topic 5-1: cooling/heating load - khon kaen university
TRANSCRIPT
![Page 1: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/1.jpg)
Topic 5-1: Cooling/Heating Load
Supply Air (SA)
Return Air (RA)
Outside Air (OA)
AHU
F CC&DHHC H
RTH = Room/Building Total Heat load RSH = Room Sensible Heat load RLH = Room Latent Heat load
RTH = RSH + RLH
Fan
Duct losses, Qs,duct + Ql,duct
VentilationQs,vent + Ql,vent
CTH = CSH + CLH
CTH = Coil Total Heat load CSH = Coil Sensible Heat load CLH = Coil Latent Heat load
Qtr = Qsr + QlrQtc = Qsc + Qlc
Qsc = Qsr + Qs,fan + Qs,vent + Qs,duct Qlc = Qlr + Ql,vent + Ql,duct
Fan motorQs,fan
![Page 2: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/2.jpg)
Design of Air Conditioning System
1. Selection of inside and outside condition
2. Estimation of requirement cooling/heating equipment
3. Selection cooling/heating equipment
4. Selection supply conditions5. Design of air transmission and distribution systems
• Input for Room heat load
1. Inside condition : thermal comfort of people, condition for storage of products, process conditions
2. Outside condition : location, structure type, usage
3. Building specification : design, drawing, solar radiation
![Page 3: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/3.jpg)
Input 1. Selection of inside condition
Consumes food → metabolism → heat and work
Generates heat at a rate 100 – 2000 W
Core temp.neutral condition →
tcore < 31C→ Lethal/deadly
tcore 35Ctcore 36.8Ctcore 39Ctcore > 43C → Lethal/deadly
Slight discomfort
Slight discomfort
100 W → sedentary person, sitting2000 W → strenuous exercise
Skin temp., tskin 33.7C
• Thermal comfort: A living human body as a heat engine
![Page 4: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/4.jpg)
Heat balance equation for a human being
Qgenerate = Qskin + Qrespiration + Qstore
Qgenerate M = c*met* As,naked
met = 58.2 W/m2
As,naked = 0.202mass0.425height0.725
![Page 5: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/5.jpg)
Heat balance equation for a human being
Qgenerate = Qskin + Qrespiration + Qstore
Qskin = Qconvection + Qradiation + Qevapoation
Qconvection = 14.8Vair0.5(tskin - tair)
Qradiation = 11.603(tskin - tsurr)
Qevapoation = 181.76Vair0.4 (psat,skin - psat,air)
Qrespiration = Qdry heat loss + Qevaporative heat loss
Qstore = 0 at neutral condition tcore 36.8C
30% + 30% + 40%
![Page 6: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/6.jpg)
Thermo-regulator system
A human body is very sensitive to temperature.
Temperature depends on heat balance which depends on
surrounding conditions.
In-built body regulatory processes against cold and heat:Try to maintain body temp. by initiating certain body regulator processes against cold and heat.
1. Colder troom < tcore 36.8C
→ Blood vessels constrict/compress → blood flow → heat transfer
→ Heat generation to take care of heat losses → body temp.
2. Hotter troom > tcore 36.8C
→ Blood vessels dilate/expand → blood flow → heat transfer
→ Sweat , evaporation to prevent body temp.
→ heat exhaustion (headache) → heat cramps (salt loss) → heat stoke
![Page 7: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/7.jpg)
7
Comfort zone for air conditioning
Comfort zone
→ Clothes→ Activities→ Time interval→ Metabolism, ages, gender→ Air velocity→ Outside condition
• Summer comfort boundary22 – 29C at 30%RH20 – 24.5C at 70%RH
• Winter comfort boundary19 – 25.5C at 30%RH18 – 23C at 70%RH
18 C 29 C
![Page 8: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/8.jpg)
Input 2. Selection of outside condition
Ambient temp. (tdb) and moisture content (W) vary from hour-to-hour and from place-to-place.
→ Construction types; heavy, medium, light→ Insulation characteristics of building→ Area of glass/transparent surfaces→ Type of usage→ Nature of occupancy→ Daily range (tmax – tmin in a given day)
Summer: tdb from sunrise, reach tmax at afternoon and towards evening
Am
bie
nt
tem
p.
Time, 0-24 h
: %RH vary with tdb, reach RHmin at tmax
Design of outside conditions
![Page 9: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/9.jpg)
Outdoor Design For Cooling
Ref: 2005 ASHRAE Handbook-Refrigeration, Ch.14 Climate Design Information
Bangkok/Don MuangLat 13.92N,Long 100.60E, Elev 12 mHottest month: 4 – April37.2 CDB, 26.5 CWB0.4% Design level (0.4% h of a year = 35*100/8670) or exceeded 99.6%MCDB = Mean Coincident Wet Bulb
0.4%, 1%, 2%; tdb is equaled or exceeded 99.6%, 99.0%, 98.0%
Recommended0.4% → light construction types, poorly insulated, critical space temp.1% → medium construction 2% → heavy construction
![Page 10: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/10.jpg)
ตารางที ่2.2 สภาวะอากาศภายนอกส าหรับการออกแบบ
อา้งอิง: มาตรฐานระบบปรบัอากาศและระบายอากาศ 2561, วิศวกรรมสถานแห่งประเทศไทย ในพระบรมราชปูถมัภ ์(วสท.)
Don Muang37.2 CDB, 26.5 CWB0.4% Design level
0.4% Design level คือ รอ้ยละของจ านวนชั่วโมงตลอดทัง้ปีที่ยอมใหส้ภาวะอากาศภายนอกจรงิสงูกวา่สภาวะอากาศภายนอกส าหรบัการออกแบบได้
![Page 11: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/11.jpg)
Input 3. Building specification; Solar radiation
Solar constant, flux of solar radiation is 1370 W/m2
The earth’s elliptical orbit→ extra radiant flux 1325 – 1418 W/m2
Total solar irradiation at :
Iirradiation = IDirect + Idiffuse + Ireflect angle of incidence
The sun as a radiant energy source, a blackbody at Ts = 6000 K
altitude angle
![Page 12: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/12.jpg)
Total solar irradiation = IDirect + Idiffuse + Ireflect
A = apparent solar radiation, 1080 – 1230 W/m2
B = atmospheric extinction coefficient, 0.14– 0.21
Calculation model in ASHRAE: IDirect = Ae(-B/sin) = ID
C = constant for clear sky, 0.058 – 0.135 FWS = view factor or configuration factor = 0.5(1+cos), = tilt angle
FWS = 1 for horizontal surface and FWS = 0.5 for vertical surface
Idiffuse = CIDFWS = Id
g = reflectivity of ground/horizontal surface, 0.058 – 0.135 FwG = view factor from ground to surface = 0.5(1-cos)FwG = 0 for horizontal surface and FwG = 0.5 for vertical surface
Solar radiation reflected from the ground: Ireflect = (ID+ Id)gFWG
![Page 13: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/13.jpg)
Solar radiation through Transparent/Glazed, QSG
clear plate glasstransmittivity τ = 0.80 reflectivity ρ = 0.08 absorptivity α = 0.12
Transmit
Reflect
Absorb
transfer to indoor
transfer to outdoor
Assume transmittivity and absorptivity same as IDirect , Idiffuse , Ireflect
QSG = A(+ Nα)Itotal radiation
N = fraction of absorbed radiation transferred to indoor
Steady, N = U/ho
QSG = AIt (+ αU/ho)
Solar Heat Gain Factor SHGF = [It (+ αU/ho)]Ref. glass
QSG = A.SHGF.SCSC = Shading Coefficient
![Page 14: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/14.jpg)
Solar Heat Gain Factor QSG = A.SHGF.SC
A glass facing south is desirable for cooling in summer as it allows low SHGF and heating in winter as it allows high SHGF.
![Page 15: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/15.jpg)
Heat transfer through Building
Analysis of heat transfer is complex:
→ Complex structure - different thermo-physical properties→ Continuously varying outdoor conditions (solar, temp., wind)→ Continuously varying indoor conditions (load patterns)
Winter, peak heat load occur at early morning before sunrise→ Solar radiation effects not considered
→ Ambient temp. variation effects not considered → Steady heat transfer
Cooling load: consider transient heat transfer for more accuracy analysis
![Page 16: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/16.jpg)
1D steady state heat transfer through buildingsqin = (qconv,o + qrad,o) = (qconv,i + qrad,i)
qin = ho(To - Tw,o) = hi(Tw,i - Ti)
ho, hi = inner, outer surfaceconductances, account both convection and radiation heat transfers
![Page 17: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/17.jpg)
Surface conductance values in W/m2.K for different orientations, air velocities and surface emissivity
Typical conductance values of air spaces
![Page 18: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/18.jpg)
Unsteady heat transfer through opaque walls and roofs
The outer wall (x = L) is subjected to - αDID direct radiations - αdId diffuse radiations- R reflected radiation - ho(To-Tw,o) convective heat transfer
Control surface at x=L at time ;qL, = -kw(T/x)L, = ho(To-TL) + αDID + αdId - R
The inner wall (x=0);- hi(Ti,w-Ti) convective+ radiation heat transfer
Control surface at x=0 at time ;q0, = -kw(T/x)0, = hi(T0 - Ti)
1D, transient heat conduction though a plane wall; 2T/x2 = (T/)For T(x,), = (k/cp)w
Initial condition at time =0; Tx,0 = Ti(x)
sol-air temperature effective outdoor temp. combines convection + radiation Tsol-air = To + (αDID + αdId - R)/ho = Te
qL, = -kw(T/x)L, = ho(Tsol-air -TL)
Because of thermal capacity of wall
q0, qL,
![Page 19: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/19.jpg)
Analytical solution with periodic boundary conditionsAn infinite Fourier series consisting of various harmonics;
Tsol-air = Tsol-air,m + M1cos1 + N1sin1+ M2cos2 + N2sin2 + …
Solution; Tx, = A + Bx +(CncosPnmx + DnsinPnmx)exp(-m22)
Q0, = UA(Te,m - Ti) + UA(Te, - - Te,m) = UATeff
Rate of heat transfer from the inner surface;q0, = function(U, Te,m , Te,1 , Te,2 ,T0,0 , time lag n , decrement factor n )
Mean sol-air temp.;
Tsol-air,m = Te,m 0)=24
Tsol−air𝑑)/24
![Page 20: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/20.jpg)
Load Calculation Methods1.Rule of thumb method
- Least accurate - eg. 400 - 1800 (Btu/h)/m2
2.Dynamic analysis (TETD/TA, TFM)- Computer modeling
- Total equivalent temp. diff. TETD/TA by ASHRAE 1967
- Transfer function method, TFM by ASHRAE 1972- hour-by-hour calculation- calculate heat gain → conversion to cooling load
3.Static analysis (ETD/CLTD/CLF/SHGF/SC)- simplified TFM, troom = constant)
- hand calculation by ASHRAE 1977, then 1989
- CLTD/CLF/SHGF/SC method
![Page 21: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/21.jpg)
Semi-empirical method based on ETD or CLTD
thermal capacity of wall → q0, qL, → time lag & decrement
Heat transferred to the outer surface of the wall is partly stored and partly transferred to the conditioned space. Due to the thermal energy storage, temperature of the wall increases and transfer to outside or/and
inside room.
Variation of heat transfer rate with time
The net effect is a greatly reduced cooling load on the building for thick walls. Requirement of cooling system of much larger capacity (hence high initial cost) for buildings with thin walls compared to thick walls.
![Page 22: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/22.jpg)
Empirical method for Cooling estimation
ETD/CLTD values in K for roofs without suspended ceiling (ASHRAE)
Q0, = UA(Te,m - Ti) + UA(Te, - - Te,m) = UATeff
![Page 23: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/23.jpg)
Principle of cooling load
• Related heat flow rates varying with time:
1. Heat gain
2. Cooling load
3. Heat extraction
The instantaneous rate at which heat enters into, out of, or generated within a space
The rate at which heat must be removed from a space to maintain air temperature and humidity at the design values
by equipment
![Page 24: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/24.jpg)
Cooling load differs from heat gain due to
* delay effect of conversion of radiation energy to heat
Due to thermal storage lag
Radiant energy is first absorbed by structure
Heat is convected from the structure surface
Surface Temperature
![Page 25: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/25.jpg)
Cooling load ≠ Heat gainThermal storage and Construction type
Actual cooling load By heavy construction
Actual cooling load By light construction
![Page 26: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/26.jpg)
Heat Gaininstantaneous rate
roof
lights
equipment
floor
glass solar
exteriorwall
glassconduction
infiltrationpeople
partitionwall
25.5 C (78 F): Indoor condition
35 C (95 F): Outdoor condition
1. External Load
2. Internal Load
1.1 Transmission
1.2 Solar radiation
1.3 Ventilation & Infiltration
2.1 Light
2.2 Equipment
2.3 People
![Page 27: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/27.jpg)
Total cooling Load
-temperature-moisture
content-air motion-air quality-noise
![Page 28: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/28.jpg)
Cooling Load
1. External Loads1.1 Transmission: Heat gains from Walls and roofs –Sensible
1.2 Solar radiation: Solar gains through fenestrations–Sensible
1.3 Outdoor air : Ventilation, Infiltration–Sensible & Latent
2. Internal Loads2.1 Light –Sensible
2.2 People –Sensible & Latent
2.3 Appliances –Sensible & Latent
Winter, 1.2 and 2 effects not considered
![Page 29: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/29.jpg)
1.1 Transmission Load (1)
• Sensible heat gain through floor, partition and ceiling at steady state:
q = UAΔt = (A/Rtot)(to– ti) where
q = heat gain, W
U = overall heat transfer coefficient, W/(m2·K) = 1/ Rtot
Rtot = total thermal resistance K/W
A = surface area, m2
Δt = (to–ti) = difference between outside air temperature and air temperature of the conditioned space, °C
= ntot RR
![Page 30: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/30.jpg)
1.1 Transmission Load (2)
• The overall coefficient of heat transfer U :
where
xn = wall thickness for material n for composite material, m
kn = thermal conductivity of wall material n, W/(m·K)
hi , ho = inside, outside surface conductance, W/(m2·K)
( ) ( ) totonionni RRRRhkxhU
11
/1//1
1=
++=
++=
![Page 31: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/31.jpg)
1.1 Transmission Load (3)
Table 4-4 Thermal resistance of selected building materialExterior materialSheathingRoofingConcreteInsulating materialsInterior materialsAir resistanceFlat glass
![Page 32: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/32.jpg)
Studs 25%insulation 75%
R1 R2 R3 R4 R6 R7
R5
Example 1. Element--------------------------------------------------1. Outside surface2. Wood bevel lapped siding3. Rigid foam insulating sheathing 4. Mineral fiber batt insulation5. Wood stud (38 mm 90 mm)6. Gypsum wallboard 13-mm7. Inside surface
--------------------------------------------------
R, m2·K/W------------------------------------R1 = 0.044R2 = 0.14R3 = 0.7R4 = 2.3R5 = 0.63R6 = x/k = 0.013/0.282 = 0.046R7 = 0.12------------------------------------
resistance networkRwall = R1 + R2 + R3 + R45 + R6 + R7
Rwall = 0.884 + 1.383 + 0.166 = 2.433 m2·K/W
Uwall = 1/Rwall = 0.411 W/m2·K
1/R45 = 0.75/R4 + 0.25/R5
R45 = 1.383
R1 + R2 + R3 = 0.884
R6 + R7 = 0.166
If the stud is not included;Rwall = 0.884 + 2.3 + 0.166 = 3.35 m2·K/WUwall = 1/Rwall = 0.298 W/m2·K
![Page 33: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/33.jpg)
1.2.1 Solar loads through transparent surfaces (1)
Static analysis (SHGF/SC)
qsg = AIt (+N)
qsg = AIt(+U/ho)
Solar energy passing through the glazing surface, qsg
It = irradiation, W/m2
N = fraction absorbed = U/ho
It(+U/ho) = SHGF
SHGF = solar heat gain factorSC = shading coefficient
qsg = (SHGFmax )(SC)A
++ = 1
![Page 34: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/34.jpg)
1.2.1 Solar loads through transparent surfaces (2)
qsg = A(SHGFmax )(SC)CLFSHGF = solar heat gain factor
![Page 35: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/35.jpg)
Time of the Day: Solar RadiationR
adia
tio
n In
ten
sity
, W/m
2
Time, 0-24 h
![Page 36: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/36.jpg)
1.2.1 Solar loads through transparent surfaces (3)
qsg = A(SHGFmax )(SC)CLFSC = shading coefficient
![Page 37: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/37.jpg)
1.2.1 Solar loads through transparent surfaces (4)
qsg = A(SHGFmax )(SC)CLFgCLF = cooling load factor
CLF accounts for the delay before radiative gains becomes a cooling load
CLFg for glass
![Page 38: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/38.jpg)
1.2.2 Solar loads on opaque surfaces (1)
+ = 1
Solar energy on opaque surface (wall, roof), qw
qw = AIt (N)
qw = AIt(Uw/ho)
With air-temp. difference (to–ti)
qw = AIt(Uw/ho) + UwA(to–ti)
qw = UwA[(to+ It/ho) - ti)]
te = to+ It/ho
qw = UwA(te–ti)
te = sol-air temperature, include solar
→ over-estimate the heat gain
By include effect of thermal storage → qw = UwA(CLTD)
![Page 39: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/39.jpg)
1.2.2 Solar loads on opaque surfaces (2)
Static analysis (CLTD/CLF)qw = UA(CLTD)CLFrCLTD = cooling load temp. difference
CLTD for roofs
![Page 40: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/40.jpg)
1.2.2 Solar loads on opaque surfaces (3)CLTD for wall
![Page 41: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/41.jpg)
1.2.2 Solar loads on opaque surfaces (4)Lower-mass wall has higher peak heat flux and occurs earlier
![Page 42: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/42.jpg)
1.3 Outdoor air (1)
Ventilation loads –Sensible & Latent
qis = 1.23 Qvol (to– ti)
qil = 3010 Qvol (Wo– Wi)
Qvol = volumetric flow rate of outside air, L/s
W = humidity ratio, water to air, kg/kg
Sensible load = flow rate x specific heat x (ΔT)
Latent load = flow rate x latent heat of vaporization x (humidity difference)
Ventilation loads due to entry of outside air by mechanical device
qtot = 1.2 Qvol (Ho– Hi)
![Page 43: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/43.jpg)
1.3 Outdoor air (2)
Infiltration loads –Sensible & Latent
Qvol = (ACH) (space volume) m3/h
V = wind velocity, m/s
ACH = a + bV + c (to– ti)
Infiltration loads due to entry of outside air by natural mean
- Estimate in terms of number of air change per hour (ACH)
![Page 44: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/44.jpg)
2. Internal Loads: 2.1 Light
heat gain by light –Sensible
q = (lamp rating in watts) (Fu)(Fb) (CLFl)
Fu = utilization factor for fraction of installed lamps in use
Fb = ballast factor for fluorescent lamps = 1.2 for most common
![Page 45: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/45.jpg)
2. Internal Loads: 2.2 People
heat gain by people –Sensible & Latent
qs = (sensible heat gain per person) (number of people) (CLFp)
ql = (latent heat gain per person) (number of people)
CLFp for people
![Page 46: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/46.jpg)
2. Internal Loads: 2.3 Appliances
Heat gain from equipment or appliances –Sensible & Latent
Heat dissipation from these equipments are mainly based data published by the manufacturers and standard handbook
![Page 47: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/47.jpg)
Total cooling loadpartition, floor, ceiling, glass qt = UA (to– ti)
transparent (glass) qs = A(SHGF)(SC)(CLF)
opaque (wall, roof) qs = UA(CLTD)(CLF)
qis = 1.23 Qvol (to– ti)
qil = 3010 Qvol (Wo– Wi)
ql = (lamp rating in watts) (Fu)(Fb=1.2)(CLF)
qel = (sensible energy rate)(CLF)
qel = (latent energy rate)
qpl = (sensible HG)(no. of people)(CLF)
qpl = (latent HG)(no. of people)
Safety factor 5-10%
![Page 48: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/48.jpg)
Summary of Cooling Loads Estimating
1. Select outdoor design condition
2. Select indoor design condition
3. Estimate adjacent unconditioned spaces
4. Compute U-value for building component
5. Estimate rate of infiltration and/or ventilation of outside air
6. Determine additional building characteristics influence solar-heat gain
7. Determine ETD/CLTD, CLF,SHGF, SC
8. On the basis of U, Area, TD, calculate the rate of heat gain to the space
9. Estimate internal heat gain from lights, equipments, people
10. Sum all load component to determine the maximum capacity
Reference: ASHRAE Fundamental Handbook
![Page 49: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/49.jpg)
A Year-round air conditioning system for a small commercial establishment such as retail store.
1.Hotwater boiler
2.Hot water coil
3.Refrigerating machinery
4.Cooling coil6.Blower Fan
12.Filter5.Humidifier
Air conditioning plenum
11.Outside air intake
10.Return-air duct
8.Supply air diffuser, Qs
7.Supply air duct
9.Return-air grille
AHU
Mechanical room
Conditioned Space
Room load
Coil load
![Page 50: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/50.jpg)
Cooling Load Calculation
Purpose:
• Load profile over a day
• Peak load (basis for equipment sizing)
• Operation Energy analysis
• HVAC Construction cost
(HVAC-Heating Ventilation Air-Conditioning)
Co
olin
g Lo
ad, W
Time, 0-24 h
![Page 51: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/51.jpg)
Example of Cooling Load Estimation
![Page 52: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/52.jpg)
Cooling Load Calculation Sheet
![Page 53: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/53.jpg)
Cooling Load Calculation Software: TLC by TRANE
![Page 54: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/54.jpg)
Cooling Load Calculation Software: TLC by TRANE
![Page 55: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/55.jpg)
Cooling Load Calculation Software: TLC by TRANE
![Page 56: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/56.jpg)
Cooling Load Calculation Software: TRACE Load® 700by Trane’s CDS Group
![Page 57: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/57.jpg)
Cooling Load Calculation Software: Elite CHVAC by Elite Softwarehttp://www.elitesoft.com/web/hvacr/chvacx.html
![Page 58: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/58.jpg)
58
Prob: 4-material wall (H,L), 3 glass window (h,l), ti, Chicago, qloss =? Assume: one-directional steady heat transfer through wall in winterSchematic:
P4.1 The exterior wall of a single-story office building near Chicago is 3 m high and 15 m long. The wall consists of 100-mm face brick, 40-mm polystyrene insulating board, 150-mm lightweight concrete block, and an interior 16-mm gypsum board. The wall contains three single-glass windows 1.5 m high by 2 m long. Calculate the heat loss through the wall at design conditions if the inside temperature is 20C.
A: 100-mm face brickB: 40-mm polystyrene insulating boardC: 150-mm lightweight concrete blockD: interior 16-mm gypsum board
A B CWallH x L
Glass window
h x l
Wall section
D
Model: qloss = UwAw(to - ti)+UgAg(to - ti)to : winter@Chicago → Design outdoor dataAg = 3*h*l, Aw = H*L – Ag
Uw = 1/Rtot , Rtot = Ri +RA+RB+RC+RD+ Ro
Ug ,R values → Thermal resistance data
qcondqconv,iqconv,o
![Page 59: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/59.jpg)
P4.1 : 4-material wall (H,L), n glass window (h,l), ti, near Chicago, qloss =?
A: 100-mm face brick → Exterior material; RA= 0.1*0.76 m2.K/WB: 40-mm polystyrene insulating board → Insulating material; RB= 0.04*27.7 m2.K/WC: 150-mm lightweight concrete block→ Concrete; RC= 0.15*1.94 m2.K/W
D: interior 16-mm gypsum board → Interior material; RD= 0.1 m2.K/W
![Page 60: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/60.jpg)
P4.1 : 4-material wall (H,L), n glass window (h,l), ti, near Chicago, qloss =?
Inside wall→ Air resistance; Ri= 0.12m2.K/WOutside wall→ Air resistance; Ro= 0.029 m2.K/Wsingle-glazed window→ Flat glass; Ug= 6.2 m2.K/W
![Page 61: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/61.jpg)
61
P4.2 For the wall and conditions stated in P4.1 determine the percent reduction in heat loss through the wall if (a) the 40 mm of polystyrene insulation is replaced with 55 mm of cellular polyurethane, (b) the single-glazed windows are replaced with double-glazed windows with a 6-mm air space. (c) If you were to choose between modification (a) or (b) to upgrade the thermal resistance of the wall, which would you choose and why?
Prob: [ABCD] wall (H,L), 3 glass window (h,l), ti, near Chicago, q(a) B replaced with B1, (q1-q)*100%/q =? (b) single-glazed replaced with double-glazed, (q2 -q)*100%/q =?
A: 100-mm face brickB: 55-mm cellular polyurethaneC: 150-mm lightweight concrete blockD: interior 16-mm gypsum board
(a) Model: q1 = Uw1Aw(to - ti)+UgAg(to - ti)Uw1 = 1/Rtot1, Rtot1 = Ri +RA+RB1+RC+RD+ Ro
if RB1>RC → Rtot1>Rtot→ Uw1<Uw → q1< q
(b) Model: q2 = UwAw(to - ti)+Ug2Ag(to - ti)Ug2 → Ug2<Ug→ q2< q
![Page 62: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/62.jpg)
62
P4.3 An office in Houston, Texas, is maintained at 25C and 55 % relative humidity. The average occupancy is five people, and there will be some smoking. Calculate the cooling load imposed by ventilation requirements at summer design conditions with supply air conditions set at 15C and 95 % relative humidity if (a) the recommended rate of outside ventilation air is used and (b) if a filtration device of contaminant removal efficiency E = (Vo – Vm)/Vr = 70 % is used. (Office; Vo = 10 L/s/person, Vm = 2.5 L/s/person)
Prob: Office (ti, i), Houston, Texas, 5 people (smoking), supply (ts, s) air qventilation = ?, (a) outside ventilation, (b) filtration device of E
Vs = Vr+Voutside
Vr
Voutside
(b) Model: Vr = (Vo – Vm)/E, Voutside = Vm, Vs = Vr+Vm
qis = 1.23Vm(to– ti) + 1.23Vs(ts– ti)
qil = 3010Vm(Wo– Wi) + 3010Vs(Ws– Wi)qtot = qis + qil
Ws= W(ts, s)
(a) Model: 100% Voutside, Vr=0Vs = Voutside = Vo
qis = 1.23Vo(to– ti)
qil = 3010Vo(Wo– Wi)qtot = qis + qil
to, twb,o : summer@Houston, TexasWo = W(to, twb,o)Wi = W(ti, i)
![Page 63: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/63.jpg)
P4.4 : A computer room located on the second floor of a five-story office building is 10 by 7 m. The exterior wall is 3.5 m high and 10 m long; it is a metal curtain wall (steel backed with 10 mm of insulating board), 75 mm of glass-fiber insulation, and 16 mm of gypsum board. Single-glazed windows make up 30 % of the exterior wall. The computer and lights in the room operate 24 hr/day and have a combined heat release to the space of 2 kW. The indoor temperature is20C. (a) If the building is located in Columbus, Ohio, determine the heating load at winter design conditions. (b) What would be the load if the windows were double-glazed?
Prob: 3-material wall (H,L), 30% Ag , ti, qinternal, Columbus, Ohio, qheating =? Assume: one-directional steady heat transfer through wall in winter
A: metal curtain wall 10 mm insulating B: 75 mm of glass-fiber insulationC: 16 mm of gypsum board
A CWallH x L
Glass window Ag
Wall sectionModel: qheating = qloss – qinternal
qloss = UwAw(to - ti)+UgAg(to - ti)to : winter@ Columbus, OhioAw = H*L – Ag, Ug = 1/Rg
Uw = 1/Rtot , Rtot = Ri +RA+RB+RC+ Ro
R values → Thermal resistance data
qcond qconv,iqconv,o
B
(b) Ug2 = 1/Rg2 (double-glazed) qloss2 <qloss
![Page 64: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/64.jpg)
P4.5 : Compute the heat gain for a window facing southeast at 32 north latitude at 10 A.M. central daylight time on August 21. The window is regular double glass with a 13-mm air space. The glass and inside draperies have a combined shading coefficient of 0.45. The indoor design temperature is 25C, and the outdoor temperature is 37C . Window dimensions are 2 m wide and 1.5 m high.Prob: double glass (W,H), SC=0.45, ti, to, SE 32 north, 10 A.M. August 21, qgain =? Assume: one-directional steady heat transfer through glass window
Double Glass Window
WxH
Model: qgain = UgAg(to - ti) + SHGFmax*SC*CLF*Ag
Ug : double glass with a 13-mm air spaceSHGFmax : August, SE, 32 north latitudeCLF : 10 A.M. , SE northAg = W*H
![Page 65: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/65.jpg)
P4.6 : The window in P4.5 has an 0.5-m overhang at the top of the window. How far will the shadow extend downward?
Prob: double glass window with overhang d = 0.5 m, yshadow =?
Model: yshadow = d*tan/cos , : August, 10 A.M. , SE, 32 north = - facing southeast = 45
![Page 66: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/66.jpg)
P4.7 : Compute the instantaneous heat gain for the window in P4.5 with the external shade in P4.6.
Prob: double glass (W,H), SC=0.45, ti, to, SE 32 north, 10 A.M. August 21,overhang d = 0.5 m, yshadow with the external shade (Ashade), qgain =?
Model: qgain = UgAg(to - ti) + SHGFmax*SC*CLF* Ashade
Ug : double glass with a 13-mm air spaceSHGFmax : August, SE, 32 north latitudeCLF : 10 A.M. , SE northAg = W*HAshade = W*(H-yshadow)
![Page 67: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/67.jpg)
P4.8 : Compute the total heat gain for the south windows for an office building that has no external shading. The windows are double-glazed with a 6-mm air space and with regular plate glass inside and out. Draperies with a shading coefficient of 0.7 are fully closed. Make calculation for 12 noon in (a) August and (d) December at 32 North Latitude. The total window area is 40 m2. Assume that the indoor temperatures are 25C and 20C and that the outdoor temperatures are 37C and 4C
Prob: qwindow =? double-glazed window(Ag), SC=0.7, S 32 north, 12 noon (a)August (ti, to), (b) December (ti, to)
Model: qgain = UgAg(to - ti) + SHGFmax*SC*CLF* Ag
Ug : double glass with a 6-mm air spaceSHGFmax : (a) August, S, 32 north latitudeSHGFmax : (b) December, S, 32 north latitudeCLF : 12 noon , S north
![Page 68: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/68.jpg)
P4.9 : Compute the instantaneous heat gain for the south wall of a building at 32 North Latitude on July 21. The time is 4 p.m. sun time. The wall is brick veneer and frame with an overall heat-transfer coefficient of 0.35 W/m2.K. The wall is 2.5 by 6 m with a 1-2-m window.Prob: qwall =? Wall (Uw, HW), window (h w), S 32 north, July, 4 p.m. sun timeAssume: ti = 25C, to = 35C , tav = 29C, daily rang 12C
Model: qwall = UwAw*CLTD, Aw= HW- h wCLTD : S, 4 p.m. , brick veneer and frame → Type F
![Page 69: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/69.jpg)
P4.10 : Compute the peak instantaneous heat gain per square meter of area for a brick west wall similar to that in Example 4-3. Assume that the wall is located at 40 North Latitude. The date is July. What time of the day does the peak occur? The outdoor daily average temperature of 30C and indoor design temperature is 25C.
Prob: qpeak/A=? Time =? Wall (Uw,), W 40 north, July, to , ti
Model: qpeak/A = Uw*CLTDpeak,adj
Uw = 1/Rtot
CLTDpeak : W, brick with insulation → Type FCLTDadj = CLTD + (25 – ti) + (tav – 29)
![Page 70: Topic 5-1: Cooling/Heating Load - Khon Kaen University](https://reader030.vdocuments.mx/reader030/viewer/2022012707/61a831bd56df41422b2ddc94/html5/thumbnails/70.jpg)
P4.10 : qpeak =? Time =? Wall (Uw, 1 m2), W 4 0 north, July, to , ti
Model: qpeak/A = Uw*CLTDpeak,adj
Uw = 1/Rtot
CLTDpeak : W, brick with insulation → Type FCLTDadj = CLTD + (25 – ti) + (tav – 29)Time = time at CLTDpeak