tp48200a-d15a1 & h15a3 & h15a5 v300r001 user manual 04 (1)

79
TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual Issue 04 Date 2013-07-23 HUAWEI TECHNOLOGIES CO., LTD.

Upload: wilder-j-ja-rz

Post on 08-Feb-2016

569 views

Category:

Documents


34 download

TRANSCRIPT

Page 1: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5 V300R001

User Manual

Issue 04

Date 2013-07-23

HUAWEI TECHNOLOGIES CO., LTD.

Page 2: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

i

Copyright © Huawei Technologies Co., Ltd. 2012. All rights reserved.

No part of this document may be reproduced or transmitted in any form or by any means without prior

written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

All other trademarks and trade names mentioned in this document are the property of their respective

holders.

Notice

The purchased products, services and features are stipulated by the contract made between Huawei and

the customer. All or part of the products, services and features described in this document may not be

within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

information, and recommendations in this document are provided "AS IS" without warranties, guarantees or

representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the

preparation of this document to ensure accuracy of the contents, but all statements, information, and

recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.

Address: Huawei Industrial Base

Bantian, Longgang

Shenzhen 518129

People's Republic of China

Website: http://www.huawei.com

Email: [email protected]

Page 3: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual About This Document

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

ii

About This Document

Purpose

This document describes the TP48200A-D15A1 & H15A3 & H15A5 in terms of overview,

component description, safety precautions, and system maintenance.

Intended Audience

This document is intended for:

Technical engineers

Maintenance engineers

System engineers

Symbol Conventions

The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level or medium level of risk

which, if not avoided, could result in death or serious injury.

Indicates a hazard with a low level of risk which, if not

avoided, could result in minor or moderate injury.

Indicates a potentially hazardous situation that, if not avoided,

could result in equipment damage, data loss, performance

deterioration, or unanticipated results.

Provides a tip that may help you solve a problem or save time.

Provides additional information to emphasize or supplement

important points in the main text.

Page 4: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual About This Document

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

iii

Change History

Changes between document issues are cumulative. The latest document issue contains all the

changes made in earlier issues.

Issue 04 (2013-07-23)

Modified section 6.2 UIM02C.

Issue 03 (2012-12-05)

Optimized the content of the document, including standardizing the terminology and

improving the accuracy of the description..

Issue 02 (2012-11-12)

Port description is modified.

Issue 01 (2011-11-15)

This issue is the first official release.

Page 5: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual Contents

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

iv

Contents

About This Document .................................................................................................................... ii

1 Overview ......................................................................................................................................... 1

1.1 Designation Explanation .................................................................................................................................. 1

1.2 Typical Networking .......................................................................................................................................... 2

1.3 Configuration ................................................................................................................................................... 2

1.4 Features ............................................................................................................................................................ 6

1.5 Working Principles ........................................................................................................................................... 7

2 Component Description ............................................................................................................... 9

2.1 Cabinet ............................................................................................................................................................. 9

2.2 Temperature Control Unit .............................................................................................................................. 10

2.2.1 Direct-Cooling Unit .............................................................................................................................. 10

2.2.2 Heat Exchanger ..................................................................................................................................... 11

2.3 Heater ............................................................................................................................................................. 12

2.4 Power Distribution Unit ................................................................................................................................. 14

2.5 Rectifier .......................................................................................................................................................... 15

2.6 Monitoring Unit ............................................................................................................................................. 16

2.7 Storage Battery (Optional) ............................................................................................................................. 17

3 Safety Precautions ....................................................................................................................... 18

4 Installation and Commissioning.............................................................................................. 22

5 System Maintenance................................................................................................................... 23

5.1 Routine Maintenance...................................................................................................................................... 23

5.2 Troubleshooting .............................................................................................................................................. 24

5.2.1 Troubleshooting Common faults ........................................................................................................... 24

5.2.2 Troubleshooting Components ............................................................................................................... 30

5.3 Component Replacement ............................................................................................................................... 32

6 Monitoring Function .................................................................................................................. 39

6.1 SMU02B ........................................................................................................................................................ 39

6.2 UIM02C ......................................................................................................................................................... 41

6.3 LCD User Interface ........................................................................................................................................ 45

6.4 Web User Interface ......................................................................................................................................... 49

Page 6: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual Contents

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

v

A Appendix ..................................................................................................................................... 61

A.1 Technical Specifications ................................................................................................................................ 61

A.2 LCD Menu..................................................................................................................................................... 64

B Acronyms and Abbreviations .................................................................................................. 72

Page 7: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

1

1 Overview

1.1 Designation Explanation

The TP48200A-D15A1 & H15A3 & H15A5 is an outdoor cabinet-type power system and

supplies power to the -48 V DC telecom equipments. The TP48200A-D15A1 & H15A3 &

H15A5 uses 50 A rectifiers and outputs a maximum of 200 A current.

Figure 1-1 shows the TP48200A-D15A1 designation explanation. Figure 1-2 shows the

TP48200A-H15A3 designation explanation. Figure 1-3 shows the

TP48200A-H15A5designation explanation.

Figure 1-1 TP48200A-D15A1 Designation explanation

Figure 1-2 TP48200A-H15A3 Designation explanation

Page 8: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

2

Figure 1-3 TP48200A-H15A5 Designation explanation

1.2 Typical Networking

The TP48200A-D15A1 & H15A3 & H15A5 power system, AC power supply, ATS, storage

batteries, and related devices constitute the site power solution. Figure 1-4 shows the

application of the TP48200A-D15A1 & H15A3 & H15A5 power system in the typical site

power solution.

Figure 1-4 TP48200A-D15A1 & H15A3 & H15A5 Typical site power solution

1.3 Configuration

The TP48200A-D15A1 & H15A3 & H15A5 power system mainly consists of the cabinet,

temperature Control Unit.rectifier, power distribution unit (PDU), and monitoring unit.

Table 1-1 Configuration

Item Composition AC input mode

TP48200A-D15A1 Cabinet: support

space for 2 groups of

storage batteries and

8 U (355.6 mm or 14

in.) space for

One-phase three-line

(L, N, PE)

Three-phase five-line

(L1, L2, L3, N, PE)

DC

AC

Storage

Batteries

DC Load

AC Load

ATS

D.G

Mains

ACDBTP48200A-D15A1

TP48200A-H15A3

TP48200A-H15A5

Page 9: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

3

Item Composition AC input mode

customer

Direct air cooling

Supports R4850G1or

R4850N1(normal 2

PCS) (1-4 PCS)

SMU02B (1 PCS)

UIM02C (1 PCS)

TP48200A-H15A3 Cabinet: support

space for 2 groups of

storage batteries and

8U (355.6 mm or 14

in.) space for

customer

Heat exchanger

Supports R4850 G1or

R4850N1 (1-4 PCS)

SMU02B (1 PCS)

UIM02C (1 PCS)

One-phase three-line

(L, N, PE)

Three-phase five-line

(L1, L2, L3, N, PE)

TP48200A-H15A5 Cabinet: support

space for 2 groups of

storage batteries and

8U(355.6 mm or 14

in.) space for

customer

Heat exchanger

Supports R4850G1 or

R4850N1 (1-4 PCS)

SMU02B(1 PCS)

UIM02C(1 PCS)

Heater:HAU03A-01

One-phase three-line

(L, N, PE)

Three-phase five-line

(L1, L2, L3, N, PE)

Page 10: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

4

Figure 1-5 TP48200A-D15A1 interior

(1) AC-DC power distribution (2) Door sensor (3) Monitoring unit

(4) Space for rectifiers (5) Space for customer (6) Space for batteries

(7) Direct air cooling (8) Air filter

Page 11: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

5

Figure 1-6 TP48200A-H15A3 interior

(1) AC-DC power distribution (2) Door sensor (3) Monitoring unit

(4) Space for rectifiers (5) Space for customer (6) Space for batteries

(7) Heat exchanger

Page 12: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

6

Figure 1-7 TP48200A-H15A5 interior

(1) AC-DC power distribution (2) Door sensor (3) Monitoring unit

(4) Space for rectifiers (5) Space for customer (6) Space for batteries

(7) Heat exchanger (8) Heater

1.4 Features

All ports in this manual are protected by a security mechanism.

Wide Range of AC Input Voltage

The AC input voltage of the system ranges from 90 V AC to 290 V AC.

Comprehensive management on itself and storage batteries.

The monitoring module is of network design and provides one FE port, one RS485 port.

Supports simple network management protocol (SNMP), control area network (CAN),

and Hypertext Transfer Protocol (HTTPS) and can communicate with NetEco or

third-party element management systems (EMSs). They can also be management

remotely and work in unattended mode.

Support the remote software upgrade.

NOTE

Page 13: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

7

Displays information on the liquid crystal display (LCD) and provides buttons for ease

of operation.

Allows you to query component information recorded on electronic labels over a web

user interface (WebUI).

Support multiple display languages, such as English, Chinese, Turkish, Spanish, and

Portuguese, German.

Rectifiers and the monitoring unit are hot-swappable.

The power factor of rectifiers is high to 0.99.

The power system use R4850G1 rectifiers with a 95% efficiency record.

Heat dissipation of the TP48200A-D15A1 is direct air cooling and the TP48200A-

H15A3 & H15A5 is heat exchanger

1.5 Working Principles

Working principles are described as follows:

The TP48200A-D15A1 & H15A3 & H15A5 is energized by 220 V/380 V three-phase or

220 V single-phase.

The rectifier converts AC power into –48 V DC power.

The direct currents (DCs) generated by rectifiers converge on a bus bar and then divide

into multiple routes to power loads.

The monitoring unit monitors operating parameters in real time, analyzes the operating

status, and generates alarms when necessary.

Figure 1-8 shows the TP48200A-D15A1 & H15A3conceptual diagram. Figure 1-9 shows the

TP48200A-H15A5 conceptual diagram.

Figure 1-8 TP48200A-D15A1 &H15A3 Conceptual diagram

Page 14: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 1 Overview

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

8

Figure 1-9 TP48200A-H15A5 Conceptual diagram

Page 15: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

9

2 Component Description

2.1 Cabinet

The cabinet size (H×W×D) of TP48200A-D15A1 & H15A3 & H15A5 is 1500 mm × 650 mm

× 650 mm (excluding base), base size (H×W×D) is 100 mm × 650 mm × 650 mm. Figure 2-1

shows the TP48200A-D15A1 cabinet. Figure 2-2 shows the TP48200A-H15A3 & H15A5

cabinet.

Figure 2-1 TP48200A-D15A1 Cabinet

Page 16: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

10

Figure 2-2 TP48200A-H15A3 & H15A5 Cabinet

2.2 Temperature Control Unit

2.2.1 Direct-Cooling Unit

The TP48200A-D15A1 adopted the direct air cooling way. The direct-cooling unit extends

the area for exchanging air inside and outside the cabinet, speeds up air circulation, and

reduces the operating temperature in the cabinet.

Page 17: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

11

Figure 2-3 Air flows

Table 2-1 describes the features of the temperature control system.

Table 2-1 Features of the temperature control systems in the TP48200A-D15A1

Item Description

Temperature Control System Direct air cooling unit

Heat Dissipation Capability 140 W/K

2.2.2 Heat Exchanger

The temperature control system is a heat exchanger. In addition, it helps decrease the power

consumption by adjusting the speed of the fan in intelligent mode.

Page 18: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

12

Figure 2-4 Temperature Control Unit

Table 2-2 describes the features of the temperature control system.

Table 2-2 Features of the temperature control systems in the TP48200A-H15A3 & H15A5

Item Description

Temperature Control System Heat exchange unit

Heat Dissipation Capability 85 W/K

2.3 Heater

A heater ensures a proper operating temperature for the equipment inside the TP48200A-

H15A5.

Page 19: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

13

Figure 2-5 HAU03A-01

(1) Alternating current (AC) input port (2) Indicator (3) Alarm port

(4) Control port

Table 2-3 Indicator description

Silk Screen

Color Status Meaning

RUN Green Blinking at 0.5 Hz The heater is working and communicating with

the element management system (EMS) properly.

Blinking at 4 Hz The heater fails to communicate with the EMS

for at least 1 minute.

Steady on The heater is powered on and takes a self-test.

Off The heater is not powered on.

ALM Red Off No alarm is generated.

Steady on An alarm is generated and the heater needs to be

replaced.

Blinking at 0.5 Hz An alarm is generated. However, whether the

heater needs to be replaced is not determined

because the alarm may be generated because of

the failure of communication, a board, or a port.

Table 2-4 Eater technical specifications

Item Specifications

Operating voltage 90 -290 V AC (110 V AC/220 V AC)

Voltage frequency 45-65 Hz (rated frequency: 50/60 Hz)

Operating temperature -40°C to +65°C (-40°F to +149°F)

Heater startup temperature

and heater stop

temperature

The heater starts when the temperature is below or equal to

-5°C (+23°F) and stops when the temperature is above or

equal to 15°C (59°F).

Operating humidity 5%-95% RH

Heating power 400 W ≤ P ≤ 600 W (90 V AC to 132 V AC)

500 W ≤ P ≤ 750 W (176 V AC to 290 V AC)

Page 20: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

14

2.4 Power Distribution Unit

The TP48200A-D15A1 & H15A3 & H15A5 power distribution unit distributes AC and DC

power for the power system.

For details about the specifications of the power distribution unit, see Table 2-5

Figure 2-6 Power distribution unit

Figure 2-7 A C output socket

Page 21: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

15

Table 2-5 Power distribution specifications

Item Specifications

AC power

distribution

Main AC input 63 A three-pole MCB x 1; level-C surge protection

AC output or

Heater

16 A one-pole MCB x 1

16 A maintenance socket MCB x 1

DC power

distribution

Load shutdown BLVD: 16 A MCB x 2;

LLVD: 63 A MCB x 2; 32 A MCB x 2

Battery branch 125 A one-pole MCB x 2

2.5 Rectifier

Figure 2-8 shows the rectifier panel of R4850G1/R4850N1.

Figure 2-8 Rectifier panel of R4850G1/R4850N1

(1) Run indicator (2) Protection indicator (3) Fault indicator

Table 2-6 R4850G1/R4850N1 Indicator description of rectifier

Indicator Color Status Description Measure

Run

indicator

Green Steady on The rectifier output is

normal.

The rectifier runs

properly, and no

measure is required.

Off The rectifier has no output. Replace the rectifier if

the AC input is normal.

Alarm Yellow Off No alarm is generated. No measure is required.

Page 22: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

16

Indicator Color Status Description Measure

indicator

Steady on The rectifier generates a

prewarning for power

limiting due to

overtemperature.The

rectifier generates an

alarm for shutdown due to

ambient overtemperature

or undertemperature

protection.

Check that the air vent is

not blocked and the

ambient temperature is

within a normal range.

The rectifier generates an

alarm due to AC input

overvoltage or

undervoltage protection.

Check that the electrical

grid voltage is within a

normal range.

The rectifier is hibernated. No measure is required.

Fault

indicator

Red Off The rectifier is not faulty. No measure is required.

Steady on The rectifier is locked due

to output overvoltage.

Pull out the rectifier and

the reinsert it after 1

minute.

There is no output because

the rectifier is faulty.

Replace the rectifier.

Blinking

at 4 Hz

The rectifier is loading an

application program.

The rectifier

automatically recovers

after loading, and no

measure is required.

2.6 Monitoring Unit

Figure 2-9 shows the monitoring unit.

Figure 2-9 Monitoring Unit

(1) Battery switch(behind the panel) (2) SMU02B (3) UIM02C

Battery switch To make the system run properly, flip the switch to Normal.

To power on the battery forcibly, flip the switch to the BAT On position, flip the switch

to Normal after operation.

Page 23: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 2 Component Description

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

17

SMU02B

See 6.1 SMU02B.

UIM02C

See 6.2 UIM02C.

2.7 Storage Battery (Optional)

Storage batteries store electrical energy and supply power to the loads when the power supply

of the D.G. and mains is insufficient.

TP48200A-D15A1 & H15A3 & H15A5 supports 2 groups 150 Ah (12 V Monobloc) VRLA

batteries.

Page 24: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 3 Safety Precautions

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

18

3 Safety Precautions

Overview

The safety precautions described in this section are also applicable to other Huawei

equipment.

To minimize the risk of personal injury and damage to equipment, read and follow all the

precautions in this document before performing any installation or maintenance. The "NOTE",

"CAUTION", and "WARNING" marks in other documents do not represent all the safety

instructions. They are only supplements to the safety instructions. Only trained and qualified

personnel are allowed to install, operate, and maintain Huawei equipment, and they must

understand basic safety precautions to avoid hazards.

To ensure safety of humans and the equipment, pay attention to the safety symbols on the

equipment and all the safety instructions in this document. Huawei will not be liable for any

consequence caused by the violation of the safety operation regulations and design,

production, and usage standards.

Local Safety Regulations

When operating Huawei equipment, you must follow the local laws and regulations. The

safety instructions in this document are only supplements to the local laws and regulations.

Grounding Requirements

Equipment to be grounded must meet the following requirements:

When installing the device, always make the ground connection first and disconnect it at

the end.

Do not damage the ground conductor.

Do not operate the device in the absence of a properly installed ground conductor.

Conduct the electrical inspection carefully.

The device (or system) must be connected permanently to the protection ground before

an operation. Before operating the device, check the electrical connection of the device to ensure that it is securely grounded.

Page 25: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 3 Safety Precautions

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

19

Human Safety Do not operate the device or cables during lightning strikes.

To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to

telecommunication network voltage (TNV) circuits.

Before operating the device, wear electrostatic discharge (ESD) clothes, ESD gloves, and

an ESD wrist strap. Do not wear jewelry or watches when you operate the device.

In the case of fire, immediately leave the building or the equipment room, and turn on

the fire alarm bell or make an emergency call. Do not enter a building that is on fire.

Equipment Safety The device must be fixed securely on the floor or to other immovable objects such as

walls and mounting racks before operation.

Do not block the ventilation while the device is operating.

Tighten the thumbscrews by using a tool after initial installation and subsequent access

to the panel.

After the installation, remove packing materials from the equipment area.

Electrical Safety

High Voltage

The high voltage power supply provides power for the device operation. Direct or indirect

contact (through damp objects) with high voltage and alternating current (AC) mains

supply may result in serious injury.

Non-standard and incorrect high voltage operations may result in fire and electric shock.

The personnel who install the AC facility must be qualified to perform high voltage and

AC operations.

You must abide by the local rules and regulations when bridging and wiring AC cables.

During the installation of the AC power supply facility, follow the local safety

regulations.

Dedicated tools must be used during high voltage and AC operations. Avoid using

ordinary tools.

When the operation is performed in a damp environment, ensure that the device is dry.

When water is found in the rack or the rack is damp, switch off the power supply

immediately.

High Electrical Leakage Ground the device before powering it on. Otherwise, personal injury or device damage

may be caused by high leakage current.

If a "high electrical leakage" tag is present on the power terminal of the device, you must

ground the device before powering it on.

Page 26: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 3 Safety Precautions

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

20

Power Cable Do not install or remove power cables when the device is on. Transient contact between

the core of the power cable and the conductor may generate electric arcs or sparks, which

may cause fire or hurt human eyes.

Before installing or removing the power cable, turn off the power switch.

Before connecting a power cable, check that the label on the power cable is correct.

Power Output

All output circuits are evaluated as SELV circuits.

Outputs are energy hazards (> 240 VA).

Fuse

To ensure that the system runs safely, if a fuse is to be replaced, the new fuse must be of the

same type and specifications.

Electrostatic Discharge

The static electricity generated by human bodies may damage the electrostatic-sensitive

components on boards, for example, the large-scale integrated (LSI) circuits.

Human body movement, friction between human bodies and clothes, friction between

shoes and floors, or handling of plastic articles causes static electromagnetic fields on

human bodies. These static electromagnetic fields cannot be eliminated until the static is

discharged.

To prevent electrostatic-sensitive components from being damaged by the static on

human bodies, you must wear a well-grounded ESD wrist strap when touching the

device or handling boards or application-specific integrated circuits (ASICs).

Figure 3-1 shows how to wear an ESD wrist strap.

WARNING

Page 27: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 3 Safety Precautions

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

21

Figure 3-1 Wearing an ESD wrist strap

Page 28: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 4 Installation and Commissioning

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

22

4 Installation and Commissioning

The detailed installation refers to the Quick Installation Guide.

Page 29: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

23

5 System Maintenance

5.1 Routine Maintenance

Maintain TP48200A-D15A1 & H15A3 & H15A5 periodically based on site requirements.

The recommended maintenance interval is 6 months. If faults are identified, clear them

immediately.

Table 5-1 Routine maintenance checklist

Maintenance Item

Maintenance Task

Check Whether

Check Method

Repair When Measures

Door lock Whether the

door lock is

damaged or

rusted

Observe

and open

the lock

The door lock is

rusty or cannot be

used

Replace the lock

Fan Whether the

fan is covered

by dust

Visual

inspection

Dust accumulates

on the fan

Clear the dust on

the fan

Whether the

fan surface is

damaged and

whether the

rotational

speed, noise,

and vibration is

in the normal

range

Visual

inspection

The fan

rotates unstably or

slowly

The fan is

damaged

Replace the fan

Heat

exchanger core

Whether dust

accumulates on

the core of heat

exchanger

Visual

inspection

Dust accumulates

on the core of heat

exchanger

Clear the dust on

the Heat exchanger

core

Direct air

cooling

Whether dust

accumulates on

the air filter

Visual

inspection

Dust accumulates

on the air filter

Clear the dust on

the air filter

Page 30: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

24

Maintenance Item

Maintenance Task

Check Whether

Check Method

Repair When Measures

Electricity The voltage

output is

normal.

Using a

multimeter

The BLVD or

LLVD voltage

exceeds the

threshold.

For details, see

section 5.2

Troubleshooting

Common Faults.

Preventive

maintenance

inspection

(PMI)

Indicators are

normal.

Observing

indicators

Alarms are

generated.

Cabinet

appearance

The coating on

the cabinet are

flaking off or

scratches

occur.

Observing

the cabinet

The cabinet

surface is damaged

or distorted.

Repaint and repair

the cabinet.

5.2 Troubleshooting

5.2.1 Troubleshooting Common faults

Table 5-2 Common faults and troubleshooting methods

Fault Type Fault Analysis Handling Method

AC power off AC input cable

fault

Grid fault or

D.G. fault

1. Check whether the AC input cable is

correctly and securely connected. If the

cable is not correctly and securely

connected, reconnect the cable.

2. Check whether the AC input is available.

If the AC input is not available, check

whether faults such as short-circuit or

open circuit exist on the AC input loop. If

the AC input loop is proper, contact the

mains supplier for troubleshooting. If the

AC input is from the D.G., check the

D.G. by referring to the Diesel Generator

User Manual.

3. If the power-off duration is short, supply

DC power using batteries. If the

power-off duration is long, start other

systems for power supply.

Page 31: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

25

Fault Type Fault Analysis Handling Method

AC overvoltage and

undervoltage

Improper setting

of monitoring

unit AC

undervoltage or

overvoltage

threshold

Mains supply

grid fault or

D.G. fault

1. Check whether the AC undervoltage or

overvoltage alarm threshold is properly

set. If the threshold is excessively high or

low, lower or raise the threshold

according to the actual conditions.

2. If the AC input is the mains supply,

contact the mains supplier for

troubleshooting. If the AC input is from

the D.G., check the D.G. by referring to

the Diesel Generator User Manual.

DC overvoltage and

undervoltage

Improper setting

of monitoring

unit DC

undervoltage or

overvoltage

threshold

Rectifier module

fault

1. Check the alarm thresholds of the DC

overvoltage and undervoltage. If the

thresholds are not proper, reset the

thresholds according to the actual

conditions.

2. When the storage battery is powering the

load, remove all the rectifiers, and then

insert each rectifier one by one. If an

overvoltage alarm is generated after a

rectifier is inserted, the voltage of the

rectifier exceeds the upper threshold.

Then replace the rectifier.

Charging

overcurrent

Communication

failure between

rectifier and

monitoring unit

Battery loop

fault

1. Check whether the rectifier module is in

position or whether contact is proper. If

the monitoring unit is inserted in an

incorrect position, insert it correctly. If

the contact is not proper, remove and

then insert it.

2. Check whether the battery loop is

short-circuited or has other faults.

3. Check whether the batteries are faulty. If

the batteries are faulty, replace them.

Page 32: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

26

Fault Type Fault Analysis Handling Method

Load shutdown Load circuit

breaker set to

OFF

Contactor fault

Excessively high

setting of

monitoring unit

load shutdown

voltage

Output

undervoltage due

to greater load

power than

configured

rectifier module

power

1. Check whether the load detection cable is

securely connected. If the cable is not

connected securely, connect it correctly.

2. Check whether the load circuit breaker is

turned off. Checking method: Check the

position of the handle on the circuit

breaker. If the circuit breaker is turned

off, turn on the circuit breaker.

3. Check whether the contactor is faulty and

whether it can be connected and

disconnected. If the contactor is faulty,

replace it.

4. Check whether the monitoring unit load

shutdown voltage is set excessively high.

If it is set excessively high, set it

according to the actual situation.

5. Check whether the load power is higher

than the configured rectifier module

power. If the load power is higher than

the configured rectifier module power,

add a rectifier module. If the load power

exceeds the maximum supported power

of the system, lower the load power.

Battery shutdown Improper setting

of monitoring

unit battery

parameters

Contactor fault

1. Check whether the mains supply is off or

the voltage of storage batteries is lower

than the “Battery Shutdown Voltage”.

2. Check whether the battery shutdown

permission is set.

3. Check whether the battery cables or the

connectors are faulty. If the cables or

connectors are faulty, replace them.

4. Check whether the contactor is faulty and

whether it can be connected and

disconnected. If the contactor is faulty,

replace it.

Battery loop failure Battery loop

fault

Contactor fault

Battery fault

1. Check whether cables of the battery loop

or connectors are faulty. If the cables or

connectors are faulty, replace them.

2. Check whether the contactor is faulty and

whether it can be connected and

disconnected. If the contactor is faulty,

replace it.

3. Check whether batteries are faulty. If the

batteries are faulty, replace them.

Page 33: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

27

Fault Type Fault Analysis Handling Method

Ambient

overtemperature or

undertemperature

alarm

(The alarm is

generated only when

the temperature

sensor is installed.)

Improper setting

of monitoring

unit temperature

alarm parameters

Overtemperature

or

undertemperatur-

e in the shelter

with the

temperature

sensor

Temperature

sensor fault

1. Check whether monitoring unit

temperature alarm thresholds are set

according to local conditions. If the

thresholds are not proper, set the

thresholds accordingly.

2. Check whether the temperature control

device in the shelter is faulty. If the

temperature control device is faulty,

repair it. The alarm is automatically

cleared when the temperature in the

shelter is adjusted to the proper range.

3. Check whether the temperature sensor is

faulty. If the temperature sensor is faulty,

replace it.

Ambient

overhumidity or

underhumidity

alarm

(The alarm is

generated only when

the humidity sensor

is installed.)

Improper setting

of monitoring

unit humidity

alarm parameters

Overhumidity or

underhumidity in

the shelter with

the humidity

sensor

Humidity sensor

fault

1. Check whether monitoring unit humidity

alarm thresholds are set according to

local conditions. If the thresholds are not

proper, set the thresholds accordingly.

2. Check whether the floor of the shelter is

wet. If the floor is wet, use a cotton cloth

to wipe the floor and ensure it is dry or

use other dehumidifiers.

3. If the alarm persists when the humidity is

proper, check whether the humidity

sensor is faulty.

Battery

overtemperature or

undertemperature

alarm

Battery cabin

overtemperature

Improper setting

of monitoring

unit battery

temperature

alarm parameters

Battery charging

overcurrent

Temperature

sensor fault

1. Check whether monitoring unit battery

temperature alarm thresholds are properly

set. If the thresholds are not proper, set

the thresholds accordingly.

2. Check whether the temperature in the

battery room is excessively high. If the

temperature is excessively high, the

alarm can be cleared when the

temperature is lowered.

3. Check the charging current. If the current

is excessively strong, switch equalized

charging to float charging and check

whether the charging current is

weakened. If the charging current is still

excessively strong, adjust the current

suppression to reduce the charging

current. If the preceding steps do not

work, replace the faulty battery.

4. Check whether the temperature sensor is

faulty. If the temperature sensor is faulty,

replace it.

Page 34: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

28

Fault Type Fault Analysis Handling Method

Door alarm

(The alarm is

generated only when

the door status

sensor is installed.)

Opened cabinet

door

Door status

sensor fault

1. The alarm is cleared after the cabinet

door is closed.

2. If the alarm persists after the cabinet door

is closed, check whether the door status

sensor is faulty.

Water immersion

alarm

(The alarm is

generated only when

the water sensor is

installed.)

Shelter water

accumulation

Water sensor

fault

1. Check whether the floor of the shelter is

wet. If the floor is wet, use a cotton cloth

to wipe the floor and ensure it is dry or

use other dehumidifiers.

2. If the alarm persists after the water is

drained, check whether the water sensor

is faulty.

Smoke alarm

(The alarm is

generated only when

the smoke sensor is

installed.)

Smoke in the

shelter

Smoke sensor

fault

1. Check whether the smoke caused by fire

pervades in the shelter. If there is fire,

extinguish the fire and ventilate the

shelter.

2. If the alarm persists when there is no

smoke, check whether the smoke sensor

is faulty.

Rectifier module

fault

Poor contact of

the rectifier

module

Rectifier module

fault

1. Check whether the ALM indicator on the

panel of the rectifier module is on. If the

ALM indicator is on, remove the rectifier

module and insert the rectifier module

after the indicator is off.

2. If the alarm persists, replace the rectifier

module.

Rectifier module

shutdown

Rectifier module

protection

Input

overvoltage or

undervoltage of

the rectifier

module

Rectifier module

fault

1. Check whether the mains voltage is over

the AC overvoltage alarm threshold (300

V) of the rectifier module or below the

AC undervoltage alarm threshold (85 V).

For the power supply network with

long-time overvoltage or undervoltage,

negotiate with the maintenance personnel

of the electricity department to improve

the power supply network.

2. If the alarm persists when the input

voltage of the rectifier module is proper,

check whether the rectifier module is

proper. If the rectifier module is faulty,

replace it.

Page 35: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

29

Fault Type Fault Analysis Handling Method

Communication

Failure between

rectifier and

monitoring unit

Poor contact of

the rectifier

module

Rectifier module

out of position

Rectifier module

fault

1. Check whether the rectifier module is in

position or whether contact is proper. If

the rectifier module is inserted in an

incorrect position, insert it correctly. If

the contact is not proper, remove and

then insert it.

2. If the alarm persists, replace the rectifier

module.

Disconnection of the

load fuse

Load circuit

breaker set to

OFF

1. Check whether the load circuit breaker is

set to OFF. If it is set to OFF, set it to

ON.

2. If the circuit breaker is automatically set

to OFF after you set it to ON, check

whether the load branch is overloaded or

short-circuited. Check and rectify the

load loop fault.

AC surge protector

fault

AC surge

protector fault

User interface

module fault

1. Check the observation window on the AC

surge protector. If the color of the

window is red, replace the surge

protector.

2. Check whether the fault detection cables

of the AC surge protector are correctly

connected or whether the cables are in

good condition. If the cables are not in

good condition, replace and reconnect

them.

3. If the cable connection is proper, it

indicates that the alarm loop is faulty.

Replace the user interface module.

DC surge protector

fault

DC surge

protector fault

1. Check whether the fault detection cables

of the DC surge protector are correctly

and securely connected. If the cables are

not correctly and securely connected,

reconnect them.

2. If the cables are correctly connected,

replace the DC surge protector.

Page 36: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

30

If you rectify the corresponding faults, the alarms in the monitoring unit are automatically cleared

and saved in history alarm information.

After the monitoring unit is replaced, set the parameters again.

The monitoring unit and rectifier module are hot-swappable.

5.2.2 Troubleshooting Components

AC SPD

Observe the indication window on the surge protection module. If the indication window

turns red, the surge protection module is damaged. In this case, replace the surge protection

module. If the indication window remains green, the SPD runs properly.

Circuit Breaker

The circuit breaker fault is usually caused by overcurrent or short circuits. To check whether a

circuit break is faulty, perform the following steps:

Step 1 Switch the circuit breaker to the ON position.

Step 2 Measure the resistance at the two ends of the circuit breaker using a multimeter. If the

resistance is infinity, the circuit breaker is damaged.

----End

DC Contactor

Table 5-3 DC contactor description

Position Type Check Method

Load

Disconnected

Branch

Closed type, (when the

contactor without electricity,

the state is closed)

When there is no voltage at the control

poles of the contactor, check whether the

input and output poles of the contactor

are proper by using the multimeter. For

example, the contactor of the power

system is closed type contactor as shown

in Figure 5-1. When there is no voltage

at control poles 1 and 2 but measuring

shows that the input and output poles 3

and 4 are disconnected, it indicates that

the contactor is faulty.

When there is voltage at the control

poles of the contactor, check whether the

input and output poles of the contactor

are proper by using the multimeter. For

example, the contactor of the power

system is a closed type contactor as

shown in Figure 5-1. When there is

voltage at control poles 1 and 2 but

measuring shows that the input and

output poles 3 and 4 are connected, it

indicates that the contactor is faulty.

Page 37: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

31

Position Type Check Method

Battery Fuse

or battery

circuit breaker

Branch

Open type, (when the

contactor without electricity,

the state is open)

When there is no voltage at the control

poles of the contactor, check whether the

input and output poles of the contactor

are proper by using the multimeter. For

example, the contactor of the power

system is an open type contactor as

shown in Figure 5-1. When there is no

voltage at control poles 1 and 2 but

measuring shows that the input and

output poles 3 and 4 are connected, it

indicates that the contactor is faulty.

When there is voltage at the control

poles of the contactor, check whether the

input and output poles of the contactor

are proper by using the multimeter. For

example, the contactor of the power

system is an open type contactor as

shown in Figure 5-1. When there is

voltage at control poles 1 and 2 but

measuring shows that the input and

output poles 3 and 4 are disconnected, it

indicates that the contactor is faulty.

Figure 5-1 DC contactor

Rectifier

The rectifier is damaged if either of the following conditions is not met:

The Run indicator of the rectifier is steady on and the Fault indicator is off when the

rectifier does not communicate with the monitoring unit and the input AC voltage is

around 220 V. The rectifier outputs power normally.

The monitoring unit can perform control on the charge mode (boost charge or floating

charge) and current for the rectifier when the rectifier communications cable is properly

connected and the rectifier communicates with the monitoring unit normally.

Page 38: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

32

Monitoring Unit

If any of the following occurs, the monitoring unit is faulty:

The monitoring unit breaks down or fails to start, or its LCD or keyboard fails.

The monitoring unit does not generate an alarm when a fault occurs in the system.

The monitoring unit generates an alarm (false alarm) when the system runs properly.

Communication between the monitoring unit and all subordinate equipment is

interrupted.

The monitoring unit fails to control or monitor all the modules when these modules run

properly and communications cables are connected properly.

The monitoring unit fails to monitor or control AC or DC distribution when AC/DC

power is distributed normally and communications cables are connected properly.

Parameters cannot be set or operating information cannot be viewed on the monitoring

unit.

5.3 Component Replacement

Describe how to replace the main components of the power system.

Load disconnection is prohibited when you replace the main components. Take measures to ensure

that important loads are always connected during the replacement. For example, keep the circuit

breaker of important loads at the ON position and ensure that either storage batteries or the AC input

is connected.

If a load must be disconnected, ask for the customer's prior permission.

The rectifier and the monitoring unit are hot-swappable.

Replacing the rectifier

To replace the rectifier, perform the following steps:

Step 1 Loosen the screws on the rectifier panel using a flat-head screwdriver.

Step 2 Pull the handle of the rectifier outwards, and then remove the rectifier from the plug-in

subrack, as shown in Figure 5-2.

Step 3 Insert the rectifier into the corresponding slot in the plug-in subrack. Then, loosen the screws

on the handle and pull out the handle.

Step 4 Slide the rectifier into the plug-in subrack slowly along the guide rails. Then, lock the handle.

Step 5 Tighten the screws on the handle, as shown in Figure 5-3.

----End

Page 39: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

33

Figure 5-2 Removing the old rectifier

Figure 5-3 Installing the new rectifier

Replacing the Door status sensor

To replace the door status sensor, perform the following steps:

Step 1 Open the front door and remove the case of the door status sensor, as shown in Figure 5-4.

Page 40: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

34

Figure 5-4 Removing the case of the door status sensor

Step 2 Record the connections of the alarm cables and then disconnect them.

Step 3 Loosen the screws on the door status sensor and then remove the sensor.

Step 4 Install a new door status sensor in position and tighten the screws.

Step 5 Install the alarm cables of the new door status sensor according to the recorded connections,

and then install the case.

----End

Replacing the monitoring unit

To replace the monitoring unit, perform the following steps:

Step 1 Push the locking latch left.

Step 2 Remove the old monitoring unit.

Step 3 Insert a new monitoring unit.

Step 4 Push the locking latch right.

Step 5 Set parameters on the monitoring unit panel.

----End

Page 41: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

35

Figure 5-5 Removing the old monitoring unit

Figure 5-6 Installing the new monitoring unit

Replacing the AC SPD

To replace the AC SPD, perform the following steps:

Step 1 Remove the faulty SPD.

Step 2 Insert the new SPD.

----End

Figure 5-7 Replacing the AC SPD of TP48200A-D15A1 & H15A3 & H15A5

Replacing Circuit breakers

To replace a circuit breaker, perform the following steps:

Step 1 Disconnect the power supply of a circuit breaker. For example, disconnect the AC input and

set the circuit breaker to OFF before replacing the input circuit breaker.

Step 2 Remove the cables or copper bars connected to the circuit breaker using a Phillips screwdriver,

and then wrap the cables or copper bars using black PVC insulation tape to avoid hazards.

Step 3 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver. Then,

remove the circuit breaker, as shown in Figure 5-8.

Page 42: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

36

Step 4 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver again

to install the new circuit breaker in the correct position. Then, push the contact plate upwards

using the screwdriver.

Step 5 Install the cables or copper bars to the circuit breaker using a Phillips screwdriver in the same

way.

Step 6 Set the circuit breaker to ON and connect power supply of this circuit breaker, as shown in

Figure 5-9.

----End

Figure 5-8 Removing the circuit breaker

Figure 5-9 Installing the circuit breaker

Replacing FansTo replace a fan, perform the following steps:

Step 1 Remove the UIM02C from the subrack, and disconnect the power cable. Figure 5-10 shows

how to disconnect the power cable from the heat exchanger.

Figure 5-10 Disconnect the power cable

Page 43: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

37

Step 2 Record the position where the cable connects to the fan, and then disconnect the cable.

Step 3 Remove the cover. If there is no cover, go to the next step. Figure 5-11 shows how to remove

the cover from the heat exchanger.

Figure 5-11 Remove the cover

Step 4 Remove the four screws from the fan, and remove the fan. Figure 5-12 shows how to remove

the fan screws from the heat exchanger.

Figure 5-12 Remove the fan

Step 5 Install a new fan.

Step 6 Reconnect the cable to the fan.

Step 7 Tighten the screws to secure the fan.

Step 8 Reinstall the cover.

Page 44: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual 5 System Maintenance

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

38

Step 9 Connect the power cable to the UIM02C and secure the UIM02C to the subrack

----End

Page 45: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

39

6 Monitoring Function

6.1 SMU02B

Panel

Figure 6-1 shows the SMU02B panel.

Figure 6-1 Panel

(1) Running status indicator (2) Minor alarm indicator (3) Major alarm indicator

(4) Liquid crystal display

(LCD)

(5) Locking latch (6) Four buttons

(7) USB (Reserved) (8) RS485/RS232 (9) FE

Indicators

Table 6-1 describes the SMU02B indicators.

Page 46: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

40

Table 6-1 Indicator description

Indicator Color Status Description

Running

status

Green Off The SMU02B is faulty or has no DC input.

Blinking at

0.5 Hz

The SMU02B runs properly and

communicates with the host properly.

Blinking at 4

Hz

The SMU02B runs properly but does not

communicate with the host properly.

Minor alarm

indicator

Yellow Off No minor and warning alarm

Steady on A minor or warning alarm is generated

Major alarm

indicator

Red Off No critical and major alarm

Steady on A critical or major alarm is generated

Buttons

Table 6-2 describes the buttons.

Table 6-2 Button description

Button Description

▲ or ▼ Allows you to view and set menu items.

Returns to the previous menu without saving the current menu settings.

Enters the main menu from the standby screen, enters a submenu from

the main menu, or saves menu settings.

NOTE:

After a menu is displayed, the standby screen is displayed and the LCD screen becomes dark if you

do not press any button within 5 minutes.

You need to log in again if you do not press any button with 8 minutes.

The preset username is admin and the preset password is 001

Communications Ports

The SMU02B communicates with the host over communications ports.

Table 6-3 Communications port description

Communications Ports Communications Parameter Protocol Compliance

FE Auto-adaptation TCP/IP, HTTPS and

SNMP

RS485 Baud rate: 9600 bit/s or 19200

bit/s

-

RS232 - YD/T 1363.2

Page 47: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

41

Figure 6-2 RJ45 pin definition

Table 6-4 FE pin definition

Pin Signal Description

1 TX+ FE transmit

2 TX-

3 RX+ FE receive

6 RX-

Table 6-5 RS485/RS232 pin definition

Pin Signal Description

1 TX+ RS485 transmit

2 TX-

4 RX+ RS485 receive

5 RX-

3 RX232 RS232 receive

7 TX232 RS232 transmit

6 PGND Ground

8 PGND Ground

6.2 UIM02C

The user interface module (UIM02C) supports eight dry contact outputs, nine Boolean value

inputs (including general DI1-6, smoke, water, door status), three analog signals inputs

(ambient temperature, humidity, and battery temperature).

Page 48: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

42

Panel

Figure 6-3 Appearance UIM02C Panel

Ports

Default mode of the dry contact output ports can be modified as required. See Setting Status

of the DO.

Table 6-6 Description of ports on the UIM02C

Port Type Silkscreen Description

Sensor ports TEM_HUM Temperature and humidity sensor

WATER Water sensor

TEMP1 Connected to environment temperature

sensor and used for fan speed adjustment

TEMP2 Reserved

GATE Door status sensor

SMOKE Smoke sensor

BTEMP Battery temperature sensor

Boolean value

input ports

DIN1 Boolean value input 1

DIN2 Boolean value input 2

DIN3 Boolean value input 3

DIN4 Boolean value input 4

DIN5 TP48200A-H15A5: Heater faults alarm

TP48200A-D15A1 & H15A3: Boolean

value input 5

DIN6 Boolean value input 6

Dry contact

output ports

ALM1 AC power failure alarm

Default mode (Close: alarm; Open:

normal) can be modified as required.

Page 49: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

43

Port Type Silkscreen Description

ALM2 DC undervoltage alarm or DC overvoltage

alarm

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM3 Rectifier faults alarm, rectifier protect

alarm, or communication faults alarm

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM4 SPD failure alarm

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM5 Fuse burn-out alarm

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM6 Battery temperature alarms

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM7 Door alarms

Default mode (Close: alarm; Open:

normal) can be modified as required.

ALM8 TCU alarms

Default mode (Close: alarm; Open:

normal) can be modified as required.

Communication

Port

COM RS485

Page 50: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

44

Pin Definition

Figure 6-4 Pins of sensor ports

Table 6-7 Pin Definition

Silk Screen Pin Pin definition

WATER 1 12 V

2 WATER

3 GND

4 -

TEMHUM 1 12 V

2 ENV_TEMP

3 12 V

4 ENV_HUM

TEMP1 1 TEMP1

2 GND

TEMP2 1 TEMP2

2 GND

GATE 1 DIN7+

2 JTD7

SMOKE 1 12 V

2 Smoke

BTEMP 1 Btemp1

Page 51: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

45

Silk Screen Pin Pin definition

2 12 V

6.3 LCD User Interface

Symbol Conventions

Table 6-8 Symbol conventions

Symbol Description

Press one time Enter button.

Press one time Down button.

Press one time Cancel button.

Press one time Up button.

Press more than one times Down button.

Press one time Enter button and more than one times Down button.

Picture with black border shows the path or view parameter

Picture with red border shows the variable parameter

Selecting a Display Language

After the SMU is powered on, the screen for selecting a display language is displayed. You

can select Chinese, English or other language by pressing ▲ or ▼ and enter the standby

screen by pressing Enter, as shown in Figure 6-5.

Enter

Down

Cancel

Up

Down

Enter Down

Page 52: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

46

Figure 6-5 Selecting Language

Querying Active Alarms

This section describes how to query active alarms on the LCD, as shown in Figure 6-6. The

parameter values in Figure 6-6 are for reference only.

Figure 6-6 Querying active alarms

110215 indicates February 15, 2011. The alarm severity and date are displayed alternatively.

Setting Parameters Quickly

This section describes how to quickly set the number of battery strings and rated battery

capacity on the LCD, as shown in Figure 6-7. The parameter values in Figure 6-7 are for

reference only.

Figure 6-7 Setting parameters quickly

To open the Settings page, Quick Setting page, and Control page, you need to enter a password. The

preset user name is admin and the preset password is 001. You can add or delete users, and change the

user name and password.

NOTE

NOTE

Page 53: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

47

Setting Status of the DO

This section describes how to set the DO status when there is an alarm on the LCD, as shown

in Figure 6-8. The parameter values in Figure 6-8 are for reference only.

For example, “DO 1 Alarm Act: Open” means that if an alarm is generated which related to Relay 1 (DO

1), the status of DO 1 port will be Open.

To relate an alarm to Relay 1 (DO 1), refer to Table A-2.

Figure 6-8 Setting Parameters of the DO

Setting Parameters of Alarm

This section describes how to set the alarm enable/disable, alarm level, related relay and

alarm delay time, as shown in Figure 6-9. The parameter values in Figure 6-9 are for

reference only.

NOTE

Page 54: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

48

Figure 6-9 Setting Parameters of the Alarm

LCD Menu Hierarchy

Figure 6-10 shows the LCD main menu.

Page 55: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

49

Figure 6-10 LCD Menu hierarchy

6.4 Web User Interface

To ensure the security of data transmission, the NetEco transmits data after encrypting it over SSL.

You can perform the following operations over the WebUI:

View the system status, including the PSU status, battery status, and active alarm

information.

Configure system parameters.

Configure network parameters, including IP addresses, host communications addresses

and baud rates under master/slave protocol.

Control the system, such as choosing battery boost or floating charge and resetting PSUs.

NOTE

Page 56: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

50

Add or delete users, and change user names and passwords.

Upgrade software online.

Query and export historical logs and alarms.

Configure alarm parameters, alarm severities, and the relationship between alarms and

dry contacts.

Set the system date and time, site and storage battery type, save, download, and upload

configuration files.

Query electronic label information.

Configure site information including date and site name and deal with configuration files

and so on.

Set the IP address, gateway, and subnet mask of the SMU on the LCD before logging into the

WebUI.

Login Web Page

Step 1 Connect an SMU to an Ethernet.

Step 2 Set the IP address, subnet mask, and gateway on the LCD based on those assigned by the

customer.

Step 3 Enter the IP address of the SMU in the Internet Explorer address box and press Enter.

Step 4 On the login page shown in Figure 6-11 set User Name to admin and Password to 001, and

then press Login.

----End

Figure 6-11 Login page

Querying System Status

To view the information about the site, active alarms, PSUs, batteries, power distribution,

TCU and fan, click System Status, as shown in Figure 6-12.

Page 57: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

51

Figure 6-12 System Status

Configuring System Parameters

You can configure the site, PSUs, and batteries in the System Configuration pane shown in

Figure 6-13.

Figure 6-13 System Configuration

Page 58: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

52

Configuring Network Parameters

In the Network Configuration pane, you can set the IP address, subnet mask, and default

gateway under System IP, the host communications address and baud rate under Master

Slave Protocol, the SNMP version under SNMP, the trap IP address under SNMP Trap, and

the server IP addresses and port number under NetEco.

Figure 6-14 shows the Network Configuration pane.

Figure 6-14 Network Configuration

Setting Control Parameters

You can set control parameters for the site, PSUs, storage batteries, and PDU in the Control

pane shown in Figure 6-15.

Page 59: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

53

Figure 6-15 Control

Managing Users

You can create and delete users and modify user information in the User Management pane

shown in Figure 6-16. Users are classified into three types: admin, engineer, and operator.

Different user types have different operation rights. Only admin users have user management

rights.

Figure 6-16 User Management

Page 60: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

54

Upgrading Software

You can upgrade SMU and PSU software in the Upgrade pane shown in Figure 6-17.

To upgrade software, perform the following steps:

Step 1 Click Browse to select the software and then click Send.

Step 2 After the software information is displayed under Available package active, select the

software and click Activate.

Step 3 The software upgrade progress is displayed. A message is displayed when the upgrade is

successful.

----End

Figure 6-17 Upgrade

Exporting Historical Logs

If you need to modify the preset file name when downloading a log file, display the extension

name. Otherwise, the file data will be abnormal.

Perform the following steps:

Step 1 Choose Organize> Folder and search options.

CAUTION

Page 61: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

55

Figure 6-18 Folder and search options

Step 2 Cancel Hide extensions for known file types tick.

Figure 6-19 Advanced settings

Page 62: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

56

----End

To download configuration files and log files, perform the following steps:

Step 1 Click Log History.

Step 2 Click Download under One-click Download.

The message "Are you sure to download the current configuration file and log file?" is

displayed.

Step 3 Click OK.

The configuration files and log files are downloaded in about 2 minutes.

----End

You can export battery testing records in Hypertext Markup Language (HTML) files by

clicking Export.

Figure 6-20 shows the Log History pane.

Figure 6-20 Log History

Exporting Historical Alarms

You can download historical alarms in the History Alarms pane shown in Figure 6-21. To

export historical alarms in HTML files, click Export. To clear historical alarms, click Clean.

Page 63: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

57

Figure 6-21 Historical Alarms

Configuring Alarm Parameters

You can set Alarm Enable, Alarm Level, and Relay in the Alarm Configuration pane

shown in Figure 6-22.

Page 64: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

58

Figure 6-22 Alarm Configuration

Configuring Site Parameters

You can set the date; time, site, and storage batteries type, and save, download, and upload

configuration files in the Site Configure pane shown in Figure 6-23.

Figure 6-23 Site Configure

Page 65: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

59

Energy Saving

You can set Basic Parameters, Control For Different Rates, Control for Exceeding Max Power,

Daily Electric Consum Mode, Monthly Electric Consum Mode in the Energy Saving pane

shown in Figure 6-24.

Figure 6-24 Energy Saving

Reading Electronic Labels

You can query electronic label information about system components such as the SMU, power

distribution subrack, and PSUs in the Electronic Label pane. To export electronic label

information in HTML files, click Export.

Page 66: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

60

Figure 6-25 Electronic Labels

Page 67: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

61

A Appendix

A.1 Technical Specifications

Table A-1 Technical specifications

Category Item Specifications

Environm

ental

conditions

Operating

temperature

TP48200A-H15A3 & D15A1: -10ºC to +45ºC (14ºF

to +113.0ºF)

TP48200A-H15A5: -40ºC to +45ºC (-40ºF to +113.0ºF)

Storage

temperature

-40°C to +70°C (-40°F to +158°F)

Transportation

temperature

-40°C to +70°C (-40°F to +158°F)

Operating

humidity

5%-95% RH (non-condensing)

Storage

humidity

5%-95% RH (non-condensing)

Altitude 0-4000 m (0-13123.2 ft)

When the altitude ranges from 2000 m (78.74 ft) to 4000 m

(13123.2 ft), the operating temperature is derated by 1ºC

(1.8ºF) for each additional 200 m (328.08 ft).

AC input Input mode TP48200A-D15A1 & H15A3 & H15A5:

Three-phase (One-phase compliant)

Input voltage Three-phase:346-415 V AC/200-240 V AC

One-phase:200-240 V AC

Input frequency 45-66 Hz (rated frequency: 50/60 Hz)

Power factor ≥ 0.99 (60%-100% load)

DC output Output voltage

range

-42 V DC to -58 V DC(Without load)

Page 68: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

62

Category Item Specifications

Default output

voltage

-53.5 V DC

Maximum

output power

Number of rectifiers multiplied by the output power of a

single rectifier

Regulated

voltage

precision

≤ 1%

Peak-to-peak

noise voltage

≤ 200 mV (0–20 MHz)

AC input

protection

AC input

overvoltage

protection

threshold

Overvoltage protection is performed when the single-phase

AC input voltage exceeds the AC input overvoltage

protection threshold (300 V AC by default).

AC input

overvoltage

recovery

threshold

When the voltage is restored to 290 V AC, the output

resumes.

AC input

undervoltage

protection

threshold

Undervoltage protection is performed when the single-phase

AC input voltage is below the AC input undervoltage

protection threshold (85 V AC by default).

AC input

undervoltage

recovery

threshold

When the voltage is restored to 90 V AC, the output

resumes.

DC output

protection

DC output

overvoltage

protection

threshold

58.5–60.5 V DC

Rectifier Efficiency R4850G1: ˃ 96% (230 V AC, 20%-90% load);

R4850N1: The peak point is ≥ 92.5 %;

≥ 91.5% (230 V AC, 35 %-80% load)

Output power R4850G1 3000 W (176-300 V AC);

1200 W (85-175 V AC)

R4850N1 2900 W (176-300 V AC);

1200 W (85-175 V AC)

Output soft

start

At the moment when the rectifier is powered on, the output

voltage rises slowly. The time for voltage rise is

configurable.

Page 69: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

63

Category Item Specifications

Overvoltage

protection

Voltage range: 58.5-60.5 V DC

If overvoltage occurs inside the rectifier due to a fault,

the rectifier experiences a deadlock.

External overvoltage:

If the external voltage is less than 63 V, the rectifier is in

the standby state. If overvoltage disappears, the rectifier

output resumes.

If the external voltage is greater than 63 V for more than

500 ms, the rectifier experiences a deadlock.

EMC CE EN300386 Class A

RE EN300386 Class A

Harmonic IEC 61000-3-12

Fluctuation and

blinking

IEC 61000-3-11

ESD Cabinet terminal: contact discharge voltage: 6 kV (Class

B); air discharge voltage: 8 kV (Class B);

EFT The voltage at signal ports is ±1 kV, and the voltage at the

power ports is ±2 kV (criterion B).

RS 10 V/m (criterion A)

CS The voltage at signal ports is 3 V and power ports is 10 V

(criterion A).

SURGE It complies with the IEC61000-4-5 standard. The voltage at

power ports in differential mode is ±2 kV. The voltage

power ports in common mode are ±4 kV (criterion B).

The voltage at signal ports in differential mode is 500 V.

The voltage at signal ports in common mode is 1 kV

Others AC surge

protection

Level-C surge protection

Standard surge discharge current: 20 kA

Maximum surge discharge current: 40 kA (8/20 µs)

Safety and

regulatory

design

IEC60950-1

MTBF 200,000 hours

Structure Dimensions (H

x W x D)

Cabinet:1600 mm x 650 mm x 650 mm (63.00 in. x 25.59

in. x 25.59 in.)(excluding base).

Base: 100 mm x 650 mm x 650 mm (3.94 in. x 25.59 in. x

25.59 in.).

Weight ≤ 120 kg (264.6 lb, without rectifiers and batteries)

Page 70: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

64

Category Item Specifications

Protection level TP48200A-H15A3 & A-H15A5: IP55

TP48200A-D15A1: IP45

Installation Installed on concrete floor or ESD floor (The bearing

capacity of the ESD floor should be greater than 800 kg.)

and 100 mm away from the wall

Maintenance From the front

Cooling TP48200A-H15A3 & A-H15A5:Heat exchange

TP48200A-D15A1: Direct air cooling

A.2 LCD Menu

Table A-2 LCD menu

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Active

Alarm

- - - -

Running

Status

Site Summary System Voltage - -

Total Load - -

Sys. Efficiency -

Peak Power - -

Peak Power Time - -

System Type - -

PSU Summary Total Current - -

Phase A Volt - -

Phase B Volt - -

Phase C Volt - -

Phase A Curr - -

Phase B Curr - -

Phase C Curr - -

AC Frequency - -

DC Total Power - -

PSU - - -

Batt Summ Total Current - -

Page 71: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

65

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Pre Disch Time - -

BattChargeSta - -

Batt Test Sta - -

Batt Temp 1 - -

VRLA Batt VRLA Batt1 Current -

Capacity -

Capa Percent -

Lithium Battery - - -

PDE Summary PDE Number - -

Comm PDE Num - -

Total Power - -

Total Current - -

Comm Status - -

PDE - - -

TCU Summary TEMP1 State - Normal

Cabinet Type - HEX Cabinet

Fan Group Fan Group1 Group Group 1

Fan(1-2) Speed -

Fan(1-2) State -

Fan Group2 Group Group 2

Fan(1-2) Speed -

Fan(1-2) State -

DCU DCU 1 Device

Address

-

SW Version -

Air Outlet T -

Fan Speed -

HEX - - -

TEC - - -

Alarm History - - -

Page 72: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

66

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Batt Test Log - - -

Settings

Alarm Setting Site Summary - -

PSU Summary - -

PSU - -

Batt Summ - -

VRLA Batt -

Lithium Battery - -

Alarm Relay - -

PDE Summary - -

PDE - -

TCU Summary - -

Fan Group - -

DCU -- -

HEX - -

TEC - -

Site Summary DC Ultra Over V - 60.0 V

DC Over Volt - 58.0 V

DC Ultra UnderV - 43.0 V

DC Under Volt - 45.0 V

Qty of Battery - 1

Shunt Current - 300 A

Shunt Voltage - 2 mV

AC Over Volt - 280 V

AC Under Volt - 180 V

System AC Type - Three Phase

Dial-up Network - Disable

DI(1~6) Alarm - Close

DO(1-8) Alarm Act - Close

Alarm Voice Dly - 10 Min

Alarm Voice En - No

Page 73: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

67

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Detect Diesel - No

DST Enable - Disable

Forbid All Alm - No

PSU Summary High PSU Cap % - 20%

Low PSU Cap % - 100%

Rect Redund Ena - Disable

VRLA Batt

Summ

Basic Para Smart Mgmt

En

Disable

Float Charge 53.5 V

Boost Charge 56.4 V

Current Limit 0.15C10

Over Current 0.25C10

Rated Capacity 150 Ah

Install Date 2010-01-01

FC BC Auto BC

Enabled Disable

Cyclic BC Ena Enable

Long Fail To

BC

Disable

AC Fail To BC

T

10 Min

Battery Test Test End Volt 46.0 V

Test End Capa 20.0%

Test End Temp 5 degC

Test End Time 480 Min

Mains Fail Test Disable

Batt Test Type No Test

Short Test Ena Enable

Short Test Intv 30 Day

ShortT

Duration

5 Min

Temp Comp TC Factor 80 mV/degC

Page 74: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

68

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Nominal Temp 25 degC

Temp source BTEMP

Charge Disch 0.05C10

DisTime 20.00 H

0.1C10 Dis

Time 10.0 H

0.2C10 Dis

Time 4.00 H

0.3C10 Dis

Time 2.42 H

0.4C10 Dis

Time 1.63 H

0.5C10 Dis

Time 1.16 H

0.6C10 Dis

Time 0.87 H

0.7C10 Dis

Time 0.61 H

0.8C10 Dis

Time 0.50 H

0.9C10 Dis

Time 0.42 H

1.0C10 Dis

Time 0.35 H

Capacity Coeff 95%

Other Batt Temp

VHigh

Lower DC

Volt

Over Temp

Volt

50.5 V

Batt High

Temp

50 degC

Bat V-High

Temp

53 degC

Batt Low

Temp -5 degC

Batt V-Low

Temp -10 degC

Page 75: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

69

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

Batt Low Capa 70%

LVD Setting BLVD Enabled - Enable

BLVD Mode - By Voltage

BLVD Voltage - 43.2 V

BLVD Recon Volt - 51.5 V

LLVD1 Enabled - Enable

LLVD1 mode - By Voltage

LLVD1 Voltage - 45.0 V

LLVD1 Recon Vol - 51.5 V

Li-Batt

Summary

Rated Capacity - 40 Ah

Li-Batt Voltage - 56.5 V

PDE - - -

TCU Summary Fan Ctrl Mode - Auto

HT Alm Thres - 68.0 degC

HT Alm Clr Thres - 65.0 degC

DCU DCU 1 HT ALM

Thres

45 degC

LT ALM Thres -20 degC

HEX HEX 1 HT ALM

Thres

45 degC

LT ALM Thres -20 degC

TEC TEC 1 HT ALM

Thres

50 degC

LT ALM Thres -20 degC

Comm Para Host Comm Addr - 0

Comm Baudrate - 9600

Ydn Comm Addr - 1

DHCP - Disable

Phone Number (1-3) - -

Account (1-3) - -

Password: - -

Page 76: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

70

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

IP Address - -

Subnet Mask - -

Gateway - -

NetEco Main IP - -

NetEco Bak IP - -

NetEco Port - 31220

System Para LUI Language - ENGLISH

Set Date - -

Set Time - -

Set Time Zone - GMT +08:00

Save As Def Cfg - Yes

Restore Def Cfg - Yes

Restore Manu Cfg - Yes

Logout - Yes

Set Site Name - -

Set Batt Type - NA

LCD Contrast - 5

Control Site Summary Auto/Man Ctrl - -

Network Detect - -

Reset Smoking - -

Clear PeakPower - -

DO(1-8) - -

Batt Summ BC/FC Ctrl - -

Battery Test - -

Reset Batt Cap - -

Clear Batt Alm - -

Short Test - -

LLVD1 Control - -

BLVD Control - -

Lithium Battery - - -

Page 77: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual A Appendix

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

71

Main Menu

Second-Level Menu

Third-Level Menu Fourth-Level Menu

Default Value

PSU Summary Current Limit - -

DC Voltage Ctrl - -

On/Off Control - -

PSU - - -

PDE Summary Clear PDE Lost - -

PDE - - -

DCU DCU 1 FAN Reset

HEX - - -

TEC - - -

Clr Alm Hist - - -

Quick

Settings

Qty of Battery - - 1

Rated Capacity - - 150 Ah

Set Date - -

Set Time - - -

IP Address - - -

Subnet mask - - -

Gateway - - -

Page 78: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual B Acronyms and Abbreviations

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

72

B Acronyms and Abbreviations

A

ATS automatic transfer switch

ACDB alternating current distribution box

B

BLVD battery low voltage disconnection

E

EMC electromagnetic compatibility

EMI electromagnetic interference

EMS electromagnetic susceptibility

F

FE fast Ethernet

L

LLVD load low voltage disconnection

I

IEC International Electrotechnical Commission

M

MTBF mean time between failures

O

OPEX operational expenditure

Page 79: TP48200A-D15A1 & H15A3 & H15A5 V300R001 User Manual 04 (1)

TP48200A-D15A1 & H15A3 & H15A5

User Manual B Acronyms and Abbreviations

Issue 04 (2013-07-23) Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

73

P

PSU power supply unit

S

SMU site monitor unit

PSNU Simple Network Management Protocol

SPD surge protection device