TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 1 of 57
TQ 4200 SERIES INFRARED
REFRIGERANT LEAK DETECTION SYSTEM
MKII
Serial No’s 20000 onwards
© This manual must not be copied or reproduced in part without the express written permission of TQ Environmental PLC. All information contained herein is subject to modification. TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP
44 (0) 1924 380700 FAX 44 (0) 1924 361700
TQ ENVIRONMENTAL PLC BS EN ISO 9001
Filename: 4200BM1 Date: 12-06/07 Author: G. Thompson
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 2 of 57
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 3 of 57
PROPRIETARY
No part of the hardware or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of TQ Environmental PLC
While great efforts have been made to assure the accuracy and clarity of this document, TQ Environmental PLC assumes no liability resulting from any omissions in this document, or from misuse of the information obtained herein. The information in this document has been carefully checked and is believed to be entirely reliable with all of the necessary information included. TQ Environmental PLC reserves the right to make changes to any products described herein to improve reliability, function, or design, and reserves the right to revise this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or changes. TQ Environmental PLC does not assume any liability arising out of the application or any use of any product or circuit described herein; neither does it convey license under its patent rights or the rights of others.
WARNINGS, CAUTIONS AND NOTES
Warnings identify an operating or maintenance procedure, practice, condition, or statement that, if not strictly followed, could result in death or injury to personnel.
Cautions, which appear elsewhere in this manual, identify an operating or maintenance procedure, practice, condition, or statement that if not strictly followed could result in equipment damage or serious impairment of system operation.
Notes highlight certain operating or maintenance conditions or statements that are essential but not of known hazardous nature as indicated by Warnings and Cautions. Warnings, Cautions and Notes are included throughout this manual, as required. Additionally, this section contains important Warnings that may not be contained elsewhere within this instruction manual.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 4 of 57
SAFETY WARNINGS
• FOR SAFETY REASONS, THE TQ4200 MUST BE INSTALLED, OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND THIS INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING THE TQ4200
• • THE OPERATION DESCRIBED IN THIS DOCUMENT IS THE INTENEDED USE OF
THE TQ4200. TQ ENVIRONMENTAL PLC CANNOT BE HELD RESPONSIBLE IF THE TQ4200 IS USED FOR ANY OTHER PURPOSE OTHER THAN THAT STATED. ANY OTHER USE OF THE TQ4200 WILL CAUSE ANY CERTIFICATES ISSUED TO NOT APPLY.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 5 of 57
CONTENTS
SECTION DESCRIPTION
1.0 Introduction
2.0 Description 2.1 Infrared Sensor 2.2 Pneumatic System 2.2.1 External Catch-Pot 2.2.2 Flow Fail 2.2.3 Pressure Sensor 2.2.4 Solenoid Valves 2.2.5 Sampling Pump 2.2.6 DC Electrical Supplies 2.2.7 Outputs
3.0 System Software
3.1 Start-up 3.2 Power on reset 3.3 System Warm-up 3.4 Normal Operating Mode 3.5 Entering Passwords 3.6 Overview of Menu System 3.6.1 Main Menu - Set Time 3.6.2 - Set Date 3.6.3 - Calibrate 3.6.4 - Change Password 3.6.5 - Parameters 3.6.5.1 - Set Location 3.6.5.2 - Set Gas Type 3.6.5.3 - Parameters - Set Alarm 1 3.6.5.4 - Parameters - Set Alarm 2 & 3
3.6.5.5 - Parameters - Set Alarm 1 Type 3.6.5.6 - Parameters - Set Alarm 2 & 3 Type 3.6.5.7 - Parameters - Set Dwell Time 3.6.5.8 - Parameters - Exit Sub Menu 3.7 Overview of the Alarm Operation 3.7.1 Alarm Control Functions 3.7.1.1 Main Menu - Mute Alarm 3.7.1.2 - Reset Alarm 3.7.1.3 - Display Alarms 3.7.1.4 - Erase Alarms 3.8 Technician Mode 3.8.1 - Set No of Zones 3.8.2 - Skip Zone Number 3.8.3 - Calibrate Pressure 3.9 Main Menu - Exit Menu
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 6 of 57
SECTION DESCRIPTION 4.0 Operation
4.1 System Warm-up 4.2 Normal 4.3 Alarms - 4.3.1 - System Fault 4.3.2 - Gas Level Alarms 4.3.2.1 - Mute Alarms 4.3.2.2 - Reset Alarms
5.0 Drawings 6.0 Maintenance 7.0 Parts List 8.0 Fault Finding 8.1 Analyser NVRAM Fault 8.2 OMNICA NVRAM Fault 8.3 Sensor Communications Fault 8.4 OMNICA Communications Fault 8.5 Zero Filter Blocked Fault 8.6 Flow Fail Fault 8.7 No Pressure Fault 8.8 Sensor Drift Fault 8.9 Sensor Fault Appendix ‘A’ Project Specific Information* * See section Sub Index for contents
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 7 of 57
1.0 INTRODUCTION
The TQ4200 is an Aspirated Infrared Refrigerant Leak Detection System (IRLDS). This system utilises infrared gas analysing technology to detect the signatures of the designated gas, thus eliminating any nuisance alarms from other gases, a selection of which are mentioned below;
a) Hydrogen b) Carbon Monoxide c) Carbon Dioxide d) Hexane e) Heat resistance aluminium paint fumes f) Epoxy finishing paint fumes. g) Epoxy finish white base paint fumes. h) Bioguard water based paint i) Methane
The TQ4200 system has the capability of monitoring up to 16 sample points by sequentially cycling through each location. Individual sample lines can be configured to detect differing refrigerant gases. The TQ4200 is currently programmed to monitor the following refrigerants:
a) R12 b) R22 c) R114 d) R134a e) R404A f) R407C g) R403B h) R236fa
Each sample point will also have three individual alarm trip levels. Any gas sample concentration reaching the ‘low’, ‘high’ and ‘high-high’ trip levels will operate the common alarm relays and provide an output to actuate audible/visual alarm devices.
The TQ4200 front panel provides the operator interface via four pushbuttons and a backlit LCD display. During normal operation the LCD display will provide the ‘location’, ‘gas type’ and sample ‘concentration’ for each individual location. The TQ4200 also has the ability to store the last twenty alarms which can be displayed in alarm/time/date format in time order. Each of the sample transport lines are constantly monitored for flow restrictions. In the event of a reduction or loss of flow, a ‘system flow alarm’ will be initiated.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 8 of 57
The TQ4200 is available in either ‘top’ or ‘bottom’ entry versions for sample lines and cabling, at 85-264V 50/60 Hz. PART NO DESCRIPTION 370-520 TQ420016-way bottom entry 85-264V
370-522 TQ4200 8-way bottom entry 85-264V
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 9 of 57
2.0 DESCRIPTION 2.1 Infrared Sensor (GD134, GD137) The operation of the infrared sensor within the TQ4200 has been developed from the infrared heat source detector utilised in the thermal imaging cameras measuring infrared radiation. These detectors have now developed into non-dispersive infrared analysers. Dispersive analysers use a wide band of infrared to identify a gas, the none-dispersive type narrows the wavelength specific to a gas. The narrow infra red band produced is passed through the gas sample and a gas specific to this wavelength will absorb this infrared depending on the concentration. The electronics converts this absorption of infrared into an electrical signal for processing. The narrowing of the band of infrared light is produced utilising filters made of specific material such as calcium fluoride, sapphire, etc. The light source is modulated by a mechanical chopper to give a high performance on very small signal. This modulated light source together with a reference sensor, which is not exposed to the gas sample, gives a very accurate signal for a concentration of the target gas. 2.2 Pneumatic System The gas sample is brought into the TQ4200 at approximately 4 litres/min from one of the 15 sample lines, into the solenoid bank manifold by a diaphragm pump and presented to the infrared sensor. A particulate filter is fitted before the pump. (Please refer to Figure 3 & 4). 2.2.1 External Catch-Pot The external catch-pot will remove the majority of moisture within the sample line. If the bowl is allowed to fill the catch-pot will automatically shut-off the sample line causing a flow fail alarm. 2.2.2 Flow Fail The flow fail is detected by the PCB mounted differential pressure switch sensing across a differential pressure tube (See Figure 4).This PCB will provide an alarm output when there is a reduction in air flow.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 10 of 57
2.2.3 Pressure Sensor A pressure sensor monitors the air pressure in the vent line of the TQ4200 to provide the electronics with pressure information when calculating the gas concentration. This pressure sensor is also a PCB mounted device. 2.2.4 Solenoid Valves The solenoid valves in either an 8-way or 16-way configuration, are mounted on an eight way common manifold and have 24V DC operating coils. Fitted within the solenoid valve connector covers are back EMF diodes and LED indicators. The common manifold also provides the individual sample line inlet ports. Each port is 1/8” BSP and can be fitted with a union connector to suit the transport tubing. (Note: these inlet connectors are not included with the standard unit). 2.2.5 Sampling Pump The sampling pump is a single ended unit power by 24VDC from the internal power supply. The pump is fitted with viton diaphragm and seals, and requires very little maintenance. Flow rate for this application is 4 litres/hour. The electrical supply to the pump is wired through Fuse 4 (See Figure 5). 2.2.6 DC Electrical Supplies The DC electrical supplies for the TQ4200 are provided by its internal 110 Watt power supply unit. This is a universal input device and will accept an input of 85 to 250 Volts AC. (See Figure 5). The mains input to the TQ4200 unit is connected to TBF-01 and then to a fused isolator via the EMC suppresser. 2.2.7 Outputs Outputs from the TQ4200 are in the form of:-
- Volt Free Contacts for Alarm 1, 2 and 3 and Common Fault
- 24V DC @ 100mA for Visual Alarm - 24V DC @ 100mA for Audible Alarm
- One 4-20mA analogue output RS485 Modbus 4-20ma Output with respect to concentratiom (0-2000ppm) 4-20ma Output with respect to locaction (1ma per location)
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 11 of 57
2.2.7 MODBUS O/P The MODBUS bus output can be connected to any MODBUS configurable device. The standard register addresses and communications protocol are defined as follows:-
Input Register (0x04)
Starting Address (High)
Starting Address (Low)
Number of Registers
(High)
Number of Registers
(Low)
Number of Bytes
Station Number Read (0x04) Write (0x10)
0x00 0x10 0x00 0x01 2
Zone 1 Conc. 0x00 0x00 0x00 0x01 2 Zone 2 Conc. 0x00 0x01 0x00 0x01 2 Zone 3 Conc. 0x00 0x02 0x00 0x01 2 Zone 4 Conc. 0x00 0x03 0x00 0x01 2 Zone 5 Conc. 0x00 0x04 0x00 0x01 2 Zone 6 Conc. 0x00 0x05 0x00 0x01 2 Zone 7 Conc. 0x00 0x06 0x00 0x01 2 Zone 8 Conc. 0x00 0x07 0x00 0x01 2 Zone 9 Conc. 0x00 0x08 0x00 0x01 2 Zone 10 Conc. 0x00 0x09 0x00 0x01 2 Zone 11 Conc. 0x00 0x0A 0x00 0x01 2 Zone 12 Conc. 0x00 0x0B 0x00 0x01 2 Zone 13 Conc. 0x00 0x0C 0x00 0x01 2 Zone 14 Conc. 0x00 0x0D 0x00 0x01 2 Zone 15 Conc. 0x00 0x0E 0x00 0x01 2 Zone 16 Conc. 0x00 0x0F 0x00 0x01 2 Discrete Inputs (0x02)
Starting Address (High)
Starting Address (Low)
Number of Registers (High)
Number of Registers (Low)
Number of Bytes
Alarm Status 0x00 0x00 0x00 0x01 2 Input
Number
Alarm 1 0 Alarm 2 1 Alarm 3 2 Fault 3
Communications Protocol Baud Rate Data Bits Parity Stop Bits Transmission Error
Check 19200 8 Even 1 RTU CRC-16
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 12 of 57
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 13 of 57
3.0 SYSTEM SOFTWARE
This section explains in detail the system set-up and operation of the TQ 4200 main board. Four keys are used to navigate through and access the system software functions, namely: MENU, SELECT, UP, and DOWN.
3.1 System Start-up
When the system is powered on or a hardware system reset occurs, the TQ 4200 main board will boot up showing the Start-up screen in Figure 3-1 below:
TQ ENVIRONMENTAL PlC
TQ4200
Figure 3-1 Start-up Display
3.1.1 NVRAM Test The TQ 4200 will perform an internal non-volatile memory self-test. The result of the test being displayed on the LCD as shown below:
Testing: NVRAM
NVRAM TEST: PASS
Figure 3-2 NVRAM Self Test
3.2 Power-on Reset*
The power-on reset function is used to load the default data into the system. The user must initiate the power-on reset by pressing and holding the SELECT key, UP key, and DOWN key simultaneously for approximately two seconds when the power is turned on.
If the user does not initiate a power-on reset then the system will begin initialisation by downloading the previous parameters into system memory from the non-volatile serial RAM. This stage is indicated on the liquid crystal display by Figure 3-3 shown below:
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 14 of 57
DOWNLOADING DATA
…….
Figure 3-3 System Initialisation Display
* The system start up is only required on the very first power up or if any data becomes corrupt.
3.3 System Warm-up
When the TQ 4200 main board is powered on or a hardware reset is applied, the system will undergo a warm-up period. This warm-up period will last no longer than 2 minutes and the liquid crystal display will be as shown in Figure 3-4 below:
SENSOR WARMUP PERIOD
PLEASE WAIT…
Figure 3-4 Warm-up Period Mode
If the warm-up period is unsuccessful and 15 minutes has elapsed since the power has been turned on, the system will select the System Fault mode.
N.B. Due to the temperature changing within the cabinet the sensor will take time to obtain 95% accuracy. After 8 hours the system will reached its peak accuracy. The systems are therefore designed for continuous operation and should not be powered down as necessary.
When the system has settled, any opening of the door on the cabinet will reduce the accuracy again of the system. Therefore several hours are required for true readings to be obtained. This is due to the fact explained in section one where originally these sensors were used for thermal imaging and the difference in temperatures affects their accuracy. Additionally the detector and reference elements in the system have different coefficients of heat dissipation which results in loss of accuracy.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 15 of 57
3.3.1 Internal System Leak Test After the warm-up period is complete the system will initiate a Pressure Test. This will test for any internal leaks within the system.
PRESSURE TEST
PLEASE WAIT…
Figure 3-5 Pressure Test
3.3.2 Sensor Auto-Zero At initial start up the system will initiate a sensor auto-zero. This will then be performed at the end of every cycle.
SENSOR AUTO-ZERO
PLEASE WAIT…
Figure 3-6 Sensor Auto-Zero
3.4 Normal Operating Mode
The TQ 4200 main board has two distinct modes of operation: the Normal Operating Mode and the Menu Mode. After system initialisation, the TQ 4200 main board will automatically select the Normal Operating Mode. In this mode the system will scan each zone location sequentially, displaying on the liquid crystal display the current zone location, the sampled gas, and the sampled gas concentration in parts per million (ppm). This information is displayed as shown in Figure 3-7 below:
ZONE 1
R134A 00000 ppm
Figure 3-7 Normal Operating Mode
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 16 of 57
When selecting a particular zone location, its corresponding solenoid is activated in order to sample the gas concentration. At the end of the ‘solenoid on’ sequence the sampled gas concentration is measured and compared with two user defined alarm levels. If the sampled gas concentration has exceeded the stored alarm levels then an appropriate alarm relay will be activated. The display will confirm the alarm condition by displaying the zone location, alarm number, and alarm status. An example of an alarm condition is shown in Figure 3-8 below, together with either the first and second red alarm LED’s.
ZONE 1
ALARM1 ACTIVE
Figure 3-8 Example of Alarm Condition
A more detailed discussion of alarm conditions will be presented in section 4 of this manual.
3.5 Entering Passwords
To gain access to the Menu Mode, the user must enter a password (four-digit code). The numbers must be selected and entered one at a time. The UP and DOWN keys are used to scroll through the numbers. When the desired number is displayed, pressing the SELECT key will ENTER that number. The entered number will be blanked out after the SELECT key is pressed to ensure restricted access to the menu system. The cursor will now move to the next digit to the right of the blanked out digit and pressing the UP and DOWN keys will again change the number as required.
ENTER PASSWORD
****
Figure 3-9 Display Password Prompt
After the four digits have been entered the system will check the entered password against the correct password. If the entered password is correct, the display will indicate this by displaying that the password has been accepted. The system will now select the Menu mode. If the entered password is incorrect the display will indicate this by displaying that the password is invalid. If the entered password is invalid, the user is again prompted to enter a password. (System default Password number is 6197).
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 17 of 57
3.6 Overview of the Menu System
The menus are accessed from the Normal Operating Mode by pressing the MENU key. A password must be entered by the user to access the Menu Mode. Once the password has been accepted, the user will be presented with the Menu Screen. The menu may be navigated by pressing the UP and DOWN keys, which will enable the user to scroll through the menu items. The menu items will wrap around from the last menu item to the first menu item and vice-versa. For example, if the UP key is pressed when the last menu item, EXIT MENU, is displayed, the first menu item, SET TIME, will be displayed. Conversely, if the DOWN key is pressed when the first menu item, SET TIME, is displayed, the last menu item, EXIT MENU, will be displayed. To select the desired menu item, the user must press the SELECT key.
3.6.1 Main Menu - Set Time
When the SET TIME menu item is entered from the display, shown below in Figure 3-10, the system time may be altered. This real time clock will remain active and maintain an accurate time even when power to the system is turned off.
MAIN MENU
SET TIME
Figure 3-10 Set Time Menu Option
If the SET TIME menu item is selected the user will be prompted to enter the desired hours and minutes. The time is configured in the 24-hour clock mode. The SET TIME menu item display is shown in Figure 3-11 below. When first entered, the ‘hours’ value will flash indicating that this is the active field. Pressing the UP and DOWN keys will alter this field. To accept the displayed value the user must press the SELECT key. The ‘minutes’ value will now flash enabling the user to alter this field. Pressing the SELECT key again will set the minutes value. The SELECT key in this menu item acts as a toggle between selecting the ‘hours’ field and the ‘minutes’ field. When the desired time has been set the user must press the MENU key to exit the SET TIME menu item and return to the main menu.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 18 of 57
SET TIME
19:04
Figure 3-11 Set Time Menu Item 3.6.2 Main Menu - Set date
When the SET DATE menu item is entered from the display, shown below in Figure 3-12, the system date may be altered. This real time clock will remain active and maintain an accurate date even when power to the system is turned off.
MAIN MENU
SET DATE
Figure 3-12 Set Date Menu Option
If the SET DATE menu item is selected the user will be prompted to ENTER the desired date, month, and year (dd/mm/yy). The date format is as shown in Figure 3-13 below. When first entered, the date value will flash indicating that this is the active field. Pressing the UP and DOWN keys will alter this field. To accept the displayed value the user must press the SELECT key. The month value will now flash enabling the user to alter this field. Pressing the SELECT key again will set the month value. Pressing the SELECT key again will enable the user to set the year value. The SELECT key in this menu item acts as a toggle between selecting the three date fields. When the desired date has been set the user must press the MENU key to exit the SET DATE menu item and return to the main menu.
SET DATE
08/01/00
Figure 3-13 Set Date Menu Item 3.6.3 Main Menu - Channel Functions
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 19 of 57
TECHNICIAN MENU
CHANNEL FUNCTIONS
Figure 3-14 Channel Functions When this menu option is selected, the user is provided with a Channel Functions sub-menu. This sub-menu allows the user to select a particular zone location and then Skip, goto, hold, or remove hold that zone location. When the zone location is in the hold state, that particular zone location will be held for a maximum period of 20 minutes before automatically reverting to normal operation. The user may remove the hold state at any time using the Remove Hold sub menu function. Please note, the channel may alarm and be muted while using this function.
The Skip function allows the user to turn off a redundant zone. This can prove useful if the user requires to do any maintenance on that line or if the line becomes obsolete.
3.6.4 Main Menu - Change Password
The user may change the password if desired. (Default 6197). This is achieved through the CHANGE PASSWORD menu option as shown in Figure 3-15 below:
MAIN MENU
CHANGE PASSWORD
Figure 3-15 Change Password Menu Option
When this option is selected the user is prompted to enter the new password. This procedure is carried out in the same manner as entering password explained previously. Once the new password has been entered the user is prompted to re-enter the new password to ensure that it is the desired password, i.e. to ensure that it was entered correctly the first time. If the password was not entered correctly the display will indicate that an invalid password was entered and prompt the user to repeat the procedure. The user will be prompted a maximum of two times and if the password is still invalid the previous password will take effect. The system will return to the main menu mode.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 20 of 57
3.6.5 Main Menu - Parameters
System parameters may be set and edited by entering the PARAMETERS menu option. This option is shown overleaf in Figure 3-16:
MAIN MENU
PARAMETERS
Figure 3-16 Parameters Menu Option
Once entered, the display will prompt the user to select a desired zone location for editing. The user must press the UP and DOWN keys to display the required zone location and then press the SELECT key to accept that zone location.
When a zone location has been selected, the user may cycle through the Parameters Sub Menu using the UP and DOWN keys and select the required Parameters Sub Menu Item using the SELECT key. A detailed description of the Parameters Sub Menu items now follow:
3.6.5.1 Set Location
The 16 zone locations are set by default to ‘ZONE 1’, ‘ZONE 15’. This option will allow the user to change the name of the zone locations to a more meaningful description up to 16 characters in length, including the <SPACE> character. An example of which is shown in Figure 3-17 below:
PARAMETERS
SET LOCATION
Figure 3-17 Example of Zone Description
The user must use the UP and DOWN keys to cycle through the alphanumeric characters, pressing the SELECT key when the display shows the required character. To leave spaces, select the <SPACE> character and press the SELECT key. When the SELECT key has been pressed the next digit on the right will be displayed.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 21 of 57
PARAMETERS
FRUIT STORE 1
Figure 3-18 Example of Location Name To accept the zone location description the user must press the MENU key to exit the PARAMETERS MENU OPTION.
3.6.5.2 Set Gas Type
This option is used to set a particular gas to a particular zone location. (Refer to page 4 of this manual for refrigerant gas list). The current zone location is the one entered at the beginning of the parameters sub menu. To select a particular gas the user must press the UP and DOWN keys to cycle through the available gases. These gases have already been calibrated via the technical menu using sample line 1. When the desired gas is displayed the user must press the SELECT key to make that gas active for that zone location. This is shown in Figure 3-18 below:
PARAMETERS
SET GAS TYPE
Figure 3-19 Set Gas Type Display
3.6.5.3 Set Alarm 1
This option is used to set the alarm level for Alarm 1. The alarm level is set in conjunction with the SET ALARM TYPE option which will be explained in section 3.6.5.5.
PARAMETERS
SET ALARM 1
Figure 3-20 Set Alarm 1 Option
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 22 of 57
When selected this option allows the UP and DOWN keys to set the gas Alarm 1 level. This level is displayed in ppm and can be set in the range 0000ppm to 10,000ppm. To select the desired alarm level the user must press the SELECT key. When the desired alarm level is set the system will go back to the PARAMETERS menu option and prompt the user to select another zone location. If the user wishes to exit the Parameters sub menu the user must select a zone location and use the EXIT SUB MENU option to return to normal system operation. (System default for alarm 1 is set to 1000 ppm).
3.6.5.4 Set Alarm 2 & 3
This option is identical to the SET ALARM 1 menu option but corresponds to Alarm 2 & 3 and works in conjunction with the SET ALARM 2 & 3 TYPE option. (System default for alarm 2 is 1250 ppm and alarm 3 is 1500 ppm).
3.6.5.5 Set Alarm 1 Type
This option is used to select whether an alarm is generated when the concentration is rising (+) or falling (-). When selected the user is presented with the display shown in Figure 3-22 below:
PARAMETERS
SET ALARM 1 TYPE
Figure 3-21 Set Alarm 1 Type Option
To change between positive going and negative going alarm levels the user must toggle between (+) and (-) using the UP and DOWN keys. When the required alarm type is displayed the user must press the SELECT key to enter the alarm type. (System default for alarm 1 is (+)).
3.6.5.6 Set Alarm 2 & 3 Type
This option is identical to the SET ALARM 1 & 3 TYPE described above but corresponds to the Alarm 2. (System default for alarm 2 is (+)).
3.6.5.7 Set Dwell Time
This option allows the user to specify the time in seconds that the system will remain in a particular zone location before sequentially incrementing to the next zone location. The dwell time is variable in the range from 0 to 300 seconds. On start up this is always 20 seconds
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 23 of 57
PARAMETERS
SET DWELL TIME
Figure 3-22 Set Dwell Time Option
To change the dwell time for a particular zone the user must press the UP and DOWN keys and the SELECT key when the desired dwell time is displayed. (System default dwell time is 20 seconds).
3.6.5.8 Exit Sub Menu
This option will allow the user to return to the Normal Operating mode and continue sampling the zone locations. The user must press the SELECT key to accept this option.
PARAMETERS
EXIT SUB MENU
Figure 3-23 Exit Sub Menu Option
3.7 Overview of the Alarm Operation As explained previously an alarm condition will occur if the sampled gas level exceeds the set alarm level. That is, for a rising (+) alarm type the alarm will be activated if the sampled gas level is greater than the alarm level, and for a falling (-) alarm type the alarm will be activated if the sampled gas level is less than the alarm level.
When an alarm occurs the zone location, alarm number, and alarm status is displayed on the LCD and the relevant alarm relays are activated. The display will freeze on the first alarm activated and the system will then continue scanning the other zone locations sequentially. If a second alarm is detected while the first alarm is still active, the system will store the zone location, alarm number, and alarm status of the second alarm and place this into a queuing system while still only displaying the first alarm conditions on the LCD. Further alarms will continue to be stored up to a maximum value of 20 alarms. The following sections will describe in detail the various functions available to control the alarm status.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 24 of 57
3.7.1 Alarm Control Functions
3.7.1.1 Main Menu - Mute Alarm (Acknowledge)
This option is used to mute the most recent alarm. When selected on the main menu, the system will display for a period of approximately 5 seconds that the alarm has been acknowledged. This is shown in Figure 3-24 and Figure 3-25 below:
ZONE 1
ALARM 1 ACTIVE
Figure 3-24 Example of Alarm 1 Active
When a mute alarm has been selected the display will be as shown in Figure 3-25 below:
ZONE 1
ALARM 1 ACK
Figure 3-25 Example of alarm mute If no other alarms are active the system will resume normal operation and continue scanning the zone locations. However, if another alarm is active the display will show this active alarm until cleared as shown in Figure 3-26 below:
ZONE 1
ALARM 2 ACTIVE
Figure 3-26 Example of Pending Alarm Active after Mute Alarm
When the user has muted an alarm and the system has cycled through the zone locations back to the muted zone location, that muted zone location will be indicated by a flashing alarm status LED to indicate the alarm location has
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 25 of 57
been acknowledged but not reset. The only way to clear a muted zone location is to use the RESET ALARM option.
3.7.1.2 Main Menu - Reset Alarm
This option is used to reset the most recent alarm. The RESET ALARM option may be performed on an active alarm or on a muted alarm. The RESET ALARM function is invoked by pressing the SELECT key when the display is as shown in Figure 3-27 below:
MAIN MENU
RESET ALARM
Figure 3-27 Reset Alarm Menu Option
When selected on the main menu, the system will de-activate the relevant alarm relay and display for a period of approximately 5 seconds that the alarm has been acknowledged. This is shown in Figure 3-28 and Figure 3-29 below:
ZONE 2
ALARM 1 ACTIVE
Figure 3-28 Example of Alarm 1 Active When a Reset Alarm has been selected the display will be as shown in Figure 3-29 below:
ZONE 2
ALARM 1 ACK
Figure 3-29 Example of Alarm Reset
If no other alarms are active the system will resume normal operation and continue scanning the zone locations. However, if another alarm is active the display will show this active alarm until cleared as shown in Figure 3-30 below:
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 26 of 57
ZONE 4
ALARM 2 ACTIVE
Figure 3-30 Example of Pending Alarm Active after Reset Alarm
When the user has reset an alarm and the system has cycled through the zone locations back to the reset zone location, then that reset zone location will alarm again if the alarm level has been or still is exceeded.
3.7.1.3 Main Menu - Display Alarms
This option is used to display the last 20 stored alarms.
MAIN MENU
DISPLAY ALARMS
Figure 3-31 Display Alarms Menu Option
The information displayed is the date and time of alarm, zone location and the order that the alarm occurred in. This is as shown in Figure 3-32 below:
ZONE 2 ALARM 4
08/01/00 07:14
Figure 3-32 Example of Display Alarms Information In the example shown in Figure 3-32 above, the alarm number is 4. This implies that this was the fourth alarm to become active. Pressing the SELECT key will display the alarm information for the third alarm to become active. Subsequent presses of the SELECT key will display the second alarm to become active, then the first alarm to become active. When Alarm 1 is displayed, pressing the SELECT key again will return the system to the Normal Operating Mode and the system will continue scanning the zone locations.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 27 of 57
3.7.1.4 Main Menu - Erase Alarms
This option is used to erase the stored alarms. To invoke this function the SELECT key must be pressed by the user on the ERASE ALARMS menu option as shown in Figure 3-33 below:
MAIN MENU
ERASE ALARMS
Figure 3-33 Erase Alarms Menu Option
This option will erase all the stored alarms at once. 3.8 Menu - Technician Menu
MENU
TECHNICIAN MODE
Figure 3-34 Technician Menu Option
This allows the user to define the number channels required by the system, calibrate the pressure being drawn thorough the system or skip a redundant zone. Once entered, the display will prompt the user to enter another password as in Section 3.5 (Entering Main Menu). This password however is different from the one mentioned in Section 3.5 and cannot be changed from the default setting: Phone TQ for Password.
ENTER PASSWORD
****
Figure 3-35 Display Password Prompt
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 28 of 57
3.8.1 Technician Menu - Set Number of Zones
When the password has been successfully entered the SET NUMBER OF ZONES menu item appears, shown below in figure 3-36
TECHNICIAN MENU
SET NUMBER OF ZONES
Figure 3-36 Display Set Number of Zones Prompt
If the SET NUMBER OF ZONES menu is selected the user will be prompted to ENTER the number of points to be sampled. The system requires ranging from 1-15; remembering that during installation sample line 0 is reserved as a zero calibration line. Pressing the UP and DOWN buttons will alter this field from the default 15 zones. Then to accept the displayed value the user must press the SELECT buttons. From here the user will return to the technical mode menu. (System default is 15 zones)
3.8.2 Technical Menu - Skip Zone Number
This part of the technical menu allows the user to turn off a redundant zone. This can prove useful if the user requires to do any maintenance on that line or if the line becomes obsolete.
TECHNICAL MENU
SKIP ZONE NUMBER
Figure 3-36 Skip Zone Number
When this menu option is selected the user is prompted to select which zone is to be skipped. Using the UP or DOWN keys will scroll through each zone in operation. When the desired zone is highlighted the SELECT key will accept that zone as the one to be ignored.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 29 of 57
SKIP ZONE NUMBER
ZONE 1
Figure 3-37 Select Zone Number
3.8.2 Technician Menu - Calibrate Pressure
This part of the technical menu is used to calibrate the pressure sensor on the Infra red sensor.
TECHNICIAN MENU
CALIBRATE PRESSURE
Figure 3-37 Calibrate Pressure This is already factory set and should not be attempted by anyone other than TQ personnel.
3.8.3 Technician Menu – Calibrate Gas
This option is factory set and will not require any attention from any one other than TQ personnel.
TECHNICIAN MENU
CALIBRATE GAS
Figure 3-38 Calibrate .
3.8.4 Technician Menu - Set Sensor Range
This part of the Technician Menu will allow the range of the sensor to be changed. The default range is factory set at 2000 ppm. This is already factory set and should not be attempted by anyone other than TQ personnel.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 30 of 57
TECHNICIAN MENU
SET SENSOR RANGE
Figure 3-39 Set Sensor Range 3.8.5 Technician Menu – Exit Menu
From here the user can exit from the technical menu back into the main. To exit the Technical menu, the user must use the UP and DOWN keys to display the EXIT MENU option as shown in Figure 3-40 below:
TECHNICIAN MENU
EXIT SUB MENU
Figure 3-40 Exit Menu
The user must press the SELECT key to invoke this function and return to the Main Menu.
3.9 Menu - Exit Menu
This option is used to exit the Main Menu Mode. To exit the main menu, the user must use the UP and DOWN keys to display the EXIT MENU option as shown in Figure 3-41 below:
MENU
EXIT MENU
Figure 3-41 Menu Exit Option
The user must press the SELECT key to invoke this function and return to the Normal Operating Mode to continue scanning the zone locations.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 31 of 57
4.0 OPERATION
This section explains the TQ4200 main functions and gives an overview of how to deal with the alarms.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 32 of 57
4.1 System warm-up
When the TQ4200 is powered up, the system enters a warm-up period. This warm-up period typically takes about five minutes to complete. During this time the liquid crystal display will indicate that the system is in the warm-up period as shown in Figure 4-2 below:
WARM-UP PERIOD
PLEASE WAIT...
Figure 4-2 Warm-up period 4.2 Normal Operating Mode
After the warm-up period is complete, the system enters the Normal Operating Mode. This mode is indicated by the display shown in Figure 4-3 below:
ZONE 1
R22 00000 ppm
Figure 4-3 Normal Operating Mode
The first line of the display indicates the current zone location. On the second line of the display, the left hand side indicates the sampled gas type and the right hand side indicates the sampled gas concentration in parts per million (ppm).
In Normal Operating Mode, the system will cycle through each zone location performing alarm checks at the end of each zone cycle. The following section describes the alarms.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 33 of 57
4.3 Alarms
The system will generate an alarm under two main conditions. 4.3.1 System Fault
The first of these conditions generates an alarm if the warm-up period has not been completed within 45 minutes of power-on. This will be displayed as a system fault as indicated by Figure 4-4 shown below:
SYSTEM FAULT
Figure 4-4 System Fault
The fault alarm will be activated under this condition. 4.3.2 Gas Level Alarms
The second condition generates an alarm if the sampled gas level exceeds the set alarm point for either Alarm 1 to Alarm 3. When an alarm is generated the TQ4200 displays the zone location, the alarm number, and the alarm status. This is shown in Figure 4-5 below:
ZONE 1
ALARM 1 ACTIVE
Figure 4-5 Alarm Status
The TQ4200 then continues to sample normally. The TQ4200 will continue to display the status of the alarm until the user acknowledges the alarm or alarms.
If a second alarm is activated while the first alarm is still active, the TQ4200 will store the zone location, alarm number, and alarm status of the second
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 34 of 57
alarm and place this into a queuing system. Further alarms will continue to be stored up to a maximum value of 20 alarms. To perform any action on a zone that is in alarm, the user must enter a password. To enter the password the user must first press the MENU button. The user is then prompted to enter the password as shown in Figure 4-6 below:
ENTER PASSWORD
****
Figure 4-6 Password Prompt
To enter the password the user must press the UP button and/or DOWN button to change the number. When the required number is displayed the user must press the SELECT button to accept the choice. This is repeated for all four password digits. Once the password has been accepted the user enters the menu mode and the required function may be selected by pressing the UP button and/or DOWN button followed by the SELECT button when the required function is displayed. (System default password is 6197).
4.3.2.1 Mute Alarms
Select the mute alarms menu to mute the most recent alarm. When this function is invoked, the alarm relay will be de-activated and the display will show that the alarm has been acknowledged as shown in Figure 4-7 below:
ZONE 1
ALARM 1 ACK
Figure 4-7 Alarm Acknowledged
If no other alarms are active, the system will resume normal operation and continue scanning the zone locations sequentially. However, if an alarm is pending after the mute function has been selected, this alarm will become the active alarm. To mute this alarm the user must repeat the procedure detailed above. When the zones cycle back to a muted alarm the alarm indication LED’s will flash indicating this alarm has not been reset.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 35 of 57
4.3.2.2 Reset Alarms
Select the ‘Reset Alarms’ menu to reset the most recent alarm. This option may be performed on a muted alarm or an active alarm producing the same effect. When ‘Reset Alarms’ is selected on the main menu, the system will de-activate the most recent alarm relay and display for a period of approximately 5 seconds that the alarm has been acknowledged. The system will then resume normal system operation. However, if more than one alarm has been activated, the above procedure will need to be repeated until all active alarms have been reset.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 36 of 57
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 37 of 57
5.0 DRAWINGS
DRAWING NO. DESCRIPTION
Figure 1 PANEL OUTLINE
Figure 2 GLAND PLATE OUTLINE
Figure 3 INTERNAL LAYOUT
Figure 4 PNEUMATIC SCHEMATIC
Figure 5 ELECTRICAL TERMINATION
Figure 6 POWER SUPPLY
Figure 7 SOLENOID VALVE CIRCUIT DIAGRAM
Figure 8 FRONT PANEL CIRCUIT DIAGRAM
Figure 9 OUTPUT RELAY WIRING DIAGRAM
Figure 10 SOLENOID DRIVER BOARD
TERMINAL IDENTIFICATION Figure 11 I.R. DRIVER BOARD CONNECTION
DIAGRAM
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 38 of 57
200210
450
490
350
4 x
Mou
ntin
g H
oles
8mm
Dia
pos
ition
ed47
5 H
igh
x 29
0 W
ide.
Hin
ge S
ide
Doo
r Fix
ing
SY
STE
MH
EA
LTH
YA
LAR
M 3
ALA
RM
2A
LAR
M 1
ME
NU
TQ4200
TQ E
NVI
RO
NM
ENTA
L PL
C
Flan
shaw
Way
, Wak
efie
ld, W
Yor
ks E
ngla
nd, W
F2 9
LPTe
l: +
44 (0
)192
4 38
0700
Fa
x: +
44
(0)1
924
3617
00
E
mai
l: S
ales
@tq
plc.
com
web
site
:http
://w
ww
.tqpl
c.co
m
Refrigerant Gas Monitoring System
NO
TES:
1) E
nclo
sure
rate
d at
IP21
Figure 1
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 39 of 57
SAM
PLE
LIN
ES
89
1011
1213
1415
SAM
PLE
LIN
ES1
23
45
67
0
Mai
ns C
able
Ent
ry
Ven
t 6m
m B
ulkh
ead
WA
RN
ING
Do
not o
bstru
ct
VFC
Cab
le E
ntry
VFC
Cab
le E
ntry
Zero
cal
ibra
tion
line
mus
t be
conn
ecte
d to
cle
an d
ry a
ir sa
mpl
e or
cha
rcoa
l filt
er a
t all
times
.
15 x
6m
m P
ipe
fitin
gs
Figure 2
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 40 of 57
1) S
olen
oids
Mou
nted
in e
ither
of o
utlin
ed
P
o siti
ons D
epe n
ding
on
C
ust o
mer
Spe
cif ic
atio
n.
2) C
ross
Re f
er th
e ci
rcle
d
com
pone
n t Id
entif
icat
i on
n
umbe
rs to
the
parts
list
.
NO
TE:
Sole
noid
Ban
k M
ount
ing
Posi
tion
Pt n
o. 3
70-5
20/5
22
Left
Han
d M
ount
ing
Plat
eR
ight
Han
d M
ount
ing
Plat
e 7
11
CA
TCH
POT
4
7 106
8
15
CONTROL PCB
92
3 PSU
T R U N K I N G
PUM
P
GD
134/
137
INFR
A R
EDSE
NSO
R
1
23
1
23
2414
2212
A2
11
RL4
2414
2212
A2
11
RL3
2414
2212
A2
11
RL2
F2F1
2A Isol
ator
N N
3 N
2 E
1 L
2414
2212
A2
11
RL1
A1
A1
A1
A1
2121
2121
F4F3
21 3
4213
4
21 3
4213
4
21 3
4213
4
21 3
4213
44
56
4
56
7
89
7
89
10
1112
10
1112
21
21
Figure 3
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 41 of 57
Pum
p
G D 1 3 4
VEN
T
E xte
rnal
Cut
Off
Cat
ch-p
ot
Pres
sure
Diff
eren
ti al
Switc
h
GD
134
P CB
Sam
ple
Line
s
1 2 3 4 5 6 7 8
ZER
OC
ALI
BR
ATI
ON
LIN
E
+Ve
-Ve
Pres
sure
Diff
eren
tial
Usi
ng V
alve
611
-03 4
F1
9 10 11 12 13 14 15 162 x
8 W
aySo
leno
id B
ank
0 Fitte
d in
top
of C
abin
et
Sing
l e W
aySo
leno
id 9
20-1
02
4mm
OD
PV
C T
ubin
g
Figure 4
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 42 of 57
NO
TES:
1) F
or T
erm
inal
wi ri
ng
refe
r to
Drg
. 420
0T, Q
, BE
2) V
isua
l Ala
r m O
/P ra
ted
1
00m
A @
24V
dc
3) A
udio
Ala
rm O
/P
Rat
ed a
t 100
mA
24 V
dc
1
23
AL1
AL2
AL3
RL1
VFC
RL2
RL3
TBF-
05
1
23
2414
2212
A2
11
RL4
2414
2212
A2
11
RL3
2414
2212
A2
11
RL2
F2F1
2A Isol
ator
N N
3 N
2 E
1 LTBF-
0 1
240/
110V
AC
50/6
0Hz
2414
2212
A2
11
RL1
FAU
LTRL4
T B-0
1TB
F -03 0v
24v0v
24v
0v4-20mA
Vis
ual
Aud
ible
4-20mA Gas Concentration Output
CONTROL PCBO/P
A1
A1
A1
A1
2121
2121
F4F3
SENSORPUMP
0v4-20mA 4-20mA Location
Output
TBF -
02
21 3
4
T BF-
04 BA 0V
MO
DB
US
RS
485
OU
TPU
T213
4
21 3
4213
4
21 3
4213
4
21 3
4213
44
56
4
56
7
89
7
89
10
1112
10
1112
Figure 5
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 43 of 57
RL1
242 221
G/Y1/2/
3 +
5
13 +
24 -0V
L N E
1
ISO
LATO
R
PUM
P
PSU
1 2 3
CO
NN
6
Con
trol B
oard
1 2
TBF-
03
141 7
10
F3(1
A)
F2(2
A)
F 1(1
A)
12
16
17
240/
110V
ac
50/6
0Hz
2AE M
C
SUPR
ESSO
R
Bro
wn
Blu
e
8 5 -
254V
AC
NO
TES:
1) A
ll w
iring
to b
e
UL
1007
20 A
WG
UO
S.
Vio
let
Bla
ck
12
TBF0
1
+24
+50V
7
3
+24
0V +24
LOC
AL
VIS
UA
L
LOC
AL
AU
DIB
L E
19
CO
NN
15
L N E
40V
Gre
en/Y
ello
w
Red
Bla
ck
4/5/
6/7
F4
12
3
CO
NN
1
17
2
45
67
89
1 3
TB-0
10V
17B
lack
1 7
Bla
ck17
Red
Bla
ck
Red
Red
Blk
Red
13R
ed
14R
ed
15R
ed
15
TB- 0
2TO
GD
1 34
See
dwg
4200
BE
1 2
Figure 6
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 44 of 57
1 2 3 4 5 6 7 8 9
SOL
#15
SOL
#14
SOL
#13
S OL
#12
SOL
#11
S OL
#10
S OL
#9
12
34
56
78
9
SOL
#8
SOL
#7
SOL
#6
SOL
#5
SOL
#4
SOL
#3
SOL
#2
SOL
#1
CONN 13
CO
NN
3
+24V
CO
NTR
OL
PCB
Red
61
Bla
ck 6
2
Red
59
Bla
ck 6
0R
ed 5
7
Bla
ck 5
8R
ed 5
5
Bla
ck 5
6R
ed 5
3
Bla
ck 5
4R
ed 5
1
Bla
ck 5
2R
ed 4
9
Bla
ck 5
0R
ed 4
7
Bla
ck 4
8
Red
45
Bla
ck 4
6
Red
43
Bla
ck 4
4R
ed 4
1
Bla
ck 4
2R
ed 3
9
Bla
ck 4
0R
ed 3
7
Bla
ck 3
8R
ed 3
5
Bla
ck 3
6R
ed 3
3
Bla
ck 3
4R
ed 3
1
Bla
ck 3
2
ON
LY IN
CL U
DE
THIS
S EC
TIO
N F
OR
16-
WA
YSY
STEM
S
+24V
21
Red
SOL
#16
123456789
CONN 4
+24V
Red
61
Bla
ck 6
2
ZER
O S
OL
Figure 7
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 45 of 57
1 2 3 4 5 6 7 8 9CO
NN
1
N.C
Con
trol P
CB
NO
TES:
1) A
l l W
iring
to b
e
UL 1
007
20A
WG
U.O
.S.
2) M
ultic
ore
To B
e 10
Cor
e
7/ 0
.2m
m O
vera
ll Sc
reen
ed
(FEC
119
026 4
)
1 2 3 4 5 6 7 8 9CO
NN
15
+24V
0V
SYST
E M H
EALT
HY
ALA
RM
3
ALA
RM
2
MEN
U
DO
WN
UP
SEL E
CT
TQ 4
200
FRO
NT
DO
OR
Bla
ck
Gre
en
Blu
e
Ora
nge
Vio
let
Bro
wn
Whi
te
1 7 731971
Red
26
IC1 4
TB-0
1
74
ALA
RM
1
Yel
low
7270
4200
T
24 25
Mul
ticor
eC
able
Figure 8
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 46 of 57
1 2 3 4 5 6 7 8 9
CONN 15
+24V
CO
NT R
OL
P CB
RL1
RL2
RL3
A1
A2
A1
A2
A1
A2
Bla
ck
Red
74
70
12
3
AL1
8 1
8 1
8 1
45
6
AL2
78
9
AL3
RL4
A1
A2
8 1
7172
731 9
12 1411
12 1411
1 2 1411
8081
8283
8485
8687
88
4200
Q
Whi
teW
hite
TBF-
05TB
F-05
TBF-
05
Whi
te
1011
12
Faul
t
12 1411
8990
91W
hite
TBF-
05
2842
00S
262524
420 0
S
Figure 9
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 47 of 57
CO
NN
9
12
34
56
78
9
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
12
34
56
78
9
9 8 7 6 5 4 3 2 1
12
31
23
12
3
+24V
SOL
15
SOL
14
SOL
13
SOL
12
SOL
11
SOL
10
SOL
9
+24V
SOL 7
SOL 6
SOL 5
SOL 4
SOL 3
SOL 2
SOL 1
MENU
0V
0V
DOWN
UP
0V
0V
SELECT
CO
MM
S
TO G
D 1
34 IN
FRA
RE D
SEN
SOR
( Ref
er T
o D
wg
4200
BE)
DIS
PLA
YO
/P
70 71 19 73 74
Blu
e
See
Drg
's 42
00R
See
Drg
's 42
00Q
See Drg's 4200Q
BA
BA
SOL 8
0V+2
4+5
0V
Blk
Yel
Grn
Red
32
13
21
32
1
60 58 56 54 52 50 48
46
44
42
40
38
36
34
32
Wht
17
17
Brn
Vio
17
17
Orn
72 64 BLK
SOL
0
4-20
mA
5
+SE
CU
RE
WIT
HTY
RA
P B
ASE
& T
YR
AP
3V
4-20
mA
6
63 RED
SOL
0
SOL
1662
Figure 10
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 48 of 57
CO
MM
S
FLY
ING
LE A
DS
FOR
CO
MM
UN
ICA
TIO
NS
AN
D P
OW
ER S
UPP
IED
WIT
H S
ENSO
R
RED
BL
12 0V
4-20mA
34 0V
4-20mA
12
12 B
A
34
0V
TBF-
04
0V
2 C
ore
Twis
ted
Pair
With
Ove
rall
S cre
en17
TBF-
02
24V
DC
F30V TB
- 01TB
-02
56
Pink
Pink
Bla
ck
NO
TES:
1) A
ll w
iring
to b
e
UL
1007
20A
WG
UO
S.
Figure 11
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 49 of 57
6.0 MAINTENANCE
Preventative maintenance requirements on the system have been designed to be
minimal and limited. The details of this maintenance plan are as follows:-
6.1 Weekly
Check external ‘catchpot’ located on the right hand side of the TQ4200 enclosure for water ingress. (See Figure 1).
To drain off water turn the bleed screw on the bottom of the bowl anti-
clockwise as you look at the bottom of the catchpot. Ensure that the bleed screw is turned full clockwise on completion of draining.
6.2 Annually
6.2.1 Replace the particulate filter (Part No. 420-026).
Power down. Locate filter ‘F1’ loose in the lower right hand side of the cabinet, refer to figure 3, Note the direction of flow arrow on the body. Remove pipe from each side change filter and refit in the reverse of above.
6.2.2 Replace the end of line filters (Part No. 420-006).
Locate filters at the sample points, unscrew the end cap and change filter element, and refit end cap.
6.2.3 Replace the charcoal filter (Part No. 420-004) fitted to the
calibration line on sample inlet ‘O’. Locate the filter fitted to the calibration line and remove by undoing the compression nut. Remove the nut from the old filter and place over the new filter port. Place the new brass 1/4” ferrule set supplied, over the same port with the cone front ferrule pointing towards the bulkhead fitting. Push new filter port into the bulkhead fitting and screw on compression nut until finger tight. Mark the nut and bulkhead fitting and tighten the compression nut ¾ to 1.0 turn.
6.2.4 Replace the pump diaphragm and seals (Part No. 920-031). Locate the sample pump, refer figure 3, remove the four screws securing the square pump housing cover plate. Remove the two seals and diaphragm, fit the new items and refit cover
plate.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 50 of 57
6.3 3 Yearly
6.3.1 Replace sample pump Pt No 920-030.
N.B However, it may be more feasible to adopt a ‘breakdown only’ approach to maintaining the system as the repairs are relatively simple and the system will always fail safe. The expected failures will be water ingress to external catchpot as above, filter blockages and pump failure all of which will generate alarms
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 51 of 57
7.0 PARTS LIST
The following pages contain the parts list for the TQ4200 and cross refer to figure 3
ITEM PART NO DESCRIPTION QTY NAME 1. 920-020 Solenoid Bank 2 2. 710-028 PSU 1 3. 710-028A PSU Cover 1 4. 920-030 Sample Pump 1 5. 100-038 Catchpot 1 6. 905-011 Isolator 1 7. 100-041 EMC Suppresser 1 8. 910-009 Relay 4 9. 370-351 4200 Controller PCB 1 10. 420-026 Disposable Filter 1 11. 134-001 GD 134 Infrared Sensor 1 TARGET GAS TO BE
SPECIFIED ON ORDER Figure 12
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 52 of 57
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 53 of 57
8.0 FAULT FINDING
The TQ 4200 has built in fault diagnostics which constantly monitor the operation of the unit and in the event of detecting a fault will indicate a ‘Fault’ followed by: - ANALYSER NVRAM FAIL - 4200 NVRAM FAIL - SENSOR COMMS FAIL - 4200 COMMS FAIL - ZERO FILTER BLOCKED - FLOW FAIL - NO PRESSURE
- SENSOR DRIFT - SENSOR FAULT
Please note that all fault alarms are latched and require an alarm reset as per section 4.3.2.2. ‘Fault’ will remain displayed until all faults have been cleared.
8.1 Analyser NVRAM Fault
FAULT
ANALYSER NVRAM FAIL
Figure 8.1 Faults – Analyser NVRAM Fail
‘Analyser NVRAM Fail’ will be displayed when the gas analyser board has failed to write or read the correct values to or from its’ non-volatile RAM.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 54 of 57
8.2 4200 NVRAM Fault
FAULT
4200 NVRAM FAIL
Figure 8.2 Faults – OMNICA NVRAM Fail
‘4200 NVRAM Fail’ will be displayed when the TQ 4200 has failed to write or read the correct values to or from its’ non-volatile RAM.
8.3 Sensor Communications Fault
FAULT
SENSOR COMMS FAIL
Figure 8.3 Faults – Sensor Communications Fail
‘Sensor Comms Fail’ will be displayed when there is a communications failure between the infrared sensor and the analyser board.
8.4 4200 Communications Fault
FAULT
4200 COMMS FAIL
Figure 8.4 Faults – OMNICA Communications Fail
‘4200 Comms Fail’ will be displayed when there is a communications failure between the TQ 4200 and the gas analyser board.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 55 of 57
8.5 Zero Filter Blocked Fault
FAULT
ZERO FILTER BLOCKED
Figure 8.5 Faults – Zero Filter Blocked
‘Zero Filter Blocked’ will be displayed when the differential pressure sensor on the gas analyser PCB is not sensing its’ correct air pressures when the Zero line solenoid is activated.
Rectification: - Check pump operation. - Check solenoid valve operation.
- Check for security and integrity of all TQ 4200 internal pipe work and fittings.
- Disconnect the ‘Zero line’ from inlet to TQ 4200.
If ‘Zero Filter Blocked’ clears after an alarm reset, check and replace charcoal filter, if necessary. Please note that the ‘Zero Filter Blocked’ alarm requires an alarm reset as it is a latched alarm.
8.6 Flow Fail Fault
FLOW FAIL
ZONE 4
Figure 8.6 Faults – Flow Fail
‘Flow Fail’ will be displayed when the differential pressure sensor on the gas analyser PCB is not sensing its’ correct air pressures. The zone location where the flow fail happened is displayed and the System Healthy LED will extinguish. The system will continue to sample
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 56 of 57
normally but if a gas alarm occurs while still in flow fail, the gas alarm will take precedence over the flow fail alarm, displaying the gas alarm and zone location. The system Healthy LED will however, remain extinguished until a reset has been performed.
Rectification: - Check pump operation. - Check solenoid valve operation.
- Check for security and integrity of all TQ 4200 internal pipe work and fittings.
- Disconnect selected ‘sample line’ from inlet to TQ 4200.
If ‘flow fail’ clears after an alarm reset, check sample line for blockages.
Please note that the ‘flow alarm’ requires an alarm reset as it is a latched alarm.
8.7 No Pressure Fault
FAULT
NO PRESSURE
Figure 8.7 Faults – No Pressure
‘No Pressure’ will be displayed when the TQ 4200 has failed its’ 24 hour pressure test. This indicates a leak within the system. Rectification - Check TQ 4200 internal pipe work for integrity and security of all pipe work and fittings.
TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual
Page 57 of 57
8.8 Sensor Drift Fault
FAULT
SENSOR DRIFT
Figure 8.8 Faults – Sensor Drift
‘Sensor Drift’ will be displayed if the sensor’s base zero level has changed more than a pre-defined percentage change when performing an auto-zero.
8.9 Sensor Fault
FAULT
SENSOR FAULT
Figure 8.9 Faults – Sensor Fault
‘Sensor Fault’ will be displayed when the digital output of the sensor falls below a pre-determined value. This value corresponds to a 2mA output.