
-
Position loop
Demandedposition
Measuredposition
Followingerror
AXIS PARAMETER
Syste
HARD 31
Revision 5.0
1. Tse
2. R3. L4. C5. C6. E
co7. U
2.7.1fig. 30The p
for eaThe pprogr
2.7.2
The pdevia(DPO
2.7.3
• Tdaco
Profile generator
Demand Position
m philosophy
WARE REFERENCE MANUAL
ransfer any moves from BASIC process buffers to motion buffers (see ction 2.8).
ead digital inputs.oad moves. (See note.)alculate speed profile. (See note.)alculate axis positions. (See note.)xecute position servo. For axis 0 this also includes the Servo Driver mmunications. (See note.)
pdate outputs.
Profile generator
rofile generator is the algorithm that calculates the demanded position ch axis. The calculation is made every motion sequence.rofile is generated according to the motion instructions from the BASIC ams.
Position loop
osition loop is the algorithm that makes sure that there is a minimal tion between the measured position (MPOS) and the demand position S) of the same axis.
Axis sequence
he motion controller applies motion commands to an axis array that is efined with the BASE command. If the motion command concerns one xis, it is applied to the first axis in the BASE array. If the motion mmand concerns more than one axis, and makes an orthogonal
NoteEach of these items will be performed for each axis in turn before moving on to the next item.
Basic Program..................MOVE(1000)..................
Syste
HARD 32
Revision 5.0
mBdP
• Ifig
• IfF---
2.7.4/i
ATYP
0
40
41
42
m philosophy
WARE REFERENCE MANUAL
ove, the axes are taken from the array in the order defined by the ASE command. For more information on the BASE command and the efinition of the axis sequence in an axis array, refer to the Trajexia rogramming Manual, chapter 3 (BASIC commands). SERVO=OFF for one axis, the motion commands for that axis are nored. the Following Error (FE) in one axis exceeds the parameter value ELIMIT, the next action occurs:
WDOG is set to OFF and all axes stop.SERVO for the axis that causes the error goes to OFF.The current move is cancelled and removed from the buffer.
Type of axis
E Applicable to Name Description
All axes Virtual axis Internal axis with no physical output. It is the only valid setting for non-allocated axes. That is, those that are not MECHATROLINK-II ser-vos or a flexible axis.
MECHATRO-LINK-II Servo Drivers con-nected to a TJ1-ML__
MECHATRO-LINK-II Posi-tion
Position loop in the Servo Driver. TJ1-MC__ sends position reference to the Servo Driver via MECHATROLINK-II.
MECHATRO-LINK-II Speed (Default)
Position loop in the Trajexia. TJ1-MC__ sends speed reference to the Servo Driver via MECHATROLINK-II.
MECHATRO-LINK-II Torque
Position loop in the Trajexia. TJ1-MC__ sends torque reference to the Servo Driver via MECHATROLINK-II.
Syste
HARD 33
Revision 5.0
Virtufig. 31You c
assigBASI
43
44
45
46
47
48
49
ATYP
ator
EASUREDOSITION
DEMANDPOSITION
=
m philosophy
WARE REFERENCE MANUAL
al axis ATYPE=0 an split a complex profile into two or more simple movements, each ned to a virtual axis. These movements can be added together with the C command ADDAX then assigned to a real axis.
External driver connected to a TJ1-FL02
Stepper output Pulse and direction outputs. Position loop is in the driver. TJ1-FL02 sends pulses and receives no feed back.
Servo axis (Default) Encoder
Analogue servo. Position loop is in the TJ1-MC__. The TJ1-FL02 sends speed reference and receives position from an incremental encoder.
Encoder out-put
The same as stepper, but with the phase differ-ential outputs emulating an incremental encoder.
Absolute Tam-agawa
The same as servo axis but the feed back is received from a Tamagawa absolute encoder.
Absolute EnDat
The same as servo axis but the feed back is received from an EnDat absolute encoder.
Absolute SSI The same as servo axis but the feed back is received from an SSI absolute encoder.
ML__ Inverter as axis
Inverters (with built-in encoder interface) are controlled on the MECHATROLINK-II bus as servo axes.
E Applicable to Name Description
Profile gener
MP
Syste
HARD 34
Revision 5.0
MECfig. 32With
settinthe S
MECfig. 33With
SpeerecomcompWith 0x400recom
ME
TJ1-ML__ SERVO
SERVO = OFFML-II
Positioncommand
owingrror
Speedcommand
Position Loop
Speed Loop
Torque Loop
SERVO
ME
SERVO = OFF
TJ1-ML__
Speedcommand
ML-IISpeed
commandSpeed Loop
Torque Loop
m philosophy
WARE REFERENCE MANUAL
HATROLINK-II position ATYPE=40 SERVO = ON, the position loop is closed in the Servo Driver. Gain gs in the TJ1-MC__ have no effect. The position reference is sent to ervo Driver.
HATROLINK-II speed ATYPE=41 SERVO = ON, the speed loop is closed in the TJ1-MC__.d reference is sent to the Servo Driver. This setting is not mended, since there is one cycle delay in the loop (DPOS(n) is
ared with MPOS(n-1)).SERVO = OFF, the speed reference is sent via S_REF command. 00000 means maximum speed of the servomotor. This is the mended setting.
Profile generator
TJ1-MC__
+
_
SERVO = OFF
Trajexia Position Loop is deactivated(Gains are not used!)
Demandedposition
Measuredposition
Position loop
Folle
NoteAlthough MPOS and FE are updated, the real value is the value in the Servo Driver. The real Following Error can be monitored by the DRIVE_MONITOR parameter by setting DRIVE_CONTROL = 2.
NoteThe MECHATROLINK-II position ATYPE = 40 is the recom-mended setting to obtain a higher performance of the servo motor.
+
_
SERVO = OFF
TJ1-MC__
Position loop
Demandedposition
Measuredposition
Profile generator
Followingerror
Syste
HARD 35
Revision 5.0
MECfig. 34With
refereWith comm
StepThe ptrain apositi
SERVO
ME
SERVO = OFF
TJ1-ML__
Torque LoopML-II
Torque command
Torquecommand
m philosophy
WARE REFERENCE MANUAL
HATROLINK-II torque ATYPE=42 SERVO = ON, the torque loop is closed in the TJ1-MC__. The torque nce in the Servo Driver depends on the FE and the gain.
SERVO = OFF, the torque reference is sent directly via the T_REF and. 0x40000000 is the maximum torque of the servomotor.
per output ATYPE=43 osition profile is generated and the output from the system is a pulse nd direction signal. This is useful to control a motor via pulses or as a
on reference for another motion controller.
+
_
SERVO = OFF Position loop
Demandedposition
Measuredposition
Profile generator
Followingerror
TJ1-MC__
NoteTo monitor the torque in the servo in DRIVE_MONITOR, set DRIVE_CONTROL=11.
Syste
HARD 36
Revision 5.0
Servfig. 35With
and inTJ1-M
fig. 36With read.be us
ingr
SpeedCommand
Encoder Signal
10V+_
TJ1-FL02 DRIVE
SERVO = OFF
ME
MeasuredPosition
TJ1-MC__ TJ1-FL02
m philosophy
WARE REFERENCE MANUAL
o axis ATYPE=44 SERVO = ON this is an axis with an analogue speed reference output cremental encoder feedback input. The position loop is closed in the C__ which sends the resulting speed reference to the axis.
SERVO = OFF, the position of the external incremental encoder is The analogue output can be set with BASIC commands only and can ed for general purposes.
FollowErro
DemandedPosition
MeasuredPosition
Position loop
+
_
TJ1-MC__
SERVO = OFF
Profile generator
Syste
HARD 37
Revision 5.0
Encofig. 37The p
increma pos
AbsoWith absolTJ1-MWith encodonly aSee f
AbsoWith absolMC__With read.be usSee f
TJ1-FL02
m philosophy
WARE REFERENCE MANUAL
der output ATYPE=45osition profile is generated and the output from the system is an ental encoder pulse. This is useful to control a motor via pulses or as
ition reference for another motion controller.
lute Tamagawa encoder ATYPE=46 SERVO = ON, this is an axis with analogue speed reference output and ute Tamagawa encoder feedback. The position loop is closed in the C__ and the resulting speed reference is sent to the axis.
SERVO = OFF, the position of the external absolute Tamagawa er is read. The analogue output can be set with BASIC commands nd can be used for general purposes.
ig. 35 for reference.
lute EnDat encoder ATYPE=47SERVO = ON, this is an axis with analogue speed reference output and ute EnDat encoder feedback. The position loop is closed in the TJ1- and the resulting speed reference is sent to the axis.
SERVO = OFF, the position of the external absolute EnDat encoder is The analogue output can be set with BASIC commands only and can ed for general purposes. ig. 35 for reference.
AXIS 1ATYPE = 45
Profile generator
Demandedposition
Syste
HARD 38
Revision 5.0
AbsoWith absoland tWith read.be usSee f
Inverfig. 38This t
the MFromservoUnlikprogr
The Srefresthat tperfo
SumThe fspeed/i
INVERTER
ME
TJ1-ML__
Speedcommand
DPRAMREFRESH EVERY 5ms
ML-IISpeed
commandSpeed Loop
SERVO = OFF
ATYP
40
40
41
m philosophy
WARE REFERENCE MANUAL
lute SSI encoder ATYPE=48SERVO = ON, this is an axis with analogue speed reference output and ute SSI encoder feedback. The position loop is closed in the TJ1-MC__ he resulting speed reference is sent to the axis.SERVO = OFF, the position of the external absolute SSI encoder is The analogue output can be set with BASIC commands only and can ed for general purposes. ig. 35 for reference.
ter axis ATYPE=49 ype allows Inverters (with built-in encoder interface) to be controlled on ECHATROLINK-II bus as servo axes. the controller point of view, Inverter axes are handled the same as axes in MECHATROLINK-II Speed Mode (ATYPE=44).e the other axis types, this Inverter axis must be defined ammatically with function 8 of the command INVERTER_COMMAND.
peed command to the Inverter and the feedback from the encoder is hed in the Inverter every 5 ms. This is a DPRAM limitation. This means
he use of the Inverter is similar to the use of a Servo Driver, but the rmance is lower.
mary of axis types and control modesollowing table lists the axis types and their recommended modes for control, position control and torque control.
+
_
TJ1-MC__
Position loop
Demandedposition
Measuredposition
Profile generator
Followingerror
SERVO = OFF
E SERVO Mode Comment
OFF Position(MECHATROLINK-II)
The position loop is closed in the Servo Driver. No new motion command is allowed.
ON Position(MECHATROLINK-II)
Recommended mode for position control with MECHATROLINK-II axes.
OFF Speed(MECHATROLINK-II)
Recommended mode for speed control with MECHATROLINK-II axes. Set the speed with S_REF.
Syste
HARD 39
Revision 5.0
41
42
42
44, 4647, 48
44, 4647, 48
49
49
ATYP
m philosophy
WARE REFERENCE MANUAL
ON Position(MECHATROLINK-II)
The position loop is closed in Trajexia. This gives lower performance than closing the posi-tion loop in the Servo Driver.
OFF Torque(MECHATROLINK-II)
Recommended mode for torque control with MECHATROLINK-II axes. Set the torque with T_REF.
ON Position via torque (MECHATROLINK-II)
The position loop is closed in Trajexia. The out-put of the position loop is sent as the torque ref-erence to the Servo Driver.
, OFF Speed(Flexible Axis)
Recommended mode for speed control with Flexible Axis.
, ON Position(Flexible Axis)
The position loop is closed in Trajexia. Recom-mended mode for position control with Flexible Axis.
OFF Speed Inverter (with built-in encoder interface) control-led on the MECHATROLINK-II bus as a servo axis. Set the speed with S_REF.
ON Position Inverter (with built-in encoder interface) control-led on the MECHATROLINK-II bus as a servo axis. The position loop is closed in Trajexia.
E SERVO Mode Comment
Syste
HARD 40
Revision 5.0
2.8fig. 39The m
BASIThe BThere• M
to• N
th• P
p
It is pproce
fig. 40Whenis loabufferIf a foBASIExam
DEMANDPOSITION
XIS(2)
ER
NTYPE
MTYPE
Waiting to be executed MOTION COMMAND
Currently executed MOTION COMMAND
AXIS BUFFER (one per axis)
Profile generator
Axis 0NTYPE MTYPE
WAITING EXECUTING
own
Axis 1NTYPE MTYPE
Axis 2NTYPE MTYPE
Axis 3NTYPE MTYPE
NTYPE MTYPEAxis 15
Each Axis has its own 2 buffers: NTYPE & MTYPE
m philosophy
WARE REFERENCE MANUAL
Motion buffers otion buffer is a temporary store of the motion instruction from the
C program to the profile generator.ASIC program continues while the instruction waits in the buffer. are three types of buffer:TYPE. The current movement that is being executed. MTYPE relates the axis and not to the process. TYPE. The new movement that waits for execution. NTYPE relates to e axis and not to the process.rocess Buffer. The third buffered movement cannot be monitored. The rocess buffer relates to the process and not to the axis.
ossible to check if the process buffer is full by checking the PMOVE ss parameter.
a motion instruction is executed in the BASIC program, the instruction ded into the process buffer and distributed to the corresponding axis in the next motion sequence.urth motion instruction is executed and the three buffers are full, the C program stops execution until a process buffer is free for use.ple of buffered instructions:
.......
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......CONNECT(1,1)
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......CONNECT(1,1)
CONNECT(1,1) A
PROCESS BUFF
Process 1 Process Buffer
Each process has its “Process Buffer”
Process Buffer Process 2
Process 3 Process Buffer
Process Buffer Process 4
Process 5 Process Buffer
Process Buffer Process 6
Process 7 Process Buffer
Process 14 Program Buffer
Syste
HARD 41
Revision 5.0
fig. 41
MOVE -500
MOVE -500
MOVE -500
2.- A second movement is loaded while the first one is not finished.The new movement waits in the
second buffer.
3.- A third movement can
still be stored in the process buIf the basic program reaches‘MOVE(200)’ it will wait.
1.- All buffers are empty
and a movement is loaded. The movement starts to execute.
5.- As the sent
movements are finished, the buffer empties.MOVE -500
MOVE 1000
DATUM (3)
MOVE -500
MOVE 1000
DATUM (3)
VE -500
MOVE 1000
DATUM (3) MOVE 200
VE -500
MOVE 1000
DATUM (3) MOVE 200
6.- If no new movements
are executed, finally, thebuffer will become empty and the profile generator
becomesinactive.
4.- The first movement has
finished. Thebuffer movesby one position . The next movement starts to
execute.
MOVE -500
MOVE 1000
MOVE -500
MOVE 1000
m philosophy
WARE REFERENCE MANUAL
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - -
---------------------------------NTYPE IDLE---------------------------------MTYPE MOVE(-500)
BUFFER
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - ----------------------------------NTYPE MOVE(1000)---------------------------------MTYPE MOVE(-500)
BUFFER
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
DATUM(3)---------------------------------NTYPE MOVE(1000)---------------------------------MTYPE MOVE(-500)
BUFFER
EXAMPLE:
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - - - ----------------------------------NTYPE MOVE(200)---------------------------------MTYPE DATUM(3)
BUFFER
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - - - ----------------------------------NTYPE MOVE(200)---------------------------------MTYPE DATUM(3)
BUFFER
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - - - ----------------------------------NTYPE IDLE---------------------------------MTYPE MOVE(200)
BUFFER
MO
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
- - - - - ----------------------------------NTYPE IDLE---------------------------------MTYPE MOVE(200)
BUFFER
MO
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
MOVE(200)---------------------------------NTYPE DATUM(3)---------------------------------MTYPE MOVE(1000)
BUFFER
BASIC PROGRAM.......MOVE(-500).......MOVE(1000).......DATUM(3).......MOVE(200).......
MOVE(200)---------------------------------NTYPE DATUM(3)---------------------------------MTYPE MOVE(1000)
BUFFER
Syste
HARD 42
Revision 5.0
2.9
2.9.1
The irelatiosystereachWith Drivecomb
2.9.2
If a mvibrat
2.9.3
A memechsystefrequThe rsettin
m philosophy
WARE REFERENCE MANUAL
Mechanical system
Inertia ratio
nertia ratio is a stability criterion. The higher the intertia of the load in n to the intertia of the motor, the lower the gains you can set in your
m before you reach oscillation, and the lower the performance you can .a ratio of 1:30 for small Servo Drivers and a ratio of 1:5 for big Servo rs you can reach the maximum dynamic of the motor-driver ination.
Rigidity
achine is more rigid and less elastic, you can set higher gains without ion, and you can reach higher dynamic and lower Following Error.
Resonant frequency
chanical system has at least one resonant frequency. If you excite your anical system to the resonant frequency, it starts oscillating. For motion ms, it is best to have mechanical systems with a very high resonant ency, that is, with low inertia and high rigidity.esonant frequency of the mechanical system is the limit for the gain gs.
Hardw
HARD 43
Revision 5.0
3
3.1fig. 1Traje
the e
Trajescalacoorde-geacomm
Trajebus oor tormake
You cdriver8 Inve
3.1.1
The m
DirecTrajePCs, over Etherto the
KeepTrajeconfid
CX-onerajexia Tools
PROFIBUS-DPMaster
DEVICENETMaster
CANopenMaster
are reference
WARE REFERENCE MANUAL
Hardware reference
Introductionxia is OMRON's motion platform that offers you the performance and ase of use of a dedicated motion system.
xia is a stand-alone modular system that allows maximum flexibility and bility. At the heart of Trajexia lies the TJ1 multi-tasking motion inator. Powered by a 32-bit DSP, it can do motion tasks such as e-cam, rbox, registration control and interpolation, all via simple motion ands.
xia offers control of up to 16 axes over a MECHATROLINK-II motion r traditional analogue or pulse control with independent position, speed que control for every axis. And its powerful motion instruction set s programming intuitive and easy.
an select from a wide choice of best-in-class rotary, linear and direct- servos as well as Inverters. The system is scalable up to 16 axes and rters & I/O modules.
Trajexia High-Lights
ain high-lights of the trajexia system are as follows:
t connectivity via Ethernetxia's Ethernet built-in connector provides direct and fast connectivity to PLCs, HMIs and other devices while providing full access to the drivers a MECHATROLINK-II motion bus. It allows explicit messaging over net and through MECHATROLINK-II to provide full transparency down actuator level, and making remote access possible.
your know-how safexia's encryption method guarantees complete protection and entiality for your valuable know-how.
NS-series HMICJ-series PLC
T
Ethernet
Digital I/O
Hostlink
MECHATROLINK-II
Hardw
HARD 44
Revision 5.0
SeriaA seror anembemach
MECThe MInversysteaccurmotio
TJ1-The Tpulseallow
DriveA widare aThe Iupda
RemThe Iexpan
PROThe Pyour
DeviThe Dmach
are reference
WARE REFERENCE MANUAL
l Port and Local I/Osial connector provides direct connectivity with any OMRON PLC, HMIs y other field device. 16 Inputs and 8 outputs are freely configurable dded I/Os in the controller to enable you to tailor Trajexia to your ine design.
HATROLINK-II MasterECHATROLINK-II master performs control of up to 16 servos,
ters or I/Os while allowing complete transparency across the whole m.MECHATROLINK-II offers the communication speed and time acy essential to guarantee perfect motion control of servos. The n cycle time is selectable between 0.5 ms, 1 ms or 2 ms.
FL02 (Flexible Axis Unit)J1-FL02 allows full control of two actuators via an analogue output or train. The module supports the main absolute encoder protocols ing the connection of an external encoder to the system.
s and Inverterse choice of rotary, linear and direct-driver servos as well as Inverters vailable to fit your needs in compactness, performance and reliability. nverters connected to the MECHATROLINK-II are driven at the same te cycle time as the Servo Drivers.
ote I/Os/Os on the MECHATROLINK-II motion bus provide for system sion while keeping the devices under one motion bus.
FIBUS-DPROFIBUS-DP slave allows connectivity to the PROFIBUS network in
machine.
ceNeteviceNet slave allows connectivity to the DeviceNet network in your
ine.
Hardw
HARD 45
Revision 5.0
CANThe Cmach
3.1.2fig. 2One
Trajeinstrugearbmotiowhile
One The pare fu
One TrajeoscillThe sbus asyste
3.1.3
This H• T• T• A
T
are reference
WARE REFERENCE MANUAL
openANopen master allows connectivity to the CANopen network in your ine.
Trajexia Studio
softwarexia's intuitive and easy programming tool, based on the Motion BASIC ction set, includes dedicated commands for linking axes, e-cams, e-oxes etc. Multi-tasking provides flexibility in application design. The n commands are "buffered" so the BASIC programs are executed motion movements are executed.
connectionarameters and functions inside the drivers on the MECHATROLINK-II lly accessible from the Ethernet connection.
minutexia Studio includes advanced debugging tools, including trace and oscope functions, to ensure efficient operation and minimum downtime.ervos, Inverters and I/Os connected to the MECHATROLINK-II motion re automatically identified and configured, allowing you to set up your m in minutes.
This manual
ardware Reference Manual gives the dedicated information for:he description, connections and use of the Trajexia unitshe description, connections and use of the MECHATROLINK-II slaves detailed philosophy of the system design to obtain the best results for rajexia
Hardw
HARD 46
Revision 5.0
3.2
3.2.1fig. 3A Tra
• A• A
--
• U• A
The eTJ1-M
A Tra• 0• 0• 0
(D• 0
A Tra• 0• 0• 0• 0
1 2 3 4 5 6
1.
are reference
WARE REFERENCE MANUAL
All units
System installation
jexia system consists of these units: Power Supply Unit. TJ1-MC__ (Motion Controller Unit). This can be one of these:
TJ1-MC16. It supports 16 real or virtual axes, and 16 axes in total.TJ1-MC04. It supports 5 real and up to 16 virtual axes, 16 axes in total.
p to 7 expansion units. TJ1-TER (Terminator Unit).
xpansion units (unit numbers 0-6) can be arranged in any order. The C__ autodetects all units.
jexia system with a TJ1-MC16 can include: to 4 TJ1-ML__ units (MECHATROLINK-II Master Unit). to 7 TJ1-FL02 units. or 1 TJ1-PRT (PROFIBUS-DP Slave Unit) or TJ1-DRT units eviceNet Slave Unit)1.
or 1 TJ1-CORT units (CANopen Master Unit).
jexia system with a TJ1-MC04 can include: to 4 TJ1-ML__ units. to 3 TJ1-FL02 units. or 1 TJ1-PRT or TJ1-DRT units1. or 1 TJ1-CORT units.
-1Unit number: 0
Trajexia does not support both a TJ1-PRT and a TJ1-DRT unit in the same system.
Hardw
HARD 47
Revision 5.0
fig. 4The fA. PB. TC. TD. SE. NF. SG. T
01234567
CN3
CN1
TERMON/OFFWIRE2/4
CN2
MC16
OMRONMOTION CONTROLLER
RUN
8F
CN1
ML16
GCBA
ED
are reference
WARE REFERENCE MANUAL
igure is an example of a simple configuration.ower supplyJ1-MC__.J1-ML__.igma-II Servo DriverS115 MECHATROLINK-II Interface Unit.igma-II servo motorJ1-TER.
F
Hardw
HARD 48
Revision 5.0
fig. 51. Rco
2. D3. To
a4. D
fig. 65. P
A
01234567
CN1
TERMON/OFFWIRE2/4
CN2
OLLER
are reference
WARE REFERENCE MANUAL
emove all the units from the packaging. Make sure all units are mplete.
o not remove the protection labels from the units. disconnect the TJ1-MC__ and the TJ1-TER, push the clips (A) on top
nd bottom of the TJ1-TER to the front.isconnect the TJ1-TER from the TJ1-MC__.
ush the clips (A) on top and bottom of all the units to the front.
01234567
CN3
CN1
TERMON/OFFWIRE2/4
CN2
MC16
OMRONMOTION CONTROLLER
CN3
MC16
OMRONMOTION CONTR
A
Hardw
HARD 49
Revision 5.0
fig. 76. A
fig. 87. P
01234567
CN3
CN1
TERMON/OFFWIRE2/4
CN2
MC16
OMRONMOTION CONTROLLER
CB
CN1
ERMN/OFF
IRE/4
CN2
A
are reference
WARE REFERENCE MANUAL
ttach the TJ1-MC__ (C) to the Power Supply Unit (B).
ush the clips (A) on top and bottom to the rear.
01234567
CN3
T
O
W
2
MC16
OMRONMOTION CONTROLLER
Hardw
HARD 50
Revision 5.0
fig. 98. R9. M
fig. 1010. P11. A
p1
12. P13. A
fr
RUN
8F
CN1
ML16
A
RUN
8F
CN1
ML16
D
are reference
WARE REFERENCE MANUAL
epeat the previous two steps for all other units.ake sure the last unit is the TJ1-TER.
ull down all the clips (D) on all units.ttach the Trajexia system to the DIN rail in an upright position to rovide proper cooling. The recommended DIN rail is of type PFP-00N2, PFP-100N or PFP-50N. ush all the clips (D) up on all units.fter you complete the wiring of the units, remove the protection labels om the units.
01234567
CN3
CN1
TERMON/OFFWIRE2/4
CN2
MC16
OMRONMOTION CONTROLLER
01234567
CN3
CN1
TERMON/OFFWIRE2/4
CN2
MC16
OMRONMOTION CONTROLLER
Hardw
HARD 51
Revision 5.0
fig. 1114. D••••
0 1 2 3 4 5 6 7
CN
3
CN
1
TE
RM
ON
/OF
F
WIR
E2/4
CN
2
MC
16
OM
RO
N
MO
TIO
N C
ON
TR
OL
LE
R
RU
N
8F
CN
1
ML
16
01234567
CN3
CN1
TERMON/OFF
WIRE2/4
CN2
MC16
OMRON
MOTION CONTROLLER
RUN
8F
CN1
ML16
are reference
WARE REFERENCE MANUAL
o not install the Trajexia units in one of these positions:Upside down.With the top side forward.With the bottom forward.Vertically.
Hardw
HARD 52
Revision 5.0
fig. 1215. Waa
3.2.2/i
Item
Ambi
Ambi
Ambi
Ambi
Atmo
Vibra
Shoc
Insula
Diele
Prote
Intern
are reference
WARE REFERENCE MANUAL
hen you design a cabinet for the units, make sure that the cabinet llows at least 20 mm of space around the units to provide sufficient irflow. We advise to allow at least 100 mm of space around the units.
Environmental and storage for all units
Specification
ent operating temperature 0 to 55°C
ent operating humidity 10 to 90% RH. (with no condensation)
ent storage temperature -20 to 70°C (excluding battery)
ent storage humidity 90% max. (with no condensation)
sphere No corrosive gases
tion resistance 10 to 57 Hz: (0.075 mm amplitude): 57 to 100 Hz: Acceleration: 9,8 m/s2, in X, Y and Z directions for 80 minutes
k resistance 147 m/s2, 3 times each X, Y and Z directions
tion resistance 20 MΩ
ctric strength 500 VAC
ctive structure IP20
ational standards CE, EN 61131-2, cULus, LloydsRoHS compliant
Hardw
HARD 53
Revision 5.0
3.2.3
The d
Trajefig. 13All m
70.3
9094
are reference
WARE REFERENCE MANUAL
Unit dimensions
imensions for the units of the Trajexia system are as follows:
xia motion controllereasurements are in mm.
62
65
71
Hardw
HARD 54
Revision 5.0
Trajefig. 14All m
70.3
90
94
are reference
WARE REFERENCE MANUAL
xia unitseasurements are in mm.
31
39.9
Hardw
HARD 55
Revision 5.0
Trajefig. 15All m
fig. 16The ithe m
3.2.4
To withese
2 29.731
90 94
70.30
81.60 to 89.0 mm
90
94
are reference
WARE REFERENCE MANUAL
xia systemeasurements are in mm.
nstallation depth of the Trajexia system is up to 90 mm, depending on odules that are mounted. Allow sufficient depth in the control cabinet.
Wire the I/O connectors
re the I/O connectors of the TJ1-MC__ and the TJ1-FL02 units, do steps:
6
65
45
PA202
Hardw
HARD 56
Revision 5.0
fig. 171. S2. To3. If
fe4. In5. In6. R7. M
Wirin/i
Cond/i
Item
Wire
Insert
Recoferrul
Stripp
Item
Clam
Wires
Wires
are reference
WARE REFERENCE MANUAL
trip the wires. make it easier to insert the wires, twist them.
necessary, crimp the plain (top) ferrules or the collared (bottom) rrules.sert the screwdriver into the inner (square) hole. Push firmly.sert the wire into the outer (circular) hole.emove the screwdriver.ake sure that there are no loose strands.
g specifications
uctor size
Specification
types 0.14−1.0 mm2
Solid, stranded or stranded with ferrule:• Crimp ferrules according to DIN46228/1• Crimp ferrules wit plastic collar according to DIN46228/4• With recommended tool Weidmüller PZ6
ion tool 2.5 mm flat-bladed screwdriver
mmended e types
WeidmüllerAEH H0,14/12AEH H0,25/12AEH H0,34/12
ing length 7 mm without ferrules (tolerance: +1 mm, −0 mm)10 mm with ferrules (tolerance: +1 mm, −0 mm)
Specification
ping range 0.08−1.0 mm2
without ferrule 0.5−1.0 mm2
with ferrule AEH H0,14/12, 0.13 mm2
AEH H0,25/12, 0.25 mm2
AEH H0,34/12, 0.34 mm2
Hardw
HARD 57
Revision 5.0
3.3
3.3.1
The Puse th
• C• C• C
3.3.2fig. 18Each
/iXXXX
POWER
L1AC100-240V
INPUTL2/N
NC
NC
A
B
C
D
E
F
Item
A
B
C
D
E
1.
F
are reference
WARE REFERENCE MANUAL
Power Supply Unit (PSU)
Introduction
SU supplies power to the other units in the Trajexia system. You can ree different types of Power Supply Unit with the Trajexia system:
J1W-PA202J1W-PA205RJ1W-PD025.
PSU Connections
Power Supply Unit has six terminals:
XGCJ1W-PA202 CJ1W-PA205R CJ1W-PD025
110 - 240 VAC input 110 - 240 VAC input 24 VDC input
110 - 240 VAC input 110 - 240 VAC input 0 V input
Line earth Line earth Line earth
Earth Earth Earth
N/C 1Wdog relay contact
Terminals E and F for the CJ1W-PA205R are relay contacts that close when Wdog is enabled. Refer to the BASIC Commands in the Program-ming manual.
N/C
N/C Wdog relay contact N/C
CautionAlways connect to a class-3 ground (to 100Ω or less) when install-ing the Units. Not connecting to a class-3 ground may result in electric shock.
Hardw
HARD 58
Revision 5.0
Eachyou c
3.3.3/i
PoweSuppUnit
CJ1W
CJ1W
CJ1W
are reference
WARE REFERENCE MANUAL
Power Supply Unit has one green LED (G). This LED comes on when onnect the Power Supply Unit to the power source.
PSU Specifications
CautionA ground of 100Ω or less must be installed when shorting the GR and LG terminals on the Power Supply Unit.Not connecting a ground of 100Ω or less may result in electric shock.
CautionTighten the screws of the power supply terminal block to the torque of 1.2 N·m. Loose screws can result in short-circuit, mal-function or fire.
rly
Inputvoltage
Maximum current consumption Outputpower5 V group 24 V group
-PA202 110 - 240 VAC 2.8 A 0.4 A 14 W
-PA205R 110 - 240 VAC 5.0 A 0.8 A 25 W
-PD025 24 VDC 5.0 A 0.8 A 25 W
CautionThe amount of current and power that can be supplied to the sys-tem is limited by the capacity of the Power Supply Unit. Refer to this table when designing your system so that the total current consumption of the units in the system does not exceed the maxi-mum current for each voltage group. The total power consumption must not exceed the maximum for the Power Supply Unit.
Hardw
HARD 59
Revision 5.0
3.3.4
• S• P• P
3.4
3.4.1
The TTJ1-Munits ProgrThereThe TThe T
fig. 19The T/i
A
B
C
D
EFGH
Part
A
B
C
D
E
F
G
H
are reference
WARE REFERENCE MANUAL
PSU box contents
afety sheet.ower Supply Unit.rotection label attached to the top surface of the unit.
TJ1-MC__
Introduction
J1-MC__ is the heart of the Trajexia system. You can program the C__ with the BASIC programming language to control the expansion
and the servo motors attached to the expansion units. Refer to the amming Manual. are two versions of the TJ1-MC__:J1-MC04 supports 5 axes (up to 4 axis on MECHATROLINK-II)J1-MC16 supports 16 axes.J1-MC__ has these visible parts:
Description
LED display
I/O LEDs 0 - 7
Battery
Ethernet connector
TERM ON/OFF switch
WIRE 2/4 switch
Serial connector
28-pin I/O connector
Hardw
HARD 60
Revision 5.0
3.4.2
The Lfig. 20/i
Inform
IP adnet m
IP ad
RUN
OFF
ERR
are reference
WARE REFERENCE MANUAL
LED Display
ED display shows the following information:
ation When
dress and sub-ask
Shows 3 times when you connect the Trajexia system to the power supply.
dress Shows 4 times when you connect an Ethernet cable to the Ethernet connector of the TJ1-MC__ and to a PC.
When the TJ1-MC__ operates a Servo Driver.
When the TJ1-MC__ does not operate a Servo Driver.
+ code When an error occurs in the Trajexia system.The code is the error code. Refer to troubleshooting chapter in the Programming Manual.
Hardw
HARD 61
Revision 5.0
3.4.3fig. 21The T
• O• O• O
The p
EtheThe EEtherused cableand naddreThe TEther
BASMakeDo no
EnviUTP systeenviroInstalgeneInstalexces
A
B
C
D
EFGH
are reference
WARE REFERENCE MANUAL
TJ1-MC__ Connections
J1-MC__ comes with these connectors:ne Ethernet connector, to connect to a PC or Ethernet network (D)ne serial connector (G). ne 28-pin I/O connector (H).
arts for the serial connector and the 28-pin connector are supplied.
rnet connector thernet connector is used to connect the TJ1-MC__ to a PC or
net network. The Ethernet connector is the only connection that can be to program the system. Use either a crossover or a Ethernet patch for this connection. If you connect the PC directly to the TJ1-MC__, ot via a hub or any other network device, the PC must have a fixed IP ss.J1-MC__ automatically detects when a cable is connected to the net connector.
IC installation precautions sure that the Ethernet system is to the IEEE Std 802.3 standard.t install the Ethernet system near a source of noise.
ronmental precautionscables are not shielded. In environments that are subject to noise use a m with shielded twisted-pair (STP) cable and hubs suitable for an FA nment.
l twisted-pair cables away from high-voltage lines and devices that rate noise.l twisted-pair cables in locations that are free of high humidity and sive dust and contaminates.
Hardw
HARD 62
Revision 5.0
Seriafig. 22The s
• R• R• R
/i
TERMSets of theserial/i
54321
Pin1
2
3
4
5
6
7
8
9
Commstand
RS42
RS42
are reference
WARE REFERENCE MANUAL
l connectorerial connector allows for three communication standards:S232.S422.S485.
ON/OFF Switchthe termination on/off of the RS422 / 485 serial connection. The setting TERM ON/OFF switch depends on the communication standard of the connection and the position of the TJ1-MC__ in the network:
9876
Communication ConnectionRS422/RS485 /Tx
RS232 Tx
RS232 Rx
N/C N/C
N/C N/C
RS422/RS485 /Rx
RS422/RS485 Tx
RS422/RS485 Rx
RS232 0 V
unication ard
Position of the TJ1-MC__ Setting of the TERM ON/OFF switch
2 or RS485 First or last Left (on)
2 or RS485 Not the first and not the last Right (off)
Hardw
HARD 63
Revision 5.0
WIREfig. 23The W
serial/i
A
B
C
D
EFGH
Comm
RS42
RS48
are reference
WARE REFERENCE MANUAL
2/4 SwitchIRE 2/4 switch sets the communication standard for the RS422/485
connection. To use one of the communication standards, do this:
unication standard How to select it
2 Set the WIRE 2/4 switch right
5 Set the WIRE 2/4 switch left
NoteIn RS485 mode, the transmit pair is connected to the receive pair.
Hardw
HARD 64
Revision 5.0
28-PThe 2B2L 3
fig. 24/i
LEDsThe IBASIThe tcomm/i
246810121416182022242628
Pin
1
3
5
7
9
11
13
15
17
19
21
23
25
27
LED label
0
1
are reference
WARE REFERENCE MANUAL
in I/O connector 8 pin connector is a Weidmuller connector designation: .5/28 LH.
0 - 7/O LEDs reflect the activity of the input and outputs. You can use the C DISPLAY=n command to set the LEDs.able below lists the configuration for LEDs 0 - 7 and the DISPLAY=n and where n ranges from 0 to 7.
13579
111315171921232527
Connection Pin Connection
0 V input common 2 0 V input common
Input 0 4 Input 1
Input 2 6 Input 3
Input 4 8 Input 5
Input 6 10 Input 7
Input 8 12 Input 9
Input 10 14 Input 11
Input 12 16 Input 13
Input 14 18 Input 15
Output 8 20 Output 9
Output 10 22 Output 11
Output 12 24 Output 13
Output 14 26 Output 15
0 V output common 28 24V Power supply Input for the Outputs.
n=0 n=1 n=2 n=3 n=4 n=5 n=6 n=7
IN 0 IN 8 IN 16 IN 24 OUT 0 OUT 8 OUT 16 OUT 24
IN 1 IN 9 IN 17 IN 25 OUT 1 OUT 9 OUT 17 OUT 25
Hardw
HARD 65
Revision 5.0
For eactivi
Digitfig. 25The f
15) s/i
The tphysiMaximor 25the in
2
3
4
5
6
7
LED label
TJ 1-MC 16
3
nput
common for Input circuits
1
nput
Item
Type
Maxim
Input
ON v
OFF
are reference
WARE REFERENCE MANUAL
xample, if you use the DISPLAY=1 command, LED 5 reflects the ty of the input in 13 (pin16) of the 28-pin I/O connector.
al inputs ollowing table and illustration details the digital input (Input 0 to Input pecifications for the I/O:
imings are dependant upon the MC16’s servo period, and include cal delays in the input circuit.
um response times of 1250 µs (for servo periods of 0.5 ms or 1.0 ms) 00 µs (for a servo period of 2.0 ms) are achieved between a change in put voltage and a corresponding change in the IN Parameter.
IN 2 IN 10 IN 18 IN 26 OUT 2 OUT 10 OUT 18 OUT 26
IN 3 IN 11 IN 19 IN 27 OUT 3 OUT 11 OUT 19 OUT 27
IN 4 IN 12 IN 20 IN 28 OUT 4 OUT 12 OUT 20 OUT 28
IN 5 IN 13 IN 21 IN 29 OUT 5 OUT 13 OUT 21 OUT 29
IN 6 IN 14 IN 22 IN 30 OUT 6 OUT 14 OUT 22 OUT 30
IN 7 IN 15 IN 23 IN 31 OUT 7 OUT 15 OUT 23 OUT 31
n=0 n=1 n=2 n=3 n=4 n=5 n=6 n=7
0V I
0V
External powersupply 24V
I
Specification
PNP/NPN
um voltage 24 VDC + 10%
current 5 mA at 24 VDC
oltage 14.4 VDC
voltage 5.0 VDC max.
Hardw
HARD 66
Revision 5.0
Digitfig. 26The f
speci/i
The tphysiMaxim0.5 mare achang
TJ 1-MC 16
Externalpowersupply24V
Load
2A Fuse24V output supply28
19 O8
27 0Vout
ircuits
Item
Type
Maxim
Curre
Max.
Prote
are reference
WARE REFERENCE MANUAL
al outputsollowing table and illustration details the digital output (O8 to O15) fications:
imings are dependant upon the MC16’s servo period, and include cal delays in the output circuit.
um response times of 250 µs on and 350 µs off (for servo periods of s or 1.0 ms) or 500 µs on and 600 µs off (for a servo period of 2.0 ms) chieved between a change in the OP parameter and a corresponding e in the digital output circuit.
Equivalentcircuit
To other output cInte
rnal
circ
uits
(gal
vani
cally
isol
ated
from
the
syst
em)Specification
PNP
um voltage 24 VDC + 10%
nt capacity 100 mA each output (800 mA for a group of 8)
Voltage 24 VDC + 10%
ction Over current, Over temperature and 2A fuse on Common
Hardw
HARD 67
Revision 5.0
3.4.4fig. 27The b
variabmust CJ1WTo reto ensunit tocapacbacku
3.4.5/i
A
B
C
D
EFGH
Item
Powe
Total
Curre
Appro
Numb
Numb
Numb
Real
are reference
WARE REFERENCE MANUAL
Battery
ackup battery provides power to the RAM, where programs and global les are stored, and real Time Clock when the power supply is off. You replace it every five years. The part number of the backup battery is -BAT01.
place the battery the power must not be off for more than five minutes ure no backup memory loss. If the TJ1-MC__ has not been on, set the on for at least five minutes before you replace the battery else the itor that gives backup power to the memory is not fully changed and p memory may be lost before the new battery is inserted.
TJ1-MC__ Specification
Specification
TJ1-MC04 TJ1-MC16
r supply 5 VDC and 24 VDC (supplied by a Power Supply Unit)
power consumption 3.3 W
nt consumption 650 mA at 5 VDC
ximate weight 230 g
er of axes 5 (up to 4 axis on MECHA-TROLINK-II)
16
er of Inverters and I/Os Up to 8 on MECHATROLINK-II, depending on the type of TJ1-ML__ in the system.
er of TJ1-ML__ units Up to 4
Time Clock Yes
Hardw
HARD 68
Revision 5.0
Seria/i
Servo
Progr
Multi-
Digita
Meas
Availagram
Data
SavinTJ1-M
Savin
Comm
Firmw
ElectrEther
Ether
Item
Item
Electr
Conn
Baud
Trans
Trans
are reference
WARE REFERENCE MANUAL
l connectors 1 and 2
period 0.5 ms, 1 ms or 2 ms
amming language BASIC-like motion language
tasking Up to 14 tasks
l I/O 16 digital inputs and 8 digital outputs, freely configurable
urement units User-definable
ble memory for user pro-s
500 kB
storage capacity Up to 2 MB flash data storage
g program data on the C__
• RAM and flash memory backup• Battery backup
g program data on the PC Trajexia Tools software manages backups on the hard-disk of the PC
unication connectors • 1 Ethernet connection• 2 serial connections
are update Via Trajexia Tools software
ical characteristics of the net connector
Conforms to IEEE 802.3 (100BaseT)
net connector RJ45
Specification
TJ1-MC04 TJ1-MC16
Specification
ical characteristics • PORT1: RS232C, non-isolated• PORT2: RS485/RS422A, isolated
ector SUB-D9 connector
rate 1200, 2400, 4800, 9600, 19200 and 38400 bps
mission format, databit length 7 or 8 bit
mission format, stop bit 1 or 2 bit
Hardw
HARD 69
Revision 5.0
3.4.6fig. 28The T
functilast u
Trans
Trans
Trans
Galva
Comm
Flow
Termi
Maxim
Item
are reference
WARE REFERENCE MANUAL
TJ1-TER
J1-TER makes sure that the internal data bus of the Trajexia system ons correctly. A Trajexia system must always contain a TJ1-TER as the nit.
mission format, parity bit Even/odd/none
mission mode • RS232C: Point-to-point (1:1)• RS422/485: Point-to-multipoint (1:N)
mission protocol • Host link master protocol• Host link slave protocol• ASCII general purpose
nic isolation RS422/485 connector only
unication buffers 254 bytes
control None
nator Yes, selected by switch
um cable length • RS232C: 15 m• RS422/485: 100 m
Specification
Hardw
HARD 70
Revision 5.0
3.4.7
• S• T• P• T• P• P• T
th• W
3.5
3.5.1
The Tdeter
fig. 29• S• In• I/
The T/i
Togetthe n• O• O
RUN
BF
CN1
A
BPart
A
B
are reference
WARE REFERENCE MANUAL
TJ1-MC__ box contents
afety sheet.J1-MC__ (battery included).rotection label attached to the top surface of the TJ1-MC__.J1-TER, attached to the TJ1-MC__.arts for a serial connector.arts for an I/O connector.wo metal DIN-rail clips, to prevent the Trajexia system from sliding off e rail.hite clip, to replace the yellow clip of the Power Supply Unit.
TJ1-ML__
Introduction
J1-ML__ controls MECHATROLINK-II devices in a cyclic and ministic way. MECHATROLINK-II devices can be:ervo Drivers.verters.Os.
J1-ML__ has these visible parts:
her the TJ1-ML__ and its devices form a serial network. The first unit in etwork is the TJ1-ML__. ne TJ1-ML16 can control 16 devices.ne TJ1-ML04 can control 4 devices.
ML16
Description
LED indicators
CN1 MECHATROLINK-II bus connector
Hardw
HARD 71
Revision 5.0
3.5.2/i
3.5.3fig. 30The M
conneMEC
The MMEC
Labe
run
BF
-
RUN
8F
ML16
CN1
A
are reference
WARE REFERENCE MANUAL
LEDs description
TJ1-ML__ connection
ECHATROLINK-II bus connector (A) fits a MECHATROLINK-II ctor. Use this connector to connect the TJ1-ML__ to a
HATROLINK-II network.
ECHATROLINK-II network must always be closed by the HATROLINK-II terminator.
l Status Description
off Start-up test failed. Unit not operationalOperation stopped. Fatal error
on Start-up test successful. Normal operation
off Normal operation
on A fault in the MECHATROLINK-II bus
Reserved
Hardw
HARD 72
Revision 5.0
Examfig. 31Exam
• 1• 1• 3• 1
ddress43
Axis 2 Axis 3 Axis 4
Address44
Address45
Terminator
Servo Driver
are reference
WARE REFERENCE MANUAL
ple connections ple 1
x TJ1-MC__ x TJ1-ML__ x Sigma-II Servo Driver x MECHATROLINK-II terminator
A
Hardw
HARD 73
Revision 5.0
fig. 32Exam• 1• 2• 1• 2
3
11
Axis 4
Axis 12
Axis 5
Axis 13
Axis 6
Axis 14
Axis 7
Axis 15
ess Address 4D
Address 4E
Address 4F
Address 50
Terminator
Servo Drive
ess Address 45
Address 46
Address 47
Address 48
Terminator
are reference
WARE REFERENCE MANUAL
ple 2 x TJ1-MC16 x TJ1-ML166 x Sigma-II Servo Driver x MECHATROLINK-II terminator
Address 49
Axis 0
Axis 8
Axis 1
Axis 9
Axis 2
Axis 10
Axis
Axis
Address 4A
Address 4B
Addr4C
Address 41
Address 42
Address 43
Addr44
Hardw
HARD 74
Revision 5.0
fig. 33The MInverExam• 1• 1• 1• 1• 3• 1
3.5.4/i
Address 61
Address 62
Address 63
I/O Memory Allocations
I/O UNITS I/O Addresses are numbered 6x
(valid range 60 to 6F) I/O Address selected on DIP Switches
sesx2F)
Terminator
0 31 32 95 96 159 160 223 224
Item
Powe
Total
Curre
are reference
WARE REFERENCE MANUAL
ECHATROLINK-II Units can control different combinations of axes, ters and I/O units.ple 3
x TJ1-MC__ x TJ1-ML16 x Sigma-II Servo Driver x Inverter x I/O units x MECHATROLINK-II terminator
TJ1-ML__ specifications
Address 41
Axis 0
Address 21
INVERTERS All Inverter Addres
are numbered 2(valid range 20 to
Specification
TJ1-ML04 TJ1-ML16
r supply 5 VDC (supplied by the TJ1-MC__)
power consumption 1.0 W
nt consumption 200 mA at 5 VDC
Hardw
HARD 75
Revision 5.0
TJ1-/i
ntents
Unit box:
to the top surface of the unit.
mmands
nds are related to the TJ1-ML__:
the Trajexia Programming Manual.
Appro
Numb
Contr
Electr
Comm
Trans
Servo
Transrepea
Name
Distriules
MECHcable
Item
FNY-W6003-05
FNY-W6003-10
FNY-W6003-20
FNY-W6003-30
resistor FNY-W6022
I series Servo Drivers rsion 39 or later)
JUSP-NS115
ed V7 Inverter (For the sup-ion details of the Inverter, con-
RON sales office).
SI-T/V7
ed F7, G7 Inverter (For the ersion details of the Inverter, r OMRON sales office).
SI-T
Model
are reference
WARE REFERENCE MANUAL
ML__ related devices 3.5.5 TJ1-ML__ box co
MECHATROLINK-II Interface• Safety sheet.• TJ1-ML__.• Protection label attached
3.5.6 Related BASIC co
The following BASIC comma• ATYPE• MECHATROLINK
For more information, refer to
ximate weight 75 g
er of controlled devices 4 16
olled devices • Omron G-Series Servo Drivers• Omron Accurax G5 Servo Drivers• Sigma-II, Sigma-V and Junma-ML Servo Drivers• I/Os• V7, F7 and G7 Inverters
ical characteristics Conforms to MECHATROLINK-II standard
unication connection 1 MECHATROLINK-II master connector
mission speed 10 Mbps
period 0.5 ms, 1 ms or 2 ms
mission distance without a ter
Up to 50 m
Remarks Model
buted I/O mod- MECHATROLINK-II Smartslice coupler GRT1-ML2
64-point digital input and 64-point digital output (24 VDC sinking)
JEPMC-IO2310
64-point digital input and 64-point digital output (24 VDC sourcing)
JEPMC-IO2330
Analogue input: -10V to +10 V, 4 channels
JEPMC-AN2900
Analogue output: -10 V to +10 V, 2 channels
JEPMC-AN2910
ATROLINK-II s
0.5 meter FNY-W6003-A5
1 meters FNY-W6003-01
3 meters FNY-W6003-03
Specification
TJ1-ML04 TJ1-ML16 5 meters
10 meters
20 meters
30 meters
MECHATROLINK-II terminator
Terminating
MECHATROLINK-II interface unit
For Sigma-I(firmware ve
For Varispeported verstact your OM
For Varispesupported vcontact you
Name Remarks
Hardw
HARD 76
Revision 5.0
3.5.7
A METrajepositisendson thOtherrate.A SerWhenautomvalue
3.5.8fig. 34To co
MECFor d
are reference
WARE REFERENCE MANUAL
MECHATROLINK-II Servo Drivers
CHATROLINK-II Servo Driver is designed to do position control in xia. In every MECHATROLINK-II cycle, the TJ1-MC__ receives the on feedback from the Servo Driver via the TJ1-ML__. The TJ1-MC__ either the target position, speed or torque to the receiver, depending
e axis type. functionality of the Servo Driver is available but refreshed at slower
vo Driver is considered an axis by the TJ1-MC__. you connect a servo to the Trajexia, the parameter does not change atically so, depending on the application, you may have to change
s.
MECHATROLINK-II Servo Drivers Sigma-II series
nnect a Sigma-II Servo Driver to a Trajexia system, a JUSP-NS115 HATROLINK-II interface must be connected to the Servo Driver.etails about the Sigma-II connections refer to the manual.
Hardw
HARD 77
Revision 5.0
LED fig. 35/i
AddrThe d
fig. 36/i
A
B
C
C
LED
Alarm
Read
1
N OFF
23
4
Dipsw
1
2
3
4
are reference
WARE REFERENCE MANUAL
indicators on the NS115
ess settings (SW1 & SW2)ipswitches (B) on the NS115 configure the communication settings.
Color Description
Red Lit: an alarm occurredNot lit: no alarm active
y Green Lit: communication activeNot lit: no communication in progress
O
itch Function Setting Description
Baud rate on 10 Mbps
Data length on 32-byte data transmission
Address range off Addresses 40-4F
on Addresses 50-5F
Maintenance (Reserved)
off Must always be set to off. on is not used
Hardw
HARD 78
Revision 5.0
fig. 37Set thto F) /i
Do no
Rotarswitcnumb
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
are reference
WARE REFERENCE MANUAL
e address selector (A, fig 35) of the NS115 to n (where n ranges from 0 to assign the following address to the NS115:
t use the addresses 40 and 51-5F. Use only the addresses 41-50.
y h er
Dipswitch 3 Station address Axis in motion controller
off 41 0
off 42 1
off 43 2
off 44 3
off 45 4
off 46 5
off 47 6
off 48 7
off 49 8
off 4A 9
off 4B 10
off 4C 11
off 4D 12
off 4E 13
off 4F 14
on 50 15
Hardw
HARD 79
Revision 5.0
MECfig. 38Conn
MECconnetermidevic
CN4 CN4 basedmotoyou h• T• T
The s
The tspeci
are reference
WARE REFERENCE MANUAL
HATROLINK-II connectors (CN1A & CN1B) ect to the MECHATROLINK-II network as in the figure using a suitable HATROLINK-II cable. Both connectors are parallelled so you can ct both cables to both connectors. Connect a MECHATROLINK-II
nator resistor in one of the connectors if the Servo Driver is the last e in the network.
Full-closed encoder connectoris for connecting a full-closed encoder, that is, the position is controlled in one external encoder, and the speed and torque loop based in the
r encoder. This is used when you install the motor in machines where ave to measure directly on the load because either:here is slip or backlash in the mechanical transmission.he precision required is very high.
upported encoder is line driver and the pinout is shown in the figure.
able shows the CN4 connector terminal layout and connector fications.
Hardw
HARD 80
Revision 5.0
fig. 39/i
Relev
External PG
Externalpower supply
FA/FA
PG0V
FB/FBFC/FC
A/A
GND
B/BZ/Z
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
are reference
WARE REFERENCE MANUAL
ant servo parameters related with the use of Trajexia:
NS115
1,2,31617
1918
1415
CN4PG0V Signal ground
PG0V Signal ground
PG0V Signal ground
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
FC Phase-C input +
/FC Phase-C input -
FA Phase-A input +
/FA Phase-A input -
FB Phase-B input +
/FB Phase-B input -
- -
NoteMake sure that shielded cable is used and that the shield is con-nected to the connector shell.
Hardw
HARD 81
Revision 5.0
EncoThesUNIT• P
m• P
Abso• P
co
Full • P
Z• P
1
Usin• P• P• P
d• P
For thinput ProgrFor th
RelaThe fServo• A• A• A• A
are reference
WARE REFERENCE MANUAL
der gear ratio resolutione two parameters define the units of the system in combination with S.n202: Gear ratio numerator. Default is 4, set to 1 to obtain the aximum encoder resolution.n203: Gear ratio denominator. Default=1.
lute encodern205= Number of multiturn limit. Default 65535. Set to suitable value in mbination with the encoder gear ratio and UNITS.
close encodern002.3: 0=Disabled, 1=uses without Z, 2=uses with Z, 3=uses without reverse rotation, 4= uses with Z reverse rotation.n206: Number of full-closed encoder pulses per revolution. Default 6384
g the Servo Driver digital inputs with Trajexian50A: Mapping of the forward limit switch (P_OT).n50B: Mapping of the reverse limit switch (N_OT).n511: Mapping of the registration inputs and zero point return eclaration.n81E: Mapping of the normal inputs.
e overview of all possible settings and parameter values to map the signals from the Servo Driver to Trajexia, refer to the Trajexia amming manual, chapter “Mapping Servo Driver inputs and outputs”.e rest of the parameters and connections refer to the Sigma-II manual.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II Drivers Sigma-II series:
TYPEXISXIS_ENABLEXISSTATUS
Hardw
HARD 82
Revision 5.0
• D• D• D• D• D• D• D• D• D
For m
3.5.9fig. 40You c
/i
43
210FEDC B A98765 ON
1
CN6
A/B
CN3
CN7
CN1
CN8
CN2
N PO
RQ
H
I
J
K
L
M
LabeA
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
are reference
WARE REFERENCE MANUAL
RIVE_ALARMRIVE_CLEARRIVE_CONTROLRIVE_INPUTSRIVE_MONITORRIVE_READRIVE_RESETRIVE_STATUSRIVE_WRITE
ore information, refer to the Trajexia Programming Manual.
MECHATROLINK-II Servo Drivers Sigma-V series
an also connect a Sigma-V Servo Driver to a Trajexia system.
CHARGE
L1
L2
L3
L1
L2
B2
B1
B3
1
2
U
V
W
A
C
D
E
B
F
G
l Terminal/LED DescriptionCHARGE Charge indicator
L1, L2, L3 Main circuit power supply terminals
L1, L2 Control power supply terminals
B1, B2 Regenerative resistor connecting terminals
1, 2 DC reactor terminals for harmonic suppression
U, V, W Servo motor terminals
+ Ground terminal
CN6A/B MECHATROLINK-II bus connectors
CN3 Connector for digital operator
CN7 PC connector
CN1 I/O signal connector
CN8 Connector for safety function devices
CN2 Encoder connector
SW1 Rotary switch for MECHATROLINK-II address settings
SW2 Dipswitches for MECHATROLINK-II communication settings
Panel display
MECHATROLINK-II communication LED
Hardw
HARD 83
Revision 5.0
Comfig. 41The 4
/i
R
Labe
1
Dipsw
1
2
3
4
are reference
WARE REFERENCE MANUAL
munication settings (SW2) dipswitches configure the communication settings.
Power LED
l Terminal/LED Description
itch Function Setting Description Factory setting
Baud rate on 10 Mbps on
Data length on 32-byte data transmission on
Address range
off Addresses 40-4F off
on Addresses 50-5F
Reserved off Must always be set to off. on is not used
off
Hardw
HARD 84
Revision 5.0
Addrfig. 42Set th
from /i
Do no
Rotarswitcnumb
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
are reference
WARE REFERENCE MANUAL
ess settings (SW1)e address selector of the Sigma-V Servo Driver to n (where n ranges
0 to F) to assign the following station address to it:
t use the addresses 40 and 51-5F. Use only the addresses 41-50.
y h er
Dipswitch 3 Station address Axis in motion controller
off 41 0
off 42 1
off 43 2
off 44 3
off 45 4
off 46 5
off 47 6
off 48 7
off 49 8
off 4A 9
off 4B 10
off 4C 11
off 4D 12
off 4E 13
off 4F 14
on 50 15
Hardw
HARD 85
Revision 5.0
LEDs/i
PaneThe pServoThe p• S
T/i
LED
Charg
Powe
MECHnicati
Displ
are reference
WARE REFERENCE MANUAL
l displayanel display is a 7-segment LED display. It indicates the status of the Driver.anel display has 3 display modes:tatus displayhe display shows the statuses listed in the table below.
Color Description
e indicator Orange Lit: main circuit power supply is on or internal capacitor is chargedNot lit: no power supply and internal capacitor is not charged
r LED Green Lit: control power is suppliedNot lit: no control power
ATROLINK-II commu-on LED
Green Lit: communication activeNot lit: no communication
ay Description Remark
Baseblock Comes on when the motor current is shut off. Does not come on when the Servo Driver is on
Rotation detection(/TGON)
Comes on when the motor speed is greater than the value set in Pn502
Reference input Comes on when a reference is being input
CONNECT Comes on during connection
Hardw
HARD 86
Revision 5.0
• Afig. 43If
wT
• Tefig. 44T
w
MECConnthe CconneTJ1-Mnext Mtermi
CN1 The t/i
Unlit Unlit Unlit
Unlit Unlit Unlit
Pin
1
2
3
4
5
6
7
8
9
10
11
are reference
WARE REFERENCE MANUAL
larm/warning an alarm or a warning occurs, the display shows the alarm code or the arning code.he figure shows an example of displaying alarm code A.E60.
st without motorhe display shows the sequence given in the figure if a test is executed ithout a motor.
HATROLINK-II connectors (CN6A & CN6B)ect the Sigma-V Servo Driver to the MECHATROLINK-II network using N6A and CN6B connectors. Use one of the MECHATROLINK-II ctors to connect to the previous MECHATROLINK-II device or the L__. Use the other MECHATROLINK-II connector to connect to the ECHATROLINK-II device, or to connect a MECHATROLINK-II
nator.
I/O Signal connectorable below shows the pin layout for the I/O signal connector (CN1).
StatusDisplay
Unlit Unlit
StatusDisplay
Unlit Unlit
I/O Signal Signal name
Output /BK+ (/SO1+) Brake interlock signal
Output /BK- (/SO1-) Brake interlock signal
Output ALM+ Servo alarm output signal
Output ALM- Servo alarm output signal
N/A N/A Not used
Input +24 V IN Control power supply for sequence signal
Input P-OT Forward run prohibited
Input N-OT Reverse run prohibited
Input /DEC Homing deceleration limit switch
Input /EXT1 External latch signal 11
Input /EXT2 External latch signal 21
Hardw
HARD 87
Revision 5.0
For m
CN2 The t/i
snds are related to the MECHATROLINK-II s:
the Trajexia Programming Manual.
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
1.
Pin1
2
3
4
5
PinPG serial signal input (-)
-
Description
are reference
WARE REFERENCE MANUAL
ore information, refer to the Sigma-V Series SERVOPACKs manual.
encoder connectorables below shows the pin layout for the Sigma-V encoder connector.
Related BASIC commandThe following BASIC commaServo Drivers Sigma-V serie• ATYPE• AXIS• AXIS_ENABLE• AXISSTATUS• DRIVE_ALARM• DRIVE_CLEAR• DRIVE_CONTROL• DRIVE_INPUTS• DRIVE_MONITOR• DRIVE_READ• DRIVE_RESET• DRIVE_STATUS• DRIVE_WRITE
For more information, refer to
Input /EXT3 External latch signal 31
Input /SIO General-purpose input signal
N/A N/A Not used
N/A N/A Not used
Output FG Signal ground
N/A N/A Not used
N/A N/A Not used
N/A N/A Not used
N/A N/A Not used
Input BAT (+) Battery (+) input signal
Input BAT (-) Battery (-) input signal
Output /SO2+ General-purpose output signal
Output /SO2- General-purpose output signal
Output /SO3+ General-purpose output signal
Output /SO3- General-purpose output signal
NPN only.
Signal DescriptionPG 5 V PG power supply +5 V
PG 0 V PG power supply 0 V
BAT (+) Battery (+)(For an absolute encoder)
BAT (-) Battery (-)(For an absolute encoder)
PS PG serial signal input (+)
I/O Signal Signal name6 /PS
Shell Shield
Pin Signal
Hardw
HARD 88
Revision 5.0
3.5.1fig. 45You c
/i
LED /i
DY
43210 F EDCBA987
65
ON
1
I GH
EF
K
LabeA
B
C
D
E
F
G
H
I
J
K
LEDCOM
ALM
RDY
are reference
WARE REFERENCE MANUAL
0 MECHATROLINK-II Servo Drivers Junma series
an also connect a Junma Servo Driver to a Trajexia system.
indicators
COM ALM R
FIL
L1
PWR
L2
U
V
W
CNBCNA
CN2
CN1
CN6
A/B
4321
0F E D CBA9
8765A
B
C
D
J
l Terminal/LED DescriptionFIL Rotary switch for reference filter setting
CN6A & CN6B MECHATROLINK-II bus connectors
CN1 I/O signal connector
CN2 Encoder input connector
SW1 Rotary switch for MECHATROLINK-II address settings
SW2 Dipswitches for MECHATROLINK-II communication settings
RDY Servo status indicator
ALM Alarm indicator
COM MECHATROLINK-II communication status indicator
CNA Connector for power supply
CNB Connector for servo motor
DescriptionLit: MECHATROLINK-II communication in progressNot lit: No MECHATROLINK-II communication
Lit: An alarm occurredNot lit: no alarm
Lit: Power is on, standby for establishment of communicationBlinking: Servo ON status
Hardw
HARD 89
Revision 5.0
Comfig. 46The 4
/i
1
Dipsw1
2
3
4
are reference
WARE REFERENCE MANUAL
munication settings (SW2) dipswitches configure the communication settings.
itch Function Setting DescriptionReserved ON Must always be set to ON. OFF is not used
Data length
ON 32 bytes
Addressrange
OFF Addresses 40-4F
ON Addresses 50-5F
Filtersetting
OFF Set the filter with the FIL rotary switch
ON Set the filter with Pn00A
Hardw
HARD 90
Revision 5.0
Addrfig. 47Set th
from /i
Do no
Rotarswitcnumb
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
are reference
WARE REFERENCE MANUAL
ess settings (SW1)e address selector of the Junma Servo Driver to n (where n ranges
0 to F) to assign the following station address to it:
t use the addresses 40 and 51-5F. Use only the addresses 41-50.
y h er
Dipswitch 3 Station address Axis in motion controller
off 41 0
off 42 1
off 43 2
off 44 3
off 45 4
off 46 5
off 47 6
off 48 7
off 49 8
off 4A 9
off 4B 10
off 4C 11
off 4D 12
off 4E 13
off 4F 14
on 50 15
Hardw
HARD 91
Revision 5.0
CN1 fig. 48The t
/i
MECConnthe CconneTJ1-Mnext Mtermi
10 11 12 13 14
2 3 4 5 6 7
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Shell
are reference
WARE REFERENCE MANUAL
I/O Signal connectorable below shows the pin layout for the I/O signal connector (CN1).
HATROLINK-II connectors (CN6A & CN6B)ect the Junma Servo Driver to the MECHATROLINK-II network using N6A and CN6B connectors. Use one of the MECHATROLINK-II ctors to connect to the previous MECHATROLINK-II device or the L__. Use the other MECHATROLINK-II connector to connect to the ECHATROLINK-II device, or to connect a MECHATROLINK-II
nator.
8 9
1
I/O Code Signal name
Input /EXT1 External latch
Input /DEC Homing deceleration
Input N_OT Reverse run prohibit
Input P_OT Forward run prohibit
Input +24VIN External input power supply
Input E-STP Emergency stop
Output SG-COM Output signal ground
N/C
N/C
N/C
N/C
Output ALM Servo alarm
Output /BK Brake
N/C
- - FG
Hardw
HARD 92
Revision 5.0
CN2 fig. 49The t
conne/i
CNAfig. 50The t
/i
246810
9 7 5 3 1Pin1
2
3
4
5
6
7
8
9
10
Shell
A
43
21
N
1
2
3
4
Pin1
2
3
4
are reference
WARE REFERENCE MANUAL
encoder input connectorables below shows the pin layout for the Junma Servo Driver encoder ctor.
power supply connectorables below shows the pin layout for the CNA power supply connector.
SignalPG5V
PG0V (GND)
Phase A (+)
Phase A (-)
Phase B (+)
Phase B (-)
Phase /Z
Phase U
Phase V
Phase W
-
Signal NameL1 Power supply terminal
L2 Power supply terminal
+ Regenerative unit connection terminal
- Regenerative unit connection terminal
Hardw
HARD 93
Revision 5.0
CNBfig. 51The t
/i
RelaThe fServo• A• A• A• A• D• D• D• D• D• D• D• D• D
For m
A
12
34
N
1
2
3
4
Pin1
2
3
4
are reference
WARE REFERENCE MANUAL
servo motor connectorables below shows the pin layout for the CNB servo motor connector.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II Drivers Junma series:
TYPEXISXIS_ENABLEXISSTATUSRIVE_ALARMRIVE_CLEARRIVE_CONTROLRIVE_INPUTSRIVE_MONITORRIVE_READRIVE_RESETRIVE_STATUSRIVE_WRITE
ore information, refer to the Trajexia Programming Manual.
Signal NameU Phase U
V Phase V
W Phase W
N/C
Hardw
HARD 94
Revision 5.0
3.5.1fig. 52You c
/i
LED /i
G
K
L
J
M
I
H
COM
X10
32
10ADR
AC SERVO DRIVE
X1
6
78
9 0 1
23
45
LabeA
B
C
D
E
F
G
H
I
J
K
L
M
LEDCOM
are reference
WARE REFERENCE MANUAL
1 MECHATROLINK-II Servo Drivers G-series
an also connect a G-Series Servo Driver to a Trajexia system.
indicators
A
E
C
B
D
F
G
IM
SP
l Terminal/LED DescriptionSP, IM, G Analog monitor check pins
L1, L2, L3 Main-circuit power terminals
L1C, L2C Control-circuit power terminals
B1, B2, B3 External Regeneration Resistor connection terminals
U, V, W Servomotor connection terminals
CN2 Protective ground terminals
--- Display area
--- Rotary switches
COM MECHATROLINK-II communications status LED indicator
CN3 RS-232 communications connector
CN6A, CN6B MECHATROLINK-II communications connector
CN1 Control I/O connector
CN2 Encoder connector
DescriptionLit: MECHATROLINK-II communication in progressNot lit: No MECHATROLINK-II communication
Hardw
HARD 95
Revision 5.0
Addrfig. 53Set th
addreThe sactuaswitccorre
MECHATROLINK-IIcommunicationsstatus LED indicator (COM)
Rotary switches for setting a node address
COM
X10
32
10ADR
AC SERVO DRIVER
X1
6
78
9 0 1
23
45
are reference
WARE REFERENCE MANUAL
ess settings (SW1)e address selector of the G-series Servo Driver to the required node ss by using the X1 (right) and X10 (left) rotary switches.etting range for the node address setting rotary switch is 1 to 31. The l station address used on the network will be the sum of the rotary h setting and the offset value of 40h. These node addresses spond to axis numbers 0 (node address = 1) to 15 (node address = 16).
7-segment LED (2 digits)
Analog monitor pinsSpeed monitorTorque monitorSignal ground
SP: IM: G:
G
IM
SP
NoteThe node address is only loaded once when the control power supply is turned ON. Changes made after turning the power ON will not be applied until the power is turned ON next time. Do not change the rotary switch setting after turning the power ON
NoteIf the rotary switch setting is not between 1 and 31, a node address setting error (alarm code 82) will occur.
Hardw
HARD 96
Revision 5.0
7-segfig. 54The d
Whendisplaparamwarni
9k0. 0k0.
upply
All OFF
All ON (approx. 0.6 s)
[nA] (Node Address) (approx. 0.6 s)
Rotary switch setting (for MSD = 0, LSD = 3) (Time set by the Power ON Address Display Duration Setting (Pn006))
lay (Pn001) is set to 0)>
Warning code (2 s) Normal Display (approx. 4 s)
lay)
Alternates between warning code (hex) and normal display (Below is an example for overload)
<Warning Display>
Warning Issued Warning Clearedleared
ervo OFF
[- -] + right dot ON
[00] + right dot ON
ain Power Supply OFF Network Not Established
[- -]
are reference
WARE REFERENCE MANUAL
ment LEDisplay of the 7-segment LED on the front panel is shown below.
the power is turned ON, the node address set with the rotary switch is yed, followed by the display content set by the Default Display (Pn001) eter. When an alarm occurs, the alarm code will be displayed. When a
ng occurs, the warning code will be displayed.
8.8.
nkak
k3k
1k6k
-k-k
-k-.
0k0.
Turn ON Control Power S
<Node Address Display>
<Normal Display (when the Default Disp
Main Power Supply ON and Network Established
Servo ON
Alarm Issued
<Alarm Display>Alarm code flashes in decimal disp(Below is an example for overload
Alarm C
S
Mor
Hardw
HARD 97
Revision 5.0
CN1 fig. 55The t
/i
20
22
24
to 24-VDC ower Supply
Input19
21
23
25
27
29
31
33
35
26
28
30
32
34
36
POTForward Drive Prohibit Input
NOT
DEC
IN0
Origin Proximity Input
OUTM2General-purpose
Output 2
BAT Backup Battery Input
BATCOMlarm Output
ternal Latch Signal 3
Reverse Drive Prohibit Input
ExternalGeneral-purpose
Input 0
rward Torque Limit Input
ternal Latch Signal 1
*
*
*
*
IN2External
General-purpose Input2
*
*
OUTM2COMGeneral-purpose
Output 2
OUTM3General-purpose
Output 3OUTM3COM General-purpose
Output 3Backup Battery
Input
OUTM1COMGeneral-purpose
Output1
OUTM1General-purpose
Output 1
*
*
*
Pin
1
2
3
4
5
6
7
8
19 to
21
22
23
11 to
9 to 1
27 to
34
33
17 to
24 to
are reference
WARE REFERENCE MANUAL
I/O Signal connectorable below shows the pin layout for the I/O signal connector (CN1).
2
4
6
8
10
12
14
16
18
12P
Emergency Stop Input
+24VIN1
3
5
7
9
11
13
15
17
IN1
EXT3
Reverse Torque Limit Input
STOP
ALMCOM Alarm Output
/ALM A
NCL
PCL
Ex
Fo
ExternalGeneral-purpose
Input 1
EXT2External Latch
Signal 2EXT1 Ex
*
*
*
*
I/O Code Signal name
Input +24VIN 12 to 24-VDC Power Supply Input
Input STOP Emergency Stop Input
Input EXT3 External Latch Signal 3
Input EXT2 External Latch Signal 2
Input EXT1 External Latch Signal 1
Input IN1 External general-purpose Input 1
Input PCL Forward Torque Limit Input
Input NCL Reverse Torque Limit Input
20 Input POT Forward Drive Prohibit Input
NOT Reverse Drive Prohibit Input
Input DEC Origin Proximity Input
Input IN0 External general-purpose Input 0
Input IN2 External general-purpose Input 2
14 Input --- Spare inputs. Do not connect anything to these inputs.
0 Input --- Spare inputs. Do not connect anything to these inputs.
28 Input --- Spare inputs. Do not connect anything to these inputs.
Input BAT BackupBattery InputInput BATCOM
18 Input --- Spare inputs. Do not connect anything to these inputs.
26 Input --- Spare inputs. Do not connect anything to these inputs.
Hardw
HARD 98
Revision 5.0
MECfig. 56Conn
the CconneTJ1-Mnext Mtermi
15
16
29
30
31
32
36
35
Shell
Pin
L2 Ln
Termination resistor
are reference
WARE REFERENCE MANUAL
HATROLINK-II connectors (CN6A & CN6B)ect the G-series Servo Driver to the MECHATROLINK-II network using N6A and CN6B connectors. Use one of the MECHATROLINK-II ctors to connect to the previous MECHATROLINK-II device or the L__. Use the other MECHATROLINK-II connector to connect to the ECHATROLINK-II device, or to connect a MECHATROLINK-II
nator.
Output /ALM Alarm Output
Output ALMCOM
Output OUTM2 General-purposeOutput 2 (READY)Output OUTM2COM
Output OUTM3 General-purposeOutput 3 (CLIM)Output OUTM3COM
Output OUTM1 General-purposeOutput 1 (BKIR)Output OUTM1COM
--- --- FG
I/O Code Signal name
0123456789A
BCDEF
MC Unit
L1
NoteCable length between nodes (L1, L2, ... Ln) should be 0.5 m or longer.Total cable length should be L1 + L2 + ... + Ln = 50 m max.
Hardw
HARD 99
Revision 5.0
CN2 The t/i
CNAThe t/i
Pin1
2
3
4
5
6
Shell
Pin1
2
3
4
5
are reference
WARE REFERENCE MANUAL
encoder input connectorable below shows the pin layout for the encoder connector.
power supply connectorable below shows the pin layout for the CNA power supply connector.
Signal NameE5V Encoder power supply +5 V
E0V Encoder power supply GND
BAT+ Battery +
BAT- Battery -
PS+ Encoder +phase S input
PS- Encoder -phase S input
FG Shield ground
Signal NameL1 Main circuit
power supply inputL2
L3
L1C Control circuitpower supply inputL2C
Hardw
HARD 100
Revision 5.0
CNBThe t/i
Pin1
2
3
4
5
6
7
8
are reference
WARE REFERENCE MANUAL
servo motor connectorable below shows the pin layout for the CNB servo motor connector.
Signal NameB1 External Regeneration Resistor
connection terminalsB2
B3
U Servomotorconnectionterminals
V
W
Frame ground
Hardw
HARD 101
Revision 5.0
3.5.1fig. 57You c
/i
LabeA
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
are reference
WARE REFERENCE MANUAL
2 MECHATROLINK-II Servo Drivers Accurax G5
an also connect an Accurax G5 Servo Driver to a Trajexia system.
l Terminal/LED Description--- Display area
CN5 Analog monitor check pins
L1, L2, L3 Main-circuit power terminals
L1C, L2C Control-circuit power terminals
CHARGE Charge lamp
B1, B2, B3 External Regeneration Resistor connection terminals
U, V, W Servomotor connection terminals
--- Protective ground terminals
COMM MECHATROLINK-II communications status LED indicator
--- Rotary switches
CN6A, CN6B MECHATROLINK-II communications connector
CN7 USB connector
CN8 Connector for safety function devices
CN1 Control I/O connector
CN4 Full-closed encoder connector
CN2 Encoder connector
Hardw
HARD 102
Revision 5.0
MECThe tcondi/i
LED Not li
Green
Green
Red F
Red L
are reference
WARE REFERENCE MANUAL
HATROLINK-II Communications Status LED Indicatorable below shows the LED indication status and the corresponding tions of the communications.
status Communications statust No communication is established.
Flash Asynchronous communications is established.
Light Synchronous communications is established.
lash A clearable error occurred in MECHATROLINK-II communications.• Communications error (Err83.0)• Transmission cycle error (Err84.0)• SSYNC_SET error (Err84.4)• Watchdog data error (Err86.0)• Transmission cycle setting error (Err90.0)• CONNECT error (Err90.1)• SYNC command error (Err91.0)
ight A non-clearable error occurred in MECHATROLINK-II communica-tions.• Node address setting error (Err82.0)• SYNC process error (Err84.3)
NoteIf any of communication related error occurs while an error that is not related to MECHATROLINK-II communications happens, the MECHATROLINK-II Communications Status LED Indicator follows the corresponding communications status as shown above.
Hardw
HARD 103
Revision 5.0
Addrfig. 58Set th
nodeThe sactuaswitccorre
MECHATROLINK-II communicationsstatus LED indicator (COMM)
Rotary switches fornode address setting
ADRCOMM
are reference
WARE REFERENCE MANUAL
ess settings (SW1)e address selector of the Accurax G5 Servo Driver to the required
address by using the X1 (right) and X10 (left) rotary switches.etting range for the node address setting rotary switch is 1 to 31. The l station address used on the network will be the sum of the rotary h setting and the offset value of 40h. These node addresses spond to axis numbers 0 (node address = 1) to 15 (node address = 16).
Connector forAnalog Monitor
7-segment LEDindicator (2-digit)
NoteThe node address set by the rotary switch is read only once when the control power is turned on. Any changes made by the rotary switches after the power-on are not reflected to the Controller.Such changes become effective only after the subsequent power-on following to a power-off. Do not change the rotary switch setting after the power-on.
NoteThe settable range for a node address is between 1 and 31. The node address used over the network is the value obtained by add-ing the offset 40h to the rotary switch set value. If any value over or under the range is set, the Node address setting error (Err82.0) occurs.
Hardw
HARD 104
Revision 5.0
7-segfig. 59The 7
Whenrotaryon therror indica
9k0. 0k0.
upply
All OFF
All ON (approx. 0.6 s)
[nA] (Node Address) (approx. 0.6 s)
Rotary switch setting (for MSD = 0, LSD = 3) (Time set by the Power ON Address Display Duration Setting (Pn006))
lay (Pn001) is set to 0)>
Warning code (2 s) Normal Display (approx. 4 s)
lay)
Alternates between warning code (hex) and normal display (Below is an example for overload)
<Warning Display>
Warning Issued Warning Clearedeared
ervo OFF
[- -] + right dot ON
[00] + right dot ON
ain Power Supply OFF Network Not Established
[- -]
are reference
WARE REFERENCE MANUAL
ment LED-segment LED indicator is on the front panel. the power is turned on, it shows the node address that is set by the switches. Then the indication changes in accordance with the setting
e Default Display (Pn700). If any alarming error occurs, it indicates the number (Errxxx) as the alarm code. If any warning situation occurs, it tes the warning number as the warning code.
8.8.
nkak
k3k
1k6k
-k-k
-k-.
0k0.
Turn ON Control Power S
<Node Address Display>
<Normal Display (when the Default Disp
Main Power Supply ON and Network Established
Servo ON
Alarm Issued
<Alarm Display>Alarm code flashes in decimal disp(Below is an example for overload
Alarm Cl
S
Mor
Hardw
HARD 105
Revision 5.0
CN1 fig. 60The t
/i14
16
18
20
22
24
26
15
17
19
21
23
25
*
BAT
BATGND
OUTM2
*
GND
OUTM2COM
*
*
*
*
*
*
General-purposeOutput 2 Common
eneral-purposeutput 1 Common
Absolute encoder backup
battery input
Absolute encoder backup
battery input
2 to 24-VDC power
supply input
General-purposeOutput 2
larm OutputCommon
eneral-purposenput 5
eneral-purposeInput 7
Signal Ground
eneral-purposeInput 3
Pin
6
5
7
8
9
10
11
12
13
3
4
1
2
25
26
14
15
16
17 to
Shell
are reference
WARE REFERENCE MANUAL
I/O Signal connectorable below shows the pin layout for the I/O signal connector (CN1).
1
3
5
7
9
11
13
2
4
6
8
10
12
IN2
IN1
OUTM1
ALMCOM
/ALM
IN8
IN3
IN4
IN5
IN6
IN7
OUTM1COM
General-purposeInput 2
General-purposeOutput 1
GO
+24 VIN1
AAlarm Output
General-purposeInput 8
General-purposeInput 4
G
General-purposeInput 6
G
General-purposeInput 1
G
I/O Code Signal name
Input +24 VIN 12 to 24-VDC Power Supply Input
Input IN1 General-purpose Input 1
Input IN2 General-purpose Input 2
Input IN3 General-purpose Input 3
Input IN4 General-purpose Input 4
Input IN5 General-purpose Input 5
Input IN6 General-purpose Input 6
Input IN7 General-purpose Input 7
Input IN8 General-purpose Input 8
Output /ALM Alarm output
Output ALMCOM
Output OUTM1 General-purposeOutput 1Output OUTM1COM
Output OUTM2 General-purposeOutput 2Output OUTM2COM
--- BAT BackupBattery Input--- BATGND
--- GND Signal ground
24 Input --- Spare inputs. Do not connect anything to these inputs.
--- --- FG
Hardw
HARD 106
Revision 5.0
MECfig. 61Conn
the CconneTJ1-Mnext Mtermi
L2 Ln
Termination resistor
are reference
WARE REFERENCE MANUAL
HATROLINK-II connectors (CN6A & CN6B)ect the G-series Servo Driver to the MECHATROLINK-II network using N6A and CN6B connectors. Use one of the MECHATROLINK-II ctors to connect to the previous MECHATROLINK-II device or the L__. Use the other MECHATROLINK-II connector to connect to the ECHATROLINK-II device, or to connect a MECHATROLINK-II
nator.
0123456789AB
CDEF
MC Unit
L1
NoteCable length between nodes (L1, L2, ... Ln) should be 0.5 m or longer.Total cable length should be L1 + L2 + ... + Ln = 50 m max.
Hardw
HARD 107
Revision 5.0
CN2 The t/i
CN4 The t/i
Pin1
2
3
4
5
6
Shell
Pin1
2
3
4
5
6
7
8
9
10
Shell
are reference
WARE REFERENCE MANUAL
Encoder input connectorable below shows the pin layout for the encoder connector.
External encoder connectorable below shows the pin layout for the external encoder connector.
Signal NameE5V Encoder power supply +5 V
E0V Encoder power supply GND
BAT+ Battery +
BAT- Battery -
PS+ Encoder +phase S input
PS- Encoder -phase S input
FG Shield ground
Signal NameE5V Encoder power supply +5 V
E0V Encoder power supply GND
PS+ Encoder +phase S input
PS- Encoder -phase S input
EXA+ Encoder +phase A input
EXA- Encoder -phase A input
EXB+ Encoder +phase B input
EXB- Encoder -phase B input
EXZ+ Encoder +phase Z input
EXZ- Encoder -phase Z input
FG Shield ground
Hardw
HARD 108
Revision 5.0
CN5 The t/i
CN7 The t/i
CN8 The t/i
Pin1
2
3
4
5
6
Pin1
2
3
4
5
Pin1
2
3
4
5
6
7
8
are reference
WARE REFERENCE MANUAL
Monitor connectorable below shows the pin layout for the CN5 monitor connector.
USB Connectorable below shows the pin layout for the CN7 USB connector.
Safety connectorable below shows the pin layout for the CN8 safety connector.
Signal NameAM1 Analog monitor output 1
AM2 Analog monitor output 2
GND Analog monitor ground
--- Reserved: do not connect.
--- Reserved: do not connect.
--- Reserved: do not connect.
Signal NameVBUS
USB signal terminalD+
D-
--- Reserved: do not connect.
SENGND Signal ground
Signal Name--- Reserved: do not connect.
--- Reserved: do not connect.
SF1- Safety input 1
SF1+
SF2- Safety input 2
SF2+
EDM- EDM output
EDM+
Hardw
HARD 109
Revision 5.0
CNAThe t/i
CNBThe t/i
RelaThe fServo• A• A• A• A• D
Shell
Pin1
2
3
4
5
Pin
Pin1
2
3
4
5
6
7
8
are reference
WARE REFERENCE MANUAL
Power supply connectorable below shows the pin layout for the CNA power supply connector.
Servo motor connectorable below shows the pin layout for the CNB servo motor connector.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II Drivers Accurax G5:
TYPEXISXIS_ENABLEXISSTATUSRIVE_ALARM
FG Shield ground
Signal NameL1 Main circuit
power supply inputL2
L3
L1C Control circuitpower supply inputL2C
Signal Name
Signal NameB1 External Regeneration Resistor
connection terminalsB2
B3
U Servomotorconnectionterminals
V
W
Frame ground
Hardw
HARD 110
Revision 5.0
• D• D• D• D• D• D• D• D
For m
are reference
WARE REFERENCE MANUAL
RIVE_CLEARRIVE_CONTROLRIVE_INPUTSRIVE_MONITORRIVE_READRIVE_RESETRIVE_STATUSRIVE_WRITE
ore information, refer to the Trajexia Programming Manual.
Hardw
HARD 111
Revision 5.0
3.5.1fig. 62A V7
speedinduc
By dean Incomminform
The iA. LB. MC. OD. CE. DF. RG. GH. C
B
F D
C
E
are reference
WARE REFERENCE MANUAL
3 MECHATROLINK-II Inverter V7
Inverter with a MECHATROLINK-II interface is designed to make and torque control (if the Inverter supports this feature) of an AC
tion motor. No position control is supported via MECHATROLINK-II.
fault an Inverter is not considered an axis by the TJ1-MC__. To control verter as a servo axis, this axis must be defined with function 8 of the and INVERTER_COMMAND. Refer to section 2.7.4 for more ation.
llustration shows the external appearance of the SI-T/V7 Unit.EDodular plug (CN10)ptional connector (CN1)ommunications connector (CN2)ipswitchotary switchround terminalommunications connector (CN2) H G
A
Hardw
HARD 112
Revision 5.0
LED fig. 63The L
MECA. RB. TC. RD. E
/i
DC
Name
RUN
ERR
TX
RX
are reference
WARE REFERENCE MANUAL
indicators ED indicators indicate the status of the communications of the
HATROLINK-II and the SI-T/V7 Unit.unXXRR
BA
Display Explanation
Color Status
Green Lit Normal operation
- Not lit Communications CPU stopped, resetting hardware, RAM check error, DPRAM check error, station address setting error or Inverter model code error
Red Lit Watchdog timeout error, communications error or reset-ting hardware
Red Flashing ROM check error (once)*, RAM check error (twice)*, DPRAM check error (3 times)*, communications ASIC self-diagnosis error (4 times)*, ASIC RAM check error (5 times)*, station address setting error (6 times)*, Inverter model code error (7 times)**: indicates the number of flashes
- Not lit No communication error or self-diagnosis error
Green Lit Sending data
- Not lit Sending of data stopped, hardware reset
Green Lit Searching for receiving carrier
- Not lit No receiving carrier found, hardware reset
Hardw
HARD 113
Revision 5.0
DipsThe f
fig. 64/i
RotaThe f
fig. 65/i
/i
2 3 4
OFF
Name
Baud
Data
Statioaddre
Maint
1.
43
21
7
65
8
B
A 9
F
E
0
Labe
S2
S1-3
off
off
off
are reference
WARE REFERENCE MANUAL
witch ollowing table shows the dipswitch settings of the SI-T/V7 Unit.
ry switchollowing table shows the rotary switch settings of the SI-T/V7 Unit.
1
Label Status Function
rate S1-1 on 10 Mbps (MECHATROLINK-II)
length S1-2 on 32-byte data transmission (MECHATROLINK-II)
n ss
S1-3 off Set the 10th digit of the station number to 2. Invalid if the maximum number of units including the S2 of the rotary switch is 20.
on Set the 10th digit of the station number to 3. Invalid if the maximum number of units including the S2 of the rotary switch is 3F.
enance S1-4 off Normally off1
For maintenance. Always leave this switch off.
on Not used
CD
l Status Function Factory setting
0 to F Set the 1st digit of the station number. Invalid if the maximum number of units including the S1-3 is 20 or 3F.
1
S2 Station number S1-3 S2 Station number
0 Fault on 0 30
1 21 on 1 31
2 22 on 2 32
Hardw
HARD 114
Revision 5.0
To usto ma• N• N
Chec
RelaThe fInver• A• IN• IN• IN
For m
off
off
off
off
off
off
off
off
off
off
off
off
off
S1-3
are reference
WARE REFERENCE MANUAL
e the V7 Inverter with the MECHATROLINK-II interface it is necessary ke the following settings in the Inverter:3=3 Sequence via MECHATROLINK-II4=9 Reference via MECHATROLINK-II
k the manual for details about the V7 Inverter.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II ters V7 series:TYPE (ATYPE=49) VERTER_COMMANDVERTER_READVERTER_WRITE
ore information, refer to the Trajexia Programming Manual.
3 23 on 3 33
4 24 on 4 34
5 25 on 5 35
6 26 on 6 36
7 27 on 7 37
8 28 on 8 38
9 29 on 9 39
A 2A on A 3A
B 2B on B 3B
C 2C on C 3C
D 2D on D 3D
E 2E on E 3E
F 2F on F Fault
S2 Station number S1-3 S2 Station number
Hardw
HARD 115
Revision 5.0
3.5.1fig. 66The F
to maAC inII.
By dean Incomminform
The iA. SB. CC. 3D. OE. 2F. 4
A
are reference
WARE REFERENCE MANUAL
4 MECHATROLINK-II Inverter F7 and G7
7 and G7 Inverters with a MECHATROLINK-II interface are designed ke speed and torque control (if the Inverter supports this feature) of an duction motor. No position control is supported via MECHATROLINK-
fault an Inverter is not considered an axis by the TJ1-MC__. To control verter as a servo axis, this axis must be defined with function 8 of the and INVERTER_COMMAND. Refer to section 2.7.4 for more ation
llustration shows the installation of the SI-T card.I-T Cardontrol terminalCN: Option D connectorption CN (To secure option C or D)CN: Option C connectorCN: Option A connector
D
F
E
C
B
Hardw
HARD 116
Revision 5.0
fig. 67The iA. LB. RC. DD. CE. CF. T
LED The LMEC
/i
A
C
B
D
Name
RUN
are reference
WARE REFERENCE MANUAL
llustration shows the external appearance of the SI-T Card.EDotary switchipswitchommunications connectorode No.ype
indicatorsED indicators indicate the status of the communications of the
HATROLINK-II and the SI-T Card.
F
E
Display Explanation
Color Status
Green Lit Normal operation
- Not lit Communication CPU stopped, resetting hardware, RAM check error, DPRAM check error, station address setting error or Inverter model code error
Hardw
HARD 117
Revision 5.0
Dipsfig. 68The f
/i
ERR
TX
RX
Name
2 3 4
OFF
Name
Baud
Data
Statioaddre
Maint
1.
are reference
WARE REFERENCE MANUAL
witchollowing table shows the dipswitch settings of the SI-T/V7 Unit.
Red Lit Watchdog timeout error, communication error, diagnosis error or resetting hardware
Red Flashing ROM check error (once)*, RAM check error (twice)*, DPRAM check error (3 times)*, communications ASIC self-diagnosis error (4 times)*, ASIC RAM check error (5 times)*, station address setting error (6 times)*, Inverter model code error (7 times)**: indicates the number of flashes
- Not lit No communication error or self-diagnosis error
Green Lit Sending data
- Not lit Sending of data stopped, hardware reset
Green Lit Searching for receiving carrier
- Not lit No receiving carrier found, hardware reset
Display Explanation
Color Status
1
Label Status Function
rate S1-1 on 10 Mbps (MECHATROLINK-II)
length S1-2 on 32-byte data transmission (MECHATROLINK-II)
n ss
S1-3 off Set the 10th digit of the station number to 2. Invalid if the maximum number of units including the S2 of the rotary switch is 20.
on Set the 10th digit of the station number to 3. Invalid if the maximum number of units including the S2 of the rotary switch is 3F.
enance S1-4 off Normally off1
For maintenance. Always leave this switch off.
on Not used
Hardw
HARD 118
Revision 5.0
RotaThe f
fig. 69/i
Switc/i
43
21
7
65
8
A 9
F
E
0
Labe
S2
S1-3
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
off
are reference
WARE REFERENCE MANUAL
ry switchollowing table shows the rotary switch settings of the SI-T/V7 Unit.
h Setting and Station Number:
BC
D
l Status Function Factory set-ting
0 to F Set the 1st digit of the station number X0H-XFH. Invalid if the maximum number of units including the S1-3 is 20 or 3F.
1
S2 Station number S1-3 S2 Station number
0 Fault on 0 30
1 21 on 1 31
2 22 on 2 32
3 23 on 3 33
4 24 on 4 34
5 25 on 5 35
6 26 on 6 36
7 27 on 7 37
8 28 on 8 38
9 29 on 9 39
A 2A on A 3A
B 2B on B 3B
C 2C on C 3C
D 2D on D 3D
E 2E on E 3E
F 2F on F Fault
Hardw
HARD 119
Revision 5.0
To usneces• B• B
Chec
RelaThe fInver• A• IN• IN• IN
For m
3.5.1
An I/Oinputsthe T
Digitfig. 70This i
MECautomand cTrajeand Oof exicorreIN(15The vA. InB. OC. In
B
C
D
A
are reference
WARE REFERENCE MANUAL
e the F7 or G7 Inverter with the MECHATROLINK-II interface it is sary to make the following settings in the Inverter:
1-01=3 Sequence via MECHATROLINK-II1-02=3 Reference via MECHATROLINK-II
k the corresponding manual for details about the F7 or G7 Inverter.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II ters F7 and G7 series:TYPE (ATYPE=49) VERTER_COMMANDVERTER_READVERTER_WRITE
ore information, refer to the Trajexia Programming Manual.
5 MECHATROLINK-II digital I/O slaves
device allows to integrate in the system remote digital and analogue and outputs. Those are autodetected and automatically allocated by
rajexia system.
al I/O module: JEPMC IO2310/IO2330 s a 64 channel Digital Input and 64 channel Digital Output HATROLINK-II slave unit. The digital inputs and outputs are
atically allocated by the Trajexia system according to the unit number an be read and set by Trajexia starting from IN(32) and OP(32).xia Inputs and outputs are automatically mapped starting from IN(32) P(32), according to the MECHATROLINK-II node number. In the case
sting several IO2310 units, the unit with lowest node number sponds to IN(32) to IN(95) and OP(32) to OP(95), the next lower to 6) to IN(219) and OP(156) to OP(219).alue is refreshed every servo period.put signal connector 1utput signal connector 1put signal connector 2
H
J
I
G
E
F
Hardw
HARD 120
Revision 5.0
D. OE. PF. I/G. SH. DI. MJ. I/
Connfig. 71I/O an
/i
IndicaSelec
fig. 72• IN• IN• O• O
fig. 73MECConn
R Active F12345678
910111213141516
1718192021222324
2526272829303132
IndicName
R
ACTI
F
1 to 3
IN22 IN1
OUT2OUT1
are reference
WARE REFERENCE MANUAL
utput signal connector 2ower supply terminalsO indicator switchtation number switchipswitch for settingECHATROLINK-II connectorO indicators
ector description d Status Indicators:
tor switch:ts which 32 I/O points are monitored by the I/O indicators.1: Input signals 1 to 322: Input signals 33 to 64UT1: Output signals 1 to 32UT2: Output signals 33 to 64
HATROLINK-II Connector:ects through a MECHATROLINK-II cable.
ator Indicator Color Meaning when lit
Yellow Not used, stays lit
VE Yellow Sending data through MECHATROLINK-II
Red Blown fuse
2 Yellow Input signal and output signal monitors.The meaning of these indicators depends on the I/O indicator switch setting.
SW
Hardw
HARD 121
Revision 5.0
I/O Sfig. 74Conn
Numb 1 OUT 1 IN 2 OUT 2
B1A1 B1A1 B1A1 B1
are reference
WARE REFERENCE MANUAL
ignal connector:ect the I/O Unit with external I/O signals through the I/O Cable.er of I/O points: 64 inputs and 64 outputs IN
A1
Hardw
HARD 122
Revision 5.0
DigitaThe pmodu
/i
Note:
No.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
are reference
WARE REFERENCE MANUAL
l I/O layoutin layout of the I/O connectors is the same for the IO2310, and IO2330 les. The following table shows the pin layout of the IN1 connector.
The +24V_1 is used for IN01 to IN16; +24V_2 is used for IN17 to IN32.
Signal name Remarks No. Signal name Remarks
(NC) B1 (NC)
+24V_2 24-V power sup-ply 2
B2 +24V_2 24-V power sup-ply 2
IN32 Input 32 B3 IN31 Input 31
IN30 Input 30 B4 IN29 Input 29
IN28 Input 28 B5 IN27 Input 27
IN26 Input 26 B6 IN25 Input 25
IN24 Input 24 B7 IN23 Input 23
IN22 Input 22 B8 IN21 Input 21
IN20 Input 20 B9 IN19 Input 19
IN18 Input 18 B10 IN17 Input 17
IN16 Input 16 B11 IN15 Input 15
IN14 Input 14 B12 IN13 Input 13
IN12 Input 12 B13 IN11 Input 11
IN10 Input 10 B14 IN09 Input 9
IN08 Input 8 B15 IN07 Input 7
IN06 Input 6 B16 IN05 Input 5
IN04 Input 4 B17 IN03 Input 3
IN02 Input 2 B18 IN01 Input 1
(NC) B19 (NC)
+24V_1 24-V power sup-ply 1
B20 +24V_1 24-V power sup-ply 1
Hardw
HARD 123
Revision 5.0
The f/i
Note:
No.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
are reference
WARE REFERENCE MANUAL
ollowing table shows the pin layout of the IN2 connector.
The +24V_3 is used for IN33 to IN48; +24V_4 is used for IN49 to IN64.
Signal name Remarks No. Signal name Remarks
(NC) B1 (NC)
+24V_4 24-V power supply 4
B2 +24V_4 24-V power sup-ply 4
IN64 Input 64 B3 IN63 Input 63
IN62 Input 62 B4 IN61 Input 61
IN60 Input 60 B5 IN59 Input 59
IN58 Input 58 B6 IN57 Input 57
IN56 Input 56 B7 IN55 Input 55
IN54 Input 54 B8 IN53 Input 53
IN52 Input 52 B9 IN51 Input 51
IN50 Input 50 B10 IN49 Input 49
IN48 Input 48 B11 IN47 Input 47
IN46 Input 46 B12 IN45 Input 45
IN44 Input 44 B13 IN43 Input 43
IN42 Input 42 B14 IN41 Input 41
IN40 Input 40 B15 IN39 Input 39
IN38 Input 38 B16 IN37 Input 37
IN36 Input 36 B17 IN35 Input 35
IN34 Input 34 B18 IN33 Input 33
(NC) B19 (NC)
+24V_3 24-V power supply 3
B20 +24V_3 24-V power sup-ply 3
Hardw
HARD 124
Revision 5.0
The f/i
Note:+24V
No.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
are reference
WARE REFERENCE MANUAL
ollowing table shows the pin layout of the OUT1 connector.
The +24V_5 and 024V_5 are used for OUT01 to OUT16;_5 and 024V_6 are used for OUT17 to OUT32.
Signal name Remarks No. Signal name Remarks
024V_6 Common ground 6
B1 024V_6 Common ground 6
+24V_6 24-V power supply 6
B2 +24V_6 24-V power sup-ply 6
OUT32 Output 32 B3 OUT31 Output 31
OUT30 Output 30 B4 OUT29 Output 29
OUT28 Output 28 B5 OUT27 Output 27
OUT26 Output 26 B6 OUT25 Output 25
OUT24 Output 24 B7 OUT23 Output 23
OUT22 Output 22 B8 OUT21 Output 21
OUT20 Output 20 B9 OUT19 Output 19
OUT18 Output 18 B10 OUT17 Output 17
OUT16 Output 16 B11 OUT15 Output 15
OUT14 Output 14 B12 OUT13 Output 13
OUT12 Output 12 B13 OUT11 Output 11
OUT10 Output 10 B14 OUT09 Output 9
OUT08 Output 8 B15 OUT07 Output 7
OUT06 Output 6 B16 OUT05 Output 5
OUT04 Output 4 B17 OUT03 Output 3
OUT02 Output 2 B18 OUT01 Output 1
024V_5 Common ground 5
B19 024V_5 Common ground 5
+24V_5 24-V power supply 5
B20 +24V_5 24-V power sup-ply 5
Hardw
HARD 125
Revision 5.0
The f/i
Note:+24V
No.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
are reference
WARE REFERENCE MANUAL
ollowing table shows the pin layout of the OUT2 connector.
The +24V_7 and 024V_7 are used for OUT33 to OUT48;_8 and 024V_8 are used for OUT49 to OUT64
Signal name Remarks No. Signal name Remarks
024V_8 Common ground 8
B1 024V_8 Common ground 8
+24V_8 24-V power supply 8
B2 +24V_8 24-V power sup-ply 8
OUT64 Output 64 B3 OUT63 Output 63
OUT62 Output 62 B4 OUT61 Output 61
OUT60 Output 60 B5 OUT59 Output 59
OUT58 Output 58 B6 OUT57 Output 57
OUT56 Output 56 B7 OUT55 Output 55
OUT54 Output 54 B8 OUT53 Output 53
OUT52 Output 52 B9 OUT51 Output 51
OUT50 Output 50 B10 OUT49 Output 49
OUT48 Output 48 B11 OUT47 Output 47
OUT46 Output 46 B12 OUT45 Output 45
OUT44 Output 44 B13 OUT43 Output 43
OUT42 Output 42 B14 OUT41 Output 41
OUT40 Output 40 B15 OUT39 Output 39
OUT38 Output 38 B16 OUT37 Output 37
OUT36 Output 36 B17 OUT35 Output 35
OUT34 Output 34 B18 OUT33 Output 33
024V_7 Common ground 7
B19 024V_7 Common ground 7
+24V_7 24-V power supply 7
B20 +24V_7 24-V power sup-ply 7
Hardw
HARD 126
Revision 5.0
fig. 75I/O CThe fcable/i
Statiofig. 76Statio
MECUse aconne
fig. 77DipswThe d/i
The d
Name
I/O C
4 3 217
6 5
8
BA
9
C
FED
0
ONOFF
123_
Displno.)
-
3
2
1
are reference
WARE REFERENCE MANUAL
able:ollowing table shows the standard I/O cable models. The standard is used for both IO2310 and IO2330 modules.
n number and dipswitch settings n Number switch sets the station number of the module in the HATROLINK-II system. The range is 0 to F. unique station number for each unit if two or more units are cted.
itch settings:ipswitch sets the communication parameters.
ata in the parentheses indicate the MECHATROLINK-II addresses.
Model Length (m)
able JEPMC-W5410-05 0.5
JEPMC-W5410-10 1
JEPMC-W5410-30 3
ay (Switch Name Status Function
Reserved by system - Be sure to turn it off
MECHATROLINK-II upperplace address setting
on 7xh
off 6xh
I/O byte setting on 32-byte mode
Baud rate setting on 10 Mbps
Hardw
HARD 127
Revision 5.0
/i
StatioAddr
1(61h
2(62h
3(63h
4(64h
5(65h
6(66h
7(67h
8(68h
9(69h
10(6A
11(6B
12(6C
13(6D
14(6E
15(6F
are reference
WARE REFERENCE MANUAL
n ess
Dipswitch 3 Station number switch
Station Address
Dipswitch 3 Station number switch
) off 1 16(70h) on 0
) off 2 17(71h) on 1
) off 3 18(72h) on 2
) off 4 19(73h) on 3
) off 5 20(74h) on 4
) off 6 21(75h) on 5
) off 7 22(76h) on 6
) off 8 23(77h) on 7
) off 9 24(78h) on 8
h) off A 25(79h) on 9
h) off B 26(7Ah) on A
h) off C 27(7Bh) on B
h) off D 28(7Ch) on C
h) off E 29(7Dh) on D
h) off F Not used on E, F
Hardw
HARD 128
Revision 5.0
Powefig. 78The e
/i
Specfig. 79 Input
The iboth /i
DC
C
Term
DC24
DC0V
FG
Input Circuit
0.01 µF
+ 5V
Item
Numb
Input
Isolat
Input
Input
on vo
off vo
on tim
Outpu
are reference
WARE REFERENCE MANUAL
r supply inputxternal wiring terminal supplies 24 VDC to the I/O module.
ification circuit:nput circuit specifications are shown below. The input circuit is used for IO2310, and IO2330 modules.
24 V
0 VD
inal name Function
V +24 VDC
0 VDC
Protective ground terminal
4.7 kΩ
680 ΩSpecifications
er of input points 64 points (32 points x 2)
type Sinking or sourcing
ion method Photocoupler
voltage 24 VDC (20.4 to 28.8 VDC)
current 5 mA/point
ltage/current 9V min./1.6 mA min.
ltage/current 7V max./1.3 mA max.
e / off time on time: 2ms, off time: 3 ms
t points per common 16 points per common (1 to 16, 17 to 32, 33 to 48, 49 to 64)
Hardw
HARD 129
Revision 5.0
fig. 80OutpuThe o/i
Gene/i
cuit IO2310
+ 24V
O24V
10 kΩ
O24V
OUT
+ 24V
cuit IO2330
+ 24V
O24V
O24V
15 kΩ
OUT
+ 24V
Item
Modu
Numb
Outpu
Isolat
Outpu
Outpu
Leaka
on tim
Outpu
Fuses
Error
Item
Name
Mode
Mode
Exter
Rated
Inrush
Dime
are reference
WARE REFERENCE MANUAL
t circuit:utput specifications are shown below.
ral specifications:
Output Cir
Output Cir
Specifications
le IO2310 IO2330
er of output points 64 points (32 point x 2)
t type Transistor, open collector or sinking
Transistor, open collector or sourcing
ion method Photocoupler
t voltage 24 VDC (20.4 to 28.8 VDC)
t current 50 mA/point
ge current when off 0.1 mA max.
e / off time on time: 2 ms max., off time: 4 ms max.
t points per common 16 points per common (1 to 16, 17 to 32, 33 to 48, 49 to 64)
A fuse for each common point to prevent fire caused by the output short-circuit
detection Blown fuse detection
Specifications
64-point I/O Module
l description IO2310/IO2330
l number JEPMC-IO2310/JEPMC-IO2330
nal power supply 24 VDC (20.4 to 28. 8VDC)
current 0.5 A
current 1A
nsions (mm) 120 x 130 x 105 (W x H x D)
Hardw
HARD 130
Revision 5.0
RelaThe fdigita• IN• N• O
For m
are reference
WARE REFERENCE MANUAL
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II l I/O module:
IOP
ore information, refer to the Trajexia Programming Manual.
Hardw
HARD 131
Revision 5.0
3.5.1
fig. 81This iinputsunit nThe IMECunits,next lThe vA. LB. MC. MD. ME. TeF. DG. EH. SI. TeJ. MK. FL. D
ConnLED
fig. 82/i
C
D
F
B
A
G E
RR FLT CH1 CH2 Ch3 Ch4
Indicname
RDY
TX
RX
are reference
WARE REFERENCE MANUAL
6 MECHATROLINK-II 4-Channel analogue input module
s a 4-channel analogue input MECHATROLINK-II slave. The analogue are automatically allocated by the Trajexia system according to the umber and can be read by Trajexia starting from AIN(0)./Os are automatically mapped in AIN(x) according to the HATROLINK-II node number. In the case of existing several AN2900 the one with lowest node number corresponds to AIN(0) to AIN(3), the owest one to AIN(4) to AIN(7).alue is refreshed every servo_period.ED indicatorsodule description (AN2900)odule mounting holes (for M4 screws) for back mountingodule mounting holes (for M4 screws) for bottom mountingrminal cover
etachable terminalxternal connector terminals (M3, Phillips-head)ignal labelrminal block mounting screws (two M3.5 screws)ECHATROLINK-II connectorront coveripswitch
ector description Indicators:
J
L
K
I
H
RDY TX RX E
ator Indicator color Meaning when lit or flashing
Green Lit The module is operating normally
Flashing The transmission cable is discon-nected or the module is waiting for communication with the master
Green Lit Sending data
Green Lit Receiving data
Hardw
HARD 132
Revision 5.0
fig. 83DipswThe dshowuppeThe fAny schang/i
SlaveSet thfront Refer
ERR
FLT
CH1
Indicname
SW ON
ON2 3 4 5 6 7 8
Pin n
1 to 5
6
7
8
are reference
WARE REFERENCE MANUAL
itch functions: ipswitch consists of eight pins. The pins are numbered 1 to 8, as n in the illustration. Each pin is turned to on when it is moved to the r position.ollowing table shows the function of each switch.witches other than pin 7 become effective when each switch is ed.
address settings:e slave address with pins 1 to 5 on the dipswitch on the front of the
of the distributed I/O module. to the following table, and set the slave addresses as required.
Red Lit A communication error occurred
Red Lit Offset/gain setting error
Flashing Self-diagnostic error
to CH4 Green Lit Each LED indicates that the input is out-of-range for that channel.Out-of-range inputs are as follows:+10.02 V < Channel input signalChannel input signal < -10.02 V
ator Indicator color Meaning when lit or flashing
1
o. Setting Function
on Set the slave address of pins 1 through 5. For details, refer to the table below.off
on 32-byte data transmission (MECHATROLINK-II).
on Software filter (average is 5 times) is set to “Enabled“.
off Software filter is set to “Disabled“.
on Sets the baud rate to 10 Mbps.
Hardw
HARD 133
Revision 5.0
/i
Pin N
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
are reference
WARE REFERENCE MANUAL
o. Slave address
2 3 4 5
0 0 0 0 Not used
0 0 0 0 1
1 0 0 0 2
1 0 0 0 3
0 1 0 0 4
0 1 0 0 5
1 1 0 0 6
1 1 0 0 7
0 0 1 0 8
0 0 1 0 9
1 0 1 0 10
1 0 1 0 11
0 1 1 0 12
0 1 1 0 13
1 1 1 0 14
1 1 1 0 15
0 0 0 1 16
0 0 0 1 17
1 0 0 1 18
1 0 0 1 19
0 1 0 1 20
0 1 0 1 21
1 1 0 1 22
1 1 0 1 23
0 0 1 1 24
Hardw
HARD 134
Revision 5.0
SpecThe pare s/i
1
0
1
0
1
0
1
Item
Name
Mode
Mode
Input
Speci
Numb
Input
Maxim
Digita
Data
Error
Input
Samp
Pin N
1
are reference
WARE REFERENCE MANUAL
ification erformance specifications of the analogue input module (±10 V, 4 CH)
hown below.
0 0 1 1 25
1 0 1 1 26
1 0 1 1 27
0 1 1 1 28
0 1 1 1 29
1 1 1 1 30
1 1 1 1 Not used
Specifications
Analog input module (-10 V to + 10 V, 4 CH)
l description AN2900
l number JEPMC-AN2900
signal range -10 to 10V
al inputs None
er of input channels 4 channels, isolated as a group
impedance 1 MΩ min.
um allowable overload -20 to 20 V
l resolution 16 bits
format Binary (2s complement) -32,000 to 32,000
±0.5% F.S. (at 25ºC)±1.0% F.S. (at 0 to 60ºC)
delay time 4 ms max.
ling interval Input data is refreshed every communication cycle
o. Slave address
2 3 4 5
Hardw
HARD 135
Revision 5.0
fig. 84/i
The f
RelaThe fanalo• A• N
For m
Input
Numb
Maint
Exter
Item
Item
Input lation
Exter
Derat
Maxim
Hot s
weigh
Dime
are reference
WARE REFERENCE MANUAL
igure shows the circuit configuration for the analogue input module.
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II gue input module:IN AIO
ore information, refer to the Trajexia Programming Manual.
filter characteristics Software filter
er of allocated words 5 words/module
enance/diagnostic functions Watchdog timer
nal connections Removable terminal block with 23 M3 screw terminals
Specifications
Specifications
circuit iso- Isolation method
Photocoupler(There is no isolation between input channels.)
Dielectric strength
1,500 VAC for 1 minute between input terminals and internal circuits
Insulation resistance
100 MΩ min. at 500 VDC between input terminals and internal circuits (at room temperature and humidity)
nal power supply Main external power supply:24 VDC (20.4 to 26.4 VDC), 120 mA max.
ing conditions The maximum ambient operating temperature is limited with some mounting directions.
um heating value 2.88 W
wapping Terminal block: not permittedCommunication connector: permitted
t Approx. 300 g
nsions (mm) 161 x 44 x 79 (W x H x D)
Hardw
HARD 136
Revision 5.0
3.5.1fig. 85This i
analoto theThe IMECthe onext oThe vA. LB. MC. MD. ME. TeF. DG. EH. SI. TeJ. MK. FL. D
ConnLED
fig. 86/i
C
D
F
B
A
G E
RR FLT
Indicname
RDY
TX
are reference
WARE REFERENCE MANUAL
7 MECHATROLINK-II 2-Channel analogue output module
s a 2-channel analogue output MECHATROLINK-II slave. The gue output is automatically allocated by the Trajexia system according unit number and can be read by Trajexia starting from AOUT(0)./Os are automatically mapped in AOUT(x) according to the HATROLINK-II node number. In case of existing several AN2910 units, ne with lower node number corresponds to AOUT(0) to AOUT(1), the ne to AOUT(3) to AOUT(4).alue is refreshed every SERVO_PERIOD.ED indicatorsodule description (AN2910)odule mounting holes (for M4 screws) for back mountingodule mounting holes (for M4 screws) for bottom mountingrminal cover
etachable terminalxternal connector terminals (M3, Phillips-head)ignal labelrminal block mounting screws (two M3.5 screws)ECHATROLINK-II connectorront coveripswitch
ector descriptionIndicators:
J
L
K
I
H
RDY TX RX E
ator Indicator color Meaning when lit or flashing
Green Lit The module is operating normally
Flashing The transmission cable is discon-nected or the module is waiting for communication with the master
Green Lit Sending data
Hardw
HARD 137
Revision 5.0
fig. 87DipswThe dshowthe u
The schangThe feach /i
SlaveSet thdistribRefer/i
RX
ERR
FLT
Indicname
SW ON
ON2 3 4 5 6 7 8
Pin n
1 to 5
6
7
8
are reference
WARE REFERENCE MANUAL
itch functions: ipswitch consists of eight pins. The pins are numbered 1 to 8, as n in the following diagram. Each pin is turned to on when it is moved to pper position.
etting of each pin becomes effective as soon as the dipswitch is ed.
ollowing table shows the functions that correspond to the settings for pin.
address settings:e slave address with pins 1 to 5 on the dipswitch on the front of the uted I/O module. to the following table, and set the slave addresses as required.
Green Lit Receiving data
Red Lit A communication error occurred
Red Lit Offset/gain setting error
Flashing Self-diagnostic error
ator Indicator color Meaning when lit or flashing
1
o. Setting Function
on Set the slave address of pins 1 through 5. For details, refer to the table below:off
on 32-byte data transmission (MECHATROLINK-II).
on The output when communication stops is set to “data immedi-ately before stop“.
off The output when communication stops is set to “0“.
on Sets the baud rate to 10 Mbps.
Hardw
HARD 138
Revision 5.0
Pin N
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
are reference
WARE REFERENCE MANUAL
o. Slave address
2 3 4 5
0 0 0 0 Not used
0 0 0 0 1
1 0 0 0 2
1 0 0 0 3
0 1 0 0 4
0 1 0 0 5
1 1 0 0 6
1 1 0 0 7
0 0 1 0 8
0 0 1 0 9
1 0 1 0 10
1 0 1 0 11
0 1 1 0 12
0 1 1 0 13
1 1 1 0 14
1 1 1 0 15
0 0 0 1 16
0 0 0 1 17
1 0 0 1 18
1 0 0 1 19
0 1 0 1 20
0 1 0 1 21
1 1 0 1 22
1 1 0 1 23
0 0 1 1 24
Hardw
HARD 139
Revision 5.0
SpecThe pCH) aThe imodu
fig. 88/i
1
0
1
0
1
0
1
Pin N
1
7CH1+
9CH1-
8Shield 1
15
17
23
CH2+
CH2-
16Shield 2
220V
24 VDC
Isolationamplifier
0V (analog)
/Aon-
erter+
-
+
-
+ -
24 VDC
Load
Load
-12V
+12V
ingCter
ingCrter
Statusdisplay
Item
Name
Mode
Mode
Input
Numb
Maxim
Digita
Data
Error
Outpu
Numb
Maint
are reference
WARE REFERENCE MANUAL
ification erformance specifications of the analogue output module (±10 V, 2 re shown below.
llustration shows the circuit configuration for the analogue input le.
0 0 1 1 25
1 0 1 1 26
1 0 1 1 27
0 1 1 1 28
0 1 1 1 29
1 1 1 1 30
1 1 1 1 Not used
o. Slave address
2 3 4 5
Dc
v
InsulatDC/D
conver
InsulatDC/D
conve
From CPU
0V
+5V
0V (analog)
+12V-12V
+5V
Inte
rnal
Circ
uits Photocoupler
Specifications
Analog output module (-10 V to +10 V, 2 CH)
l description AN2910
l number JEPMC-AN2910
signal range -10 to 10V
er of output channels 2 channels
um allowable load current ±5 mA (2 kΩ)
l resolution 16 bits
format Binary (2s complement) -32,000 to 32,000
±0.2% F.S. (at 25ºC)±0.5% F.S. (at 0 to 60ºC)
t delay time 1 ms
er of allocated words 2 words/module
enance/diagnostic functions Watchdog timer
Hardw
HARD 140
Revision 5.0
RelaThe fanalo• A
For m
3.5.1
The JrangeMEC
Outpu
Exter
Outpuisolat
Exter
Derat
Maxim
Hot s
weigh
Dime
Item
are reference
WARE REFERENCE MANUAL
ted BASIC commandsollowing BASIC commands are related to the MECHATROLINK-II gue output module:OUT
ore information, refer to the Trajexia Programming Manual.
8 MECHATROLINK-II repeater
EPMC-REP2000 is a MECHATROLINK-II repeater. It extends the and the maximum number of MECHATROLINK-II devices in the
HATROLINK-II network.
t status when master stops Mode selected with the dipswitch (SW7):SW7 off: clear outputs (output 0 V)SW7 on: retain prior output status
nal connections Removable terminal block with M3 screw terminals
t circuit ion
Isolation method Photocoupler(There is no isolation between channels.)
Dielectric strength
1,500 VAC for 1 minute between output terminals and internal circuits
Insulation resist-ance
100 MΩ min. at 500 VDC between input terminals and internal circuits (at room temperature and humidity)
nal power supply Main external power supply:24 VDC (20.4 to 26.4 VDC), 120 mA max.
ing conditions The maximum ambient operating temperature is lim-ited with some mounting directions.
um heating value 2.88 W
wapping Terminal block: not permittedCommunication connector: permitted
t Approx. 300 g
nsions (mm) 161 x 44 x 79 (W x H x D)
Specifications
Hardw
HARD 141
Revision 5.0
fig. 89/i
LED /i
MECUse orepeaTJ1-MextenBoth
PowConn(CN3
C
AB
Term
A
B
C
D
E
F
LED
POW
TX1
TX2
are reference
WARE REFERENCE MANUAL
indicators
HATROLINK-II connectorsne MECHATROLINK-II connector (CN1 or CN2) to connect the ter to the master-side network, i.e. the part of the network that had the L__. Use the other connector to connect the repeater to the network
sion.connectors have a built-in terminator.
er supply connectorect an external 24 VDC power supply to the power supply connector ).
DE
F
inal/LED Label Description
TX1 CN1 communication indicator
TX2 CN2 communication indicator
POWER Power indicator
SW Dipswitch
CN1 & CN2 MECHATROLINK-II connectors
CN3 Power supply connector
Description
ER Lit: Power onNot lit: No power
Lit: Communication via CN1Not lit: No communication via CN1
Lit: Communication via CN2Not lit: No communication via CN2
Hardw
HARD 142
Revision 5.0
fig. 90The t/i
DipsThe d
Systfig. 91The m
in theMEC/i
The t• T• T
Termtermi
3
2
1
Pin
1
2
3
15 16
REP2000
CN1 CN2
B C
ANetw
1.
Maste
Exten
are reference
WARE REFERENCE MANUAL
able below gives the pin layout for the power supply connector.
witch settings (SW)ipswitch is for future use. Set all the pins to OFF.
em configurationaximum number of MECHATROLINK-II devices that you can connect
MECHATROLINK-II network with a repeater is set by the HATROLINK-II cable length.
otal number of MECHATROLINK-II devices is set by the TJ1-ML__:he TJ1-ML04 can have up to 4 MECHATROLINK-II devices.he TJ1-ML16 can have up to 16 MECHATROLINK-II devices.
inate the last MECHATROLINK-II device with a MECHATROLINK-II nator (A).
Signal Description
FG Frame ground
0 V 0 VDC input
+24 V 24 VDC input
1
TJ1-ML16
ork part MECHATROLINK-IIcable length
Maximum number ofMECHATROLINK-II devices1
The repeater itself is included in the maximum number of MECHATRO-LINK-II devices.
r-side (B) Max. 30 m 16
Max. 50 m 15
sion (C) Max. 30 m 16
Max. 50 m 15
Hardw
HARD 143
Revision 5.0
3.6
3.6.1
The GbetweMECMECrefer
fig. 92/i
Unit fig. 93/i
1234
SW2SW2
ONON
+V+V
-V-V
+V+V
-V-V
UNITUNIT
I/OI/O
DC24VDC24VINPUTINPUT
REGS
NC
ADR
BACK
1
2
3
4
RUN
ALARM
ML COM
TS
UNIT PWR
I/O PWR
1-ML2
A
B
C
D
Labe
A
B
C
D
E
F
G
H
ON1
2
3
4
RE GS
NC
ADR
B ACK
Dipsw
REGS
NC
are reference
WARE REFERENCE MANUAL
GRT1-ML2
Introduction
RT1-ML2 SmartSlice Communication Unit controls data exchange en a TJ1-MC__ Motion Controller Unit (via a connected TJ1-ML__
HATROLINK-II Master Unit) and SmartSlice I/O Units over a HATROLINK-II network. For more information on SmartSlice I/O Units, to the GRT1 Series SmartSlice I/O Units Operation Manual (W455).
dipswitches
SW1SW1
CN2CN2
CN1CN1A/BA/B
OMRON GRT
87
6
54
3
2 1 0 F
ED
CB
A9
G
H
F
E
l Description
LED indicators
Unit dipswitches
Unit power supply terminals
I/O power supply terminals
MECHATROLINK-II connectors
Shielding terminal
Rotary switch
Communication dipswitches
itch Function Setting Description
Create/enable registration table
ON Registered table is enabled
OFF Registered table is disabled
OFF to ON1 Register I/O unit table
ON to OFF1 Clear registered I/O unit table
N/A OFF Not used, always set to OFF
Hardw
HARD 144
Revision 5.0
fig. 94
The f
ADR
BACK
1.2.3.
Dipsw
OF F ON
1 s 1 s
operation starts after DIP switch 4 is N to OF F to ON within 3 seconds.
are reference
WARE REFERENCE MANUAL
actory setting of all dipswitches is OFF.
Automatic restore
OFF to ON When the SmartSlice I/O Units are replaced, the parameter data that was backed up with the BACK dipswitch is automatically restored2
OFF Automatic restore disabled
Backup trigger ON to OFF to ON in 3 s3
Parameter data of all connected Smart-Slice I/O Units is backed up2
When the unit power is on.When dipswitch 1 is set to ON.The setting of dipswitch 4 (BACK) is given in figure 94.
itch Function Setting Description
ON
1 s
T he backup turned from O
CautionThe Backup and Restore functionality is available in the GRT1-ML2. However, the backed up and restored parameters cannot be accessed via MECHATROLINK-II communication.
Note
• It is recommended to do a registration of the SmartSlice I/O Units (see the Trajexia Programming Manual).
• It is recommended to set dipswitches 1, 3 and 4 on after this registration.
Hardw
HARD 145
Revision 5.0
LED fig. 95/i
RUN
ALARM
ML COM
TS
UNIT PWR
I/O PWR
LED
RUN
ALAR
ML C
are reference
WARE REFERENCE MANUAL
indicators
Description Color Status Meaning
Unit status Green Not lit • Startup test failed, unit not opera-tional
• Operation stopped due to a fatal error
Lit Initialization successful, unit is in nor-mal operation
M Unit error Red Not lit Unit is in normal operation
Flashing A startup error has occurred
Lit Unit is in alarm state, or a fatal error has occurred
OM MECHATRO-LINK-II com-munication
Green Not lit No MECHATROLINK-II communication
Lit MECHATROLINK-II communication active
Hardw
HARD 146
Revision 5.0
hes
TS
UNITPWR
I/O P
LED
of the Trajexia system is turned on, the TJ1-its startup sequence before it initializes the K-II bus. During this startup sequence, the ML
C__ initializes the MECHATROLINK-II bus d MECHATROLINK(unit,0), the ML COM
-ML2 loses the MECHATROLINK-II communi-aster, or when the command K(unit,1) is executed, the ML COM LED goes
Setting Description
I ON 70 hex − 7F hex
OFF 60 hex − 6F hex
I OFF 10 Mbps1
Mbps bus speed. Therefore always set
OFF 32 bytes2
-byte communication. Therefore always set
ON HOLD: All outputs hold their values when communication is lost
OFF CLEAR: All outputs become 0 when communication is lost
are reference
WARE REFERENCE MANUAL
Communication dipswitc/i
SmartSlice I/O system com-munication status
N/A Not Lit • No power supply• Communication with SmartSlice I/
O Unit has not started • Overcurrent detected
Green Flashing(every second)
SmartSlice I/O Unit added to the sys-tem
Flashing(every 0.5 second)
Backup/Restore function operating:• Restoring settings to SmartSlice I/
O Unit, backup function operating• Downloading SmartSlice I/O Unit
settings
Lit Communication with SmartSlice I/O Unit established
Red Flashing Non-fatal communication error occurred.• Communication timeout• Verification error occurred with
registered table• Different model unit detected after
SmartSlice I/O Unit replacement
Lit Fatal communication error occurred.
Lit for 2 s Failure occurred while restoring set-tings to I/O unit or downloading I/O unit settings
Green Not Lit No power supply to the unit(All LEDs are off)
Lit Power supply to the unit
WR Green Not Lit No power supply to the SmartSlice I/O (No output from the SmartSlice I/O Units, even when they are in operation)
Lit Power supply to the SmartSlice I/O
Description Color Status MeaningNote
• When the powerMC__ executes MECHATROLINCOM LED is off.
• When the TJ1-Mwith the commanLED goes on.
• When the GRT1cation with the mMECHATROLINoff.
Dipswitch Function
1 MECHATROLINK-Iaddress range
2 MECHATROLINK-Ibus speed
1. Trajexia only supports 10dipswitch 2 to OFF.
3 Frame size
2. Trajexia only supports 32dipswitch 3 to OFF.
4 HOLD/CLEAR
Hardw
HARD 147
Revision 5.0
RotaThe rthe Gfrom To se1. T
2. Toro/i
Dipsw
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
are reference
WARE REFERENCE MANUAL
ry switchotary switch (SW1) sets the MECHATROLINK-II address that identifies RT1-ML2 in the MECHATROLINK-II network. The settings range is 0 hex to F hex.t the MECHATROLINK-II address of the GRT1-ML2, do these steps:urn off the Unit power supply of the GRT1-ML2.
set the address of the unit, set communication dipswitch 1 and the tary switch as given in the table below.
NoteThe address of the GRT1-ML2 is read only at power on. Setting the new address when the power is on has no effect.
itch 1 Rotaryswitch
Address Dipswitch 1 Rotaryswitch
Address
0 60 hex ON 0 70
1 61 hex ON 1 71
2 62 hex ON 2 72
3 63 hex ON 3 73
4 64 hex ON 4 74
5 65 hex ON 5 75
6 66 hex ON 6 76
7 67 hex ON 7 77
8 68 hex ON 8 78
9 69 hex ON 9 79
A 6A hex ON A 7A
B 6B hex ON B 7B
C 6C hex ON C 7C
D 6D hex ON D 7D
E 6E hex ON E 7E
Hardw
HARD 148
Revision 5.0
3. T
Powfig. 96The G
/i
OFF
Dipsw
UNIT
+V
-V
+V
-V
DC24VINPUT
I/O
DC
DC
Labe
A
B
are reference
WARE REFERENCE MANUAL
urn the power on.
er supply connectorRT1-ML2 has 2 24 VDC power supply terminals:
F 6F hex ON F 7F
NoteMake sure that the address is unique in the MECHATROLINK-II network. If two or more units have the same MECHATROLINK-II address, they cannot be initialized properly.
NoteTo make the MECHATROLINK-II address of the unit valid, do one of these steps:• Restart the TJ1-MC__.• Execute the command MECHATROLINK(unit,0).
itch 1 Rotaryswitch
Address Dipswitch 1 Rotaryswitch
Address
A 24 V
24 VB
l Power supply terminal Description
Unit power supplyterminal
Power supply to the internal circuits of the GRT1-ML2 and to the internal circuits of the connected SmartSlice I/O Units (through the SmartSlice bus)
External I/O powersupply terminal
Power supply to the external I/Os connected to the SmartSlice I/O Units
NoteThe unit power supply and the external I/O power supply are not transferred through the GCN2-100 Turnback cable. The GRT1-TBR units have the same power supply terminals as the GRT1-ML2.
Hardw
HARD 149
Revision 5.0
3.6.2/i
Item
Inst
alla
tion
U
M
I
P
C
D
W
Env
ironm
ent
Ap
Ah
S
V
S
D
Cas
E
are reference
WARE REFERENCE MANUAL
Specifications
Specification
nit type SmartSlice GRT1 series
odel GRT1-ML2
nstallation position On a DIN rail
ower supply 24 VDC +10% −15% (20.4 to 26.4 VDC)
urrent consumption 110 mA typical at 24 VDC
imensions (W × H × D) 58 × 80 × 70 mm
eight 130 g
mbient operating tem-erature
−10 to 55°C (no icing or condensation)
mbient operating umidity
25% to 85% Relative humidity
torage temperature −20 to 65°C (no icing or condensation)
ibration resistance 10 to 57 Hz, 0.7 mm amplitude57 to 150 Hz, acceleration: 49 m/s2
hock resistance 150 m/s2
ielectric strength 500 VAC (between isolated circuits)
onformance to EMC nd electrical safety tandards
EN61131-2:2003
nclosure rating IP20
Hardw
HARD 150
Revision 5.0
SuppThe GSmar/i
Sm
artS
lice
I/O
NS
B
Cl
Ct
T
Sn
B
E
ME
CH
ATR
OLI
NK
-II B
D
Func
4 NPN
4 PNP
8 NPN
8 PNP
4 NPN
Item
are reference
WARE REFERENCE MANUAL
orted SmartSlice I/O UnitsRT1-ML2, in combination with the Trajexia system, supports these
tSlice I/O Units.
umber of connectable martSlice I/O Units
64 Units max.Connected directly to the GRT1-ML2 or via Turnback exten-sion units
aud rate 3 Mbps
ommunication signal evel
RS485
ommunication dis-ance
SmartSlice I/O Units: 64 Units coupled (about 2 m max.)Turnback cable: 2 m max. (2 cables, 1 m each)
urnback cable Length 1 m max., up to 2 cables can be connected
martSlice I/O Unit con-ections
Building-block style configuration with slide connectors (Units connect with Turnback cables).
aseblock power supply Voltage: 24 VDCCurrent: 4 A max.
vent messaging Supported
aud rate 10 Mbps (MECHATROLINK-II)
ata length 17-byte and 32-byte data transmission
tion Specification Model
inputs 24 VDC, 6 mA, 3-wire connection GRT1-ID4
inputs 24 VDC, 6 mA, 3-wire connection GRT1-ID4-1
inputs 24 VDC, 4 mA, 1-wire connection + 4xG GRT1-ID8
inputs 24 VDC, 4 mA, 1-wire connection + 4xV GRT1-ID8-1
outputs 24 VDC, 500 mA, 2-wire connection GRT1-OD4
Specification
Hardw
HARD 151
Revision 5.0
4 PNP
4 PNPcircui
8 NPN
8 PNP
8 PNPcircui
2 rela
2 anavoltag
2 ana
2 ana
Func
are reference
WARE REFERENCE MANUAL
outputs 24 VDC, 500 mA, 2-wire connection GRT1-OD4-1
outputs with short-t protection
24 VDC, 500 mA, 3-wire connection GRT1-OD4G-1
outputs 24 VDC, 500 mA, 1-wire connection + 4xV
GRT1-OD8
outputs 24 VDC, 500 mA, 1-wire connection + 4xG
GRT1-OD8-1
outputs with short-t protection
24 VDC, 500 mA, 1-wire connection + 4xG
GRT1-OD8G-1
y outputs 240 VAC, 2A, normally-open contacts GRT1-ROS2
log inputs, current/e
10 V, 0-10 V, 0-5 V, 1-5 V, 0-20 mA, 4-20 mA
GRT1-AD2
log outputs, voltage 10 V, 0-10 V, 0-5 V, 1-5 V GRT1-DA2V
log outputs, current 0-20 mA, 4-20 mA GRT1-DA2C
tion Specification Model
Hardw
HARD 152
Revision 5.0
DimeThe e
fig. 97
3.6.3
Follow• B
oe
• MU
0 F
ED
CB
A987
6
54
3
2 1
1234
SW1SW1 SW2SW2
CN2CN2
CN1CN1A/BA/B
ONON
+V+V
-V-V
+V+V
-V-V
UNITUNIT
I/OI/O
DC24VDC24VINPUTINPUT
REGS
NC
ADR
BACK
1
2
3
4
RUN
ALARM
ML COM
TS
UNIT PWR
I/O PWR
OMRON GRT1-ML2
17.1
36.8
58 2.4
16.2
35.5
83.5
2.9
2.9
54
are reference
WARE REFERENCE MANUAL
nsionsxternal dimensions are in mm.
Installation
these rules when installing the GRT1-ML2:efore installing the GRT1-ML2 or connect or disconnect cables, switch ff the power of the Trajexia system, the SmartSlice I/O Units and the xternal I/Os.ake sure that the power supplies of the GRT1-ML2, the SmartSlice I/O nits and the external I/Os are correctly connected.
28.8
26.3
61.2
69.71.5
11.9
Hardw
HARD 153
Revision 5.0
• Ph
• It• In
infro
• ToD
Connfig. 98Conn
• A• S
See tinformEnd U
WirinThe Ghave To deThe mblock
RUN
ALARM
ML COM
TS
UNIT PWR
I/O PWR
ON
+V
-V
+V
-V
UNIT
I/O
DC24V
INPUT
REGS
NC
ADR
BACK
1
2
3
4
are reference
WARE REFERENCE MANUAL
rovide separate conduits or ducts for the I/O lines to prevent noise from igh-tension lines or power lines. is possible to connect up to 64 SmartSlice I/O Units to 1 GRT1-ML2.stall the GRT1-ML2 and the SmartSlice I/O Units on a DIN rail. To stall a GRT1-ML2 on the DIN rail, press it onto the DIN track from the ont, and press the unit firmly until it clicks. Check that all DIN rail sliders f the unit are locked onto the DIN rail. remove the GRT1-ML2 from the DIN rail, release the sliders from the
IN rail with a screwdriver, and pull the unit straight from the DIN rail.
ectionsect the first SmartSlice I/O Unit to the GRT1-ML2:lign the sides of the GRT1-ML2 and the SmartSlice I/O Unit.lide the SmartSlice I/O Unit to the rear until it clicks onto the DIN rail.
he GRT1 Series SmartSlice I/O Units Operation Manual for more ation on connecting additional SmartSlice I/O Units, Turnback Units, nits and end plates.
gRT1-ML2 has 2 power supply terminals. Both power supply terminals
screwless clamping-type connections.termine the power supply requirements, do the steps below.aximum power consumption for SmartSlice I/O Units is 80 W per
.
CN2
SW1SW2
CN1
A/B
GRT1-ML2
CautionDo not touch the connectors on the side of GRT1-ML2 and the SmartSlice I/O Units.
Hardw
HARD 154
Revision 5.0
1. CtoOU
2. If(Gco
3. CT
The m1. C
coU(W
2. Ifseap
The f
are reference
WARE REFERENCE MANUAL
alculate the power consumption of all SmartSlice I/O Units connected the GRT1-ML2. Refer to the GRT1 Series SmartSlice I/O Units peration Manual (W455) for the power value for each SmartSlice I/O nit. the power consumption exceeds 80 W, mount a Right Turnback Unit RT1-TBR) on the SmartSlice I/O Unit at the point where the power nsumption is less than 80 W.
onnect the 24 VDC unit power supply to the Left Turnback Unit (GRT1-BL).
aximum I/O current consumption is 4 A.alculate the total current consumption used by all external I/Os of the nnected SmartSlice I/O Units (including other units like Turnback
nits). Refer to the GRT1 Series SmartSlice I/O Units Operation Manual 455) for the current value for each SmartSlice I/O Unit.
the current consumption exceeds 4 A or if you want to provide parate systems for inputs and outputs, divide the SmartSlice I/O Units
t the desired point with a GRT1-PD_(-1) I/O Power Supply Unit and rovide a separate external I/O power supply.
igure gives a wiring example.
NoteIt is also possible to provide a separate external I/O power supply at a Left Turnback Unit (GRT1-TBL).
NoteMake sure the power supply is isolated.
NoteThe GCN2-100 Turnback cable does not supply power.
Hardw
HARD 155
Revision 5.0
fig. 99To suwirespin te
fig. 100To remprecis
It is rewith oincrea42.4 Reco• S• S
It is re1.25 Strip (stran8 to 1
I/O (AD)
I/O (AD)
I/O (OUT )
I/O (OUT )
I/O (OUT )
I/O (OUT )
I/O (OUT )
(-1) I/O Power Supply Unit
E nd Unit
T urnback cable
GRT 1-T B R Right T urnback Unit
max. 80 W
max. 80 W
Precis ion screwdriver
Release button
are reference
WARE REFERENCE MANUAL
pply power to the units and the I/O devices, connect the power supply to the power supply terminals of the GRT1-ML2. If the wire ends have rminals, just insert the pin terminals in the power supply terminals.
ove the wires, press the release button above the terminal hole with a ion screwdriver, and pull out the wire.
commended to use a SELV (Safety Extra Low Voltage) power supply ver-current protection. A SELV power supply has redundant or sed insulation between the I/O, an output voltage of 30 V rms and a
V peak or maximum of 60 VDC.mmended power supplies are:82K-01524 (OMRON)8TS-06024 (OMRON).
commended to use wires with a gauge of 20 AWG to 16 AWG (0.5 to mm2).the wire between 7 and 10 mm of insulation at the ends of the wires ded or solid wire), or use pin terminals with a pin (conductor) length of 0 mm.
I/O (AD)
I/O (IN)
I/O (IN)
I/O (AD)
I/O (AD)
I/Opowersupply
GRT 1-PD_
GRT 1 - ML2
Power supply(24 VDC)
I/Opowersupply
I/Opowersupply
GRT 1-T B L Left T urnback Unit
Hardw
HARD 156
Revision 5.0
Repl
To re• T
a• M• If
th-
--
• Wd
• B-
-
3.6.4
It is pwhenI/O UTo re1. T
p(f
2. RD
are reference
WARE REFERENCE MANUAL
ace
place the unit, follow these rules:urn off the power before replacing the unit. This includes the power to ll master and slave units in the network.ake sure that the new unit is not damaged. a poor connection is the probable cause of any malfunctioning, do ese steps:
Clean the connectors with a clean, soft cloth and industrial-grade alcohol.Remove any lint or threads left from the cloth.Install the unit again.
hen returning a damaged unit to the OMRON dealer, include a detailed amage report with the unit.efore reconnecting the new unit, do these steps:
Set the MECHATROLINK-II station address to the same address as the old unit.If the table registration function was used for the old unit, create a new registration table for the new unit. See the Trajexia Programming Manual.
Online replacement
ossible to replace SmartSlice I/O Units connected to a GRT1-ML2 the power is on. The I/O communication continues while a SmartSlice nit is removed and replaced.place a SmartSlice I/O Unit online, do these steps:urn off all power supplies of the SmartSlice I/O Unit. This is the I/O ower supply, plus possible external power supplies to the terminal block or example, a Relay Output Unit).elease the locks on the front of the unit and remove the terminal block. o not remove the wiring.
CautionThe GRT1-ML2 is a unit that is part of a network. If the GRT1-ML2 is damaged, it effects the whole network. Make sure that a dam-aged GRT1-ML2 is repaired immediately.
Hardw
HARD 157
Revision 5.0
3. RU
4. A5. T
When• W
o• If
si• O• If
o• If
re
Whenreporback,detecbeforrepla1. E
b2. R3. E
e
3.6.5
The fGRT1• M
For m
are reference
WARE REFERENCE MANUAL
emove the main block of the unit. Replace it with a new SmartSlice I/O nit of the same type.ttach the new unit to the system. Close the locks on the front of the unit.urn on the power supplies to the unit.
replacing a SmartSlice I/O Unit online, note the following things:hen a unit is removed from the I/O communication, the withdrawn flag
f the unit is set on and the TS LED on the GRT1-ML2 flashes red. I/O power supply of the unit is not turned off, there can be false output gnals, false input signals and electrical shocks.nly replace one SmartSlice I/O Unit at a time. a unit is replaced with a different type of unit, there can be unexpected utputs and the restore operation can be incomplete. the base block has faults or damage, turn off the power supply and place the entire unit.
an online replacement is performed, the status word of the GRT1-ML2 ts an error (missing I/O Unit). When the I/O Unit is replaced or put the status word changes to 8000 hex, but the error has already been ted by the TJ1-MC__. To avoid this, it is necessary to mask the errors e the online replacement is performed. To perform the online cement do the following:xecute MECHATROLINK(unit,37,station_addr, 0). This masks all its, including errors, in the GRT1-ML2 status word.eplace the I/O Unit.xecute MECHATROLINK(unit,37,station_addr, $4000). This sets the rror mask to its default value.
Related BASIC commands
ollowing BASIC commands are related to the MECHATROLINK-II -ML2 module:ECHATROLINK
ore information, refer to the Trajexia Programming Manual.
Hardw
HARD 158
Revision 5.0
3.7
3.7.1fig. 101The T
netwoThe T/i
3.7.2/i
0 9 8 7654
3210 9 876
54
321
H
B A
B
D
C
Part
A
B and
D
Labe
run
ERC
ERH
are reference
WARE REFERENCE MANUAL
TJ1-PRT
Introduction
J1-PRT is an interface between the Trajexia system and a PROFIBUS rk.J1-PRT has these visible parts.
LEDs description
Description
LEDs
C Node number selectors
PROFIBUS connector
l Status Description
off Start-up test failed. Unit not operationalOperation stopped. Fatal error
on Start-up test successful. Normal operation
off Normal operation
flashing Start-up error
on Fatal error in programError occurred while Reading or Writing error log
off Normal operation
flashing I/O-size not configured
on Error detected in communication with controller
Hardw
HARD 159
Revision 5.0
3.7.3
You cPRT. The ulowerselecthe laProgr
COM
BF
Labe
are reference
WARE REFERENCE MANUAL
Node number selectors
an use the node number selectors to assign a node number to the TJ1-This node number identifies the TJ1-PRT in the PROFIBUS network.pper node number selector sets the tens of the node number. The node number selector sets the units of the node number. Both tors range from 0 to 9. To set a selector to n, turn the arrow to point to bel n. Refer to the chapter, Communication Protocols in the amming Manual.
off No PROFIBUS data exchange communication
on I/O data exchange on PROFIBUS is active
off No PROFIBUS bus communication errors
flashing Parameter values sent by the PROFIBUS master unit are invalid. I/O data exchange is not possible.
on No PROFIBUS communication is detected by the unit
l Status Description
Hardw
HARD 160
Revision 5.0
3.7.4fig. 102/i
3.7.5/i
54321
Pin
1
2
3
4
5
6
7
8
9
Item
Powe
Powe
Curre
Appro
Electr
Comm
Trans
Node
I/O si
Galva
are reference
WARE REFERENCE MANUAL
TJ1-PRT Connections
TJ1-PRT Specifications
9876
Signal Description
Shield Connected to the metal shell
N/A N/A
B-line Data signal
RTS Direction control signal for repeaters
DGND Data 0 Volts
VP Power output for the termination, 5 V, 10 mA
N/A N/A
A-line Data signal
N/A N/A
Specification
r supply 5 VDC (supplied by the TJ1-MC__)
r consumption 0.8 W
nt consumption 150 mA at 5 VDC
ximate weight 100 g
ical characteristics Conforms to PROFIBUS-DP standard EN50170 (DP-V0)
unication connector 1 PROFIBUS-DP slave connector
mission speed 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000 and 12000 Kbps
numbers 0 to 99
ze 0 to 122 words (16-bit), configurable, for both directions
nic isolation Yes
Hardw
HARD 161
Revision 5.0
3.7.6
TJ1-P• S• T• P
3.7.7
The f• P
For m
are reference
WARE REFERENCE MANUAL
TJ1-PRT unit box contents
RT box:afety sheet.J1-PRT.rotection label attached to the top surface of the unit.
Applicable BASIC commands
ollowing BASIC commands are applicable for the TJ1-PRT:ROFIBUS
ore information, refer to the Trajexia Programming Manual.
Hardw
HARD 162
Revision 5.0
3.8
3.8.1fig. 103The T
netwo/i
3.8.2/i
0 9 8 7654
3210 9 876
54
321
V-
CAN L
DRAIN
CAN H
V+
A
B
D
C
Part
A
B and
D
Labe
RUN
ERC
ERH
NOK
are reference
WARE REFERENCE MANUAL
TJ1-DRT
Introduction
J1-DRT is an interface between the Trajexia system and a DeviceNet rk.
LEDs description
Description
LEDs
C Node number selectors
DeviceNet connector
l Status Description
off Start-up test failed. Unit not operationalOperation stopped. Fatal error
on Start-up test successful. Normal operation
off Normal operation
flashing Start-up error
on Fatal error in programError occurred while Reading or Writing error log
off Normal operation
flashing I/O-size not configured
on Error detected in communication with controller
off Baud rate not detected or node address duplication check not completed.
flashing Slave not allocated to a DeviceNet master.
on Slave is on-line and allocated to a DeviceNet master.
Hardw
HARD 163
Revision 5.0
3.8.3
You cDRT. The ulowerselecthe laProgr
The Dnumbselecsoftw
NF
Labe
are reference
WARE REFERENCE MANUAL
Node number selectors
an use the node number selectors to assign a node number to the TJ1-This node number identifies the TJ1-DRT in the DeviceNet network.pper node number selector sets the tens of the node number. The node number selector sets the units of the node number. Both tors range from 0 to 9. To set a selector to n, turn the arrow to point to bel n. Refer to the chapter, Communication Protocols in the amming Manual.
eviceNet node numbers range from 0 to 63. If you select a node er with the node number selectors that exceeds this range, you will t the node number that is set by software. The nodes that enable are settings are 64 to 99.
off No network error detected.
flashing Connection time-out detected for I/O connection with the Device-Net master.
on Other device detected with the same node number or severe net-work error detected.
l Status Description
Hardw
HARD 164
Revision 5.0
3.8.4fig. 104/i
3.8.5/i
Pin
1
2
3
4
5
Item
Powe
Powe
Netw
Netwtion
Powe
Appro
Electr
Comm
Trans
are reference
WARE REFERENCE MANUAL
TJ1-DRT Connections
TJ1-DRT Specifications
1
2
3
4
5
Signal Description
V- Power supply input, negative voltage
CAN L Communication line, low
DRAIN Shield
CAN H Communication line, high
V+ Power supply input, positive voltage
Specification
r supply 5 VDC (supplied by the TJ1-MC__)
r consumption 120 mA at 5 VDC
ork power supply 24 VDC
ork current consump- 15 mA at 24 VDC
r dissipation 0.6 W
ximate weight 100 g
ical characteristics Conforms to DeviceNet standard of CIP edition 1.
unication connector 1 DeviceNet slave connector
mission speed 125, 250 and 500 Kbps, auto-detected
Hardw
HARD 165
Revision 5.0
3.8.6
TJ1-D• S• T• D• P
3.8.7
The f• D
For m
Node
I/O si
Galva
Item
are reference
WARE REFERENCE MANUAL
TJ1-DRT unit box contents
RT box:afety sheet.J1-DRT.eviceNet connector.rotection label attached to the top surface of the unit.
Applicable BASIC commands
ollowing BASIC commands are applicable for the TJ1-DRT:EVICENET
ore information, refer to the Trajexia Programming Manual.
numbers 0 to 63
ze 0 to 32 words (16-bit), configurable, for both directions
nic isolation Yes
Specification
Hardw
HARD 166
Revision 5.0
3.9
3.9.1
The Csyste
fig. 105/i
3.9.2/i
0 9 8 7654
3210 9 876
54
321
V-
CAN L
DRAIN
CAN H
V+
CORT
NWST
BF A
B
D
C
Part
A
B and
D
Labe
RUN
ERC
are reference
WARE REFERENCE MANUAL
TJ1-CORT
Introduction
ANopen Master Unit (TJ1-CORT) is an interface between the Trajexia m and a CANopen network.
LEDs description
Description
LED indicators
C Node number selectors
CANopen port
l Status Description
off Start-up test failed. Unit not operational.Operation stopped. Fatal error.
on Start-up test successful. Normal operation.
off Normal operation
flashing Start-up error
on Fatal error in program.Error occurred while Reading or Writing error log.
Hardw
HARD 167
Revision 5.0
3.9.3
You cCORTThe ulowerselecthe laThe Conly sinvaliTJ1-C
ERH
NWS
BF
1.2.3.
Labe
are reference
WARE REFERENCE MANUAL
Node number selectors
an use the node number selectors to assign a node number to the TJ1-. This node number identifies the TJ1-CORT in the CANopen network.pper node number selector sets the tens of the node number. The node number selector sets the units of the node number. Both tors range from 0 to 9. To set a selector to n, turn the arrow to point to bel n.ANopen node number can range from 0 to 127. But the TJ1-CORT upports node numbers from 1 to 99. The default node number, 0, is
d. Therefore, the default node number must be changed before the ORT is used.
off Normal operation.
flashing I/O size not configured.
on Error detected in communication with controller.
T off Start-up error or fatal error detected.
single flash TJ1-CORT in stopped state.
flashing TJ1-CORT in pre-operational state.
on TJ1-CORT in operational state.
off No network error detected.
single flash1 Warning limit reached.At least one of the error counters of the CAN controller has reached or exceeded the warning level (too many errors).
double flash2 A remote error or a heartbeat event has occurred.
flashing3 Invalid configuration.
on A duplicate node address has been detected, orthe unit is in Bus OFF state.
Single flash: one 200ms pulse, followed by 1 second off.Double flash: two 200ms pulses, followed by 1 second off.LED flashing frequency: 2.5 Hz.
l Status Description
Hardw
HARD 168
Revision 5.0
3.9.4fig. 106/i
3.9.5/i
Pin
1
2
3
4
5
Item
Powe
Powe
Netw
Netwsump
Powe
Appro
Electrtics
are reference
WARE REFERENCE MANUAL
TJ1-CORT connections
TJ1-CORT specifications
1
2
3
4
5
Signal Description
V- Power supply input, negative voltage
CAN L Communication line, low
DRAIN Shield
CAN H Communication line, high
V+ Power supply input, positive voltage
Specification
r supply 5 VDC (supplied by the TJ1-MC__)
r consumption 120 mA at 5 VDC
ork power supply 24 VDC
ork current con-tion
15 mA at 24 VDC
r dissipation 0.6 W
ximate weight 100 g
ical characteris- Conforms to ISO 11898-1
Hardw
HARD 169
Revision 5.0
3.9.6
CANo• S• C• D• P
3.9.7
The f• C
For m
Comm
Trans
Node
I/O si
Galva
Devic
Item
are reference
WARE REFERENCE MANUAL
TJ1-CORT unit box contents
pen Master Unit box:afety sheet.ANopen Master Unit.eviceNet connector.rotection label attached to the top surface of the unit.
Applicable BASIC commands
ollowing BASIC commands are applicable for the TJ1-CORT:AN_CORT
ore information, refer to the Trajexia Programming Manual.
unication ports 1 CAN port
mission speed 20, 50, 125 and 500 Kbps
numbers 1 to 99
ze 8 RPDO and 8 TPDO
nic isolation Yes
e profile DS302: CANopen manager profile Note:This CANopen master does not support motion control features of slaves with the DS401 profile
Specification
Hardw
HARD 170
Revision 5.0
3.10
3.10.
fig. 107The Tin the• A• In• P
At stasequein uni(usingfree aThe T/i
3.10.
The fAXIS
FL02
A
B
C
Part
A
B
C
are reference
WARE REFERENCE MANUAL
TJ1-FL02
1 Introduction
J1-FL02 is an analogue control unit. It controls up to two axes A and B se modes:nalogue speed reference plus encoder feedback.cremental or absolute encoder input.ulse output.
rt up the TJ1-MC__ assigns the TJ1-FL02 to the first 2 free axes in nce. When multiple TJ1-FL02 units are connected they are assigned
t sequence 0..6. Any MECHATROLINK-II axes that are assigned the driver switches) will not change. The TJ1-MC__ assigns the next xis.J1-FL02 has these visible parts:
2 LED description
unction of the LEDs is defined by the BASIC command _DISPLAY. For more information, refer to the Programming Manual.
WARNINGDo not start the system until you check that the axes are present and of the correct type.The numbers of the Flexible axes will change if MECHATROLINK-II network errors occur during start-up or if the MECHATROLINK-II network configuration changes.
Description
LEDs
15-pin connector
18-pin connector
Hardw
HARD 171
Revision 5.0
/i
3.10.
The sselec
Axis
All
A
B
are reference
WARE REFERENCE MANUAL
3 TJ1-FL02 connections
ignals of the 15-pin connector depend on the type of interface ted:
Label Status AXIS_DISPLAY parameter
0 1 2 3
run on The TJ1-MC__ recognises the TJ1-FL02
A EN on Axis enabled.
flashing Axis error
off Axis disabled
A 0 on REG 0 AUX OUT 0 Encoder A
A 1 on REG 1 Encoder Z OUT 1 Encoder B
B EN on Axis enabled
flashing Axis error
off Axis disabled
B 0 on REG 0 AUX OUT 0 Encoder A
B 1 on REG 1 Encoder Z OUT 1 Encoder B
Hardw
HARD 172
Revision 5.0
15-pfig. 108/i
510
49
38
27
16
Pin
1.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
are reference
WARE REFERENCE MANUAL
in connector
1514131211
Axis Encoder input1
With the VERIFY parameter the input type can be changed from phase differential (VERIFY=ON, default) to Step (Channel A) and Direction (Channel B) (VERIFY=OFF).
Encoder output
Stepper output
SSI/EnDat Tamagawa
A A+ A+ Step+ Clock+
A A- A- Step- Clock-
A B+ B+ Dir+
A B- B- Dir-
GND GND GND GND GND
A Z+ Enable+ Data+ SD+
A Z- Enable- Data- SD-
B Z+ Enable+ Enable+ Data+ SD+
B Z- Enable- Enable- Data- SD-
+5V out Do not use Do not use Do not use Do not use
B A+ A+ Step+ Clock+
B A- A- Step- Clock-
B B+ B+ Dir+
B B- B- Dir-
GND GND GND GND GND
Hardw
HARD 173
Revision 5.0
18-pfig. 109/i
Digit
fig. 110The f/i
Input• w• w
2
4
6
8
10
12
14
16
18
Pin
1
3
5
7
9
11
13
15
17
TJ 1-FL02
Reg A0 7
0V I/O
0V common for Input circuits
17
Item
Type
Maxim
Input
on vo
off vo
are reference
WARE REFERENCE MANUAL
in connector
al inputs
ollowing table and illustration details the digital input specifications:
response time (registration):ithout noise filter: 0.5µs maximum.ith noise filter 3.5µs maximum.
1
3
5
7
9
11
13
15
17
Axis Signal Pin Axis Signal Description
A Vout 2 B Vout Analog output
A 0V 4 B 0V 0V Reference for Vout
Wdog- 6 Wdog+ Enable relay contacts
A Reg 0 8 B Reg 0 24V registration inputs
A Reg 1 10 B Reg 1 24V registration inputs
A AUX 12 B AUX 24V auxiliary inputs
A OUT 0 14 B OUT 0 position switch outputs(HW_PSWITCH)
A OUT 1 16 B OUT 1 OUT1 Auxiliary outputs
I/O 0VCommon
18 I/O +24 V 24V Power supply Input for the Outputs.
External powersupply 24V
Specification
PNP
um voltage 24 VDC + 10%
current 8 mA at 24 VDC
ltage 18.5 VDC min
ltage 5.0 VDC max
Hardw
HARD 174
Revision 5.0
Digitfig. 111The f
/i
Outpu• 1
TJ 1-FL02
Externalpowersupply24V
Load
2A Fuse24V output supply18
13 Out 0
17 0V I/O
ircuits
Item
Type
Maxim
Curre
Max.
Prote
are reference
WARE REFERENCE MANUAL
al outputsollowing table and illustration details the digital output specifications:
t response time (PSwitch):40 µs maximum
NoteIn the case of an incorrect registration due to slow edges or noise, a digital noise filter can be enabled with the REGIST command. Refer to the BASIC Commands in the Programming Manual.
NoteA maximum of 4 inputs on is allowed simultaneously.
Equivalentcircuit
To other output cInte
rnal
circ
uitr
y (g
alva
nica
llyis
olat
ed fr
om s
yste
m)
Specification
PNP
um voltage 24 VDC + 10%
nt capacity 100 mA each output (400 mA for a group of 4)
Voltage 24 VDC + 10%
ction Over current, Over temperature and 2A fuse on Common
Hardw
HARD 175
Revision 5.0
Analfig. 112The f
/i
Wdofig. 113The f
/i
TJ1-FL02
Vout 0
-15V
+15V 1
30V
Item
Outpu
Reso
Outpu
Load
TJ1-FL02
WDOG+ 5
6WDOG-
Item
Type
Curre
on re
Maxim
are reference
WARE REFERENCE MANUAL
og outputsollowing table and illustration details the analog output specifications:
g relayollowing table and illustration details the Wdog relay:
Isolated 0V
Specification
t voltage -10 to +10 V
lution 16 bit
t impedance 100 Ω
impedance 10 k Ω min
NoteThe analogue output of one flexible axis is always 0V unless both axes in the TJ1-FL02, axis A & B are enabled, that is:WDOG=ONAXIS_ENABLE AXIS(A)=1AXIS_ENABLE AXIS(B)=1
Specification
Solid state relay
nt capacity 50 mA
sistance 25 Ω max.
um voltage 24 VDC + 10%
Hardw
HARD 176
Revision 5.0
Encofig. 114The f
/i
Conn
fig. 115The epositiThe e(PG-Xthe coMaketermi/i
+5V
0V
TJ1-FL02
0
,15
Item
Type
Signa
Input
Load
Termi
Encoder Feedback
ENC MOTOR
TJ1-Fpin n
1
3
5
are reference
WARE REFERENCE MANUAL
der interfaceollowing table and illustration details the encoder interface:
ection example
xample shows the connections for the TJ1-FL02 to a F7 Inverter for on control. ncoder from the motor must be connected to the encoder interface 2) in the Inverter (connector TA1). The encoder signal is forwarded in nnector TA2 of the (PG-X2). the connections for the 18 pin connector on the TJ1-FL02 to the nal board on the F7 Inverter as follows:
+5V
0V
1A0+ /STEP0+ /...A0- /STEP0- /...
B0+ /DIR0+ /...B0- /DIR0- /...
Z0+ /ENA0+ /...Z0- /ENA0- /...
2
3
4
6
7
1
5
Specification
Phase differential incremental encoder
l level EIA RS-422-A Standards (line-driver)
impedance 48 kΩ min
impedance 220 Ω min
nation None
L02umber
F7 InverterTA1
Signal Description
A1 Vout Analog output
AC 0V 0V Reference for Vout
S1 Wdog- Enable relay contacts
Hardw
HARD 177
Revision 5.0
The cThe c
MakeX2 op/i
3.10./i
6
TJ1-Fpin n1
2
3
4
5
TJ1-Fpin n
Item
Powe
Total
Curre
Appro
Galva
Outpu
are reference
WARE REFERENCE MANUAL
able for pins 1 and 3 must be shielded twisted pair.ables for pins 5 and 6 are two single strand cables.
the connections for the 15 pin connector on the TJ1-FL02 to the PG-tion board on the F7 Inverter as follows:
4 TJ1-FL02 specifications
SP Wdog+ Enable relay contacts
L02umber
F7 InverterTA2
Signal Description
1 A+ Pulse monitor input phase A+
2 A- Pulse monitor input phase A-
3 B+ Pulse monitor input phase B+
4 B- Pulse monitor input phase B-
7 GND Isolated controller circuit GND
NoteThe cables are twisted pair (A+,A- and B+,B-) and shielded with the shield connected to the shell of the TJ1-FL02 15 pin connector.
L02umber
F7 InverterTA1
Signal Description
Specification
r supply 5 VDC and 24 VDC (supplied by the TJ1-MC__)
power consumption 3.35 W
nt consumption 190 mA at 5 VDC and 100 mA at 24 VDC
ximate weight 110 g
nic isolation • Encoder interface• Analogue outputs• Digital interface
t power supply 5 VDC, 150 mA Maximum
Hardw
HARD 178
Revision 5.0
3.10.
The f• A• A• D• D
Numb
Contr
Enco
Absoporte
Enco
Encoquenc
Maxim
Auxili
Item
are reference
WARE REFERENCE MANUAL
5 Applicable BASIC commands
ollowing BASIC commands are applicable for the TJ1-FL02:TYPEXIS_DISPLAYRIVE_CONTROLRIVE_STATUS
er of axes 2
ol method • +/- 10 V analogue output in Closed Loop• Pulse Train output in Open Loop
der position/speed feedback Incremental and absolute
lute encoder standards sup-d
• SSI 200 kHz• EnDat 1 MHz• Tamagawa
der input maximum frequency 6 MHz
der/pulse output maximum fre-y
2 MHz
um cable length: • SSI 200 kHz, 100 m• EnDat 1 MHz, 40 m• Tamagawa, 50 m• Encoder input, 100 m• Encoder/stepper output, 100 m
ary I/Os • Two fast registration inputs per axis• Two definable inputs• Two hardware position switch outputs• One enable output• Two definable outputs
Specification
NoteThe 5 VDC power supply can only be used when both axes are in SERVO_AXIS mode (ATYPE=44).
Hardw
HARD 179
Revision 5.0
BASIcorreBASI
3.10.
An in• A• A
By mrotatiothe cocountMost referedeter
Encofig. 116The p
for eiThe fforwa(E).The sand ZmakeWhenspecidiffererever
7 76 65 5 4 3 2 1 0
E
are reference
WARE REFERENCE MANUAL
C commands applicable for specific encoder types, are listed with the sponding explanations in the next chapters. For more information of C commands, refer to the Trajexia Programming Manual.
6 Incremental encoder
cremental encoder has this phase definition:n advanced phase A for forward rotation.n advanced phase B for reverse rotation.
onitoring the relative phase of the 2 signals, you can easily detect the n direction. If signal A leads signal B, the movement is clockwise and unter increments. If channel B leads channel A, the movement is erclockwise and the counter decrements.rotary encodes also provide an additional Z marker. This Z marker is a nce pulse within each revolution. With these 3 signals, you can
mine the direction, the speed and the relative position.
der inputulse ratio of the TJ1-MC__ is 1: every encoder edge (i.e., a pulse edge
ther phase A or B) is equal to one internal count.igure shows phase A (A), phase B (B) and the number of counts (C) for rd or clockwise rotation (D) and reverse or counterclockwise rotation
ignals A, B and Z appear physically as A+ and A-, B+ and B- and Z+ -. They appear as differential signals on twisted-pair wire inputs. This s sure that common mode noise is rejected. you use an encoder from other manufacturers, check the encoder fication for the phase advancement carefully. If the phase definition is nt from the phase definition of the standard OMRON equipment,
se the B-phase wiring between the TJ1-MC__ and the encoder.
D
43210
A
B
C
NoteThe TJ1-FL02 does not have a termination inside. In case of long distances or disturbed communication, add an external termina-tion to the TJ1-FL02.
Hardw
HARD 180
Revision 5.0
fig. 117The tOMR/i
Encofig. 118The T
(C), t(B).
RelaThe f• A• E
For m
123467510
A+
TJ1-FL02
A-B+B-Z+Z-0 V (COM)5 VDC
Enco
Signa
A+
A-
B+
B-
Z+
Z-
0 V (C
5 VDC
2 3 4 5 6 7
are reference
WARE REFERENCE MANUAL
able below and the figure give an example of how to connect the ON E6B2-CWZ1Z encoder to the TJ1-FL02.
der outputJ1-FL02 can generate encoder type pulses. For each internal count
he TJ1-FL02 produces one encoder edge for phase A (A) or phase B
ted BASIC commandsollowing BASIC commands are related to incremental encoders:TYPE (ATYPE=44 and ATYPE=45) NCODER_RATIO
ore information, refer to the Trajexia Programming Manual.
der TJ1-FL02
l Wire color Pin Signal
Black 1 A+
Black/red 2 A-
White 3 B+
White/red 4 B-
Orange 6 Z+
Orange/red 7 Z-
OM) Blue 5 GND
Brown 10 + 5V
0 1
A
B
C
Hardw
HARD 181
Revision 5.0
3.10.
SSISSI (Sserialsensoout thThe Sif the 25 bitsent twith t
fig. 119WhencommThesset. T32 µssensoThe lA. TB. CC. CD. DE. MF. LG. C
Wheninterppositi
The c
µs32
G
F
are reference
WARE REFERENCE MANUAL
7 Absolute encoder
ynchronous Serial Interface) is a digital system for transferring data in form. SSI is the most widely used serial interface between absolute rs and controllers. SSI uses a pulse train from the controller to clock e data from the sensor.SI interface of the TJ1-FL02 accepts absolute values from an encoder data is in Gray Code format or in binary format and if the resolution is s or less. The number of bits, and therefore the number of clock pulses o the encoder in each frame, is programmable. You set this number he BASIC command ENCODER_BITS = n. you have initialized the TJ1-FL02 with the ENCODER_BITS and, the TJ1-FL02 continuously sends clock pulses to the encoder.
e clock pulses are sent in frames of n+2 pulses, where n is the bit count he clock rate is fixed at 200 kHz. The clock interval between frames is . The resulting maximum cable length between the controller and the r is 200 m.
abels in the figure are:iming diagram.lock sequence.lock.ata.SB (Most Significant Bit).SB (Least Significant Bit).lock frame.
the data is clocked into the TJ1-MC__, the position value is reted. With this position value, it produces a value for MPOS and a on error that is used to close the control loop.
onnections for SSI are:
A
B
G
C
D E
Hardw
HARD 182
Revision 5.0
/i
fig. 120The tStegm/i
RelatThe f• A• E
For m
Enco
DATA
DATA
CLOC
CLOC
GND
24 VDC Power Supply
24 V0 V
67125
2
TJ1-FL02
103111
8
Enco
Pin
2
10
3
11
1
8
1.
are reference
WARE REFERENCE MANUAL
able below and the figure give an example of how to connect the ann ATM 60-A encoder to the TJ1-FL02.
ed BASIC commandsollowing BASIC commands are related to SSI absolute encoders:TYPE (ATYPE=48) NCODER_BITS
ore information, refer to the Trajexia Programming Manual.
der signal Axis A Axis B
+ 6 8
- 7 9
K+ 1 11
K- 2 12
5 / 15 5 / 15
NoteThe TJ1-FL02 does not have a termination inside. In case of long distances or disturbed communication, add an external termina-tion to the TJ1-FL02.
der TJ1-FL02
Signal Wire color Pin Signal
DATA+ White 6 DATA+
DATA- Brown 7 DATA-
CLOCK+ Yellow 1 CLOCK+
CLOCK- Lilac 2 CLOCK-
GND Blue 5 GND
Us Red See footnote 1
Use an external power supply
Hardw
HARD 183
Revision 5.0
EnDaYou cinterfencodrespoData when
fig. 121The tan exHeideC4 en
Enco
DATA
/DATA
CLOC
/CLO
GND
5 VDC Power Supply
5 V0 V
67125
3
TJ1-FL02
4765
21
Enco
Pin
3
4
7
6
5
are reference
WARE REFERENCE MANUAL
tan configure the TJ1-FL02 to ace directly to EnDat absolute ers. EnDat absolute encoders nd on a dedicated Clock and 1 MHz RS485 serial interface their position is requested by
the controller. When you set the encoder to the relevant encoder mode, the axis transmits an information request to the encoder on a fixed 250 µs cycle. The connections for EnDat are: /i
able below and the figure give ample of how to connect the nhain ROC 425 2048 5XS08-coder to the TJ1-FL02.
/i
der signal Axis A Axis B
6 8
7 9
K 1 11
CK 2 12
5 / 15 5 / 15
NoteThe TJ1-FL02 does not have a termination inside. In case of long distances or disturbed communication, add an external termination to the TJ1-FL02.
der TJ1-FL02
Signal Wire color Pin Signal
DATA Grey 6 DATA
/DATA Pink 7 /DATA
CLOCK Violet 1 CLOCK
/CLOCK Yellow 2 /CLOCK
GND White/Green 5 GND
Hardw
HARD 184
Revision 5.0
RelatThe forelate• A• E• E• E• E• E
For mTraje
Tamafig. 122In the
and B
2
1
1.
Enco
Pin
kΩ
kΩ20
kΩ
V
TJ1-FL02B
Enco
SD
/SD
GND
are reference
WARE REFERENCE MANUAL
ed BASIC commandsllowing BASIC commands are d to EnDat absolute encoders:TYPE (ATYPE=47) NCODER_BITS NCODER_CONTROL NCODER_READ NCODER_TURNS NCODER_WRITE
ore information, refer to the xia Programming Manual.
gawa
The TJ1-FL02 can interface directly to Tamagawa “SmartAbs” absolute encoders. Tamagawa encoders respond on a dedicated 2.5 MHz RS485 serial interface when their position is requested by the controller. When you set the encoder to the relevant encoder mode, the axis transmits an information request to the encoder on a fixed 250 µs cycle. The data returned is available to BASIC and you can use it to drive a servo motor.
figure, A is the encoder side, is the receiving side.
The connections for Tamagawa are: /i
0 V White See footnote 1
Up Blue
Use an external power supply
der TJ1-FL02
Signal Wire color Pin Signal
1
2
1
5
DE
ADM485
A
der signal Axis A Axis B
6 8
7 9
5 / 15 5 / 15
NoteThe TJ1-FL02 does not have a termination inside. In case of long distances or disturbed communication, add an external termination to the TJ1-FL02.
Hardw
HARD 185
Revision 5.0
fig. 123The tTama/i
RelatThe fencod• A• E• E• E
For m
675
SD
TJ1-FL02
/SDGND
VCC
5 VDC Power Supply
5 V0 V
Enco
Signa
SD
/SD
GND
Vcc
are reference
WARE REFERENCE MANUAL
able below and the figure give an example of how to connect the gawa TS5667N420 encoder to the TJ1-FL02.
ed BASIC commandsollowing BASIC commands are related to Tamagawa absolute ers:
TYPE (ATYPE=46) NCODER_ID NCODER_STATUS NCODER_TURNS
ore information, refer to the Trajexia Programming Manual.
der TJ1-FL02
l Wire color Pin Signal
Blue 6 SD
Blue/Black 7 /SD
Black 5 GND
Red Use an external power supply
Hardw
HARD 186
Revision 5.0
3.10.fig. 124The T
amplithis in• E• S• D
RelaThe f• A• IN
For m
3.10.
The TeventfallingcaptucorreYou sThe poverhBecacombcan utime fWe remore
MOVE(4) MOVE(-4)
are reference
WARE REFERENCE MANUAL
8 Stepper
J1-FL02 can generate pulses to drive an external stepper motor fier. You can use single step, half step and micro-stepping drivers with terface. Applicable signals:nabletepirection.
ted BASIC commandsollowing BASIC commands are related to stepper outputs:TYPE (ATYPE=43) VERT_STEP
ore information, refer to the Trajexia Programming Manual.
9 Registration
J1-FL02 can capture the position of an axis in a register when an occurs. The event is called the print registration input. On the rising or edge of an input signal (either the Z marker or an input), the TJ1-FL02 res the position of an axis in hardware. You can use this position to ct possible errors between the actual position and the desired position. et up the print registration with the REGIST command.osition is captured in hardware and therefore there is no software ead. This eliminates the need to deal with timing issues.use the registration inputs are very fast, they are susceptible to noise in ination with slow rising and falling edges. To counter this problem, you se a digital noise filter. Use of the noise filter increases the response rom 0.5 µs to 3.5 µs.fer to the REGIST command in the Trajexia Programming Manual for
information on using the registration inputs.
ENABLE
STEP
WDOG=ON
DIRECTION
Hardw
HARD 187
Revision 5.0
3.10.
The TswitcpredereachThe otimesWe reManu
3.10.
• S• T• P• P• P
are reference
WARE REFERENCE MANUAL
10 Hardware PSWITCH
J1-FL02 has 2 outputs that you can use as hardware position hes. These outputs go on when the measured position of the fined axis is reached. They go off when another measured position is ed.utputs are driven by hardware only. This means that the response do not have software delays.fer to the HW_PSWITCH command in the Trajexia Programming al for more information on using the position switches.
11 TJ1-FL02 box contents
afety sheet.J1-FL02.rotection label attached to the top surface of the unit.arts for a 15-pin connector.arts for an 18-pin connector.
Differences between Sigma-II and Junma
HARDWARE REFERENCE MANUAL 188
Revision 5.0
A Differences between Sigma-II and JunmaThese are the differences between Sigma-II and Junma Servo Drivers and motors.1. Motor
• The Sigma-II Servo Driver can control a large range of servo motors. These include rotary, DD and Linear motors with different encoders, IP rates, inertias and other electrical and mechanical characteristics.
• The Junma can only control Junma motors with a 13-bit incremental encoder. These motors have a low IP rate and medium inertia.
2. Power and voltage range• The output power of Sigma-II Servo Drivers and motors range from
30 W to 15 kW. The input voltages of Sigma-II Servo Drivers and motors are 200 V single phase and 400 V three phase.
• The output power of Junma Servo Drivers and motors range from 100W to 800W. The input voltage of Junma Servo Drivers and motors is 200V single phase.
3. Power circuit• Sigma-II always has a breaking chopper. Most models have internal
braking resistor too. The voltage supplies for power and control circuits are separate.
• Junma has no breaking chopper or resistor. The same voltage supply is used for both power and control circuits.
4. Motion control algorithm• Sigma-II has a traditional PID control algorithm, which in most cases
needs adjustments and tuning of parameters. Sometimes adjusting and tuning can be time consuming but the benefit is full coverage of a very wide range of applications regarding mechanical characteristics of the system, such as inertia ratio, rigidity etc.
• Junma supports a new and innovative self-tuning control algorithm, which requires no adjustment and tuning from the user. The benefit of this algorithm is that commissioning of the system is very fast and easy. The drawback is a limited range of applications covered. This particularly applies to inertia ratio. Junma Servo Drivers and motors cannot serve applications where the inertia ratio is larger than 1:10 approximately.
5. Control modes
• Sigma-II can work in all three control modes: position mode (ATYPE=40), speed mode (ATYPE=41) and torque (force) mode (ATYPE=42).
• Junma can work only in position mode (ATYPE=40). Trying to set an axis assigned to a Junma Servo Driver and motor to some other control mode results in an alarm on the driver
6. I/O• Sigma-II has 7 digital inputs and 4 digital outputs. Functionality of
these I/Os is very flexible and can be configured using drivers parameters. Analog control is possible (with the TJ1-FL02). There is an encoder output as well, and fully closed encoder configuration is possible.
• Junma has 4 digital inputs and 2 digital outputs. They are not flexible, but have fixed functionality. Fully closed encoder configuration is not possible.
7. Operator interface and settings• The Sigma-II Servo Driver has a full operator interface. It consists of
a 4-digits display and 4 buttons. The interface can be used to monitor and change parameters, perform tuning etc. Changing parameters by using the CX-Drive software or by sending MECHATROLINK-II commands from Trajexia is also possible.
• The Junma Servo Driver has a limited operator interface. It consists of a 1-digit display that shows the driver status and alarms. Monitoring and changing of parameters is only possible by using a separate operator panel, the CX-Drive software or by sending MECHATROLINK-II commands from Trajexia.
For more detailed information on the differences between Sigma-II and Junma Servo Drivers and motors, please see their respective manuals.
Revision history
HARDWARE REFERENCE MANUAL 189
Revision 5.0
Revision historyA manual revision code shows as a suffix to the catalogue number on the front cover of the manual./i
Revision code Date Revised content
01 August 2006 Original
02 October 2006 DeviceNet update
03 May 2007 Updated with TJ1-MC04, TJ1-ML04, JUNMA series Servo Drivers and the MECHATROLINK-II repeater.Updated with motion control concepts, servo system principles and detailed encoder information.
04 June 2008 Updated with TJ1-CORT, GRT1-ML2, Sigma-V Servo Driver and MECHATROLINK-II functionality (Inverter as an axis)
05 January 2010 Updated with G-Series and Accurax G5 Servo Drivers
Trajexia motion control systemTJ1-MC04, TJ1-MC16, TJ1-ML04, TJ1-ML16, TJ1-PRT, TJ1-DRT, TJ1-CORT, TJ1-FL02 GRT1-ML2
hardware reference manual
Cat. No. I51E-EN-04
Austria Tel: +43 (0) 2236 377 800www.omron.at
Belgium Tel: +32 (0) 2 466 24 80 www.omron.be
Czech Republic Tel: +420 234 602 602 www.omron-industrial.cz
Denmark Tel: +45 43 44 00 11 www.omron.dk
Finland Tel: +358 (0) 207 464 200www.omron.fi
France Tel: +33 (0) 1 56 63 70 00www.omron.fr
Germany Tel: +49 (0) 2173 680 00 www.omron.de
Hungary Tel: +36 1 399 30 50 www.omron.hu
Italy Tel: +39 02 326 81www.omron.it
Middle East & AfricaTel: +31 (0) 23 568 11 00www.omron-industrial.com
Netherlands Tel: +31 (0) 23 568 11 00 www.omron.nl
Norway Tel: +47 (0) 22 65 75 00 www.omron.no
Poland Tel: +48 (0) 22 645 78 60 www.omron.pl
Portugal Tel: +351 21 942 94 00 www.omron.pt
Russia Tel: +7 495 648 94 50 www.omron-industrial.ru
Spain Tel: +34 913 777 900 www.omron.es
Sweden Tel: +46 (0) 8 632 35 00 www.omron.se
Switzerland Tel: +41 (0) 41 748 13 13 www.omron.ch
Turkey Tel: +90 216 474 00 40 www.omron.com.tr
United Kingdom Tel: +44 (0) 870 752 08 61 www.omron.co.uk
OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.omron-industrial.com
Authorised Distributor:
Note:Although we do strive for perfection, Omron Europe BV and/or its subsidiary and affiliated companies do not warrant or make any representations regarding the correctness or completeness of information described in this catalogue. Product information in this catalogue is provided ‚as is‘ without warranty of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability, fitness for a particular purpose, or non-infringement. In a jurisdiction where the exclusion of implied warranties is not valid, the exclusion shall be deemed to be replaced by such valid exclusion, which most closely matches the intent and purpose of the original exclusion. Omron Europe BV and/or its subsidiary and affiliated companies reserve the right to make any changes to the products, their specifications, data at its sole discretion at any time without prior notice. The material contained in this catalogue may be out of date and Omron Europe BV and/or its subsidiary and affiliated companies make no commitment to update such material.
Cat. No. I51E-EN-05
Trajexia motion control system hardware reference manualCat. No. I51E-EN-04